EQUIPMENT PERFORMANCE SPILL PREVENTION AND PIPING KEVIN HENDERSON
|
|
- Kristian Welch
- 6 years ago
- Views:
Transcription
1 EQUIPMENT PERFORMANCE SPILL PREVENTION AND PIPING KEVIN HENDERSON 20 th ANNUAL NATIONAL TANKS CONFERENCE March 17-19, 2008 ATLANTA, GEORGIA
2 SPILL BUCKETS: OPW 1 PETRO STOPPING CENTER JACKSON, MS Six 20,000 gallon tanks installed May 1999 One regular tank One premium tank Four diesel tanks all manifolded together Direct and remote fills for all six tanks (12 buckets)
3 Petro Stopping Center Jackson, MS DOUBLE-WALLED TANKS & PIPING Interstitial Monitoring Tanks Hydrostatic Piping Electronic sump sensors - Mechanical leak detectors No indication of any suspected release with the release detection systems utilized by owner/operator (no alarms). Observation wells installed at each corner of the tank bed but not utilized (never checked).
4 Petro Stopping Center Jackson, MS
5 Petro Stopping Center Jackson, MS
6 Inspected in May 2007
7 OPW 1
8 OPW 1
9 OPW 1
10 OPW 1
11 OPW 1
12 OPW 1
13 OPW 1
14 OPW 1
15 OPW 1
16 OPW 1
17 OPW 1
18 Duratuff OPW 1
19 Petro Stopping Center Jackson, MS 4800 Gallons Recovered
20 What s Wrong With This Picture?
21 Ball Float Valves
22 Flex Connectors
23 PIPING: APT XP The Pantry - Flowood, MS STORE REGULAR R-1 R-2 PREMIUM P-1 P Originally piped with Western flex pipe in rigid PVC electrical conduit May R-2 replaced July 2006 by Contractor A because fuel found dripping from conduit into STP sump. R-1, P-1 and P-2 replaced March 2007 by Contractor B.
24 APT - XP
25 APT XP Dispenser Premium
26 APT XP Dispenser 9-10 Premium
27 APT XP Dispenser 9-10 Premium
28 APT XP Dispenser 1-2 Premium
29 APT XP Dispenser 9-10 Premium 28 feet between dispensers 6 inches cut off pipe to get riser lined-up underneath dispenser 9-10 Represents 1.8 % swell rate
30 APT XP R-1 (installed July 2006) and R-2 (installed March 2007) have not significantly swelled. P-1 installed March 2007 has swollen enough to crack shear valve at termination dispenser (1-2) at least once. No length had to be cut off this pipe. P-2 installed March 2007 has swollen significantly: Shear valve at terminating dispenser (9-10) has been broken at least twice. 6 inches cut off the length of this pipe. Shear valve at dispenser cracked at least once.
31 PIPING: UPP EXTRA MURPHY OIL -GREENWOOD, MS Installed October 2005 Passed precision tightness testing Brought into use June 2006 Leak Reported July 2006
32 Leaking Coupling UPP EXTRA Murphy Oil Greenwood, MS Coupling Already Replaced 3rd Coupling Not Leaking (out of picture frame)
33 UPP EXTRA Murphy Oil Greenwood, MS Secondary to Primary Termination Fitting Primary Piping Welding Sockets Coupling Welding Indicators Termination Fitting Leaking Coupling - Note fuel within sockets of welding pins.
34 UPP EXTRA Murphy Oil Greenwood, MS Coupling Pipe Termination Fitting
35
36 PetroTechnik Analysis on reported leakage of fuel through welding pins
37 Analysis of the sample received Pressure test on the sample could not replicate the leak through the welding pins The sample was subjected to X-Ray, and the result highlighted two important facts: Pipe and termination fitting were not fully inserted The assembly was exposed to bending stress during welding
38 Incomplete insertion
39 X-ray: Resistor displacement induced by welding under stress
40 Conclusions The assembly was exposed to external loads and partial insertion of either the pipe or fitting prior and during electrofusion. Both the partial insertion and external loading resulted in the molten material moving into the bore of the welding coupler. Molten material was forced out of the fusion area to form material tongues. This movement of molten material has resulted in unsatisfactory fusion welds. The movement of molten material has also resulted in the exposure of the welding coil. Thus the cause of the assembly failure is due to poor installation with the pipe and fitting not fully inserted squarely and also the assembly exposed to external forces prior to, during and after electrofusion. The x-ray results of the original Murphy sample conclude the original findings that poor installation of pipe and fitting was the cause of the assembly failure.
41 Actioned Review of installation manuals and documentation emphasizing the critical steps Efficiently communicate this information to installers Post the revised installation manual on Murphy Oil s web site Petrotechnik is progressively recertifying contractors in line the Murphy new site build program
42 UPP EXTRA MURPHY OIL - INDIANOLA, MS Installed October 2005 Passing precision tightness test results Inspected May 2007
43 UPP EXTRA Murphy Oil Indianola, MS Premium Sump
44 UPP EXTRA Murphy Oil Indianola, MS Regular Sump
45 UPP EXTRA Murphy Oil Indianola, MS
46 ENVIRON GeoFlex
47 ENVIRON GeoFlex+Plus
48 ENVIRON GeoFlex+Plus
49 KEVIN HENDERSON
ANNUAL UST SYSTEM INSPECTION CHECKLIST
APPENDIX A-3: SAMPLE FORM FOR ANNUAL UNDERGROUND STORAGE SYSTEM INSPECTION CHECKLIST Page 1 ANNUAL UST SYSTEM INSPECTION CHECKLIST Facility ID# Facility Name/Address Qualified Technician Signature Date
More informationFINAL UNDERGROUND STORAGE TANK RULE CHANGES. Heather Peters UST Compliance and Technology Unit
FINAL UNDERGROUND STORAGE TANK RULE CHANGES Heather Peters UST Compliance and Technology Unit Regulation Changes Federal Rule Based Changes Federal Regulations finalized in July 2015 Federal Rules effective
More informationNew UST Installation Inspection Checklist
Nebraska State Fire Marshal Fuels Division - FLST Section 246 South 14 TH Street - Lincoln, NE 68508-1804 (402) 471-9466 New UST Installation Inspection Checklist (Petroleum or Hazardous Substances) Inspection
More informationEZ FIT SYSTEM FLEXIBLE CONNECTORS: SERVICE STATION HARDWARE
SERVICE STATION HARDWARE : EZ FIT SYSTEM By stocking just a few fittings and the right kind of FLEX-ING brand flexible connectors, you can transform your inventory into a versatile offering that s ready
More informationINTEGRITY TESTING OF CONTAINMENT SUMPS AND SPILL BUCKETS PEI RP1200
INTEGRITY TESTING OF CONTAINMENT SUMPS AND SPILL BUCKETS PEI RP1200 Storage Tank Professionals KEVIN HENDERSON CONSULTING, LLC 25 th National Tanks Conference & Expo Phoenix, Arizona September 14-16, 2015
More informationBUREAU OF UNDERGROUND STORAGE TANK REGULATIONS RELEASE PREVENTION SECTION
BUREAU OF UNDERGROUND STORAGE TANK REGULATIONS RELEASE PREVENTION SECTION Page 3 Federal law requires the Division of State Fire Marshal, Bureau of Underground Storage Tank Regulations (BUSTR) to inspect
More informationEPA UST Regulations Update May 22, 2018
EPA UST Regulations Update May 22, 2018 Founded in 1988, Tanknology has grown to become one of the largest testing and inspection service companies in the world. Our fleet of 150 vehicles provides service
More informationUnderground Storage Tank Annual Compliance Inspection (Revised 1/2015)
Colorado Department of Labor and Employment Division of Oil and Public Safety Compliance Section 633 17 th Street, Suite 500 Denver, CO 80202-3610 Phone: 303-318-8525 Fax: 303-318-8518 Email: cdle_oil_inspection@state.co.us
More informationP.O. Box 435 Saratoga Springs, NY 12866
Petroleum Storage Equipment Design, Installation & Maintenance September 7, 2016 As a family- and employee-owned business that owns its real estate, Stewart s puts a tremendous investment into our high
More informationCounty of Yolo UNDERGROUND STORAGE TANK PROGRAM INSTALLATION/MODIFICATION/REPAIR APPLICATION
April Meneghetti, REHS Environmental Health Divison Manager County of Yolo DEPARTMENT OF COMMUNITY SERVICES Environmental Health Division 292 West Beamer St., Woodland, CA 95695 PHONE - (530) 666-8646
More informationLorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA
Lorri Grainawi Steel Tank Institute PA NISTM April 25, 2013 Harrisburg, PA PEI/RP1200-12 ------------------------------------------------------ 1. Introduction 2. Definitions 3. Safety 4. Tank Secondary
More informationMonthly Walkthrough Inspections
This form must be used to document the monthly walkthrough inspections. Only complete the sections that apply to your facility. Inspect the applicable items below for your site. If an item is not applicable,
More informationGeneral information about underground storage tank (UST) fueling systems in every day language.
What this document contains: General information about underground storage tank (UST) fueling systems in every day language. What you need to know about Texas Commission on Environmental Quality (TCEQ)
More informationNorth Carolina Department of Environment and Natural Resources Division of Waste Management Underground Storage Tank Section
North Carolina Department of Environment and Natural Resources Division of Waste Management Underground Storage Tank Section To discover a release before a major contamination incident occurs Required
More information(Please type or use black ink)
(Please type or use black ink) PNIPUG ALABAMA DEPARTMENT OF ENVIRONMENTAL MANAGEMENT NOTICE OF PROPOSED UST NEW INSTALLATION OR UPGRADE (Use a separate form for each separate place of operation) Date of
More informationUST Compliance Assistance Handbook
UST Compliance Assistance Handbook O N E I D A E N V I R O N E N T A L, H E A L T H A N D S A F E T Y D I V I S I O N Oneida Tribe of Indians of Wisconsin P.O. Box 365 Oneida, WI 54155 Created by the Oneida
More informationNew UST Regulations. What follows are the changes to EPA s regulations that TMS believes impacts you, the owner/operator, the most.
New UST Regulations The long awaited UST regulations were released by the EPA on June 22, 2015 and soon will be published in the Federal Register. The new regulations will go into effect 90 days after
More informationFLEXIBLE CONDUIT SYSTEM
SUBMERSIBLE PUMPING SYSTEMS PIPING & CONTAINMENT SYSTEMS CABLE-TIGHT SYSTEM FLEXIBLE CONDUIT SYSTEM For far too long our industry has relied on old and outdated methods of conveying cables underground
More informationPEI/RP Recommended Practices for the Inspection and Maintenance of UST Systems
PEI/RP900-08 Recommended Practices for the Inspection and Maintenance of UST Systems Recommended Practices for the Inspection and Maintenance of UST Systems CONTENTS Foreword...iii SECTIONS 1. Introduction
More informationOperational Compliance Closure/Release Response/Corrective Action at Underground Storage Tank Facilities
Connecticut Department of Energy and Environmental Protection Operational Compliance Closure/Release Response/Corrective Action at Underground Storage Tank Facilities May 15, 2015 Peter Zack, Assistant
More informationNCDEQ Underground Storage Tank Section
NCDEQ Underground Storage Tank Section Operation And Maintenance Manual Revised 10/30/2015 i Table of Contents CHAPTER 1. INTRODUCTION... 1 A. Why an Operation and Maintenance Manual?... 1 B. Benefits
More informationNew Regs Get Ready for Containment Testing if You Haven t Done So Already!
New Regs Get Ready for Containment Testing if You Haven t Done So Already! Edward S. Kubinsky Jr. CROMPCO, LLC Director of Regulatory Affairs, Training and Certification ed.kubinsky@crompco.com NISTM Conference
More informationHow a UST Site May Become Contaminated -- Even When The Leak Detection is Passing
Release Prevention Through Compliance/Remediation Integration How a UST Site May Become Contaminated -- Even When The Leak Detection is Passing National Tanks Conference Phoenix, AZ September 14, 2015
More informationOverview of Revisions to the Federal Underground Storage Tank (UST) Regulations. Storage Tank Advisory Committee Harrisburg, PA September 1, 2015
Overview of Revisions to the Federal Underground Storage Tank (UST) Regulations Storage Tank Advisory Committee Harrisburg, PA September 1, 2015 Why is EPA making changes to the UST regulations? The Energy
More informationApplication for Permit to Install Underground Storage Tanks (Petroleum or Hazardous Substances) 1. Owner Information 2. Installation Site Information
Papillion/La Vista Fire Marshal s Office Fuels Division FLST Section 146 rth Adams Street Papillion, NE 68046 (402) 829-1398 Application for Permit to Install Underground Storage Tanks (Petroleum or Hazardous
More informationADDENDUM NO. #1 ITB # FLORIDA A&M UNIVERSITY (FAMU) FUEL STORAGE TANK INSPECTIONS December 8, 2017
ADDENDUM NO. #1 ITB #0003-2018 FLORIDA A&M UNIVERSITY (FAMU) FUEL STORAGE TANK INSPECTIONS December 8, 2017 ITB Services: Subject: The purpose of this solicitation is to acquire sealed competitive bids
More informationFACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL WHO CAN PERFORM THE TEST
FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL On January 26, 2005, the Maryland Department of the Environment (the Department) implemented, in the Code of Maryland Regulations (COMAR) 26.10,
More informationChanges to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC
Changes to EPA s AST & UST Rules Mott-Smith Consulting Group, LLC Marshall T. Mott-Smith, President Mott-Smith Consulting Group, LLC 111 North Calhoun Street, Tallahassee, FL 32301 marshall@mott-smithconsulting.com
More informationCompliance Strategies and Benefits
Compliance Strategies and Benefits NISTM St. Louis Conference October 17, 2012 Brad Walls Director, Central Division Welcome Agenda Introduction Proposed Revisions to Federal Regulations Best Practices
More informationOKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS
OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS PO BOX 52000 OKC, OK 73152-2000 www.occeweb.com Created on 10/1/2008
More informationChanges to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC
Changes to EPA s AST & UST Rules Mott-Smith Consulting Group, LLC Marshall T. Mott-Smith, President Mott-Smith Consulting Group, LLC 111 North Calhoun Street, Tallahassee, FL 32301 marshall@mott-smithconsulting.com
More informationCompliance Strategies and Benefits. Brian Derge Tanknology Inc. December 6, 2012
Compliance Strategies and Benefits Brian Derge Tanknology Inc. December 6, 2012 Welcome Introduction Tanknology Proposed Revisions to Federal Regulations What we have learned over 15 years of testing Sump
More informationMassachusetts Department of Environmental Protection Underground Storage Tank Program
Massachusetts Department of Environmental Protection Underground Storage Tank Program Tom DeNormandie, Chief Underground Storage Tank and Stage I/II Branch 2016 New England Storage Tank Conference Westborough,
More informationMark S. Morgan, Regulatory Counsel
SUBJECT: ISSUE: PMAA CONTACT: EPA UST Regulations Final UST Rules Mark S. Morgan, Regulatory Counsel mmorgan@pmaa.org DATE: November 16, 2015 U.S. EPA FINAL UNDERGROUND STORAGE TANK REQUIREMENTS: I. BACKGROUND
More informationUST General Requirements Inspection Checklist
UST General Requirements Inspection Checklist Inspection Date: Inspector s Name: Facility ID#: I. Ownership of s II. Location of s Owner's Name (Corporation, Individual, Public Agency, or other entity):
More informationTest Date: 3/30/2018 Order Number: Dear Regulator, Enclosed are the results of recent testing performed at the following facility:
11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 4/17/2018 STATE OF NEW HAMPSHIRE-DES HARDING SCHOFIELD Upload to website https://www2.des.state.nh.us/onestopdataproviders/deslogin.aspx
More information6. Tanks - Leak Detection. NCDENR Division of Waste Management Underground Storage Tank Section
6. Tanks - Leak Detection NCDENR Division of Waste Management Underground Storage Tank Section Why conduct Leak Detection? Required for regulated systems: EXCEPTIONS: Temporarily closed tanks Emergency
More informationInspector's Initials: Tank Owner or Agent Signature: Title: Date:
STATE OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION DIVISION OF UNDERGROUND STORAGE TANKS 4 TH Floor, L & C Tower 401 Church Street Nashville, TN 37243-1541 UST OPERATIONS INSPECTION Mo /Day
More informationUnderstanding the Colorado Annual Compliance Package. William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety
Understanding the Colorado Annual Compliance Package William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety Overview Required Documentation: UST / AST Annual Compliance Package Release
More informationDEFENDER SERIES. 5 Gallon, Double Walled, Field Replaceable Spill Container Model Series INSTALLATION, OPERATION, & MAINTENANCE
DEFENDER SERIES 5 Gallon, Double Walled, Field Replaceable Spill Container Model 705-550 Series INSTALLATION, OPERATION, & MAINTENANCE Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel:
More informationRecommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at UST Facilities
PEI/RP1200-17 Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at UST Facilities Inside Front Cover This page is intentionally
More informationStage I Vapor Recovery Testing
Stage I Vapor Recovery Testing Results of Testing for NESHAP Regulations 40CFR63 Part CCCCCC ASTSWMO Conference March 2, 2011 Brad Hoffman Outline Overview of NESHAP Regulation and Equipment Requirements
More informationQuestions And Answers About The 2015 Underground Storage Tank Regulation As Of May 2017
Questions And Answers About The 2015 Underground Storage Tank Regulation As Of May 2017 The questions and answers below provide information about the 2015 federal underground storage tank (UST) regulation.
More informationOperating And Maintaining Underground Storage Tank Systems UPDATED Practical Help And Checklists. Printed on Recycled Paper
UPDATED 2016 Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists EPA 510-K-16-001 Printed on Recycled Paper EPA wrote this booklet for owners and operators of underground
More informationCONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR
Environmental Health - UST Program CONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR As part of our inter-local contract with the Nevada Division of Environmental
More informationOhio Department of Commerce, Division of State Fire Marshal, BUSTR Performing Work on Existing UST Systems June 6, 2012
The Regulatory History of Double Wall Tanks, Piping and Containments On May 16, 2011, the Division of State Fire Marshal, Bureau of Underground Storage Tank Regulations (BR) amended several regulations
More information2018 UST Regulation Revision Comment Worksheet
Comment # Commenter Section Comment DEM Response 1 Overall NECSEMA requests that UST system compliance or installation testing that results in an inconclusive finding be given period of time for investigation
More informationElectronic Line Leak Detectors
Manual No: 577013-465 Revision: W Electronic Line Leak Detectors Application Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied
More informationUnderground Oil Storage Tanks Annual Inspection Report
Underground Oil Storage Tanks Annual Inspection Report Rev 3/26/2018 Form Instructions To Installers and Inspectors: This electronic document (the overall workbook and each individual inspection worksheet)
More informationProvide the following information: Site Address: City: Zip: Project Contact Name: Phone No.: ( ) ext.
UNDERGROUND STORAGE TANK SYSTEM INSTALLATION/UPGRADE SUPPLEMENT For use by Unidocs Member Agencies or where approved by your Local Jurisdiction Authority Cited: California Fire (CFC); Chapter 6.7, Health
More informationChanges to Chapter , Florida Administrative Code Underground Storage Tank Systems (USTs) Effective 1/11/2017
Changes to Chapter 62-761, Florida Administrative Code Underground Storage Tank Systems (USTs) Effective 1/11/2017 Rule Organization The rule sections are reorganized a bit with separate sections now for:
More informationOverview of an Underground Storage Tank Inspection
Overview of an Underground Storage Tank Inspection PURPOSE OF INSPECTION Protect drinking water, lakes, streams, etc. Education. Protect property value. TECHNICAL ASSISTANCE INSPECTIONS Technical Assistance
More informationFrequent Mishaps and Solutions with Regulated Underground Storage Tanks in Pennsylvania
Frequent Mishaps and Solutions with Regulated Underground Storage Tanks in Pennsylvania NISTM 6 th Annual Pennsylvania Storage Tank Conference April 9, 2015 Presented by: Randy Martin Solid Waste Program
More informationNew Tank Installations. Peter Rollo
New Tank Installations Peter Rollo New Tank Installations What tanks are regulated? All tanks with a capacity greater than 1,100 gallons Commercial tanks, other than heating fuel tanks, with a capacity
More information401 KAR 42:020. UST systems: design, construction, installation, and registration.
401 KAR 42:020. UST systems: design, construction, installation, and registration. RELATES TO: KRS 224.01, 224.10, 224.60, Chapter 322, Chapter 322A, 40 C.F.R. Part 280 Subpart B 42 U.S.C. 6991c, 6991e,
More informationUPP Polyethylene Dispenser Sump
UPP Polyethylene Dispenser Sump For Standard and Ribbed sump models DS2111, 4111, 3017, 4417, 3617 and 3915 Installation Guide Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608
More informationLOW LEVEL SUMP TESTING ORIGINS
LOW LEVEL SUMP TESTING ORIGINS Bruce Garrett Volta Oil Company/Dependable Petroleum Service One Roberts Road Plymouth, MA 02360 508-747-6238 bgarrett@dependablecompany.com Who is PMAA PMAA member associations
More informationKWA. Evaluation of the Vaporless Manufacturing LD 3000 and LD 3000S Mechanical Line Leak Detector on Large Rigid and Flexible Pipelines.
Evaluation of the Vaporless Manufacturing LD 3000 and LD 3000S Mechanical Line Leak Detector on Large Rigid and Flexible Pipelines (Addendum to the August 20, 1993 Evaluation of the Vaporless LD 3000 and
More informationSemiannual Report Of UST Performance Measures End Of Fiscal Year 2018 (October 1, 2017 September 30, 2018)
Semiannual Report Of UST Performance Measures End Of Fiscal Year 208 (October, 207 September 30, 208) Where does EPA get the performance data? Twice each year, EPA collects data from states and territories
More informationEarthsafe Systems, Inc. Emergency Power Fuel Systems Recommended System Standard
Copyright 2008 Earthsafe Systems, Inc. This information is provided to consulting engineers and prospective customers for the purpose of specifying Earthsafe Emergency Power Fuel Systems. Reproduction
More informationThis handbook is provided as a general guide. https://floridadep.gov/waste/permitting-compliance- assistance/content/storage-tank-compliance
This handbook is provided as a general guide. For specific regulatory requirements refer to the underground and aboveground storage tank systems rules (Chapters 62-761 and 62-762, Florida Administrative
More informationINSTALLATION, OPERATION, SERVICE & REPAIR PARTS MANUAL FOR
INSTALLATION, OPERATION, SERVICE & REPAIR PARTS MANUAL FOR RED JACKET Extracta Remote Gasoline Pumps Models P75S17-3, P150S17-3 & X4P150S17 380 Volt, 3 Phase, 50 Hertz by 051-138 Rev. C ELECTRICAL SERVICE
More informationHow to Stop Spill Buckets from Draining You Dry
How to Stop Spill Buckets from Draining You Dry Presented by: Dan Crawford, P.G. Murphy USA, Inc. Kenneth Earnest, P.G. Kadence Consultants, Inc. Introduction Based on a review of the most recent underground
More informationLARGE DIAMETER ELECTROFUSION COUPLERS
JILIN SONG JIANG SMART JOINT CO.,LTD www.smartjoint.net sales@smartjoint.net Tel: 0086-432-66976665 Fax: 0086-432-66976664 LARGE DIAMETER ELECTROFUSION COUPLERS METRIC SIZE UP TO 1000MM ASTM SIZE UP TO
More informationFocus on the engineering & permitting requirements for installing a new fuel facility at the Port of Olympia;
Port of Olympia Marine Fueling Station Project Fuel Dock Design Overview KPFF Consulting Engineers April 8, 2015 Fueling Station ti Feasibility Analysis Focus on the engineering & permitting requirements
More informationSPCC Regulation Integrity and Leak Testing Methods
SPCC Regulation Integrity and Leak Testing Methods NISTM New England December 3 rd, 2015 Founded in 1988, Tanknology has grown to become one of the largest testing and inspection service companies in the
More information(Addendum to the March 1994 Evaluation) March 11, 1999
Evaluation of the Red Jacket Fx1DV and Fx2DV Installed in the Big-Flo Diaphragm Valve (BFDV) for Hourly Testing on Flexible Pipelines Containing Diesel Fuel (Addendum to the March 1994 Evaluation) PREPARED
More informationUPP Semi-Rigid Pipework System
UPP Semi-Rigid Pipework System Since being introduced as the world s first electrofusion pipework system for fuel applications over thirty years ago, UPP brand semi-rigid pipework has become known globally
More informationEDS Ball Valves 101. Concerns about debris, damage, interstitial
EDS Ball Valves 101 Concerns about debris, damage, interstitial cavity contamination, and leakage relative to Effluent Decontamination System application of a ball valve vertically subpositioned in the
More informationPreventing Leaks and Spills at Service Stations. A Guide for Facilities
Preventing Leaks and Spills at Service Stations A Guide for Facilities United States Environmental Protection Agency Pacific Southwest/Region 9 EPA-909-K-03-001/October 2003 Contents Underground Storage
More informationOPW Installation and Maintenance Instructions OPW Series Primary and Secondary Bucket Replacement Instructions
OPW Installation and Maintenance Instructions OPW 1-3100 Series Primary and Secondary Bucket Replacement Instructions IMPORTANT: Please read these warnings and follow the assembly instructions completely
More informationWhat you need to know to be EPA compliant by the Oct. 13, 2018, deadline.
OPW GUIDE TO 018 EPA REGULATIONS What you need to know to be EPA compliant by the Oct. 1, 018, deadline. Oct. 1, 018, looms as a significant date for Retail Fueling operators in the United States. That
More informationUnderground Storage Tank. City of Burbank UST Owners & Operators
Underground Storage Tank City of Burbank UST Owners & Operators Created by: Kern County Environmental Health CUPA, Edited by: Burbank Fire Department for the Burbank Fire Department s use Burbank Fire
More informationPRODUCT CATALOGUE FRANKLIN FUELING SYSTEMS PIPING & CONTAINMENT SYSTEMS SERVICE STATION HARDWARE
PRODUCT CATALOGUE FRANKLIN FUELING SYSTEMS PIPING & CONTAINMENT SYSTEMS SERVICE STATION HARDWARE 1 TABLE OF CONTENTS ABOUT US 5 Total System Solution 6 Pipe & Containment 8 Semi-Rigid Pipework System
More information2016 PRICE LIST TOTAL SYSTEM SOLUTIONS
2016 PRICE LIST TOTAL SYSTEM SOLUTIONS Effective February 1, 2016 Submersible Pumping Systems 1 Submersible Turbine Pumps 1 Variable Speed Submersible Turbine Pumps 1 Intelligent Submersible Turbine Pumps
More informationTypical Install Instructions
Typical Install Instructions Read & understand all steps of these instructions before beginning this installation. WEBER Conversion Kit, VW T-1/2, up to 1835cc 32 / 36 DFEV Weber Carburetor These instructions
More informationSECTION VEHICLE FUEL DISPENSING EQUIPMENT
SECTION 23 10 13 PART 1 GENERAL 1.01 SUMMARY A. Provide vehicle fuel storage and dispensing equipment, including but not necessarily limited to: 1. Two compartment above ground gasoline and diesel tank.
More informationDefender Series. Overfill Prevention Valve. Automatic Shutoff for USTs. Installation, Operation and Maintenance Series
Defender Series Overfill Prevention Valve Automatic Shutoff for USTs Installation, Operation and Maintenance 708-590 Series For use in 4" gravity-fill applications only 25-370 Gallons per Minute flow Compatible
More informationReport for CSP Joint Venture Click to edit Master text styles Second level Third level. Fifth level
Report for CSP Joint Venture Click to edit Master text styles Second level Third level Out of service examination, ultrasonic thickness Fourth survey and level paint evaluation for tanks T221 & T222 Fifth
More informationUST Compliance Review
UST Compliance Review Certificate Dispenser Card Reader Annular probe Spill bucket Fill pipe Tank sump Veeder Root Line Files Tank probe Dispenser sump Note: pumps are either submersible (in tank) or suction
More informationManagement of Underground Storage Tanks
Management of Underground Storage Tanks Course No: C03-049 Credit: 3 PDH Mark Rossow, PhD, PE, Retired Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800
More informationIntroduction. Lubrication Related Failures. Gear Couplings. Failure Analysis All Types (Page 1 of 7)
All Types (Page 1 of 7) Introduction A gear coupling serves as a mechanical device which connects shafts of two separate machines and accommodates small amounts of shaft misalignment. Commercial gear couplings
More informationSTP-MLD. Installation and Owner s Manual
The Leader in Submersible Technology Mechanical Leak Detector STP-MLD STP-MLD-D STP-MLD-E Gasoline Diesel Flexible Pipe STP-MLD STP-MLD Installation and Owner s Manual 4805 Voges Rd., P.O. Box 139 McFarland,
More informationPipe & Re-Pipe A Perspective from Florida. R. Steven Miller Project Manager Downstream Data Corporation
Pipe & Re-Pipe A Perspective from Florida R. Steven Miller Project Manager Downstream Data Corporation Presented By Ernest M. Roggelin Pinellas CHD - Engineering Perspective on Florida 2009 D/W construction
More informationLarge Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC
Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC One of the most frequently quoted studies related to electric motor reliability
More informationB-8000/9000 D-AB DOUBLE WALL
B-8000/9000 D-AB DOUBLE WALL UDC INSTALLATION INSTRUCTIONS FOR HYDROSTATIC AND VACUUM MONITORING B-8000-D-AB REQUIRED TOOLS (NOT PROVIDED) Power/air Sanders. Acetone to clean up tools/applicators. Power
More informationFeatures of the FAFNIR technology
VISY-Stick The level and environmental sensor based on the magnetostrictive measuring principle VISY-Stick is a level and environmental sensor that has been specially designed to offer highprecision volume
More informationExecutive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer. Exhibit 2 System Specifications
Executive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer Exhibit 2 System Specifications This exhibit contains the installation, maintenance and compliance standards and specifications
More informationBlack Hills Energy Contractor Covered Task List Last updated 10/10/2018
007 Operate Valves 103 Non-destructive Testing (Other than testing of welds) -- Mag Particle 201 Abnormal Operating Conditions Related to Welding on Pipelines 195.452(h) 192.225 192.227 192.715 192.717
More information40 CFR 63, Subpart CCCCCC
0 CFR 3, Subpart CCCCCC The Unmatched Solution to Meeting U.S. EPA National Emissions Standards for New National Emission Standards have gone into effect for Hazardous Air Pollutants at Gasoline-Dispensing
More informationGeneral Issues of Line Leak Detection
Quality Petroleum Equipment Solutions for Over 20 Years ARM-4073 AST-4010 AST-4012 CFOSI FST-200 ISM-4080 ISM-4081 ISM-4080 MC LD-2000 LD-2000\E LD-2200 LD-2200\75 LD-3000 LD-3000\E LD-3000\FL LDT-890
More informationGeomembrane Test Methods
Appendix 2 Geomembrane Test Methods AMERICAN SOCIETY FOR TESTING AND MATERIALS (arranged by number) ASTM D-5 ASTM D-36 ASTM D-256 ASTM D-412 ASTM D-413 ASTM D-471 ASTM D-570 ASTM D-638 ASTM D-696 ASTM
More informationFranklin Fueling Systems
Franklin Fueling Systems SOLUTIONS YOU CAN TRU S T CATALOG Table of Contents Franklin Fueling Systems has contributed many innovative product designs to the petroleum industry, including the highest performing
More informationSubmersible Pumping Systems. Product Catalog
Submersible Pumping Systems Product Catalog SUBMERSIBLE PUMPING SYSTEMS Table of Contents Submersible Pumping Systems Franklin Fueling Systems has contributed many innovative product designs to the petroleum
More informationRefuel Systems Fuel Management System Specification Revision RS1.01
Refuel Systems Fuel Management System Specification Revision RS1.01 Part 1 General 1.1 GENERAL.1 Provide a pre-packaged factory assembled fuel management system that provides filtration of stored distillate
More informationChanging Industry. UST Population (Ohio) Number of Tanks. Year 60,000 50,000 40,000 30,000 20,000 10,000
1 Number of Tanks Changing Industry 60,000 UST Population (Ohio) 50,000 40,000 30,000 20,000 10,000 0 Year Source: Ohio Petroleum Underground Storage Tank Release Compensation Board (2010) 2 Changing Industry
More informationSyracuse University Petroleum Bulk Storage Tank Program Manual
Syracuse University Petroleum Bulk Storage Tank Program Manual August 23, 2017 Prepared by: Syracuse University Environmental Health & Safety Services Division of Campus Safety and Emergency Services 029
More informationDispenser Containment Manual. Product Manual * Publication Number: DCM-0001 * Issue Date: 05/27/09 Supercedes: 11/01/07
Dispenser Containment Manual Product Manual * Publication Number: DCM-0001 * Issue Date: 05/27/09 Supercedes: 11/01/07 INDEX 1.0 Introduction 1.1 General Information 1.2 Independent Testing 1.3 Liquid
More informationOperating And Maintaining Underground Storage Tank Systems. Practical Help And Checklists. Printed on Recycled Paper
Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists Printed on Recycled Paper Contents How to Use This Booklet...1 Section 1 Identifying The Equipment At Your UST Facility...3
More informationContact Name: Company Name: Technician Name: Company Address: Company Phone: Company Fax: Address. Technician SSN:
Certification Exam Product Line & Leak Detector Testing COVER SHEET Contact : Company : Technician : Company Address: Company Phone: Company Fax: E-Mail Address Technician SSN: (Last 6 digits - ONLY!)
More information