WEST OFFALY POWER PEAT FIRED PLANT FUNCTIONAL DESCRIPTION OF I&C LOOPS AUXILIARY STEAM SYSTEM. Document Code: 1 (11) Issuing date: Status: Project :

Size: px
Start display at page:

Download "WEST OFFALY POWER PEAT FIRED PLANT FUNCTIONAL DESCRIPTION OF I&C LOOPS AUXILIARY STEAM SYSTEM. Document Code: 1 (11) Issuing date: Status: Project :"

Transcription

1 Document Code: 1 (11) Project : WEST OFFALY POWER PEAT FIRED PLANT Author: Approved: Language: JJA Document title: FUNCTIONAL DESCRIPTION OF I&C LOOPS AUXILIARY STEAM SYSTEM Submitted for: Customer reference: Other information:

2 Document Code: 2 (11) CONTENT: 1. INSTRUMENT LOOPS & CLOSED LOOP CONTROLS... 3 S1LBC30CF901 Steam Flow To Feed Water Tank... 3 S1LBC30CF201 Steam Flow To Feed Water Tank... 3 S1LBC30CP201 Steam Pressure To Feed Water Tank... 3 S1LBC30CT201 Steam Temperature To Feed Water Tank... 4 S1LBD20CF201 Auxiliary steam flow... 4 S1LBD20CF901 Auxiliary steam flow, calc S1LBG01CP201 Aux. steam header pressure... 5 S1LBG01CT201 Aux. steam header temperature... 5 S1LBG40CT201 Auxiliary steam temp S1LBG40CT202 Auxiliary steam temp S1MAW11CT201 T/G sealing steam temperature MOTORS AND SHUT-OFF VALVES... 6 S1LAF40AA101 Auxiliary Steam Spray Water Shut-off Valve... 6 S1LBC30AA101 Feed Water Tank Steam Line Shut-off Valve... 7 S1LBC40AA101 The Auxiliary Steam Red Station Shut-off Valve... 8 S1LBD10AA101 Shut off Valve for Extraction 4 Steam to Feed Water Tank... 8 S1LBD20AA101 Shut off Valve for Extraction 4 Steam to Auxiliary Steam Header... 9 S1LBG10AA101 Extraction 3 Steam Shut-off Valve to Air Preheaters... 9 S1LBG45AA101 Extraction 3 Steam Shut-off Valve to Auxiliary Steam Header S1LBG50AA101 Auxiliary Steam Header Shut off Valve

3 Document Code: 3 (11) INSTRUMENT LOOPS & CLOSED LOOP CONTROLS S1LBC30CF901 Steam Flow To Feed Water Tank Function Alarms Indicates steam flow corrected with pressure and temperature to the feed water tank. The correction measurements are S1LBC30CP201 Steam pressure to the feed water tank S1LBC30CT201 Steam temperature to the feed water tank Information to other loops S1LBC30CF201 Steam Flow To Feed Water Tank Function Indicates steam flow to the feed water tank Alarms Information to other loops S1LBC30CF S1LBC30CP201 Steam Pressure To Feed Water Tank Function Indicates steam pressure to the feed water tank Alarms 3

4 Document Code: 4 (11) Information to other loops S1LBC30CF S1LBC30CT201 Steam Temperature To Feed Water Tank Function Indicates steam temperature to the feed water tank Alarms Information to other loops S1LBC30CF S1LBD20CF201 Auxiliary steam flow Function Indicates the auxiliary steam flow from extraction Alarms Information to Other Loops S1LBD20CF901 Auxiliary steam flow, calc Function Alarms Indicates the auxiliary steam flow from extraction 4. Corrected with steam pressure (S1LBG01CP201) and temperature (S1LBG01CT201) 4

5 Document Code: 5 (11) Information to Other Loops S1LBG01CP201 Aux. steam header pressure Function Alarms Indicates the steam pressure in the auxiliary steam header. Pressure is controlled with the auxiliary steam reduction station S1LBC40AA201, when auxiliary steam is taken from the cold reheat line. Pressure > max Pressure < min Information to Other Loops S1LBD20CF901 S1LBG01DP S1LBG01CT201 Aux. steam header temperature Function Alarms Indicates the steam temperature in the auxiliary steam header. Temperature > max Temperature < min Information to Other Loops S1LBD20CF S1LBG40CT201 Auxiliary steam temp Function Indicates the auxiliary steam temperature after auxiliary steam reduction station. Temperature is controlled with auxiliary steam reduction station spray water control valve S1LAF40AA201. 5

6 Document Code: 6 (11) Alarms Temperature > max Information to Other Loops S1LBG40CT202 Auxiliary steam temp Function Indicates the auxiliary steam temperature after auxiliary steam reduction station Alarms Temperature > max Information to Other Loops S1MAW11CT201 T/G sealing steam temperature Function Indicates the auxiliary steam temperature in th steam turbine gland steam line Alarms Temperature < min Information to Other Loops MOTORS AND SHUT-OFF VALVES S1LAF40AA101 Auxiliary Steam Spray Water Shut-off Valve Function The valve opens and closes the spray water line to auxiliary steam reduction station 6

7 Document Code: 7 (11) Interlocking The valve is switched to auto mode when the auxiliary steam temperature controller S1LBG40DT201 is switched to auto mode In auto mode the valve will open, when the auxiliary steam temperature control deviation is more than max In auto mode the valve will close, when the control output of the auxiliary steam temperature controller is zero The valve can be controlled manually from the DCS screen Alarms Information to other loops S1LBG40DT S1LBC30AA101 Feed Water Tank Steam Line Shut-off Valve Function Interlocking The valve opens and closes the steam line to feed water tank The valve is switched to auto mode when the feed water tank pressure controller S1LAA10DP201 is switched to auto mode In auto mode the valve will open, when the FW tank pressure control deviation is more than max In auto mode the valve will close, when the control output of the FW tank pressure controller is zero The valve can be controlled manually from the DCS screen Alarms Information to other loops S1LAA10DP201 7

8 Document Code: 8 (11) S1LBC40AA101 The Auxiliary Steam Red Station Shut-off Valve Function Interlocking Alarms The valve opens and closes the steam line to auxiliary steam reduction station The valve is switched to auto mode when the auxiliary steam pressure controller S1LBG01DP201 is switched to auto mode In auto mode the valve will open, when the auxiliary steam pressure control deviation is more than max In auto mode the valve will close, when the control output of the auxiliary steam pressure controller is zero The valve can be controlled manually from the DCS screen The valve is closed with 2 minutes delay if temperature S1LBG40CT202 > max Information to other loops S1LBG01DP S1LBD10AA101 Shut off Valve for Extraction 4 Steam to Feed Water Tank Function The valve opens and closes the steam line from extraction 4 to feed water tank In auto mode the valve will open, when the extraction 4 steam pressure is more than min 1 In auto mode the valve will close, when the extraction 4 steam pressure is less than min 2 The valve can be controlled manually from the DCS screen Interlocking Alarms 8

9 Document Code: 9 (11) Information to other loops S1LBD20AA101 Shut off Valve for Extraction 4 Steam to Auxiliary Steam Header Function The valve opens and closes the steam line from extraction 4 to auxiliary steam header In auto mode the valve will open, when the extraction 4 steam pressure is more than min 1 In auto mode the valve will close, when the extraction 4 steam pressure is less than min 2 The valve can be controlled manually from the DCS screen Interlocking Alarms Information to other loops S1LBG10AA101 Extraction 3 Steam Shut-off Valve to Air Preheaters Function The valve opens and closes the steam line from extraction 3 to primary and secondary air preheaters In auto mode the valve will open if S1LBS10CP201 Extraction 3 steam pressure is more than min In auto mode the valve will close if S1LBS10CP201 Extraction 3 steam pressure is less than min AND S1LBG45AA101 Extraction 3 steam shut off valve to auxiliary steam header is opened The valve is controlled manually from the DCS screen 9

10 Document Code: 10 (11) Interlocking Alarms Information to other loops Opened signal to S1LBG45AA S1LBG45AA101 Extraction 3 Steam Shut-off Valve to Auxiliary Steam Header Function Interlocking The valve opens and closes the steam line from extraction 3 to auxiliary steam header In auto mode the valve will open if S1LBS10CP201 Extraction 3 steam pressure is less than min In auto mode the valve will close if S1LBS10CP201 Extraction 3 steam pressure is more than min AND S1LBG10AA101 Extraction 3 steam shut off valve to air preheaters is opened The valve is controlled manually from the DCS screen Alarms Information to other loops Opened signal to S1LBG10AA S1LBG50AA101 Auxiliary Steam Header Shut off Valve The valve opens and closes the steam line from auxiliary steam header to feed water tank 10

11 Document Code: 11 (11) Interlocking The valve is switched to auto mode when the feed water tank pressure controller S1LAA10DP202 is switched to auto mode In auto mode the valve will open, when the FW tank pressure control deviation is more than max In auto mode the valve will close, when the control output of the FW tank pressure controller is zero The valve can be controlled manually from the DCS screen Alarms Information to other loops S1LAA10DP202 11

Document Code: 1 (8) Issuing date: Status:

Document Code: 1 (8) Issuing date: Status: Document Code: 1 (8) Project : MULTI FUEL CFB BOILER SIMULATOR Author: Approved: Employer: JJA Document title: SYSTEM DESCRIPTION TURBINE CONTROL Submitted for: Employer reference: Other information: Document

More information

ABB PSPG-E7 MODAKOND More efficient and dynamic unit control. ABB Group May 8, 2014 Slide 1 ABB

ABB PSPG-E7 MODAKOND More efficient and dynamic unit control. ABB Group May 8, 2014 Slide 1 ABB ABB PSPG-E7 MODAKOND More efficient and unit control Group May 8, 2014 Slide 1 OPTIMAX MODAKOND Challenge Conventional solution for frequency control (or to improve control performance for flexible plant

More information

Startup and Operation of SEE-THRU Nuclear Power Plant for Student Performance MP-SEE-THRU-01 Rev. 018

Startup and Operation of SEE-THRU Nuclear Power Plant for Student Performance MP-SEE-THRU-01 Rev. 018 Student Operating Procedure Millstone Station Startup and Operation of SEE-THRU Nuclear Power Plant for Student Performance Approval Date: 01/12/2011 Effective Date: 01/12/2011 TABLE OF CONTENTS 1. PURPOSE...3

More information

SEMPELL TURBINE BYPASS VALVE MODEL 115 CHP

SEMPELL TURBINE BYPASS VALVE MODEL 115 CHP A range of high pressure turbine bypass valves that provide greater reliability under extreme conditions. FEATURES Pressure reduction by multi-stage controlled expansion Atomizing steam desuperheater,

More information

Model Temp. Water flow rate at indicated HWT, CWT & WBT ( M 3 /Hr ) HWT o C 33 33 37 33 37 35 34 37 36 35 CWT o C 28 27 32 28 32 30 29 32 31 30 WBT o C 23 23 24 24 25 25 25 26 26 26 FWS-94-3.7 89 67 142

More information

Mitsubishi Hitachi Power Systems America. Coal to Gas Conversions

Mitsubishi Hitachi Power Systems America. Coal to Gas Conversions Mitsubishi Hitachi Power Systems America Coal to Gas Conversions Joe Brown AMS Product Manager 9/28/15 MITSUBISHI HITACHI POWER SYSTEMS AMERICAS, INC. Units Faced with Environmental Challenges Shut Down

More information

First Correlating Revision No. 1-NFPA [ Section No ]

First Correlating Revision No. 1-NFPA [ Section No ] First Correlating Revision No. 1-NFPA 85-2013 [ Section No. 3.3.52.1 ] 3.3.52.1 Booster Fan. A device fan used to assist in the supply of air to, or the removal of flue gas products from, the combustion

More information

Designed to provide maximum service life with minimum maintenance.

Designed to provide maximum service life with minimum maintenance. Designed to provide maximum service life with minimum maintenance. Fastest In-Line Repair Repairable in-line more easily and at less cost than any other valve. Stem, disc, and packing can be quickly removed

More information

PREHEATER BYPASS SYSTEMS

PREHEATER BYPASS SYSTEMS PREHEATER BYPASS SYSTEMS PREHEATER BYPASS SYSTEMS OVERVIEW 2014 GS FEED WATER HEATER BYPASS SYSTEM General Description These valves are designed to bypass high pressure feed water around the pre-heaters

More information

Sturdy Truck Body Poultry Shipping Truck - Operations Manual August 2003

Sturdy Truck Body Poultry Shipping Truck - Operations Manual August 2003 1.0 Introduction The Sturdy ventilation controller is designed to automatically control indoor air quality including: temperature, relative humidity, carbon dioxide and oxygen in the interior of the vehicle

More information

Possible Change of Ship Design Including Engine Room about Emissions of NOx and SOx

Possible Change of Ship Design Including Engine Room about Emissions of NOx and SOx Possible Change of Ship Design Including Engine Room about Emissions of NOx and SOx Masaki Ohtsu Mitsui Engineering & Shipbuilding Co., Ltd. February 28, 2007 Introduction of Mitsui -3 rd position in production

More information

AP1000 European 7. Instrumentation and Controls Design Control Document

AP1000 European 7. Instrumentation and Controls Design Control Document 7.3 Engineered Safety Features AP1000 provides instrumentation and controls to sense accident situations and initiate engineered safety features (ESF). The occurrence of a limiting fault, such as a loss

More information

AQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start)

AQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start) AQUASTAR C6 (Comfort 6000) Next Generation Auto Backwash Valve System (selectable time-pressure or remote cycle start) SIDE MOUNTED AND TOP MOUNTED VALVES WITH QUICK INSTALL ELECTRIC ACTUATORS FOR PIPE

More information

FIREPAK-E21 & FIREPAK-ED21

FIREPAK-E21 & FIREPAK-ED21 FIREPAK-E21 & FIREPAK-ED21 Fire Pumps Set Designation of FIREPAK - E 2 1-120 / 80 - WTM 80-250 / 55 + DJ MV FIREPAK: Package Type E: All pumps in the set electric driven 2: No. main pumps 1: no. jockey

More information

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS PCT plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS Ver. DESCRIPTION The PCT plus is a pressure controller for refrigeration plants that require control in their suction and discharge stages. With

More information

For Sale: Used Steam Turbine Generator Sets. Offer Ref. STG MW Steam Turbine Genset Condensing-Extraction type

For Sale: Used Steam Turbine Generator Sets. Offer Ref. STG MW Steam Turbine Genset Condensing-Extraction type Sonnenberger Str.16 Tel. +49 (0) 611-701888 www.lohrmann.com 65193 Wiesbaden - Germany Fax +49 (0) 611-701895 info@lohrmann.com For Sale: Used Steam Turbine Generator Sets Offer Ref. STG - 25.02 10 MW

More information

Power Generation Flexibilisation Case Studies from Germany. By Ronald Rost & Arun Kumar Sarna

Power Generation Flexibilisation Case Studies from Germany. By Ronald Rost & Arun Kumar Sarna Power Generation Flexibilisation Case Studies from Germany By Ronald Rost & Arun Kumar Sarna Agenda About VPC & Encotec Moorburg Flexibilisation flexgen Jaenschwalde 2 VPC GmbH Flexibilisation case studies

More information

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL SO TOUGH, WE GUARANTEE IT. SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL SBH SBV www.superiorrex.com SO TOUGH, WE GUARANTEE IT! www.superiorrex.com SBH / SBV Series: CONSTRUCTION FEATURES

More information

Mitsubishi Auxiliary Boiler : MAC-B

Mitsubishi Auxiliary Boiler : MAC-B Mitsubishi Auxiliary Boiler : MAC-B Meaning of MAC-B M : Mitsubishi A : Auxiliary C : Compact B : Type December, 2007 History of Mitsubishi Marine Boiler -More than 120 years history *1885 : The first

More information

YARWAY NARVIK MODEL 33/43 STANDARD DUTY QUE-TEMP DESUPERHEATER

YARWAY NARVIK MODEL 33/43 STANDARD DUTY QUE-TEMP DESUPERHEATER Yarway covers requirements for desuperheaters, pneumatic actuators, strainers with a wide range of models, sizes and materials to satisfy all the specifications of the power-pulp and paper industry and

More information

B. Sc., Mechanical power science Engineering, May 1987, Monofia University. - Construction Safety Health 30 hours Administration Training by (OSHA).

B. Sc., Mechanical power science Engineering, May 1987, Monofia University. - Construction Safety Health 30 hours Administration Training by (OSHA). PM-SOM-E-0137-1987 Mechanical Commissioning Manager He is an expert in fossil fuel power generating plants operation and commissioning. He has 23 years of experience in this field (in Egypt, KSA, Syria

More information

Dash8-200/300 - Auxiliary Power Unit APU CONTROLS AND INDICATORS. Page 1

Dash8-200/300 - Auxiliary Power Unit APU CONTROLS AND INDICATORS. Page 1 APU CONTROLS AND INDICATORS Page 1 APU control and indicators Page 2 closed APU controls and indicators Page 3 SYSTEM DESCRIPTION General The auxiliary power unit (APU) is a gas turbine engine, located

More information

Introduction. APU Location

Introduction. APU Location B737 NG APU Introduction The auxiliary power unit (APU) is a self contained gas turbine engine installed within a fireproof compartment located in the tail of the airplane. The APU supplies bleed air for

More information

Standard Duty Que - Temp Desuperheater Model: 33 / 43

Standard Duty Que - Temp Desuperheater Model: 33 / 43 Model: 33 / 43 Narvik-Yarway covers requirements for desuperheaters, pneumatic actuators, strainers with a wide range of models, sizes and materials to satisfy all the specifications of the power-pulp

More information

Sub title. PR series (Toggle type) Servo Hybrid system

Sub title. PR series (Toggle type) Servo Hybrid system Sub title PR series (Toggle type) Servo Hybrid system PR Series Feature Improved reproducibility and handling by excellent position sensor of mold close/open Outstanding injection molding for thin and

More information

Generator Controller Manual

Generator Controller Manual Generator Controller Manual Web Site:http://www.monicon.com.tw E-mail:sales@monicon.com.tw 1. Controller Description is low cost but multi-function diesel engine generator controller. It applies with 3

More information

ICX-CMOS-S-2004 Senior I&C Technician PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS

ICX-CMOS-S-2004 Senior I&C Technician PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS 102068-ICX-CMOS-S-2004 Senior I&C Technician Holds an Industrial Diploma and has about 14 years hands-on experience working as I&C Technician at several Power Plants and other industrial projects. PERSONAL

More information

MIB 303 AC Separation System, Module. System Reference. Product No Aug V1. Printed Book No. Alfa Laval Marine & Power

MIB 303 AC Separation System, Module. System Reference. Product No Aug V1. Printed Book No. Alfa Laval Marine & Power MIB 303 AC Separation System, Module System Reference Product No. 1765785-80 Printed Book No. Aug 1997 1810598-02 V1 Alfa Laval Marine & Power Alfa Laval reserve the right to make changes at any time without

More information

Sempell controlled non-return or Bled Steam Check Valves prevent unallowable pressure built up in the turbine coming due to back-flowing steam.

Sempell controlled non-return or Bled Steam Check Valves prevent unallowable pressure built up in the turbine coming due to back-flowing steam. Sempell controlled non-return or Bled Steam Check Valves prevent unallowable pressure built up in the turbine coming due to back-flowing steam. Features and Benefits Special advantages of the valve series

More information

MERS. MERS Presentation MITSUBISHI ENERGY RECOVERY SYSTEM FOR MOTOR VESSELS. Feb., Engineering Dept., Marine Machinery Div.

MERS. MERS Presentation MITSUBISHI ENERGY RECOVERY SYSTEM FOR MOTOR VESSELS. Feb., Engineering Dept., Marine Machinery Div. MERS Presentation MERS MITSUBISHI ENERGY RECOVERY SYSTEM FOR MOTOR VESSELS Feb., 2014 Engineering Dept., Marine Machinery Div. Contents 1. Type of MERS 2. Feature 3. Economical Evaluation 4. History &

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Acceptance Inspection Date of Review / / BLD20 - Project Address: Project Name: Numbers following worksheet comments represent an NFPA

More information

Power Generation Services Solutions for challenging Markets

Power Generation Services Solutions for challenging Markets Power Generation Services Solutions for challenging Markets Philipp Leifeld, GT Service Engineering / Dirk Kampe Marketing GT Modernizations & Upgrades Matthias Migl, Principal Key Expert Overall Plant

More information

Instruction Manual. Q Series 2 Motor Control Modules - OEM

Instruction Manual. Q Series 2 Motor Control Modules - OEM A382-21-880 Issue B Instruction Manual Q Series 2 Motor Control Modules - OEM Pump/ Q Motor Control Module Item Number pumping system Electrical supply 24 V d.c. control 24 V a.c. control QDP40 200-230

More information

Combustion Control Problem Solution Combustion Process

Combustion Control Problem Solution Combustion Process Combustion Control Problem Until recent years, only the largest boilers could justify sophisticated combustion controls. Now, higher fuel costs and occasionally limited fuel availability make it necessary

More information

FIREWATER PUMPS WEEKLY INSPECTION & TEST

FIREWATER PUMPS WEEKLY INSPECTION & TEST Effective 08/06/10 Page 1 of 11 Rev: 07/30/2010 FIREWATER PUMPS WEEKLY INSPECTION & TEST SAFETY INSTRUCTIONS AND PROCEDURES Document Revision Change Table Revision Number Revision Description Revised By

More information

Control Pacs. Position Controlled Power Actuator (Westinghouse) Control Pac is short for Position-Controlled

Control Pacs. Position Controlled Power Actuator (Westinghouse) Control Pac is short for Position-Controlled Control Pacs Position Controlled Power Actuator (Westinghouse) Control Pac is short for Position-Controlled Power Actuator. The position controlled power actuator provides the power to open and close the

More information

Aeroflow SCV Steam Control Steam Conditioning Turbine Bypass Valve

Aeroflow SCV Steam Control Steam Conditioning Turbine Bypass Valve Aeroflow SCV Steam Control Steam Conditioning Turbine Bypass Valve High Performance in a Competitive Package ZERO Leak Technology Non-Binding Trim Design Quick, Easy Maintenance 5/1 Version 3 Product Information

More information

Heavy Duty Que - Temp Desuperheater Model: 13 / 23

Heavy Duty Que - Temp Desuperheater Model: 13 / 23 Narvik covers requirements for Desuperheaters, pneumatic actuators, strainers with a wide range of models, sizes and materials to satisfy all the specifications of the power, pulp & paper industry and

More information

Q&A FOR Webinar on Electrical Basics & Boiler Wiring

Q&A FOR Webinar on Electrical Basics & Boiler Wiring Q&A FOR Webinar on Electrical Basics & Boiler Wiring 4-20-16 Q: Is a dual fuel burner flame guard system more complicated than the one you showed us today? A: Not really. If the boiler is equipped for

More information

DATA FOR AUTOMATIC AND REMOTE CONTROL OF MACHINERY SYSTEM

DATA FOR AUTOMATIC AND REMOTE CONTROL OF MACHINERY SYSTEM DATA-DF(2004.6) SHIPBUILDER: HULL NO.: DATA FOR AUTOMATIC AND REMOTE CONTROL OF MACHINERY SYSTEM Diesel Ship NIPPON KAIJI KYOKAI Summary of Description 1. If the ships are designed in accordance with description

More information

AUE-AUD-AU2E AU2D-AUED

AUE-AUD-AU2E AU2D-AUED AUE-AUD-AU2E AU2D-AUED EN12845 Fire Pump Stations Designation of AUE 120 / 100 - N 80-250/75 + DJ MV 708 AUE: One electric main pump + jockey 120: Rated Flow (m 3 /h) 100: Rated Pressure (Hm) N 80-250/75:

More information

MSC Guidelines for Fired Thermal Fluid Heaters Procedure Number: E1-28 Revision Date: 06/11/2014

MSC Guidelines for Fired Thermal Fluid Heaters Procedure Number: E1-28 Revision Date: 06/11/2014 References P. W. Gooding, Chief of Engineering Division a. 46 CFR Part 52 Power Boilers b. 46 CFR Part 54 Pressure Vessels c. 46 CFR Part 63 Automatic Auxiliary Boilers Contact Information If you have

More information

Sempell Dewrance Check valves Bled steam

Sempell Dewrance Check valves Bled steam Features General application The Dewrance bled steam check valve has been designed specifically for use on power generation steam turbines for extraction and cold reheat applications where reliable non-return

More information

Submittal 30 [762] 36 [914] 40 [1016] 50 [1270] 60 [1524] 70 [1778]

Submittal 30 [762] 36 [914] 40 [1016] 50 [1270] 60 [1524] 70 [1778] FCU-THBP-1.0 08-22-18 THBP Horizontal Low Profile Plenum Return Top View (Drain Pan Omitted) Bottom View Front View Left hand unit shown. All dimensions are inches [millimeters]. Side View Unit Size A

More information

Local Union No International Brotherhood of Electrical Workers, AFL-CIO P. O. Box 4790 Walnut Creek, California 94596

Local Union No International Brotherhood of Electrical Workers, AFL-CIO P. O. Box 4790 Walnut Creek, California 94596 Local Union No. 1245 International Brotherhood of Electrical Workers, AFL-CIO P. O. Box 4790 Walnut Creek, California 94596 Company proposes adoption of the attached three versions of the revised Assistant

More information

Typical Feed Water Heater Isolation System.

Typical Feed Water Heater Isolation System. Type AVS 4/5 Typical Feed Water Heater Isolation System. Features and Benefits These valves are designed to bypass high pressure feedwater around a group of heaters in the event of high water level in

More information

Experiences with the improvement of minimum load in coal fired power stations. Manfred Schesack

Experiences with the improvement of minimum load in coal fired power stations. Manfred Schesack Experiences with the improvement of minimum load in coal fired power stations Manfred Schesack Outline 1 2 STEAG Minimum load reduction 3 Frequency control 4 Roadmap 2017-12-01 Improvement of flexibility

More information

Non-Return Valves - Type 801 ASME SEMPELL

Non-Return Valves - Type 801 ASME SEMPELL SEMPELL Sempell controlled and uncontrolled Non-Return or Swing Check Valves prevent unallowable pressure built up in the turbine coming due to back-flowing steam. Features and Benefits low maintenance

More information

Standard Duty SLN - Temp Desuperheater Model: 50 / 60

Standard Duty SLN - Temp Desuperheater Model: 50 / 60 Narvik-Yarway covers requirements for Desuperheaters, pneumatic actuators, strainers with a wide range of models, sizes and materials to satisfy all the specifications of the power-pulp & paper industry

More information

Heat Tracing Sales Mt. Airy, Maryland Controls

Heat Tracing Sales Mt. Airy, Maryland Controls Heat Tracing Line Sensing Control Panels Solid State Relay Output Rated 30 Amps or Two-Pole Contactor Control Output Universal Inputs NEMA 4/4X Enclosure Ground Fault Alarm/Trip Monitor or GFI Circuit

More information

HGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL

HGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL HGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD. Chinese trademark English trademark SmartGen make your generator smart SmartGen Technology Co.,

More information

HRSG Operational Challenges and Siemens Solutions

HRSG Operational Challenges and Siemens Solutions Intelligent Energy Solutions HRSG Operational Challenges and Siemens Solutions Gary Gong Ph.D P.E. Siemens Energy Inc 4400 N Alafaya Trl Orlando, FL 32766 Siemens Energy, Inc. Siemens 2010. All Energy,

More information

CM7200 Option Tables and Programming Instructions Firmware: v3.03

CM7200 Option Tables and Programming Instructions Firmware: v3.03 CM7200 Tables and ming Instructions Firmware: v3.03 If you are new to installing Firstech Series Remote s and/or Alarms, we recommended that you thoroughly review this manual to installing your first unit.

More information

Please note this is a condensed catalog. For a complete version, contact Velan directly.

Please note this is a condensed catalog. For a complete version, contact Velan directly. Please note this is a condensed catalog. For a complete version, contact Velan directly. VELAN VALVES IN POWER With an installed base covering over 300 nuclear power plants and over 2,000 thermal power

More information

CM7000 Option Tables and Programming Instructions Firmware: v3.03

CM7000 Option Tables and Programming Instructions Firmware: v3.03 CM7000 Tables and ming Instructions Firmware: v3.03 If you are new to installing Firstech Series Remote s and/or Alarms, we recommended that you thoroughly review the full manual before installing your

More information

NARVIK-YARWAY. Heavy Duty A.T. - Temp Desuperheater Model: 18/54 and 28/64

NARVIK-YARWAY. Heavy Duty A.T. - Temp Desuperheater Model: 18/54 and 28/64 NARVIK-YARWAY Narvik-Yarway covers requirements for Desuperheaters, pneumatic actuators, strainers with a wide range of models, sizes and materials to satisfy all the specifications of the power-pulp &

More information

ECO3-601/602 EcoStar III * Chevy Express/GMC Savana Contact Intermotive for additional vehicle applications

ECO3-601/602 EcoStar III * Chevy Express/GMC Savana Contact Intermotive for additional vehicle applications An ISO 9001:2015 Registered Company ECO3-601/602 EcoStar III 2009-2019* Chevy Express/GMC Savana Contact Intermotive for additional vehicle applications * In 2017-2018, the ignition switches on Chevy Express

More information

YARWAY NARVIK STANDARD DUTY A.T.-TEMP DESUPERHEATER MODEL 38/48

YARWAY NARVIK STANDARD DUTY A.T.-TEMP DESUPERHEATER MODEL 38/48 Yarway covers requirements for Desuperheaters, pneumatic actuators, strainers with a wide range of models, sizes and materials to satisfy all the specifications of the power-pulp and paper industry and

More information

3VF3 to 3VF8 Circuit-Breakers

3VF3 to 3VF8 Circuit-Breakers 3VF3 to 3VF8 Circuit-Breakers Accessories Operating mechanisms For other s for 3VF3 with knob Rotary drive, complete, scope of supply Cubicle door for 3VF6 Motor operating mechanism for 3VF3 Motor operating

More information

Standard Duty A.T.S.A. - Temp Desuperheater Model 24 / 34

Standard Duty A.T.S.A. - Temp Desuperheater Model 24 / 34 Narvik-Yarway covers requirements for desuperheaters, pneumatic actuators, strainers with a wide range of models, sizes and materials to satisfy all the specifications of the power, pulp & paper industry

More information

DETECTION & RECTIFICATION OF TURBINE BALANCE DRUM LABYRINTH SEAL FAILURE OF TDBFP: A CASE STUDY

DETECTION & RECTIFICATION OF TURBINE BALANCE DRUM LABYRINTH SEAL FAILURE OF TDBFP: A CASE STUDY DETECTION & RECTIFICATION OF TURBINE BALANCE DRUM LABYRINTH SEAL FAILURE OF TDBFP: A CASE STUDY P r e s e n t e d b y U j j w a l S a r k a r, S u p d t ( O & M / T M D ) S a n a t a n P a l, S u p d t

More information

Two shift operation power plants. Stop valves. Body materials

Two shift operation power plants. Stop valves. Body materials Two shift operation power plants Power stations that were originally designed for base load applications are now increasingly being asked to operate on a two shift, stop/start regime; this is more commonly

More information

(770) Turning Parts Changers Into TROUBLESHOOTERS!

(770) Turning Parts Changers Into TROUBLESHOOTERS! Hydraulic Consulting, Inc. Turning Parts Changers Into TROUBLESHOOTERS! This e-book manual is your customized troubleshooting manual in Adobe Acrobat Portable Document File (PDF) format. It requires the

More information

SOAPP-CT.25 WorkStation 11/1/00. Equipment List Project: Sample Outputs Conceptual Design: Cogen, 1 x 27 MW, NG, Quarterly

SOAPP-CT.25 WorkStation 11/1/00. Equipment List Project: Sample Outputs Conceptual Design: Cogen, 1 x 27 MW, NG, Quarterly GENERAL PROJECT DATA Ambient Conditions Maximum Site Ambient Dry Bulb Temp 85.00 F Maximum Site Ambient Wet Bulb Temp 74.00 F Minimum Site Ambient Dry Bulb Temp -20.00 F Site Average Annual Rainfall 31.00

More information

FN Fan-Coil Units High-Performance, Horizontal

FN Fan-Coil Units High-Performance, Horizontal FN Fan-Coil Units High-Performance, Horizontal Model FNX Exposed-Cabinet Dimensional Data Notes: 1. All dimensions are in inches [mm] and are +/- 1/8" [3 mm]. Metric values are soft conversions. 2. See

More information

USER MANUAL ZHENGZHOU SMARTGEN TECHNOLOGY CO.,LTD

USER MANUAL ZHENGZHOU SMARTGEN TECHNOLOGY CO.,LTD HGM400 Series Genset Controller (HGM410/HGM420) USER MANUAL ZHENGZHOU SMARTGEN TECHNOLOGY CO.,LTD CONTENTS 1 OVERVIEW... 5 2 PERFORMANCE AND CHARACTERISTICS... 6 3 SPECIFICATION... 8 4 OPERATION... 9 4.1

More information

Section 3 Technical Information

Section 3 Technical Information Section 3 Technical Information In this Module: Engine identification Modes of operation Battery charging and heat manage operation Service and repair procedures Maintenance requirements Engine Identification

More information

FEED WATER REGULATOR EVM-1F FOR CONTINUOS REGULATION

FEED WATER REGULATOR EVM-1F FOR CONTINUOS REGULATION 1. Feed water regulator type EVM 1 F 2. Electrode stand type C DN 50 100 / PN 16 100 with 2 electrodes type ENT 120. 3. Control range 15 mm. 4. HORA Feed water regulating valve with electric actuator.

More information

TES (Thermo Efficiency System)

TES (Thermo Efficiency System) TES (Thermo Efficiency System) Theoretical background Confirmation of potential Application possibilities Future application possibilities Turbocharging Efficiency Turbocharger/Turbocharging efficiency

More information

THYRISTORS T2-2PH from 45A to 2700A Specifications Universal 2 Phase Thyristor Unit , March 2012

THYRISTORS T2-2PH from 45A to 2700A Specifications Universal 2 Phase Thyristor Unit , March 2012 Technical Information THYRISTORS T-PH from 5A to 700A Specifications Universal Phase Thyristor Unit 55-77-03-63, March 0 GENERAL DESCRIPTION THYRISTORS T-PH is a full digital and universal Thyristor unit

More information

Proposed New ISO Rules Section Version 2.0 Generating Unit Technical Requirements ( New ISO Rules Section Version 2.

Proposed New ISO Rules Section Version 2.0 Generating Unit Technical Requirements ( New ISO Rules Section Version 2. Stakeholder Comment and Rationale Form AESO AUTHORITATIVE DOCUMENT PROCESS Stakeholder Consultation Draft 2012-11-29 Proposed New ISO Rules Section 502.5 Version 2.0 Generating Unit Technical Requirements

More information

VELOCITY CONTROL TECHNOLOGY DESUPERHEATERS

VELOCITY CONTROL TECHNOLOGY DESUPERHEATERS VELOCITY CONTROL TECHNOLOGY DESUPERHEATERS D Series 1 KOSO offers an adequate variety of desuperheating solutions. Most importantly, KOSO has the knowhow to help select the right solution using software

More information

Diagnostic Trouble Codes (continued) SAE Defined Codes

Diagnostic Trouble Codes (continued) SAE Defined Codes 78 SAE Defined Codes P01XX Fuel and Air Metering P0100 Mass or Volume Airflow Circuit Problem P0101 Mass or Volume Airflow Circuit Range or Performance Problem P0102 Mass or Volume Airflow Circuit Low

More information

FIS Low Pressure Leak Test March Publication Number / Title Platform Section Title Change. FIS Low Pressure Leak Test- Three-Filter Fuel System

FIS Low Pressure Leak Test March Publication Number / Title Platform Section Title Change. FIS Low Pressure Leak Test- Three-Filter Fuel System 1 3 02-13 SUBJECT DATE FIS Low Pressure Leak Test March 2013 Additions, Revisions, or Updates Publication Number / Title Platform Section Title Change DDC-SVC-MAN-0084 DD Platform FIS Low Pressure Leak

More information

1 Name any 5stationary parts and moving partsof a large 2-stroke diesel engine?

1 Name any 5stationary parts and moving partsof a large 2-stroke diesel engine? 2 Marks question Bank for ME 802 General & Motor 1 Name any 5stationary parts and moving partsof a large 2-stroke diesel engine? 2 Why in certain engine the bottom half of crosshead bearing is of single

More information

Yarway Narvik Desuperheater Model 18/54 and 28/64 Heavy Duty

Yarway Narvik Desuperheater Model 18/54 and 28/64 Heavy Duty Yarway covers requirements for Desuperheaters, pneumatic actuators, strainers with a wide of models, sizes and materials to satisfy the specifications of the power, pulp and paper industries along with

More information

SMT-150 Installer Manual

SMT-150 Installer Manual SMT-150 Installer Manual 3 Stage Digital HVAC Controller Version 1.0 Version History January 2019 Version 1 - Original Document Thank you for your purchase of this premier product. Please take the time

More information

DKG-114 MANUAL AND REMOTE START UNIT

DKG-114 MANUAL AND REMOTE START UNIT DKG-114 MANUAL AND REMOTE START UNIT FEATURES Both manual and remote controlled engine starting and stopping, Automatic shutdown on fault condition, Optional cooldown cycle on remote start operation, Optional

More information

ELECTRIC POWER RESEARCH INSITUTE (EPRI) 2011 CONDENSER TECHNOLOGY CONFERENCE AUGUST 3-4, 2011, CHICAGO, ILLINOIS

ELECTRIC POWER RESEARCH INSITUTE (EPRI) 2011 CONDENSER TECHNOLOGY CONFERENCE AUGUST 3-4, 2011, CHICAGO, ILLINOIS ELECTRIC POWER RESEARCH INSITUTE (EPRI) 2011 CONDENSER TECHNOLOGY CONFERENCE AUGUST 3-4, 2011, CHICAGO, ILLINOIS IMPORTANCE OF TEMPERATURE OF BYPASS STEAM ADMITTED INTO A STEAM SURFACE CONDENSER IN A COMBINED

More information

Model H30 Operation Manual

Model H30 Operation Manual Model H30 Operation Manual Model H30 Version 1.0 August 1, 2007 2 135 West Davenport Street Rhinelander WI 54501 Phone: 866.441.7997 Fax: 866.278.0036 info@houstonst.com www.houstonst.com 3 Table of Contents

More information

CHAPTER 10 STEAM CATAPULTS General

CHAPTER 10 STEAM CATAPULTS General CHAPTER 10 STEAM CATAPULTS 10.1 General The purpose of the steam catapult is to provide a means to safely launch aircraft from carrier decks, day or night, in almost any kind of weather. The steam catapult

More information

PORTISHEAD B POWER STATION

PORTISHEAD B POWER STATION PORTISHEAD B POWER STATION Portishead B Statistics: Main Building (General) Overall length: 704 ft. Overall width: 186 ft. Height above ground: 138 ft. (boiler house) Height above ground: 80 ft. (turbine

More information

MHI-MME WHRS - STG. Environment friendly and economical solution MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.

MHI-MME WHRS - STG. Environment friendly and economical solution MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved. MHI-MME WHRS - STG Environment friendly and economical solution 2017.01.24 2016 MITSUBISHI HEAVY INDUSTRIES MARINE MACHINERY & ENGINE CO., LTD. All Rights Reserved. 1 Contents Overview 1. Outline, WHRS-STG

More information

3VU13, 3VU16 Circuit-Breakers

3VU13, 3VU16 Circuit-Breakers 3VU3, 3VU6 Circuit-Breakers Description The 3VU3, 3VU6 circuit-breakers are compact circuit-breakers for currents up to 80 A which operate according to the current limiting principle. The devices are used

More information

MSC Guidelines for Fired Thermal Fluid Heaters Procedure Number: E1-28 Revision Date: April 20, 2018

MSC Guidelines for Fired Thermal Fluid Heaters Procedure Number: E1-28 Revision Date: April 20, 2018 References C. J. Robuck, LCDR, Chief, Engineering Division a. 46 CFR Part 52 Power Boilers b. 46 CFR Part 54 Pressure Vessels c. 46 CFR Part 63 Automatic Auxiliary Boilers Contact Information If you have

More information

Electric Resistance Boilers Steam or Hot Water

Electric Resistance Boilers Steam or Hot Water Electric Resistance Boilers Steam or Hot Water CONTENTS FEATURES AND BENEFITS...................................................... 3 PRODUCT OFFERING..........................................................

More information

Evaluating Generation Considering All Plant Losses and Efficiencies Duane H. Morris, P.E. Tennessee Valley Authority

Evaluating Generation Considering All Plant Losses and Efficiencies Duane H. Morris, P.E. Tennessee Valley Authority Evaluating Generation Considering All Plant Losses and Efficiencies Duane H. Morris, P.E. Tennessee Valley Authority James W. Brower Scientech a business unit of Curtiss-Wright Flow Control Company Evaluating

More information

SLUG CONTROL PLAN. Section A - Spills from Water-Using Process Areas

SLUG CONTROL PLAN. Section A - Spills from Water-Using Process Areas SLUG CONTROL PLAN Company Name Address Telephone Number Fax Number In order to assist the applicant in determining what facilities are needed to install and to prepare the description of spill prevention

More information

MGL Avionics EFIS G2 and iefis

MGL Avionics EFIS G2 and iefis MGL Avionics EFIS G2 and iefis Guide to using the MGL RDAC CAN interface with the LAD AERO Injection Kit on ROTAX 912-912S General... 3 Data connections... 3 LAD AERO ROTAX 912 engine data from ECU...

More information

D-Series. Simple Design Simple Opera on Simple Maintenance ALL-PURPOSE BALANCED CAGE-GUIDED CONTROL VALVES ANSI CLASS TO 16 (50MM TO 400MM)

D-Series. Simple Design Simple Opera on Simple Maintenance ALL-PURPOSE BALANCED CAGE-GUIDED CONTROL VALVES ANSI CLASS TO 16 (50MM TO 400MM) 10/7.5.4B ALL-PURPOSE BALANCED CAGE-GUIDED CONTROL VALVES ANSI CLASS 150-1500 2 TO 16 (50MM TO 400MM) Simple Design Simple Opera on Simple Maintenance D-Series R u g g e d C a g e G u i d i n g * H a r

More information

YARWAY NARVIK MODEL 60/70 STANDARD DUTY SLN-TEMP DESUPERHEATER

YARWAY NARVIK MODEL 60/70 STANDARD DUTY SLN-TEMP DESUPERHEATER Yarway covers requirements for Desuperheaters, pneumatic actuators, strainers with a wide range of models, sizes and materials to satisfy all the specifications of the power-pulp and paper industry and

More information

ENERGY SAVING INITIATIVES

ENERGY SAVING INITIATIVES ENERGY SAVING INITIATIVES CURRENT STATUS Condensate Extraction Pumps of unit 1 &2 of BBGS MODEL: EN 5J40; MAKE:WEIR PUMPS LIMITED,5 STAGE WITH DOUBLE ENTRY AT FIRST STAGE Motor Make: PEEBLES ELECTRIC LIMITED.6.6KV

More information

Submittal. Front View Side View

Submittal. Front View Side View RBHO Horizontal Low Profile Concealed Free Return Submittal FCU-RBHO-1.0 07-25-18 Top View (Drain Pan Omitted) Bottom View Front View Side View Left hand unit shown. All dimensions are inches [millimeters].

More information

Equipment Specification ARC528E-ICC Arc Spray System

Equipment Specification ARC528E-ICC Arc Spray System Equipment Specification ARC528E-ICC Arc Spray System TYPICAL SYSTEM CONFIGURATIONS Pictured below is a range of typical system configurations. Variations of these configurations may be possible. Contact

More information

SRC. An Outdoor Reset Control for Sub-Atmosphere Steam Systems OUTDOOR TEMPERATURE

SRC. An Outdoor Reset Control for Sub-Atmosphere Steam Systems OUTDOOR TEMPERATURE SRC STEAM RESET CONTROL An Outdoor Reset Control for Sub-Atmosphere Steam Systems Heat-Timer s theory of steam reset heating is as follows: Pulse the valve open to a limited valve position, very slowly

More information

CSP-gas hybrid plants: Cost effective and fully dispatchable integration of CSP into the electricity mix

CSP-gas hybrid plants: Cost effective and fully dispatchable integration of CSP into the electricity mix CSP-gas hybrid plants: Cost effective and fully dispatchable integration of CSP into the electricity mix Erik Zindel Director Marketing CSP (Power Block) Energy Sector Siemens AG 2012 Copyright Siemens

More information

SUB-CHAPTER B.3 COMPARISON TABLE COMPARISON WITH REACTORS OF SIMILAR DESIGN (N4 AND KONVOI)

SUB-CHAPTER B.3 COMPARISON TABLE COMPARISON WITH REACTORS OF SIMILAR DESIGN (N4 AND KONVOI) CHAPTER B: INTRODUCTION AND GENERAL DESCRIPTION OF THE SUB-CHAPTER: B.3 SECTION : - PAGE : 1 / 9 SUB-CHAPTER B.3 COMPARISON TABLE COMPARISON WITH REACTORS OF SIMILAR DESIGN (N4 AND KONVOI) A comparison

More information

Ceramic PTC Thermistor:

Ceramic PTC Thermistor: Motor Starter In starter circuit for single-phase a.c. motor, CPTC thermistor is in series connection with starting winding of motor. When motor starts, initial resistance of CPTC thermistor is low and

More information

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology HGM501 Gen-set Controller USER MANUAL Smartgen Technology Contents 1. 2. 3. 4. 5. 6. 7. 8. 9. OVERVIEW... 4 PERFORMANCE AND CHARACTERISTICS... 4 TECHNICAL DATA... 5 OPERATION... 6 4.1. BUTTON DESCRIPTION...

More information

UNDERGROUND STORAGE TANK INSPECTION CHECKLIST

UNDERGROUND STORAGE TANK INSPECTION CHECKLIST UNDERGROUND STORAGE TANK INSPECTION CHECKLIST Facility Name: Inspector will mail copy of this inspection report to the tank owner at: General Requirements A. Site Administration 1. Submit/revise Facility

More information