HIGH VOLTAGE TEF 1060 HV ENCLOSURE WITH A-BLOCK SOLUTIONS USER MANUAL
|
|
- Suzan Wilcox
- 5 years ago
- Views:
Transcription
1 HIGH VOLTAGE TEF 1060 HV ENCLOSURE WITH A-BLOCK SOLUTIONS USER MANUAL Subject to change without prior notice TUM5461 REV. B IMPORTANT Read this instruction carefully before installing the product Danger! High Voltage! Do not open when engergized! R. Stahl Tranberg AS E info@stahl-tranberg.com stahl-tranberg.com Main office: Strandsvingen 6 N-4032 Stavanger Norway T F Office Oslo: Luhrtoppen 2 N-1470 Lørenskog Norway T
2 INTRODUCTION Thank you for purchasing this product! For installation, maintenance and assurance of a long life of this product, please follow this manual. APPROVALS Marking to 2014/34/EU: II 2 G Ex eb IIC T4, T5, T6 IECEx PRE Presafe 14ATEX4124 Enclosure solutions with optional technical specifications upon request. These solutions are subject to unit verification certifications or field certifications. SAFETY INSTRUCTION Tranberg High Voltage A-block series 1060 enclosures, are suitable for use in hazardous areas zone 1-2, and also in safe areas. Changes made to the product which do not confirm to the approvals of this equipment, is a safety violation. The manufacturer is under no circumstances responsible for personal injuries, death or any other damage caused by such activities. For replacement and repair of the enclosure only Tranberg AS spare parts may be used. Repair that effects the explosion protection, may only be carried out by Tranberg AS, or a qualified electrician in compliance with the respective national regulation. Notified Body: DNV Nemko Presafe A/S, Norway Fig. 1 MAINTENANCE / REPAIR / MODIFICATION Before opening the enclosure make sure that the power is disconnected. In case of intrinsically safe circuits, working is permitted while voltage applies. Before starting Maintenance, repair or modification, remove safety cover (see figure 1) and measure that there is no high voltage on the terminals. Servicing the enclosure is done by checking the intactness of the enclosure, gasket and glands. If necessary lubricate the lid bolt threads or the quick lock closing with grease type Renolit Unitemp 2 from Fuchs or equal. If repair or overhaul is necessary this may only be done with Tranberg spare parts. Modification of the enclosure or change of design are not permitted, except for installing additional glands and terminals according to the approval of the enclosure.
3 INSTALLATION No spare parts, tools, measuring equipment or any other item shall be stored inside the high voltage enclosure. The inside of the enclosure, terminals and cables shall be clean and dry. If dust or water is present, the enclosure shall be disconnected, earthed, cleaned and measures shall be taken to prevent further ingress of dust or water. Measures should be taken to prevent condensation inside the enclosure. An equipotential bonding wire should always be connected to the enclosure. This is to ensure any fault current shall be lead safely to earth, and that the enclosure in no way may be dangerous to touch. The bonding wire should be of a suitable cross section so that it may safely lead the foreseen fault-current to the ground. Installation is to be performed by skilled personnel, familiar with high voltage installations and regulations, Ex regulations, the ATEX Directive and/or IECEx norms and standards. This includes but is not limited to: IEC/EN , IEC/EN , IEC/EN , company routines and national and international regulations. Ferrules shall always be used on fine-stranded cables. All clearance and creepage distances shall be according to IEC/EN after installation. Regardless of the regulations taking precedence in any installation, a dielectric strength test is highly recommended after installation, before the equipment is put in service. In most cases, this test will be mandatory. Disposal/Recycling: When the apparatus is disposed of, the respective national regulations shall be observed. Mounting The 1060 enclosure must be fastened by 4 pcs. of M10 bolts, or M8 bolt at holes in back of enclosure Connection In order to maintain the mode of protection, the conductors will have to be connected with special care. The insulation must reach up to the terminal and the conductor must not be damage. All screw and nut of the terminals, also those remaining vacant, must be tighten down. For earth connection to stud or bar, cable shoes will have to be used. Only certified cable entries and blinds may be used. Gland has to be chosen according to cable diameter used. To ensure the required minimum protection category glands has to be tighten properly and unused holed has to be closed with certified blinds according to hole diameter. Close and lock door / lid. In case of bolt tight these firmly with suitable tool by hand force. Over tightening may impair the protection category. Important The panel must be mounted vertically to a wall or structure. Make sure to use all four (and sometimes more) fixing points, as the weight of the panel with components inside may be considerable. It is also very important that the rear of the panel stays level, meaning that the fixing points on the structure must be in the same plane. If one or more of the fixing points are out of line, the panel is likely to be bent when fixed to the structure. If the panel is bent it may result in several problems, such as: Fault on IP degree of ingress protection, due to certificate. Water intrusion (uneven pressure on door gaskets) Doors may not close completely or become difficult to open The load on the fixing bolts may not be fully distributed (excessive load on some points) Permanent deformation of the panel
4 CONNECTION DATA FOR PHOENIX CONTACT UT TERMINALS Connection type: Screw connection, Connection in acc.standard : IEC UT Terminal type UT 2,5 UT 4 UT 6 Min./ max. Solid conductor cross section 0,14 mm² - 4 mm² 0,14 mm² - 6 mm² 0,2 mm² - 10 mm² Min./max. Conductor cross section AWG Min./max. Stranded conductor diameter 0,14 mm² - 4 mm² 0,14 mm² - 6 mm² 0,2 mm² - 10 mm² Conductor cross stranded AWG min Conductor cross flexible AWG max with ferrule without plastic sleeve with ferrule with plastic sleeve solid min./max. stranded min./max. stranded, TWIN ferrules with plastic sleeve min./max. stranded, ferrules without plastic sleeve min./max. 0,14 mm² - 2,5 mm² 0,14 mm² - 4 mm² 0,25 mm² - 6 mm² 0,14 mm² - 2,5 mm² 0,14 mm² - 4 mm² 0,25 mm² - 6 mm² 0,14 mm² - 1,5 mm² 0,14 mm² - 1,5 mm² 0,2 mm² - 2,5 mm² 0,14 mm² - 1,5 mm² 0,14 mm² - 1,5 mm² 0,2 mm² - 2,5 mm² 0,5 mm² - 1,5 mm² 0,5 mm² - 2,5 mm² 0,5 mm² - 4 mm² 0,14 mm² - 1,5 mm² 0,14 mm² - 1,5 mm² 0,25 mm² - 1,5 mm² Connection in acc. standard IEC/EN IEC/EN IEC/EN Min./ max. Solid conductor cross section 0,14 mm² - 4 mm² 0,14 mm² - 6 mm² 0,2 mm² - 10 mm² Conductor cross section AWG min. / max Min./ max. stranded conductor diameter 0,14 mm² - 2,5 mm² 0,14 mm² - 4 mm² 0,2 mm² - 6 mm² Stripping length 9 mm 9 mm 10 mm cylindrical gage A3 A4 A5 Screw size M3 M3 M4 Tightening min. 0,5 Nm 0,6 Nm 1,5 Nm Torque max. 0,6 Nm 0,8 Nm 1,8 Nm
5 CONNECTION DATA FOR PHOENIX CONTACT UT TERMINALS Connection type: Screw connection, Connection in acc.standard : IEC UT Terminal type UT 10 UT 16 UT 35 Min./ max. Solid conductor cross section 0,5 mm² - 16 mm² 1,5 mm² - 25 mm² 1,5 mm² - 50 mm² Min./max. Conductor cross section AWG Min./max. Stranded conductor diameter 0,5 mm² - 16 mm² 1,5 mm² - 25 mm² 1,5 mm² - 50 mm² Conductor cross stranded AWG min Conductor cross flexible AWG max with ferrule without plastic sleeve with ferrule with plastic sleeve solid min./max. stranded min./max. stranded, TWIN ferrules with plastic sleeve min./max. stranded, ferrules without plastic sleeve min./max. 0,5 mm² - 10 mm² 1 mm² - 16 mm² 1,5 mm² - 35 mm² 0,5 mm² - 10 mm² 1 mm² - 16 mm² 1,5 mm² - 35 mm² 0,5 mm² - 4 mm² 1 mm² - 6 mm² 1,5 mm² - 16 mm² 0,5 mm² - 4 mm² 1 mm² - 6 mm² 1,5 mm² - 10 mm² 0,5 mm² - 6 mm² 0,75 mm² - 10 mm² 1,5 mm² - 16 mm² 0,5 mm² - 2,5 mm² 1 mm² - 6 mm² 1,5 mm² - 10 mm² Connection in acc. standard IEC/EN IEC/EN IEC/EN Min./ max. Solid conductor cross section 0,5 mm² - 16 mm² 1,5 mm² - 25 mm² 1,5 mm² - 50 mm² Conductor cross section AWG min. / max Min./ max. stranded conductor diameter 0,5 mm² - 10 mm² 1,5 mm² -16 mm² 1,5 mm² - 35 mm² Stripping length 10 mm 14 mm 18 mm cylindrical gage A6 A7 B9 Screw size M4 M5 M6 Tightening min. 1,5 Nm 2,5 Nm 3,2 Nm Torque max. 1,8 Nm 3 Nm 3,7 Nm
6 TECHNICAL DATA Housing: Max voltage: IP-rating: Tamb: Acid proof stainless steel 11000V AC/DC IP66 Note: IP-classification may be different, determinated by components used in enclosure. -20 C C Silicone gasket: -50 C to 60 C Certification: IECEx PRE Presafe 14ATEX4124 Enclosure solutions with optional technical specifications upon request. These solutions are subject to unit verification certifications or field certifications. Compliance with: EN :2012 EN :2007 IEC :2011 IEC :2011 Area of use: Zone 1, Zone 2 and safe area R. Stahl Tranberg AS E info@stahl-tranberg.com stahl-tranberg.com Main office: Strandsvingen 6 N-4032 Stavanger Norway T F Office Oslo: Luhrtoppen 2 N-1470 Lørenskog Norway T
LIGHTING TEF 9964 XENON HELIDECK FLOODLIGHT INDUSTRY SAFE AREA USER MANUAL
Subject to change without prior notice TUM1024 REV. J 14.07.2017 LIGHTING TEF 9964 XENON HELIDECK FLOODLIGHT INDUSTRY SAFE AREA USER MANUAL IMPORTANT Read this instruction carefully before installing the
More informationOperating Instructions
Operating Instructions Terminal Box > 8150/1 > 8150/2 Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2 2.2 Operating Instructions Information...2 3 Intended Use...2 4 Safety
More informationExplosion protected terminal boxes type, GHG 72.
1 Technical data 1.1 Plastic terminal boxes GHG 721... ATX type examination certificate BVS 13 ATX 013 X Marking acc. to 94/9/G and standard ATX x (d e mb) II T5* -55 T amb +55 Gb x (d e mb) II T6* -55
More informationPlugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581
www.stahl.de > Various versions Extra-low voltage up to 16 A 16, 32, 125 A > Large handle, can be locked in position 0 and I > Clear switch position indication > Optimal contact by means of self-cleaning
More informationEVZ Series (Small body) Explosion protected luminaire Operating Instructions
EVZ Series (Small body) Explosion protected luminaire Operating Instructions Cooper Crouse-H i n d s Cooper E l ec t ron i c T ec h n ol og i es ( S h a n g h a i ) Co., L t d. No. 955 Shengli Road, East
More informationEmergency Light Fitting for Fluorescent Lamps Series 6009
> As wall, ceiling and pendant light fitting or pole mounted light fitting > Version with 2 lamps: 18 W and 36 W > Central locking > All-pole disconnection via N/C switch when opening light fitting or
More informationINSTRUCTION MANUAL (ATEX / IECEx)
INSTRUCTION MANUAL (ATEX / IECEx) BExBG10D-P and BExBG15D-P Flameproof Xenon Beacons For use in Flammable Gas and Dust Atmospheres BExBG10D-P / BExBG15D-P 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE
More informationINSTRUCTION MANUAL (ATEX / IECEx)
INSTRUCTION MANUAL (ATEX / IECEx) BExBGL2D LED BEACON For use in Flammable Gas and Dust Atmospheres BExBGL2D 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGIZED POTENTIAL
More informationLinear Luminaire for Fluorescent Lamps Series EXLUX 6401
> As wall, ceiling and pendant light fitting or pole mounted light fitting > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp
More information11mm Slot Label S1 = 162, S2 = 170, S3 = 250, S4 = 305, S5 = 330, S6 = 410, S7 = 490, S8 = 570, S9 = 650. Maximum Power Dissipation (Watts) T** T**
Assembly Instructions for: S1 Assembly to S Junction Instructions Boxes for: MS1 to MS Junction Boxes Boxes MS1 to MS Junction Boxes IMPORTANT: This document should be read carefully before commencing
More informationINSTALLATION AND SERVICE INSTRUCTIONS FOR 2000 SERIES FLAMEPROOF XENON AND FLUORESCENT BEACONS
INSTALLATION AND SERVICE INSTRUCTIONS FOR 2000 SERIES FLAMEPROOF XENON AND FLUORESCENT BEACONS Address all communications and shipments to: FEDERAL SIGNAL CORPORATION Industrial Systems Group 2645 Federal
More informationEmergency Luminaire with LED Series EXLUX 6009/1 Version IIC
> For use in hazardous areas with gas group IIC > Emergency luminaire for wall, ceiling, pendant or pole installation > Latest LED technology with a high luminous efficacy and a long service life > Central
More informationOperating Instructions
Operating Instructions Pendant Light Fitting > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Instructions...3 4 Conformity to Standards...3 5 Intended Field of Application...3
More informationOperating Instructions in accordance with IECEx Scheme rules, IECEx 02 polykom
Operating Instructions in accordance with IECEx Scheme rules, IECEx 02 polykom Page 1 of 9 Rev. A / 2008-06-18 Product group: Empty enclosure polykom Terminal enclosures polykom The basic safety and health
More informationOperating Instructions
Operating Instructions Load and Motor Switch, Load-Break Switch > 8544/1 Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Instructions...3 4 Designated Use...4 5 Technical
More informationOperating Instructions
Operating Instructions Pendant Light Fitting > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Notes Regarding Safety...3 4 Intended Area of Application...4 5 Technical Data...5
More informationOperating Instructions
Operating Instructions Ex UPS Combination of > 8265/5 GUBox control panel > 8316 battery box Contents 1 Contents 1 Contents 2 2 General Information 2 3 Safety Instructions 2 4 Conformity to standards 3
More informationCapanivo Series CN 4000
Capanivo Series CN 4000 Instruction manual 010516 1 UWT GmbH Westendstraße 5 Tel.: +49 (0)831 57123-0 Internet:www.uwt.de D-87488 Betzigau Fax: +49 (0)831 76879 E-Mail: info@uwt.de Scope of this instruction
More informationEmergency Luminaire with LED Series EXLUX 6409/1
> Emergency luminaire for wall, ceiling, pendant or pole installation > Latest LED technology with a high luminous efficacy and a long service life > Central locking system > Weekly functional test > Annually
More informationPlug and Socket Devices SolConeX 16 A Series 8570
Plug and Socket Devices SolConeX 16 A Series 8570 www.stahl.de > Switch socket / plug 16 A > Minimal force required to insert and remove > Can be optionally equipped with an auxiliary contact for control
More informationControl and Terminal Box Type A21-**-*****
e pd Control and Terminal Box Exepd GmbH i_park TAUBERFRANKEN Building 23 Becksteinerstrasse 100 97922 Lauda-Königshofen Germany Phone: ++49 (0) 9343 627055-0 Fax: ++49 (0) 9343 627055-99 Mail: info@exepd.de
More informationInstallation and Operating Instructions
Plastic encased safety interlocking switch Type PSEN me4 Intended use The plastic encased safety switches PSEN me4 with separate actuator are suitable for the mounting on safety guards. They are designated
More informationLinear Luminaire with LED
Linear Luminaire with LED Operating instructions Additional languages www.stahl-ex.com Contents 1 General Information...3 1.1 Manufacturer...3 1.2 Information regarding the operating instructions...3 1.3
More informationOPERATING INSTRUCTIONS
OPERATING INSTRUCTIONS RTECK terminal boxes RTKB series IEC Ex EX010 TECHNICAL FILES CONTENTS: 1) Contents 2) General information 3) Safety information 4) Conformity to standards 5) Function 6) Technical
More informationLinear Luminaire for Fluorescent Lamps
Linear Luminaire for Fluorescent Lamps Operating instructions Additional languages www.stahl-ex.com General Information Contents 1 General Information...2 1.1 Manufacturer...2 1.2 Information regarding
More informationOperating Instructions
Important Information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
More informationClarius EP PLUS LED FLOODLIGHT Installation Guide
Clarius Clarius EP PLUS LED FLOODLIGHT Installation Guide CERTIFICATION: SIRA09ATEX5159X AND IECEx SIR 09.0064X AND ABS 11-LD801943-PDA II 2 G D Ex emb IIC T4 Gb Ex t IIIC T103oC Db IP66/67 T4-20 oc to
More informationSynergEX Panelboards. Installation & Maintenance Information IF Panelboards for Hazardous Locations SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
SynergEX Panelboards Panelboards for Hazardous Locations Installation & Maintenance Information IF 1659 SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE CAUTION Read these operating instructions and all other
More informationPlugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581
Series 8570, 8571, 8575, 8581 www.stahl.de > Various versions 16 A, extra-low voltage 16, 32, 125 A > Large handle, can be locked in position 0 and 1 > Clear switch position indication > Optimal contact
More informationInstallation and Operating Instructions
Plastic encased safety interlocking switch Type PSEN me2/psen me3 Intended use The plastic encased safety switches PSEN me2 and PSEN me3 with separate actuator are suitable for the mounting on safety guards.
More informationLoad and Motor Switches, Load-Break Switches Series 8544
www.stahl.de > Innovative switch concept > State-of-the-art contact arrangement > Easy and clear connection technology > Wiring channel for auxiliary contacts > Retrofittable: Alligator clip Auxiliary
More informationEx UPS standard Series 8265
> Guard battery monitoring according to IEC/EN 60079 et seq. > Adjustable buffer time > Battery function test > Potential-free signal outputs > Maximum efficiency > Increased for reliable triggering of
More informationSERIES 54 Inductive Proximity Sensor
SENSOR FEATURES > 2-wire DC sensor with minimum off-state current > ATEX-approval for zone 2 and zone 22 > High temp, UV, salt water resistant > Rugged metal base > IP66/67/69K > High impact protection
More informationFlameproof Enclosures
Flameproof Enclosures The range comprises many standard sizes of enclosures manufactured in stainless steel 316L and/or in painted carbon steel. The enclosures allow for utilization of standard electrical
More informationDimensions shown apply to both Stainless Steel and Mild Steel S1, SF*1 = 162, S2, SF*2, S2L, SF*2L = 170, S3, SF*3 = 250,
Assembly Instructions for junction boxes type: Assembly Instructions for: S1 to S / SFI1 to SFI / SFE1 to SFE S1 to S Junction Boxes MS1 to MS Junction Boxes IMPORTANT: This document should be read carefully
More informationEx e, ia Junction boxes TNCN. Features
TNCN Features The TNCN/TNCC range comprises many standard sizes of enclosure manufactured in 316L acid resistant stainless steel to give the maximum environmental protection. The main body is manufactured
More informationTechnical Data. Dimensions
Model Number Features 40 mm flush 4-wire DC ATEX-approval for zone 2 and zone 22 S Technical Data specifications Switching element function PNP NO/NC Rated operating distance s n 40 mm Installation flush
More informationPlugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581
www.stahl.de > Various versions 16 A, extra-low voltage 16, 32, 125 A > Large handle, can be locked in position 0 and 1 > Clear switch position indication > Optimal contact by means of self-cleaning laminated
More informationLoad and Motor Switches, Load-Break Switches Series 8549
www.stahl.de > Innovative switch concept > State-of-the-art contact arrangement > Easy and clear connection technology > Wiring channel for auxiliary contacts > Retrofittable: Pick-off terminal block Auxiliary
More informationEC-TYPE EXAMINATION CERTIFICATE (MODULE B)
EC-TYPE EXAMINATION CERTIFICATE (MODULE B) Certificate No: MEDB000025U Revision No: 1 Application of: Directive 2014/90/EU of 23 July 2014 on marine equipment (MED), issued as "Forskrift om Skipsutstyr"
More informationPlugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8579, 8581
Plugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8579, 8581 www.stahl.de > Various versions 16 A, extra-low voltage 16, 32, 63, 125 A > Large handle, can be locked in position 0 and 1 > Clear
More informationLoad disconnect switch Series 8146/5-V11
www.stahl.de Load disconnect switch > Motor switching capacity AC-3 and AC-23 acc. to DIN VDE 0660 part 107 IEC/EN 60947-3 > Isolating characteristics acc. to IEC/EN 60947-3 > Positive opening operation
More informationPosition Switches Series 8070/2
www.stahl.de > Ex e plastic enclosure > Operating temperature range -60 to +60 C > Dimensions and characteristic values according to EN 50041 > Degree of protection IP66 / IP67 > Extensive assortment of
More informationUZK12.261, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 26AH 1/10.
BATTERY MODULE Long Life Battery: 10 to 12 Years According to EUROBAT Small Mounting Footprint Easy Access to the Terminals and the Fuse Heavy Duty Fuse Holder and Spare Fuse Included 3 Year Warranty,
More informationEStrong-series Emergency Stop
Original instructions EStrong-series Emergency Stop ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand
More information2000 Series Flameproof Xenon and Fluorescent Beacons Installation and Service Instructions
2000 Series Flameproof Xenon and Fluorescent Beacons Installation and Service Instructions 2562179B REV. B 818 Printed in USA 2013-2018 Federal Signal Corporation. All rights reserved. Limited Warranty
More informationLinear Luminaire for Fluorescent Lamps Series EXLUX 6001
> As wall, ceiling and pendant light fitting or side entry lamp > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp is opened
More informationUSER MANUAL FOR THE BULKHEAD LIGHT FITTING, TYPE /..
d.o.o. tel. 049 222 900, fax 049 426 450 e-mail: tepex@tepex.hr www.tepex.hr USER MANUAL FOR THE BULKHEAD LIGHT FITTING, TYPE 0403.24/.. No: TEPEx.RS.077 Rev : 0 Date: 02.2016. CONTENT 1. Manufacturer
More informationUZK24.071, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS
BATTERY MODULE 24V, 7Ah Battery Capacity (2x 12V Batteries in Series) Small Mounting Footprint 2m Power Leads Included PT1000 Sensor for Battery Module Temperature Included Includes a Center-tap Terminal
More informationPosition Switches Series 8060/2
www.stahl.de > Ex e plastic enclosure > Operating temperature range -60 to +60 C > Dimensions and characteristic values according to EN 50047 > Degree of protection IP66 / IP67 > Extensive assortment of
More informationEx m Solenoid Operator Type 0519
nass magnet GmbH Eckenerstrasse 4-6 D-30179 Hannover Doc. No. 113-720-0002 Revision No. 2 01.06.2015 Ex m Solenoid Operator Type 0519 Operating Instructions Dear Customer! To ensure the function and for
More informationOperating Instructions (Translation)
Product Description Definition The ANTARES RCU consists of the ANTARES Head Module and the ANTARES Connection Module. The ANTARES Head Module contains a CPU, communication interface and power pack. In
More informationSegurança. Segurança. PSB Heating System Cold applied connection technology. Compulsório. Compulsório. Operation Manual and Installation Instructions
Segurança TC RU C-DE.ГБ06.B.00230 OCP 0004 Compulsório INMETRO Operation Manual and Installation Instructions Segurança PSB Heating System Cold applied connection technology Compulsório Type 27-1680-...0/...
More informationABG Cable Glands Installation Procedure
ABG Cable Glands Installation Procedure ABG Cable Gland Range Baseefa 16ATEX0004X IECEx BAS 16.0011X Installation, Operation and Maintenance Instructions Material: Brass/ Brass with Nickel plated and Stainless
More informationILED Dorado. User Manual
10NM U-code Medium Intensity Obstruction Light Helideck Status Light 15NM U-code Contents 1. Safety... 3 2. Warranty... 3 2.1 General... 3 2.2 Life span... 3 3. Type plate... 4 4. Product Description...
More informationLinear Luminaire with LED Series EXLUX 6002/2 Version IIC
> For use in hazardous areas with gas group IIC > Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or pole mounted light fitting > Central locking
More informationCompact Sheet-Steel Light Fittings Series 6114/1
> As 1- or 3-lamp version > Versions Pendant fitting Wall-mounting fitting Flush mounted fitting > Powder-coated steel or stainless steel > Central lock > All pole disconnection via NC switch in positive
More informationLight Fittings for Fluorescent Lamps Series EXLUX 6000 / 6400
> As pendant light fitting or side entry lamp > Version with 1 or 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp is opened > End of life
More informationSafety Switches Series 8537
Safety Switches www.stahl.de > 3- and 6-pole switches 12 / 16, 25, 40, 63 / 80, 125 / 160, 250, 315, 400, 500 A > Motor switching capacity AC-3 and AC-23 acc. to IEC 60947-3, EN 60947, DIN VDE 0660 part
More informationPendant Light Fitting IEC
Pendant Light Fitting IEC Operating instructions Additional languages www.r-stahl.com Contents 1 General Information...3 1.1 Manufacturer...3 1.2 Information regarding the operating instructions...3 1.3
More information10 Load and Motor Switchgear
10 Load and Motor gear Safety es 01941E00 Safety switches ensure the obligatory isolation of electrical power under condition of equipment cleaning, maintenance and repair. Other methods of isolation,
More informationPower (W) Tamb 40 o C LX1GAM4LB57 5,700 10, T3 T100 o C T4 T85 o C 13
Gamma Floodlight IP66/67 The Gamma is a high output LED floodlight is designed for use in Zone 1 & 21 hazardous areas. The compact design and flexible mounting allows the Gamma to also be used as a lowbay.
More information2/2 Solenoid Cartridge Valve, Size 6
/ Solenoid Cartridge Valve, Size 6 Q max = l/min (.3 gpm), p max = 3 bar (4 psi) Bidirectional leak-proof shutoff, direct acting, with EX-safty solenoid coil Description Valve: Bidirectional leak-proof
More informationOperating Instructions
Operating Instructions Repair Light > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4 6 Transport, Storage and Disposal...6
More informationControl Buttons Series 8082
www.stahl.de > Contact element with 1 NO contact 1 NC contact, positive opening > Contact material silver-nickel or gold-plated > 9 different actuators Push Mushroom push Selector switch Rotary actuator
More informationLinear Luminaire for Fluorescent Lamps Series ECOLUX 6600
> 2-lamp version: 18 W 36 W 58 W > Enclosure in polyester resin, glass fibre reinforced and cover in polycarbonate, impact-resistant > Quick fasteners www.stahl.de 10032E00 The light fittings series 6600
More informationEx-proof proportional relief valves Direct or pilot operated, without transducer - ATEX, IECEx, EAC or CULUS
Table FX1-/E Replaces F6-5 /E E125-16 /E Ex-proof proportional relief valves Direct or pilot operated, without transducer - ATEX, IECEx, EAC or CULUS Valve main body Cartridge Mechanical pressure limiter
More informationLinear Luminaire for Fluorescent Lamps Series ECOLUX METAL 6010/1
> For use in Zones 1, 2, 21, 22 and safe area > 2-lamp version: 18 W 36 W > Housing made of sheet steel or stainless steel SS304 / > Quick fasteners www.stahl.de 15709E00 The light fittings of Series ECOLUX
More informationPlugs and Sockets SolConeX & CES Series 7570, 7571, 7575, 7579, 7581
Plugs and Sockets SolConeX & CES Series 7570, 7571, 7575, 7579, 7581 www.stahl.de > For use in Zones 2 and 22 > Various versions 16 A, extra-low voltage 16, 32, 63, 125 A > Large handle, can be locked
More information8150 Series Terminal Boxes
8150 Series Terminal Boxes TEMINATION eady-term 8150 Terminal Boxes Features Enclosures made of stainless (AISI 304) or (AISI 316L) Optional hinges with cam locks or screws cover Hinged Versions 130 opening
More informationBETA SWITCHES FOR HAZARDOUS AREA
BETA offers complete line of switches for (classified) hazardous locations! The BETA Switch, well known as a safety instrument, adds an extra dimension to industrial safety by having area approval up to
More informationTerminal Boxes TNCN. Explosion protection Marking
Terminal boxes TNCN Terminal Boxes TNCN The TNCN range comprises many standard sizes of enclosures manufactured in stainless steel 316L for maximum environmental protection. The main box is manufactured
More informationYFC. Limit switch. Ex d. 24 operating head types
Ex d YFC Limit switch 24 operating head types - Group IIC - Zone 1, 2, 21, 22 - Aluminium alloy - Easy installation, wiring and maintenance - Durable and safe over time Fastening system Earth screw RAL735
More informationINSTALLATION &SAFETY DATA SHEET
INSTALLATION &SAFETY DATA SHEET TYPE SIZE 1 TO SIZE 9 JUNCTION BOX (S1 to S9 Stainless Steel MS1 to MS9 Mild Steel) IMPORTANT : THIS DOCUMENT SHOULD BE READ CAREFULLY BEFORE COMMENCING INSTALLATION ZONES
More informationLight Fitting for Fluorescent Lamps Series ECOLUX 6600
> 1- or 2-lamp version: 18 W 36 W 58 W > Enclosure in polyester resin, glass fibre reinforced and cover in polycarbonate, impact-resistant > Quick fasteners www.stahl.de 10032E00 The light fittings series
More informationControl Buttons / Switches for Panel Mounting Series 8003
www.stahl.de > Different actuators pushbutton mushroom pushbutton mushroom stay-put button mushroom stay-put button with key lock key-operated button key-operated switch > 2 contact elements > Spring clamp
More informationLight Fitting for Fluorescent Lamps Series ECOLUX 6600
> 1- or 2-lamp version: 18 W 36 W 58 W > Enclosure in polyester resin, glass fibre reinforced and cover in polycarbonate, impact-resistant > Quick fasteners www.stahl.de 10032E00 The light fittings series
More informationGuide for installers. METTLER TOLEDO MultiRange Explosionsproof weighing system with the ID3sTx weighing terminal.
Guide for installers METTLER TOLEDO MultiRange Explosionsproof weighing system with the ID3sTx weighing terminal Hazardous zone ID3sTx weighing terminal LWL Safe zone Dual Channel Fiber Optic Converter
More informationTERMINAL BOXES FOR HARSH & HAZARDOUS ENVIRONMENTS
OSUR CL HA ES EN KILLARK Z LO C SJIC SERIES TERMINAL BOXES FOR HARSH & HAZARDOUS ENVIRONMENTS Screw cover style, with or without continuous hinge 3/16 (5mm) wide flat flange for maximum gasket surface
More informationLinear Luminaire with LED Series EXLUX 6402/2
> Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the
More informationSpec Sheet: IEC309 Panel Socket, Angled 16A IP67. Part Number
Spec Sheet: IEC309 Panel Socket, Angled 16A IP67 Part Numbers Part Number EU67SA316 EU67SA416 EU67SA516 Specification Description IEC309 16A 3 Pin panel socket, angled, IP67 IEC309 16A 4 Pin panel socket,
More informationCompact Sheet-steel Emergency Light Fitting Series 6118/1
www.stahl.de Compact Sheet-steel Emergency Light Fitting > Electronic ballast with integrated emergency light electronics for emergency light mode in case of power failure, charging of battery and automatic
More informationVALIADIS S.A. HELLENIC MOTORS
Explosion proof motors MAK 56-250 (MAKe 63-250) series Groups IIB and IIC Ex db / Ex db e (EPL) executions Gb or Ex tb IIIC (EPL) Db II 2 G, II 2D, 2GD SAFETY INSTRUCTIONS Safety Instructions MAK and MAKe
More informationLED Linear Luminaire Series EXLUX 6402
> Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the
More informationBattery Boxes Series 8316
www.stahl.de > Back-up power supply > Maintenance-free batteries > Low self-discharge > Extremely low gas emissions > Electrolyte-tight > No acid surface coating > Protection against total disch arge >
More informationFlameproof Alternators
Overview Standard automotive type alternators are a continuous potential source of ignition when operated in hazardous atmospheres where combustible concentrations of gas, vapor or dusts may exist. To
More informationLoad and Motor Switches, Load-Break Switches Series 8544
www.stahl.de > Innovative switch concept > State-of-the-art contact arrangement > Easy and clear connection technology > Wiring channel for auxiliary contacts > Retrofittable: alligator clip auxiliary
More informationNumber: TEPEx.RS.067 Rev : 02 Date: Manufacturer General safety information s Purpose Degree of protection 2.
CONTENT 1. Manufacturer 1. 2. General safety information s 1. 3. Purpose 2. 4. Degree of protection 2. 5. Product compliance 2. 6. Table types 2. 7. Technical data 5. 8. Inspection, maintenance, repair
More informationINSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SOLAS LED Luminaire ATEX & IECEx
IOM SOLAS - ZONE 1 Luminaire (ATEX & IECEx) Issue 01 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SOLAS LED Luminaire ATEX & IECEx Important: Please read these instructions carefully before installing
More informationControl Stations & Switches: Control Stations Increased Safety Unicode 2 Series: Pre-drilled Control Stations
Unicode 2 Series: Pre-drilled Control Stations Polamide U43W211 Polyester U23W211 Compliance Data: ATEX IEC and IECEx (Polyester): Stainless Steel U62W229 Aluminum U83W211 ATEX IEC / IECEx CE Ex de IIC
More informationOperation & Maintenance Manual
Operation & Maintenance Manual Submersible pumps type LANDY DWP & Submersible pumps type LANDY DNP Explosion proof version Landustrie Sneek BV Tel. +31 515-486888 Pieter Zeemanstraat 6 Fax +31 515-412398
More informationILED Aquarius Illuminated Windsock. User Manual
Contents 1. Safety... 3 2. Warranty... 3 2.1 General... 3 2.2 Life span... 3 3. Type plate... 4 3.1 The light fitting has a type plate:... 4 3.2 The junction box has a type plate:... 5 4. Product Description...
More informationLIMIT SWITCH Hawkeye - HX Magnetic Solid State Proximity Sensors Installation, Maintenance and Operating Instructions (HX )
LIMIT SWITCH Hawkeye - HX Magnetic Solid State Proximity Sensors Installation, Maintenance and Operating Instructions (HX ) Publication# 03revA Table of Contents Publication# 03revA Table Of Contents...
More informationPosition Switches Series 8074/2
www.stahl.de > Ex e metal enclosure > Operating temperature range -40 C... +70 C > Dimensions and characteristic values according to EN 50041 > Degree of protection IP66 > Extensive assortment of actuators,
More informationFloodlight LED Series 6125
www.stahl.de > Floodlight Zones 1, 2 and 21, 22 with highly efficient LEDs > 3 different light distribution types for adjusting to the illumination task > Enclosure made of sheet steel single powder coated
More informationResistance thermometer For additional thermowell, flameproof enclosure (Ex d) Model TR10-L
Temperature Resistance thermometer For additional thermowell, flameproof enclosure (Ex d) Model TR10-L WIKA data sheet TE 60.12 for further approvals see page 2 Applications Chemical industry Petrochemical
More informationPXN12C DXN25C DXN37C MULTI-CONTACT CONNECTORS 10 A TECHNICAL FEATURES
PXN12C DXN25C DXN37C MULTI-CONTACT CONNECTORS II2 G D Ex e ia or ib IIC FROM 12 TO 37 CONTACTS LOCKING IN CONNECTED OR DISCONNECTED POSITION CORROSION-FREE METAL CASING TECHNICAL FEATURES PXN12C DXN25C
More informationM-0. M-0... series control, monitoring and signalling devices. Ex e
M-0 The new Cortem M-0 series control, monitoring and signalling devices are installed as external accessories on '' enclosures and boards used in any industrial environment where an explosive atmosphere
More informationZS50-PE Screw Clamp Terminal Blocks Ground
Technical Datasheet SNK607D00 Catalogue Page ZS0-PE Screw Clamp Terminal Blocks Ground - Reliable electrical and mechanical contact with the rail that exceeds the requirements of the IEC 60947-7- terminal
More informationNew products Ex Equipment 2015
New products Ex Equipment 2015 ROSE Systemtechnik GmbH ROSE Systemtechnik GmbH was founded in Porta Westfalica, Germany, in 199 and is today one of the world s leading and innovative providers of industrial
More information