1 Issued by : Switchgear Contracts Division LARSEN & TOUBRO LIMITED Powai Works, Mumbai October December 1996 Prospect/ Retrospect IS/IEC Specification In the previous three issues of L&T Current Trends, we have published an article on IS/IEC specification for Low Voltage Switchgear and Controlgear (IS 13947) in three parts. Our readers have written to us to give a condensed summary of these three parts. In this issue, we are publishing the summary alongwith important tables which were included in main article. Though our efforts are to make this summary as exhaustive as possible, so that it can be preserved by our readers as a handy reference, if any clarification is required, we suggest that our readers refer to the original Indian Standards. FEATURE Introduction to IS : A new Indian Standard on Switchgear and Controlgear Products - Summary - H.T. Mistry, Senior Executive-Design, Switchgear Design and Product Development In a major revision, International Electrotechnical Commission (IEC) introduced a new specification, IEC 947, on low voltage switchgear and controlgear in Bureau of Indian Standards also decided to adopt the text of IEC 947 and consequently, in1993, introduced a new dual number specification IS 13947/ IEC pub 947 on switchgear and controlgear products. National Annex has been added to IEC text in IS to cover typical requirements e.g. use of aluminium conductors, ambient conditions, preferred voltages. etc. This specification is divided into two documents. as general have been consolidated in this first part. 2) Product standard Specific testing and performance requirements of the products are covered by relevant product standards. These are : Part 2 : Circuit breakers Part 3 : Switches, disconnectors, switch disconnectors and fuse combination units Part 4 : Contactors and motor starters (section 1 : Electromechancal contactors and starters) 1) General rules (Part 1) : All those parts of various prooduct standards which can be considered Part 5 : Control circuit devices and switching elements Part 6 : Multiple function devices

2 Part 7 : Ancillary equipments PART 1 : GENERAL RULES : This standard states those general rules and requirements which are common to low voltage switchgear products e.g. definitions; characteristics; normal service, mounting and transport conditions; information to be supplied with the equipment; constructional and performance requirements and verification of these requirements. Following are the major revisions introduced in part 1 : I) DEFINITIONS : Disconnector: Definition of disconnector has been enlarged. A disconnector has now been defined as a mechanical device which in the open position complies with the requirements of isolating function. As per the new definition, a disconnector needs to meet performance requirements in addition to minimum isolating distance. II) RATINGS AND LIMITING VALUES : i) Conventional thermal currents Following two new limiting currents have been introduced to define thermal characteristics of the product. a) Conventional free air thermal current (Ith) b) Conventional enclosed thermal current (Ithe) These currents are defined as the maximum values of currents to be used for temperature rise tests on unenclosed equipment (Ith) or on equipment in smallest enclosure specified by the manufacturer (Ithe). These currents are not the ratings and need not be marked on the equipment. ii) Rated impulse withstand voltage (Uimp) : Overvoltages originate from causes like load fluctuations, switching operations, resonances, faults and lightening discharges on low voltage (LV) systems. These overvoltages affect common LV installations and equipment. In view of this, in order to evaluate adequacy of design of low voltage switchgear products to withstand overvoltages, concept of rated impulse withstand voltage has been introduced. Preferred values of rated impulse withstand voltage are specified in new IS. Theses are reproduced in table 1. Overvoltage category for the equipment is decided by its location in the installation. (Origin of installation, distribution, load etc.) Preferred value of impulse withstand voltage reduces as the equipment is located further away from the source of energy. I) NORMAL SERVICE CONDITIONS : Pollution degrees : In order to define environmental conditions more precisely and to evaluate clearance and creepage distances following four pollution degrees are established. Pollution degree 1 : No pollution or only dry, non-conductive pollution occurs. Pollution degree 2 : Normally non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation may be expected. Pollution degree 3 : Conductive pollution occurs or dry, non-conductive pollution occurs which becomes conductive due to condensation. Pollution degree 4 : The pollution generates persistent conductivity caused, for instance, by conductive dust or rain of snow. Unless otherwise specified equipment or industrial application is generally suitable for use in pollution degree 3 environment. II) CONSTRUCTIONAL REQUIREMENTS : a) Materials : The suitability of insulating material is verified with respect to its resistance to abnormal heat and fire through elaborate tests. These tests are either conducted on the equipment (glow wire test) or on specimen of the material (hot wire ignition and arc ignition tests). b) Terminals : Constructional requirements e.g. strength, size etc. for terminals suitable for unprepared copper conductors are evaluated through following tests. i) Tests for verification of mechanical strength ii) Flexion test (test for damage to conductors and their accidental loosening) iii) Pull out test iv) Test for insertability of conductors c) Clearance and creepage distances : Clearance : Minimum clearance values have been specified in new IS on the basis of rated impulse withstand voltage and pollution degree. Clearance is verified through a type a test for verification of dielectric properties. To account for deterioration of properties of insulating materials minimum creepage distance are specified based on following factors

3 - Rated insulation voltage - Environmental conditions or pollution degree - Insulating materials used b) Short circuit ratings : Following two new short circuit ratings have been introduced. i) Rated ultimate short circuit breaking capacity (Icu) : Minimum number of operations for breakers for ratings up to 100A and above 1250A have been revised as shown in table VI. c) Number of units to be tested : Insulating materials can be roughly characterized according to the damage they suffer due to flow and interruption of leakage current on contaminated surfaces. Though no direct relationship exists, it has been found by tests and experience that insulating materials with higher comparative tracking index (CTI) have relatively better performance. Hence for the purpose of specifying minimum creepage distance, insulating materials have been classified into four material groups in terms of CTI, as given in table II. Minimum creepage distances for low voltage switchgear products are given in table III. PART 2 : CIRCUIT BREAKERS This standard replaces IS 2516 (Parts 1&2/Sec. 1)-1985 I) CHARACTERISTICS : a) Utilization category : In the new IS, utilization categories have been specified for circuit breakers also. These have been defined with reference to selectivity i.e. whether a circuit breaker is intended for selectivity by means of an intentional time delay under short circuit conditions. Circuit breakers not specifically intended for selectivity can be assigned utilization category A e.g. moulded case circuit breakers. These breakers need not have short time withstand rating (Icw). Circuit breakers specifically meant for selectivity are assigned utilization category B. Air circuit breakers with intentional time delay for tripping in short circuit condition can be assigned utilization category B. These breakers will also be assigned short time withstand rating (Icw). Ultimate short circuit breaking capacity is assigned by the manufacturer. As the term indicates, continued service from the breaker is not expected after the breaker has cleared a short circuit fault of such magnitude. This rating is similar to P1 category rating defined in IS ii) Service short circuit breaking capacity (Ics) : Service short circuit breaking capacity is also assigned by the manufacturer and can be expressed as percentage of ultimate short circuit breaking capacity (Icu). The ratio shall be selected from standard ratios indicated in table IV. This rating is similar to P2 category rating specified in the earlier standard. II) PERFORMANCE REQUIREMENTS : a) Test sequences : In order to evaluate performance of a product comprehensively, relevant type tests are grouped into test sequences. All tests in a given sequence are carried out on the same unit in prescribed order. Such sequential testing represents actual service conditions more closely. Details of test sequences applicable to circuit breakers are given in table V. b) Operational performance capability : This test, a part of test sequence 1, is to verify capability of breakers to perform minimum number of mechanical (without current) and electrical (with current) operations. Number of units to be tested is arrived at based on whether - the product is assigned more than one operational voltage - terminals for line and load connections are identified d) Conductors for short circuit test : For circuit breakers of ratings upto 630A, conductors to be used for terminal connections in short circuit tests (Ics and Icu) have now been specified as given below. "A cable of 75 cm in length having a cross section corresponding to the conventional thermal current shall be included as follows: - 50 cm on supply side - 25 cm on load side." PART 3 : SWITCHES, DISCONNECTORS, SWITCH DISCONNECTORS AND FUSE COMBINATION UNITS This part replaces both parts of IS Following changes have been incorporated in the new IS. I) CHARACTERISTICS : a) Rated short time withstand current (Icw) : As per IS 4064, minimum short time withstand current was 20 times the maximum rated operational current for a duration of 1 second. This has been changed to 12 times the maximum rated operational current. b) Utilization category : Designation of utilization category

4 has been changed. In the new IS the designation is completed by suffix A or B according to whether the intended applications require frequent or infrequent operations. Utilization categories with suffix B are appropriate for devices which, due to design or application, are only intended for infrequent operations. Category AC 23A includes occasional switching of individual motors. II) PERFORMANCE REQUIREMENTS : Performance requirements are verified through type tests. All relevant type tests are grouped into four test sequences. These are given in table VII. Performance requirements have, in general, become more onerous. Expected minimum electrical and mechanical life corresponding to rating have been indicated. Expected life for category A is higher than category B. PART 4 : CONTACTORS AND MOTOR STARTERS : SECTION 1 : ELECTROMECHANICAL CONTACTORS AND STARTERS: So far, requirements of contactors and motor starters were covered by separate standards, namely IS 2959 and four parts of IS 8544 respectively. These are now covered by part 4/Section 1 of IS There are significant changes in performance requirements. Attempt has also been made, wherever possible, to align with North American practices. I) Utilization categories : In the new IS scope has been widened to include various applications of contactors. These are listed in Table VII. Presently, utilization categories are characterised by i) rated making and breaking capacities of the contactors and ii) electrical life. In the new IS, one more criterion, conventional operational performance, has been introduced. This requirement does not evaluate expectancy of life but verifies capability of the contactor to make and break, for specified number of times, normal and marginal overload currents. II) Terminal markings : The terminals for main circuits are required to be marked by a single digit number (IEC 445) and aplhanumeric system (North American practice). III) Trip classes for overload relays : In the new IS, selection of relay has been facilitated by introduction of trip classes. Relays are classified into four trip classes based on tripping time at 7.2 times the setting of the relay. In other words, trip classes indicate maximum motor starting time permitted by the relay.. Trip classes are indicated in Table IX. Definition of trip classes 10, 20 and 30 is in line with North American standards. IV) Tests : a) Test sequences : All type tests are segregated in five test sequences. b) Performance under short circuit condition : In new IS, this test has been significantly revised as follows : 1) Performance is verified through three tests : a) Verification to short circuit performance at "r" current, "r" current is decided corresponding to maximum AC3 rating as indicated in table X. b) Verification of short circuit performance at "q" current declared by the manufacturer c) Verification of co-ordination at "p" current. (a) and (b) are now mandatory tests while (c) is a special test. (2) Only two types - type 1 and 2 - of co-ordinations are specified in new IS instead of three types - type A, B and C as in IS Type of co-ordination, is defined based on the extent of damage during short circuit test. For type 1 co-ordination, damage to the contactor/starter is permitted. However, there should be no danger to the operator or damage to the installation. These conditions are similar to those for type A co-ordination. No damage is permitted for type 2 coordination. However, light contact welding which can easily be opened (with a screw driver) is acceptable. This is analogous to type C coordination. Type B co-ordination defined in IS 8544 has been excluded. For type B co-ordination, no damage was permitted except alteration of overload relay characteristics. For further information, please contact Larsen & Toubro Limited, Packing Division, Powai Works, Saki-Vihar Road, Mumbai Edited, printed and published by Cerena de Souza for Larsen & Toubro Limited. Published from L&T House, Narottam Morarjee Marg, Balard Estate, Mumbai and printed at Uma Offset, 359, A to Z Indl. Estate, G. Kadam Marg, Lower Parel, Mumbai Associate Editor: Luis S. R. Vas.

5 Table I PREFERRED VALUES OF IMPULSE WITHSTAND VOLTAGE MAXIMUM VALUE OF TATED OPERATIONAL VOLTAGE TO EARTH V IV ORIGIN OF INSTALLATION PREFERRED VALUES OF IMPULSE WITHSTAND VOLTAGE in kv (1.2 / 50 µs) OVER VOLTAGE CATEGORY III DISTRIBUTION CIRCUIT II LOAD I SPECIALLY PROTECTED TABLE - III MINIMUM CREEPAGE DISTANCES RATED INSULATION VOLTAGE, V POLLUTION DEGREE 2 CREEPAGE DISTANCES, in mm POLLUTION DEGREE 3 POLLUTION DEGREE 4 MATERIAL GROUP I II IIIA IIIB MATERIAL GROUP I II IIIA IIIB MATERIAL GROUP I II IIIA IIIB TABLE II MATERIAL GROUPS MATERIAL GROUP I 600 <= CTI MATERIAL GROUP II 400 <= CTI < 600 MATERIAL GROUP IIIa 175 <= CTI < 400 MATERIAL GROUP IIIb 100 <= CTI < q 32 - TABLE V : CIRCUIT BREAKERS - TEST SEQUENCES TABLE IV Standard ratios between Ics and Icu Utilization Utilization Category A Category B Ics (as % of Icu) Ics (as % of Icu) TEST SEQUENCE APPLICABLE TO TESTS I General Performance Characteristics II Rated service s.c. breaking capacity (Ics) III Rated ultimate s.c. breaking capacity (Icu) IV Rated short time withstand current (Icw) Combined test sequence. All circuit breakers All circuit breakers All circuit breakers Circuit breaker of utilization category B Circuit breakers of utilization category B i) when Icw=Ics (Replaces Seq II & IV) ii) when Icw=Ics=Icu (Replaces Seq II, III&IV) 1.Tripping limits and characteristics 2.Dielectric properties 3.Operational performance capability 4.Overload performance 5.Verification of dielectric withstand 6.Verification of temperature rise 7.Verification of overload releases 1.Rated service s.c. breaking capacity 2.Verification of dielectric withstand 3.Verification of temperature rise 4.Verification of overload releases 1.Verification of overload releases 2.Rated ultimate s.c. breaking capacity 3.Verification of dielectric withstand 4.Verification of overload releases 1.Verification of overload releases 2.Rated ultimate s.c. breaking capacity 3.Verification of temperature rise 4.S.c. breaking capacity at maximum short time withstand current 5.Verification of dielectric withstand 6.Verification of overload releases 1.Verification of overload releases 2.Rated short time withstand current 3.Rated service s.c. breaking capacity 4.Verification of dielectric withstand 5.Verification of temperature rise 6.Verification of overload releases

6 RATED A TABLE VI : CIRCUIT BREAKERS COMPARISION OF MINIMUM OPERATING CYCLES WITHOUT IS IS 2516 MINIMUM OP. CYCLES MINIMUM OP. CYCLES WITH TOTAL WITHOUT WITH TOTAL In < = 100 A < In < = < In < = < In Subject to agreement TABLE VIII Utilization categories for contactors/starters IS (Part 4/Sec. 1) Utilization category AC-1 AC-2 AC-3 AC-4 AC-5a AC-5b AC-6a AC-6b Typical applications Non inductive or slightly inductive loads resistance furnaces Slip-ring motors: starting, switching off Squirrel cage motors: starting, switching off while running Squirrel cage motors: starting, plugging, inching Switching of electric discharge lamp controls Switching of incandescent lamps Switching of transformers Switching of capacitor banks TABLE VII : SWITCHES, DISCONNECTRS, FUSE COMBINATION UNITS TEST SEQUENCES TEST SEQUENCE I General performance characteristics II Operational performance capacity III Short circuit performance capability IV Conditional short circuit current TEST (1) Temperature rise (2) Dielectric properties (3) Making and breaking capacities (4) Dielectric verification (5) Leakage current (6) Temperature rise verification (7) Strength of actuator mechanism (1) Operational performance (2) Dielectric verification (3) Leakage current (4) Temperature rise verification (1) Short time withstand current (2) Short circuit making capacity (3) Dielectric verification (4) Leakage current (5) Temperature rise verification (1) Fuse protected s.c. withstand (2) Fuse protected s.c. making (3) Dielectric verification (4) Leakage current (5) Temperature rise verification AC-8a AC-8b DC-1 DC-3 DC-5 DC-6 Hermatic refrigerent compressor motor control with manual resetting of overload releases Hermatic refrigerent compressor motor control with automatic resetting of overload releases Non-Inductive or slightly inductive loads resistance furnace Shunt motors: starting plugging, inching, dynamic braking of d. c. motors. Series motors: starting, plugging, inching dynamic braking of d. c. motors. Switching of incandescent lamps Table X Value of r current IS (Part 4/sec. 1) Table IX Trip classes for overload relays IS (Part 4/sec. 1) Trip Class Tripping time, Sec. * 10A < Tp <= 10 4 < Tp <= 10 6 < Tp <= 20 9 < Tp <= 30 * At 7.2 times relay setting starting from cold Rated Operational Current Ie (AC3), A 0 < le <= < le <= < le <= < le <= < le <= < le <= < le <= < le r Current ka Subject to agreement

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

General information about motor protection

General information about motor protection Application guide General information about motor protection Typical construction of a motor starter Disconnect Switch UL 98 - UL489 CSA C22.2 # 4 CSA C22.2 # 5 Fuses SIRCO Non-Fusible Disconnect Switch

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60470 Second edition 1999-10 High-voltage alternating current contactors and contactor-based motor-starters Contacteurs pour courants alternatifs haute tension et démarreurs

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60269-1 Edition 3.1 2005-04 Edition 3:1998 consolidated with amendment 1:2005 Low-voltage fuses Part 1: General requirements IEC 2005 Copyright - all rights reserved No part

More information

3TM Vacuum Contactors

3TM Vacuum Contactors Catalog Extract HG 11.23 Edition 2016 Catalog Extract Medium-Voltage Equipment siemens.com/3tm R-HG11-343.psd 2 Siemens HG 11.23 2016 Contents Medium-Voltage Equipment Catalog Extract HG 11.23 2016 Contents

More information

15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD. DATASHEET - DILMC9-10(24VDC) Technical data General Contactor, 3p+1N/O, 4kW/400V/AC3 Part no. DILMC9-10(24VDC) Catalog No. 277468 Eaton Catalog No. XTCEC009B10TD EL-Nummer 4110305 (Norway) Standards IEC/EN

More information

Presented to the IAPMO Standards Review Committee on December 9, 2013

Presented to the IAPMO Standards Review Committee on December 9, 2013 Summary of Substantive Changes between the 2010 edition including Updates No. 1 and No. 2 dated September 2010 and August 2011 and the 2013 edition of CSA C22.2 No. 14 Industrial control equipment Presented

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN Motor Contactor Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN rail) up to 45 kw Range from 4 to 110 kw (AC 3, 380/415V) Finger proof ( VBG 4) Accessoires

More information

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Specification for 70mm pole pitch Air circuit breaker up to 1600 A Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with

More information

Menu. Home About this portal Latest updates. Print Save Resource detail Citations. Table of Contents

Menu. Home About this portal Latest updates. Print Save  Resource detail Citations. Table of Contents Menu Home About this portal Latest updates Print Save Email Resource detail Citations AS/NZS 60898.1:2004 Electrical accessories - Circuit-breakers for overcurrent protection for household and similar

More information

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing Introduction A contactor is an electrical device which is used for switching an electrical circuit on or off. It is considered to be a special type of relay. However, the basic difference between the relay

More information

E-12 Low-voltage Switchboard

E-12 Low-voltage Switchboard Guideline No.E-12 (201510) E-12 Low-voltage Switchboard Issued date: 20 October 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly

More information

An electrical panel capable of evolving

An electrical panel capable of evolving An electrical panel capable of evolving Prisma TT Low voltage factory built assemblies Buildings Commercial & Industrial Make the most of your energy General For a dependable electrical installation Total

More information

Technical data OT16E3 OT160E3 UL & CSA

Technical data OT16E3 OT160E3 UL & CSA Technical data OT16E3 OT16E3 UL & CSA UL & CSA Catalog number 3 pole OT16E3 OT25E3 OT32E3 OT45E3 OT63E3 OT3E3 OT6E3 OT1E3 OT16E3 Approvals 1 2 pole N/A N/A N/A N/A N/A N/A N/A N/A UL98 & EC 3 pole UL58

More information

Other Devices. Installation Contactors Z-SCH. Connection diagrams Z-SCH NO 3 NO / 1 NC. Permitted Installation Positions

Other Devices. Installation Contactors Z-SCH. Connection diagrams Z-SCH NO 3 NO / 1 NC. Permitted Installation Positions Installation Contactors Z-SCH These switching devices have been designed and rated particularly for modular installation in modular distribution boxes for electrical installation or cabinets with device

More information

Application Mini Contactors for Motors and Resistive Loads

Application Mini Contactors for Motors and Resistive Loads Delivery program Contactor, 4p, 4kW/400V/AC3 Part no. DILEM4-G(24VDC) Catalog No. 012701 Eaton Catalog No. XTMF9A00TD Product range Contactors Application Mini Contactors for Motors and Resistive Loads

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

CI-TI Contactors and motor starters Types CI 61 - CI 98

CI-TI Contactors and motor starters Types CI 61 - CI 98 Data sheet CI-TI Contactors and motor starters s CI 6 - CI 98 Contactors CI 6, CI 7, CI 86 and CI 98 switch powers of up to 0 kw, 7 kw, 45 kw and 55 kw respectively under 80 V - loads. Accessories include

More information

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS

More information

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5 3-pole DC Operated Ratings Rated Aux. Contacts Type Coil voltage 1) AC2 Current Built-in Additional 24 24V= DC 5 AC3 see 48 60V= DC 6 380V AC1 page 34 110 110V= DC 7 400V 660V 220 220V= DC 8 415V 690V

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60092-503 Second edition 2007-06 Electrical installations in ships Part 503: Special features AC supply systems with voltages in the range of above 1 kv up to and including 15

More information

TEST REPORT IEC Low-voltage switchgear and control gear Part 7-4: Ancillary equipment PCB terminal blocks for copper conductors

TEST REPORT IEC Low-voltage switchgear and control gear Part 7-4: Ancillary equipment PCB terminal blocks for copper conductors r Test Report issued under the responsibility of: TEST REORT Low-voltage switchgear and control gear art 7-4: Ancillary equipment CB terminal blocks for copper s Report Number.... : 2169331.75 Date of

More information

SWITCHGEAR. 4G cam switches

SWITCHGEAR. 4G cam switches SWITCHGEAR 178 4G cam switches ENERGY SAFELY SWITCHED 179 SWITCHGEAR 180 GENERAL INFORMATION 4G-series cam switches are low voltage switches, designed according to the latest knowledge about switchgear

More information

Electrical Control System Components Basics of Magnetic Control :

Electrical Control System Components Basics of Magnetic Control : Electrical Control System Components Basics of Magnetic Control : Dr.M.S.Narkhede, LEE, GP Mumbai 1 Contact Types : Contacts are classified into different ways as follows. According to applications contacts

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Industrial Protection Products Edition

Industrial Protection Products Edition Industrial Protection Products 2016 Edition COMPANY PROFILE Shanghai Liangxin Electrical Co., LTD. one of the leading low-voltage electrical component manufacture in the high-end market, was established

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France Contact us ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F-69687 Chassieu cedex / France You can find the address of your local sales organisation on

More information

FAQ S. Main Switchboard Design Criteria. ENGINEERED SOLUTIONS FOR ALL YOUR SWITCHBOARD NEEDS

FAQ S. Main Switchboard Design Criteria.   ENGINEERED SOLUTIONS FOR ALL YOUR SWITCHBOARD NEEDS FAQ S Main Switchboard Design Criteria h ENGINEERED SOLUTIONS FOR ALL YOUR SWITCHBOARD NEEDS www.electricalswitchboards.com.au Main switchboard Design criteria Q: What is the Australian standard for main

More information

Effective discrimination of protective devices

Effective discrimination of protective devices Effective discrimination of protective devices In the event of a fault occurring on an electrical installation only the protective device nearest to the fault should operate,leaving other healthy circuits

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 62271-102 First edition 2001-12 High-voltage switchgear and controlgear Part 102: Alternating current disconnectors and earthing switches This English-language version is derived

More information

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA 023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir

More information

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 Functions and characteristics Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 NT and NW selection criteria Masterpact NT Masterpact NW NT06, NT08, NT10, NT12, NT16 NT06, NT08, NT10

More information

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24

More information

Model Number Legend. Motor Contactor J7KN. Motor Contactor J7KN 1

Model Number Legend. Motor Contactor J7KN. Motor Contactor J7KN 1 Motor Contactor J7KN Range from 4 to 500 kw (AC 3, 380/415 V) AC and DC operated Integrated auxiliary contacts; integrated aux. contact of J7KN contactors up to 11kW suitable for electronic circuits Screw

More information

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop

More information

cor Long Run Experience

cor Long Run Experience Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30

More information

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting.

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting. DATASHEET - ZB12-2,4 Delivery program Overload relay, 1.6-2.4 A, 1N/O+1N/C Part no. ZB12-2,4 Catalog No. 278437 Eaton Catalog No. XTOB2P4BC1 EL-Nummer 0004131832 (Norway) Product range Overload relay ZB

More information

E-12 Low-voltage Switchboard

E-12 Low-voltage Switchboard Guideline No.E-12 (201705) E-12 Low-voltage Switchboard Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements, inspection

More information

045 : 2000 CEB STANDARD

045 : 2000 CEB STANDARD 045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

Micro Contactor MA Series

Micro Contactor MA Series Relay-sized contactor, making it the world s smallest >3mm contact clearance acc. to IEC 60335-1 for Safety Applications Reversing contactor with mechanical interlock 3 Pole and 1 Aux. Contact NO or NC

More information

About us. Switchgear Factory, Mumbai

About us. Switchgear Factory, Mumbai About us Larsen & Toubro is a technologydriven USD 8.5 billion company that infuses engineering with imagination. The Company offers a wide range of advanced solutions in the field of Engineering, Construction,

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases Index Page Circuit-Breakers M4 166 for motor protection Auxiliary contacts 167 Signalling switch Auxiliary releases Insulated 3-pole busbar system 168 Terminal block DIN-rail adapters 169 Busbar adapters

More information

Innovation in soft start technology HFE-2 USER MANUAL. MAN-HFE-002. Version 01

Innovation in soft start technology HFE-2 USER MANUAL. MAN-HFE-002. Version 01 Innovation in soft start technology HFE-2 USER MANUAL MAN-HFE-002. Version 01 HFE-2 user guide Fairford Electronics Ltd Bristow House Gillard Way, Ivybridge PL21 9GG UK www.fairford.com 2016 by Fairford

More information

ELECTRICAL ENGINEERING & COMPUTER SCIENCE NEWSLETTER Volume

ELECTRICAL ENGINEERING & COMPUTER SCIENCE NEWSLETTER Volume ELECTRICAL ENGINEERING & COMPUTER SCIENCE NEWSLETTER Volume 4 2016 Electrical Conductor Spacing Standards for Printed Circuit Boards Authors: Sonal Kothari Phan, Ph.D.; Jeremiah Stepan, Ph.D., P.E.; Benjamin

More information

NXPLUS C Single busbar. Maintenance-free for lifetime

NXPLUS C Single busbar. Maintenance-free for lifetime NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage

More information

Technical Information

Technical Information C5 C5- C5- C5- C5- C5-550 ➊ 700 860 1000 1200 Rated Insulation Voltage U i to IEC 947-1 [V] 1000V 1000V 1000V 690V 690V UL/CS [V] 600V Rated Impulse Voltage U imp C5-550 / 700 / 860 [kv] 3.5 C5-1000 /

More information

Moulded Case Circuit Breakers

Moulded Case Circuit Breakers Moulded Case Circuit Breakers DU Series About us Larsen & Toubro is a technologydriven company that infuses engineering with imagination. The Company offers a wide range of advanced solutions in the field

More information

Essential Loads also use stand by generator systems mostly in process industries as they relate to high restarting times or high down times.

Essential Loads also use stand by generator systems mostly in process industries as they relate to high restarting times or high down times. The need for continuous power supply and its reliability has increased rapidly over the years, especially in all those areas where uninterrupted power supply is a must. Modern systems are power dependent.

More information

RESIDUAL CURRENT CIRCUIT BREAKER

RESIDUAL CURRENT CIRCUIT BREAKER Quality Features Mid Trip - Different knob position to indicate whether the device is Switched OFF by a fault or Switched OFF manually Inscription Window - Ensures circuit identification and hence reduces

More information

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers: 4 (Four) Pole Monoblock: Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers: Designed and manufactured in accordance with EN 50336:2002 and BS 2562: 1979 1 Introduction:

More information

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2. Index Index Page Manual Motor Starters 1 Auxiliary Contact Blocks 1 Trip Alarm Auxiliary 1 Switch Shunt Release 1 Under-voltage Release 2 Accessories 2 Busbar Connectors 2 Enclosures 2 Leistung, kw C mv

More information

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

Motor Protection Circuit Breakers

Motor Protection Circuit Breakers Motor Protection Circuit Breakers About us Larsen & Toubro is a technologydriven USD 9.8 billion company that infuses engineering with imagination. The Company offers a wide range of advanced solutions

More information

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction.

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction. HHD High Voltage Fuses German DIN Standard For Air & Gas Insulated Switchgear Indoor and Outdoor Application The striker pin system is connected by means of a high resistance parallel conductor. After

More information

Data sheet. CI-tronic Soft start motor controller Type MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 50 I-O 520B1443

Data sheet. CI-tronic Soft start motor controller Type MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 50 I-O 520B1443 CI-tronic Soft start motor controller Type MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 50 I-O December 2002 DKACT.PD.C50.G2.02 520B1443 2 DKACT.PD.C50.G2.02 Danfoss A/S 12-2002 Introduction The MCI soft starters

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

8DJ. Maintenance-free for lifetime

8DJ. Maintenance-free for lifetime 8DJ Maintenance-free for lifetime Energy Distribution Welcome! Page 2 October 1 st 2008 8DJ Main Applications for Medium-Voltage Switchgear Power generation Power stations G Power transmission High and

More information

Item 1: Contents of the complete training & CV of the lecturer

Item 1: Contents of the complete training & CV of the lecturer Course DESIGN CONCEPTS + software SwitchgearDesign for SWITCHGEAR, SWITCHBOARDS, BUSDUCTS & SUBSTATIONS" Item 1: Contents of the complete training & CV of the lecturer Presented by Sergio Feitoza Costa

More information

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

ECET Circuit Design Motor Loads. Branch Circuits. Article 210 ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Circuit Design Motor Loads Branch Circuits Article 210 210.1 Scope This article covers branch circuits except for those that supply

More information

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer DATASHEET - ZB65-65 Delivery program Overload relay, 50-65A, 1N/O+1N/C Part no. ZB65-65 Catalog No. 278460 Eaton Catalog No. XTOB065DC1 EL-Nummer 0004131855 (Norway) Product range Overload relay ZB up

More information

CI-tronic Soft starters for Danfoss commercial compressor applications Type MCI 15C, MCI 25C, MCI 50CM-3 I-O

CI-tronic Soft starters for Danfoss commercial compressor applications Type MCI 15C, MCI 25C, MCI 50CM-3 I-O Data sheet CI-tronic Soft starters for Danfoss commercial compressor applications Type, MCI 25C, MCI 50CM-3 I-O The MCI compressor soft starters are designed for soft starting of 3 phase compressors. During

More information

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters Text Book: Chapter 6, Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Paul I-Hai

More information

atalog Welcome to ATO.com! Contact us... Tel: (Toll-free) Website:

atalog Welcome to ATO.com! Contact us...   Tel: (Toll-free) Website: atalog Welcome to.com! Contact us... Email: sales@ato.com Tel: +1 800-585-1519 (Toll-free) Website: ZMQ2E Series Dual Power Automatic Transfer Switch (ATS) Applications ZMQ2E dual auto transfer switch

More information

B kv Gas-insulated Substations

B kv Gas-insulated Substations 72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.

More information

33KV INDOOR SWITCHGEAR

33KV INDOOR SWITCHGEAR 33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

Controls. CONTACTORS CWB Line (up to 40A)

Controls. CONTACTORS CWB Line (up to 40A) Controls CONTACTORS CWB Line (up to 40A) 0800 367 934 Contactors CWB Line (up to 40A) CONTACTORS CWB Line (up to 40A) Summary New WEG CWB Contactors 4 The Technology Within 6 Energy Savings 7 Easy Panel

More information

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are: Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor.

More information

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3

More information

CI-Tronic Soft start motor controller MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 40-3D and MCI 50-3 I-O

CI-Tronic Soft start motor controller MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 40-3D and MCI 50-3 I-O Data sheet CI-Tronic Soft start motor controller MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 40-3D and MCI 50-3 I-O The MCI soft starters are designed for soft starting and stopping of 3 phase AC motors, thus

More information

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.02 2011 Answers for energy. R-HG11-172.tif 2 Siemens HG 11.02 2011 Contents SION Vacuum Circuit-Breakers Medium-Voltage Equipment Catalog

More information

Euroload Changeover Switch

Euroload Changeover Switch Euroload Features: Quick make & quick break mechanism. High electrical & mechanical endurance. Advance neutral. Enclosed housing to avoid dust ingress. Staggered terminals upto 800A. Load and Line reversibility.

More information

The Contactor. Antonino Daviu, Jose Alfonso Departamento de Ingeniería Eléctrica. Universitat Politècnica de València

The Contactor. Antonino Daviu, Jose Alfonso Departamento de Ingeniería Eléctrica. Universitat Politècnica de València The Contactor Surnames, name Antonino Daviu, Jose Alfonso (joanda@die.upv.es) Department Centre Departamento de Ingeniería Eléctrica Universitat Politècnica de València 1 1 Summary The aim of this paper

More information

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA 017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS PAGE 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable Standards 3 5. Basic Features 4 6. Quality

More information

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction.

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction. HHD HIGH VOLTAGE GERMAN DIN STANDARD FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS The striker pin system is connected by means of a high resistance parallel conductor. After melting the main

More information

MAGNETIC MOTOR STARTERS

MAGNETIC MOTOR STARTERS Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors

More information

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC AF0... AF0 -pole Contactors up to 20 HP / 480 VAC Contactors and Overload Relays Overview...2 AF0... AF0 -pole Contactors Ordering Details...4 Main Technical Data...20 DC Circuit switching...2 Main Accessory

More information

AF40... AF96 3-pole contactors Technical data

AF40... AF96 3-pole contactors Technical data Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional

More information

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features Standard Features Table : Standard Features GV2ME GV2P GV3P GV7RE/GV7RS 0. to 32 A Up to 20 hp @ 460 V 0 SCCR @ 480 V Push Button Operator 0. to 30 A Up to 5 hp @ 460 V 50 SCCR @ 480 V Rotary Handle Operator

More information

The need for continuous power supply and its reliability has increased rapidly over the years, especially in all those areas where uninterrupted

The need for continuous power supply and its reliability has increased rapidly over the years, especially in all those areas where uninterrupted 110 The need for continuous power supply and its reliability has increased rapidly over the years, especially in all those areas where uninterrupted power supply is a must. Modern systems are power dependent.

More information

UniSec Maintenance solutions

UniSec Maintenance solutions DISTRIBUTION SOLUTIONS UniSec Maintenance solutions ABB supports you to improve the reliability, safety and efficiency of your electrical equipment UniSec Maintenance solutions Table of contents 004 00

More information

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING 1 DEPARTMENT OF ELECTRICAL ENGINEERING Introduction to High Voltage Testing It is essential to ensure that the electrical equipment is capable of withstanding the overvoltages that are met within the service.

More information

A Contactors. Technical Information. CA4 Miniature Contactors. Technical Information A94 CA4. Switching Motor Loads.

A Contactors. Technical Information. CA4 Miniature Contactors. Technical Information A94 CA4. Switching Motor Loads. C4 Miniature Contactors Contactors C4 Rated Insulation Voltage U i to IEC 947-1 [V] 500V UL/CS [V] 600V Rated Impulse Voltage U imp [kv] 8 Rated Voltage U e Main Contacts C 50/60Hz [V] 230, 240, 400, 415,

More information

Page 2 of 39 Report No. CTI PA Testing location:

Page 2 of 39 Report No. CTI PA Testing location: age 2 of 39 Report No. CTI A 2841-2 Tests performed (name of test and test clause): according to :2009: 5 - Interface characteristics, 6 Information, 7 - Service conditions, 10.2.3.3 - Verification of

More information

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:

More information

KD LV Motor Protection Relay

KD LV Motor Protection Relay 1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage

More information

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This

More information

Modular contactor for installation into distribution boards

Modular contactor for installation into distribution boards Modular contactor for installation into distribution boards Description Modular contactors are used for installation in consumer units in dwellings, business premises, hotels, hospitals, shopping centres,

More information

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MV Air Insulated Switchgear TAP17. Technical Data TGOOD MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)

More information

Contactor Types CI 61-98

Contactor Types CI 61-98 MKING MODERN LIVING POSSIBLE Data sheet Contactor s CI 6-98 Contactors CI 6, CI 73, CI 86 and CI 98 switch powers of up to 30 kw, 37 kw, 45 kw and 55 kw respectively under 3 380 V C-3 loads. ccessories

More information

1 Phase electronic contactor (SC 1)

1 Phase electronic contactor (SC 1) 1 Phase electronic contactor (SC 1) - Rated operational voltage up to 600VAC 50/60 Hz - Rated operational current up to 15/30A/50/63A AC-1 - Control voltage from or - Compact modular design 22.5, 45, or

More information