ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters
|
|
- Marianna Walsh
- 6 years ago
- Views:
Transcription
1 ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters Text Book: Chapter 6, Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, Paul I-Hai Lin, Professor of Electrical and Computer Engr. Tech. P.E. States of Indiana & California Dept. of Computer, Electrical and Information Technology Purdue University Fort Wayne Campus Prof. Paul Lin 1 Lecture 6 Contactors and Motor Starters Part 1. Magnetic Contactor Part 2. Contactor Ratings, Enclosures, and Solid State Types Prof. Paul Lin 2 1
2 Part 1. Magnetic Contactor NEMA Definition - Magnetic Contactor A magnetically actuated device for repeatedly establishing or interrupting an electric power. Designed to make and break electric power circuit loads in excess of 15A without being damage. Figure 6-1 Typical magnetic contactor May be for switching AC motor load, not requiring overload protection Includes 3 main contacts, plus 1 auxiliary contact for 3- wire PB control Prof. Paul Lin 3 Part 1. Magnetic Contactor Figure 6-2 Three-pole magnetic contactor Connection for Two circuits Control Circuit Power Circuit Operating principle Voltage => Coil => Current => Magnetic field Coil => energize the stationary iron frame => Electromagnet Draw armature (plunger) => pulling the movable and stationary contacts together Power source => Main circuit current => Load side Prof. Paul Lin 4 2
3 Switching Loads Part 1. Magnetic Contactor Figure 6-3 Contactor used in conjunction with pilot devices Temperature and Liquid Level Control (non motor load) Liquid Level sensor Temperature sensor Heating element On/Off control Solenoid On/Off control Prof. Paul Lin 5 Switching Loads - Motor Load Part 1. Magnetic Contactor Figure 6-4 IEC contactor used in combination with an overload relay module to switch a motor load Two-wire control device: Automatic control applications for pumps, electric heating, air compressors Three-wire control Motor controlled by On/Off PB to initiate and terminate the system processes Prof. Paul Lin 6 3
4 Part 1. Magnetic Contactor Switching Loads High Voltage Load Kept the high voltage away from the operator to increase the safety Use Step-down transformer Primary-side voltage levels: 208, 220, 240, 460, 480, or 600V Secondary-side voltage levels: 12, 24 or 120V Figure 6-5 Heater circuit controlled by a magnetic contactor (page 152) Prof. Paul Lin 7 Figure 6-5 (page 152) Operation of the Circuit Part 1. Magnetic Contactor Prof. Paul Lin 8 4
5 Definite-purpose Contactors Figure 6-6 Electrically and mechanically held lighting contactors Mounted in enclosures Figure 6-7 Mechanically held lighting contactor Part 1. Magnetic Contactor Prof. Paul Lin 9 Part 2. Contactor Rating, Enclosures, and Solid State Types NEMA Ratings Figure 6-22 NEMA contactor size guide Order a contactor by the current, motor horse power, and voltage ratings Copper contact, Silver alloy contact The current rating for each size is an 8-hour open rating the contactor must be operated at least once every 8-hours to prevent copper oxide forming on the tips and causing excessive contact heating Prof. Paul Lin 10 5
6 Part 2. Contactor Rating, Enclosures, and Solid State Types NEMA Ratings Example 6-1. Use the table 6-22 to determine the NEMA size of an AC contactor required for a 480V heating element load with continuous current rating of 80A. Solution: Size 2 rated 45A Size 3 rated 90A NEMA rating 600 volts max Prof. Paul Lin 11 Part 2. Contactor Rating, Enclosures, and Solid State Types NEMA Ratings Load Utilization Categories: Nolinear loads tungsten lamps for lighting (large hot-to-cold resistance ratio: typically 10:1 or higher, current and voltage in phase) Resistive loads: heating elements for furnaces and ovens (constant resistance; current and voltage in phase) Inductive loads: industrial motors and transformers (current lags behind voltage) Capacitive loads: industrial capacitors for power factor correction (current leads voltage) Prof. Paul Lin 12 6
7 Part 2. Contactor Rating, Enclosures, and Solid State Types IEC Ratings Downsized to provide higher ratings in a smaller package IEC devices are 30 to 70 percent smaller than their NEMA counterparts Evaluated the contactor to meet the requirements of a number of defined applications. AC Categories AC-1: for all AC loads where the PF is at least 0.95; primarily for noninductive or slightly inductive loads AC-3: for squirrel-cage motors where the breaking of the power contacts would occur while motor is running. On closing, the contactor experiences an inrush current: 5 to 8 times the nominal motor current, and the voltage at terminals is approximately 20 percent of line voltage. AC-4: for the starting and breaking of a squirrel-case motor during an inch or plug reverse. Prof. Paul Lin 13 Part 2. Contactor Rating, Enclosures, and Solid State Types IEC Ratings DC Categories DC-1: This applies to all DC loads where the time constant (L/R) is less than or equal to 1 ms; primarily for noninductive or slightly inductive loads DC-2: This applies to the breaking of shunt motors while they are running. On closing, the contactor makes the inrush current around 2.5 times the nominal current DC-3: This applies to the starting and breaking of a shunt motor during inching or plugging. DC-5: This applies to the starting and breaking of a series motor during inching or plugging. Prof. Paul Lin 14 7
8 Part 2. Contactor Rating, Enclosures, and Solid State Types Contactor Enclosures Environmental factors: Expose to damaging fumes Operating in damp places Exposure to excessive dust Subject to vibration, shocks, and tilting Subject to high ambient air temperature NEMA Enclosures: Nonhazadous-location enclosure General purpose Watertight Oil-tight Dust-tight Hazadous-location enclosure Gaseous vapors (acetylene, hydrogen, gasoline, etc) Combustible dusts (meta dust, coal dust, grain dust, etc) Prof. Paul Lin 15 Part 2. Contactor Rating, Enclosures, and Solid State Types Figure 6-24 Typical contactor enclosure types NEMA Type 1 general purpose type NEMA Type 4 and 4X watertight and dust tight NEMA Type 12 provides a degree of protection from noncorrosive dripping liquids, falling dirt, and dust NEMA Type 7 and 9 for used in hazardous locations Prof. Paul Lin 16 8
9 Part 2. Contactor Rating, Enclosures, and Solid State Types Solid-State Contactor Solid-state switching refers to interruption of power by non-mechanical electronics means; Figure 6-25 Single-pole solid state contactor Figure 6-26 Silicon Controlled Rectifier switching semiconductor Prof. Paul Lin 17 Part 2. Contactor Rating, Enclosures, and Solid State Types SCR Theory and Biasing Prof. Paul Lin 18 9
10 Part 2. Contactor Rating, Enclosures, and Solid State Types Figure 6-29 SCR snubber circuit Figure 6-30 Solid-state contactor digital control Prof. Paul Lin 19 Magnetic Motor Starters Motor Overcurrent Protection Motor Overload Relays Thermal Overload Relays Electronic Overload Relays Dual Element Fuse NEMA and IEC Symbols Prof. Paul Lin 20 10
11 Magnetic Motor Starter Magnetic contactor - for switching power in resistance heating elements, lighting, magnetic brakes, and heavy industrial solenoids A contactor with an overload protective device (overload relay) Overload protective device protects motors from overheating and burning up. Figure 6-31 Magnetic Motor Starter (with some manufacturer installed control wiring) Prof. Paul Lin 21 Magnetic Motor Starter Two-, three, or four-pole magnetic contactor An overload relay Suitable enclosure Figure 6-32 Magnetic motor starter enclosure General-purpose sheet-metal Dust-tight Water-tight Explosion resisting Start/Stop PB may be mounted in the cover of the enclosure Prof. Paul Lin 22 11
12 Magnetic Motor Starter Figure 6-33 Magnetic motor starter with separately mounted start-stop pushbutton station Start/Stop PB may be mounted in the cover of the enclosure Prof. Paul Lin 23 Motor Overcurrent Protection Figure 6-34 Major functional blocks for motor operation Motor circuit and controller disconnecting means Motor branch short-circuit and ground-fault protection Motor controller and overload protection Sometimes motor disconnecting means, often referred to as the at the motor disconnecting means Prof. Paul Lin 24 12
13 Motor Overcurrent Protection Figure 6-35 Motor overcurrent protection Hot-circuit and ground-fault motor protection Overload protection Prof. Paul Lin 25 Motor Overcurrent Protection Figure 6-36 The basic difference between a contactor and motor starter is the addition of overload relays. Prof. Paul Lin 26 13
14 Motor Overload Relays Overload relays are designed to meet the special protective needs of motor control circuits. Overload relays are rated by a trip class define the length of time it will take for the relay to trip in an overload condition. Most common trip classes: Class 10: trip motor offline in 4-10 sec at 600 percent of the fullload amperes Class 20: trip in 6-20 seconds Class 30: trip in 9-30 seconds Prof. Paul Lin 27 Motor Overload Relays Overload protection devices have Trip Indicator Reset: manual/automatic Nominal current setting Figure 6-37 Overload relay trip indicator Prof. Paul Lin 28 14
15 Motor Overload Relays Thermal Overload Relays, Figure 6-38 A heater is connected in series with the motor supply. Two types Melting alloy Bimetallic Figure 6-39 Melting alloy-type thermal overload relay Prof. Paul Lin 29 Motor Overload Relays Figure 6-40 Bimetallic type of thermal overload relay Prof. Paul Lin 30 15
16 Motor Overload Relays Figure 6-41 Thermal overload relay circuit operation Figure 6-42 Typical motor overload heater selection chart Prof. Paul Lin 31 Electronic Overload Relays Figure 6-43 Thermal overload relay circuit operation Figure 6-44 Electronic solid-state overload relay Prof. Paul Lin 32 16
17 Electronic Overload Relays Figure 6-45 Microprocessor-based type modular overload relay Prof. Paul Lin 33 Dual Element Fuse Figure 6-46 Dual-element fuse Prof. Paul Lin 34 17
18 NEMA and IEC Symbols Figure 6-47 Comparison of NEMA and IEC symbols Prof. Paul Lin 35 NEMA and IEC Symbols Figure 6-48 Typical NEMA and IEC symbols found in a motor control schematic Prof. Paul Lin 36 18
19 Summary & Conclusion Questions? Contact Prof. Lin through: Prof. Paul Lin 37 19
ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters (2 of 2) Lecture 6 Contactors and Motor Starters
ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters (2 of 2) Text Book: Chapter 6, Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015.
More informationECET 211 Electric Machines & Controls Lecture 2-3 (Part 3 of 3) Symbols and Drawing for Electric Motor Control Systems
ECET 211 Electric Machines & Controls Lecture 2-3 (Part 3 of 3) Symbols and Drawing for Electric Motor Control Systems Text Book: Chapter 2. Understanding Electrical Drawings, Electric Motors and Control
More informationECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits
ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Paul I-Hai Lin, Professor
More informationECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (2 of 2) Lecture 8 Motor Control Circuits
ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (2 of 2) Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Paul I-Hai Lin, Professor
More informationECET 211 Electric Machines & Controls Lecture 3-1 (Part 1 of 2) Motors, Transformers and Distribution Systems
ECET 211 Electric Machines & Controls Lecture 3-1 (Part 1 of 2) Motors, Transformers and Distribution Systems Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw
More informationECET 211 Electric Machines & Controls Lecture 2-2 (Part 2 of 3) Symbols and Drawing for Electric Motor Control Systems
ECET 211 Electric Machines & Controls Lecture 2-2 (Part 2 of 3) Symbols and Drawing for Electric Motor Control Systems Text Book: Chapter 2. Understanding Electrical Drawings, Electric Motors and Control
More informationECET 211 Electric Machines & Controls Lecture 1-3 (Part 2) Electrical Safety in the Workplace Electrical Safety in the Workplace
ECET 211 Electric Machines & Controls Lecture 1-3 (Part 2) Electrical Safety in the Workplace Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Other
More informationECET 211 Electric Machines & Controls Lecture 4-1 Motor Control Devices: Lecture 4 Motor Control Devices
ECET 211 Electric Machines & Controls Lecture 4-1 Motor Control Devices: Part 1. Manually Operated Switch Part 2. Mechanically Operated Switch Text Book: Electric Motors and Control Systems, by Frank D.
More informationECET 211 Electric Machines & Controls Lecture 5-1 Electric Motors. Lecture 5-1 Electric Motors
ECET 211 Electric Machines & Controls Lecture 5-1 Electric Motors (2 of 4) Text Book: Chapter 5 Electric Motors, Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015.
More informationMAGNETIC MOTOR STARTERS
Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors
More informationECET 211 Electric Machines & Controls Lecture 5-4 Electric Motors. Lecture 5-4 Electric Motors
ECET 211 Electric Machines & Controls Lecture 5-4 Electric Motors (4 of 4) Text Book: Chapter 5 Electric Motors, Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015.
More informationECET 211 Electric Machines & Controls Lecture 5-1 Electric Motors. Lecture 5-1 Electric Motors
ECET 211 Electric Machines & Controls Lecture 5-1 Electric Motors (1 of 4) Text Book: Chapter 5 Electric Motors, Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015.
More informationTHE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing
Introduction A contactor is an electrical device which is used for switching an electrical circuit on or off. It is considered to be a special type of relay. However, the basic difference between the relay
More informationModule 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS
1 Module 2 CONTROL SYSTEM COMPONENTS Lecture - 4 RELAYS Shameer A Koya Introduction Relays are generally used to accept information from some form of sensing device and convert it into proper power level,
More informationAF series contactors (9 2650)
R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00
More informationMOTOR CONTROLLERS. STATE the function of motor controllers.
Electrical Distribution Systems Motor controllers range from a simple toggle switch to a complex system using solenoids, relays, and timers. The basic functions of a motor controller are to control and
More informationDirect On Line (DOL) Motor Starter. Direct Online Motor Starter
Direct On Line (DOL) Motor Starter Direct Online Motor Starter Different starting methods are employed for starting induction motors because Induction Motor draws more starting current during starting.
More informationAF series contactors (9 2650)
R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00
More informationTypes of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:
Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor.
More informationElectrical Control System Components Basics of Magnetic Control :
Electrical Control System Components Basics of Magnetic Control : Dr.M.S.Narkhede, LEE, GP Mumbai 1 Contact Types : Contacts are classified into different ways as follows. According to applications contacts
More informationECET 211 Electric Machines & Controls Lecture 1-4 (Part 1) Electrical Safety in the Workplace Electrical Safety in the Workplace
ECET 211 Electric Machines & Controls Lecture 1-4 (Part 1) Electrical Safety in the Workplace Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Other
More informationSECTION MOTOR CONTROL
SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters
More information3. Coils shall be of molded construction
.7-4 Motor Starters & Contactors Low Voltage Enclosures General Non-Combination Starters January 00 Sheet 8 0 7 8 9 4 Non-Combination Starters Maximum hp, Volts Typical Non-Combination Starter Application
More informationElectrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition)
Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition) 1. Which drawing type shows physical details as seen by the eye? 2. Which drawing is similar to a pictorial drawing but has
More informationProgrammable Logic Controller. Mat Nor Mohamad
Programmable Logic Controller Mat Nor Mohamad Relays Electromagnetic Control Relays The PLC's original purpose was the replacement of electromagnetic relays with a solid-state switching system that could
More informationChapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits.
Chapter 8 Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits. Article 430 of the NEC covers application and installation of
More informationIEC Utilization Categories (Explanation)
IEC Utilization Categories (Explanation) IEC Utilization Categories Voltage Category Typical Applications A.C. A.C. and D.C. D.C. AC AC AC AC ACa ACb AC6a AC6b AC7a AC7b AC8a AC8b AC AC AC AC AC AC AC
More informationMOTOR TERMINAL CONNECTIONS
MOTOR TERMINAL CONNECTIONS Motor Classification Most of the industrial machines in use today are driven by electric motors Motors are classified according to the type of power used (AC or DC) and the motors
More informationECN A A A - B - C - D - E - F - A - B - C - D - E - F - NEMA Size 5 - Size Size Size Size Size 9
February 999 NEA Freedom Contactors and ers Catalog Number Selection - ECN A A F - Design N = Nema odification Codes (See Pages -6 to -) Class Page 0 - Contactors -4 0 - Reversing Contactors -8 05 - FVNR
More informationXT IEC Power Control Manual Motor Protectors
May 07 Product Selection Table 7. Rotary with Screw Terminals Global Ratings and North American Ratings Type and Type 2 Coordination Motor Protective Device with Thermal and Magnetic Trip Rated Uninterrupted
More informationECET 211 Electric Machines & Control Lecture 1-1 Electrical Power Generation, Transmission and Distribution
ECET 211 Electric Machines & Control Lecture 1-1 Electrical Power Generation, Transmission and Distribution Paul I-Hai Lin, Professor of Electrical and Computer Engineering Technology P.E. States of Indiana
More informationElectric Motor Controls BOMA Pre-Quiz
Electric Motor Controls BOMA Pre-Quiz Name: 1. How does a U.P.S. (uninterruptable power supply) work? A. AC rectified to DC batteries then inverted to AC B. Batteries generate DC power C. Generator, batteries,
More informationNEMA Contactors & Starters (Freedom)
Page 1 February, 1 Supersedes TIP AN1, AN, CN1, CN Pages 1-0, Dated 1/1/4 ECN01, ECN0, ECN0, ECN0, ECN0 AN1, AN, CN1 & CN Sizes 00-, 00V Max. Non-Reversing & Reversing NEMA Type Enclosures 1, R, 4X & 1
More informationCI-TI Contactors and motor starters Types CI 61 - CI 98
Data sheet CI-TI Contactors and motor starters s CI 6 - CI 98 Contactors CI 6, CI 7, CI 86 and CI 98 switch powers of up to 0 kw, 7 kw, 45 kw and 55 kw respectively under 80 V - loads. Accessories include
More informationMotor Protection. Presented By. Scott Peele PE
Motor Protection Presented By Scott Peele PE Motor Protection Overload on the motor load Fuses Heater Magnetic relay Short Circuit on motor circuit Fuses Breakers Single Phasing Overload Protection NEC
More informationMotor Protection Fundamentals. Motor Protection - Agenda
Motor Protection Fundamentals IEEE SF Power and Energy Society May 29, 2015 Ali Kazemi, PE Regional Technical Manager Schweitzer Engineering Laboratories Irvine, CA Copyright SEL 2015 Motor Protection
More informationDesensitizing Electric Motor Controls
Pacific Gas and Electric Company Desensitizing Electric Motor Controls Introduction. This note is not meant to be a complete discussion of this topic; it is only an attempt to explain some basic operating
More informationSIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC
c c SIEMENS Series 8100oT Vacuum Controllers Bulletin CC3802-02 Technological Development Vacuum technology has developed rapidly in recent years and is becoming widely accepted for medium voltage motor
More information3.1. NEMA Manual Starters. Contents Description Types B230, B330, Switches... MS Series, Single-Phase Starters...
Product Description The B100 Manual Motor Starters can be used in single-phase applications rated hp at 240 Vac or 2 hp at 20 Vdc. The starter can also be rated for three-phase applications up to 10 hp
More informationABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet
ABB Instruction Leaflet 41-137.2E Effective: February 1994 Supersedes I.L. 41-137.2D, Dated February 1973 ( )Denotes Change Since Previous Issue. Type KRV Directional Before putting relays into service,
More informationMagnetic Overload Relays
Magnetic Overload Relays Series N147 Series N147 Overload Relays are of the magnetically operated self reset type, designed for use on or motor starters and controllers for Navy Service A applications.
More informationElectrical Motor Controls (Fourth Edition)
Electrical Motor Controls (Fourth Edition) 1. Which drawing type shows physical details as seen by the eye? Pictorial Drawing 2. Which drawing is similar to a pictorial drawing but has circles or rectangles
More informationContactor Types CI 61-98
MKING MODERN LIVING POSSIBLE Data sheet Contactor s CI 6-98 Contactors CI 6, CI 73, CI 86 and CI 98 switch powers of up to 30 kw, 37 kw, 45 kw and 55 kw respectively under 3 380 V C-3 loads. ccessories
More informationDATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.
DATASHEET - DILMC9-10(24VDC) Technical data General Contactor, 3p+1N/O, 4kW/400V/AC3 Part no. DILMC9-10(24VDC) Catalog No. 277468 Eaton Catalog No. XTCEC009B10TD EL-Nummer 4110305 (Norway) Standards IEC/EN
More informationMAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-
MKING MODERN LIVING POSSIBLE Technical brochure Minicontactors CI 5- www.danfoss.com 2 IC.PD.C10.F3.02-520B4167 Danfoss /S, C-SMC, mr, 07-2010 Contents Page Minicontactor CI 5- Introduction...............................................................................4
More informationKtec Contactors and thermal overloads
Contactors and thermal overloads Techna KTEC series contactors provide a complete solution for your ac contactor requirements.the range carries TUV, UL & CSA certification, for use in Europe, North America
More informationAdapted from presentation developed by Scott Fausneaucht
Adapted from presentation developed by Scott Fausneaucht Definition of Electricity Electrical Fundamentals Generation & Transmission Transformers Fuses & Circuit Breakers Motors Motor Controls Safety Not
More informationOverview V10-T1-2 V10-T1-2 V10-T1-3 V10-T1-4 V10-T1-5 V10-T1-6 V10-T1-7 V10-T1-7 V10-T1-8
Enclosed Control. Welcome............................................... Eaton Corporation........................................ Eaton Support and Service Center Capabilities.................. Technical
More informationExercise 1-5. Current Protection Devices EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Circuit breakers
Exercise 1-5 Current Protection Devices EXERCISE OBJECTIVE Describe and test the operation of circuit breakers, fuses, and overload relays. DISCUSSION OUTLINE The Discussion of this exercise covers the
More informationEnclosures. See Section Typical Description
January 00 Sheet 1187 Motor Starters & Contactors Low Voltage Enclosures General Individual Enclosed, ac Full Voltage.7- Combination Starters Maximum 00 hp, Volts Application Size 1, NEMA 1, Enclosed Magnetic
More informationBasics of Control Components
Basics of Control Components Table of Contents Introduction...2 Electrical Symbols...6 Line Diagrams...16 Overload Protection...22 Overload Relays...26 Manual Control...35 Magnetic Contactors and Starters...41
More informationA Special Note To Our Customers
A Special Note To Our Customers Here s a valuable handbook that you can use right now. This particular reference is taken from one of the video programs in our training series Electrical & Motor Controls
More information3TM Vacuum Contactors
Catalog Extract HG 11.23 Edition 2016 Catalog Extract Medium-Voltage Equipment siemens.com/3tm R-HG11-343.psd 2 Siemens HG 11.23 2016 Contents Medium-Voltage Equipment Catalog Extract HG 11.23 2016 Contents
More informationlectronic starter for single phase duction motor
lectronic starter for single phase duction motor PROJECT NO: 104 SUPERVISOR: DR. WEKESA EXAMINER: PROF MANG OLI Prepared by: GITONGA HILDA WANJIKU- F17/39921/2011 PROJECT OUTLINE 1. Project Objective 2.
More informationECET Circuit Design Motor Loads. Branch Circuits. Article 210
ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Circuit Design Motor Loads Branch Circuits Article 210 210.1 Scope This article covers branch circuits except for those that supply
More informationA. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:
SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification
More informationStarting of Induction Motors
1- Star Delta Starter The method achieved low starting current by first connecting the stator winding in star configuration, and then after the motor reaches a certain speed, throw switch changes the winding
More informationOther Devices. Installation Contactors Z-SCH. Connection diagrams Z-SCH NO 3 NO / 1 NC. Permitted Installation Positions
Installation Contactors Z-SCH These switching devices have been designed and rated particularly for modular installation in modular distribution boxes for electrical installation or cabinets with device
More informationEngineering Information. Solenoid Valves Principles of Operation. Solenoid Valves. Direct Acting Valves (Figures 1A, 1B)
4 Engineering Information Principles of Operation A solenoid valve is a combination of two basic functional units: A solenoid (electromagnet) with its core A valve body containing one or more orifices
More informationApproved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN
Motor Contactor Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN rail) up to 45 kw Range from 4 to 110 kw (AC 3, 380/415V) Finger proof ( VBG 4) Accessoires
More informationAC Relays. Type IC5182. Ordering Information. Control Power Requirements. Contact Ratings (Amperes)
AC Relays Type IC5182 Series N147 Overload Relays are of the magnetically operated self reset type, designed for use on A.C. or D.C. motor starters and controllers for Navy Service A applications. Specification
More informationWARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.
SECTION 230513 - MOTORS AND ADJUSTABLE SPEED DRIVES PART 1 - GENERAL 1.1 DESCRIPTION A. Provide labor, materials, equipment and services as required for the complete installation designed in Contract Documents.
More informationTechnical Information
C5 C5- C5- C5- C5- C5-550 ➊ 700 860 1000 1200 Rated Insulation Voltage U i to IEC 947-1 [V] 1000V 1000V 1000V 690V 690V UL/CS [V] 600V Rated Impulse Voltage U imp C5-550 / 700 / 860 [kv] 3.5 C5-1000 /
More informationHazardous Factory Sealed Control Devices
Hazardous Factory Sealed Control Devices Description Page No. Application/Selection 428, 429 Dimensions 40 Manual Motor Starting Switches & Enclosures EDS Series 440, 44 Pilot Lights EFS Series 45 Pilot
More informationSECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
More informationA. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:
SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationSafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure
2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear
More informationCh 4 Motor Control Devices
Ch 4 Motor Control Devices Part 1 Manually Operated Switches 1. List three examples of primary motor control devices. (P 66) Answer: Motor contactor, starter, and controller or anything that control the
More informationSelection Guide Motor Control Device Solutions
Selection Guide Motor Control Device Solutions Expect more and get it from c3controls. Our portfolio of Motor Control Devices consists of worldclass products designed and manufactured to meet your requirements
More informationAF40... AF96 3-pole contactors Technical data
Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional
More informationA200 NEMA Contactors and Starters A200
Starters Non-reversing and Reversing 11 Not to be used for construction purposes unless approved. Table 11. Open Reversing Starters Dimensions NEM of Poles Fig. Mounting Dimensions in Inches (mm) Screws
More informationProtectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.
Types MS116, MS132, MS5x, MS9x are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/OFF control, and protection against short circuit,
More informationSWITCHGEAR. 4G cam switches
SWITCHGEAR 178 4G cam switches ENERGY SAFELY SWITCHED 179 SWITCHGEAR 180 GENERAL INFORMATION 4G-series cam switches are low voltage switches, designed according to the latest knowledge about switchgear
More informationSECTION MOTORS & MOTOR CONTROLLERS
SECTION 15170 MOTORS & MOTOR CONTROLLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Electric motors. B. Motor controllers for Packaged equipment. 1.02 SUBMITTALS A. Wiring diagrams with electrical characteristics
More informationCOM Overcurrent Relay
41-102.1B COM Overcurrent Relay Figure 1: COM-5 Class 1E Relay (Front View) 9664A28 Photo Figure 2: COM-5 Class 1E Relay (Rear View) 9664A29 Photo Photo needed here 2 COM Overcurrent Relay 41-102.1B 3
More information9/7/2010. Chapter , The McGraw-Hill Companies, Inc. MOTOR CLASSIFICATION. 2010, The McGraw-Hill Companies, Inc.
Chapter 2 MOTOR CLASSIFICATION 1 In general, motors are classified according to the type of power used (AC or DC) and the motor's principle of operation. AC DC Motor Family Tree 2 DC MOTOR CONNECTIONS
More informationSafeGear TM Motor Control Center Arc resistant metal-clad construction
SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor
More informationThe Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller
The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller A pre-engineered solution with an integrated circuit breaker disconnect and an Altistart 22 soft start in a stand-alone enclosure Make the
More informationELECTROGALVANIZED ALUMINUM ACRYLIC PAINTED FERALOY IRON ALLOY
EDSC210 -Way Switch Cooper Crouse-Hinds Catalog Number Manufacturer Description Weight per unit Product Category Features Box Type Contact Configuration Current Rating Voltage Rating Material, Color, and
More informationSALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN
Form 1254 BRAKETRON Electronic Motor Brake Instructions SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN TABLE OF CONTENTS SECTION TITLE PAGE I. Introduction 1 II. Specifications 1 III. Principles
More information4.0 OPERATION Type ITH-T Relay
41-771.2 Type ITH-T Relay 3.3 OPERATION INDICATOR This operation indicator is a small solenoid coil connected in the trip circuit. When the coil is energized a spring-restrained armature releases the white
More informationA - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION
ABB Effective: November 1990 This Addendum Supersedes all Previous Addenda Addendum to Instruction Leaflet 41-137.3H Type KRD-4 Directional Overcurrent Ground Relay A - Add New Information C - Change Existing
More informationLatch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5
3-pole DC Operated Ratings Rated Aux. Contacts Type Coil voltage 1) AC2 Current Built-in Additional 24 24V= DC 5 AC3 see 48 60V= DC 6 380V AC1 page 34 110 110V= DC 7 400V 660V 220 220V= DC 8 415V 690V
More informationType S Contactors and Starters
Type S Contactors and Starters Class 8536/8502/8736/8702/8810/8811/8812 CONTENTS Description Page Magnetic Contactors and Starters.......................................1 Reversing Magnetic Starters and
More informationTA Ta VA CTRL-XFRMR
3804 South Street 7964-7263, TX Nacogdoches Phone: 936-69-7941 Fax: 936-60-468 TA2437 Ta-2-437 10VA CTRL-XFRMR Acme Electric Catalog Number TA2437 Manufacturer Acme Electric Description Control Transformer,
More informationAF09... AF30 3-pole Contactors up to 25 HP / 600 VAC
AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24
More informationPower System Solutions (PSS)
About Power System Solutions mission The Power System Solutions Mission Statement To achieve customer satisfaction by providing innovative solutions to improve upon power quality, energy efficiency, and
More informationPower systems Protection course
Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used
More informationECET Distribution System Protection. Overcurrent Protection
ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Distribution System Protection Overcurrent Protection One of the most important aspects of distribution system design is system protection.
More informationPage. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases
Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar
More information3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00,
Low-Voltage Controls and Distribution > Industrial Controls > Protection Equipment > Circuit Breakers/Motor Starter Protectors > Motor Starter Protectors SIRIUS RV up to 00 A RV0-0DA5 CIRCUIT-BREAKER,
More informationAF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals
AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals 25 to 55 A culus CE Application AF09... AF38 4-pole contactors are used for controlling power circuits up to 600 V AC and 240 V DC.
More informationComponents for EEx e Panels
Circuit Interrupters / Motor Switches 8006/3 8543/1 8543/2 8548/2 40 A 63 A 80 A 1 160 A 500 V 660 V 500 V 01766E00 No. of poles 12 poles Isolator features Switching capacity 400 V, AC3 11 kw 22 kw 37
More informationThe Contactor. Antonino Daviu, Jose Alfonso Departamento de Ingeniería Eléctrica. Universitat Politècnica de València
The Contactor Surnames, name Antonino Daviu, Jose Alfonso (joanda@die.upv.es) Department Centre Departamento de Ingeniería Eléctrica Universitat Politècnica de València 1 1 Summary The aim of this paper
More informationInstallation Sheet January, 2016 Supersedes February, 2013
s Installation Sheet January, 016 Supersedes February, 013 E87010-A0104-T003-A6-CLM0 Lighting and Heating Contactor 30 Amp, 3, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting
More informationAF09... AF30 3-pole Contactors up to 20 HP / 480 VAC
AF0... AF0 -pole Contactors up to 20 HP / 480 VAC Contactors and Overload Relays Overview...2 AF0... AF0 -pole Contactors Ordering Details...4 Main Technical Data...20 DC Circuit switching...2 Main Accessory
More informationIndustrial Control Transformers
6 Industrial Control Transformers Section 6 Industrial Control Transformers provide a low and safe control voltage for the operation of electromagnetic devices, such as motor starters, contactors, solenoids
More informationAC Rectifiers for use with Armature Actuated Brakes. Product Overview. Full Wave. Half Wave. Combination Full and Half Wave. TOR-AC Full and Half Wave
Rectifiers for use with Armature Actuated Brakes Product Overview NOTE: For brake response times with and without rectifiers see page 94. Full Wave A rectifier in which both positive and negative half-cycles
More informationGeneral + Definite Purpose Contactors
General + Definite Purpose General Information... 2 Horse Power Rating Charts... 4 Contact Life... 8 Contactor Number Structure... Series C8 Miniature and Starters... 3 ccessories... 2 Contactor Cross
More informationDesign Standard. Purpose: Design Standard:
Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard
More information