Title: WF Report No: Prepared for: Simonswerk UK Ltd. Burcott Works, Spring Street, Tipton, West Midlands, DY4 8TF. Date: 20 th April 2012

Size: px
Start display at page:

Download "Title: WF Report No: Prepared for: Simonswerk UK Ltd. Burcott Works, Spring Street, Tipton, West Midlands, DY4 8TF. Date: 20 th April 2012"

Transcription

1 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) F : +44 (0) E : warrington@exova.com W: Title: The fire resistance performance of two specimens of single-acting doorsets incorporating various items of building hardware when tested in accordance with BS EN : 2008 WF Report No: Prepared for: Simonswerk UK Ltd. Burcott Works, Spring Street, Tipton, West Midlands, DY4 8TF. Date: 20 th April 2012 Notified Body No: Registered Office: Exova (UK) Ltd, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Reg No.SC 70429

2 Page 2 of 32 Summary Objective Sponsor Summary of the Tested Specimens To determine the fire resistance performance of two specimens of single-acting doorsets incorporating two different hinge models when tested in accordance with BS EN : Simonswerk UK Ltd. Burcott Works, Spring Street, Tipton, West Midlands. For the purposes of the test the doorsets were referenced Doorset A and Doorset B. Doorset A had overall dimensions of 2020 mm high by 1027 mm wide and incorporated a door leaf of overall dimensions 1980 mm high by 933 mm wide by 44 mm thick. The door leaf was hung within a softwood door frame on three Simonswerk GmbH concealed hinges, referenced TECTUS TE 340 3D FR. The hinges incorporated internal graphite based intumescent strips, referenced ROKU Strip M130. The door leaf comprised 3 layers of particleboard with 8 mm hardwood lippings to the vertical edges. Doorset B had overall dimensions of 2020 mm high by 1027 mm wide and incorporated a door leaf of overall dimensions 1980 mm high by 933 mm wide by 44 mm thick. The door leaf was hung within a softwood door frame on three Simonswerk GmbH concealed hinges, referenced TECTUS TE 640 3D A8 FR. The hinges incorporated internal graphite based intumescent strips, referenced ROKU Strip M130. The door leaf comprised 3 layers of particleboard with 8 mm hardwood lippings to the vertical edges. The leaves were orientated such that they opened towards the heating conditions of the test and were unlatched for the duration of the test. Test Results: Doorset A Doorset B Integrity Sustained Flaming 34 minutes* 34 minutes* Cotton wool pad 34 minutes* 34 minutes* Gap gauge 34 minutes* 34 minutes* Insulation 34 minutes* 34 minutes* Date of Test 13 th March 2012 *The test was discontinued after a period of 34 minutes This report may only be reproduced in full. Extracts or abridgements of reports shall not be published without permission of Exova Warringtonfire

3 Page 3 of 32 Signatories Responsible Officer S. Gilfedder* Testing Officer Approved D. Forshaw* Principal Certification Engineer Head of Department S. Hankey* Operations Manager * For and on behalf of Exova Warringtonfire. Report Issued Date : 20 th April 2012 This version of the report has been produced from a.pdf format electronic file that has been provided by Exova Warringtonfire to the sponsor of the report and must only be reproduced in full. Extracts or abridgements of reports must not be published without permission of Exova Warringtonfire. The original signed paper version of this report, which includes signatures in blue ink, is the sole authentic version. Only original paper versions of this report bear authentic signatures of the responsible Exova Warringtonfire staff.

4 Page 4 of 32 CONTENTS PAGE NO. SUMMARY...2 SIGNATORIES...3 TEST PROCEDURE...5 TEST SPECIMENS...6 DOORSET CLEARANCE GAPS...12 INSTRUMENTATION...13 TEST OBSERVATIONS...14 TEST PHOTOGRAPHS...16 TEMPERATURE AND DEFLECTION DATA...19 PERFORMANCE CRITERIA AND TEST RESULTS...31 ONGOING IMPLICATIONS...31 CONCLUSIONS...32

5 Page 5 of 32 Test Procedure Introduction The doorsets are required to provide a fire separating function and were therefore tested in accordance with BS EN : 2008 Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware - Part 1: Fire resistance tests for doors, shutters and openable windows. This test report should be read in conjunction with that Standard and with BS EN : 1999, Fire resistance tests - Part 1: General requirements and BS EN : 1999, Fire resistance tests - Part 2: Alternative and additional procedures. The specimens were judged on their ability to comply with the performance criteria for integrity and insulation, as required by BS EN : The specific purpose of the test was to evaluate the effects of the inclusion of items of building hardware into a previously tested Doorset construction. Because of this, no direct field of application for the doorsets is included in this report. Fire Test Study Group/EGOLF Instruction to test Certain aspects of some fire test specifications are open to different interpretations. The Fire Test Study Group and EGOLF have identified a number of such areas and have agreed Resolutions which define common agreement of interpretations between fire test laboratories which are members of the Groups. Where such Resolutions are applicable to this test they have been followed. The test was conducted on the 13 th March 2012 at the request of Simonswerk UK Ltd. the test sponsor. Mr Robin Guy, a representative of the test sponsor, witnessed the test. Test Specimen Construction Installation Sampling Conditioning A comprehensive description of the test construction is given in the Schedule of Components. The description is based on a detailed survey of the specimens and information supplied by the sponsor of the test. The doorsets were mounted within apertures in a blockwork wall construction such that their door leaves opened towards the heating conditions of the test. Representatives of Exova Warringtonfire conducted the installation work on the 13 th March 2012 The specimen hinges used in the test were sample selected by Mr. J. Corcoran, a representative of Warrington Certification Limited, on the 29 th February The specimens storage, construction, and test preparation took place in the test laboratory over a total combined time of approximately 7 days. Throughout this period both the temperature and the humidity of the laboratory were measured and recorded as being within a range of from 12 o C to 18 o C and 45% to 78% respectively.

6 Test Specimens Figure 1- General Elevation of Test Specimens and Unexposed Face Thermocouples Page 6 of frame 1980 leaf hinge centres DOORSET 'A' DOORSET 'B' leaf 2020 frame 933 leaf 933 leaf 1027 frame 1027 frame Positions of thermocouples GENERAL ELEVATION OF UNEXPOSED FACE FIRE 150 thick blockwork wall 44 PLAN 44 Do not scale. All dimensions are in mm

7 Page 7 of 32 Figure 2 Typical Details for Both Doorsets 1027 frame 933 leaf FIRE leaf frame fixings hinged jamb HORIZONTAL SECTION THROUGH DOORSET 45 closing jamb 72 4 head frame 1980 leaf FIRE 44 leaf VERTICAL SECTION THROUGH DOORSET Do not scale. All dimensions are in mm

8 Page 8 of 32 Figure 3 Details of Hinges (item 1) for Doorset A blade to door leaf blade to door frame single strip of intumescent double strip of intumescent FIRE 44 leaf Details of Intumescent protection Typical location of hinges Do not scale. All dimensions are in mm

9 Page 9 of 32 Figure 4 Details of Hinges (item 2) for Doorset B blade to door leaf blade to door frame FIRE single strip of intumescent 44 leaf 72 4 Details of Intumescent protection double strip of intumescent 57 Typical location of hinges Do not scale. All dimensions are in mm

10 Page 10 of 32 Schedule of Components (Refer to Figures 1 to 4) (All values are nominal unless stated otherwise) (All other details are as stated by the sponsor) Item Description 1. Hinges Doorset A Manufacturer : Simonswerk GmbH Type : Concealed hinge system Reference : TECTUS TE 340 3D FR Material i. hinge body parts : Zinc die cast ii. central knuckle parts : Aluminium Overall sizes : See Figure 3 Fixing method : Hinges screw fixed within routed slots in both door frame and door leaf. Hinges supplied pre-fitted with intumescent strips to internal faces of each hinge blade. Details of Fixings i. type : Countersunk head woodscrews ii. material : Stainless steel iii. sizes : 40 mm long x 5.2 mm diameter iv. number off per blade : 4 no. screws Details of Intumescent Protection i. manufacturer : Rolf Kuhn GmbH ii. reference : ROKU Strip M130 iii. material : Graphite based intumescent iv. overall size : Single strip 1 mm thick x 27 mm wide x 47 mm long. Double strip, each 2 mm thick x 17 mm wide x 59 mm long. v. location : Self adhesive fixed along internal faces of each hinge blade. See Figure Hinges Doorset B Manufacturer : Simonswerk GmbH Type : Concealed hinge system Reference : TECTUS TE 640 3D A8 FR Material i. hinge body parts : Zinc die cast ii. central knuckle parts : Aluminium Overall sizes : See Figure 4 Fixing method : Hinges screw fixed within routed slots in both door frame and door leaf. Hinges supplied pre-fitted with intumescent strips to internal faces of each hinge blade. Details of Fixings i. type : Countersunk head woodscrews ii. material : Stainless steel iii. sizes : 40 mm long x 5.2 mm diameter iv. number off per blade : 4 no. screws Details of Intumescent Protection i. manufacturer : Rolf Kuhn GmbH ii. reference : ROKU Strip M130 iii. material : Graphite based intumescent

11 Page 11 of 32 Item Description 2. Hinges Doorset B continued iv. overall size : Single strip 1 mm thick x 36 mm wide x 115 mm long. Double strip, each 2 mm thick x 22 mm wide x 115 mm long. v. location : Self adhesive fixed along internal faces of each hinge blade. See Figure 4. Timber Doorset A & B (supplied by Exova warringtonfire) each consisting of items 3 to 5 3. Door frame Jambs and Head Material : Timber, softwood Nominal Density : 510 kg/m 3 Overall section size i. closing jamb and head : 45 mm x 72 mm, with a 13 mm deep rebate ii. hinged jamb : 57 mm x 72 mm, with a 13 mm deep rebate Jambs to head jointing method : Butt joint and screwed Fixing method to masonry surround i. type : Countersunk head steel screws into plastic plugs through jambs. ii. size : 100 mm long x 5.6 mm (No.12) diameter screws iii. quantity : 4 no. screws along full height of closing jamb. 6 no. screws along height of hinged jamb (2 no. screws at 350 mm centres about each hinge position). 4. Door Frame Intumescent seal Manufacturer : Intumescent Seals Limited (supplied by Exova warringtonfire) Reference : Therm-A-Seal Overall section size : 15 mm wide x 4 mm deep carrier Fixing method : Single seal self-adhesive fixed within a groove along the rebate of the door frame jambs and head. The seal was interrupted at each hinge position. 5. Door Leaf Manufacturer : Halspan Reference : Optima door blank Material : 3-layer particle board. Door blank fitted with 8 mm thick Sapele hardwood lipping along the vertical edges by Exova warringtonfire using formaldehyde adhesive. Thickness : 44 mm 6. Overhead Door Closer Reference : Briton 121 CE (supplied by Exova warringtonfire) Location : Exposed face of each doorset Maximum opening moments (measured by Exova warringtonfire) i. doorset A : 60.1 Nm (Newton metre) ii. doorset B : 69.1 Nm Maximum closing moments (measured by Exova warringtonfire) i. doorset A : 25.6 Nm ii. doorset B : 27.7 Nm

12 Page 12 of 32 Doorset Clearance Gaps Doorset A Doorset B View from unexposed face View from unexposed face Door Ref Gap Dimension in mm at Positions A * 9* 10* B * 23* 24* A Mean 2.7 Maximum 3.4 Minimum 2 B Mean 2.4 Maximum 3 Minimum 1.1 Door Ref A B Gap Between Face of Leaf and Doorstop in mm at Position * 9* 10* n/a n/a n/a * 23* 24* n/a n/a n/a * Dimension not included in calculations # Gap not measured

13 Page 13 of 32 Instrumentation General Furnace Thermocouple Allocation Thermocouples 2 to 6 Doorset A and 7 to 11 Doorset B Thermocouples 20 to 23 (Doorset A) & Thermocouples 24 to 27 (Doorset B) The instrumentation was provided in accordance with the requirements of the Standard. The furnace was controlled so that its mean temperature complied with the requirements of BS EN : 1999 Clause 5.1 using six plate thermometers, distributed over a plane 100 mm from the surface of the test construction. Thermocouples were provided to monitor the unexposed surface of the specimens. The output of all instrumentation was recorded at no less than one minute intervals as follows: At five positions on the unexposed surface of the doorset, one approximately at the centre and one at approximately the centre of each quarter section of the doorset. At three positions on the unexposed surface of the door frame, one at the approximate mid-height of each of the vertical frame members and one approximately mid-span of the head member. The locations and reference numbers of the various unexposed surface thermocouples are shown in Figure 1. Roving Thermocouple A roving thermocouple was available to measure temperatures on the unexposed surface of the specimens at any position which might appear to be hotter than the temperatures indicated by the fixed thermocouples. Integrity Criteria Furnace Pressure Cotton pads and gap gauges were available to evaluate the integrity of the specimens where relevant. After the first five minutes of testing and for the remainder of the test, the furnace atmospheric pressure was controlled so that it complied with the requirements of BS EN : Clause 5.2.The calculated pressure differential relative to the laboratory atmosphere was 12.9 (±2) at the head of both doorsets.

14 Page 14 of 32 Test Observations Time All observations are from the unexposed face unless noted otherwise. mins secs The ambient air temperature in the vicinity of the test construction was 14ºC at the start of the test with a maximum variation of -1ºC during the test The test commences Smoke release commences at the head of Doorset A Smoke release increases around both doorsets The exposed faces of both doorsets have ignited Heavy smoke release around the perimeters of both door leaves Slight discolouration of the leaf visible at the top two hinge positions on Doorset B and also at the top hinge position of Doorset A Viewed from the exposed side, both doorsets are cracked and charred; there are no significant visible changes on the exposed side of the doorsets around the hinge positions Smoke release continues from the top two hinge position of both doorsets, most noticeable from Doorset B The threshold gap of Doorset B is now approx 3 to 4 mm in the leading edge corner. The threshold gap of Doorset A has only reduced slightly Discolouration continues to increase at the top hinge position on Doorset B Discolouration increasingly top in the top trailing edge corner of Doorset A A small drop of molten metal can be seen between the leaf and frame at the top hinge position of Doorset A The threshold gap of Doorset A has reduced slightly but is still approx 6 to 8 mm Smoke release continues in the top trailing edge corners of both doorsets Faint glowing visible at the top hinge positions on both doorsets Both doorsets continue to maintain the integrity and insulation criteria of the test A cotton pad applied over the top hinge position of Doorset B, the pad discolours but fails to ignite.

15 Page 15 of 32 Time mins secs A cotton pad applied over the top hinge position of Doorset A, the pad discolours but fails to ignite Glowing continues to increase at the top hinge positions of both doorsets Test is discontinued at the sponsor s request.

16 Page 16 of 32 Test Photographs The unexposed face of the test construction prior to testing The unexposed face of the doorsets prior to testing

17 Page 17 of 32 The unexposed face of the doorsets after 10 minutes of testing The unexposed face of the doorsets after 20 minutes of testing

18 Page 18 of 32 The unexposed face of the doorsets after 30 minutes of testing The exposed face of the doorsets immediately after testing

19 Page 19 of 32 Temperature and Deflection Data Mean Furnace Temperature, Together With The Temperature/Time Relationship Specified In The Standard Time Specified Actual Furnace Furnace Mins Temperature Temperature Deg. C Deg. C

20 Page 20 of 32 Individual And Mean Temperatures Recorded On The Unexposed Surface Of Doorset A Time T/C T/C T/C T/C T/C Mean Number Number Number Number Number Mins Temp Deg. C Deg. C Deg. C Deg. C Deg. C Deg. C

21 Page 21 of 32 Individual And Mean Temperatures Recorded On The Unexposed Surface Of Doorset B Time T/C T/C T/C T/C T/C Mean Number Number Number Number Number Mins Temp Deg. C Deg. C Deg. C Deg. C Deg. C Deg. C * * Denotes temporary thermocouple failure

22 Page 22 of 32 Individual Temperatures Recorded On The Frame Of Doorset A Time T/C T/C T/C T/C Number Number Number Number Mins Deg. C Deg. C Deg. C Deg. C * * * Denotes thermocouple failure

23 Page 23 of 32 Individual Temperatures Recorded On The Frame Of Doorset B Time T/C T/C T/C T/C Number Number Number Number Mins Deg. C Deg. C Deg. C Deg. C * * Denotes a temporary thermocouple failure

24 Page 24 of 32 Additional UXF Thermocouples to Doorset A Time T/C T/C T/C T/C Number Number Number Number Mins Deg. C Deg. C Deg. C Deg. C * * * Denotes thermocouple failure

25 Page 25 of 32 Additional UXF Thermocouples to Doorset B Time T/C T/C T/C T/C Number Number Number Number Mins Deg. C Deg. C Deg. C Deg. C

26 Page 26 of 32 Deflection Of The Door Leaves During The Test A B C D E A B C D E Doorset A Doorset B F G H I J F G H I J K L M N O K L M N O Doorset A Deflections mm TIME mins A B C D E F G H I J K L M N O Doorset B Deflections mm TIME mins A B C D E F G H I J K L M N O

27 Page 27 of 32 Graph Showing Mean Furnace Temperature, Together With The Temperature/Time Relationship Specified In The Standard Temperature - Deg. C Specified Furnace Temperature Deg. C Actual Furnace Temperature Deg. C Time - Minutes

28 Page 28 of 32 Graph Showing Mean Temperature Recorded On The Unexposed Surface Of Doorset A Temperature - Deg. C Time - Minutes

29 Page 29 of 32 Graph Showing Mean Temperature Recorded On The Unexposed Surface Of Doorset B Temperature - Deg. C Time - Minutes

30 Page 30 of 32 Graph Showing the furnace pressure recorded during the test Pressure - Pa Time - Minutes

31 Page 31 of 32 Performance Criteria and Test Results Integrity It is required that the specimens retain their separating function, without either causing ignition of a cotton pad when applied, or permitting the penetration of a gap gauge as specified in BS EN : 2008, or resulting in sustained flaming on the unexposed surface. These requirements were satisfied for the periods shown below: Doorset A Doorset B Sustained Flaming 34 minutes* 34 minutes* Cotton wool pad 34 minutes* 34 minutes* Gap gauge 34 minutes* 34 minutes* Insulation Insulation performance The mean temperature rise of the unexposed surface shall not be greater than 140 C and that the maximum temperature rise shall not be greater than 180 C (except on the door frame, where the maximum temperature rise shall not exceed 360 C). Insulation failure also occurs simultaneously with integrity failure as specified in BS EN : These requirements were satisfied for the periods shown below: Doorset A Doorset B 34 minutes* 34 minutes* *The test duration, the test was discontinued after 34 minutes. Ongoing Implications Limitations This report details the method of construction, the test conditions and the results obtained when the specific element of construction described herein was tested following the procedure outlined in BS EN : 1999, and where appropriate BS EN : Any significant deviation with respect to size, constructional details, loads, stresses, and edge or end conditions other than those allowed under the field of direct application in the relevant test method is not covered by this report. Annex A of BS EN : 1999, provides guidance information on the application of fire resistance tests and the interpretation of test data. Because of the nature of fire resistance testing and the consequent difficulty in quantifying the uncertainty of measurement of fire resistance, it is not possible to provide a stated degree of accuracy of the result.

32 Page 32 of 32 Conclusions Evaluation Against Objective Two specimens of single-acting, single-leaf timber based doorsets, incorporating items of building hardware have been subjected to a fire resistance test in accordance with BS EN : 2008, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware,, BS EN : 1999, General requirements and BS EN : 1999, Alternative and additional procedures. The evaluation of the doorsets against the requirements of BS EN : 2008 showed that the doorsets satisfied the requirements for the following periods. Test Results: Doorset A Doorset B Integrity Sustained Flaming 34 minutes* 34 minutes* Cotton wool pad 34 minutes* 34 minutes* Gap gauge 34 minutes* 34 minutes* Insulation 34 minutes* 34 minutes* *The test duration, the test was discontinued after 34 minutes.

WF Report No: Prepared for: Rohden UK Ltd Unit 2, Hayleys Manor Farm Upland Road, Epping Upland, Essex, CM16 6PQ. Date: Notified Body No:

WF Report No: Prepared for: Rohden UK Ltd Unit 2, Hayleys Manor Farm Upland Road, Epping Upland, Essex, CM16 6PQ. Date: Notified Body No: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The fire resistance performance

More information

Title: Fire resistance test in accordance with BS EN : 2008 on an uninsulated, face fixed rolling shutter doorset. Report No: Prepared for:

Title: Fire resistance test in accordance with BS EN : 2008 on an uninsulated, face fixed rolling shutter doorset. Report No: Prepared for: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: Fire resistance test in accordance

More information

Title: Fire Resistance Test In Accordance With BS EN : 1999 On A Glazed Screen Assembly. WF Report No: , Issue 2. Prepared for: Date:

Title: Fire Resistance Test In Accordance With BS EN : 1999 On A Glazed Screen Assembly. WF Report No: , Issue 2. Prepared for: Date: Title: Fire Resistance Test In Accordance With BS EN 1364-1: 1999 On A Glazed Screen Assembly WF Report No: 164311, Prepared for: AGC Flat Glass Europe. Chaussee de la Hulpe 166 1170 Brussels. Date: 19

More information

Title: WF Report No:

Title: WF Report No: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance

More information

Title: The fire resistance performance of a specimen of single-acting single-leaf doorset in accordance with BS EN : Report No: A

Title: The fire resistance performance of a specimen of single-acting single-leaf doorset in accordance with BS EN : Report No: A Title: The fire resistance performance of a specimen of single-acting single-leaf doorset in accordance with BS EN 1634-1: 2000 Report No: 163712 A Prepared for: Novoferm GmbH Haldern Isselburger Str.

More information

13 th December Title: The Fire Resistance Performance Of Doorsets When Fitted With Perko Powermatic R100 Jamb Mounted Concealed Door Closers

13 th December Title: The Fire Resistance Performance Of Doorsets When Fitted With Perko Powermatic R100 Jamb Mounted Concealed Door Closers Warringtonfire Holmesfield Road Warrington WA1 2DS T: +44 (0)1925 655 116 F: +44 (0)1925 655 419 info.warrington@warringtonfire.com warringtonfire.com Title: The Fire Resistance Performance Of Doorsets

More information

BS EN :2006. Windows and doors Product standard, performance characteristics. A Report To: Mila Hardware Ltd. Document Reference:

BS EN :2006. Windows and doors Product standard, performance characteristics. A Report To: Mila Hardware Ltd. Document Reference: Exova Warringtonapt Key Industrial Park Fernside Road Willenhall West Midlands WV13 3YA T : +44 (0) 1902 722 122 F : +44 (0) 1902 727 242 E : willenhall@exova.com W: www.exova.com BS EN 14351-1:2006 Test

More information

Report Number BTC 12024F

Report Number BTC 12024F Report Number BTC F A FIRE RESISTANCE TEST ON A GYPROC GYPWALL PARTITION INCORPORATING A DOUBLE LAYER OF mm SOUNDBLOC EACH SIDE OF S STUDS, CONDUCTED IN ACCORDANCE WITH BS EN 4:999. Test Date: 9 th June

More information

Report Number BTC 12261F

Report Number BTC 12261F Report Number BTC 6F A FIRE RESISTANCE TEST ON A 5m HIGH X m WIDE GYPROC SHAFTWALL SYSTEM INCORPORATING A 6mm METAL STUD FRAMEWORK CLAD WITH A DOUBLE LAYER OF 5mm GYPROC FIRELINE, EXPOSED TO THE FIRE FROM

More information

Title: The Fire Resistance Performance of Modified Doorsets. WF Assessment Report No: Prepared for:

Title: The Fire Resistance Performance of Modified Doorsets. WF Assessment Report No: Prepared for: assessment report Title: The Fire Resistance Performance of Modified Doorsets WF Assessment Report No: 187254 Prepared for: Phoenix Door Panels Ltd. Westnewlands Ind. Estate Somersham Huntingdon Cambs

More information

Fire resistance test in accordance with BS 476 Perko (R1, R2 & R21) and Perkomatic (R85) concealed door closers

Fire resistance test in accordance with BS 476 Perko (R1, R2 & R21) and Perkomatic (R85) concealed door closers Fire resistance test in accordance with BS 476 Perko (R1, R2 & R21) and Perkomatic (R85) concealed door closers Independent fire assessments for all products are effective for a five year period. Where

More information

Report No: Test of: Reversible aluminium/timber window. Tested to: BS :2009 Performance of windows & doors Part 2: Operation & strength

Report No: Test of: Reversible aluminium/timber window. Tested to: BS :2009 Performance of windows & doors Part 2: Operation & strength Report No: 181947 Test of: Reversible aluminium/timber window Tested to: BS 6375-2:2009 Performance of windows & doors Part 2: Operation & strength For: A/S Peder Nielsen Beslagfabrik Norregade 25 Bronderslev

More information

EN 1154:1997 / A1:2002

EN 1154:1997 / A1:2002 Exova Warringtonapt Key Industrial Park Fernside Road Willenhall West Midlands WV13 3YA T : +44 (0) 1902 722 122 F : +44 (0) 1902 727 242 E : willenhall@exova.com W: www.exova.com EN 1154:1997 / A1:2002

More information

BS EN ISO :2006

BS EN ISO :2006 Exova (UK) Ltd Key Industrial Park Fernside Road Willenhall West Midlands WV13 3YA T : +44 (0) 1902 722 122 F : +44 (0) 1902 727 242 E : willenhall@exova.com W: www.exova.com BS EN ISO 10077-1:2006 Calculation

More information

Introduction. Our Ref: Chilt/IF12041 AR1. 24 th June Astra Door Controls Ltd Unit 10 Astra Business Centre Roman Way Preston PR2 5AP

Introduction. Our Ref: Chilt/IF12041 AR1. 24 th June Astra Door Controls Ltd Unit 10 Astra Business Centre Roman Way Preston PR2 5AP Chiltern House Stocking Lane Hughenden Valley High Wycombe Buckinghamshire HP14 4ND UK t +44 (0) 1494 569 800 f +44 (0) 1494 564895 e cif@chilternfire.co.uk w www.chilternfire.co.uk Our 24 th June 2012

More information

No. Pr FIRE RESISTANCE TEST REPORT. Issued on: AUTHORIZED BODY AO 216. Project No: (Z )

No. Pr FIRE RESISTANCE TEST REPORT. Issued on: AUTHORIZED BODY AO 216. Project No: (Z ) Project No: 1 04 177 (Z210040305) AUTHORIZED BODY AO 216 TEST LABORATORY IN VESELÍ NAD LUŽNICÍ Accredited Test Laboratory - accreditation issued by the Czech Institute for Accreditation, o. p. s. Registered

More information

CERTIFICATE OF APPROVAL No CF 5543 ASSA ABLOY SECURITY SOLUTIONS

CERTIFICATE OF APPROVAL No CF 5543 ASSA ABLOY SECURITY SOLUTIONS CERTIFICATE OF APPROVAL No CF 5543 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of School Street, Willenhall,

More information

FIRE TEST REPORT FH 5154

FIRE TEST REPORT FH 5154 1222 Moonshine Road Judgeford RD1 Porirua 5381 New Zealand T +64 4 237 1170 F +64 4 237 1171 branz@branz.co.nz www.branz.co.nz FIRE TEST REPORT FH 5154 CONE CALORIMETER TEST AND NCC SPECIFICATION C1.10

More information

InnoBYG small scale demonstration tests - Part 2

InnoBYG small scale demonstration tests - Part 2 Test report InnoBYG small scale demonstration tests - Part 2 File Serial No.: 2 Ref.: TDJ/AND Pages: 17 Enclosures: 31 2014-03-18 Date: 2014-07-09 Jernholmen 12, DK-2650 Hvidovre Phone: +45 36 34 90 00,

More information

CERTIFICATE OF APPROVAL No CF 5505 CONSORT ARCHITECTURAL HADWARE LTD

CERTIFICATE OF APPROVAL No CF 5505 CONSORT ARCHITECTURAL HADWARE LTD CERTIFICATE OF APPROVAL No CF 5505 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of CONSORT ARCHITECTURAL

More information

Urban Wildfire Interface: Exterior Wall Wildfire Testing

Urban Wildfire Interface: Exterior Wall Wildfire Testing Urban Wildfire Interface: Exterior Wall Wildfire Testing PN# 04018 Conducted for: WILDLAND FIRE TASK GROUP TESTING CONDUCTED ON APRIL 5 AND MAY 6, 2004 REPORT ISSUED ON: APRIL 25, 2004 Kelso, Washington

More information

Report No 2370/ This Report consists of 40 pages. Authority & date Request by Client dated 25 November 2010

Report No 2370/ This Report consists of 40 pages. Authority & date Request by Client dated 25 November 2010 Test Report Report No 2370/7612199 This Report consists of 40 pages Client Smarts Systems Limited Arnolds Way Yatton BS49 4QN Authority & date Request by Client dated 25 November 2010 Items tested 3 off

More information

Test report No

Test report No Exova Warringtonfire, Frankfurt Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : EBH@exova.com W: www.exova.com Test report No. 2015-1661

More information

Test report No

Test report No Exova Warringtonfire, Frankfurt Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : EBH@exova.com W: www.exova.com Test report No. 2016-1390

More information

InnoBYG small scale demonstration tests - Part 1

InnoBYG small scale demonstration tests - Part 1 Test report InnoBYG small scale demonstration tests - Part 1 File FUN0001 Serial No.: 1 Ref.: TDJ/AND Pages: 18 2013-12-11 Date: 2014-01-20 Jernholmen 12, DK-2650 Hvidovre Phone: +45 36 34 90 00, Fax:

More information

FIRE TEST REPORT FH 5078

FIRE TEST REPORT FH 5078 1222 Moonshine Road Judgeford RD1 Porirua 5381 New Zealand T +64 4 237 1170 F +64 4 237 1171 branz@branz.co.nz www.branz.co.nz FIRE TEST REPORT FH 5078 CONE CALORIMETER TEST AND NZBC ACCEPTABLE SOLUTIONS

More information

European B1 Fire Rating. soft collection softwall + softblock Fire Retardant (FR) Treated textile products. molo design, ltd

European B1 Fire Rating. soft collection softwall + softblock Fire Retardant (FR) Treated textile products. molo design, ltd European B1 Fire Rating soft collection softwall + softblock Fire Retardant (FR) Treated textile products molo design, ltd 1470 Venables Street Vancouver, B.C. Canada V5L 2G7 t +1 604 696 2501 f +1 604

More information

TEST REPORT No. : SHCCM Date : May. 17, 2013 Page: 1 of 5

TEST REPORT No. : SHCCM Date : May. 17, 2013 Page: 1 of 5 Page: 1 of 5 IGEPA GROUP GMBH & CO. KG SACHSENFELD 4, 20097 HAMBURG, GERMANY The following sample(s) was/ were submitted and identified on behalf of the client as: Sample Name : MASTER JET S PREMIUM MESH

More information

Test Report No.: SDHGR FM Date: Jun.08, 2012 Page 1 of 3

Test Report No.: SDHGR FM Date: Jun.08, 2012 Page 1 of 3 Test Report No.: SDHGR120501002FM Date: Jun.08, 2012 Page 1 of 3 HONGGE (GUANGZHOU) PAPER CO., LTD BUILDING 1, HE TAI INDUSTRY ZONE, HE TAI ROAD NO.2, HE BIAN, JIA HE TOWN, BAI YUN DISTRICT, GUANGZHOU.

More information

your and attach spreadsheet of 23 December 2003; and

your  and attach spreadsheet of 23 December 2003; and s Science and Engineering 14 Julius Avenue, Riverside Corporate Park North Ryde NSW 2113 PO Box 310, North Ryde NSW 2113, Australia Telephone: (02) 9490 5444 Facsimile: (02) 9490 5555 ABN 41 687 119 230

More information

CERTIFICATE OF APPROVAL No CF 209 ROYDE & TUCKER LIMITED

CERTIFICATE OF APPROVAL No CF 209 ROYDE & TUCKER LIMITED CERTIFICATE OF APPROVAL No CF 209 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Bilton Road, Cadwell

More information

With Compliments PLEASE FIND ENCLOSED OUR REPORT REFERENCE ALC E : : 1006

With Compliments PLEASE FIND ENCLOSED OUR REPORT REFERENCE ALC E : : 1006 For the Attention of: Mr Ian Davies Mideas Limited 12 Openshaw Drive Blackburn Lancashire BB1 8RH With Compliments DATE REPORT ISSUED: 10/11/2006 PLEASE FIND ENCLOSED OUR REPORT REFERENCE ALC E : 99316

More information

Germany B1 Fire Rating. kraft paper products. molo design, ltd Venables Street Vancouver, B.C. Canada V5L 2G7

Germany B1 Fire Rating. kraft paper products. molo design, ltd Venables Street Vancouver, B.C. Canada V5L 2G7 Germany B1 Fire Rating kraft paper products molo design, ltd 1470 Venables Street Vancouver, B.C. Canada V5L 2G7 t +1 604 696 2501 f +1 604 685 0342 info@molodesign.com www.molodesign.com molo kraft paper

More information

Test report no

Test report no Exova Warringtonfire, Frankfurt Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : EBH@exova.com W: www.exova.com Test report no. 2015-1339

More information

NFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH

NFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH NFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH Contego Latex Fire Barrier Intumescent (Also marketed in Canada by Pyrologistics,

More information

56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM. Test Report EN : TA11/0004c.

56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM. Test Report EN : TA11/0004c. 56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM Email: testing@inspec-international.com Website: www.inspec-international.com Tel: +44 (0) 16 17 37 06 99 Fax: +44 (0) 16 17 36 01 01

More information

TEST REPORT No. : SHCCM Date : Mar. 12, 2013 Page: 1 of 5

TEST REPORT No. : SHCCM Date : Mar. 12, 2013 Page: 1 of 5 Page: 1 of 5 IGEPA GROUP GMBH & CO.KG SACHSENFELD 4, 20097 HAMBURG, GERMANY The following sample(s) was/ were submitted and identified on behalf of the client as: Sample Name : MASTER JET S FRONTLIT 510

More information

Test Report NO. AJHL FB Date: JUN.21, 2016 Page 1 of 6

Test Report NO. AJHL FB Date: JUN.21, 2016 Page 1 of 6 Test Report. AJHL1606005783FB Date: JUN.21, 2016 Page 1 of 6 IGEPA GROUP GmbH & CO., KG SACHSENFELD 4, 20097 HAMBURG, GERMANY The following sample(s) was / were submitted and identified on behalf of the

More information

Test report No

Test report No Exova Warringtonfire, Frankfurt Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : EBH@exova.com W: www.exova.com Test report No. 2014-1940

More information

FIRE TEST REPORT FH 5728

FIRE TEST REPORT FH 5728 1222 Moonshine Road Judgeford RD1 Porirua 5381 New Zealand T +64 4 237 1170 F +64 4 237 1171 branz@branz.co.nz www.branz.co.nz FIRE TEST REPORT FH 5728 CONE CALORIMETER TEST AND NZBC VERIFICATION METHOD

More information

Test report No

Test report No Exova Brandhaus Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : Brandhaus@exova.com W: www.exova.com Test report No. 2009-2211 for applying

More information

Test Report No

Test Report No Exova Warringtonfire, Frankfurt Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : Ebh@exova.com W: www.exova.com Test Report No. 2015-1365

More information

Sound-absorbing spacer Sorp10

Sound-absorbing spacer Sorp10 Sponsor: Reference number: 7.3 / 27080 This document is only a translated version; not legally attested Max Frank GmbH & Co. KG Mitterweg 1 94339 Leiblfing Federal Institute for Materials Research and

More information

CERTIFICATE OF APPROVAL No CF 5418 C.ED. SCHULTE GMBH

CERTIFICATE OF APPROVAL No CF 5418 C.ED. SCHULTE GMBH CERTIFICATE OF APPROVAL No CF 5418 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Friedrichstrasse

More information

Test report No

Test report No Exova Brandhaus Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : Brandhaus@exova.com W: www.exova.com Test report No. 2009-2296 for applying

More information

Godkjennelsesdokumenter for art. 4509, 4511

Godkjennelsesdokumenter for art. 4509, 4511 Godkjennelsesdokumenter for art. 4509, 4511 Innholdsliste: Samsvarserklæring side 2 SINTEF Produktdokumentasjon 050-0204 side 3 Efectis Nederland BV branntestunderlag side 8 Efectis Nederland BV testrapport

More information

Test Report No. AJHL FB Date: APR.06, 2016 Page 1 of 5

Test Report No. AJHL FB Date: APR.06, 2016 Page 1 of 5 Test Report AJHL1603002392FB Date: APR.06, 2016 Page 1 of 5 SOYANG TECHNICAL TEXTILE (ZHEJIANG) CO., LTD NO.36 JINNIU ROAD, JIANSHAN DISTRICT, HAINING CITY, ZHEJIANG PR., CHINA The following sample(s)

More information

Classification report No K1

Classification report No K1 Exova Warringtonfire, Frankfurt Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : EBH@exova.com W: www.exova.com Classification report No.

More information

Test Report No. AJHL FB Date: OCT.26, 2016 Page 1 of 6

Test Report No. AJHL FB Date: OCT.26, 2016 Page 1 of 6 Test Report No. AJHL1609010810FB Date: OCT.26, 2016 Page 1 of 6 SOYANG TECHNICAL TEXTILE (ZHEJIANG) CO., LTD NO.36 JINNIU ROAD, JIANSHAN DISTRICT, HAINING CITY, ZHEJIANG PR., CHINA The following sample(s)

More information

Evidence of Performance Burglar resistance

Evidence of Performance Burglar resistance Test Report No. 16-001785-PR03 (PB-C01-05-en-01) Client ALUMIL S.A. Industrial Area 61100 Kilkis Greece Product Burglar resistant Smart SD77 glass door RC 2 Designation SMART DOORS Overall dimensions (W

More information

Test Report No. AJHL FB-2 Date: OCT.24, 2016 Page 1 of 6

Test Report No. AJHL FB-2 Date: OCT.24, 2016 Page 1 of 6 Test Report. AJHL1610011324FB-2 Date: OCT.24, 2016 Page 1 of 6 POSTER AND PANEL CPERE ANDORRA, SN, POL. IND, ILLA,SUD, NAUS, 4, 5, I6,08650, SALLENT, BARCELONA, SPAIN The following sample(s) was were submitted

More information

Test report No

Test report No Exova Warringtonfire, Frankfurt Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : EBH@exova.com W: www.exova.com Test report No. 2014-1031

More information

Certifikat och provningsprotokoll för art. 4512, 4513, 4514 och 4515

Certifikat och provningsprotokoll för art. 4512, 4513, 4514 och 4515 Certifikat och provningsprotokoll för art. 4512, 4513, 4514 och 4515 Innehållsförteckning: Declaration of conformity... sid 2 SINTEF Produktdokumentation... sid 3 Efectis Nederland BV Brandtestunderlag...

More information

High Performance Door Products. Information Guide Ironmongery.

High Performance Door Products. Information Guide Ironmongery. High Performance Door Products Information Guide Ironmongery www.halspan.com Introduction Established over a decade ago, Halspan very quickly built up a reputation for innovation. First, we developed an

More information

Equipotential Bonding of Rail Vehicles to Running Rail Potential

Equipotential Bonding of Rail Vehicles to Running Rail Potential Railway Group Standard Equipotential Bonding of Rail Vehicles to Running Rail Potential Synopsis This standard mandates the requirements for equipotenial bonding of rail vehicles to comply with the Electricity

More information

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC. AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: MASTER WINDOW SYSTEMS, INC. SERIES/MODEL: Master 2000 Double Hung Window PRODUCT TYPE: PVC Double Hung Window Summary of Results Title Test Specimen

More information

Test Report No. AJHL FB Date: JUN.21, 2016 Page 1 of 6

Test Report No. AJHL FB Date: JUN.21, 2016 Page 1 of 6 Test Report No. AJHL1606005818FB Date: JUN.21, 2016 Page 1 of 6 HAINING JINMAO WARP KNITTING CO., LTD NO. 38 LUHONG ROAD DINGQIAO TOWN HAINING CITY ZHEJIANG CHINA The following sample(s) was / were submitted

More information

Test report no

Test report no Exova Warringtonfire, Frankfurt Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : EBH@exova.com W: www.exova.com Test report no. 2014-1452-2

More information

Briton 2000 Series - a compact series of closers designed for the most common door sizes

Briton 2000 Series - a compact series of closers designed for the most common door sizes Briton 2000 Series - Classic medium duty Briton 2000 Series - a compact series of closers designed for the most common door sizes The Briton 2000 Series of closers includes the UK s No.1 door closing product,

More information

Test report no

Test report no Exova Warringtonfire, Frankfurt Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : EBH@exova.com W: www.exova.com Test report no. 2017-2132-1

More information

SINGLE SLIDING WINDOW 1000 SERIES 4-1/2" FRAME SINGLE SLIDER LIFT OUT

SINGLE SLIDING WINDOW 1000 SERIES 4-1/2 FRAME SINGLE SLIDER LIFT OUT PERFORMANCE EVALUATION OF SINGLE SLIDING WINDOW 1000 SERIES 4-1/2" FRAME SINGLE SLIDER LIFT OUT For Dominion Doors & Windows Ltd. IN ACCORDANCE WITH: AAMA/WDMA/CSA 101/I.S.2/A440-11 AND A440S1-17 Report

More information

DOOR BOTTOM SMOKE SEALS

DOOR BOTTOM SMOKE SEALS Raven Products Smoke Seals DOOR BOTTOM SMOKE SEALS Raven RP8Si : Raven RP38Si : Raven RP70Si : Raven RP99Si : Raven RP129Si Raven Seals have been designed to accommodate a variety of duty levels, classified

More information

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES FIREGARD Curtain Fire Dampers DAMPERS SFB (.) X UDC. FEBRUARY 00 FEATURES Galvanised or Stainless Steel Interlocking Blades in Airtight Casing. Optional Stainless Steel Side Seals. Constant Tension Stainless

More information

SAMPLE RETENTION POLICY

SAMPLE RETENTION POLICY For the Attention of: Sandy Chadha Supreme Imports Limited 4 Beacon Road Ashburton Park Asburton Road West, Trafford Park Manchester M17 1AF With Compliments DATE REPORT ISSUED 17/01/2011 PLEASE FIND ENCLOSED

More information

Understanding BS 1363 Amendment No.4

Understanding BS 1363 Amendment No.4 Intertek Hilton House, Corporation Street, Rugby, Warwickshire, CV21 2DN UK info.uk@intertek.com 01788 578435 www.intertek.com Introduction A new Amendment applying to several parts of the BS 1363 standard

More information

Testing of Baier Plasterboard to AS/NZS (Electronic copy (PDF format) original signed by author) Materials Scientist.

Testing of Baier Plasterboard to AS/NZS (Electronic copy (PDF format) original signed by author) Materials Scientist. DC1333 Testing of aier Plasterboard to AS/NZS 2588 (Electronic copy (PDF format) original signed by author) Author: Neil Lee Materials Scientist Reviewer: ryan Keen Senior Technician Contact: RANZ Limited

More information

Copyright Statement FPC International, Inc

Copyright Statement FPC International, Inc Copyright Statement All rights reserved. All material in this document is, unless otherwise stated, the property of FPC International, Inc. Copyright and other intellectual property laws protect these

More information

TEST REPORT Reference No. : TRHZ _R1 Date : Nov. 27, 2012 Page No.: 1 of 5

TEST REPORT Reference No. : TRHZ _R1 Date : Nov. 27, 2012 Page No.: 1 of 5 Reference. : TRHZ0630_R Date : v. 27, 202 Page.: of pplicant : ddress : HINING LOFTY XUN BNNER TEXTILE CO., LTD. NO.70-,LONGXING ROD, HICHNG STREET, HINING CITY, ZHEJING, CHIN. The following merchandise

More information

E/ECE/324/Rev.2/Add.102/Rev.1 E/ECE/TRANS/505/Rev.2/Add.102/Rev.1

E/ECE/324/Rev.2/Add.102/Rev.1 E/ECE/TRANS/505/Rev.2/Add.102/Rev.1 30 August 2011 Agreement Concerning the adoption of uniform technical prescriptions for wheeled vehicles, equipment and parts which can be fitted and/or be used on wheeled vehicles and the conditions for

More information

CERTIFICATE OF APPROVAL No CF 5235 AVIANS INNOVATIONS TECHNOLOGY PVT. LTD

CERTIFICATE OF APPROVAL No CF 5235 AVIANS INNOVATIONS TECHNOLOGY PVT. LTD CERTIFICATE OF APPROVAL No CF 5235 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of AVIANS INNOVATIONS

More information

TNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft. T F

TNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft.   T F ederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / etherlands Organisation for Applied Scientific Research TO report E 13823:22 "Single Burning Item" and E 11925-2:22 "Ignitability"

More information

TEST REPORT. Ceram Reference: (QT21489/2/SL)/Ref: 1.0A. Tensile and Frictional Tests on the Fast Fit BeamClamp Systems.

TEST REPORT. Ceram Reference: (QT21489/2/SL)/Ref: 1.0A. Tensile and Frictional Tests on the Fast Fit BeamClamp Systems. TEST REPORT Ceram Reference: 121557 (QT21489/2/SL)/Ref: 1.0A Project Title: Tensile and Frictional Tests on the Fast Fit BeamClamp Systems Client: Kee Safety Limited For The Attention of: Mr Phil Higgs

More information

Code no STRONG STAINLESS STEEL BUTT HINGES

Code no STRONG STAINLESS STEEL BUTT HINGES STRONG STAINLESS STEEL BUTT HINGES Code no. 60-090Q1 STRONG BUTT HINGE L 160 x B 90 x 3 With holes Code no. 60-090A STRONG BUTT HINGE L 90 x B 85 x 2.5 Without holes Code no. 60-090A1 STRONG BUTT HINGE

More information

Betatrak Compliance Standard

Betatrak Compliance Standard Betatrak Compliance Standard ASTA Certificate of Verification Tests Laboratory Ref. No: 45673/1 APPARATUS: Rated current 63A, rated voltage 240V/415V, rated impulse voltage 4kV, 50Hz, a range of underfloor

More information

TESTING LABORATORY FOR CIVIL ENGINEERING MATERIALS

TESTING LABORATORY FOR CIVIL ENGINEERING MATERIALS TESTING LABORATORY FOR CIVIL ENGINEERING MATERIALS INSTITUTE FOR REASEARCH OF CIVIL ENGINEERING MATERIALS, STONE- AND CONCRETE CONSTRUCTION AND FIRE INTEGRITY MPA BRAUNSCHWEIG Inspection report nr (3329/2706)

More information

Multideck 50-V2 Features and Applications

Multideck 50-V2 Features and Applications Features and Applications is a dovetail profile deck with a depth of 50mm providing spans up to 4m unpropped. Greater Design Efficiency The larger range of Multideck gauge thicknesses available allow much

More information

Bostik Intucrylic Sealant INTUMESCENT ACRYLIC JOINT SEALANT

Bostik Intucrylic Sealant INTUMESCENT ACRYLIC JOINT SEALANT Bostik Intucrylic Sealant INTUMESCENT ACRYLIC JOINT SEALANT Date: 02 July 2014 Fact Sheet No.: TDS00644 YOUR SMART ADVANTAGES High levels of certification Will not slump in joints up to 30mm Prevents passage

More information

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES DAMPERS 4 SFB (57.9) X UDC AUGUST 2006

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES DAMPERS 4 SFB (57.9) X UDC AUGUST 2006 FIREGARD Curtain Fire Dampers DAMPERS SFB (.) X UDC. AUGUST 00 FEATURES Galvanised or Stainless Steel Interlocking Blades in Airtight Casing. Stainless Steel Side Seals. Constant Tension Stainless Steel

More information

Temperature Life with or without Electrical Load Test Procedure for Electrical Connectors and Sockets

Temperature Life with or without Electrical Load Test Procedure for Electrical Connectors and Sockets ANSI/EIA-364-17B-1999 Approved: April 23, 1999 EIA STANDARD EIA-364-17B TP-17B Temperature Life with or without Electrical Load Test Procedure for Electrical Connectors and Sockets EIA-364-17B (Revision

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A6458.01 801 18 Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas PRODUCT TYPE: Fiberglass In Swing Glazed Double Doors SERIES/MODEL:

More information

Grilles & Diffusers. Series NV Non-vision grilles. Incorporating. Sight blocking design ensures privacy is maintained

Grilles & Diffusers. Series NV Non-vision grilles. Incorporating. Sight blocking design ensures privacy is maintained Grilles & Diffusers Incorporating Series NV Sight blocking design ensures privacy is maintained Perfect for areas like changing rooms Four models available including units to suit door mounting and dark

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A6839.01 801 18 Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas PRODUCT TYPE: In Swing Fiberglass Double Doors with Speak Easy

More information

Lloyd s Register Type Approval System Test Specification Number GT04

Lloyd s Register Type Approval System Test Specification Number GT04 Lloyd s Register Type Approval System Test Specification Number GT04 Gas Turbines Performance and test specifications for Gas Turbines to be used in Marine, Offshore and Industrial Applications 2004 Lloyd's

More information

TABLE OF CONTENTS FOREWORD...3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS...

TABLE OF CONTENTS FOREWORD...3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS... TITLE SPECIFICATION FOR PORTABLE DATE: JULY 2006 PAGE: 1 OF 25 TABLE OF CONTENTS Page FOREWORD...3 INTRODUCTION...4 1 SCOPE...4 2 NORMATIVE S...4 3 DEFINITIONS AND ABBIATIONS...4 4 REQUIREMENTS...5 4.1

More information

NFPA 285 TEST REPORT. Report No.: H Test Date: June 1, Rendered to: ARCONIC ARCHITECTURAL PRODUCTS Eastman, Georgia

NFPA 285 TEST REPORT. Report No.: H Test Date: June 1, Rendered to: ARCONIC ARCHITECTURAL PRODUCTS Eastman, Georgia NFPA 285 TEST REPORT Report No.: H1152.01-121-24 Test Date: June 1, 2017 Rendered to: ARCONIC ARCHITECTURAL PRODUCTS Eastman, Georgia WALL SYSTEM: Exterior Non-loadbearing Wall Assembly COMBUSTIBLE COMPONENTS:

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A6457.01 801 18 Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas PRODUCT TYPE: In Swing Fiberglass Door with Side Lites SERIES/MODEL:

More information

Multideck 60-V2. Contents

Multideck 60-V2. Contents The original and still the most popular deck in the market is a 60mm high, structurally efficient trapezoidal profile providing an excellent composite union between steel and concrete to maximise the load

More information

TransShield Mode 1/2. Transfer Stainless Steel Sliding Plate Fire Dampers.

TransShield Mode 1/2. Transfer Stainless Steel Sliding Plate Fire Dampers. TransShield Mode 1/2 Transfer Stainless Steel Sliding Plate Fire Dampers www.actionair.co.uk sales@actionair.co.uk Introduction The TransShield Modes 1 and 2 stainless steels stainless steel sliding plate

More information

ENEC LICENCE. Licence No. ENEC Page 1/3 Date of Issue

ENEC LICENCE. Licence No. ENEC Page 1/3 Date of Issue ENEC LICENCE Licence No. ENEC-01360 Page 1/3 Date of Issue 2016-03-04 Licence Holder WAGO KONTAKTTECHNIK GMBH & CO KG HANSASTRASSE 27 MINDEN, 32423 Germany Production site WAGO CONTACT SA ROUTE DE L'INDUSTRIE

More information

Amendment 69 FR (20 December 2004) Section 5 Hydraulic brake hose, brake hose assemblies, and brake hose end fittings ESN270529

Amendment 69 FR (20 December 2004) Section 5 Hydraulic brake hose, brake hose assemblies, and brake hose end fittings ESN270529 Vehicle Certification Agency 1 The Eastgate Office Centre Eastgate Road Bristol BS5 6XX United Kingdom Telephone: +44 (0) 117 951 5151 Fax: +44 (0) 117 952 4103 Email: enquiries@vca.gov.uk www.dft.gov.uk/vca/

More information

SECTION 8 RAIL FREIGHT VEHICLE UNDERFRAME AND BODY STRUCTURES

SECTION 8 RAIL FREIGHT VEHICLE UNDERFRAME AND BODY STRUCTURES SECTION 8 RAIL FREIGHT VEHICLE UNDERFRAME AND BODY STRUCTURES ROA MANUAL SCHEDULE OF AMENDMENTS SECTION 8 AMENDMENT NUMBER PAGES AMENDED AMENDMENT SUMMARY DATE ISSUED Portions of this Section of the ROA

More information

Multideck 80-V2 Features and Applications

Multideck 80-V2 Features and Applications Features and Applications is designed to incorporate all the advantages of the Multideck 60-V2 but in a deeper profile to provide longer spans up to 5.4m unpropped. Concrete Volume Savings Due to its unique

More information

Series HCD Airfoil Control Damper

Series HCD Airfoil Control Damper Series HCD Airfoil Control Damper Model: HCD-1 The Holyoake HCD-1 is a precisely made volume and pressure control device with extremely low leakage when closed, (in the range of 0.003m 3 /s at 100 Pa).

More information

ESF on Fire Protection Proposed ESF on Fire Protection Engine attachment points applicable to Piston Engines EASA

ESF on Fire Protection Proposed ESF on Fire Protection Engine attachment points applicable to Piston Engines EASA ESF on Fire Protection Proposed ESF on Fire Protection Engine attachment points applicable to Piston Engines EASA UK CAA Comment: Paragraph (2) of the ESF should clarify whether the other features of the

More information

FD-C Series. Circular Single Blade Externally Resettable Combination Fire and Volume Control Damper B RITAI N

FD-C Series. Circular Single Blade Externally Resettable Combination Fire and Volume Control Damper B RITAI N V1175 FD-C Series Circular Single Blade Externally Resettable Combination Fire and Volume Control Damper ES classified fire dampers with reduced smoke leakage characteristics (BS E 1366-2) Aerodynamically

More information

Ride-on lawnmowers (combustion engine powered)

Ride-on lawnmowers (combustion engine powered) Compliance Guide Rev.2.3 Edition 04/2018 Ride-on lawnmowers (combustion engine powered) This guide is intended to help market surveillance authorities with the checking of conformity of combustion engine

More information

Outside Louvers. Series OHCL, OHL, OHL-CD, OHL-D, OHL-KD, OHL-LAOGS, OHL-LOUVER DOOR, OHL-ST2/ST4, OVL & PHL

Outside Louvers. Series OHCL, OHL, OHL-CD, OHL-D, OHL-KD, OHL-LAOGS, OHL-LOUVER DOOR, OHL-ST2/ST4, OVL & PHL Series OHCL, OHL, OHL-CD, OHL-D, OHL-KD, OHL-LAOGS, OHL-LOUVER DOOR, OHL-ST2/ST4, OVL & PHL OHCL Outside Horizontal Closable Louvers - mm Curved Profile 226-228F OHCL 124 Outside Horizontal Closable Louvers

More information

EU RO Mutual Recognition Technical Requirements

EU RO Mutual Recognition Technical Requirements 1. PRODUCT DESCRIPTION... 1 2. DESIGN EVALUATION... 2 3. PRODUCTION REQUIREMENTS... 6 4. MARKING REQUIREMENTS... 6 5. TYPE APPROVAL CERTIFICATE CONTENT... 7 6. APPROVAL DATE AND REVISION NUMBER... 7 7.

More information

CI/SfB (31.59) X. January Briton. Overhead Door Controls 2700 Series. page 1

CI/SfB (31.59) X. January Briton. Overhead Door Controls 2700 Series. page 1 Uniclass L EPIC D CI/SfB (.9) X January 00 Briton Overhead Door Controls 700 Series page Briton 700 Features & Functions Versatile and elegant The Briton 700 Series is a precision manufactured cam-action,

More information

Cylinders. Hinges. Bolts

Cylinders. Hinges. Bolts BOLOTA 304 BOLOTA 304 THE COMPANY PRODUCT RANGES SERVICE SAMPLES INDEX Lever Handles Escutcheons Turn and Release Sets Pull Handles Push Plates and Signage Locks and Latches Cylinders Door Closers Hinges

More information