TransShield Mode 1/2. Transfer Stainless Steel Sliding Plate Fire Dampers.
|
|
- Lionel Atkins
- 5 years ago
- Views:
Transcription
1 TransShield Mode 1/2 Transfer Stainless Steel Sliding Plate Fire Dampers
2 Introduction The TransShield Modes 1 and 2 stainless steels stainless steel sliding plate dampers are designed for air transfer applications through fire rated doors and dry wall partitions, providing up to 2 hour fire protection. The Range Flanged 18 gauge stainless steel Sliding Seal and Static Damper Plates with horizontal perforations which provide, whilst the Seal Plate is in the open position, a free area of not less than that of the specially designed Grilles, for the passage and transfer of ventilation air in either direction. The Damper Sliding Plate is retained to the Damper Static Plate with stainless steel shouldered rivets and fails-safe to the instant closed position, powered by two stainless steel tension springs, with the melting and parting at a temperature of 72 C of an all brass Fusible Link attached to Sliding Seal Plate, to form a fire resistant shield from either air flow direction. The Fusible Link functions independently and regardless of choice or status of Release and Reset Mechanism. Slimline Casing Both Damper Plates together with a choice of two interchangeable and replaceable Release and Reset Mechanisms with both being self contained in a removable Cassette, are housed within an 18 gauge stainless steel Slimline Damper Casing which has integral flanges with prepunched fixing and alignment holes for ease of installation. The TransShield Damper complete with 18 gauge stainless steel flanged backing sleeve and matching Transfer Grilles can be readily accommodated in half-hour fire rated 44mm thick and 1 hour fire rated 54mm thick doors as well as fire rated dry wall/partitions. Control Options A choice of two interchangeable and replaceable Release and Reset Mechanisms is available with either a Manual Release (Mode 1) or a Manual and 24 Volt DC Electro Magnet Release (Mode 2) being self contained in a compact Cassette with simple screw attachment direct to the Damper. For easy withdrawal without disturbance other than the removal of the relevant Transfer Grille. Removal of the Release and Reset Mechanism Cassette provides the further fail-safe feature of Damper instant closure which cannot be reversed until the proper replacement is made. Control Mode 1 A fusible link actuates the instant closure of the damper due to an abnormal rise in temperature. Control Mode 2 The 24 Volt DC Electro Magnet is normally energised to hold open the TransShield Damper, which will instantly close when the electrical supply is interrupted, either as a function of a smoke detection system or due to failure of the electrical supply and in both events, prior to the operation of the Fusible Link on temperature rise or a full fire condition. It is recommended that the continuous electrical supply (83mA Load) to the 24 Volt DC Electro Magnet is through a battery circuit and not an automatic change-over system. External Manual Release, Resetting and Testing Facilities The Cassette also contains, recessed but readily accessible externally operated Release and a Resetting facility through the Transfer Grille. The Release Lever when manually depressed overrides all other functions to close the TransShield Damper for periodic operational testing. The Resetting Shaft when manually turned in a partial anti-clockwise direction automatically resets the TransShield Damper in the open position assuming all other functions are intact. External Visual Indication of Damper Status The TransShield Damper on closing, automatically disengages a spring loaded Damper Set and Status Pin, which is encapsulated with a distinct red plastic capping, providing visual indication of Damper status. Matched Transfer Grilles A pair of specially designed matching non vision Transfer Grilles with radius edges and countersunk fixing holes are always supplied with each TransShield Damper for fitting to both sides of door or dry wall/partition. The Transfer Grilles are constructed in 18 gauge galvanised mild steel finished in Polyester Powder coat to RAL 8025 gloss brown, as standard. As an optional additional cost, the grilles can be finished in either BS or RAL standard colours. 2
3 Installation Procedure 1. Make the the structural opening to the actual dimensions of the Cutting Hole Size of the selected Damper. 2. Locate the Flanged Backing Sleeve with the 8mm flange height at the top into whichever side is deemed to be the rear of the structural opening and when uniformly spaced therein use as template to mark position of all flanged 4mm diameter screw holes. 3. The Flanged Backing Sleeve can then be removed and all pilot holes drilled accordingly. 4. Relocate the Flanged backing Sleeve at the same time providing an application of the fire resistant sealant between the back of the flange and the structural opening periphery, before screw fixing with the slotted head screws provided to the structure face using all the countersunk flange holes only, as the remaining four side plain holes are for alignment with and fixing through to the structure, of the rear Transfer Grille complete with non vision baffle. Flanged backing Sleeve TOP FRONT ELEVATION PLAN VIEW FIXED TO REAR OF STRUCTURAL OPENING FIRE RESISTANCE SEALANT BETWEEN BACK OF FLANGE AND STRUCTURAL OPENING PERIPHERY THE 4 PLAIN HOLES ARE FOR TRANSFER GRILLE ALIGNMENT AND FIXING COUNTERSUNK HOLES ARE FOR FIXING TO STRUCTURAL FACE AND THE NUMBER VARY DEPENDENT ON DAMPER SIZE 5. Locate the Damper Assembly with the Cassette at the top into the opposite front side of the structural opening and inside the Flanged backing Sleeve and when uniformly spaced therein use as template to mark position of all flanged 4mm diameter screw holes, and note that the two holes in line with the Cassette at each end of both sides of the Damper Assembly are alternative electrical supply entry points for Dampers fitted with Mode The Damper Assembly can then be removed and all pilot holes drilled accordingly. 7. Relocate the Damper Assembly and if the Damper is fitted with Mode 2, ensure that the electrical power supply is isolated and the wiring is then continued through the appropriate side hole of the Damper Assembly before applying the necessary fire resistant and screw fixing with the slotted head screws provided to the structure face in the same manner as described for the Flanged Backing Sleeve in (4) above. Damper Assembly FIRE RESISTANCE SEALANT BETWEEN BACK OF FLANGE AND STRUCTURAL OPENING PERIPHERY TOP FRONT ELEVATION PLAN VIEW FIXED TO FRONT OF STRUCTURAL OPENING ALTERNATIVE ELECTRICAL SUPPLY ENTRY POINTS FOR DAMPERS FITTED WITH MODE 2 THE 4 PLAIN HOLES ARE FOR TRANSFER GRILLE ALIGNMENT AND FIXING COUNTERSUNK HOLES ARE FOR FIXING TO STRUCTURAL FACE AND THE NUMBER VARY DEPENDENT ON DAMPER SIZE 8. If the Damper is fitted with Mode 2 connect the electrical supply wiring to the Cassette terminal block. 9. Set the damper in the open position by engaging 4mm hexagon allen key in the Cassette Resetting Shaft and turning same in a partial anti-clockwise direction when the Damper should remain in the open position, unless, in the case of Mode 2 operation there is no electrical power supply to the 24 VOLT DC Electro Magnet, in which event the Damper will immediately fail-safe closed. 10. Release the Damper to the closed position by also using 4mm hexagon allen key to manually depress the Cassette release Lever and closing the Damper disengages within the Cassette a spring load Damper Set & Status Pin, the end of which is encapsulated with a distinctive red coloured plastic capping and with an outward movement to a completely exposed position on the Cassette front face provides visual indication of Damper status. 11. Once satisfied with the operational testing of the damper, complete the installation by aligning the side countersunk holes to the rear and front transfer Grilles with the corresponding side holes in the two non vision baffles (should they have separated from the Grille) and the remaining side flange holes of the Flanged backing Sleeve and the Damper Assembly respectively. Screw fix with the pozi-driv screws provided, to either side of the structural opening, ensuring that the 45mm flange height on the rear Transfer Grille is at the top and that the three holes in the centre of the 45mm flange height of top of the front Transfer Grille are in line with and provide access to the functional aspects of the Damper Cassette Transfer Grilles FRONT GRILLE REAR GRILLE REAR FRONT SIDE ELEVATION IN STRUCTURAL OPENING Cassette Interchangeability or Replacement 1. Un-screw the four pozi-driv fixing screws of the front Transfer Grille and remove same together with the non vision baffle to expose the Cassette. 2. If the Damper is fitted with Mode 2 isolate the electrical power supply before disconnecting the wiring from the Cassette terminal block. 3. The Cassette has simple two screw attachment direct to the Damper Static Plate within the Damper Assembly and unscrewing the two slotted head screws enables the Cassette to be withdrawn outward from the Damper Assembly. 4. Cassette interchangeability or replacement is achieved through reversing all the foregoing procedure 3
4 RESET STATUS RELEASE RESET STATUS RELEASE RESET STATUS RELEASE RESET STATUS RELEASE RESET STATUS RELEASE TransShield Modes 1 & 2 Control Mode 2 Electrical Wiring with optional microswitch Microswitch positioning (by others) ORANGE BROWN 24 VOLT DC ELECTROMAGNET ALL EXTERNA L WIRING BY OTHERS RED BLACK YELLOW RED 15mm CABLE BLACK 15mm CABLE YELLOW 15mm CABLE MICROSWITCH OPTIONAL EXTRA Dimensional Data 1. Dampers are suitable for vertical application only, with the passage and transfer of ventilation air in either direction. 2. Dampers are supplied with the Sliding Seal Plate in the closemicroswitch is fitted prevent damage in transit and the ingress of building dust and dirt on site and during installation; and it is recommended that the Sliding Seal Plate should remain closed until the actual date of commissioning. 3. Flanged Backing Sleeves have a sleeve depth of 38mm, a top flange height of 8mm, sides and bottom flange heights of mm, and are supplied 5mm, under the cutting hole size. 4. Damper Assemblies have a sleeve depth of mm, a top flange height of 8mm, sides and bottom flange heights of mm, and are supplied 5mm, under the Flanged Backing Sleeve size for always fitting within the Sleeve. 5. The Cassette regardless of choice of Mode is 1mm wide x 35mm high x 26mm deep. 6. Transfer Grilles have a top flange height of 45mm, with sides and bottom flange heights of 25mm. Size 1 x1 7. To order specify TransShield Cutting Hole Size and Mode Number. Size 310 x 1 8. TransShield Dampers are an Actionair Quality Engineered Life Safety product and should always be fitted and operated in accordance with instructions provided. Size 310 x 0 Cutting Hole Size W x H Grille O/A Size W x H Effective Free Area m2 Damper (Including Grilles) Approx Weight Kg Grilles Only (Per Pair) Approx Weight Kg Size 4 x 0 1 x x x x x x 3 4 x x 3 4 x x Size 4 x 4 4
5 Non Door Applications Suggested builder s work detail for fitting TransShield Damper in blockwork wall DRILL HOLE FOR CABLE WHEN FITTING TRANS/SHIELD MODE 2 DAMPER TRANS/SHIELD GRILLE MUST OVERLAP APERTURE-HARDWOOD STRIPS TO MAINTAIN FIRE BARRIER INTEGRITY A HARDWOOD STRIPS FIXED INTO WALL OPENING C B TransShield Mode 1 and 2 Damper MIN SIDE ELEVATION PLAN FLANGED DAMPER SLEEVE X 14 MIN 8 MODE 1 OR MODE 2 CASSETTE 8 32 GRILLE Nominal Size A B C 1 x x x x GRILLE 8mm Dia. HOLE FOR MODE 2 CABLE ENTRY FLANGED DAMPER SLEEVE (INCLUDING DAMPER) 4 x All dimensions are in millimetres. SPECIAL EXTENDED WALL SLEEVE OF 18 GAUGE STAINLESS STEEL FACTORY FITTED TO STANDARD TRANS/SHIELD FLANGED DAMPER SLEEVE Standard units are suitable for wall thickness 44mm to 75mm. TransShield Mode 1 and 2 Damper complete with Extended Wall Sleeve Wall sleeves are required for greater wall depths. With this sleeve arrangement, Dimension X can vary according to wall thickness, from 82mm up to a maximum of 0mm. Please advise Dimension X. 5
6 Acoustic Data The data presented is from the Laboratory Determination of Acoustic and Aerodynamic Performance of TransShield Stainless Steel Sliding Plate Fire and Smoke Dampers complete with matching non vision Transfer Grilles. Example: With an air transfer air volume requirement of I/s and selecting Size 310 x 0 TransShield Damper and Grilles. Pressure Drop = 14 Pa. Multiply Volume X Pressure Drop x 14 = 8. Pressure Drop Vs Velocity A programme of extensive tests was carried out in the Reverberation Room of Sound Research Laboratories Limited, Holbrook Hall, Sudbury, Suffolk, generally in accordance with BRITISH STANDARDS From the Graph Sound Power Level dbw = 43 less Spectrum Corrections. From the Pressure Drop Vs Velocity Graph the selected Size 310 x 0 TransShield Damper and Grilles at a Nos. 27, 4196, ISO. 1 and 3741 pressure drop of 14 Pa produces a Part 1. This independent test facility is velocity of 2.1 m/s. approved under the NAMAS Scheme. Selection and Acoustic Performance With a known air volume select a suitable size of TransShield Damper and a resultant pressure drop can be determined and the sum of these two 5 components applied to the Volume X 4 Pressure Drop Vs Sound Power Level Graph. This graph is the result of a full range of acoustic tests on the TransShield Damper 2 complete with matching Transfer Grilles. The Spectrum Correction Data is applied to the number obtained from the graph and a full Sound Spectrum of Flow Generated Noise (outlet) is obtained VELOCITY m/s PRESSURE DROP Pa SIZE 4 x 4 SIZE 4 x 0 SIZE 310 x 0 SIZE 310 x 1 SIZE 1 x 1 Air Volume Vs Pressure Drop Air Volume (l/s) x Pressure Drop (Pa) Vs Sound Power Level (dbw) PRESSURE DROP Pa SIZE 1 x 1 SIZE 310 x 1 SIZE 310 x 0 SIZE 4 x 0 SIZE 4 x 4 SOUND POWER LEVEL (dbw) AIR VOLUME I/s AIR VOLUME X PRESSURE DROP (I/s Pa) Outlet (in duct) Spectrum Correction Octave band K 2K 4K OPEN K 28 Hz db 6
7 Specification The design of the TransShield Dampers shall comprise of flanged 18 gauge stainless steel Sliding Seal and Static Damper Plates with horizontal perforations to provide whilst the Seal Plate is in the open position, a free area of not less than that of the matching Transfer Grilles, for the passage and transfer of ventilation air in either direction. The Damper Sliding Seal Plate shall be retained to the Static Damper Plate with stainless steel shouldered rivets and failsafe to the instant closed position powered by two stainless steel tension springs either by the melting and parting of an attached Fusible Link at a temperature of 72 C, or the functioning of the relevant Release and Reset Mechanism to maintain integrity and not permit the passage of flame when exposed to the time/temperature curve of BS476 Part: 1987 for a period of two hours as tested by the Fire Insurers Research & Testing Organisation (Approval TE 6523). Both Damper Plates together with a removable Release and Reset Mechanism Cassette shall be housed within an 18 gauge stainless steel slimline Damper Casing having integral flanges with prepunched fixing holes. The Cassette shall have screw fixing for ease of attachment to and withdrawal from the Damper Static Plate without disturbance to the Damper and shall contain recessed from view but readily accessible, a Release Lever and Resetting Shaft, both manually operated, and a spring loaded Damper Set and Status Pin which in the exposed position shall provide visual indication of Damper status. The Cassette shall also contain either of two interchangeable and replaceable Release and Reset Mechanisms. Mode 1 Manual Release Fusible Link shall actuate the instant closure of the Damper due to an abnormal rise in temperature. Mode 2 Manual and Electro Magnet Release A 24 Volt DC Electro Magnet shall actuate the instant closure of the Damper when the electrical supply is interrupted, either as a function of a Smoke Detector System or due to failure of the electrical supply and in both events, before the operation of the Fusible Link due to an abnormal rise in temperature or a full fire condition occurs. Each TransShield Damper shall be complete with 18 gauge stainless steel flanged backing sleeve and a pair of specially designed matching non vision Transfer Grilles with radius edges, countersunk fixing holes and constructed in 18 gauge galvanised mild steel finished in Polyester Powder coat to RAL 8025 gloss brown. The TransShield Dampers and Transfer Grilles suitable for mounting in the vertical plane only, shall be manufactured by Actionair. Customer Service Actionair provides quality products backed by a dedicated team committed to providing the very best in customer service. Offering experienced technical backup, comprehensive sales and administrative customer support, product commissioning and maintenance service. Approvals Product Conformity awarded by The Loss Prevention Certification Board Limited. Fire tested (2 hour rating) Fire Insurers Research and Testing Organisation. Ordering Information The information contained herein is subject to change without notice due to continuing research and development. Example Quantity Series Control Mode Cutting Hole Size Accessories 7 Trans/Shield M2 310 x 0 Extended Sleeve x =? Number of units Trans/Shield. Mode 1 Sizes Customer to provide required Fail-Safe Fusible Link. (W) x (H) mm dimension x, please refer to 1 x 1 page 5. Mode x 1 24 Volt DC Electro Magnet 310 x 0 and Fail-Safe Fusible Link. 4 x 0 4 x 4 Special Grille Finish (Options) Volt Free Contact for Status Indication (Single Pole Micro Switch) 1. Special paint finishes specify BS or RAL number and gloss or matt finish (extra cost). 2. Unpainted galvanised steel grilles. Volt Free Contact for open or closed status indication. Connection strip on left hand side (when viewing grille front elevation). For further application, technical and pricing information, please refer to Actionair Sales Office. 7
8 actionair air diffusion airfiltrera airolution naco Metal Louvre South Street, Whitstable, Kent, CT5 3DU Tel: +44 (0) Website: actionair.co.uk The statements made in this brochure or by our representatives in consequence of any enquires arising out of this document are given for information purposes only. They are not intended to have any legal effect and the company is not to be regarded as bound thereby. The company will only accept obligations, which are expressly negotiated for and agreed and incorporated into a written agreement made with its customers. Due to policy of continuous product development the specification and details contained herein are subject to alteration without prior notice. LNNN00115(1.0)
IrisControlDamper. For Adjustment and Measuring of Airflow.
IrisControlDamper For Adjustment and Measuring of Airflow www.actionair.co.uk sales@actionair.co.uk Iris Control Damper (ICD) Quick, silent and efficient is the simple summary of the features of the Actionair
More informationNEW. Iris Control Damper (ICD) For adjustment and measuring of airflow. Features. Quick and simple installation and maintenance
March 29 Iris Control Damper (ICD) NEW Iris Control Damper (ICD) For adjustment and measuring of airflow Features Quick and simple installation and maintenance Extended spigot connections 1% opening capacity
More informationBlade Features. AirShield Control and Shut Off Dampers. AirShield
April 2011 AirShield AirShield AirShield Aerofoil Air Control Dampers AirShield Aeroseal Air Control and Shut Off Dampers AirShield Features and Design Guide Opposed blade dampers suitable for systems
More informationEnergyShield ES. Air Control and Shut off Dampers. Dampers Controls Fancoils. Ruskin Air Management Limited
April 11 EnergyShield ES EnergyShield ES Air Control and Shut off Dampers Features Dampers suitable for systems requiring air control and low closed blade leakage characteristics. Low torque characteristics.
More informationFire Block and Pressed Steel Grilles
Catalogue Fire Block and Pressed Steel Grilles Fire Block FB60 Fire Block FB120 www.air-diffusion.co.uk sales@air-diffusion.co.uk Fire Block FB60 Features Fits directly into ducts, doors or wall apertures
More informationAnti-Ligature Grille. There s a much bigger picture to be found at Ruskin Air Management. Model AL/35 Model AL/24. range available.
June 2013 Anti-Ligature Grille Model AL/35 Model AL/24 l Cost effective l Robust construction l Supply and exhaust l Complete plenum box range available l Full range of accessories available There s a
More informationCell Ventilation Security Grille
June 2010 Cell Ventilation Security Grille Cell Ventilation Security Grille Model CV Features Stainless Steel Construction Galvanised Steel/ PPC Construction Supply and Exhaust Tested "Fit For Purpose"
More informationActionair A-60 Marine Fire Damper Designed for inclusion in Marine and Offshore Projects
March 06 A-60 Marine Fire Dampers Tests and Approvals A60 Fire Rated. Lloyds Register of Shipping Approved. Marine Equipment Directive compliant. USCG Approved. Germanischer Lloyds Approved. American Bureau
More informationSSV Smoke Shaft Ventilation System
SSV Smoke Shaft Ventilation System sales@actionair.co.uk Introduction Installation Method The growing demand for multi storey apartment, hotels and flats requires safe evacuation of smoke and toxic gases
More informationFire Block and Pressed Steel Grilles
September 2010 Fire Block and Pressed Steel Grilles Fire Block FB60 Sodium silicate based intumescent material. Provides the lowest activation temperature of any intumescent material at degrees C. It is
More informationFlowBar High Capacity Slot Diffuser
October 2016 FlowBar High Capacity Diffuser Model HT (High Throw) Model JT (Jet Throw) Features HT & JT 25mm, 38mm, 51mm, 63mm & 76mm s Ceiling or Sidewall Applications Modular or Continuous s Curved Sections
More informationPanel Floor Grilles Model LDA, MDA, HDA, PFS and F48
May 2010 Panel Floor Grilles Panel Floor Grilles Model LDA, MDA, HDA, PFS and F48 Features l Model LDA Light Duty Panel Floor Grille l Model MDA Medium Duty Panel Floor Grille l Model HDA Heavy / Extra
More informationCatalogue. FlowBar. High Capacity Slot Diffuser.
Catalogue FlowBar High Capacity Slot Diffuser www.air-diffusion.co.uk sales@air-diffusion.co.uk Content Introduction... 4 Diffuser Specification... 5 Air Patterns... 6 Flange Styles... 7 Curved Sections...
More informationNEW. A-60 Marine Fire Damper. Includes new casing depths and thickness, Atex rated motor and visual indication options.
January 2008 A-60 Marine Fire Dampers Includes new casing depths and thickness, Atex rated motor and visual indication options. NEW A-60 Marine Fire Damper Designed for inclusion in Marine and Offshore
More informationLinear Floor Grilles Models FG, F20, F25 and FRO
April 2010 Linear Floor Grilles Linear Floor Grilles Models FG, F20, F25 and FRO Features Model FG Recessed Linear Floor Grille Model F20 and F25 Flanged Linear Floor Grille Model FRO Roll Out Floor Grille
More informationActionair Control and Shut Off Dampers
December 2003 Air/Shield (Incorporating Energy/Shield ES35 & ES36) Actionair Control and Shut Off Dampers Air/Shield Aerofoil Air Control Dampers Air/Shield Aeroseal Air Control and Shut-Off Dampers Energy/Shield
More informationFIREGARD GILBERTS. Curtain Fire Dampers FEATURES
FIREGARD Curtain Fire Dampers DAMPERS SFB (.) X UDC. FEBRUARY 00 FEATURES Galvanised or Stainless Steel Interlocking Blades in Airtight Casing. Optional Stainless Steel Side Seals. Constant Tension Stainless
More informationActionair Smoke/Shield PTC
September 2004 Smoke/Shield PTC Actionair Smoke/Shield PTC Proportional Torque Control Automatic Smoke and Fire Dampers Features and Design Guide Proportional Torque Control for optimised torque performance.
More informationFloor Swirls Models BZD and SZD
July 09 Floor Swirls Floor Swirls Models BZD and SZD Features Model BZD Circular Floor Swirl Model SZD Circular Step Diffuser Grilles Diffusers Louvres Chilled Beams Ruskin Air Management Limited www.ruskinuk.co.uk
More informationFIREGARD GILBERTS. Curtain Fire Dampers FEATURES DAMPERS 4 SFB (57.9) X UDC AUGUST 2006
FIREGARD Curtain Fire Dampers DAMPERS SFB (.) X UDC. AUGUST 00 FEATURES Galvanised or Stainless Steel Interlocking Blades in Airtight Casing. Stainless Steel Side Seals. Constant Tension Stainless Steel
More informationHydropac. Waterside Control Fan Coil Units For Horizontal and Vertical Applications. June Hydropac. Features
June 2003 Hydropac Hydropac Waterside Control Fan Coil Units For Horizontal and Vertical Applications Features Flush panel extra rigid construction. Low noise levels. Eleven speed transformer. Full acoustic
More informationCatef Marine-Fire. A-60 Marine Fire Damper. Includes new casing depths and thickness, Atex rated motor and visual indication options.
Includes new casing depths and thickness, Atex rated motor and visual indication options. Features Blades 430 stainless steel and 316 stainless steel options. Casings Lightweight cost effective design.
More informationSFD-EN Smoke/Fire Dampers
December 2009 SFD-EN SFD-EN Smoke/Fire Dampers Features Proportional Torque Control for optimised torque performance. Unique snaplock drive interface ensures user friendly connection of Control Actuator
More informationGrilles & Diffusers. Series NV Non-vision grilles. Incorporating. Sight blocking design ensures privacy is maintained
Grilles & Diffusers Incorporating Series NV Sight blocking design ensures privacy is maintained Perfect for areas like changing rooms Four models available including units to suit door mounting and dark
More informationC O L M A N. Air Distribution PERFORATED FACE DIFFUSERS P SERIES SERIES
C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S PERFORATED FACE DIFFUSERS P SERIES P SERIES PERFORATED FACE DIFFUSERS P SERIES QUALITY AND EFFICIENCY WITHOUT COMPROMISE Application:
More informationFire Dampers. Types FKA FRL FRK 4/1/EN/1
Fire Dampers Types FKA FRL FRK /1/EN/1 Contents Description Description... Construction... Standard Sizes Installation Details... Functional Description Product Range... Accessories... Circuit Diagrams...
More informationLinear Slot Diffusers Model Slot 20 and Model Slot 25
December 06 Linear Slot Diffusers Linear Slot Diffusers Model Slot and Model Slot 25 Features 1 to 8 Slots mm or 25mm Slot widths Ceiling or Sidewall Applications Modular or Continuous Lengths Curved Sections
More informationFree Fall Fire Valve Range & Accessories
Free Fall Fire Valve Range & Accessories 1 Contents Screwed Free Fall Fire Valves... 3 Flanged Free Fall Fire Valves... 6 Free Fall Valve Accessories... 8 Fitting Kits... 8 Mercury and Non-Mercury Switches...
More informationCONTROL SMOKE AND BALANCING DAMPERS
(UK) Limited CONTROL SMOKE AND BALANCING DAMPERS 00 SERIES - UNIVERSAL F e a t u r e s Robust construction of galvanised steel, with stainless steel options Opposed or parallel blade pattern Unsealed,
More informationSystempac. Fan Coil Unit / Acoustic Flex / Diffuser System Package. Systempac. January Features and Design Guide
January 2002 Systempac Features and Design Guide Specifically Designed for Design and Build Projects. Complete package including Waterside Control Fan Coil Unit / Controls / Flexible Ducting / Plenum Box
More informationLouvre systems. Series WL Standard weather louvres. Incorporating. Standard range of single bank louvres as used in countless installations worldwide
Louvre systems Incorporating Series WL Standard range of single bank louvres as used in countless installations worldwide Good resistance to water ingress, with low resistance to airflow Approximately
More informationIncorporating V2.1. Product spec >>> > Series ECG - Egg crate grilles
Incorporating V2.1 Product spec >>> > Series ECG - Egg crate grilles Grilles Egg crate Recommended for: Wall, ceiling & duct Extract Overview Industry standard extract grille Plastic egg crate core optional
More informationC O L M A N. Air Distribution LINEAR BAR GRILLES T SERIES SERIES
C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S LINEAR BAR GRILLES T SERIES T SERIES C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S LINEAR BAR GRILLES T SERIES
More informationCONSTANTFLOW Volume Flow Controllers
5/9.1/EN/8 CONSTANTFLOW Volume Flow Controllers for constant volume systems Type EN The art of handling air Contents Description Description 2 Application 3 Construction Dimensions Accessories 4 Dimensions
More informationLINEAR BAR GRILLES T SERIES. Quality and e!ciency without compromise
LINEAR BAR GRILLES T SERIES Quality and e!ciency without compromise Weltech Business Centre - Ridgeway - Welwyn Garden City - Hertfordshire AL7 2AA Tel: 01707 871526 - Fax: 01707 871 527 - email sales@jprservices.co.uk
More informationFD-C Series. Circular Single Blade Externally Resettable Combination Fire and Volume Control Damper B RITAI N
V1175 FD-C Series Circular Single Blade Externally Resettable Combination Fire and Volume Control Damper ES classified fire dampers with reduced smoke leakage characteristics (BS E 1366-2) Aerodynamically
More informationIncorporating V2.0. Product spec >>> > Series DD - Double deflection grilles
Incorporating V2.0 Product spec >>> > Series DD - Double deflection grilles Grilles Double deflection Recommended for: Wall, ceiling & duct Supply & extract Overview Enhanced functionality As per the name,
More informationIncorporating V2.0. Product spec >>> > Series DJ - Drum jet diffusers
Incorporating V2.0 Product spec >>> > Series DJ - Drum jet diffusers Diffusers Drum jets (Premium) Recommended for: Wall, ceiling & duct Supply Overview Exceptional throw Throw completely adjustable Drum
More informationA-60 Marine Fire Damper
Catalogue A-60 Marine Fire Damper Designed for inclusion in Marine and Offshore Projects Suitable for applications in A0, A15, A30 and A60 class bulkheads and decks www.actionair.co.uk sales@actionair.co.uk
More informationPerforated Face Ceiling Diffusers
February 2011 Perforated Face Ceiling Diffusers Perforated Face Ceiling Diffuser Models PD, DFP and DPP Features NEW DROP PLQUE DESIGN 3 Model Types 1, 2, 3 or 4 way ir Patterns Extruded luminium Sections
More informationShutter Fire Damper Type FSD GFSD 4/1.1/B/1
Shutter Fire Damper Type FSD GFSD /./B/ Contents Description Description... Construction... Installation Details... Control Accessories... Technical Data... Order Details... 7 8 9 FSD-L GFSD-L FSD Fire
More informationSpecification. Introduction. A-60 Marine Fire Damper
March 2015 YY denotes last two digits of year that Wheelmark is affixed to damper A-60 Marine Fire Damper Designed for inclusion in Marine and Offshore Projects. Suitable for applications in A0, A15, A30,
More informationVC Series. Volume Control Dampers M A N U F A C T U R E R S O F A I R, F I R E A N D S M O K E C O N T R O L P R O D U C T S
V41706 VC Series Volume Control Dampers Roll formed steel blades with three material options DW144 compliant Flanged models with 65mm deep mechanically fixed casings Rectangular spigotted models with 85mm
More informationC O L M A N. Air Distribution LINEAR SLOT DIFFUSERS CD SERIES SERIES
C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S LINEAR SLOT DIFFUSERS CD SERIES CD SERIES LINEAR SLOT DIFFUSERS QUALITY AND EFFICIENCY WITHOUT COMPROMISE Application Colman Moducel
More informationAdjustable Curved Vane Diffusers. Vanes are parallel to the width dimension Vanes are parallel to the height dimension
Adjustable Curved Vane Diffusers ACDH ACDV Vanes are parallel to the width dimension Vanes are parallel to the height dimension Diffusers 2 Adjustable Curved Vane Diffusers ACDH / ACDV Introduction The
More informationC O L M A N. Air Distribution SWIRL DIFFUSERS DWT SERIES DWT SERIES
C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S SWIRL DIFFUSERS DWT SERIES DWT SERIES DISTRIBUTION PATTERNS & FIXING OPTIONS Application The DWT Series of swirl diffusers have been
More informationIncorporating V2.0. Product spec >>> > Series NV - Non vision grilles
Incorporating V2.0 Product spec >>> > Series NV - Non vision grilles Grilles Non-vision Recommended for: Wall & door Supply & extract Overview Block line of sight into private areas Giving adequate ventilation
More informationC O L M A N. Air Distribution TRANSFER GRILLES G SERIES SERIES
C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S TRANSFER GRILLES G SERIES G SERIES TRANSFER GRILLES G SERIES QUALITY AND EFFICIENCY WITHOUT COMPROMISE Application Colman s range
More informationCatalogue. HotShieldPTC TM. High Operating Temperature Smoke Management and Fire Dampers.
Catalogue HotShieldPTC TM High Operating Temperature Smoke Management and Fire Dampers www.actionair.co.uk sales@actionair.co.uk Product Features Smoke Management & Fire Dampers operational up to 00 C
More informationHEAVY DUTY BALANCE AND CONTROL DAMPER B A L A N C E C O N T R O L SERIES
HEAVY DUTY BALANCE AND CONTROL DAMPER B A L A N C E C O N T R O L HD SERIES MANUFACTURERS OF AIR/FIRE/SMOKE CONTROL PRODUCTS Product Description and Features Introduction The HD Series Multi-Leaf Volume
More informationFor installation into ductwork
X X testregistrierung Non-return dampers Type For installation into ductwork Non-return dampers prevent unwanted airflows against the intended airflow direction when the system is not in operation Maximum
More informationWall and Ceiling Grille
September 14 Wall and Ceiling Grille Models SD, DD, EC, PG, G45, NVG, NB, GN, WB and GW Single and Double Deflection Fixed and Removable Core Eggcrate Perforated Grille 45 Fixed Blade Non Vision Bar Grilles
More informationFire Damper. Grilles Diffusers Dampers Louvers VAV Boxes Sound Attenuators. Spectrum Industries
Fire Damper A Wide Range of High Quality Air Distribution Products. Grilles Diffusers Dampers Louvers VAV Boxes Sound Attenuators Spectrum Industries Fire Damper Application Fire damper are required by
More informationOptima EXHAUST GRILL AND AIR LOUVER. Perforated Ceiling Diffusers. Features: Standard square sizes:
Perforated Ceiling Diffusers OPTIMA ceiling diffuser with perforated face, are recoended for heating, ventilating and cooling in centralized air conditioning systems. Perforated face diffusers, with 4-3-
More information1/3/EN/4. Ventilation Grilles Types TRS-K TRS-R TRSE-R
1/3/EN/4 Ventilation Grilles Types TRS-K TRS-R TRSE-R Contents Description Description 2 Constructions Dimensions TRS-K 3 Constructions Dimensions TRS-R 4 Constructions Dimensions TRSE-R 5 Installation
More informationBX-1H. Fire Valve FIRE SAFETY FUNCTION APPLICATION DESCRIPTION. in libraries of
FIRE SAFETY Fire Valve in libraries of EI 60 (v e -o i) S EN 131-3+A1:10 EN 156:10 Certificate of Conformity 1488-CPD-02 82/W FUNCTION The fire valves are designed for buildings where in the event of a
More informationCircular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/
6/5/EN/6 Circular Silencer Rigid and flexible construction Type CA CB CF CS TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/2 02-2 65 Heinrich-Trox-Platz e-mail trox@trox.de D-47504 Neukirchen-Vluyn
More informationSDV Vane Swirl Diffusers
SDV Vane Swirl Diffusers SDVSA Square plate vane swirl diffuser (angled slot) SDVCA Circular plate vane swirl diffuser (angled slot) SDVSB Square plate vane swirl diffuser (normal slot) SDVCB Circular
More informationCeiling swirl diffusers
X X testregistrierung Ceiling swirl diffusers Type Horizontal swirling air discharge Adjustable blades Protective cage For high rooms, with adjustable air control blades Circular ceiling swirl diffusers,
More informationHIGH CAPACITY LINEAR SLOT DUFFUSERS
HIGH CAPACITY LINEAR SLOT DUFFUSERS CB SERIES Quality and efficiency without compromise Weltech Business Centre - Ridgeway - Welwyn Garden City - Hertfordshire AL7 2AA Tel: 01707 871526 - Fax: 01707 871
More informationAir Distribution SWIRL DIFFUSERS DW SERIES SERIES
COLMAN Air Distribution E N G I N E E R E D SWIRL DIFFUSERS DW SERIES DW SERIES A I R P R O D U C T S SWIRL DIFFUSERS DW SERIES QUALITY AND EFFICIENCY WITHOUT COMPROMISE Application The DW type swirl diffuser
More informationLouvre systems. Series WLD Weather louvre doors. Incorporating. Fully active louvre panel integrated into a door
Louvre systems Incorporating Series WLD Fully active louvre panel integrated into a door Full range of hardware from basic deadlocks to panic bars and door closers Good resistance to water ingress, with
More informationHotShield PTC TM. High Operating Temperature Smoke Management and Fire Dampers. Features
December 2009 HotShield PTC HotShield PTC TM High Operating Temperature Smoke Management and Fire Dampers Features Smoke Management and Fire Dampers operational up to 300 C for a period of 1 or 2 hours
More informationVAV terminal units. Type TVM. For dual duct systems PD TVM 1
X X testregistrierung VAV terminal units Type Variant -S Rectangular connection on the room end For dual duct systems VAV dual duct terminal units for dual duct systems with variable volume flows in buildings
More informationC O L M A N. Air Distribution LINEAR SLOT DIFFUSERS CE SERIES SERIES
C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S LINEAR SLOT DIFFUSERS CE SERIES CE SERIES LINEAR SLOT DIFFUSERS CE SERIES QUALITY AND EFFICIENCY WITHOUT COMPROMISE Application Colman
More informationCeiling swirl diffusers with perforated face plate
X X testregistrierung Ceiling swirl diffusers with perforated face plate Type Horizontal swirling air discharge For horizontal swirling supply air discharge creating high induction levels, with fixed air
More informationLouvre systems. Series WL Standard weather louvres. Incorporating. Standard range of single bank louvres as used in countless installations worldwide.
Louvre systems Incorporating Series WL Standard range of single bank louvres as used in countless installations worldwide. Good resistance to water ingress, with low resistance to airflow. Approximately
More informationLINEAR SLOT DIFFUSERS
LINEAR SLOT DIFFUSERS MODEL CD Weltech Business Centre - Ridgeway - Welwyn Garden City - Hertfordshire AL7 2AA Tel: 01707 871526 - Fax: 01707 871 527 - email sales@jprservices.co.uk - www.jprservices.co.uk
More informationINDEX. Chapter3. air master. Linear Bar Grilles
Chapter3 INDEX A Linear bar grilles: 1. Supply linear bar grille...: ASLG...3.1 2. Supply linear bar register...: ASLR...3.2 3. Return linear bar grille...: ARLG...3.3 4. Return linear bar register...:
More informationFire/combustion gas damper EKO-JBG
Fire/combustion EKO-JBG Description The EKO-JBG fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting.
More informationC O L M A N. Air Distribution CIRCULAR DIFFUSERS LRS SERIES LRS SERIES
C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S CIRCULAR DIFFUSERS LRS SERIES LRS SERIES CIRCULAR DIFFUSERS L SERIES Application Colman Air Distribution L series circular swirl diffusers
More informationHomepage > Products > External louvres - louvre blades > Mechanically self-powered dampers > Non-return dampers > Type KUL.
Homepage > Products > External louvres - louvre blades > Mechanically self-powered dampers > Non-return dampers > Type KUL Type KUL FOR INSTALLATION INTO DUCTWORK Non-return dampers prevent unwanted airflows
More informationType WG. External weather louvre made of galvanised steel sections FOR THE MOST DIVERSE APPLICATIONS, AVAILABLE ALSO IN LARGE SIZES
Homepage > Products > External Louvres & Dampers > External weather louvres > External weather louvres > Type WG Type WG External weather louvre made of galvanised steel sections FOR THE MOST DIVERSE APPLICATIONS,
More informationCeiling swirl diffusers with perforated face plate
X X testregistrierung Ceiling swirl diffusers with perforated face plate Type Horizontal swirling air discharge Diffuser face plate with perforated circular face style and exposed discharge nozzle Diffuser
More informationEX C E L L E N C E ISO 9001 CERTIFIED COMPANY LINEAR BAR GRILLES.
25 YEARS OF EX C E L L E N C E ISO 9001 CERTIFIED COMPANY 3.0 INDEX ISO 9001 CERTIFIED COMPANY SECTION TOPIC PAGE 3.1 Double deflection linear bar grille ASLG 3 3.2 Double deflection linear bar register
More informationVolume Control Dampers. Series LF upvc-vcd High performance plastic volume control dampers. Incorporating
Volume Control Dampers Incorporating Series LF upvc-vcd 2.76 m 3 /hr/m 2 leakage at 50 Pa, over 70% better than required by Part L of Building Regulations Corrosion resistant, perfect for chlorinated atmospheres
More informationType VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL
Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES Circular ceiling swirl diffusers, with manual or motorised adjustment of the
More informationSERIES GZL. High Induction Linear Diffuser (Patented)
SERIES GZL High Induction Linear Diffuser (Patented) PUBLICATION DIFFUSERS 9 APRIL 2012 Features - One or Two Slot Design. - High Induction Effect. - Unique Crossflow Jet Air Distribution. - Dynamic Modern
More informationCADENZA. Sound attenuator with tapered acoustic baffles for rectangular ducts QUICK FACTS
Sound attenuator with tapered acoustic baffles for rectangular ducts QUICK FACTS Rectangular sound attenuator with connection to the outer casing, which also enables flange connection Excellent aerodynamic
More informationDD Series. Duct Regulating Dampers M A N U F A C T U R E R S O F A I R, F I R E A N D S M O K E C O N T R O L P R O D U C T S. Two blade options.
Duct Regulating Dampers Two blade options. DW144 compliant Four case options Three control options Nylon bushes as standard Suitable for vertical and horizontal ducted systems. M A N U F A C T U R E R
More informationSmoke Dampers. Installation Instructions
Smoke Dampers Installation Instructions Installation Details 1. Dampers should be installed to provide proper operation and performance. They should be installed to permit them to maintain their shape
More informationCeiling swirl diffusers
X X testregistrierung Ceiling swirl diffusers Type RFD-Sirius, cross bar Horizontal swirling air discharge Circular diffuser face, integral measuring tubes is an air terminal device combined with a VAV
More informationCAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1
X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical
More informationEYELASH DIFFUSERS E SERIES. Quality and efficiency without compromise
EYELASH DIFFUSERS E SERIES Quality and efficiency without compromise Weltech Business Centre - Ridgeway - Welwyn Garden City - Hertfordshire AL7 2AA Tel: 01707 71526 - Fax: 01707 71 527 - email sales@jprservices.co.uk
More informationNEO. Fire Damper. air handling intelligence FIRE SAFETY FUNCTION
air handling intelligence FIRE SFETY Fire Damper in libraries of EI 10 (v e -i o) S EN 13501-3+1:01 EN 15650:0 Certificate of Conformity 1488-CPD-081/W EUROPEN PTENT PPLICTION EP 01158318 GOLD MEDL MTP
More informationCAV controllers. Type VFL. Volume flow limiter for insertion into ducting K
.1 X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical
More informationHOTCHKISS AIR ACOUSTICS
HOTCHKISS AIR ACOUSTICS C 3 & C 4 C I R C U L A R A T T E N U A T O R S Description Hotchkiss Air Acoustic type C3 & C4 Circular attenuators are available in all standard circular fan sizes from 315mm
More informationseries RVV Variable flow rate controllers
series RVV Variable flow rate controllers www.koolair.com Series RVV 1 CONTENTS Variable flow rate controllers, type RVV Description 2 Dimensions and product code 3 Selection tables 4 Variable flow rate
More informationPlaster In Grilles 1/1.5/B/1. AHP Plaster-in Linear Bar Grille ADMP Plaster-in Linear Diffuser ALSP Plaster-in Linear Slot Diffuser
1/1.5/B/1 Plaster In Grilles AHP Plaster-in Linear Bar Grille ADMP Plaster-in Linear Diffuser ALSP Plaster-in Linear Slot Diffuser TROX UK Ltd Caxton Way Thetford Norfolk IP24 3SQ Telephone +44 (0) 1842
More informationFire/combustion gas damper EKO-JBL
Fire/combustion Description The fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting. The damper is designed
More informationGDD - Supply Grille. Halton GDD. Supply Grille
Halton GDD Supply Grille Horizontal supply, for circular duct installations For cooling and heating applications; suitable also for exhaust Adjustable vertical front vanes, adjustable horizontal rear vanes
More informationWall air diffusers with discs for supply air and flush mounting. Quick guide COLIBRI WALL
Wall air diffusers with discs for supply air and flush mounting General Rectangular supply air diffusers with rotatable discs. The disc technique enables supply of air above or below room temperature as
More informationType DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION LEVELS, WITH FIXED AIR CONTROL BLADES
Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Ceiling swirl diffusers with perforated face plate > Type DCS Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION
More informationsupplied in Form (B) configuration. Airflow over Impeller- Motor.
CYLINDRICAL CASED AXIAL FLOW FANS COMPACT Series TCBB-TCBT (Aluminium impellers) and TCFB-TCFT (Plastic impellers) NEW VERSIONS Description The S&P Cylindrical Cased Axial Fans feature, as the name suggests,
More informationROM Series. Keeping the World Flowing. Installation Manual. Valve Actuators
ROM Series Installation Manual Valve Actuators Keeping the World Flowing Contents Section Page Health and safety 3 Storage 4 Mounting the actuator 4 Setting the actuator stop bolts 5 Cable connections
More informationActionpac LNS4. Panel Installation Datasheet. Actionpac LNS4 RELEASE 1.0 JUNE In partnership
Actionpac LNS4 Panel Installation Datasheet ELECTROSTATIC SENSITIVE DEVICE This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product will directly
More informationBifurcated Case Axial Fans (BIFA)
Bifurcated Case Axial Fans (BIFA) Sizes 250 to 1000 dia Motors protected to IP55 Motor insulation Class F Maximum ambient temperature 200 C Speed controllable via transformer or inverter (when the ambient
More information(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm.
Fire damper pl-30 General characteristics Application Fire dampers prevent fire and smoke from spreading through ventilation ducts in buildings. The dampers are intended for use inside buildings and are
More informationAxial fans. What s more, non-stock models are normally available within two weeks.
Axial fans 7 sees the introduction of a new production line at Xpelair s Peterborough plant for the Scimitar Sickle blade fans in Plate, Short Case and Roof versions up to 63mm. Scimitar will join an impressive
More informationVentilation grilles for installation into walls, sills or rectangular
X X testregistrierung Ventilation grilles for installation into walls, sills or rectangular ducts Type Ventilation grilles, made of sheet steel, with individually adjustable, horizontal blades Ventilation
More information