INSPECTION FORM VARIABLE FREQUENCY DRIVE, 600V, <37 kw
|
|
- Charla Owen
- 6 years ago
- Views:
Transcription
1 VRIBLE FREQUENCY DRIVE, 600V, <37 kw Page 1 of 3 Project Facility: rea : Project Name: Bid Opportunity: Load: VFD Location: Cell #: VFD: Serial #: Size: Rated Voltage: V Current Control Voltage: V Circuit Protection: Fused Disc. Fuse Size: Breaker Inst. Setting: Fuse Mfg. VFD Data Line Reactor: Load Reactor: Present N/ Present N/ Bypass Contactor: Type: NEM IEC N/ NEM Size: IEC C-3 C-4 Bypass Overload Protection: Thermal Electronic Not pplicable Class: Unknown Setting / Control Power Transformer: Size: V Sec. Voltage: V Primary Fuse: Secondary Fuse: Current Transformer: Ratio: Type: Motor Data Size: kw / HP Voltage: V Full Load mps: Service Factor: Inverter Duty Yes No Other: Starter Identification Tag Installed: Yes No Visual Signs of Overheating: Yes No Visual Inspection / Cleaning Cleanliness (s Found): Good cceptable Poor Support Insulators: Good cceptable Poor Connections Good cceptable Poor Electro/Mechanical Interlock: Good cceptable Poor Ground Connection Good cceptable Poor Contactor Condition: Good cceptable Poor Door Mechanical Good cceptable Poor Contact lignment: Good cceptable Poor Verify Bypass O/L element is correctly sized for the load: Yes No N/ Exercise Circuit Breaker/MCP/Disconnect Yes Cables Supported ppropriately: Yes No Unit Cleaned: Yes Photograph Taken: Yes Form VFD-600V-37kW Rev 00, Created by SNC-Lavalin Inc. L:\40ENG\Clients\City of Winnipeg\Forms\Electrical\F-VFD-600V-37kW.doc
2 VRIBLE FREQUENCY DRIVE, 600V, <37 kw Page 2 of 3 B C Summary Contact / Pole Measurements Bypass Contactor Contact Resistance (µω) Breaker/Disconnect Resistance (µω) Main Fuse Resistance (µω) Passed Further Investigation Required. Preparation: Source: Contactor: Isolated Open Cable Dest. / Load: Disconnected Connected with Load Isolated Note: pproval of City s Representative is required, prior to leaving cables connected during the test. WRNING: DISCONNECT LL POWER CBLES FROM VFD MODULE ND LL CONTROL POWER FUSES PRIOR TO TEST. Insulation Resistance Disconnect Line to GND Disconnect Load to GND Disconnect Line to Load Bypass Contactor Line To GND Bypass Contactor Load To GND Bypass Contactor Line to Load Voltage Insulation Resistance (MΩ) B C Ground all phases not under test! Summary Passed Further Investigation Required. Form VFD-600V-37kW Rev 00, Created by SNC-Lavalin Inc. L:\40ENG\Clients\City of Winnipeg\Forms\Electrical\F-VFD-600V-37kW.doc
3 VRIBLE FREQUENCY DRIVE, 600V, <37 kw Page 3 of 3 Preparation: Run motor at full load. Operational Inspection Ramp Up Time Specified: sec ctual: sec Measured Motor Current Ø ØB ØC VFD Motor Current Ø ØB ØC Remote (RTU/PLC/DCS) Displayed Motor Current: Ramp Down Time Specified: sec ctual: sec Settings Record Parameters and Settings on Separate Sheet. Completed: Yes No Returned to Service: Yes No Final nalysis Monitoring / Further Inspection Required: Yes Repair / Replacement Required: Yes No No Company Name Signature Date (yyyy/mm/dd) Performed By Checked By Note: The person performing the check is responsible for ensuring that the data is transcribed from the handwritten form correctly, and that the analysis results are correct. Form VFD-600V-37kW Rev 00, Created by SNC-Lavalin Inc. L:\40ENG\Clients\City of Winnipeg\Forms\Electrical\F-VFD-600V-37kW.doc
4 MOTOR STRTER, FVNR, 600V Page 1 of 2 Project Facility: rea : Project Name: Bid Opportunity: Load: Starter Location: Cell #: Type: Serial #: Size: Rated Voltage: V Current Control Voltage: V Starter Data Circuit Protection: Overload Protection: Fused Disc. Fuse Size: Breaker MCP Thermal Electronic Intelligent Class: Unknown Inst. Setting: Setting / Fuse Mfg. Control Power Transformer: Current Transformers: Size: V Sec. Voltage: V Primary Fuse: Secondary Fuse: Phases: B C None Ratio: Ground Fault CT: Present Not Present Ratio: Motor Data Size: kw / HP Voltage: V Full Load mps: Service Factor: Other: Starter Identification Tag Installed: Yes No Visual Signs of Overheating: Yes No Visual Inspection / Cleaning Cleanliness (s Found): Good cceptable Poor Support Insulators: Good cceptable Poor Connections Good cceptable Poor Electro/Mechanical Interlock: N/ Good cceptable Poor Ground Connection: Good cceptable Poor Contactor Condition: Good cceptable Poor Door Mechanical Good cceptable Poor Contact lignment: Good cceptable Poor Verify O/L element is correctly sized for the load: Yes No Exercise Circuit Breaker/MCP/Disconnect Yes Cables Supported ppropriately: Yes No Unit Cleaned: Yes Photograph Taken: Yes B C Summary Contact/Pole Measurements Contact Resistance (µω) Disconnect / Breaker / MCP Resistance (µω) Fuse Resistance (µω) Passed Further Investigation Required. Form MS-FVNR-600V Rev 02, Created by SNC-Lavalin Inc. L:\40ENG\Clients\City of Winnipeg\Forms\Electrical\F-MS-FVNR-600V.doc
5 MOTOR STRTER, FVNR, 600V Page 2 of 2 Insulation Resistance Preparation: Source: Contactor: Isolated Open Voltage Cable Dest. / Load: Disconnected Connected with Load Isolated Note: pproval of City s Representative is required, prior to leaving cables connected during the test. Insulation Resistance (MΩ) B C Ground all phases not under test! Contactor Line To GND Summary Passed Contactor Load To GND Further Investigation Required. Contactor Line to Load Returned to Service: Yes No Final nalysis Monitoring / Further Inspection Required: Yes Repair / Replacement Required: Yes No No Company Name Signature Date (yyyy/mm/dd) Performed By Checked By Note: The person performing the check is responsible for ensuring that the data is transcribed from the handwritten form correctly, and that the analysis results are correct. Form MS-FVNR-600V Rev 02, Created by SNC-Lavalin Inc. L:\40ENG\Clients\City of Winnipeg\Forms\Electrical\F-MS-FVNR-600V.doc
6 C MOTOR, LOW VOLTGE Page: 1 of 2 Project Facility: rea : Project Name: Bid Opportunity: Size: kw / HP Voltage: V R.P.M: Motor Data Serial Number: Frame Type: FL: Service Factor: Other: Cooling: ir Fan # Cooling Fans: Winding Material: Motor Identification Tag Installed: Yes No Visual Signs of Overheating: Yes No Visual Inspection / Cleaning Connections: Good cceptable Poor ir Baffles: Good cceptable Poor Paint: Good cceptable Poor Filter Media: N/ Good cceptable Poor Cooling Fans: N/ Good cceptable Poor Fan Controls: N/ Good cceptable Poor nchorage/lignment: Good cceptable Poor Ground Connection: Good cceptable Poor Mechanical/Electrical Noise During Operation: Yes No Lubrication Required: Yes No Cleanliness (s Found): Good cceptable Poor Unit Cleaned: Yes Photograph Taken: Yes Stator Winding Voltage (Vdc) Winding Temperature ( C) Resistance (MΩ) 30 Sec 1 min. 10 min. (a) Dielectric bsorption Ratio Polarization Index (a) Winding Insulation Resistance Notes: (a) ing to 10 minutes and calculation of Polarization Index is only required for motors > 150 kw (200 HP) Summary Passed. Further Investigation Required. Winding Resistance Resistance (µω) Summary - B B C - C Passed Further Investigation Required. Form F-MTR-LV Rev 01, Created by SNC-Lavalin Inc. L:\40ENG\Clients\City of Winnipeg\Forms\Electrical\F-MTR-LV.doc
7 C MOTOR, LOW VOLTGE Page: 2 of 2 Bearing Insulation Resistance Not pplicable Bearing Voltage (Vdc) Bearing Temperature ( C) Resistance (MΩ) 1 min. Corrected to 40 C Summary Passed. Further Investigation Required. Not pplicable ctual Winding Temperature: C ctual Bearing Temperature C RTD Resistance (Ω) Calculated Temperature ( C) RTD Resistance (Ω) Calculated Temperature ( C) RTD Resistance Summary Passed. Further Investigation Required. Note: connection resistance of bolted connections. Report on cable inspection sheet. Returned to Service: Yes No Final nalysis Monitoring / Further Inspection Required: Yes Repair / Replacement Required: Yes No No Company Name Signature Date (yyyy/mm/dd) Performed By Checked By Note: The person(s) performing the check is responsible for ensuring that the data is transcribed from the handwritten form correctly, and that the analysis results are correct. Form F-MTR-LV Rev 01, Created by SNC-Lavalin Inc. L:\40ENG\Clients\City of Winnipeg\Forms\Electrical\F-MTR-LV.doc
8 POWER CBLE < 1000V Page 1 of 1 Cable Project Facility: rea : Project Name: Bid Opportunity: Source: Dest. / Load: Cable Data Type: Conductor: Copper luminum No. of Conductors: Rated Voltage: Installation: Cable Tray Strapped Size: V Operating Voltage: EMT Steel Conduit WG MCM V Length: Date Installed: lum. Conduit PVC Conduit m Measured Jacket Markings Direct Buried Underground Duct Other: Previous Data TDR Visual Inspection Physical Damage on Exposed Ends: Yes No Cable Identification Tag Installed: Yes No Visual Signs of Overheating: Yes No Cable Supported ppropriately: Yes No Bend Radius cceptable: Yes No Insulation Resistance Preparation: Source: Disconnected Connected with Source Isolated Cable Dest. / Load: Disconnected Connected with Load Isolated Cable Temperature: C Temperature Correction Factor for 20 C: Voltage V Reading Corrected to 20 o C Insulation Resistance (MΩ) -GND B-GND C-GND N-GND Utilize 1000VDC Voltage for 600V rated cables, VDC for cables rated <= 300V. Note: pproval of City s Representative is required, prior to leaving cables connected during the test. Ground all conductors not under test for each reading. Summary Passed Further Investigation Required. Connection Resistance Note: Torque check required for all cables. Connection Resistance required for cables 4/0 WG or larger. Connection Resistance (µω) - s Left Termination Torque Check B C N Source OK Dest. / Load OK Final nalysis Cable Returned to Service: Yes No Monitoring / Further Inspection Required: Yes No Repair / Replacement Required: Yes No Company Name Signature Date (yyyy/mm/dd) Performed By Checked By Form CBL-LV Rev 00, Created by SNC-Lavalin Inc. L:\40ENG\Clients\City of Winnipeg\Forms\Electrical\F-CBL-LV.doc
2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4
CHAPTER ELECTRICAL 2 INSTALLATION Contents of this Chapter... 2.1 Warnings & Agency Approvals..................2 2 2.1.1 Isolation..............................................2 2 2.1.2 Electrical Power
More informationSIRCO PV UL98B Load break switches for photovoltaic applications from 100 to 2000 A - up to 1500 VDC
Load break switches sircopv_058_a cat SIRCO PV UL98 from 00 to 2000 up to 500 VDC sircopv_059_a cat Strong points > Patented switching technology. > Positive break indication. > Up to 000 VDC as per characteristics
More information1-3 MANUAL STARTERS EXERCISE OBJECTIVE. Examine and describe the operation of manual motor starters. DISCUSSION
1-3 MANUAL STARTERS EXERCISE OBJECTIVE Examine and describe the operation of manual motor starters. DISCUSSION Motor starters are made out of power switches and overload protection devices. They can be
More informationSED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options
SED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options Product Description The SED2 Conventional Bypass (C-Bypass) Options are companion packages for the family of SED2 Variable Frequency
More informationSelection HP V Class V Class Input: 3 Phase Output Voltage: 3 Phase V at 60Hz Voltage Toleran
4 Project:_ Engineer:_ Mitsubishi Electric Automation, Inc. (MEAU) Variable Frequency Drives - HVAC System Submittal Summary Data Form NEMA 1 Bypass Systems Architect:_ Contractor:_ Submitted by: Date:
More informationSoftstarters Type PSS. Softstarters. General information
General information The PSS Softstarter line brings a wide array of benefits for smaller motors in a flexible, compact form. The PSS "Flexible" Softstarter line PSS18/30 to PSS300/515 softstarters provide
More informationContinuing Education Course #206 Introduction to Designing Machine Control Systems Part 2
1 of 5 Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2 1. Continuing to answer the following questions indicates that you understands that the presented material
More informationELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET54 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three hours
More informationSIRCO PV UL98B Load break switches for photovoltaic applications from 100 to 2000 A, up to 1500 VDC
Load break switches sircopv_058_a cat SIRCO PV UL98 new sircopv_059_a cat The solution for > Combiner box > Recombiner box > Inverter Function SIRCO PV UL98 non fusible disconnect switches are heavy duty
More informationB BASIC HEAT TREATMENT CONSOLE
Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL
More informationHigh Frequency SineWave Guardian TM
High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation
More informationISSUE DATE JANUARY 1st, 2008 SECTION 5C 240V 1PHASE W/TCU AND VFD
ISSUE DATE JANUARY 1st, 2008 SECTION 5C 240V 1PHASE W/TCU AND VFD CONTROL PANEL MOUNTING PAGE No. 74 NUMBER: LS-240V1PH-TCU-VFD 35 38 47 U A 9 33 V 26 24 25 41 43 7 7 44 ALUMINUM BACKPLATE 41 42 50 46
More informationWARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.
SECTION 230513 - MOTORS AND ADJUSTABLE SPEED DRIVES PART 1 - GENERAL 1.1 DESCRIPTION A. Provide labor, materials, equipment and services as required for the complete installation designed in Contract Documents.
More informationMotor Controllers AC Semiconductor Motor Controller Type RSHP Flexy
otor Controllers AC Semiconductor otor Controller Type RSHP Flexy Soft starting and stopping of 3-phase squirrel cage motors Low surge and vibration-free starting User-selected ramping profiles Integral
More informationSineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING
SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of
More informationApplication Description
-14 Type, Intelligent Technologies (IT.) Soft Starters February 2007 Contents Description Page Type, Intelligent Technologies (IT.) Soft Starters Product Description....... -14 Application Description....
More information600/1000V XLPE Insulated PVC Sheathed Power Cables (Multicore)
600/1000V XLPE Insulated PVC Sheathed Power Cables (Multicore) FGD400 1RV-R (CU/XLPE/PVC 600/1000V Class 2) Outdoor Cabling Earth Conductor Earth Conductor APPLICATION The cables are mainly used in power
More informationExercise 1-3. Manual Starters EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Direct-on-line (DOL) starters. Reversing starters
Exercise 1-3 Manual Starters EXERCISE OBJECTIVE Examine and describe the operation of manual motor starters. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Direct-on-line
More informationBasics of Medium Voltage Motor Control Starter Power Components & Starter Types
Basics of Medium Voltage Motor Control Starter Power Components & Starter Types Larry Dalton Lead Operation Specialist Jude Hernandez - Application Engineer GE Industrial Solutions Slide # 1, Rev 3, 11/8/16
More informationSDS Enclosed Star-Delta Starter User Guide
SDS Enclosed Star-Delta Starter User Guide (7.5kW~90kW) V2.0.0 PLEASE NOTE: AS STANDARD AND UNLESS OTHERWISE SPECIFIED, THIS PRODUCT IS EQUIPPED WITH A BASIC LOW INTEGRITY EMERGENCY STOP CIRCUIT STOPPING
More informationMAGNETIC MOTOR STARTERS
Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors
More informationMCE TM Product Information 5 kv Electric Motor Analyzer
www.pdma.com MCE TM Product Information 5 kv Electric Motor Analyzer Portable and battery powered Monitors Power Circuit, Insulation, Stator, Rotor, and Air Gap Variable test voltage from 250 to 5000 V
More informationSpring Test 7 due 05/03/2013
Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous
More information2015 EDITION SUBMERSIBLE MOTORS AIM MANUAL. APPLICATION INSTALLATION MAINTENANCE 60 Hz, Single-Phase and Three-Phase Motors. franklinwater.
0 EDITION AIM MANUAL SUBMERSIBLE MORS APPLICATION INSTALLATION 60 Hz, Single-Phase and Three-Phase Motors franklinwater.com All Motors System Troubleshooting Motor Does Not Start A. No power or incorrect
More informationAFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
PART B-07 TITLE: SERVICE CONNECTIONS SPECIFICTION NO: B-07 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) AMENDMENTS / REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationOpen Chassis Star-Delta Starter User Guide
Open Chassis Star-Delta Starter User Guide (7.5kW~90kW) V2.0.1 Contents 1 Safety information... 1 2 Technical Data... 2 3 Supply & Motor Connections & Circuit Diagrams... 5 4 Control Connections & Operation...
More informationB-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE
B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE Duty B: Power Distribution (600V and below) B-03: Troubleshoot 480V System Issued 06/01/98 Task Preview Troubleshoot 480V System The 480V distribution
More informationBAC Custom Engineered Controls
BAC Custom Engineered Controls Product Detail Product Introduction......................................... K2 BAC Custom Engineered Controls Benefits....................................................
More informationMAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-
MKING MODERN LIVING POSSIBLE Technical brochure Minicontactors CI 5- www.danfoss.com 2 IC.PD.C10.F3.02-520B4167 Danfoss /S, C-SMC, mr, 07-2010 Contents Page Minicontactor CI 5- Introduction...............................................................................4
More informationTechnical Information
Miniature Technical Information -09-12 Rated Insulation Voltage U i to IEC947-1 [V] 690V UL/CS [V] 600V Rated Impulse Voltage Withstand U imp [kv] 6 Rated Voltage Ue-Main Contacts C 50/60Hz [V] 230, 240,
More informationA200 NEMA Contactors and Starters A200
Starters Non-reversing and Reversing 11 Not to be used for construction purposes unless approved. Table 11. Open Reversing Starters Dimensions NEM of Poles Fig. Mounting Dimensions in Inches (mm) Screws
More informationChest Heated Ironer Refer to Page 3 for Model Numbers
Chest Heated Ironer Refer to Page 3 for Model Numbers Parts www.comlaundry.com Part No. 1800144R1 February 2008 Table of Contents Title Page Parts Ordering Information... 2 Nameplate Location... 2 Model
More informationSED2 Variable Frequency Drive Electronic Bypass (E-Bypass) Options
SED2 Variable Frequency Drive Electronic Bypass (E-Bypass) Options Product Description The SED2 Electronic Bypass (E-Bypass) Options are companion packages for the family of SED2 Variable Frequency Drives
More informationABB Softstarter Benefits Charnchanok Thongprad
ABB Softstarter Benefits Charnchanok Thongprad tomation Technology Products AB Control - 1 - - Why Softstarters? Benefits for the Electrical network Reduces voltage drops on networks Minimizes starting
More informationA. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:
SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationELECTRICIAN S THEORY EXAMINATION 19 June 2010 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET34 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 19 June 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three hours
More informationTechnical specifications
Technical specifications Type 3RW30 03 3RW3-1B0 3RW3-1B1 Control electronics Rated control supply voltage V 24 230 CDC 24 CDC (+10 %-15 %) 110 230 CDC (+10 %-15 %) Rated control supply Without fanwith
More informationMultiquip Submersible Pump Model ST-3050D
OPERATION AND PARTS MANUAL Multiquip Submersible Pump Model ST-3050D COPYRIGHT 2002, MULTIQUIP INC. Revision #1 (11/18/02) MULTIQUIP INC. 18910 WILMINGTON AVENUE CARSON, CALIFORNIA 90746 310-537-3700 800/421-1244
More informationHVAC Drives Lenze AC Tech MCH Series Price Book May US Dollars
HVAC Drives Lenze AC Tech MCH Series Price Book May 2015 - US Dollars Document: pcmchusd-0515_a MCH Series Drives: Model Number Designation Code The MCH Series drives are rated for variable torque applications,
More informationAGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS
Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This
More informationTABLE OF CONTENTS. Description Page Description Page. SETI Finland. Approvals:
3 ulletin 100 IEC Contactors ulletin 100 15 Sizes, 9 600 Guarded Terminals Dual Terminal Markings DC Control Option through 180 Wide Range of ccessories Top and Side Mounting uxiliary Contacts Timers Latches
More informationMatrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL
Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages
More informationHVW701 HVAC Drive with By-Pass
s Automation Energy Transmission & Distribution Coatings HVW701 HVAC with By-Pass Designed Especially for HVAC Systems US.HVW701.By-Pass.07/2017 www.weg.net WEG HVAC-R Products WEG, a leading supplier
More informationSolar Inverter Manual
Solar Inverter Manual Introduction SMPS series solar inverter power charging efficiency increased by 30%~60% than traditional controller charging. This inverter has automatic identification, three-stage
More informationTechnical Information
Contactors Contactors 95(-EI) 110(-EI) 140(-EI) 180(-EI) 210-EI 250-EI 300-EI 420-EI 630-EI 860-EI Rated Insulation Voltage U i IEC, S, BS, SEV, VDE 0660 [V] 1000V UL; CS [V] 600V Rated Impulse Voltage
More informationElectric Motor Controls BOMA Pre-Quiz
Electric Motor Controls BOMA Pre-Quiz Name: 1. How does a U.P.S. (uninterruptable power supply) work? A. AC rectified to DC batteries then inverted to AC B. Batteries generate DC power C. Generator, batteries,
More informationTypes of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:
Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor.
More informationGenerator Fire Safety: Generator assemblies should be located outside the building.
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building
More informationCutler-Hammer. Instructions for Installation, Operation, and Maintenance of the AMPGARD Reduced Voltage Soft Starter
Operation, and Maintenance of the Instruction Bulletin Read and understand these instructions before attempting any installation, operation, or maintenance of the. This equipment shall be installed and
More informationElectronic Circuit Breaker ESS20
Electronic Circuit Breaker ESS20 Description Electronic circuit breaker type ESS20 is designed to ensure selective disconnection of individual loads in systems which are powered by a DC 24 V switch-mode
More informationUBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit
More informationSensorless Vector Drives
STANDARD PRODUCTS Sensorless Vector Drives SG SERIES STANDARD DUTY / HEAVY DUTY RATINGS Variable Torque: 7.5 to 700HP @ 460V 7.5 to 40HP @ 2V Standard Duty: 7.5 to 600HP @ 460V 7.5 to 40HP @ 2V Heavy Duty:
More informationREFERENCE MANUAL FORM: MX-TRM-E REL REV MTE
Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation
More informationPure sine wave charger inverter Product Manual
Pure sine wave charger inverter Product Manual The inverter installer must be professional, for the high pressure in the inverter, unprofessional person please do not open it. The inverter should be installed
More informationThermal overload relays Type TA Class 10
Thermal overload relays Type TA Class Thermal Overload relays Description Available for starter construction with A Line contactors and separate panel mounting Designed for close couple mounting Separate
More informationSIDERMAT Load break switches for power distribution from 250 to 1800 A with tripping function
The solution for Load break switches sdmat_066_a cat > Main switchboard > Distribution panel > Motor load break unction SIDERMT 4 x 630 External front operation SIDERMT are manually operated 3 or 4 pole
More informationOperation and Protection of Motors up to 600Hp at 460Vac (800A)
Operation and of Motors up to 600Hp at 460Vac (800) WEG enclosed starters series were designed to meet the requirements and flexibility frequently demanded in industrial applications. Featuring components
More information320A Single Phase URD Meter Loop Installations
320A Single Phase URD Meter Loop Installations Location: The meter loop shall be mounted on the side of the pedestal facing the consumer's lot. (The side being one of the four flat surfaces of the pedestal
More informationA. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.
PART 1: GENERAL 1.01 This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to apply the
More information9/7/2010. Chapter , The McGraw-Hill Companies, Inc. MOTOR CLASSIFICATION. 2010, The McGraw-Hill Companies, Inc.
Chapter 2 MOTOR CLASSIFICATION 1 In general, motors are classified according to the type of power used (AC or DC) and the motor's principle of operation. AC DC Motor Family Tree 2 DC MOTOR CONNECTIONS
More informationC -5 to +55 (0.8 to 1.1Uc) Permissible o
T - Line Contactors 3 & 4 Pole Contactors with C operating coils General Characteristics Type Unit TC1-D09 ~ TC1-D95 Rated insulation voltage (Ui) (Conforming to IEC 158-1) V 750 VDEO 110grC/IEC 60947-4
More informationPRODUCT DRAWING WIRING DIAGRAM FIELD CONNECTIONS MILLENNIUM MODEL YT CHILLERS (STYLE J) WITH ELECTRO-MECHANICAL STARTER JOB DATA:
Supersedes: 160.55-PW4 (1199) FORM 160.55-PW4 (600) PRODUCT DRAWING YORK INTERNATIONAL CORPORATION P.O. Box 1592, YORK, PA 17405 CONTRACTOR ORDER NO. YORK CONTRACT NO. YORK ORDER NO. WIRING DIAGRAM FIELD
More informationElectronic Circuit Breaker ESS20-0..
Electronic Circuit Breaker ES-0.. Description Electronic circuit breaker type ES-0.. is designed to ensure selective disconnection of individual loads in systems which are powered by a DC 4 V switch-mode
More informationAC Drives Selection Guide
AC Drives Selection Guide Class 8839 CATALOG CONTENTS Description.................................................... Page Specifications..................................................... 3 Open Style
More information1333 (SERIES B & C) TROUBLESHOOTING GUIDE
1333 (SERIES B & C) TROUBLESHOOTING GUIDE Preventive Maintenance: Problems with Your Drive? Bulletin 1333 is convection or fan cooled by air flowing through the heat sink slots. The slots must never be
More informationREVISIONS. App Thom. App Sud. App PC T.C. 2013/10/01
REQUIREMENTS / REVISIONS Rev Description Rev n by Sud PC Thom VB LH Clyd Act Issue Date YYYY/MM/DD Standard Created T.C. 203/0/0 T.C. 203/0/0 Pending Pending Pending Pending Pending Pending 203/0/0 Sud
More informationSERVICE MANUAL MULTI DECK HOT MERCHANDISERS MD Versions. Solid back 3 and 5 level Pass through 3 and 5 level
SERVICE MANUAL MULTI DECK HOT MERCHANDISERS MD 60-100 - 120 Versions Solid back 3 and 5 level Pass through 3 and 5 level MD 60-3 solid back MD 100-3 pass through - NOTICE - This manual is prepared for
More informationInstruction Bulletin. Enclosed ALTISTART 46 Controller Supplemental Instruction Bulletin Class 8638 and 8639 INTRODUCTION
Instruction Bulletin Bulletin No. 0006-39-03 May 997 Raleigh, NC, USA Enclosed ALTISTART 6 Controller Supplemental Instruction Bulletin Class 8638 and 8639 INTRODUCTION This bulletin is a supplement to
More information1. INTRODUCTION SYSTEM DESCRIPTION Front Panel CONNECTION AND OPERATION TROUBLESHOOTING...8
Contents : 1. INTRODUCTION...1 2. IMPORTANT SAFETY INSTRUCTIONS...2 3. SYSTEM DESCRIPTION...4 3.1 Front Panel...4 4. CONNECTION AND OPERATION...6 5. TROUBLESHOOTING...8 6. MAINTENANCE...9 6.1 Operation...9
More informationChapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits.
Chapter 8 Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits. Article 430 of the NEC covers application and installation of
More informationASL09..S 3-pole Contactors - Spring Terminals
4 kw 5 hp ASL09..S 3-pole Contactors - Spring DC Operated Description - 3-pole contactors with spring terminals, - N.C. or N.O. built-in auxiliary contact, - Low coil consumption, - Polarity on the coil
More informationFor Type 2, No Damage circuit protection in all the configurations you need. A Amp-Trap 2000 Fuses
mp-trap 2000 Fuses For Type 2, No Damage circuit protection in all the configurations you need. Your problem: You need maximum overcurrent protection to prevent costly damage to today s highly sensitive
More informationC1000 Series Automatic Cap Bank
C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution
More informationData sheet. CI-tronic Soft start motor controller Type MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 50 I-O 520B1443
CI-tronic Soft start motor controller Type MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 50 I-O December 2002 DKACT.PD.C50.G2.02 520B1443 2 DKACT.PD.C50.G2.02 Danfoss A/S 12-2002 Introduction The MCI soft starters
More informationPanel SCCR 50kA RMS Symmetrical 480V Maximum
Panel SCCR 50kA RMS Symmetrical 480V Maximum 4 Short-Circuit Current Rating SCCR: The perspective or maximum symmetrical fault current at a nominal voltage to which an apparatus or system is able to be
More informationUser s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual
User s Manual ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual ii ACH550-CC/CD Packaged Drive with Classic Bypass ACH550 Drive Manuals GENERAL MANUALS ACH550-UH
More informationFUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A
Fuse protection The solution for > Motor load break > Protection of industrial cabinet > Electrical distribution fusom_063_b_1_cat Strong points > Tripping upon overload > High breaking capacity > Improved
More informationELECTRICIAN S THEORY EXAMINATION 21 June 2014 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET49 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 21 June 2014 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three hours
More informationUSER MANUAL MPS 1-5KW SERIES
USER MANUAL MPS 1-5KW SERIES Low Series Frequency Solar and Wind Power Charging Inverter CONTENTS 1 WWW.NEXTGENNRG.COM 1. Introduction... 3 2. Profile Structure 4 2.1. Working Principle 4 2.2.Product Features..5
More informationA. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.
DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings
More informationELECTRIC MACHINES EUROLAB 0.3 kw
index SINGLE-PHASE MOTORS SPLIT-PHASE MOTOR DL 30130 CAPACITOR MOTOR DL 30140 UNIVERSAL MOTOR DL 30150 REPULSION MOTOR DL 30170 THREE PHASE ASYNCHRONOUS MOTORS SQUIRREL CAGE THREE PHASE ASYNCHRONOUS MOTOR
More informationP445 Series Electronic Lube Oil Control
FANs 125, 121 s Section P Product/Technical Bulletin P445 Issue Date 0100 P445 Series Electronic Lube Oil The P445 Series Electronic Lube Oil is designed for use on refrigeration compressors equipped with
More informationdv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING
dv Sentry TM 208V 600V INSTALLATION GUIDE FORM: DVS-IG-E REL. January 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.
More informationD9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE
SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.
More informationSeries CA6 Contactors
Series C6 Contactors classic contactor for demanding applications from 75 to 600HP (@460V) - 100 to 700HP (@ 575V) This series is being replaced by the C9 Series of contactors Sprecher + Schuh s C6 contactor
More informationMULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers
IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when
More informationCompact Circuit Protector (CCP) Application Note
Compact Circuit Protector (CCP) Application Note Table Of Contents Application Note Description Page Objective............................................... 3 Compact Circuit Protector (CCP).............................
More informationChapter 6 Generator-Voltage System
Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals
More information1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3.
1332 TROUBLESHOOTING GUIDE Maintenance The Drive is convection or fan cooled by air flowing through the heat sink slots. The slots must never be allowed to become obstructed with dirt or foreign matter.
More informationPower Controller. (see note 1) 10 sec
Power Controller Single-phase Models EUN Series AC Power Controller with Phase-control System Allows Precise Temperature Control Models with Base-up and Soft-start Functions Available EH Series Phase Control
More informationBulletin 825 SMM Smart Motor Manager
Bulletin 825 SMM Smart Motor Manager Your order must include: Cat. no. of the Smart Motor Manager selected with supply Voltage Suffix Code, Cat. no. of Converter Module selected, and, If required, Cat.
More informationElectronic Bypass Controller
Installation and Commissioning Guide Electronic Bypass Controller HVAC Drive H300, Unidrive M200 and Unidrive M400 Part Number: PSD-H300BP-ICG Issue: 5.0 Contents Section 1 - Introduction... 5 Section
More informationELECTRICAL SERVICE TECHNICIAN EXAMINATION 16 September 2017 QUESTION AND ANSWER BOOKLET
Candidate Code No. EST 2074 For Board Use Only Result Date Int Result Date Int ELECTRICAL SERVICE TECHNICIAN EXAMINATION 16 September 2017 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed:
More informationEssential equipment for all your requirements
NEW CTX CONTACTORS Essential equipment for all your requirements 9 A TO 310 A THREE-POLE INDUSTRIAL CONTACTORS CTX three-pole industrial contactors, a sense of family The new range of CTX contactors provides
More informationQuick Start Guide TS 910
Quick Start Guide TS 910 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer is responsible
More informationManual motor starter MS132
Data sheet Manual motor starter MS132 Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less
More informationPentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION
PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company
More informationCI-Tronic Soft start motor controller MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 40-3D and MCI 50-3 I-O
Data sheet CI-Tronic Soft start motor controller MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 40-3D and MCI 50-3 I-O The MCI soft starters are designed for soft starting and stopping of 3 phase AC motors, thus
More informationXR500B Universal Voltage Regulator
XR500B Universal Voltage Regulator The XR500B is a unique voltage regulator that is designed specifically for Professional Electrical Generator Service and Repair Technicians. The XR500B incorporates patented
More informationREVELSTOKE - 1 YEAR DOWN. Applied to Equipment Instruction Number R Class-Group Generate Date: 11 March 2004
Page 1 of 7 Planned Maint. Type Turbo file - Job Group 1Y-DOWN Lead Trade Applied to Equipment Instruction Number R Class-Group Generate Date: 11 March 2004 Isolation Zone Supersedes References J:\PS\mep\Maintenance
More information