PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper
|
|
- Baldric Andrews
- 5 years ago
- Views:
Transcription
1 GE Grid Solutions PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper PNO bushings are capacitance graded bushings with an oil impregnated paper core. PNO bushings are conform to IEC / ISIS 2099 standards. Bushings are designed for use in power transformers and can be installed up to a maximum of 45 inclination from vertical. Key Benefits Bushings with longer lifetime and higher reliability Utilisation under extreme weather condition (lower pour-point value) No performance reduction with age Voltage and Current Ratings Rated voltage range for PNO bushings, normal cantilever load, is 52 to 170 kv. Heavy cantilever load is for bushings rated > 245 kv. PNO bushings, for a rated voltage, are designed in order to have the same overall dimensions for all the normal service currents. There are three connection alternatives for the conductor: Draw lead connection Draw rod connection Bottom/Solid Stem connection Bushing Design Design, components and manufacturing technology promote an average lifetime in excess of 30 years under normal operating conditions. Imagination at work
2 Main Features Range 52 to 420 kv Current up to 3,150 A Oil-impregnated paper Air side: porcelain insulator Oil side: epoxy resin insulator Partial discharge: max. 5 pc at 1.5 Un/ 3 High grade insulating oil Provided with power factor tap Head made of special UHV filter prismatic glass with oil level indication visible at any angle of sight for bushings rated up to 245 kv and metallic head with magnetic oil gauge for 420 kv bushings Flange made of cast aluminum alloy Standard angle of installation max. of 45 from vertical Components Fig. 2: Bushings 245 kv 1. HV Terminal 2. UHV filter glass 3. Porcelain 4. OIP Condenser 5. Winding tube 6. Power factor tap 7. Flange 8. Epoxy resin insulator 9. Oil side shield Fig. 1: Bushings 52 kv to 170 kv Fig. 2: Bushings 245 kv Fig. 3: Bushings 420 kv Fig. 3: Bushings 420 kv 1. HV Terminal 2. Oil level guage 3. Metal oil reservoir 4. Porcelain 5. OIP Condenser 6. Winding tube 7. Power factor tap 8. Flange 9. Epoxy resin insulator 10. Oil side shield 2
3 Manufacturing The active part of the bushing is the condenser body, manufactured using a continuous sheet of pure Kraft paper, wound around a central conductor tube or rod. During the winding process, the paper is dried by heated cylinders in order to reduce its water content to 1% maximum. A series of aluminum foils are coaxially inserted between the layers of the paper, to achieve the best possible distribution of the radial and longitudinal electrical gradients between the central tube and the flange, which is grounded. The winding is made by computer-controlled machines, with subsequent machining to achieve the final shape. After winding, each bushing is individually assembled and placed into an oven and then processed under vacuum for the appropriate period of time. Each bushing is then impregnated with Insulating Oil, which has been degassed and processed so that it has a maximum water content of 5 ppm. Each bushing is placed under pressure to ensure thorough impregnation and to test that it is properly sealed. After impregnation, the bushing head is filled with nitrogen gas cushion. This process is automatic and computer controlled. Top Terminal The standard bushing top terminal is made of tin plated copper. Upon request, it can be silver plated. The terminal is connected to the copper inner terminal lug or the draw rod by means of multiblade contacts and is secured to the bushing head by screws. Air Side The air side insulator is made of brown porcelain. The typical creepage distance is suitable for heavily polluted (25 mm/kv) atmospheres. The shed configuration is an alternating type: shortlong shed. The shed profile complies with IEC recommendations. A one-piece porcelain or multiple pieces porcelain, in order to meet Standards or special requirements, are used for bushings. Multiple pieces are glued using epoxy resin, without the use of gaskets, and the final porcelain is considered as a single piece. Flange The flange is made of aluminum castings, and is equipped with the following accessories: Eye Bolt for lifting purpose Power factor tap, tested at 2 kv for 60 s (fig. 4) Buchholz relay connection: 1/2 BSP outlet plug Oil sampling plug (for 245 kv bushings). Head and Oil Inducation Bushings are provided with glass or metallic head. Glass Head Bushings with oil head reservoir are prismatic in shape, made of borosilicate glass, and containing a UHV filter, which allows for an easy check of the oil level even from a distance and at any angle of sight. Metallic Head The metal component of the head is made of a cast aluminum alloy and is provided with oil level guage. Fig. 4: Power Factor Tap 1. Closing and grounding cap 2. Measurement electrode 3. Insulation tap 4. Gasket 5. Tap flange 6. Bushing flange 7. Last layer 3
4 Oil Side The oil side envelope is made of a molded epoxy resin. This resin is a two-part compound consisting of a resin base and a hardener; the filler material is quartz sand. The epoxy resin envelope permits shapes, thickness and dimensional tolerances not possible with porcelain. Under flange sleeve length for CT accommodation, different from standard, is available upon request. In this case, the grounded part is obtained by means of a metallic tube or directly by the last metallic layer inside the condenser body. Oil Side Shield The bottom end of the bushing is shielded by a proper deflector, made of aluminum alloy. It is designed to reduce the electric field stress in oil and to screen the connection between the lead coming from the transformer winding and the bushing itself. Bushings up to and including 170 kv have an integrated deflector. Bushings rated 245 kv and above have detachable deflector. Assembling The mechanical coupling among all the parts of the bushing is made by means of springs placed into the head of the bushings. 245 kv bushing are always assembled using (air side) porcelain cemented to flange (fig.5) as well as the ones for heavy cantilever ( H ) loads. All cemented surfaces, potentially in contact with the external environment, are silicone sealed (fig. 5). Fig. 5: Cemented porcelain 1. Porcelain 2. Cement 3. Metal cemented ring 4. Flange 5. Silicone sealing 4
5 Gaskets Made of Viton, a fluorocarbon rubber elastomer (FPM), o-ring type. They are compatible with all the fluids they are in contact with. Air side gaskets are carefully protected, by means of a sealing, against influence of polluting weather elements. For special requirements, such as low ambient temperatures (down to -55 C), special o-rings are used. Arcing Horns Adjustable arcing horns are available upon request. The upper arcing horn is fixed by means of one screw used to secure the top terminal, while the lower arcing horn is fixed on the flange (fig. 6). Tests All bushings are tested in accordance with IEC 60137/IS 2099 Standards: insulated bushing for alternating voltages above 1000 V. Fig. 6: Discharge distance for a bushing equipped with arcing horns 5
6 PNO Range 52 to 420 kv 4
7 Fig. 7: Draw lead conductor sections Fig. 8: H1 head type (Draw lead or draw rod up to 245 kv) Fig. 9: H2 head type (Bottom connection up to 245 kv - 2,000 A) Fig. 10: H3 head type (Draw lead or draw rod 362 to 420 kv) 1. Air draining plug 2. Lifting holes 3. Power factor tap 1. Air draining plug 2. Power factor tap 3. Lifting holes 4. Oil sampling valve 5. Magnetic oil sight glass Fig. 13: Flange fixing holes Fig. 11: PNO Bushings 52 through 170 kv Fig. 12: PNO Bushings 245 kv Fig. 14: PNO Bushings 420 kv 5
8 Packing - Transportation After tests and before packing, the bushing is cleaned of any oil or dust. Thanks to a special device to prevent the diffusion of the nitrogen cushion out of the head and into the lower end of the bushings, each bushing can be packed and shipped secured in horizontal position. Proper protection is used for oil side shields. Nameplate Each bushing is provided with a nameplate, containing complete electrical data and its serial number, in accordance with the requirements of IEC Standards. The stainless steel name plate is secured to the flange. Detail A Fig. 15: PNO Bushings 52 kv to 170 kv (draw rod connection) Fig. 16: PNO Bushings 245 kv (draw rod connection) Fig. 19: Bottom terminal connector for 800 A - 1,250 A Fig. 20: Bottom terminal connector for above 1,250 A - 3,150 A Fig. 18: PNO Bushings 52 kv to 170 kv (solid stem connection) Fig. 17: PNO Bushings 145 kv to 245 kv (solid stem connection) For more information please contact GE Grid Solutions Worldwide Contact Center Web: Phone: +44 (0) IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council. NIST is a registered trademark of the National Institute of Standards and Technology. GE and the GE monogram are trademarks of General Electric Company. GE reserves the right to make changes to specifications of products described at any time without notice and without obligation to notify any person of such changes. PNO-Brochure-EN Grid-PTR Copyright 2018, General Electric Company. All rights reserved. Imagination at work
Condenser Bushings. OIL-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C AND IEEE C AN ALSTOM COMPANY
PAO Condenser Bushings - kv BUSHINGS OI-TO-AIR - Oil-Impregnated Paper ANSI STANDARDS IEEE C.9.0-000 AND IEEE C.9.0-99 AN ASTOM COMPANY PAO bushings are capacitance-graded bushings with an oil-impregnated
More informationOTCF. Grid Solutions. Capacitor Voltage Transformers 72.5 kv to 800 kv. Quality Product Design. Seismic Withstand Capability.
GE Grid Solutions OTCF Capacitor Voltage Transformers 72.5 kv to 800 kv In high and extra high voltage transmission systems, capacitor voltage transformers (CVTs) are used to provide potential outputs
More informationOIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC
OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) 1800 24kV to 550kV up to 5000A IEC 60137-2008 Features If you need any transformer bushing proven in operation conditions around the world, Trench
More informationOIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC
OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) 1800 24kV to 550kV up to 5000A IEC 60137-2008 Features If you need any transformer bushing proven in operation conditions around the world, Trench
More informationBushings for High Voltage AC Applications
Bushings for High Voltage AC Applications Selection guide 1ZSE 2750-100 en, Rev. 3, 2006-03-15 During selection of for high voltage applications several important factors have to be considered to ensure
More informationTransformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC
Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC 60137-2008 High current bushings for transformer Features Bushing Type CFPT version Porcelain Insulator Trench RIG technology for
More informationOIL TO AIR BUSHINGS SERIES PNO. VOLTAGE FROM 52 kv TO 245 kv
Nuova Strada di Piano PPR 20099 Sesto San Giovanni (MI), Italy Tel. +39 02 24 10 50 01 www.alstom.com Page 1 of 17 OIL TO AIR BUSHINGS SERIES PNO VOLTAGE FROM 52 kv TO 245 kv INSTRUCTION FOR STORAGE, TRANSPORTATION,
More information1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide
1ZSE 2750-102 en, Rev. 7 Transformer bushings, type GOB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical
More informationPABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY
PABS Air-to-SF 6 Bushings 7.5-800 kv BUSHINGS AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS 7 - ANSI STANDARDS AN ALSTOM COMPANY PABS bushings are gas-insulated types that meet IEC 7, ANSI/IEEE or
More informationTransformer bushings, type GOH. Technical guide
Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More informationResin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide
1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More information1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide
1ZSE 2750-112 EN, REV. 4 Wall bushings type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More information1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide
1ZSE 2750-106 EN, REV. 7 Oil SF 6 bushings type GOEK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More information1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide
1ZSE 2750-102 en, Rev. 9 Transformer bushings, type GOB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More information1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide
1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationdfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide
dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide Table of contents 1 Introduction... 3 1.1 Style Number... 3 1.1.1 Style Number Examples... 3 2 Basic Characteristics... 4 2.1
More informationProduct presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 New RIS transformer bushings The paper-free solution Transformer condenser bushings Why a new technology? To preserve
More informationOTAA Oil Impregnated Paper (OIP) Bushing for IEEE/ANSI Market
OTAA Oil Impregnated Paper (OIP) Bushing for IEEE/ANSI Market OTAA The OTAA is the next generation of Oil Impregnated Paper condenser bushing manufactured to IEEE C57.19.01 from 25 kv to 500 kv system
More information1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide
1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover
More informationResin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK
1ZSC563-AAA en, Rev. 2 Resin Impregnated Paper Bushing, Oil to SF 6, Type GSBK Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More informationInstallation Manual Bushings, IEEE/ANSI Standard
Installation Manual Bushings, IEEE/ANSI Standard Type COTA 150.2050 for Transformers Type COBA for OCB Bushing Replacement E 8322.72 2007 Contents Page 1. Introduction 3 2. Scope 3 3. Construction 3-5
More informationOIL-TO-OIL BUSHINGS SERIES PCTO SINGLE FLANGE TYPE VOLTAGE FROM 72,5 kv TO 420 kv
Page 1 of 14 OIL-TO-OIL BUSHINGS SERIES PCTO SINGLE FLANGE TYPE VOLTAGE FROM 72,5 kv TO 420 kv STORAGE, OPERATING AND MAINTENANCE INSTRUCTIONS Page 2 of 14 INDEX 1. DESCRIPTION...3 1.1 GENERAL...3 1.2
More informationTransformer Bushing Type EKTO
Transformer Bushing Type EKTO Mounting Operating and Maintenance Instructions Operating Instructions BAL EKTO/04e Visum 01/14 T/gue Page 1 of 16 SAFETY INSTRUCTIONS These instructions are valid for mounting,
More informationMicafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB
Micafil transformer oil-sf 6 bushings GARIP / RTKG 72.5 55 kv Power and productivity for a better world TM ABB Design and accessories The design of the main RIP insulating body includes a solid, non-removable
More information1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide
1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationTransformer Bushings Type COT COT kv to 245 kv up to 3150 A IEC 137
Transformer Bushings Type COT 5... COT 050 4 kv to 45 kv up to A IEC 37 Features If you need any transformer bushing proven in operation conditions around the world, Trench has it! experience in bushing
More informationTransformer Bushings Type. STARIP / STARIP -Si. Mounting Operating and Maintenance Instructions
Transformer Bushings Type STARIP / STARIP -Si Mounting Operating and Maintenance Instructions Service Instructions BAL STARIP /STARIP -Si/02e Visum 01/14 T/gue Page 1 of 17 SAFETY INSTRUCTIONS These instructions
More informationTransformer bushings, type GOA 250. Installation and maintenance guide
Transformer bushings, type GOA 250 Installation and maintenance guide This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor
More informationINESING GROUP. Power System Solution
INESING GROUP INESING GROUP Power System Solution Power System Solution INESING Group Via Dell'Industria 18B 24040 Casirate D'Adda Italy t: +39 3388263363 f: +39 04381890521 e: info@inesing.com introduction
More informationDM Condenser bushings, kV DURESCA
DM Condenser bushings, 36 DURESCA Through wall bushings for indoor and outdoor applications, Resin Impregnated Paper IEC 601378 and IEEE C57.19.01.004 DURESCA Wall bushings Swiss quality combined with
More informationMICAFIL RIP Transformer Bushings AirRIP / RTKF kv
INSULATION AND COMPONENTS MICAFIL RIP Transformer Bushings AirRIP / RTKF kv MICAFIL AirRIP bushings offer an extended service life combined with enhanced reliability and safety to ensure the maximum availability
More informationProduct Information. Neutral Wall Bushing GOFL
ABB Components Info-No. 2750 515-93en, Rev. 1 From / Date Product Information Neutral Wall Bushing GOFL Description Page Design 2 Voltage tap 2 Dimensions 2 Terminals 2 Mounting instruction Packing 4 Storing
More informationPumped Storage Power Plants Solution
GE Grid Solutions Pumped Storage Power Plants Solution Flexibility for Grid Operators Pumped storage power plants are the largest and most cost-effective means of storing energy for electricity grids.
More informationTransformer bushings, type GSA-OA Technical guide
Transformer bushings, type GSA-OA Technical guide ZSE 2750- en, Rev. 5, 2005-05-5 This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to
More informationInstruction Manual for POC Bushings
1. Scope This instruction contains general procedures to be followed during receiving, installation, storage and maintenance of all PCORE POC bushings. This instruction does not cover all contingencies
More informationTransformer Bushing Type EKTG
Transformer Bushing Type EKTG Mounting Operating and Maintenance Instructions Operation Instructions BAL EKTG/05e Visum 01/14 T/gue Page 1 of 18 SAFETY INSTRUCTIONS These instructions are valid for mounting,
More information1ZSE en, Rev. 9. Transformer bushings, type GSA-OA Technical guide
1ZSE 2750-111 en, Rev. 9 Transformer bushings, type GSA-OA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationDistribution transformers Efficiency over life-cycle
Distribution transformers Efficiency over life-cycle ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while
More informationEMPAC Metal enclosed capacitor bank for wind applications
EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks
More informationACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE
ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE hvgrid-tech designs and manufactures high voltage cable accessories for all types of cable systems, ranging from 69 kv to
More informationHVDC bushing without oil side porcelain Type GOF, for outdoor mounting. Installation and maintenance guide
HVDC bushing without oil side porcelain Type GOF, for outdoor mounting Installation and maintenance guide This document must not be copied without our written permission, and the contents thereof must
More informationMEDIUM POWER TRANSFORMER
MEDIUM POWER TRANSFORMER MEDIUM POWER TRANSFORMER FROM 3,15 TO 31,5 MVA HIGHEST VOLTAGE FOR MATERIAL 72,5kV GENERAL CHARACTERISTICS Three phase oil-immersed naturally cooled type ONAN medium power transformers.
More informationCLICK-FIT. High Voltage Accessories for Extruded Cables
CLICK-FIT High Voltage Accessories for Extruded Cables Linking the future As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy
More informationBUSHINGS: GENERAL INFORMATION
BUSHINGS: GENERAL INFORMATION 1.0 Electrical characteristics (Ir = rated current; Ur = rated voltage) 1.1Standard insulation levels Rated voltage Ur kv (r.m.s.) 1 3,6 12 24 36 52 One minute power frequency
More informationkv А
66-220 kv 2000-4000 А Publication 11.2011 "IZOLYATOR" PLANT performs design, manufacturing, warranty and post-warranty service of high-voltage bushings for various applications. The enterprise is the main
More informationA of 14. Edition : Date : Page : Document No. Amendments :
&RQWHQWV,QVWUXFWLRQVIRU(UHFWLRQ 2SHUDWLRQ 2XWGRRU7UDQVIRUPHU%XVKLQJ 57.)N9.6,7 6HULHV&25,3 +/$%( Document No. Edition : Date : Page : Amendments : A 29.11.02 1 of 14 *(1(5$/'(6,*1 3$&.,1* %XVKLQJ6XSSO\&RQGLWLRQV
More informationField Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI
Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI T. Schütte, ABB Schweiz Ltd, High Voltage Components, Bushings, 2015-10-19 INMR2015 - Munich Field experience and
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 245) kv General description Voltage transformers type EOF are used in high voltage networks within the 24 245 kv range. They
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 245) kv General description Voltage transformers type EOF are used in high voltage networks within the 24 245 kv range. They
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 245) kv General description Voltage transformers type EOF are used in high voltage networks within the 24 245 kv range. They
More information1ZSC AAX EN, Transformer bushing, type GSC Installation and maintenance guide
1ZSC000563-AAX EN, 2018-01-16 Transformer bushing, type GSC Installation and maintenance guide The information contained in this document may be subject to change without prior warning and should not be
More informationProduct presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 Dry-type transformers Innovative Technology What is a dry transformer? ABB manufactures a transformer which does
More informationen, Rev. 10. Transformer bushings, type GOH Installation and maintenance guide
2750 515-85 en, Rev. 10 Transformer bushings, type GOH Installation and maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all
More information25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable ELRIM Cycloaliphatic
More informationABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers
ABB PTTR SPAIN Zaragoza. The product: Cast coil transformers ABB BA Transformers - 1-5/7/2007 Dry Type Vacuum Cast Coil Transformer INTRODUCTION ABB BA Transformers - 2 - Product Portfolio II Dry Type
More informationTransformer Bushing Type SETFt. Mounting Operating and Maintenance Instructions. Service Instructions BAL SETFt/06e Visum 01/14 T/gue Page 1 of 21
Transformer Bushing Type SETFt Mounting Operating and Maintenance Instructions Service Instructions BAL SETFt/06e Visum 01/14 T/gue Page 1 of 21 SAFETY INSTRUCTIONS These instructions are valid for mounting,
More information35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection 35 kv Separable Insulated Connector (elbow) Bus Bar or Other Component Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other
More informationBRUDA. Removable control gear plate. Computer aided design reflector. Single piece high-pressure diecast aluminium housing.
, designed specifically to allow for tool free maintenance is a single piece high pressure die cast area light. High output computer designed reflector with a removable control gear plate. is equipped
More informationKuhlman Electric Corporation Volt Instrument Transformers
Kuhlman Electric Corporation 46000 Volt Instrument Transformers 46000 Volt Table of Contents Description Model Page Wound, Dry-Type VT (High Accuracy available) U/VRU-52(H) 3-4 Wound, Oil-Filled VT (High
More information2. INDUCTIVE VOLTAGE TRANSFORMERS Dry and oil-paper insulation
2. INDUCTIVE VOLTGE TRNSFORMERS Dry and oil-paper insulation 12 Instrument transformers Outdoor medium voltage 2. INDUCTIVE VOLTGE TRNSFORMERS > Dry and oil-paper insulation INTRODUCTION Inductive voltage
More informationBusiness Edge. Global Leadership
Business Edge Business Edge The Switchgear Works of Crompton Greaves is located on a 1,32,540 sq.mtrs. plot in Nashik on the Mumbai Agra National Highway and is demarcated in four main divisions: EHV SF6
More information35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 35 kv Separable Insulated Connector (elbow) Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other
More informationA manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard
A manufacturer s view of bushing reliability, testing and analysis By Lars Jonsson Håkan Rudegard 1 A manufacturer s view of bushing reliability, testing and analysis Lars Jonsson Håkan Rudegard ABB Sweden
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 245) kv General description Voltage transformers type EOF are used in high voltage networks within the 24 245 kv range. They
More informationGE TRANQUELL Surge Arresters
GE Grid Solutions GE TRANQUELL Surge Arresters Product Selection Guide IEC Line Discharge Classes with 2, 3, and 4 Polymer Housings GE Surge Protection The performance and reliability of today s electric
More information35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Equipment Connection Bus Bar, or Grounded Metal Equipment Plate F Series Mounting Holes ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric
More informationType HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv
Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv HS PEXLIM-P Metal Oxide Surge Arrester HS PEXLIM-P Surge Arresters are used for the protection of switchgear, transformers and other
More informationBushing Insulators according to DIN and UNEL Standards
Bushing Insulators according to DIN and UNEL Standards Description and general specifications Outdoor transformer bushing DIN 42532 and UNEL 38159/74 rated current 630A Bushing EN 50180 12-24-36/630-1250-2000-3150
More informationExcitation system is of Static Silicon Excitation System, including excitation transformer, thyristors, and AVR.
Turbo - Generator Type: QF Series 1. General The generator is a two pole, cylindrical rotor type synchronous machine, directly coupled with steam turbine. It has a closed-circuit cooling system to cool
More information25 kv Apparatus Bushings
Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation
More informationPSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables.
Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables. Sizes are available for all shielded cables in voltage classes from 15kV through 46kV.
More informationCAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION
CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION TMC TRANSFORMERS - GLOBAL NETWORK UK & IRELAND SPAIN NORTH AMERICA & CANADA GERMANY SWITZERLAND BENELUX & AUSTRIA ITALY POLAND INDIA CENTRAL & SOUTH AMERICA
More information25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection 15 kv or 25 kv Separable Insulated Connector (elbow) Grounded Metal Equipment Plate Equipment Connection Power Cable Power Cable ELRIM Cycloaliphatic
More informationBus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:
4 (Four) Pole Monoblock: Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers: Designed and manufactured in accordance with EN 50336:2002 and BS 2562: 1979 1 Introduction:
More informationDrive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer
Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer This document contains sample specifications for Liquid-Filled Type Drive Transformers You may
More informationCAST RESIN TRANSFORMERS CRT ED.: DEC.13 REV.00
CAST RESIN TRANSFORMERS CRT ED.: DEC.13 REV.00 1 HISTORY INESING SRL is a dynamic and modern company, very well known in the design and production of dry type (cast resin ) transformer up to 36kV -10MVA,
More informationP2 : About Us. P3 : Elsewedy Transformers. P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers. P7 : Technical Data Sheets
P2 : About Us P3 : Elsewedy Transformers P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers P7 : Technical Data Sheets P8 : Transformer s Outline Drawing P9 : Accessories About Us
More informationA of 3. Edition : Date : Page : Document No. Amendments :
&RQWHQWV,QVWUXFWLRQIRURSHUDWLRQ %XVKLQJ7HVW7DS +/$%( Document No. Edition : Date : Page : Amendments : A 7..99 of 3 *((5$/'(6,* 38536( &(&7, &DSDFLWDQFHDQGSRZHUIDFWRUPHDVXUHPHQWV 3HUPDQHQWPHDVXUHPHQWV,68/$7,7(676
More informationINSTRUCTION MANUAL CRS Combined insulation bushing
INSTRUCTION MANUAL CRS Combined insulation bushing 5COH020200 CRS REV03 2 TABLE OF CONTENTS 1 SAFETY... 5 1.1 SAFETY INSTRUCTION... 5 1.2 SPECIFIED APPLICATION... 5 1.3 SAFETY NOTES ON THE EQUIPMENT OPERATION...
More informationTechnical Specification For Outdoor Substation Harmonic Filter Banks
Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field
More informationYOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS
YOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS 1 TABLE OF CONTENTS ABOUT SVEL GROUP CAST-RESIN TRANSFORMERS ACCESSORIES AND OPTIONAL EQUIPMENT ENCLOSURE AND HOUSING TESTS AND QUALITY
More informationLoadbreak Apparatus Connectors
Loadbreak Apparatus Connectors 200 A 25 kv Class POSI-BREAK Loadbreak Elbow Connector with Optional Integral Jacket Seal* Electrical Apparatus 500-29-7 general The POSI-BREAK Loadbreak Elbow Connector
More informationHigh Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide
1ZUA2761-500 rev. 5, 6 April 2010 High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide 1ZUA2761-500 rev. 5, 6 April 2010 2 / 9 Table of contents 1 Description... 3 2 Ratings...
More informationwww. ElectricalPartManuals. com Instructions for Cast Resin Bushing, 15 KV & Below
Instructions for Cast Resin Bushing, 15 KV & Below Fig. 1 Cast Resin Bushing The Westinghouse Cast Resin Bushing, used for voltages 15KV and below, is made by casting an insulating resin around the conductor.
More informationHIGH-VOLTAGE BUSHINGS FOR POWER TRANSFORMERS AND SHUNT REACTORS
HIGH-VOLTAGE BUSHINGS FOR POWER TRANSFORMERS AND SHUNT REACTORS «AIR OIL» Rated Voltage 10 1150 kv Alternating current 315 3500 A WE CREATE THE FOUNDATION FOR A SUSTAINABLE POWER SUPPLY 2019 Edition www.mosizolyator.com
More informationDeadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL
Deadbreak Apparatus Connectors 600 A 15/25 kv Class BOL-T Deadbreak Connector Electrical Apparatus 600-30 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class BOL-T Deadbreak Connector is used to terminate
More informationB kv Gas-insulated Substations
72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.
More informationCompleting the picture
HIGH VoltaGe cable accessories for 72 kv up to 170 kv Completing the picture based on experience is the future nkt cables GmbH nkt was established in 1891 as cable manufacturer. in 1999 nkt a/s denmark
More informationCurrent transformers. Outdoor operation SF 6 -gas insulated. JGF ( ) kv
Current transformers Outdoor operation SF 6 -gas insulated JGF (245 550) kv General description Current transformers type JGF are used in high voltage switchgear within the 245 550 kv range. They transform
More informationHigh-Voltage Cable Accessories. 72 kv up to 245 kv. nkt.com
High-Voltage Cable Accessories 72 kv up to 245 kv nkt.com 1 Table of contents General NKT: The Profile... 3 The product range: High-Voltage Cable Accessories... 4 XLPE-Cable Terminations THV 72-145...
More informationVolt Instrument Transformers
www. kuhlman. com Kuhlman Electric Corporation Instrument Transformers 1 Table of Contents Description Model Page Wound, Oil-Filled VT (High Accuracy available) UTE-145-OH 3-4 Wound, Oil-Filled CCVT (High
More informationVariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified
Surge s Catalog Data CA235022EN Supersedes TD235009EN September 2014 COOPER POWER SERIES VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified General Eaton s Cooper
More informationCertified for best-in-class performance, reliability, and safety. Trihal sets a new standard for dry-type cast resin transformers
Certified for best-in-class performance, reliability, and safety Trihal sets a new standard for dry-type cast resin transformers Setting a new standard for dry-type cast resin transformers hospitals wind
More informationGE TRANQUELLTM Surge Arresters
GE Digital Energy GE TRANQUELLTM Surge Arresters Product Selection & Application Guide Heavy Duty Distribution Class-Polymer and Riser Pole Polymer Arresters IEEE /ANSI C62.11 GE Surge Protection The performance
More informationABB SpA COMEM Operating Unit Power Grids Division Strada Regionale 11, Signolo Montebello Vicentino (VI) - ITALY
ABB SpA COMEM Operating Unit Power Grids Division Strada Regionale 11, Signolo 22 36054 Montebello Vicentino (VI) - ITALY www.abb.com/transformercomponents The information contained in this document is
More information15 kv and 25 kv Thru-Bushings
Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation
More informationJOSLYN. Underground Cable Accessories. Table of Contents. JPT/JIPT Polymer Terminations. ShrinkTite Sealing Kits. Easy-On II Terminations
Underground Cable Accessories JOSLYN Table of Contents JPT/JIPT Polymer Terminations 15kV, 25kV & 35kV ShrinkTite Sealing Kits 1kV In-Line Splice Sealing Kit Cable Jacket Sealing Kit Easy-On II Terminations
More informationMedium Voltage. Joints & Terminations
57 - Cold Shrink Joints Supporting Core Radially shrinkable elastomeric splice Semi-conductive layer High permitivity insulation layer 6.6/11/(12) kv 3M QS1000 is a one-piece cold shrink joint body manufactured
More information100 / 110 DRYWELL FUSE SPECIFICATION
100 / 110 DRYWELL FUSE SPECIFICATION 15KV & 25KV SUBMERSIBLE VACUUM LOAD INTERRUPTERS AND DRYWELL FUSE ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED SUBMERSIBLE SWITCHGEAR WITH LOAD INTERRUPTING SWITCHES
More information