A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

Size: px
Start display at page:

Download "A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein."

Transcription

1 DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein. B. All variable frequency drives on the project shall be by the same manufacturer QUALITY ASSURANCE A. All equipment shall be UL listed and labeled and in accordance with applicable NEMA and ANSI Standards. B. The variable frequency drive(s) shall be provided with a three (3) year full parts and labor warranty, commencing at Project Completion. Warranty periods that begin at startup or on a ship date are not sufficient. C. NEMA ICS Safety Standards for Construction and Guide for Selection, Installation and Operation of Variable Frequency Drive Systems. D. NEMA - Enclosure for Electrical Equipment. E. IEEE Standard 444 (ANSI-C343). F. IEEE Standard 519. G. IEC 146A. H. IEC 16800, Parts 1 and MANUFACTURERS A. Square D, ABB, Toshiba, Eaton/Cutler-Hammer, and Yaskawa RELATED WORK SPECIFIED ELSEWHERE A. Conformance with all sections of the specifications is required. Additional requirements for the equipment specified within this section are included in, but not limited to the following Sections: , "TEMPERATURE CONTROL" 13-HC

2 PART 2 PRODUCTS 2.01 VARIABLE FREQUENCY DRIVE UNIT WITH BYPASS (ALL VFD'S EXCEPT THOSE FOR AIR HANDLING UNITS) A. The drive unit shall be microprocessor based using insulated gate bipolar transistors (IGBT). The unit shall put out variable frequency and voltage at a constant volts-per-hertz ratio for controlling standard AC induction motors using pulse width modulated technology. B. The drive unit and all components shall be mounted in a single NEMA 1 enclosure with a front accessibility only requirement. Enclosure shall contain a disconnect switch and semiconductor type current limiting fuses or circuit breaker giving the unit a 65,000 AIC rating. The disconnect switch shall extend through the enclosure front and be pad-lockable. All system components shall be mounted in a common steel enclosure. C. The enclosure shall contain separate fuses or circuit breaker for the drive unit and fuse or circuit breaker in the bypass circuit. There shall be a manually operated integrated bypass contactor interlocked and electrically with a drive output contactor allowing removal of the drive unit while permitting motor operation. Units serving 50 Hp motors or larger shall be provided with soft start on the bypass circuit. D. A minimum of 3% impedance by line reactors and/or input DC bus reactor shall be provided to limit the total harmonic voltage distortion to 5%. E. Motor thermal overloads shall be on the load side of the contactors. F. Output 3 - phase current sensing overload relay to provide motor protection in either VFD or bypass mode. G. Switching Frequency: To minimize electrical and acoustical noise the switching frequency shall be adjustable from 2 khz to 10 khz (minimum range). The anticipated full-speed carrier frequency settings are as follows: volt up to 30 Hp: 8-10 khz volt, 40 Hp and above: 4 khz volt up to 50 Hp: 10 khz volt, 60 to 100 Hp: 8 khz volt, 100 Hp and above: 4 khz. H. Adaptive electronic motor overload protection shall be provided which shall protect both motor and VFD at all frequencies. Electronic circuits protecting the motor at full speed are not acceptable. The circuits shall sense load and speed and shall reset the thermal trip curve for low speed motor protection. The initial trip point shall be adjustable from 40% of VFD continuous rating RATINGS A. Efficiency: 96% at 100% speed 80% at 50% speed B. Displacement Power Factor: 0.98 minimum HC1-033

3 C. Input Voltage: 460 or 208 (as shown on plans) volt +15%. D. Input Voltage Frequency: 48 to 63 Hz. E. Ambient Temperature Tolerance for Continuous Operation: 0-40 degrees C. F. Relative Humidity Tolerance for Continuous Operation: 0-95% at 40 degrees C. G. Maximum Non-Derated Altitude for Continuous Operation: 1000 meters. H. Speed Range: 2.5 Hz to 72 Hz. I. Minimum Powerloss Ride Thru: 2.0 seconds for units 5 Hp and larger. J. Adjustable Ramp Time Range: 0.1 to 999 seconds. K. Speed Regulation: 3%. L. Skip Frequencies: Two (2) or more. M. Maximum Corrected Harmonic Voltage Distortion Reflected into Supply: 5%. N. Operating Capacity: Provide variable frequency drives sized for continuous operation at 110% of the driven motor's full load rated current. Base sizing on the ambient environmental conditions listed above. O. Input surge protection using metal oxide varistors CONTROL FUNCTIONS A. All programmable parameters shall be adjustable from a digital operator keypad located on the front door of the VFD. Parameters shall include: 1. Programmable frequency command (keypad, remote). 2. Programmable start command (keypad, remote). 3. Forward start, stop, and digital speed control via digital operator keypad. 4. Programmable maximum and minimum frequency limits. 5. Programmable acceleration and deceleration times. 6. Programmable carrier frequencies, V/Hz, and critical frequency avoidance lockout zones. 7. Programmable electronic overload and torque limits. 8. Programmable multiple attempt restart. 9. Programmable preset speeds. 10. Programmable dwell time at start to maximize motor starting torque. 11. Programmable "Speed Search Transfer" function. (The VFD shall be capable of start from bypass or fault trip into a spinning load from 100% forward to 100% reverse rotation without stopping the motor or creating a fault condition. 13-HC

4 B. The VFD shall have the following system interfaces: 1. Inputs a. Process control speed reference interface to receive a 0-10 volt DC signal or 4-20 milliamp signal. b. Remote mode start contact. c. Remote preset speed contacts. d. Remote reset contact. 2. Outputs a. Run relay with an isolated set of Form C contacts. b. Dry contact output to indicate protective function trip. c. Analog output signal proportional to output frequency. d. Provide serial communications link via RS-485 connection. e. Provide BACNet Communication Protocol connection in accordance with the requirements of the Building Automation System (BAS). C. Monitoring and Displays 1. The VFD shall have an alpha-numeric display indicating monitored functions as described in the following: a. Output current b. Output frequency c. Motor rpm percent d. Trip cause (up to four sequential faults. All system information shall be stored for the three (3) seconds previous to the last fault) e. Output voltage f. DC bus voltage g. Output power 2. External Pilot Devices or Functions: a. Hand-Off-Auto Switch (for speed control) b. Speed potentiometer c. Fault Pilot Light (LED) d. Drive on Pilot Light (LED) D. Protection Functions 1. The VFD shall include the following protective features: a. AC input line current limiting fuses rated 200,000 AIC b. Overcurrent protection c. Overvoltage protection d. Undervoltage protection e. Overfrequency protection f. Phase loss protection g. Overtemperature protection h. Ground fault protection i. Adjustable current limit j. Line-to-line and line-to-ground short circuit protection k. Input line reactors HC1-033

5 E. Other Functions 1. Auxiliary drive status relay with two Form C relay pairs, rated 2 amps resistive at 120- volt AC for indication of running condition. 2. VFD shall include dv/dt filtering or line reactors on all 460 volt motors 15 Hp and less if the wiring between the VFD and the motor exceeds 120 feet (wire path) and on all 460 volt motors 20 Hp and greater if the wiring between the VFD and motor exceeds 200 feet /460 volt motors operating at volts and 460 volt inverter duty motors in full compliance with NEMA MG-Part 31, are not required to have output filtering. Adjust the distances per manufacturer's recommendation and submit chart for review VARIABLE FREQUENCY DRIVE UNIT WITHOUT BYPASS (ONLY FOR AIR HANDLING UNIT VFD'S) A. The drive unit shall be microprocessor based using insulated gate bipolar transistors (IGBT). The unit shall put out variable frequency and voltage at a constant volts-per-hertz ratio for controlling standard AC induction motors using pulse width modulated technology. B. The drive unit and all components shall be mounted in a single NEMA 1 enclosure with a front accessibility only requirement. Enclosure shall contain a disconnect switch and semiconductor type current limiting fuses or circuit breaker giving the unit a 65,000 AIC rating. The disconnect switch shall extend through the enclosure front and be pad-lockable. All system components shall be mounted in a common steel enclosure. C. A minimum of 3% impedance by line reactors and/or input DC bus reactor shall be provided to limit the total harmonic voltage distortion to 5%. D. Motor thermal overloads shall be on the load side of the contactors. E. Output 3 - phase current sensing overload relay to provide motor protection. F. Switching Frequency: To minimize electrical and acoustical noise the switching frequency shall be adjustable from 2 khz to 10 khz (minimum range). The anticipated full-speed carrier frequency settings are as follows: volt up to 30 Hp: 8-10 khz volt, 40 Hp and above: 4 khz volt up to 50 Hp: 10 khz volt, 60 to 100 Hp: 8 khz volt, 100 Hp and above: 4 khz. G. Adaptive electronic motor overload protection shall be provided which shall protect both motor and VFD at all frequencies. Electronic circuits protecting the motor at full speed are not acceptable. The circuits shall sense load and speed and shall reset the thermal trip curve for low speed motor protection. The initial trip point shall be adjustable from 40% of VFD continuous rating. 13-HC

6 H. Adaptive electronic motor overload protection shall be provided which shall protect both motor and VFD at all frequencies. Electronic circuits protecting the motor at full speed are not acceptable. The circuits shall sense load and speed and shall reset the thermal trip curve for low speed motor protection. The initial trip point shall be adjustable from 40% of VFD continuous rating RATINGS A. Efficiency: 96% at 100% speed 80% at 50% speed B. Displacement Power Factor: 0.98 minimum. C. Input Voltage: 460 or 208 (as shown on plans) volt +15%. D. Input Voltage Frequency: 48 to 63 Hz. E. Ambient Temperature Tolerance for Continuous Operation: 0-40 degrees C. F. Relative Humidity Tolerance for Continuous Operation: 0-95% at 40 degrees C. G. Maximum Non-Derated Altitude for Continuous Operation: 1000 meters. H. Speed Range: 2.5 Hz to 72 Hz. I. Minimum Powerloss Ride Thru: 2.0 seconds for units 5 Hp and larger. J. Adjustable Ramp Time Range: 0.1 to 999 seconds. K. Speed Regulation: 3%. L. Skip Frequencies: Two (2) or more. M. Maximum Corrected Harmonic Voltage Distortion Reflected into Supply: 5%. N. Operating Capacity: Provide variable frequency drives sized for continuous operation at 110% of the driven motor's full load rated current. Base sizing on the ambient environmental conditions listed above. O. Input surge protection using metal oxide varistors CONTROL FUNCTIONS A. All programmable parameters shall be adjustable from a digital operator keypad located on the front door of the VFD. Parameters shall include: 1. Programmable frequency command (keypad, remote). 2. Programmable start command (keypad, remote). 3. Forward start, stop, and digital speed control via digital operator keypad. 4. Programmable maximum and minimum frequency limits. 5. Programmable acceleration and deceleration times HC1-033

7 6. Programmable carrier frequencies, V/Hz, and critical frequency avoidance lockout zones. 7. Programmable electronic overload and torque limits. 8. Programmable multiple attempt restart. 9. Programmable preset speeds. 10. Programmable dwell time at start to maximize motor starting torque. 11. Programmable "Speed Search Transfer" function. (The VFD shall be capable of start from bypass or fault trip into a spinning load from 100% forward to 100% reverse rotation without stopping the motor or creating a fault condition. B. The VFD shall have the following system interfaces: 1. Inputs a. Process control speed reference interface to receive a 0-10 volt DC signal or 4-20 milliamp signal. b. Remote mode start contact. c. Remote preset speed contacts. d. Remote reset contact. 2. Outputs a. Run relay with an isolated set of Form C contacts. b. Dry contact output to indicate protective function trip. c. Analog output signal proportional to output frequency. d. Provide serial communications link via RS-485 connection. e. Provide BACNet Communication Protocol connection in accordance with the requirements of the Building Automation System (BAS). C. Monitoring and Displays 1. The VFD shall have an alpha-numeric display indicating monitored functions as described in the following: a. Output current b. Output frequency c. Motor rpm percent d. Trip cause (up to four sequential faults. All system information shall be stored for the three (3) seconds previous to the last fault) e. Output voltage f. DC bus voltage g. Output power 2. External Pilot Devices or Functions: a. Hand-Off-Auto Switch (for speed control) b. Speed potentiometer c. Fault Pilot Light (LED) d. Drive on Pilot Light (LED) D. Protection Functions 1. The VFD shall include the following protective features: a. AC input line current limiting fuses rated 200,000 AIC b. Overcurrent protection c. Overvoltage protection d. Undervoltage protection e. Overfrequency protection f. Phase loss protection g. Overtemperature protection 13-HC

8 h. Ground fault protection i. Adjustable current limit j. Line-to-line and line-to-ground short circuit protection k. Input line reactors E. Other Functions 1. Auxiliary drive status relay with two Form C relay pairs, rated 2 amps resistive at 120- volt AC for indication of running condition. 2. VFD shall include dv/dt filtering or line reactors on all 460 volt motors 15 Hp and less if the wiring between the VFD and the motor exceeds 120 feet (wire path) and on all 460 volt motors 20 Hp and greater if the wiring between the VFD and motor exceeds 200 feet /460 volt motors operating at volts and 460 volt inverter duty motors in full compliance with NEMA MG-Part 31, are not required to have output filtering. Adjust the distances per manufacturer's recommendation and submit chart for review. PART 3 EXECUTION 3.01 INSTALLATION A. Install fabricated steel floor stands for mounting drives where loads are in the center of a room or mounting the drive to a wall as required. Floor stands shall be an appropriatelysized galvanized metal framing system or 2 inch steel angle with galvanized finish. Provide the complete installation of all accessories provided with the variable frequency drive (including but not limited to the line reactor and the output filter). This contractor shall provide fuses (as furnished by the variable frequency drive manufacturer) in all fuse holders. Final connections to equipment shall be by the Electrical Contractor and shall be made using liquid-tight flexible steel conduit. B. Provide nameplates in accordance with all other provisions of these specifications. C. Drives shall be protected from dirt and moisture at all times. D. The line reactors and output filters shall be integral to package STARTUP AND TESTING A. Start up and testing shall be conducted by manufacturer's authorized field technical representative. B. Provide a full functional test of all components and operation of variable frequency drives in accordance with manufacturer's recommended procedure. C. Operate system for a minimum period of seven (7) consecutive days with no problems before final acceptance by Owner. END OF SECTION HC1-033

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK PART 1 - GENERAL 1.1 GENERAL: SECTION 15150 MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK A. The Mechanical Contractor shall furnish to the Electrical Contractor for installation,

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

VARIABLE FREQUENCY DRIVES

VARIABLE FREQUENCY DRIVES 262923 VARIABLE FREQUENCY DRIVES PART 1: GENERAL 1.01 SUMMARY A. Section Includes: 1. Variable Frequency Drives (VFD) B. Related Sections: 1. Section 230000 - Basic HVAC Requirements 2. Section 230900

More information

SECTION VARIABLE FREQUENCY DRIVE UNITS

SECTION VARIABLE FREQUENCY DRIVE UNITS SECTION 26 29 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide variable frequency drive (VFD) units, complete and operable, in accordance with the Contract Documents. It

More information

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Related Sections: 1. Section 15050 - Basic Mechanical Requirements. 2. Section 15051 - Motors. 3. Section 15185 - Hydronic Pumps. 4. Section 15625 - Centrifugal

More information

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives. SECTION 230513 - MOTORS AND ADJUSTABLE SPEED DRIVES PART 1 - GENERAL 1.1 DESCRIPTION A. Provide labor, materials, equipment and services as required for the complete installation designed in Contract Documents.

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP Phoenix DX Sensorless AC Vector Drive 3 HP to 3500 HP Standard Features: * PRECISE CONTROL OF MOTOR SPEED AND TORQUE * BI-DIRECTIONAL FLYCATCHER (CATCH SPINNING MOTOR) * EASY TO USE, SIMPLE SETUP * POWER

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

CTi Automation - Phone: Fax: Web:

CTi Automation - Phone: Fax: Web: CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net The control & protection you expect in an innovative soft starter design... Flexibility

More information

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

Softstarters. Softstarters Type SSM Medium voltage ,800V 1 Medium voltage 2300 13,800V 1 Description Fused disconnect switch with blown fuse indicators and door safety interlocks rated for load break/fault make with automatic grounding arm Inline isolation vacuum

More information

Delta Products VFD CP2000 Bypass Control Packages.

Delta Products VFD CP2000 Bypass Control Packages. Delta Products VFD CP2000 Bypass Control Packages www.deltaww.com Delta Products VFD CP2000 Bypass Control Packages The Delta Products VFD CP2000 Bypass Control Packages are designed for the Delta Products

More information

Selection HP V Class V Class Input: 3 Phase Output Voltage: 3 Phase V at 60Hz Voltage Toleran

Selection HP V Class V Class Input: 3 Phase Output Voltage: 3 Phase V at 60Hz Voltage Toleran 4 Project:_ Engineer:_ Mitsubishi Electric Automation, Inc. (MEAU) Variable Frequency Drives - HVAC System Submittal Summary Data Form NEMA 1 Bypass Systems Architect:_ Contractor:_ Submitted by: Date:

More information

SECTION 16483C ADJUSTABLE FREQUENCY DRIVE - CLEAN POWER (CPX)

SECTION 16483C ADJUSTABLE FREQUENCY DRIVE - CLEAN POWER (CPX) ADJUSTABLE FREQUENCY DRIVE - CLEAN POWER (CPX) PART 1 GENERAL 1.01 SCOPE A. This specification describes the electrical, mechanical, environmental, agency and reliability requirements for three-phase,

More information

SmartVFD HVAC FEATURES APPLICATION SPECIFICATION DATA

SmartVFD HVAC FEATURES APPLICATION SPECIFICATION DATA SmartVFD HVAC APPLICATION The SmartVFD HVAC is a variable frequency drive designed for use in HVAC application to control the speed of HVAC pumps and fans in order to maximize energy efficiency. Smart

More information

VSD Series II Variable Speed Micro Drives

VSD Series II Variable Speed Micro Drives VSD Series II Variable Speed Micro Drives Product Bulletin Code No. LIT-12011813 Issued March 26, 2013 Refer to the QuickLIT website for the most up-to-date version of this document. Johnson Controls VSD

More information

ROBICON W120 enclosed drive

ROBICON W120 enclosed drive SINAMICS Drives ROBICON W120 enclosed drive 1 HP to 200 HP Introduction This technical data sheet provides a short overview of the most important characteristics of the ROBICON W120 enclosed standard 6-pulse

More information

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards: SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

www. ElectricalPartManuals. com

www. ElectricalPartManuals. com General Information The Westinghouse Accutrol 300 consists of a family of microprocessor-based, digital high efficiency, adjustable frequency motor controllers in the power range from 15 to 500 HP constant

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph

More information

Description 1/8-7.5HP

Description 1/8-7.5HP Description 1/8-7.5HP J1000 In our pursuit to create drives optimized for variable speed needs in compact applications, the J1000 is the solution. This micro-drive is simple and reliable with Yaskawa quality.

More information

WARREN COUNTY, N.Y. M/E REFERENCE

WARREN COUNTY, N.Y. M/E REFERENCE SECTION 262000 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 DESCRIPTION A. Provide a complete secondary distribution system as indicated on the Contract Documents and as specified herein. 1.2 QUALITY ASSURANCE

More information

Ice Rink Renovation & New Clubhouse

Ice Rink Renovation & New Clubhouse SECTION 262913 - ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

TR1 Series VFD. Variable Frequency Drives TR1-SLB005-EN

TR1 Series VFD. Variable Frequency Drives TR1-SLB005-EN TR1 Series VFD Variable Frequency Drives April 2003 175R5568 Introduction Trane TR1 Series VFD The most commonly used motor in HVAC installations today is the three-phase, asynchronous AC induction motor,

More information

J1000 D E F I 1000 J1000 J1000 J1000 J1000

J1000 D E F I 1000 J1000 J1000 J1000 J1000 Compact Inverter SERIES J1000 GB D E F I 1000 J1000 J1000 J1000 J1000 The J-Type YASKAWA Inverter Drive Technology Contents Page 2 Experience & Innovation A leader in Inverter Drives technology Page 3

More information

J1000. Compact Inverter Series.

J1000. Compact Inverter Series. J1000 Compact Inverter Series www.yaskawa.eu.com Focus on Application Customer orientation and application focus two attributes of machine equipment YASKAWA offers with its J1000 compact inverter drive

More information

JC-VSD FP Series II Drives Product Bulletin 1

JC-VSD FP Series II Drives Product Bulletin 1 JC-VSD FP Series II Drives Product Bulletin Code No. LIT-12012081 Issued May 2017 The Johnson Controls VSD FP Series II provides the advanced technology and features of the Johnson Controls VSD Series

More information

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting

More information

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible

More information

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

1333 (SERIES B & C) TROUBLESHOOTING GUIDE 1333 (SERIES B & C) TROUBLESHOOTING GUIDE Preventive Maintenance: Problems with Your Drive? Bulletin 1333 is convection or fan cooled by air flowing through the heat sink slots. The slots must never be

More information

Illuminator Series CR NEMA 3R

Illuminator Series CR NEMA 3R Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the

More information

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp VS1MX AC Micro Drive 1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp & Controls 115 VAC 230 VAC 230 VAC 460 VAC 1 Phase - 50/60 Hz 1 Phase - 50/60 Hz 3 Phase - 50/60 Hz 3 Phase - 50/60 Hz Applications:

More information

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp VS1MX AC Micro Drive 1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp & Controls 115 VAC 230 VAC 230 VAC 460 VAC 1 Phase - 50/60 Hz 1 Phase - 50/60 Hz 3 Phase - 50/60 Hz 3 Phase - 50/60 Hz Applications:

More information

RVS-DN Digital Reduced Voltage Motor Starter

RVS-DN Digital Reduced Voltage Motor Starter RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

HVAC Products. Introducing the SED2 Variable Frequency Drives

HVAC Products. Introducing the SED2 Variable Frequency Drives HVAC Products Introducing the SED2 Variable Frequency Drives Designed Specifically for HVAC Applications From a global leader in drives technology and innovation, now comes a drive specifically configured

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 MOTOR CONTROLLERS SPEC WRITER NOTE: Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

MaxPak Plus Analog DC V S Drive

MaxPak Plus Analog DC V S Drive Three-Phase 3-600 HP non-regenerative and 5-150 HP regenerative drives Designed to accommodate a wide range of industrial requirements, the DC V S Drive has been widely applied worldwide. Selected ratings

More information

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM Contents Section Page 1.0 Introduction 1 2.0 Specification 1-4 3.0 Installation 5-8 4.0 Programming 9-10 5.0 Menus 10-12 6.0 Fault Finding/Diagnostics 12-13 7.0 Communication 13 8.0 Setting Up 13-16 1.0

More information

Varispeed E7. Varispeed E7. Varispeed. Varispeed E7. Varispeed E7. Varispeed E7 INVERTER SERIES

Varispeed E7. Varispeed E7. Varispeed. Varispeed E7. Varispeed E7. Varispeed E7 INVERTER SERIES INVERTER SERIES Varispeed E VARISPEED E YASKAWA INVERTER DRIVE TECHNOLOGY Contents Content Page 2 Experience & Innovation A leader in Drives technology Page 3 Specifications Experience & Innovation For

More information

GS2 Series - Introduction

GS2 Series - Introduction GS2 Series - Introduction GS2 Series Drives Rating Hp.25.5 1 2 3 5 7.5 10 kw 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 Single-Phase 115 Volt Class Single/Three-Phase 230 Volt Class Three-Phase 230 Volt Class Three-Phase

More information

Honeywell CORE Drive FEATURES APPLICATION SPECIFICATION DATA

Honeywell CORE Drive FEATURES APPLICATION SPECIFICATION DATA Honeywell CORE Drive SPECIFICATION DATA FEATURES APPLICATION The new Honeywell VFD CORE Drive addresses the need to save time for installation, and provides the lower total installed costs with years of

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting

More information

RVS-DX Digital Reduced Voltage Motor Starter

RVS-DX Digital Reduced Voltage Motor Starter RVS-DX Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

VLT HVAC Drives Technical Reference Supplement

VLT HVAC Drives Technical Reference Supplement VLT HVAC Drives Technical Reference Supplement 37 million tons of CO 2 are saved every year by the 4 million VLT Drives installed worldwide from Danfoss www.danfossdrives.com Automated Operational Features

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS SECTION 16420 ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

VSD Series II Variable Speed Enclosed IntelliPass and IntelliDisconnect Drives

VSD Series II Variable Speed Enclosed IntelliPass and IntelliDisconnect Drives VSD Series II Variable Speed Enclosed IntelliPass and IntelliDisconnect Drives Product Bulletin Code No. LIT-12011814 Issued February 4, 2013 The Johnson Controls VSD Series II Variable Speed Enclosed

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual User s Manual ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual ii ACH550-CC/CD Packaged Drive with Classic Bypass ACH550 Drive Manuals GENERAL MANUALS ACH550-UH

More information

Large Drive. Variable Speed Control is Just the Beginning. Franklin FastApp Firmware. Variable Speed Control NEMA. Standard Features (Enclosed Drives)

Large Drive. Variable Speed Control is Just the Beginning. Franklin FastApp Firmware. Variable Speed Control NEMA. Standard Features (Enclosed Drives) Large Drive Variable Speed Control is Just the Beginning NEMA Franklin FastApp Firmware Pre-configured for easy operation and optimal performance PSI unit display Sleep and wake up functions Lubrication

More information

TECHNICAL BROCHURE BAQUACPC. Aquavar CPC VARIABLE SPEED CENTRIFUGAL PUMP CONTROLLER

TECHNICAL BROCHURE BAQUACPC. Aquavar CPC VARIABLE SPEED CENTRIFUGAL PUMP CONTROLLER TECHNICAL BROCHURE BAQUACPC Aquavar CPC VARIABLE SPEED CENTRIFUGAL PUMP CONTROLLER Introduction The Aquavar CPC (Centrifugal Pump Controller) from incorporates the latest state-of-the-art Aquavar technology,

More information

300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds

300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds Digital Soft Start Controls 9 thru 900 Amps 208-460V 50/60 Hz. 9 thru 900 Amps 208-575V 50/60 Hz. Applications: Controlled ramp start and stop, minimize spillage in material handling, reduced water hammer

More information

Regenerative DC Common Bus Supply

Regenerative DC Common Bus Supply Regenerative DC Common Bus Supply The Regenerative DC Common Bus Supply supplies both motoring and regenerative current to the DC bus of one or more AC drives without the need of rectifier front end in

More information

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical

More information

RPM AC TM Direct Drive Synchronous PM Cooling Tower Motor and Matched AF Controller Specification Guide

RPM AC TM Direct Drive Synchronous PM Cooling Tower Motor and Matched AF Controller Specification Guide RPM AC TM Direct Drive Synchronous PM Cooling Tower Motor and Matched AF Controller Specification Guide Part 1 General 1.1 Purpose and Scope: Motor Revision 2.0, January 7, 2011 Motor Revision 3.0, May

More information

BR Second Position Voltages. AA Fourth Position

BR Second Position Voltages. AA Fourth Position 1336S First Position Bulletin Number BR Second Position Voltage Letter AQ BR CW A B BP BX C Q R RX W Voltages 200-240V AC or 3V DC 380-480VAC or 513-620V DC 500-600V AC or 775V DC or 200-240V AC 380-480V

More information

Standard Features 200-600V, 50/60Hz input power supply Built-in run rated (AC1) By-pass contactor up to 820 A * Rated 450% current Conformal coated circuit board Voltage ramp or current limit start modes

More information

150 B180 N B D A 8L. Enclosure Type. Input Line Voltage Open Type V AC, 3-phase, 50 and 60 Hz V AC, 3-phase, 50 and 60 Hz

150 B180 N B D A 8L. Enclosure Type. Input Line Voltage Open Type V AC, 3-phase, 50 and 60 Hz V AC, 3-phase, 50 and 60 Hz Catalog Number Explanation Open Controllers a Bulletin Number Solid-State Controller B H H B B B B B B B B B B B B B Solid-State Controller and Isolation Contactor (enclosed only) b Controller Ratings

More information

SED2. Variable Frequency Drives. with Conventional Bypass Options. Variable Frequency Drives. Description. Features F-9.

SED2. Variable Frequency Drives. with Conventional Bypass Options. Variable Frequency Drives. Description. Features F-9. SED2 with Conventional Bypass Options Important Note: VD products are only available through authorized distribution channels. To locate an authorized distributor, please contact a Siemens Building Technologies

More information

RVS-AX Instruction Manual

RVS-AX Instruction Manual RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3

More information

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Retain for future use. 30072-450-47A July 2002 Raleigh, NC, USA HAZARDOUS VOLTAGE Read and understand

More information

SECTION DC POWER SUPPLY/BATTERY CHARGER

SECTION DC POWER SUPPLY/BATTERY CHARGER SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance

More information

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual User s Manual ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual ii ACH550-CC/CD Packaged Drive with Classic Bypass ACH550 Drive Manuals GENERAL MANUALS ACH550-UH

More information

BRAQCPC IT T. Goulds Pumps AQUAVAR CPC. Variable Speed Centrifugal Pump Controller. Engineered for life

BRAQCPC IT T. Goulds Pumps AQUAVAR CPC. Variable Speed Centrifugal Pump Controller. Engineered for life BRAQCPC IT T Goulds Pumps AQUAVAR CPC Variable Speed Centrifugal Pump Controller Engineered for life Goulds Pumps Variable Speed Centrifugal Pump Controller 2 Introduction The Aquavar CPC (Centrifugal

More information

VS1PFB 230V, 50/60 Hz, 3-Phase

VS1PFB 230V, 50/60 Hz, 3-Phase Farm Duty Unit Handling Brake 200 & 575 Volt Pump and Fan Bypass AC Drive 7.5 thru 40 Hp 7.5 thru 125 Hp & Controls 230 VAC 460 VAC 3 Phase - 50/60 Hz 3 Phase - 50/60 Hz Applications: Pump and Fan AC Drive

More information

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation M T E C o r p o r a t i o n MTE Series RL Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL. 050516 2002 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RL Line/Load Reactors are components

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Hp V AC Current Rating [A] 230V AC 60 Hz

Hp V AC Current Rating [A] 230V AC 60 Hz Product Selection/Options Open Type Controllers Up to V AC kw Hp V AC Current Rating [A] V AC Hz V AC Hz V AC Hz V AC Hz V AC Hz / Hz Control V AC/DC Control.. -BNBD -BNBR. -BNBD -BNBR -BNBD -BNBR -BNBD

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090529 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW Line/Load Reactors are components designed to improve the

More information

SMC -50 Reduced Voltage Solid-State Smart Motor Controllers

SMC -50 Reduced Voltage Solid-State Smart Motor Controllers ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION SMC -50 Reduced Voltage Solid-State Smart Motor Controllers NOTICE: The specification guidelines in this document are intended to

More information

Sensorless Vector Drives

Sensorless Vector Drives STANDARD PRODUCTS Sensorless Vector Drives SG SERIES STANDARD DUTY / HEAVY DUTY RATINGS Variable Torque: 7.5 to 700HP @ 460V 7.5 to 40HP @ 2V Standard Duty: 7.5 to 600HP @ 460V 7.5 to 40HP @ 2V Heavy Duty:

More information

2.3. Adjustable Frequency Drives. Contents. Standards and Certifications

2.3. Adjustable Frequency Drives. Contents. Standards and Certifications Contents Selection................ Product Selection....................... Accessories........................... Technical Data and Specifications.......... Dimensions........................... Page

More information

SINUS PENTA 2T/4T SINUS PENTA 2T/4T

SINUS PENTA 2T/4T SINUS PENTA 2T/4T SINUS PENTA 2T/4T SINUS PENTA 2T/4T Technical Highlights One product, 5 integrated functions - IFD (Inverter Frequency Drive): vector modulation function for general-purpose applications (V/F pattern).

More information

Sola/Hevi-Duty S3K Series Mini-Tower UPS

Sola/Hevi-Duty S3K Series Mini-Tower UPS Sola/Hevi-Duty S3K Series Mini-Tower UPS GUIDE SPECIFICATIONS 700VA to 1600VA 120V models Single - Phase Uninterruptible Power Supply Systems 1.1 SUMMARY 1.0 GENERAL This specification defines the electrical

More information

ACH550 VARIABLE FREQUENCY DRIVES FOR HVAC APPLICATIONS

ACH550 VARIABLE FREQUENCY DRIVES FOR HVAC APPLICATIONS ACH550 VARIABLE FREQUENCY DRIVES FOR HVAC APPLICATIONS (Disconnect and Bypass Packages are available on Pages 56 and 57) Two Year Warranty* *When Gerrie commissions the drive Features: UL/cUL/CSA Approved

More information

AC Drives Selection Guide

AC Drives Selection Guide AC Drives Selection Guide Class 8839 CATALOG CONTENTS Description.................................................... Page Specifications..................................................... 3 Open Style

More information

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs. SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products

More information

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and

More information

BAC Custom Engineered Controls

BAC Custom Engineered Controls BAC Custom Engineered Controls Product Detail Product Introduction......................................... K2 BAC Custom Engineered Controls Benefits....................................................

More information

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD Safety Precautions Read this manual thoroughly before proceeding with installation, connections (wiring), or maintenance and inspection. Ensure you

More information

300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds

300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds Digital Soft Start Controls Soft Starters & 9 thru 900 s 208-460V 50/60 Hz. 9 thru 900 s 208-575V 50/60 Hz. Farm Duty Applications: Controlled ramp start and stop, minimize spillage in material handling,

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3.

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3. 1332 TROUBLESHOOTING GUIDE Maintenance The Drive is convection or fan cooled by air flowing through the heat sink slots. The slots must never be allowed to become obstructed with dirt or foreign matter.

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

GUIDE SPECIFICATIONS 15-45kVA and 15-90kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

GUIDE SPECIFICATIONS 15-45kVA and 15-90kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL 1.1 SUMMARY Liebert APM UPS GUIDE SPECIFICATIONS 15-45kVA and 15-90kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL Liebert APM UPS, 15-45 kva and 15-90 kva Scalable This specification

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 24 14 600 VOLT DRAWOUT SWITCHGEAR PART 1 - GENERAL 1.01 SECTION INCLUDES: A. Individually mounted rear-accessible low voltage switchgear ANSI rated switchgear and low voltage power circuit breakers

More information

PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 23 74 13 PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Chapter 1: Getting Started User Manual Overview...1 2

Chapter 1: Getting Started User Manual Overview...1 2 Getting Started Chapter 1 Table of Contents Chapter 1: Getting Started User Manual Overview.........................................1 2 Overview of this Publication.........................................

More information

SED2 VFD NEMA Type 3R and Type 3R Harsh Environment (3RHE) Bypass

SED2 VFD NEMA Type 3R and Type 3R Harsh Environment (3RHE) Bypass SED2 VD NEMA Type 3R and Type 3R Harsh Environment (3RHE) Bypass Description The NEMA Type 3R Bypasses are companion packages for the family of SED2 Variable requency Drives (VD). NEMA Type 3R/3RHE enclosed

More information

Critical Power Switchboards. Selection and Application Guide

Critical Power Switchboards. Selection and Application Guide Selection and Application Guide Siemens RCIII (rear connected) switchboards utilizing Siemens Type SB Encased Breakers are a perfect solution for your critical power distribution needs. Whether your installation

More information

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of

More information

SD700FR. Regenerative Active Front End VARIABLE SPEED DRIVES POWER ELECTRONICS / SD700 SERIES 4 QUADRANT. icool

SD700FR. Regenerative Active Front End VARIABLE SPEED DRIVES POWER ELECTRONICS / SD700 SERIES 4 QUADRANT. icool FR VARIABLE SPEED DRIVES Regenerative Active Front End icool 4 QUADRANT POWER ELECTRONICS / SD700 SERIES FR SD700FR SERIES goes one step ahead keeping the family unique characteristics. Based on the latest

More information

REGAL-BELOIT SpinMaster AC Adjustable Speed Drives

REGAL-BELOIT SpinMaster AC Adjustable Speed Drives REGAL-BELOIT SpinMaster Volts/Hertz Constant Torque, Micro Inverter Applications: Constant torque or constant horsepower applications. Typical applications include conveyors, packaging machinery, machine

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information