1 Assembly Instructions for junction boxes type: Assembly Instructions for: S1 to S / SFI1 to SFI / SFE1 to SFE S1 to S Junction Boxes MS1 to MS Junction Boxes IMPORTANT: This document should be read carefully before commencing installation M1 to M / MFI1 to MFI / MFE1 to MFE AI 2 / Issue W - / Zones of Use for Box - as defined in IEC/EN and IEC/EN Group II Category 1G, for use in Zone 0 (plus Zone 1 and Zone 2). Group II Category 1D, for use in Zone 20 (plus Zone 21 and Zone ). Group II Category 2G, for use in Zone 1 (plus Zone 2). Group II Category 2D, for use in Zone 21 (plus Zone ). Service Temperature: -0 C to +80 C Minimum Installation Temperature: -5 C Certification Details Box : S1 to S, SFI1 to SFI, SFE1 to SFE & MF1 to MF, MFI1 to MFI, MFE1 to MFE II 2G Exe IIC T* Gb, II 2D Extb IIIC T** C Db IP II 2G Exib IIC T* Gb, II 2D Exib IIIC T** C Db IP (N/A c CSA us) II 1G Exia IIC T* Ga, II 1D Exia IIIC T** C Da IP (N/A c CSA us) Baseefa08ATEX0208X / IECEx BAS08.005X IEx.0144X TC RU C-GB.AA87.B c CSA us No: Class I Zone 1 AExe IIC Gb, T5 or T; AExtb IIIC T** C Db; IP, 4X Class 1 Div 2 Group A, B, C, D, T4, T5 or T; 4X This is a certified product which should be installed in line with the Assembly Instructions provided with the product. Failure to follow the Assembly Instructions, or making any changes to the product, may invalidate the product certification. S1, SF*1 = 0, S2, SF*2, S2L, SF*2L, S3, SF*3, S4, S4L, SF*4, SF4L = 0, S5, SF*5, S, SF*, S7, SF*7, S8, SF*8, S, SF* = 2 (Extra Depth: S1, SF*1 = 200, S2, SF*2 to S, SF* - 2) Body Dimensions shown apply to both Stainless Steel and Mild Steel S1, SF*1 = 208, S2, SF*2 = 3, S3, SF*3 = 3, S2L, SF*2L & S4, SF*4 = 423, S5, SF*5 = 423, S4L, SF*4L, S, SF* = 50, S7, SF*7 = 0, S8, SF*8 =, S, SF* = 7 S1, SF*1 = 3, S2, SF*2 = 23, S3, SF*3 = 23, S2L, SF*2L, S4, SF*4 = 373, S5, SF*5 = 373, S4L, SF*4L, S, SF* = 450, S7, SF*7 = 550, S8, SF*8 =, S, SF* = 7 External Flange SFE & MFE Range Only SFE1 to SFE + 44mm S1, SF*1 = 233, S2, SF*2, S2L, SF*2L = 23, S3, SF*3-4, S4, SF*4, S4L, SF*4L = 425, S5, SF*5 = 523, S, SF* =, S7, SF*7 = 70, S8, SF*8 = 880, S, SF* = 00 Cover Hasp ( Dia. 8mm) Gland Plates (up to 2 per face) mm Slot S1, SF*1 = 2, S2, SF*2, S2L, SF*2L = 0, S3, SF*3 = 250, S4, SF*4, S4L, SF*4L = 305, S5, SF*5 = 330,S, SF* = 4, S7, SF*7 = 40, S8, SF*8 = 570, S, SF* = 50 Label SFE & MFE Range (SFE1 to SFE) with External Flange increase dimensions by +44mm Adjustable Clamp Fixed Clamp ± mm Drawings for illustration purposes only M Integral Earth Stud W = Maximum Dissipated Wattage N = No. of s Fitted F = I = Maximum Current W = N x F x I ² N = W / F x I ² I = Sqrt (W / N x F) Note: = of Maximum Conductor (see BS 30 and table below) + Maximum Power Dissipation (Watts) Box S1, SFI1, SFE S2, SFI2, SFE S2L, SFI2L, SFE2L S3, SFI3, SFE3 S4L, SFI4L, SFE4L S5, SFI5, SFE5 S, SFI, SFE S7, SFI7, SFE7 S8, SFI8, SFE8 S, SFI, SFE T* T T** 80 C T*** T* T** T*** T* T** T*** T* T** T*** T* T** T*** T* T** T*** + C T 80 C +55 C T 80 C +5 C T5 80 C + C T5 80 C +55 C T5 80 C +5 C Cable Per (M) S4, SFI4, SFE Connection Solutions Hawke International is a division of Hubbell Ltd. Registered No. 7 in England. Registered Office: Cannon Place, 78 Cannon Street, London EC4N AF. A member of the Hubbell Group of Companies UK Office Oxford Street West, Ashton-Under-Lyne, Lancashire. OL7 0NA. UK Sales: +44 (0) Technical: +44 (0) Fax: +44 (0) sales@ehawke.com For any enquiries within EAC countries, please contact: MACDEM P. O. Box, Moscow, 571, Russia Tel / Fax: office@macdem.ru Website: AI 2 - Issue W / Page 1 of 7

2 SPECIAL CONDITIONS FOR SAFE USE: 1. Unused entry holes shall be fitted with stopping plugs as specified in the empty enclosure certificates Baseefa 08ATEX0207U and IECEx BAS U. The operating temperature range of the enclosure is limited to that of the stopping plug fitted. 2. Only breather / drain devices as specified in the empty enclosure certificates Baseefa 08ATEX0207U and IECEx BAS U may be used with these enclosures. The breather / drain devices must be installed in their correct orientation in either the bottom face or bottom face gland plate of the enclosure. The operating temperature range of the enclosure is limited to that of the breather / drain device fitted. 3. All terminal screws, used and unused, shall be tightened down by the end user. 4. of conductors must extend to within 1mm of the metal of the terminal throat unless specified otherwise on the terminal certificate. 5. No more than one single or multi-stranded lead shall be connected to either side of any terminal unless multiple conductors have been joined in a suitable manner e.g. two conductors into a single insulated bootlace ferrule, or any method indicated on the terminal certificate.. s shall be installed in such a manner that the creepage and clearance distances between the terminal and adjacent components, enclosure walls and covers comply with the requirements of EN for Exe IIC junction boxes, or IEC 007- for Exia IIC / Exib IIC junction boxes, for the rated voltage of the equipment. 7. temperatures must not exceed the operating range specified on the component certificate. 8. All terminals and accessories such as cross-connectors, shall be installed in accordance with the terminal manufacturers instructions.. The maximum voltage, current and dissipated power shown on the rating label must not be exceeded.. When connecting conductors of cross section below the maximum allowed for the particular terminal then the maximum amps per pole must be reduced in line with the maximum amps permitted for a terminal equivalent to the conductor size fitted e.g. if a terminal that can take a sq. mm. conductor at 2 amps is fitted with a sq. mm. conductor then the current shall be reduced to a maximum of amps, or the rating marked on the apparatus label, whichever is the lower.. When metallic and non-metallic trunking is provided inside the junction box, the trunking shall be suitable for use at 80 C, meet the creepage and clearance requirements of EN and not affect the IP rating of the junction box, and the maximum current in any circuit will be limited to 0%.. When a self adhesive certification label is fitted, the minimum ambient temperature shall be - C. When optional additional non-metallic labels greater than 0.2mm thick are fitted, they shall be mounted direct on to the metal enclosure and there shall be at least mm between adjacent non-metallic labels.. Unused entries may be fitted with alternative stopping plugs and/or breather drains to those listed in the schedule. The user is responsible for ensuring that the protection concept temperature class and relevant IP rating are maintained. 14. When the junction box is coated with K-MASS, the maximum permitted current is limited to 80% and there shall be a label stating Warning: Static Hazard, clean only with a damp cloth.. a) When a heater plate is fitted the temperature classification of the junction box is increased to T4 T5 C. b) The junction box shall be fitted with a warning label This enclosure contains more than one power supply. Each power supply shall be isolated elsewhere before opening the main enclosure lid and the internal enclosure lid or equivalent wording. c) The junction box shall be fitted with a warning label The heater plate shall not be energised when the power terminals are energised, or equiivalent wording. This condition is not applicable to the special terminal arrangement in a Size 2 deep junction box do Drg. No: 85. d) The installed cabling / terminals must be positioned at least 50mm away from the heater plate.. When a document pocket is fixed to the inside of the lid, care must be taken by the installer / end user to prevent static build up i.e. plastic wallets must not be used to contain documents inside the enclosure.. When fuse terminals are fitted, the low ambient temperature is limited to -25 C and the junction box becomes a defined arrangement. TO OPEN THE LID: 1. Disconnect power (isolate all circuits). 2. Unlock padlock (if fitted) and remove. 3. Untighten the M lid securing screws. 4. a) Carefully swing the lid back on its hinges ensuring the seal is not displaced or damaged. b) The lid may be removed completely by opening to approximately 1 and lifting off. c) Ensure correct gasket is fitted for area of use. TO CLOSE THE LID: 1. Check that the gasket is correctly secured to the underside of the lid and undamaged. If the lid has been removed, completely reverse the procedure at 4b) ensuring that the correct lid is refitted. 2. Locate and tighten all M lid securing screws into the box body. 3. Replace and lock the padlock on the lid, if required. ENCLOSURE INSTALLATION (EI) a) The IP rating of the enclosure must be maintained for the area of use (e.g. IP* for Zone 21 dust environment) by the use of correct arrangement of cable/gland/sealing arrangements and in accordance with the installation codes as detailed in IEC/EN and these installation instructions. b) Where other certified components are part of the assembly, the user must take account of any limitations listed on relevant certificates. c) The enclosure may be ready supplied with cable entries. Where the customer drills cable entries they must be installed in accordance with the component certificates Baseefa 08ATEX0207U or IEC Ex BAS U and enclosure limitations, these specify a maximum clearance on the entry thread of 0.7mm for plain holes and where adjacent cable entries are installed sufficient clearance must be maintained to allow for the fitting of sealing/retaining washers and the rotation of the cable gland hexagons, and leave a minimum of material between adjacent holes in line with the above certificate number(s). TERMINAL WIRING (TW) a) All wiring must be carried out in accordance with the relevant code of practice and/or instructions e.g. IEC/EN b) When used as a general purpose junction box or marshalling box the circuits carrying currents 1A shall be individually protected against over current such that the protective device operates effectively at no more than 1.45 times the current carrying capacity of the smallest conductor used in that circuit. c) Where a major portion of the terminals are carrying maximum rate current the temperature at the branching point of the conductors may exceed 70 C. Under these circumstances the installer must ensure that the limiting temperature for the cable insulation used is acceptable e.g. 85 C (T) or 0 C (T5). AI 2 - Issue W / Page 2 of 7

3 EARTHING: a) Where there is a requirement for bonding of gland plate, this can be achieved by using earthtags on the outside of the enclosure in conjunction with cable glands or by use of gland plates and enclosure lids with factory fitted earth studs. In the case of painted boxes, consideration must be given to the removal of the paint. e.g. under a serrated washer on the inside of the box which may lead to corrosion of the enclosure and potential reduction in earthing protection. This area must be protected against corrosion following installation. SCHEDULE OF TERMINALS FITTED S1, SFI1 & SFE1 Capacity Data Content Reduced Content at Maximum WDU WDU SAKK ** * Complete with cover Note: s listed (with the exception of **) are only suitable for a minimum operating temperature of -50 C SAKK terminals are suitable for -0 C WDU WDU * Complete with cover S2, SFI2 & SFE2 Capacity Data Content Reduced Content at Maximum SAKK ** Bolt Size M Note: s listed (with the exception of **) are only suitable for a minimum operating temperature of -50 C SAKK terminals are suitable for -0 C S2, SFI2L & SFE2L Capacity Data Content Reduced Content at Maximum WDU WDU WDU50N Bolt Size M SAKK ** * Complete with cover AI 2 - Issue W / Page 3 of 7

4 WDU WDU SAKK ** S3, SFI3 & SFE3 Capacity Data Content Reduced Content at Maximum Bolt Size M * Complete with cover Note: s listed (with the exception of **) are only suitable for a minimum operating temperature of -50 C SAKK terminals are suitable for -0 C WDU WDU WDU70/5 WDU70/5 WDU0/0 WDU0/0 WFF0 * SAKK ** S4, SFI4 & SFE4 Capacity Data Content Reduced Content at Maximum Bolt Size M Bolt Size M * Complete with cover Note: s listed (with the exception of **) are only suitable for a minimum operating temperature of -50 C SAKK terminals are suitable for -0 C WDU WDU WFF0 * SAKK ** S4L, SFI4L & SFE4L Capacity Data Content Reduced Content at Maximum WDU WDU70/ WDU70/ WDU0/ WDU0/ Bolt Size M Bolt Size M * Complete with cover Note: s listed (with the exception of **) are only suitable for a minimum operating AI 2 - Issue W / Page 4 of 7 temperature of -50 C SAKK terminals are suitable for -0 C

5 S5, SFI5 & SFE5 Capacity Data WDU WDU WDU70/5 WDU70/5 WDU0/0 WDU0/0 WFF0 * SAKK ** Content Reduced Content at Maximum Bolt Size M Bolt Size M * Complete with cover Note: s listed (with the exception of **) are only suitable for a minimum operating temperature of -50 C SAKK terminals are suitable for -0 C S, SFI & SFE Capacity Data WDU WDU WDU70/5 WDU70/5 WDU0/0 WDU0/0 WFF0 * WFF5 * SAKK ** Content Reduced Content at Maximum Bolt Size M Bolt Size M Bolt Size M Bolt Size M * Complete with cover AI 2 - Issue W / Page 5 of 7

6 S7, SFI7 & SFE7 Capacity Data WDU WDU WDU70/5 WDU70/5 WDU0/0 WDU0/0 WFF0 * WFF5 * SAKK ** Content Reduced Content at Maximum Bolt Size M Bolt Size M Bolt Size M Bolt Size M * Complete with cover Note: s listed (with the exception of **) are only suitable for a minimum operating temperature of -50 C SAKK terminals are suitable for -0 C S8, SFI8 & SFE8 Capacity Data WDU WDU WDU70/5 WDU70/5 WDU0/0 WDU0/0 WFF0 * WFF5 * SAKK ** Content Reduced Content at Maximum Bolt Size M Bolt Size M Bolt Size M Bolt Size M * Complete with cover Note: s listed (with the exception of **) are only suitable for a minimum operating temperature of -50 C SAKK terminals are suitable for -0 C AI 2 - Issue W / Page of 7

7 WDU WDU WDU70/5 WDU70/5 WDU0/0 WDU0/0 WFF0 * WFF5 * SAKK ** S, SFI & SFE Capacity Data Content Reduced Content at Maximum Bolt Size M Bolt Size M Bolt Size M Bolt Size M * Complete with cover Note: s listed (with the exception of **) are only suitable for a minimum operating temperature of -50 C SAKK terminals are suitable for -0 C BARTEC FUSE / TERMINALS Technical Data - Physical Features Bartec Fuse J2/JM J2/KM J2/JT J2/KT 1.A medium time lag 2.0A medium time lag 1.A time lag 2.0A time lag Nominal Voltage Electric Connections Screw for Std. Ferrule s mm2, solid Nm 8mm s mm2, fine stranded EU Declaration of Conformity in accordance with European Directive 2014/34/EU Manufacturer: Hawke International Address: Oxford Street West, Ashton-under-Lyne, OL7 0NA, United Kingdom Equipment: Range of Stainless and Mild Steel Boxes S1 to S & M1 to M SFI1 to SFI & MFI1 to MFI SFE1 to SFE & MFE1 to MFE Provisions of the Directive fulfilled by the Equipment: Group II Category 2G Exe IIC T* Gb, II 2D Extb IIIC T** C Db IP Group II Category 2G Exib IIC T* Gb, II 2D Exib IIIC T** C Db IP Group II Category 1G Exia IIC T* Ga, II 1D Exia IIIC T** C Da IP Notified Body for EU- Examination: Baseefa Buxton UK EU-type Examination Certificate: Baseefa08ATEX0208X Notified Body for production: SGS-Baseefa Buxton UK Harmonized Standards used: EN 007-0:20+A:20, EN007-7:2007, EN007-:20 EN007-31:2014 On behalf of the above named company, I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment conforms with all technical and regulatory requirements of the above listed directives.. A. Tindall Technical Manager AI 2 - Issue W / Page 7 of 7

11mm Slot Label S1 = 162, S2 = 170, S3 = 250, S4 = 305, S5 = 330, S6 = 410, S7 = 490, S8 = 570, S9 = 650. Maximum Power Dissipation (Watts) T** T**

11mm Slot Label S1 = 162, S2 = 170, S3 = 250, S4 = 305, S5 = 330, S6 = 410, S7 = 490, S8 = 570, S9 = 650. Maximum Power Dissipation (Watts) T** T** Assembly Instructions for: S1 Assembly to S Junction Instructions Boxes for: MS1 to MS Junction Boxes Boxes MS1 to MS Junction Boxes IMPORTANT: This document should be read carefully before commencing

More information

INSTALLATION &SAFETY DATA SHEET

INSTALLATION &SAFETY DATA SHEET INSTALLATION &SAFETY DATA SHEET TYPE SIZE 1 TO SIZE 9 JUNCTION BOX (S1 to S9 Stainless Steel MS1 to MS9 Mild Steel) IMPORTANT : THIS DOCUMENT SHOULD BE READ CAREFULLY BEFORE COMMENCING INSTALLATION ZONES

More information

IECEx Certificate of Conformity

IECEx Certificate of Conformity T ~ IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate

More information

POWER CONNECTOR TERMINATION / HOOK UP PROCEDURE

POWER CONNECTOR TERMINATION / HOOK UP PROCEDURE Power POWER CONNECTOR TERMINATION / HOOK UP PROCEDURE (AI365 Rev 7 15Nov16) Hawke International UK Office, Oxford Street West, Ashton-under-Lyne, Lancashire. OL7 0NA. UK Sales: +44 (0) 161 830 6698 Technical:

More information

LIVE DEMATEABLE CONNECTOR TERMINATION / HOOK UP PROCEDURE

LIVE DEMATEABLE CONNECTOR TERMINATION / HOOK UP PROCEDURE Instrum LIVE DEMATEABLE CONNECTOR TERMINATION / HOOK UP PROCEDURE (AI364 Rev 11 05Oct17) Hawke International UK Office, Oxford Street West, Ashton-under-Lyne, Lancashire. OL7 0NA. UK Sales: +44 (0) 161

More information

E A E xe ENCLOSURES. For Harsh & Hazardous Environments.

E A E xe ENCLOSURES. For Harsh & Hazardous Environments. E A E xe ENCLOSURES For Harsh & Hazardous Environments www.ehawke.com Connecting you through innovation Experienced With over 60 years experience protecting people and assets in the world s most demanding

More information

AI352 ATEX INLINE CONNECTOR TERMINATION PROCEDURE

AI352 ATEX INLINE CONNECTOR TERMINATION PROCEDURE IMPORTANT NOTE Hawke International does not recommend the use of their ControlEx Connectors in applications where rigid PVC / SWA / PVC power cabling (typically to BS 6346 standards) is used in portable

More information

IECEx Certificate of Conformity

IECEx Certificate of Conformity Certificate of Conformity: IECEx BAS 07.0033X http://iecex.iec.ch/iecex/iecexweb.nsf/fc034777969a786bc1256d42005bd791/9e9052... Page 1 of 4 18/06/2008 IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS RTECK terminal boxes RTKB series IEC Ex EX010 TECHNICAL FILES CONTENTS: 1) Contents 2) General information 3) Safety information 4) Conformity to standards 5) Function 6) Technical

More information

Cubo X Stainless Steel Enclosures

Cubo X Stainless Steel Enclosures Cubo X Stainless Steel Enclosures for Zones 1, 21, 2 & 22 Material ilecsys Ex Terminal Enclosures are manufactured from stainless steel AISI 316L, suitable for the most demanding of conditions. Our enclosures

More information

AI352 ATEX INLINE CONNECTOR TERMINATION PROCEDURE (Rev 6 02May07)

AI352 ATEX INLINE CONNECTOR TERMINATION PROCEDURE (Rev 6 02May07) IMPORTANT NOTE Hawke International does not recommend the use of their ControlEx Connectors in applications where rigid PVC / SWA / PVC power cabling (typically to BS 6346 standards) is used in portable

More information

Clarius EP PLUS LED FLOODLIGHT Installation Guide

Clarius EP PLUS LED FLOODLIGHT Installation Guide Clarius Clarius EP PLUS LED FLOODLIGHT Installation Guide CERTIFICATION: SIRA09ATEX5159X AND IECEx SIR 09.0064X AND ABS 11-LD801943-PDA II 2 G D Ex emb IIC T4 Gb Ex t IIIC T103oC Db IP66/67 T4-20 oc to

More information

Terminal Boxes in Stainless Steel SLS**.T

Terminal Boxes in Stainless Steel SLS**.T Features Variant options Stainless steel enclosures Suitable for installation in Zones 0, 1, 2, 21 and 22 Certified Ex e, Ex ia and Ex tb 6 enclosure size options Various terminal and cable gland configurations

More information

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX / IECEx) INSTRUCTION MANUAL (ATEX / IECEx) BExBG10D-P and BExBG15D-P Flameproof Xenon Beacons For use in Flammable Gas and Dust Atmospheres BExBG10D-P / BExBG15D-P 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE

More information

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX / IECEx) INSTRUCTION MANUAL (ATEX / IECEx) BExBGL2D LED BEACON For use in Flammable Gas and Dust Atmospheres BExBGL2D 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGIZED POTENTIAL

More information

Operating Instructions

Operating Instructions Operating Instructions Terminal Box > 8150/1 > 8150/2 Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2 2.2 Operating Instructions Information...2 3 Intended Use...2 4 Safety

More information

EVZ Series (Small body) Explosion protected luminaire Operating Instructions

EVZ Series (Small body) Explosion protected luminaire Operating Instructions EVZ Series (Small body) Explosion protected luminaire Operating Instructions Cooper Crouse-H i n d s Cooper E l ec t ron i c T ec h n ol og i es ( S h a n g h a i ) Co., L t d. No. 955 Shengli Road, East

More information

JBEP Series Fiberglass Reinforced Polyester Terminal Junction Boxes for Instrumentation Applications Increased Safety. Factory Drilled and Equipped

JBEP Series Fiberglass Reinforced Polyester Terminal Junction Boxes for Instrumentation Applications Increased Safety. Factory Drilled and Equipped Enclosures and Junction Boxes Enclosures and Junction Boxes: Hazardous Location Outlet Boxes Applications Instrumentation junction boxes are used to run process or remote information to control room. For

More information

Ex m Solenoid Operator Type 0519

Ex m Solenoid Operator Type 0519 nass magnet GmbH Eckenerstrasse 4-6 D-30179 Hannover Doc. No. 113-720-0002 Revision No. 2 01.06.2015 Ex m Solenoid Operator Type 0519 Operating Instructions Dear Customer! To ensure the function and for

More information

Load and Motor Switches, Load-Break Switches Series 8549

Load and Motor Switches, Load-Break Switches Series 8549 www.stahl.de > Innovative switch concept > State-of-the-art contact arrangement > Easy and clear connection technology > Wiring channel for auxiliary contacts > Retrofittable: Pick-off terminal block Auxiliary

More information

Thermocouple For additional thermowell, flameproof enclosure (Ex d) Model TC10-L

Thermocouple For additional thermowell, flameproof enclosure (Ex d) Model TC10-L Temperature Thermocouple For additional thermowell, flameproof enclosure (Ex d) Model TC10-L WIKA data sheet TE 65.12 for further approvals see page 2 Applications Chemical industry Petrochemical industry

More information

Ex d. S.1 series. - Zone 1, 2, 21, 22 - Group IIC - Aluminium junction boxes - Wide selection of models - IP66 / 67. SSC series

Ex d. S.1 series. - Zone 1, 2, 21, 22 - Group IIC - Aluminium junction boxes - Wide selection of models - IP66 / 67. SSC series Ex d S S.1 series - Zone 1, 2, 21, 22 - Group IIC - Aluminium junction boxes - Wide selection of models - IP66 / 67 SSC series Temperature sensor box SWS series SF series A.117 S... series Junction boxes

More information

TERMINAL BOXES FOR HARSH & HAZARDOUS ENVIRONMENTS

TERMINAL BOXES FOR HARSH & HAZARDOUS ENVIRONMENTS OSUR CL HA ES EN KILLARK Z LO C SJIC SERIES TERMINAL BOXES FOR HARSH & HAZARDOUS ENVIRONMENTS Screw cover style, with or without continuous hinge 3/16 (5mm) wide flat flange for maximum gasket surface

More information

Segurança. Segurança. PSB Heating System Cold applied connection technology. Compulsório. Compulsório. Operation Manual and Installation Instructions

Segurança. Segurança. PSB Heating System Cold applied connection technology. Compulsório. Compulsório. Operation Manual and Installation Instructions Segurança TC RU C-DE.ГБ06.B.00230 OCP 0004 Compulsório INMETRO Operation Manual and Installation Instructions Segurança PSB Heating System Cold applied connection technology Compulsório Type 27-1680-...0/...

More information

CCAI, CCAIF, CCAIF..H

CCAI, CCAIF, CCAIF..H CCAI, CCAIF, CCAIF..H - Zone 1, 2, 21, 22 - Group IIC - Stainless steel junction boxes - Choice of 4 sizes - IP66 AISI 316L stainless steel Grub screws for opening lid Lid opening system Detail of inside

More information

HIGH VOLTAGE TEF 1060 HV ENCLOSURE WITH A-BLOCK SOLUTIONS USER MANUAL

HIGH VOLTAGE TEF 1060 HV ENCLOSURE WITH A-BLOCK SOLUTIONS USER MANUAL HIGH VOLTAGE TEF 1060 HV ENCLOSURE WITH A-BLOCK SOLUTIONS USER MANUAL Subject to change without prior notice TUM5461 REV. B 20.07.2017 IMPORTANT Read this instruction carefully before installing the product

More information

Load and Motor Switches, Load-Break Switches Series 8544

Load and Motor Switches, Load-Break Switches Series 8544 www.stahl.de > Innovative switch concept > State-of-the-art contact arrangement > Easy and clear connection technology > Wiring channel for auxiliary contacts > Retrofittable: alligator clip auxiliary

More information

Load disconnect switch Series 8146/5-V11

Load disconnect switch Series 8146/5-V11 www.stahl.de Load disconnect switch > Motor switching capacity AC-3 and AC-23 acc. to DIN VDE 0660 part 107 IEC/EN 60947-3 > Isolating characteristics acc. to IEC/EN 60947-3 > Positive opening operation

More information

GuaRdboX - Gd series IOM (Installation, Operation & Maintenance Manual) 0100-ENG rev.4

GuaRdboX - Gd series IOM (Installation, Operation & Maintenance Manual) 0100-ENG rev.4 1. Introduction: This instruction manual contains important information regarding the safety instructions, installation, operation, maintenance and storage of the Guardbox limit switch boxes. The limit

More information

Hazardous Area Electrical Equipment. TBKF/CBKF Stainless Steel Flat Roof Keyed Terminal Box Zones 1&2, 21&22. Index

Hazardous Area Electrical Equipment. TBKF/CBKF Stainless Steel Flat Roof Keyed Terminal Box Zones 1&2, 21&22. Index Hazardous Area Electrical Equipment Made TBKF/CBKF Stainless Steel Flat Roof Keyed Terminal Box Zones 1&2, 21&22 Index Dimension Sheet Catalogue Information Leaflet Web Links TBKF/CBKF Information Page

More information

Floodlight Range Installation Guide

Floodlight Range Installation Guide SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected

More information

HTSB system System overview

HTSB system System overview HTSB system System overview Easy planning of heating circuits Simple installation on site Wide operating temperature range The BARTEC HTSB heating system covers a wide range of applications in trace heating.

More information

Terminal Boxes TNCN. Explosion protection Marking

Terminal Boxes TNCN. Explosion protection Marking Terminal boxes TNCN Terminal Boxes TNCN The TNCN range comprises many standard sizes of enclosures manufactured in stainless steel 316L for maximum environmental protection. The main box is manufactured

More information

2.4. Ex-Emergency light fittings with a self-contained battery system for fluorescent lamps

2.4. Ex-Emergency light fittings with a self-contained battery system for fluorescent lamps .4 Ex-Emergency light fittings with a self-contained battery system for fluorescent lamps ellk 18/18 NE / ellk 36/36 NE / ellm 18/18 NE (Zone 1,, 1, ) If you need a reliable and decentralized emergency

More information

5.1. GHG 26 / EXKO 2.. Ex-Safety Switches Rated current from 10 A A

5.1. GHG 26 / EXKO 2.. Ex-Safety Switches Rated current from 10 A A .1 GHG 26 / EXKO 2.. Ex-Safety Switches Rated current from 10 A - 630 A Safety for your protection CEAG safety switches can be protected against inadvertent switching on by our integrated locking facility

More information

Assembly. Trunk IN + - S U, I U, I. Spur 1

Assembly. Trunk IN + - S U, I U, I. Spur 1 FieldBarrier FD0-FB-Ex.* Features Assembly outputs Ex ia IIC FieldBarrier in Zone /Div. Instruments in Zone 0.../Div. Short circuit current limitation per output For FOUNDATION Fieldbus H and PROFIBUS

More information

Terminal Boxes Series 8125

Terminal Boxes Series 8125 Series > Wide product range > Enclosure of electropolished stainless steel.0 (AISI L) or galvanised steel sheet painted > basic enclosure sizes various heights > Fitted according to the customer's requirements

More information

Segurança. Segurança. MSB/HSB Heating System. Compulsório. Compulsório. Operation Manual/Installation Instructions. Cold applied connection technology

Segurança. Segurança. MSB/HSB Heating System. Compulsório. Compulsório. Operation Manual/Installation Instructions. Cold applied connection technology Segurança TC RU C-DE.ГБ06.B.00230 OCP 0004 Compulsório INMETRO Operation Manual/Installation Instructions Segurança MSB/HSB Heating System Cold applied connection technology Compulsório Type 27-1.80-...0/...

More information

TBKS/CBKS Stainless Steel Sloping Roof Keyed Terminal Box Zones 1&2, 21&22

TBKS/CBKS Stainless Steel Sloping Roof Keyed Terminal Box Zones 1&2, 21&22 Hazardous Area Electrical Equipment TBKS/CBKS Stainless Steel Sloping Roof Keyed Terminal Box Zones 1&2, 21&22 Index Dimension Sheet Catalogue Information Leaflet Web Links TBKS/CBKS Information Page Ask

More information

Junction Boxes & Enclosures JBES and ECES Series: 316L Stainless Steel Enclosures Increased Safety

Junction Boxes & Enclosures JBES and ECES Series: 316L Stainless Steel Enclosures Increased Safety JBES Series Medium Voltage 11 kv ECES Series Compliance Data: ATEX - IEC: ATEX IEC CE Ex e II Ex ia IIC; Ex ib IIC T6 to T4 Ex td A21 T80 C to T130 C Ex de IIC; Ex demb IIC Operating Temperatures: -50

More information

Resistance thermometer For additional thermowell, flameproof enclosure (Ex d) Model TR10-L

Resistance thermometer For additional thermowell, flameproof enclosure (Ex d) Model TR10-L Temperature Resistance thermometer For additional thermowell, flameproof enclosure (Ex d) Model TR10-L WIKA data sheet TE 60.12 for further approvals see page 2 Applications Chemical industry Petrochemical

More information

SPOOL VALVES solenoid air operated 1/4 to 1/2 tapped body and NAMUR for integrated pilot

SPOOL VALVES solenoid air operated 1/4 to 1/2 tapped body and NAMUR for integrated pilot SPOOL VALVES operated / to / tapped body and NAMUR for integrated pilot ATEX /-/ Series - FEATURES The valves offer environmental protection against the ingress of liquids, dusts or other foreign matter

More information

SynergEX Panelboards. Installation & Maintenance Information IF Panelboards for Hazardous Locations SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

SynergEX Panelboards. Installation & Maintenance Information IF Panelboards for Hazardous Locations SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE SynergEX Panelboards Panelboards for Hazardous Locations Installation & Maintenance Information IF 1659 SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE CAUTION Read these operating instructions and all other

More information

Position Switches Series 8060/2

Position Switches Series 8060/2 www.stahl.de > Ex e plastic enclosure > Operating temperature range -60 to +60 C > Dimensions and characteristic values according to EN 50047 > Degree of protection IP66 / IP67 > Extensive assortment of

More information

Thermocouple For additional thermowell Model TC10-B

Thermocouple For additional thermowell Model TC10-B Temperature Thermocouple For additional thermowell Model TC10-B WIKA data sheet TE 65.02 for further approvals see page 2 Applications Machine building, plant and vessel construction Energy and power plant

More information

USER MANUAL FOR THE BULKHEAD LIGHT FITTING, TYPE /..

USER MANUAL FOR THE BULKHEAD LIGHT FITTING, TYPE /.. d.o.o. tel. 049 222 900, fax 049 426 450 e-mail: tepex@tepex.hr www.tepex.hr USER MANUAL FOR THE BULKHEAD LIGHT FITTING, TYPE 0403.24/.. No: TEPEx.RS.077 Rev : 0 Date: 02.2016. CONTENT 1. Manufacturer

More information

Technical Data. Dimensions

Technical Data. Dimensions Model Number Features 40 mm flush 4-wire DC ATEX-approval for zone 2 and zone 22 S Technical Data specifications Switching element function PNP NO/NC Rated operating distance s n 40 mm Installation flush

More information

Plugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581

Plugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581 www.stahl.de > Various versions Extra-low voltage up to 16 A 16, 32, 125 A > Large handle, can be locked in position 0 and I > Clear switch position indication > Optimal contact by means of self-cleaning

More information

Zone 1 Linear Range - Installation Guide

Zone 1 Linear Range - Installation Guide Zone 1 Linear Range - Installation Guide CML14ATEX3119 & IEC Ex CML15.0001 This installation guide provides instructions for installing SPARTAN series of explosion protected Zone 1 Linear luminaires. Text

More information

Position Switches Series 8074/2

Position Switches Series 8074/2 www.stahl.de > Ex e metal enclosure > Operating temperature range -40 C... +70 C > Dimensions and characteristic values according to EN 50041 > Degree of protection IP66 > Extensive assortment of actuators,

More information

ANNEX to IECEx BAS X Issue No. 0 Date: 27/02/2012

ANNEX to IECEx BAS X Issue No. 0 Date: 27/02/2012 The range of GRP terminal boxes consists of a range of empty enclosures that are component certified. The range of terminal boxes is listed in the table below; Box Type GRP 80 GRP 110 OGRP 122 GRP 122

More information

Operating Instructions

Operating Instructions Important Information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect

More information

ILED Dorado. User Manual

ILED Dorado. User Manual 10NM U-code Medium Intensity Obstruction Light Helideck Status Light 15NM U-code Contents 1. Safety... 3 2. Warranty... 3 2.1 General... 3 2.2 Life span... 3 3. Type plate... 4 4. Product Description...

More information

Plug and Socket Devices SolConeX 16 A Series 8570

Plug and Socket Devices SolConeX 16 A Series 8570 Plug and Socket Devices SolConeX 16 A Series 8570 www.stahl.de > Switch socket / plug 16 A > Minimal force required to insert and remove > Can be optionally equipped with an auxiliary contact for control

More information

Linear Luminaire for Fluorescent Lamps Series ECOLUX 6600

Linear Luminaire for Fluorescent Lamps Series ECOLUX 6600 > 2-lamp version: 18 W 36 W 58 W > Enclosure in polyester resin, glass fibre reinforced and cover in polycarbonate, impact-resistant > Quick fasteners www.stahl.de 10032E00 The light fittings series 6600

More information

Terminal Boxes Series 8125

Terminal Boxes Series 8125 Series > Wide product range > Enclosure of electropolished stainless steel.0 (AISI L) or galvanised steel sheet > basic enclosure sizes various heights > Fitted according to the customer's requirements

More information

ANNEX to IECEx BAS X Issue No. 0 Date: 15/05/2012

ANNEX to IECEx BAS X Issue No. 0 Date: 15/05/2012 The range of stainless steel terminal boxes consists of a range of empty enclosures that are component certified under certificates IECEx DNV 11.0005UDNV11ATEX98909U. The range of terminal boxes is listed

More information

Operating Instructions

Operating Instructions Operating Instructions Pendant Light Fitting > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Instructions...3 4 Conformity to Standards...3 5 Intended Field of Application...3

More information

Ex e, ia Junction boxes TNCN. Features

Ex e, ia Junction boxes TNCN.   Features TNCN Features The TNCN/TNCC range comprises many standard sizes of enclosure manufactured in 316L acid resistant stainless steel to give the maximum environmental protection. The main body is manufactured

More information

Operating Instructions

Operating Instructions Operating Instructions Repair Light > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4 6 Transport, Storage and Disposal...6

More information

Resistance thermometer Without thermowell Model TR10-H

Resistance thermometer Without thermowell Model TR10-H Temperature Resistance thermometer Without thermowell Model TR10-H WIKA data sheet TE 60.08 for further approvals see page 2 Applications For direct installation into the process Machine building Motors

More information

IECEx Certificate of Conformity

IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate No.: Certificate history: Status:

More information

Operating Instructions

Operating Instructions Operating Instructions Load and Motor Switch, Load-Break Switch > 8544/1 Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Instructions...3 4 Designated Use...4 5 Technical

More information

Ex-proof proportional relief valves Direct or pilot operated, without transducer - ATEX, IECEx, EAC or CULUS

Ex-proof proportional relief valves Direct or pilot operated, without transducer - ATEX, IECEx, EAC or CULUS Table FX1-/E Replaces F6-5 /E E125-16 /E Ex-proof proportional relief valves Direct or pilot operated, without transducer - ATEX, IECEx, EAC or CULUS Valve main body Cartridge Mechanical pressure limiter

More information

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SOLAS LED Luminaire ATEX & IECEx

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SOLAS LED Luminaire ATEX & IECEx IOM SOLAS - ZONE 1 Luminaire (ATEX & IECEx) Issue 01 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SOLAS LED Luminaire ATEX & IECEx Important: Please read these instructions carefully before installing

More information

OPERATION AND MAINTENANCE INSTRUCTIONS

OPERATION AND MAINTENANCE INSTRUCTIONS ATEX LED WORKLITE WL-85, WL-80 OPERATION AND MAINTENANCE INSTRUCTIONS CONTENTS EU Declaration of Conformity 3 Approval Codes/Certification 3 IECEx Scheme Certification 3 Special Conditions of Use (X Condition)

More information

Light Fitting for Fluorescent Lamps Series ECOLUX 6600

Light Fitting for Fluorescent Lamps Series ECOLUX 6600 > 1- or 2-lamp version: 18 W 36 W 58 W > Enclosure in polyester resin, glass fibre reinforced and cover in polycarbonate, impact-resistant > Quick fasteners www.stahl.de 10032E00 The light fittings series

More information

Safety Switches Series 8537

Safety Switches Series 8537 Safety Switches www.stahl.de > 3- and 6-pole switches 12 / 16, 25, 40, 63 / 80, 125 / 160, 250, 315, 400, 500 A > Motor switching capacity AC-3 and AC-23 acc. to IEC 60947-3, EN 60947, DIN VDE 0660 part

More information

Thermocouple Without thermowell Model TC10-H

Thermocouple Without thermowell Model TC10-H Temperature Thermocouple Without thermowell Model TC10-H WIKA data sheet TE 65.08 for further approvals see page 2 Applications For direct installation into the process Machine building Motors Bearing

More information

Explosion Protected Group IIB Zone 1 Ex d Ring Enclosure Ex e Terminal Boxes Hollow Shaft Option OPERATING SPECIFICATION TECHNICAL DETAILS

Explosion Protected Group IIB Zone 1 Ex d Ring Enclosure Ex e Terminal Boxes Hollow Shaft Option OPERATING SPECIFICATION TECHNICAL DETAILS Ex d Ring Enclosure Ex e Terminal Boxes Hollow Option Ambient Temperature Maximum Throughput Current Protection Mounting (increased range available) 20 rpm (higher on request) 770V ac 1166 Amps In any

More information

M-0. M-0... series control, monitoring and signalling devices. Ex e

M-0. M-0... series control, monitoring and signalling devices. Ex e M-0 The new Cortem M-0 series control, monitoring and signalling devices are installed as external accessories on '' enclosures and boards used in any industrial environment where an explosive atmosphere

More information

Solutions Ex d IIB+H2, Stainless Steel EJBX*

Solutions Ex d IIB+H2, Stainless Steel EJBX* Features Assembly Examples Enclosures manufactured from AISI 316L stainless steel Suitable for operation in Zones 1, 2, 21 and 22 Certified Ex d IIB+H2 and Ex tb More than 20 enclosure size options Free

More information

Segurança. Segurança. PSB Heating System Heat shrink technology. Compulsório. Compulsório. Operation Manual/Installation Instructions

Segurança. Segurança. PSB Heating System Heat shrink technology. Compulsório. Compulsório. Operation Manual/Installation Instructions Segurança TC RU C-DE.ГБ06.B.00230 OCP 0004 Compulsório INMETRO Operation Manual/Installation Instructions Segurança PSB Heating System Heat shrink technology Compulsório Type 27-1680-...0/... OCP 0004

More information

Position Switches Series 8070/2

Position Switches Series 8070/2 www.stahl.de > Ex e plastic enclosure > Operating temperature range -60 to +60 C > Dimensions and characteristic values according to EN 50041 > Degree of protection IP66 / IP67 > Extensive assortment of

More information

Ex eb IIC Gb Ex ia IIC Ga Ex Tb IIIC Db DRILLING AND ASSEMBLY OF JBEP JUNCTION BOXES AND ENCLOSURES GUIDE

Ex eb IIC Gb Ex ia IIC Ga Ex Tb IIIC Db DRILLING AND ASSEMBLY OF JBEP JUNCTION BOXES AND ENCLOSURES GUIDE Ex eb IIC Gb Ex ia IIC Ga Ex Tb IIIC Db DRILLING AND ASSEMBLY OF JBEP JUNCTION BOXES AND ENCLOSURES GUIDE To easily accommodate your unique application requirements and maintain compliance with certification

More information

Explosion protected terminal boxes type, GHG 72.

Explosion protected terminal boxes type, GHG 72. 1 Technical data 1.1 Plastic terminal boxes GHG 721... ATX type examination certificate BVS 13 ATX 013 X Marking acc. to 94/9/G and standard ATX x (d e mb) II T5* -55 T amb +55 Gb x (d e mb) II T6* -55

More information

Linear Luminaire for Fluorescent Lamps Series EXLUX 6401

Linear Luminaire for Fluorescent Lamps Series EXLUX 6401 > As wall, ceiling and pendant light fitting or pole mounted light fitting > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp

More information

Reg No: 1999/027771/07 ACCREDITED AND APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS

Reg No: 1999/027771/07 ACCREDITED AND APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS Government Approved Test Laboratory (Previously AIA) Reg No: 1999/027771/07 Equipment: Manufacturer: Type: ACCREDITED AND APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION

More information

PXN12C DXN25C DXN37C MULTI-CONTACT CONNECTORS 10 A TECHNICAL FEATURES

PXN12C DXN25C DXN37C MULTI-CONTACT CONNECTORS 10 A TECHNICAL FEATURES PXN12C DXN25C DXN37C MULTI-CONTACT CONNECTORS II2 G D Ex e ia or ib IIC FROM 12 TO 37 CONTACTS LOCKING IN CONNECTED OR DISCONNECTED POSITION CORROSION-FREE METAL CASING TECHNICAL FEATURES PXN12C DXN25C

More information

TB range of empty sheet metal enclosures. R S Sindair K~'

TB range of empty sheet metal enclosures. R S Sindair K~' of Conform ity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certitication Scheme tor Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate No.: Status: Applicant:

More information

Load and Motor Switches, Load-Break Switches Series 8544

Load and Motor Switches, Load-Break Switches Series 8544 www.stahl.de > Innovative switch concept > State-of-the-art contact arrangement > Easy and clear connection technology > Wiring channel for auxiliary contacts > Retrofittable: Alligator clip Auxiliary

More information

VALIADIS S.A. HELLENIC MOTORS

VALIADIS S.A. HELLENIC MOTORS Explosion proof motors MAK 56-250 (MAKe 63-250) series Groups IIB and IIC Ex db / Ex db e (EPL) executions Gb or Ex tb IIIC (EPL) Db II 2 G, II 2D, 2GD SAFETY INSTRUCTIONS Safety Instructions MAK and MAKe

More information

IECEx Certificate of Conformity

IECEx Certificate of Conformity Annex Page 1 of 14 Details associated with Issue 0 Conditions of Certification: Limiting parameters and temperature classification are listed in Tables 1, 2 and 3. Table 1: ES/DS Range Maximum Power Dissipation

More information

UZK12.261, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 26AH 1/10.

UZK12.261, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 26AH 1/10. BATTERY MODULE Long Life Battery: 10 to 12 Years According to EUROBAT Small Mounting Footprint Easy Access to the Terminals and the Fuse Heavy Duty Fuse Holder and Spare Fuse Included 3 Year Warranty,

More information

CONTENTS INTRODUCTION. Company Profile QUALITY CERTIFICATE EN ISO 9001: NEXT - Steel Enclosure Range. Product specification.

CONTENTS INTRODUCTION. Company Profile QUALITY CERTIFICATE EN ISO 9001: NEXT - Steel Enclosure Range. Product specification. CONTENTS INTRODUCTION Company Profile QUALITY CERTIFICATE EN ISO 9001: 2000. NEXT - Steel Enclosure Range Product specification. Product technical parameters. General arrangement drawing. Ex-Cell - Steel

More information

ILED Aquarius Illuminated Windsock. User Manual

ILED Aquarius Illuminated Windsock. User Manual Contents 1. Safety... 3 2. Warranty... 3 2.1 General... 3 2.2 Life span... 3 3. Type plate... 4 3.1 The light fitting has a type plate:... 4 3.2 The junction box has a type plate:... 5 4. Product Description...

More information

HKH Series. HAZCON Controls for Harsh and Hazardous Environments

HKH Series. HAZCON Controls for Harsh and Hazardous Environments HKH Series HAZCON Controls for Harsh and Hazardous Environments Z A H LO C NON-METALLIC DIN RAIL MOUNT Component Mounting Rail Optional Customer I.D. Nameplate Optional Legend Plate Explosion Protective

More information

GOVERNMENT APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS

GOVERNMENT APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS Reg No: 1999/027771/07 (Pty) Ltd 7 Spanner Rd / PO Box 467 Olifantsfontein 1665 Tel: +27 (11) 316 4601 Fax: +27 (11) 316 5670 E-mail: admin-mgr@explolabs.co.za GOVERNMENT APPROVED TEST LABORATORY IN TERMS

More information

Data Sheet DS/NGB-EN Rev. B. Multi barriers. Measurement made easy. Fieldbus barrier for PROFIBUS PA for FOUNDATION Fieldbus-H1

Data Sheet DS/NGB-EN Rev. B. Multi barriers. Measurement made easy. Fieldbus barrier for PROFIBUS PA for FOUNDATION Fieldbus-H1 Data Sheet DS/NGB-EN Rev. B Multi barriers Measurement made easy Fieldbus barrier for PROFIBUS PA for FOUNDATION Fieldbus-H1 Change from two to one column Multi barriers Change from one to two columns

More information

Control Stations & Switches: Control Stations Increased Safety Unicode 2 Series: Pre-drilled Control Stations

Control Stations & Switches: Control Stations Increased Safety Unicode 2 Series: Pre-drilled Control Stations Unicode 2 Series: Pre-drilled Control Stations Polamide U43W211 Polyester U23W211 Compliance Data: ATEX IEC and IECEx (Polyester): Stainless Steel U62W229 Aluminum U83W211 ATEX IEC / IECEx CE Ex de IIC

More information

Surface thermocouple Model TC50

Surface thermocouple Model TC50 Temperature Surface thermocouple Model TC50 WIKA data sheet TE 65.50 for further approvals see page 2 Applications To measure surface temperatures on flat surfaces or pipes, in both laboratory and industrial

More information

UZK24.071, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS

UZK24.071, UZO GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE 24V, 7Ah Battery Capacity (2x 12V Batteries in Series) Small Mounting Footprint 2m Power Leads Included PT1000 Sensor for Battery Module Temperature Included Includes a Center-tap Terminal

More information

GOVERNMENT APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS

GOVERNMENT APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS Reg No: 1999/027771/07 (Pty) Ltd 7 Spanner Rd / PO Box 467 Olifantsfontein 1665 Tel: +27 (11) 316 4601 Fax: +27 (11) 316 5670 E-mail: admin-mgr@explolabs.co.za GOVERNMENT APPROVED TEST LABORATORY IN TERMS

More information

The cover screws and all other external metal parts are made of stainless steel (AISI 316L). International approvals

The cover screws and all other external metal parts are made of stainless steel (AISI 316L). International approvals E X - J U N C T I O N B O X Plastic version for Zone 1,, 1 and The robust junction boxes made of plastic and light alloy are featured by their simple mounting and installation capability and their design.

More information

Flameproof - Group IIB or IIB + H 2 Carbon steel - DE8BC series. Painted steel. -40 C or -20 C C or +50 C or +60 C

Flameproof - Group IIB or IIB + H 2 Carbon steel - DE8BC series. Painted steel. -40 C or -20 C C or +50 C or +60 C Enclosures Flameproof - Group IIB or IIB + 2 Carbon steel - DE8BC series The flameproof control cabinets DE8BC are designed for the control, automation, distribution boards, motor starters or any other

More information

Control Buttons / Switches for Panel Mounting Series 8003

Control Buttons / Switches for Panel Mounting Series 8003 www.stahl.de > Different actuators pushbutton mushroom pushbutton mushroom stay-put button mushroom stay-put button with key lock key-operated button key-operated switch > 2 contact elements > Spring clamp

More information

Load cells. Data sheet. Special features. Cable assignment (six wire configuration)

Load cells. Data sheet. Special features. Cable assignment (six wire configuration) HLC A1 HLC B1 HLC F1 Load cells Special features - Hermetically encapsulated (IP68) - Maximum capacities: 110 kg... 10 t - Rust resistant materials - Low height of construction - Meets EMC requirements

More information

Glass Reinforced Polyester Enclosures

Glass Reinforced Polyester Enclosures 42 The GRP range comprises 16 sizes of enclosure manufactured in glass reinforced polyester (GRP). This material is highly resistant to contamination from oils, fats, aliphatic and aromatic carbohydrates,

More information

PTB 14 ATEX 2023 X, EPS 16 ATEX 1046 X. Operating Instructions. Solenoid coil Type AC10 Magnetspule Typ AC10 Bobine magnétique Type AC10

PTB 14 ATEX 2023 X, EPS 16 ATEX 1046 X. Operating Instructions. Solenoid coil Type AC10 Magnetspule Typ AC10 Bobine magnétique Type AC10 PTB 14 ATEX 2023 X, EPS 16 ATEX 1046 X Solenoid coil Type AC10 Magnetspule Typ AC10 Bobine magnétique Type AC10 Device with II 2G/D Ex approval Geräte mit II 2G/D Ex Zulassung Appareils avec mode de protection

More information

Flameproof Alternators

Flameproof Alternators Overview Standard automotive type alternators are a continuous potential source of ignition when operated in hazardous atmospheres where combustible concentrations of gas, vapor or dusts may exist. To

More information