1 EQUIPMENT PERFORMANCE SPILL PREVENTION AND PIPING KEVIN HENDERSON 20 th ANNUAL NATIONAL TANKS CONFERENCE March 17-19, 2008 ATLANTA, GEORGIA

2 SPILL BUCKETS: OPW 1 PETRO STOPPING CENTER JACKSON, MS Six 20,000 gallon tanks installed May 1999 One regular tank One premium tank Four diesel tanks all manifolded together Direct and remote fills for all six tanks (12 buckets)

3 Petro Stopping Center Jackson, MS DOUBLE-WALLED TANKS & PIPING Interstitial Monitoring Tanks Hydrostatic Piping Electronic sump sensors - Mechanical leak detectors No indication of any suspected release with the release detection systems utilized by owner/operator (no alarms). Observation wells installed at each corner of the tank bed but not utilized (never checked).

4 Petro Stopping Center Jackson, MS

5 Petro Stopping Center Jackson, MS

6 Inspected in May 2007

7 OPW 1

8 OPW 1

9 OPW 1

10 OPW 1

11 OPW 1

12 OPW 1

13 OPW 1

14 OPW 1

15 OPW 1

16 OPW 1

17 OPW 1

18 Duratuff OPW 1

19 Petro Stopping Center Jackson, MS 4800 Gallons Recovered

20 What s Wrong With This Picture?

21 Ball Float Valves

22 Flex Connectors

23 PIPING: APT XP The Pantry - Flowood, MS STORE REGULAR R-1 R-2 PREMIUM P-1 P Originally piped with Western flex pipe in rigid PVC electrical conduit May R-2 replaced July 2006 by Contractor A because fuel found dripping from conduit into STP sump. R-1, P-1 and P-2 replaced March 2007 by Contractor B.

24 APT - XP

25 APT XP Dispenser Premium

26 APT XP Dispenser 9-10 Premium

27 APT XP Dispenser 9-10 Premium

28 APT XP Dispenser 1-2 Premium

29 APT XP Dispenser 9-10 Premium 28 feet between dispensers 6 inches cut off pipe to get riser lined-up underneath dispenser 9-10 Represents 1.8 % swell rate

30 APT XP R-1 (installed July 2006) and R-2 (installed March 2007) have not significantly swelled. P-1 installed March 2007 has swollen enough to crack shear valve at termination dispenser (1-2) at least once. No length had to be cut off this pipe. P-2 installed March 2007 has swollen significantly: Shear valve at terminating dispenser (9-10) has been broken at least twice. 6 inches cut off the length of this pipe. Shear valve at dispenser cracked at least once.

31 PIPING: UPP EXTRA MURPHY OIL -GREENWOOD, MS Installed October 2005 Passed precision tightness testing Brought into use June 2006 Leak Reported July 2006

32 Leaking Coupling UPP EXTRA Murphy Oil Greenwood, MS Coupling Already Replaced 3rd Coupling Not Leaking (out of picture frame)

33 UPP EXTRA Murphy Oil Greenwood, MS Secondary to Primary Termination Fitting Primary Piping Welding Sockets Coupling Welding Indicators Termination Fitting Leaking Coupling - Note fuel within sockets of welding pins.

34 UPP EXTRA Murphy Oil Greenwood, MS Coupling Pipe Termination Fitting

35

36 PetroTechnik Analysis on reported leakage of fuel through welding pins

37 Analysis of the sample received Pressure test on the sample could not replicate the leak through the welding pins The sample was subjected to X-Ray, and the result highlighted two important facts: Pipe and termination fitting were not fully inserted The assembly was exposed to bending stress during welding

38 Incomplete insertion

39 X-ray: Resistor displacement induced by welding under stress

40 Conclusions The assembly was exposed to external loads and partial insertion of either the pipe or fitting prior and during electrofusion. Both the partial insertion and external loading resulted in the molten material moving into the bore of the welding coupler. Molten material was forced out of the fusion area to form material tongues. This movement of molten material has resulted in unsatisfactory fusion welds. The movement of molten material has also resulted in the exposure of the welding coil. Thus the cause of the assembly failure is due to poor installation with the pipe and fitting not fully inserted squarely and also the assembly exposed to external forces prior to, during and after electrofusion. The x-ray results of the original Murphy sample conclude the original findings that poor installation of pipe and fitting was the cause of the assembly failure.

41 Actioned Review of installation manuals and documentation emphasizing the critical steps Efficiently communicate this information to installers Post the revised installation manual on Murphy Oil s web site Petrotechnik is progressively recertifying contractors in line the Murphy new site build program

42 UPP EXTRA MURPHY OIL - INDIANOLA, MS Installed October 2005 Passing precision tightness test results Inspected May 2007

43 UPP EXTRA Murphy Oil Indianola, MS Premium Sump

44 UPP EXTRA Murphy Oil Indianola, MS Regular Sump

45 UPP EXTRA Murphy Oil Indianola, MS

46 ENVIRON GeoFlex

47 ENVIRON GeoFlex+Plus

48 ENVIRON GeoFlex+Plus

49 KEVIN HENDERSON

ANNUAL UST SYSTEM INSPECTION CHECKLIST

ANNUAL UST SYSTEM INSPECTION CHECKLIST APPENDIX A-3: SAMPLE FORM FOR ANNUAL UNDERGROUND STORAGE SYSTEM INSPECTION CHECKLIST Page 1 ANNUAL UST SYSTEM INSPECTION CHECKLIST Facility ID# Facility Name/Address Qualified Technician Signature Date

More information

FINAL UNDERGROUND STORAGE TANK RULE CHANGES. Heather Peters UST Compliance and Technology Unit

FINAL UNDERGROUND STORAGE TANK RULE CHANGES. Heather Peters UST Compliance and Technology Unit FINAL UNDERGROUND STORAGE TANK RULE CHANGES Heather Peters UST Compliance and Technology Unit Regulation Changes Federal Rule Based Changes Federal Regulations finalized in July 2015 Federal Rules effective

More information

New UST Installation Inspection Checklist

New UST Installation Inspection Checklist Nebraska State Fire Marshal Fuels Division - FLST Section 246 South 14 TH Street - Lincoln, NE 68508-1804 (402) 471-9466 New UST Installation Inspection Checklist (Petroleum or Hazardous Substances) Inspection

More information

EZ FIT SYSTEM FLEXIBLE CONNECTORS: SERVICE STATION HARDWARE

EZ FIT SYSTEM FLEXIBLE CONNECTORS: SERVICE STATION HARDWARE SERVICE STATION HARDWARE : EZ FIT SYSTEM By stocking just a few fittings and the right kind of FLEX-ING brand flexible connectors, you can transform your inventory into a versatile offering that s ready

More information

INTEGRITY TESTING OF CONTAINMENT SUMPS AND SPILL BUCKETS PEI RP1200

INTEGRITY TESTING OF CONTAINMENT SUMPS AND SPILL BUCKETS PEI RP1200 INTEGRITY TESTING OF CONTAINMENT SUMPS AND SPILL BUCKETS PEI RP1200 Storage Tank Professionals KEVIN HENDERSON CONSULTING, LLC 25 th National Tanks Conference & Expo Phoenix, Arizona September 14-16, 2015

More information

BUREAU OF UNDERGROUND STORAGE TANK REGULATIONS RELEASE PREVENTION SECTION

BUREAU OF UNDERGROUND STORAGE TANK REGULATIONS RELEASE PREVENTION SECTION BUREAU OF UNDERGROUND STORAGE TANK REGULATIONS RELEASE PREVENTION SECTION Page 3 Federal law requires the Division of State Fire Marshal, Bureau of Underground Storage Tank Regulations (BUSTR) to inspect

More information

EPA UST Regulations Update May 22, 2018

EPA UST Regulations Update May 22, 2018 EPA UST Regulations Update May 22, 2018 Founded in 1988, Tanknology has grown to become one of the largest testing and inspection service companies in the world. Our fleet of 150 vehicles provides service

More information

Underground Storage Tank Annual Compliance Inspection (Revised 1/2015)

Underground Storage Tank Annual Compliance Inspection (Revised 1/2015) Colorado Department of Labor and Employment Division of Oil and Public Safety Compliance Section 633 17 th Street, Suite 500 Denver, CO 80202-3610 Phone: 303-318-8525 Fax: 303-318-8518 Email: cdle_oil_inspection@state.co.us

More information

P.O. Box 435 Saratoga Springs, NY 12866

P.O. Box 435 Saratoga Springs, NY 12866 Petroleum Storage Equipment Design, Installation & Maintenance September 7, 2016 As a family- and employee-owned business that owns its real estate, Stewart s puts a tremendous investment into our high

More information

County of Yolo UNDERGROUND STORAGE TANK PROGRAM INSTALLATION/MODIFICATION/REPAIR APPLICATION

County of Yolo UNDERGROUND STORAGE TANK PROGRAM INSTALLATION/MODIFICATION/REPAIR APPLICATION April Meneghetti, REHS Environmental Health Divison Manager County of Yolo DEPARTMENT OF COMMUNITY SERVICES Environmental Health Division 292 West Beamer St., Woodland, CA 95695 PHONE - (530) 666-8646

More information

Lorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA

Lorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA Lorri Grainawi Steel Tank Institute PA NISTM April 25, 2013 Harrisburg, PA PEI/RP1200-12 ------------------------------------------------------ 1. Introduction 2. Definitions 3. Safety 4. Tank Secondary

More information

Monthly Walkthrough Inspections

Monthly Walkthrough Inspections This form must be used to document the monthly walkthrough inspections. Only complete the sections that apply to your facility. Inspect the applicable items below for your site. If an item is not applicable,

More information

General information about underground storage tank (UST) fueling systems in every day language.

General information about underground storage tank (UST) fueling systems in every day language. What this document contains: General information about underground storage tank (UST) fueling systems in every day language. What you need to know about Texas Commission on Environmental Quality (TCEQ)

More information

North Carolina Department of Environment and Natural Resources Division of Waste Management Underground Storage Tank Section

North Carolina Department of Environment and Natural Resources Division of Waste Management Underground Storage Tank Section North Carolina Department of Environment and Natural Resources Division of Waste Management Underground Storage Tank Section To discover a release before a major contamination incident occurs Required

More information

(Please type or use black ink)

(Please type or use black ink) (Please type or use black ink) PNIPUG ALABAMA DEPARTMENT OF ENVIRONMENTAL MANAGEMENT NOTICE OF PROPOSED UST NEW INSTALLATION OR UPGRADE (Use a separate form for each separate place of operation) Date of

More information

UST Compliance Assistance Handbook

UST Compliance Assistance Handbook UST Compliance Assistance Handbook O N E I D A E N V I R O N E N T A L, H E A L T H A N D S A F E T Y D I V I S I O N Oneida Tribe of Indians of Wisconsin P.O. Box 365 Oneida, WI 54155 Created by the Oneida

More information

New UST Regulations. What follows are the changes to EPA s regulations that TMS believes impacts you, the owner/operator, the most.

New UST Regulations. What follows are the changes to EPA s regulations that TMS believes impacts you, the owner/operator, the most. New UST Regulations The long awaited UST regulations were released by the EPA on June 22, 2015 and soon will be published in the Federal Register. The new regulations will go into effect 90 days after

More information

FLEXIBLE CONDUIT SYSTEM

FLEXIBLE CONDUIT SYSTEM SUBMERSIBLE PUMPING SYSTEMS PIPING & CONTAINMENT SYSTEMS CABLE-TIGHT SYSTEM FLEXIBLE CONDUIT SYSTEM For far too long our industry has relied on old and outdated methods of conveying cables underground

More information

PEI/RP Recommended Practices for the Inspection and Maintenance of UST Systems

PEI/RP Recommended Practices for the Inspection and Maintenance of UST Systems PEI/RP900-08 Recommended Practices for the Inspection and Maintenance of UST Systems Recommended Practices for the Inspection and Maintenance of UST Systems CONTENTS Foreword...iii SECTIONS 1. Introduction

More information

Operational Compliance Closure/Release Response/Corrective Action at Underground Storage Tank Facilities

Operational Compliance Closure/Release Response/Corrective Action at Underground Storage Tank Facilities Connecticut Department of Energy and Environmental Protection Operational Compliance Closure/Release Response/Corrective Action at Underground Storage Tank Facilities May 15, 2015 Peter Zack, Assistant

More information

NCDEQ Underground Storage Tank Section

NCDEQ Underground Storage Tank Section NCDEQ Underground Storage Tank Section Operation And Maintenance Manual Revised 10/30/2015 i Table of Contents CHAPTER 1. INTRODUCTION... 1 A. Why an Operation and Maintenance Manual?... 1 B. Benefits

More information

New Regs Get Ready for Containment Testing if You Haven t Done So Already!

New Regs Get Ready for Containment Testing if You Haven t Done So Already! New Regs Get Ready for Containment Testing if You Haven t Done So Already! Edward S. Kubinsky Jr. CROMPCO, LLC Director of Regulatory Affairs, Training and Certification ed.kubinsky@crompco.com NISTM Conference

More information

How a UST Site May Become Contaminated -- Even When The Leak Detection is Passing

How a UST Site May Become Contaminated -- Even When The Leak Detection is Passing Release Prevention Through Compliance/Remediation Integration How a UST Site May Become Contaminated -- Even When The Leak Detection is Passing National Tanks Conference Phoenix, AZ September 14, 2015

More information

Overview of Revisions to the Federal Underground Storage Tank (UST) Regulations. Storage Tank Advisory Committee Harrisburg, PA September 1, 2015

Overview of Revisions to the Federal Underground Storage Tank (UST) Regulations. Storage Tank Advisory Committee Harrisburg, PA September 1, 2015 Overview of Revisions to the Federal Underground Storage Tank (UST) Regulations Storage Tank Advisory Committee Harrisburg, PA September 1, 2015 Why is EPA making changes to the UST regulations? The Energy

More information

Application for Permit to Install Underground Storage Tanks (Petroleum or Hazardous Substances) 1. Owner Information 2. Installation Site Information

Application for Permit to Install Underground Storage Tanks (Petroleum or Hazardous Substances) 1. Owner Information 2. Installation Site Information Papillion/La Vista Fire Marshal s Office Fuels Division FLST Section 146 rth Adams Street Papillion, NE 68046 (402) 829-1398 Application for Permit to Install Underground Storage Tanks (Petroleum or Hazardous

More information

ADDENDUM NO. #1 ITB # FLORIDA A&M UNIVERSITY (FAMU) FUEL STORAGE TANK INSPECTIONS December 8, 2017

ADDENDUM NO. #1 ITB # FLORIDA A&M UNIVERSITY (FAMU) FUEL STORAGE TANK INSPECTIONS December 8, 2017 ADDENDUM NO. #1 ITB #0003-2018 FLORIDA A&M UNIVERSITY (FAMU) FUEL STORAGE TANK INSPECTIONS December 8, 2017 ITB Services: Subject: The purpose of this solicitation is to acquire sealed competitive bids

More information

FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL WHO CAN PERFORM THE TEST

FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL WHO CAN PERFORM THE TEST FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL On January 26, 2005, the Maryland Department of the Environment (the Department) implemented, in the Code of Maryland Regulations (COMAR) 26.10,

More information

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC Changes to EPA s AST & UST Rules Mott-Smith Consulting Group, LLC Marshall T. Mott-Smith, President Mott-Smith Consulting Group, LLC 111 North Calhoun Street, Tallahassee, FL 32301 marshall@mott-smithconsulting.com

More information

Compliance Strategies and Benefits

Compliance Strategies and Benefits Compliance Strategies and Benefits NISTM St. Louis Conference October 17, 2012 Brad Walls Director, Central Division Welcome Agenda Introduction Proposed Revisions to Federal Regulations Best Practices

More information

OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS

OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS OKLAHOMA CORPORATION COMMISSION PETROLEUM STORAGE TANK DIVISION THE ABC S OF AST S AN OVERVIEW OF ABOVEGROUND STORAGE TANK REQUIREMENTS PO BOX 52000 OKC, OK 73152-2000 www.occeweb.com Created on 10/1/2008

More information

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC

Changes to EPA s AST & UST Rules. Mott-Smith Consulting Group, LLC Changes to EPA s AST & UST Rules Mott-Smith Consulting Group, LLC Marshall T. Mott-Smith, President Mott-Smith Consulting Group, LLC 111 North Calhoun Street, Tallahassee, FL 32301 marshall@mott-smithconsulting.com

More information

Compliance Strategies and Benefits. Brian Derge Tanknology Inc. December 6, 2012

Compliance Strategies and Benefits. Brian Derge Tanknology Inc. December 6, 2012 Compliance Strategies and Benefits Brian Derge Tanknology Inc. December 6, 2012 Welcome Introduction Tanknology Proposed Revisions to Federal Regulations What we have learned over 15 years of testing Sump

More information

Massachusetts Department of Environmental Protection Underground Storage Tank Program

Massachusetts Department of Environmental Protection Underground Storage Tank Program Massachusetts Department of Environmental Protection Underground Storage Tank Program Tom DeNormandie, Chief Underground Storage Tank and Stage I/II Branch 2016 New England Storage Tank Conference Westborough,

More information

Mark S. Morgan, Regulatory Counsel

Mark S. Morgan, Regulatory Counsel SUBJECT: ISSUE: PMAA CONTACT: EPA UST Regulations Final UST Rules Mark S. Morgan, Regulatory Counsel mmorgan@pmaa.org DATE: November 16, 2015 U.S. EPA FINAL UNDERGROUND STORAGE TANK REQUIREMENTS: I. BACKGROUND

More information

UST General Requirements Inspection Checklist

UST General Requirements Inspection Checklist UST General Requirements Inspection Checklist Inspection Date: Inspector s Name: Facility ID#: I. Ownership of s II. Location of s Owner's Name (Corporation, Individual, Public Agency, or other entity):

More information

Test Date: 3/30/2018 Order Number: Dear Regulator, Enclosed are the results of recent testing performed at the following facility:

Test Date: 3/30/2018 Order Number: Dear Regulator, Enclosed are the results of recent testing performed at the following facility: 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 4/17/2018 STATE OF NEW HAMPSHIRE-DES HARDING SCHOFIELD Upload to website https://www2.des.state.nh.us/onestopdataproviders/deslogin.aspx

More information

6. Tanks - Leak Detection. NCDENR Division of Waste Management Underground Storage Tank Section

6. Tanks - Leak Detection. NCDENR Division of Waste Management Underground Storage Tank Section 6. Tanks - Leak Detection NCDENR Division of Waste Management Underground Storage Tank Section Why conduct Leak Detection? Required for regulated systems: EXCEPTIONS: Temporarily closed tanks Emergency

More information

Inspector's Initials: Tank Owner or Agent Signature: Title: Date:

Inspector's Initials: Tank Owner or Agent Signature: Title: Date: STATE OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION DIVISION OF UNDERGROUND STORAGE TANKS 4 TH Floor, L & C Tower 401 Church Street Nashville, TN 37243-1541 UST OPERATIONS INSPECTION Mo /Day

More information

Understanding the Colorado Annual Compliance Package. William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety

Understanding the Colorado Annual Compliance Package. William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety Understanding the Colorado Annual Compliance Package William Holman & Robert Schlegel Inspectors Division of Oil and Public Safety Overview Required Documentation: UST / AST Annual Compliance Package Release

More information

DEFENDER SERIES. 5 Gallon, Double Walled, Field Replaceable Spill Container Model Series INSTALLATION, OPERATION, & MAINTENANCE

DEFENDER SERIES. 5 Gallon, Double Walled, Field Replaceable Spill Container Model Series INSTALLATION, OPERATION, & MAINTENANCE DEFENDER SERIES 5 Gallon, Double Walled, Field Replaceable Spill Container Model 705-550 Series INSTALLATION, OPERATION, & MAINTENANCE Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel:

More information

Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at UST Facilities

Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at UST Facilities PEI/RP1200-17 Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at UST Facilities Inside Front Cover This page is intentionally

More information

Stage I Vapor Recovery Testing

Stage I Vapor Recovery Testing Stage I Vapor Recovery Testing Results of Testing for NESHAP Regulations 40CFR63 Part CCCCCC ASTSWMO Conference March 2, 2011 Brad Hoffman Outline Overview of NESHAP Regulation and Equipment Requirements

More information

Questions And Answers About The 2015 Underground Storage Tank Regulation As Of May 2017

Questions And Answers About The 2015 Underground Storage Tank Regulation As Of May 2017 Questions And Answers About The 2015 Underground Storage Tank Regulation As Of May 2017 The questions and answers below provide information about the 2015 federal underground storage tank (UST) regulation.

More information

Operating And Maintaining Underground Storage Tank Systems UPDATED Practical Help And Checklists. Printed on Recycled Paper

Operating And Maintaining Underground Storage Tank Systems UPDATED Practical Help And Checklists. Printed on Recycled Paper UPDATED 2016 Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists EPA 510-K-16-001 Printed on Recycled Paper EPA wrote this booklet for owners and operators of underground

More information

CONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR

CONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR Environmental Health - UST Program CONTRACTOR S SELF-INSPECTION CHECKLIST for UST INSTALLATION REPLACEMENT UPGRADE RETROFIT REPAIR As part of our inter-local contract with the Nevada Division of Environmental

More information

Ohio Department of Commerce, Division of State Fire Marshal, BUSTR Performing Work on Existing UST Systems June 6, 2012

Ohio Department of Commerce, Division of State Fire Marshal, BUSTR Performing Work on Existing UST Systems June 6, 2012 The Regulatory History of Double Wall Tanks, Piping and Containments On May 16, 2011, the Division of State Fire Marshal, Bureau of Underground Storage Tank Regulations (BR) amended several regulations

More information

2018 UST Regulation Revision Comment Worksheet

2018 UST Regulation Revision Comment Worksheet Comment # Commenter Section Comment DEM Response 1 Overall NECSEMA requests that UST system compliance or installation testing that results in an inconclusive finding be given period of time for investigation

More information

Electronic Line Leak Detectors

Electronic Line Leak Detectors Manual No: 577013-465 Revision: W Electronic Line Leak Detectors Application Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied

More information

Underground Oil Storage Tanks Annual Inspection Report

Underground Oil Storage Tanks Annual Inspection Report Underground Oil Storage Tanks Annual Inspection Report Rev 3/26/2018 Form Instructions To Installers and Inspectors: This electronic document (the overall workbook and each individual inspection worksheet)

More information

Provide the following information: Site Address: City: Zip: Project Contact Name: Phone No.: ( ) ext.

Provide the following information: Site Address: City: Zip: Project Contact Name: Phone No.: ( ) ext. UNDERGROUND STORAGE TANK SYSTEM INSTALLATION/UPGRADE SUPPLEMENT For use by Unidocs Member Agencies or where approved by your Local Jurisdiction Authority Cited: California Fire (CFC); Chapter 6.7, Health

More information

Changes to Chapter , Florida Administrative Code Underground Storage Tank Systems (USTs) Effective 1/11/2017

Changes to Chapter , Florida Administrative Code Underground Storage Tank Systems (USTs) Effective 1/11/2017 Changes to Chapter 62-761, Florida Administrative Code Underground Storage Tank Systems (USTs) Effective 1/11/2017 Rule Organization The rule sections are reorganized a bit with separate sections now for:

More information

Overview of an Underground Storage Tank Inspection

Overview of an Underground Storage Tank Inspection Overview of an Underground Storage Tank Inspection PURPOSE OF INSPECTION Protect drinking water, lakes, streams, etc. Education. Protect property value. TECHNICAL ASSISTANCE INSPECTIONS Technical Assistance

More information

Frequent Mishaps and Solutions with Regulated Underground Storage Tanks in Pennsylvania

Frequent Mishaps and Solutions with Regulated Underground Storage Tanks in Pennsylvania Frequent Mishaps and Solutions with Regulated Underground Storage Tanks in Pennsylvania NISTM 6 th Annual Pennsylvania Storage Tank Conference April 9, 2015 Presented by: Randy Martin Solid Waste Program

More information

New Tank Installations. Peter Rollo

New Tank Installations. Peter Rollo New Tank Installations Peter Rollo New Tank Installations What tanks are regulated? All tanks with a capacity greater than 1,100 gallons Commercial tanks, other than heating fuel tanks, with a capacity

More information

401 KAR 42:020. UST systems: design, construction, installation, and registration.

401 KAR 42:020. UST systems: design, construction, installation, and registration. 401 KAR 42:020. UST systems: design, construction, installation, and registration. RELATES TO: KRS 224.01, 224.10, 224.60, Chapter 322, Chapter 322A, 40 C.F.R. Part 280 Subpart B 42 U.S.C. 6991c, 6991e,

More information

UPP Polyethylene Dispenser Sump

UPP Polyethylene Dispenser Sump UPP Polyethylene Dispenser Sump For Standard and Ribbed sump models DS2111, 4111, 3017, 4417, 3617 and 3915 Installation Guide Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608

More information

LOW LEVEL SUMP TESTING ORIGINS

LOW LEVEL SUMP TESTING ORIGINS LOW LEVEL SUMP TESTING ORIGINS Bruce Garrett Volta Oil Company/Dependable Petroleum Service One Roberts Road Plymouth, MA 02360 508-747-6238 bgarrett@dependablecompany.com Who is PMAA PMAA member associations

More information

KWA. Evaluation of the Vaporless Manufacturing LD 3000 and LD 3000S Mechanical Line Leak Detector on Large Rigid and Flexible Pipelines.

KWA. Evaluation of the Vaporless Manufacturing LD 3000 and LD 3000S Mechanical Line Leak Detector on Large Rigid and Flexible Pipelines. Evaluation of the Vaporless Manufacturing LD 3000 and LD 3000S Mechanical Line Leak Detector on Large Rigid and Flexible Pipelines (Addendum to the August 20, 1993 Evaluation of the Vaporless LD 3000 and

More information

Semiannual Report Of UST Performance Measures End Of Fiscal Year 2018 (October 1, 2017 September 30, 2018)

Semiannual Report Of UST Performance Measures End Of Fiscal Year 2018 (October 1, 2017 September 30, 2018) Semiannual Report Of UST Performance Measures End Of Fiscal Year 208 (October, 207 September 30, 208) Where does EPA get the performance data? Twice each year, EPA collects data from states and territories

More information

Earthsafe Systems, Inc. Emergency Power Fuel Systems Recommended System Standard

Earthsafe Systems, Inc. Emergency Power Fuel Systems Recommended System Standard Copyright 2008 Earthsafe Systems, Inc. This information is provided to consulting engineers and prospective customers for the purpose of specifying Earthsafe Emergency Power Fuel Systems. Reproduction

More information

This handbook is provided as a general guide. https://floridadep.gov/waste/permitting-compliance- assistance/content/storage-tank-compliance

This handbook is provided as a general guide. https://floridadep.gov/waste/permitting-compliance- assistance/content/storage-tank-compliance This handbook is provided as a general guide. For specific regulatory requirements refer to the underground and aboveground storage tank systems rules (Chapters 62-761 and 62-762, Florida Administrative

More information

INSTALLATION, OPERATION, SERVICE & REPAIR PARTS MANUAL FOR

INSTALLATION, OPERATION, SERVICE & REPAIR PARTS MANUAL FOR INSTALLATION, OPERATION, SERVICE & REPAIR PARTS MANUAL FOR RED JACKET Extracta Remote Gasoline Pumps Models P75S17-3, P150S17-3 & X4P150S17 380 Volt, 3 Phase, 50 Hertz by 051-138 Rev. C ELECTRICAL SERVICE

More information

How to Stop Spill Buckets from Draining You Dry

How to Stop Spill Buckets from Draining You Dry How to Stop Spill Buckets from Draining You Dry Presented by: Dan Crawford, P.G. Murphy USA, Inc. Kenneth Earnest, P.G. Kadence Consultants, Inc. Introduction Based on a review of the most recent underground

More information

LARGE DIAMETER ELECTROFUSION COUPLERS

LARGE DIAMETER ELECTROFUSION COUPLERS JILIN SONG JIANG SMART JOINT CO.,LTD www.smartjoint.net sales@smartjoint.net Tel: 0086-432-66976665 Fax: 0086-432-66976664 LARGE DIAMETER ELECTROFUSION COUPLERS METRIC SIZE UP TO 1000MM ASTM SIZE UP TO

More information

Focus on the engineering & permitting requirements for installing a new fuel facility at the Port of Olympia;

Focus on the engineering & permitting requirements for installing a new fuel facility at the Port of Olympia; Port of Olympia Marine Fueling Station Project Fuel Dock Design Overview KPFF Consulting Engineers April 8, 2015 Fueling Station ti Feasibility Analysis Focus on the engineering & permitting requirements

More information

SPCC Regulation Integrity and Leak Testing Methods

SPCC Regulation Integrity and Leak Testing Methods SPCC Regulation Integrity and Leak Testing Methods NISTM New England December 3 rd, 2015 Founded in 1988, Tanknology has grown to become one of the largest testing and inspection service companies in the

More information

(Addendum to the March 1994 Evaluation) March 11, 1999

(Addendum to the March 1994 Evaluation) March 11, 1999 Evaluation of the Red Jacket Fx1DV and Fx2DV Installed in the Big-Flo Diaphragm Valve (BFDV) for Hourly Testing on Flexible Pipelines Containing Diesel Fuel (Addendum to the March 1994 Evaluation) PREPARED

More information

UPP Semi-Rigid Pipework System

UPP Semi-Rigid Pipework System UPP Semi-Rigid Pipework System Since being introduced as the world s first electrofusion pipework system for fuel applications over thirty years ago, UPP brand semi-rigid pipework has become known globally

More information

EDS Ball Valves 101. Concerns about debris, damage, interstitial

EDS Ball Valves 101. Concerns about debris, damage, interstitial EDS Ball Valves 101 Concerns about debris, damage, interstitial cavity contamination, and leakage relative to Effluent Decontamination System application of a ball valve vertically subpositioned in the

More information

Preventing Leaks and Spills at Service Stations. A Guide for Facilities

Preventing Leaks and Spills at Service Stations. A Guide for Facilities Preventing Leaks and Spills at Service Stations A Guide for Facilities United States Environmental Protection Agency Pacific Southwest/Region 9 EPA-909-K-03-001/October 2003 Contents Underground Storage

More information

OPW Installation and Maintenance Instructions OPW Series Primary and Secondary Bucket Replacement Instructions

OPW Installation and Maintenance Instructions OPW Series Primary and Secondary Bucket Replacement Instructions OPW Installation and Maintenance Instructions OPW 1-3100 Series Primary and Secondary Bucket Replacement Instructions IMPORTANT: Please read these warnings and follow the assembly instructions completely

More information

What you need to know to be EPA compliant by the Oct. 13, 2018, deadline.

What you need to know to be EPA compliant by the Oct. 13, 2018, deadline. OPW GUIDE TO 018 EPA REGULATIONS What you need to know to be EPA compliant by the Oct. 1, 018, deadline. Oct. 1, 018, looms as a significant date for Retail Fueling operators in the United States. That

More information

Underground Storage Tank. City of Burbank UST Owners & Operators

Underground Storage Tank. City of Burbank UST Owners & Operators Underground Storage Tank City of Burbank UST Owners & Operators Created by: Kern County Environmental Health CUPA, Edited by: Burbank Fire Department for the Burbank Fire Department s use Burbank Fire

More information

PRODUCT CATALOGUE FRANKLIN FUELING SYSTEMS PIPING & CONTAINMENT SYSTEMS SERVICE STATION HARDWARE

PRODUCT CATALOGUE FRANKLIN FUELING SYSTEMS PIPING & CONTAINMENT SYSTEMS SERVICE STATION HARDWARE PRODUCT CATALOGUE FRANKLIN FUELING SYSTEMS PIPING & CONTAINMENT SYSTEMS SERVICE STATION HARDWARE 1 TABLE OF CONTENTS ABOUT US 5 Total System Solution 6 Pipe & Containment 8 Semi-Rigid Pipework System

More information

2016 PRICE LIST TOTAL SYSTEM SOLUTIONS

2016 PRICE LIST TOTAL SYSTEM SOLUTIONS 2016 PRICE LIST TOTAL SYSTEM SOLUTIONS Effective February 1, 2016 Submersible Pumping Systems 1 Submersible Turbine Pumps 1 Variable Speed Submersible Turbine Pumps 1 Intelligent Submersible Turbine Pumps

More information

Typical Install Instructions

Typical Install Instructions Typical Install Instructions Read & understand all steps of these instructions before beginning this installation. WEBER Conversion Kit, VW T-1/2, up to 1835cc 32 / 36 DFEV Weber Carburetor These instructions

More information

SECTION VEHICLE FUEL DISPENSING EQUIPMENT

SECTION VEHICLE FUEL DISPENSING EQUIPMENT SECTION 23 10 13 PART 1 GENERAL 1.01 SUMMARY A. Provide vehicle fuel storage and dispensing equipment, including but not necessarily limited to: 1. Two compartment above ground gasoline and diesel tank.

More information

Defender Series. Overfill Prevention Valve. Automatic Shutoff for USTs. Installation, Operation and Maintenance Series

Defender Series. Overfill Prevention Valve. Automatic Shutoff for USTs. Installation, Operation and Maintenance Series Defender Series Overfill Prevention Valve Automatic Shutoff for USTs Installation, Operation and Maintenance 708-590 Series For use in 4" gravity-fill applications only 25-370 Gallons per Minute flow Compatible

More information

Report for CSP Joint Venture Click to edit Master text styles Second level Third level. Fifth level

Report for CSP Joint Venture Click to edit Master text styles Second level Third level. Fifth level Report for CSP Joint Venture Click to edit Master text styles Second level Third level Out of service examination, ultrasonic thickness Fourth survey and level paint evaluation for tanks T221 & T222 Fifth

More information

UST Compliance Review

UST Compliance Review UST Compliance Review Certificate Dispenser Card Reader Annular probe Spill bucket Fill pipe Tank sump Veeder Root Line Files Tank probe Dispenser sump Note: pumps are either submersible (in tank) or suction

More information

Management of Underground Storage Tanks

Management of Underground Storage Tanks Management of Underground Storage Tanks Course No: C03-049 Credit: 3 PDH Mark Rossow, PhD, PE, Retired Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800

More information

Introduction. Lubrication Related Failures. Gear Couplings. Failure Analysis All Types (Page 1 of 7)

Introduction. Lubrication Related Failures. Gear Couplings. Failure Analysis All Types (Page 1 of 7) All Types (Page 1 of 7) Introduction A gear coupling serves as a mechanical device which connects shafts of two separate machines and accommodates small amounts of shaft misalignment. Commercial gear couplings

More information

STP-MLD. Installation and Owner s Manual

STP-MLD. Installation and Owner s Manual The Leader in Submersible Technology Mechanical Leak Detector STP-MLD STP-MLD-D STP-MLD-E Gasoline Diesel Flexible Pipe STP-MLD STP-MLD Installation and Owner s Manual 4805 Voges Rd., P.O. Box 139 McFarland,

More information

Pipe & Re-Pipe A Perspective from Florida. R. Steven Miller Project Manager Downstream Data Corporation

Pipe & Re-Pipe A Perspective from Florida. R. Steven Miller Project Manager Downstream Data Corporation Pipe & Re-Pipe A Perspective from Florida R. Steven Miller Project Manager Downstream Data Corporation Presented By Ernest M. Roggelin Pinellas CHD - Engineering Perspective on Florida 2009 D/W construction

More information

Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC

Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC One of the most frequently quoted studies related to electric motor reliability

More information

B-8000/9000 D-AB DOUBLE WALL

B-8000/9000 D-AB DOUBLE WALL B-8000/9000 D-AB DOUBLE WALL UDC INSTALLATION INSTRUCTIONS FOR HYDROSTATIC AND VACUUM MONITORING B-8000-D-AB REQUIRED TOOLS (NOT PROVIDED) Power/air Sanders. Acetone to clean up tools/applicators. Power

More information

Features of the FAFNIR technology

Features of the FAFNIR technology VISY-Stick The level and environmental sensor based on the magnetostrictive measuring principle VISY-Stick is a level and environmental sensor that has been specially designed to offer highprecision volume

More information

Executive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer. Exhibit 2 System Specifications

Executive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer. Exhibit 2 System Specifications Executive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer Exhibit 2 System Specifications This exhibit contains the installation, maintenance and compliance standards and specifications

More information

Black Hills Energy Contractor Covered Task List Last updated 10/10/2018

Black Hills Energy Contractor Covered Task List Last updated 10/10/2018 007 Operate Valves 103 Non-destructive Testing (Other than testing of welds) -- Mag Particle 201 Abnormal Operating Conditions Related to Welding on Pipelines 195.452(h) 192.225 192.227 192.715 192.717

More information

40 CFR 63, Subpart CCCCCC

40 CFR 63, Subpart CCCCCC 0 CFR 3, Subpart CCCCCC The Unmatched Solution to Meeting U.S. EPA National Emissions Standards for New National Emission Standards have gone into effect for Hazardous Air Pollutants at Gasoline-Dispensing

More information

General Issues of Line Leak Detection

General Issues of Line Leak Detection Quality Petroleum Equipment Solutions for Over 20 Years ARM-4073 AST-4010 AST-4012 CFOSI FST-200 ISM-4080 ISM-4081 ISM-4080 MC LD-2000 LD-2000\E LD-2200 LD-2200\75 LD-3000 LD-3000\E LD-3000\FL LDT-890

More information

Geomembrane Test Methods

Geomembrane Test Methods Appendix 2 Geomembrane Test Methods AMERICAN SOCIETY FOR TESTING AND MATERIALS (arranged by number) ASTM D-5 ASTM D-36 ASTM D-256 ASTM D-412 ASTM D-413 ASTM D-471 ASTM D-570 ASTM D-638 ASTM D-696 ASTM

More information

Franklin Fueling Systems

Franklin Fueling Systems Franklin Fueling Systems SOLUTIONS YOU CAN TRU S T CATALOG Table of Contents Franklin Fueling Systems has contributed many innovative product designs to the petroleum industry, including the highest performing

More information

Submersible Pumping Systems. Product Catalog

Submersible Pumping Systems. Product Catalog Submersible Pumping Systems Product Catalog SUBMERSIBLE PUMPING SYSTEMS Table of Contents Submersible Pumping Systems Franklin Fueling Systems has contributed many innovative product designs to the petroleum

More information

Refuel Systems Fuel Management System Specification Revision RS1.01

Refuel Systems Fuel Management System Specification Revision RS1.01 Refuel Systems Fuel Management System Specification Revision RS1.01 Part 1 General 1.1 GENERAL.1 Provide a pre-packaged factory assembled fuel management system that provides filtration of stored distillate

More information

Changing Industry. UST Population (Ohio) Number of Tanks. Year 60,000 50,000 40,000 30,000 20,000 10,000

Changing Industry. UST Population (Ohio) Number of Tanks. Year 60,000 50,000 40,000 30,000 20,000 10,000 1 Number of Tanks Changing Industry 60,000 UST Population (Ohio) 50,000 40,000 30,000 20,000 10,000 0 Year Source: Ohio Petroleum Underground Storage Tank Release Compensation Board (2010) 2 Changing Industry

More information

Syracuse University Petroleum Bulk Storage Tank Program Manual

Syracuse University Petroleum Bulk Storage Tank Program Manual Syracuse University Petroleum Bulk Storage Tank Program Manual August 23, 2017 Prepared by: Syracuse University Environmental Health & Safety Services Division of Campus Safety and Emergency Services 029

More information

Dispenser Containment Manual. Product Manual * Publication Number: DCM-0001 * Issue Date: 05/27/09 Supercedes: 11/01/07

Dispenser Containment Manual. Product Manual * Publication Number: DCM-0001 * Issue Date: 05/27/09 Supercedes: 11/01/07 Dispenser Containment Manual Product Manual * Publication Number: DCM-0001 * Issue Date: 05/27/09 Supercedes: 11/01/07 INDEX 1.0 Introduction 1.1 General Information 1.2 Independent Testing 1.3 Liquid

More information

Operating And Maintaining Underground Storage Tank Systems. Practical Help And Checklists. Printed on Recycled Paper

Operating And Maintaining Underground Storage Tank Systems. Practical Help And Checklists. Printed on Recycled Paper Operating And Maintaining Underground Storage Tank Systems Practical Help And Checklists Printed on Recycled Paper Contents How to Use This Booklet...1 Section 1 Identifying The Equipment At Your UST Facility...3

More information

Contact Name: Company Name: Technician Name: Company Address: Company Phone: Company Fax: Address. Technician SSN:

Contact Name: Company Name: Technician Name: Company Address: Company Phone: Company Fax:  Address. Technician SSN: Certification Exam Product Line & Leak Detector Testing COVER SHEET Contact : Company : Technician : Company Address: Company Phone: Company Fax: E-Mail Address Technician SSN: (Last 6 digits - ONLY!)

More information