500KV BUSHINGS FAILURES AND BUSHING OIL SAMPLING PROGRAM. Mike Lau BC Hydro

Size: px
Start display at page:

Download "500KV BUSHINGS FAILURES AND BUSHING OIL SAMPLING PROGRAM. Mike Lau BC Hydro"

Transcription

1 500KV BUSHINGS FAILURES AND BUSHING OIL SAMPLING PROGRAM Mike Lau BC Hydro ABSTRACT In June 2001, a 500KV bushing ( CGE, type U ) failed and resulted in a catastrophic failure of a generator step-up transformer in one of our major generating facility. Moisture ingress was the primary suspected cause of failure. Since then, an oil sampling program on bushings was launched and a high percentage of bushings were found to have either high moisture and/or high combustible gases. One 230KV ( CGE Type F ) bushing was found to have high combustible gases and subsequent investigation revealed heavy tracking on the innermost Herkolite cylinder. A few other 500KV bushings ( Bushing Company Type 500HA67B ) was found to have moisture ingress through the top filling plugs. Amidst all these bushing testing and change-out activities, another 500KV ( A hybrid unit -- ABB Type O plus C and CGE Type U ) bushing failed while in service on a relatively new ( in service in 1994 ) shunt reactor in November, Two months later, another 500KV ( similar hybrid unit ) bushing on the same shunt reactor also failed and resulted a huge fire which burnt for hours. Investigation on the failures of these hybrid bushings continues at the time of writing and no firm conclusion on the cause of failures can be drawn. This paper provides some details on the bushing failures and oil sample results. INTRODUCTION Small oil volume apparatus, such as oil-filled current transformers, potential transformers and bushings contain small amount of oil which could be easily contaminated and greatly reduce its insulation integrity. The failures of these apparatus are usually explosive with ensuing fires and detrimental to both equipment and personnel. Until recently, in BC Hydro, except for Doble testing, no other routine testing are specified for these apparatus. Oil samples had been taken from some makes of CT s in the past but only for diagnostic purposes and oil sampling was certainly not a routine maintenance task. However, with recent failures of 500KV bushings and poor test results on oil samples taken from other bushings, the current maintenance practices on bushings needed to be re-examined. BACKGROUND Failure of a 500KV CGE Type U Bushing ( Note : Not to be confused with GE Type U ) In June 2001, at the G.M. Shrum Generating Station, one 500KV bushing on one of the unit transformer, T4C, failed violently with all the porcelain ( both above and below the mounting flange ) blew up into pieces the size of a fist. Oil was drained out of the conservator tank through the bushing and fires started 1

2 both on top and at the bottom of the tank. Fortunately, the sprinkler systems operated ( the heat was so intense that the sprinkler system for the adjacent bank also operated) and cooled down the adjacent equipment allowing the fire crew put out the fire eventually. An internal explosion was evident from the bulging and welding cracks on the tank. There were severe damages internally that the transformer was scraped. (Photos 1,2,3, and 4). Investigation of the failed bushing confirmed a dielectric failure with the paper insulation punctured through from the center draw rod, at a location about one third of the way down from the top terminal, to the grounded capacitance tap. While the construction of the CGE Type U bushings ( manufactured by Canadian General Electric in Guelph, Ontario )was different from that of a GE type U ( ie no herring-bone inking process ), we were surprised to see the capacitance layers were made up of paper coated with some semi-conductive graphite like material. Smears of this material was evident in many places ( Photo 5 ). The subject bushing was Doble tested in Oct 1998 and both C1 and C2 insulation power factors were good. No definite cause of failure was determined and external moisture ingress was the primary suspected cause. INITIAL OIL SAMPLING PROGRAM Prior to the above bushing failure incident, oil samples were rarely taken from small oil volume apparatus including oil-filled bushings. After the incident, it was decided that additional information on the condition of the bushings is needed and a small scale oil sampling program was launched. Oil samples were taken from all other 500KV bushings in GM Shrum Generating Station. The results was very alarming: Of a total of 41 other bushings (of different manufacturers including CGE, Bushing Company, and Toshiba ), 11 bushings (27%) were found to have either unacceptable DGA results or unacceptable high moisture content. The results are included in Appendix 1. Further investigation on those bushings with unacceptable results were carried out and detailed below. INVESTIGATION OF BUSHING PROBLEMS Of the 11 bushings that there found bad, 8 were found to have high moisture content ( 23ppm to 72 ppm ); 3 were found to have abnormal amount of combustible gases. All 11 bushings were removed from services for further investigation and dryout. A. High Moisture Content A1. The GMS T4A bushing ( CGE Type U, with 62 ppm of H2O ) was removed from service and sent to Powertech Lab for partial discharge ( PD ) test. It failed the PD test. The unit was subsequently drained, dried out extensively with high vacuum and heat, refilled under vacuum. Subsequently, it passed the PD test and returned to service without incident. A2. Other CGE Type U bushings found to have high moisture content, such as GMS T1B ( 23 ppm ), T12A ( 52 ppm ), and T14A ( 62 ppm ), were all similarly dried out extensively with heat and high vacuum, tested, and returned to service without incident. 2

3 A3. GMS T8C ( with 65 ppm of H2O ) and T9C ( with 72 ppm of H2O ) were both Bushing Company bushings, Cat # ART-500HA67B. The location and the likely causes of moisture ingress have been identified: With reference to Figure 1, moisture was found getting inside the bushings through the small oil filling plugs (Item 10) located on the top of the expansion metal can (Item13) and inside the terminal cap (Item 1). The underside surface of the oil filling plugs were found to be rusty and the surfaces inside of the terminal caps were coated with white powdery material indicating signs of moisture ingress. Further investigation revealed that the moisture somehow managed to penetrate three layers of protection; namely ; the outer gasket seal for the terminal caps ( gaskets found to be brittle and cracked ); the inner gasket seal ( gasket found to be in reasonably good order, but the caps were not seating squarely due to the ends of some helical coils improperly protruding outside of their threaded holes ), and finally the sealing washers of the oil filling plugs ( washers found missing completely! ). Other Bushing Company bushings were checked but so far none was found to have a similar problem. The two bushings were also dried out, tested, and returned to service without incident. B. Abnormal amount of combustible gases B1. GMS T10B was found to have high combustible gases ( but only 1 ppm of C2H2 ). This CGE Type U bushing was removed from service and sent to Powertech Labs for testing. Surprisingly, it passed the PD test. However, there is a significant difference in the Dissipation Factor measured before (0.49%) and after ( 0.74%) the AC withstand test. Further investigation is pending, and the bushing will not be returned to service B2. GMS T7B and GMS T7C Both have high combustible gases including a fair amount of C2H2 ( 62 and 60 ppm respectively ). These two bushing were Doble tested prior to their removal from the transformer. The Doble test results are enclosed in Appendix 2. It was reported that on the GMS T7C bushing, oil was dripping out of the capacitance tap continuously when the cap was removed. The oil was black and had a burnt smell to it. This bushing failed the PD test miserably. These two bushings, together with a third one from another station (WSN T4A), which also has high combustible gases ( 3005 ppm of C2H2 ), will be returned to the manufacturer in UK for investigation and possible refurbishment. B3. A 230 KV bushing, CGE Type F bushing at Rosedale Substation, (ROS T1A Low Voltage bushing), was found to have high combustible gases. It was immediately removed from service. The bushing was subsequently dismantled for examination. Heavy tracking was found on the bottom end of the innermost Herkolite cylinder. See Photo 6. This bushing was scraped. EXPANDED BUSHING OIL SAMPLING PROGRAM Encouraged with the success of the oil sampling program, the program has been extended to include other 500 KV bushings in all our generating stations and in some critical transmission stations. 3

4 MORE FAILURES OF 500KV BUSHINGS As if we don t have enough bushing problems, in November 2001, another 500 KV bushing failed on a shunt reactor at Kelly Lake Substation ( KLY 5RX5 ). The reactor is a relatively new 3-phase 135 MVAR unit put in service in Dark oil and burnt paper sprayed out from the joints between sections of the porcelain. No porcelain were broken and no significant damages to the reactor. The bushing was replaced with a new spare. All the bushings as well as the reactor were Doble tested satisfactory and the unit was returned to service in early December Two months later, in the mid-night hours of 26 February 2002, another 500 KV bushing on the same shunt reactor failed explosively and resulted a huge fire which burnt for 4-5 hours. It destroyed the adjacent new spare bushing, a surge arrestor and caused significant damages to the adjacent circuit breaker.( see photo 7 ). These two failed bushings were hybrid units made with ABB condenser core ( with semi-conductive capacitance layers ) and other CGE Type U components. A type problem was suspected and consequently, two other similar 500 KV shunt reactors were removed from service pending further investigation. CONCLUSION Failures of small oil volume apparatus, such as bushings, are often explosive with ensuing fires, and are indeed great threats to personnel and equipment. On-line monitoring equipment are readily available to monitor the integrity of bushings by means of unbalanced neutral current, leakage current, power factor etc. However, it would be difficult, if not impossible, to justify economically, on-line monitoring equipment on every bushing. As demonstrated in this paper, oil testing for DGA and moisture content prove to be a good compliment to other routine testing to provide additional information on the integrity of bushings. It would also be desirable that a guide or a standard be established for the acceptable gas level limits and interpretation of the DGA results. 4

5 Photo 1 : GMS Generator Step up Transformer banks Photo 2: Overview of faulted bushing on GMS T4C 5

6 Photo 3 : GMS T4C Overview of faulted bushing 6

7 Photo 4 : GMS T4 C Removal of faulted bushing 7

8 Photo 5 : GMS T4C Bushing Tracking on semi-conductive paper Photo 6 : CGE Type F bushing : Tracking on ht e innermost Herkolite cylinder 8

9 Photo 7; KLY 5RX5 Failure of ABB/CGE hybrid bushing. 9

10 FIGURE 1: VIEW OF BUSHING COMPANY BUSHING TOP ASSEMBLY 10

11 APPENDIX 1 DISSOLVED GAS IN OIL RESULTS IN BUSHINGS STN UNIT PH DATE C2H2 C2H4 C2H6 CH4 CO CO2 H2 H2O N2 O2 VOLUME GMS T1 B 20-Jul-01 < % GMS T1 C 20-Jul-01 < < % GMS T1 A 11-Oct-01 < % GMS T2 A 06-Oct-01 < < % GMS T2 B 06-Oct-01 < % GMS T2 C 06-Oct-01 < < % GMS T3 A 06-Oct-01 < < % GMS T3 B 06-Oct-01 < < % GMS T3 C 06-Oct-01 < % GMS T4 B 04-Jul-01 < < % GMS T4 A 04-Jul-01 < % GMS T5 C 04-Oct-01 < % GMS T5 A 04-Oct-01 < < % GMS T5 B 04-Oct-01 < % GMS T6 B 18-Sep-01 < % GMS T6 A 18-Sep-01 < % GMS T6 C 18-Sep-01 < % GMS T7 B 05-Sep % GMS T7 C 05-Sep % GMS T7 A 05-Sep-01 < % GMS T8 C 22-Sep-01 < % GMS T8 B 22-Sep-01 < % GMS T8 A 22-Sep % GMS T9 A 22-Sep-01 < % GMS T9 C 22-Sep-01 < % GMS T9 B 22-Sep-01 < % GMS T10 A 15-Aug-01 < % GMS T10 B 15-Aug % GMS T10 C 15-Aug-01 < % GMS T11 C 26-Aug-01 < % GMS T11 A 26-Aug-01 < % GMS T11 B 26-Aug-01 < % GMS T12 A 30-Aug-01 < % GMS T12 C 30-Aug-01 < % GMS T12 B 30-Aug-01 < % GMS T13 A 30-Oct-01 < < % GMS T13 B 30-Oct-01 < % GMS T13 C 30-Oct-01 < < % GMS T14 A 14-Nov-01 < % GMS T14 B 14-Nov-01 < % GMS T14 C 14-Nov-01 < % ROS T1-X A 22-Oct % WSN T2 A 14-Nov % 11

12 Appendix 2 a Doble test result of GMS T7B bushing Company : BC Hydro Test Date: Sep Division: NORTHERN (PA) Location: GMS (G.M. SHRUM) Special ID: CCT Desig: T7-B Mfr: Pi Yr Mfr: 1970 Serial #: WT Ph : 1 Cfg: 1-PHASE kv : 512.5/13.8 MVA:44.6 / 59.8 / 80.0 // Tanktype: SEALED- CONSER Coolant: OIL Air temp: 14 C Apparatus temp: 12 C RH:26% Weather: PTCLDY Bushing Tests C1 Nameplate Data Test Results Bush Mfr Type S/N Cap(pF) %PF kv %PF Cap(pF) RTG H1 BUSH G D C2 Nameplate Data Test Results Bush Mfr Type S/N Cap(pF) %PF kv %PF Cap(pF) RTG H1 BUSH I 12

13 Appendix 2b Doble test results of GMS T7C bushing Company : BC Hydro Test Date: Sep Division: NORTHERN (PA) Location: GMS (G.M. SHRUM) Special ID: CCT Desig: T7-C Mfr: Pi Yr Mfr: 1970 Serial #: WT Ph : 1 Cfg: 1-PHASE kv : 512.5/13.8 MVA:44.6 / 59.8 / 80.0 // Tanktype: SEALED- CONSER Coolant: OIL Air temp: 15 C Apparatus temp: 12 C RH:50% Weather: PTCLDY Bushing Tests C1 Nameplate Data Test Results Bush Mfr Type S/N Cap(pF) %PF kv %PF Cap(pF) RTG H1 Bush OTHER 5BBf D I D I C2 Nameplate Data Test Results Bush Mfr Type S/N Cap(pF) %PF kv %PF Cap(pF) RTG H1 Bush OTHER 5BBf G I 13

Diagnostic Experience on HV Bushings Retired from Service MANUEL GUZMÁN-V

Diagnostic Experience on HV Bushings Retired from Service MANUEL GUZMÁN-V Diagnostic Experience on HV Bushings Retired from Service MANUEL GUZMÁN-V Diagnostic experience on HV bushing retired from service. Manuel Guzmán; Fernando Elizarraraz; Ricardo Montes Comisión Federal

More information

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard A manufacturer s view of bushing reliability, testing and analysis By Lars Jonsson Håkan Rudegard 1 A manufacturer s view of bushing reliability, testing and analysis Lars Jonsson Håkan Rudegard ABB Sweden

More information

V. Design, Application, Maintenance & Operation Technical Requirements

V. Design, Application, Maintenance & Operation Technical Requirements V. Design, Application, Maintenance & Operation Technical Requirements V.L Line & Substation Operation and Maintenance 1.0 General Requirements 1.1 Each facility owner shall have an established and documented

More information

Primary Heat Transport (PHT) Motor Rotor Retaining Ring Failure

Primary Heat Transport (PHT) Motor Rotor Retaining Ring Failure 1 Primary Heat Transport (PHT) Motor Rotor Retaining Ring Failure Ali Malik Components & Equipment Eng. Ontario Power Generation - Darlington Nuclear 2 Ontario Power Generation Darlington Darlington Nuclear

More information

Technical Specification For Outdoor Substation Harmonic Filter Banks

Technical Specification For Outdoor Substation Harmonic Filter Banks Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field

More information

Alstom Grid provides smart, efficient and environmentally-friendly solutions to deliver electricity reliably across the world GRID

Alstom Grid provides smart, efficient and environmentally-friendly solutions to deliver electricity reliably across the world GRID Alstom Grid provides smart, efficient and environmentally-friendly solutions to deliver electricity reliably across the world GRID Maintenance & Onsite Repair of Transformers NTPC O&M Conference IPS 2013,

More information

Transformer bushings, type GOH. Technical guide

Transformer bushings, type GOH. Technical guide Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required

More information

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 1 2 3 4 5 6 7 8 9 Q. Please describe Hydro s terminal station and substation inspections policies and practices. In

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

Transformer Components & Accessories

Transformer Components & Accessories Transformer Components & Accessories Brian Brinson Mechanical Design Manager brian.brinson@spx.com Agenda 1. Standards / Equipment Overview 2. Bushings 3. Arresters 4. Cooling Equipment 5. Instrument Transformers

More information

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide 1ZSE 2750-106 EN, REV. 7 Oil SF 6 bushings type GOEK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids

A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids Author Company Email Presenter T.A. Messinger BC Hydro toly.messinger@bchydro.com E. Burt BC Hydro ed.burt@bchydro.com P.Glaubitz Siemens

More information

Failure of Transformer Cable box A case study

Failure of Transformer Cable box A case study Failure of Transformer Cable box A case study Presented by Janardan Choudhary, Executive Director (O&M) 1 INTRODUCTION The 280 MW Dhauliganga Power Station, NHPC Ltd, situated at remote place of Pithoragarh

More information

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

www. ElectricalPartManuals. com INSTRUCTIONS INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE r \ FIG. 1. Cutaway View of Typical Switch. I.L. 46-723-1 DESCRIPTION INSTALLATION MAINTENANCE INSTRUCTIONS THE INERTEEN AND OIL INSULATED FEEDER SWITCH provides complete switching facilities in a minimum

More information

Natural Ester Fluid Diagnostics

Natural Ester Fluid Diagnostics Natural Ester Fluid Diagnostics Weidmann 7 th Annual Technical Conference September 17, 2008 BY: C. Patrick McShane and John Luksich Market Demand Accelerating More than 130,000 transformers in service

More information

EA Closing Report Page 1 of 9

EA Closing Report Page 1 of 9 EA06-002 Closing Report Page 1 of 9 SUBJECT: Rear coil spring fracture ENGINEERING ANALYSIS CLOSING REPORT EA No: EA06-002 DATE OPENED: 24-Jan-2006 DATE CLOSED: 05-Feb-2007 SUBJECT VEHICLES: Model Year

More information

Hydro Plant Risk Assessment Guide

Hydro Plant Risk Assessment Guide September 2006 Hydro Plant Risk Assessment Guide Appendix E2: Circuit Breaker Condition Assessment E2.1 GENERAL Circuit breakers are key components in the power train at hydroelectric powerplants and are

More information

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES Description JRS arc-resistant fused/non-fused load break and fused/non-fused disconnect switches are available for applications

More information

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide 1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide 1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

PRILIMINARY REPORT ON THE ACCIDENT AT RANTAMBE 132 KV SWITCHYARD 21 ST FEBRUARY 2011

PRILIMINARY REPORT ON THE ACCIDENT AT RANTAMBE 132 KV SWITCHYARD 21 ST FEBRUARY 2011 PRILIMINARY REPORT ON THE ACCIDENT AT RANTAMBE 132 KV SWITCHYARD 21 ST FEBRUARY 2011 DGM (MAHAWELI COMPLEX OFFICE) CEYLON ELECTRICITY BOARD MAHAWELI COMPLEX 07 th MARCH 2011 1 Detail of Accident The bus

More information

Dual Power. Protection. Protection

Dual Power. Protection. Protection 54 Fault Clearing Systems by Damien Tholomier., AREVA T&D Automation, Canada Dual Power Single Battery What if it? Short circuits and other abnormal power system conditions are very rear, but may result

More information

Hydro Plant Risk Assessment Guide

Hydro Plant Risk Assessment Guide September 2006 Hydro Plant Risk Assessment Guide Appendix E8: Battery Condition Assessment E8.1 GENERAL Plant or station batteries are key components in hydroelectric powerplants and are appropriate for

More information

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 New RIS transformer bushings The paper-free solution Transformer condenser bushings Why a new technology? To preserve

More information

www. ElectricalPartManuals. com Instructions for Cast Resin Bushing, 15 KV & Below

www. ElectricalPartManuals. com Instructions for Cast Resin Bushing, 15 KV & Below Instructions for Cast Resin Bushing, 15 KV & Below Fig. 1 Cast Resin Bushing The Westinghouse Cast Resin Bushing, used for voltages 15KV and below, is made by casting an insulating resin around the conductor.

More information

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper GE Grid Solutions PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper PNO bushings are capacitance graded bushings with an oil impregnated paper core. PNO bushings are conform

More information

Energy Transmission & Distribution Services - Italy. SVEPPI laboratory...our services for your success. Answers for energy.

Energy Transmission & Distribution Services - Italy. SVEPPI laboratory...our services for your success. Answers for energy. Energy Transmission & Distribution Services - Italy SVEPPI laboratory...our services for your success. Answers for energy. ...our services for your success ENERGY - T&D Services Experience teaches us that

More information

DELTA4000 Accessories

DELTA4000 Accessories DELTA4000 Accessories TESTING LARGE SPECIMENS Resonating Inductor The resonating inductor expands the capacitance range of the DELTA automated insulation power factor test sets. The resonating inductor

More information

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide 1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,

More information

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK 1ZSC563-AAA en, Rev. 2 Resin Impregnated Paper Bushing, Oil to SF 6, Type GSBK Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,

More information

General information on handling and maintenance of SDC TM Solid Dielectric Capacitor Bushings

General information on handling and maintenance of SDC TM Solid Dielectric Capacitor Bushings General information on handling and maintenance of SDC TM Solid Dielectric Capacitor Bushings Electro Composites (2008) ULC Tel: (450) 431-2777 Web site: http://www.hubbellpowersystems.com/about/ec/ Revision

More information

SIEMENS Transmission and Distribution

SIEMENS Transmission and Distribution TITLE Long Term Maintenance and Care for Reyrolle L800/1000T E. C. Wright 19/07/04 This document is to be used in conjunction with Installation, Operation and Maintenance Schedule IOMS 864. Its aim is

More information

Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress.

Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress. Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress. George Fofeldea Power Engineer, 3M Canada August 2018 Abstract 3M invented cold shrink

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide 1ZSE 2750-112 EN, REV. 4 Wall bushings type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI

Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI T. Schütte, ABB Schweiz Ltd, High Voltage Components, Bushings, 2015-10-19 INMR2015 - Munich Field experience and

More information

Energy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th. Alex Bettencourt Managing Director

Energy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th. Alex Bettencourt Managing Director Energy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th Alex Bettencourt Managing Director National Association Made Up of Entire Industry Utilities Industry Academia / R&D

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide 1ZSE 2750-102 en, Rev. 7 Transformer bushings, type GOB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical

More information

LISTING REPORT/INSPECTION PROCEDURE

LISTING REPORT/INSPECTION PROCEDURE LISTING REPORT/INSPECTION PROCEDURE 291 Fairfield Avenue, Fairfield, NJ 07004 USA (973) 575-5252 File No. E1052012, Section 1 Issued: December 16, 2008 A representative sample of the product covered by

More information

SWITCHGEAR DIVISION PRODUCT PROFILES

SWITCHGEAR DIVISION PRODUCT PROFILES SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,

More information

Power Products Division. Power Services Service underpins everything we do

Power Products Division. Power Services Service underpins everything we do Power Products Division Power Services Service underpins everything we do Business Overview ABB s Power Services is a support group to all power products and systems business units within ABB. We provide

More information

Independent Testing Laboratory for High Voltage Equipment

Independent Testing Laboratory for High Voltage Equipment T E S T I N G L A B O R A T O R Y Independent Testing Laboratory for High Voltage Equipment 1 CHALLENGING ENVIRONMENT The primary concern for utilities is to ensure grid reliability, efficiency, and security.

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide Table of contents 1 Introduction... 3 1.1 Style Number... 3 1.1.1 Style Number Examples... 3 2 Basic Characteristics... 4 2.1

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

Table of Contents. 4. Before a New Turbocharger is Installed

Table of Contents. 4. Before a New Turbocharger is Installed Table of Contents 1. Turbocharger Overview ------------------------------------------------------------------ 1.1. Definition -----------------------------------------------------------------------------

More information

McNary Northshore Fishway Hydro Project. History & Lessons Learned

McNary Northshore Fishway Hydro Project. History & Lessons Learned McNary Northshore Fishway Hydro Project History & Lessons Learned May 6, 2017 21 th Annual TECHNICAL SEMINAR Machines, Maintenance, and Management: Keeping Hydro Facilities Up and Running History & Lessons

More information

Impact of Burnout Ovens on Reliability. Mechanical Impact of High Temperature Stripping Of Induction Motor Stators

Impact of Burnout Ovens on Reliability. Mechanical Impact of High Temperature Stripping Of Induction Motor Stators Mechanical Impact of High Temperature Stripping Of Induction Motor Stators Howard W Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc. Introduction

More information

LEARNING BY FAILURES A TRANSFORMER CASE STUDY A QUALITY PRESPECTIVE

LEARNING BY FAILURES A TRANSFORMER CASE STUDY A QUALITY PRESPECTIVE LEARNING BY FAILURES A TRANSFORMER CASE STUDY A QUALITY PRESPECTIVE A K Sharma, GM (IS) Nishith Mehta DGM (IS) M Misbahul Islam, Sr Manager (IS) Amit Kumar, Manager (IS) NTPC, Regional Inspection Office,

More information

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide 1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

NXPLUS C Single busbar. Maintenance-free for lifetime

NXPLUS C Single busbar. Maintenance-free for lifetime NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage

More information

CHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS

CHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS 22 CHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS 3.1 INTRODUCTION A large number of asynchronous motors are used in industrial processes even in sensitive applications. Consequently, a defect can induce

More information

GENERAL. CONSTRUCTION External

GENERAL. CONSTRUCTION External Surge Arresters VariSTAR Type AZG4 Surge Arresters for Systems through 400 kv IEC 20-kA; Line Discharge Class 4 Electrical Apparatus I235-84 GENERAL VariSTAR AZG4 Surge Arresters incorporate the latest

More information

Transformer bushings, type GOA 250. Installation and maintenance guide

Transformer bushings, type GOA 250. Installation and maintenance guide Transformer bushings, type GOA 250 Installation and maintenance guide This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor

More information

Product Information. Neutral Wall Bushing GOFL

Product Information. Neutral Wall Bushing GOFL ABB Components Info-No. 2750 515-93en, Rev. 1 From / Date Product Information Neutral Wall Bushing GOFL Description Page Design 2 Voltage tap 2 Dimensions 2 Terminals 2 Mounting instruction Packing 4 Storing

More information

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent

More information

170/8 Unusual Accident No. 118 In this issue UPLIFT

170/8 Unusual Accident No. 118 In this issue UPLIFT No. 170 An Engineer s Casebook No.70:- Glandless Pumps 170/1 Our Most Frequent Accidents 170/2 A Runaway FLT 170/3 An Unexpected Fall 170/4 Crash Barriers 170/5 A Leak Leads to a Fire 170/6 Another Unexpected

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Case Study: Silver Lining in Plants Oil Analysis Program Prevents Catastrophic Generator Failure

Case Study: Silver Lining in Plants Oil Analysis Program Prevents Catastrophic Generator Failure Case Study: Silver Lining in Plants Oil Analysis Program Prevents Catastrophic Generator Failure Analysts, Inc. Contributing Authors: Tim Gibbons, Data Analysts, OMA I Kris Sherman, National Account Manager,

More information

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required! DB 750-205 January 2007 Supercedes: December 2006 Now available with Vacuum Interrupter Monitor VBT Switch 15kV - 69kV VBU-T Switch 69kV - 230kV Longest Life Product for Electric Furnace Applications!

More information

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing

More information

Transformers for Power Applications

Transformers for Power Applications Power Applications for Power Applications Tamini designs power transformers for the distribution, transmission and production of electricity from both conventional and renewable sources. The Company s

More information

EMPAC Metal enclosed capacitor bank for wind applications

EMPAC Metal enclosed capacitor bank for wind applications EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks

More information

ENGINE, COMBUSTION ASSEMBLY - INSPECTION OF OUTER COMBUSTION CASE P/N M

ENGINE, COMBUSTION ASSEMBLY - INSPECTION OF OUTER COMBUSTION CASE P/N M SERVICE BULLETIN 206L-16-179 7 October 2016 Revision A, 8 December 2016 MODEL AFFECTED: 206L-1, 206 L-3, and 206 L-4 SUBJECT: HELICOPTERS AFFECTED: ENGINE, COMBUSTION ASSEMBLY - INSPECTION OF OUTER COMBUSTION

More information

CAST RESIN TRANSFORMERS

CAST RESIN TRANSFORMERS MODEL TAM CAST RESIN - TAM TYPE Epoxy cast resin dry-type transformers are recommended to operate in places that require security, the materials used in its construction are hard to combust and are self-extinguishable

More information

Type VRLTC load tap changer

Type VRLTC load tap changer Pilot inspection report Type VRLTC load tap changer Product: Type VRLTC, on-tank, vacuum reactance load tap changer Rating: 1500 A, 150 kv BIL By: Jon Brasher - Technical Specialist and Senior Account

More information

Targeted Application of STATCOM Technology in the Distribution Zone

Targeted Application of STATCOM Technology in the Distribution Zone Targeted Application of STATCOM Technology in the Distribution Zone Christopher J. Lee Senior Power Controls Design Engineer Electrical Distribution Division Mitsubishi Electric Power Products Electric

More information

LEAP - Life Expectancy Analysis Program For Electrical Rotating Machines. Marcio Gennari ABB Brazil Automation Products Machines Service Osasco

LEAP - Life Expectancy Analysis Program For Electrical Rotating Machines. Marcio Gennari ABB Brazil Automation Products Machines Service Osasco LEAP - Life Expectancy Analysis Program For Electrical Rotating Machines Marcio Gennari ABB Brazil Automation Products Machines Service Osasco LEAP - Introduction ABB India (excellence center in insulation

More information

First Applications on AltaLink s Network. Roggero Ciofani, P. Eng. Colin Clark, P. Eng.

First Applications on AltaLink s Network. Roggero Ciofani, P. Eng. Colin Clark, P. Eng. First Applications on AltaLink s Network Roggero Ciofani, P. Eng. Colin Clark, P. Eng. Overview Technology Overview Applications and Alternatives Advantages Alberta Special Considerations Operational Implications

More information

ENVIRONMENTAL & ENGINEERING SERVICES DEPARTMENT

ENVIRONMENTAL & ENGINEERING SERVICES DEPARTMENT CITY OF LONDON ENVIRONMENTAL & ENGINEERING SERVICES DEPARTMENT WASTEWATER TREATMENT OPERATIONS VAUXHALL WASTEWATER TREATMENT PLANT 2013 ANNUAL REPORT FEBRUARY 2014 Vauxhall Wastewater Treatment Plant 2013

More information

CHAPTER 20: Operation and maintenance

CHAPTER 20: Operation and maintenance Pressurized Irrigation Techniques 20.1 CHAPTER 20: Operation and maintenance INTRODUCTION The efficient operation of an irrigation system depends mainly on the ability of the farmer to make the best use

More information

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide 1ZSE 2750-102 en, Rev. 9 Transformer bushings, type GOB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

INESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation

INESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation MOBILE SUBSTATIONS Energy Solution INTERNATIONAL FAIR MOBILE SUBSTATIONS ENERGY SOLUTION Complete design for energy s generations, transmission and distribution Mobile Substations Applications of Inesing

More information

MOBILE SUBSTATION DESIGN Brad Bozich & Vitor Vieira 2755 Northwoods Parkway Norcross, Georgia

MOBILE SUBSTATION DESIGN Brad Bozich & Vitor Vieira 2755 Northwoods Parkway Norcross, Georgia MOBILE SUBSTATION DESIGN Brad Bozich & Vitor Vieira 2755 Northwoods Parkway Norcross, Georgia 30071 678.982.8928 brad.bozich@efacec.com SCOPE This document is intended to help define the main parameters

More information

Case Study: Silver Lining in Plants Oil Analysis Program Prevents Catastrophic Generator Failure

Case Study: Silver Lining in Plants Oil Analysis Program Prevents Catastrophic Generator Failure Case Study: Silver Lining in Plants Oil Analysis Program Prevents Catastrophic Generator Failure Analysts, Inc. Contributing Authors: Tim Gibbons, Data Analysts, OMA I Kris Sherman, National Account Manager,

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical vo1e.5s 0j 44, AMY., CK NI r. SIGNATURE Mechanical Civil Protection & Control t^ /DATE 1 o Transmission & Distribution AND Telecontrol

More information

Customer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment

Customer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment Customer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment ABB LEAP Overview ABB LEAP - Benefits for customer Motivation to perform LEAP Failures

More information

Introduction to Condition-Based Maintenance Best Practices

Introduction to Condition-Based Maintenance Best Practices Introduction to Condition-Based Maintenance Best Practices Maintenance Strategy Breakdown Maintenance Preventive Maintenance (Time Base) Predictive Maintenance Proactive Maintenance Rationalizing Spending

More information

High voltage in motion Environmentally friendly circuit breakers and economic long-rod insulators

High voltage in motion Environmentally friendly circuit breakers and economic long-rod insulators High voltage in motion Environmentally friendly circuit breakers and economic long-rod insulators Christian Hückler, Sales Manager Air-Insulated Switchgears siemens.at/future-of-energy High voltage in

More information

TRANSFORMERS UP TO 750 kv

TRANSFORMERS UP TO 750 kv Electric Co. Ltd. TRANSFORMERS UP TO 750 kv CONTENTS General... 2 Products... 3 Construction...4 Magnetic core... 4 Windings...5 Frame structure... 6 Connections...6 Tap changer and motor drive...7 Tank...

More information

ACCELERATED CABLE AGING TESTS for DISTRIBUTION and TRANSMISSION CABLES PART 1 HV AC PAPER CABLES

ACCELERATED CABLE AGING TESTS for DISTRIBUTION and TRANSMISSION CABLES PART 1 HV AC PAPER CABLES ACCELERATED CABLE AGING TESTS for DISTRIBUTION and TRANSMISSION CABLES PART 1 HV AC PAPER CABLES Joseph T. Zimnoch Consultant ICC Educational Program October 26, 2011 Denver, Colorado ACKNOWLEDGMENT The

More information

Transformer bushings, type GSA-OA Technical guide

Transformer bushings, type GSA-OA Technical guide Transformer bushings, type GSA-OA Technical guide ZSE 2750- en, Rev. 5, 2005-05-5 This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to

More information

Report for CSP Joint Venture Click to edit Master text styles Second level Third level. Fifth level

Report for CSP Joint Venture Click to edit Master text styles Second level Third level. Fifth level Report for CSP Joint Venture Click to edit Master text styles Second level Third level Out of service examination, ultrasonic thickness Fourth survey and level paint evaluation for tanks T221 & T222 Fifth

More information

PR-PUB-NLH-034 NLH 2015 Prudence Review Page 1 of 1

PR-PUB-NLH-034 NLH 2015 Prudence Review Page 1 of 1 PR-PUB-NLH-034 NLH 2015 Prudence Review Page 1 of 1 1 2 3 Q. Western Avalon T5 Tap Changer: Please provide the oil quality testing result records for the Western Avalon T5 transformer tap changer compartment

More information

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number: 25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report Report Number: Date: RN-R7604 9/16/2013 Table of Contents I. OBJECTIVE... 2 II. SUMMARY... 2 III. CONCLUSION... 2 IV. CABLE DATA... 2 V.

More information

Health and Safety Executive, Technology and Health Sciences Division, Magdalen House, Bootle.

Health and Safety Executive, Technology and Health Sciences Division, Magdalen House, Bootle. SECURITY OF ELECTRICAL SUPPLY SYSTEMS INCLUDING STANDBY SUPPLIES Eur.Ing J.A. McLean B.Sc. C.Eng. MIEE. FIOSH Health and Safety Executive, Technology and Health Sciences Division, Magdalen House, Bootle.

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

Instruction Manual for POC Bushings

Instruction Manual for POC Bushings 1. Scope This instruction contains general procedures to be followed during receiving, installation, storage and maintenance of all PCORE POC bushings. This instruction does not cover all contingencies

More information

S1 Series. 5-kV and 10-kV Insulation Resistance Testers. S1 Series 5-kV and 10-kV Insulation Resistance Testers

S1 Series. 5-kV and 10-kV Insulation Resistance Testers. S1 Series 5-kV and 10-kV Insulation Resistance Testers S1 Series CAT IV 600 V safety rating Line supply or battery operated Noise rejection (2mA or 4mA rms@200v and above) for use in high voltage substations or switchyards 5mA output current provides fast

More information

Replacement Parts Bulletin For Line Backer TM Circuit Switchers

Replacement Parts Bulletin For Line Backer TM Circuit Switchers Replacement Parts Bulletin For Line Backer TM Circuit Switchers Do you have Line Backer TM circuit switchers on your system? Have they given you problems? Do they still? Don t know where to turn for help?

More information

Experience on Deterioration Survey of Aged 550 kv GIS and Optimized Evaluation Model in Thailand

Experience on Deterioration Survey of Aged 550 kv GIS and Optimized Evaluation Model in Thailand PS1 Experience on Deterioration Survey of Aged 550 kv GIS and Optimized Evaluation Model in Thailand S. Singharerg T. Watanabe Electricity Generating Authority of Thailand Chubu Electric Power Co., Inc.

More information

www. ElectricalPartManuals. com Substation Transformers Primary or Secondary Open

www. ElectricalPartManuals. com Substation Transformers Primary or Secondary Open Substation Transformers Primary or Secondary Open GENERAL Cooper Power Systems Primary or Secondary Open Substation Transformers are designed to meet exact customer specifications. Flexibility in design,

More information

P O B o x S t. L o u i s, M O P h o n e : ( ) ~ E m a i l : w m h u I t a o l.

P O B o x S t. L o u i s, M O P h o n e : ( ) ~ E m a i l : w m h u I t a o l. P O B o x 3 11 5 4 S t. L o u i s, M O 6 3 1 3 1-0 1 5 4 P h o n e : ( 3 1 4 ) 9 6 6-8 9 1 9 ~ E m a i l : w m h u I t t @ a o l. c o m Triboelectric Charge Generation with regard to Partially and Fully

More information

26 - COOLING SYSTEM CONTENTS ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 COOLING SYSTEM FAULTS... 1

26 - COOLING SYSTEM CONTENTS ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 COOLING SYSTEM FAULTS... 1 26 - COOLING SYSTEM CONTENTS Page LAND ROVER V8 DESCRIPTION AND OPERATION ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 FAULT DIAGNOSIS COOLING SYSTEM FAULTS... 1 REPAIR COOLANT - DRAIN

More information

SECTION 3. EXHAUST SYSTEMS

SECTION 3. EXHAUST SYSTEMS 9/8/98 AC 43.13-1B 8-45. GENERAL. Any exhaust system failure should be regarded as a severe hazard. Depending upon the location and type of failure, it can result in carbon monoxide (CO) poisoning of crew

More information

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB Micafil transformer oil-sf 6 bushings GARIP / RTKG 72.5 55 kv Power and productivity for a better world TM ABB Design and accessories The design of the main RIP insulating body includes a solid, non-removable

More information

DELTA4000. Accessories

DELTA4000. Accessories DELTA4000 Accessories WWW.MEGGER.COM TESTING LARGE SPECIMENS Resonating Inductor The resonating inductor expands the capacitance range of the DELTA automated insulation power factor test sets. The resonating

More information