Product Data Sheet Content

Size: px
Start display at page:

Download "Product Data Sheet Content"

Transcription

1 Product Data Sheet Model 8800 Smart Vortex Flowmeter TH MODL 8800 Fully cast, all welded meter body requires no process seals and eliates sources of fugitive emissions. Non-clogging sensor design with no ports or crevices to clog and degrade performance. Superior vibration immunity with mass balanced sensing design and Adaptive Digital Signal Processing. Advanced flow simulation diagnostics has a flow signal generator built in for remote verification of electronics. ommunicates digitally using HART protocol. ontent Specifications page 3 Hazardous Locations ertifications page 9 Dimensional Drawings page 10 Ordering Information page 21 onfiguration Data Sheet page 25

2 Model 8800 Smart Vortex Flowmeter TH MODL 8800 DLIVRS... SUPRIOR PRFORMAN High-accuracy and ambient-temperature immunity improve process control Adaptive digital-signal processing provides clean output in difficult applications Sensing mechanism design imizes vibration effects ROSMOUNT RLIABILITY All-welded meter body requires no process seals and eliates sources of fugitive emissions No ports or crevices to clog and degrade performance APPLIATION FLXIBILITY Smart/HART communications eliate unnecessary trips to the field Wide rangeability eliates the need for more than one flowmeter on a process Microprocessor-based electronics reduce setup time Simultaneous analog, digital, and pulse output signals allow multiple devices to monitor and control the flow xtended temperature range allows measurement of more processes Integral or remote electronics provide mounting flexibility ommon parts reduce spares inventory TH 8800 VORTX FLOWMTR OFFRINGS... The Model 8800A is available with wafer and flanged style meter bodies for ½- through 8-inch line sizes and accepts ASM B16.5 (ANSI), DIN, or JIS flanges. Both wafer and flanged style meter bodies are available in 316L and optional Hastelloy. Alignment rings, provided with each wafer-style flowmeter, ensure that the meter body is properly centered with the adjacent piping. The Dual-Sensor Vortex Flowmeter The dual-sensor vortex flowmeter option is designed for special applications that require redundant flow measurement. This style flowmeter is constructed of two complete vortex meters: sensor, electronics, and shedder bar (see Figure 2). The two flowmeters are welded together to provide one flowmeter with two independent flow measurements. The dual-sensor vortex flowmeter is ideally suited for critical applications requiring redundancy in plant safety shutdown systems. Applications that require two flowmeters in the same process piping and have limited piping requirements are also good applications for this style flowmeter. FIGUR 2. The Dual-Sensor Vortex Flowmeter FIGUR 1. Model 8800A Remote Mount G G910 2

3 Rosemount Inc. Specifications FUNTIONAL SPIFIATIONS Service Liquid, gas, and steam applications. Fluids must be homogeneous and single-phase. Line Sizes Wafer 1 /2, 1, 1 1 /2, 2, 3, 4, 6, and 8 inches (DN 15, 25, 40, 50, 80, 100, 150, and 200) Flanged, and Dual-Sensor Style 1 /2, 1, 1 1 /2, 2, 3, 4, 6, 8, 10, and 12 inches (DN 15, 25, 40, 50, 80, 100, 150, 200, 250, and 300) Pipe Schedules Process piping Schedules 10, 40, and 80 The appropriate bore diameter of the process piping must be entered using the HART ommunicator or AMS. Meters will be shipped from the factory at the Schedule 40 default value unless otherwise specified. TABL 1. Minimum Measurable Reynolds Numbers Line Sizes (Inches / DN) 1 /2 through 4 15 through through through 300 Reynolds Number Limitations imum imum TABL 2. Minimum Measurable Velocities (Use the larger of the two values) Feet per Second Meters per Second Liquids (1) 36/ or / or 0.22 Gases 36/ or / or 2.0 The is the process fluid density at flowing conditions in lb/ft 3 for ft/s and kg/m 3 for m/s (1) The imum measurable velocity for the 10in. line size is 0.9 ft/s (.27m/s) and 1.1 ft/s (.34m/s) for the 12in. line size. TABL 3. Maximum Measurable Velocities (Use the smaller of the two values) Feet per Second Meters per Second Liquids 90,000/ or ,000/ or 7.6 Gases (1) 90,000/ or ,000/ or 76 The is the process fluid density at flowing conditions in lb/ft 3 for ft/s and kg/m 3 for m/s (1) Accuracy limitations for gas and steam for Dual-style meters (all sizes): velocity of 100 ft/s (30.5 m/s). TABL 4. Water Flow Rate Limits in Schedule 40 Pipe Line Size (Inches/ DN) Minimum and Maximum Measurable Water Flow Rates* Gallons/Minute Scalable Frequency Adjustment Value of one pulse can be set to equal desired volume in selected engineering units. Ambient Temperature Limits Operating 58 to 185 F (50 to 85 ) ubic Meters/Hour ½/ to to / to to ½/ to to / to to / to to 130 4/ to to 225 6/ to to 511 8/ to to / to to / to to 2002 *onditions: 77 F (25 ) and 14.7 psia (1.01 bar absolute) 4 to 185 F (20 to 85 ) for flowmeters with local indicator Measurable Flow Rates apable of processing signals from flow applications which meet the sizing requirements below. To detere the appropriate flowmeter size for an application, process conditions must be within the Reynolds number and velocity limitations for the desired line size provided in Table 1, Table 2, and Table 3. onsult your local sales representative to obtain a computer sizing program that describes in greater detail how to specify the correct flowmeter size for an application. The Reynolds number equation shown below combines the effects of density ( ), viscosity ( cp ), pipe inside diameter (D), and flow rate (V). Process Temperature Limits Standard 40 to 450 F (40 to 232 ) xtended 330 to 800 F (200 to 427 ) Output Signals 420 ma Digital HART Signal Superimposed on 420 ma signal Optional Scalable Pulse Output 0 to Hz; transistor switch closure with adjustable scaling via HART communications; capable of switching up to 30 V dc, 120 ma imum Analog Output Adjustment ngineering units and lower and upper range values are user-selected. Output is automatically scaled to provide 4 ma at the selected lower range value, 20 ma at the selected upper range value. No frequency input is required to adjust the range values. Storage 58 to 250 F (50 to 121 ) 50 to 185 F (46 to 85 ) for flowmeters with local indicator Pressure Limits Flange and dual-sensor style rated for ASM B16.5 (ANSI) lass 150, 300, 600, and 900, DIN PN 10, 16, 25, 40, 64, 100, and 160, and, 20K, and 40K Wafer rated for ASM B16.5 (ANSI) lass 150, 300, and 600, DIN PN 10, 16, 25, 40, 64, and 100, and, 20K, and 40K Power Supply xternal power supply required. Flowmeter operates on 10.8 to 42 V dc teral voltage (with 250-ohm imum load required for HART communications, 16.8 V dc power supply is required) Power onsumption One watt imum 3

4 Model 8800 Smart Vortex Flowmeter TABL 5. Air Flow Rate Limits at 59 F (15 ) Process Pressure 0 psig (0 bar G) 50 psig (3,45 bar G) 100 psig (6,89 bar G) 150 psig (10,3 bar G) 200 psig (13,8 bar G) 300 psig (20,7 bar G) 400 psig (27,6 bar G) 500 psig (34,5 bar G) Flow Rate Limits Minimum and Maximum Air Flow Rates for line sizes 1 /2 inch/dn 15 through 3 inch/dn 80 1 /2 Inch/DN 15 1 Inch/DN 25 1½ Inch/DN 40 2 Inch/DN 50 3 Inch/DN 80 AFM AMH AFM AMH AFM AMH AFM AMH AFM AMH TABL 6. Air Flow Rate Limits at 59 F (15 ) Process Pressure 0 psig (0 bar G) 50 psig (3,45 bar G) 100 psig (6,89 bar G) 150 psig (10,3 bar G) 200 psig (13,8 bar G) 300 psig (20,7 bar G) 400 psig (27,6 bar G) 500 psig (34,5 bar G) Flow Rate Limits Minimum and Maximum Air Flow Rates for line sizes 4 inch/dn 100 through 12 inch/dn Inch/DN Inch/DN Inch/DN Inch/DN Inch/DN 300 AFM AMH AFM AMH AFM AMH AFM AMH AFM AMH The Model 8800 measures the volumetric flow under operating conditions (i.e. the actual volume at the operating pressure and temperatureacfm or acmh), as shown above. However, gas volumes are strongly dependent on pressure and temperature. Therefore, gas quantities are typically stated in standard or normal conditions (e.g. Scfm or Ncmh). (Standard conditions are typically 59 F and 14.7 psia. Normal conditions are typically 0 and 1 bar abs.) The flow rate limits in standard conditions are found using the equations below: Standard Flow Rate = Actual Flow Rate X Density Ratio Density Ratio = Density at Actual (Operating) onditions / Density at Standard onditions 4

5 Rosemount Inc. TABL 7. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%) Process Pressure 15 psig (1,03 bar G) 25 psig (1,72 bar G) 50 psig (3,45 bar G) 100 psig (6,89 bar G) 150 psig (10,3 bar G) 200 psig (13,8 bar G) 300 psig (20,7 bar G) 400 psig (27,6 bar G) 500 psig (34,5 bar G) Flow Rate Limits (1) Assumes steam quality is 100% Minimum and Maximum Saturated Steam (1) Flow Rates for line sizes 1 /2 inch/dn 15 through 3 inch/dn 80 ½ Inch/DN 15 1 Inch/DN 25 1½ Inch/DN 40 2 Inch/DN 50 3 Inch/DN 80 lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr TABL 8. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%) Process Pressure 15 psig (1,03 bar G) 25 psig (1,72 bar G) 50 psig (3,45 bar G) 100 psig (6,89 bar G) 150 psig (10,3 bar G) 200 psig (13,8 bar G) 300 psig (20,7 bar G) 400 psig (27,6 bar G) 500 psig (34,5 bar G) Flow Rate Limits Minimum and Maximum Saturated Steam (1) Flow Rates for line sizes 4 inch/dn 100 through 12 inch/dn Inch/DN Inch/DN Inch/DN Inch/DN Inch/DN 300 lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr (1) Assumes steam quality is 100% 5

6 Model 8800 Smart Vortex Flowmeter Load (Ohms) Load Limitations Maximum loop resistance is detered by the voltage level of the external power supply, as described by: HART ommunication requires a imum loop resistance of 250 ohms. Optional LD Indicator Displays flow variable, percent of range, current output, and/or totalized flow. nclosure Rating NMA Type 4X; SA Type 4X; IP66 PRFORMAN SPIFIATIONS Accuracy Operating Region Power Supply (Volts) R = 41.7(V ps 10.8) V ps = Power Supply Voltage (Volts) R = Maximum Loop Resistance (Ohms) Includes linearity, hysteresis, and repeatability. Liquids for Reynolds Numbers over Digital and Pulse Output ±0.65% of rate Analog Output Same as pulse output plus an additional 0.025% of span Gas and Steam for Reynolds Numbers over 15,000 Digital and Pulse Output ±1.35% of rate For 1 /2-in. through 4-in. (15 mm through 100 mm) line sizes, as the Reynolds number decreases below the stated limit to 10000, the positive limit of the accuracy error band will increase to 2.1% for the pulse output. xample: +2.1% to 0.65% for liquids. Repeatability ± 0.1% of actual flow rate Stability Analog Output Same as pulse output plus an additional 0.025% of span Accuracy limitations for gas and steam: - for 1 /2- and 1-in. (DN 15 and DN 25): velocity of 220 ft/s (67.06 m/s) - for Dual-style meters (all sizes): velocity of 100 ft/s (30.5 m/s) ±0.1% of rate over one year Process Temperature ffect Automatic K-factor correction with user-entered process temperature Table 8 indicates the percent change in K-factor per 100 F (50 ) in process temperature from reference temperature of 77 F (25 ) for direct pulse, or user-entered process temperature. TABL 9. Process Temperature ffect Material < 77 F (25 ) > 77 F (25 ) < 77 F (25 ) > 77 F (25 ) Ambient Temperature ffect Digital and Pulse Outputs No effect Analog Output Percent hange in K-Factor per 100 F (50 ) (+ 0,20) (- 0,24) (+ 0,20) (- 0,20) ±0.1% of span from 40 to 185 F (40 to 85 ) Vibration ffect An output with no process flow may be detected if sufficiently high vibration is present. The meter design will imize this effect, and the factory settings for signal processing are selected to eliate these errors for most applications. If an output error at zero flow is still detected, it can be eliated by adjusting the low flow cutoff, trigger level, or low-pass filter. As the process begins to flow through the meter, most vibration effects are quickly overcome by the flow signal. At or near the imum liquid flow rate in a normal pipe mounted installation, the imum vibration should be inch (2,21 mm) double amplitude displacement or 1 g acceleration, whichever is smaller. At or near the imum gas flow rate in a normal pipe mounted installation, the imum vibration should be inch (1,09 mm) double amplitude displacement or 1 /2 g acceleration, whichever is smaller. Mounting Position ffect Meter will meet accuracy specifications when mounted in horizontal, vertical, or inclined pipelines. MI/RFI ffect Output error less than ±0.025% of span with twisted pair from MHz for radiated field strength of 10 V/m and from MHz for conducted RF of 3V (tested per N61326). Magnetic-Field Interference Output error less than ±0.025% of span at 30 A/m (rms); meets I , Section Series Mode Noise Rejection Output error less than ±0.025% of span at 1 V rms, 60 Hz; meets I , Section ommon Mode Noise Rejection Output error less than ±0.025% of span at 30 V rms, 60 Hz; meets I , Section Power Supply ffect Less than 0.005% of span per volt 6

7 Rosemount Inc. where: P f D Q gpm or lpm Q acfm or acmh Pressure Loss The approximate pressure loss from the flowmeter can be detered using the following equations: nglish Metric Pressure loss is 1.8 meter. P for the dual sensor Minimum Back Pressure (Liquids) x x Flow metering conditions that would allow cavitation, the release of vapor from a liquid, should be avoided. This flow condition can be avoided by remaining within the proper flow range of the meter and by following appropriate system design. x x = Pressure loss (psi or kpa) = Density at operating conditions (lb/ft 3 or kg/m 3 ) = Flowmeter bore diameter (in. or mm) = Actual volumetric flow rate (gal/ or l/) = Actual volumetric flow rate (ft 3 / or m 3 /hour) x x x x x x For some liquid applications, incorporation of a back pressure valve should be considered. To prevent cavitation, the imum back pressure should be: P = 2.9 P p v P = Line pressure five pipe diameters downstream of the meter (psia or kpa abs) P= Pressure loss across the meter (psi or kpa) p v = Liquid vapor pressure at operating conditions (psia or kpa abs) Pressure loss is 1.8 meter. Failure Mode Alarm P for the dual sensor If self-diagnostics detect a gross flowmeter failure, the analog signal will be driven either below 3.75 ma or above ma to alert the user. Also, high or low alarm signal is user-selectable through the fail mode alarm jumper on the electronics. NAMUR-compliant alarm limits are available through the 4 or N Option. NAMUR-compliant limits are 3.6 ma (low) or 22.5 ma (high). Saturation Output Values When the operating flow is outside the range points, the analog output continues to track the operating flow until reaching the saturation value listed below; the output does not exceed the listed saturation value regardless of the operating flow. The 420 ma Saturation Values are 3.9 ma (low) or 20.8 ma (high). The NAMUR-ompliant Saturation Values (Option 4 or N) are 3.8 ma (low) or 20.5 ma (high). Damping Adjustable between 0.2 and 255 seconds Response Time Three vortex shedding cycles or 0.2 seconds, whichever is greater, imum required to reach 63.2% of actual input with the imum damping (0.2 seconds). Turn-on Time Less than four (4) seconds plus the response time to rated accuracy from power up. Transient Protection The optional transient teral block prevents damage to the flowmeter from transients induced by lightning, welding, heavy electrical equipment, or switch gears. The transient protection electronics are located in the teral block. The transient teral block meets the following specifications: ASM B16.5 (ANSI)/I (I 587) ategories A, B 3 ka crest (8 20 s) 6 kv crest ( s) 6 kv/0.5 ka (0.5 s, 100 khz, ring wave) Security Lockout When the security lockout jumper is enabled, the electronics will not allow you to modify functions that affect flowmeter output. Output Testing urrent Source Flowmeter may be commanded to set the current to a specified value between 4 and 20 ma. Frequency Source Flowmeter may be commanded to set the frequency to a specified value between 0 and Hz. Low Flow utoff Adjustable over entire flow range. Below selected value, output is driven to 4 ma and zero pulse output frequency (in the scaled pulse mode only). Humidity Limits Operates in 095% relative humidity under noncondensing conditions (tested to I 770, Section ). Overrange apability Analog signal output continues to 105 percent of span, then remains constant with increasing flow. The digital and pulse outputs will continue to indicate flow up to the upper sensor limit of the flowmeter and a imum frequency of Hz. Flow alibration Meter bodies are flow-calibrated and assigned a unique calibration factor (K-factor) at the factory. The calibration factor is entered into the electronics, enabling interchangeability of electronics and/or meter bodies without calculations or compromise in accuracy. 7

8 Model 8800 Smart Vortex Flowmeter PHYSIAL SPIFIATIONS NA ompliance Meets the requirements of NA (National Association of orrosion ngineers) Standard MR (96) lectrical onnections 1 /2 14 NPT, PG 13.5, or M conduit threads; screw terals provided for 420 ma and pulse output connections; communicator connections permanently fixed to teral block Non-Wetted Materials Housing Low-copper aluum (NMA 4X, SA Type 4X, IP66) Paint Polyurethane over O-rings Buna-N Flanges 316/316L lap joint Process-Wetted Materials Meter Body 316L wrought stainless and F-3M cast stainless or -22 and -276 wrought Hastelloy or X2MW and W12MW cast Hastelloy Flanges 316/316L stainless steel ollars Hastelloy -22 Surface Finish of Flanges and ollars Standard: 125 to 250 inches (3.1 to 6.3 meters) Ra roughness Smooth: 63 to 125 inches (1.6 to 3.1 meters) Ra roughness Process onnections Mounts between the following flange configurations: ASM B16.5 (ANSI): lass 150, 300, 600, 900 Mounting DIN: PN 10, 16, 25, 40, 64, 100, 160 JIS: 10K, 20K, and 40K Integral (Standard) lectronics are mounted on meter body Remote (Optional) lectronics may be mounted remote from the meter body. Interconnecting coaxial cable available in nonadjustable 10, 20, and 30 ft (3,0, 6,1, and 9,1 m) lengths. onsult factory for non-standard lengths up to 75 ft (22,9 m). Remote mounting hardware includes a polyurethane painted, carbon steel pipe mount bracket with one carbon steel u-bolt. Pipe Length Requirements The vortex meter may be installed with a imum of ten straight pipe diameters (D) upstream and five straight pipe diameters (D) downstream. Rated accuracy is based on the number of pipe diameters from an upstream disturbance. An additional 0.5% shift in K-factor may be introduced between 10 D and 35 D, depending on disturbance. For more information on installation effects, see Technical Data Sheet Tagging The flowmeter will be tagged at no charge, according to customer requirements. All tags are stainless steel. The standard tag is permanently attached to the flowmeter. haracter height is 1/16-inch (1,6 mm). A wired-in tag is available on request. Flow alibration Information Flowmeter calibration and configuration information is provided with every flowmeter. For a certified copy of flow calibration data, Option Q4 must be ordered in the model number. 8

9 Rosemount Inc. Hazardous Locations ertifications Factory Mutual (FM) Approvals 5 xplosion-proof for lass I, Division 1, Groups B,, and D; Dust-ignition proof for lass II/III, Division 1, Groups, F, and G; factory sealed. I5 Intrinsically safe for use in lass I, Division 1, Groups A, B,, and D; lass II/III, Division 1, Groups, F, and G; temp. code T4 only when connected in accordance with Rosemount drawings and ; non-incendive for lass I, Division 2, Groups A, B,, and D; factory sealed. ntity Parameters: U i = 30 V I i = 300 ma P i = 1.3 W i = 0.0 F L i = 40 H K5 5 and I5 combination U i = 30 V I i = 300 ma i = 0.0 F L i = 40 H anadian Standards Association (SA) Approvals 6 I6 xplosion-proof for lass I, Division 1, Groups B,, and D; Dust-ignition proof for lass II, Division 1, Groups, F, and G; lass III, Division 1 hazardous locations; lass I, Division 2, Groups A, B,, and D; factory sealed. Intrinsically safe for lass I, Division 1, Groups A, B,, and D; Intrinsic safety approval only when connected in accordance with Rosemount drawing ; temperature code T3 (see Table 10) 6 6 and I6 combination (see Table 10) TABL 10. SA ntity Approvals NL Intrinsic Safety and Dust ertification I1 ATX Marking x II 1 GD T 70 ertification No. BAS99ATX1222 x ia II T5 (T amb = -50 to 40 ) x ia II T4 (T amb = -50 to 70 ) ntity Parameters: U i = 30 VD I (1) i = 300 ma P (1) i = 1 W i = 0.0 F L i = 40 H NL Type N ertification N1 Barrier Manufacturer/Model Any SA approved zener barrier 30 V, 330 or 28 V, 300 or 25 V, 200 or 22 V, 180 Foxboro onverters 2AI-12V-GB 2AI-13V-GB 2AS-I3I-GB 3A2-I2D-GB 3A2-I3D-GB 3AD-I3I-GB 3A4-I2D-GB 2AS-I2I-GB 3F4-I2DA Any SA approved zener barrier 30 V, 150 SA Approved for lass I, Division 1, Groups A B D NA NA NA ATX Marking x II 3 GD T70 ertification No. BAS99ATX3221 x nl II T5 (T amb = -40 to 70 ) 42 Vdc NL Flameproof ertification D ATX Marking Remote Mount: x II 2 (1) G T70 ATX Marking Integral Mount x II 1/2 G T70 KMA ertification No. 99ATX3852X x d [ia] II T6 (T amb = -50 to 70 ) Special onditions When installed particular precautions must be taken to ensure taking account with the effect of the fluid temperature, that the ambient temperature of the electrical parts of the apparatus is comprised between -50 and 70. Standards Association of Australia (SAA) (2) ertifications 7 Flameproof: x d [ia] II T6 (T amb = 40 ) x d [ia] II T4 (T amb = 70 ) lass I, Zone 1; IP66 I7 When connected in accordance with Rosemount Drawing Intrinsic Safety: x ia II T6 (T amb = 40 ) x ia II T4 (T amb = 70 ) lass I, Zone 0 ntity Parameters: U i = 30 V I (1) i = 300 ma P (1) i = 1 W i = F L i = 40 H N7 Type N: x n II T6 (T amb = 40 ) x n II T4 (T amb = 85 ) lass I, Zone 2 (1) Total for transmitter (2) Pending final approval 9

10 Model 8800 Smart Vortex Flowmeter Dimensional Drawings FIGUR 1. Flanged-Style Flowmeter Dimensional Drawings ( 1 /2- through 12-in./15 through 300 mm Line Sizes) 3.20 (81) 2.56 (65) 1.10 (28) Teral over 2.85 (72) Diameter 3.06 (78) 1.00 (25) Display Option Diameter B lectrical onnection ASM B16.5 (ANSI) ½14 NPT (2 places) 2.00 (51) 2.00 (51) Dimensions are in inches (millimeters) A A02B, 0002B02B 10

11 Rosemount Inc. TABL 11. Flanged-Style Flowmeter ( 1 /2-through 3in./15 through 80 mm Line Sizes) Noal Size Flange Rating ½ (15) lass 150 PN 16/40 /20K 1 (25) lass 150 lass 900 PN 16/40 PN 160 /20K 1 ½ (40) lass 150 lass 900 PN 16/40 PN 160 /20K 2 (50) lass 150 lass 900 PN 16/40 PN (80) lass 150 lass 900 PN 16/40 PN 160 (1) ±0.14 inch (3.6 mm) (2) ±0.03 inch (0.8 mm) (3) ±0.20 inch (5.1 mm) (4) Add 0.2 lb (0,1 kg) for display option. Face-to-face A (1) 6.9 (175) 7.2 (183) 6.1 (155) 6.6 (168) 6.3 (160) 7.3 (185) 7.5 (191) 8.0 (203) 9.4 (239) 6.3 (160) 7.7 (195) 7.7 (195) 6.5 (165) 7.9 (200) 8.2 (208) 8.7 (221) 9.4 (239) 10.4 (264) 6.9 (175) 8.2 (208) 8.4 (213) 7.3 (185) 8.5 (215) 9.3 (236) 9.8 (249) 10.5 (267) 8.0 (203) 9.2 (234) 10.2 (259) 7.7 (195) 8.3 (210) 9.8 (249) 9.9 (251) 10.6 (269) 11.4 (290) 12.9 (328) 8.9 (226) 10.0 (254) 10.5 (267) 11.2 (284) 7.9 (200) 9.3 (235) 11.0 (280) A-ANSI RTJ 8.0 (203) 9.4 (239) 8.7 (221) 9.2 (234) 9.4 (239) 10.4 (264) 9.8 (249) 10.4 (264) 10.7 (271) 12.9 (328) 10.4 (264) 11.2 (284) 11.5 (292) 13.0 (330) Diameter B (2) Weight (4) (3) lb (kg) 9.1 (4,1) 10.4 (4,7) 10.8 (4,9) 10.4 (4,7) 12.3 (5,6) 10.1 (4,5) 13.5 (6,1) 12.3 (5,6) 15.0 (6,8) 15.8 (7,2) 24.3 (11,0) 13.5 (6,1) 19.5 (8,8) 19.5 (8,8) 13.7 (6,2) 17.4 (7,9) 17.6 (8,0) 23.0 (10,4) 25.3 (11,5) 36.3 (16,5) 19.3 (8,8) 27.9 (12,7) 29.3 (13,3) 18.6 (8,4) 25.6 (11,6) 22.0 (10,0) 26.0 (11,8) 29.6 (13,4) 59.4 (26,9) 23.0 (10,4) 30.6 (13,9) 36.4 (16,5) 38.7 (17,6) 19.5 (8,8) 20.1 (9,1) 28.3 (12,8) 36.9 (16,7) 46.1 (20,9) 52.1 (26,6) 75.5 (34,2) 36.3 (16,5) 45.1 (20,5) 54.4 (24,7) 59.6 (27,0) 27.6 (12,5) 35.0 (15,9) 50.0 (22,7) 11

12 Model 8800 Smart Vortex Flowmeter TABL 12. Flanged-Style Flowmeter (4-through 12-in./100 through 300mm Line Sizes) (Refer to Figure 1) Noal Size Flange Rating 4 (100) lass 150 lass 900 PN 16 PN 40 PN (150) lass 150 PN 16 PN 40 8 (200) lass 150 PN 10 PN 16 PN 25 PN (250) lass 150 PN 10 PN 16 PN 25 PN (300) lass 150 PN 10 PN 16 PN 25 PN 40 Face-to-face A (1) 10.3 (262) 11.0 (279) 13.8 (351) 8.4 (213) 9.4 (239) 10.4 (264) 11.3 (287) 12.1 (307) 8.7 (220) 8.7 (220) 11.8 (300) 11.6 (295) 12.4 (315) 14.3 (363) 8.9 (226) 10.5 (267) 12.1 (307) 10.6 (270) 10.6 (270) 14.2 (360) 13.6 (345) 14.3 (363) 16.6 (422) 10.5 (266) 10.5 (266) 11.9 (302) 12.5 (318) 14.2 (361) 15.8 (401) 12.2 (310) 12.2 (310) 16.5 (420) 14.6 (371) 15.8 (401) 19.1 (485) 11.9 (302) 12.1 (307) 13.5 (343) 14.8 (376) 16.4 (417) 18.9 (480) 14.6 (371) 14.6 (371) 18.1 (460) 16.8 (427) 18.0 (457) 20.5 (521) 13.2 (335) 13.9 (353) 15.0 (381) 16.9 (429) 18.8 (478) 21.2 (538) 15.7 (399) 15.7 (399) 19.7 (500) A ANSI RTJ 11.6 (295) 12.9 (328) 13.9 (353) 12.1 (307) 13.0 (330) 14.5 (368) 14.1 (358) 15.0 (381) 16.7 (424) 15.1 (384) 16.4 (417) 19.2 (488) 17.3 (439) 18.7 (475) 20.7 (526) Diameter B (2) Weight (4) (3) lb (kg) 50.7 (23,0) 70.8 (32,1) 96.5 (43,8) (54,3) 40.1 (18,2) 49.2 (22,3) 62.1 (28,2) 78.5 (35,6) 85.8 (38,9) 37.0 (16,8) 44.9 (20,4) 75.3 (34,2) 90.0 (40,8) (58,7) (88,7) 75.6 (34,3) 95.3 (43,2) (63,0) (76,4) 79.8 (36,2) 97.7 (44,3) (79,8) (63,3) (89,0) (133,8) (49,7) (49,2) (61,8) (70,2) (97,3) (127) (49,9) (60,9) (116) (89) (129) (216) (71) (73) (90) (111) (139) (201) (79) (100) (171) (134) (187) (269) (92) (101) (121) (157) (194) (291) (102) (130) (229) (1) ±0.14 inch (3.6 mm) (2) ±0.03 inch (0.8 mm) (3) ±0.20 inch (5.1 mm) (4) Add 0.2 lb (0,1 kg) for display option. 12

13 Rosemount Inc. FIGUR 2. Wafer-Style Dimensional Drawings ( 1 /2-through 1 1 /2in./15 through 40 mm Line Sizes) Teral over 2.00 (51) 2.00 (51) lectrical onnection ASM B16.5 (ANSI) 1 /2-14 NPT (2 places) 3.20 (81) 2.56 (65) 1.10 (28) 2.85 (72) Diameter 3.06 (78) 1.00 (25) Display Option Diameter D Dimensions are in inches (millimeters) lectronics housing may be rotated in 90 degree increments A Diameter B D01D, TABL 13. Model 8800 Stainless Steel Wafer Noal Size Face-to-face A (1) Diameter B (2) (3) Diameter D Weight lb (kg) (4) ½ (15) 2.56 (65) 0.54 (13,7) 7.63 (194) 1.38 (35,1) 0.23 (5,9) 7.3 (3,3) 1 (25) 2.56 (65) 7.74 (197) 1.98 (50,3) 0.23 (5,9) 7.4 (3,4) 1½ (40) 2.56 (65) 8.14 (207) 0.18 (4,6) 10.0 (4,5) (1) ±0.14 inch (3.6 mm) (2) ±0.03 inch (0.8 mm) (3) ±0.20 inch (5.1 mm) (4) Add 0.2 lb (0,1 kg) for display option. TABL 14. Model 8800A Hastelloy Wafer Noal Size Face-to-face A (1) Diameter B (2) (3) Diameter D Weight lb (kg) (4) ½ (15) 2.44 (62) 7.63 (194) 1.38 (35,1) 0.17 (4,3) 6.8 (3,1) 1 (25) 2.44 (62) 7.74 (197) 1.98 (50,3) 0.17 (4,3) 7.6 (3,4) 1½ (40) 3.11 (79) 8.08 (205) 0.47 (11,9) 10.8 (4,9) (1) ±0.14 inch (3.6 mm) (2) ±0.03 inch (0.8 mm) (3) ±0.20 inch (5.1 mm) (4) Add 0.2 lb (0,1 kg) for display option. 13

14 Model 8800 Smart Vortex Flowmeter FIGUR 3. Wafer-Style Dimensional Drawings (2-through 8-in./50 through 200 mm Line Sizes) 2.00 (51) 2.00 (51) lectrical onnection ASM B16.5 (ANSI) 1 /2-14 NPT (2 places) 3.20 (81) 2.56 (65) Teral over 2.85 (72) 1.10 (28) 1.00 (25) Diameter 3.06 (78) Display Option Diameter D Dimensions are in inches (millimeters) lectronics housing may be rotated in 90 degree increments A Diameter B B01, 0002A01D TABL 15. Model 8800 Stainless Steel Wafer Noal Size Face-to-face A (1) Diameter B (2) (3) Diameter D Weight lb (kg) (4) 2 (50) 2.56 (65) 1.92 (49) 8.85 (225) 3.86 (98) 0.12 (3) 10.6 (4,8) 3 (80) 2.56 (65) 2.87 (73) 9.62 (244) 5.00 (127) 0.25 (6) 13.6 (6,2) 4 (100) 3.42 (87) 3.79 (96) (266) 6.20 (158) 0.44 (11) 21.4 (9,7) 6 (150) 4.99 (127) 5.70 (145) (273) 8.50 (216) 1.11 (28) 49.1 (22,3) 8 (200) 6.60 (168) 7.55 (192) (296) (270) 0.89 (23) 85 (38,6) (1) ±0.14 inch (3.6 mm) (2) ±0.03 inch (0.8 mm) (3) ±0.20 inch (5.1 mm) (4) Add 0.2 lb (0,1 kg) for display option. TABL 16. Model 8800A Hastelloy Wafer Noal Size Face-to-face A (1) Diameter B (2) (3) Diameter D Weight lb (kg) (4) 2 (50) 3.81 (97) 1.92 (49) 8.45 (215) 3.86 (98) 0.86 (22) 10.8 (4,9) 3 (80) 3.92 (100) 2.87 (73) 9.10 (231) 5.00 (127) 0.76 (19) 15.0 (6,8) 4 (100) 4.47 (114) 3.79 (96) 6.20 (158) 0.82 (21) 23.0 (10,4) 6 (150) 4.99 (127) 5.70 (145) (273) 8.50 (216) 1.11 (28) 49.1 (22,3) 8 (200) 6.60 (168) 7.55 (192) (296) (270) 0.89 (23) 85 (38,6) (1) ±0.14 inch (3.6 mm) (2) ±0.03 inch (0.8 mm) (3) ±0.20 inch (5.1 mm) (4) Add 0.2 lb (0,1 kg) for display option. 14

15 Rosemount Inc. FIGUR 4. Vortex Dual-Sensor Style Flowmeter Dimensional Drawings( 1 /2-through 8-in./15 through 200 mm Line Sizes) 3.20 (81) 2.56 (65) 1.10 (28) Teral over 2.85 (72) 2.00 (51) 2.00 (51) lectrical onnection ASM B16.5 (ANSI) 1 /2-14 NPT (2 places) 3.06 (78) 1.00 (25) Display Option Dimensions are in inches (millimeters) Diameter B A A01A, 0006B01A FIGUR 5. Vortex Dual-Sensor Style Flowmeter Dimensional Drawings(10-through 12-in./250 through 300 mm Line Sizes) lectrical onnection ASM B16.5 (ANSI) 1 /2-14 NPT (2 places) (51) (51) 3.20 (81) 2.56 (65) 1.10 (28) 2.85 (72) Teral over 3.06 (78) 1.00 (25) Display Option Dimensions are in inches (millimeters) A Diameter B _01, 8800_02 15

16 Model 8800 Smart Vortex Flowmeter TABL 17. Vortex Dual-Sensor Style Flowmeter ( 1 /2-through 3-in./15 through 80 mm Line Sizes) Noal Size Flange Rating ½ (15) lass 150 PN 16/40 /20K 1 (25) lass 150 lass 900 PN 16/40 PN 160 /20K 1 ½ (40) lass 150 lass 900 PN 16/40 PN 160 /20K 2 (50) lass 150 lass 900 PN 16/40 PN (80) lass 150 lass 900 PN 16/40 PN 160 (1) ±0.14 inch (3.6 mm) (2) ±0.03 inch (0.8 mm) (3) ±0.20 inch (5.1 mm) (4) Add 0.4 lb (0,2 kg) for display option. Face-to-face A (1) 12.0 (305) 12.3 (312) 11.2 (284) 11.8 (300) 11.4 (290) 12.4 (315) 15.1 (384) 15.6 (396) 16.1 (409) 17.0 (432) 13.9 (353) 15.3 (389) 15.3 (389) 14.1 (358) 15.5 (394) 11.3 (287) 11.8 (300) 12.5 (318) 13.5 (343) 10.0 (254) 11.3 (287) 11.5 (292) 10.4 (264) 11.5 (292) 13.0 (330) 13.6 (345) 14.3 (363) 16.6 (422) 11.8 (300) 12.9 (328) 13.4 (340) 14.0 (356) 11.5 (292) 12.1 (307) 13.6 (345) 14.3 (363) 15.0 (381) 15.8 (401) 17.3 (439) 13.4 (340) 14.5 (367) 14.9 (378) 15.6 (396) 12.3 (312) 15.5 (394) A ANSI RTJ 15.6 (396) 16.1 (409) 16.1 (409) 17.0 (432) 11.8 (300) 12.3 (312) 12.5 (318) 13.5 (343) 13.6 (345) 14.1 (358) 14.3 (363) 16.7 (424) 14.8 (376) 15.7 (399) 15.8 (401) 17.4 (442) Diameter B (2) (3) Weight lb (kg) (4) 16.2 (7,4) 17.4 (7,9) 17.9 (8,1) 17.2 (7,8) 19.2 (8,7) 17.1 (7,8) 20.6 (9,3) 19.8 (9,0) 22.5 (10,2) 23.3 (10,6) 31.8 (14,4) 21.0 (9,5) 27.0 (12,3) 27.0 (12,3) 22.1 (10,0) 25.8 (11,7) 27.0 (12,3) 32.4 (14,7) 34.8 (15,8) 45.7 (20,7) 28.7 (13,0) 37.4 (17,0) 38.8 (17,6) 27.9 (12,6) 34.9 (15,8) 31.9 (14,5) 35.9 (16,3) 39.5 (17,9) 69.2 (31,4) 32.9 (14,9) 40.5 (18,4) 46.2 (21,0) 48.5 (22,0) 29.1 (13,2) 29.7 (13,5) 37.9 (17,2) 50.3 (22,8) 59.5 (27,0) 65.5 (29,7) 88.9 (40,3) 49.7 (22,5) 58.5 (26,5) 67.8 (30,8) 73.0 (33,1) 41.0 (18,6) 48.4 (22,0) 63.4 (28,8) 16

17 Rosemount Inc. TABL 18. Vortex Dual-Sensor Style Flowmeter (4- through 12-in./100 through 300 mm Line Sizes) Noal Size Flange Rating 4 (100) lass 150 lass 900 PN 16 PN 40 PN (150) lass 150 PN 16 PN 40 8 (200) lass 150 PN 10 PN 16 PN 25 PN (250) lass 150 PN 10 PN 16 PN 25 PN (300) lass 150 (1) ±0.14 inch (3.6 mm) (2) ±0.03 inch (0.8 mm) (3) ±0.20 inch (5.1 mm) PN 10 PN 16 PN 25 PN 40 (4) Add 0.4 Lb (0,2 kg) for display option. Face-to-face A (1) 15.2 (386) 16.0 (406) 17.7 (450) 18.7 (475) 13.3 (338) 14.4 (366) 15.4 (391) 16.3 (414) 17.1 (434) 13.6 (345) 13.6 (345) 16.8 (427) 19.4 (493) 20.2 (513) 22.2 (564) 16.8 (427) 18.3 (465) 19.9 (505) 21.5 (546) 18.5 (470) 18.5 (470) 22.0 (559) 24.0 (610) 24.8 (630) 27.0 (686) 20.9 (531) 20.9 (531) 22.3 (566) 22.9 (582) 24.7 (627) 26.3 (668) 22.6 (574) 22.6 (574) 27.0 (686) 14.6 (371) 15.8 (401) 19.1 (485) 11.9 (302) 12.1 (307) 13.5 (343) 14.8 (376) 16.4 (417) 18.9 (480) 14.6 (371) 14.6 (371) 18.1 (460) 16.8 (427) 18.0 (457) 20.5 (521) 13.2 (335) 13.9 (353) 15.0 (381) 16.9 (429) 18.8 (478) 21.2 (538) 15.7 (399) 15.7 (399) 19.7 (500) A ANSI RTJ 15.7 (399) 16.6 (422) 17.7 (450) 18.9 (480) 19.9 (505) 20.8 (528) 22.3 (566) 24.5 (622) 25.4 (645) 27.1 (688) 15.1 (384) 16.4 (417) 19.2 (488) 17.3 (439) 18.7 (475) 20.7 (526) Diameter B (2) (3) Weight lb (kg) (4) 68.1 (30,9) 88.2 (40,0) (51,7) (62,2) 57.6 (26,1) 66.6 (30,2) 79.6 (36,1) 95.9 (43,5) (46,8) 55.4 (25,1) 63.2 (28,7) 93.7 (42,5) (57,3) (75,3) (105,2) (50,8) (59,7) (79,5) (92,9) (56,2) (64,4) (99,8) (86,2) (111,9) (156,7) (72,7) (72,1) (83,4) (93,2) (120,2) (149,9) (80,8) (91,9) (147,0) (91) (131) (218) (73) (75) (96) (113) (141) (203) (81) (102) (173) (136) (189) (271) (94) (103) (123) (159) (196) (293) (104) (132) (231) 17

18 Model 8800 Smart Vortex Flowmeter FIGUR 6. Dimensional Drawings for Remote Mount Transmitters Teral over 3.20 (81) 2.56 (65) 1.10 (28) 2.85 (72) 1.00 (25) 3.06 (78) Display Option 2.65 (68) 2.81 (71) 4.50 (114) 2.81 (71) 4.50 (114) 2.00 (51) 2.00 (51) lectrical onnection ASM B16.5 (ANSI) 1 /2-14 NPT (2 places) 1.80 (46) 4.90 (124) Dimensions are in inches (millimeters) 1 /2-14 NPT (For Remote able onduit) 5.50 (140) A04B, 0002B04B 18

19 Rosemount Inc. FIGUR 7. Dimensional Drawings for Remote Mount Wafer-Style Flowmeters ( 1 /2- through 8-in./15 through 200 mm Line Sizes) 1 /2-14 NPT (For Remote able onduit) Dimensions are in inches (millimeters) B TABL 19. Model Stainless Steel Wafer Noal Size Wafer Style ½ (15) 6.4 (163) 1 (25) 6.5 (165) 1½ (40) 6.9 (175) 2 (50) 3 (80) 8.3 (211) 4 (100) 9.2 (234) 6 (150) 9.5 (241) 8 (200) 10.4 (264) TABL 20. Model 8800A - Hastelloy Wafer Noal Size Wafer Style ½ (15) 6.3 (160) 1 (25) 6.5 (165) 1½ (40) 6.8 (173) 2 (50) 7.2 (183) 3 (80) 7.8 (198) 4 (100) 8.3 (211) 6 (150) 9.5 (241) 8 (200) 10.4 (264) 19

20 Model 8800 Smart Vortex Flowmeter FIGUR 8. Dimensional Drawings for Flanged-and Dual-Sensor Flanged-Style Remote Mount Flowmeters ( 1 /2-through 12-inch/15 through 300 mm Line Sizes) 1 /2-14 NPT (For Remote able onduit) 1 /2-14 NPT (For Remote able onduit) Flanged Flowmeter Dimensions are in inches (millimeters) Dual-Sensor Style Flowmeter B02, A TABL 21. Remote Mount, Flanged-and Dual Sensor Flowmeter Dimensions Noal Size Flange Style ½ (15) 6.4 (162) 1 (25) 6.5 (165) 1½ (40) 6.8 (173) 2 (50) 7.2 (183) 3 (80) 7.8 (198) 4 (100) 8.3 (211) 6 (150) 9.5 (241) 8 (200) 10.4 (264) 10 (250) 11.5 (292) 12 (300) 12.4 (315) 20

21 Rosemount Inc. Ordering Information Model A ode W F D Product Description Vortex Flowmeter Vortex Flowmeter, Hastelloy wafer meters only Meter Style Wafer style Flanged style Dual-sensor style (Flanged style only) ode Line Size /2 Inch (15 mm) Inch (25 mm) /2 Inches (40 mm) Inches (50 mm) Inches (80 mm) Inches (100 mm) Inches (150 mm) Inches (200 mm) Inches (250mm) Inches (300mm) ode Wetted Materials S 316L wrought stainless and F-3M cast stainless H (1) -22 and -276 wrought Hastelloy ; X2MW and W12MW cast Hastelloy ode Flange or Alignment Ring Size A1 ASM B16.5 (ANSI) RF lass 150 A3 ASM B16.5 (ANSI) RF A6 ASM B16.5 (ANSI) RF A7 (2) ASM B16.5 (ANSI) RF lass 900 B1 ASM B16.5 (ANSI) RTJ lass 150 for flange-style only B3 ASM B16.5 (ANSI) RTJ for flange-style only B6 ASM B16.5 (ANSI) RTJ for flange-style only B7 (2) ASM B16.5 (ANSI) RTJ lass 900 for flange-style only 1 ASM B16.5 (ANSI) RF lass 150, smooth finish 3 ASM B16.5 (ANSI) RF, smooth finish 6 ASM B16.5 (ANSI) RF, smooth finish 7 (2) ASM B16.5 (ANSI) RF lass 900, smooth finish D0 DIN PN Type D D1 DIN PN 16 (PN 10/16 for wafer-style)2526-type D D2 DIN PN Type D D3 DIN PN 40 (PN 25/40 for wafer-style) 2526-Type D D4 DIN 2526-Type D D6 (3) DIN 2526-Type D D7 (2) DIN PN Type D G0 DIN PN Type N for flange-style only G1 DIN PN Type N for flange-style only G2 DIN PN Type N for flange-style only G3 DIN PN Type N for flange-style only G4 DIN 2512-Type N for flange-style only G6 DIN 2512-Type N for flange-style only G7 (2) DIN PN Type N for flange-style only ontinued on Next Page 21

22 Model 8800 Smart Vortex Flowmeter ode H0 H1 H2 H3 H4 H6 (3) H7 (2) J1 J2 J4 ode N ode Flange or Alignment Ring Size DIN PN Type DIN PN 16 (PN 10/16 for wafer-style) 2526-Type DIN PN Type DIN PN 40 (PN 25/40 for wafer-style) 2526-Type DIN 2526-Type DIN 2526-Type DIN PN Type Sensor Process Temperature Range Standard: -40 to 450 F (-40 to 232 ) xtended: -330 to 800 F (-200 to 427 ) onduit ntry 1 1 /2-14 NPT 2 M PG 13.5 ode D P ode Outputs 4-20 ma digital electronics (Hart protocol) 4-20 ma digital electronics (Hart protocol) with scaled pulse alibration 1 Flow calibration ode Options Hazardous Locations ertifications 5 Factory Mutual (FM) explosion-proof approval I5 Factory Mutual (FM) intrinsic safety approval K5 Factory Mutual (FM) 5 and I5 combination approval I1 NL intrinsic safety and dust certification N1 NL Type N certification D NL flameproof certification 6 anadian Standards Association (SA) explosion-proof approval I6 anadian Standards Association (SA) intrinsic safety approval 6 anadian Standards Association (SA) 6 and I6 combination approval 7 Standards Association of Australia (SAA) flameproof certification (pending final approval) I7 Standards Association of Australia (SAA) intrinsic safety certification (pending final approval) N7 Standards Association of Australia (SAA) Type N certification (pending final approval) Other Options M5 LD indicator P2 leaning for special services 4 Analog output levels compliant with NAMUR recommendation N43, 18-January-1994 and high alarm level (4) N Analog output levels compliant with NAMUR recommendation N43, 18-January-1994 and low alarm level (4) R10 Remote electronics with 10 ft (3,0 m) cable R20 Remote electronics with 20 ft (6,1 m) cable R30 Remote electronics with 30 ft (9,1 m) cable RXX Remote electronics with customer-specified cable length (up to 75 ft (23 m) imum) (5) T1 Transient protection teral block V5 xternal ground screw assembly (6) 22

23 Rosemount Inc. Options ontinue ertification Options Q4 alibration data sheet per ISO B Q8 Material traceability certification per ISO B Q14 German TRB 801 Nr.45 certification per ISO B (7) Q69 Inspection certificate weld exaation (wafer) per ISO B (8) Q70 Inspection certificate weld exaation (flanged) per ISO B Q71 Inspection certification weld exaation (flanged) per ISO B (includes x-rays) Typical Model Number: 8800 F 020 S A1 N 1 D 1 M5 (1) 1 /2-in. (15 mm) through 4-in. (100 mm) flanged-style meters are with A1, A3, A6, 1, 3, D1, D3, D6, H1, H3, J1, J2, and J4 flange codes only. 6-in, (150mm) and 8-in. (200 mm) are only available in A1, A3, A6, D1, D3, D6, J1, J2, and J4 flange codes. 1 /2-in. (15mm)through 4-in. (100mm) with flange codes A1, A3, A6, 1, and 3; 2-in. (50 mm) through 4-in. (100mm) with flange codes D1, D3, H1, and H3 codes use lap joint flanges; all others use weld-neck flanges. (2) Only available for stainless steel flanged and dual-sensor style meters in line sizes 1-in. (25 mm) through 4-in. (100 mm). (3) D6 and H6 are not available for stainless steel 3-in. (80 mm) wafer meter style). (4) NAMUR compliant operation and the alarm latch options are pre-set at the factory and cannot be changed to standard operation in the field. (5) XX is a customer specified length in feet. (6) V5 only available with no approval or 5, I5, K5, 6, I6, and 6; it is standard with the other approvals. (7) Q14 is not available with flange codes A7, B7, 7, D7, G7, H7 and 10in.-12in. meters. (8) Q69 available for all Hastelloy wafers and stainless steel wafers in line sizes 1 /2-in. (15 mm), 6-in. (150 mm), and 8-in. (200 mm). TABL 22. DS Default onfiguration Item U.S. Unit (SI Unit) Service: liquid Flow rate: 0 to meter imum flow, GPM (AMH) Density: 62.4 lb/ft 3 Operating Temperature: Pipe ID: Service: LD onfiguration: Alarm: Security: Burst Mode: Software Tag: (1000 kg/m 3 ) 77 F (25 ) Schedule 40 line sizes liquid Alternating between % of range and flow rate High Off Off (Blank) 23

24 Model 8800 Smart Vortex Flowmeter 24

25 Rosemount Inc. onfiguration Data Sheet APPLIATION AND ONFIGURATION DATA SHT RQUIRD WITH ORDR Sold to: P.O. #: nd ustomer: Model No: 8800 SST Tag #: (21 characters imum) Software Tag #: (8 characters imum) Default onfiguration** U.S. Units Name: Date: S.I. Units Service: Liquid Gas Steam Fluid Description: Flow Rates: Maximum URV (20 ma value) (Default value is imum). Minimum LRV (4 ma value) 0 (Minimum flow to be measured not LRV) ( If you want LRV 0; enter desired value here ) Flow Rate Units: gal/s igal/s l/s AFM AMM kg/s lb/s gal/ igal/ l/ AFH AMH kg/ lb/ gal/h igal/h l/h AFD AMD kg/h lb/h gal/d igal/d l/d bbl/ MAMD kg/d lb/d ton/h bbl/h ston/h ft/s m/s ton/d bbl/d ston/d (1 bbl = 42 gal., 1 ston = 2000 lb, 1 ton = 1000 kg) If you select one of the following units, be sure to fill out the density ratio information below: NMD SFM SFH NMM NMH Density Ratio (from sizing program) Note: If no density ration is given, calculate the ratio with an assumed base pressure of psia, a base temperature of 59 F, and a base compressibility of one (1) for SFM and SFH. For NMM, NMH, and NMD, calculate with a base pressure of 1,01 bar, a base temperature of 0, and a base compressibility of one (1). Special: Special flow rate units (4 characters) / Second Minute Hour Day Special units conversion number: (1 Base Volume Unit = onversion Number, number of Special Units; ex. 1 gal = 1/31 barrels) Base volume unit: ubic ft Gallons Barrels ubic m Liters Imp. Gal Note: The Model 8800A/ measures actual volumetric flow rates. To use units not shown above, a conversion factor must be entered into the electronics through the use of special units. Use of this special conversion factor or the density value (used in mass flow units) requires that the process density remain constant. hanges in the process density will result in an inaccurate flow output. Operating Temperature F Operating Pressure Gauge Absolute Operating Density or Specific Gravity Viscosity (At operating temperature) Vapor Pressure (At operating temperature required for liquids only) Mating Pipe Schedule Sch 10 Sch 40 Sch 80 (Will default to Sch 40; Pipe I.D., dependent on line size) OR Mating Pipe I.d. inches mm Signal Options - required only if output Option ode P is selected ma and scaled pulse-digital smart electronics with HART protocol Pulse Mode: Direct Scaled (1 Pulse = unit) (e.g. 1 pulse = 1 gal or 1 pulse = 1 lb) Off OR ( Hz= unit) (e.g., 1000 Hz = 10 gal/) For Rosemount Internal Use Only Sales Order Line Item # ID # ont. Ad. Salesperson 25

26 Model 8800 Smart Vortex Flowmeter APPLIATION AND ONFIGURATION DATA SHT (Optional Information) Other Functions LD onfiguration: (Select as many as desired) Damping % of Range* Flow Rate* Output urrent Totalizer 2 seconds* Other (Value between 0.2 and 255 seconds.) Hardware Selectable: Alarm Security High* Low Off* On * Default setting if no options are selected Transmitter Information Descriptor (16 characters imum) Message (32 characters imum) Date: / / or / / : Default is date of calibration (Month/Day/Year) Month / Day / Year or Day / Month / Year HART Output Options The following output options are specifically used for special HART ommunications configurations Burst mode of HART digital process variable (Select one option below.) Primary variable in engineering units Primary variable in percent of range **By selecting Default onfiguration, Rosemount Inc. does not verify flowmeter sizing for your application. 26

THE ROSEMOUNT 8800C DELIVERS RELIABILITY Rosemount Reliability -The 8800C Vortex eliates impulse lines, ports, and gaskets to improve reliabil

THE ROSEMOUNT 8800C DELIVERS RELIABILITY Rosemount Reliability -The 8800C Vortex eliates impulse lines, ports, and gaskets to improve reliabil E-MAIL: Vortex Flowmeter HART AND FOUNDATION FIELDBUS PROTOCOLS Available in wafer, flanged, dual, and reducer designs. Only manufacturer of Reducer Vortex which extends the measurable flow range, reduces

More information

Rosemount 8800D Series Vortex Flowmeter

Rosemount 8800D Series Vortex Flowmeter Product Data Sheet HART AND FOUNDATION FIELDBUS PROTOCOLS Available in wafer, flanged, dual, reducer and high pressure designs. Only manufacturer of Reducer Vortex which extends the measurable flow range,

More information

Rosemount 8800D Series Vortex Flowmeter

Rosemount 8800D Series Vortex Flowmeter Product Data Sheet HART AND FOUNDATION FIELDBUS PROTOCOLS Available with optional MultiVariable output and temperature compensated mass flow for saturated steam. Available in wafer, flanged, dual, reducer

More information

Rosemount 8800D Series Vortex Flowmeter

Rosemount 8800D Series Vortex Flowmeter Product Data Sheet HART AND FOUNDATION FIELDBUS PROTOCOLS Available with optional MultiVariable output and temperature compensated mass flow for saturated steam. Available in wafer, flanged, dual, reducer

More information

Rosemount 8800D Series Vortex Flowmeter

Rosemount 8800D Series Vortex Flowmeter Product Data Sheet November 2014 00813-0100-4004, Rev KA Rosemount 8800D Series Vortex Flowmeter HART and FOUNDATION fieldbus Protocols All welded, non-clog design provides imum performance, reliability

More information

Model 8800C Vortex Flowmeter

Model 8800C Vortex Flowmeter Vortex Flowmeter Start Step 1: Mount the Flowmeter Step 2: Consider Housing Rotation Step 3: Set the Jumpers Step 4: Connect the Wiring and Power Up Step 5: Review Flowmeter Configuration Product Certifications

More information

Satellite photo of cloud vortices caused by a mountain (Courtesy of our friends at NASA) tekvorx Operation Showing Simplified Construction

Satellite photo of cloud vortices caused by a mountain (Courtesy of our friends at NASA) tekvorx Operation Showing Simplified Construction Sensing the pulse of industry tekvorx TV01 Multivariable Vortex flow Sensors Vortex flow sensors derive their name from a natural phenomenon of fluid dynamics. When a gas or relatively low viscosity liquid

More information

Rosemount 8800D Series Vortex Flowmeter

Rosemount 8800D Series Vortex Flowmeter Product Data Sheet October 2017 00813-0100-4004, Rev KE Rosemount 8800D Series Vortex Flowmeter HART and FOUNDATION Fieldbus Protocols All welded, non-clog design provides imum performance, reliability

More information

Vortex Flowmeters VFM 3100 F-T VFM 3100 W-T

Vortex Flowmeters VFM 3100 F-T VFM 3100 W-T KROHNE 10/2001 7.02313.23.00 GR/OP Vortex Flowmeters F-T W-T Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass flowmeters Level measuring

More information

PanaFlow MV80. In-line Multivariable Flowmeter for Mass, Temperature, and Pressure. GE Sensing. Applications. Key Benefits

PanaFlow MV80. In-line Multivariable Flowmeter for Mass, Temperature, and Pressure. GE Sensing. Applications. Key Benefits Key Benefits Multivariable vortex flowmeter for measuring volumetric flow, temperature, pressure, density, and mass flow using a single meter Measures most gases, liquids and steam without the need to

More information

Vortex In Line Flow Meter

Vortex In Line Flow Meter Principles of Operation Vortices are created when a fluid passes around a bluff body as shown below. Vortices are alternately shed on each side of the body, 0 degrees out of phase to each other, resulting

More information

VersaFlow Vortex 100 Vortex Flow Meter Specifications

VersaFlow Vortex 100 Vortex Flow Meter Specifications VersaFlow Vortex 100 Vortex Flow Meter Specifications 34-VF-03-05 May 2011 The All-In-One Solution The VERSAFLOW is the only vortex flowmeter with integrated and temperature compensation in 2- wire technology.

More information

Rosemount 8750WB Magnetic Flowmeter System

Rosemount 8750WB Magnetic Flowmeter System Rosemount 8750WB Magnetic Flowmeter System for Utility, Water, and Wastewater Applications Product Data Sheet 00813-0200-4750 Rev AA THE 8750W MAGNETIC FLOWMETER Rosemount reliability customized for Water,

More information

Rosemount 8750WA Magnetic Flowmeter System For Water and Wastewater Industries

Rosemount 8750WA Magnetic Flowmeter System For Water and Wastewater Industries Product Data Sheet January 214 813-1-475, Rev FA Rosemount 875WA Magnetic Flowmeter System For Water and Wastewater Industries THE 875WA MAGNETIC FLOWMETER Rosemount reliability in a customized offering

More information

VORTEX IN-LINE FLOW METERS

VORTEX IN-LINE FLOW METERS VORTEX IN-LINE FLOW METERS Principles of Operation Vortices are created when a fluid passes around a bluff body as shown below. Vortices are alternately shed on each side of the body, degrees out of phase

More information

Vortex In Line Flow Meter

Vortex In Line Flow Meter Vortex In Line Flow Meter Principles of Operation Vortices are created when a fluid passes around a bluff body as shown below. Vortices are alternately shed on each side of the body, 0 degrees out of phase

More information

Rosemount 1810 Flush Mount Pressure Transmitter ROSEMOUNT 1810 FEATURES:

Rosemount 1810 Flush Mount Pressure Transmitter ROSEMOUNT 1810 FEATURES: Rosemount 1810 Rosemount 1810 Flush Mount Pressure Transmitter ROSEMOUNT 1810 FEATURES: A cleanable and compact stainless steel design An innovative patented venting configuration that prevents gauge reference

More information

Pro-V Multivariable Flowmeter Model M24 In-line Vortex

Pro-V Multivariable Flowmeter Model M24 In-line Vortex Pro-V Multivariable Flowmeter Model M24 In-line Vortex Pro-V TM Advantage: VorTek Instruments Pro-V multivariable flowmeters utilize three primary sensing elements a vortex shedding velocity sensor, an

More information

Innova-Mass Model 240 & 241. Multivariable Mass Vortex Flow Meter. For information online...

Innova-Mass Model 240 & 241. Multivariable Mass Vortex Flow Meter. For information online... Multivariable Mass Vortex Flow Meter Features Volumetric or mass flow monitoring of gases, liquids and steam Smart electronics extends range down to a Reynolds number of 5000 Ideal for steam applications

More information

F-2600 SERIES INLINE VORTEX FLOW METER

F-2600 SERIES INLINE VORTEX FLOW METER F-2600 SERIES INLINE VORTEX FLOW METER APPLICATIONS Saturated steam Hot water to 500 F (260 C) standard 750 F (400 C) optional Applications with optional pressure sensor Superheated steam to 500 F (260

More information

Armstrong In-Line and Insertion Vortex Flow Meters

Armstrong In-Line and Insertion Vortex Flow Meters Armstrong In-Line and Insertion Vortex Flow Meters Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. 1 In-Line

More information

F-1500 SERIES INSERTION TURBINE FLOW METER FEATURES Belcher Road South, Largo, FL USA Tel +1 (727) Fax +1 (727)

F-1500 SERIES INSERTION TURBINE FLOW METER FEATURES Belcher Road South, Largo, FL USA Tel +1 (727) Fax +1 (727) F-1500 SERIES INSERTION TURBINE FLOW METER Insertion turbine flow meters are ideal for use in larger steam lines where downsizing the line size to improve flow measurement is not desirable. In these applications,

More information

Smart Pressure Transmitter

Smart Pressure Transmitter DOC. NO.: C3100L-E16B Smart Pressure Transmitter with Diaphragm Seal MODEL APT3100L DUON System Co., Ltd. 298-29, GONDAN-RO, GUNPO-SI, GYEONGGI-DO, KOREA 15809 Tel : +82-31-3-6100 Fax : +82-31-29-7200

More information

F-2700 SERIES INSERTION VORTEX FLOW METER

F-2700 SERIES INSERTION VORTEX FLOW METER F-2700 SERIES INSERTION VORTEX FLOW METER CALIBRATION Every ONICON flow meter is wet calibrated in a flow laboratory against standards that are directly traceable to N.I.S.T. A certificate of calibration

More information

InnovaMass 240 & 241. Multivariable Mass Vortex Flow Meter. FEATURES DESCRIPTION

InnovaMass 240 & 241. Multivariable Mass Vortex Flow Meter.   FEATURES DESCRIPTION Multivariable Mass Vortex Flow Meter FEATURES Mass and volumetric flow measurement of gas, liquid, and steam Multivariable outputs for five process parameters: mass flow rate volumetric flow rate temperature

More information

Multivariable Vortex Flow Meter

Multivariable Vortex Flow Meter Multivariable Vortex Flow Meter DVH Sensor Design w/o sealing Fully welded sensor Integrated temperature and pressure measurement (optional) Calculation of mass and density possible High temperature version

More information

Rosemount 3051CFA Annubar Flowmeter

Rosemount 3051CFA Annubar Flowmeter December 2013 Rosemount 3051 Rosemount 3051CFA Annubar Flowmeter The Rosemount 3051CFA Annubar Flowmeter utilizes the patented T-shaped sensor design that delivers best in class accuracy and performance.

More information

F-2700 SERIES INSERTION VORTEX FLOW METER

F-2700 SERIES INSERTION VORTEX FLOW METER F-2700 SERIES INSERTION VORTEX FLOW METER APPLICATIONS Saturated steam Hot water to 500 F (260 C) standard 750 F (400 C) optional Applications with optional pressure sensor Superheated steam to 500 F (260

More information

Multivariable Vortex Flow Meter

Multivariable Vortex Flow Meter Multivariable Vortex Flow Meter DVH Sensor Design w/o sealing Fully welded sensor Integrated temperature and pressure measurement (optional) Calculation of mass and density possible High temperature version

More information

Low Profile Insertion Vortex

Low Profile Insertion Vortex Low Profile Insertion Vortex Product Features The same insertion meter can measure Steam, Gases or Liquids. Standardize on an insertion bar that can measure line sizes 2 24 Heavy Duty & Maintenance Free

More information

STEEMCO Flowmeter for Steam

STEEMCO Flowmeter for Steam STEEMCO Flowmeter for Steam Typical Applications The STEEMCO flow meters measure the flow of saturated and superheated steam within the process industries, including chemical, petro-chemical, pharmaceutical

More information

VLM20 In-line Vortex Flowmeter

VLM20 In-line Vortex Flowmeter ocal regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

F-1500 SERIES INSERTION TURBINE FLOW METER

F-1500 SERIES INSERTION TURBINE FLOW METER F-1500 SERIES INSERTION TURBINE FLOW METER APPLICATIONS Saturated steam Hot water to 450 F (232 C) standard 850 F (454 C) optional Applications with optional pressure sensor Superheated steam to 450 F

More information

Product Data Sheet , Rev GA Catalog Content

Product Data Sheet , Rev GA Catalog Content HIGHLY ACCURATE SMALL-BORE FLOW MEASUREMENT CAPABILITY WITH MINIMAL INSTALLATION AND MAINTENANCE REQUIREMENTS Improves accuracy and repeatability in 1 /2-in., 1-in., and 1 1 /2-in. line sizes Reduces leak

More information

220 Series Innova-Flo o

220 Series Innova-Flo o Smart Vortex Flow Meter Features Volumetric flow monitoring of most gases, liquids and steam Smart electronics extends range down to a Reynolds number of 5000 Insertion style allows installation in any

More information

Hot Tap Insertion Vortex

Hot Tap Insertion Vortex Hot Tap Insertion Vortex Product Features The same insertion meter can measure Steam, Gases or Liquids. Standardize on an insertion bar that can measure line sizes 2 48 Heavy Duty & Maintenance Free Design

More information

Smart Pressure Transmitter

Smart Pressure Transmitter DOC. NO.: C3500L-E16A Smart Pressure Transmitter with Diaphragm Seal MODEL APT3500L 298-29, GONDAN-RO, GUNPO-SI, GYEONGGI-DO, KOREA 15809 Tel : +82-31-3-6100 Fax : +82-31-29-7200 E-mail: autrol@duon.co.kr,

More information

VIM20 Vortex Insertion Flowmeter

VIM20 Vortex Insertion Flowmeter Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

VersaFlow Vortex 100 Vortex Flow Meter Specifications

VersaFlow Vortex 100 Vortex Flow Meter Specifications VersaFlow Vortex 100 Vortex Flow Meter Specifications 34-VF-03-05 May 2011 The All-In-One Solution The VERSAFLOW is the only vortex flowmeter with integrated pressure and temperature compensation in 2-

More information

STEEMCO-MAS Flowmeter for Steam

STEEMCO-MAS Flowmeter for Steam STEEMCO-MAS Flowmeter for Steam Typical Applications The STEEMCO-MAS flow meters measure the mass flow of superheated steam within the process industries, including chemical, petro-chemical, pharmaceutical

More information

The readings you need, right where you need them. AX Series Vortex Meters

The readings you need, right where you need them. AX Series Vortex Meters The readings you need, right where you need them. AX Series Vortex Meters Multivariable function from a single meter Vortex multivariable meters from Azbil North America employ three sensing elements in

More information

F-2600 SERIES INLINE VORTEX FLOW METER

F-2600 SERIES INLINE VORTEX FLOW METER F-2600 SERIES ININE VORTEX FOW METER APPICATIONS Saturated steam Hot water to 500 F (260 C) standard 750 F (400 C) optional Applications with optional pressure sensor Superheated steam to 500 F (260 C)

More information

Rosemount 1151 Pressure Transmitter

Rosemount 1151 Pressure Transmitter Product Data Sheet Rosemount 1151 Rosemount 1151 Pressure Transmitter Proven field performance and reliability Commitment to continuous improvement Reference accuracy of 0.075% Two-year stability of 0.1%

More information

Smart Pressure Transmitter

Smart Pressure Transmitter DOC. NO.: C3200L-E16B Smart Pressure Transmitter with Diaphragm Seal MODEL APT3200L DUON System Co., Ltd. 298-29, GONDAN-RO, GUNPO-SI, GYEONGGI-DO, KOREA 15809 Tel : +82-31-3-6100 Fax : +82-31-29-7200

More information

INTERPLANT STANDARD - STEEL INDUSTRY. Specification for Smart Pressure & Differential Pressure Transmitter

INTERPLANT STANDARD - STEEL INDUSTRY. Specification for Smart Pressure & Differential Pressure Transmitter INTERPLANT STANDARD - STEEL INDUSTRY IPSS Specification for Smart Pressure & Differential Pressure Transmitter Corresponding IS does not exist IPSS: 2-07-104-15 1. Scope 1.1 This Interplant Standard covers

More information

Rosemount DP Flowmeters and Primary Elements

Rosemount DP Flowmeters and Primary Elements meters and Primary Elements Multivariable capabilities allow for real time fully compensated mass and energy flow Fully-Integrated Wireless Flowmeters allow for easy installation Minimize permanent pressure

More information

Model 1151 Alphaline Pressure Transmitters

Model 1151 Alphaline Pressure Transmitters Alphaline Pressure Transmitters FEATURES A complete family of transmitters Ranges from 0 0.5 inh 2 0 to 6,000 psig (1.24 kpa to 41370 kpa) Solid-state, plug-in circuit boards Compact, rugged construction

More information

Model FVP General Specification. Flanged Vortex Plate. Product Features

Model FVP General Specification. Flanged Vortex Plate. Product Features Flanged Vortex Plate Product Features Our Inline meters can measure Steam, Gases or Liquids. Measures two times lower than any other Vortex Meter. Heavy Duty & Maintenance Free Design C&C Machined from

More information

The EPSILON is based on the principle of measuring velocity in the pipe line, therefore the flow measurement is volumetric.

The EPSILON is based on the principle of measuring velocity in the pipe line, therefore the flow measurement is volumetric. Typical Applications EPSILON Flowmeter The EPSILON flow meters measure the flow of most liquids and gases within the process industries, including chemical, petro-chemical, pharmaceutical and the power

More information

VIM20 Vortex Insertion Flowmeter

VIM20 Vortex Insertion Flowmeter VIM20 Principle of Operation Vortex flowmeters measure flows of liquid, gas and steam by detecting the frequency at which vortices are alternately shed from a bluff body. According to proven laws of physics,

More information

Rosemount 3051T In-Line Pressure Transmitter

Rosemount 3051T In-Line Pressure Transmitter Rosemount 3051T In-Line Pressure Transmitter Rosemount 3051T In-line Pressure Transmitters are the industry standard for Gage, and Absolute pressure measurement. The in-line, compact design allows the

More information

ORIMAS Mass Flowmeter

ORIMAS Mass Flowmeter Typical Applications ORIMAS Mass Flowmeter The ORIMAS mass flow meters measure the mass flow of most liquids and gases within the process industries, including chemical, petro-chemical, pharmaceutical

More information

Vortex Plate. Model VP General Specification. Product Features

Vortex Plate. Model VP General Specification. Product Features Vortex Plate Product Features Our Inline meters can measure Steam, Gases or Liquids. Heavy Duty & Maintenance Free Design C&C Machined from one piece of solid stainless steel Absolutely NO o-rings or seals

More information

Smart Pressure Transmitter

Smart Pressure Transmitter DOC. O.: C3700-L-E16A Smart Pressure Transmitter with Diaphragm Seal MODEL APT3700-L 298-29, GODA-RO, GUPO-SI, GYEOGGI-DO, KOREA 15809 Tel : +82-31-3-6100 Fax : +82-31-29-7200 E-mail: autrol@duon.co.kr,

More information

The readings you need, right where you need them. AX Series Vortex Meters

The readings you need, right where you need them. AX Series Vortex Meters The readings you need, right where you need them. AX Series Vortex Meters Multivariable function from a single meter Principles of Operation Vortex multivariable meters from Azbil North America employ

More information

F-2500 SERIES VORTEX METER

F-2500 SERIES VORTEX METER F-500 SERIES VORTEX METER APPLICATIONS Saturated steam Hot water to F (0 C) Applications with optional pressure sensor Superheated steam to F (0 C) Compressed air Industrial gases CALIBRATION Each meter

More information

Rosemount 3051S Electronic Remote Sensor (ERS) System

Rosemount 3051S Electronic Remote Sensor (ERS) System Rosemount 3051S Electronic Remote Sensor (ERS) System The Rosemount 3051S ERS System is a flexible, 2-wire 4-20 ma ART architecture that calculates differential pressure (DP) electronically using two pressure

More information

Digital Vortex Flowmeter. digitalyewflo. Digital Vortex Flowmeter. Series

Digital Vortex Flowmeter. digitalyewflo. Digital Vortex Flowmeter. Series Digital Vortex meter digitalyewflo Digital Vortex meter Series Unrivaled Performance, Functionality and Ease of Use Series Standard Type / Multi-variable Type High Temperature / Cryogenic Type Reduced

More information

VORTEX FLOW METTER DVH. Despriction. Advantages of the DVH Vortex Flow Meter

VORTEX FLOW METTER DVH. Despriction. Advantages of the DVH Vortex Flow Meter R VORTEX FLOW METTER DVH Measuring range: 3-8... 3 057-280 187 m3n/h Accuray: ± 0,7 % of reading (liquids) ± 1 % of reading (gases and steam) P m a x : 100 bar abs; tm ax : 400 C Connection: ANSI ½ up

More information

VIM20 Vortex Insertion Flowmeter

VIM20 Vortex Insertion Flowmeter Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

Product Data Sheet 2012 Rev 5 FLOWMETRIX SA SAFMAG Electromagnetic Flowmeter Doc Date

Product Data Sheet 2012 Rev 5 FLOWMETRIX SA SAFMAG Electromagnetic Flowmeter Doc Date FLOWMETRIX SA Doc Date 17.07.2012 PERFORMANCE * 0,5% of rate (Standard) * 0,25% of rate (Optional) * 1000 : 1 operable flow range * Excellent repeatability * Optional Bi-directional measurement * Advanced

More information

Metal tube variable area flowmeter for gases, liquids and steam

Metal tube variable area flowmeter for gases, liquids and steam Metal tube variable area flowmeter for gases, liquids and steam Metallic or plastic tube with a robust construction Indication by means of magnetic coupling Scales calibrated in l/h, m 3 /h, kg/h, t/h,

More information

Rosemount Product Data Sheet , Rev GA Catalog FIELDBUS PROTOCOL. Hazardous Locations Certifications

Rosemount Product Data Sheet , Rev GA Catalog FIELDBUS PROTOCOL. Hazardous Locations Certifications Product Data Sheet Rosemount 3051 FIELDBUS PROTOCOL Hazardous Locations Certifications North American Certifications FM Approvals E5 Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof

More information

Rosemount 4088 MultiVariable Transmitter

Rosemount 4088 MultiVariable Transmitter Product Data Sheet January 2018 00813-0100-4088, Rev BA Rosemount 4088 MultiVariable Transmitter With the innovative Rosemount 4088 MultiVariable Transmitter, you can maximize your measurement accuracy

More information

Metal tube flowmeters. Series SC250. Metal Tube Flow Meters. Series SC250. Variable area flowmeter for liquids, gases and steam

Metal tube flowmeters. Series SC250. Metal Tube Flow Meters. Series SC250. Variable area flowmeter for liquids, gases and steam Metal tube flowmeters Variable area flowmeter for liquids, gases and steam Metallic or plastic tube with a robust construction Indication by means of magnetic coupling Scales calibrated in l/h, m 3 /h,

More information

9900 Series Oval Flowmeter/Transmitter with SMART METER MANAGER

9900 Series Oval Flowmeter/Transmitter with SMART METER MANAGER Design Specifications DS-9900 Revision 04 9900 Series Oval Flowmeter/Transmitter with SMART METER MANAGER 2-Wire loop powered flowmeter/transmitter 316 Stainless steel measuring unit Automatic temperature

More information

DVH. Vortex Flowmeter. Measuring range: Nm³/h. Accuracy: ± 0,7% of reading (liquids) ± 1% of reading (gases and steam) p max

DVH. Vortex Flowmeter. Measuring range: Nm³/h. Accuracy: ± 0,7% of reading (liquids) ± 1% of reading (gases and steam) p max Vortex Flowmeter measuring monitoring analysing DVH Measuring range: 3-8... 3057-280187 Nm³/h Accuracy: ± 0,7% of reading (liquids) ± 1% of reading (gases and steam) p max : 100 bar abs; t max : 400 C

More information

Type E-10, E-11 Hazardous Area Explosion-proof Transmitters

Type E-10, E-11 Hazardous Area Explosion-proof Transmitters Electronic Pressure Catalog > Hazardous Area > E-10, E-11 Type E-10, E-11 Hazardous Area Explosion-proof Transmitters Meets ANSI / ISA 12.27.01-2003 single seal requirements - no dual seal required Applications

More information

OPTIMASS 2000 Technical Datasheet

OPTIMASS 2000 Technical Datasheet OPTIMASS 2000 Technical Datasheet Sensor for bulk mass flow Large diameter for bulk measurement and custody transfer of liquids and gases Stainless Steel measuring tubes (NACE Compliant) Modular electronics

More information

METAL VAREA-METER STRAIGHT THROUGH TYPE ROTAMETER

METAL VAREA-METER STRAIGHT THROUGH TYPE ROTAMETER TECHNICAL INFORMATION METAL VAREA-METER STRAIGHT THROUGH TYPE ROTAMETER Electronic Transmitter INTRODUCING THE METAL TUBE VAREA-METER U.S. Filter/Wallace & Tiernan Products straight through metal tube

More information

OPTISWIRL 4070 Technical Datasheet

OPTISWIRL 4070 Technical Datasheet OPTISWIRL 4070 Technical Datasheet Vortex flowmeter Integrated pressure and temperature compensation Temperature compensation for saturated steam included as standard All OPTISWIRL versions in 2-wire technology

More information

AST46HA Factory Sealed Gauge / ASIC

AST46HA Factory Sealed Gauge / ASIC AST46HA Factory Sealed Gauge / ASI Explosionproof Transmitter SA Approved For Hazardous Locations Overview AST46HA high accuracy Explosionproof Transducer/Transmitter is SA approved for use in hazardous

More information

Rosemount 4088 MultiVariable Transmitter

Rosemount 4088 MultiVariable Transmitter Product Data Sheet May 2015 00813-0100-4088, Rev AC Rosemount 4088 MultiVariable Transmitter With the innovative Rosemount 4088 MultiVariable Transmitter, you can maximize your measurement accuracy and

More information

SITRANS F flowmeters SITRANS F US. SITRANS FUT1010 Ultrasonic flowmeter. Overview. Application

SITRANS F flowmeters SITRANS F US. SITRANS FUT1010 Ultrasonic flowmeter. Overview. Application Overview SITRANS F flowmeters Application Liquid applications Gas applications Pipelines Custody transfer, allocation, Upstream Production wells, line balance, gathering, separation interface/densitometer

More information

ISTEC MAGNETIC METERS

ISTEC MAGNETIC METERS ISTEC MAGNETIC METERS MEASURE ANY CONDUCTIVE LIQUIDS OR SLURRIES (EVEN ABRASIVE OR CORROSIVE) WITH THE NEW MICROPROCESSOR-BASED MAGNETIC METER -- A QUALITY PRODUCT - SIMPLE - RELIABLE - AT AN AFFORDABLE

More information

Vortex Flow Meter Model DVH

Vortex Flow Meter Model DVH Vortex Flow Meter measuring monitoring analysing DVH Measuring range: 3-8... 3057-280187 Nm³/h Accuracy: ± 0,7 % of reading (liquids) ± 1 % of reading (gases and steam) p max : 100 bar abs; t max : 400

More information

Rosemount DP Flowmeters and Primary Elements

Rosemount DP Flowmeters and Primary Elements Product Data Sheet Rosemount DP Flowmeters and Primary Elements Rosemount DP Flow Multivariable capabilities allow for real time fully compensated mass and energy flow Fully-Integrated Wireless Flowmeters

More information

Series Level-Trol Electronic Liquid Level Transmitters

Series Level-Trol Electronic Liquid Level Transmitters 0- Level-Trol Series 0- Series Level-Trol Electronic Liquid Level Transmitters W0-/IL Non-Interactive Zero and Span Adjustments; Dry Span Calibration Allows Field Recalibration without Removing Wiring

More information

SMART VALVE POSITIONER 4 to 20 ma + HART Digital Communication. smar B87

SMART VALVE POSITIONER 4 to 20 ma + HART Digital Communication. smar B87 SMART VALVE POSITIONER to ma + HART Digital Communication B87 DESCRIPTION The FY microprocessor based positioner provides fast and accurate positioning of diaphragm or cylinder actuators. The FY produces

More information

Digital Vortex Flowmeter. digitalyewflo. Digital Vortex Flowmeter. Series. Bulletin 01F06A02-00E.

Digital Vortex Flowmeter. digitalyewflo. Digital Vortex Flowmeter. Series. Bulletin 01F06A02-00E. Digital Vortex meter digitalyewflo Digital Vortex meter Series Bulletin 01F06A02-00E www.yokogawa.com/ Series Simple body construction for easy installation and high level of safety 2 3 Standard Type /

More information

OPTISWIRL 4070 Technical Datasheet

OPTISWIRL 4070 Technical Datasheet OPTISWIRL 4070 Technical Datasheet Vortex flowmeter Integrated pressure and temperature compensation Temperature compensation for saturated steam included as standard All OPTISWIRL versions in 2-wire technology

More information

Rosemount 3051 Pressure Transmitter

Rosemount 3051 Pressure Transmitter Rosemount 3051 Rosemount 3051 Pressure Transmitter HART AND FIELDBUS PROTOCOLS Industry s best total performance of ±0.15% Five year stability of ±0.125% Unmatched dynamic performance Coplanar platform

More information

Intrinsically safe presure transmitters for hazardous environments Type MBS 4201, MBS 4251, MBS 4701 and MBS Technical brochure

Intrinsically safe presure transmitters for hazardous environments Type MBS 4201, MBS 4251, MBS 4701 and MBS Technical brochure Intrinsically safe presure transmitters for hazardous environments Type MBS 4201, MBS 4251, MBS 4701 and MBS 4751 Technical brochure Features Ex ll 1G EEx ia llc T4 - T6 in compliance with ATEX 100a Applicable

More information

M3500 Industrial Pressure Transmitter

M3500 Industrial Pressure Transmitter M3500 Industrial Pressure Transmitter The M3500 is a high accuracy industrial pressure transmitter featuring HART communications and a cast aluminum enclosure for indoor or outdoor use. Typical output

More information

SITRANS F X SITRANS FX300 3/355

SITRANS F X SITRANS FX300 3/355 Siemens AG 204 Flow Measurement Overview vortex flowmeters provide accurate volumetric and mass flow measurement of steam, gases and liquids as an all-in-one solution with integrated temperature and pressure

More information

Rosemount 3051S Series of Instrumentation

Rosemount 3051S Series of Instrumentation Product Data Sheet 3051S Series delivers highest field performance and reliability SuperModule Platform provides a foundation for integrated pressure, flow, and level solutions IEC 62591 (WirelessHART

More information

RIM20 Rotor Insertion Flowmeter

RIM20 Rotor Insertion Flowmeter Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

Rosemount 3051 Pressure Transmitter

Rosemount 3051 Pressure Transmitter Product Data Sheet Rosemount 3051 Rosemount 3051 Pressure Transmitter THE PROVEN INDUSTRY LEADER IN PRESSURE MEASUREMENT Best-in-Class performance with 0.04% High Accuracy option Industry first installed

More information

Rosemount DP Flowmeters and Primary Elements

Rosemount DP Flowmeters and Primary Elements Product Data Sheet March 2015 00813-0100-4485, Rev FB Rosemount DP Flowmeters and Primary Elements Multivariable capabilities allow for real time fully compensated mass and energy flow Fully-Integrated

More information

F6700 ELECTROMAGNETIC METER

F6700 ELECTROMAGNETIC METER EETROMAGNETI FOW TRANSMITTER Special Features: F6700 Full Bore type Simple and ost effective onstruction Absolutely Maintenance free Suitable for all conductive liquids and slurries Outstanding Accuracy

More information

SITRANS FX300 4/289. System Overview. Overview

SITRANS FX300 4/289. System Overview. Overview Siemens G 2008 SITRNS F flowmeters Overview System Overview Version Single transmitter Dual transmitter Options Standard Pressure sensor Flange Pressure sensor and isola- Standard tion valve Sandwich vortex

More information

RCM - Direct Reading Flowmeters

RCM - Direct Reading Flowmeters Compact Design Easy to Install Horizontal or Vertical Installation Flow Rates up to 3000 GPM (Liquid) or 20000 SCFM (Gas) Low Pressure Drop Optional Alarms and Output Signals Accuracy: ± 3% of full scale

More information

VersaFlow Vortex 100 Vortex Flow Meter Technical Datasheet. Specification. The all-in-one solution. Highlights. Industries.

VersaFlow Vortex 100 Vortex Flow Meter Technical Datasheet. Specification. The all-in-one solution. Highlights. Industries. VersaFlow Vortex 100 Vortex Flow Meter Technical Datasheet 34-VF-03-05 September 3rd, 2008 Specification The all-in-one solution The VERSAFLOW is the only vortex flowmeter with integrated pressure and

More information

VFM4070C SWIRLMAX. Vortex Flowmeter OUTLINE FEATURES OPERATING PRINCIPLE STANDARED SPECIFICATION. General Specification. Sensor Specification

VFM4070C SWIRLMAX. Vortex Flowmeter OUTLINE FEATURES OPERATING PRINCIPLE STANDARED SPECIFICATION. General Specification. Sensor Specification SWIRMAX VFM4070C Vortex Flowmeter OUTINE SWIRMAX is 2-wire, all-in-one type vortex flowmeter with both temperature and pressure sensors integrally mounted into the housing. It allows temperature and pressure

More information

MagneW Neo+ Two-wire Electromagnetic Flowmeter Integral type TIIS Explosion-protected Apparatus

MagneW Neo+ Two-wire Electromagnetic Flowmeter Integral type TIIS Explosion-protected Apparatus MagneW Neo+ Two-wire Electromagnetic Flowmeter Integral type TIIS Explosion-protected Apparatus OVERVIEW The MagneW Neo+ is a high performance two wired electromagnetic flowmeter based on field proven

More information

KDM ARMORED FLOW METER & SWITCH

KDM ARMORED FLOW METER & SWITCH KDM ARMORED FLOW METER & SWITCH Flow Pressure Level Temperature measurement monitoring control S2 Short Installation Length SS, PTFE or Hastelloy Wetted Parts Analog Output Available 110 F to + 390 F Temperature

More information

Micro Motion ELITE High Capacity Coriolis Flow and Density Meters

Micro Motion ELITE High Capacity Coriolis Flow and Density Meters Product Data Sheet PS-001041, Rev. F February 2010 Micro Motion ELITE High Capacity Coriolis Flow and Density Meters Micro Motion ELITE High Capacity Coriolis meters offer unparalleled flow and density

More information

Hydro-Flow Model 3100 Retractable Insertion Vortex Flowmeter Installation and Operation Manual

Hydro-Flow Model 3100 Retractable Insertion Vortex Flowmeter Installation and Operation Manual Hydro-Flow Model 00 Retractable Insertion Vortex Flowmeter Installation and Operation Manual Table of Contents Model and Suffix Codes. Theory and Identification.. Installation Guidelines Mechanical Drawing:

More information

Rosemount 3051 Pressure Transmitter

Rosemount 3051 Pressure Transmitter Product Data Sheet Rosemount 3051 Rosemount 3051 Pressure Transmitter THE PROVEN INDUSTRY LEADER IN PRESSURE MEASUREMENT Best-in-Class performance with 0.04% High Accuracy option Industry first installed

More information

BARTON 7400 Precision Gas Turbine Flow Meters

BARTON 7400 Precision Gas Turbine Flow Meters TECHNICAL SPECIFICATIONS BARTON 7400 Precision Gas Turbine Flow Meters BARTON Model 7400 Precision Turbine Flow Meters are designed for gas service in a wide range of industrial, commercial, pipeline and

More information