AGENDA. NEC Code-Making Panel 12. Report on Proposal Meeting DATES: 1/19/2012 1/21/2012. Hilton Head, SC
|
|
- Edith Knight
- 5 years ago
- Views:
Transcription
1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: AGENDA NEC Code-Making Panel 12 Report on Proposal Meeting DATES: 1/19/2012 1/21/2012 Hilton Head, SC Item No. Subject Call to Order Introduction of Members and Guests Review of Meeting Procedures and Revision Schedule Comments/Questions from Committee Members and/or Guests Task Group Reports a. Editorial Task Group b. Electric Vehicle Task Group Processing of Proposals Fire Protection Research Foundation Requests Old Business New Business Adjournment
2 Chair Report 11/25/2011 Log Proposal No. Code Reference Log Proposal No. Code Reference 1170k 12-1 Entire Document Exception 921k 12-2 Entire Document Portable Equipment (New) (C) (C) (C) (B) (B) (B) (2) (2) Control Room (for Machine Room (for (A) and (C) d , 640.3, 640.9, and Exception (New) (A)(1)(c) (A)(3)(e) (A) (A) (A) (A) Exception No (A) Exception No (C)(1) (C)(1) (C)(1) (C)(2) (B) Exception (New) Electric Vehicle Electric Vehicle Electric Vehicle Inlet Electric Vehicle Wireless Charging (New) (D), Table (D)(1), (B) (New) Cord Connector Truck Flanged Surface (D) (B) Exception (B)(1) (C) (C) 1
3 Chair Report 11/25/2011 Log Proposal No. Code Reference Log Proposal No. Code Reference (C) (A) (A) (A) Audio Amplifier or Audio Autotransformer Audio Signal Processing Equipment Rack Loudspeaker Maximum Output Power Mixer-Amplifier Powered Loudspeaker Powered Loudspeaker Rated Load Impedance Rated Output Voltage Rated Output Voltage Temporary Equipment (A) (B) (B) (2) and 645.5(2) (New) (2) (E)(2) (E)(2), Table 645.5, and (E)(2) (E)(2) (E)(2) (E)(2) (E)(2) (E)(2) (E)(2) (E)(2) (E)(2) (E)(2) (E)(3) (E)(4) (E)(5) (E)(6) , Informational Note (A)(2) (B) and (New) (B) (B)(5) (New) (New) (New) (New) (New) X (New) (A) (A)(2) (A) (A) (C) Converting Device Heating Equipment Cell Line Attachments (A) (C)(2) (C)(2) (C)(2) Industrial Machinery (New)
4 12-1 Log #1170k NEC-P12 Russell LeBlanc, The Peterson School In articles 90 through 830, if the wording is not already there, then add the words (or other structure(s)) after the word BUILDING(S) wherever the intent of the requirement is to also include STRUCTURES as well as buildings. There is a flaw in the NEC. The term "building" is used over 1000 times in the NEC, and in most of the cases the words "or other structure" should follow and apply the same requirements to bridges, billboards, towers, tanks, and other structures that are by definition NOT BUILDINGS. One specific example I can use is section Wiring on Buildings. I believe that this section is also intended to be applied structures, but the wording "or other structures" is not in the heading or the paragraph. There are literally thousands of other instances throughout the code that this same problem exists. This can easily be seen by doing an electronic search for the word "building". In some cases the words "or other structure" (or similar wording) are present, but in the vast majority where the requirements should also be applied to structures other than buildings, the wording is not there Log #921k NEC-P12 Joe Tedesco, Boston, MA The term "adequate" and "adequately" and "inadequately" and "inadequate" should be replaced with terms that can be properly enforced and understood. Terms are not defined and are considered vague and unenforceable per Table in the NEC Style Manaual. They are all "incorrect" 148 times in the NEC Log #2897 NEC-P12 James F. Williams, Fairmont, WV Equipment with electrical components intended to be moved from one place to another. Equipment fed with portable cords or cables intended to be moved from one place to another. The defined term is referenced in several articles of the NEC: 100 I Electric Sign, 110, 210, 250, 368, 400, 430, 490, 500, 501, 505, 511, 513, 514, 515, 516, 517, 518, 520, 525, 530, 545, 600, 640, 668, 680 It is defined in 513.2, 520.2, 530.2, 640.2, & Suggest that a single definition in 100 I is better. In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the. 1
5 12-4 Log #2770 NEC-P12 James F. Williams, Fairmont, WV Where flexible connections are necessary, flexible stranded conductors shall be used. Conductors shall be in flexible metal conduit, liquidtight flexible metal conduit, liquidtight flexible nonmetallic conduit, or multiconductor cable, or an approved nonmetallic flexible raceway. Are there any approved nonmetallic flexible raceway other than LFNC? 12-5 Log #2838 NEC-P12 James F. Williams, Fairmont, WV Where flexible connections are necessary, flexible stranded conductors shall be used. Conductors shall be in flexible metal conduit, liquidtight flexible metal conduit (LFMC), liquidtight flexible nonmetallic conduit, multiconductor cable, or an approved nonmetallic flexible raceway. "Liquidtight Flexible Metal Conduit" is also referred to as LFMC Suggest that (LFNC) be added to all references. This will make finding all references to " Liquidtight Flexible Metal Conduit " easier and more reliable Log #2865 NEC-P12 James F. Williams, Fairmont, WV Add text to read as follows: Where flexible connections are necessary, flexible stranded conductors shall be used. Conductors shall be in flexible metal conduit, liquidtight flexible metal conduit, liquidtight flexible nonmetallic conduit (LFNC), multiconductor cable, or an approved nonmetallic flexible raceway. "Liquidtight Flexible Nonmetallic Conduit" is also referred to as LFNC Suggest that (LFNC) be added to all references. This will make finding all references to "Liquidtight Flexible Nonmetallic Conduit" easier and more reliable. 2
6 12-7 Log #1824 NEC-P12 James F. Williams, Fairmont, WV A bushing shall be permitted to be used in lieu of a box at the end of a rigid metal conduit, intermediate metal conduit, or electrical metallic tubing (EMT) where the raceway terminates at unenclosed controls or similar equipment, including contact conductors, collectors, resistors, brakes, power-circuit limit switches, and dc split-frame motors. "electrical metallic tubing" is also referred to as EMT Suggest that "EMT" be added to all references. This will make finding all references to "electrical metallic tubing" easier and more reliable. [The following files are related: 100_EMT, 225_EMT, 230_EMT, 250_EMT, 300_EMT, 334_EMT, 374_EMT, 392_EMT, 398_EMT, 424_EMT, 426_EMT, 427_EMT, 430_EMT, 502_EMT, 503_EMT, 506_EMT, 517_EMT, 520_EMT, 550_EMT, 551_EMT, 552_EMT, 600_EMT, 610_EMT, 620_EMT, 645_EMT, 680_EMT, 695_EMT, 725_EMT, 760_EMT] 12-8 Log #2414 NEC-P12 James F. Williams, Fairmont, WV Add text to read as follows: A bushing shall be permitted to be used in lieu of a box at the end of a rigid metal conduit, intermediate metal conduit (IMC), or electrical metallic tubing where the raceway terminates at unenclosed controls or similar equipment, including contact conductors, collectors, resistors, brakes, power-circuit limit switches, and dc split-frame motors.. "Intermediate Metal Conduit" is also referred to as IMC Metallic Conduit Suggest that "IMC" be added to all references. This will make finding all references to Intermediate Metal Conduit" easier and more reliable Log #2438 NEC-P12 James F. Williams, Fairmont, WV A bushing shall be permitted to be used in lieu of a box at the end of a rigid metal conduit (RMC), intermediate metal conduit, or electrical metallic tubing where the raceway terminates at unenclosed controls or similar equipment, including contact conductors, collectors, resistors, brakes, power-circuit limit switches, and dc split-frame motors. "Rigid Metal Conduit" is also referred to as RMC Metallic Conduit Suggest that "RMC" be added to all references. This will make finding all references to "Rigid Metal Conduit" easier and more reliable. 3
7 12-10 Log #675 NEC-P12 Matthew D. Frederick, City of Mattoon Such disconnecting means shall consist of a motor-circuit switch, circuit breaker, fuseable disconnect, or molded case switch. (4) Placed within view when at the furthest point of travel of the runway contact conductors. Many cranes and hoists run entire lengths of factories. Sometimes this allows hundreds of feet of travel. Most cranes are fed from either end which is also a common place for the disconnect location. This does not always afford the "in view" from every place along the crane rail. The current code is vague. Adding "when at the furthest point of travel" defines better the intent of "in view" without applying the much more defined and restrictive "within sight" as in other sections. A disconnect may be "in view" from the feed end of the crane, but at the furthest point not visible. The current code does not specify what point along the runway contact conductors applies. Furthermore many facilities are designed with fuseable bucket-type disconnects, allowing fuseable disconnects to meet the requirements of only makes sense, as many engineers feel they are superior to breakers or switches Log #303 NEC-P12 Stanley J. Folz, Morse Electric Company (2) Lockable in accordance with Capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted as the means required to be installed at and remain with the equipment. This proposal has been developed by the Usability Task Group assigned by the Technical Correlating Committee. The committee members were Stanley Folz, James Dollard, William Fiske, David Hittinger, Andy Juhasz, Amos Lowrance, Susan Newman-Scearce, Marc Bernsen and Vincent Zinnante. Requirements for a disconnecting means to be lockable in the open position exist in numerous locations in the NEC. A new section has been proposed in Article 110 to consolidate the requirements for a disconnecting means required to be capable of being locked in the open position in a single section for clarity. It is understood that this requirement includes more than disconnecting and locking electrical power sources. This proposal is intended to facilitate a lockout/tagout scenario. It is equally important to ensure that the means for placing the lock remain in place. The concept suggested by this proposal is necessary to provide correlation throughout the NEC with respect to the capability of placing a lock on a disconnecting means to secure it in the open position. 4
8 12-12 Log #483 NEC-P12 Edward G. Kroth, Verona, WI Delete text as follows: (2) Capable of being locked in the open position. The provisions for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted as the means required to be installed at and remain with the equipment. The rest of this section is to remain the same. This is a companion proposal to one submitted to Code-Making Panel 1 and should be accepted only if said proposal or some equivalent proposal is accepted by Code-Making Panel 1. Said proposal is to put the criteria for a lockable disconnecting means in Article 110 and, thus, be able to eliminate similar repetitions in at least 19 different sections of the NEC. It would also help to standardize the usage of the term "capable of being locked" which has at least four variations in the 2011 NEC Log #304 NEC-P12 Stanley J. Folz, Morse Electric Company A motor-circuit switch, molded-case switch, or circuit breaker shall be provided in the leads from the runway contact conductors or other power supply on all cranes and monorail hoists. The disconnecting means shall be lockable in accordance with capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. Where a monorail hoist or hand-propelled crane bridge This proposal has been developed by the Usability Task Group assigned by the Technical Correlating Committee. The committee members were Stanley Folz, James Dollard, William Fiske, David Hittinger, Andy Juhasz, Amos Lowrance, Susan Newman-Scearce, Marc Bernsen and Vincent Zinnante. Requirements for a disconnecting means to be lockable in the open position exist in numerous locations in the NEC. A new section has been proposed in Article 110 to consolidate the requirements for a disconnecting means required to be capable of being locked in the open position in a single section for clarity. It is understood that this requirement includes more than disconnecting and locking electrical power sources. This proposal is intended to facilitate a lockout/tagout scenario. It is equally important to ensure that the means for placing the lock remain in place. The concept suggested by this proposal is necessary to provide correlation throughout the NEC with respect to the capability of placing a lock on a disconnecting means to secure it in the open position. 5
9 12-14 Log #1236 NEC-P12 Marcelo M. Hirschler, GBH International An enclosed control space outside the hoistway, intended for full bodily entry, that contains the elevator motor controller. The room could also contain electrical and/or mechanical equipment used directly in connection with the elevator or dumbwaiter but not the electric driving machine or the hydraulic machine. : The room could also contain electrical and/or mechanical equipment used directly in connection with the elevator or dumbwaiter but not the electric driving machine or the hydraulic machine. A space inside or outside the hoistway, intended to be accessed with or without full bodily entry, that contains the elevator motor controller. This space could also contain electrical and/or mechanical equipment used directly in connection with the elevator or dumbwaiter but not the electrical driving machine or the hydraulic machine. : This space could also contain electrical and/or mechanical equipment used directly in connection with the elevator or dumbwaiter but not the electrical driving machine or the hydraulic machine. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note Log #1237 NEC-P12 Marcelo M. Hirschler, GBH International An enclosed machinery space outside the hoistway, intended for full bodily entry, that contains the electrical driving machine or the hydraulic machine. The room could also contain electrical and/or mechanical equipment used directly in connection with the elevator or dumbwaiter. : The room could also contain electrical and/or mechanical equipment used directly in connection with the elevator or dumbwaiter. A space inside or outside the hoistway, intended to be accessed with or without full bodily entry, that contains elevator or dumbwaiter mechanical equipment, and could also contain electrical equipment used directly in connection with the elevator or dumbwaiter. This space could also contain the electrical driving machine or the hydraulic machine. : This space could also contain the electrical driving machine or the hydraulic machine. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note Log #880 NEC-P12 Michael J. Johnston, National Electrical Contractors Association Add a new last sentence as follows: " Where the voltage exceeds 600 volts, warning labels or signs that read DANGER HIGH VOLTAGE shall be attached to the equipment and shall be plainly visible. The danger sign(s) or label(s) shall comply with (B). This proposal is one of several coordinated companion proposals to provide consistency of danger, caution, and warning sign or markings as required in the NEC. The proposed revision will correlate this danger marking requirement with proposed (B) and the requirements in ANSI Z
10 12-17 Log #999 NEC-P12 James T. Dollard, Jr., IBEW Local Union 98 Replace 600V with 1000V. This proposal is the work of the High Voltage Task Group appointed by the Technical Correlating Committee. The task group consisted of the following members: Alan Peterson, Paul Barnhart, Lanny Floyd, Alan Manche, Donny Cook, Vince Saporita, Roger McDaniel, Stan Folz, Eddie Guidry, Tom Adams, Jim Rogers and Jim Dollard. The Task Group identified the demand for increasing voltage levels used in wind generation and photovoltaic systems as an area for consideration to enhance existing NEC requirements to address these new common voltage levels. The task group recognized that general requirements in Chapters 1 through 4 need to be modified before identifying and generating proposals to articles such as 690 specific for PV systems. These systems have moved above 600V and are reaching 1000V due to standard configurations and increases in efficiency and performance. The committee reviewed Chapters 1 through 8 and identified areas where the task group agreed that the increase in voltage was of minimal or no impact to the system installation. Additionally, there were requirements that would have had a serious impact and the task group chose not to submit a proposal for changing the voltage. See table (supporting material) that summarizes all sections considered by the TG. Note: Supporting material is available for review at NFPA Headquarters Log #1000 NEC-P12 James T. Dollard, Jr., IBEW Local Union 98 Replace 600V with 1000V. This proposal is the work of the High Voltage Task Group appointed by the Technical Correlating Committee. The task group consisted of the following members: Alan Peterson, Paul Barnhart, Lanny Floyd, Alan Manche, Donny Cook, Vince Saporita, Roger McDaniel, Stan Folz, Eddie Guidry, Tom Adams, Jim Rogers and Jim Dollard. The Task Group identified the demand for increasing voltage levels used in wind generation and photovoltaic systems as an area for consideration to enhance existing NEC requirements to address these new common voltage levels. The task group recognized that general requirements in Chapters 1 through 4 need to be modified before identifying and generating proposals to articles such as 690 specific for PV systems. These systems have moved above 600V and are reaching 1000V due to standard configurations and increases in efficiency and performance. The committee reviewed Chapters 1 through 8 and identified areas where the task group agreed that the increase in voltage was of minimal or no impact to the system installation. Additionally, there were requirements that would have had a serious impact and the task group chose not to submit a proposal for changing the voltage. See table (supporting material) that summarizes all sections considered by the TG. Note: Supporting material is available for review at NFPA Headquarters. 7
11 12-19 Log #2638d NEC-P12 John R. Kovacik, Underwriters Laboratories Inc. Update the references to UL Standards in the Informational Notes as shown below: The insulation of conductors shall comply with (A) through (D). Informational Note: One method of determining that conductors are flame retardant is by testing the conductors to the VW-1 (Vertical-Wire) Flame Test in ANSI/UL Circuits and equipment shall comply with 640.3(A) through (M), as applicable. See for circuits and equipment installed in ducts or plenums or other space used for environmental air. Informational Note: NFPA 90A-2009,, Section , permits loudspeakers, loudspeaker assemblies, and their accessories listed in accordance with UL ,, to be installed in other spaces used for environmental air (ceiling cavity plenums). Amplifiers with output circuits carrying audio program signals shall be permitted to employ Class 1, Class 2, or Class 3 wiring where the amplifier is listed and marked for use with the specific class of wiring method. Such listing shall ensure the energy output is equivalent to the shock and fire risk of the same class as stated in Article 725. Overcurrent protection shall be provided and shall be permitted to be inherent in the amplifier. Audio amplifier output circuits wired using Class 1 wiring methods shall be considered equivalent to Class 1 circuits and shall be installed in accordance with , where applicable. Audio amplifier output circuits wired using Class 2 or Class 3 wiring methods shall be considered equivalent to Class 2 or Class 3 circuits, respectively. They shall use conductors insulated at not less than the requirements of and shall be installed in accordance with and Informational Note No. 1: ANSI/UL ,, contains requirements for the listing of amplifiers used for fire alarm systems in compliance with -2010,. Informational Note No. 2: Examples of requirements for listing amplifiers used in residential, commercial, and professional use are found in ANSI/UL , ; ANSI/UL , ; ANSI/UL , ; and ANSI/UL ,. (6) Cables, other than those covered in (E)(2) and (E)(3), and those complying with (E)(6)(a) or (E)(6)(b), shall be listed as Type DP cable having adequate fire resistant characteristics suitable for use under raised floors of an information technology equipment room. a. Interconnecting cables enclosed in a raceway. b. Cable type designations shown in Table shall be permitted. Green, or green with one or more yellow stripes, insulated single-conductor cables, 4 AWG and larger, marked for use in cable trays or for CT use shall be permitted for equipment grounding. Informational Note: One method of defining is by establishing that the cables do not spread fire to the top of the tray in the UL Flame Exposure, Vertical Tray Flame Test in UL ,. The smoke measurements in the test method are not applicable. Conductors shall comply with 650.6(A) through (D). Each cable shall be provided with an outer covering, either overall or on each of any subassemblies of grouped conductors. Tape shall be permitted in place of a covering. Where not installed in metal raceway, the covering shall be resistant to flame spread, or the cable or each cable subassembly shall be covered with a closely wound listed fireproof tape. 8
12 Informational Note: One method of determining that cable is resistant to flame spread is by testing the cable to thevw-1 (vertical-wire) flame test in the ANSI/UL ,. References to UL Standards in the NEC should reflect the current edition Log #1825 NEC-P12 James F. Williams, Fairmont, WV Conductors and optical fibers located in hoistways, in escalator and moving walk wellways, in platform lifts, stairway chairlift runways, machinery spaces, control spaces, in or on cars, in machine rooms and control rooms, not including the traveling cables connecting the car or counterweight and hoistway wiring, shall be installed in rigid metal conduit, intermediate metal conduit, electrical metallic tubing (EMT), rigid nonmetallic conduit, or wireways, or shall be Type MC, MI, or AC cable unless otherwise permitted in (A) through (C). "electrical metallic tubing" is also referred to as EMT Suggest that "EMT" be added to all references. This will make finding all references to "electrical metallic tubing" easier and more reliable. [The following files are related: 100_EMT, 225_EMT, 230_EMT, 250_EMT, 300_EMT, 334_EMT, 374_EMT, 392_EMT, 398_EMT, 424_EMT, 426_EMT, 427_EMT, 430_EMT, 502_EMT, 503_EMT, 506_EMT, 517_EMT, 520_EMT, 550_EMT, 551_EMT, 552_EMT, 600_EMT, 610_EMT, 620_EMT, 645_EMT, 680_EMT, 695_EMT, 725_EMT, 760_EMT] Log #1976 NEC-P12 Jonathan R. Althouse, Michigan State University In the third to last line of this paragraph delete rigid nonmetallic conduit and replace with Type PVC conduit, Type RTRC conduit so the paragraph reads as follows:..... shall be installed in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, rigid nonmetallic conduit, Type PVC conduit, Type RTRC conduit, or wireways, or shall be... The reference to rigid nonmetallic conduit is too general, and the actual types of rigid nonmetallic conduit need to be specified Log #2049 NEC-P12 James F. Williams, Fairmont, WV Conductors and optical fibers located in hoistways, in escalator and moving walk wellways, in platform lifts, stairway chairlift runways, machinery spaces, control spaces, in or on cars, in machine rooms and control rooms, not including the traveling cables connecting the car or counterweight and hoistway wiring, shall be installed in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, rigid nonmetallic conduit (PVC), or wireways, or shall be Type MC, MI, or AC cable unless otherwise permitted in (A) through (C). "Rigid Polyvinyl Chloride Conduit" is also referred to as PVC and sometimes as rigid nonmetallic conduit Suggest that "PVC" be added to all references. This will make finding all references to easier and more reliable. 9
13 12-23 Log #2413 NEC-P12 James F. Williams, Fairmont, WV Add text to read as follows: Conductors and optical fibers located in hoistways, in escalator and moving walk wellways, in platform lifts, stairway chairlift runways, machinery spaces, control spaces, in or on cars, in machine rooms and control rooms, not including the traveling cables connecting the car or counterweight and hoistway wiring, shall be installed in rigid metal conduit, intermediate metal conduit (IMC), electrical metallic tubing, rigid nonmetallic conduit, or wireways, or shall be Type MC, MI, or AC cable unless otherwise permitted in (A) through (C). "Intermediate Metal Conduit" is also referred to as IMC Metallic Conduit Suggest that "IMC" be added to all references. This will make finding all references to Intermediate Metal Conduit" easier and more reliable Log #2439 NEC-P12 James F. Williams, Fairmont, WV Conductors and optical fibers located in hoistways, in escalator and moving walk wellways, in platform lifts, stairway chairlift runways, machinery spaces, control spaces, in or on cars, in machine rooms and control rooms, not including the traveling cables connecting the car or counterweight and hoistway wiring, shall be installed in rigid metal conduit (RMC), intermediate metal conduit, electrical metallic tubing, rigid nonmetallic conduit, or wireways, or shall be Type MC, MI, or AC cable unless otherwise permitted in (A) through (C). "Rigid Metal Conduit" is also referred to as RMC Metallic Conduit Suggest that "RMC" be added to all references. This will make finding all references to "Rigid Metal Conduit" easier and more reliable. 10
14 12-25 Log #2805 NEC-P12 James F. Williams, Fairmont, WV (1)(c) (1) Flexible metal conduit (FMC) (a) Flexible metal conduit (FMC), liquidtight flexible metal conduit, or liquidtight flexible nonmetallic conduit of metric designator 12 (trade size 3/8), or larger, not exceeding 1.8 m (6 ft) in length, shall be permitted on cars where so located as to be free from oil and if securely fastened in place. (1) Flexible metal conduit (FMC) (a) Flexible metal conduit (FMC), liquidtight flexible metal conduit, or liquidtight flexible nonmetallic conduit of metric designator 12 (trade size 3/8), or larger, not exceeding 1.8 m (6 ft) in length, shall be permitted between control panels and machine motors, machine brakes, motor-generator sets, disconnecting means, and pumping unit motors and valves. (1) Flexible metal conduit (FMC) Flexible metal conduit (FMC), liquidtight flexible metal conduit, or liquidtight flexible nonmetallic conduit shall be permitted in escalator and moving walk wellways. Flexible metal conduit (FMC) or liquidtight flexible conduit of metric designator 12 (trade size 3/8) shall be permitted in lengths not in excess of 1.8 m (6 ft). Flexible metal conduit (FMC) or liquidtight flexible metal conduit shall be permitted in platform lifts and stairway chairlift runways and machinery spaces. Flexible metal conduit (FMC) or liquidtight flexible conduit of metric designator 12 (trade size 3/8) shall be permitted in lengths not in excess of 1.8 m (6 ft). "Flexible Metal Conduit" is also referred to as FMC Suggest that (FMC) be added to all references. This will make finding all references to "Flexible Metal Conduit" easier and more reliable. 11
15 12-26 Log #2839 NEC-P12 James F. Williams, Fairmont, WV (c)(2) Liquidtight flexible metal conduit (LFMC) (a) Flexible metal conduit, liquidtight flexible metal conduit (LFMC), or liquidtight flexible nonmetallic conduit of metric designator 12 (trade size 3/8), or larger, not exceeding 1.8 m (6 ft) in length, shall be permitted on cars where so located as to be free from oil and if securely fastened in place. )(d)(2) Liquidtight flexible metal conduit (LFMC) )(a) Flexible metal conduit, liquidtight flexible metal conduit (LFMC), or liquidtight flexible nonmetallic conduit of metric designator 12 (trade size 3/8), or larger, not exceeding 1.8 m (6 ft) in length, shall be permitted between control panels and machine motors, machine brakes, motor-generator sets, disconnecting means, and pumping unit motors and valves. )(2) Liquidtight flexible metal conduit (LFMC) Flexible metal conduit, liquidtight flexible metal conduit (LFMC), or liquidtight flexible nonmetallic conduit shall be permitted in escalator and moving walk wellways. Flexible metal conduit or liquidtight flexible conduit (LFMC) of metric designator 12 (trade size 3/8) shall be permitted in lengths not in excess of 1.8 m (6 ft). Flexible metal conduit or liquidtight flexible metal conduit (LFMC) shall be permitted in platform lifts and stairway chairlift runways and machinery spaces. Flexible metal conduit or liquidtight flexible conduit (LFMC) of metric designator 12 (trade size 3/8) shall be permitted in lengths not in excess of 1.8 m (6 ft). "Liquidtight Flexible Metal Conduit" is also referred to as LFMC Suggest that (LFNC) be added to all references. This will make finding all references to " Liquidtight Flexible Metal Conduit " easier and more reliable. 12
16 12-27 Log #2866 NEC-P12 James F. Williams, Fairmont, WV (3) Liquidtight flexible nonmetallic conduit (LFNC) (a) Flexible metal conduit, liquidtight flexible metal conduit, or liquidtight flexible nonmetallic conduit (LFNC) of metric designator 12 (trade size 3/8), or larger, not exceeding 1.8 m (6 ft) in length, shall be permitted on cars where so located as to be free from oil and if securely fastened in place. (3) Liquidtight flexible nonmetallic conduit (LFNC) (a) Flexible metal conduit, liquidtight flexible metal conduit, or liquidtight flexible nonmetallic conduit (LFNC) of metric designator 12 (trade size 3/8), or larger, not exceeding 1.8 m (6 ft) in length, shall be permitted between control panels and machine motors, machine brakes, motor-generator sets, disconnecting means, and pumping unit motors and valves. (3) Liquidtight flexible nonmetallic conduit (LFNC) Flexible metal conduit, liquidtight flexible metal conduit, or liquidtight flexible nonmetallic conduit (LFNC) shall be permitted in escalator and moving walk wellways. Flexible metal conduit or liquidtight flexible conduit (LFNC) of metric designator 12 (trade size 3/8) shall be permitted in lengths not in excess of 1.8 m (6 ft). Flexible metal conduit or liquidtight flexible metal conduit shall be permitted in platform lifts and stairway chairlift runways and machinery spaces. Flexible metal conduit or liquidtight flexible conduit (LFNC) of metric designator 12 (trade size 3/8) shall be permitted in lengths not in excess of 1.8 m (6 ft). "Liquidtight Flexible Nonmetallic Conduit" is also referred to as LFNC Suggest that (LFNC) be added to all references. This will make finding all references to " Liquidtight Flexible Nonmetallic Conduit " easier and more reliable Log #680 NEC-P12 Andy Juhasz, Kone, Inc. Add new exception as follows: Exception: Listed cord and plug connected equipment. In many cases listed cord and plug connected equipment is used within the installation such as computer displays, power supplies, etc. The conductors to/from this equipment are flexible cords and conductors not intended to be run in a raceway. Listed cord and plug connected equipment is intended and should be allowed to be run without a raceway. 13
17 12-29 Log #2316 NEC-P12 Eric Kench, Kench Engineering Consultant Flexible cords and cables that are components of listed equipment and used in circuits operating at 30 volts rms or less or 42 volts dc ac or less shall be permitted in lengths not to exceed 1.8 m (6 ft), provided the cords and cables are supported and protected from physical damage and are of a jacketed and flame-retardent type. I see a potential typing error in this NEC section. I believe it should read 42 volts ac and not dc. What struck me was the fact that the rms calculation revealed the following: =30. This was a coincidence that I could not ignore so I am making this proposal Log #681 NEC-P12 Andy Juhasz, Kone, Inc (A)(3) (e). Flexible cords and cables in lengths not to exceed 1.8m (6 ft.) that are of a flame-retardant type and located to be protected from physical damage under normal usage shall be permitted in these rooms and spaces without being in stalled in a raceway. They shall be part of the following: (1) Listed equipment (2) A driving machine, or (3) A driving machine brake and located to be protected from physical damage is highly subjective and has been interpreted differently by individual AHJs. Change will limit scope if interpretation and allow for consistent application of the rule Log #1782 NEC-P12 George M. Stolz, II, Quicksilver Electrical Training Add the following text after the existing language: Receptacles for sump pumps shall not be connected to this circuit. This proposal is intended to clarify whether a sump pump can be connected to this circuit. As it stands, a receptacle serving a pump is technically a receptacle in the pit, which appears to defeat the intent of this section. 14
18 12-32 Log #1001 NEC-P12 James T. Dollard, Jr., IBEW Local 98 Replace 600V with 1000V. This proposal is the work of the High Voltage Task Group appointed by the Technical Correlating Committee. The task group consisted of the following members: Alan Peterson, Paul Barnhart, Lanny Floyd, Alan Manche, Donny Cook, Vince Saporita, Roger McDaniel, Stan Folz, Eddie Guidry, Tom Adams, Jim Rogers and Jim Dollard. The Task Group identified the demand for increasing voltage levels used in wind generation and photovoltaic systems as an area for consideration to enhance existing NEC requirements to address these new common voltage levels. The task group recognized that general requirements in Chapters 1 through 4 need to be modified before identifying and generating proposals to articles such as 690 specific for PV systems. These systems have moved above 600V and are reaching 1000V due to standard configurations and increases in efficiency and performance. The committee reviewed Chapters 1 through 8 and identified areas where the task group agreed that the increase in voltage was of minimal or no impact to the system installation. Additionally, there were requirements that would have had a serious impact and the task group chose not to submit a proposal for changing the voltage. See table (supporting material) that summarizes all sections considered by the TG. Note: Supporting material is available for review at NFPA Headquarters Log #307 NEC-P12 Stanley J. Folz, Morse Electric Company The disconnecting means shall be an enclosed externally operable fused motor circuit switch or circuit breaker that is lockable in accordance with capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted as the means required to be installed at and remain with the equipment. The disconnecting means shall be a listed device. This proposal has been developed by the Usability Task Group assigned by the Technical Correlating Committee. The committee members were Stanley Folz, James Dollard, William Fiske, David Hittinger, Andy Juhasz, Amos Lowrance, Susan Newman-Scearce, Marc Bernsen and Vincent Zinnante. Requirements for a disconnecting means to be lockable in the open position exist in numerous locations in the NEC. A new section has been proposed in Article 110 to consolidate the requirements for a disconnecting means required to be capable of being locked in the open position in a single section for clarity. It is understood that this requirement includes more than disconnecting and locking electrical power sources. This proposal is intended to facilitate a lockout/tagout scenario. It is equally important to ensure that the means for placing the lock remain in place. The concept suggested by this proposal is necessary to provide correlation throughout the NEC with respect to the capability of placing a lock on a disconnecting means to secure it in the open position. 15
19 12-34 Log #484 NEC-P12 Edward G. Kroth, Verona, WI Delete text as follows: The provisions for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted as the means required to be installed at and remain with the equipment. The rest of this section is to remain the same. This is a companion proposal to one submitted to Code-Making Panel 1 and should be accepted only if said proposal or some equivalent proposal is accepted by Code-Making Panel 1. Said proposal is to put the criteria for a lockable disconnecting means in Article 110 and, thus, be able to eliminate similar repetitions in at least 19 different sections of the NEC. It would also help to standardize the usage of the term "capable of being locked" which has at least four variations in the 2011 NEC Log #306 NEC-P12 Stanley J. Folz, Morse Electric Company Exception No. 1: Where an individual branch circuit supplies a platform lift, the disconnecting means required by (C)(4) shall be permitted to comply with (C). This disconnecting means shall be listed and shall be lockable in accordance with capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted as the means required to be installed at and remain with the equipment. This proposal has been developed by the Usability Task Group assigned by the Technical Correlating Committee. The committee members were Stanley Folz, James Dollard, William Fiske, David Hittinger, Andy Juhasz, Amos Lowrance, Susan Newman-Scearce, Marc Bernsen and Vincent Zinnante. Requirements for a disconnecting means to be lockable in the open position exist in numerous locations in the NEC. A new section has been proposed in Article 110 to consolidate the requirements for a disconnecting means required to be capable of being locked in the open position in a single section for clarity. It is understood that this requirement includes more than disconnecting and locking electrical power sources. This proposal is intended to facilitate a lockout/tagout scenario. It is equally important to ensure that the means for placing the lock remain in place. The concept suggested by this proposal is necessary to provide correlation throughout the NEC with respect to the capability of placing a lock on a disconnecting means to secure it in the open position. 16
20 12-36 Log #485 NEC-P12 Edward G. Kroth, Verona, WI Delete text as follows:. The rest of this exception is to remain the same. This is a companion proposal to one submitted to Code-Making Panel 1 and should be accepted only if said proposal or some equivalent proposal is accepted by Code-Making Panel 1. Said proposal is to put the criteria for a lockable disconnecting means in Article 110 and, thus, be able to eliminate similar repetitions in at least 19 different sections of the NEC. It would also help to standardize the usage of the term "capable of being locked" which has at least four variations in the 2011 NEC Log #305 NEC-P12 Stanley J. Folz, Morse Electric Company On elevators without generator field control, the disconnecting means shall be located within sight of the motor field controller. Where the motor controller is located in the elevator hoistway, the disconnecting means required by (A) shall be located in a machinery space, machine room, control space or control room outside the hoistway; and an additional, non-fused externally operable motor circuit switch that is lockable in accordance with capable of being locked in the open position to disconnect all ungrounded main power-supply conductors shall be located within sight of the motor controller. The additional switch shall be a listed device and shall comply with (C). The provision for locking or adding a lock to the disconnecting means, required by this section, shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. Driving machines or motion and operation controllers not within sight of the disconnecting means shall be provided with a manually operated switch installed in the control circuit to prevent starting. The manually operated switch(es) shall be installed adjacent to this equipment. Where the driving machine of an electric elevator or the hydraulic machine of a hydraulic elevator is located in a remote machine room or remote machinery space, a single means for disconnecting all ungrounded main power-supply conductors shall be provided and be lockable in accordance with capable of being locked in the open position. This proposal has been developed by the Usability Task Group assigned by the Technical Correlating Committee. The committee members were Stanley Folz, James Dollard, William Fiske, David Hittinger, Andy Juhasz, Amos Lowrance, Susan Newman-Scearce, Marc Bernsen and Vincent Zinnante. Requirements for a disconnecting means to be lockable in the open position exist in numerous locations in the NEC. A new section has been proposed in Article 110 to consolidate the requirements for a disconnecting means required to be capable of being locked in the open position in a single section for clarity. It is understood that this requirement includes more than disconnecting and locking electrical power sources. This proposal is intended to facilitate a lockout/tagout scenario. It is equally important to ensure that the means for placing the lock remain in place. The concept suggested by this proposal is necessary to provide correlation throughout the NEC with respect to the capability of placing a lock on a disconnecting means to secure it in the open position. 17
21 12-38 Log #309 NEC-P12 Stanley J. Folz, Morse Electric Company On elevators without generator field control, the disconnecting means shall be located within sight of the motor field controller. Where the motor controller is located in the elevator hoistway, the disconnecting means required by (A) shall be located in a machinery space, machine room, control space or control room outside the hoistway; and an additional, non-fused externally operable motor circuit switch that is lockable in accordance with capable of being locked in the open position to disconnect all ungrounded main power-supply conductors shall be located within sight of the motor controller. The additional switch shall be a listed device and shall comply with (C). The provision for locking or adding a lock to the disconnecting means, required by this section, shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. This proposal has been developed by the Usability Task Group assigned by the Technical Correlating Committee. The committee members were Stanley Folz, James Dollard, William Fiske, David Hittinger, Andy Juhasz, Amos Lowrance, Susan Newman-Scearce, Marc Bernsen and Vincent Zinnante. Requirements for a disconnecting means to be lockable in the open position exist in numerous locations in the NEC. A new section has been proposed in Article 110 to consolidate the requirements for a disconnecting means required to be capable of being locked in the open position in a single section for clarity. It is understood that this requirement includes more than disconnecting and locking electrical power sources. This proposal is intended to facilitate a lockout/tagout scenario. It is equally important to ensure that the means for placing the lock remain in place. The concept suggested by this proposal is necessary to provide correlation throughout the NEC with respect to the capability of placing a lock on a disconnecting means to secure it in the open position Log #682 NEC-P12 Andy Juhasz, Kone, Inc.. On elevators without field generator field control, the disconnecting means shall be located within sight of the motor controller. When the motor controller is located in the elevator hoistway the disconnecting means required by (A) shall be located in a machinery space, machinery room, control space or control room outside the hoistway; and an additional fused or non-fused enclosed externally-operable motor circuit switch capable of being locked in the open position to disconnect all ungrounded main power-supply conductors shall be located within sight of the motor controller. The additional switch shall be a listed device, and shall comply with (C). When motor controllers are a) installed within the elevator hoistway and b) not supplied with a means for protection from internal short circuits, the option to add fuses to the additional motor circuit switch in (C )(1) would provide a safe and clearly-recognized means to access fuses dedicated for protection of that motor controller. Selective coordination of overcurrent protection is still required. 18
AGENDA. NEC Code-Making Panel 4. Report on Proposal Meeting. January 16-21, Hilton Head, SC
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 4 Report on Proposal Meeting January 16-21,
More informationAGENDA. NEC Code-Making Panel 11. Report on Proposal Meeting. January 9 11, Hilton Head, SC
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 11 Report on Proposal Meeting January 9 11,
More informationAGENDA. NEC Code-Making Panel 10. Report on Proposal Meeting. January 12-14, Hilton Head, SC
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 10 Report on Proposal Meeting January 12-14,
More informationReport on Proposals June 2013 NFPA 70
11-1 Log #1170j NEC-P11 Russell LeBlanc, The Peterson School In articles 90 through 830, if the wording is not already there, then add the words (or other structure(s)) after the word BUILDING(S) wherever
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of Code Making Panel 11 FROM: Jean O Connor
More informationNEC 2011 Code Changes
NEC 2011 Code Changes Articles 280.21-300.50 CHANGES FROM 2008 TO 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1kV III. Connecting Surge Arresters 280.21 Connection
More informationPanel 11 FD Agenda Page 1
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 11 First Draft Meeting January 15-17, 2015
More informationLoad Side PV Connections
Perspectives on PV Load Side PV Connections 705.12(D) in the 2014 NEC by John Wiles Through the exceptional efforts of the members of NFPA NEC Code-Making Panel 4 working with the proposals and comments
More informationSpring Test 7 due 05/03/2013
Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous
More informationA Look at the 2017 NEC Significant Changes
A Look at the 2017 NEC Significant Changes A Look at the 2017 NEC Significant Changes Michael J. Johnston NECA James T. Dollard Local 98 Philadelphia Electrical JATC This session is eligible for 1 Continuing
More informationTEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES
INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR
More informationSecond Revision No. 25-NFPA [ Section No ]
Second Revision No. 25-NFPA 79-2013 [ Section No. 1.1.1 ] 1.1.1 The provisions of this standard shall apply to the electrical/electronic equipment, apparatus, or systems of industrial machines operating
More informationNFPA World Safety Congress & Exposition 2005 NEC Proposals Report of CMP-12
2005 NEC Proposals Report of CMP-12 NEC Code Making Panel 12 is responsible for: Articles 610, 620, 630, 640, 645, 647, 650, 660, 665, 668, 669, 670, 685, and Annex D Examples D9 and D10 2005 NEC Proposals
More informationNEC Code-Making Panel 11. Second Draft Meeting Agenda. November 5-7, San Diego, CA Introduction of Members and Guests
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NEC Code-Making Panel 11 Second Draft Meeting Agenda November 5-7, 2015
More information90.2 Scope. The installation of electrical conductors, equipment and raceways for:
NEC Generator Primer Rules on the installation of generators and transfer switches 1 90.2 Scope The installation of electrical conductors, equipment and raceways for: public and private premises Conductors
More informationChapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9
Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6
More informationCHAPTER 10 ELECTRICAL. Notes:
CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic
More informationPermit for Charging Equipment Installation Electric Vehicle Supply Equipment (EVSE)
Permit for Charging Equipment Installation Electric Vehicle Supply Equipment (EVSE) Town of Lake George, New York Compliance with the following permit will allow the installation and operation of electric
More informationHave You Been Grounded Lately
Have You Been Grounded Lately Thurs, Oct. 26, 2017 9:15-10:15 Phil Simmons Author, Electrical Grounding and Bonding Author Cengage Learning Phil Simmons Have You Been Grounded Lately 2017 NEC Changes Relative
More informationSUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More information9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC
2011 NEC Significant Changes Courtesy of NJATC Courtesy of NFPA Presented By: Michael J. Johnston Executive Director of Standards and Safety, NECA Objectives Review significant revisions in the 2011 NEC
More informationENGINEERING SPECIFICATION
December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References
More informationSOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST
SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST The following checklist is an outline of the general requirements found in the 1999 National Electrical Code (NEC) Article 690 for Photovoltaic (PV) Power
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Aircraft Rescue
More informationBulletin Wiring methods for Solar Photovoltaic Systems Rules and , Tables 11 and 19
Bulletin 50-4-1 Wiring methods for Solar Photovoltaic Systems Rules 50-018 and 50-020, Tables 11 and 19 Issued December 2012 Supersedes Bulletin 50-4-0 (1) (2) (3) (4) (5) Scope Introduction New cable
More informationBulletin Wiring methods for Solar Photovoltaic Systems Rules, 2-034, , and , Tables 11 and 19
Bulletin 50-4-4 Wiring methods for Solar Photovoltaic Systems Rules, 2-034, 50-014, 50-018 and 50-020, Tables 11 and 19 Scope (1) Introduction (2) New cable types RPV & RPVU (3) Wiring methods within photovoltaic
More information2014 NEC Changes (Homestudy)
2014 NEC Changes (Homestudy) Idaho Electrical License This course will review the most important National Electrical Code changes from the 2014 NEC. Changes in Articles 100 - Chapter 9 will be covered.
More informationNEC Code-Making Panel 4. Second Draft Meeting Agenda. November 2-7, San Diego, CA Introduction of Members and Guests
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NEC Code-Making Panel 4 Second Draft Meeting Agenda November 2-7, 2015
More information2014 NEC Changes Part 1 (Homestudy)
2014 NEC Changes Part 1 (Homestudy) Wisconsin Electrical License This course will review the first half of the most important National Electrical Code changes from the 2014 NEC. Changes in Articles 100-404.2
More information2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
More information2016 Photovoltaic Solar System Plan Review List
Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE
More informationPanel 8 FD Agenda Page 1
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 8 First Draft Meeting January 19-24, 2015
More informationAGENDA. NEC Code-Making Panel 17. Report on Comment Meeting. December 3 December 5, Redondo Beach, CA
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 17 Report on Comment Meeting December 3 December
More informationUNDERGROUND SERVICES - SECONDARY
UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service
More information2011 NEC Code Updates Part 3
www.garyklinka.com Page 1 of 22 Instructions: Fee $35 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More informationCHAPTER 10 ELECTRICAL
1001.0 General Requirements. 1001.1 Electrical Wiring and Equipment. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances.
More informationNEC Article 620: Elevators, Part 2
CERTIFIED ELEVATOR TECHNICIAN Continuing Education NEC Article 620: Elevators, Part 2 by David Herres Learning Objectives After reading this article, you should have learned: Which locations require separate,
More informationThis is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationThe following are specific provisions of 1910(a)(2) that could be seen in the LBM sector
Know the Rules on Temporary Wiring OSHA Standard 1910.305, Wiring methods, components, and equipment for general use, addresses wiring methods, components, and equipment for general use as one of several
More informationSERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING
SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company
More informationTEK Brief July Is there a difference in installation requirements between communications cables with and without the LP designation?
BECAUSE YOUR BUSINESS RUNS THROUGH US TEK Brief July 2016 LP Cabling: Frequently Asked Questions Table of Contents Introduction Prior to the beginning of the review cycle of the 2017 National Electrical
More informationARKANSAS ELECTRICIANS
CONTINUING EDUCATION FOR ARKANSAS ELECTRICIANS 2014 NEC Code Change 8 Hours AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Drive, Suite 290 Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER
More informationBulletin Wiring methods for Solar Photovoltaic Systems Rule and , Tables 11 and 19
-4-0 Bulletin -4-0 Wiring methods for Solar Photovoltaic Systems Rule -018 and -020, Tables 11 and 19 Scope Issued May 2012 (1) Introduction (2) New cable types RPV & RPVU (3) Wiring methods within photovoltaic
More informationPanel 6 Agenda Page 1
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 6 First Draft Meeting January 19-21, 2015
More informationData Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?
Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0
More informationPHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST
PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST The following checklist is an outline of the general requirements found in the 2005 National Electrical Code (NEC) Article 690 for Photovoltaic
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not
More informationReport on Comments June 2013 NFPA 70
17-1 Log #920 NEC-P17 James F. Williams, Fairmont, WV 17-18a Revise text to read as follows: The manufacturer of portable or mobile signs shall provide a listed appliance ground-fault circuit-interrupter
More informationGenerator Fire Safety: Generator assemblies should be located outside the building.
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building
More informationPhotovoltaic Solar Plan Review
PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check
More informationSolar Power Installation Application
Solar Power Installation Application This Form must be filled out and submitted to Logan City Light and Power Department and given authorization to proceed PRIOR to installing a solar system. Also, please
More informationARTICLE SAFETY CODES FOR ELEVATORS, ESCALATORS, MANLIFTS AND HOISTS. Elevator Safety
ARTICLE 21. 3 SAFETY CODES FOR ELEVATORS, ESCALATORS, MANLIFTS AND HOISTS Elevator Safety (The following Indiana Amendments are reprinted here from the Indiana government web site for your convenience.
More informationINSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL
Photovoltaic (PV) Residential Page 1 of 10 Revision Date: 07/18/2018 INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL INSPECTION CODE: 703 SCOPE: RESIDENTIAL APPLICABLE CODES: 2016 CBC, CRC, CPC,
More informationINTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES
INTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES 3. Definitions ( cont'd) Parallel System: A generating facility that is electrically interconnected
More informationWIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST
WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.
More informationEV Charging Station Submittal Requirements
EV Charging Station Submittal Requirements To obtain a permit for an Electric Vehicle Charging Station, please provide the following: Plan and details of the charging system installation o Print applicable
More informationOutdoor Power Transmission & Distribution
Description: The purpose of the section is to highlight the current applicable UMCP Design Standards and requirements for Outdoor Power Transmission and Distribution, including but not limited to the following:
More informationgrounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2
grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2 grounded in service wired to innovate www.cable.alcan.com Type XHHW-2 and Type USE-2/RHH/RHW-2 Alcan manufactures XHHW-2 and
More informationSECTION 300 OVERHEAD SERVICE
SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to
More informationANAMET Electrical, Inc. Worldwide Leader in Flexible Conduit Technology
ANAMET Electrical, Inc. Worldwide Leader in Flexible Conduit Technology ANACONDA SEALTITE 2018 ANAMET Electrical, Inc. AN ANAMET COMPANY When you say SEALTITE, there is only one: ANACONDA. Type MTC Type
More information36CSR27 TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS
TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS 36-27-1. General. 1.1. Scope. -- Rules and Regulations Governing Surface Areas. 1.2.
More informationNEC Code-Making Panel 5. Second Draft Meeting Agenda. November 9-14, San Diego, CA Introduction of Members and Guests
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NEC Code-Making Panel 5 Second Draft Meeting Agenda November 9-14, 2015
More informationCellwatch Electrical Installation
Tech20081110-1-1 Cellwatch Electrical Installation Critical Distances...2 Typical Layout...3 Typical ibmu Placement...4 Typical Control Unit Placement...5 Physical Mounting and Location - General...6 CU
More informationSECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems
COUNTY OF SANTA CRUZ PLANNING DEPARTMENT 701 OCEAN STREET, 4 th FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 KATHLEEN MOLLOY PREVISICH, PLANNING DIRECTOR Photovoltaic
More informationCity of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems <48kW)
City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems
More informationNEC REQUIREMENTS FOR GENERATORS
PROFESSIONAL DEVELOPMENT SEMINAR SERIES NEC REQUIREMENTS FOR GENERATORS (Based on NEC 2005 with limited 2008 commentary) AIA certified Continuing Education Units (CEU) Available GPS-140 National Electric
More informationSpecific Purpose Equipment and Installations -- OSHA Standard
ABE286 Specific Purpose Equipment and Installations -- OSHA Standard 1910.306 1 Carol J. Lehtola, Charles M. Brown, and William J. Becker 2 The Impact of Safety on Florida Agriculture Florida agriculture,
More informationElectrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University
Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University Electrical Code Changes in Michigan 1 (Based on Part 8, P.A. 230, the 2005 NEC and the 2003 MRC) This
More informationCHAPTER V RESIDENTIAL WIRING
CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this
More informationPanel 13 FD Agenda page 1
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 13 First Draft Meeting January 12-17, 2015
More informationMecklenburg County Common Code Defects
Electrical Code Defects Improper Over Current Protection Code Description 310.15 Ampacities for s Rated 0 2000 Volts. (A) General. (1) Tables or Engineering Supervision. Ampacities for conductors shall
More informationTRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES
TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary
More informationTechnical Summary of Battery Energy Storage Systems
Technical Summary of Battery Energy Storage Systems Based on the 2017 Massachusetts Electrical Code This document summarizes the new Article 706 in the Massachusetts Electrical Code (MEC). Article 706
More informationDIVISION 16 - ELECTRICAL SECTION 16xx0 MANUFACTURED WIRING SYSTEM ACCESS FLOOR
DIVISION 16 - ELECTRICAL SECTION 16xx0 16xx0-1. GENERAL MANUFACTURED WIRING SYSTEM ACCESS FLOOR The modular convenience power system ensures the electrification and delivery of power from the power panels
More informationSee Part 3 for the Introduction for Article 314
See Part 3 for the Introduction for Article 314 76 314.25 Covers and Canopies When the installation is complete, each outlet box must be provided with a cover or faceplate, unless covered by a fixture
More informationCode Compliance. Perspectives on PV. Back to the Grid, Designing PV Systems for
Perspectives on PV A series of articles on photovoltaic (PV) power systems and the National Electrical Code by John Wiles Back to the Grid, Designing PV Systems for Code Compliance 20 IAEI NEWS January.February
More informationDISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS
Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.
More informationELECTRICAL CONSISTENCY MEETING
ELECTRICAL CONSISTENCY MEETING Date: 10/14/2015 Our Goal is FOR ALL STAKEHOLDERS TO HAVE A SUCCESSFUL PROJECT with us and that together we keep people and structures safe and economically viable to serve
More informationCity of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA (925) phone (925) fax
City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA 94596 (925) 943-5834 phone (925) 256-3500 fax Issued September 30, 2017 Policy Bulletin No. PB-72 Background Residential
More informationTable of Contents. Unit 3 Magnetism Unit 1 Matter Unit 4 Electricity Unit 2 Electron Theory Unit 5 Electromagnetism...
Introduction...x How to Use This Textbook...xi About the Author...xii About the Graphic Illustrator...xiii Mike Holt Enterprises Team...xiv Chapter 1 Electrical Fundamentals... 1 Unit 1 Matter... 3 Introduction...
More informationDesign Standards NEMA
Design Standards Although several organizations are involved in establishing standards for the design, construction, and application of motor control centers, the primary standards are established by UL,
More informationThe Reliable Choice. Field Pocket Guide
The Reliable Choice Field Pocket Guide Allowable Ampacities of STABILOY Brand XHHW-2 and Copper 75 C (167 F) 90 C (194 F) 75 C (167 F) 90 C (194 F) Conductor Size (AWG or kcmil) Types RHW, THHW, THW, THWN,
More informationWhat's New with UL508A Codes & Standards Presented by Jeff Woolfolk Manufacturing in America March 14-15, 2018
What's New with UL508A Codes & Standards Presented by Jeff Woolfolk Manufacturing in America March 14-15, 2018 Before we start A Penny for Your Thoughts At the end of the session, share your feedback via
More informationSolar PV Standard Electric Plan
*** Provide this document to the inspector along with ALL system installation instructions *** SCOPE: Standard plan for the installation of microinverter solar PV systems, not exceeding a total AC output
More informationDefinitions. Scope. Customer Generation Interconnection Requirements
Updated 02/1 Page 1 Scope The purpose of this document is to describe Idaho Power s requirements for the installation and testing of Customer Generation acilities that are interconnected with Idaho Power
More informationSolar PV Standard Plan Simplified Microinverter and ACM Systems for One- and Two-Family Dwellings
TOOLKIT DOCUMENT #4 Your City logo here Solar Standard Plan Simplified Microinverter and M Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters
More informationElectrical Installation
Electrical Installation Symmetra LX Tower UPS Models 200 V, 4-8 kva 208/240 V, 4-8 kva 220/230/240 V, 4-8 kva 200 V, 4-16 kva 208/240 V, 4-16 kva 220/230/240 V, 4-16 kva Important Safety Messages SAVE
More informationSECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT
SECTION 22 05 12 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable in the section
More informationDESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5
DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this
More informationMike Holt s Illustrated Guide to SOLAR PV SYSTEMS
Mike Holt s Illustrated Guide to Directory, Identification, Label, Marking, Plaque, and Sign Requirements for SOLAR PV SYSTEMS Extracted From Mike Holt s Illustrated Guide to Understanding NEC Requirements
More informationPOLLUTION PREVENTION AND RESPONSE. Application of more than one engine operational profile ("multi-map") under the NOx Technical Code 2008
E MARINE ENVIRONMENT PROTECTION COMMITTEE 71st session Agenda item 9 MEPC 71/INF.21 27 April 2017 ENGLISH ONLY POLLUTION PREVENTION AND RESPONSE Application of more than one engine operational profile
More information2014 NEC Update RV
PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.
More informationSINGLE PHASE WIRING SPECIFICATIONS
SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425
More informationCorrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections
Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of
More informationELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST Guidelines: This checklist covers
More informationManaging Electric Vehicle Supply Equipment (EVSE) Installations
Managing Electric Vehicle Supply Equipment (EVSE) Installations Introduction to Electric Vehicle EVSE Electric vehicles create a need to build an infrastructure that will supply the added load of charging.
More informationDER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.
Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations
More informationEvaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers
Evaluating Selective Coordination Between And Non Current-Limiting Circuit Breakers Tech Topics: Selective Coordination Note 1, Issue 1 Steve Hansen Sr. Field Engineer Robert Lyons Jr. Product Manager
More informationNFPA 105 Public Input Report Page 1 of 22
of 20 11/4/2016 5:57 PM Public Input No. 6-NFPA 105-2016 [ Section No. 2.3.2 ] 2.3.2 UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096. ANSI/UL 10B, Standard
More information