1 TOWN OF FRIDAY HARBOR WWTP IMPROVEMENTS ADDENDUM NO. (7 pages total) Issue Date: September 0, 08 General: Recitations of each and every section of the bid documents impacted by this addendum are not given. The described changes impact all relevant portions of the bid documents whether specifically cited below or not. BID FORM: ARTICLE 7 Attachments to this Bid, 7.0: CHANGE The following documents are submitted with and made a condition of this Bid: TO The following documents are submitted per these specifications and made a condition of this Bid: SPECIFICATIONS: SECTION 000 Summary of Work ADD Part.0, E: Contractor shall complete the construction of the west access road prior to work in the headworks improvements area to maintain access to the south property for Town staff. SECTION 000 Temporary Facilities ADD Part.0, B, : Prior to the WWTP startup, the Contractor is responsible for obtaining water and piping water to the proposed headworks as necessary for a clean water leakage test. Contractor shall completely fill to the rim the aerated grit chambers and mechanical screen channels. Chambers and channels shall remained filled for hours with no visible leakage. ADD Part.0, I: Tie-in to Existing Forcemain and 6 Screened Wastewater Lines: Contractor to submit a bypass plan for review and approval Months (min.) prior to tie-in for the existing forcemain and 6 screened wastewater lines. At a minimum, plan to include the following provisions: A. Understanding that roughly hours of sewage storage is available in the existing north post-equalization basin (approximately,000 gallons) for temporary storage of influent wastewater and sewage spills are not acceptable and sewage containment is crucial. B. Contractor must provide a portable pump to drain the 6 screened wastewater line and pump to the north post-equalization basin. Pump should be a minimum of 00 0 TDH and provide a minimum of 00 LF of discharge hose. WWTP IMPROVEMENTS ADDENDUM NO. TOWN OF FRIDAY HARBOR, WASHINGTON
2 C. The Owner will provide pumping necessary to pump the influent wastewater and drained forcemain wastewater (approximately 00 gallons) from the Influent Pump Station to the north Post-Equalization basin. D. The Contractor shall perform this tie-in work no earlier than :00am and no later than 7:00am. SECTION 080 Fences and Gates, Part.0, A: CHANGE Chain link fabric to conform to ASTM A 9, No. 9 gage wire, -inch mesh, Class galvanizing. TO Chain link fabric to conform to ASTM A 9, No. 9 gage wire, -inch mesh, Class galvanizing. SECTION 000 Cast-in-place & Precast Concrete CHANGE Part, C, C TO WSDOT Standard Specifications for Road, Bridge and Municipal Construction, latest edition including section 6-0.()A Qualification of Concrete Suppliers. ADD Part, D, H: Submit qualifications per WSDOT Specification 6-0.()A. DRAWINGS (ATTACHED): REVISED DRAWINGS E., E., E., E., E. WWTP IMPROVEMENTS ADDENDUM NO. TOWN OF FRIDAY HARBOR, WASHINGTON
3 MCC A - IN MCC ROOM REPLACE EXISTING EXHAUST FAN 9 MCC BUCKET WITH NEW 00A CIRCUIT BREAKER FEEDER. PROVIDE NEW COMPLETE BLOWER SYSTEM PER SPECIFICATIONS. BLOWER SHALL BE ALLEN BRADLEY POWERFLEX 0 SERIES. BLOWER SHALL BE PROVIDED WITH HIM LOCATED ON FRONT OF. SECTION SECTION SECTION SECTION SECTION SECTION 6 SECTION 7 CALCULATION POINT FOR UTILITY DEMAND DATA AS PROVIDED BY ORCAS POWER & LIT COOPERATIVE METER #78797 PAD MOUNTED 00KVA C UTILITY TRANSFORMER 80Y/77V, -PHASE UTILITY METER 80V PH, W, 00A, 6KAIC () 00: 00/ 600/ () 00: POWER MONITOR 0/ / 70/ 70/ 00/ 00/ 00/ / 0/ 0/ 0/ 0/ / / / 0/ 0/ 0/ SEE CONTINUATION BELOW 00A P TRANSFER SWITCH GEN 600/ UV PNL-0 9 KVA 7 KVA 08Y/0V 00 KVA 08Y/0V KVA 0/0V PH KVA 0/0V PH 00 KVA 0/0V PH GEN STANDBY GENERATOR 80Y/77V PHASE 0kW/8kVA LPA LPB A MTG RM ANNEX PNL-80 PNL-LPH (EXIST) BELT FILTER PRESS BUILDING TO MCC B IN BLOWER TO MCC C IN WATER UTILITIES PNL-LPF (EXIST) MAINTENANCE BUILDING INF PUMP P-0 INF PUMP P-0 INF PUMP P-0 GRIT PUMP P- / GRIT WSHR WHR-0 W P-60 W P-60 EFF PMP - P- EFF PMP - P- EFF PMP - P- MCC A - IN MCC ROOM SECTION 8 SECTION 9 SECTION 0 MAIN DISTRIBUTION - 80Y/77V - 00A - kaic P-00N SEE CONTINUATION ABOVE 0/ 0/ 0/ 00/ / SPARE PNL-608 0/ 0/ BLO-00 / 70/ 0/ KVA 08Y/0V 0 0/ 0 KVA 0/0V PH 0/ 00/ P-0 GP-C MS / / 0/ P-0 GP-C MS P-0 BL-C P-0 0/ 0/ P-0 P-0 0/ / / P-0 P-0 HW-T kva 80V- 0/0 PHASE P-0N 0/ P-60N SPARE EFF PMP - P- SLUDGE GLRY SUMP PUMP P-608 SLUDGE GLRY SUMP PUMP P-609 / FUME HOOD EXHAUST FAN FAN-9 0 DIGESTER MIXER MIX-6 BIO FILTER BLO-00 INF SCREEN SCN-0 LPC PUMP STATION # FEEDER 60/ 70A TRANSFER SWITCH SITE AREA LITING 7. GP- GRIT PUMP # GP- GRIT PUMP# BL- BLOWER # MS- SCREEN # MS- SCREEN # CL- CLASSIFIER UH- UNIT HEATER # KW UH- UNIT HEATER # KW 0/0V 60A MAIN HW-LP POWER STANDBY POWER FOR BFP ONE LINE DIAGRAM : NONE Call 8 One Fifth Street, Ste 0 Wenatchee, WA 9880 Tel: Fax: /07/08 E. OB NUMBER 9 OF
4 GENERAL NOTES:. CONDUIT ROUTING AND EQUIPMENT LOCATIONS SHOWN ARE SCHEMATIC. CONTRACTOR SHALL PROVIDE ALL CONNECTIONS PER MANUFACTURER AND CODE REQUIREMENTS FOR A COMPLETE AND OPERATIONAL SYSTEM.. EQUIPMENT LOCATIONS AND ARRANGEMENT ARE SCHEMATIC. CONTRACTOR SHALL COORDINATE WITH EQUIPMENT MANUFACTURER FOR DETAILED CONNECTION REQUIREMENTS AND PROVIDE MATERIALS AND INSTALLATION FOR A COMPLETE AND OPERATIONAL SYSTEM.. POWER AND S TO EXISTING EQUIPMENT MUST REMAIN OPERATIONAL UNTIL NEW IS COMPLETE.. HAZARDOUS LOCATIONS - INTERIOR IS CLASS I, DIV. BUILDING IS UNCLASSIFIED PER NFPA 80, TABLE.., ROWS 8 AND 0. ALL INSTRUMENTATION, ELECTRICAL EQUIPMENT AND INSTALLATION SHALL BE IN ACCORDANCE WITH NEC ARTICLE 00. HAZARDOUS LOCATIONS - VALVE AND FLOW METER VAULT IS CLASS I, DIV PER NFPA 80, TABLE., ROW a. ALL INSTRUMENTATION, ELECTRICAL EQUIPMENT AND INSTALLATION SHALL BE IN ACCORDANCE WITH NEC ARTICLE 00. COORDINATE HANDHOLE LOCATION DURING CONSTRUCTION. PROVIDE CONDUIT SPARE TO LIT POLE, STUB UP AND CAP FOR FUTURE USE. SEE LITING POLE DETAIL. FUTURE FLOW SPLITTER, CONTRACTOR SHALL KEEP AREA CLEAR OF ALL HANDHOLES AND ELECTRICAL RACEWAY. # E. VENTILATION 0. CL- CLASSIFIER # S-BL P-0 BLOWER # 7. BL- BLOWER # CHECK VALVE # LIMIT SWITCH CLASS I DIV HAZARDOUS S-GP INFLUENT SAMPLER CL-C () P-0 - CONDUIT E. SCREEN # MS-.0 GP- GRIT PUMP #.0 P-0 S-GP GRIT PUMP # MS- SCREEN # E..0 PLC HW-T HW-LP P-0 () () - CONDUIT, SPARES () - " CONDUIT, SPARES MS-C MS-C S-HH P-0 S-HH P-0 COMM () - CONDUIT, SPARES GP-C GP-C BL-C # FLOW METER DISPLAY P-0 S-FM P-0 S-BL P-0 () - CONDUIT GP- GRIT PUMP # S-GP.0 CHECK VALVE # LIMIT SWITCH GRIT PUMP # P-0 S-GP P-0 () S-GP S-GP S-GP CLASS I DIV HAZARDOUS E. HH-P E. P-00N () - " CONDUIT, SPARES HH-C () () P-0 P-0 S-FM S-BL S-PH S-GP S-GP S-GP S-GP - CONDUIT S-FM COMM () - CONDUIT, SPARES TO (E) FLOW SPLITTER (FUTURE) INFLUENT FLOW METER ELECTRICAL SITE PLAN : = ' CLASS I DIV HAZARDOUS AREA INSIDE FLOW METER VAULT Call 8 Tel: One Fifth Street, Ste 0 Fax: Wenatchee, WA /07/08 E. OB NUMBER 0 OF
5 GENERAL NOTES:. CONDUIT ROUTING AND EQUIPMENT LOCATIONS SHOWN ARE SCHEMATIC. CONTRACTOR SHALL PROVIDE ALL CONNECTIONS PER MANUFACTURER AND CODE REQUIREMENTS FOR A COMPLETE AND OPERATIONAL SYSTEM.. EQUIPMENT LOCATIONS AND ARRANGEMENT ARE SCHEMATIC. CONTRACTOR SHALL COORDINATE WITH EQUIPMENT MANUFACTURER FOR DETAILED CONNECTION REQUIREMENTS AND PROVIDE MATERIALS AND INSTALLATION FOR A COMPLETE AND OPERATIONAL SYSTEM. PROVIDE TWO () COMPLETE SCREEN SYSTEMS MANUFACTURER REQUIREMENTS. PER SPECIFICATIONS AND. POWER AND S TO EXISTING EQUIPMENT MUST REMAIN OPERATIONAL UNTIL NEW IS COMPLETE. PROVIDE NEW COMPLETE CLASSIFIER SYSTEM REQUIREMENTS. PER SPECIFICATIONS AND MANUFACTURER. HAZARDOUS LOCATIONS - INTERIOR IS CLASS I, DIV. BUILDING IS UNCLASSIFIED PER NFPA 80, TABLE.., ROWS 8 AND 0. ALL INSTRUMENTATION, ELECTRICAL EQUIPMENT AND INSTALLATION SHALL BE IN ACCORDANCE WITH NEC ARTICLE 00. PROVIDE NEW GRIT PUMPS, MOTOR STARTERS AND LOCAL S. PROVIDE NEW COMPLETE BLOWER SYSTEM PER SPECIFICATIONS. BLOWER SHALL BE ALLEN BRADLEY POWERFLEX 70 SERIES. BLOWER SHALL BE PROVIDED WITH HIM LOCATED ON FRONT OF. BLOWER NO. LOCAL L L T T L L T T 7. BLOWER NO. BLOWER # -0,, L L T T 0. CL- CLASSIFIER # UH- UNIT HEATER # -,7,9 P-0 BL- 7. BLOWER POWER - WIRING DIAGRAM : NONE P-0 CL-C -,,7 TO P-0 BLOWER # BLOWER DOOR OFF VARIABLE FREQUENCY DRIVE SCREEN # MS-.0 7 E. GP- GRIT PUMP #.0 GRIT PUMP # P-0 HAND AUTO HIM MODULE DIG. INPUT A DIG. INPUT B PLC DIGITAL INPUT HAND MODE UH- UNIT HEATER # -9,, MS- SCREEN # P-0 P-0N.0 P-0 P-0 P-0 HW-T P-0 -,6 HW-LP PLC MS-C MS-C -7,9, -8,0, P-0 P-0 HH-P P-0 P-0 P-0 P-0 BL-C GP-C -,,6 6 E. GP-C -,, GP- GRIT PUMP #.0 GRIT PUMP # P-0 PLC CR BLOWER CALL TO RUN RUN VDC () RUNNING SPEED OUTPUT (-0mA) SPEED INPUT (-0mA) AUTO MODE ANALOG INPUT ANALOG INPUT (PLC - SPEED FEEDBACK) ANALOG OUTPUT ANALOG OUTPUT (PLC - SPEED COMMAND) DIGITAL INPUT COM RUNNING () - " CONDUIT, SPARES P-0 () FAULT P-00N HH-C FAULT TO (E) BLOWER FUNCTIONAL WIRING DIAGRAM : NONE - POWER PLAN : = ' Call 8 Tel: One Fifth Street, Ste 0 Fax: Wenatchee, WA /07/08 E. OB NUMBER OF
6 GENERAL NOTES:. CONDUIT ROUTING AND EQUIPMENT LOCATIONS SHOWN ARE SCHEMATIC. CONTRACTOR SHALL PROVIDE ALL CONNECTIONS PER MANUFACTURER AND CODE REQUIREMENTS FOR A COMPLETE AND OPERATIONAL SYSTEM.. EQUIPMENT LOCATIONS AND ARRANGEMENT ARE SCHEMATIC. CONTRACTOR SHALL COORDINATE WITH EQUIPMENT MANUFACTURER FOR DETAILED CONNECTION REQUIREMENTS AND PROVIDE MATERIALS AND INSTALLATION FOR A COMPLETE AND OPERATIONAL SYSTEM.. POWER AND S TO EXISTING EQUIPMENT MUST REMAIN OPERATIONAL UNTIL NEW IS COMPLETE.. HAZARDOUS LOCATIONS - INTERIOR IS CLASS I, DIV. BUILDING IS UNCLASSIFIED PER NFPA 80, TABLE.., ROWS 8 AND 0. ALL INSTRUMENTATION, ELECTRICAL EQUIPMENT AND INSTALLATION SHALL BE IN ACCORDANCE WITH NEC ARTICLE 00. HAZARDOUS LOCATIONS - VALVE VAULT IS CLASS I, DIV PER NFPA 80, TABLE., ROW a. ALL INSTRUMENTATION, ELECTRICAL EQUIPMENT AND INSTALLATION SHALL BE IN ACCORDANCE WITH NEC ARTICLE 00. PROVIDE GAS MONITOR WITH DUAL SENSORS FOR HYDROGEN SULFIDE AND METHANE GAS DETECTION. COORDINATE INSTALLATION WITH MANUFACTURER TO PROVIDE AIR TIT PENETRATION OF CHANNEL HATCH FOR INFLUENT ULTRA SONIC LEVEL SWITCH. SWITCH SHALL BE EASILY ACCESSIBLE FOR CALIBRATION AND REPLACEMENT WHEN REQUIRED. COORDINATE INSTALLATION WITH MANUFACTURER TO PROVIDE AIR TIT PENETRATION OF CHANNEL HATCH FOR PH AND SALINITY PROBES. PROBES SHALL BE EASILY ACCESSIBLE FOR CALIBRATION AND REPLACEMENT WHEN REQUIRED. EXHAUST FANS AND LOUVERS SHALL OPERATE WHEN THE FOUL AIR SYSTEM FAILS OR THE BUILDING TEMPERATURE REQUIRES COOLING. SEE E.6 FOR WIRING DIAGRAM. # VENTILATION C-RP M.S. # S-GM SOLENOID VALVES GAS MONITOR C-RP C-AS BLOWER # BL- CLASS I DIV HAZARDOUS CLASSIFIER # W SOLENOID C-CS 0. CL- CLASSIFIER # CL-C 7. INFLUENT SAMPLER S-CL S-VC S-SM S-BL S-GP C-AS SCREEN # MS- M.S. # E-STOP C-MS C-MS SCREEN # MS- M.S. # E-STOP C-MS C-MS HW-T HW-LP 7 E..0.0 S-GM S-FM S-MS S-MS S-GP S-GP S-SM PLC HH-P S-PH M.S. # SOLENOID VALVES M.S. # HI FLOAT M.S. # SOLENOID VALVES PH/SALINITY METER MS-C S-HH S-HH M.S. # HI FLOAT MS-C AIR FLOW SWITCH ULTRA SONIC # LEVEL SWITCH ULTRA SONIC # LEVEL SWITCH BL-C C-MS C-MS S-GP S-GP S-BL S-FM FLOW METER DISPLAY 6 E. GP-C GP-C S-FM C-RP # CHECK VALVE # LIMIT SWITCH GP- GRIT PUMP # GP- GRIT PUMP # S-GP.0.0 S-GP S-GP CLASS I DIV HAZARDOUS S-GP S-GP S-GP TO INFLUENT FLOW METER VAULT HH-C S-FM S-GP S-GP S-GP S-GP S-BL S-FM S-GP S-GP S-GP S-GP S-FM - S PLAN : = ' Call 8 Tel: One Fifth Street, Ste 0 Fax: Wenatchee, WA /07/08 E. OB NUMBER OF
7 SINGLE PHASE RACEWAY & CONDUCTORS THREE PHASE RACEWAY & CONDUCTORS FEEDER ID P-0 P- P-0 P- P-0 P- P-0 P-60 P-70 P-80 P-90 P-00 P- P-0 P-7 P-00 P- P-0 P-00 P-0 P-00 P-600 P-800 AMPERAGE 0A A 0A A 0A A 0A 60A 70A 80A 90A 00A A 0A 7A 00A A 0A 00A 0A 00A 600A 800A # OF SETS () () () CONDUIT /" /" /" -/" -/" -/" -/" -/" " " " -/" -/" " " " " EACH () # () # () #0 ()#8 () #8 ()#6 () #6 () # () # () # () # () # () # () #/0 () #/0 () #/0 () #/0 () #0 () #0 ()#00 () #/0 () #/0 () #/0 GROUND # # #0 #0 #0 #0 #0 #0 #8 #8 #8 #8 #6 #6 #6 #6 # # # # # # #/0 FEEDER ID P-0 P- P-0 P- P-0 P- P-0 P-60 P-70 P-80 P-90 P-00 P- P-0 P-7 P-00 P- P-0 P-00 P-0 P-00 P-0 P-00 P-600 AMPERAGE 0A A 0A A 0A A 0A 60A 70A 80A 90A 00A A 0A 7A 00A A 0A 00A 0A 00A 0A 00A 600A # OF SETS () () () CONDUIT /" /" /" -/" -/" -/" -/" -/" -/" " " " -/" -/" " " -/" -/" -/" " NOTES:. FEEDER ID FOLLOWED BY THE SUFFIX "N" INDICATES NEUTRAL CONDUCTOR. PROVIDE ADDITIONAL NEUTRAL CONDUCTOR SIZED TO MATCH PHASE CONDUCTORS.. CONDUCTOR AMPACITY BASED ON NEC TABLE CONDUIT FILL BASED ON NEC ANNEX C, TABLE C. FOR THHN TYPE CONDUCTORS. CONTRACTOR SHALL PROVIDE ADUSTMENTS AS NECESSARY FOR OTHER CONDUCTOR TYPES.. CONTRACTOR MAY COMBINE BRANCH CIRCUITS IN COMMON RACEWAY UP TO SIX CURRENT CARRYING CONDUCTORS. ADUSTMENT FACTORS SHALL BE APPLIED PER NEC TABLE 0.(B)()(a).. MINIMUM CONDUIT SIZE FOR UNDERGROUND RACEWAY IS INCH. EACH () # () # () #0 ()#8 () #8 () #6 () #6 () # () # () # () # () # () # () #/0 () #/0 () #/0 () #/0 () #0 () #0 () #00 () #600 () #/0 () #0 () #0 GROUND # # #0 #0 #0 #0 #0 #0 #8 #8 #8 #8 #6 #6 #6 #6 # # # # # # # # CONDUIT SCHEDULE : NONE ID VOLTAGE CONDUIT WIRE QTY SIZE GND DESCRIPTION C-MS C-MS C-MS C-MS C-MS C-MS C-RP C-RP C-AS C-CS SCREEN # - SPRAY VALVE # SCREEN # - UNIT EMERAGENCY STOP SWITCH SCREEN # - MULTI-POINT ULTRASONIC LEVEL SWITCH & REDUNDANT HI FLOAT SCREEN # - SPRAY VALVE # SCREEN # - UNIT EMERAGENCY STOP SWITCH SCREEN # - MULTI-POINT ULTRASONIC LEVEL SWITCH & REDUNDANT HI FLOAT GAS MONITOR - # SIGNALS GAS MONITOR - # SIGNALS GAS MONTIOR - AIR FLOW SWITCH STATUS CLASSIFIER # - W SOLENOID VALVE COMMAND S-HH S-HH S-BL S-BL S-CL S-VC S-GM S-MS S-MS S-GP S-GP S-GP S-GP S-GP S-GP S-FM S-SM S-FM S-PH COMM " " () FACTORY 8 TSP 8 TSP 8 TSP 8 TSP 8 TSP 8 TSP 8 TSP CAT6 PLC - FIELD DEVICE DIGITAL STATUS PLC - FIELD DEVICE ANALOG STATUS SPARE GRIT BLOWER - RUNNING, FAULT, AUTO SIGNAL, AND START COMM. GRIT BLOWER - BLOWER SPEED FEEDBACK AND COMMAND GRIT BLOWER - HI AIR TEMP CLASSIFIER # - RUNNING, FAULT, START COMMAND CLASSIFIER # - SPEED FEEDBACK VENTILATION - LOSS OF AIR FLOW STATUS GAS MONITOR - HAZARDOUS GAS DETECTION GAS MONITOR - HAZARDOUS GAS READINGS SCREEN # - RUNNING, FAULT, EMER. STOP, REDUND. FLOAT, LEVEL SWITCH SCREEN # - RUNNING, FAULT, EMER. STOP, REDUND. FLOAT, LEVEL SWITCH GRIT PUMP # - RUNNING, FAULT, HAND, AUTO SIGNAL, AND START COMM. GRIT PUMP # - SEAL FAIL, OVER TEMP. GRIT PUMP # - CHECK VALVE STATUS GRIT PUMP # - RUNNING, FUALT, HAND, AUTO SIGNAL, AND START COMM. GRIT PUMP # - SEAL FAIL, OVER TEMP. GRIT PUMP # - CHECK VALVE STATUS INFLUENT FLOW METER - TOTALIZER PULSE INFLUENT FLOW METER - FLOW RATE INFLUENT SAMPLER - SAMPLE START COMMAND SIGNAL INFLUENT SAMPLER - FLOW PACE SIGNAL INFLUENT FLOW METER - FACTORY CABLES REQUIRED FOR MOUNT HEAD UNIT Ph/SALINITY ANALYZER - SIGNALS COMMUNICATION CABLE SIGNAL - CONDUIT SCHEDULE : NONE Tel: One Fifth Street, Ste 0 Fax: Wenatchee, WA /07/08 E. OB NUMBER 6 OF
CITY OF MOSES LAKE MUNICIPAL SERVICES DEPARTMENT EN GINEERING DIVISION
CITY OF MOSES LAKE MUNICIPAL SERVICES DEPARTMENT EN GINEERING DIVISION 321 South Balsam Street P.O. Box 1579 Mt)$es Lake, WA 98837 (509) 764-3183 WINONA LIFT STATION PROJECT- 2016 C.269 Bid Opening:, AUGUST
More informationPretest Module 24 Three-phase Service Entrance
Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?
More informationBID SPECIFICATIONS FOR (1) 300kW STANDBY GENERATOR
BID SPECIFICATIONS FOR (1) 300kW STANDBY GENERATOR Bid Specifications for 300 kw Standby Generator Compliance CITY OF GENEVA PUBLIC WORKS DEPARTMENT ENGINE In-Line Six Cylinder, turbocharged ATAAC aspirated,
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not
More informationBID SPECIFICATIONS 2018 TERMINAL BUILDING STANDBY GENERATOR PROJECT
BID SPECIFICATIONS 2018 TERMINAL BUILDING STANDBY GENERATOR PROJECT The County of Hancock, Maine is seeking bids from qualified firms for the purchase and installation of at least a 20KW backup generator
More informationA. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:
SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification
More informationAPPENDIX G PH NEUTRALIZATION SYSTEM TECHNICAL MEMORANDUM
APPENDIX G PH NEUTRALIZATION SYSTEM TECHNICAL MEMORANDUM BCM Construction Project No.: 151-205 ProDELTA Plus Continuous ph Neutralization System PDP-200-2-SC-G-B-T-AX-4-N4-LR-OCV 9/4/2015 Submitted for
More informationBackup Generation Application
Backup Generation Application For connection of non-parallel generation between Menard Electric Cooperative s Electric system and standby generation that will operate with a manual or automatic transfer
More information2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code
2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of
More informationLIFT STATION 11 ONE-LINE DIAGRAM
LAC JOB : 118-086 OSG-D-ELEC06.DWG LIFT STATION 11 ONE-LINE DIAGRAM DWG : SHEET : E15 33 47 NEW NEW GENERATOR PAD BOLLARD BOLLARD WETWELL ACCESS HATCH WETWELL OUTLINE HANDHOLE SEWER MANHOLE LIFT STATION
More information1 OF 8 LAD LAD PROJECT AREA KIMBERLY GERBER TITLE SHEET C.E.S. DWG. NO. NPN12045 SHEET INDEX
LAD05-9, CA 964 TITLE SHEET LAD05-9 SHEET INDEX 00 DEXTER AVE. SUITE 50 SEATTLE, WA 9809 PROJECT SUMMARY PROJECT DESCRIPTION COORDINATES LATITUDE: 33.678084 N LONGITUDE: -7.84858 W 0640 Sepulveda Blvd.
More informationAppendix C Capital Improvement Program Project Descriptions and Details
Appendix C Capital Improvement Program Project Descriptions and Details GIG HARBOR WW COMP PLAN DRAFT CAPITAL IMPROVEMENT PROGRAM LIFT STATION COST ESTIMATE Lift Station 1 Item Qty Units Unit Cost Extended
More informationThe City of Sturgis Wastewater Treatment Plant Septage Waste Receiving Facility Operating Plan
The City of Sturgis Wastewater Treatment Plant Septage Waste Receiving Facility Operating Plan Introduction/Purpose: The City of Sturgis Wastewater Treatment Plant is owned and operated by the City of
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationGenerator Fire Safety: Generator assemblies should be located outside the building.
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building
More informationAREA OF WORK ENERGY
THIS DOCUMENT CONTAINS PROPRIETARY 408-859-545 AREA OF WORK THIS DOCUMENT CONTAINS PROPRIETARY Chlorking Chlor-25SM Controllers Chlorking & CO-2 controlled by chemical controller 3 x Chlorking Cells, 25
More informationCOMMERCIAL QUICK REFERENCE
COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR
More informationRAS & WAS Pumps (FLYGT Pump)
RAS/WAS Pumping Pumping of sludge from the secondary clarifiers to the aeration tanks maintains active biomass in the aeration tanks This is referred to as return activated sludge (RAS) pumping RAS pumps
More information9. Non-Residential Services (Commercial, Industrial, and Agricultural)
Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect
More informationPermit for Charging Equipment Installation Electric Vehicle Supply Equipment (EVSE)
Permit for Charging Equipment Installation Electric Vehicle Supply Equipment (EVSE) Town of Lake George, New York Compliance with the following permit will allow the installation and operation of electric
More informationFLORIDA DEPARTMENT OF TRANSPORTATION
FLORIDA DEPARTMENT OF TRANSPORTATION ADDENDUM NO. 1 DATE: 3/8/2011 RE: BID/RFP #: RFP-DOT-10/11-9031-LG BID/RFP TITLE: FURNISH AND INSTALL EMERGENCY GENERATOR POWER SYSTEM AT CARYVILLE OPENING DATE: March
More informationFLORIDA GOVERNMENTAL UTILITY AUTHORITY (FGUA)
FLORIDA GOVERNMENTAL UTILITY AUTHORITY (FGUA) BID NO. GG P07; Rehabilitation of Treatment Unit No. 1, Golden Gate Wastewater Treatment Plant in the Golden Gate Utility System A. SCOPE Addendum No. 1 September
More informationWARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.
SECTION 230513 - MOTORS AND ADJUSTABLE SPEED DRIVES PART 1 - GENERAL 1.1 DESCRIPTION A. Provide labor, materials, equipment and services as required for the complete installation designed in Contract Documents.
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationAppendix Technical Memorandum PS-1 on Pumping Stations Condition Assessment
Appendix 4-28 Technical Memorandum PS-1 on Pumping Stations Condition Assessment TECHNICAL MEMORANDUM PS-1 March 8, 2013 To Copy to From Town of Falmouth, MA File; Project Team Nathan C. Weeks, P.E., BCEE
More informationLift Station Design Standards and Details. Summary of Revisions
Lift Station Design Standards and Details Summary of Revisions April 2017 Updates Standard Detail SLS 19 SUBMERSIBLE LIFT STATION GROUDING PLAN & S Removed Barbed Wire from FENCE GROUNDING. TYPICAL LIFT
More informationSECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2
SECTION 1. 600V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2 Soft Starters SECTION 2. LIQUID COOLED VFD I 3 Liquid Cooled
More informationME3H/ME3F SERIES. Automatic and manual models. Single phase power only 115 or 230 volt.
ME3H SUMP/EFFLUENT PUMP ME3F SUMP/EFFLUENT PUMP ME3H/ME3F SERIES SUBMERSIBLE SUMP AND EFFLUENT PUMPS INSTALLATION AND SERVICE MANUAL Automatic and manual models. Single phase power only 115 or 230 volt.
More informationMECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL
13686.00 MECHANICAL AND ELECTRICAL COORDINATION 230002-1 SECTION 230002 MECHANICAL AND ELECTRICAL COORDINATION 1.1 WORK INCLUDED PART 1 - GENERAL A. Work Included in This Section: Materials, equipment,
More informationSERVICE REQUIREMENTS COMMERCIAL & INDUSTRIAL CUSTOMERS
ENERGY SERVICES ENGINEERING 840 Northgate Drive Telephone (509) 942-7403 Fax (509) 942-7405 P.O. Box 190 Richland, WA 99352 www.ci.richland.wa.us SERVICE REQUIREMENTS COMMERCIAL & INDUSTRIAL CUSTOMERS
More informationISSUE DATE JANUARY 1st, 2008 SECTION 5C 240V 1PHASE W/TCU AND VFD
ISSUE DATE JANUARY 1st, 2008 SECTION 5C 240V 1PHASE W/TCU AND VFD CONTROL PANEL MOUNTING PAGE No. 74 NUMBER: LS-240V1PH-TCU-VFD 35 38 47 U A 9 33 V 26 24 25 41 43 7 7 44 ALUMINUM BACKPLATE 41 42 50 46
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationRAPIDMIX 400CW. Length of Machine (19.5m) Length when erected Width of Machine 9-10 (3.00 m) Width Same
Machinery Manufacturers to the Concrete Industry RAPIDMIX 400CW The Rapidmix 400CW has been designed to be totally mobile and completely self-contained with its own power source. It is also completely
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary
More informationGreen Building Technology
Green Building Technology Renewable Energy Sources and Design/Specification Guidelines Presented by: Kurt Uhlir & Brian Kustwin Why Renewables? Reduction of SO 2 and NOX along with greenhouse gases such
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More informationDiesel Engines for Fire Protection Applications
Cincinnati, Ohio USA - Glasgow, Scotland UK Diesel Engines for Fire Protection Applications Based on NFPA 20 2010 Edition www.clarkefire.com NFPA 20 Engine Type Diesel Engines for fire pump drive shall
More informationwww. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide
Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Retain for future use. 30072-450-47A July 2002 Raleigh, NC, USA HAZARDOUS VOLTAGE Read and understand
More informationBAC Custom Engineered Controls
BAC Custom Engineered Controls Product Detail Product Introduction......................................... K2 BAC Custom Engineered Controls Benefits....................................................
More informationADDENDUM NO. 1. This Addendum shall form part of the Contract Documents.
Date: January 4, 2018 To: Bidders for Rodney Pumping Station Upgrades Tender 173747 From: Muhannad Bagajati, R.V. Anderson Associates Ltd. mbagajati@rvanderson.com Subject: Addendum No. 1 ADDENDUM NO.
More informationQuick Start Guide TS 910
Quick Start Guide TS 910 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer is responsible
More informationA. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.
16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to
More informationC. System Design and Performance Requirements
Change History Date Description of Change Pages / Sections Modified 6/15/16 Updated division section from 16361-E-E to 26 10 03, removed references to other section numbers A. Summary - mgl44 Change Approver
More informationADDENDUM #2 TO BID # BID NUMBER: ISSUE DATE: Friday, January 18, 2019
Georgetown County, South Carolina 129 Screven Street, Suite 239 Post Office Drawer 421270 Georgetown, SC 29442-4200 (843) 545-3083 Fax (843) 545-3500 E-Mail purch@gtcounty.org Website http://www.gtcounty.org
More informationElectrical Design/Build Guide
2017 Electrical Design/Build Guide Based on the 2017 National Electrical Code Copyright Durand & Associates 1986-2016 60 C Copper Ampacity 4 - Wire Fill - (Non-Current Carrying Neutral) 4 or 5 - Parallel
More informationTRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES
TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC
More informationENGINEERING SPECIFICATION
December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References
More informationUltrasonic Two-Wire Point Level Control with Tip-Type Sensor
Ultrasonic Two-Wire Point Level Control with Tip-Type Sensor General Instructions The Ultrasonic Point Level Control produces an 8mA or l6ma current to indicate liquid presence/absence within a sensor
More informationMYERS MODELS 4VC & 4VCX
MYERS MODELS 4VC & 4VCX 4" SOLIDS HANDLING WASTEWATER PUMPS STANDARD (4VC) AND HAZARDOUS LOCATION (4VCX) CONSTRUCTION WWW.FEMYERS.COM MYERS MODELS 4VC & 4VCX Solids Handling Wastewater Pumps Cut Your Pumping
More informationIRRIGATION RENOVATION PROJECT Construction Documents
P 10-49 TOUCHET VALLEY GOLF COURSE AND FAIRGROUNDS Dayton, Washington IRRIGATION RENOVATION PROJECT Construction Documents NOVEMBER 2015 Sheet Layout COVER IR0.1 PROJECT SUMMARY IR1.0 GOLF IRRIGATION PLAN
More information10 Commercial, Industrial, Agricultural Services
10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three
More informationExisting 400A Circuit Breaker For B Secondary Chill Water Pump. Existing Single 2.5 Conduit. Reuse As Much As Practical
New A Secondary Chill / 60V /36A Fused Disconnect For A Secondary Chill and Flex New B Secondary Chill / 60V / 36A B Secondary Chill Single 2.5 Conduit. Install New Additional 2.5 R.S.G. Conduit From 00A
More informationWARREN COUNTY, N.Y. M/E REFERENCE
SECTION 262000 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 DESCRIPTION A. Provide a complete secondary distribution system as indicated on the Contract Documents and as specified herein. 1.2 QUALITY ASSURANCE
More informationNEC REQUIREMENTS FOR GENERATORS
PROFESSIONAL DEVELOPMENT SEMINAR SERIES NEC REQUIREMENTS FOR GENERATORS (Based on NEC 2005 with limited 2008 commentary) AIA certified Continuing Education Units (CEU) Available GPS-140 National Electric
More informationCITY OF WEST PALM BEACH
REVISION: OCT. 2018 SUBMERSIBLE LIFT STATION - WET WELL SECTION VIEW SLS-2 WETWELL DATA PUMP/ELECTRICAL DATA REVISION: OCT. 2018 SUBMERSIBLE LIFT STATION - REQUIRED DATA SLS-3 PUMP TEST / START-UP FORM
More informationQuick Start Guide TS 910 & TS 920
Quick Start Guide TS 910 & TS 920 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer
More informationCENTRIFUGAL CHILLER TECHNICAL DATA SHEET Job Name: Mt Healthy Junior Senior HS Date: 6/25/2009 Version: 06.12 Submitted By: Mary Wilking Unit Description: McQuay Model Number: WSC100MBJ72R/E4212-CE-3**/C3612-BLYY-2*****/R134-BAABM
More informationEMERGENCY GENERATOR SET
PART 8.1: EMERGENCY GENERATOR SET PART 1 - GENERAL I SCOPE A. This specification covers the design, furnishing, installation and start up of a factory built, production tested, operable, liquid cooled
More informationRESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS
SECTION VI SERVICE REQUIREMENTS This section discusses the requirements for establishing electric service to new residential subdivisions in Palo Alto. Subdivisions are normally constructed on dedicated
More informationSECTION ENCLOSED CONTROLLERS
SECTION 16420 ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationCHAPTER V RESIDENTIAL WIRING
CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this
More informationMODEL "454L" MOBILE HIGH PRODUCTION CENTRAL MIX PLANT
MODEL "454L" MOBILE HIGH PRODUCTION CENTRAL MIX PLANT AGGREGATE STORAGE AND BATCHING MODULE AGGREGATE STORAGE BIN 60 CUBIC YARD X THREE (3) COMPARTMENT AGGREGATE BIN EQUAL IN-LINE COMPARTMENTS SIX (6)
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to
More informationSECTION VARIABLE FREQUENCY DRIVE UNITS
SECTION 26 29 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide variable frequency drive (VFD) units, complete and operable, in accordance with the Contract Documents. It
More informationMYERS MODELS 6VC & 6VCX
MYERS MODELS 6VC & 6VCX 6" SOLIDS HANDLING WASTEWATER PUMPS STANDARD (6VC) AND HAZARDOUS LOCATION (6VCX) CONSTRUCTION WWW.FEMYERS.COM MYERS MODELS 6VC & 6VCX Solids Handling Wastewater Pumps High Operating
More informationPERMANENT RESIDENTIAL UNDERGROUND SERVICE
CITY OF RICHLAND ENERGY SERVICES DEPARTMENT 505 Swift Boulevard, MS-21 Richland, WA 99352 Telephone (509) 942-7403 Fax (509) 942-7405 PERMANENT RESIDENTIAL UNDERGROUND SERVICE A. INTRODUCTION This guide
More informationStandards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.
FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared
More informationMATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****
Page 1 of 8 ****Supercedes BECo Standard E2.12-2.14 and ComElectric Spec 7-0895**** THREE-PHASE DEADFRONT PAD-MOUNTED DISTRIBUTION TRANSFORMERS, LOOP & RADIAL FEED DESIGNS 1.0 General Requirements 1.1
More informationUNDERGROUND SERVICES - SECONDARY
UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service
More informationMYERS MODELS 4V AND 4VX
MYERS MODELS 4V AND 4VX SOLIDS HANDLING WASTEWATER PUMPS STANDARD (4V) AND HAZARDOUS LOCATION (4VX) CONSTRUCTION WWW.FEMYERS.COM MYERS MODELS 4V AND 4VX Solids Handling Wastewater Pumps The Right Choice
More information90.2 Scope. The installation of electrical conductors, equipment and raceways for:
NEC Generator Primer Rules on the installation of generators and transfer switches 1 90.2 Scope The installation of electrical conductors, equipment and raceways for: public and private premises Conductors
More informationEarthsafe Systems, Inc. Emergency Power Fuel Systems Recommended System Standard
Copyright 2008 Earthsafe Systems, Inc. This information is provided to consulting engineers and prospective customers for the purpose of specifying Earthsafe Emergency Power Fuel Systems. Reproduction
More informationTEMPORARY ELECTRICAL SERVICE
ENERGY SERVICES ENGINEERING 840 Northgate Drive Telephone (509) 942-7403 Fax (509) 942-7405 P.O. Box 190 Richland, WA 99352 www.ci.richland.wa.us/energyservices TEMPORARY ELECTRICAL SERVICE A. INTRODUCTION
More informationFULLY MOBILE, - TRACK MOUNTED, SELF CONTAINED, FULLY WEIGHED HIGH VOLUME MIXING PLANT
Specification 250 FULLY MOBILE, - TRACK MOUNTED, SELF CONTAINED, FULLY WEIGHED HIGH VOLUME MIXING PLANT The Trakmix 250 has been designed to be totally mobile and completely self-contained with its own
More informationPUBLIC WORKS AND SERVICES PETROLEUM PRODUCTS DIVISION STANDARD DETAILED DRAWINGS FOR NORTHERN FUEL STORAGE AND DISTRIBUTION FACILITIES
PUBLIC WORKS AND SERVICES PETROLEUM PRODUCTS DIVISION STANDARD DETAILED DRAWINGS FOR NORTHERN FUEL STORAGE AND DISTRIBUTION FACILITIES 3rd EDITION - 01/2006 Foreword This publication, together with the
More informationAPPENDIX B FUNCTIONAL DESIGN SPECIFICATIONS (Sequence of Operation)
APPENDIX B FUNCTIONAL DESIGN SPECIFICATIONS (Sequence of Operation) B.1 WATER SUPPLY FACILITIES 1. General A. The tag number of the equipment comprise three designations (W10 CM 01), where the three designations
More informationATTACHMENT I BID SCHEDULE IFB NO , CHURCH FARMS EAST STORAGE TANK AND BOOSTER PUMP STATION
ATTACHMENT I BID SCHEDULE IFB NO. 19-021, CHURCH FARMS EAST STORAGE TANK AND BOOSTER PUMP STATION Item No. Description Qty Unit Unit Cost Amount Pump Station Site Work 1 Site Demolition / Removals / Haul
More informationRAPIDMIX 600C CHASSIS
Machinery Manufacturers to the Concrete Industry RAPIDMIX 600C The Rapid Mix 600C has been designed to be totally mobile and completely self-contained with its own power source. It is also completely self
More informationGCG ASSOCIATES, INC. PROFESSIONAL CIVIL ENGINEERS AND LAND SURVEYORS 84 Main Street Wilmington, Massachusetts 01887
GCG ASSOCIATES, INC. PROFESSIONAL CIVIL ENGINEERS AND LAND SURVEYORS 84 Main Street Wilmington, Massachusetts 01887 Phone: (978) 657-9714 Fax: (978) 657-7915 December 31,2.012 Mr. Charles Aspinwall Town
More informationEast Central College
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Wall switches. b. Receptacles c. Device plates and decorative box covers. 1.2 RELATED
More informationRequirements for Secondary Voltage Revenue Metering (750 V and less)
Requirements for Secondary Voltage Revenue Metering (750 V and less) To view the latest revision of this document go to: http://www.bchydro.com/ext/metering/ January 28, 2010 Copyright 2008 by BC Hydro.
More informationUltrasonic Two-Wire Point Level Control
Ultrasonic Two-Wire Point Level Control General Instructions The Ultrasonic Point Level Control indicates liquid presence/absence within a sensor cavity. Two piezoelectric crystals face each other across
More informationOutdoor Power Transmission & Distribution
Description: The purpose of the section is to highlight the current applicable UMCP Design Standards and requirements for Outdoor Power Transmission and Distribution, including but not limited to the following:
More informationZERO EMISSION in the School Zone. The affordable no-idle solution
ZERO EMISSION in the School Zone The affordable no-idle solution Rev 5 2/5/18 ZERO EMISSION in the School Zone Why Improve School Zone Air Quality? The US Environmental Protection Agency (EPA) maintains
More informationMulti-Institutional Academic Health Science & Research Center Evansville, IN
SECTION 263213 - ENGINE GENERATORS PART 1 - GENERAL 1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSpecial Specification 6058 Battery Back-Up System for Signal Cabinets
Special Specification Battery Back-Up System for Signal Cabinets 1. DESCRIPTION 2. DEFINITIONS Install a Battery Back-Up System (BBU System) for traffic signals that will provide reliable emergency power
More informationALTERNATOR STARTUP Turning gear to full operation. Procedure initiated by:. 7/03 Before starting procedure, remove all check marks.
ALTERNATOR STARTUP Turning gear to full operation. Procedure initiated by:. 7/03 Before starting procedure, remove all check marks. 1. Check log book for incomplete compliance for further operation. 2.
More informationUNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK
UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK 5 October 2017 John A. Weber Principal Electrical Engineer, Hartford Steam Boiler Inspection and Insurance Company Electrical Power Transmission
More informationInstallation, Maintenance, and Operation Manual
GTX TM UNIT SUBSTATION Installation, Maintenance, and Operation Manual Rev.3 03-10-15 Marina Electrical Equipment, Inc. 100 Warwick Court Williamsburg, VA 23185 Toll Free: 1-855-258-3939 Fax: 1-757-258-3988
More informationCorrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections
Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of
More information.3 Section Waste Management and Disposal.
Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section
More informationBAS Construction Checklist
BAS Construction Checklist Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing. The checklist items
More informationZG 521 Padvault Three-Phase Transformer
E n g in e e r :R.An th o n Ap p r o v e r :Jo s h u a Jo n e s 2 0 De c 1 7 2 0 De c 1 7 ZG 521 Padvault Three-Phase Transformer ZG 521 Padvault Three-Phase Transformer 1. Scope This material specification
More informationCommercial Electric Policy
Commercial Electric Policy 7/19/16 1 Table of Contents General Information..3 Construction.3 Ownership.4 Multi-Unit/Multi-Service Buildings....4 Secondary Termination Enclosures.4 Meter Bases.5 Temporary
More informationWhat's New with UL508A Codes & Standards Presented by Jeff Woolfolk Manufacturing in America March 14-15, 2018
What's New with UL508A Codes & Standards Presented by Jeff Woolfolk Manufacturing in America March 14-15, 2018 Before we start A Penny for Your Thoughts At the end of the session, share your feedback via
More informationGP7RD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Air Conditioner, Single Phase WARRANTY
TECHNICAL SPECIFICATIONS GP7RD Series Single Packaged Air Conditioner, Single Phase GP7RD 13 SEER, R-410A 2 thru 4 Ton Units Cooling: 24,000 to 47,000 Btuh The GP7 Series single packaged air conditioners
More informationSecondary Digester Cleaning to Meet Ohio Sludge Rules. Timothy McCann AECOM Keith Bovard Rocky River WWTP
Timothy McCann AECOM Keith Bovard Rocky River WWTP Agenda Rocky River WWTP Background Ohio Sludge Rules EPA Request for Alternative Digester Cleaning Project Page 2 Rocky River WWTP Background and History
More informationManaging Electric Vehicle Supply Equipment (EVSE) Installations
Managing Electric Vehicle Supply Equipment (EVSE) Installations Introduction to Electric Vehicle EVSE Electric vehicles create a need to build an infrastructure that will supply the added load of charging.
More information.3 Section Concrete Forms and Accessories: Installation of Anchor Devices, Setting Templates
Issued 2005/06/01 Section 16239 Power Generation to 30 kw Page 1 of 7 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01355 Waste Management and Disposal..2 Section 01810 Commissioning..3 Section 03100 Concrete
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL
SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More information