Thomas R. Proctor High School

Size: px
Start display at page:

Download "Thomas R. Proctor High School"

Transcription

1 System Overview Thomas R. Proctor High School has been upgraded from an existing radial electrical system to an expanded radial system. The new system incorporates two separate substations, one located in the main electrical room of sector D in the existing building and one located in the main electrical room of sector K in a new wing of the addition (refer to figure 1). Both main electrical rooms are located in the basement of their respective sectors. The incoming electrical service into Thomas R. Proctor High School is provided by Nimo Power Company. Before reaching the school, the 13.2 kv Figure 1 Locations of the two underground service enters new metal enclosed outdoor main substations in Proctor H.S. switchgear, containing a 600A fused disconnect switch. The utility metering equipment is located on the primary side of this switchgear (explanation of primary vs. secondary metering is described in the Utility Rate Structure section of the report). The service is stepped down in each main substation from 13.2 kv to 480Y/277V via a -Y transformer. Each transformer is protected on the primary side by a 600A fused disconnect switch. All the loads in the school that operate at 208Y/120V are stepped down by 480Y/ Y/120 V transformers (explained further in the Transformer Configuration section). Figure 2 Proctor H.S. Expanded Radial Distribution 1

2 Substation 1: The main switchboard in sector D of the existing building is a 4000A, 480Y/277V, 3Ø-4W switchboard with and AIC rating of 65,000A. It generally contains loads in the existing building, as well as most of the larger new and existing HVAC equipment (chillers, boilers, etc.) throughout the entire building. Although the existing 1938 building electrical system needed replacement, some of the 1990 renovated spaces were able to remain. The main distribution panels that did not need replacement in the existing building have been back-fed by this switchboard. Due to the quantity and size of the loads on this switchboard, it is sized larger than the main switchboard located in the new addition. Substation 2: The main substation in sector K of the new addition consists of a 3000A, 480Y/277V, 3Ø-4W switchboard with an AIC rating of 65,000A. This switchboard supplies power to sectors H, J, and K, as well as some renovated areas in the existing building. The loads include general power, lighting, elevators, electric heaters, VAV boxes, unit vents, fan coils, air handling units, fire pump, exhaust fans and relief fans. This substation also contains the school s emergency generator that supplies emergency power to all of the life safety loads in the school (explained further in the Emergency Power/Lighting section). Since the loads on this switchboard (especially the mechanical equipment) are smaller than the substation 1, it is sized accordingly. My electrical system analysis will focus on this substation, however, since the entire electrical system for the new addition gets power from it. Transformer Configuration Unlike many smaller schools, Proctor High School does not have an exterior transformer. Instead, the underground service is transformed in each of the two main switchgear rooms. Both of these transformers are 13.2 kv 480Y/277V. The transformer for substation 1 is 2000 kva while the transformer for substation 2 is 1500 kva. Aside from the two main transformers, there are (21) Δ-Y 480Y/277V transformers of all sizes ranging from 15 kva kva for receptacles and smaller loads. Eleven of the transformers are fed from substation 1 and 10 are 2

3 fed from substation 2 (see one-line diagram in appendix for exact locations of transformers). These transformers are ventilated, low-sound-level units with one leg and coil per phase (in primary and secondary). The K-13 design rating of the transformers prevents overheating when carrying full load with harmonic content. Emergency Power System The large size of the school demands back-up power in case of emergency. Such back-up is provided via a 500 kw/625 kva diesel fuel emergency generator that is fed from the main switchboard. The generator has the following features: 1. Air-intake silencer 2. Battery charger 3. Sub-base mounted fuel tank with double-wall protection 4. Engine generator set 5. Muffler 6. Exhaust piping external to set 7. Remote annunciator 8. Remote stop switch 9. Starting battery 10. Load bank (furnished for initial testing only) 11. Load-bank remote-control panel 12. Fuel tank leak detection system 13. Vibration isolation The generator is designed to supply AC power backup (with an approximate 10 second delay) to different loads throughout the building. The generator supplies back-up power to life safety loads (emergency lighting and fire alarm systems) and select non-life safety loads. Specifically, the emergency generator panel feeds three separate distribution panels and a 100 hp fire pump. One distribution panel controls all of the emergency lighting for the school and certain small power loads. Another distribution panel contains two elevator controllers which each have a 200A switch. The last panel controls select HVAC loads such as boilers, sensible coolers for the main telephone/data room and main electrical room, as well as unit heaters and a storm water ejector pump for the generator room. The fire alarm system in the building also has DC (battery) backup that provides at least 90 minutes of power if AC power fails. The 3

4 telephone system, although not a life safety load, has a similar backup system. The three main emergency panels are linked from normal power (main switchboard 2) to emergency backup power through the use of an automatic transfer switch (ATS) for each emergency panel. It is important to note that shunt trip is provided to be used during generator load shedding to disconnect all but the life safety loads (refer to the appendix for a generator system diagram). Automatic Transfer Switches: The ATS switches used in the building are contained in NEMA 250, Type 1 general-purpose enclosures. The switching arrangement is double-throw so that the switch is incapable of pauses or intermediate position stops during normal function. The switch has an adjustable voltage relay that is pre-set to 90% of the nominal voltage to avoid premature transfer to emergency power. The time delay for re-transfer to normal power is adjustable from 0-30 minutes and is pre-set to 10 minutes. The unit contains a test switch that simulates normal-source power failure. A transfer override switch is provided to supersede automatic retransfer to normal power. This forces the ATS to remain on emergency power regardless of the state of normal power if is so desired. Switchgear and Overcurrent Devices Switchgear: As described in the system overview, the incoming electrical service enters an exterior with a 600A fused disconnect switch. The switchgear maintains its 20 distance from the utility pole, as per the NEC regulations. The switchgear load interrupter switch has the following characteristics: System Voltage: 13.2kV, 3Ø-4W Maximum Design Voltage: 15 kv Amperes Continuous: 600A Fault Close: 61 ka 4

5 Main Substation Room 1 Exterior Switchgear Main Substation Room 2 Figure 4 Site plan of exterior switchgear, manholes, and substation rooms Scale: NTS Enclosed Switches and Circuit Breakers: Enclosed Switches: All enclosed non-fusible switches are NEMA KS 1, type HD, with lockable handle. All enclosed fusible switches are NEMA KS 1, type HD, with clips to accommodate the specified fuse. The switch has a lockable handle with two padlocks and is interlocked with the enclosure cover when it is in the closed position. The fuse associated with each fused switch is a NEMA FU 1, nonrenewable cartridge fuse. Enclosed Circuit Breakers: The circuit breakers are molded-case NEMA AB 1, with interrupting capacity to meet the available fault currents. The following four types of circuit breakers are found in the building Molded-Case Circuit Breaker: contains an inverse time-current element for low-level overloads and an instantaneous magnetic trip element for short circuits 5

6 Adjustable Instantaneous-Trip Circuit Breaker: contains a magnetic trip element with front-mounted, field-adjustable setting. GFCI Circuit Breaker: Single and two-pole configurations with 5- ma trip sensitivity. Molded-Case Switch: Molded-case circuit breaker without trip units. Wiring and Bus Types While the existing building electrical system that has been back-fed by switchboard 1 uses 1200A bus duct as its means of conductors, the new electrical system uses copper conductors. Medium-Voltage Cable: The main service into the building is type MV90, compact class B copper. The conductor interstices are filled with impermeable compound. The rubber insulation complies with AEIC CS 6. The rated voltage is 15 kv. The shielding is copper tape applied over semi-conducting insulation shield. The outside jacket is sunlight-resistant PVC. Conductors: No. 10 AWG and smaller is solid copper conductor that complies with NEMA WC 5. No. 8 AWG and larger is stranded copper conductor that complies with NEMA WC 5. Cables: The following describes the type of cable used in its specific location or application: Service Entrance: Type THWN in raceway. Feeders: Type THHN/THWN in raceway. Branch Circuits: Type THHN/THWN in raceway. Fire Alarm Circuits: Power-limited, fire-protective signaling circuit cable or THHN/THWN in raceway. 6

7 Class 1 Control Circuits: Type THHN/THWN in raceway. Class 2 Control Circuits: Power-limited cable, concealed in building finishes or type THHN/THN in raceway Motor Power Distribution The vast majority of motor loads are in conjunction with mechanical equipment. Most of these loads are distributed via HVAC panelboards. Larger HVAC loads (such as chillers) are fed directly from the main switchboard and protected by individual 800A, 3-pole circuit breakers. The remaining motors are dispersed among regular power panels. No motor control centers are present in the school. Power Factor Correction As is typical with a school building, no capacitors or other components were necessary for power factor correction at Proctor High School. Since buildings of this nature typically have a high power factor (>.95), power factor correction is not an issue. A large portion of the total load in the school is resistive or high power factor lighting loads. Even the motor load, although a very substantial amount of the total load, consists of high efficiency and high power factor energy saving motors. The motor loads, in conjunction with the resistive and lighting loads, rarely results in an overall power factor that drops below.95. UPS Systems The electrical engineering contractor did not need to provide any kind of UPS system anywhere in the building. However, the school district did buy their own mini-ups systems to back-up the school s data servers. These are likely 3-12 KW output UPS units that sit on the floor and provide uninterrupted backup to the network servers. These loads are not backed by the emergency generator, so they rely strictly on their own charged batteries to provide constant power in case of power failure. 7

8 Typical Lighting System The entire lighting system in Proctor H.S. operates at 277V. The majority of the lighting is fluorescent, with compact fluorescent lighting and HID lighting in certain areas. Some lighting in the classrooms, labs, office spaces, corridors, and toilets are controlled using a programmable lighting panel. This lighting control system includes a network control unit, lighting control unit, and lighting control relay panel (with mounted relays). Since manufacturer names are not specified for lamps and ballasts, Philips Lighting lamps and advanced transformer ballasts are used for the purpose of this report. Lamp Schedule: Lamp Wattage Ballast Fluorescent CFTR26W/GX24q/ REZ-1T32 ICF-2S26-H1-LD@120 Ballast Factor Input Watts Operating Voltage Current Power Factor F54T5/835/HO/ALTO 54 ICN4S5490C2LS@ CFT7W/G23/825 7 H-1B-TP-BLS F4OT8/TL835/ALTO 40 ROP-3P32-SC F24T5/835/HO 24 ICN-2S24@277V PL-T 18W/835/4P/ALTO PL-C 13W/835/4P/ALTO 13 RCF-2S13-M1-LS-QS Metal Halide CDM70/TD/ A52M >.9 CDM100/PAR38/SP/3K A53M >.9 MHC100/C/U/MP/3K/ALTO A53M MH175/3K/BU B55N MH250/C/U A57M MS400/3K/BU A60M

9 Fluorescent Lamps: Fluorescent Lamps are specified to be 3500K. The lamps are specified to have a CRI of >85. The rated average life is 20,000 hours at 3 hours per start on a rapid-start circuit. Fluorescent Ballasts: All ballasts are designed for a total harmonic distortion (THD) of <10% and an A sound rating. Electronic ballasts for linear lamps: are energy saving and without potting compound voids. Recessed compact fluorescent ballasts: are electronic, fully encapsulated with a minimum power factor of 90%. The lamps have an operating frequency of <5% and a lamp current crest factor of <1.7. Non-recessed compact fluorescent ballasts: have a power factor of >90% and a coil temperature of 65 degrees C. HID Lamps: All of the metal-halide lamps are specified to have a color temperature of 3600K and a CRI of 70. All of the lamps are a self-extinguishing type. HID Ballasts: All ballasts are to match the system voltage. The minimum starting temperature is -22 degrees F and normal ambient operating temperature is 104 degrees F. The ballasts have open-circuit operation that will not reduce lamp life. The ballasts provide an auxiliary, instant-on, quartz system. This automatically switches quartz lamps on when the fixture is initially energized and when momentary power outages occur. The ballasts also provide an auxiliary emergency transfer system. Lighting Control Devices: The following devices are integrated into the lighting design of the school: Time Switches: Solid-state programmable time switch units with alphanumeric display, complying with UL

10 Photoelectric Relays: consists of a single-pole, double-throw dry contacts. The time delay prevents false operation. Multi-pole Contactors and Relays: These contactors are electrically operated and mechanically held, complying with UL 508. Mechanical Equipment Characteristics Refer to the appendix for mechanical equipment schedules. NEC building Design Load The building design load was calculated for the new addition to Proctor H.S. (substation 1) and compared to the original design load and switchboard size. This was determined by separating the loads in the building into three categories: receptacle/small power, lighting, and motor loads. An estimated power of 180 VA was used for each receptacle in which the actual power was not known. For any dedicated receptacle, or receptacle that is to have a specific appliance associated with it at all times, the known power of the load was used for calculations. The known power of all other small power loads (electric resistive cabinet heaters, etc.) was used for calculations. The lighting system was calculated in two different ways. First, an actual existing lighting load calculation was performed to try to get an accurate impression of the lighting load. The lighting load was also estimated using Table 220.3(A) for general lighting loads by occupancy in the NEC Handbook for. The greater of these two values was used for the final calculation of the demand load for switchboard sizing. The motor loads on switchboard 2 are small in comparison to the overall motor load. The motors on the switchboard consist of elevator control motors, air handling units, VAV boxes, unit vents, fan coils, exhaust fans, relief fans, fire shutters, and the school s fire pump. The loads were calculated by multiplying the largest motor by 0.25 and adding it to the sum of all of the motor loads. To determine the total connected load, power factor assumptions were made for each type of load: Small power:.85 PF Lighting:.95 PF Motors:.85 PF 10

11 Spare Capacity (25%):.85 PF These values were used in order to remain very conservative in the calculations. School buildings would rarely ever have a power factor as low as.85 and lighting power factors are typically >.95. The loads were then separated by utilization voltage and then added together to calculate the total connected load. Total demand load was then calculated by using the proper demand factors for the loads: Receptacles: Lighting: 1.25 Motors: 1 Spare Capacity: 1 1 (for the first 10 kva).5 (remaining kva) Connected and Demand Load Power Calculations: Small Power: Total Connected Load: Total Demand Load: Lighting: Actual Load Total Connected Load: Total Demand Load: PF = j369.7 kva = 702 kva j5.27 kva (1 st 10 kva) + ( kva) (x 0.5) j = 245 kva PF = j53.66 kva ( j53.66) x (1.25) = kva NEC occupancy load Square feet x NEC VA/sq.ft: 124,588 x 3 = 373,764 VA 21,986 x 0.5 = 10, VA 1,240 x 1 = 1,240 VA Total = kva Total Connected Load = PF = j120.5 kva Total Demand Load = ( j120.5) x (1.25) = j kva 11

12 Motors: Total Connected Load: Total Demand Load: Spare (25%): Total Connected Load: Total Demand Load: Fire pump (largest motor): PF x j9.82 kva Motors: PF = j kva j9.82 kva j kva ( ) x (1) = kva PF = j kva j x (1) = j kva The total connected and demand loads were calculated by adding together the loads, making sure to keep the loads on different operating voltages separate, and then adding the combined 480Y/277V load to the combined 208Y/120 load. Then the total current was derived by dividing the demand load power by (1.732 x voltage) since the entire system is three-phase. Once again, it is important to make sure that the loads on different voltages are seaparted and then the currents are added at the end. Results: Total Connected Load (Actual) Total Connected Load (NEC) Total Demand Load (Actual) Total Demand Load (NEC) Total Demand Current (NEC) Total Demand Current (NEC) kva kva kva kva A A Switchboard Power Capacity: P=VIcos(σ) P = (480) (3000)(1) = kva In both the actual and NEC cases, the demand load is well under the switchboard capacity, even with 25% spare capacity. Switchboard Current Capacity: In both the actual and NEC cases, the demand current is well under the switchboard capacity, even with 25% spare capacity. 12

13 Utility Rate Structure Before the electrical service was installed, a rate analysis of primary vs. secondary metering on the exterior switchgear was conducted to determine which system would be the cheapest. Estimated Maximum Demand for Entire Building = 3300 kw 80% Diversity Average Demand = 2640 kw = 2640 kw (summer) = 1980 kw (winter) Primary Usage: Summer Total = 918,000 kwh Winter Total = 688,400 kwh Summer Charges Demand $33,501/ month for 3 months = $100,503 kwh charge $25,633.80/month for 3months = $75,795 Winter Charges Demand $25,633.80/month for 9 months = $230,704 kwh charge $18,947.20/month for 9 months = $170,525 Supply benefit charge (12 months) = $5,240 Service charge (12 months) = $5,240 Supply charge (12 months) = $251,929 Grand Total = $840,176 Secondary Usage: Summer Total= 918,000 kwh Winter Total = 688,400 kwh Summer Charges Demand $39,520/month for 3 months = $118,562 kwh charge $25,326/month for 3 months = $74,978 Winter Charges Demand $30,239/month for 9 months = $272,155 kwh charge $18,933/month for 9 months = $170,939 13

14 Supply Benefit (12 months) = $5,480 Supply Charge (12 months) = $3,122 Supply Charge (12 months) = $261,929 Grand Total = $908,165 Summary Secondary Service Annual Cost = $908,165 Primary Service Annual Cost = $840,176 Savings for Primary Service = $67,989 (Annual) As a result of the cost analysis, the school decided upon primary service metering because of the annual savings. It was determined that the initial cost would be paid back in approximately 4 years. 14

15 APPENDIX 15

University of California, San Diego Cal (IT) 2 Technical Assignment #2. Brian Smith

University of California, San Diego Cal (IT) 2 Technical Assignment #2. Brian Smith University of California, San Diego Cal (IT) 2 Technical Assignment #2 Brian Smith Advisor: Dr. Moeck 31 October 2005 Brian Smith Lighting/Electrical Option University of California, San Diego Cal (IT)

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

A. This section includes unit capacitors for power factor correction.

A. This section includes unit capacitors for power factor correction. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

Electrical Existing Conditions and Building Load Summary Report

Electrical Existing Conditions and Building Load Summary Report Electrical Existing Conditions and Building Load Summary Report Executive Summary: This Electrical Existing Conditions and Building Load Summary Report will describe the general and specific characteristics

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

A. This section includes enclosed dry type transformers for lighting and power loads, with primaries and secondaries rated 600 volts and less.

A. This section includes enclosed dry type transformers for lighting and power loads, with primaries and secondaries rated 600 volts and less. PART 1: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

EON Model EL3 Three Phase Centralized Emergency Lighting Inverter. General Specification 10KW 33KW Systems

EON Model EL3 Three Phase Centralized Emergency Lighting Inverter. General Specification 10KW 33KW Systems EON Model EL3 Three Phase Centralized Emergency Lighting Inverter General Specification 10KW 33KW Systems 1.0 GENERAL This specification defines the electrical and mechanical characteristics and requirements

More information

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of

More information

Low Voltage Automatic Transfer Switch Systems

Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in

More information

EON Model EL3 Three Phase Centralized Emergency Lighting Inverter. General Specification 40KW 55KW Systems

EON Model EL3 Three Phase Centralized Emergency Lighting Inverter. General Specification 40KW 55KW Systems EON Model EL3 Three Phase Centralized Emergency Lighting Inverter General Specification 40KW 55KW Systems 1.0 GENERAL This specification defines the electrical and mechanical characteristics and requirements

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

Bussmann series Quik-Spec Coordination Panelboard

Bussmann series Quik-Spec Coordination Panelboard Quik-Spec electrical gear 12 Contents Bussmann series Quik-Spec Coordination Panelboard Section page Description Quik-Spec Coordination Panelboards Up to 400 A 2 600 to 1200 A 3 Quik-Spec elevator disconnects

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage Switchgear Low Voltage Introduction...13-1 AKD-10 Low-Voltage Switchgear...13-3 AKD-20 Low-Voltage Switchgear...13-3 Low Voltage Switchgear GE low-voltage switchgear is heavy-duty equipment built to ANSI

More information

ECET Distribution System Protection. Overcurrent Protection

ECET Distribution System Protection. Overcurrent Protection ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Distribution System Protection Overcurrent Protection One of the most important aspects of distribution system design is system protection.

More information

TRANSMISSION SYSTEMS

TRANSMISSION SYSTEMS TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

1. Division 26 Section Elevator Shunt-Trip Fused Disconnect Switches. SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

Illuminator Series CR NEMA 3R

Illuminator Series CR NEMA 3R Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

2016 Photovoltaic Solar System Plan Review List

2016 Photovoltaic Solar System Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

C1000 Series Automatic Cap Bank

C1000 Series Automatic Cap Bank C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

GE Energy Industrial Solutions. EV Charging Station. Application Guide. imagination at work

GE Energy Industrial Solutions. EV Charging Station. Application Guide. imagination at work GE Energy Industrial Solutions EV Charging Station Application Guide imagination at work EV Charging Station Introduction The GE EV Charging Station offers Level II charging capable of reducing charge

More information

ASCO Low Voltage Automatic Transfer Switch Systems

ASCO Low Voltage Automatic Transfer Switch Systems ASCO Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications ASCO s experience and commitment to excellence in designing and building Emergency Power

More information

Quik-Spec Electrical Gear

Quik-Spec Electrical Gear Section Contents Page Quik-Spec Coordination Panel Boards......... 266-267 Quik-Spec Power Module Switches and Panels.. 268-269 Quik-Spec DC Safety Switches.................. 270 Quik-Spec AC Safety Switches..................

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

1. Field verify measurements and circuiting arrangements as shown on as-built drawings.

1. Field verify measurements and circuiting arrangements as shown on as-built drawings. 26 00 00 Electrical 26 05 00 Common Work Results for Electrical 1. No more than three phase conductors, each of opposite phases for a three phase WYE system, shall be combined in a single raceway unless

More information

Spring Test 10 due 05/11/2013

Spring Test 10 due 05/11/2013 Spring Test 10 due 05/11/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. When installed in an agricultural building that houses livestock

More information

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK 5 October 2017 John A. Weber Principal Electrical Engineer, Hartford Steam Boiler Inspection and Insurance Company Electrical Power Transmission

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

Electrical Design/Build Guide

Electrical Design/Build Guide 2017 Electrical Design/Build Guide Based on the 2017 National Electrical Code Copyright Durand & Associates 1986-2016 60 C Copper Ampacity 4 - Wire Fill - (Non-Current Carrying Neutral) 4 or 5 - Parallel

More information

Self-protected Combination Starters System PKZ 2-SP

Self-protected Combination Starters System PKZ 2-SP Self-protected Combination Starters System PKZ 2-SP 03/035 PKZ 2/ZM/S-SP motor starters: a higher level of protection and versatility : The PKZ 2/ZM/S-SP is a self-protected starter, the first motor controller

More information

Busway Construction. Bus Bars

Busway Construction. Bus Bars Busway Construction Bus Bars A better understanding of what busway is can be gained by examining its construction. A typical Siemens Sentron busway section has three or four formed aluminum or copper bars

More information

Electrical Depth. Josh Kreutzberger Lighting/Electrical

Electrical Depth. Josh Kreutzberger Lighting/Electrical Electrical Depth Electrical Introduction The current power distribution system provides the building with power; however, an alternative design solution was analyzed. This analysis was done in order to

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best. Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution

More information

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection

More information

Power System Solutions (PSS)

Power System Solutions (PSS) About Power System Solutions mission The Power System Solutions Mission Statement To achieve customer satisfaction by providing innovative solutions to improve upon power quality, energy efficiency, and

More information

Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals?

Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals? White paper Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals? Darryl Moser, Business Development Manager, DEM Sales, ABB, Electrification Products Division

More information

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System 2004 Specifications CSJ 2121-04-072 SPECIAL SPECIFICATION 5066 Packaged Engine Generator System 1. Description. Furnish and install packaged engine generator system complete with transfer switch and service

More information

Rex Healthcare Medium Voltage System Presentation APEC 2015 March 15-19, 2015

Rex Healthcare Medium Voltage System Presentation APEC 2015 March 15-19, 2015 Rex Healthcare Medium Voltage System Presentation APEC 2015 March 15-19, 2015 Maximizing the Efficiency of Hospital Distribution Systems Through the Use of Advancing Technology and Design Creativity MISSION:

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives. SECTION 230513 - MOTORS AND ADJUSTABLE SPEED DRIVES PART 1 - GENERAL 1.1 DESCRIPTION A. Provide labor, materials, equipment and services as required for the complete installation designed in Contract Documents.

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

SECTION BASIC ELECTRICAL REQUIREMENTS

SECTION BASIC ELECTRICAL REQUIREMENTS SECTION 16001 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

PROTECTION OF THE BRANCH CIRCUIT

PROTECTION OF THE BRANCH CIRCUIT PROTECTION OF THE BRANCH CIRCUIT Branch circuit should always be protected from over current. Hence, an overall current devices shall be installed in all branch circuitries. Function of the over-current

More information

Outdoor Power Transmission & Distribution

Outdoor Power Transmission & Distribution Description: The purpose of the section is to highlight the current applicable UMCP Design Standards and requirements for Outdoor Power Transmission and Distribution, including but not limited to the following:

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

90.2 Scope. The installation of electrical conductors, equipment and raceways for:

90.2 Scope. The installation of electrical conductors, equipment and raceways for: NEC Generator Primer Rules on the installation of generators and transfer switches 1 90.2 Scope The installation of electrical conductors, equipment and raceways for: public and private premises Conductors

More information

Arc Fault Circuit Interrupter (AFCI) FACT SHEET

Arc Fault Circuit Interrupter (AFCI) FACT SHEET Arc Fault Circuit Interrupter (AFCI) FACT SHEET THE AFCI The AFCI is an arc fault circuit interrupter. AFCIs are newly-developed electrical devices designed to protect against fires caused by arcing faults

More information

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein. 16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION Specification Number: 26 24 13.20 Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION 26 24 13.20 SWITCHBOARDS (Long) Main Disconnect Group Mounted Fusible

More information

Service Entrance Methods

Service Entrance Methods Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility

More information

SECTION DISTRIBUTION AND GROUNDING

SECTION DISTRIBUTION AND GROUNDING SECTION 16400 DISTRIBUTION AND GROUNDING PART 1 GENERAL 1.01 SECTION INCLUDES A. Furnishing and installation of a complete electrical distribution and grounding system. B. Furnish and install motor control

More information

Pretest Module 29 High Voltage Unit 1

Pretest Module 29 High Voltage Unit 1 Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition

More information

BGE STRATEGIC CUSTOMER ENGINEERING

BGE STRATEGIC CUSTOMER ENGINEERING TABLE OF CONTENTS 1. GENERAL.. 2 2. BGE SUPPLY FEEDER.. 4 3. SWITCHGEAR ENCLOSURE AND ASSEMBLY... 5 4. SWITCHGEAR MANUFACTURERS.. 8 5. CIRCUIT BREAKER.. 8 6. SWITCHGEAR EQUIPMENT.... 10 7. MAIN AND GROUND

More information

Series KTU7 UL489 Molded Case Circuit Breakers

Series KTU7 UL489 Molded Case Circuit Breakers Series UL489 Molded Case Circuit Breakers Versatile, convenient and space saving for a variety of applications Sprecher+Schuh s series of UL are UL489 and CE listed for global applications. The current

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 MOTOR CONTROLLERS SPEC WRITER NOTE: Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

2010 PM CM ELECTRICAL. The High-Velocity Edge: Achieving Operational Excellence. 21st Annual Conference

2010 PM CM ELECTRICAL. The High-Velocity Edge: Achieving Operational Excellence. 21st Annual Conference 2010 / PM CM 21st Annual Conference The High-Velocity Edge: Achieving Operational Excellence ELECTRICAL / PM CM 2010 Conference Basic Electrical Rick Miller, PE, LEED AP RNM Engineering, Inc. Vanir Corp.

More information

WARREN COUNTY, N.Y. M/E REFERENCE

WARREN COUNTY, N.Y. M/E REFERENCE SECTION 262000 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 DESCRIPTION A. Provide a complete secondary distribution system as indicated on the Contract Documents and as specified herein. 1.2 QUALITY ASSURANCE

More information

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

MAGNETIC MOTOR STARTERS

MAGNETIC MOTOR STARTERS Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors

More information

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear 13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of

More information

Technical Report 2: Electrical Systems Existing Conditions + Building Load Summary Report

Technical Report 2: Electrical Systems Existing Conditions + Building Load Summary Report Technical Report 2: Electrical Systems Existing Conditions + November 4, 2008 Advisor: Professor Ted Dannerth EXECUTIVE SUMMARY This technical report examines the existing electrical conditions for The

More information

SWITCHGEAR DIVISION PRODUCT PROFILES

SWITCHGEAR DIVISION PRODUCT PROFILES SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,

More information

Volume 2 Charts, Formulas, and Other Useful Information

Volume 2 Charts, Formulas, and Other Useful Information Volume 2 Charts, Formulas, and Other Useful Information Aluminum Conductor Conductor Terminations 61 Compact Aluminum (Conduit Fill Tables) 68-79 Ampacity Dwelling Services 48 1-phase Loads on a 3-phase

More information

Series KTU7 UL489 Molded Case Circuit Breakers

Series KTU7 UL489 Molded Case Circuit Breakers Series KTU7 UL489 Molded Case Circuit Breakers Versatile, convenient and space saving for a variety of applications Sprecher+Schuh s KTU7 series of UL Molded Case Circuit Breakers are UL489 and CE listed

More information

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear Robert J. Gustin Eaton Fellow Application Engineer, P. E. Southfield, Michigan Definitions Metal-enclosed load interrupter switchgear type ME Metal-enclosed switchgear is defined in ANSI C37.20.3-1987,

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Main Service s INTRODUCTION by Robert E. Fuhr, P.E. The use of electronic equipment has dramatically increased

More information

Overcurrent Protection According to the 2011 NEC

Overcurrent Protection According to the 2011 NEC Overcurrent Protection According to the 2011 NEC Utah Electrical License This course will cover overcurrent protection according to the 2011 NEC. The key sections of Article 240 will be discussed. Overcurrent

More information

Schedules 1 to 4, Lot B: Extension of the Lessos Substation

Schedules 1 to 4, Lot B: Extension of the Lessos Substation 1.0 LIGHTNING ARRESTORS 1.1 ZNO lightning arrester, 192 kv rated voltage, 10 ka nominal discharge current 2.0 CAPACITIVE VOLTAGE TRANSFORMER ea. 45 2.1 220 kv capacitive voltage transformer 220/ 3 / 0.11/

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

Power Break II Switchboard

Power Break II Switchboard Power Break II Switchboard Now available with PowerBreak II Circuit Breakers through 4000A GE s Power Break II Switchboard is now available with the new Power Break II Insulated Case Circuit Breaker (800A

More information

Pretest Module 24 Three-phase Service Entrance

Pretest Module 24 Three-phase Service Entrance Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?

More information

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton Advances in technology to address safety Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton 1 Advances in technology could mean use existing technology & back to basics Advances in safety are

More information

GLX. Series. 1kW to 16kW Central System

GLX. Series. 1kW to 16kW Central System GLX Series 1kW to 16kW Central System GLX Series Sine Wave RATINGS TABLE Size Input Current @120V Output Current @120V Input Current @277 Output Current @277 Output Watts Battery (DC) Voltage 1kW 16 8

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations 1 IEEE1818-2017 Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations Sponsored by the IEEE Substations Committee Presented By Joe Gravelle Organization of the Guide 1. Scope

More information

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified. SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information