1 1ZSC563-AAA en, Rev. 2 Resin Impregnated Paper Bushing, Oil to SF 6, Type GSBK Technical guide
2 This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required to assist them in their selection of the appropriate transformer bushing. The guide should be used in conjunction with the Selection Guide to allow the optimum selection to be made. The technical information pertaining to bushings manufactured by ABB has been divided into separate documents, with one document for each type. The information provided in this document is intended to be general and does not cover all possible applications. Any specific application not covered should be referred directly to ABB, or its authorised representative. ABB makes no warranty or representation and assumes no liability for the accuracy of the information in this document or for the use of such information. All information in this document is subject to change without notice.
3 Table of contents Standards 4 Design 4 Test tap 5 Testing 5 Routine testing 5 Type tests 5 Special tests 5 Transportation and storage 5 Dimensions 6 Electrical data 7 General specifications 7 Connection details 8 Draw rod system 8 Fixed bottom contact 9 SF 6 side terminal 9 Standard end-shield 9 Conductor loading 1 Overloading of bushings acc. to IEC 1 Short-time current 1 Ordering particulars 1 Recommendations for positioning 1
4 4 1ZSC563-AAA en, Rev. 2 Standards Design The GSBK bushing is designed and tested according to IEC 6137 and IEC GSBK is a Resin Impregnated Paper (RIP) bushing intended for immersed oil SF 6 service. The bushing can be mounted in any direction from vertical to horizontal. It can also be used for oil oil application. Contact the supplier for further information and current ratings. The insulation core of the GSBK is produced by winding crepe paper onto a center tube, with aluminium foil insert for electrical stress control. The manufacturing process is optimized to give a partial discharge free bushing with low dielectric losses. As a current conductor, GSBK uses the center tube, which is moulded into the RIP core. The outer terminal is fit to the center tube by a bolted joint. The bottom contact on the transformer side is mounted by a draw rod system or by a bolted joint. Outer terminal RIP core Mounting flange Test tap Center tube gsbk_2 Fig. 1. Transformer bushing type GSBK oil SF 6 connection. Features Solid Seals the transformer Benefits Reduced risk of fire. No restriction in mounting angle. Oil leakage from the bushing eliminated. Reduced risk of fire. Risk of oil leakage from the transformer reduced. Non-brittle materials Protection of people and equipment. Easy handling. Safe transport - even when mounted on the transformer. High earthquake withstand. Light weight, compact Easy handling, small space requirements inside transformer, low life cycle environmental impact.
5 1ZSC563-AAA en, Rev. 2 5 Test tap The outer conducting layer of the condenser core is connected to an insulated test tap on the flange. During operation the protective cap must be fitted in order to ground the outer layer to the flange. The maximum test voltage is 2 kv, 5 Hz for 1 minute. The maximum service voltage is 6 V. Voltage tap is available as on request. The maximum test voltage is 2 kv, 5 Hz for 1 minute. The maximum service voltage is 6 kv. The test tap and voltage tap have dimensions according to IEEE, potential tap type A. gsbk_18 Test tap adapter Testing Routine testing Type tests Special tests Fig. 2. Test tap. For permanent connection of the test tap to the measuring circuits, a test tap adapter (catalog number C) is sometimes required, for example if the IEEE dimension standard for measuring tap is not used. The bushing is routine tested according to IEC 6137 and IEC The tests include measurement of partial discharge quantity, tan δ, capacitance and power frequency voltage withstand test. On each bushing, an external pressure test is performed and the tightness between the gas side and the oil side is confirmed. An individual routine test report is issued with each bushing. The routine test is carried out at room temperature with the bushing immersed in transformer oil. Type tests have been performed according to above standards and are available on request. A number of tests not specified by the above standards have also been performed and summaries are available on request. Transportation and storage The bushing is wrapped in a sealed moisture-proof wrapping material together with a drying agent upon delivery. The protective wrapping shall not be opened if the bushings are intended to be stored. The protective wrapping can be re-sealed, or a similar sealed moisture-proof wrapping can be used, together with a drying agent.
6 6 1ZSC563-AAA en, Rev. 2 Dimensions D4 R1 Ø 87 Shield SF 6 side Ø 87 R58 R R58 R58 R1 R1 L1 L5 D1 GSBK 17 GSBK Flange SF 6 side 1.6 D7 x n1 L L3 L4 D5 D6 L2 D2 Flange oil side D1 x n2 D8 D9 Fig. 3. Dimensions. D3 gsbk_4 Dimensions are subject to modification without notice. Type GSBK Rated current (A) Dimensions in mm Cat. No. 1ZSC... Space for current Net Test tap Voltage tap 6 kv transformer (mm) mass (kg) L L1 L2 L3 L4 L AAA 917-ABA AAB -ABB ACA -ADA ACB -ADB AAA -ABA AAB -ABB ACA -ADA ACB -ADB AAA -ABA AAB -ABB AAA -ADA AAB -ADB AAA -ABA AAB -ABB
7 1ZSC563-AAA en, Rev. 2 7 Electrical data Ratings GSBK Rated voltage IEC (kv), U m Rated phase-to-ground voltage IEC (kv) Basic Insulation Level (kv), BIL Dry switching impulse level (kv), SI N.A Routine test 1 minute dry (kv), 5 Hz, rms Rated current (A), I r 16/25 16/ Rated frequency (Hz), fr 5/6 5/6 5/6 5/6 5/6 Temporary over voltage (kv), IEC 6137 clause Space for current transformer (mm) 3/6 3/6 3/6 3/6 3/6 Nominal capacitance between conductor and test tap C1 ±1 % (pf) General specifications 496/656 5/622 45/ / /352 Application: Classification: Ambient temperature: Immersion medium on switchgear side: Max pressure of medium on switchgear side: Immersion medium on transformer side: Oil level in transformer: Max. pressure of medium: Angle of mounting: Test tap: Voltage tap: Capacitance C2 of test tap: Conductor: Markings: Transformers Resin impregnated paper, capacitance graded, completely immersed bushing, temperature class E (12 C) according to IEC C to -4 C, minimum value acc. to temperature class 2 of IEC 6137 SF 6 gas. Max daily mean temperature +75 C. 75 kpa (over pressure) Transformer oil. Max daily mean oil temperature +9 C. Max temporary oil temperature +115 C. Not lower than 3 mm from the bushing flange. 1 kpa (over pressure) Horizontal to vertical Dimensions according to IEEE, Type A. Max. service voltage 6 V. Dimensions according to IEEE, Type A. Max. service voltage 6 kv. < 5 pf Integrated tube conductor Conforming to IEC Condenser core D1 D2 D3 D4 D5 D6 D7 x n1 D8 D9 D1 x n2 Cantilever load Max operating load (kn) x x x x x x x x x x x x x x x x x x x x x x x x x x x x Test load (kn)
8 8 1ZSC563-AAA en, Rev. 2 Connection details Draw rod system The draw rod system offers the following advantages compared to other connection systems: No hand holes required in the transformer tank. Easy bushing installation and removal no connection work inside the transformer at site. No special supports required in the transformer as is the case with plug contacts. Perfect guiding of the bushing into the transformer. The lower end shield may be fixed to the contact and will thus be correctly positioned with respect to the lower end plate of the bushing. The center tube of the bushing is used as current conductor. The transformer leads are fitted with cable lugs, which are bolted to a bottom contact. This contact is pressed against the bottom end of the bushing tube by a steel draw rod. The upper end of this rod is bolted to a compensating device, which consists of a spring and is so designed that it gives the required contact pressure at all temperatures. The draw rod is divided at the level of the flange. If required by the transport conditions, an additional joint can be positioned below the flange. This must be stated in the order. The lower part with contact end shield can then be secured to the cover during transport and storage of the transformer. Bottom contacts with 4 threaded holes for cable lugs are available. The bottom contacts are made of copper in one piece. To this bottom contact there is a suitable end shield, cat. No. 1ZSC9993. Special bottom contacts are available on request. Catalogue number for draw rod: 1ZSC9994. Threaded hole M8 for pulling wire L 25 Additional joint on request 6 L H1 min 2 gsbk_23 Fig. 4. Draw rod system. M12 (4x) gsbk_24
9 1ZSC563-AAA en, Rev. 2 9 Fixed bottom contact A system with a fixed bottom contact is also available. The bottom contact is pressed against the bottom end of the conductor tube by means of bolts, screwed into a pulling ring, see Fig. 5. The bottom contact is made of copper in one piece and is prepared with 4 threaded holes for cable lugs connection. To this bottom contact there is a suitable end shield, Cat. No. 1ZSC9993. Special bottom contacts are available on request. Catalogue number for fixed bottom contact: 1ZSC9992-AAA. L gsbk_25 gsbk_21 Fig. 5. Fixed bottom contact. M12 (4x) SF 6 side terminal The dimensions on the SF 6 side terminal fully comply to IEC and include 4 threaded holes for GIS connection. The terminal is fitted to the top end of the conductor tube by means of bolts, screwed into a pulling ring. The terminal surface for GIS connection is silver plated. Special terminals are available on request. gsbk_22 Fig. 6. SF 6 side terminal. gsbk_26 Standard end-shield The end-shield is made of aluminium coated with insulating epoxy paint or 3 mm pressboard. It is equipped with a locking device to fit to the standard bottom contact for draw rod system or fixed bottom contact. See Fig. 9. Cat. No. 1ZSC9993-AAA 1ZSC9993-AAB Coating Epoxy paint 3 mm pressboard
10 1 1ZSC563-AAA en, Rev. 2 Conductor loading The GSBK bushings fulfill the temperature rise test requirements according to IEC for the currents in the table below. The rated thermal short-time current (I th ) is calculated according to IEC Contact the supplier for current ratings for GSBK in oil - oil applications. Bushing GSBK Rated current A Short-time current (I th ) ka, rms 1 s 2 s Dynamic current (I d ) ka, peak Overloading of bushings acc. to IEC Short-time current If the conductor for the bushing is selected with 12 % of the rated current of the transformer, the bushing is considered to be able to withstand the overload conditions stated in IEC when following the directions: for long time and short time emergency loading the oil temperature must be 115 C max. and the daily mean oil temperature must be 9 C max. For overload conditions other than the above-mentioned IEC overload, contact the supplier for permissible currents and temperatures. The rated thermal short-time current (I th ) is calculated according to IEC Ordering particulars When ordering, please state: Type and catalogue number for bushing Connection details: fixed bottom contact or draw rod Catalogue number for shield on oil side Additional accessories or modifications Test required, in addition to the normal routine tests gsb_16 Nameplate Recommendations for positioning The maximum stresses in the oil at the surface of the shield and the parts surrounding the bushing must be limited to the normal values for insulated conductors and other similar components in the same transformer. The withstand voltages in a specific case depend upon many factors beyond the control of the bushing manufacturer. Therefore the configurations and distances given in the table and figures are only intended as guidelines.
11 1ZSC563-AAA en, Rev D3 D4 3 E min R5 1 /3 x L4 max L4 Type GSBK E (mm) L4 (mm) d3 min (mm) d4 (mm) 17/16/ ± /25/ ± /16/ ± /25/ ± /16/ ± /25/ ± /16/ ± /25/ ± /16/ ± /16/ ± /16/ ± /16/ ± /125/ ± /125/ ± R gsbk_7 Fig. 7. Recommendations for positioning Radius (mm) Fig. 8. Recommended minimum distance R, for standard shield at 1 minute power frequency (rms) test. U (kv) gsbk_19 R Ø 142 Ø 258 R9 R32 R35 gsbk_9 gsb_14 Fig. 9. End shield.
12 ABB AB Components Visiting address: Lyviksvägen 1 Postal address: SE Ludvika, SWEDEN Tel Fax sales@se.abb.com 1ZSC563-AAA en, Rev. 2,
1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide
1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover
More information1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide
1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationResin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide
1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More information1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide
1ZSE 2750-106 EN, REV. 7 Oil SF 6 bushings type GOEK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationTransformer bushings, type GOH. Technical guide
Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More information1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide
1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More information1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide
1ZSE 2750-102 en, Rev. 7 Transformer bushings, type GOB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical
More informationBushings for High Voltage AC Applications
Bushings for High Voltage AC Applications Selection guide 1ZSE 2750-100 en, Rev. 3, 2006-03-15 During selection of for high voltage applications several important factors have to be considered to ensure
More information1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide
1ZSE 2750-112 EN, REV. 4 Wall bushings type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationTransformer bushings, type GSA-OA Technical guide
Transformer bushings, type GSA-OA Technical guide ZSE 2750- en, Rev. 5, 2005-05-5 This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to
More information1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide
1ZSE 2750-102 en, Rev. 9 Transformer bushings, type GOB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More information1ZSE en, Rev. 9. Transformer bushings, type GSA-OA Technical guide
1ZSE 2750-111 en, Rev. 9 Transformer bushings, type GSA-OA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationMicafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB
Micafil transformer oil-sf 6 bushings GARIP / RTKG 72.5 55 kv Power and productivity for a better world TM ABB Design and accessories The design of the main RIP insulating body includes a solid, non-removable
More informationProduct presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 New RIS transformer bushings The paper-free solution Transformer condenser bushings Why a new technology? To preserve
More informationA of 3. Edition : Date : Page : Document No. Amendments :
&RQWHQWV,QVWUXFWLRQIRURSHUDWLRQ %XVKLQJ7HVW7DS +/$%( Document No. Edition : Date : Page : Amendments : A 7..99 of 3 *((5$/'(6,* 38536( &(&7, &DSDFLWDQFHDQGSRZHUIDFWRUPHDVXUHPHQWV 3HUPDQHQWPHDVXUHPHQWV,68/$7,7(676
More informationTransformer bushings, type GOA 250. Installation and maintenance guide
Transformer bushings, type GOA 250 Installation and maintenance guide This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor
More informationTransformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC
Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC 60137-2008 High current bushings for transformer Features Bushing Type CFPT version Porcelain Insulator Trench RIG technology for
More informationOIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC
OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) 1800 24kV to 550kV up to 5000A IEC 60137-2008 Features If you need any transformer bushing proven in operation conditions around the world, Trench
More information1ZSC ABJ EN, REV. 1. Gas insulated wall bushings type GGFL Technical guide
1ZSC000563-ABJ EN, REV. 1 Gas insulated wall bushings type GGFL Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More informationA of 14. Edition : Date : Page : Document No. Amendments :
&RQWHQWV,QVWUXFWLRQVIRU(UHFWLRQ 2SHUDWLRQ 2XWGRRU7UDQVIRUPHU%XVKLQJ 57.)N9.6,7 6HULHV&25,3 +/$%( Document No. Edition : Date : Page : Amendments : A 29.11.02 1 of 14 *(1(5$/'(6,*1 3$&.,1* %XVKLQJ6XSSO\&RQGLWLRQV
More informationMotor-drive mechanism, type BUL. Technical guide
Motor-drive mechanism, type BUL Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More informationINTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.
INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side
More informationDM Condenser bushings, kV DURESCA
DM Condenser bushings, 36 DURESCA Through wall bushings for indoor and outdoor applications, Resin Impregnated Paper IEC 601378 and IEEE C57.19.01.004 DURESCA Wall bushings Swiss quality combined with
More informationdfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide
dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide Table of contents 1 Introduction... 3 1.1 Style Number... 3 1.1.1 Style Number Examples... 3 2 Basic Characteristics... 4 2.1
More informationINSTRUCTION MANUAL CRS Combined insulation bushing
INSTRUCTION MANUAL CRS Combined insulation bushing 5COH020200 CRS REV03 2 TABLE OF CONTENTS 1 SAFETY... 5 1.1 SAFETY INSTRUCTION... 5 1.2 SPECIFIED APPLICATION... 5 1.3 SAFETY NOTES ON THE EQUIPMENT OPERATION...
More informationkv А
66-220 kv 2000-4000 А Publication 11.2011 "IZOLYATOR" PLANT performs design, manufacturing, warranty and post-warranty service of high-voltage bushings for various applications. The enterprise is the main
More informationACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE
ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE hvgrid-tech designs and manufactures high voltage cable accessories for all types of cable systems, ranging from 69 kv to
More informationOIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC
OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) 1800 24kV to 550kV up to 5000A IEC 60137-2008 Features If you need any transformer bushing proven in operation conditions around the world, Trench
More informationHVDC bushing without oil side porcelain Type GOF, for outdoor mounting. Installation and maintenance guide
HVDC bushing without oil side porcelain Type GOF, for outdoor mounting Installation and maintenance guide This document must not be copied without our written permission, and the contents thereof must
More informationCP Automatic capacitor bank
CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor
More informationB kv Gas-insulated Substations
72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.
More information1ZSC AAX EN, Transformer bushing, type GSC Installation and maintenance guide
1ZSC000563-AAX EN, 2018-01-16 Transformer bushing, type GSC Installation and maintenance guide The information contained in this document may be subject to change without prior warning and should not be
More information1ZSC ABE en, Rev. 1. HVDC bushing, type GSD Installation and maintenance guide
1ZSC000563-ABE en, Rev. 1 HVDC bushing, type GSD Installation and maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More informationDURESCA Busbar system. For indoor and outdoor applications, type DE / type DG DURESCA
DURESCA Busbar system For indoor and outdoor applications, type DE / type DG DURESCA DURESCA Busbar system Swiss quality combined with global experience PRODUCT OVERVIEW Moser Glaser General description
More informationBus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:
4 (Four) Pole Monoblock: Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers: Designed and manufactured in accordance with EN 50336:2002 and BS 2562: 1979 1 Introduction:
More informationPABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY
PABS Air-to-SF 6 Bushings 7.5-800 kv BUSHINGS AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS 7 - ANSI STANDARDS AN ALSTOM COMPANY PABS bushings are gas-insulated types that meet IEC 7, ANSI/IEEE or
More informationMICAFIL RIP Transformer Bushings AirRIP / RTKF kv
INSULATION AND COMPONENTS MICAFIL RIP Transformer Bushings AirRIP / RTKF kv MICAFIL AirRIP bushings offer an extended service life combined with enhanced reliability and safety to ensure the maximum availability
More informationen, Rev. 10. Transformer bushings, type GOH Installation and maintenance guide
2750 515-85 en, Rev. 10 Transformer bushings, type GOH Installation and maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all
More informationen, Transformer bushing, type GSA-OA Installation and maintenance guide...
Transformer bushing, type GSA-OA Installation and maintenance guide... The information contained in this document may be subject to change without prior warning and should not be considered as binding
More informationProduct presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 Dry-type transformers Innovative Technology What is a dry transformer? ABB manufactures a transformer which does
More informationPNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper
GE Grid Solutions PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper PNO bushings are capacitance graded bushings with an oil impregnated paper core. PNO bushings are conform
More informationSF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv
Three-phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv 06B1-E-0020 Small Space Requirement, High Reliability and Safety ー 72.5 to 145kV GIS, SDH714 The number of application
More informationHigh Voltage Surge Arresters Buyer s Guide Section PEXLIM R
High Voltage Surge Arresters Buyer s Guide Section PEXLIM R Zinc Oxide Surge Arrester PEXLIM R Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching
More informationMedium voltage products. KEVCD A combined current and voltage sensor Instructions for installation, use and maintenance
Medium voltage products KEVCD A combined current and voltage sensor Instructions for installation, use and maintenance Instructions for installation, use and maintenance for the KEVCD A combined current
More informationSF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv 06B1-E-0002 Small Space Requirement, High Reliability and Safety ー 72.5 to 145 kv GIS, SDH314/SDHa314
More informationSF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)
SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) About company The «Elektroapparat» plant starts its operation in 1922 as a plant manufacturing high-voltage electrical equipment. During the first two
More informationCurrent transformers. Outdoor operation SF 6 -gas insulated. JGF ( ) kv
Current transformers Outdoor operation SF 6 -gas insulated JGF (245 550) kv General description Current transformers type JGF are used in high voltage switchgear within the 245 550 kv range. They transform
More informationHigh Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide
1ZUA2761-500 rev. 5, 6 April 2010 High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide 1ZUA2761-500 rev. 5, 6 April 2010 2 / 9 Table of contents 1 Description... 3 2 Ratings...
More informationCAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION
CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION TMC TRANSFORMERS - GLOBAL NETWORK UK & IRELAND SPAIN NORTH AMERICA & CANADA GERMANY SWITZERLAND BENELUX & AUSTRIA ITALY POLAND INDIA CENTRAL & SOUTH AMERICA
More informationB kv T&D GAS INSULATED SWITCHGEAR
GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission
More informationTransformer Bushing Type EKTG
Transformer Bushing Type EKTG Mounting Operating and Maintenance Instructions Operation Instructions BAL EKTG/05e Visum 01/14 T/gue Page 1 of 18 SAFETY INSTRUCTIONS These instructions are valid for mounting,
More informationZinc Oxide Surge Arrester EXLIM R
Zinc Oxide Surge Arrester EXLIM R Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching overs. For use when requirements of lightning intensity, energy
More information37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS
SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS
More information3 TM Cold Applied Barrier Boot System
M Technical Information : Barrier Boot TM Cold Applied Barrier Boot System For rated voltages 6.5/11(12) kv and 8.7/15(17.5) kv 92-EE 717-1 Product Description The Cold Applied Barrier Boot System consist
More information15 kv and 25 kv Thru-Bushings
Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation
More informationGAS INSULATED VOLTAGE TRANSFORMERS.
GAS INSULATED VOLTAGE TRANSFORMERS. This document may be subject to changes. Contact ARTECHE NISSIN to confirm the characteristics and availability of the products described here. CONTENTS 1. Presentation
More informationOFFSHORE WIND FEASIBILITY STUDY APPENDICES Appendix C.2 Subsea Cable Data Sheets
OFFSHORE WIND FEASIBILITY STUDY APPENDICES 10-7 10.3.2 Appendix C.2 Subsea Cable Data Sheets Design data for TFVA 36 kv 3x1x240 mm 2 KQ Metallic Laying up Inner sheath Bedding Armor Diameter of conductor
More informationLow voltage bushings for pad-mounted distribution transformers Technical information guide
Transformer components Low voltage bushings for pad-mounted distribution transformers Technical information guide ABB low voltage bushings terminate a transformer s internal low voltage leads at the tank
More informationtests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.
tests ( Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. electrical tests These tests verify contractual
More informationPower Voltage Transformers for Air Insulated Substations
Power Voltage Transformers for Air Insulated Substations Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the application of a
More informationen, Rev. 7. Transformer bushings, type GOM Installation and maintenance guide
2750 515-41 en, Rev. 7 Transformer bushings, type GOM Installation and maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all
More information35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Equipment Connection Bus Bar, or Grounded Metal Equipment Plate F Series Mounting Holes ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric
More informationIEC Separable Connectors 17.5 kv/24 kv, 630A
IEC Separable Connectors 17.5 kv/24 kv, 630A Front T-Body / Coupling (Rear) T-Body Connector Application The Chardon T-Body connectors are used to terminate polymeric cable to dead front apparatus such
More information25 kv Apparatus Bushings
Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation
More information11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls
11kV Compact Switchgear tec - range Minimum to Zero SF6 Insulation Gas. Outec Controls 1 tec xx - 11kV Switchgear Contents 1 tec CB - SF6 Free Switchgear... 3 1.1 Description:... 3 1.2 1.3 Features the
More informationUniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions
UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions ABB a global leader ABB is a global leader in power and automation technologies that
More informationMedium Voltage. Joints & Terminations
57 - Cold Shrink Joints Supporting Core Radially shrinkable elastomeric splice Semi-conductive layer High permitivity insulation layer 6.6/11/(12) kv 3M QS1000 is a one-piece cold shrink joint body manufactured
More informationNXPLUS C Single busbar. Maintenance-free for lifetime
NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage
More informationABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers
ABB PTTR SPAIN Zaragoza. The product: Cast coil transformers ABB BA Transformers - 1-5/7/2007 Dry Type Vacuum Cast Coil Transformer INTRODUCTION ABB BA Transformers - 2 - Product Portfolio II Dry Type
More informationTransformer Bushing Type EKTO
Transformer Bushing Type EKTO Mounting Operating and Maintenance Instructions Operating Instructions BAL EKTO/04e Visum 01/14 T/gue Page 1 of 16 SAFETY INSTRUCTIONS These instructions are valid for mounting,
More informationField Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI
Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI T. Schütte, ABB Schweiz Ltd, High Voltage Components, Bushings, 2015-10-19 INMR2015 - Munich Field experience and
More informationIEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector
www.chardongroup.com IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector Application Chardon Front T-Body / Coupling (Rear) T-Body connectors are fully
More informationTransformer Bushings Type COT COT kv to 245 kv up to 3150 A IEC 137
Transformer Bushings Type COT 5... COT 050 4 kv to 45 kv up to A IEC 37 Features If you need any transformer bushing proven in operation conditions around the world, Trench has it! experience in bushing
More informationSERIES TAP-CHANGER
SERIES 090 - TAP-CHANGER Main characteristics This is an off-circuit tap changer. It means DO NOT OPERATE WHILE THE TRANSFORMER IS ENERGISED. Main characteristics of this tap-changer series are: dimensional
More informationHigh Voltage and Extra High Voltage Cables
High Voltage and Extra High Voltage Cables GUIDE TO THE SELECTION OF EHV AND HV CABLES EHV and HV cables are specially designed on the basis of the project data. To determine appropriate design of a high
More informationEMPAC Metal enclosed capacitor bank for wind applications
EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks
More informationType SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear
Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated
More informationSeparable Connectors and Kits
Important Notice While Woer has made every effort to ensure the accuracy of the information in this catalog, Woer does not guarantee that it is errorless. Nor does Woer make any other warranty or guarantee
More informationZinc Oxide Surge Arrester PEXLIM Q
Zinc Oxide Surge Arrester Protection of switchgear, transformers and other equipment in high voltage systems against atmospheric and switching overvoltages. in areas with high lightning intensity and high
More informationA manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard
A manufacturer s view of bushing reliability, testing and analysis By Lars Jonsson Håkan Rudegard 1 A manufacturer s view of bushing reliability, testing and analysis Lars Jonsson Håkan Rudegard ABB Sweden
More informationHigh Voltage Surge Arresters Buyer s Guide Section PEXLIM P-Y
High Voltage Surge Arresters uyer s Guide Section PEXLIM P-Y Zinc Oxide Surge Arrester PEXLIM P-Y Protection of switchgear, transformers and other equipment in high voltage systems against atmospheric
More informationAIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR
AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector
More informationDCX-M. changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
DCX-M changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES FOR COMMERCIAL BUILDINGS AND DCX-M In = 63 A Quality & design CONFORM TO EN/IEC
More information3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series
3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series Data Sheet 1. Product Description 3M Cold Shrink Termination Kit QT-III 7672-S-8 Series contains one silicone rubber termination
More informationCGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.
MV Switchgear for CGMCOSMOS Fully gas insulated modular and compact (RMU)system Up to 24 kv Up to 27 kv mediumvoltage mediumvoltageag AG Langackerstrasse Langackerstrasse 25 25 CH CH 6330 6330 Cham Cham
More informationCurrent accuracy class. Sensor principles
Indoor Combi Sensor 12, 17.5 and 25 kv 1250 A and 3200 A KEVCD Highest voltage for equipment kv 12.24 Rated continuous primary current A 1250.3200 Rated transformation ratio for current measurement, K
More informationFuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A
DISTRIBUTION SOLUTIONS Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A Efficient protection of voltage transformer circuits Extending the lifetime of installed electrical
More information43-SDMS-01 SPECIFICATIONS FOR
SPECIFICATIONS FOR MV SHUNT POWER CAPACITOR BANK UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description Page 1.0 SCOPE 3
More informationMedium Voltage Products. KEVA 24 B20; KEVA 24 B21 Voltage Sensors Instructions for installation, use and maintenance
Medium Voltage Products KEVA 24 B20; KEVA 24 B21 Voltage Sensors Instructions for installation, use and maintenance Instructions for installation, use and maintenance for the KEVA 24 B20 and KEVA 24 B21
More informationZinc-Oxide Surge Arrester TEXLIM Q-C
Zinc-Oxide Surge Arrester TEXLIM Q-C Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching overs. in areas with very high lightning intensity where
More informationMODVAR Low voltage reactive power compensation modules Installation manual
MODVAR Low voltage reactive power compensation modules Installation manual MODVAR Low voltage reactive power compensation modules Before installation, read this manual carefully and keep at the disposal
More informationTE S RAYCHEM RSTI-CC-58 SCREENED, SEPARABLE COUPLING SYSTEM
Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle. industry photo. This image and the one above should be different versions of the same photo
More informationPRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT
PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT COS 38kV 100A 8kA asym. Type PGC Parallel groove terminal bronze with tin plated NEMA Bracket type B Upper contact copper with silver plated Cap - Cast bronze
More information25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable ELRIM Cycloaliphatic
More informationDeadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL
Deadbreak Apparatus Connectors 600 A 15/25 kv Class BOL-T Deadbreak Connector Electrical Apparatus 600-30 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class BOL-T Deadbreak Connector is used to terminate
More information35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection 35 kv Separable Insulated Connector (elbow) Bus Bar or Other Component Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationEaton s Cooper Power Systems
Page: 1 of CERTIFIED TEST REPORT Eaton s Cooper Power Systems 600 Amp - 35 kv Class Deadbreak Bushing With Internal Ground Screen Design Qualification Tests December 17, 2013 Supersedes 10/20 2013 Eaton
More informationTechnical Specification For Outdoor Substation Harmonic Filter Banks
Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field
More information35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 35 kv Separable Insulated Connector (elbow) Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other
More information