ADDENDUM #2 TO BID # BID NUMBER: ISSUE DATE: Friday, January 18, 2019

Size: px
Start display at page:

Download "ADDENDUM #2 TO BID # BID NUMBER: ISSUE DATE: Friday, January 18, 2019"

Transcription

1 Georgetown County, South Carolina 129 Screven Street, Suite 239 Post Office Drawer Georgetown, SC (843) Fax (843) Website ADDENDUM #2 TO BID # BID NUMBER: ISSUE DATE: Friday, January 18, 2019 OPENING DATE: Wednesday, January 23, 2019 OPENING TIME: 3:00 PM (Eastern NIST) Bid Opening Location: Georgetown County Courthouse, Suite #239, (Purchasing Conference Room) Pre-Bid Conference/Site Inspection: Voluntary-By Prior Appointment PROCUREMENT FOR: Emergency Generator Replacement at Georgetown County Landfill Commodity Code(s): 28539, This addendum will amend Bid #18-085, Emergency Generator Replacement at Georgetown County Landfill originally issued on Friday, January 4, This clarification is being provided to all known and registered correspondents in response to questions received. All addenda and original bid documents are also available online at: select Quick Links, Bid Opportunities and Current Bids. Question 1: I wanted to submit the attached informational submittal for confirmation that Caterpillar would be considered an approved equal for this project. I have several contractors asking me for pricing, if you can advise once the information is reviewed. Yes, we will accept the Caterpillar Diesel powered engine as equivalent. Question 2: The specifications do not call for a Service Entrance rated transfer switch, however, the drawing does not show a disconnect between the meter and the transfer switch. Will you be providing a disconnect before the transfer switch, or will the transfer switch need to be service entrance rated? The transfers switch will need to be service entrance rated. By code, there must be a means of disconnect at the service entrance (meter) of a building. If the transfer switch is fed directly from the meter, it must be service entrance rated (meaning, it will have a service disconnect breaker integrated in the switch gear). If it is not a service entrance rated transfer switch, then there must be a service disconnect (breaker or fused) between the meter and the transfer switch.

2 Question 3: In the proposed Power Riser diagram, it does not show the new generator feeding the new Environmental Services Administration Building. Will this building need to be backed up by the generator as well as the Scale House? And if this building also needs to be fed from the new generator, the Proposed Riser Diagram does not show a sub-panel after the transfer switch to feed the (2) different loads. Yes the NEW Environmental Services Administration Building as well as the Scale house will be hooked to the generator. The Current Administration building is NOT to be connected to this generator. See attached for revised Proposed Riser Diagram. Question 4: For the Scale House, will we be reusing the existing feeders between the generator and the scale house, or will the feeders need to be replaced? Use the existing feeders between the generator and the scale house. Question 5: There is currently a pole that feeds the Admin Building. Will there be a new feed from the existing pole or pedestal to our 200 amp meter already installed? Is everything going to be installed by others up to the meter prior to this project starting? Yes, everything up to the meter is already installed. Question 6: It states that County is providing the Pedestal and conduit from the Pedestal to the Admin Building. Please confirm this also means the County is having that conduit installed by others prior to the start of this project. The Proposed Power Riser Diagram does not show the Admin Building being included in this scope. Yes, the conduit is installed by others prior to the project start. The New Admin Building (under construction) is to be connected to the Generator (the old/current building will not be connected, that building is being removed). Question 7: The Scale house is fed from a different pole than the existing generator. Do we need to demolish this and do away with the existing meter? The contractor does not need to do anything with the existing pole or meter. Question 8: If we are not able to remove the existing conductors or pull back a conduit piston/rat. Will a change order be allowed to replace the entire amount of conduit in the damaged run? We do not see the need to remove the existing conductors at this time. Question 9: Out of the two buildings one will not work without two transfer switches. You can leave the scale house on manual and the office on an auto transfer switch.

3 We do not believe this is accurate, we have a 150 amp breaker on the pedestal to feed the scale house from the automatic transfer switch. [THE REMAINDER OF THIS PAGE IS INTENTIONALLY LEFT BLANK]

4 GEORGETOWN COUNTY ENVIRONMENTAL SERVICES OFFICE & WEIGHT STATION 60 KW DIESEL STANDBY GENERATOR - 120/208 VOLT DELTA 200 AMP - NEMA 3R AUTOMATIC TRANSFER SWITCH (ATS) 200 AMP, 3 PHASE, 4 WIRE SERVICE ENTRANCE ALL A.C. POWER WIRING - COPPER CONDUCTORS ALL D.C. CONTROLS - STRANDED COPPER CONDUCTORS EXISTING POWER RISER 75 kva Utility XFMR 120/240 D S.E.C METER 320 AMP MANUAL TRANSFER SWITCH DPDT OFFICE MAIN PANEL 200 AMP 120/240 1 PH 60 KW DIESEL GENERATOR 120/240 VD SCALE MAIN PANEL 200 AMP 120/240 1 PH (REVISED) PROPOSED POWER RISER UPDATE S.E.C METER 200 AMP 3PH (already Installed) AUTOMATIC TRANSFER SWITCH 200 AMP 60 KW DIESEL GENERATOR 120/208 VD 3PH SCALE HOUSE DISCONNECT 150AMP 1 PH ADMIN Building MAIN PANEL 200 AMP 120/240 3 PH (installed already by county)

5 Schematic Diagram (not to scale) Existing Power Generator Meter Pedestal Manual Transfer Scalehouse Admin Building

6 Schematic Diagram (not to scale) Proposed Power Junction Meter Automatic Transfer Generator Pedestal 150 disconnect New Admin Building 200 amp (existing) Scalehouse

7 ADDENDUM ACKNOWLEDGEMENT Bid # Emergency Generator Replacement at Georgetown County Landfill Mandatory Submittal Form To be returned with the final proposal submission to Georgetown County. COMPANY NAME: Addendum #1 Received Date: Addendum #2 Received Date: Addendum #3 Received Date: Addendum #4 Received Date: Addendum #5 Received Date: Addendum #6 Received Date: If your Bid submission has already been mailed, acknowledgment may be provided by faxing this form to (843) , or attaching a digital scan and sending by . [THE REMAINDER OF THIS PAGE IS INTENTIONALLY LEFT BLANK]

County of Georgetown, South Carolina

County of Georgetown, South Carolina County of Georgetown, South Carolina 129 Screven Street, Suite 239 Georgetown, SC 29440-3641 Post Office Box 421270, Georgetown, SC 29442-4200 (843)545-3082 Fax (843)545-3500 purch@gtcounty.org ADDENDUM

More information

Page 1 of 6 ADDENDUM NO. 1. January 11, Shuttle Bus Service RFP # H General

Page 1 of 6 ADDENDUM NO. 1. January 11, Shuttle Bus Service RFP # H General ADDENDUM NO. 1 January 11, 2018 Shuttle Bus Service RFP # H18-0002 1. This addendum revises RFP documents. This addendum is issued to respondents of record prior to execution of contract, and forms a part

More information

South Dock Replacement Prescott Park. This addendum forms part of the original document marked: Bid#44-14 South Dock Replacement Prescott Park.

South Dock Replacement Prescott Park. This addendum forms part of the original document marked: Bid#44-14 South Dock Replacement Prescott Park. City of Portsmouth Public Works Department June 27, 2014 Addendum #3 Bid #44-14 South Dock Replacement Prescott Park This addendum forms part of the original document marked: Bid#44-14 South Dock Replacement

More information

BID SPECIFICATIONS 2018 TERMINAL BUILDING STANDBY GENERATOR PROJECT

BID SPECIFICATIONS 2018 TERMINAL BUILDING STANDBY GENERATOR PROJECT BID SPECIFICATIONS 2018 TERMINAL BUILDING STANDBY GENERATOR PROJECT The County of Hancock, Maine is seeking bids from qualified firms for the purchase and installation of at least a 20KW backup generator

More information

ADDENDUM No. 1 Prospective Bidders

ADDENDUM No. 1 Prospective Bidders Page 1 of 1 Attachment to Addendum # 1 Revised Itemized Bid ADDENDUM No. 1 TO: Prospective Bidders FROM: Gregory Tate, Construction Contracts Administrator DATE: January 24, 2019 PROJECT: Traffic Signal

More information

ADVANCED CALCULATIONS

ADVANCED CALCULATIONS ADVANCED CALCULATIONS 101. Why is it permissible in some cases to fuse a #14 AWG motor conductor with a 60 amp breaker when normally a #14 AWG should only be fused at 15 amps? a) the motor can't start

More information

Eagle Mountain-Saginaw Independent School District REQUEST FOR COMPETITIVE SEALED PROPOSALS (RFCSP)

Eagle Mountain-Saginaw Independent School District REQUEST FOR COMPETITIVE SEALED PROPOSALS (RFCSP) Eagle Mountain-Saginaw Independent School District REQUEST FOR COMPETITIVE SEALED PROPOSALS (RFCSP) RFCSP Number: 1718-005-2023 RFCSP Title: Cabling Infrastructure Job Order Contract Due Date: February

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

ADDENDUM NO. THREE (3) INSTALL BACKUP GENERATOR TERMINAL BUILDING SALISBURY-OCEAN CITY: WICOMICO REGIONAL AIRPORT SALISBURY, MARYLAND

ADDENDUM NO. THREE (3) INSTALL BACKUP GENERATOR TERMINAL BUILDING SALISBURY-OCEAN CITY: WICOMICO REGIONAL AIRPORT SALISBURY, MARYLAND ADDENDUM NO. THREE (3) INSTALL BACKUP GENERATOR TERMINAL BUILDING SALISBURY, MARYLAND Delta Project No. 15065 MARCH 15, 2017 From: To: Delta Airport Consultants, Inc. 9711 Farrar Court, Suite 100 Richmond,

More information

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location.

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. UNDERGROUND SERVICE No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. Entrance cabinet must be directly through wall or directly under meter in basement.

More information

Customer Requirements Downtown Secondary Network Service

Customer Requirements Downtown Secondary Network Service Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard

More information

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of

More information

Solar Power Installation Application

Solar Power Installation Application Solar Power Installation Application This Form must be filled out and submitted to Logan City Light and Power Department and given authorization to proceed PRIOR to installing a solar system. Also, please

More information

Pretest Module 24 Three-phase Service Entrance

Pretest Module 24 Three-phase Service Entrance Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?

More information

EDS FUSE RATINGS AT DISTRIBUTION SUBSTATIONS

EDS FUSE RATINGS AT DISTRIBUTION SUBSTATIONS Document Number: EDS 05-4001 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 05-4001 FUSE RATINGS AT DISTRIBUTION SUBSTATIONS EPN, LPN, SPN This design standard details the HV and LV fuse ratings

More information

THE CARMONY BUILDING ELECTRICAL SYMBOLS AND ABBREVIATIONS NOT ALL SYMBOLS, DEVICES OR ABBREVIATIONS MAY BE USED ELECTRICAL SYMBOLS AND ABBREVIATIONS

THE CARMONY BUILDING ELECTRICAL SYMBOLS AND ABBREVIATIONS NOT ALL SYMBOLS, DEVICES OR ABBREVIATIONS MAY BE USED ELECTRICAL SYMBOLS AND ABBREVIATIONS LIGHTING ELECTRICAL SYMBOLS AND ABBREVIATIONS ABBREVIATIONS ELECTRICAL GENERAL NOTES EQUIPMENT POWER DEVICES NOT ALL SYMBOLS, DEVICES OR ABBREVIATIONS MAY BE USED LINE TYPE LEGEND CIRCUITS TELECOMMUNICATION

More information

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location.

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. UNDERGROUND SERVICE No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. Entrance cabinet must be directly through wall or directly under meter in basement.

More information

Australian Wiring Instructions:

Australian Wiring Instructions: Australian Wiring Instructions: Generator/Switch Wiring: Remove the generator controller fascia and identify wire #44 going to the circuit breaker in the external connection box, this wire is the active

More information

Customer Name : Account Number: Customer Service Address (Street, City, State, ZIP Code): Customer Mailing Address: Customer Telephone Number:

Customer Name : Account Number: Customer Service Address (Street, City, State, ZIP Code): Customer Mailing Address: Customer Telephone Number: Please print the following information. Interconnect Customer Information Customer Name : Account Number: Customer Service Address (Street, City, State, ZIP Code): Customer Mailing Address: Customer Telephone

More information

University of California, San Diego Cal (IT) 2 Technical Assignment #2. Brian Smith

University of California, San Diego Cal (IT) 2 Technical Assignment #2. Brian Smith University of California, San Diego Cal (IT) 2 Technical Assignment #2 Brian Smith Advisor: Dr. Moeck 31 October 2005 Brian Smith Lighting/Electrical Option University of California, San Diego Cal (IT)

More information

1. Do the two Gillig 40 (2401H & 2402H) Hybrid have batteries, if so, what type? IPTC Response: Yes, I believe phosphate.

1. Do the two Gillig 40 (2401H & 2402H) Hybrid have batteries, if so, what type? IPTC Response: Yes, I believe phosphate. October 6, 2017 To: All Vendors of Record Re: Addendum #1 All vendors are to accept the information contained herein as the official response of IPTC. TO ALL BIDDERS OF RECORD AND TO WHOM IT MAY CONCERN:

More information

BID SPECIFICATIONS FOR (1) 300kW STANDBY GENERATOR

BID SPECIFICATIONS FOR (1) 300kW STANDBY GENERATOR BID SPECIFICATIONS FOR (1) 300kW STANDBY GENERATOR Bid Specifications for 300 kw Standby Generator Compliance CITY OF GENEVA PUBLIC WORKS DEPARTMENT ENGINE In-Line Six Cylinder, turbocharged ATAAC aspirated,

More information

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally.

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally. This page left blank intentionally. 38 Chapter 4: Commercial Metering / January 2011 APPENDIX Glossary Approval Acceptable to the authority having jurisdiction. Associated equipment As related to metering

More information

CITY OF SIDNEY EXECUTIVE ORDER COURTHOUSE SQUARE ELECTRICAL HOOKUP STANDARDS

CITY OF SIDNEY EXECUTIVE ORDER COURTHOUSE SQUARE ELECTRICAL HOOKUP STANDARDS CITY OF SIDNEY EXECUTIVE ORDER TITLE: ISSUE BY: COURTHOUSE SQUARE ELECTRICAL HOOKUP STANDARDS Steven B. Stilwell, City Manager EFFECTIVE DATE: January 1, 2004 PURPOSE The purpose of this policy is to provide

More information

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.

More information

INVITATION TO BID (ITB)

INVITATION TO BID (ITB) INVITATION TO BID (ITB) WHITFIELD COUNTY, GEORGIA ITB# PW-100-4-200-TSS-2019 73 HP TRACK SKID STEER Date: JANUARY 31st 2019 Time: 2:00 PM BRIAN MCBRAYER STAFF ACCOUNTANT (706) 275-7504 / (706) 275-7501

More information

ADDENDUM NO. 1 INVITATION FOR BID FOR BUS ENGINE SUPPLY. IFB NO: 2018-FP-08 Date Issued: August 6, 2018

ADDENDUM NO. 1 INVITATION FOR BID FOR BUS ENGINE SUPPLY. IFB NO: 2018-FP-08 Date Issued: August 6, 2018 602 N. Staples, Corpus Christi, Texas 78401 p. 361-289-2712 f. 361-903-3578 www.ccrta.org ADDENDUM NO. 1 INVITATION FOR BID FOR BUS ENGINE SUPPLY IFB NO: 2018-FP-08 Date Issued: August 6, 2018 INSTRUCTIONS:

More information

The Green Meter Adapter (GMA) program will become effective on January 15, Customers may start applying for a GMA on January 15, 2018.

The Green Meter Adapter (GMA) program will become effective on January 15, Customers may start applying for a GMA on January 15, 2018. SUMMARY This bulletin introduces a new PG&E program that allows the installation of an electric meter socket adapter that will accept a wired connection directly from a residential customer s Photo Voltaic

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary

More information

LIFT STATION 11 ONE-LINE DIAGRAM

LIFT STATION 11 ONE-LINE DIAGRAM LAC JOB : 118-086 OSG-D-ELEC06.DWG LIFT STATION 11 ONE-LINE DIAGRAM DWG : SHEET : E15 33 47 NEW NEW GENERATOR PAD BOLLARD BOLLARD WETWELL ACCESS HATCH WETWELL OUTLINE HANDHOLE SEWER MANHOLE LIFT STATION

More information

ENGINEERING SPECIFICATION

ENGINEERING SPECIFICATION December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References

More information

Central Florida Regional Transportation Authority d.b.a.

Central Florida Regional Transportation Authority d.b.a. Central Florida Regional Transportation Authority d.b.a. 455 N. Garland Avenue Orlando, FL 32801 AMENDMENT OF SOLICITATION 1. AMENDMENT NO: 2. SOLICITATION NO: 3. SOLICITATION DATE: 4. EFFECTIVE DATE:

More information

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code 2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of

More information

Notice is hereby given of the following changes and questions and answers to the above referenced Bid:

Notice is hereby given of the following changes and questions and answers to the above referenced Bid: FLORIDA DEPARTMENT OF TRANSPORTATION Procurement Office Joyce Plummer Joyce.plummer@dot.state.fl.us 605 Suwannee Street, MS 20 Tallahassee, Florida 32399-0450 Phone: (850) 414-4568 ADDENDUM NO. 3 DATE:

More information

ECS CONNECTION OF LARGE LV SERVICES TO SECONDARY DISTRIBUTION SUBSTATIONS

ECS CONNECTION OF LARGE LV SERVICES TO SECONDARY DISTRIBUTION SUBSTATIONS Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 03-0054 CONNECTION OF LARGE LV SERVICES TO SECONDARY DISTRIBUTION SUBSTATIONS EPN, LPN, SPN This standard details the procedures to be undertaken

More information

ADDENDUM No. 2. Bid #: 13-B-016 Purchase of Solid Waste Trucks

ADDENDUM No. 2. Bid #: 13-B-016 Purchase of Solid Waste Trucks City of Titusville Purchasing & Contracting Administration 555 S. Washington Avenue Titusville, FL 32796 Phone 321.383.5767 Facsimile 321.383.5628 ADDENDUM No. 2 May 15, 2013 Bid #: 13-B-016 To All Bidders:

More information

ADDENDUM NO.1 IFB NO.V-1821 CUTAWAY BUS. July 3, 2018

ADDENDUM NO.1 IFB NO.V-1821 CUTAWAY BUS. July 3, 2018 ADDENDUM NO.1 IFB NO.V-1821 CUTAWAY BUS July 3, 2018 Dear Prospective Bidders: The purpose of this addendum is to answer questions for and revise the above referenced Invitation for Bids (IFB). The following

More information

FLORIDA DEPARTMENT OF TRANSPORTATION

FLORIDA DEPARTMENT OF TRANSPORTATION FLORIDA DEPARTMENT OF TRANSPORTATION ADDENDUM NO. 1 DATE: 3/8/2011 RE: BID/RFP #: RFP-DOT-10/11-9031-LG BID/RFP TITLE: FURNISH AND INSTALL EMERGENCY GENERATOR POWER SYSTEM AT CARYVILLE OPENING DATE: March

More information

Purchasing Services 4202 East Fowler Avenue, SVC 1073 Tampa, Florida (813) Addendum No. 1

Purchasing Services 4202 East Fowler Avenue, SVC 1073 Tampa, Florida (813) Addendum No. 1 Purchasing Services 4202 East Fowler Avenue, SVC 1073 Tampa, Florida 33620 (813) 974-2481 Invitation to Bid No.: 18-12-YH Entitled: Opening Date: Bulk Fuel Delivery (PATS) November 14, 2017 at 3:00 p.m.

More information

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016 DISTRIBUTED GENERATION CHAPTER 5 500. SCOPE This chapter includes distributed or customer-owned generation connected in parallel and operating with Alliant Energy s electric distribution system. For all

More information

CONTENTS BY CHAPTER. Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES

CONTENTS BY CHAPTER. Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES CONTENTS BY CHAPTER Chapter 1: GENERAL INFORMATION Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES Chapter 3: SERVICE ENTRANCES Chapter 4: METERING INSTALLATION Chapter 5: CUSTOMER-INSTALLED SERVICE

More information

Technical Specification for Pole Mounted Capacitor Rack

Technical Specification for Pole Mounted Capacitor Rack Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to

More information

UTILITY CROSSING DETAIL

UTILITY CROSSING DETAIL 6" OF CSBC COMPACTED TO A FIRM AND UNYIELDING CONDITION. NOTE: - SILT FENCE SHALL CONFORM TO 8-01.3(9)A - SILT FENCES SHALL BE INSTALLED ALONG CONTOUR WHENEVER POSSIBLE. - POST SPACING MAY BE INCREASED

More information

ANZI Transfer Switch and Generator Wiring Installation Addendum

ANZI Transfer Switch and Generator Wiring Installation Addendum ANZI Transfer Switch and Generator Wiring Installation Addendum Reference all appropriate documentation. NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS. THIS PRODUCT CAN BE INSTALLED BY THE

More information

HORRY COUNTY SOLID WASTE AUTHORITY, INC.

HORRY COUNTY SOLID WASTE AUTHORITY, INC. HORRY COUNTY SOLID WASTE AUTHORITY, INC. The Horry County Solid Waste Authority, Inc. is requesting sealed proposals from qualified firms to provide a turnkey service for the collection of household hazardous

More information

(ADDENDUM COVER SHEET)

(ADDENDUM COVER SHEET) (ADDENDUM COVER SHEET) TO ALL PROSPECTIVE BIDDERS: PLEASE NOTE THE FOLLOWING CHANGES: PURCHASING DIVISION BOARD OF COUNTY COMMISSIONERS BROWARD COUNTY, FLORIDA A D D E N D U M NO. 1 DUMP TRUCK (NON-SHELTERED

More information

INVITATION TO BID (ITB)

INVITATION TO BID (ITB) INVITATION TO BID (ITB) WHITFIELD COUNTY, GEORGIA ITB# PW-100-4-200-SPB-2019 Self- Propelled Broom front mounted Date: JANUARY 31st 2019 Time: 2:00 PM BRIAN MCBRAYER STAFF ACCOUNTANT (706) 275-7504 / (706)

More information

Solar PV Standard Plan Simplified Microinverter and ACM Systems for Oneand Two-Family Dwellings

Solar PV Standard Plan Simplified Microinverter and ACM Systems for Oneand Two-Family Dwellings County of Santa Barbara Your City logo here Solar Standard Plan Simplified Microinverter and M Systems for Oneand Two-Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

Electric Vehicle Charging Station Article California Electrical code (CEC) General Requirements:

Electric Vehicle Charging Station Article California Electrical code (CEC) General Requirements: Checklist for Multi-Family Residential Electric Vehicle Charging Station Article 625 2016 California Electrical code (CEC) General Requirements: Level 1 Charger: 110V dedicated 20 amp circuit No electrical

More information

PURCHASING DEPARTMENT

PURCHASING DEPARTMENT PURCHASING DEPARTMENT TWELVE EAST 4 TH AVENUE, SUITE 106 ROME, GEORGIA 30161 PHONE: 706.291.5118 FAX: 706.290.6099 www.romefloyd.com Date: 7/26/2016 To: To Whom It May Concern Request for Quote: 16-0808

More information

TEMPORARY SERVICE TABLE OF CONTENTS PUD SERVICE TERRITORY AND CONTACTS CHAPTER ONE - INTRODUCTION CHAPTER TWO - TEMPORARY OVERHEAD SERVICE

TEMPORARY SERVICE TABLE OF CONTENTS PUD SERVICE TERRITORY AND CONTACTS CHAPTER ONE - INTRODUCTION CHAPTER TWO - TEMPORARY OVERHEAD SERVICE Electrical Service Requirements TEMPORARY SERVICE TABLE OF CONTENTS PUD SERVICE TERRITORY AND CONTACTS CHAPTER ONE - INTRODUCTION Inspections and codes Underground Utility locates Meter socket requirements

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

New Panelboard for Lot H, EV Charger Energization, Las Positas College. Scope of Work and Technical Specifications

New Panelboard for Lot H, EV Charger Energization, Las Positas College. Scope of Work and Technical Specifications CHABOT-LAS POSITAS COMMUNITY COLLEGE DISTRICT New Panelboard for Lot H, EV Charger Energization, Las Positas College Scope of Work and Technical Specifications Chabot-Las Positas Community College District

More information

Quik-Spec Coordination Panelboard Specifications

Quik-Spec Coordination Panelboard Specifications Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY

More information

STAUNTON CITY SCHOOL BOARD STAUNTON, VIRGINIA

STAUNTON CITY SCHOOL BOARD STAUNTON, VIRGINIA STAUNTON CITY SCHOOL BOARD STAUNTON, VIRGINIA REQUEST FOR PROPOSALS FOR DIMMING SYSTEM & CONTROL UPGRADE February 27, 2009 GENERAL INFORMATION Proposal Staunton City Schools is seeking proposals from qualified

More information

Please Refer to Attached Sample Form

Please Refer to Attached Sample Form Pacific Gas and Electric Company San Francisco, California U 39 Revised Cal. P.U.C. Sheet No. 32105-E Cancelling Revised Cal. P.U.C. Sheet No. 28313-E Electric Sample Form No. 62-0686 Application for Service

More information

Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)

Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less) Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less) Interconnection Customer Contact Information Name Alternative Contact Information (if different

More information

Washoe County PLAN SUBMITTAL

Washoe County PLAN SUBMITTAL Washoe County PLAN SUBMITTAL Washoe County PLAN SUBMITTAL Solar Photo Voltaic Systems Electrical Generation Systems December 2013 Washoe County Permits Plus Zone 1001 East Ninth Street PO Box 11130 Reno,

More information

District-Wide Prop 39, Interior LED Lighting Upgrades Pre-Conference Meeting Re-Bid No January 9 at 10:00 AM Las Positas College

District-Wide Prop 39, Interior LED Lighting Upgrades Pre-Conference Meeting Re-Bid No January 9 at 10:00 AM Las Positas College January 9 at 10:00 AM Las Positas College AGENDA I. Welcome & Introduction II. Project Overview III. Site, Constraints & Challenges IV. Bid Document Summary V. Bid Schedule II. Project Overview A. Project

More information

Application for Service Residential Subdivision / Development

Application for Service Residential Subdivision / Development Application for Service Residential Subdivision / Development Please complete this application and submit the completed form and attachments to PG&E Application for Service at P.O. Box 24047 Fresno CA

More information

City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems <48kW)

City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems <48kW) City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems

More information

INDIANA DEPARTMENT OF TRANSPORTATION PAGE 1 NOTICE TO HIGHWAY CONTRACTORS

INDIANA DEPARTMENT OF TRANSPORTATION PAGE 1 NOTICE TO HIGHWAY CONTRACTORS INDIANA DEPARTMENT OF TRANSPORTATION PAGE 1 NOTICE TO HIGHWAY CONTRACTORS DATE OF LETTING: March 04, 2015 TIME OF LETTING: 10:00 AM EASTERN STD DESIGN BUILD CONTRACTS Sealed proposals for certain highway

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This

More information

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016 UTILITY/CATV SERVICES CHAPTER 9 900. GENERAL A. Alliant Energy receives many requests for electric service from other utilities; telephone, telecommunications companies, cable television, the Department

More information

EV Charging Station Submittal Requirements

EV Charging Station Submittal Requirements EV Charging Station Submittal Requirements To obtain a permit for an Electric Vehicle Charging Station, please provide the following: Plan and details of the charging system installation o Print applicable

More information

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation Feasibility Study Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection J.E.D. Solid Waste Management Facility Holopaw Substation September 2013 1 of 12 Table of Contents GENERAL... 3 SHORT

More information

PURCHASING DEPARTMENT DIVISION OF BUDGET & FINANCE

PURCHASING DEPARTMENT DIVISION OF BUDGET & FINANCE PURCHASING DEPARTMENT DIVISION OF BUDGET & FINANCE 100 West Washington Street, Room 3200 Hagerstown, MD 21740-4748 P: 240.313.2330 F: 240.313.2331 www.washco-md.net PUR-1362 ADDENDUM NO. 1 INVITATION TO

More information

COMMERCIAL QUICK REFERENCE

COMMERCIAL QUICK REFERENCE COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

Please find attached the Dealer Notification Preliminary Letter for Toyota Safety Recall 14V-312 on the following Toyota and Lexus vehicles:

Please find attached the Dealer Notification Preliminary Letter for Toyota Safety Recall 14V-312 on the following Toyota and Lexus vehicles: TMS-NTC-14104 June 18, 2014 Toyota Motor Sales, U.S.A., Inc. 19001 South Western Avenue, S207 Torrance, CA 90509-2991 Recall Management Division National Highway Traffic Safety Administration 1200 New

More information

Appendix Item Addendum

Appendix Item Addendum Addendum to ESAH Version 3 Supply Application Appendix Item Addendum 1 Electrical System Item 1.4.5 Short Circuit Ratings Addendum for type of short circuit rating for system voltage of 275kV. 2 Types

More information

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION 100 KVA AND LARGER (CONCRETE PADS ONLY) 27.05-01 CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION

More information

Solar PV Standard Plan Simplified Microinverter and ACM Systems for One- and Two-Family Dwellings

Solar PV Standard Plan Simplified Microinverter and ACM Systems for One- and Two-Family Dwellings TOOLKIT DOCUMENT #4 Solar Standard Plan Simplified Microinverter and M Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters or Modules

More information

Request for Proposals: (1) 2018 FORD TAURUS SEDAN SE (1) 2018 Ford F-150 XL Regular cab 4x4 (2) 2018 Ford F-150 XL 4x4 Crew Cab 4x4

Request for Proposals: (1) 2018 FORD TAURUS SEDAN SE (1) 2018 Ford F-150 XL Regular cab 4x4 (2) 2018 Ford F-150 XL 4x4 Crew Cab 4x4 Request for Proposals: (1) 2018 FORD TAURUS SEDAN SE (1) 2018 Ford F-150 XL Regular cab 4x4 (2) 2018 Ford F-150 XL 4x4 Crew Cab 4x4 Greenville-Spartanburg Airport District Proposals Due: Friday July 20,

More information

REQUEST FOR BIDS (RFB) # (1) NEW X4-3/4 TON EXTENDED CAB PICKUP TRUCK WITH LIFT GATE POSTING DATE: MARCH 7, 2018

REQUEST FOR BIDS (RFB) # (1) NEW X4-3/4 TON EXTENDED CAB PICKUP TRUCK WITH LIFT GATE POSTING DATE: MARCH 7, 2018 REQUEST FOR BIDS (RFB) #18-022-25 (1) NEW 2018 4X4-3/4 TON EXTENDED CAB PICKUP TRUCK WITH LIFT GATE POSTING DATE: MARCH 7, 2018 RESPONSE DEADLINE: MARCH 27, 2018 11:00 A.M. CENTRAL STANDARD TIME (CST)

More information

City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA (925) phone (925) fax

City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA (925) phone (925) fax City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA 94596 (925) 943-5834 phone (925) 256-3500 fax Issued September 30, 2017 Policy Bulletin No. PB-72 Background Residential

More information

April 27, 2015 ADDENDUM #1. To the Plans and Specifications for: CENTRAL CAMPUS ELECTRICAL MODIFICATIONS PHASE II. for MIAMI UNIVERSITY.

April 27, 2015 ADDENDUM #1. To the Plans and Specifications for: CENTRAL CAMPUS ELECTRICAL MODIFICATIONS PHASE II. for MIAMI UNIVERSITY. April 27, 2015 ADDENDUM #1 To the Plans and Specifications for: CENTRAL CAMPUS ELECTRICAL MODIFICATIONS PHASE II for MIAMI UNIVERSITY Oxford, Ohio To: All Plan Holders Prepared by: M Engineering 750 Brooksedge

More information

Specifications for 6 locations have been revised. Please use the Revised Price Proposal section provided below for your bid submission.

Specifications for 6 locations have been revised. Please use the Revised Price Proposal section provided below for your bid submission. CARLOS PABELLON Director of Administration COUNTY OF DANE DEPARTMENT OF ADMINISTRATION PURCHASING DIVISION Room 425 City-County Building 210 Martin Luther King Jr. Blvd. Madison, WI 53703-3345 608-266-4131

More information

ATTACHMENT A - STATEMENT OF WORK INVITATION TO BID FOR CHILLER INSPECTION SERVICES ITB NO.: DMS-13/14-035

ATTACHMENT A - STATEMENT OF WORK INVITATION TO BID FOR CHILLER INSPECTION SERVICES ITB NO.: DMS-13/14-035 4050 Esplanade Way Tallahassee, Florida 32399-0950 Tel: 850.488.2786 Fax: 850. 922.6149 Rick Scott, Governor Craig J. Nichols, Agency Secretary ATTACHMENT A - STATEMENT OF WORK INVITATION TO BID FOR CHILLER

More information

Solar PV Standard Plan Simplified Microinverter and ACM Systems for One- and Two-Family Dwellings

Solar PV Standard Plan Simplified Microinverter and ACM Systems for One- and Two-Family Dwellings TOOLKIT DOCUMENT #4 Your City logo here Solar Standard Plan Simplified Microinverter and M Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

Public Review Draft Proposed Addendum cv to Standard , Energy Standard for Buildings Except Low-Rise Residential Buildings

Public Review Draft Proposed Addendum cv to Standard , Energy Standard for Buildings Except Low-Rise Residential Buildings BSR/ASHRAE/IES Addendum CV to ANSI/ASHRAE/IES Standard 90.1-2013 Public Review Draft Proposed Addendum cv to Standard 90.1-2013, Energy Standard for Buildings Except Low-Rise Residential Buildings First

More information

(i) in paragraph 9, for sub-paragraph (i) the following shall be substituted, namely:-

(i) in paragraph 9, for sub-paragraph (i) the following shall be substituted, namely:- Revision 3 Date: 28/01/2016 Amendment to Schedule 6 for Induction Motor In the said schedule, (i) in paragraph 9, for sub-paragraph (i) the following shall be substituted, namely:- Effective from 1 st

More information

UN-Priced Offers Due: Wednesday, April 25, 2018 at 10:00 a.m. Reverse Auction/Bid: Wednesday, May 9, 2018 starting at 11:00 a.m.

UN-Priced Offers Due: Wednesday, April 25, 2018 at 10:00 a.m. Reverse Auction/Bid: Wednesday, May 9, 2018 starting at 11:00 a.m. LAUDERDALE COUNTY BOARD OF SUPERVISERS 410 Constitution Ave, 11 th Floor Meridian, Mississippi 39301 601-482-9746 Main 601-482-9744 Fax BIDDERS INFORMATION PACKET BID NO: 3809 One (1) or more Single Axle

More information

ROCKLIN UNIFIED SCHOOL DISTRICT ADDENDUM NUMBER 1 TO THE BID DOCUMENTS Amendment Date: January 25, 2019

ROCKLIN UNIFIED SCHOOL DISTRICT ADDENDUM NUMBER 1 TO THE BID DOCUMENTS Amendment Date: January 25, 2019 ROCKLIN UNIFIED SCHOOL DISTRICT ADDENDUM NUMBER 1 TO THE BID DOCUMENTS Amendment Date: January 25, 2019 E-rate Year 22 RFP 2019-115 Cabling Fiber Optic Infrastructure, 4 Sites A. This Amendment shall be

More information

ADDENDUM NO. 3. Kansas City Area Transportation Authority (KCATA) 1350 E. 17 th Street Kansas City, Missouri 64108

ADDENDUM NO. 3. Kansas City Area Transportation Authority (KCATA) 1350 E. 17 th Street Kansas City, Missouri 64108 Issue Date: April 7, 2017 ADDENDUM NO. 3 Kansas City Area Transportation Authority (KCATA) 1350 E. 17 th Street Kansas City, Missouri 64108 Project #17-7006-39 This Addendum is hereby made a part of the

More information

STATE OF NORTH CAROLINA UTILITIES COMMISSION RALEIGH NOTICE TO CUSTOMERS DOCKET NO. E-34, SUB 46 BEFORE THE NORTH CAROLINA UTILITIES COMMISSION

STATE OF NORTH CAROLINA UTILITIES COMMISSION RALEIGH NOTICE TO CUSTOMERS DOCKET NO. E-34, SUB 46 BEFORE THE NORTH CAROLINA UTILITIES COMMISSION Page 1 of 5 STATE OF NORTH CAROLINA UTILITIES COMMISSION RALEIGH NOTICE TO CUSTOMERS DOCKET NO. E-34, SUB 46 BEFORE THE NORTH CAROLINA UTILITIES COMMISSION Notice is given that Appalachian State University,

More information

Electrical Depth. Mark W. Miller Sibley memorial Hospital Grand Oaks Washington, DC CURRENT SYSTEM

Electrical Depth. Mark W. Miller Sibley memorial Hospital Grand Oaks Washington, DC CURRENT SYSTEM CURRENT SYSTEM The current electrical system can best be described as star; one main switchboard that feeds to the main distribution panel, which then feeds the other panels. The normal power is provided

More information

PERMANENT RESIDENTIAL UNDERGROUND SERVICE

PERMANENT RESIDENTIAL UNDERGROUND SERVICE CITY OF RICHLAND ENERGY SERVICES DEPARTMENT 505 Swift Boulevard, MS-21 Richland, WA 99352 Telephone (509) 942-7403 Fax (509) 942-7405 PERMANENT RESIDENTIAL UNDERGROUND SERVICE A. INTRODUCTION This guide

More information

RFQ Fleet Vehicles. The City of Dawson Creek is requesting quotations for the supply and delivery of:

RFQ Fleet Vehicles. The City of Dawson Creek is requesting quotations for the supply and delivery of: RFQ 2016-23 Fleet Vehicles The City of Dawson Creek is requesting quotations for the supply and delivery of: One (1) 2016 Minimum GVW 4300kg, 4 Wheel Drive, Regular Cab, Long Box Truck. One (1) 2016 Minimum

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

Parkland Light & Water Co. ELECTRIC SERVICE REQUEST AND METER STANDARDS

Parkland Light & Water Co. ELECTRIC SERVICE REQUEST AND METER STANDARDS Parkland Light & Water Co. ELECTRIC SERVICE REQUEST AND METER STANDARDS Revised: January, 2017 Contents SERVICE REQUEST FORMS RECEIPT OF ELECTRIC SERVICE REQUEST AND METER STANDARDS ELECTRIC SERVICE REQUEST

More information

NORTH CAROLINA SHERIFFS ASSOCIATION

NORTH CAROLINA SHERIFFS ASSOCIATION NORTH CAROLINA SHERIFFS ASSOCIATION Name of Dealership Type of Vehicle Zone 600 AMP AUTOMATIC TRANSFER SWITCH (Specification #07) Base Unit Price 207 ASCO AC600 Appalachia -- NB -- 207 ASCO AC600 Dogwood

More information

STREAMLINED SOLAR CHECKLIST Owner Name:

STREAMLINED SOLAR CHECKLIST Owner Name: STREAMLINED SOLAR CHECKLIST Owner Name: Address: DEPARTMENT OF PUBLIC WORKS AND PLANNING ALAN WEAVER, DIRECTOR This checklist must be completed by the contractor or an authorized agent of the contractor

More information

CONFERENCE LOCATION EXHIBIT HOURS & EVENTS

CONFERENCE LOCATION EXHIBIT HOURS & EVENTS Welcome to Eastern Area Conference (EAC) being held October 1-3 at the Hilton Myrtle Beach Resort in Myrtle Beach, South Carolina. This document is meant as an exhibitor planning tool for the event. If

More information

705.12(D) The requirements pertaining to the connection. Unraveling the Mysterious. Load Side PV Connections. by John Wiles

705.12(D) The requirements pertaining to the connection. Unraveling the Mysterious. Load Side PV Connections. by John Wiles Unraveling the Mysterious 705.12(D) Load Side PV Connections by John Wiles The requirements pertaining to the connection of utility-interactive photovoltaic (PV) power systems to the load side of the main

More information

PUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS

PUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS PUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS 1. General Metering Requirements a. Interpretation The District s metering requirements shall not be interpreted to conflict with the

More information

Solid Waste Management Division Landfill Compactor Procurement 2/2/10

Solid Waste Management Division Landfill Compactor Procurement 2/2/10 2010 Solid Waste Management Division Landfill Compactor Procurement 2/2/10 TABLE OF CONTENTS SECTION TITLE SECTION NUMBER Purpose of Bid 1.1 Background 1.2 Time Line 1.3 Evaluation of Bids 1.4 Cart Specifications

More information