1 Diagnostic Experience on HV Bushings Retired from Service MANUEL GUZMÁN-V
2 Diagnostic experience on HV bushing retired from service. Manuel Guzmán; Fernando Elizarraraz; Ricardo Montes Comisión Federal de Electricidad MEXICO
3 Introduction. In order to attend the electricity demand in Mexico, CFE operates and maintains more than 2700 power transformers in 470 substations with a near capacity of MVA. In the substations at generation plant, CFE uses three-phase power transformers. In transmission substations, uses single phase auto transformers The nominal voltages are 400 kv, 230 kv and < 230 kv. Most of bushings installed are Oil Impregnated Paper (OIP) and some are of Resin Bonded Paper (RBP) and Resin Impregnated Paper (RIP). CFE Substations Substations 470 MVA in operation MVA instaled Power Transformers 2 762
4 According with statistical analysis about failures on power transformers, since 2000 to 2014, 27.7% were due to bushing failures. It s the second cause of power transformer failures Main causes of Power Transformer Failures
5 The percentage of bushing failures related with the nominal voltage is: Bushing failures related with nominal voltage
6 And 53% of total failures with transformer burning was due to bushing failure. Power Transformer burning causes
7 Findings about failures on polymeric housing bushings were discussed in previous document (INMR 20013).
8 Technical reference for laboratory test. CFE buys power transformers and the manufacturers are in charge of select the standard for bushings, however the CFE technical specification [1] is based on the international standard IEC [2]. This standard indicates the bushings reference values for C1 in laboratory test: Tan δ of Max Δtan δ for OIP (at Um & 1.05Um/ 3) Partial discharges of 10 Um and Um/ 3 But for Tan δ, most of the manufacturers have lower values. Tan δ for OIP
9 In the diagnostic process these values are used only as a reference, then a technique that combines several tests is applied, such as measuring C1, tanδ, (before and after) a power frequency (80% to 85%) withstand voltage test and the measurement of partial discharges. There are no tests on insulating oil.
10 The CFE substations manual recomends to make diagnostic test on bushing due the following causes:! Lost of oil level.! When occurs a failure on power transformer.! On the other two bushings if one fails (three phase power transformer).! If the bushing remains on warehouse during years and is necesary to install it (spare parts).! If the results of on site test of Power Factor is high.! When the power transformer is repaired and its necesary to verify the old bushing condition.! After severe earthquake.! When the bushing is retired from the power transformer because it is relocated in other substation.! In order to prevent a failure at the end of its useful life.! When the bushing is refurbished. Laboratory test set up
11 Technical reference for on site test Taking in account previous experiences and different recommendations from technical groups, CFE developed a bushing test on site procedure. The technical document is a substation maintenance manual named Manual de Transformadores y Reactores de potencia, Tomo I y Tomo II, junio 2007 [3] wich is also referenced on CFE Technical Spec [1]. For bushing test on site the reference values are: FP: Up to 0.5% at 20 C. C1: ± 2% of original value C2: ± 2% of original value
12 In some cases if there is not enough information from test results, a dielectric spectroscopy test could give us more information about insulation condition.
13 Findings during test on laboratory Always with the time of operation in mind, and the Std. of reference. " The bushing presents changes in C1 and in tan δ values. " Presents a fault (perforation) during the power frequency withstand test. " Values of partial discharges from 50 pc up to 500 PC. " All the previous results have been presented either alone or in combinations, which helps us to give a recommendation, for example: " If the bushing has DP values near to 100 pc and tanδ values near to 0.008, but the C1 and power frequency withstand test shows good results, a regeneration of the insulating oil is recommended, and re-testing after the regeneration.
14 Findings during test on site According to [3] the period of maintenance on transformers is two years, then the most common findings between periods are: Power Factor differences up to 1% Exponential differences on C1 measurements due to foils degradation. Corrosion on capacitive tap connections to the outside, leads false connections. Movement of section of the porcelain from flange.
15 Most common failed parts on bushings
16 Degradation of sealing and moisture ingress.
17 Corrosion on Capacitive tap materials. This kind of failure is common on bushings. This connection is one of the weakest part of bushings. The material used in the connection to outside suffer corrosion and its severity depends on: Material Weather In may cases the cost of spare parts is expensive. If the bad connection is not detected, the results would be catastrophic.
18 Capacitive foil degradation. Degradation of insulating material by ageing. Degradation of insulating material by moisture.
19
20 Rupture or separation of porcelain from flange.
21 Bushing repair. If there is not bushing for substituting one failed, a common practice is to repair it. The repair includes: " Repair the connection, installation and sealing of C1 Tap. " Regeneration or change of insulating oil. " Drying of insulating parts. " Re-tightening of flanges, connectors and bushing terminals. " Rewinding of the last paper foils without modifying the capacitive foils. " Alignment of porcelain hollow core insulator and flange. " Re-sealing between porcelain sections and flange. " Minor repairs on external porcelain parts. " Oil level recovery.! The C1 is not repaired # After bushing repairing activities, a diagnostic test routine is performed. If the test results are satisfactory, according with criteria mentioned before, the bushing is installed.
22 Discussion about standards. CFE bases its bushing technical specification on IEC [2] standard and the last edition takes flange dimensions from ANSI standard [4]. It is necessary to add a technical criteria considering C1 increase that indicates incipient fail (1% every 5 years). There is not technical criteria that consider the increase of tanδ (as CT standard indicates). A sampling valve to test de insulating oil might be necessary. IEC standard [2] don t include flange dimensions.
23 Final remarks. The bushing is an accessory for the power transformer but bushing contributes importantly to power transformer failure. Its important to have diagnostic tools in order to prevent bushing failures and power transformer failures. Depending on transformer importance, it is possible to carry out high voltage diagnostic tests on site, mainly with 400 kv and above, avoiding bushing risk damage due movement to laboratory facilities. Have bushings as spare parts is expensive because of lack of definitions about flange dimensions and their different designs. It s important to have experience in bushing rebuild and diagnostic test. It is helpful for bushing recovery in a short time.
24 Final remarks. Online monitoring systems have not been shown effectiveness yet, there are some doubts about operation and performance in service: Furthermore, monitoring systems, in some cases are cause of failure in power transformers, rather than being a stand for reliability. Regeneration of bushing is a technical and economic option to reenergize the power transformer in a short time, while it is possible to buy a new one. CFE has been done these activities in México since 20 years ago, with successful results.
25 Bibliography. [1] Esp CFE , Boquillas de alta tensión de 15 kv a 420 kv para transformadores y reactores de potencia, 2011 [2] International Standard IEC 60137, Insulated bushings for alternating voltages above 1000 V, [3] Manual Transformadores y Reactores de potencia, Tomo I y Tomo II, junio [4] ANSI/IEEE C , General requirements and test procedures for Aparatus Bushings, 2004.
26 Thanks for your kind attention!! Manuel Guzmán Fernando Elizarraraz Ricardo Montes
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 New RIS transformer bushings The paper-free solution Transformer condenser bushings Why a new technology? To preserve
More informationTechnical Specification For Outdoor Substation Harmonic Filter Banks
Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field
More informationField Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI
Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI T. Schütte, ABB Schweiz Ltd, High Voltage Components, Bushings, 2015-10-19 INMR2015 - Munich Field experience and
More informationResin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK
1ZSC563-AAA en, Rev. 2 Resin Impregnated Paper Bushing, Oil to SF 6, Type GSBK Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More informationA manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard
A manufacturer s view of bushing reliability, testing and analysis By Lars Jonsson Håkan Rudegard 1 A manufacturer s view of bushing reliability, testing and analysis Lars Jonsson Håkan Rudegard ABB Sweden
More information1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide
1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationOIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC
OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) 1800 24kV to 550kV up to 5000A IEC 60137-2008 Features If you need any transformer bushing proven in operation conditions around the world, Trench
More information1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide
1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover
More informationOIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC
OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) 1800 24kV to 550kV up to 5000A IEC 60137-2008 Features If you need any transformer bushing proven in operation conditions around the world, Trench
More information1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide
1ZSE 2750-106 EN, REV. 7 Oil SF 6 bushings type GOEK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationA of 3. Edition : Date : Page : Document No. Amendments :
&RQWHQWV,QVWUXFWLRQIRURSHUDWLRQ %XVKLQJ7HVW7DS +/$%( Document No. Edition : Date : Page : Amendments : A 7..99 of 3 *((5$/'(6,* 38536( &(&7, &DSDFLWDQFHDQGSRZHUIDFWRUPHDVXUHPHQWV 3HUPDQHQWPHDVXUHPHQWV,68/$7,7(676
More information1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide
1ZSE 2750-112 EN, REV. 4 Wall bushings type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationTransformer bushings, type GOH. Technical guide
Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More informationResin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide
1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More informationPNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper
GE Grid Solutions PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper PNO bushings are capacitance graded bushings with an oil impregnated paper core. PNO bushings are conform
More informationEnergy Transmission & Distribution Services - Italy. SVEPPI laboratory...our services for your success. Answers for energy.
Energy Transmission & Distribution Services - Italy SVEPPI laboratory...our services for your success. Answers for energy. ...our services for your success ENERGY - T&D Services Experience teaches us that
More informationMicafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB
Micafil transformer oil-sf 6 bushings GARIP / RTKG 72.5 55 kv Power and productivity for a better world TM ABB Design and accessories The design of the main RIP insulating body includes a solid, non-removable
More informationCABLE SYSTEMS. Accessories and Systems for Medium and High-Voltage Cables up to 300 kv.
MV-CONNEX, HV-CONNEX, IXOSIL Terminations, IXOSIL MSA Slip-on Joint Boxes CABLE SYSTEMS Accessories and Systems for Medium and High-Voltage Cables up to 300 kv. Welcome to the CABLE SYSTEMS Centre of Competence.
More informationTransformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC
Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC 60137-2008 High current bushings for transformer Features Bushing Type CFPT version Porcelain Insulator Trench RIG technology for
More informationHigh Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide
1ZUA2761-500 rev. 5, 6 April 2010 High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide 1ZUA2761-500 rev. 5, 6 April 2010 2 / 9 Table of contents 1 Description... 3 2 Ratings...
More information500KV BUSHINGS FAILURES AND BUSHING OIL SAMPLING PROGRAM. Mike Lau BC Hydro
500KV BUSHINGS FAILURES AND BUSHING OIL SAMPLING PROGRAM Mike Lau BC Hydro ABSTRACT In June 2001, a 500KV bushing ( CGE, type U ) failed and resulted in a catastrophic failure of a generator step-up transformer
More informationEMPAC Metal enclosed capacitor bank for wind applications
EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks
More informationA of 14. Edition : Date : Page : Document No. Amendments :
&RQWHQWV,QVWUXFWLRQVIRU(UHFWLRQ 2SHUDWLRQ 2XWGRRU7UDQVIRUPHU%XVKLQJ 57.)N9.6,7 6HULHV&25,3 +/$%( Document No. Edition : Date : Page : Amendments : A 29.11.02 1 of 14 *(1(5$/'(6,*1 3$&.,1* %XVKLQJ6XSSO\&RQGLWLRQV
More informationSIEMENS Transmission and Distribution
TITLE Long Term Maintenance and Care for Reyrolle L800/1000T E. C. Wright 19/07/04 This document is to be used in conjunction with Installation, Operation and Maintenance Schedule IOMS 864. Its aim is
More informationABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers
ABB PTTR SPAIN Zaragoza. The product: Cast coil transformers ABB BA Transformers - 1-5/7/2007 Dry Type Vacuum Cast Coil Transformer INTRODUCTION ABB BA Transformers - 2 - Product Portfolio II Dry Type
More informationProduct presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 Dry-type transformers Innovative Technology What is a dry transformer? ABB manufactures a transformer which does
More informationBushings for High Voltage AC Applications
Bushings for High Voltage AC Applications Selection guide 1ZSE 2750-100 en, Rev. 3, 2006-03-15 During selection of for high voltage applications several important factors have to be considered to ensure
More informationSolid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER
Solid Dielectric Load Break Switch SPECIFICATION 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED VACUUM LOAD INTERRUPTING
More informationHigh Voltage and Extra High Voltage Cables
High Voltage and Extra High Voltage Cables GUIDE TO THE SELECTION OF EHV AND HV CABLES EHV and HV cables are specially designed on the basis of the project data. To determine appropriate design of a high
More informationTransformers for Power Applications
Power Applications for Power Applications Tamini designs power transformers for the distribution, transmission and production of electricity from both conventional and renewable sources. The Company s
More informationFundamentals of condenser bushings
FUNDAMENTALS Fundamentals of condenser bushings Bushing is a device that enables one or several conductors to pass through a partition such as a wall or a tank, insulating the conductor from it ABSTRACT
More informationExperience on Deterioration Survey of Aged 550 kv GIS and Optimized Evaluation Model in Thailand
PS1 Experience on Deterioration Survey of Aged 550 kv GIS and Optimized Evaluation Model in Thailand S. Singharerg T. Watanabe Electricity Generating Authority of Thailand Chubu Electric Power Co., Inc.
More informationHigh voltage in motion Environmentally friendly circuit breakers and economic long-rod insulators
High voltage in motion Environmentally friendly circuit breakers and economic long-rod insulators Christian Hückler, Sales Manager Air-Insulated Switchgears siemens.at/future-of-energy High voltage in
More informationSmall wonder. Station service voltage transformers for small power requirements
Small wonder Station service voltage transformers for small power requirements MATHEW PAUL An estimated 1.3 billion people worldwide have no access to electricity. In small communities, this is often due
More informationAnalysis of Partial Discharge in OIP Bushing Models
Analysis of Partial Discharge in OIP Bushing Models ZEESHAN AHMED Degree project in Electical Engineering Electromagnetic Engineering Stockholm, Sweden 2011 XR-EE-ETK 2011:008 Analysis of Partial Discharge
More information1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide
1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationMOBILE SUBSTATION DESIGN Brad Bozich & Vitor Vieira 2755 Northwoods Parkway Norcross, Georgia
MOBILE SUBSTATION DESIGN Brad Bozich & Vitor Vieira 2755 Northwoods Parkway Norcross, Georgia 30071 678.982.8928 brad.bozich@efacec.com SCOPE This document is intended to help define the main parameters
More informationSolution Overview. Asset Condition Monitoring. Extend operational life and reduce downtime
Solution Overview Asset Condition Monitoring Extend operational life and reduce downtime QUALITROL Integrated Monitoring Server : Data Integration Diagram SMARTSUB Substation Condition Monitoring: Transformer
More informationVEIKI-VNL Electric Large Laboratories Ltd. H-1158-Budapest, Vasgolyó utca 2-4. HUNGARY
VEIKI-VNL Electric Large Laboratories Ltd. H-1158-Budapest, Vasgolyó utca 2-4. HUNGARY VEIKI-VNL Ltd. VEIKI-VNL Electric Large Laboratories Ltd. is an independent accredited testing member laboratory of
More informationOur Global Solutions CAPABILITIES
Our Global Solutions COMPANY With our headquarters in Ontario, Canada, Hammond Power Solutions (HPS) operates out of multiple plants located throughout Canada, India, US, Mexico and Europe. HPS has expanded
More informationCP Automatic capacitor bank
CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor
More informationOTCF. Grid Solutions. Capacitor Voltage Transformers 72.5 kv to 800 kv. Quality Product Design. Seismic Withstand Capability.
GE Grid Solutions OTCF Capacitor Voltage Transformers 72.5 kv to 800 kv In high and extra high voltage transmission systems, capacitor voltage transformers (CVTs) are used to provide potential outputs
More informationHIGH VOLTAGE MODULE TEST SYSTEM
HIGH VOLTAGE MODULE TEST SYSTEM 4.0/4 Module Test Systems n AC, DC, and impulse testing n Factory testing n R&D n Education / training MODULES FOR VOLTAGE GENERATION Test transformers for 100 and 200 kv
More informationHigh Voltage Technology & Testing
The Power of Trust. The Future of Energy. HIGH VOLTAGE TESTING Qualification testing, condition assessment, and forensic analysis Manufacturers and utility users of high-voltage electrical equipment face
More informationZREW Transformers Perfection in Detail. a company of Rauscher & Stoecklin SERW ZREW Tesar
ZREW Transformers Perfection in Detail a company of Rauscher & Stoecklin SERW ZREW Tesar ZREW Your partner for high quality transformers A basic requirement for power transformers is a reliable and efficient
More information1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide
1ZSE 2750-102 en, Rev. 7 Transformer bushings, type GOB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical
More informationDRY TYPE TRANSFORMERS
DRY TYPE Trafotek transformers are made to meet customer requirements in demanding applications. We are specially focused on manufacturing transformers for different types of frequency converters and special
More informationEnergy Division. PCA Single Column Polymeric Surge Arrester
Energy Division PCA Single Column Polymeric Surge Arrester Bowthorpe EMP pioneered the development of the polymeric composite housed surge arrester in the early 1980 s and since 1986 has a proven service
More information8DJ. Maintenance-free for lifetime
8DJ Maintenance-free for lifetime Energy Distribution Welcome! Page 2 October 1 st 2008 8DJ Main Applications for Medium-Voltage Switchgear Power generation Power stations G Power transmission High and
More informationTamini is the leading Italian company in the world for the design and production of industrial, power and special transformers.
Power Tamini is the leading Italian company in the world for the design and production of industrial, power and special transformers. Founded in 1916 in Milan, it supplies its products to the most important
More informationCustomer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment
Customer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment ABB LEAP Overview ABB LEAP - Benefits for customer Motivation to perform LEAP Failures
More informationINTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.
INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side
More informationLEAP - Life Expectancy Analysis Program For Electrical Rotating Machines. Marcio Gennari ABB Brazil Automation Products Machines Service Osasco
LEAP - Life Expectancy Analysis Program For Electrical Rotating Machines Marcio Gennari ABB Brazil Automation Products Machines Service Osasco LEAP - Introduction ABB India (excellence center in insulation
More informationDRIESCHER Y WITTJOHANN, S.A. MEDIUM VOLTAGE SOLUTIONS
DRIESCHER Y WITTJOHANN, S.A. MEDIUM VOLTAGE SOLUTIONS TECHNICAL SPECIFICATION LOAD BREAK DISCONNECTOR SWITCHES WITHOUT FUSE HOLDER UIT FUSE HOLDER SECTION CONTENTS PAGE 1 General Features 3 2 Standards
More informationOTAA Oil Impregnated Paper (OIP) Bushing for IEEE/ANSI Market
OTAA Oil Impregnated Paper (OIP) Bushing for IEEE/ANSI Market OTAA The OTAA is the next generation of Oil Impregnated Paper condenser bushing manufactured to IEEE C57.19.01 from 25 kv to 500 kv system
More informationPABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY
PABS Air-to-SF 6 Bushings 7.5-800 kv BUSHINGS AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS 7 - ANSI STANDARDS AN ALSTOM COMPANY PABS bushings are gas-insulated types that meet IEC 7, ANSI/IEEE or
More informationAnnex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005
Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate DPL110551000 according to DIN EN ISO/IEC 17025:2005 Period of validity: 20140612 to 20160711 Date of issue: 20140612 Holder of
More informationREAP CARE ROTATING ELECTRICAL ASSET PROGNOSTIC CARE
REAP CARE ROTATING ELECTRICAL ASSET PROGNOSTIC CARE Longevity approach Assess & Avoid Failures ROTATING ELECTRICAL ASSET PROGNOSTIC CARE Failure Statistics Failure Statistics Failure Statistics BEARING
More informationThe construction features of EdM transformers
S GENERAL Thanks to the long experience of EdM and to the sophisticated calculation and design techniques, our transformers for distribution, rectifiers and distribution can be realised in a very large
More information3EP1 Surge Arrester. Metal-oxide surge arrester without series gaps for high-voltage systems up to U m. = 170 kv
3EP1 Surge Arrester Metal-oxide surge arrester without series gaps for high-voltage systems up to U m = 170 kv Rated voltage up to 180 kv Nominal discharge current 10 ka, 8/20 µs Line discharge class LD1,
More informationCondenser Bushings. OIL-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C AND IEEE C AN ALSTOM COMPANY
PAO Condenser Bushings - kv BUSHINGS OI-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C.9.0-000 AND IEEE C.9.0-99 AN ASTOM COMPANY PAO bushings are capacitance-graded bushings with an oil-impregnated
More informationPower Arc Testing on Insulator Sets
Power Arc Testing on Insulator Sets Abstract:Insulator sets are among the most common components in transmission networks and their quality and performance play a vital role in ensuring a reliable electricity
More informationIncrease transformer reliability and availability: From Condition Assessment to Site Repair
Increase transformer reliability and availability: From Condition Assessment to Site Repair Lars Eklund Pierre Lorin Lars Pettersson ABB AB. ABB Sécheron Ltd ABB AB Ludvika, Sweden Geneva, Switzerland
More informationABB Transformadores para aplicaciones solares y eolicas
ABB Transformadores para aplicaciones solares y eolicas Product offering overview - Jeff City 1Ø and 3Ø pad-mounted transformers 10-250 kva 45-3000 kva ABB Group abril 9, 2016 Slide 2 Product offering
More informationBus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:
4 (Four) Pole Monoblock: Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers: Designed and manufactured in accordance with EN 50336:2002 and BS 2562: 1979 1 Introduction:
More information43-SDMS-04 REV. 00 SPECIFICATIONS FOR
43-SDMS-04 REV. 00 SPECIFICATIONS FOR SHUNT CAPACITOR BANK 13.8 kv THROUGH 69 kv FOR PRIMARY DISTRIBUTION SUBSTATIONS This specification is property of SEC and subject to change or modification without
More informationP2 : About Us. P3 : Elsewedy Transformers. P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers. P7 : Technical Data Sheets
P2 : About Us P3 : Elsewedy Transformers P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers P7 : Technical Data Sheets P8 : Transformer s Outline Drawing P9 : Accessories About Us
More informationChristian Ohler, ABB Switzerland Corporate Research Physics of Electric Power Systems. ABB Group August 1, 2012 Slide 1
Christian Ohler, ABB Switzerland Corporate Research Physics of Electric Power Systems ABB Group August 1, 2012 Slide 1 Purpose of this Presentation Describe power systems from a physicists point of view
More informationSUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationGAS INSULATED VOLTAGE TRANSFORMERS.
GAS INSULATED VOLTAGE TRANSFORMERS. This document may be subject to changes. Contact ARTECHE NISSIN to confirm the characteristics and availability of the products described here. CONTENTS 1. Presentation
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More information750 kva Transformer V Delta Primary Voltage - 480Y/277 Wye-N Voltage Secondary - NEMA 3R
750 kva Transformer - 12470V Delta Primary Voltage - 480Y/277 Wye-N Voltage Secondary - NEMA 3R Part #: MT-PMD-3P-12470D-750KVA-480Y.277-N3R Page: 1 The MT-PMD-3P-12470D-750KVA-480Y.277-N3R 12470D 3 Phase
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More informationGas-insulated medium-voltage switchgear. For the mining industry. Answers for energy.
Gas-insulated medium-voltage switchgear For the mining industry Answers for energy. Full power even under extreme conditions Reliable All over the world, the demand for mineral resources is increasing.
More informationGuideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society
Guideline No.: E-07(201501) E-07 TRANSFORMERS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and
More informationLow voltage bushings for pad-mounted distribution transformers Technical information guide
Transformer components Low voltage bushings for pad-mounted distribution transformers Technical information guide ABB low voltage bushings terminate a transformer s internal low voltage leads at the tank
More informationdfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide
dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide Table of contents 1 Introduction... 3 1.1 Style Number... 3 1.1.1 Style Number Examples... 3 2 Basic Characteristics... 4 2.1
More informationTransformers Global product offering
Distributor Line Card Transformers Global product offering ABB is a major transformer manufacturer throughout the world and offers both liquid-filled and dry-type transformers as well as services for complete
More informationNXPLUS C Single busbar. Maintenance-free for lifetime
NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage
More informationVisual comparison of Plain & Hazy PP Film
ECOVAR High Voltage Power Capacitors are manufactured at our Sinnar Plant in India which is an ISO 9001 accredited facility & houses a computer aided design manufacturing processing and testing infrastructure
More informationGuideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society
Guideline No.: E-07(201610) E-07 TRANSFORMERS Issued date: October 28,2016 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and
More information1ZSE en, Rev. 9. Transformer bushings, type GSA-OA Technical guide
1ZSE 2750-111 en, Rev. 9 Transformer bushings, type GSA-OA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationGuideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society
Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection
More informationTransformer Components & Accessories
Transformer Components & Accessories Brian Brinson Mechanical Design Manager brian.brinson@spx.com Agenda 1. Standards / Equipment Overview 2. Bushings 3. Arresters 4. Cooling Equipment 5. Instrument Transformers
More informationMICAFIL RIP Transformer Bushings AirRIP / RTKF kv
INSULATION AND COMPONENTS MICAFIL RIP Transformer Bushings AirRIP / RTKF kv MICAFIL AirRIP bushings offer an extended service life combined with enhanced reliability and safety to ensure the maximum availability
More informationDM Condenser bushings, kV DURESCA
DM Condenser bushings, 36 DURESCA Through wall bushings for indoor and outdoor applications, Resin Impregnated Paper IEC 601378 and IEEE C57.19.01.004 DURESCA Wall bushings Swiss quality combined with
More informationTransformer Bushing Type EKTO
Transformer Bushing Type EKTO Mounting Operating and Maintenance Instructions Operating Instructions BAL EKTO/04e Visum 01/14 T/gue Page 1 of 16 SAFETY INSTRUCTIONS These instructions are valid for mounting,
More informationRESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE.
RESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE. Alfonso Avila Ramírez. Corporativo Arian, S.A. de C.V., Hidalgo 6 Santa Ana Tlacotenco,
More informationtests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.
tests ( Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. electrical tests These tests verify contractual
More informationkv А
66-220 kv 2000-4000 А Publication 11.2011 "IZOLYATOR" PLANT performs design, manufacturing, warranty and post-warranty service of high-voltage bushings for various applications. The enterprise is the main
More informationCAST RESIN TRANSFORMERS
MODEL TAM CAST RESIN - TAM TYPE Epoxy cast resin dry-type transformers are recommended to operate in places that require security, the materials used in its construction are hard to combust and are self-extinguishable
More informationOIL-TO-OIL BUSHINGS SERIES PCTO SINGLE FLANGE TYPE VOLTAGE FROM 72,5 kv TO 420 kv
Page 1 of 14 OIL-TO-OIL BUSHINGS SERIES PCTO SINGLE FLANGE TYPE VOLTAGE FROM 72,5 kv TO 420 kv STORAGE, OPERATING AND MAINTENANCE INSTRUCTIONS Page 2 of 14 INDEX 1. DESCRIPTION...3 1.1 GENERAL...3 1.2
More informationCertified for best-in-class performance, reliability, and safety. Trihal sets a new standard for dry-type cast resin transformers
Certified for best-in-class performance, reliability, and safety Trihal sets a new standard for dry-type cast resin transformers Setting a new standard for dry-type cast resin transformers hospitals wind
More informationHoward Industries. Single-Phase Step
Howard Industries Utility Products Division Single-Phase Step Catolog Section 28-10 Voltage Regulators INTRODUCTION Howard Industries SVR-1 single-phase step voltage regulators are tapchanging autotransformers
More information3EP6 porcelain surge arrester
www.siemens.com/energy/arrester 3EP6 porcelain surge arrester Safe, reliable, long-lasting, and stable Answers for energy. Compact design high mechanical stability Sealing system Spring Maximum values
More informationYOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS
YOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS 1 TABLE OF CONTENTS ABOUT SVEL GROUP CAST-RESIN TRANSFORMERS ACCESSORIES AND OPTIONAL EQUIPMENT ENCLOSURE AND HOUSING TESTS AND QUALITY
More informationPORCELAIN BUSHINGS ED Series
PORCELAIN BUSHINGS ED Series An innovative design: the most popular and most reliable 1 kv bushing on the market www.cedaspe.com LV BUSHINGS ED by CEDASPE CEDASPE is happy to present a complete new family
More informationTransformer bushings, type GSA-OA Technical guide
Transformer bushings, type GSA-OA Technical guide ZSE 2750- en, Rev. 5, 2005-05-5 This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to
More informationAlstom Grid provides smart, efficient and environmentally-friendly solutions to deliver electricity reliably across the world GRID
Alstom Grid provides smart, efficient and environmentally-friendly solutions to deliver electricity reliably across the world GRID Maintenance & Onsite Repair of Transformers NTPC O&M Conference IPS 2013,
More informationGuideline for Using IEEE 1547 for Solar PV Interconnection Page 1
Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1 A Guide for Iowa s Municipal Electric Utilities On the How the IEEE 1547 Distributed Generation Interconnection Standard Affects Solar
More information