Motor Protection Circuit Breaker and Motor Circuit Protector Specifications

Size: px
Start display at page:

Download "Motor Protection Circuit Breaker and Motor Circuit Protector Specifications"

Transcription

1 Technical Data Motor Protection Circuit Breaker and Motor Circuit Protector Specifications Bulletin Number 140M Topic Page Bulletin 140M Motor Protection Circuit Breakers 3 Overview 3 Catalog Number Explanation 5 Application Diagrams 6 Bulletin 140M Motor Circuit Protectors 9 Overview 9 Catalog Number Explanation 10 Application Diagrams 11 Specifications 13 Application Ratings 13 Definition of Type 2 Short Circuit Coordination: 19 Specifications 22 Cutoff Current 33 Approximate Dimensions 39 Summary of Changes This publication updates current rating information beginning on page 22. Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Use of Motor Protection Circuit Breakers with Variable- Frequency Drives, publication 140M-AT002 Industrial Automation Wiring and Grounding Guidelines, publication Product Certifications website, Description Provides application information about using 140M devices with variable-frequency drives. Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details. You can view or download publications at To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

2 Motor Protection Circuit Breaker and Motor Circuit Protector Specifications Notes: 2 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

3 Bulletin 140M Motor Protection Circuit Breakers Overview Motor Protection Circuit Breakers may provide the following protective and control functions. Disconnect for Motor Branch Circuit Branch-Circuit, Short-Circuit Protection (Magnetic Protection) Overload Protection (Thermal Protection) Switching (Manual) In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-Protected Combination Motor Controller. 140M-C, D, and F Frames The 140M-C, D, and F frame Motor Protection Circuit Breakers may have two culus Listings - as Manual, Self-Protected Combination Motor Controllers and as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). Cat. No. 140M-D8V* can also be applied at the output of a variable frequency drive (VFD) in multi-motor applications. When UL/CSA listed as Manual, Self-Protected Combination Motor Controllers, the 140M Motor Protection Circuit Breakers provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices. At some higher voltages and currents (particularly at 600V), a few of the 140M-C, D, and F frame devices are only UL/CSA Listed as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). Standards Compliance and Certifications Standards Compliance IEC/EN ,-2,-4-1,-5-1 IEC/EN CSA,C22.2 No.14 UL508 Certifications CE Marked CCC CSA Certified culus Listed (File No. E54612, NLRV(7); E205542, NKJH(7); E197878, DIVQ(7);) ATEX Rockwell Automation Publication 140M-TD002F-EN-P - September

4 Bulletin 140M Motor Protection Circuit Breakers C-Frame D-Frame F-Frame CMN-Frame Max. Current I e 32 A 32 A 45 A 90 A Current Rating A A A A Short Circuit Protection Standard Magnetic T rip High Magnetic Trip Magnetic Only Trip (MCP) Overload Protection Trip Class Application at output of VFD (multi-motor) (140M-D8V) Standards Compliance: CSA22.2, No.14 UL508 (Group Installation) (see ratings) (see ratings) (see ratings) (see ratings) UL508 Manual, Self Protected (Type E) (see ratings) (see ratings) (see ratings) UL508 (Overload Protection) IEC ,-2 IEC CE ATEX (IEC ) (up to 25 A) (up to 25 A; except 140M-D8V) CCC (up to 25 A) (up to 25 A) Accessories External Rotary Operator Auxiliary Contacts Trip Indication Contacts 4 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

5 Bulletin 140M Motor Protection Circuit Breakers Catalog Number Explanation Examples given in this section are not intended to be used for product selection. 140M C 2 E A63 KN CC GJ a b c d e f g h a b c d Bulletin Number Frame/Rating Interrupting Rating/Breaking Capacity Protection Type Code Description Code Description Code Description Code Description 140M Motor Protection Circuit Breaker C 32 A 2 Normal Break E Adj Thermal/ Fixed Mag(13 x I n ) D 32A 8 High Break T Adj Thermal/Fixed Mag (Fixed at x I n ) F 45A V Adj Thermal/Fixed Mag application at output of VFD (multi-motor) e f g Current Range Miscellaneous Auxiliary Trip Contacts Code Description Example Code Description Frame Size C, D, F Frames A A=.10 A16=0.16 KN Black Lockable Knob C,D,F,CMN 1st Code Description 2nd Code Description B B=1.0 B16=1.6 KRY Red/Yellow Lockable Knob C,D,F,CMN Bottom Front Right Side C C=10 C16=16 Spacing Adapter for Self- X Placeholder X Placeholder TE C,D,F D D=100 D16=160 Protected Starters (TypeE) A 1 N.C. C 1 N.O.+1 N.C. E E=1000 E16=1600 MT STD BusBar Mount, Top C,D,F,CMN B 1 N.O. D 2 N.O. C 1 N.O.+1 N.C. E 2 N.C. D 2N.O. K 1 N.C. (SC+OL) + 1 N.C. (SC) E 2N.C. L 1 N.O. (SC+OL) + 1 N.O. (SC) R 1 N.C.+ 1 N.O. (SC + OL) M 1 N.C. (SC + OL)+ 1 N.O. (SC) S 1 N.O.+1 N.O.(SC+OL) N 1 N.O. (SC + OL) + 1 N.C. (SC) Q 1 N.O. (SC)+1 N.C.(SC) h UV and Shunt Trips C, D, F Frame 1st Code Description 2nd Code Description Left Side Voltage G Undervoltage Trip J 24V AC, 60 Hz K 24V AC, 50 Hz D 120V AC, 60 Hz C 110V AC, 50 Hz H 208V AC, 60 Hz F V AC, 50 Hz P Shunt Trip A 240V AC, 60Hz T 277V AC, 60 Hz N V AC, 50 Hz B 480V AC, 60Hz and 415V AC, 50 Hz VC 600V AC, 60Hz M 575V AC, 60Hz and 500V AC, 50 Hz Rockwell Automation Publication 140M-TD002F-EN-P - September

6 Bulletin 140M Motor Protection Circuit Breakers Application Diagrams Group Installation with MPCBs There is only one Branch Circuit Protective Device (BCPD) for the Group Group installation has been successfully used for many years in the U.S. and Canada. It allows two or motors or one or more motors and other loads to be connected to the same branch-circuit. The most restrictive part of the conditions specified for Group Installation is the requirement for the protection of the conductors for each motor circuit. In the U.S. NEC for 2002, a new rule for the conductor sizing was added for devices that are listed and marked Suitable for use as Tap Conductor Protection. Below is an example that illustrates installations involving multiple motors with a single BCPD protecting the entire Group. Bulletin 140M Motor Protection Circuit Breakers UL/CSA Listed for Group Installation Conductors from the BCPD to each motor must be a minimum of 1/3 the ampacity of the Branch Circuit conductors. Bulletin 140M Motor Protection Circuit Breakers UL/CSA Listed for Tap conductor Protection in Group Installations Conductors from the BCPD to manual motor controller listed as Tap Conductor Protection must be minimum of 1/10 the rating or setting of the BCPD. Conductors from the controller to the motor must be 125% of the motor FLA. Group Installation: Single Motor Taps Must be 1/3 the ampacity of the Branch-Circuit conductors Branch Circuit conductors BCPD Branch Circuit Protective Device Fuses or Circuit Breaker Tap Conductor Protection in Group Installation: Conductors from BCPD to manual motor controller listed as Tap Conductor Protection must be minimum of 1/10 the rating or setting of the BCPD Tap Conductor Protection in Group Installation: Conductors to each motor sized normally at 125% of motor FLA 6 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

7 Bulletin 140M Motor Protection Circuit Breakers Multiple Motor Installation with MPCBs Each Motor has an Individual Branch Circuit Protective Device Bulletin 140M Motor Protection Circuit Breakers (MPCBs) UL/CSA Listed as Type E Manual Self-Protected Combination Motor Controllers or UL/CSA Listed as Circuit Breakers These UL/CSA Listings allow the Bulletin 140M MPCBs to provide the branch-circuit, short-circuit protection (as well as overload protection) for each individual motor circuit. Additional short-circuit protection is not required for the protection of the individual motor circuits, leaving only the requirement for protection of the feeder circuit conductors by an upstream protective device. Below is an example that illustrates installations involving multiple motors, each with its own branch-circuit protection (BCPD). Bulletin 140M-J L (Inverse Time Circuit Breakers) may provide the branch-circuit protection for each individual motor circuit Bulletin 140M-C F (Type E Self-Protected Combination Motor Controllers) may provide the branch-circuit protection for each individual motor circuit Feeder Circuit Conductors Conductors to each motor sized normally at 125% FLA Rockwell Automation Publication 140M-TD002F-EN-P - September

8 Bulletin 140M Motor Protection Circuit Breakers Type E and Type F Combination Motor Controllers Most of the 140M-C F motor protection circuit breakers are UL Listed as a manual Type E self-protected combination motor controller. Although there are many tests involved, one of the critical tests a self-protected combination motor controller must pass, is to perform 6000 electrical operations and an additional 4000 mechanical operations after a short circuit. By definition, a Type F combination motor controller consists of a Type E manual self protected combination motor controller and a magnetic or solid-state motor controller (such as a Bulletin 100-C contactor or an SMC). As with a manual Type E self-protected combination motor controller, additional short-circuit protection is not required for the individual motor circuits. A combination of a Bulletin 140M manual self protected combination motor controller and 100-C contactor can be listed as a Type E self-protected combination motor controller. In this case, both the 140M and 100-C must pass the additional 6000 electrical and 4000 mechanical operational test. In some cases, this may require over sizing of the Bulletin 140M MPCB or the 100-C contactor to achieve weld free performance and meet the additional life requirements. 8 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

9 Bulletin 140M Motor Circuit Protectors Overview Motor Circuit Protectors may provide the following protective and control functions. Disconnect for Motor Branch Circuit Branch-Circuit, Short-Circuit Protection (Magnetic Protection) Switching (Manual) In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-Protected Combination Motor Controller. 140M-C, D, and F Frames: The 140M-C, D and F frame Motor Circuit Protectors have one UL/CSA Listing - as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules, which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). The 140M-C, D and F Frame Motor Circuit Protectors are also UL/CSA Listed, together with a Bulletin 100C contactor and Bulletin 193 overload relay, as part of our Bulletin 103T and 107T Self-Protected IEC Combination Starters. These starters are then able to provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices. Standards Compliance and Certifications Standards Compliance IEC/EN ,-2,-4-1,-5-1 IEC/EN CSA,C22.2 No.14 UL508 Certifications CE Marked CCC culus Listed (File No. E54612, Guide No. NLRV, NLRV7) C-Frame D-Frame F-Frame Max. Current I e 25 A 32A 45 A Current Rating A A A Short Circuit Protection Standards Compliance: CSA22.2, No.14 UL508 (Group Installation) IEC CE CCC (up to 25 A) Accessories External Rotary Operator Auxiliary Contacts Trip Indication Contacts Rockwell Automation Publication 140M-TD002F-EN-P - September

10 Bulletin 140M Motor Circuit Protectors Catalog Number Explanation Examples in this section are not intended to be used for product selection. 140M C 2 N A63 KN CC GJ a b c d e f g h a b c d Bulletin Number Frame/Rating Interrupting Rating/Breaking Capacity Protection Type Code Description Code Description Code Description Code Description 140M Motor Circuit Protector C 25 A 2 Normal Break N Fixed Mag only (13 x I n ) D 32A 8 High Break P Adj Mag only (<13 x I n ) F 45A R Adj Mag only (>13 x I n ) e f g Current Range Miscellaneous Auxiliary Trip Contacts Code Description Example Code Description Frame Size C, D, F Frames A A=0.10 A16=0.16 KN Black Lockable Knob C,D,F,CMN 1st Code Description 2nd Code Description B B=1.0 B16=1.6 KRY Red/Yellow Lockable Knob C,D,F,CMN Bottom Front Right Side C C=10 C16=16 Spacing Adapter for Self- X Placeholder X Placeholder TE C,D,F D D=100 D16=160 Protected Starters (Type E) A 1 N.C. C 1 N.O.+1 N.C. E E=1000 E16=1600 MT STD BusBar Mount, Top C,D,F,CMN B 1 N.O. D 2 N.O. C 1 N.O.+1 N.C. E 2 N.C. D 2N.O. K 1 N.C. (SC+OL) + 1 N.C. (SC) E 2N.C. L 1 N.O. (SC+OL) + 1 N.O. (SC) R 1 N.C.+ 1 N.O. (SC + OL) M 1 N.C. (SC + OL)+ 1 N.O. (SC) S 1 N.O.+1 N.O.(SC+OL) N 1 N.O. (SC + OL) + 1 N.C. (SC) Q 1 N.O. (SC)+1 N.C.(SC) h UV and Shunt Trips C, D, F Frame 1st Code Description 2nd Code Description Left Side Voltage G Undervoltage Trip J 24V AC, 60 Hz K 24V AC, 50 Hz D 120V AC, 60 Hz C 110V AC, 50 Hz H 208V AC, 60 Hz F V AC, 50 Hz P Shunt Trip A 240V AC, 60Hz T 277V AC, 60 Hz N V AC, 50 Hz B 480V AC, 60Hz and 415V AC, 50 Hz VC 600V AC, 60Hz M 575V AC, 60Hz and 500V AC, 50 Hz 10 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

11 Bulletin 140M Motor Circuit Protectors Application Diagrams Group Installation with MCPs There is only one Branch Circuit Protective Device (BCPD) for the Group Group installation has been successfully used for many years in the U.S. and Canada. It allows two or motors or one or more motors and other loads to be connected to the same branch-circuit. The most restrictive part of the conditions specified for Group Installation is the requirement for the protection of the conductors for each motor circuit. Below is an example that illustrates installations involving multiple motors with a single BCPD protecting the entire Group. Bulletin 140M Motor Circuit Protectors UL/CSA Listed for Group Installation Conductors from the BCPD to each motor must be a minimum of 1/3 the ampacity of the Branch Circuit conductors. Motor Circuit Protectors do not provide thermal protection, so a separate overload relay must be used. Therefore, MCPs cannot be UL/CSA Listed for Tap Conductor Protection in Group Installations. Bulletin 140M-C F Group Installation: Single Motor Taps Must be 1/3 the ampacity of the Branch-Circuit conductors Branch Circuit conductors BCPD Branch Circuit Protective Device Fuses or Circuit Breaker Rockwell Automation Publication 140M-TD002F-EN-P - September

12 Bulletin 140M Motor Circuit Protectors 12 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

13 Application Ratings UL/CSA Listed Application Ratings, Motor Protection Circuit Breaker Only Cat. No. Max. Fuse or C.B. per NEC UL 508 Manual Motor Controller UL 508 Self-Protected Group Motor Installation Motor Disconnect Tap Conductor Protection (Type E) Combination Motor Controller Max. Short Circuit Current Max. Short Circuit Current Max. Short Circuit Current Max. Short Circuit Current [ka] [ka] [ka] [ka] 480V 600V 480V 600V 480Y/277V (1) 600Y/347V (1) 480Y/277V (1) 600Y/347V (1) C-Frame 140M-C2E-A M-C2E-A M-C2E-A M-C2E-A M-C2E-B M-C2E-B M-C2E-B M-C2E-B M-C2E-B M-C2E-C M-C2E-C M-C2E-C M-C2E-C M-C2E-C M-C2E-C M-C2T-A M-C2T-A M-C2T-A M-C2T-A M-C2T-B M-C2T-B M-C2T-B M-C2T-B M-C2T-B M-C2T-C M-C2T-C D-Frame (D8E) 140M-D8E-B M-D8E-B M-D8E-B M-D8E-C M-D8E-C M-D8E-C M-D8E-C M-D8E-C M-D8E-C (1) For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. Rockwell Automation Publication 140M-TD002F-EN-P - September

14 Cat. No. Max. Fuse or C.B. per NEC UL 508 Manual Motor Controller UL 508 Self-Protected Group Motor Installation Motor Disconnect Tap Conductor Protection (Type E) Combination Motor Controller Max. Short Circuit Current Max. Short Circuit Current Max. Short Circuit Current Max. Short Circuit Current [ka] [ka] [ka] [ka] 480V 600V 480V 600V 480Y/277V (1) 600Y/347V (1) 480Y/277V (1) 600Y/347V (1) D-Frame (D8V, D8T) 140M-D8T-C M-D8T-C M-D8V-B M-D8V-B M-D8V-B M-D8V-B M-D8V-C M-D8V-C M-D8V-C M-D8V-C M-D8V-C M-D8V-C F-Frame 140M-F8E-C M-F8E-C M-F8E-C M-F8E-C M-F8E-C M-F8E-C M-F8T-C M-F8T-C (1) For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. 14 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

15 UL Listed Application Ratings, Motor Circuit Protector Only (Separate Overload Protection Required) UL 508 Manual Motor Controller Cat. No. Group Motor Installation Motor Disconnect Max. Fuse or C.B. per NEC Max. Short Circuit Current [ka] Max. Short Circuit Current [ka] 480V 600V 480V 600V C-Frame 140M-C2N-A M-C2N-A M-C2N-A M-C2N-A M-C2N-B M-C2N-B M-C2N-B D-Frame 140M-D8N-B M-D8N-B M-D8N-B M-D8N-C M-D8N-C M-D8N-C M-D8N-C F-Frame 140M-F8N-C M-F8N-C M-F8N-C Rockwell Automation Publication 140M-TD002F-EN-P - September

16 UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-K Contactors Cat. No. Max. Fuse or C.B. per NEC Minimum Contactor Size (1) For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. UL 508 Manual Motor Controller UL508 Type F Combination Motor Controller Group Motor Installation Motor Disconnect Max. Short Circuit Current [ka] Max. Short Circuit Current [ka] Minimum Max. Short Circuit Current [ka] Contactor 480V 600V 480V 600V Size 480Y/277V (1) 600Y/347V (1) C-Frame 140M-C2E-A K K M-C2E-A K K M-C2E-A K K M-C2E-A K K M-C2E-B K K M-C2E-B K K M-C2E-B K K M-C2E-B K K M-C2E-B K K M-C2E-C K K M-C2E-C K K12 30 D-Frame 140M-D8E-B K K M-D8E-B K K M-D8E-B K K M-D8E-C K K M-D8E-C K K Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

17 UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-C Contactors Cat. No. Max. Fuse or C.B. per NEC Minimum Contactor Size UL 508 Manual Motor Controller Group Motor Installation Max. Short Circuit Current [ka] Motor Disconnect Max. Short Circuit Current [ka] 480V 600V 480V 600V (1) For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. UL508 Type F Combination Motor Controller Minimum Contactor Size Max. Short Circuit Current [ka] 480Y/ 600Y/ 277V (1) UL508 Type E Self-Protected Combination Motor Controller Minimum Contactor Size 480Y/ 347V (1) Max. Short Circuit Current [ka] 600Y/ 277V (1) 347V (1) C-Frame 140M-C2E-A C C C M-C2E-A C C C M-C2E-A C C C M-C2E-A C C C M-C2E-B C C C M-C2E-B C C C M-C2E-B C C C M-C2E-B C C M-C2E-B C C M-C2E-C C C M-C2E-C C C M-C2E-C C C M-C2E-C C C M-C2E-C C M-C2E-C C D-Frame 140M-D8E-B C C C C M-D8E-B C C C M-D8E-B C C C M-D8E-C C C C M-D8E-C C C C M-D8E-C C C C M-D8E-C C C C M-D8E-C C M-D8E-C C F-Frame 140M-F8E-C C C C M-F8E-C C C C M-F8E-C C C C M-F8E-C C C C M-F8E-C C C C M-F8E-C C C C37 65 Rockwell Automation Publication 140M-TD002F-EN-P - September

18 UL Listed Application Ratings - Motor Circuit Protectors with Bulletin 100-C Contactors (Separate Overload Protection Required) Cat. No. Max. Fuse or C.B. per NEC Minimum Contactor Size UL 508 Manual Motor Controller Group Motor Installation (1) For full-voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. Motor Disconnect UL508 Type E Self-Protected Combination Motor Controller Max. Short Circuit Current Max. Short Circuit Current Minimum Max. Short Circuit Current [ka] [ka] Contactor [ka] 480V 600V 480V 600V Size 480Y/277V (1) 600Y/347V (1) C-Frame 140M-C2N-A C C M-C2N-A C C M-C2N-A C C M-C2N-A C C M-C2N-B C C M-C2N-B C C M-C2N-B C C09 65 D-Frame 140M-D8N-B C C C M-D8N-B C C M-D8N-B C C M-D8N-C C C M-D8N-C C C M-D8N-C C C M-D8N-C C F-Frame 140M-F8N-C C C M-F8N-C C C M-F8N-C C C Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

19 Definition of Type 2 Short Circuit Coordination: The contactor or starter must not endanger persons or plant in the event of a short circuit. No damage to the motor protection device or other parts may occur with the exception of welding of the contactor or starter contacts if these can be easily separated without appreciable deformation (such as with a screwdriver). In the event of short circuit, fast-opening, current-limiting Bulletin 140M Motor Protection Circuit Breakers make it possible to build economical, fully short-circuit coordinated starter combinations with Type 2 coordination. Type 2 Coordination, 400V Cat. No. Max. Short-Circuit Current [ka] Standard Motor Protection High Inrush Motor Protection Motor Circuit Protection 400V Minimum Contactor Size C-Frame 140M-C2E-A16 140M-C2N-A C09 140M-C2E-A25 140M-C2T-A16 140M-C2N-A C09 140M-C2E-A40 140M-C2T-A25 140M-C2N-A C09 140M-C2E-A63 140M-C2T-A40 140M-C2N-A C09 140M-C2E-B10 140M-C2T-A63 140M-C2N-B C09 140M-C2E-B16 140M-C2T-B10 140M-C2N-B C09 140M-C2E-B25 140M-C2T-B16 140M-C2N-B C09 140M-C2E-B40 140M-C2T-B C09 140M-C2E-B63 140M-C2T-B C09 140M-C2E-C10 140M-C2T-B C09 140M-C2E-C16 140M-C2T-C C12 (1) 140M-C2E-C20 140M-C2T-C C23 140M-C2E-C C30 140M-C2E-C C30 140M-C2E-C C37 D-Frame 140M-D8E-B25 140M-D8N-B C09 140M-D8E-B40 140M-D8N-B C09 140M-D8E-B63 140M-D8N-B C09 140M-D8E-C10 140M-D8N-C C09 140M-D8E-C16 140M-D8N-C C12 140M-D8E-C20 140M-D8T-C C23 140M-D8E-C25 140M-D8T-C20 140M-D8N-C C23 140M-D8E-C C30 140M-D8E-C32 140M-D8N-C C37 F-Frame 140M-F8E-C C09 140M-F8E-C C12 140M-F8E-C C23 140M-F8E-C25 140M-F8N-C C30 140M-F8E-C32 140M-F8T-C25 140M-F8N-C C30 140M-F8E-C45 140M-F8T-C32 140M-F8N-C C37 (1) Cat. No. 100-C16 contactors Type 1 only Rockwell Automation Publication 140M-TD002F-EN-P - September

20 Type 2 Coordination, 480V Cat. No. Max. Short-Circuit Current [ka] Standard Motor Protection High Inrush Motor Protection Motor Circuit Protection 480V Minimum Contactor Size C-Frame 140M-C2E-A16 140M-C2N-A C09 140M-C2E-A25 140M-C2T-A16 140M-C2N-A C09 140M-C2E-A40 140M-C2T-A25 140M-C2N-A C09 140M-C2E-A63 140M-C2T-A40 140M-C2N-A C09 140M-C2E-B10 140M-C2T-A63 140M-C2N-B C09 140M-C2E-B16 140M-C2T-B10 140M-C2N-B C09 140M-C2E-B25 140M-C2T-B16 140M-C2N-B C16 140M-C2E-B40 140M-C2T-B C30 140M-C2E-B63 140M-C2T-B C30 140M-C2E-C10 140M-C2T-B C30 140M-C2E-C16 140M-C2T-C C30 140M-C2E-C20 140M-C2T-C C30 140M-C2E-C C30 140M-C2E-C C30 140M-C2E-C C37 D-Frame 140M-D8E-B25 140M-D8N-B C09 140M-D8E-B40 140M-D8N-B C09 140M-D8E-B63 140M-D8N-B C09 140M-D8E-C10 140M-D8N-C C09 140M-D8E-C16 140M-D8N-C C12 140M-D8E-C20 140M-D8T-C C23 140M-D8E-C25 140M-D8T-C20 140M-D8N-C C23 140M-D8E-C C30 140M-D8E-C32 140M-D8N-C C37 F-Frame 140M-F8E-C C09 140M-F8E-C C12 140M-F8E-C C23 140M-F8E-C25 140M-F8N-C C30 140M-F8E-C32 140M-F8T-C25 140M-F8N-C C30 140M-F8E-C45 140M-F8T-C32 140M-F8N-C C37 20 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

21 Type 2 Coordination, 600V Cat. No. Max. Short-Circuit Current [ka] Standard Motor Protection High Inrush Motor Protection Motor Circuit Protection 600V Minimum Contactor Size C-Frame 140M-C2E-A16 140M-C2N-A C09 140M-C2E-A25 140M-C2T-A16 140M-C2N-A C09 140M-C2E-A40 140M-C2T-A25 140M-C2N-A C09 140M-C2E-A63 140M-C2T-A40 140M-C2N-A C09 140M-C2E-B10 140M-C2T-A63 140M-C2N-B C09 140M-C2E-B16 140M-C2T-B10 140M-C2N-B C09 140M-C2E-B25 140M-C2T-B16 140M-C2N-B C16 140M-C2E-B40 140M-C2T-B C16 140M-C2E-B63 140M-C2T-B C23 140M-C2E-C10 140M-C2T-B C30 140M-C2E-C16 140M-C2T-C C30 140M-C2E-C20 140M-C2T-C C30 140M-C2E-C C30 140M-C2E-C C30 140M-C2E-C C37 D-Frame 140M-D8E-B25 140M-D8N-B C30 140M-D8E-B40 140M-D8N-B C30 140M-D8E-B63 140M-D8N-B C30 140M-D8E-C10 140M-D8N-C C30 140M-D8E-C16 140M-D8N-C C30 140M-D8E-C20 140M-D8T-C C30 140M-D8E-C25 140M-D8T-C20 140M-D8N-C C30 140M-D8E-C C30 140M-D8E-C32 140M-D8N-C C37 F-Frame 140M-F8E-C C30 140M-F8E-C C30 140M-F8E-C C30 140M-F8E-C25 140M-F8N-C C30 140M-F8E-C32 140M-F8T-C25 140M-F8N-C C30 140M-F8E-C45 140M-F8T-C32 140M-F8N-C C37 Rockwell Automation Publication 140M-TD002F-EN-P - September

22 Specifications IEC Performance Data Cat.No.140M-C2E- A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16 C20 C25 C29 C32 Rated Operational Current, I e [A] Magnetic Release Current [A] Switching of Standard Three-Phase Motors, AC-3 230/240V [kw] /415V [kw] V [kw] V [kw] Back-Up Fuses gg, gl, only if I cc I cu 230/240V [A] /415V [A] /460V [A] V [A] V [A] Ultimate Short Circuit Breaking Capacity, I cu 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] Rated Service Short Circuit Breaking Capacity, I cs 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] No back-up fuse required. 22 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

23 Cat.No.140M-D8E- Cat.No.140M-F8E- B25 B40 B63 C10 C16 C20 C25 C29 C32 C10 C16 C20 C25 C32 C45 Rated Operational Current, I e [A] Magnetic Release Current [A] Switching of Standard Three-Phase Motors, AC-3 230/240V [kw] /415V [kw] V [kw] V [kw] Back-Up Fuses gg, gl, only if I cc I cu 230/240V [A] 400/415V [A] /460V [A] V [A] V [A] Ultimate Short Circuit Breaking Capacity, I cu 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] Rated Service Short Circuit Breaking Capacity, I cs 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] No back-up fuse required. Rockwell Automation Publication 140M-TD002F-EN-P - September

24 Cat. No. 140M-D8V- B16 B25 B40 B63 C10 C16 C20 C25 C29 C32 Rated Operational Current, I e [A] Magnetic Release Current [A] Switching of Standard Three-Phase Motors, AC-3 230/240V [kw] /415V [kw] V [kw] Back-Up Fuses gg, gl, only if I cc I cu 230/240V [A] 400/415V [A] /460V [A] V [A] Ultimate Short Circuit Breaking Capacity, I cu 230/240V [ka] /415V [ka] /460V [ka] V [ka] Rated Service Short Circuit Breaking Capacity, I cs 230/240V [ka] /415V [ka] /460V [ka] V [ka] Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

25 Cat.No.140M-C2N- A16 A25 A40 A63 B10 B16 B25 Rated Operational Current, I e [A] Magnetic Release Current [A] Switching of Standard Three-Phase Motors, AC-3 230/240V [kw] /415V [kw] V [kw] V [kw] Back-Up Fuses gg, gl, only if I cc I cu 230/240V [A] 400/415V [A] 440/460V [A] 500V [A] 690V [A] Ultimate Short Circuit Breaking Capacity, I cu 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] Rated Service Short Circuit Breaking Capacity, I cs 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] Rockwell Automation Publication 140M-TD002F-EN-P - September

26 Cat.No.140M-D8N- Cat.No.140M-F8N- B25 B63 B40 C10 C16 C25 C32 C25 C32 C45 Rated Operational Current, I e [A] Magnetic Release Current [A] Switching of Standard Three-Phase Motors, AC-3 230/240V [kw] /415V [kw] V [kw] V [kw] Back-Up Fuses gg, gl, only if I cc I cu 230/240V [A] /415V [A] /460V [A] V [A] V [A] Ultimate Short Circuit Breaking Capacity, I cu 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] Rated Service Short Circuit Breaking Capacity, I cs 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] No back-up fuse required. 26 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

27 Cat.No.140M-C2T- A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16 Rated Operational Current, I e [A] Magnetic Release Current [A] Switching of Standard Three-Phase Motors, AC-3 230/240V [kw] /415V [kw] V [kw] V [kw] Back-Up Fuses gg, gl, only if I cc I cu 230/240V [A] 400/415V [A] /460V [A] V [A] V [A] Ultimate Short Circuit Breaking Capacity, I cu 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] Rated Service Short Circuit Breaking Capacity, I cs 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] No back-up fuse required. Rockwell Automation Publication 140M-TD002F-EN-P - September

28 Cat.No.140M-D8T- Cat.No.140M-F8T- C16 C20 C25 C32 Rated Operational Current, I e [A] Magnetic Release Current [A] Switching of Standard Three-Phase Motors, AC-3 230/240V [kw] /415V [kw] V [kw] V [kw] Back-Up Fuses gg, gl, only if I cc I cu 230/240V [A] 400/415V [A] /460V [A] V [A] V [A] Ultimate Short Circuit Breaking Capacity, I cu 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] Rated Service Short Circuit Breaking Capacity, I cs 230/240V [ka] /415V [ka] /460V [ka] V [ka] V [ka] No back-up fuse required. Consult your local Rockwell Automation sales office or Allen-Bradley distributor. General Data Cat.No. 140M-C 140M-D 140M-F Rated Insulation Voltage U i IEC, SEV, VDE0660 [V] 690 UL, CSA [V] 600 Rated Impulse Withstand Voltage U imp Pollution degree 3 Main circuits U imp /Overvoltage Category 6kV/III Auxiliary circuits U imp /Overvoltage Category 6kV/III Rated Frequency [Hz] 50/60 Utilization Category IEC (Circuit breaker) A IEC (Motor starter) AC-3 Lifespan Mechanical [operations] Electrical (I e max.) [operations] Switching Frequency [operations/h] max Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

29 Cat.No. 140M-C 140M-D 140M-F Ambient Temperature Storage [ C] Operation [ C] Climatic resistance Moisture change climate ( ) 23 C/83% relative humidity and 40 C/92% relative humidity, 56 cycles Dry heat ( ) 100 C, relative humidity <50%, 7 days Moisture heat ( ) 40 C, relative humidity 93%, 56 days Site Altitude [m] to 2000 N.N. Protection Class 140M-C; 140M-D : IP2X from all directions 140M-F : IP2X from front with front (upper) terminal wired Resistance to Shock, Transport ( ) 30 g,11ms,all axes Resistance to Vibration, Operation ( ) 5g Rated Thermal Current I th up to 40 C ambient temperature [A] ( for -D8V) up to 60 C ambient temperature [A] ( for -D8V) Rated Supply Current I e [A] ( for -D8V) Dependence on Temperature 40 C [A] no reduction 50 C [A] no reduction 60 C [A] no reduction 70 C [A] 15% current reduction of the upper rated current I e Overload Protection Characteristics IEC Motor protection (except Cat.Nos.140M-C2N,140M-D8N,140M-F8N) Ambient Temperature Compensation [ C] Phase-loss Protection Differential release Trip class 10 (except Cat.Nos.140M-C2N,140M-D8N,140M-F8N) fixed setting Magnetic Release Release current(+/-20%) Circuit Breaker at rated load operating temperature Main Disconnect Switch Application Application Conditions Application Conditions (140M-D8V) fixed setting x I e max. (for 140M-C2E,140M-D8E,140M-F8E,140M-C2N,140M-D8N,140M-F8N) x I e max. (for 140M-C2T, 140M-D8T, 140M-F8T) I e max. = maximum values of setting ranges fixed magnetic setting for 140M-D8V; see ratings Total Power Loss P v [W] Yes, with accessories For utilization outside North America, assemblies (of products) shall comply to the IEC requirements 140M manual motor starters are intended for use in closed areas without hazardous operating conditions such as dust or explosive or corrosive gases. Enclosures of appropriate manner need to be in place to protect devices in such environments. PWM frequency 4 khz VFD output frequency Hz Rockwell Automation Publication 140M-TD002F-EN-P - September

30 Cat.No. 140M-C 140M-D 140M-F Conformity to Standards IEC ;-2;-4-1; EN ;-2;-4-1; UL508; CSA22.2, No.14 Approvals CE,UL,CSA Terminal Parts Type of terminals Screwdriver PozidrivNo.2/BladeNo.3 PozidrivNo.2/BladeNo.3 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor 1 6/No /No /No /No /No /No /No /No /No /No /No /No /No /No /No /No.14 8 Tightening torque [N m]/[lb in] 2 2.5/ /27 30 Cat.No. 140M-RC Terminal Parts Type of terminals Screwdriver 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor / / /No /No /No /No Accessories for Bulletin 140M Motor Protection Circuit Breakers Rated Thermal Current I th at 40 C ambient temperature at 60 C ambient temperature [A] [A] Contact Class Coordination According to NEMA AC (UL/CSA Standards) DC Auxiliary Contact Blocks for Front Mounting Cat.No.140M-C-AFA,140M-C-AFAR 5 4 B300 Q300 Auxiliary Contact Blocks for Right-Side Mounting Cat.No.140M-C-ASA,140M-C-ASAR Back-Up Fuses gg, gl [A] Rated Supply Current [V] AC-15 [A] DC-13 [V] [A] Terminal Parts Type of terminals Screwdriver PozidrivNo.2/BladeNo B600 Q Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

31 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor Auxiliary Contact Blocks for Front Mounting Cat.No.140M-C-AFA,140M-C-AFAR / / / / / /18 14 Auxiliary Contact Blocks for Right-Side Mounting Cat.No.140M-C-ASA,140M-C-ASAR / / / / / /18 14 Tightening torque [N m]/[lb in] / / Undervoltage Trip for Left-Side Mounting Cat.No.140M-C-UX Undervoltage Trip with 2 Auxiliary Contacts for Left-Side Mounting Cat.No.140M-C-UC Shunt Trip for Left-Side Mounting Cat.No.140M-C-SN Actuating Voltage Pull-in Drop-out Rated Control Voltage Coil Rating min. max x U s x U s 21V 50 Hz,24V 60 Hz 600V 50 Hz x U s x U s 21V 50 Hz,24V 60 Hz 600V 50 Hz x U s 21V 50 Hz, 24V 60 Hz 600V 50 Hz On-Time 100% 100% AC: 100%; DC: max. 5 sec. Terminal Parts Type of terminals Screwdriver 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor Pull-in Hold 8.5VA, 8 W 4VA, 2 W 8.5VA, 8 W 4VA, 2 W PozidrivNo.2/BladeNo /No /No /No /No /No /No Tightening torque [N m]/[lb in] / VA, 8 W 4VA, 2 W Compact Busbar Feeder Terminal 140M-C-WTN 140M-C-WTEN 140M-F-WTE 140M-C -W Compact Busbar 140M-F -W 140M-C- WBEL1,L2,L3 Compact Busbar Feeder Block 140M-C- WBET1,T2,T3 140M-F- WBEL1,L2,L3 140M-F- WBET1,T2,T 3 Rated Thermal Current I th at 60 C ambient temperature [A] IEC120/UL115 1.conductor / / conductor / conductor / /12 1/ / 12 1/0 4 25/10 4 Tightening torque [N m]/[lb in] 3 3.5/ / / / for use with 140M-C-W for use with 140M-C-W for use with 140M-C-W 2.5 3/ / / / /45 54 for use with 140M-F-W for use with 140M-F-W for use with 140M-F-W Rockwell Automation Publication 140M-TD002F-EN-P - September

32 Accessories for Bulletin 140M Screwless Cat.No. 140M-RC Terminal Parts Type of terminals Screwdriver 1.conductor 2.conductor 1.conductor 2.conductor 1.conductor 2.conductor / / /No /No /No /No Weights Description Weight [g] Cat.No. Description Weight [g] Cat.No MC-C2E- Anti-Tamper Cover 2 140M-C-CA M-D8E- 140M-C-KN1 Lockable Twist Knob MC-F8E- 140M-C-KRY M-C2N- Locking Tag M-C-M3 Motor Protection Circuit Breakers M-D8N- 140M-C-DN66 Door Coupling Handle M-F8N- 140M-C-NRY M-C2T- Extension Shaft M-C-DS M-D8T- Legend Plate 4 140M-C-DFC M-F8T M-C-WTEN Feeder Terminal 140M-C-AFA M-F-WT 140M-C-AFA M-C-W452N M-C-AFA M-C-W453N 140M-C-AFA M-C-W454N Auxiliary Contacts 140M-C-ASA M-C-W455N Compact Busbars 140M-C-AFAR10A M-C-W542N M-C-ASAR M M-C-W543N 140M-C-ASAM M-C-W544N M-C-UX M-C-W545N Undervoltage Trip M-C-SN Top Hat Rail Adapter KBH M-C-UC 32 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

33 Cutoff Current The Bulletin 140-M limits solid short-circuit current ICC (prospective short-circuit current). ID is the maximum cutoff current (highest instantaneous value of the limited short-circuit current). This value is indicated in the following diagrams as a function of the progressive system short-circuit current. Î s Icc asymmetrical I D Icc symmetrical Figure 1 - Bulletin140M-C Circuit Breaker (Maximum Cutoff Current) 140M-C2E, -C2N, -C2T Max. Cut-Off Current, U e = V Peak current [ka] / 32 A 25 A 20 A 16 A 10 A 6.3 A 4.0 A A cos φ 1.0 A Prospective current [ka r.m.s] Rockwell Automation Publication 140M-TD002F-EN-P - September

34 Figure 2 - Bulletin140M-D8E, -D8N, D8T Circuit Breaker (Maximum Cutoff Current) 140M-D8E, -D8N, -D8T Max. Cut-Off Current, U e = V Peak current [ka] / 32 A 25 A 16 / 20 A 10 A 6.3 A 4.0 A A cos φ Prospective current [ka r.m.s] Figure 3 - Bulletin140M-D8V Circuit Breaker (Maximum Cutoff Current) M-D8V Max. Cut-Off Current, U e = V / 32 A 25 A 16 / 20 A Peak current [ka] 1 cos A 6.3 A 4.0 A 2.5 A 1.6 A Prospective current [ka r.m.s] 34 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

35 Figure 4 - Bulletin140M-F Circuit Breaker (Maximum Cutoff Current) M-F8E, -F8N, -F8T Max. Cut-Off Current, Ue = V Peak current [ka] A 32 / 25 A 20 A 16 A 10 A 1 cos φ Prospective current [ka r.m.s] Figure 5 - Bulletin140M-C Circuit Breaker (Maximum Let-through Energy) 140M-C2E, -C2N, -C2T Max. Let-Through-Energy, U e = V 1.00E+06 1 Half-Cycle (50Hz) Let-through energy [A 2 s] 1.00E E / 32 A 25 A 20 A 16 A 10 A 6.3 A 4.0 A 1.00E A 1.6 A 1.00E Prospective current [ka r.m.s] Rockwell Automation Publication 140M-TD002F-EN-P - September

36 Figure 6 - Bulletin140M-D8E, -D8N, -D8T Circuit Breaker (Maximum Let-through Energy) 1.00E M-D8E, -D8N, -D8T Max. Let-Through-Energy, U e = V Let-through energy [A 2 s] 1.00E E+04 1 Half-Cycle (50Hz) 32 A 29 A 25 A 20 / 16 A 10 A 6.3 A 4.0 A 1.00E A 1.00E Prospective current [ka r.m.s] Figure 7 - Bulletin140M-D8V Circuit Breaker (Maximum Let-through Energy) 1.E M-D8V Max. Let-Through-Energy, U e = V 1 Half-Cycle (50 Hz) 1.E A 29 A 25 A Let-through energy [ A 2 s] 1.E+04 1.E / 16 A 10 A 6.3 A 4.0 A 2.5 A 1.6 A 1.E Prospective current [ka r.m.s] 36 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

37 Figure 8 - Bulletin140M-F Circuit Breaker (Maximum Let-through Energy) 140M-F8E, -F8N, -F8T Max. Let-Through-Energy, U e = V 1.00E+06 Let-through energy [A 2 s] 1.00E E+04 1 Half-Cycle (50Hz) 45 A 32 A 25 A 20 A 16 A 10 A 1.00E E Prospective current [ka r.m.s] Rockwell Automation Publication 140M-TD002F-EN-P - September

38 Time-Current Characteristic Figure 9 - Motor Protection Circuit Breakers Time-Current Characteristic h Release Time [s] Multiple of the set current IeF 140M-C, -D, -F Motor Protection Circuit Breakers (for 140M-D8V, see ratings) Thermal Release Trip Current The adjustable current-dependent delayed bimetal release protects motors against overload. The curve shows the mean operating current at an ambient temperature of 20 C starting from the cold state. Careful testing and setting ensures effective motor protection even in the case of single phasing. The overload characteristic is also valid for transformer protection. Magnetic Release Trip Current The instantaneous magnetic trip has a fixed operating current setting. This corresponds to times the maximum value of setting range. (Transformer protection up to 20 x I e max.) At a lower setting it is correspondingly higher. Current Setting I e F The overload trip corresponds to a thermal overload relay in a motor starter conforming to IEC If a different value is prescribed (e.g., reduced I e for cooling medium having a temperature higher than 40 C or a place of installation higher than 2000 m above sea level), the setting current is equal to the reduced rated current I e of the motor. 38 Rockwell Automation Publication 140M-TD002F-EN-P - September 2016

Motor Protection Circuit Breaker and Motor Circuit Protector Specifications

Motor Protection Circuit Breaker and Motor Circuit Protector Specifications Technical Data Motor Protection Circuit Breaker and Motor Circuit Protector Specifications Bulletin 140M Topic Page Topic Page Bulletin 140M Motor Protection Circuit Breakers 3 Accessories 17 Overview

More information

Bulletin 140M Motor Protectors

Bulletin 140M Motor Protectors 0Circuit Breaker Bulletin 140M Bulletin 140M Cat. No. 140M-C2E Cat. No. 140M-F8E Current Range 0.1...45 A With 140-CMN up to 90 A Type 2 Coordination with Bulletin 100-C Contactors UL Listed Self-protected

More information

FMotor Circuit Controllers

FMotor Circuit Controllers Technical Information Motor Circuit Controller IEC Performance Data Catalog Number KTA7-25S...32S 0.16A 0.25A 0.4A 0.63A 1A 1.6A 2.5A 4A 6.3A 10A 16A 20A 25A 29A 32A Rated Operational Current, I e [A]

More information

IEC Motor Control Table of Contents

IEC Motor Control Table of Contents IEC Motor Control Table of Contents Motor Protection Circuit Breakers Bul. M Motor Protection Circuit Breakers...Page - Bul. M Motor Circuit Protectors...Page - Bul. -H Rotary Mechanism for Molded Case

More information

Series KTU7 UL489 Molded Case Circuit Breakers

Series KTU7 UL489 Molded Case Circuit Breakers Series KTU7 UL489 Molded Case Circuit Breakers Versatile, convenient and space saving for a variety of applications Sprecher+Schuh s KTU7 series of UL Molded Case Circuit Breakers are UL489 and CE listed

More information

Series KTU7 UL489 Molded Case Circuit Breakers

Series KTU7 UL489 Molded Case Circuit Breakers Series UL489 Molded Case Circuit Breakers Versatile, convenient and space saving for a variety of applications Sprecher+Schuh s series of UL are UL489 and CE listed for global applications. The current

More information

KT4 Manual Motor Starter

KT4 Manual Motor Starter KT4 Manual Motor Starter Ideal for use as a manual starter The KT4 is a manual motor starter that employs the features of power switching, thermal overload protection and control circuit signaling in one

More information

Ideal for use as a manual starter

Ideal for use as a manual starter Manual Motor Starter Ideal for use as a manual starter The is a manual motor starter that employs the features of power switching, thermal overload protection and control circuit signaling in one compact

More information

Technical Information

Technical Information -100 Controller IEC Performance Data (CSA C22.2, UL 508 No. 14 in connection with a short-circuit protection device Catalog No. -100... 25A 40A 63A 90A Maximum Short-Circuit Current 480V [ka] 65 65 42

More information

1489-M Circuit Breakers

1489-M Circuit Breakers Dual terminals provide wiring/bus bar flexibility and clamp from both sides to improve connection reliability Terminal design helps prevent wiring misses Scratch- and solventresistant printing Suitable

More information

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features Standard Features Table : Standard Features GV2ME GV2P GV3P GV7RE/GV7RS 0. to 32 A Up to 20 hp @ 460 V 0 SCCR @ 480 V Push Button Operator 0. to 30 A Up to 5 hp @ 460 V 50 SCCR @ 480 V Rotary Handle Operator

More information

MS General Information Extended Product Type: MS

MS General Information Extended Product Type: MS MS132-1.6 General Information Extended Product Type: MS132-1.6 Product ID: 1SAM350000R1006 EAN: 4013614400063 Catalog Description: MS132-1.6 Manual Motor Starter Long Description: The MS132-1.6 manual

More information

KT4 Manual Motor Starters

KT4 Manual Motor Starters s General Description...F99 Quick Selection Guide...F100 Accessories...F101 Contact Blocks...F101 Adapter Plates...F101 Release Modules...F102 Connecting Modules...F102 Mounting...F103 Enclosures...F103

More information

Manual Motor Starters. Meta-MEC

Manual Motor Starters. Meta-MEC Manual Motor Starters Meta-MEC Manual Motor Starters LS Meta-MEC Manual Motor Starters provide completed ranges up to 100A 45 mm 55 mm 32AF 2 2 45 mm 70 mm 63AF 100AF 3 3 Manual LS Meta-MEC Motor Starters

More information

FMotor Circuit Controllers & Circuit Breakers

FMotor Circuit Controllers & Circuit Breakers Motor Circuit Controllers & Circuit Breakers Motor Controllers and MCCBs Series KT7 Motor Circuit Controllers...2 Series KTA7 Base Units...4 Series KTC7 Base Units...6 Series KTB7 Base Units...8 Series

More information

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427 Data sheet CI-TI TM Contactors and Motor Starters Circuit Breakers November 2002 DKACT.PD.C00.L2.02 520B1427 Introduction Circuit breakers/manual motor starters cover the power ranges 0.09-12.5 kw This

More information

XT IEC Power Control Manual Motor Protectors

XT IEC Power Control Manual Motor Protectors May 07 Product Selection Table 7. Rotary with Screw Terminals Global Ratings and North American Ratings Type and Type 2 Coordination Motor Protective Device with Thermal and Magnetic Trip Rated Uninterrupted

More information

ACS motor protection circuit breakers KT 7 Introduction

ACS motor protection circuit breakers KT 7 Introduction Introduction Automatic Type 2 coordination The right circuit breaker for all applications The KT 7 circuit breaker family consists of two basic frame sizes of mm and 5 mm in three variations with different

More information

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4. Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type

More information

Selection Guide. Control Circuit and Load Protection

Selection Guide. Control Circuit and Load Protection Selection Guide Control Circuit and Load Protection Circuit Protection Portfolio 1489-M Circuit Breakers Approved for branch circuit protection in the United States and Canada, and certified as Miniature

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

MS /27/2015. ABB contact for United States of America. General Information Extended Product Type: Categories

MS /27/2015. ABB contact for United States of America. General Information Extended Product Type: Categories Page 1 of 5 MS132-10 ABB contact for United States of America General Information Extended Product Type: Product ID: EAN: Catalog Description: Long Description: MS132-10 1SAM350000R1010 4013614400100 MS132-10

More information

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction Introduction Introduction Schneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection

More information

F Motor Circuit Controllers. Series KT7 Motor Circuit Controllers. KT4 Manual Motor Starters. General Description...F2

F Motor Circuit Controllers. Series KT7 Motor Circuit Controllers. KT4 Manual Motor Starters. General Description...F2 Series KT7 General...2 Series & KTA3-100 Base Units...4 Series Base Units...6 Series Base Units...8 Accessories...10 Technical Information - KT7...20 Dimensions - KT7...32 Technical Information - KTA3-100...37

More information

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases Index Page Circuit-Breakers M4 166 for motor protection Auxiliary contacts 167 Signalling switch Auxiliary releases Insulated 3-pole busbar system 168 Terminal block DIN-rail adapters 169 Busbar adapters

More information

Motor Controllers + Circuit Breakers

Motor Controllers + Circuit Breakers Series General...2 Series & KTA3-100 Base Units...4 Series Base Units...6 Series Base Units...8 Accessories...10 Technical Information -...20 Dimensions -...33 Technical Information - KTA3-100...39 Dimensions

More information

Product index. 4 - Manual motor protectors. Phone: Fax: Web: -

Product index. 4 - Manual motor protectors. Phone: Fax: Web:  - Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type

More information

Siemens AG Price groups PG 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J

Siemens AG Price groups PG 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J Protection Equipment Siemens AG 2015 Click on the Article No. in the catalog PDF to access it in the Industry Mall and get all related information. Article-No. 3RA1943-2C 3RA1943-2B 3RA1953-2B 3RA1953-2N

More information

Bulletin 190-M Compact Starters. Selection Guide

Bulletin 190-M Compact Starters. Selection Guide Bulletin 190-M Selection Guide Bulletin 190-M Selection Guide 3 Bulletin 190-M Compact Design to 45mm Wide Common Adapter for Panel or DIN Rail Mounting Pre-Wired Assembly All Control Terminations Located

More information

Protection Equipment

Protection Equipment Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection

More information

Protection Equipment. 5/2 Introduction

Protection Equipment. 5/2 Introduction Protection Equipment /2 Introduction SIRIUS 3RV2 Motor Starter Protectors/ Circuit Breakers up to 40 A /6 General data /12 For motor protection /14 For motor protection with overload relay function /1

More information

Selection Guide Motor Control Device Solutions

Selection Guide Motor Control Device Solutions Selection Guide Motor Control Device Solutions Expect more and get it from c3controls. Our portfolio of Motor Control Devices consists of worldclass products designed and manufactured to meet your requirements

More information

Bulletin 190S/191S Direct On-Line Compact Combination Starters

Bulletin 190S/191S Direct On-Line Compact Combination Starters Bulletin 190S/191S Direct On-Line Compact Combination Starters Group Motor, Type E and Type F Combination Motor Controllers (UL/CSA) The 190S/191S motor controllers can be used in a variety of applications.

More information

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x. Types MS116, MS132, MS5x, MS9x are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/OFF control, and protection against short circuit,

More information

MCS MINIATURE CONTACTORS SELECTION GUIDE THE MINIATURE MODULAR CONTROL SYSTEM SMALL IN DIMENSIONS - BIG IN PERFORMANCE

MCS MINIATURE CONTACTORS SELECTION GUIDE THE MINIATURE MODULAR CONTROL SYSTEM SMALL IN DIMENSIONS - BIG IN PERFORMANCE MCS MINIATURE CONTACTORS SELECTION GUIDE THE MINIATURE MODULAR CONTROL SYSTEM SMALL IN DIMENSIONS - BIG IN PERFORMANCE DOL-Starter Overload Protection PROTECTION FOR AC AND DC MOTORS The Bulletin 193-K

More information

Features 1 Phase HP/Volts 1/6 HP AT 230 V 3 Phase HP/Volts 1/2 HP AT 200/230 V, 1-1/2 HP AT 460/575 V

Features 1 Phase HP/Volts 1/6 HP AT 230 V 3 Phase HP/Volts 1/2 HP AT 200/230 V, 1-1/2 HP AT 460/575 V 804 South Street 7964-76, TX Nacogdoches Phone: 96-69-794 Fax: 96-60-468 A07NN A Man Motor Protector Eaton Corp Catalog Number A07NN Manufacturer Eaton Corp Description Manual Motor Starter, Motor Protector;

More information

Technical data for manual motor starters Type MS325

Technical data for manual motor starters Type MS325 for manual mor starters Type MS325 General data Rated voltage 600 V Rated current 25 A (14 setting ranges, 0.1 25A) Rated frequency 50-60 Hz Electrical and mechanical life endurance 100,000 operations

More information

3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00,

3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00, Low-Voltage Controls and Distribution > Industrial Controls > Protection Equipment > Circuit Breakers/Motor Starter Protectors > Motor Starter Protectors SIRIUS RV up to 00 A RV0-0DA5 CIRCUIT-BREAKER,

More information

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24

More information

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates Motor Starter Protectors/Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates Overview Enclosures For stand-alone installation of 3RV20

More information

UL/CSA Non-fused Disconnect Switches

UL/CSA Non-fused Disconnect Switches Product Selection UL/CSA Non-fused Disconnect Switches Cat. No. 194R-N30-1753 Cat. No. 194R-J100-1753 Note: Your order must include 1) Cat. No. of disconnect switch, 2) shaft, 3) handle, and 4) any accessories.

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

Short form catalogue. Motor protection & control

Short form catalogue. Motor protection & control Short form catalogue Star Series Motor protection & control Motor Protection and Control up to 25 HP / 600 VAC Overview...2 Contactors and Overload Relays...11 4-pole Contactors...41 Control Relays...59

More information

Bulletin 1489 Circuit Breakers. Selection Guide

Bulletin 1489 Circuit Breakers. Selection Guide Bulletin 1489 s Selection Guide Bulletin 1489-A Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable

More information

Bulletin 193-T1 Bimetallic Overload Relays

Bulletin 193-T1 Bimetallic Overload Relays Bulletin 193T1 Bimetallic Overload Relays Overload protection trip class 10 / 10A Phase loss protection Ambient temperature compensation Auxiliary contacts (1 N.O. and 1 N.C.) Manual/automatic reset mode

More information

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU 200 M is ABB s solution for UL 489 branch

More information

Technical Information

Technical Information Technical Information KT7 Controller Time-Current Characteristic KT7 Manual Motor Starter/Protector 1. Thermal Release Trip Current The adjustable current-dependent delayed bimetal release protects motors

More information

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X Manual motor protectors Type MS116 Type MS32 Type MS4X Type MS49X Manual motor protectors MS116 MS32 MS4X MS49X Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL ed and

More information

Control Circuit Protection

Control Circuit Protection Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC

More information

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories Manual motor protectors Manual motor protectors Manual motor Protectors MS116 MS32 MS4X MS49X Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL Listed and CSA certified

More information

EC Declaration of Conformity

EC Declaration of Conformity The undersigned, representing the manufacturer Rockwell Automation AG Buchserstr. 7 CH-5000 Aarau Switzerland herewith declare that the Products Product identification (brand and catalogue number/part

More information

Motor-protectivecircuit-breaker,3p,Ir=2.5-4A. Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton actuation

Motor-protectivecircuit-breaker,3p,Ir=2.5-4A. Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton actuation Motor-protectivecircuit-breaker,3p,Ir=2.5-4A Partno. PKZM01-4 Articleno. 278482 CatalogNo. XTPB004BC1 Deliveryprogramme Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton

More information

AF40... AF96 3-pole contactors Technical data

AF40... AF96 3-pole contactors Technical data Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional

More information

Certifications UL Listed (File No. E 14841, Guide NLRV; File No. E 47426, Guide WHTY) CSA Certified (File No. LR1234) CE

Certifications UL Listed (File No. E 14841, Guide NLRV; File No. E 47426, Guide WHTY) CSA Certified (File No. LR1234) CE Bulletin R Overview Bulletin R Next Generation Global Fused and Non-Fused Disconnects 0 A A Sizes Fused Switch Versions: - BS - DIN - CSA HRCII-C - CSA HRCI-MISC - UL Class J - UL Class CC - NFC Non-Fused

More information

CENTERLINE 2100 Motor Control Centers

CENTERLINE 2100 Motor Control Centers TECHNICAL DATA CENTERLINE 2 Motor Control Centers Instantaneous Trip Motor Circuit Protectors (MCP) in Combination NEMA Starter, Soft Starter (SMC) and Variable Frequency AC Drive Units 1A Frame Instantaneous

More information

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X Manual motor protectors Type MS116 Type MS32 Type MS4X Type MS49X Manual motor protectors Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL Listed and CSA certifi ed for

More information

Approved Standards. Ordering Information. Mini Motor Contactor J7KNA. Model Number Legend. Main contactor. Accessories. Mini Motor Contactor J7KNA 1

Approved Standards. Ordering Information. Mini Motor Contactor J7KNA. Model Number Legend. Main contactor. Accessories. Mini Motor Contactor J7KNA 1 Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC

More information

and other modular devices for low voltage installation

and other modular devices for low voltage installation Technical catalogue System and other modular devices for low voltage installation 2CSC400002D0204 SUMMARY Introduction Miniature Circuit-Breakers Residual Current Devices Auxiliary elements and accessories

More information

AF / AF12Z pole Contactors AC / DC Operated - with Screw Terminals

AF / AF12Z pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101404D0201 24/03/11-30-10-.. / Z-30-10-.. 3-pole Contactors AC / DC Operated - with Screw Terminals (Z) contactors are used for controlling power circuits up to 690 V AC and 220

More information

3VU13, 3VU16 Circuit-Breakers

3VU13, 3VU16 Circuit-Breakers 3VU3, 3VU6 Circuit-Breakers Description The 3VU3, 3VU6 circuit-breakers are compact circuit-breakers for currents up to 80 A which operate according to the current limiting principle. The devices are used

More information

D509E. Manual Motor - Starters

D509E. Manual Motor - Starters D509E Manual Motor - Starters Index Page Manual Motors Starters 182 Auxilliary Contact Blocks 182 Trip Alarm Aux. Switch 182 Shunt Release 182 Under-voltage Release 183 Accessories 183 Busbar Connectors

More information

Cat. No. 194R-J Note: Your order must include 1) Cat. No. of disconnect switch, 2) shaft, 3) handle, and 4) any accessories.

Cat. No. 194R-J Note: Your order must include 1) Cat. No. of disconnect switch, 2) shaft, 3) handle, and 4) any accessories. Product Selection UL/CSA Fused Disconnect Switches Cat. No. 194R-J30-1753 Cat. No. 194R-J100-1753 Note: Your order must include 1) Cat. No. of disconnect switch, 2) shaft, 3) handle, and 4) any accessories.

More information

WELCOME TO THE WORLD OF COMPLETE AUTOMATION. Innovative MCS Starter Solutions. MCS Starters and the New Mounting System 141A

WELCOME TO THE WORLD OF COMPLETE AUTOMATION. Innovative MCS Starter Solutions. MCS Starters and the New Mounting System 141A WELCOME TO THE WORLD OF COMPLETE AUTOMATION Innovative MCS Starter Solutions MCS Starters and the New Mounting System 141A Welcome to the Wide World of Allen-Bradley Starters Innovative solutions for state

More information

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC AF0... AF0 -pole Contactors up to 20 HP / 480 VAC Contactors and Overload Relays Overview...2 AF0... AF0 -pole Contactors Ordering Details...4 Main Technical Data...20 DC Circuit switching...2 Main Accessory

More information

Manual Motor Starters

Manual Motor Starters Leader in Electrics & Automation Meta-MEC Manual Motor Starters Electric Equipment LG Meta-MEC Manual Motor Starters provide completed ranges up to 100A 45 mm 55 mm 32AF 2 45 mm 70 mm 63AF 100AF 3 LG Meta-MEC

More information

CI-TI Contactors and motor starters Types CI 61 - CI 98

CI-TI Contactors and motor starters Types CI 61 - CI 98 Data sheet CI-TI Contactors and motor starters s CI 6 - CI 98 Contactors CI 6, CI 7, CI 86 and CI 98 switch powers of up to 0 kw, 7 kw, 45 kw and 55 kw respectively under 80 V - loads. Accessories include

More information

PKZ and PKE motor-protective circuit-breakers

PKZ and PKE motor-protective circuit-breakers PKZ and PKE motor-protective circuit-breakers Machinery and installation downtimes should be kept as short as possible. The PKZ fuseless motor-protective circuit-breakers combine short-circuit and overload

More information

Approvals UL 508; CSA-C22.2 No ; CSA-C22.2 No. 94; IEC/EN ; CE marking

Approvals UL 508; CSA-C22.2 No ; CSA-C22.2 No. 94; IEC/EN ; CE marking MainswitchSurfacemounting Partno. P1-25/I2/SVB-SW Articleno. 207294 IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches

More information

Low-Peak 600V Class RK1

Low-Peak 600V Class RK1 LPS-RK 600Vac/300Vdc, 1 10-60A, Dual Element, Time-Delay Fuses Dimensions - in 5" (± 0.31) 5.5" (± 0.31) Available with easyid open fuse indication 1/10 to 30A 0.81" (±0.008) 35 to 60A 1.06" (±0.008) Description:

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

MAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-

MAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5- MKING MODERN LIVING POSSIBLE Technical brochure Minicontactors CI 5- www.danfoss.com 2 IC.PD.C10.F3.02-520B4167 Danfoss /S, C-SMC, mr, 07-2010 Contents Page Minicontactor CI 5- Introduction...............................................................................4

More information

Control Power V AC, 50/60 Hz 150-C30NBD 150-C30FHD

Control Power V AC, 50/60 Hz 150-C30NBD 150-C30FHD Bulletin Product Selection Open Type and Non-Combination Enclosed (IP, NEMA /) Controllers For use with Line-Connected Motors Rated Voltage [V AC] / Motor Current [A]...... Max. kw, Hz Max. Hp, Hz Control

More information

Data Sheet Manual Motor Starters Ex9SN Series

Data Sheet Manual Motor Starters Ex9SN Series Data Sheet Manual Motor Starters Ex9SN Series www.noarkusa.com NOARK Ex9SN Series Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors

More information

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489 Data Sheet System pro M compact for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU200 M is BB s solution for UL 489 branch circuit protection

More information

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control Contents Description Relays and Timers......................... Miniature Controls......................... Contactors and Starters.................... Thermal Overload Relays.................... C440/XT

More information

Self-protected Combination Starters System PKZ 2-SP

Self-protected Combination Starters System PKZ 2-SP Self-protected Combination Starters System PKZ 2-SP 03/035 PKZ 2/ZM/S-SP motor starters: a higher level of protection and versatility : The PKZ 2/ZM/S-SP is a self-protected starter, the first motor controller

More information

IEC Starter Approximate Dimensions

IEC Starter Approximate Dimensions Technical Data IEC Starter Approximate Dimensions Bulletin Numbers 103H/107H/140M, 103-C/107/C, 105, 109, 106, 112, 113, 190E/191E, 190S/191S, 103S/107S, 103T/107T Topic Page Enclosed Starters and Motor

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control . Contents Description Relays and Timers......................... Miniature Controls......................... Contactors and Starters.................... Thermal Relays.................... C440/XT Electronic

More information

AF40... AF96 3-pole contactors 30 to 60 hp at 480 V AC AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts

AF40... AF96 3-pole contactors 30 to 60 hp at 480 V AC AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts AF4... AF96 -pole contactors to 6 hp at 48 V AC AC / DC operated with N.O. N.C. auxiliary contacts Description AF4... AF96 contactors are mainly used for controlling -phase motors and power circuits up

More information

Motors Automation Energy Transmission & Distribution Coatings. Automation Contactors - CWM Line

Motors Automation Energy Transmission & Distribution Coatings. Automation Contactors - CWM Line Motors Automation Energy Transmission & Distribution Coatings Automation Contactors - CWM Line 2 Contactores Compactos CWC0 Contactors - CWM Line Sumary Presentation Accessories Overview 5 Three-Pole Contactors

More information

Protective Devices: Circuit-Breakers 1 )

Protective Devices: Circuit-Breakers 1 ) Protective Devices: Circuit-Breakers 1 ) /2 Introduction SIRIUS circuit-breakers 1 ) up to 100 A / General data /20 For motor protection /22 For motor protection with overload relay function /23 For starter

More information

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting.

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting. DATASHEET - ZB12-2,4 Delivery program Overload relay, 1.6-2.4 A, 1N/O+1N/C Part no. ZB12-2,4 Catalog No. 278437 Eaton Catalog No. XTOB2P4BC1 EL-Nummer 0004131832 (Norway) Product range Overload relay ZB

More information

Series L9 UL489 Miniature Circuit Breakers

Series L9 UL489 Miniature Circuit Breakers Series L9 UL489 iniature Circuit Breakers Industrial Circuit Breakers for Branch Circuit Protection up to 63 Amps L9 Series B Circuit Breakers Series B L9 UL489 circuit breakers offer new features, expanded

More information

Approvals UL 508; CSA-C22.2 No ; IEC/EN ; CE marking

Approvals UL 508; CSA-C22.2 No ; IEC/EN ; CE marking MainswitchRearmounting Partno. T0-2-1/V/SVB-SW Articleno. 045992 Front IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches

More information

ASL09..S 3-pole Contactors - Spring Terminals

ASL09..S 3-pole Contactors - Spring Terminals 4 kw 5 hp ASL09..S 3-pole Contactors - Spring DC Operated Description - 3-pole contactors with spring terminals, - N.C. or N.O. built-in auxiliary contact, - Low coil consumption, - Polarity on the coil

More information

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD. DATASHEET - DILMC9-10(24VDC) Technical data General Contactor, 3p+1N/O, 4kW/400V/AC3 Part no. DILMC9-10(24VDC) Catalog No. 277468 Eaton Catalog No. XTCEC009B10TD EL-Nummer 4110305 (Norway) Standards IEC/EN

More information

Essential equipment for all your requirements

Essential equipment for all your requirements NEW CTX CONTACTORS Essential equipment for all your requirements 9 A TO 310 A THREE-POLE INDUSTRIAL CONTACTORS CTX three-pole industrial contactors, a sense of family The new range of CTX contactors provides

More information

Meta Solution. Contactors and Overload relays

Meta Solution. Contactors and Overload relays Meta Solution Contactors and Overload relays Meta Solution New generation of Contactors from LSIS Contactors and Overload Relays Metasol Contactors Designed to show superior technology: The Metasol series

More information

Bulletin 190E/191E Direct On-Line Eco Starters

Bulletin 190E/191E Direct On-Line Eco Starters Bulletin 190E/191E Direct On-Line Eco Starters Group Motor, Type E and Type F Combination Motor Controllers (UL/CSA) The 190E/191E motor controllers can be used in a variety of applications. These starters

More information

Panel SCCR 50kA RMS Symmetrical 480V Maximum

Panel SCCR 50kA RMS Symmetrical 480V Maximum Panel SCCR 50kA RMS Symmetrical 480V Maximum 4 Short-Circuit Current Rating SCCR: The perspective or maximum symmetrical fault current at a nominal voltage to which an apparatus or system is able to be

More information

Application Mini Contactors for Motors and Resistive Loads

Application Mini Contactors for Motors and Resistive Loads Delivery program Contactor, 4p, 4kW/400V/AC3 Part no. DILEM4-G(24VDC) Catalog No. 012701 Eaton Catalog No. XTMF9A00TD Product range Contactors Application Mini Contactors for Motors and Resistive Loads

More information

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer DATASHEET - ZB65-65 Delivery program Overload relay, 50-65A, 1N/O+1N/C Part no. ZB65-65 Catalog No. 278460 Eaton Catalog No. XTOB065DC1 EL-Nummer 0004131855 (Norway) Product range Overload relay ZB up

More information

Protection components

Protection components Presentation, characteristics Presentation 1 2 3 motor circuit-breakers are 3-pole thermal-magnetic circuit-breakers standards IEC 60947-2 and IEC 60947-4-1. Connection These circuit-breakers are designed

More information

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI . Technical Data and Specifications Ratings Frames EG, JG and LG EG JG LG Maximum rated current (amperes) 15, 160 1 50 400, 630 Breaker type 3 B B E S S H H C E S H C U X E S H C U X of poles 1, 3, 4,

More information

Control and Load Switch Specifications Bulletin Number 194E, 194L

Control and Load Switch Specifications Bulletin Number 194E, 194L Technical Data Control and Load Switch Specifications Bulletin Number 194E, 194L Topic Page Product Line Overview 2 194E General Specifications 3 194E Approximate Dimensions 5 194L Circuit Diagrams 13

More information

B115...B180 RF200 RFN200 B250...B400 RF400 RFN400

B115...B180 RF200 RFN200 B250...B400 RF400 RFN400 Page -2 Page -4 Page -6 FOR BG SERIES MINI-CONTACTORS Type RF9, phase failure sensitive, manual resetting Type RFA9, phase failure sensitive, automatic resetting Type RFN9, non-phase failure sensitive,

More information

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse LPSRK100SP 600V TD Dual Elem Class RK1 Low Peak Fuse Catalog Number Manufacturer Description Weight per unit Product Category LPSRK100SP 600V Class RK1 Low Peak Dual Element, Time Delay Fuse 0.4100 (lbs/each)

More information

AF / AF38Z pole Contactors AC / DC Operated - with Screw Terminals

AF / AF38Z pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101412D0201 25/03/11-30-00-.. / Z-30-00-.. 3-pole Contactors AC / DC Operated - with Screw Terminals (Z) contactors are used for controlling power circuits up to 690 V AC and 220

More information

Circuit-Breakers Bulletin 140 / KTA 3

Circuit-Breakers Bulletin 140 / KTA 3 Motor Protection Characteristics High Switching Capacity High Current Limiting For Compact Motor Starters Overview... - Product Selection -Pole... - 4-Pole... -7 Accessories... -8 Type: Bulletin 40-MN

More information