CASE STUDY ON PIPELINE UNDER-PROTECTION ALONG WITH MITIGATION METHODS. Vipul Vilas Sawant. Mahanagar Gas Ltd, Mumbai, India

Size: px
Start display at page:

Download "CASE STUDY ON PIPELINE UNDER-PROTECTION ALONG WITH MITIGATION METHODS. Vipul Vilas Sawant. Mahanagar Gas Ltd, Mumbai, India"

Transcription

1 Paper No. CAP34 CASE STUDY ON PIPELINE UNDER-PROTECTION ALONG WITH MITIGATION METHODS Vipul Vilas Sawant Mahanagar Gas Ltd, Mumbai, India com ABSTRACT Mahanagar Gas Ltd is a City Gas Distribution Company engaged in the distribution of Natural Gas in and around Mumbai. We presently have around 400 Kms of steel pipeline. All our steel pipelines are coated with 3 Layer Poly Ethylene coating. As a supplementary protection against corrosion, we have also installed Cathodic Protection system over the entire network. Since Mumbai is a congested city with a lot of underground utilities, our assets are prone to damage due to third party excavations in the vicinity of our pipeline. Coating damages on the pipeline and cable cuts in CP assets can subsequently lead to a failure of the CP system and cause under-protection of the Steel pipeline. If these issues are not resolved on priority it may lead to major hazards. This paper deals with an issue of under-protection at two of our locations Mantralaya and Andheri: The under-protection at Mantralaya was due to the addition of many spur lines from the main pipeline over a period of time, coating defects on the pipeline and due to the high corrosive nature of the surrounding soil. The under-protection at Andheri was due to coating defects on the pipeline which was difficult to repair as the pipeline is under a concretized road. This paper also includes the various measures and mitigation methods that were employed at site to resolve these under-protection issues. Keywords: Cathodic Protection; Under-protection;

2 INTRODUCTION Mahanagar Gas Ltd is a city gas distribution company, supplying gas in constantly evolving cities like Mumbai and adjoining areas. In such regions damages to pipeline coatings and construction near or on pipeline is frequent. If care is not taken during construction stage, it may lead to underprotection of pipelines. We shall be discussing two issues faced by Mahanagar Gas in last year at Andheri (Metro) Region and Mantralaya Area. Issue at Ghatkopar-Andheri Metro Line History Mumbai Metro is a rapid transit system serving the city of Mumbai, Maharashtra. The system is designed to reduce traffic congestion in the city, and supplement the overcrowded Mumbai Suburban Railway (colloquially called local trains) network. Construction of Metro started on Feb 2008 and was completed on June The stretch of metro is constructed over 12 header line of Gas Pipeline of about 4km. Problem We have faced under-protection in this 4km of section due to coating damages and Bonding Cable Cuts. Figure 1: Schematic Diagram of Ghatkopar- Andheri Line Previously the said section was getting protection from Gupta TRU but due to cable cut at IJ location at Sakinaka VC the under protection was observed on pipeline. Then we have bonded the same stretch at Leela VC with JB TRU but again due to coating damage the CP current were getting drain at some locations due to which again the line was not getting adequate protection. The matter was further investigated. It was seen that the anode bed of JB Nagar TRU had failed and the resistance had gone upto 18 ohms. Rectification of coating damages and cable cut was not possible due to concretization of road.

3 Mitigation Identification of faults was necessary to apply mitigation methods. We carried out CIPL as well as DCVG survey to identify exact location of coating damages and identification of cables cuts but due to low soil resistivity and concretization, all nearest metallic structures were getting charged and identification of exact location was not possible. Also, excavation of doubtful stretch was not possible as CC road was newly constructed. After carrying out all the surveys, we decided to carry out Current Drain survey to find out the requirement of CP current to protect the 4kM of Section such that a new TRU can be installed to meet the requirement. Installation of TRU was not feasible on main line as it was under CC road and Bore well for Anode bed was also not possible on road due to permission issues. We decided to install a new TRU on the 800mtrs spur line at Intel carport. The spur line is of 3 diameter. During Current Drain survey the current requirement came out to 2A for 4km of under-protected section which is quite high than the normal MGL pipeline requirements due to coating damages. Current Requirement Calculations: Surface Area= Length of Pipe x Diameter of Pipe x π = (2800 x π x 0.304) + (1300 x x π ) (12inch 0.304m & 3inch m) = 2985 m2 Current Requirement= Surface Area x Current Density x Safety Factor = 2985 x 0.9 x 1.3 (Current Density- 0.9 A/m) = 1.2 A To meet this requirement as well to supplement the JB Nagar TRU we installed 50V/50A TRU on spur-line for CNG Station I Carport which was the only feasible location and was meeting the requirement of Protection Criteria. As the protection criteria says (CSE) at end location we have maintained TRU potential of - 1.5(CSE) at drain point. After this we have achieved protection till the end points of Section. Figure 2: Schematic Diagram of Ghatkopar- Andheri Line with Solution

4 Issue At Mantralaya Section History This section of 14kms has 4 nos. of sectionalizing insulating joints (IJs). The TRU for this section was initially designed for up to Mantralaya DRS 33; and was installed at new Modern auto in the year After the TR was commissioned, over a period of time, spur lines for Royal auto (Bhendi bazaar) was laid and mainline was extended beyond Mantralaya DRS up to Oberoi Trident hotel. Problem From the year 2012, we started observing under-protection issues from Mantralaya to Oberoi Trident. (4kms). We then installed temporary anodes at 4 locations (total number of 36 Mg anodes 2.1 Kg each for 4kms). This improved the PSP for a few months after which again the values went down. Anode measurements were seen to be healthy. However the required current was not being dissipated. The matter was investigated further. We initially carried out DCVG survey on the entire pipeline. 17 nos. of minor coating defects and 6 nos. of medium coating defects were recorded in the survey. These defects were in close proximity to each other and were spread out in a distance of 300mtrs. The under protection on 3.8km of line was not only due to addition of spur lines on main line but also due to lots of minor coating damages on line and contact with foreign water pipeline. Mostly minor faults does not contribute much to under-protection of pipeline but all 17 minor faults were on a stretch of 300mtrs contributed well in under-protection of section. All these damages were due third party excavations and during backfilling by third party after completion of work. Out of 17, 8 nos of coating damages observe due to hammering of Crowbar during third party excavation and remaining 9 were due to falling of stones/rocks during backfilling over line.

5 Figure 3: Schematic Diagram of Mantralaya Section Mitigation The consumption rate of Mg Anode was also very high at this stretch due to coastal salt enriched soil. As protection level was not achieved, we have carried out CIPL and DCVG survey for the area, in which all 23 coating defects were identified. After rectification of coatings at 17 minor locations we have observed that the line PSP is increasing at starting location near Thakurdwar which was previously under-protected. After rectification of 17 minor defect locations 700mtrs section bought under protection out of 3.8km. Further, when we started rectification of remaining 6 locations, it has been observed that MGL pipeline is in contact with water pipeline flange. Due to deterioration of additional insulation sheet and pipeline factory coating at Flange location the flange came in contact with MGL pipeline. The CP current of MGL pipeline was getting drained in BMC Water pipeline, due to which the MGL pipeline was not getting adequate CP current. The bolts of Flanges were penetrating the coating with a high force which resulted in coating damage over a period of time. The insulation sheet was installed at the time of pipeline laying but after around 3 years the coating along with insulation sheet got damaged and resulted in direct shorting of MGL pipeline with Water pipeline. Figure 4: Shorting of MGL Gas Line and Water Line To mitigate this we have inserted an insulator having life more than neoprene/ rubber sheets viz., Clock-spring. Pipeline cold wrap coating was not possible at such congested location due to inadequate space for rolling of coating rolls. To mitigate this contact we have inserted a clock-spring in between flange and pipe after application one coat of zinc based primer.

6 Figure 5: Insertion of Clockspring between Shorting of MGL Gas Line and Water Line After carrying out application of Clock-spring, we have managed to obtain protection till Metro VC. Protection of whole section was not possible as the strength of anode bed degraded over a period of time as it was supplying current to BMC non-coated pipeline. Also, The cables used for the deep well anode bed were XLPE / PVC which is not resistant to chemical attack. Also due to road development, the anode bed was buried and hence there was no path for accumulated gas to escape. This may have damaged the cables over a period of time. In the present anode bed at new modern auto, only 3 anodes were seen to be conducting, out of 15 anodes that were installed. For the remaining section to bought under protection level we need to install a separate TRU but due to discontinuity of pipelines at many places it was not possible. Hence we decided to install cable jumper between pipeline to make them electrical continue and TRU installation can be made possible. Figure 6: Schematic Diagram of Mantralaya Section Hence we carry out current drain survey with the drain point at GoM Nariman point which is the midpoint of section considering future expansions of MGL Pipeline. After carrying out current drain survey, the requirement of section comes out to 3Amp for a section of 6km. Current Requirement Calculations: Surface Area = Length of Pipe x Diameter of Pipe x π

7 = (3328 x π x ) + (1990 x π x ) (4inch m & 6inch m) = 2014 m2 Current Requirement = Surface Area x Current Density x Safety Factor = 2014 x 0.9 x 1.3 (Current Density- 0.9 A/m) = 2.4 A The requirement was still high but it was due to the coastal region. Installation of new TRU is carried out along with Cable jumper installation at discontinuity near GoM Nariman point and it is thus protecting whole section now and capable to take new spur/main line. Figure 7: Jumper installation for Electrical Continuity at GoM Narimanpoint LEARNINGS 1. Close observation on Excavation site. 2. Maintaining records of exposed pipelines, Thickness and Coating rectifications. 3. CIPL/ DCVG Survey Frequency reduced to 3yrs. 4. None of the Coating defects to be left unattended. 5. All precautions against shorting need to be taken in construction stage only. 6. Monitoring and maintenance of the CP system should be done as per the scheduled frequency to maintain the CP system effectively.

8 ACKNOWLEDGEMENTS I would like to mention special thanks to my superiors and project colleagues of MGL for study and consolidation of the practices and their effectiveness for Cathodic protection system of Natural Gas pipelines as well as limitation and scope of improvement. REFERENCES 1. NACE 1 & II Course Manual 2. NACE RP MGL CP philosophy 4. OISD Standard Corrosion Survey Data of MGL Pipelines

PIPELINE INTEGRITY CONFERENCE BHR GROUP 5th-7th NOVEMBER 2008 SCHIPOL, THE NETHERLANDS PIPPELINE IN INDIA

PIPELINE INTEGRITY CONFERENCE BHR GROUP 5th-7th NOVEMBER 2008 SCHIPOL, THE NETHERLANDS PIPPELINE IN INDIA PIPELINE INTEGRITY CONFERENCE BHR GROUP 5th-7th NOVEMBER 2008 SCHIPOL, THE NETHERLANDS REHABILITATING A MAJOR OIL PIPPELINE IN INDIA K.G. GUPTA, INDIAN OIL CORPORATION LTD, INDIA R. JOHN, BERRY PLASTICS

More information

Cathodic Protection for AST s. Why is Cathodic Protection Important?

Cathodic Protection for AST s. Why is Cathodic Protection Important? Cathodic Protection for AST s Presented by: James T. Lary Corrpro Companies, inc. 1055 West Smith Road Medina, Ohio 44256 jlary@corrpro.com 330-241-6615 Why is Cathodic Protection Important? Preserve Assets

More information

TransCanada US Contractor Covered Task List Last updated 9/27/2018

TransCanada US Contractor Covered Task List Last updated 9/27/2018 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 Oral 005 Repair Breakout Tank Overfill Protective Devices 195.428

More information

Enbridge Gas Transmission and Midstream and Enbridge Liquid Pipelines (Express-Platte) Contractor Covered Task List Last updated 8/30/2018

Enbridge Gas Transmission and Midstream and Enbridge Liquid Pipelines (Express-Platte) Contractor Covered Task List Last updated 8/30/2018 001 Provide Security for Pipeline Facilities 195.436 Oral 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 Oral

More information

Howard Midstream Energy Partners LLC Contractor Covered Task List Last updated 10/11/2013

Howard Midstream Energy Partners LLC Contractor Covered Task List Last updated 10/11/2013 001 Provide Security for Pipeline Facilities 195.436 Oral 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 005

More information

This article discusses a tank

This article discusses a tank CASE HISTORY Hot Oil Aboveground Storage Tank Bottom Corrosion Failure and Cathodic Protection Upgrade Part 2 KEVIN C. GARRITY AND PHILIP D. SIMON, CC Technologies, Inc. Several types of anode installations

More information

Dominion Energy Questar Pipeline LLC Contractor Covered Task List Last updated 10/3/2017

Dominion Energy Questar Pipeline LLC Contractor Covered Task List Last updated 10/3/2017 007 Operate Valves 008 Measurement of Wall Thickness with Ultrasonic Device 103 Non-destructive Testing (Other than testing of welds) -- Mag Particle 104 Non-destructive Testing (Other than testing of

More information

Epic Consolidated Operations LLC Contractor Covered Task List Last updated 9/6/2018

Epic Consolidated Operations LLC Contractor Covered Task List Last updated 9/6/2018 003 Test Breakout Tank Overfill Protective 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective 195.428 Oral 005 Repair Breakout Tank Overfill Protective 195.428 006 Inspection of Breakout

More information

Northern Natural Gas Contractor Covered Task List Last updated 4/26/2018

Northern Natural Gas Contractor Covered Task List Last updated 4/26/2018 001 Provide Security for Pipeline Facilities 195.436 Oral 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 Oral

More information

FINAL REPORT CATHODIC PROTECTION EVALUATION. 42-Inch Water Transmission Pipeline Contract 1 Station 0+00 to South Texas Water Authority

FINAL REPORT CATHODIC PROTECTION EVALUATION. 42-Inch Water Transmission Pipeline Contract 1 Station 0+00 to South Texas Water Authority FINAL REPORT CATHODIC PROTECTION EVALUATION 42-Inch Water Transmission Pipeline Contract 1 Station 0+00 to 50+00 South Texas Water Authority Prepared for: South Texas Water Authority P.O. Box 1701 Kingsville,

More information

Black Hills Energy Contractor Covered Task List Last updated 10/10/2018

Black Hills Energy Contractor Covered Task List Last updated 10/10/2018 007 Operate Valves 103 Non-destructive Testing (Other than testing of welds) -- Mag Particle 201 Abnormal Operating Conditions Related to Welding on Pipelines 195.452(h) 192.225 192.227 192.715 192.717

More information

Energy Transfer Partners LP Contractor Covered Task List Last updated 3/2/2018

Energy Transfer Partners LP Contractor Covered Task List Last updated 3/2/2018 001 Provide Security for Pipeline Facilities 195.436 Oral 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 Oral

More information

Energy Transfer Partners LP Contractor Covered Task List Last updated 12/10/2018

Energy Transfer Partners LP Contractor Covered Task List Last updated 12/10/2018 001 Provide Security for Pipeline Facilities 195.436 Oral 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 005

More information

Noble Energy Contractor Covered Task List Last updated 2/20/2019

Noble Energy Contractor Covered Task List Last updated 2/20/2019 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 005 Repair Breakout Tank Overfill Protective Devices 195.428

More information

Columbia Pipeline Group Contractor Covered Task List Last updated 1/8/2018

Columbia Pipeline Group Contractor Covered Task List Last updated 1/8/2018 001 Provide Security for Pipeline Facilities 195.436 Oral 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 Oral

More information

Southern Star Central Gas Pipeline Contractor Covered Task List Last updated 8/15/2018

Southern Star Central Gas Pipeline Contractor Covered Task List Last updated 8/15/2018 007 Operate Valves 008 Measurement of Wall Thickness with Ultrasonic Device 018 Inspect Navigable Waterway Crossing 195.412(b) 201 Abnormal Operating Conditions Related to Welding on Pipelines 192.225

More information

Saddle Butte Rockies Midstream LLC Contractor Covered Task List Last updated 12/6/2017

Saddle Butte Rockies Midstream LLC Contractor Covered Task List Last updated 12/6/2017 003 Test Breakout Tank Overfill Protective N/A 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective N/A 195.428 Oral 005 Repair Breakout Tank Overfill Protective N/A 195.428 007 Operate

More information

Test Stations and Pipe-to-Soil Potential Measurements

Test Stations and Pipe-to-Soil Potential Measurements Test Stations and Pipe-to-Soil Potential Measurements Period #7 Practical Applications Course 2017 Mark James NACE CP II #5619, NACE CIP I #37041 1 Introduction Test Stations Wire Connection to Pipe Pipe-to-Soil

More information

Boardwalk Pipeline Partners, LP Contractor Covered Task List Last updated 9/17/2018

Boardwalk Pipeline Partners, LP Contractor Covered Task List Last updated 9/17/2018 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 Oral 005 Repair Breakout Tank Overfill Protective Devices 195.428

More information

Williams Contractor Covered Task List Last updated 11/7/2017

Williams Contractor Covered Task List Last updated 11/7/2017 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 Oral 005 Repair Breakout Tank Overfill Protective Devices 195.428

More information

DCP Midstream Contractor Covered Task List Last updated 7/11/2018

DCP Midstream Contractor Covered Task List Last updated 7/11/2018 001 Provide Security for Pipeline Facilities 195.436 Oral 007 Operate Valves 008 Measurement of Wall Thickness with Ultrasonic Device 009 Movement and/or Relocation of Liquid Pipelines 195.424 011 Inspect,

More information

ASMECourseCatalog.

ASMECourseCatalog. ASMECourseCatalog www.energyu.org www.midwestenergy.org ASME Abnormal Operating Conditions... 6 ASME GAS01 Hazards of Natural Gas and Prevention of Accidental Ignition... 6 ASME 0001 Measure Structure-to-Electrolyte

More information

Monitoring of Shoring Pile Movement using the ShapeAccel Array Field

Monitoring of Shoring Pile Movement using the ShapeAccel Array Field 2359 Royal Windsor Drive, Unit 25 Mississauga, Ontario L5J 4S9 t: 905-822-0090 f: 905-822-7911 monir.ca Monitoring of Shoring Pile Movement using the ShapeAccel Array Field Abstract: A ShapeAccel Array

More information

CNG Developments An Indian Experience

CNG Developments An Indian Experience 23rd World Gas Conference, Amsterdam 26 CNG Developments An Indian Experience Main author A.K.Purwaha India ABSTRACT Vehicular emission is the main contributor to urban air pollution. In line with public

More information

PREVENTION OF STRAY CURRENT BY THE MAINTENANCE-OF-WAY

PREVENTION OF STRAY CURRENT BY THE MAINTENANCE-OF-WAY PREVENTION OF STRAY CURRENT BY THE MAINTENANCE-OF-WAY Eugene D. Kale Senior Corrosion Engineer Parsons Transportation Group, Inc. 12160 North Abrams Road, Suite 200 Dallas, Texas 75243 Tp: (214) 570-8590

More information

EnLink Midstream Contractor Covered Task List Last updated 11/8/2017

EnLink Midstream Contractor Covered Task List Last updated 11/8/2017 003 Test Breakout Tank Overfill Protective Devices 195.428 Oral 004 Inspect and Calibrate Breakout Tank Overfill Protective Devices 195.428 005 Repair Breakout Tank Overfill Protective Devices 195.428

More information

WYOMING STORAGE TANK PROGRAM GALVANIC (SACRIFICIAL ANODE) CATHODIC PROTECTION SYSTEM EVALUATION

WYOMING STORAGE TANK PROGRAM GALVANIC (SACRIFICIAL ANODE) CATHODIC PROTECTION SYSTEM EVALUATION WYOMING STORAGE TANK PROGRAM GALVANIC (SACRIFICIAL ANODE) CATHODIC PROTECTION SYSTEM EVALUATION A site drawing depicting the UST Cathodic Protection (CP) system and all reference electrode placements should

More information

An Introduction to Constructing and Maintaining Cathodic Protection Systems

An Introduction to Constructing and Maintaining Cathodic Protection Systems An Introduction to Constructing and Maintaining Cathodic Protection Systems Course No: T02-009 Credit: 2 PDH J. Paul Guyer, P.E., R.A., Fellow ASCE, Fellow AEI Continuing Education and Development, Inc.

More information

Appendix A Kinder Morgan Operator Qualification Program List of Covered Tasks - Natural Gas - Part 192 Revised 12/13/2017

Appendix A Kinder Morgan Operator Qualification Program List of Covered Tasks - Natural Gas - Part 192 Revised 12/13/2017 01.01.01 Abnormal Operating Conditions (AOC) - Outside of Room 01.01.02 Abnormal Operating Conditions (AOC) - Inside of Room (new task effective 1/1/2018) 02.01.01 Gas Detection & Alarm System Maintenance

More information

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2 Electrical Learning Notes MODULE 2.2 UNIT 2.2.6 Installation Techniques Earthing & Bonding PHASE:2 Table of Contents INTRODUCTION... 3 DEFINITIONS... 4 EARTHING... 5 TYPES OF SYSTEM EARTHING... 10 EQUIPOTENTIAL

More information

Operator Qualification (OQ) Report

Operator Qualification (OQ) Report AOCF 66102/67107 Abnormal Operating Conditions Field for Natural Gas and Hazardous Liquids 5/15/2014 5/15/2017 AOCG 67107 Abnormal Operating Conditions for Natural Gas 5/16/2014 5/16/2017 TM001 66101 02

More information

Earthing UNIT. Learning Objectives. Introduction. To understand purpose of Earthing. To learn system of earthing.

Earthing UNIT. Learning Objectives. Introduction. To understand purpose of Earthing. To learn system of earthing. 274 Electrical Technician UNIT 10 Earthing Learning Objectives To understand purpose of Earthing. To learn system of earthing. Introduction The very purpose of earthing is to safe against dangers of shock

More information

GEMSCAB has been associated with marketing and manufacturing of Electric Cables

GEMSCAB has been associated with marketing and manufacturing of Electric Cables I NTRODUCTION GEMSCAB has been associated with marketing and manufacturing Electric Cables for over a period 4 decades now. Customer satisfaction has been the prime focus GEMSCAB and today it has established

More information

The Knowledge Bank at The Ohio State University. Ohio State Engineer. Electrolysis in Underground Structures

The Knowledge Bank at The Ohio State University. Ohio State Engineer. Electrolysis in Underground Structures The Knowledge Bank at The Ohio State University Ohio State Engineer Title: Creators: Issue Date: Publisher: Electrolysis in Underground Structures Rei, P. F. Pepper, H. C. Hoover, C. H. Frankenberg, R.

More information

Monitoring Cathodic Protection of Natural Gas Pipelines

Monitoring Cathodic Protection of Natural Gas Pipelines Monitoring Cathodic Protection of Natural Gas Pipelines Period #8 Basic Corrosion Course 2017 February 21-23, 2017 Steve Glover - Vectren 0 Chapter Objective: Introduction Reasons to monitor What to monitor

More information

Processing Plant Enters. the Pipeline World. A Case Study of a Chemically Welded Anomaly Repair. By Randy Vaughn. R&F Pipecon Resources

Processing Plant Enters. the Pipeline World. A Case Study of a Chemically Welded Anomaly Repair. By Randy Vaughn. R&F Pipecon Resources Processing Plant Enters the Pipeline World A Case Study of a Chemically Welded Anomaly Repair By Randy Vaughn R&F Pipecon Resources Introduction A processing plant entered into the pipeline industry in

More information

Point A Point B Point C Point D. Fulton County Board of Commissioners and Mayors Meeting December 14, 2017

Point A Point B Point C Point D. Fulton County Board of Commissioners and Mayors Meeting December 14, 2017 Fulton County Board of Commissioners and Mayors Meeting December 14, 2017 Master Plan Overview Phase 1 Community Vision and Existing Transit Conditions Phase 2 Scenario Development Phase 3 Transit Master

More information

EMERGING REQUIREMENTS

EMERGING REQUIREMENTS EB-00-0 Exhibit D Schedule Page of EMERGING REQUIREMENTS 0 EQUIPMENT STANDARDIZATION THESL plans, designs and constructs distribution system assets in accordance with approved standards. The standards

More information

Exercise 3-3. Basic Operations of GTO Thyristors EXERCISE OBJECTIVES

Exercise 3-3. Basic Operations of GTO Thyristors EXERCISE OBJECTIVES Exercise 3-3 Basic Operations of GTO Thyristors EXERCISE OBJECTIVES At the completion of this exercise, you will be able to switch on and off the power GTO thyristor using the 0 to 10 V positive power

More information

7. Protection System Testing

7. Protection System Testing MANUAL FOR INSTALLATION AND MONITORING OF UNDERGROUND STORAGE TANKS WITH FACTORY INSTALLED ANODES 1. SCOPE Manufactured by: Granby Industries 1020 André-Liné Granby, Québec, Canada, J2J 1J9. Telephone:

More information

Installation & Operation Manual

Installation & Operation Manual Installation & Operation Manual Thank you for purchasing our AS4795.1 Butterfly Valve. Before installing or operating, please carefully read this manual to know thoroughly how to install or operate. The

More information

Cathodic Protection Guidance? Who needs that? Aren t t NACE & STI enough? David Robinett Virginia Dept. of Environmental Quality

Cathodic Protection Guidance? Who needs that? Aren t t NACE & STI enough? David Robinett Virginia Dept. of Environmental Quality Cathodic Protection Guidance? Who needs that? Aren t t NACE & STI enough? David Robinett Virginia Dept. of Environmental Quality December 22,1998 CP required for USTs CP required for USTs Huge demand for

More information

Instruction and Installation Guide

Instruction and Installation Guide Instruction and Installation Guide Type 2A Arc Resistant tiastar Motor Control Center www.usa.siemens.com/mcc DANGER Hazardous voltage. Will cause death or serious injury. Keep out. Qualified personnel

More information

4. Good Practice Example: Automatic light metro system (Brescia, Italy)

4. Good Practice Example: Automatic light metro system (Brescia, Italy) 4. Good Practice Example: Automatic light metro system (Brescia, Italy) Keywords Sustainable mobility, automatic light metro system Name and location Automatic light metro system, Brescia, Italy Brescia

More information

Appendix B Kinder Morgan Operator Qualification Program List of Covered Tasks Hazardous Liquid Pipelines Part 195 revised 8/24/2018

Appendix B Kinder Morgan Operator Qualification Program List of Covered Tasks Hazardous Liquid Pipelines Part 195 revised 8/24/2018 Abnormal Operating Conditions Outside of 101.01 Room Abnormal Operating Conditions Inside of 101.02 Room 102.01 Measure Structure-to-Soil Potentials 102.02 Advanced Cathodic Testing 102.03 Active Corrosion/MIC

More information

PPTS OPERATOR ADVISORY: FACILITIES PIPING AND EQUIPMENT: FOCUS ON ITEMS INVOLVED AND CAUSES OF INCIDENTS

PPTS OPERATOR ADVISORY: FACILITIES PIPING AND EQUIPMENT: FOCUS ON ITEMS INVOLVED AND CAUSES OF INCIDENTS The petroleum pipeline industry has undertaken a voluntary environmental performance tracking initiative, recording detailed information about spills and releases, their causes and consequences. The pipeline

More information

E/ECE/324/Rev.2/Add.102/Rev.1 E/ECE/TRANS/505/Rev.2/Add.102/Rev.1

E/ECE/324/Rev.2/Add.102/Rev.1 E/ECE/TRANS/505/Rev.2/Add.102/Rev.1 30 August 2011 Agreement Concerning the adoption of uniform technical prescriptions for wheeled vehicles, equipment and parts which can be fitted and/or be used on wheeled vehicles and the conditions for

More information

The Gradient Control Mat (GCM)

The Gradient Control Mat (GCM) The (GCM) Installation Instructions INTRODUCTION Most gradient control mats are designed and installed around above ground pipeline appurtenances to limit power frequency voltages. The Dairyland gradient

More information

Control of Static Electricity during the Fuel Tanker Delivery Process

Control of Static Electricity during the Fuel Tanker Delivery Process Control of Static Electricity during the Fuel Tanker Delivery Process Hanxiao Yu Victor Sreeram & Farid Boussaid School of Electrical, Electronic and Computer Engineering Stephen Thomas CEED Client: WA/NT

More information

Introduction. for over a period 4 decades now. Customer satisfaction has been the prime focus of

Introduction. for over a period 4 decades now. Customer satisfaction has been the prime focus of Introduction GEMSCAB has been associated with marketing and manufacturing Electric s for over a period 4 decades now. Customer satisfaction has been the prime focus GEMSCAB and today it has established

More information

Complicated Minimal Piping Authors: Presenters: Shelley

Complicated Minimal Piping Authors: Presenters: Shelley Pipeline Station Pulsati ion Case Study: Minimal Piping Change Creates Complicated Problems Authors: Noah Dixon, Sr. Technical Specialist, Williams Gas Pipeline Carol Palynchuk, Design Project Manager,

More information

Asset Protection Cathodic Protection Testing of Insulating Joints. Work Instruction No.:

Asset Protection Cathodic Protection Testing of Insulating Joints. Work Instruction No.: Asset Protection Cathodic Protection Testing of Insulating Joints Approved by: Manager Pipeline Standards 1 PURPOSE This work instruction describes the requirements and process for testing the integrity

More information

Defect Monitoring In Railway Wheel and Axle

Defect Monitoring In Railway Wheel and Axle IJR International Journal of Railway, pp. 1-5 The Korean Society for Railway Defect Monitoring In Railway Wheel and Axle Seok-Jin Kwon, Dong-Hyoung Lee *, and Won-Hee You * Abstract The railway system

More information

GATE VALVES. Type P (Standard: Plug) Type S (Soft Seal) Contents. (1) Be sure to read the following warranty clauses of our product 1

GATE VALVES. Type P (Standard: Plug) Type S (Soft Seal) Contents. (1) Be sure to read the following warranty clauses of our product 1 Serial No. H-V011-E-12 GATE VALVES Type P (Standard: Plug) Type S (Soft Seal) Contents (1) Be sure to read the following warranty clauses of our product 1 User s Manual (2) General operating instructions

More information

Prerequisites for Increasing the Axle Load on Railway Tracks in the Czech Republic M. Lidmila, L. Horníček, H. Krejčiříková, P.

Prerequisites for Increasing the Axle Load on Railway Tracks in the Czech Republic M. Lidmila, L. Horníček, H. Krejčiříková, P. Prerequisites for Increasing the Axle Load on Railway Tracks in the Czech Republic M. Lidmila, L. Horníček, H. Krejčiříková, P. Tyc This paper deals with problems of increasing the axle load on Czech Railways

More information

CP-1TT Remote System

CP-1TT Remote System CP-1TT Remote System (9 volt & 12 volt systems) INSTALLATION/OPERATION MANUAL Manufactured by: Preferred Technologies Group www.cartell.com TABLE OF CONTENTS This Table of Contents is clickable. Point

More information

PHMSA Office of Pipeline Safety Dave Mulligan Western Region

PHMSA Office of Pipeline Safety Dave Mulligan Western Region PHMSA Office of Pipeline Safety Dave Mulligan Western Region Chevron Pipeline Releases Salt Lake City, Utah June 11, 2010 & December 1, 2011 Dave Mulligan U.S. Department of Transportation (US DOT) Pipeline

More information

Mechanical department, Pune University, Pune, India

Mechanical department, Pune University, Pune, India To Check Tir Of Gears Using Hydro-Pneumatic Intensifier After Heat Treatment Rohan Ghorpade 1, Rahul Parikh 2, Parag Gholawde 3, Amol Pangare 4, Mr. Mukesh Chaudhari 5 1,2,3,4,5 (student, student, student,

More information

EARTHING YOUR QUESTIONS ANSWERED

EARTHING YOUR QUESTIONS ANSWERED 18 EARTHING YOUR QUESTIONS ANSWERED By Geoff Cronshaw What are earthed and unearthed systems? What are the requirements of BS 7671? What are the advantages and disadvantages of the various types of earthing

More information

Appendix B Kinder Morgan Operator Qualification Program List of Covered Tasks Hazardous Liquid Pipelines Part 195 revised 12/12/2017

Appendix B Kinder Morgan Operator Qualification Program List of Covered Tasks Hazardous Liquid Pipelines Part 195 revised 12/12/2017 Abnormal Operating Conditions Outside of 101.01 Room Abnormal Operating Conditions Inside of 101.02 Room 102.01 Measure Structure-to-Soil Potentials 102.02 Advanced Cathodic Testing 102.03 Active Corrosion/MIC

More information

RISK ASSESSMENT PROGRAM UNDERGROUND STORAGE TANK SYSTEMS

RISK ASSESSMENT PROGRAM UNDERGROUND STORAGE TANK SYSTEMS RISK ASSESSMENT PROGRAM of UNDERGROUND STORAGE TANK SYSTEMS Presented by GS Holt at the IIR Corrosion Conference Johannesburg June 24-26, 1997 SYNOPSIS This paper describes the Risk Assessment Program

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS R913 FRP COMPOSITE STEEL UNDERGROUND STORAGE TANKS INSTALLATION INSTRUCTIONS February 2017 1.0 EXCAVATION AND BEDDING 1.1 The bottom of the excavation shall be covered with a minimum of 12 inches (305

More information

THE APPLICATION OF LONG RANGE GUIDED ULTRASONICS FOR THE INSPECTION OF RISER PIPES

THE APPLICATION OF LONG RANGE GUIDED ULTRASONICS FOR THE INSPECTION OF RISER PIPES THE APPLICATION OF LONG RANGE GUIDED ULTRASONICS FOR THE INSPECTION OF RISER PIPES J. McGregor, B. Nooteboom, N. Ivory PTAS-ITS Lot 1 and 2 Tapak Perindustrian Pekan Belait, Jalan Setia Di-Raja, Kuala

More information

Paper No. 150 VALIDATING STATED PARKING DURATION OF DRIVERS IN KOTA CITY, INDIA

Paper No. 150 VALIDATING STATED PARKING DURATION OF DRIVERS IN KOTA CITY, INDIA Paper No. 150 VALIDATING STATED PARKING DURATION OF DRIVERS IN KOTA CITY, INDIA Dr. Rajat Rastogi Assistant Professor, Indian Institute of Technology Roorkee Roorkee 247 667, Uttarakhand, India Email:

More information

Design of Automated Outriggers for Self- Propelled Hydraulic Scissor Lift - A Case Study At Air India

Design of Automated Outriggers for Self- Propelled Hydraulic Scissor Lift - A Case Study At Air India Design of Automated Outriggers for Self- Propelled Hydraulic Scissor Lift - A Case Study At Air India Dileep Kanojia 1 Shubhankar Gokhale 3 Chinmay Rohekar 2 Sanjay Bokade 4 Department Of Mechanical Engineering,

More information

Your Partner in Safe Power Solutions. About RESCAB

Your Partner in Safe Power Solutions. About RESCAB Your Partner in Safe Power Solutions About RESCAB Red Sea Cables Company (RESCAB) was established as a closed joint stock company in 2008 in the Kingdom of Saudi Arabia with a capital of 370 million SAR.

More information

Declaration of Conformity as per Directive 97/23/EC

Declaration of Conformity as per Directive 97/23/EC Declaration of Conformity as per Directive 97/23/EC The manufacturer declares that:, 47906 Kempen, Germany PTFE-lined Rotary plug valves Series 23e, with packing with lever for 90 operation with worm gear

More information

Mechanical Trainstop Systems

Mechanical Trainstop Systems Mechanical Trainstop Systems Synopsis This document defines the functional requirements for mechanical trainstop systems and the requirements relating to their use on both track and trains. Signatures

More information

SELECTION OF TRACTION SYSTEMS & ENERGY CONSERVATION IN METRO SYSTEMS. BY BRIJESH DIXIT MANAGING DIRECTOR Nagpur Metro Rail Corporation Ltd.

SELECTION OF TRACTION SYSTEMS & ENERGY CONSERVATION IN METRO SYSTEMS. BY BRIJESH DIXIT MANAGING DIRECTOR Nagpur Metro Rail Corporation Ltd. SELECTION OF TRACTION SYSTEMS & ENERGY CONSERVATION IN METRO SYSTEMS BY BRIJESH DIXIT MANAGING DIRECTOR Nagpur Metro Rail Corporation Ltd. ALTERNATIVES TRACTION SYSTEMS AC Traction DC Traction 25 KV 50

More information

Fault Finding. Standard/Fundamental Faults

Fault Finding. Standard/Fundamental Faults Fault Finding There is a generally recognised method of approaching faultfinding, which is referred to as the 5-Point Fault Finding approach... the most important factor in this method concerns attaining

More information

DETAILS OF THE EXPRESSION OF INTEREST(EOI) NO.: PL.G03.EOI

DETAILS OF THE EXPRESSION OF INTEREST(EOI) NO.: PL.G03.EOI DETAILS OF THE EXPRESSION OF INTEREST(EOI) NO.: PL.G03.EOI.09.001 Date: 29/05/2009 For Annual Operation and Maintenance Service Contract of HT/LT Panels,Motors,Transformers,UPS,Air Conditiners,Lightings

More information

Ensuring the Safety Of Medical Electronics

Ensuring the Safety Of Medical Electronics Chroma Systems Solutions, Inc. Ensuring the Safety Of Medical Electronics James Richards, Marketing Engineer Keywords: 19032 Safety Analyzer, Medical Products, Ground Bond/Continuity Testing, Hipot Testing,

More information

The impact of the 18 th Edition (BS 7671:2018) Sections 722, 753 and [new] 730

The impact of the 18 th Edition (BS 7671:2018) Sections 722, 753 and [new] 730 The impact of the 18 th Edition (BS 7671:2018) Sections 722, 753 and [new] 730 In this article, Geoff Cronshaw looks at the impact that some of the proposed changes in the DPC (draft for public comment)

More information

TERRATORQUE HELICAL ANCHORS AND HELICAL PILING PRODUCT CATALOG

TERRATORQUE HELICAL ANCHORS AND HELICAL PILING PRODUCT CATALOG TERRATORQUE HELICAL ANCHORS AND HELICAL PILING PRODUCT CATALOG INTRODUCTION TerraTorque offers quality helical anchors and helical piling to industry. Our products are available in square shaft (type TS)

More information

CONTENTS. Foreword...iii. 1. Introduction...1

CONTENTS. Foreword...iii. 1. Introduction...1 Installation of Aboveground Storage Systems for Motor-Vehicle Fueling CONTENTS Foreword...iii SECTIONS 1. Introduction...1 1.1 Background...1 1.2 Purpose...1 1.3 Scope...1 1.4 Source...1 1.5 Use of PEI/RP100...1

More information

Abstract. General N BANDA

Abstract. General N BANDA Abstract General For mining operations, both underground and open cast, there are generally accepted criteria used to arrive at the optimum mining method with which to exploit the ore body economically.

More information

INSTALLATION GUIDELINES

INSTALLATION GUIDELINES SUMP TANKS INSTALLATION GUIDELINES Thank you for purchasing a quality SumpTank. In order to gain the maximum benefit from your purchase, we have outlined the following instructions for the installation

More information

Road Condition Assessment and Road Contributions Study. 270 Grants Road, Somersby. June 2015 Our Ref: SY140135

Road Condition Assessment and Road Contributions Study. 270 Grants Road, Somersby. June 2015 Our Ref: SY140135 Condition Assessment and Contributions Study 270 June 2015 Our Ref: SY140135 Copyright Barker Ryan Stewart Pty Ltd 2015 All Rights Reserved Project No. SY140135 Author DH Checked PM Approved GB Rev No.

More information

Selection of Technologies to Integrate Urban and Suburban Public Rail Transport

Selection of Technologies to Integrate Urban and Suburban Public Rail Transport Selection of Technologies to Integrate Urban and Suburban Public Rail Transport Kurt Rieckhoff 22 nd Metros & Railways Technology Meeting Instructons for presentation The presentation must be in English

More information

Gerardo G. Clemeiia Senior Research Scientist

Gerardo G. Clemeiia Senior Research Scientist 549 INTERIM REPORT CATHODIC PROTECTION OF TWO CONCRETE BRIDGE DECKS USING TITANIUM-MESH ANODES Gerardo G. Clemeiia Senior Research Scientist (The opinions, findings, and conclusions expressed in this report

More information

Mass Tank Inspection Services, LLC 29 Abbey Lane Middleboro, MA masstankinspection.com

Mass Tank Inspection Services, LLC 29 Abbey Lane Middleboro, MA masstankinspection.com June 18, 2018 Mrs. Nancy Cole Administrator Village of Eidelweiss 1680 Conway RD Madison, NH 03849 Mass Tank Inspection Services, LLC 29 Abbey Lane Middleboro, MA 02346 508-947-8826 masstankinspection.com

More information

Northeast Ohio AWWA October 26, 2017

Northeast Ohio AWWA October 26, 2017 Northeast Ohio AWWA October 26, 2017 Introduction Karl Dickinson Regional Sales Manager Jack Doheny Companies Sell & Rent Vacuum Trucks, Sewer Cleaning Equipment, & Pipeline Inspection Systems 16 Service

More information

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS ENERGY FACILITY SITING BOARD

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS ENERGY FACILITY SITING BOARD STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS ENERGY FACILITY SITING BOARD In re : : Docket No. SB-00-0 () : Testimony of David M. Campilii, P.E. June, 00 PROV-- 0 0 TESTIMONY OF DAVID M. CAMPILII,

More information

Title Low Voltage Distribution and Installations Earthing References and Definitions. Reference Number PDS 03 (ARTC Standard: EP SP)

Title Low Voltage Distribution and Installations Earthing References and Definitions. Reference Number PDS 03 (ARTC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Low Voltage Distribution and Installations Earthing References and Definitions Reference Number PDS 03 (ARTC Standard: EP 12 00 00 02 SP) Document

More information

Powering Sydney s Future

Powering Sydney s Future Powering Sydney s Future Frequently Asked Questions December 2017 Project background Q: Why is this project needed? A: Inner Sydney is one of the most critical parts of the NSW electricity network. However,

More information

E. V. Gray Historical Series

E. V. Gray Historical Series E. V. Gray Historical Series Starting with the Start Motor Mark McKay, PE. The Start Motor as Found in 2000 EMA4 and EMA5 Motors as Found in 2000 E. V. Gray once commented to John Bedini that his early

More information

IDCOL Technical Standard for Solar Irrigation Pump (SIP) Projects

IDCOL Technical Standard for Solar Irrigation Pump (SIP) Projects P a g e 1 IDCOL Technical Standard for Solar Irrigation Pump (SIP) Projects Scope of standardization: Equipment standardization : 1. Pump & Motor 2. PV panels 3. Controller Civil construction standardization:

More information

RB72-3 HD Flush Mounted Directional Traffic Spikes Installation and Operating Precautions

RB72-3 HD Flush Mounted Directional Traffic Spikes Installation and Operating Precautions RB723 HD Flush Mounted Directional Traffic Spikes Installation and Operating Precautions 1. Install the Directional Traffic Controller perpendicular to the flow of traffic. If vehicles cross the controller

More information

CANADA LABOUR CODE PART II OCCUPATIONAL SAFETY AND HEALTH

CANADA LABOUR CODE PART II OCCUPATIONAL SAFETY AND HEALTH Decision: 92-009 CANADA LABOUR CODE PART II OCCUPATIONAL SAFETY AND HEALTH Review under section 146 of the Canada Labour Code, Part II of a direction issued by a safety officer Applicant: Interested Party:

More information

Welcome to Open House #5 Scarborough Rapid Transit

Welcome to Open House #5 Scarborough Rapid Transit Welcome to Open House #5 Scarborough Rapid Transit Welcome to the Scarborough Rapid Transit (SRT) Conversion and Extension Study, including Kennedy Station improvements. Tonight s event provides details

More information

SUSTAINABLE URBAN TRANSPORTATION DEVELOPMENT WITH ITS

SUSTAINABLE URBAN TRANSPORTATION DEVELOPMENT WITH ITS SUSTAINABLE URBAN TRANSPORTATION DEVELOPMENT WITH ITS Arshad Alam 1, S.D.Ghodmare 2 1 Civil Engineering Department, G.H. Raisoni College of Engineering, Nagpur, (India) 2 Assistant Professor, Civil Engineering

More information

Fluid Filled Cables. Alan Ainsley. Asset Integrity Cable System Engineer NGT

Fluid Filled Cables. Alan Ainsley. Asset Integrity Cable System Engineer NGT Fluid Filled Cables Alan Ainsley Asset Integrity Cable System Engineer NGT Overview Function of cable fluid in fluid filled cables Types of fluids used Movement of fluid in cable circuits unction of cable

More information

Assets Installation, operation and maintenance of Street Lighting Assets

Assets Installation, operation and maintenance of Street Lighting Assets Agenda 9:00 AM ADMINISTRATIVE ITEMS Chair of Working Group 9:30 AM ONGOING ISSUES Present and examine ongoing issues associated with Street Lighting Assets Installation, operation and maintenance of Street

More information

PROJECTS $500K AND OVER FOR 2014

PROJECTS $500K AND OVER FOR 2014 Page of PROJECTS $00K AND OVER FOR 0 STANDARDIZATION PORTFOLIO Table : Standardization Projects Estimate Estimated Cost Project Title Number ($ Millions) Grounding Compliance Program. Porcelain Insulator

More information

Removal of Underground Storage Tanks (UST) Encountered during Construction

Removal of Underground Storage Tanks (UST) Encountered during Construction Removal of Underground Storage Tanks (UST) Encountered during Construction Technical Guide Environmental Affairs Division TxDOT Environmental Affairs Division Release Date: 2/2014 510.06.GUI Version 1

More information

Public Works Operations Manual Standard Operating Procedures for Water and Sewer WS - B311 Sanitary Sewer Connection Repair

Public Works Operations Manual Standard Operating Procedures for Water and Sewer WS - B311 Sanitary Sewer Connection Repair Public Works Operations Manual Standard Operating Procedures for Water and Sewer WS - B311 Sanitary Sewer Connection Repair 1. Objective: 1.1. To repair the sanitary sewer connection in a timely and efficient

More information

VW Embedment Jointmeter

VW Embedment Jointmeter VW Embedment Jointmeter 52632244 Copyright 2003 Slope Indicator Company. All Rights Reserved. This equipment should be installed, maintained, and operated by technically qualified personnel. Any errors

More information

Adapting and Applying Process Safety Management (PSM) Concept in Fuel/NGV Retail Stations

Adapting and Applying Process Safety Management (PSM) Concept in Fuel/NGV Retail Stations Adapting and Applying Process Safety Management (PSM) Concept in Fuel/NGV Retail Stations Ms Sulo Belawan CCPS Asia Pacific Regional TSC Meeting, Singapore 2 nd Oct 2018 2018 PETROLIAM NASIONAL BERHAD

More information

Underground Storage Tank Guidance for Commercial Building Inspectors

Underground Storage Tank Guidance for Commercial Building Inspectors National Association of Commercial Building Inspectors & Thermographers Contributor/Author: John Bowman The content provided in these white papers is intended solely for general information purposes only,

More information

RESOURCE CENTRE GUIDELINES IMPACT MOLING AND RAMMING

RESOURCE CENTRE GUIDELINES IMPACT MOLING AND RAMMING TRENCHLESS RESOURCE CENTRE TECHNOLOGIES TRENCHLESS GUIDELINES TECHNOLOGY SECOND EDITION IMPACT MOLING AND RAMMING UPDATED JUNE 2006 1 OVERVIEW Although the first attempts at producing Impact mole systems

More information