1 Report for CSP Joint Venture Click to edit Master text styles Second level Third level Out of service examination, ultrasonic thickness Fourth survey and level paint evaluation for tanks T221 & T222 Fifth level 19 th March

2 Presentation Title Section 1. Scope Third and Procedures level 2. Executive Summary Table of Contents 6 3. External examination for T221 and T222» Fifth level 4. Internal Examination T Internal Examination T Conclusions and Recommendations 7. Appendix A: UT measurements reports Page

3 Click to edit Master text styles Second level Third level 1. Scope & Procedure Fourth level Fifth level 3

4 Presentation Scope of our Title work and procedures followed The scope of work for this out of service inspection was to evaluate the current condition of the tanks T221 and T222 through visual examination and ultrasonic thickness survey and recommend, if required any rectifying actions to be taken These tanks are coated with epoxy paint and, without removing the paint, MPI and vacuum box testing cannot be performed. However, we have assessed the quality of the paint by carrying out a visual examination and adhesion tests at random location at the bottom» Fifth of both level tanks. Emphasis was given at the areas where paint has failed and rust started to significantly affect the shell plates The procedures followed for the above scope were in accordance with BS EN 12285, EEMUA 159, ISO EN and ISO EN

5 Click to edit Master text styles Second level Third level 2. Executive summary Fourth level Fifth level 5

6 Item Presentation Title Summary of our findings Bund wall area Foundation & Supports External Inspection Internal Inspection Adhesion test UT measurements Other areas of risk Observation Overall found to be in good condition. Erosion observed in North West corner. Wooden ladder leading into area represents a fire hazard and risk for injuries Generally in good condition. Where the steel supports is bolted into the concrete foundation, the concrete sealing has been damaged. Some corrosion was also observed at the points where the steel supports are welded on the tank Paint has failed in a number of areas. There is corrosion in number of places, across the length of the tank. There are also a number of reinforcing plates not properly welded onto the tank which resulted in corrosion initiation» Fifth level There are number of areas where paint has failed and localised corrosion observed. The paint has failed beyond any repair. Severe pitting was also observed in a number of areas, reaching the depth of 5mm (particularly in T221) There are also a number of paint blisters, which represent significant risk to the lifecycle of the tank painting Adhesion test results indicated 100% paint failure i.e. insufficient bonding due to poor initial surface preparation in both tanks T221 & T222 Thickness observed is within the required limits for both tanks Other areas of high risk, for both tanks, are the lack of striking plate for the pontoon leg, improper welding of the striking plate for the measuring ruler, severely corroded internal pipe and the need for adjustment for the floating suction system which is not moving freely Recommendation Repair eroded bund wall and replace wooden ladder by a metallic one Repair the foundation by using appropriate oil resistant sealant Clean, re-evaluate and repair the corroded areas where the steel supports are welded on the tank Clean, repair and test painting where it failed Clean, repair and test corroded areas Remove partially welded reinforcing plates, evaluate condition of shell plate underneath, clean, repair and test Remove paint and evaluate condition of plates and welds Repair all severe pittings by welding lap patch plates and subsequently test the repair works Re-paint, following the correct preparation and painting procedure as per manufacturer s specifications Remove paint, carry out a correct surface preparation and re-paint with appropriate paint as per manufacturer s specifications Introduce striking plate for pontoon leg and test it Repair and test striking plate for measuring ruler Repair, evaluate and test corroded internal pipe Adjust floating suction system 6

7 Click to edit Master text styles Second level Third level 3. External examination for Fourth level T221 and T222 Fifth level 7

8 Presentation The tanks are Titleof a horizontal construction, built in 2001 in accordance to BS 2594:1975 The tanks are of a horizontal welded construction, built in accordance to BS 2594:1975 in 2001 (see photo 1) The tank s main characteristics are:» Fifth level Tank Characteristics Photo 1: Diameter 2.75m Length 9.20m Capacity 55m 3 Product Slop 8

9 Presentation The bund wall Titlearea was found to be in good condition with minor repairs required Visual external examination for T221 and T222 Photo 2: a) Bund walls (T221 and T222) The tanks are located within a bund Third wall area. level Overall, the bund walls appear to be in good condition Part of the wall» Fifth at the level north west corner has eroded and needs to be repaired (see photo 2). Access into the bund wall area is via a wooden ladder (see photo 3). This ladder appears to be unstable, represents a fire hazard and risk for injuries and needs to be replaced by a metallic one Photo 3: 9

10 Presentation Tanks supports Title and foundation also require minor repairs Photo 4: b) Tank Supports (T221 & T222) The steel supports have been welded Second the tanks level as shown in picture 4. These supports are supported on concrete stands by Click large bolts as to shown edit in photo 5Master title style The steel supports Fourth are level welded onto a reinforcing plate, and this has prevented» severe Fifth corrosion level on the supports from taking place. However, some areas of corrosion have been identified The concrete foundation however, requires minor repairs, particularly around the steel base (see photo 5), in order to prevent underside corrosion Photo 5: 10

11 Presentation The shells have Title areas of severe localised corrosion c) Shells The shells, both tanks, show signs of localised corrosion, particularly Second in areas level where the paint has failed and where reinforcing plates have not been fully welded on the shells Click Paint failure to has been edit observed Master on numerous locations title on both style tanks, on the Fourth shells and level across welds, which has caused severe localised corrosion (see photos on pages 16 & 17). There are also» a number Fifth level of reinforcing plates on the shells which support the platform. These have not been properly welded onto the shells and have caused severe corrosion. The corrosion around these plates appears to be severe (see photos 6-15 on pages 13-15). We also suspect that there is serious corrosion underneath the plates which is not visible, due to the lack of welding on 2 of the 4 sides of the plates These represent areas of high risk which need to be addressed immediately. For our recommendations, please refer to section 6 11

12 Improper welding Presentation Title of the reinforcing plates has caused extensive corrosion (1 of 3) Photo 6: Photo 7: Click Fourth to edit level Master title style» Fifth level Photo 8: Photo 9: 12

13 Improper welding of the reinforcing plates has Presentation Title caused extensive corrosion (2 of 3) Photo 10: Photo 11:» Fifth level Photo 12: Photo 13: 13

14 Improper welding of the reinforcing plates has Presentation Title caused extensive corrosion (3 of 3) Photo 14: Photo 15:» Fifth level 14

15 Presentation Paint failure Title has initiated serious localised corrosion (1 of 2) Photo 16: Photo 17:» Fifth level Photo 18: Photo 19: 15

16 Presentation Paint failure Title has initiated serious localised corrosion (2 of 2) Photo 20: Photo 21:» Fifth level 16

17 Click to edit Master text styles Second level 4. Internal Third Examination level Fourth T221 level Fifth level 17

18 Presentation There are signs Title of severe internal corrosion, primarily at places where the paint has failed Photo 22 The tank is coated with epoxy paint and the plates are not directly visible However, the paint has failed in a number of places, causing localised corrosion and serious pitting. There is an area of over 0.5m» 2 where the paint has completely failed Fifth exposing level the plates to the stored product (see photo 22) Photo 23 There are also numerous paint blisters in the tank, which represent areas of risk and should be addressed promptly (see photos 23 & 24. Potential further exposure of the shell plate to the stored product, will result in exponential growth of the corroded areas Photo 24 18

19 Severe pitting has reached depths of 5mm Presentation Title As mentioned previously, the paint failure has caused localised corrosion which has Second subsequently level resulted in severe pitting Pitting has reached, in some locations, the depth of over 5mm, which is over half the original shell thickness (see photos 25 & 26)» Fifth level Photo 25: The depth of this pitting is critical and requires immediate remedial work to prevent further localised corrosion, which could result in fuel leakage Photo 26: 19

20 Presentation The paint adhesion Title results indicate a poor paint bonding strength Photo 27: We have carried out a paint adhesion test to evaluate the quality of the paint s Second bonding strength level (see photos 27 & 28) The results of the test have shown that the paint bonding strength is extremely low and the paint failure is beyond repair» Fifth level Primary reason for this appears to be poor initial surface preparation prior to the initial painting This needs to be addressed promptly to ensure the tanks integrity is maintained. The paint provides protection to the shell plates and further paint failure could result in product leakage The results of paint failure are already evident in areas where the lack of paint has caused pitting of 5mm depth Photo 28: 20

21 Presentation Other areas Title of risk include lack or poor welding of striking plates We asasastext have also identified a styles number of other areas which pose significant risk and need to be addressed in order to Second ensure the tanks level integrity. These are the: Lack of striking plate for the pontoon leg (see photo Fourth 29) level Improper welding of the striking plate for the measuring» ruler, Fifth which level allows the product to penetrate underneath it. We suspect the area underneath is not coated, and this could potentially result in significant material loss of the shell course underneath (photo 30) Severely corroded pipe, which requires immediate repair (see photo 31) The floating suction system is not moving freely and requires adjustment Photo 29 Photo 30 Photo 31 21

22 Presentation Ultrasonic thickness Title measurements were taken as per BS EN We have taken ultrasonic thickness measurements from the inside of the tanks, as per EN at approximately every 0.3m length Third at level the locations shown on the right» Fifth level The measurements indicate that the shell plates are in good condition (with the exception of the localised pitting described in section 3) and average thickness above the minimum required Measurement positions Detailed results of the ultrasonic thickness measurements can be found in the corresponding report in Appendix A 22

23 Click to edit Master text styles Second level 5. Internal Third Examination level Fourth T222 level Fifth level 23

24 Presentation There are signs Title of corrosion inside the shell, primarily at places where the paint has failed Photo 32 The tank is coated with epoxy paint and the plates are not directly visible. However, the paint has failed in number of places, and there Third is decolourisation level of the paint on the side of the tank Pitting has also initiated at a number of places» Fifth level There are also numerous paint blisters in the tank, which represent areas of risk and should be addressed promptly. Potential further exposure of the plate to the stored product, will multiply the localised corroded areas. There are also areas of paint discolourisation inside the tank, indicating an area where paint has started to fail Area covered in paint blisters Photo 33 Photo 34 Paint discolourisation 24

25 Presentation The poor condition Title of the paint is evident in number of places Photo 35: Photo 36:» Fifth level Photo 37: Photo 38: 25

26 Presentation Other areas Title of risk include lack or poor welding of striking plates We have also identified a number of other areas which pose significant risk and need Second to be addressed level in order to ensure the tanks integrity. These are the: Lack of striking plate for the pontoon leg (see photo 39) Improper welding of» the Fifth striking level plate for the measuring ruler, which allows the product to penetrate underneath it. We suspect the area underneath is not coated, and this could potentially result in significant damage to the shell (photo 40) Severely corroded pipe, which requires immediate repair (see photo 41) The floating suction system is not moving freely and requires adjustment Photo 39 Photo 40 Photo 41 26

27 Presentation The paint adhesion Title results indicate a poor paint bonding strength Photo 42 We have carried out a paint adhesion test to evaluate the quality of the paint s bonding strength The results of the test have shown that the paint bonding strength is extremely low and the paint failure is beyond repair» Fifth level Primary reason for this appears to be poor initial surface preparation prior to the initial painting This needs to be addressed promptly to ensure the tanks integrity is maintained. The paint provides protection to the shell plates and further paint failure could result in catastrophic failure Photo 43 27

28 Presentation Ultrasonic thickness Title measurements were taken across the length of the tank Measurement positions We have taken ultrasonic thickness measurements from the inside of the tanks as per EN 12819, at approximately every 0.3m Second length at the level locations shown on the right The measurements indicate that the shell plates are in good condition» Fifth (with level the exception of the localised pitting described in section 3) and average thickness above the minimum required Detailed results of the ultrasonic thickness measurements can be found in the corresponding report in Appendix A 28

29 Click to edit Master text styles Second level 6. Conclusions Third level and Recommendations Fourth level Fifth level 29

30 Presentation The bund wall Titlearea appears to be in good condition with minor repairs required 1. Bund wall area The bund wall area was found to be in good condition, with the exception of the NW corner and the wooden ladder used to enter the area a) We recommend to repair the area where the wall has eroded. Bund wall area needs to be in good condition to ensure it holds any spillage» Fifth level b) We also recommend to replace the existing unstable, wooden ladder that leads into the bund wall with a metallic one, as it represents both a fire hazard and a Health and Safety risk. This will limit the fire risk and the risk of injuries of people entering the bund wall 30

31 Presentation Foundations Title and supports of the tanks also require some repairs 2. Foundations and supports The foundations and supports were also found to be, generally, in good condition, with the exception Third level of a few areas where corrosion has initiated, and where the supports sealing Fourth needs level to be repaired» Fifth level a) We recommend to clean and repair the paint at the areas on the steel supports where paint has failed and corrosion initiated. This will ensure that further corrosion in this critical area is prevented b) At the area where the steel supports are bolted into the concrete foundation, the concrete used to seal the gap between the steel support and the concrete foundation, has failed in number of places and there is a risk of underside corrosion. We recommend to remove any remaining of this concrete layer and seal all supports for both tanks with oil resistant sealant 31

32 Presentation Externally, the Titleseverely corroded areas require immediate attention 3. External Examination The external shells of both T221 and T222 show signs of corrosion, particularly around the reinforcing plates which have been partially welded on the tanks. There are also other areas where the paint has failed and corrosion has initiated a) We recommend that the externally corroded areas are cleaned, reevaluated» and Fifth repaired level accordingly. Similarly, all areas where the paint has failed should also be repaired b) The partially welded reinforcing plates have to be removed and the condition of the shell underneath them to be inspected and evaluated. Depending on the inspection results, the shells will need to be repaired appropriately and any reinforcing plates should be welded properly on the tank shell and tested 32

33 The Presentation paint has Title failed in numerous places within both tanks leading to localised corrosion 4. asasastext Internal examination: styles During our internal examination of both T221 and T222 tanks we have observed the following: The overall thickness of the plates appears to be satisfactory based on the ultrasonic Third level thickness measurements taken across both tanks, which showed low level Fourth of overall level corrosion The plates are painted with epoxy paint and therefore MPI and Vacuum box testing» Fifth could not level be performed However, there are areas where that paint has failed and localised corrosion observed. There are also numerous paint blisters, which represent significant risk to the lifecycle of the paint the tank The paint strength has also proved to be very poor in both tanks as they 100% failed the adhesion test Pitting, which represent areas of high risk, was also observed in both tanks Tank T221 in particular, has areas of significant pitting, reaching, in some cases, the depth of 5mm There are other areas of risk which need to be addressed and include the lack of striking plate for the pontoon leg, a semi-welded striking plate for the measuring ruler, a severely corroded internal plate and lack of adjustment for the floating suction system 33

34 Presentation We recommend Title to address all issues identified to ensure the tanks integrity We therefore recommend the following measures to be taken: As the paint s condition is poor, we recommend to initially completely remove the paint internally This will enable further inspection of the tank s plates through full visual, vacuum box and MPI testing in order to establish the actual condition of the entire tanks Click and of to the welds edit Master title style The identified Fourth damaged level and corroded areas can then be repaired, ensuring the tanks are fit to return to service and prolong their lifetime. This should» also Fifth include level the repair of the semi-welded striking plate for the measuring ruler and of the severely corroded internal pipe The shells should subsequently be properly be painted, ensuring correct surface preparation is followed, in line with the manufacturer s specifications. This will avoid any paint blisters which will speed up paint failure and localised corrosion Additionally, striking plate for the pontoon should be added, after carefully cleaning and evaluating the area The floating suction system should be adjusted appropriately to enable it to move freely Prepared by: C.Kallis, CEng, Mins NDT, Tank Integrity Assessor 02/ATC5E/010 S.Kallis, MEng, CEng, Tank Integrity Assessor 09/11L1/84 34

35 Click to edit Master text styles Second level APPENDIX Third levela UT measurements Fourth levelreports Fifth level 35

API 653 TANK INSPECTION, TANK MAINTENANCE, AND CAUSES OF TANK FAILURE

API 653 TANK INSPECTION, TANK MAINTENANCE, AND CAUSES OF TANK FAILURE API 653 TANK INSPECTION, TANK MAINTENANCE, AND CAUSES OF TANK FAILURE API 653 Tank Inspections Why Inspect Your Tanks? Prevent leaks into your secondary containment or to groundwater (if you do not have

More information

Pressure Vessel Assessment Report

Pressure Vessel Assessment Report Project Information Client: Total Energy Location: Blackwell OK Date: 7/23/2013 Contact: Integrity Mgmt. Advisor: Chuck Easterbrooks - API 510 #2212 Cc: API / UT Inspector: Robert Van Pelt-API 510# 40899

More information

Tank Maintenance and Renovation. Statoil Refining Denmark Kalundborg Refinery

Tank Maintenance and Renovation. Statoil Refining Denmark Kalundborg Refinery Tank Maintenance and Renovation Statoil Refining Denmark Kalundborg Refinery Classification: Open 2017-11--03 Denmark Hedehusene Kalundborg København Classification: Open Statoil Kalundborg seen from the

More information

ENGINEERING BULLETIN

ENGINEERING BULLETIN EFFECTIVE - DECEMBER 14, 2017 Table of contents: 1. Introduction 2. Materials and Methods 3. Observations, Failure modes and Immediate Safety Concerns 4. Summary 5. Conclusion 1. Introduction As is sometimes

More information

Installation and Maintenance Manual CORRUGATED RIVETED GALVANIZED STEEL WATER STORAGE TANKS

Installation and Maintenance Manual CORRUGATED RIVETED GALVANIZED STEEL WATER STORAGE TANKS BH TANK A Division Of American Tank Co., Inc. Installation and Maintenance Manual CORRUGATED RIVETED GALVANIZED STEEL WATER STORAGE TANKS American Tank Co., Inc. P.O. Box 340 Windsor CA 95492 www.bhtank.com

More information

CARES Technical Approval Report TA1B

CARES Technical Approval Report TA1B CARES Technical Approval Report TA1B - 5029 Issue 4 LENTON Standard, Standard Transition, Position, Position Transition, Parallel Bolt Couplers and Mechanical Anchors Assessment of the LENTON Standard,

More information

CARES Technical Approval Report TA1C

CARES Technical Approval Report TA1C CARES Technical Approval Report TA1C - 5057 Issue 1 LENTON Standard, Position, Parallel Bolt Couplers and Mechanical Anchor Assessment of the LENTON Standard, Standard Transition, Position, Parallel Bolt

More information

Car Company Quality: A Vehicle Test Fit Study of 1,907 Car Company Service Parts

Car Company Quality: A Vehicle Test Fit Study of 1,907 Car Company Service Parts Car Company Quality: A Vehicle Test Fit Study of 1,907 Car Company Service Study Dates: March 1999 March 2002 Prepared By Certified Automotive Association 1518 K Street NW, Suite 306 Washington, DC 20005

More information

FINAL REPORT CATHODIC PROTECTION EVALUATION. 42-Inch Water Transmission Pipeline Contract 1 Station 0+00 to South Texas Water Authority

FINAL REPORT CATHODIC PROTECTION EVALUATION. 42-Inch Water Transmission Pipeline Contract 1 Station 0+00 to South Texas Water Authority FINAL REPORT CATHODIC PROTECTION EVALUATION 42-Inch Water Transmission Pipeline Contract 1 Station 0+00 to 50+00 South Texas Water Authority Prepared for: South Texas Water Authority P.O. Box 1701 Kingsville,

More information

Table of Contents. 4. Before a New Turbocharger is Installed

Table of Contents. 4. Before a New Turbocharger is Installed Table of Contents 1. Turbocharger Overview ------------------------------------------------------------------ 1.1. Definition -----------------------------------------------------------------------------

More information

Investigation into UK socket-outlets incorporating USB charging points

Investigation into UK socket-outlets incorporating USB charging points Investigation into UK socket-outlets incorporating USB charging points Electrical Safety First investigated a number of commercially available UK socket-outlets incorporating USB ports, as a repeat of

More information

Storage Tank Management

Storage Tank Management Storage Tank Management Background Any Oil terminal, production or petrochemical company handling thousands of barrels of crude oil or other liquid product per day needs to ensure that there is continuity

More information

Overview. MISTRAS Overview

Overview. MISTRAS Overview 1 MISTRAS 2 Improved RBI Analysis of Above Ground Storage Tanks Through the Use of On Stream Inspections Sam Ternowchek Mistras Group Internal Inspections of Tank Floors is Expensive Inspection Frequency

More information

Driver Operator Aerials: Maintenance and Testing. 4 Skills Total. NFPA 1002, Standard for Driver Operator Professional Qualifications, 2014 Edition

Driver Operator Aerials: Maintenance and Testing. 4 Skills Total. NFPA 1002, Standard for Driver Operator Professional Qualifications, 2014 Edition Driver Operator Aerials: Maintenance and Testing 4 Skills Total NFPA 1002, Standard for Driver Operator Professional Qualifications, 2014 Edition Driver Operator Aerials Maintenance & Testing Skills Book

More information

SAFE USE AND HANDLING OF HOSES AND FLEXIBLE CONNECTIONS IN THE SOLVENTS INDUSTRY

SAFE USE AND HANDLING OF HOSES AND FLEXIBLE CONNECTIONS IN THE SOLVENTS INDUSTRY GUIDANCE NOTE No. 60 SAFE USE AND HANDLING OF HOSES AND FLEXIBLE CONNECTIONS IN THE SOLVENTS INDUSTRY 1. Introduction The Solvents Industry Association has issued this Guidance Note because of the specific

More information

Steel Tank Maintenance. Fluid Fertilizer Foundation December 4, 2012

Steel Tank Maintenance. Fluid Fertilizer Foundation December 4, 2012 Steel Tank Maintenance Fluid Fertilizer Foundation December 4, 2012 Tank Failure History Storage tank failure is as old as storage tank usage On January 15, 1919 a U.S. Industrial Alcohol Company s tank

More information

Monthly Checklist For Depot

Monthly Checklist For Depot Monthly Checklist For Depot ANNEXURE 1.L(iv) TANK FARM Notes : i. The scope covers piping, valve & fittings, general housekeeping, pumps & motors, effluent management, fire protection and security within

More information

Section 03 Marine and Mooring Equipment - Sales Item

Section 03 Marine and Mooring Equipment - Sales Item Section 03 Marine and Mooring Equipment - Sales Item 03030512 SBM Standard Wheel and Rail CALM Buoy. 12.5m Diameter x 4.8m Deep Buoy, complete with 2 x 24 and 1 x 16 Inlet/outlets at 225psi DETAIL AS FOLLOWS:

More information

ESTABLISHMENT OF ULTRASONIC TESTING IN UNIQUE DESIGNED PARTIAL PENETRATION END PLUG OF HEADER IN BOILERS.

ESTABLISHMENT OF ULTRASONIC TESTING IN UNIQUE DESIGNED PARTIAL PENETRATION END PLUG OF HEADER IN BOILERS. Proceedings of the National Seminar & Exhibition on Non-Destructive Evaluation NDE 2011, December 8-10, 2011 ESTABLISHMENT OF ULTRASONIC TESTING IN UNIQUE DESIGNED PARTIAL PENETRATION END PLUG OF HEADER

More information

BOSS ZONE 1 GRP MOBILE WORKING TOWER INSPECTION PROCEDURE. Youngman Group Ltd Issue B Date 23/03/09 Page 1 of 8 Pages

BOSS ZONE 1 GRP MOBILE WORKING TOWER INSPECTION PROCEDURE. Youngman Group Ltd Issue B Date 23/03/09 Page 1 of 8 Pages BOSS ZONE 1 GRP MOBILE WORKING TOWER INSPECTION PROCEDURE Youngman Group Ltd Issue B Date 23/03/09 Page 1 of 8 Pages INTRODUCTION This inspection procedure applies to BoSS Zone 1 GRP Mobile Working Towers

More information

GB NDT AXLE TESTING & DEFECT TYPES FOUND

GB NDT AXLE TESTING & DEFECT TYPES FOUND Applied Inspection Ltd GB NDT AXLE TESTING & DEFECT TYPES FOUND ESIS TC24 Workshop at RSSB 03/04 March 2011 Presented by Roy Archer (Technical Manager Rail - Level 3) Manual ultrasonic testing used for

More information

Aftermarket Part Quality: A Report on Parts that Fail CAPA s Certification Requirements

Aftermarket Part Quality: A Report on Parts that Fail CAPA s Certification Requirements Aftermarket Part Quality: A Report on Parts that Fail CAPA s Certification Requirements Study Dates: March 1999 May 2003 Prepared By Certified Automotive Parts Association 1518 K Street NW, Suite 306 Washington,

More information

TURBOCHARGER WARRANTY ANALYSIS GUIDELINES

TURBOCHARGER WARRANTY ANALYSIS GUIDELINES ABOUT US Rotomaster is a turbocharger manufacturing company driven by customer demand and focused on our customer s success. The quality put forth by Roto is world class utilizing modern CNC (Computerized

More information

Turbocharger Warranty Analysis Guidelines

Turbocharger Warranty Analysis Guidelines Turbocharger Warranty Analysis Guidelines Authorized Agent Use Only INTERSTATE-McBEE, LLC 5300 Lakeside Avenue Cleveland, Ohio 44114 U.S.A. 216-881-0015 Toll Free: 1-800-321-4234 Fax: 216-881-0805 www.interstate-mcbee.com

More information

SubC Partner A/S. JibFlex JF-150-4

SubC Partner A/S. JibFlex JF-150-4 SubC Partner A/S JibFlex JF-150-4 Version 2 02-01-2017 Contents 1. Legal...2 1.1 EC declaration of conformity...2 1.2 Safety and Compliance...3 2. Description of JibFlex JF 150-4:...4 2.1 Description of

More information

BRISTLE BLASTING SURFACE PREPARATION METHOD FOR MAINTENANCE. Neil Wilds

BRISTLE BLASTING SURFACE PREPARATION METHOD FOR MAINTENANCE. Neil Wilds Paper No. 09004 2009 BRISTLE BLASTING SURFACE PREPARATION METHOD FOR MAINTENANCE Neil Wilds International Paint Ltd., Protective Coatings Stoneygate Lane, Gateshead Tyne and Wear, NE10 0JY United Kingdom

More information

EA Closing Report Page 1 of 9

EA Closing Report Page 1 of 9 EA06-002 Closing Report Page 1 of 9 SUBJECT: Rear coil spring fracture ENGINEERING ANALYSIS CLOSING REPORT EA No: EA06-002 DATE OPENED: 24-Jan-2006 DATE CLOSED: 05-Feb-2007 SUBJECT VEHICLES: Model Year

More information

McCannalok HIGH PERFORMANCE BUTTERFLY VALVE OPERATION AND MAINTENANCE MANUAL. The High Performance Company

McCannalok HIGH PERFORMANCE BUTTERFLY VALVE OPERATION AND MAINTENANCE MANUAL. The High Performance Company McCannalok HIGH PERFORMANCE BUTTERFLY VALVE OPERATION AND MAINTENANCE MANUAL The High Performance Company Table of Contents Safety Information - Definition of Terms... 1 Introduction... 1 Installation...

More information

I N F O R M A T I O N S H E E T # Dece m b e r

I N F O R M A T I O N S H E E T # Dece m b e r I N F O R M A T I O N S H E E T # 0 3-2 0 1 7 Dece m b e r 2 0 1 7 LOW V O L U M E V E H I C L E T E C H N I C A L A S S O C I A T I O N I n c Total Cost Involved (TCI) Independent Front Suspension System

More information

The aim is the detection of

The aim is the detection of The aim is the detection of material defects such as pores and cracks, other mechanical damage, and also from errors in applying the covering material. Testing for defective areas for pipe laying is covered

More information

D J A INSPECTION SERVICES, INC. Storage Tank Management & Inspection

D J A INSPECTION SERVICES, INC. Storage Tank Management & Inspection D J A INSPECTION SERVICES, INC. Storage Tank Management & Inspection 814-676-3663 P. O. Box 384 Reno, PA 16343 661-363-5453 P. O. Box 544 Edison, CA 93220 PORT OIL PORTLAND, CT Tank #5 Date of Out - of

More information

ROHRBACK COSASCO SYSTEMS TEST REPORT

ROHRBACK COSASCO SYSTEMS TEST REPORT ROHRBACK COSASCO SYSTEMS TEST REPORT Subject: RSL Retriever 2500 psi Debris Test Report Issued By: Rohrback Cosasco Systems, Santa Fe Springs, CA USA Date: June 6, 2012 E-mail: services@cosasco.com Website:

More information

PISTON ENGINE OVERHAUL PERIODS FOR AIRCRAFT HOLDING A NATIONAL CERTIFICATE OF AIRWORTHINESS

PISTON ENGINE OVERHAUL PERIODS FOR AIRCRAFT HOLDING A NATIONAL CERTIFICATE OF AIRWORTHINESS Irish Aviation Authority The Times Building 11 12 D Olier Street Dublin 2, Ireland www.iaa.ie Safety Regulation Division Údarás Eitlíochta na héireann Foirgneamh na hamanna 11 12 Sráid D Olier Baile Átha

More information

High Quality Filter Elements How can you recognize quality? Practice Theory

High Quality Filter Elements How can you recognize quality? Practice Theory High Quality Filter Elements How can you recognize quality? Original Filter Elements with Constant Quality Five Performance Figures Theoretical Principles The filter elements of meet very high standards

More information

Comprehensive Management of Hydrocarbon Storage Tanks Ageing

Comprehensive Management of Hydrocarbon Storage Tanks Ageing ECNDT 2006 - Fr.2.2.2 Comprehensive Management of Hydrocarbon Storage Tanks Ageing Vincent LESUEUR, Mathieu RIETHMULLER, Daniel CHAUVEAU, IS Services, France Abstract. Corrosion generates considerable

More information

PORTABLE LADDER SAFETY PROGRAM

PORTABLE LADDER SAFETY PROGRAM PORTABLE LADDER SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR 1910.25 Portable Wood Ladders* - 29 CFR 1910.26 Portable Metal Ladders* - 29 CFR 1926.1050-1060* *The above standards are intended to prescribe

More information

Assessment of Elevator and Escalator Maintenance & Repair Program Final Elevator Audit Submission Foggy Bottom Station - Escalator C04X03 (Entrance)

Assessment of Elevator and Escalator Maintenance & Repair Program Final Elevator Audit Submission Foggy Bottom Station - Escalator C04X03 (Entrance) Foggy Bottom Station - Escalator C04X03 (Entrance) 217 Foggy Bottom Station - Escalator C04X04 (Platform) Foggy Bottom Station Escalator C04X04 (Platform) Escalator Audit Equipment Description The escalator

More information

Hi-Force Limited Prospect Way Daventry Northants NN11 8PL United Kingdom Tel: +44(0) : Fax: +44(0) : Website:

Hi-Force Limited Prospect Way Daventry Northants NN11 8PL United Kingdom Tel: +44(0) : Fax: +44(0) : Website: TWM High Capacity Aluminium Manual Torque Wrench Range glasses/ visor and protective gloves should be worn at all times. All relevant risk assessments should be completed prior to use of the equipment.

More information

STATE OF NORTH CAROLINA D DEPARTMENT OF ADMINISTRATION MARCH 20, 1995 PURCHASE AND CONTRACT DIVISION 7125-LM-2C November 9, 1989

STATE OF NORTH CAROLINA D DEPARTMENT OF ADMINISTRATION MARCH 20, 1995 PURCHASE AND CONTRACT DIVISION 7125-LM-2C November 9, 1989 STATE OF NORTH CAROLINA 7125-2D DEPARTMENT OF ADMINISTRATION MARCH 20, 1995 PURCHASE AND CONTRACT DIVISION Superseding 7125-LM-2C November 9, 1989 SPECIFICATION FOR LOCKERS, METAL (This specification is

More information

Evaluation Report of Rust Grip Test Samples Hwy. 190 Mississippi River Bridge Located in Baton Rouge, LA. Prepared For:

Evaluation Report of Rust Grip Test Samples Hwy. 190 Mississippi River Bridge Located in Baton Rouge, LA. Prepared For: CORRTECH CORROSION ENGINEERING INFRASTRUCTURE TECHNOLOGIES Evaluation Report of Rust Grip Test Samples Hwy. 190 Mississippi River Bridge Located in Baton Rouge, LA Prepared For: Superior Products International

More information

Mass Tank Inspection Services, LLC 29 Abbey Lane Middleboro, MA masstankinspection.com

Mass Tank Inspection Services, LLC 29 Abbey Lane Middleboro, MA masstankinspection.com June 18, 2018 Mrs. Nancy Cole Administrator Village of Eidelweiss 1680 Conway RD Madison, NH 03849 Mass Tank Inspection Services, LLC 29 Abbey Lane Middleboro, MA 02346 508-947-8826 masstankinspection.com

More information

Folksam Mazda 6 Post-Impact Inspection 22/02/18

Folksam Mazda 6 Post-Impact Inspection 22/02/18 Offset Deformable Barrier Frontal Impact Dummy Score 2003 Test at TRL Driver Passenger Score (worst) 11 2018 Test at Thatcham Score (worst) 12.289 Modifier Score Reason Head airbag contact Bottoming out

More information

YOUR GLOBAL FLOW CONTROL PARTNER. BRAY/MCCANNALOK EN High Performance Butterfly Valve Operation and Maintenance Manual

YOUR GLOBAL FLOW CONTROL PARTNER. BRAY/MCCANNALOK EN High Performance Butterfly Valve Operation and Maintenance Manual YOUR GLOBAL FLOW CONTROL PARTNER BRAY/MCCANNALOK EN High Performance Butterfly Valve TABLE OF CONTENTS 1.0 Definition of Terms....................................... 2 2.0 Introduction...........................................

More information

: 1250 gpm in the deck mode : 800 gpm while operating in the ground base - Dual Inlet : 1000 gpm while operating in the ground base - Single Inlet

: 1250 gpm in the deck mode : 800 gpm while operating in the ground base - Dual Inlet : 1000 gpm while operating in the ground base - Single Inlet APOLLO HI-RISER MONITOR STYLE 3433/3431 INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS The following is intended to provide the basic instructions for installation, operation and maintenance of

More information

DISTRIBUTION: Electronic Recipients List TRANSMITTAL LETTER NO. (15-01) MINNESOTA DEPARTMENT OF TRANSPORTATION. MANUAL: Road Design English Manual

DISTRIBUTION: Electronic Recipients List TRANSMITTAL LETTER NO. (15-01) MINNESOTA DEPARTMENT OF TRANSPORTATION. MANUAL: Road Design English Manual DISTRIBUTION: Electronic Recipients List MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards Unit ISSUED BY: Office of Project Management and Technical Support TRANSMITTAL LETTER NO.

More information

Providing Quality Technical Services to the Coating Industry. 60,000 Gallon Elevated Water Storage Tank

Providing Quality Technical Services to the Coating Industry.   60,000 Gallon Elevated Water Storage Tank P.O. Box 801357 Santa Clarita, CA 91380-2316 Toll free: 877.274.2422 Fax: 661.775.7628 www.csiservices.biz Providing Quality Technical Services to the Coating Industry Via E-mail Mr. Rob Rush City of Clovis

More information

EQUIPMENT PERFORMANCE SPILL PREVENTION AND PIPING KEVIN HENDERSON

EQUIPMENT PERFORMANCE SPILL PREVENTION AND PIPING KEVIN HENDERSON EQUIPMENT PERFORMANCE SPILL PREVENTION AND PIPING KEVIN HENDERSON 20 th ANNUAL NATIONAL TANKS CONFERENCE March 17-19, 2008 ATLANTA, GEORGIA SPILL BUCKETS: OPW 1 PETRO STOPPING CENTER JACKSON, MS Six 20,000

More information

Understanding the Inspection Process for Owners and Operators

Understanding the Inspection Process for Owners and Operators Underground Storage Tanks (UST s) Metal Integrity and Lining Inspections Understanding the Inspection Process for Owners and Operators Presented By: Robert L. McChan II General Manager/Senior Project Manager/Steel

More information

Dust cover. Plug. Outlet. Wire pole holder

Dust cover. Plug. Outlet. Wire pole holder Thank you for choosingxtreme machine,baby -Mammoth (4 head), designing with double gear-driving, planetary grinding with four plates. The machine speed can reach 1800 rpm. Aluminum alloy gear box with

More information

INSTALLATION, OPERATION, MAINTENANCE MANUAL FOR MANUALLY OPERATED STOP CHECK VALVE

INSTALLATION, OPERATION, MAINTENANCE MANUAL FOR MANUALLY OPERATED STOP CHECK VALVE INSTALLATION, OPERATION, MAINTENANCE MANUAL FOR MANUALLY OPERATED STOP CHECK VALVE Page 1 of 13 1.1 General CHAPTER 1 - GENERAL INFORMATION This manual contains maintenance instructions with pertinent

More information

Ultrasonic Thickness Measurements Shipboard Manuals Condition Surveys Ship Studies

Ultrasonic Thickness Measurements Shipboard Manuals Condition Surveys Ship Studies Page 1 of 8 Vessels Name: Place & Date of inspection: Pre-Purchase Survey Documentation / Bridge Completed Not Found Not Given Priority General Particulars Time Charter Description (if available on board)

More information

HYDRAULIC SPREADER. Max. Pressure: 10,000 PSI (700 BAR) Unit Weight: HS2000 = 4.8 LBS. (2.17 Kg) HS3000 = 22 LBS. (9.98 Kg)

HYDRAULIC SPREADER. Max. Pressure: 10,000 PSI (700 BAR) Unit Weight: HS2000 = 4.8 LBS. (2.17 Kg) HS3000 = 22 LBS. (9.98 Kg) Form No. 103525 Operating Instructions for: HS2000 HS3000 HYDRAULIC SPREADER Max. Pressure: 10,000 PSI (700 BAR) Unit Weight: HS2000 = 4.8 LBS. (2.17 Kg) HS3000 = 22 LBS. (9.98 Kg) Definition: Hydraulic

More information

Vehicle Maintenance Bulletin

Vehicle Maintenance Bulletin .T.P00 T.P. 50 Vehicle Maintenance Bulletin UNITED STATES POSTAL SERVICE VEHICLE MAINTENANCE LLV FRAME INSPECTION I. Introduction The service life of approximately 142,000 Long Life Vehicles (LLVs) has

More information

of Fire Pump Assemblies

of Fire Pump Assemblies A.1.0 A.1.1 A.2.0 A.2.1 A.2.2 A.2.3 A.2.4 A.2.5 A.2.6 A.3.0 A.3.1 A.4.0 A.4.1 Report of Inspection, Testing & Maintenance System in service before conducting tasks Pertinent parties notified before conducting

More information

Southern Star Central Gas Pipeline Contractor Covered Task List Last updated 8/15/2018

Southern Star Central Gas Pipeline Contractor Covered Task List Last updated 8/15/2018 007 Operate Valves 008 Measurement of Wall Thickness with Ultrasonic Device 018 Inspect Navigable Waterway Crossing 195.412(b) 201 Abnormal Operating Conditions Related to Welding on Pipelines 192.225

More information

OVERALL INSPECTION AND INTEGRITY ASSESSMENT OF OIL AND OIL PRODUCTS STORAGE TANKS R.S.

OVERALL INSPECTION AND INTEGRITY ASSESSMENT OF OIL AND OIL PRODUCTS STORAGE TANKS R.S. OVERALL INSPECTION AND INTEGRITY ASSESSMENT OF OIL AND OIL PRODUCTS STORAGE TANKS R.S. Gaspariants., G.A. Giller (JSC VNIIST, RUSSIA) L.Y. Mogilner., Y.Y. Semin (CJSC VNIIST-Diagnostika, RUSSIA) Steel

More information

Volume 1 Series 2200 Specification for Road Works. Clause Title Page

Volume 1 Series 2200 Specification for Road Works. Clause Title Page PARAPETS Contents Clause Title Page 2201 General... 2 2202 Vehicle... 2 2203 Anchorages and Attachment Systems for Vehicle... 2 2204 Amendments and Additions to BS 6779... 3 2205 Protection Against Corrosion...

More information

Maintenance Manual 6-INCH INTERNAL VALVE F620 SERIES

Maintenance Manual 6-INCH INTERNAL VALVE F620 SERIES Maintenance Manual 6-INCH INTERNAL VALVE F620 SERIES REVISION 1.1 03/15/2002 LIST OF EFFECTIVE PAGES On a revised page, the portion of text or illustrations affected by the change is indicated by a vertical

More information

NYL Resilient Seated Butterfly Valves Operation and Maintenance Instructions

NYL Resilient Seated Butterfly Valves Operation and Maintenance Instructions COMMERCIAL Bray Controls Commercial Division 13788 West Road, Suite 200A Houston, Texas 77041 BCDSales@Bray.com Phone: 1-888-412-2729 Fax: 1-888-412-2720 www.braycommercialdivision.com NYL Resilient Seated

More information

Hydro Plant Risk Assessment Guide

Hydro Plant Risk Assessment Guide September 2006 Hydro Plant Risk Assessment Guide Appendix E8: Battery Condition Assessment E8.1 GENERAL Plant or station batteries are key components in hydroelectric powerplants and are appropriate for

More information

Demand Better From Your Cartridge Dust Collector By Gary Berwick, P.Eng. Quality Air Management Corp. Published November, 2006

Demand Better From Your Cartridge Dust Collector By Gary Berwick, P.Eng. Quality Air Management Corp. Published November, 2006 Demand Better From Your Cartridge Dust Collector By Gary Berwick, P.Eng. Quality Air Management Corp. Published November, 2006 Early Development The cartridge dust collector was a response to the flawed

More information

Load Cell Troubleshooting

Load Cell Troubleshooting VPG TRANSDUCERS Load Cells Application Note VPG-08 Scope Load cells are designed to sense force or weight under a wide range of adverse conditions; they are not only the most essential part of an electronic

More information

Report of Inspection

Report of Inspection P. O. Box 8238 Searcy, AR 72145 866.811.5237 / 501.279.1166 Fax: 501.279.1225 As required by NFPA 1911 19.3: CFS Inspections is accredited to the requirements of ISO/IEC 17020. Report of Inspection SAFET

More information

Nic Mason Technical Services Manager Kuwait Petroleum International Aviation Company

Nic Mason Technical Services Manager Kuwait Petroleum International Aviation Company Nic Mason Technical Services Manager Kuwait Petroleum International Aviation Company EI 1584 Hydrant pit valves and couplers EI 1529 Aircraft Fuelling Hoses EI 1584 Third Edition EI 1584 Third Edition

More information

VP, Facilities and Construction Management

VP, Facilities and Construction Management Title: Effective Date: November 2005 Revision Date: January 12, 2017 Issuing Authority: Responsible Officer: VP, Facilities and Construction Management Director Environmental Health and Safety PURPOSE

More information

INSTALLATION GUIDELINE -SARAN VAPOR RETARDER FILM AND SARAN VAPOR RETARDER TAPE ITW INSULATION SYSTEMS

INSTALLATION GUIDELINE -SARAN VAPOR RETARDER FILM AND SARAN VAPOR RETARDER TAPE ITW INSULATION SYSTEMS INSTALLATION GUIDELINE -SARAN VAPOR RETARDER FILM AND SARAN VAPOR RETARDER TAPE ITW INSULATION SYSTEMS 1 SCOPE SARAN FILM AND SARAN TAPE APPLIED AS A VAPOR RETARDER ON MECHANICAL INSULATION SYSTEMS 1.1

More information

Cleaning of Heavy Duty Air Filter Elements for Re-Use and Remanufacturing Elements

Cleaning of Heavy Duty Air Filter Elements for Re-Use and Remanufacturing Elements Technical Service Bulletin 89-4R2 Cleaning of Heavy Duty Air Filter Elements for Re-Use and Remanufacturing Elements Cleaning of Heavy Duty Air Filters Some vehicle owners and maintenance supervisors,

More information

The FRACOF Composite Slab Test

The FRACOF Composite Slab Test The FRACOF Composite Slab Test Experiment, Predictions & Results Anthony Abu & Ian Burgess Fire Resistance Assessment of partially protected COmposite Floors - FRACOF Introduction To increase the use of

More information

BUREAU OF STANDARDS. Effective Date: 8/19/2016 Section No. 4. Version: 1.2 Procedure No. 3

BUREAU OF STANDARDS. Effective Date: 8/19/2016 Section No. 4. Version: 1.2 Procedure No. 3 BUREAU OF STANDARDS Effective Date: 8/19/2016 Section No. 4 Version: 1.2 Procedure No. 3 TITLE: LP Gas Bulk Plant Final Inspection PURPOSE: This document details the procedures used to conduct a Final

More information

APPENDIX G. Towing Survey for Concrete Floats

APPENDIX G. Towing Survey for Concrete Floats APPENDIX G Towing Survey for Concrete Floats June 3, 2016 Our File # V 16/039 Trip in Tow Survey Of Concrete Floats For Vancouver Pile Driving Ltd. Report of survey undertaken March 8, 2010 review for

More information

MK Series - High Performance Butterfly Valves Operation and Maintenance Instructions

MK Series - High Performance Butterfly Valves Operation and Maintenance Instructions COMMERCIAL Bray Controls Commercial Division 13788 West Road, Suite 200A Houston, Texas 77041 BCDSales@Bray.com Phone: 1-888-412-2729 Fax: 1-888-412-2720 www.braycommercialdivision.com MK Series - High

More information

15/ Reconstruction and protection of tanks

15/ Reconstruction and protection of tanks 15/ Reconstruction and protection of tanks Tanks are containers, usually steel or concrete, used for storing different materials. They can be divided into: storage tanks, pressure tanks (used for storing

More information

Final Report. LED Streetlights Market Assessment Study

Final Report. LED Streetlights Market Assessment Study Final Report LED Streetlights Market Assessment Study October 16, 2015 Final Report LED Streetlights Market Assessment Study October 16, 2015 Funded By: Prepared By: Research Into Action, Inc. www.researchintoaction.com

More information

Yukon Oil Inspection Survey Results and Recommendations

Yukon Oil Inspection Survey Results and Recommendations Yukon Oil Inspection Survey Results and Recommendations CSA B139-04 Installation Code for Oil-Burning Equipment 1 Agenda 1. Inspection Survey Results 2. Solutions to the problems identified Your participation

More information

EVALUATION OF THE 200,000 GALLON ELEVATED SINGLE PEDESTAL SPHEROID SPECKS RUN ROAD (RIDGEWAY) TANK BUNKER HILL, WEST VIRGINIA

EVALUATION OF THE 200,000 GALLON ELEVATED SINGLE PEDESTAL SPHEROID SPECKS RUN ROAD (RIDGEWAY) TANK BUNKER HILL, WEST VIRGINIA EVALUATION OF THE 200,000 GALLON ELEVATED SINGLE PEDESTAL SPHEROID SPECKS RUN ROAD (RIDGEWAY) TANK BUNKER HILL, WEST VIRGINIA FOR DEWBERRY CONSULTANTS, LLC FAIRFAX, VIRGINIA November 9 and 10, 2016 Page

More information

STANDARD PRACTICE INSTRUCTION

STANDARD PRACTICE INSTRUCTION STANDARD PRACTICE INSTRUCTION DATE: March 1, 2010 SUBJECT: Ladder Safety Program. REGULATORY STANDARD: 29 CFR 1910.25 Portable Wood Ladders. 29 CFR 1910.26 Portable Metal Ladders. 29 CFR 1926.1052-1060

More information

Nurse Tank Inspection Report Instructions (DOT-SP Special Permit)

Nurse Tank Inspection Report Instructions (DOT-SP Special Permit) Nurse Tank Inspection Report Instructions (DOT-SP 13554 Special Permit) Following numbers correspond to each box on the Nurse Tank Inspection Report form. 1. PREVIOUS NTIP NUMBER Insert the previous NTIP

More information

Dupont Circle Station - Escalator A03S01 (South Entrance) Assessment Checklist

Dupont Circle Station - Escalator A03S01 (South Entrance) Assessment Checklist Dupont Circle Station - Escalator A03S01 (South Entrance) Assessment Checklist 143 Dupont Circle Station - Escalator A03S02 (South Entrance) Dupont Circle Station Escalator A03S02 (South Entrance) Escalator

More information

Tank Lining Service. For a quote & FREE site survey call to speak to our specialist team.

Tank Lining Service. For a quote & FREE site survey call to speak to our specialist team. Tank Lining Service Tank Lining Service 2 Frequently Asked Questions 3-4 Tank Problems 5 Health and Safety 6 Other 7 Sectional Braithwaite water storage tank. Process water tanks. Caustic acid bund and

More information

LONG TERM LIFE CYCLE EVALUATION OF TAYLOR DEVICES PRODUCTS

LONG TERM LIFE CYCLE EVALUATION OF TAYLOR DEVICES PRODUCTS 15 JANUARY 1993 REV 20 JANUARY 2000 REV 7 JULY 2017 LONG TERM LIFE CYCLE EVALUATION OF TAYLOR DEVICES PRODUCTS The purpose of this report is to study the long-term effect of environmental influences of

More information

NZQA Expiring unit standard version 2 Page 1 of 5. Perform minor servicing tasks on a petrol fuel system

NZQA Expiring unit standard version 2 Page 1 of 5. Perform minor servicing tasks on a petrol fuel system Page 1 of 5 Title Perform minor servicing tasks on a petrol fuel system Level 2 Credits 2 Purpose This unit standard is for people who wish to enter or are employed in the automotive repair industry. People

More information

ANNEX 3 / APPENDIX 10 EUROPEAN VISUAL INSPECTION CATALOGUE (EVIC) FOR WHEELSETS

ANNEX 3 / APPENDIX 10 EUROPEAN VISUAL INSPECTION CATALOGUE (EVIC) FOR WHEELSETS GENERAL CONTRACT OF USE FOR WAGONS APPENDIX 10 ANNEX 3 ANNEX 3 / APPENDIX 10 EUROPEAN VISUAL INSPECTION CATALOGUE (EVIC) FOR WHEELSETS Notice In comparison with the previous version, from this version,

More information

Product Code * Mammoth800

Product Code * Mammoth800 X T R E M E P O L I H I N G Y T E M M A M M O T H F L O O R G R I N D I N G M A C H I N E Product Code * Mammoth800 2200 NW 32ND T. POMPANO BEACH, FL 33069 11 TOLL FREE (800) 659-5843 FAX (954) 933-3473

More information

Case Study Horse Trailer Metallurgical Failure Analysis September 15th, 2003

Case Study Horse Trailer Metallurgical Failure Analysis September 15th, 2003 Case Study Horse Trailer Metallurgical Failure Analysis September 15th, 2003 Background In the summer of 2002 three family members were driving north after dark on US 101 near the central coast of California.

More information

Stack Parking Surface Mounted Stackers

Stack Parking Surface Mounted Stackers / 5 Stack Parking Surface Mounted Stackers swiss-park V- Junior The V- is the ideal machine for low ceiling garages. Its angled platform allows space for parking one car over another in garages where stacked

More information

PROJECTS $500K AND OVER FOR 2014

PROJECTS $500K AND OVER FOR 2014 Page of PROJECTS $00K AND OVER FOR 0 STANDARDIZATION PORTFOLIO Table : Standardization Projects Estimate Estimated Cost Project Title Number ($ Millions) Grounding Compliance Program. Porcelain Insulator

More information

DCP Midstream Contractor Covered Task List Last updated 7/11/2018

DCP Midstream Contractor Covered Task List Last updated 7/11/2018 001 Provide Security for Pipeline Facilities 195.436 Oral 007 Operate Valves 008 Measurement of Wall Thickness with Ultrasonic Device 009 Movement and/or Relocation of Liquid Pipelines 195.424 011 Inspect,

More information

Enbridge Gas Transmission and Midstream and Enbridge Liquid Pipelines (Express-Platte) Contractor Covered Task List Last updated 8/30/2018

Enbridge Gas Transmission and Midstream and Enbridge Liquid Pipelines (Express-Platte) Contractor Covered Task List Last updated 8/30/2018 001 Provide Security for Pipeline Facilities 195.436 Oral 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 Oral

More information

An Urgent Bulletin from CSA Group

An Urgent Bulletin from CSA Group An Urgent Bulletin from CSA Group Occupational Health & Safety Products No. 115 (Replaces Occupational Health & Safety Products No. 92 Ref No. N16-002) Effective Date: July 1, 2019 Date: May 24, 2018 Apply

More information

Maintenance Manual. 4-Inch Internal Valve. F614 Series

Maintenance Manual. 4-Inch Internal Valve. F614 Series 4-Inch Internal Valve F614 Series LIST OF EFFECTIVE PAGES On a revised page, the portion of text or illustrations affected by the change is indicated by a vertical line in the outer margin of the page.

More information

SERVICE BULLETIN SB1250

SERVICE BULLETIN SB1250 SERVICE BULLETIN SB1250 ADDRESSEES SYSTEM COMPONENT BULLETIN TYPE : ABC Customer Care and Parts Source (Other) Owners and operators of coaches listed under Application : Rear Axle Chassis Reinforcement

More information

Incline Lever Row. Use various tools and clamps in process of welding, so you could weld the items together with accuracy.

Incline Lever Row. Use various tools and clamps in process of welding, so you could weld the items together with accuracy. Project: Incline Lever Row Page 1 of 38 Incline Lever Row NOTE: The measurements within this text and 2D documentation are given both in millimeters and inches (in brackets). This website is based on ISO

More information

This ICA is Transport Canada Accepted RECORD OF REVISIONS

This ICA is Transport Canada Accepted RECORD OF REVISIONS CI-06-03 Revision: A Issue Date: May 02, 2003 Print Date: 02/05/03 Page 1 of 5 This ICA is Transport Canada Accepted RECORD OF REVISIONS Revision Effective date for Date of withdrawal of Person making

More information

Performance of Batteries in Grid Connected Energy Storage Systems. June 2018

Performance of Batteries in Grid Connected Energy Storage Systems. June 2018 Performance of Batteries in Grid Connected Energy Storage Systems June 2018 PERFORMANCE OF BATTERIES IN GRID CONNECTED ENERGY STORAGE SYSTEMS Authors Laurie Florence, Principal Engineer, UL LLC Northbrook,

More information

ANNUAL UST SYSTEM INSPECTION CHECKLIST

ANNUAL UST SYSTEM INSPECTION CHECKLIST APPENDIX A-3: SAMPLE FORM FOR ANNUAL UNDERGROUND STORAGE SYSTEM INSPECTION CHECKLIST Page 1 ANNUAL UST SYSTEM INSPECTION CHECKLIST Facility ID# Facility Name/Address Qualified Technician Signature Date

More information

Urea Reactor Height Extension to Increase Capacity

Urea Reactor Height Extension to Increase Capacity Technical Paper June 2014 Urea Reactor Height Extension to Increase Capacity Hermann Kernberger Schoeller-Bleckmann Nitec GmbH (SBN), Austria Bob Edmondson Yara Belle Plaine, Canada Summary A discussion

More information

Dalchully, Laggan PH20 1BU, UK T: +44 (0) E: W:

Dalchully, Laggan PH20 1BU, UK T: +44 (0) E: W: Dalchully, Laggan PH20 1BU, UK T: +44 (0) 1528 544 201 E: angus@adac-structures.co.uk W: www.adac-structures.co.uk Location map for various sites Job name: Condition report into foundations of various

More information

HURRICANE 300 INSPECTION/MAINTENANCE MANUAL. N7959 BIRCH ROAD IXONIA, WI FAX:

HURRICANE 300 INSPECTION/MAINTENANCE MANUAL. N7959 BIRCH ROAD IXONIA, WI FAX: HURRICANE 300 INSPECTION/MAINTENANCE MANUAL N7959 BIRCH ROAD IXONIA, WI 53036 www.industrialvacuum.com 800-331-4832 FAX: 920-261-11 OPERATION / MAINTENANCE MANUAL HURRICANE 300 INTRODUCTION The Hurricane

More information

Principle Decision by the Central Experience Exchange Circle of the Notified Bodies and the GS Bodies according to the Product Safety Act ZEK

Principle Decision by the Central Experience Exchange Circle of the Notified Bodies and the GS Bodies according to the Product Safety Act ZEK -GB-2017-01: Defining the requirements for a GS mark approval Principle Decision by the Central Experience Exchange Circle of the Notified Bodies and the GS Bodies according to the Product Safety Act about

More information

Fluid Fertilizer Foundation December 10, 2013

Fluid Fertilizer Foundation December 10, 2013 Storage Tank Inspection, Maintenance, and Failure Fluid Fertilizer Foundation December 10, 2013 1 Tank Failure History Storage Tank Failure is as old as storage tank usage http://en.wikipedia.org/wiki/boston_molasses_disaster

More information