Communications cable with PC COM ERR. Copy. RJ-45 / USB Adapter. Verify. Remote Operator Extansion Cable. 24 VDC Control Board Power Supply

Size: px
Start display at page:

Download "Communications cable with PC COM ERR. Copy. RJ-45 / USB Adapter. Verify. Remote Operator Extansion Cable. 24 VDC Control Board Power Supply"

Transcription

1 YSKW IMR- 000 High performance Vector ontrol urrent vector control, with or without PG High starting torque (200% / 0.3 Hz, spd range :200 OLV), (200% at 0 r/min, spd range :500 LV) ouble rating N 20%/min and H 50%/ min IM&PM motor control dvanced uto-tuning for IM & PM s Open Loop ontrol of PM s Low-noise Low carrier technology 0 years lifetime design Screw-less terminals ontrol Terminals with memory backup 24 V control board power supply option Fieldbus communications: Modbus, Profibus, anopen, evicenet, ML-II Safety embedded: EN954- safety cat. 3, stop category 0, IE EN 6508 SIL 2 and EN with EM E, UL, cul and TUV Ratings 200 V lass three-phase 0.4 to 0 kw 400 V lass three-phase 0.4 to 35 kw System configuration Power Supply MB ommunications cable with P USB opy Unit OM ERR Reactor opy Verify Read LOK JVOP-8 RJ-45 / USB dapter USB able X-rive X-One Filter Remote Operator Extansion able L Remote Operator 24 V ontrol Board Power Supply 000 ommunication Option Board hoke Feedback Speed Option ards Braking Resistor Ground Reactor 000

2 Specifications Type designation IMR F rive 000 series : European standard specifications Version oating specs: : Standard Enclosure, Fin: : IP00 F: IP20 / Nema Voltage: 2: Three-phase 200 V 4: Three-phase 400 V : Standard specs Rated output urrent Normal uty 0004: 3.5 [] ~ 0675: 675 [] 200 V class kw Output characteristics Power supply Three-phase: IMR-@ For H setting For N setting Inverter capacity kv at H Inverter capacity kv at N Rated output current () at H Rated output current () at N Max. output voltage Proportional to input voltage: V Max. output frequency 400 Hz Rated input voltage and frequency 3-phase V 50/60 Hz llowable voltage fluctuation -5%..+0% llowable frequency fluctuation +5% Input urrent () at H Input urrent () at N Based on a standard 4-pole motor for maximum applicable motor output: 2. Rated apacity is calculated with a rated output voltage of 220 V: 3. arrier frequency is set to 2kHz. urrent derating is required in order to raise the carrier frequency: 4. arrier frequency can be increased up to 8 khz while keeping this current rating. Higher carrier frequency settings require derating: 5. arrier frequency can be increased up to 5 khz while keeping this current rating. Higher carrier frequency settings require derating: 6. ssumes operation at rated output current. Input current rating varies depending on the power supply transformer, input reactor, Wiring conditions, and power supply impedance: 400 V class Three-phase: IMR-@ For H setting kw For N setting Inverter capacity kv at H Output characteristics Power supply Inverter capacity kv at N Rated output current () at H Rated output current () at N Max. output voltage V (proportional to input voltage) Max. output frequency 400 Hz Rated input voltage and frequency 3-phase V, 50/60 Hz llowable voltage fluctuation -5%..+0% llowable frequency fluctuation +5% Input urrent () at H Input urrent () at N Frequency inverters

3 Specifications Three-phase: For H setting kw For N setting Inverter capacity kv at H Output characteristics Power supply Inverter capacity kv at N Rated output current () at H Rated output current () at N Max. output voltage V (proportional to input voltage) Max. output frequency 400 Hz Rated input voltage and frequency 3-phase V, 50/60 Hz llowable voltage fluctuation -5%..+0% llowable frequency fluctuation +5% Input urrent () at H Input urrent () at N Based on a standard 4-pole motor for maximum applicable motor output: 2. Rated apacity is calculated with a rated output voltage of 440 V: 3. arrier frequency is set to 2kHz. urrent derating is required in order to raise the carrier frequency: 4. arrier frequency can be increased up to 8 khz while keeping this current rating. Higher carrier frequency settings require derating: 5. arrier frequency can be increased up to 5 khz while keeping this current rating. Higher carrier frequency settings require derating: 6. ssumes operation at rated output current. Input current rating varies depending on the power supply transformer, input reactor, Wiring conditions, and power supply impedance: ommom specifications ontrol functions Functionality Protection functions Model number IMR- ontrol methods Output frequency range Frequency tolerance Resolution of frequency set value Resolution of output frequency Frequency set value Starting Torque Speed ontrol Range Speed ontrol ccuracy Speed Response Torque Limit ccel/ecel Time Braking torque V/f haracteristics Main ontrol Functions protection Momentary overcurrent Protection Specifications Sine wave PWM (V/f control, V/f control with PG, Open loop vector control, losed loop vector control, Open loop vector control for PM, losed loop vector control for PM, dvanced Open Loop Vector ontrol for PM) Hz igital set value: ±0.0% of the max. output frequency ( º) nalogue set value: ±0.% of the max. output frequency (25 ±0 º) igital set value: 0.0 Hz nalogue set value: 0.03 Hz / 60 Hz ( bit) 0.00 Hz V (20 kω),0..0 V (20 kω), m (250 Ω), Pulse train input, frequency setting value (selectable) 50%/3Hz (V/f control, V/f control with PG), 200%/0.3Hz* (Open loop vector control), 200%/ 0 r/min* (losed loop vector control, losed loop vector control for PM, dvanced Open Loop Vector ontrol for PM), 00% / 5% speed (Open loop vector control for PM), :500 (losed loop vector control, losed loop vector control for PM), :200 (Open loop vector control), :40 (V/f control, V/f control with PG), :20 (Open Loop Vector ontrol for PM), :00 (dvanced Open Loop Vector ontrol for PM) ±0.2% in Open loop vector control (25 ±0 º) * 2, 0.02% in losed loop vector control (25 ±0 º) 0 Hz in Open loop vector control (25 ±0 º), 50Hz in losed loop Vector ontrol (25 ±0 º), )(excludes temperature fluctuation when performing Rotational uto-tuning) ll Vector ontrol allows seperate settings in four quadrants 0.00 to s (4 selectable combinations of independent acceleration and deceleration settings) rives of 200/400 V 30 kw or less have a built-in braking transistor.. Short-time decel torque* 3, over 00% for 0.4/0.75 kw motors, over 50% for.5 kw motors, and over 20% for 2.2 kw and above motors (over excitation braking/high-slip Braking approx. 40%) 2. ontinuous regen, torque approx. 20% (approx. 25% with dynamic braking resistor option* 4, 0% E,0 s, internal braking transistor) User-selected programs and V/f preset pattens possible Torque ontrol, roop control, Speed/torque control switching, Feedforward control, Zero-servo control, Momentary power loss ride-thru, Speed search, Overtorque detection, Torque Limit, 7-step speed (max), ccel/ecel time switch S-curve ccel/ecel, 3-wire sequence, uto-tuning (rotational, stationary), Online Tuning, well ooling fan on/off switch, slip compensation, Torque compensation, Frequency Jump, Upper/lower limits for frequency, injection braking at start and stop, Over excitation braking, High Slip braking, PI control (with sleep function), Energy saving control, MEMOBUS comm. (RS-485/422 max. 5.2kbps), Fault restart, pplication presets, Removable terminal block with parameter backup function... overheat protection based on output current rive stops when ouput current exceeds 200% of Heavy uty Rating Overload Protection rive stops after 60 s at 50% of rated output current (Heavy uty Rating)* 5 Overvoltage Protection Undervoltage Protection Momentary power loss Ride-Thru Heatsink Overheat Protection Braking Resistance Overheat Protection 200 V class: Stops when bus exceeds approx. 40 V, 400 V class: Stops when bus exceeds approx. 820V 200 V class: Stops when bus exceeds approx. 90 V, 400 V class: Stops when bus exceeds approx. 380V Immediately stop after 5 ms or longer power loss (default), ontinuous operation during power loss than 2 s (srandard)* 6 Protected by thermister Overheat sensor for braking resistor (optional) Stall prevention Stall prevention during acceleration/deceleration and constant speed operation Ground fault Protected by electronic circuit* 7 Power charge indication harge LE remains lit until bus has fallen below approx. 50 V

4 mbient conditions rea of Use Indoor (no corrosive gas, dust, etc.) mbient Temperature -0º..+50º(open chassis) up to 60º with output current derating, -0º..+40º (NEM Type ) mbient humidity 95% RH or less (without condensation) Storage temperature -20º..+60º (short-term temperature during transportation) ltitude Up to 000 meters (output derating of % per 00 m above 000 m, max m) Vibration / Shock 0 Hz to 20 Hz, 9.8 m/s 2 max. 20 Hz to 55Hz, 5.9 m/s 2 (200 V: 45kW or more, 400 V: 55kW or more) or 2.0 m/s 2 max. (200 V: 55 kw or less, 400 V: 75 kw or less) Safety Standard EN954- safe category 3 stop category 0; EN ISO 3849-; IE EN 6508 SIL2 Protection esign IP00 open-chassis, IP20, NEM Type enclosure. Requires a drive with recommended capacity. 2. Speed control accuracy may vary slightly depending on installation conditions or motor used. 3. Momentary average deceleration torque refers to the deceleration torque form 60 Hz down to 0 Hz. This may vary depending on the motor. 4. If L3-04 is enabled when using a braking resistor or braking resistor unit, the motor may not stop in the specified deceleration time. 5. Overload protection may be triggered when operating with 50% of the rated output current, if the output frequency is less than 6 Hz. 6. Varies in accordance with the drive capacity and load. rives with a capacity of smaller than kw in the 200 V (model IMR or 400 V (model 7. IMR- 003) require a seperate Momentary Power Loss Unit to continue operating. Protection may not be provided under the following conditions as the motor windings are grounded internally during run: #Low resistance to ground from the motor cable or terminal block. #rive already has a short-circuit when the power is turned on. imensions Open-hassis [IP00] W 4-d t2 W 4-d t2 W 4-d t2 H H H H H H Max 0 W H2 Max 0 Figure t Max 7.7 H2 W Max 7.7 t Max 6 W H2 Max 6 t Figure 2 Figure 3 Voltage class Three-phase 200 V Three-phase 400 V Max. applicable imensions in mm motor output kw Inverter model Figure IMR-@ N H W H W H H2 t t2 d M M M M M M Weight (kg) 4 Frequency inverters

5 Enclosed Panel [NEM Type] W 4-d.5 W 4-d.5 W H2 H 5 H t W H H3 H2 Figure Figure 2 H 8 t Voltage class Three-phase 200 V Three-phase 400 V Max. applicable motor output kw imensions in mm Inverter model IMR-@ Figure N H W H W H H2 t t2 d M M M M6 8.3 Weight (kg) Schaffner Flat Filters F E E B Figure Figure V 400 V Flat Filters Fig imensions Weight KG B E F G H I L 3G3RV-PFI2035-SE M5 23 M5.4 3G3RV-PFI2060-SE M6 30 M6 3 3G3RV-PFI200-SE M6 40 M G3RV-PFI300-SE M4 23 M5.2 3G3RV-PFI308-SE M4 23 M5.3 3G3RV-PFI3035-SE M5 25 M G3RV-PFI3060-SE M M6 4 3G3RV-PFI340-SE M G3RV-PFI3600-SE M G3RV-PFI3800-SE M

6 Bookform Filters H B E G F 200 V 400 V Bookform Filters imensions B E F G H 3G3RV-PFI230-SE M G3RV-PFI260-SE M G3RV-PFI2200-SE M0.0 3G3RV-PFI3070-SE M G3RV-PFI330-SE M G3RV-PFI370-SE M G3RV-PFI3250-SE M0.7 3G3RV-PFI340-SE M G3RV-PFI3600-SE M2.0 3G3RV-PFI3800-SE M2 3.0 Weight KG Remote L operator (0.06) (0.48) Installation holes (2-M3 screws, depth 5 (0.9)) 90 (3.54) 78 (3.07) <> 5 (0.59) 60 (2.36) 7.9 (0.3) minimum 50 (.96) 44 (.73) Unit : mm (in) hokes X escription diameter KW imensions Weight Kg L W H X Y m 000-FEV202-RE 2 < FEV255-RE 25 < FEV5045-RE 50 < FEV6045-RE 60 > W Y H L Ø d Ø m 6 Frequency inverters

7 I79E-EN atasheet.fm Seite 7 Freitag, 5. Januar 200 2:29 4 Braking Unit or more or more or more lead Wire Inlet (20 ia. Rubber Bush) 00 or less Lead Wire Inlet (28 ia. Rubber Bush) 2-lead Wire Inlet (35 ia. Rubber Bush) Main ircuit Terminal M6 30 or more or less M6 MTG Holes or more 4-M4 MTG Holes Model BR-20 B Model BR-205 B, B, -4030B, B 30 or more Mass 8.5 Kg Mass.8 K 04 Lead Wire Inlet (28 ia. Rubber Bush) 2-lead Wire Inlet (35 ia. Rubber Bush) or more or more 30 or more 00 or more Main ircuit Terminal M M6 MTG Holes Model BR-4220 B Mass 2 Kg Resistor imensions 000-REJ0K5 000-REJ0K Braking Resistor Unit M5 x M6 x M8 x 4 M8 x 4 MTG Screw 50 or more MTG Screw or more M8 x M5 x M5 x M6 x M6 x M8 x M8 x 4 M8 x 4 M8 x or more 30 or more or more MTG Screw 50 or more 50 or more or more B (KI B Mass kg B 400 V lass imensions in mm 220 V lass Model LKEB-_ 2P5 22P2 23P7 25P5 27P P5 42P2 43P7 45P5 47P Voltage 7

8 Installation Standard connections Terminals -, +, +2, B, B2 are for connection options. Never connect power supply lines to these terminals reactor (option) U X Jumper Thermal relay (option) Braking resistor (option) Three-phase power supply 200 to 400 V 50/60 Hz R/L S/L2 T/L3 Main Switch Fuse Multi-function digtial inputs (default setting) EM Filter Forward Run / Stop Reverse Run / Stop External fault Fault reset Multi-speed step Multi-speed step 2 Jog speed External Baseblock Sink / Source mode selection wire link (default: Sink) R/L S/L2 T/L3 S S2 S3 S4 S5 S6 S7 S8 SN S SP +24 V B B2 Main ircuit ontrol ircuit 000 Option card connectors N5- N5-B N5- Terminal board jumpers and switches V Off PT I I IP Switch S 2 Volt/urr. Sel IP Switch S2 On Term. Res. On/Off Jumper S3 H, H2 Sink/Source Sel. IP Switch S4 3 nalog/pt Input Sel Jumper S5 V M/FM Volt./urr. I Selection U/T V/T2 W/T3 Ground Shielded able U V W M Multi-function analog/ pulse train inputs Safety switch S2 S Open Safety relay / controller 2 kω MEMOBUS/Modbus comm. RS485/422 max. 5.2 kbps RP R + R S + S IG Safe isable inputs H Wire jumper +V Power supply +0.5 Vdc, max. 20 m nalog Input (Frequency Reference Bias) -0 to +0 Vdc (20 kω) 2 nalog Input 2 (Frequency Reference Bias) -0 to +0 Vdc (20 kω) 0 or 4 to 20 m (250 Ω) 3 nalog Input 3 / PT Input (ux. frequency reference) -0 to +0 Vdc (20 kω) 0 V V H2 H FM M Shield ground terminal Pulse Train Input (max 32 khz) Power supply, -0.5 Vdc, max. 20 m Termination resistor (20 Ω, /2 W) IP Switch S2 0 V 0 V M MB M M M2 M3 M4 M5 M6 MP FM M E (G) Fault relay output 250 Vac, max. 30 Vdc, max (min. 5 Vdc, 0 m) Multi-function relay output (uring Run) 250 Vac, max. 30 Vdc, max (min. 5 Vdc, 0 m) Multi-function relay output (Zero Speed) 250 Vac, max. 30 Vdc, max (min. 5 Vdc, 0 m) Multi-function relay output (Speed gree ) 250 Vac, max. 30 Vdc, max (min. 5 Vdc, 0 m) Multi-function pulse train output (Output frequency) 0 to 32 khz (2.2 kω) + FM M + Multi-function analog output (Output frequency) -0 to +0 Vdc (2m) or 4 to 20 m Multi-function analog output 2 (Output current) -0 to +0 Vdc (2m) or 4 to 20 m EM (Safety Electronic evice Monitor) M + M shielded line twisted-pair shielded line control circuit terminal main circuit terminal Main circuit Terminal Name Function (signal level) R/L, S/L2, T/L3 Main circuit power supply input Used to connect line power to the drive. U/T, V/T2, W/T3 Inverter output Used to connect the motor B, B2 Braking resistor connection vailable for connecting a braking resistor or the braking resistor unit option. +2, + reactor connection Remove the short bar between +2 and + when connecting reactor (option) +, power supply input For power supply input (+: positive electrode; : negative electrode)* +3 Braking Unit onnection for Braking Unit between terminals +3 and Grounding For grounding (grounding should conform to the local grounding code.) 8 Frequency inverters

9 ontrol ircuit Type No. Signal name Function Signal level S Multi-function input selection Factory setting: runs when LOSE, stops when OPEN. S2 Multi-function input selection 2 Factory setting: runs when LOSE, stops when OPEN. igital input signals S3 Multi-function input selection 3 Factory setting: External Fault (N.O.) S4 Multi-function input selection 4 Factory setting: Fault reset S5 Multi-function input selection 5 Factory setting: Multi-step speed cmd S6 Multi-function input selection 6 Factory setting: Multi-step speed cmd 2 S7 Multi-function input selection 7 Factory setting: Jog Frequency 24 V, 8 m photocoupler insulation S8 Multi-function input selection 8 Factory setting: losed gives external baseblock S Multi-function input selection ommon ommon for control signal +V Power Supply for Frequency Setting +0.5 V (allowable max current 20 m) nalog input signals Safety Input V Power Supply for Frequency Setting 0.5 V (allowable max current 20 m) Multi-function analogue input Main Frequency Reference -0 to +0 V, 0 to +0 V (20 kω) 2 Multi-function analogue input 2 Voltage input or current input -0 to +0 V, 0 to +0 V (20 kω) 4 to 20 m (250 Ω) 3 Multi-function analogue input 3 0 to +0 V, 0 to +0 V (20 kω) Frequency reference common 0V H Safety Input ommon +24 V (max allowable current 0 m) H Safety Input H2 Safety Input 2 Open: Stop losed: Normal Operation Photocoupler 24 V, 8 m Safety monitor output M+ M Safety monitor output Safety monitor output common Open: Safety inputs and 2 are open 48 Vdc, 50m or less M NO contact output igital output signals nalog output signals PulseI/O MB N Output Factory setting: "fault" M Relay Output common M Multi-function contact output (N.O ) Factory setting losed: uring run M2 P Photocoupler output Factory setting: Zero speed P2 Photocoupler output 2 Factory setting: Frequency gree P Photocoupler output common 0V FM Multi-function analog monitor () Factory setting: Output frequency M Multi-function analog monitor (2) Factory setting: "urrent monitor, 5 V/drive rated current nalog monitor common 0V RP Main Speed md Pulse Train Input 32 khz max. (3 kω) MP Pulse Train Output Factory setting: Frequency reference input (H6-0=0) 0 to 33 khz (2.2 kω) ontact capacity 250 V, or less 30 V, or less Photocoupler output: +48 V, 50 m or less 0 to 0 V ±5%, (2 m or less) 0 to 0 V 4-20 m R+ ommunication input (+) RS-485/422 R ommunication input ( ) S+ ommunication output (+) S ommunication output ( ) For MEMOBUS communication operation by RS-485 or RS-422 communication is available. RS-485/422 MEMOBUS protocol 000 9

10 Inverter heat loss Three-phase 200 V class Model Number IMR- Rated mps () Heatsink Loss (W) Heavy uty Interior Unit Loss (W) Total Loss (W) Rated mps () Heatsink Loss (W) Normal uty Interior Unit Loss (W) Total Loss (W) Three-phase 400 V class Model Number IMR- Rated mps () Heatsink Loss (W) Heavy uty Interior Unit Loss (W) Total Loss (W) Rated mps () Heatsink Loss (W) Normal uty Interior Unit Loss (W) Total Loss (W) Frequency inverters

11 onnections for braking unit and braking resistor Power supply MB M Thermal relay R/L B B2 S/L2 U/T T/L3 V/T2 Braking resistor + 3 Braking Resistor Overheat ontact (Thermal Relay Trip ontact) P 2 B Braking Resistor Unit THRX OFF S Thermal relay switch for external braking resistor M ON M S M THRX TRX S TRX FLT- FLT-B Fault contact 000 W/T Level etector MSTER SLVE Braking Unit ooling Fin Overheat ontact (Thermoswitch ontact) reactor reactor 000 Power supply MB U X R/L V Y S/L2 W Z T/L3 200 V class 400 V class urrent value Inductance Max. applicable urrent value mh motor output kw / / /85/ Max. applicable motor output kw Inductance mh reactor Power supply MB R/L 000 S/L2 T/L reactor 200 V class 400 V class Max. applicable motor output kw urrent value Inductance mh Max. applicable motor output kw urrent value Inductance mh to 0 Built-in 22 to 35 Built-in 000

12 Safety System 000 provides Safe Torque Off (STO) functional safety in compliance with EN954- safety category 3 stop category 0, EN ISO 3849-, PL, IE/EN6508 SIL2. n External evice Monitor (EM) function has also been added to monitor the safety status of the drive. EN954- Safety at.3 ompliance Safety controller ontroller Power supply Feedback loop 2 Frequency inverters

13 opy LOK YSKW Ordering information Power Supply MB ommunications cable with P Reactor Filter Verify Read USB opy Unit OM ERR JVOP-8 RJ-45 / USB dapter Remote Operator Extansion able USB able L Remote Operator X-rive X-One 24 V ontrol Board Power Supply 000 B ommunication Option Board hoke F Feedback Speed Option ards E Braking Resistor Ground Reactor V 400 V Specifications Model Heavy uty Normal uty Standard 0.4 kw kw 3.5 IMR-20004F 0.75 kw 5.0. kw 6.0 IMR-20006F.5 kw kw 9.6 IMR-2000F 2.2 kw kw 2.0 IMR-2002F 4.0 kw kw 2.0 IMR-2002F 5.5 kw kw 30.0 IMR-20030F 7.5 kw kw 40.0 IMR-20040F kw kw 56.0 IMR-20056F 5 kw kw 69.0 IMR-20069F 8.5 kw kw 8 IMR-2008F 22 kw kw 0 IMR kw 5 37 kw 38 IMR kw kw 69 IMR kw kw 2 IMR kw kw 250 IMR kw kw 32 IMR kw kw 360 IMR kw 45 0 kw 45 IMR kw kw 2. IMR-40002F 0.75 kw kw 4. IMR-40004F.5 kw kw 5.4 IMR-40005F 2.2 kw kw 6.9 IMR-40007F 3.0 kw kw 8.8 IMR-40009F 4.0 kw kw. IMR-400F 5.5 kw kw 7.5 IMR-4008F 7.5 kw kw 23.0 IMR-40023F kw kw 3.0 IMR-4003F 5 kw kw 38.0 IMR-40038F 8.5 kw kw 44 IMR-40044F 22 kw kw 58 IMR kw kw 72 IMR kw kw 88 IMR kw 9 55 kw 03 IMR kw 2 75 kw 39 IMR kw kw 65 IMR kw 80 0 kw 208 IMR kw kw 250 IMR kw kw 296 IMR kw kw 362 IMR kw kw 44 IMR kw kw 55 IMR kw kw 675 IMR

14 Line filters hokes B ommunication cards ccessories Inverter Line filter Voltage Model IMR- Reference Rated current () Weight (kg) 3-Phase 200 V 3-Phase 400 V ommunication option board / / G3RV-PFI300-SE / 2002 / 2008 / G3RV-PFI308-SE / / G3RV-PFI2035-SE / G3RV-PFI2060-SE / G3RV-PFI200-SE / 202 3G3RV-PFI370-SE /40004 / / G3RV-PFI300-SE /400 3G3RV-PFI308-SE / / G3RV-PFI3035-SE /40044 / G3RV-PFI3060-SE / G3RV-PFI300-SE / 4039 / G3RV-PFI370-SE / G3RV-PFI3200-SE / G3RV-PFI3400-SE / G3RV-PFI3600-SE G3RV-PFI3800-SE Model iameter escription 000-FEV202-RE 2 Recommended for motors below 2.2 KW 000-FEV255-RE 25 Recommended for motors below 5 KW 000-FEV5045-RE 50 Recommended for motors below 45 KW 000-FEV6045-RE 60 Recommended for motors above 45 KW Type Model escription Function Used for running or stopping the inverter, setting or referencing parameters, and monitoring SI-N3 evicenet option card output frequency, output current, or similar items through evicenet communi- cation with the host controller. Used for running or stopping the inverter, setting or referencing parameters, and monitoring SI-P3 PROFIBUS-P option card output frequency, output current, or similar items through PROFIBUS-P com- munication with the host controller. SI-S3 SI-T3 an open option card Mechatrolink II option card Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through Nopen communication with the host controller. Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through Mechatrolink II communication with the host controller. Types Model escription Functions JVOP-80 L remote operator L isplay operator with language support igital operator 3G3X-JOP300-EE Remote operator cable 3 meters cable for connecting remote operator JVOP-8 USB converter / USB cable USB converter unit with copy and backup function ccessories PS-V0S 24V control board power supply VZ-B/2/4 from 0. to 4 KW 24 V option board PS-V0M 24V control board power supply VZ-2/4 from 5.5 to 5 KW 000-VP232-EE P connection cable RS232 P tool connection cable omputer software Types Model escription Installation Software X-drive omputer software onfiguration and monitoring software tool X-One omputer software onfiguration and monitoring software tool 4 Frequency inverters

15 E Braking unit, braking resistor unit Inverter Max. pplicable kw 200 V lass 400 V lass Model Braking unit Model BR_ No. of used Model 000-RE_ Specifications of Resistor Qty Braking Resistor Type Braking torque % Model (3% E) LKEB- Specifications of Resistor Qty Braking Min torque % Resist (0% E) Value Ω H N J0K5200-IE 90W 200 Ω H N H 50 2P5 260W 00Ω N J0K500-IE 90 W 00 Ω 25 2P5 260W 00Ω 000 H N 48 J0K5070-IE 90 W 70 Ω 20 22P2 260W 70Ω H N P7 390W 40Ω H J0K5062-IE 90 W 62 Ω 008 N P7 390W 40Ω H N 2 0 Built-in 25P5 520W 30Ω 0030 H N P5 780W 20Ω H N W 3.6Ω 0056 H N W 0Ω 0069 H N W 0Ω 008 H N W 0Ω H W 6.8Ω N W 6.8Ω 038 H N W 6.8Ω H 205B W 0Ω N W 0Ω B 2 02 H W 6.8Ω N B W 6.8Ω H N - 20B 032 H W 6.8Ω N - 20B 0360 H W 6.8Ω N - 20B 045 H W 8Ω H J0K0750-IE 60 W 750 Ω N J0K0750-IE 60 W 750 Ω H N 96 J0k5400-IE 90 W 400 Ω 25 4P5 260W 400Ω H N 0007 H J0k5300-IE 90 W 300 Ω 5 42P2 260W 250Ω N 42P2 260W 250Ω J0k5200-IE 90 W 200 Ω H 43P7 390W 50Ω N 00 H J0k5200-IE 90 W 200 Ω 05 43P7 390W 50Ω N J0k5200-IE 90 W 00 Ω H - 45P5 520W 00Ω N Built in H - 47P5 780W 75Ω N W 50Ω H N H W 40Ω N W 32Ω H N H W 27.2Ω N H W 20Ω N W 20Ω H 4045B W N B 003 H W 3.6Ω N 4045B W 3.6Ω H 4030B W 20Ω N 4030B W 20Ω H 4045B W 3.6Ω N B H W 3.6Ω N B 0250 H W 20Ω

16 Inverter Braking unit Braking Resistor Type Max. Model Model No. of Model Specifications of Braking Model Specifications of Braking Min pplicable IMR- BR_ used 000-RE_ Resistor Qty torque % (3% E) LKEB- Resistor Qty torque % Resist (0% E) Value Ω N B 0296 H W 3.6Ω N B 0362 H W 3.6Ω N B 044 H W 3.6Ω N B 055 H W 6Ω N 4220B H 4220B W 3.6Ω N 4220B When connecting a mounting type resistor or braking resistor unit, set system constant L3-04 to 0 (Stall prevention disabled during deceleration). will not stop at set deceleration time if this constant is not changed. dditionally the Internal braking transistor protection (L8-55) should be set to 0 when a external braking unit (BR-) is used. 400 V lass F Feedback speed option card Type Model escription Function PG-B3 omplementary PG For speed feedback input by connecting a motor encoder Input: 3 track (one or two tracks), for HTL encoder connection, 50 KHz max Output: 3 track open collector Encoder power supply: 2 V, 200 m max PG-X3 Line river PG For speed feedback input by connecting a motor encoder Input: 3 track, line driver, 300 khz max Output: 3 track, line driver Encoder power supply: 5 V or 2 V, 200 m max PG option card Qnisz ING Krzysztof Kunisz Janówek Pierwszy, ul. Nowodworska 96 tel./fax: , tel.kom: adres Qnisz@Qnisz.pl LL IMENSIONS SHOWN RE IN MILLIMETERS. To convert millimeters into inches, multiply by To convert grams into ounces, multiply by at. No. I79E-EN-0 In the interest of product improvement, specifications are subject to change without notice. 6 Frequency inverters

A1000. High performance vector control.»» Able to control IM & PM motors»»safety built-in»»application parameter presets

A1000. High performance vector control.»» Able to control IM & PM motors»»safety built-in»»application parameter presets 000 High performance vector control»» ble to control IM & PM motors»»safety built-in»»pplication parameter presets High performance motor control The 000 provides remarkable advantages through excellent

More information

US B Copy Unit CO M ERR. Copy. RJ-45 / USB Adapter. Verify. Read LOCK YASKA WA J VOP-181. Remote Operator Extansion Cable.

US B Copy Unit CO M ERR. Copy. RJ-45 / USB Adapter. Verify. Read LOCK YASKA WA J VOP-181. Remote Operator Extansion Cable. Read opy LOK YSK IMR 1000 igh performance Vector ontrol urrent vector control, with or without PG igh starting torque (200% / 0.3 z, spd range 1:200 OLV), (200% at 0 r/min, spd range 1:1500 LV) ouble rating

More information

USB Copy Unit COM ERR. Copy. RJ-45 / USB Adapter. Verify. Read LOCK YASKAWA JVOP-181. Remote Operator Extansion Cable. Communication Option Board

USB Copy Unit COM ERR. Copy. RJ-45 / USB Adapter. Verify. Read LOCK YASKAWA JVOP-181. Remote Operator Extansion Cable. Communication Option Board YSKW VZ V1000 More performance & Quality in less space Current vector control High starting torque (200% / 0.5 Hz) 1:100 speed control range Double rating ND 120%/1min and HD 150%/1 min IM&PM motor control

More information

RS232 Communications cable with PC ER M. RJ-45 / USB Adapter Remote Operator Extansion Cable. Communication Unit. Mounting Accesories

RS232 Communications cable with PC ER M. RJ-45 / USB Adapter Remote Operator Extansion Cable. Communication Unit. Mounting Accesories JZ J1000 The basic inverter V/f controlled inverter Good torque performance (150% / 3 Hz) Double rating ND 120%/1min and HD 150%/1 min Overload detection function (150% during 60s) Motor thermal function

More information

RV SYSDrive AC Inverters

RV SYSDrive AC Inverters 7160_Omron 3/31/04 4:38 PM Page 1 OMRON IM ONTROLS, IN. RV SYSrive Inverters High-Value, 4-in-1 Inverter Solutions for General-Purpose & High-End pplications 7160_Omron 3/31/04 4:38 PM Page RV Inverter

More information

Varispeed J7 CIMR-J7AZ. System configuration

Varispeed J7 CIMR-J7AZ. System configuration CIMR-J7AZ Varispeed J7 Small, simple and smart V/f controlled inverter Compact size Good torque performance: 100% torque at 1.5 Hz, 150% at 3 Hz 150% overload / 60sec Overload detection function. Motor

More information

V1000. Inverter Series.

V1000. Inverter Series. V1000 Inverter Series www.yaskawa.eu.com One for all The V1000 is a general purpose inverter drive covering the demands of a wide field of applications. Simple duties as well as requirements of complex

More information

V1000 Inverter Series

V1000 Inverter Series V1000 Inverter Series www.yaskawa.eu.com One for all The V1000 is a general purpose inverter drive covering the demands of a wide field of applications. Simple duties as well as requirements of complex

More information

J1000 D E F I 1000 J1000 J1000 J1000 J1000

J1000 D E F I 1000 J1000 J1000 J1000 J1000 Compact Inverter SERIES J1000 GB D E F I 1000 J1000 J1000 J1000 J1000 The J-Type YASKAWA Inverter Drive Technology Contents Page 2 Experience & Innovation A leader in Inverter Drives technology Page 3

More information

Q2A. System configuration

Q2A. System configuration Q2 riving Quality dvanced motor control for IM, PM & SynRM motors Open/closed loop speed or torque control Embedded functional safety (STO SIL3) Built-in C3 class EMC filter Conform to EN 60721-3-3, 3S2

More information

A1000 D E A1000 A1000 A1000 A1000

A1000 D E A1000 A1000 A1000 A1000 Inverter Series High Performance Vector Control GB D E F I 1000 Yaskawa High Performance Drive Contents Page 2 Experience & Innovation A leader in Inverter Drives technology Main Features Page 3 Customize

More information

V1000 DE ES FR IT V1000 V1000 V1000 V1000

V1000 DE ES FR IT V1000 V1000 V1000 V1000 Inverter Series V1000 EN DE ES FR IT 1000 V1000 V1000 V1000 V1000 V1000 YASKAWA Inverter Drive Technology Contents Page 2 Experience & Innovation A leader in Inverter Drives technology V1000 Easy and cost-saving

More information

LIFT INVERTER SERIES L1000A

LIFT INVERTER SERIES L1000A LIFT INVERTER SERIES L1000A EN DE For Modernization and New Installation YASKAWA L1000A FOR HIGH PERFORMANCE LIFT APPLICATION Contents Page 2 Experience & Innovation Page 3 Main Features Page 4 Energy

More information

SYSDrive Frequency Inverter

SYSDrive Frequency Inverter SYSDrive Frequency Inverter T V/f control T PID control T Standard LED, optional LCD operator T Fieldbus options: DeviceNet T 7 configurable digital inputs T 3 configurable digital outputs T Low audible

More information

J1000. Compact Inverter Series.

J1000. Compact Inverter Series. J1000 Compact Inverter Series www.yaskawa.eu.com Focus on Application Customer orientation and application focus two attributes of machine equipment YASKAWA offers with its J1000 compact inverter drive

More information

Technical Information

Technical Information Yaskawa Electric Europe GmbH Hauptstraße 185 65760 Eschborn Germany Tel. +49 (0)61 96/569 300 Technical Information Topic Replacement Varispeed C+ with Reference: UEW0101D Source: Based on YEC document

More information

Varispeed E7. Varispeed E7. Varispeed. Varispeed E7. Varispeed E7. Varispeed E7 INVERTER SERIES

Varispeed E7. Varispeed E7. Varispeed. Varispeed E7. Varispeed E7. Varispeed E7 INVERTER SERIES INVERTER SERIES Varispeed E VARISPEED E YASKAWA INVERTER DRIVE TECHNOLOGY Contents Content Page 2 Experience & Innovation A leader in Drives technology Page 3 Specifications Experience & Innovation For

More information

LIFT INVERTER SERIES L1000V DE ES FR IT 1000V L1000V L1000V L1000V L1000V

LIFT INVERTER SERIES L1000V DE ES FR IT 1000V L1000V L1000V L1000V L1000V LIFT INVERTER SERIES EN DE ES FR IT 1000V YASKAWA INVERTER DRIVE TECHNOLOGY Contents Page 2 Introduction Experience & Innovation YASKAWA speaks Lift Page 3 YASKAWA Main Features Page 4 Specifications Page

More information

CIMR-V7AZ Varispeed V7

CIMR-V7AZ Varispeed V7 CIMR-V7AZ Sensorless vector in pocket size 150% overload / 60 sec 100% torque at 0.5 Hz Autotuning High carrier up to 14 khz Stop accuracy 2 motors controller Integrated PID controller and bidireccional

More information

Honeywell CORE Drive FEATURES APPLICATION SPECIFICATION DATA

Honeywell CORE Drive FEATURES APPLICATION SPECIFICATION DATA Honeywell CORE Drive SPECIFICATION DATA FEATURES APPLICATION The new Honeywell VFD CORE Drive addresses the need to save time for installation, and provides the lower total installed costs with years of

More information

Experience & Innovation

Experience & Innovation Yaskawa L1000A For High-Performance Elevator Application CONTENTS Experience & Innovation...2 Advanced Motor / Drive Technology...3-5 Simple Programming...5 Main Features...6-7 Maintainability & Certifications...8

More information

A V Class: ½ to 175 HP 480V Class: ½ to 1000 HP 600V Class: ½ to 250 HP

A V Class: ½ to 175 HP 480V Class: ½ to 1000 HP 600V Class: ½ to 250 HP A1000 240V Class: ½ to 175 HP 480V Class: ½ to 1000 HP 600V Class: ½ to 250 HP A single drive for all your needs, with outstanding performance and flexibility! The A1000 is a full-featured drive, providing

More information

DE ES A A. For Modernisation and New Installation L1000A L1000A L1000A

DE ES A A. For Modernisation and New Installation L1000A L1000A L1000A lift Inverter Series L1000A EN DE ES FR IT A1000 1000A L1000A L1000A L1000A For Modernisation and New Installation Yaskawa L1000A for High Performance Lift Application Contents Page 2 Experience & Invation

More information

LIFT INVERTER SERIES L1000A

LIFT INVERTER SERIES L1000A LIFT INVERTER SERIES L1000A EN DE ES FR IT For Modernisation and New Installation YASKAWA L1000A FOR HIGH PERFORMANCE LIFT APPLICATION Contents Page 2 Experience & Innovation Page 3 Main Features Page

More information

INVERTER SERIES HIGH PERFORMANCE VECTOR CONTROL A1000

INVERTER SERIES HIGH PERFORMANCE VECTOR CONTROL A1000 INVERTER SERIES HIGH PERFORMANCE VECTOR CONTROL EN DE YASKAWA HIGH PERFORMANCE DRIVE Contents Page 2 Experience & Innovation A leader in Inverter Drives technology Main Features Page 3 Customize Your Drive

More information

ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL. Dual Rating. Technologies Inc. mgitech.com NRTL/C CERTIFIED

ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL. Dual Rating. Technologies Inc. mgitech.com NRTL/C CERTIFIED ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL Dual Rating NRTL/C CERTIFIED Technologies Inc. mgitech.com Sensor/Sensorless Vector Control Dual current rated for constant and variable torque Auto

More information

Constant torque, Constant power, Torque boost Six selectable pre-set patterns

Constant torque, Constant power, Torque boost Six selectable pre-set patterns VT20 Micro variable speed drives Single-phase or three-phase digital inverters for controlling the speed of three-phase induction motors from 02 to 22kW uilt-in keypad and display P20 or P65 protection

More information

YASKAWA AC Drive Compact V/f Control Drive J1000

YASKAWA AC Drive Compact V/f Control Drive J1000 YASKAWA AC Drive Compact V/f Control Drive 200 V CLASS, THREE-PHASE INPUT: 0.1 to 5.5 kw 200 V CLASS, SINGLE-PHASE INPUT: 0.1 to 2.2 kw 400 V CLASS, THREE-PHASE INPUT: 0.2 to 5.5 kw Reliable and Smart

More information

Delta Products VFD CP2000 Bypass Control Packages.

Delta Products VFD CP2000 Bypass Control Packages. Delta Products VFD CP2000 Bypass Control Packages www.deltaww.com Delta Products VFD CP2000 Bypass Control Packages The Delta Products VFD CP2000 Bypass Control Packages are designed for the Delta Products

More information

V1000. YASKAWA AC Drive. Compact Vector Control Drive

V1000. YASKAWA AC Drive. Compact Vector Control Drive YASKAWA Compact Vector Control Drive YASKAWA AC Drive V1000 200 V CLASS, THREE-PHASE INPUT: 0.1 to 18.5 kw 200 V CLASS, SINGLE-PHASE INPUT: 0.1 to 3.7 kw 400 V CLASS, THREE-PHASE INPUT: 0.2 to 18.5 kw

More information

V1000. AC Drive Series.

V1000. AC Drive Series. V1000 AC Drive Series www.yaskawa.eu.com One for all The V1000 is a compact general purpose AC drive covering the demands of a wide range of applications. Simple duties as well as requirements of complex

More information

YASKAWA AC DRIVES. Yaskawa AC Drives The Global Leader in Quality and Reliability. Certified for ISO9001 and ISO14001

YASKAWA AC DRIVES. Yaskawa AC Drives The Global Leader in Quality and Reliability. Certified for ISO9001 and ISO14001 YASKAWA AC DRIVES Yaskawa AC Drives The Global Leader in Quality and Reliability Certified for ISO9001 and ISO14001 JQA-QMA14913 JQA-EM0202 With world-leading quality and technology, Yaskawa delivers AC

More information

U1000. Low Harmonics Regenerative Matrix Converter EN DE U1000 U1000 U1000 U1000 U1000 U1000

U1000. Low Harmonics Regenerative Matrix Converter EN DE U1000 U1000 U1000 U1000 U1000 U1000 Low armonics Regenerative Matrix Converter EN E Content 02 About YASKAA A Leader in Inverter rives Technology 03 - The rive for Maximum Efficiency 04 Compact and Effective 05 Features and Functions 06

More information

L1000A. Lift Inverter Drives.

L1000A. Lift Inverter Drives. L1000A Lift Inverter Drives www.yaskawa.eu.com Rise to the top YASKAWA L1000 lift drives are the solution to technical requirements of today s elevators. This inverter controls induction and permanent

More information

LIFT INVERTER SERIES L1000A

LIFT INVERTER SERIES L1000A LIFT INVERTER SERIES L1000A EN DE For Modernization and New Installation 02 03 04 06 07 08 09 10 Content About YASKAWA A Leader in Inverter Drives Technology L1000A - Rise To The Top Benefits at a Glance

More information

GS2 Series - Introduction

GS2 Series - Introduction GS2 Series - Introduction GS2 Series Drives Rating Hp.25.5 1 2 3 5 7.5 10 kw 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 Single-Phase 115 Volt Class Single/Three-Phase 230 Volt Class Three-Phase 230 Volt Class Three-Phase

More information

YASKAWA AC Drive A1000

YASKAWA AC Drive A1000 YASKAWA AC Drive A000 High Performance Vector Control Drive Quick Start Guide Type: CIMR-AC Models: 200 V Class: 0.4 to 55 kw 400 V Class: 0.4 to 90 kw To properly use the product, read this manual thoroughly

More information

YASKAWA AC Drive V1000. YASKAWA AC Drive V1000

YASKAWA AC Drive V1000. YASKAWA AC Drive V1000 MANUAL NO. TOEP C710606 15E YASKAWA AC Drive V1000 Compact Vector Control Drive Quick Start Guide Type: CIMR-VC Models: 200 V Class, Three-Phase Input: 0.1 to 18.5 kw 200 V Class, Single-Phase Input: 0.1

More information

V1000. YASKAWA AC Drive Compact Vector Control Drive NEMA4X/IP66

V1000. YASKAWA AC Drive Compact Vector Control Drive NEMA4X/IP66 YSK YSK C rive Compact Vector Control rive V000 NEM4X/IP66 00 V CLSS, TREE-PSE INPUT: 0. to 8.5 k 00 V CLSS, SINGLE-PSE INPUT: 0. to.0 k 400 V CLSS, TREE-PSE INPUT: 0. to 8.5 k Certified for ISO900 and

More information

Description 1/8-7.5HP

Description 1/8-7.5HP Description 1/8-7.5HP J1000 In our pursuit to create drives optimized for variable speed needs in compact applications, the J1000 is the solution. This micro-drive is simple and reliable with Yaskawa quality.

More information

P V Class: ¾ to 175 HP 480V Class: 1 to 1000 HP 600V Class: 2 to 250 HP

P V Class: ¾ to 175 HP 480V Class: 1 to 1000 HP 600V Class: 2 to 250 HP P1000 240V Class: ¾ to 175 HP 480V Class: 1 to 1000 HP 600V Class: 2 to 250 HP The Flexible and Intuitive Solution for Fan and Pump Applications. The P1000 drive provides simple, reliable, cost-effective

More information

YASKAWA AC DRIVES. Yaskawa AC Drives The Global Leader in Quality and Reliability. Certified for ISO9001 and ISO14001

YASKAWA AC DRIVES. Yaskawa AC Drives The Global Leader in Quality and Reliability. Certified for ISO9001 and ISO14001 YASKAWA AC DRIVES Yaskawa AC Drives The Global Leader in Quality and Reliability Certified for ISO9001 and ISO14001 JQA-QMA14913 JQA-EM0202 With world-leading quality and technology, Yaskawa delivers AC

More information

IP 20/NEMA 1 & IP 66/NEMA 4X Compact Vector Control Drive

IP 20/NEMA 1 & IP 66/NEMA 4X Compact Vector Control Drive IP 0/NMA & IP 66/NMA 4X Compact Vector Control rive APPLICATIONS General multi-function model IP 0/NMA Textiles oodworking Small andling Machine Simple Metal Processing Machine Tools Packaging & Labeling

More information

THE NEW V1000 INVERTER 1 0 x = 1

THE NEW V1000 INVERTER 1 0 x = 1 THE NEW V1000 INVERTER 1 0 x 1 0 0 = 1 D e s i g n e d f o r :» 1 0 y e a r s l i f e t i m e» 1 0 0 % ex p e c t a t i o n m a t c h» 1 i n 1 0,0 0 0 f i e l d f a i l u re ra t e Quality has a new formula

More information

U1000. Low Harmonics Regenerative Matrix Converter.

U1000. Low Harmonics Regenerative Matrix Converter. U1000 Low Harmonics Regenerative Matrix Converter www.yaskawa.eu.com A class of its own The U1000 is a highly efficient inverter drive based on latest matrix converter technology. With full power regeneration

More information

A V Class: ¾ to 175 HP 480V Class: ¾ to 1000 HP 600V Class: 1 to 250 HP

A V Class: ¾ to 175 HP 480V Class: ¾ to 1000 HP 600V Class: 1 to 250 HP A1000 240V Class: ¾ to 175 HP 480V Class: ¾ to 1000 HP 600V Class: 1 to 250 HP A Single Drive for all Your Needs, with Outstanding Performance and Flexibility! The A1000 is a full-featured drive, providing

More information

D1000 REGENERATIVE CONVERTER UNIT EN DE

D1000 REGENERATIVE CONVERTER UNIT EN DE 1000 RGNRTI ONRTR NIT N 02 03 04 05 06 08 09 10 11 ontent bout SK Leader in Inverter rives Technology The Power Regenerative onverter nit iscover new nergy Saving Potentials pplications Package Selection

More information

Frequency Inverters SJ Series Type P1

Frequency Inverters SJ Series Type P1 Frequency Inverters SJ Series Type P1 Automation Solutions by Hitachi SJ Series, Type P1 High Performance Inverter Hitachi maintains research and development departments throughout the business. These

More information

Datasheet VFD-CP2000. Type number key A B C S -XY VFD 007 CP 43. Option cards. Slot 3

Datasheet VFD-CP2000. Type number key A B C S -XY VFD 007 CP 43. Option cards. Slot 3 Type number key VFD 007 CP 43 Option cards A B C S -XY Y=0: UL open 1: NEMA1 X=0: IP00 2: IP20 Version number: A=Wall mount B=Higher rated current C=Cabinet S=Frame D0 Input voltage 23=230VAC 3φ 43=400VAC

More information

P-SERIES VFD WITH BYPASS

P-SERIES VFD WITH BYPASS P-SERIES VFD WITH BYPSS 1 40 HP (200~230 VC) 1 100 HP (380~480 VC), 3Ø Enclosed Bypass - UL Type 3R Standard Controls for Bypass & Local/Remote Operation Special Instructions: FETURES ND OPTIONS Compact

More information

L300P Inverter Specifications

L300P Inverter Specifications L300P Inverter Specifications Tables for 200V class inverters Note that General Specifications on page 1 9 covers all L300P inverters, followed by footnotes for all specifications tables. Seven 200V models

More information

More freedom - lower cost

More freedom - lower cost More freedom - lower cost V1000 MMD - Flexible to operate The V1000 MMD is a frequency converter for decentralized use. It can be mounted directly on the motor, or installed directly next to the motor

More information

YASKAWA AC Drive A1000

YASKAWA AC Drive A1000 YASKAWA AC Drive A000 IP54 Ready Quick Start Guide Type: CIMR-AC4A WAA Models: 400 V Class: 8.5 to 90 kw To properly use the product, read this manual thoroughly and retain for easy reference, inspection,

More information

Technical Explanation for Inverters

Technical Explanation for Inverters CSM_Inverter_TG_E_1_2 Introduction What Is an Inverter? An inverter controls the frequency of power supplied to an AC motor to control the rotation speed of the motor. Without an inverter, the AC motor

More information

BR Second Position Voltages. AA Fourth Position

BR Second Position Voltages. AA Fourth Position 1336S First Position Bulletin Number BR Second Position Voltage Letter AQ BR CW A B BP BX C Q R RX W Voltages 200-240V AC or 3V DC 380-480VAC or 513-620V DC 500-600V AC or 775V DC or 200-240V AC 380-480V

More information

YASKAWA AC Drive High Performance Vector Control A1000

YASKAWA AC Drive High Performance Vector Control A1000 YASKAWA AC Drive High Performance Vector Control A1000 200 V CLASS, 0.4 to 110 kw 400 V CLASS, 0.4 to 630 kw Certified for ISO9001 and ISO14001 JQA-0422 JQA-EM0498 The Birth of Yaskawas Ace Drive Offering

More information

NEW NEW. Power Regenerative Unit R1000. Power Regenerative Converter D1000. Low Harmonics Regenerative Matrix Converter U1000

NEW NEW. Power Regenerative Unit R1000. Power Regenerative Converter D1000. Low Harmonics Regenerative Matrix Converter U1000 NEW Power Regenerative Unit 200 V lass, 3.5 kw to 105 kw 400 V lass, 3.5 kw to 300 kw Power Regenerative onverter 200 V lass, 5.0 kw to 130 kw 400 V lass, 5.0 kw to 630 kw Low Harmonics Regenerative Matrix

More information

Unidrive M400 Fast set-up and diagnostics with real-text display, integrated PLC and safety inputs

Unidrive M400 Fast set-up and diagnostics with real-text display, integrated PLC and safety inputs Unidrive M400 Fast set-up and diagnostics with real-text display, integrated PLC and safety inputs 0.25 kw - 110 kw (0.33 hp - 150 hp) 100 V 200 V 400 V 575 V 690 V Unidrive M400 features Optional AI-485

More information

Chapter 1: Getting Started User Manual Overview...1 2

Chapter 1: Getting Started User Manual Overview...1 2 Getting Started Chapter 1 Table of Contents Chapter 1: Getting Started User Manual Overview.........................................1 2 Overview of this Publication.........................................

More information

BLV Series. Brushless Motor and Driver Package DC Power Supply Input, High Power. Features. Standard Type/Electromagnetic Brake Type

BLV Series. Brushless Motor and Driver Package DC Power Supply Input, High Power. Features. Standard Type/Electromagnetic Brake Type rushless Motor and river Package Power Supply Input, High Power LV Series Standard Type/Electromagnetic rake Type Introducing the new high power, input LV Series brushless motor and driver with output

More information

ADJUSTABLE FREQUENCY CRANE CONTROLS

ADJUSTABLE FREQUENCY CRANE CONTROLS IMPULSE G+ MINI ADJUSTABLE FREQUENCY CRANE CONTROLS The IMPULSEG+ Mini from Magnetek continues our history of providing the most reliable and cost-effective adjustable frequency crane controls available.

More information

MX1S Matrix Converter

MX1S Matrix Converter MX1S Matrix Converter Energy-Saving Medium-Voltage Drive with Power Regeneration 4.16 kv, 500 to 4000 HP, UL Listed Also available in 3 kv and 6kV Class Certified for ISO9001 and ISO14001 CERTI F I ED

More information

Unidrive M600 High performance drive for induction and sensorless permanent magnet motors

Unidrive M600 High performance drive for induction and sensorless permanent magnet motors Unidrive M600 High performance drive for induction and sensorless permanent magnet motors 0.75 kw - 2.8 MW Heavy Duty (1.0 hp - 4,200 hp) 200 V 400 V 575 V 690 V Unidrive M600 features Easy click-in keypad

More information

5.1 Errors (Alarms) Error (alarm) definitions PROTECTIVE FUNCTIONS. (1) Major faults

5.1 Errors (Alarms) Error (alarm) definitions PROTECTIVE FUNCTIONS. (1) Major faults .1 Errors (Alarms) If any fault has occurred in the inverter, the corresponding protective function is activated and the error (alarm) indication appears automatically on the PU display. When the protective

More information

Braking unit, Braking resistor unit

Braking unit, Braking resistor unit YASKAWA AC Drive Option Braking unit, Braking resistor unit Installation Manual BRAKING UNIT CDBR- BRAKING RESISTOR UNIT LKEB- To properly use the product, read this manual thoroughly and retain for easy

More information

Total efficiency 26.7% ( ) Required power. Power consumption Pressure (MPa) , , ,000. Power (W) 100,000 80,000 60,000

Total efficiency 26.7% ( ) Required power. Power consumption Pressure (MPa) , , ,000. Power (W) 100,000 80,000 60,000 Power Motor efficiency (%) 100 Theoretical maximum operating efficiency 80 60 40 20 Power which can be saved by inverter control +energy saving control 0 20 Power which can be saved by inverter control

More information

V1000. YASKAWA AC Drive. Compact Vector Control Drive

V1000. YASKAWA AC Drive. Compact Vector Control Drive Compact Vector Control Drive YASKAWA AC Drive V1000 200 V CLASS, THREE-PHASE INPUT: 0.1 to 18.5 kw 200 V CLASS, SINGLE-PHASE INPUT: 0.1 to 3.7 kw 400 V CLASS, THREE-PHASE INPUT: 0.2 to 18.5 kw So advanced!

More information

VFD E Series. Features

VFD E Series. Features VFD E Series Output Frequency : 0.1 ~ 600 Hz. Built in PLC Function 500 Step program in Ladder Language. Side by side installation. Easy maintenance. Modular & Compact Design. Built-in MODBUS communication.

More information

High performance Vector Control. Ratings. System configuration

High performance Vector Control. Ratings. System configuration System configuration High performance Vector Control Low harmonic or regenerative drive IP54 full range Compact design and robustness Built-in filter (according to C3 class) Built-in fuses (from 200 kw)

More information

SJ300 Inverter Specifications

SJ300 Inverter Specifications SJ300 Inverter Specifications Tables for 200V class inverters Note that General Specifications on page 1 9 covers all SJ300 inverters, followed by footnotes for all specifications tables. The 200V models

More information

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Retain for future use. 30072-450-47A July 2002 Raleigh, NC, USA HAZARDOUS VOLTAGE Read and understand

More information

V1000. YASKAWA AC Drive Compact Vector Control Drive

V1000. YASKAWA AC Drive Compact Vector Control Drive YASKAWA AC Drive Compact Vector Control Drive V1000 200 V CLASS, THREE-PHASE INPUT: 0.1 to 18.5 kw 200 V CLASS, SINGLE-PHASE INPUT: 0.1 to 3.7 kw 400 V CLASS, THREE-PHASE INPUT: 0.2 to 18.5 kw So advanced!

More information

Data Bulletin. ALTIVAR FLEX58 Chassis Drive Controllers Class 8806 INTRODUCTION DESIGN CONCEPT. Bulletin No. 8806DB0102 August 2001 Raleigh, NC, USA

Data Bulletin. ALTIVAR FLEX58 Chassis Drive Controllers Class 8806 INTRODUCTION DESIGN CONCEPT. Bulletin No. 8806DB0102 August 2001 Raleigh, NC, USA Data Bulletin Raleigh, NC, USA ALTIVAR FLEX58 Chassis Drive Controllers Class 8806 INTRODUCTION The ALTIVAR FLEX58 chassis drive controller offers OEMs, panel builders, integrators, and users a unique

More information

VSD Series II Variable Speed Micro Drives

VSD Series II Variable Speed Micro Drives VSD Series II Variable Speed Micro Drives Product Bulletin Code No. LIT-12011813 Issued March 26, 2013 Refer to the QuickLIT website for the most up-to-date version of this document. Johnson Controls VSD

More information

2.3. Adjustable Frequency Drives. Contents. Standards and Certifications

2.3. Adjustable Frequency Drives. Contents. Standards and Certifications Contents Selection................ Product Selection....................... Accessories........................... Technical Data and Specifications.......... Dimensions........................... Page

More information

SD700FR. Regenerative Active Front End VARIABLE SPEED DRIVES POWER ELECTRONICS / SD700 SERIES 4 QUADRANT. icool

SD700FR. Regenerative Active Front End VARIABLE SPEED DRIVES POWER ELECTRONICS / SD700 SERIES 4 QUADRANT. icool FR VARIABLE SPEED DRIVES Regenerative Active Front End icool 4 QUADRANT POWER ELECTRONICS / SD700 SERIES FR SD700FR SERIES goes one step ahead keeping the family unique characteristics. Based on the latest

More information

CDBR-B. Dynamic Braking Unit Instruction Manual. April 2009 Part Number: R1 Copyright 2009 Electromotive Systems

CDBR-B. Dynamic Braking Unit Instruction Manual. April 2009 Part Number: R1 Copyright 2009 Electromotive Systems CDBR-B Dynamic Braking Unit Instruction Manual April 2009 Part Number: 146-10001-R1 Copyright 2009 Electromotive Systems 2009 MAGNETEK All rights reserved. This notice applies to all copyrighted materials

More information

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp VS1MX AC Micro Drive 1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp & Controls 115 VAC 230 VAC 230 VAC 460 VAC 1 Phase - 50/60 Hz 1 Phase - 50/60 Hz 3 Phase - 50/60 Hz 3 Phase - 50/60 Hz Applications:

More information

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp VS1MX AC Micro Drive 1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp & Controls 115 VAC 230 VAC 230 VAC 460 VAC 1 Phase - 50/60 Hz 1 Phase - 50/60 Hz 3 Phase - 50/60 Hz 3 Phase - 50/60 Hz Applications:

More information

RM B. Features. Drive Model Number Scheme. A RM6 Product Series

RM B. Features. Drive Model Number Scheme. A RM6 Product Series Features RM6 series are suitable for constant and variable torque loads (mixer, conveyor, fan, pump, etc.) Overload capacity with 150% drive s rated output current for 1 min can sustain heavy load conditions

More information

Unidrive M700 Class leading performance with onboard real-time Ethernet

Unidrive M700 Class leading performance with onboard real-time Ethernet Unidrive M Class leading performance with onboard real-time Ethernet. kw -.8 MW Heavy Duty (. hp -, hp) V V V 9 V Unidrive M features Easy click-in keypad connection Range of multi-language LCD keypads

More information

SD1 Series General Purpose AC Variable Speed Drives

SD1 Series General Purpose AC Variable Speed Drives 1 200/240V 50/60Hz 0.4~2.2kW (0.5~3HP) 3 200/240V 50/60Hz 0.4~7.5kW (0.5~10HP) 3 380/440V 50/60Hz 0.75~110kW (1~150HP) IP20 Torque Vector Control STO (safe torque off) Up to 150% Starting Torque Front

More information

YASKAWA AC Drive High Performance Vector Control A1000

YASKAWA AC Drive High Performance Vector Control A1000 YASKAWA AC Drive High Performance Vector Control A1000 200 V CLASS, 0.4 to 110 kw 400 V CLASS, 0.4 to 630 kw Certified for ISO9001 and ISO14001 JQA-QMA14913 JQA-EM0202 The Birth of Yaskawas Ace Drive Offering

More information

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings

More information

Low voltage AC drives

Low voltage AC drives General machinery drives Main features and dimensions Unique features Fast and extensive I/O PID control Application macros Many installation possibilities 200 to 480 V, 1-phase or 3-phase More value for

More information

3G3JX AC DRIVES. Compact and complete. »» Cost a n d e co-friendly. Downloaded from Elcodis.com electronic components distributor

3G3JX AC DRIVES. Compact and complete. »» Cost a n d e co-friendly. Downloaded from Elcodis.com electronic components distributor AC DRIVES Compact and complete»» Q u a l i t y & re l i a b i l i t y y o u c a n d e p e n d o n»» Co m m u n i c a t i o n s b u i l t- i n»» Cost a n d e co-friendly The smallest gets integrated...

More information

Disconnect Switch and Circuit Breaker Mechanism Specifications Bulletin Number 1494

Disconnect Switch and Circuit Breaker Mechanism Specifications Bulletin Number 1494 Technical ata isconnect Switch and ircuit reaker Mechanism Specifications ulletin Number 1494 Topic Page 1494U isconnect Switch Specifications 2 1494, 1494F, 1494G, 1494R, 1494V isconnect Switch Specifications

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary

More information

YASKAWA AC Drive High Performance Vector Control A1000

YASKAWA AC Drive High Performance Vector Control A1000 YASKAWA YASKAWA AC Drive High Performance Vector Control A1000 200 V CLASS, 0.4 to 110 kw 400 V CLASS, 0.4 to 630 kw Certified for ISO9001 and ISO14001 CERT I FI ED MANAGEMENT SYSTEM CERTI F I ED MANAGEMENT

More information

MX2-Series V1 type. kw VT motor capacity

MX2-Series V1 type. kw VT motor capacity Multi-function Compact MX-Series V1 type With Machine Automation Mentality Positioning functionality. Fieldbus communications with optional unit *1 EtherCAT, CompoNet and DeviceNet Drive Programming. Current

More information

Shenzhen Sine Electric Co., Ltd.

Shenzhen Sine Electric Co., Ltd. Page 1 of 5 Favorite Contact 中文 Please enter key words 提交查 Home Products Solutions Service About us Products EM500 Open loop Inverter Your current location:home > Products Standard Inverters EM500 Open

More information

YASKAWA AC Drive High Performance Vector Control A1000

YASKAWA AC Drive High Performance Vector Control A1000 YASKAWA YASKAWA AC Drive High Performance Vector Control A000 200 V CLASS, 0.4 to 0 kw 400 V CLASS, 0.4 to 630 kw Certified for ISO900 and ISO400 CERT I FI ED MANAGEMENT SYSTEM CERTI F I ED MANAGEMENT

More information

KBAC SERIES Adjustable Frequency Drives for 3-Phase AC Motors NEMA-4X / IP-65

KBAC SERIES Adjustable Frequency Drives for 3-Phase AC Motors NEMA-4X / IP-65 Installation & Operation Manual KBAC SERIES Adjustable Frequency Drives for 3-Phase AC Motors NEMA-4X / IP-65 Variable Speed / Soft-Start AC Motor Drive with Electronic Motor Overload Protection for Inverter

More information

MX2 inverter. »»Built-in safety. Born to drive machines. »» Omron Quality with a capital Q»»High programming functionality

MX2 inverter. »»Built-in safety. Born to drive machines. »» Omron Quality with a capital Q»»High programming functionality MX2 inverter Born to drive machines»» Omron Quality with a capital Q»»High programming functionality»»built-in safety Harmonised motor and machine control The MX2 is specifically designed to drive machines.

More information

Quick Start Guide of CV50- ControlVIT Series

Quick Start Guide of CV50- ControlVIT Series ❶ Safety precautions Do not refit the inverter unauthorizedly; otherwise fire, electric shock or other injury may occur. Please install the inverter on fire-retardant material and keep the inverter away

More information

Variable speed drives

Variable speed drives 5 192 Variable speed drives SED2 Variable speed drives for speed control of three-phase a.c. motors actuating fans or pumps. Range: 0.75 kw to 90 kw for IP20/21 version, 1.1 kw to 90 kw for IP54 version.

More information

Description VE1 VFNC3 VFS15 VFPS1

Description VE1 VFNC3 VFS15 VFPS1 Page -2 Page -4 Page -5 V1 N VFN3 TYPS Single-phase 200-240V supply Three-phase motor power, 0.2 to 2.2kW / 0.25 to 3HP ratings at 230V ompliant with I/N 1800-3 standards, first environment, without external

More information

Variable Frequency Drive NEW! Moving your Control. Forward VFD from Unitronics kW Single Phase kW Three Phase

Variable Frequency Drive NEW! Moving your Control. Forward VFD from Unitronics kW Single Phase kW Three Phase Variable Frequency Drive Moving your Control NEW! Forward VFD from Unitronics 0.4-2.2kW Single Phase 0.75-110kW Three Phase Total Solution All-in-One software PLC programming HMI design NEW! VFD configuration

More information

Main Features of Varis

Main Features of Varis Main Features of Varis Feature 1: Matrix Converter Technology High efficiency Because of its basic construction, without use of the conventional Rectifier-DC-Bus configuration, the Matrix Converter provides

More information

3 Year. Warranty. Maximum Engineering for Global Advantage. The High Performance Multifunctional Inverter CEN-G1EN18.05

3 Year. Warranty. Maximum Engineering for Global Advantage. The High Performance Multifunctional Inverter CEN-G1EN18.05 3 Year Maximum Engineering for Global Advantage Warranty The High Performance Multifunctional Inverter CEN-G1EN18.05 Perfomance reaching the peak in the industry Why FRENIC-MEGA? Able to drive induction

More information