1 Q&A FOR Webinar on Electrical Basics & Boiler Wiring Q: Is a dual fuel burner flame guard system more complicated than the one you showed us today? A: Not really. If the boiler is equipped for dual fuel burning, it will have a simple selector switch which puts you in either the gas or oil firing mode. The sequence the BMS follows is then the same, only the devices controlled are different. Q: Single phasing of 3 phase motor destroys motor how can this be prevented? A: Single phasing means one of the phases is open causing increased amperage draw as the motor seeks to reach its full rated capacity or horsepower. Protection for the motor in this situation is through the use of three properly sized overload relays, inherent motor protection, and/or three dual element fuses. Good question! Q: Where are your Electrical BM courses offered? A: Our boiler maintenance courses are offered at your facility with a tailored program, at a CB Rep. sponsored regional site or, at our training facility (The CB Boiler House and R&D Center) in Milwaukee, WI. Q: When does pilot drop out? How long after the main burner is lit? A: The pilot should extinguish right after the main flame is proven by the BMS/Scanner. Q: Are you going to consider a class on controls such as building controls Backnet or direct digital controls, ddc? A: We have had a couple of webinars covering controls, but have not concentrated on those subjects specifically. It s an excellent suggestion, and one we will certainly consider for the future. Thank you!! Q: Is this presentation applicable to Fire tube as well as water tube boiler? A: Absolutely! Q: Is the BMS different than CMS - Combustion Monitoring System? If yes, in what manner? A: The answer is yes. The BMS is the supervisor and sequencer for all of the burner functions from proving initial power at our hot and neutral wiring connections to post purge and shutdown of the burner once the load is satisfied. The CMS, also referred to as the CCS or Combustion Control System, is there to provide other energy and safety functions including full metering of fuel and air, cross limiting, oxygen trim, two or three element feed water control, etc. The BMS and CMS/CCS are separate systems, but functionality is totally integrated.
2 Q: Which system (BMS or CMS) controls Flue Gas Oxygen and Air Emissions? A: The CMS. Q: Are there safety hardwire interlocks around the BMS to avoid failures in the BMS causing high hazard by not closing the safety shut of valves in a gas system? (For example e-stop hard wire to close the SSVs, power failure to the BMS...) A: Yes Q: What dictates if a safety device is manual reset or automatic reset? A: This is controlled by NFPA standards, local codes, customer preference, and Insurance requirements. Q: Is BMS basically a safety system where as CMS is a system that responds to changes to the load? A: Not really. The BMS is totally integrated with the firing rate control also known as the modulating control which is sensing the system pressure or temperature and sending a signal to drive the fuel and air valves open or closed as the system load varies. Q: How many control systems do you typically see your equipment controlled by which are non on board? A: Control systems which are not part of the boiler manufacturer s design and applied to the unit at time of manufacture cannot control the operation of the boiler as it relates to any safety limits and functions. This limits those extraneous controls to (possibly) turning boilers on and off, and monitoring. Q: Can PLC control replace BMS with same functionality? A: Actually, the PLC becomes the electronic platform, and will incorporate the BMS which normally is manufactured by either Honeywell or Fireye. Q: Recently we have purchased a fire tube boiler. Is BMS and CCS fully described in the manuals? A: The manuals you received with the unit should include all the manuals you need with complete detail. If you are lacking anything, please contact your local CB representative who if they can t assist, will call us for help. Your complete satisfaction is our ultimate goal, and thank you for your business! Q: How could damper position affect blower motor amperage? A: As the air damper blade or air metering system begins closing to reduce the amount of combustion air, the static pressure increases; increasing the amperage draw on the motor. This can be largely mitigated through the use of a variable speed drive on the motor. Q: From an experience perspective- As the ability to troubleshoot burner wiring issues, what do you see as the min amount of time (years) before a technician becomes a true expert in burner wiring?
3 A: This is totally dependent on the individual and their innate ability to grasp the theory of electricity and wiring logic. Some people with this ability can attend one class on how that particular equipment is designed and wired, and be safe and productive in a matter of a few weeks (Rare, but it happens). Others of average or below aptitude will struggle a bit, and besides a basic wiring course on electrical theory, and related wiring logic, will need field mentoring and tutoring before they are reliable with the equipment and its electrical issues. I d say this could mean several months of training (class & field) before they are productive, reliable and safe in the field alone. The other variable is system complexity involving both PLC based logic controls working in concert with electromechanical devices. This gets tricky even for the most blest in the area. Here it boils down to training and hands on experience, the timing of which varies based on exposure. Q: What is difference between 240VAC and 230VAC A: Very small difference in EMF (Electromotive Force) which has little impact on the motor its driving. Q: What is the maximum length of wire for a 4-20ma transmitter, using a 3 conductor 22 awg cable? Example header steam pressure transmitter to master panel. A: There are two factors that affect the maximum length. This is the resistance of the shielded instrument cable and the 24VDC power source that is driving the loop. The Belden 3105A, #22 AWG shield cable used by Cleaver- Brooks has a resistance of 14.7 ohms per 1000 feet. Kirchhoff`s second law states the sum of all voltages in a circuit is 0. The master panel PLC analog input module has 250 ohms of resistance, which equates to 20mA (0.02 amps). See example below of analog loop with voltage drops and resistance (ohms) at each major component in the loop. As shown below, the cable length is 3,700 meters which is 12,139 feet. This is an extreme example, but as you can see a 4-20mA signal can be run in a typical boiler room without any concern for exceeding the maximum cable length. It is recommended to use an instrument cable larger than #22 AWG for significant length runs and #18 AWG would be a sized cable to use. When running CAT 5 Ethernet cable, the maximum cable run is 300 feet and if this distance is to be exceeded, then fiber optic cable is required.
4 How does AC current flow to where it needs to go when its traveling in both direction? A: Even though the current flows in both directions at a frequency of 60 cycles per second, as the resistance increases during current flow, you have a potential difference occurring which moves the power along to the place with the least electrons. Isn t voltage really the power in the circuit? A: No, actually voltage is the electromotive force we best describe as pressure. The power is really measured in Watts which is determined by multiplying voltage times amperage which is determined by overcoming one ohm of resistance with a single volt. In our facility we use the terms ground and neutral as meaning the same. Problem? A: Yes, from a safety perspective it is Technically neutral is really a common wire allowing for the flow of current. Ground, is really a safety wire which normally does not have current flow unless there is a short or a floating neutral which might allow current to flow to areas on the equipment where severe shocking could occur. That is why ground is exactly that, a pathway for the current to be safely discharged.
5 In your example with AC power you re going from 10 amps at 4800 volts and wind up at 100 amps at 480 volt. How did you get to 100 amps? A: We re back to Ohm s law which states you calculate amperage by dividing voltage by the resistance. In the case I showed you with 480 volts coming into the facility the resistance was about 5 Ohms. 480/5 =96 Amps. Why can t DC power be transformed? A: It s really kind of complicated, but it gets back to the characteristics of AC power including a varying voltage and current going from let s say zero to 120 and back again 60 times a second. This is a time delay which sets up a magnetic flux which can tie into the transformer producing a higher or lower EMF on its secondary side. This is not possible with DC voltage because of its unidirectional flow characteristics. We have electric actuators on our boiler controlling the fuel and air. Are these AC or DC powered? A: It depends. If you have a system which is primarily electro-mechanical controlled they are most likely AC powered. If on the other hand you have a PLC based platform, then the AC power is most likely converted to DC to power the actuators you refer to. # # #
First Correlating Revision No. 1-NFPA [ Section No ]
First Correlating Revision No. 1-NFPA 85-2013 [ Section No. 3.3.52.1 ] 3.3.52.1 Booster Fan. A device fan used to assist in the supply of air to, or the removal of flue gas products from, the combustion
More informationX4 Installation and Operation Manual - POWER FLAME INCORPORATED
7.13.2 Set the burner s combustion air inlet damper to the approximate setting as shown in this manual for the desired firing rate. Also, verify that the correct main orifice is installed in the main orifice
More informationBCS Modutrol Motor M7484A
BCS 7700 Modutrol Motor M7484A The M7484A is a low voltage, reversing proportional modutrol motor used to drive a fuel valve and combustion air damper as commanded by the BCS 7700. Electronic, vibration
More informationTECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence
The Universal TM gas LowNOx series water heaters contain an electronic spark ignition system. The heater is connected to a 120VAC power source required by the transformer. The transformer steps down the
More informationINSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER
5500 COMBUSTION SAFETY CONTROL INSTALLATION MANUAL FOR 5500 COMBUSTION SAFETY CONTROLLER WARNING This manual must be read in its entirety before installation of this controller. Installation must be performed
More informationContinuing Education Course #206 Introduction to Designing Machine Control Systems Part 2
1 of 5 Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2 1. Continuing to answer the following questions indicates that you understands that the presented material
More informationElectrical Safety. Introduction
Electrical Safety Introduction Electrical hazards 300 electrocutions every year in the U.S. Leading cause is insufficient training ALL were preventable What is Electricity? How Electricity Works Created
More informationInstallation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor
World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com
More informationTIME REQUIREMENT GUIDE (TRG)
CAT SWITCHGEAR TIME REQUIREMENT GUIDE (TRG) This warranty repair time requirement guide is designed to: Provide detailed guidance on troubleshooting Determine possible solutions Guide the technician to
More informationTI23 Pre-Instructional Survey
TI23 Pre-Instructional Survey Name: Date: 1. Identify the balloon contents that represent the relationship between the three electrical measurements as they relate to Ohm s Law. 2. Which of the statements
More informationELECTRICAL. CDTA Technical Training Center
ELECTRICAL ATOMIC STRUCTURE Protons positive charge Electron negative charge Neutron - neutral Electricity is the movement of electrons from atom to atom ELECTRON FLOW CONDUCTOR - Materials which have
More informationAQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start)
AQUASTAR C6 (Comfort 6000) Next Generation Auto Backwash Valve System (selectable time-pressure or remote cycle start) SIDE MOUNTED AND TOP MOUNTED VALVES WITH QUICK INSTALL ELECTRIC ACTUATORS FOR PIPE
More informationHow to use the Multirotor Motor Performance Data Charts
How to use the Multirotor Motor Performance Data Charts Here at Innov8tive Designs, we spend a lot of time testing all of the motors that we sell, and collect a large amount of data with a variety of propellers.
More informationFull file at
CHAPTER 2 FUNDAMENTALS OF ELECTRICITY Job Assignment for This Chapter: You are on a service call and a customer does not understand the basic theory of electricity and thinks you are trying to sell parts
More informationACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS
II 1400-10 ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS Features: Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit Protection Standby Battery
More informationCombustion Control Problem Solution Combustion Process
Combustion Control Problem Until recent years, only the largest boilers could justify sophisticated combustion controls. Now, higher fuel costs and occasionally limited fuel availability make it necessary
More informationTroubleshooting Bosch Proportional Valves
Troubleshooting Bosch Proportional Valves An Informative Webinar Developed by GPM Hydraulic Consulting, Inc. Instructed By Copyright, 2009 GPM Hydraulic Consulting, Inc. TABLE OF CONTENTS Bosch Valves
More informationBuilding Operator Certification Level I
Building Operator Certification Level I A Partnership of the CUNY Institute for Urban Systems Building Performance Lab, the CUNY School of Professional Studies, and the New York State Energy Research &
More informationModulating Furnace Information. Warning on Meter Setting - Read First!
Modulating Furnace Information Pressure Transducer Pressure DC Volts 0.00" 0.25 0.20" 0.63 0.25" 0.72 0.30" 0.82 0.35" 0.91 0.40" 1.00 0.45" 1.09 0.50" 1.19 0.55" 1.28 0.60" 1.38 0.65" 1.47 0.70" 1.56
More informationBASIC ELECTRICAL MEASUREMENTS By David Navone
BASIC ELECTRICAL MEASUREMENTS By David Navone Just about every component designed to operate in an automobile was designed to run on a nominal 12 volts. When this voltage, V, is applied across a resistance,
More informationCSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:
CSDA Best Practice Title: Hi-Cycle Concrete Cutting Equipment Issue No: CSDA-BP-010 : Oct 1, 2010 Revised : Introduction Hi-cycle/high frequency concrete cutting equipment has become more prevalent in
More information100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE
100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE Start-up must be performed by a trained, experienced service person. The following general start-up
More informationG203V / G213V MANUAL STEP MOTOR DRIVE
G203V / G213V MANUAL STEP MOTOR DRIVE PRODUCT DIMENSIONS PHYSICAL AND ELECTRICAL RATINGS Minimum Maximum Units Supply Voltage 18 80 VDC Motor Current 0 7 A Power Dissipation 1 13 W Short Circuit Trip 10
More informationG213V STEP MOTOR DRIVE REV 7: March 25, 2011
Thank you for purchasing the G213V drive. The G213V is part of Geckodrive s new generation of CPLD-based microstep drives. It has short-circuit protection for the motor outputs, over-voltage and under-voltage
More informationHP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control
SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains
More informationElectrical Maintenance
Electrical Maintenance You Will Learn: The installation, operation, maintenance and management of boiler plants The steam and combustion processes Safe boiler operation techniques About pollutants and
More information2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4
CHAPTER ELECTRICAL 2 INSTALLATION Contents of this Chapter... 2.1 Warnings & Agency Approvals..................2 2 2.1.1 Isolation..............................................2 2 2.1.2 Electrical Power
More informationPower Flame Incorporated
Power Flame Incorporated DC-4 SEQUENCE OVERFIRE DRAFT CONTROL SYSTEM OPERATING AND MAINTENANCE MANUAL THE POWER TO MANAGE ENERGY 2001 South 21 st Street, Parsons, Kansas 67357 Telephone 620-421-0480, Fax
More informationData Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931
Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC
More informationXCITE Owner s Manual. Reso-not TM Damping System XCITE 1502C HYDRAULIC POWER SUPPLY
Reso-not TM Damping System XCITE Owner s Manual 1502C HYDRAULIC POWER SUPPLY Xcite Systems Corporation 675 Cincinnati RDS Batavia - 1 Pike Cincinnati, Ohio 45245 Tel: (239) 980-9093 Fax: (239) 985-0074
More informationElectric Circuits. Lab. FCJJ 16 - Solar Hydrogen Science Kit. Goals. Background
Goals Build a complete circuit with a solar panel Power a motor and electrolyzer with a solar panel Measure voltage and amperage in different circuits Background Electricity has fundamentally changed the
More informationSelected excerpts from the book: Lab Scopes: Introductory & Advanced. Steven McAfee
Selected excerpts from the book: Lab Scopes: Introductory & Advanced Steven McAfee 1. 2. 3. 4. 5. 6. Excerpt from Chapter 1 Lab Scopes How do they work? (page 6) Excerpt from Chapter 3 Pattern Recognition
More informationChapter 19: DC Circuits
Chapter 19: DC Circuits EMF and Terminal Voltage Resistors in Series and in Parallel Kirchhoff s Rules EMFs in Series and in Parallel; Charging a Battery Capacitors in Series and in Parallel RC Circuits
More informationXID ENHANCEMENT SYSTEM IMPROVED EFFICIENCY AND PERFORMANCE
IMMERSION FIRED HOT WATER BOILER April 1, 2003 GENERAL DESCRIPTION The Sellers immersion fired hot water boiler is a horizontal, single pass, firetube boiler designed to burn natural gas. The unique burner
More informationCHAPTER 19 DC Circuits Units
CHAPTER 19 DC Circuits Units EMF and Terminal Voltage Resistors in Series and in Parallel Kirchhoff s Rules EMFs in Series and in Parallel; Charging a Battery Circuits Containing Capacitors in Series and
More informationMODEL 422 Submersible Pump Controller
MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and
More informationExplanation 1 Input External Switch 2 Input Hipot Safety Switch
on the 1100H+ The 1100H+ has capability, which allows you to set up the tester to control external devices with tester functions. You can also use an input on the tester to start a test. For example, the
More informationthree different ways, so it is important to be aware of how flow is to be specified
Flow-control valves Flow-control valves include simple s to sophisticated closed-loop electrohydraulic valves that automatically adjust to variations in pressure and temperature. The purpose of flow control
More informationMaxPak Plus Analog DC V S Drive
Three-Phase 3-600 HP non-regenerative and 5-150 HP regenerative drives Designed to accommodate a wide range of industrial requirements, the DC V S Drive has been widely applied worldwide. Selected ratings
More informationDFC-1 STANDARD TEMPERATURE CONTROL. DFC-2 TEMPERATURE CONTROL w/ INTEGRAL 40 F-90 F SELECTOR DFTD TEMPERATURE SELECTION DIAL DFTS TEMPERATURE SENSOR
24 Volt AC input Built in 15 second low fire start timer 0-24 Volt DC modulating output Remote temperature selection Calibration trim pot Rated for -40 F (-40 C) DFC-1 STANDARD TEMPERATURE CONTROL DFC-2
More informationRODIX, INC. FC-40-PLC Plus Series Control Troubleshooting Guide for Circuit Board P/Ns and
RODIX, INC. FC-40-PLC Plus Series Control Troubleshooting Guide for Circuit Board P/Ns 24-488 and 24-489 Control must be connected to a known GOOD LOAD prior to testing Problem: No output from the control
More informationSERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL
SERIES 35-72 120 VAC Microprocessor Based Direct Spark Ignition Control 35.72.03 FEATURES Two Mounting Configurations Open Board With Stand-Off's - saves space and cost Potted - protection for washdown
More informationSuper Calendar. Heated rolls
Application Assistant Surface Winders are used to roll up material such as wire, paper, film, metals and textiles. The surface winding method applies the driving power to a fixed diameter roll or rolls,
More informationTROUBLESHOOTING GUIDE FOR HEAT PUMP BOOSTERS MODELS: HPB11, HPB15, & HPB22
V3 TROUBLESHOOTING GUIDE FOR HEAT PUMP BOOSTERS MODELS: HPB11, HPB15, & HPB22 PREFACE This guide contains instructions for troubleshooting the Steffes Corporation room heating units: Models HPB 11, HPB
More informationENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER
ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE MEMBER GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA 01001-2907, USA LSM672 LOAD SHARING MODULE PRODUCT TECHNICAL INFORMATION PTI 4000 AUGUST
More informationDIESEL Engine Fire Pump Controllers Features
1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status
More informationSuper Calendar. Heated rolls
Application Report Surface Winders are used to roll up material such as wire, paper, film, metals and textiles. The surface winding method applies the driving power to a fixed diameter roll or rolls, on
More informationPhysical Science. Chp 22: Electricity
Physical Science Chp 22: Electricity Yes, we all know what electricity is, but exactly what is it? -where does it come from -can you see it -how is it created Electricity Electricity is a force created
More informationEE30181A DC Electronic Load 300 Watt
EE30181A DC Electronic Load 300 Watt Input Voltage 0 150 Volts DC (Absolute Max 162V) Input Current (adjustable) 10k pot Int./ Ext. 0 80 Amps (Quasi Power Mode / Constant Current are Standard) Optional
More informationARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI
II 1400-6 ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI ACSI 1426-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1092, REV. C INSTALLATION For C-UL Listed applications,
More informationGeneral Purpose Buck - Boost Wiring Diagrams... 86
SECTION LOW VOLTAGE/ LIGHTING TRANSFORMERS General Purpose... 84 Buck - Boost... 85 Wiring Diagrams... 8 LOW VOLTAGE LIGHTING TRANSFORMERS & POWER SUPPLIES Low Voltage Lighting A greater selection for
More informationFACT SHEET Standard: Electrical Safety
What is a Ground Fault Circuit Interrupter? FACT SHEET The ground-fault circuit interrupter, or GFCI, is a fast-acting circuit breaker designed to shut off electric power in the event of a ground-fault
More informationWelcome to the SEI presentation on the basics of electricity
Welcome to the SEI presentation on the basics of electricity 1 Electricity is a secondary energy source, meaning that it is produced from other, primary, energy sources. There are several primary sources
More information1333 (SERIES B & C) TROUBLESHOOTING GUIDE
1333 (SERIES B & C) TROUBLESHOOTING GUIDE Preventive Maintenance: Problems with Your Drive? Bulletin 1333 is convection or fan cooled by air flowing through the heat sink slots. The slots must never be
More informationApplication Information
Moog Components Group manufactures a comprehensive line of brush-type and brushless motors, as well as brushless controllers. The purpose of this document is to provide a guide for the selection and application
More informationAdapted from presentation developed by Scott Fausneaucht
Adapted from presentation developed by Scott Fausneaucht Definition of Electricity Electrical Fundamentals Generation & Transmission Transformers Fuses & Circuit Breakers Motors Motor Controls Safety Not
More informationApplication Engineering
Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor
More informationCM 5000D IN A HURRY?
CM 5000D Conventional and Tunnel Instructions IN A HURRY? Flip to Pages 6-13 for Wiring Diagrams 4-11. Investigate The REEL-FREE Winch Handle The REEL-FREE Winch Handle adds features to your curtain winching
More informationTHE MOTOR/GENERATOR OF ROBERT ADAMS
THE MOTOR/GENERATOR OF ROBERT ADAMS WHEN HE WAS 70 YEARS OLD, ROBERT ADAMS OF NEW ZEALAND DESIGNED A VERY EFFECTIVE MOTOR/GENERATOR. HE WAS TOLD TO DESTROY HIS DEVICE OR HE WOULD BE KILLED. ROBERT DECIDED
More informationCV - 6SL INSTRUCTION MANUAL 6000W POWER SUPPLY
CV - 6SL INSTRUCTION MANUAL 6000W POWER SUPPLY 1 TABLE OF CONTENTS 1.0 Specification 5 2.0 Installation 7 2.1 Rack Mounted 7 2.2 Cooling 7 2.3 Filament Module 8 2.4 Electrical Power Input 8 2.5 Grounds
More informationValcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual
Valcom Failsafe Unit 1620ESv2 SERIES Operation and Maintenance Manual Table of Contents Section Title Page 1. - Introduction.. 2. - Unpacking the Failsafe unit. 3. - Installation 3.1 - Auto / Timed UPS
More informationColeman Air C440-HVM 440 Amp Diversion Controller Version 3.2
Coleman Air C440-HVM 440 Amp Diversion Controller Version 3.2 With Extended Diversion Mode Page 1 Page 2 Introduction This diversion controller is the result of our many attempts to use the controllers
More informationSec 3 TROUBLESHOOTING VARIABLE SPEED DRIVE ASC450 SOFTWARE
Sec 3 Sec 1 Sec 2 Sec 3 Sec 4 Sec 5 Sec 6 Sec 7 Sec 8 Sec 9 Sec 10 OVERVIEW MOUTIG WIRIG PARAMETERS TROUBLESHOOTIG O2 TRIM VARIABLE SED DRIVE MODbus ASC450 SOFTWARE SCIFICATIOS Sec 3 Sec 1 Sec 2 Sec 3
More informationLecture PowerPoints. Chapter 19 Physics: Principles with Applications, 6 th edition Giancoli
Lecture PowerPoints Chapter 19 Physics: Principles with Applications, 6 th edition Giancoli 2005 Pearson Prentice Hall This work is protected by United States copyright laws and is provided solely for
More informationApplication. Tek-Air Systems, Inc. 41 Eagle Road Danbury, CT (203) FAX: (203) SALES FAX: (203)
TEK-AIR TECHNICAL PRODUCT DATA SHEET FVC2600 SASH SENSING VAV FUME HOOD SYSTEM MODEL 2600: Variable volume control based on sash position utilizes microprocessor based electronics and linear air control
More informationElectricity 1
1 Tom Fritts tom@residentialsewage.com 2 Minnesota code?? Why this class?? Troubleshooting Selling the system Know how to calculate usage cost for the homeowner Minimize the surprises You are responsible.
More informationGay E. Canough. OFF-GRID Design. Dr. Gay E. Canough, Master trainer. Living Off the Grid
OFF-GRID Design Dr. Gay E. Canough, Master trainer 1 Understand the Customer s load 2 Load sizing Gay E. Canough AC Appliance watts amps how many of these? number of hours it is used per day equals watt-hr/
More informationVariable Air Volume (VAV) Pressure Independent Control
VAV Terminal Units Asli Variable Air Volume (Vav) Terminal Units are volume flow rate controller for supply air on variable air volume system. These units are designed to control the airflow rate of conditioned
More informationLab # 4 Parallel Circuits
Lab # 4 Parallel Circuits Name(s) Obtain an Electro-Trainer and wire it exactly as shown (Be sure to use the 100 ohm resistor) 1) Record the volt drop and current flow for the Switch, the Resistor and
More informationCenter Winder Specification
Center Winder Specification Bump Roll Edge Guide Photo Eye 2000 Ft/ Min Dancer Arm Center Winder Overview Winding is simply a rotational means to take up and package material for more efficient handling
More informationIs Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics
Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics Synopsis: This paper describes the use of AC power supplies
More informationQ35 Series Automatic Vent Damper System
Installation Sheets Manual 121 Energy Conservation and Miscellaneous Kits Section Q Technical Bulletin Q35 Issue Date 0999 Q35 Series Automatic Vent Damper System Figure 1: Q35 Automatic Vent Damper System
More informationPhysics Work with your neighbor. Ask me for help if you re stuck. Don t hesistate to compare notes with nearby groups.
Physics 9 2016-04-13 Work with your neighbor. Ask me for help if you re stuck. Don t hesistate to compare notes with nearby groups. Today we ll build on what we did Monday with batteries and light bulbs.
More informationProcess switches and PLC circuits
Process switches and PLC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
More informationArt. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2
SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2 DESCRIPTION AND FEATURES... 3 CHARGING STAGES... 4 Art. No. EC-315 Art. No. EC-330 Art. No. EC-340 PROTECTIONS... 5 INSTALLATION...
More informationApplication Engineering
Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the
More informationAbstract. GLV Systems Test Plan 1
GLV Systems Test Plan 1 Abstract This document details the acceptance test plan for the Grounded Low Voltage system being developed for the LFEV design project. This is only a test plan draft, and will
More informationBattery Power Inverters
Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.4 Important Safety Instructions Please save these instructions.
More informationPCS 100 SYSTEM INSTALLATION INSTRUCTIONS
PCS 00 SYSTEM INSTALLATION INSTRUCTIONS PCS - 00 + - POWER 4VDC CW TIME LO NL 4 5 6 ON C&K SDA06 CCW HI RL WHITE BROWN BLACK NC L NC L ON C&K SDA04 4 NO M NO M RESET START 5V 4V COM (0) BLUE SCU-00 Made
More informationAdvantage-D. Operating Instructions and Maintenance Manual. Central Vacuum Systems (Expandable/Modular Models) (Ver.
Advantage-D Series 3 Central Vacuum Systems (Expandable/Modular Models) (Ver. 8/05) Operating Instructions and Maintenance Manual DESCRIPTION The Becker Advantage-D and Advantage-L central vacuum systems
More informationPARTS & SERVICE MANUAL
PARTS & SERVICE MANUAL Impinger Low Profile Advantage Digital Series (Electric) International Models MODELS: Please note that the model numbering system changed March 2007. The chart below shows the old
More informationA.C.E.S. Series ACES 3 & 6 MODULE PANELS. System Manual. Touch-Plate Lighting Controls. ACES 3 & 6 Module System Manual
Touch-Plate Lighting Controls ACES 3 & 6 Module System Manual A.C.E.S. Series ACES 3 & 6 MODULE PANELS System Manual Touch-Plate Lighting Controls 1830 Wayne Trace Fort Wayne, IN 46803 Phone: 260-424-4323
More informationECET Distribution System Protection. Overcurrent Protection
ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Distribution System Protection Overcurrent Protection One of the most important aspects of distribution system design is system protection.
More informationComponents of Hydronic Systems
Valve and Actuator Manual 977 Hydronic System Basics Section Engineering Bulletin H111 Issue Date 0789 Components of Hydronic Systems The performance of a hydronic system depends upon many factors. Because
More informationElectric Drive Vehicle Infrastructure Training. Instructor s Manual. National Alternative Fuels Training Consortium
Electric Drive Vehicle Infrastructure Training Instructor s Manual National Alternative Fuels Training Consortium Part 4: : Service Panel to Receptacle Overview of Service Panel The role of the service
More informationMaintenance Manual 13 AMPERE POWER SUPPLY 19A704647P1-P3. Mobile Communications LBI-31801C
C Mobile Communications 13 AMPERE POWER SUPPLY 19A704647P1-P3 CAUTION THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALI- FIED PERSONNEL ONLY. TO AVOID ELECTRIC SHOCK DO NOT PERFORM ANY SERVICING OTHER
More informationCENTRIFUGAL CHILLER. Lubrication System Pull oil sample for spectroscopic analysis.
CENTRIFUGAL CHILLER Annual Inspection Refrigerant Circuit Check and record refrigerant level Inspect for leak results Calculate refrigerant lass and report to the customer. Repair minor leaks as required
More informationElectrical Systems. Introduction
Electrical Systems Figure 1. Major Components of the Car s Electrical System Introduction Electricity is used in nearly all systems of the automobile (Figure 1). It is much easier to understand what electricity
More informationElectric Motor Controls BOMA Pre-Quiz
Electric Motor Controls BOMA Pre-Quiz Name: 1. How does a U.P.S. (uninterruptable power supply) work? A. AC rectified to DC batteries then inverted to AC B. Batteries generate DC power C. Generator, batteries,
More informationBMS 12/200 for 12,8 Volt lithium iron phosphate batteries Especially designed for vehicles and boats
BMS 12/200 for 12,8 Volt lithium iron phosphate batteries Especially designed for vehicles and boats www.victronenergy.com Why lithium-iron phosphate? Lithium-iron-phosphate (LiFePO4 or LFP) is the safest
More informationPF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016
PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS v1.1 Revised Table of Contents 1 Common Alarms and Warnings... 1 2 Common Issues... 6 2.1 Communication problems... 6 2.1.1 Controller communication
More informationElectrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition)
Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition) 1. Which drawing type shows physical details as seen by the eye? 2. Which drawing is similar to a pictorial drawing but has
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More informationAUTO CHARGE DUAL MODEL #: AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL. Ph: Fax:
INSTRUCTION MANUAL AUTO CHARGE DUAL AUTOMATIC DUAL OUTPUT BATTERY CHARGER MODEL #: 091-145-12 INPUT: 120 Volt, 50/60 Hz, 3.5 Amps OUTPUT BAT 1: 10 Amps OUTPUT BAT 2: 10 Amps File: IM_091-145-12_revb.indd
More informationHEATEC TEC-NOTE. Troubleshooting modulation motors
HEATEC TEC-NOTE Revised 4-24-07 Troubleshooting modulation motors Purpose This document provides a guide for troubleshooting burner modulation motors (Figure 1), which are commonly called mod motors. They
More informationModel No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Model No. DFC-X Support 877-351-4702 DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This manual covers the following products: DFC-X TS-01 DFTD RDU DAT-12 PWM-10V
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More information(For serial numbers before w/ analog control)
SEQUENCE OF OPERATIONS (For serial numbers before 2038616 w/ analog control) MODEL 1154-000-EA NAT. GAS 230 VAC 50 HZ. 1 PHASE MODEL 1155-000-EA LP GAS 230 VAC 50 HZ. 1 PHASE POWER SUPPLY Electrical power
More informationHIGH CAPACITY POWER VENT KIT
IMPORTANT: THESE INSTRUCTIONS ARE TO REMAIN WITH THE APPLIANCE INSTRUCTIONS These instructions are supplementary to the Installation and Operating Instructions supplied with the fi replace and should be
More informationCost Affective Dockside Crane Retrofit Utilizing Existing SCR s
Cost Affective Dockside Crane Retrofit Barry W. Wiles Industry Manager Crane Systems Avtron Manufacturing Inc. 7900 E. Pleasant Valley Rd. Independence, OH 44131 Phone: (216) 642-1230 FAX: (216) 642-6037
More information