1 Variable frequency transformer for asynchronous power transfer by Einar Larsen, Richard Piwko and Donald McLaren, GE Energy A new power transmission technology has been developed. The variable frequency transformer (VFT) is a controllable, bidirectional transmission device that can transfer power between asynchronous networks. Functionally, the VFT is similar to a back-to-back HVDC converter. The core technology of the VFT is a rotary transformer with three-phase windings on both rotor and stator. A motor and drive system are used to adjust the rotational position of the rotor relative to the stator, thereby controlling the magnitude and direction of the power flowing through the VFT [1]. The world s first VFT was recently installed and commissioned in Hydro- Quebec s Langlois substation, where it will be used to exchange up to 100 MW of power between the asynchronous power grids of Quebec (Canada) and New York (USA) [2]. General VFT concept and core components The variable frequency transformer (VFT) is essentially a continuously variable phase shifting transformer that can operate at an adjustable phase angle. The core technology of the VFT is a rotary transformer with three-phase windings on both rotor and stator (Fig. 1). The collector system conducts current between the three-phase rotor winding and its stationary buswork. One power grid is connected to the rotor side of the VFT and another power grid is connected to the stator side of the VFT. Power flow is proportional to the angle of the rotary transformer, as with any other AC power circuit. The impedance of the rotary transformer and AC grid determine the magnitude of phase shift required for a given power transfer. Power transfer through the rotary transformer is a function of the torque applied to the rotor. If torque is applied in one direction, then power flows from the stator winding to the rotor winding. If torque is applied in the opposite direction, then power flows from the rotor winding to the stator winding. Power flow is proportional to the magnitude and direction of the torque applied. If no torque is applied, then no power flows through the rotary transformer. Regardless of power flow, the rotor inherently orients itself to follow the phase angle difference imposed by the two asynchronous systems, and will rotate continuously if the grids are at different frequencies. Torque is applied to the rotor by a drive motor, which is controlled by the variable speed drive system. When a VFT is used to interconnect two power grids of the same frequency, its normal operating speed is zero. Therefore, the motor and drive system is designed to continuously produce torque while at zero speed (standstill). However, if the power grid on one side experiences a disturbance that causes a frequency excursion, the VFT will rotate at a speed proportional to the difference in frequency between the two power grids. During this operation the load flow is maintained. The VFT is designed to continuously regulate power flow with drifting frequencies on both grids. A closed loop power regulator maintains power transfer equal to an operator setpoint. The regulator compares measured Fig. 1: Core components of the VFT. Fig. 2: One-line diagram of langlois VFT. power with the setpoint, and adjusts motor torque as a function of power error. The power regulator is fast enough to respond to network disturbances and maintain stable power transfer. Reactive power flow through the VFT follows conventional AC-circuit rules. It is determined by the series impedance of the rotary transformer and the difference in magnitude of voltages on the two sides. Unlike power-electronic alternatives, the VFT produces no harmonics and cannot cause undesirable interactions with neighboring generators or other equipment on the grid. energize - June Page 34
2 Langlois 100 MW VFT station Hydro-Quebec s Langlois substation is located southwest of Montreal, Quebec, at the electrical interface between the Quebec and USA power grids. A 100 MW VFT was installed at Langlois to enable power transfer between the two asynchronous power grids. Fig. 2 shows a simplified one-line diagram of the Langlois VFT, which is comprised of the following: One 100 MW, 17 kv rotary transformer One 3000 HP DC motor and variable speed drive system Three 25 MVAr switched shunt capacitor banks Two 120/17 kv conventional generator step-up transformers. The Langlois VFT station has been designed to be expandable, accommodating another 100 MW rotary transformer and its auxiliary equipment. The yard has space for transformers, capacitor banks, and switchgear associated with the second VFT unit. Fig. 3: Physical layout of a typical 200 MW VFT station with two units. VFT Station layout Fig. 3 shows a typical physical layout for a 200 MW VFT station, with two 100 MW VFT units. The rotary transformer, drive motor, collector, and ventilation system are located in the large section of the building. Control and auxiliary equipment are located in the smaller wing of the building. VFT operation and control features From an operational perspective, a VFT is very similar to a back-to-back HVDC converter station. The VFT has automated sequences for energisation, starting, and stopping. When starting, the VFT automatically nulls the phase angle across the synchronising switch, closes the breaker, and engages the power regulator at zero MW. The operator then enters a desired power order (MW) and ramp rate (MW/minute). Power regulation is the normal mode of operation. The VFT uses a closed-loop power regulator to maintain constant power transfer at a level equal to the operator order. The power order may be modified by other control functions, including governor, isochronous governor, powerswing damping, and power runback. Governor The governor adjusts VFT power flow on a droop characteristic when frequency on either side exceeds a deadband. This function is designed to assist one of the interconnected power grids during a major disturbance involving significant generation/load imbalance. If frequency falls below the deadband threshold, the VFT will increase power import (or reduce export) to assist in returning grid frequency to the normal range. The VFT is designed Fig. 4: VFT control and protection system. Fig. 5: VFT power circuit model for short-circuit and power flow analysis. to operate with one side isolated. If the local grid on one side of the Langlois VFT becomes isolated from the rest of the network, the VFT will continue to operate regardless of whether the isolated system has local generation. If there is no local generation, the VFT will automatically feed all the necessary power up to its full rating. If there is local generation, the VFT will make up the difference between energize - June Page 35
3 local generation and local load, and share frequency governing with the local generator. VFT also has an isochronous governor that will regulate the frequency of the isolated network to 60 Hz, when engaged by the operator. Power-swing damping This function adds damping to inter-area electromechanical oscillations, normally in the range of 0,2 Hz to 1 Hz. This function is installed but disengaged at Langlois, as system conditions do not require it at this time. Power runback This function quickly steps VFT power to a preset level. It is externally triggered following major network events (e.g., loss of a critical line or generator). The VFT control system is designed to accommodate up to four runbacks with separate triggers and runback levels, but only one is presently used at Langlois. Like any other transformer, the VFT has leakage reactance that consumes reactive power as a function of current passing through it. Shunt capacitor banks are switched on and off to compensate for the reactive power consumption of the VFT and the adjacent transmission network. The reactive power controller has three modes: Fig. 6: VFT model for dynamic simulations. Parameter Typical value (based on VFT rating) XVFT 12% XmagVFT 5,6 pu (i.e., magnetizing current = 18%) XT1, XT2 10% B1, B2 20% to 80% total, depending on transmission grid needs H 26 pu-sec Table 1: Typical VFT data for preliminary planning studies. Power schedule mode: The capacitor banks are switched as a function of VFT power transfer, with appropriate hysteresis to prevent hunting. This mode includes a voltage supervision function that takes precedence if the bus voltage falls outside of an acceptable range. Voltage mode: The capacitor banks are switched to maintain the bus voltage within an operator-settable range. Manual mode: The capacitor banks are switched on and off by the operator. VFT control and protection system The control system for the Langlois VFT is comprised of digital processors arranged in a modular configuration (Fig 4). A VFT unit is controlled by the unit VFT control (UVC), which contains automated sequencing functions (start/stop, synchronisation, etc.) power regulator, governor, reactive power control, power runback, and a variety of monitoring functions. The UVC also includes a local manual operator panel, which is a backup to the higher-level operator interface system. A VFT unit is protected by redundant unit protection systems, each comprised of about ten standard protective relays. Protective functions are typical of AC substations and generating plants, including ground fault, negative sequence, differential, over-current, over-voltage, breaker failure, capacitor protections, and synchronisation-check. The UVC and unit protections are essentially identical for any VFT unit. Redundant bus and line protections are specific to each VFT installation. The protections cover the interconnections between the VFT equipment and the local grid. At Langlois, these protections cover a section of the Langlois bus on one side of the VFT and a transmission line to Les Cedres substation on the other side of the VFT. The main VFT control (MVC) is primarily a data concentrator and communications interface. It contains high-level functions for the entire VFT station, SCADA interface to enable unmanned operation, and s u b s t a t i o n a u t o m a t i o n a n d d a t a concentration from the digital relays, UVC processors, and other intelligent electronic devices (IEDs). The MVC s primary purposes are to support the operator interface, SCADA interface, and to coordinate multiunit VFTs. The human-machine interface or operator interface (HMI) uses a GE D200 data concentrator coupled with PowerLink Advantage software for the graphical operator interface. Operator screens include one-lines with several levels of detail, unit control, station control, temperature, ventilation, communication diagram, active alarm, historical alarm (sequence of event recorder), and trending. The local operator HMI has energize - June Page 36 Fig. 7: VFT step response. dual flat panel color screens. A remote operator HMI with similar features is located in another building within the Langlois substation. This overall control system design enables separation of control functions by priority within the overall control hierarchy (i.e., higher priority functions are implemented at lower levels within the hierarchy). It also supports expandability to several VFT units within a substation sharing the same operator interface. VFT models for system planning studies For power flow analysis, the VFT is represented
4 as a phase angle regulator. The limits of phase angle can be set as large as needed to obtain the desired power flow. The series reactances of the system and the level of reactive compensation determine maximum achievable power flow. Fig. 5 illustrates the power circuit to be included between two high-voltage buses. Reactive compensation is represented as switched shunt capacitors. For short-circuit calculations, the impedance is the only information required. The contribution to a bus will be on the order of 150% to 250% of the VFT rating, depending upon the strength of the transmission grid on the opposite side. The step-up transformers are similar to those used on generators, with the high-voltage side grounded-wye and a delta winding on the machine side. A VFT model for dynamic simulations is shown in Fig. 6. The power circuit representation is identical with that for the power flow model. For dynamic events, the phase angle of the VFT varies as a function of rotor inertia dynamics and the torque applied by the drive motor. The VFT control system measures power, shaft speed, and several other signals. The power regulator, in conjunction with the governor, power swing damping control, and other active functions within the VFT control system, develops a torque command, which the drive system applies to the VFT rotor. The difference between the drive motor torque (T d ) and the electrical torque on the rotary transformer windings (T e ) produces an accelerating torque. The rotor inertia equations calculate speed of the rotor and phase angle of the rotary transformer. Typical parameters for the power flow and dynamic VFT models are indicated in Table 1. VFT dynamic response Dynamic performance of the VFT has been analysed and verified by a combination of digital computer simulations, realtime simulator tests using the actual VFT control system, and staged tests at the Langlois VFT station. A few examples of VFT performance are presented here. Fig. 7 illustrates the response of the VFT to steps in power order. The red trace shows the torque command stepping from zero, to 1 pu (100 MW), to 1 pu, and back to zero. The blue traces show the VFT actual power transfer and the angle of the rotary transformer. This response was recorded on the real-time VFT simulator. Step tests were also performed at the Langlois VFT station with similar results. Fig. 8 illustrates the response of the VFT to a fault in the AC network. The voltage on the machine terminals remains above zero, due to contribution from the unfaulted side. The large inertia holds the rotor relatively stationary during the fault, and after recovery the control readjusts the position to meet the desired power flow. Fig. 9 illustrates the Langlois VFT power transfer between the asynchronous Quebec Fig. 8: VFT response to fault in AC network. Fig. 9: VFT power ramps during asynchronous operation with the New York and Quebec power networks. energize - June Page 37
5 and New York power grids. Note that the time scale covers 70 minutes. The top trace shows VFT power in MW as the operator ramped power from zero to +100 MW to 100 MW and back to zero. Unlike conventional HVDC transmission that cannot operate below about 10% power, the VFT s ramp through zero MW is smooth. Also note that power transfer is smooth despite frequency variances in the two grids including the trip of a large unit in the Quebec grid during the measuring period. Fig. 10 shows the response of the VFT governor in a condition where one side of the VFT has a small isolated grid. Initially, two generators at the nearby Hydro Plant were connected to one side of the VFT, together with a small amount of local load. The generating plant was producing a total of 45 MW. Generated power not consumed in the island was transmitted through the VFT to the Hydro-Quebec grid. The plot shows the VFT power transfer and the frequency of the isolated grid for an event where the 35 MW generator was tripped off line, leaving only 10 MW of generation. VFT power dropped instantly, and frequency of the isolated grid declined at a rate of 1,5 Hz/sec. The VFT governor engaged when the frequency dropped below 59,4 Hz. A steady state operating point was reached with VFT power at 10 MW and the frequency at about 59,2 Hz, per the deadband and droop characteristic of the VFT governor. Conclusions Although the VFT concept is new, VFT equipment is comprised of well-established hydrogenerator, motor, and variablespeed drive technology. The world s first VFT for bulk system power transfer between large asynchronous power grids has been successfully installed and tested at Hydro-Quebec s Langlois substation in Canada. The VFT is a viable alternative to back-to-back HVDC converters for the interconnection of asynchronous power grids. References [1] Development of a 100 MW Variable Frequency Transformer, by P Doyon, D McLaren, M White, Fig. 10: VFT response to generator trip on islanded grid. Y Li, P Truman, E Larsen, C Wegner, E Pratico, R Piwko, presented at Canada Power, Toronto, Ontario, Canada, September 28-30, [2] First VFT Application and Commissioning, by M Dusseault, J-M.Gagnon, D Galibois, M Granger, D McNabb, D Nadeau, J Primeau, S Fiset, E Larsen, G Drobniak, I McIntyre, E Pratico, C Wegner, presented at Canada Power, Toronto, Ontario, Canada, September 28-30, Acknowledgements Development of the VFT was a major team effort, including many individuals and business units working in excellent cooperation between GE and Hydro- Québec TransÉnergie. Contact Mark Digby, GE Energy, Tel , mark.digby@ge.com v energize - June Page 38
GE Energy. Variable Frequency Transformers Grid Inter-tie
GE Energy Variable Frequency Transformers Grid Inter-tie Variable Frequency Transformers GE Energy revolutionizes the world of transmission solutions with its new Variable Frequency Transformer (VFT).
More informationEvaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection
Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection B. Bagen, D. Jacobson, G. Lane and H. M. Turanli Manitoba
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements
Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner
More informationVFT Response to a Breaker Trip and Runback Event
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium VFT Response to a Breaker Trip and Runback Event P.E. MARKEN GE Digital Energy Indiana,
More informationCHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM
61 CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 3.1 INTRODUCTION The modeling of the real time system with STATCOM using MiPower simulation software is presented in this
More informationTieline Controls in Microgrid Applications
Tieline Controls in Microgrid Applications M. Adamiak GE Digital Energy, Multilin K.Bahei-Eldin GE Global Research, S.Bose, GE Global Research, J.deBedout GE Global Research, Y.Liu, GE Global Research,
More informationHVDC. TMT&D provides the best and most economical HVDC system.
HVDC TMT&D HVDC TMT&D provides the best and most economical HVDC system. In 1955, TMT&D started the development of HVDC and is the leading HVDC supplier in Japan. TMT&D has continued to develop HVDC technology
More informationJemena Electricity Networks (Vic) Ltd
Jemena Electricity Networks (Vic) Ltd Embedded Generation - Technical Access Standards Embedded Generation - 5 MW or Greater ELE SP 0003 Public 1 October 2014 TABLE OF CONTENTS TABLE OF CONTENTS Abbreviations...
More informationCHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK
91 CHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK CHAPTER CONTENTS: 5.1 INTRODUCTION 5.2 CONDUCTION OF VARIOUS POWER FLOW STUDIES ON THE MODEL 5.3 EXPERIMENTS CONDUCTED FOR VARIOUS POWER FLOW
More informationModular Standardized Electrical and Control Solutions for Fast Track Projects
Modular Standardized Electrical and Control Solutions for Supporting fast track projects ABB is the leading supplier of electrical and control equipment for power plants. The company offers a comprehensive
More informationGrid-Friendly Utility-Scale PV Plants
White Paper Grid-Friendly Utility-Scale PV Plants Mahesh Morjaria & Dmitriy Anichkov, First Solar, Tempe, Arizona, USA 13 August 2013 Table of Contents Introduction.... 3 Power Plant Controller Architecture...
More informationUnit Protection System for Pumped-Storage Power Stations
Unit Protection System for Pumped-Storage Power Stations 1. Introduction In many power systems, pumped-storage power stations are used in addition to run-of-river power stations. These power stations serve
More informationPJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008
PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral
More informationGenerator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood
Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents
More informationStatic frequency converter couples US paper mill s 25-Hz and 60-Hz electricity grids
Static frequency converter couples US paper mill s 2-Hz and 0-Hz electricity grids Before 0 Hz was adopted as the standard frequency for electricity distribution in the USA, power companies across the
More informationWind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment
2012 2nd International Conference on Power and Energy Systems (ICPES 2012) IPCSIT vol. 56 (2012) (2012) IACSIT Press, Singapore DOI: 10.7763/IPCSIT.2012.V56.2 Wind Power Plants with VSC Based STATCOM in
More informationFifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008
Performance Evaluation of Composite Islanding and Load Management System using Real Time Digital Simulator Sachin Srivastava, Meera K.S, R.S. Shivakumara Aradhya and Sunil Verma Abstract A Composite Islanding
More informationGrid Stability Analysis for High Penetration Solar Photovoltaics
Grid Stability Analysis for High Penetration Solar Photovoltaics Ajit Kumar K Asst. Manager Solar Business Unit Larsen & Toubro Construction, Chennai Co Authors Dr. M. P. Selvan Asst. Professor Department
More informationShunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian
Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission
More informationT5S4P3 Synchronous Condensers Application. Mr. Marco Schenone Mr. Sandro Tuscano Mr. Alessandro Oldrati
Mr. Marco Schenone Mr. Sandro Tuscano Mr. Alessandro Oldrati 1 Introduction Ansaldo Energia has recently completed the manufacture, installation and commissioning of two synchronous condenser sets for
More informationSession 10 NERC Interconnection Requirements
GE Energy Session 10 NERC Interconnection Requirements UVIG Short Course 2014 Portland, Oregon Jason MacDowell NERC Standards Recently Adopted NERC GVSDT* standards MOD (Model Validation): MOD-025: Verification
More informationThe 1,400-MW Kii-Channel HVDC System
The 1,4-MW Kii-Channel HVDC System The 1,4-MW Kii-Channel HVDC System 114 Hiroyuki Nakao Masahiro Hirose Takehisa Sakai Naoki Kawamura Hiroaki Miyata Makoto Kadowaki Takahiro Oomori Akihiko Watanabe OVERVIEW:
More informationFuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators
Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators Abstract: G. Thrisandhya M.Tech Student, (Electrical Power systems), Electrical and Electronics Department,
More informationSYSTEM INTEGRATION. Railway and urban transport electrification Energy-efficient and reliable solutions
SYSTEM INTEGRATION Railway and urban transport electrification Energy-efficient and reliable solutions 2 R A I LWAY & U R B A N T R A N S P O R T E L E C T R I F I C AT I O N S O L U T I O N S ABB s substation
More informationWang Bin & Michael Ho, TIIAE Power management system
Wang Bin & Michael Ho, TIIAE 2011 Power management system Content Introduction System configuration Functionality Reference Summary Live demonstration Q & A ABB Group September 5, 2011 Slide 2 Content
More informationGrid Integration Costs: Impact of The IRP Capacity Mix on System Operations
Grid Integration Costs: Impact of The IRP Capacity Mix on System Operations Presenter: Bernard Magoro, System Operator, Transmission Division, Eskom SOC Holdings Date: 05 October 2018 Contents 1. Background
More informationREDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION
REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION Summary Abhay Kumar Mata Prasad R C Maheshwari Asea Brown Boveri Ltd. 4th Floor, 71 Nehru Place, New Delhi
More informationAdvanced Protective Relay Training
Advanced Protective Relay Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq A properly designed protection
More informationPerformance Analysis of Transient Stability on a Power System Network
Performance Analysis of Transient Stability on a Power System Network Ramesh B Epili 1, Dr.K.Vadirajacharya 2 Department of Electrical Engineering Dr. Babasaheb Ambedkar Technological University, Lonere
More informationCHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM
106 CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 5.1 INTRODUCTION Inherent characteristics of renewable energy resources cause technical issues not encountered with conventional thermal,
More informationDate Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS
Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...
More informationFAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE
FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE Yunqi WANG, B.T. PHUNG, Jayashri RAVISHANKAR School of Electrical Engineering and Telecommunications The
More informationPID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation
PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date
More informationDesign considerations for generator set mounted paralleling breakers
Our energy working for you. Design considerations for generator set mounted paralleling breakers White Paper Hassan Obeid, Application Group Cummins Power Generation Cummins Power Systems has been delivering
More informationCONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation
CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent
More informationFeasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation
Feasibility Study Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection J.E.D. Solid Waste Management Facility Holopaw Substation September 2013 1 of 12 Table of Contents GENERAL... 3 SHORT
More informationIslanding of 24-bus IEEE Reliability Test System
Islanding of 24-bus IEEE Reliability Test System Paul Trodden February 14, 211 List of Figures 1 24-bus IEEE RTS, with line (3,24) tripped and buses 3,24 and line (3,9) uncertain....................................
More informationPossibilities of Distributed Generation Simulations Using by MATLAB
Possibilities of Distributed Generation Simulations Using by MATLAB Martin Kanálik, František Lizák ABSTRACT Distributed sources such as wind generators are becoming very imported part of power system
More informationThe Application of Power Electronics to the Alberta Grid
The Application of Power Electronics to the Alberta Grid Peter Kuffel, Michael Paradis ATCO Electric APIC May 5, 2016 Power Electronics Semiconductor devices used in power transmission systems Types: Thyristor
More informationControl System for a Diesel Generator and UPS
Control System for a Diesel Generator and UPS I. INTRODUCTION In recent years demand in the continuity of power supply in the local distributed areas is steadily increasing. Nowadays, more and more consumers
More informationLegal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:
Generating Facility Level 2 or 3 Interconnection Review (For Generating Facilities with Electric Nameplate Capacities no Larger than 20 MW) Instructions An Interconnection Customer who requests a Utah
More informationBasics of Paralleling
Basics of Paralleling Revised: February 1, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Discuss basic paralleling control functions to gain a better understanding
More informationPower Solutions Manager Generac Power Systems, Inc.
Engine Generator Paralleling Concepts Gen. #1 Gen. #2 Gen. #3 Gen. #4 Gen. #5 Presenter: Daniel Barbersek Power Solutions Manager Generac Power Systems, Inc. RUNNING HEADLINE What Topics Will Be Covered
More informationABB POWER SYSTEMS CONSULTING
ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February
More informationDynamic Reactive Power Control for Wind Power Plants
Dynamic Reactive Power Control for Wind Power Plants Ernst Camm, Charles Edwards, Ken Mattern, Stephen Williams S&C Electric Company, 6601 N. Ridge Blvd, Chicago IL 60626 USA ecamm@sandc.com, cedwards@sandc.om,
More informationELECTRICAL POWER SYSTEMS 2016 PROJECTS
ELECTRICAL POWER SYSTEMS 2016 PROJECTS DRIVES 1 A dual inverter for an open end winding induction motor drive without an isolation transformer 2 A Robust V/f Based Sensorless MTPA Control Strategy for
More informationTransmission Grid Reinforcement with Embedded VSC-HVDC. Jonatan Danielsson, Sugam Patel, Jiuping Pan, Reynaldo Nuqui
Transmission Grid Reinforcement with Embedded VSC-HVDC Jonatan Danielsson, Sugam Patel, Jiuping Pan, Reynaldo Nuqui Outline Introduction HVDC-Light Transmission Technologies Embedded VSC-HVDC for AC Grid
More informationJournal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E
Integration of wind Power Plant on Electrical grid based on PSS/E S. Othman ; H. M. Mahmud 2 S. A. Kotb 3 and S. Sallam 2 Faculty of Engineering, Al-Azhar University, Cairo, Egypt. 2 Egyptian Electricity
More informationFunctions provided by measuring relays in railway equipment
Functions provided by measuring relays in railway equipment 1-Current relays -Minimum current relays (During normal operation, if the current is present these relays are in operating position and switch
More informationMICROGRIDS DESIGNING AN IMPROVED GRID
North America MICROGRIDS DESIGNING AN IMPROVED GRID WWW.SWITCHGEARPOWER.COM Utility Grade Central generation including renewables 50-25 000 MW Grid has evolved, due to policies, and is primarily central
More informationSIEMENS POWER SYSTEM SIMULATION FOR ENGINEERS (PSS/E) LAB1 INTRODUCTION TO SAVE CASE (*.sav) FILES
SIEMENS POWER SYSTEM SIMULATION FOR ENGINEERS (PSS/E) LAB1 INTRODUCTION TO SAVE CASE (*.sav) FILES Power Systems Simulations Colorado State University The purpose of ECE Power labs is to introduce students
More informationTechnical & Regulatory Standards Development
GE Energy Management Technical & Regulatory Standards Development RENEW / ISONE Interconnection of Renewable Generation Jason MacDowell GE Energy Consulting September 30, 2014 Global Renewable Codes &
More informationSINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options
/2 Overview /2 Benefits /2 Design /6 Function /8 Selection and ordering data /8 Options Technical data /1 General technical data /15 Control properties /15 Ambient conditions /16 Installation conditions
More informationSEL Microgrid Lessons Learned
SEL Microgrid Lessons Learned Will Edwards (SEL Engineering Services Division) Copyright SEL 2016 Essential Keys to Successful Microgrid Projects? Comprehensive HIL testing Subcycle fast controls Adaptive
More informationRefurbishment and Life Extension of Existing Facilities in Vermont
Refurbishment and Life Extension of Existing Facilities in Vermont Prepared by Joshua Burroughs, Joanne Hu & Jeff Carrara 2015 Grid of Future Symposium Life Extension Projects in Vermont Highgate Converter
More information3.0 Radial Distribution Systems
3.0 Radial Distribution Systems Radial distribution systems (RDS) are the most common design used by electric utilities, and are the least expensive to plan, construct, and maintain. They generally consist
More informationS C ELECTRIC EUROPE LTD. Excellence Through Innovation. Harnessing the Wind. November 2011 Descriptive Bulletin E
S C ELECTRIC EUROPE LTD. Excellence Through Innovation Harnessing the Wind November 2011 Descriptive Bulletin 2000-42E Introduction Founded in 1911, S&C Electric Company is a global provider of equipment
More informationIslanding of 24-bus IEEE Reliability Test System
Islanding of 24-bus IEEE Reliability Test System Paul Trodden February 17, 211 List of Figures 1 24-bus IEEE RTS, with line (3,24) tripped and buses 3,24 and line (3,9) uncertain....................................
More informationModeling and Simulation of Battery Energy Storage Systems for Grid Frequency Regulation. X. XU, M. BISHOP, D. OIKARINEN S&C Electric Company USA
, rue d Artois, F-8 PARIS CIGRE US National Committee http : //www.cigre.org Grid of the Future Symposium Modeling and Simulation of Battery Energy Storage Systems for Grid Frequency Regulation X. XU,
More informationIntegration of Large Wind Farms into Electric Grids
Integration of Large Wind Farms into Electric Grids Dr Mohammad AlZoubi Introduction Development WHAT IS NEXT!! Over the next 12 years, Europe must build new power capacity equal to half the current total.
More informationENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER
ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE MEMBER GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA 01001-2907, USA LSM672 LOAD SHARING MODULE PRODUCT TECHNICAL INFORMATION PTI 4000 AUGUST
More informationPower Conditioning of Microgrids and Co-Generation Systems
Power Conditioning of Microgrids and Co-Generation Systems Nothing protects quite like Piller piller.com Content 1 Introduction 3 2 Basic requirements of a stable isolated network 3 3 Requirements for
More informationEssential Reliability Services Engineering the Changing Grid
Essential Reliability Services Engineering the Changing Grid Robert W. Cummings Senior Director Engineering and Reliability Initiatives i-pcgrid March 39, 2016 Change is Coming Characteristics and behavior
More informationTECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008
NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0
More informationExperiences with Wind Power Plants with Low SCR
1 Experiences with Wind Power Plants with Low SCR Lessons learned from the analysis, design and connection of wind power plants to weak electrical grids IEEE PES General Meeting Denver CO, 26 March 2015
More informationHigh speed, closed loop frequency control using PMU measurements for power grids
PXiSE Energy Solutions, LLC High speed, closed loop frequency control using PMU measurements for power grids By: Chuck Wells and Raymond de Callafon Date: September 27, 2017 PXiSE Energy Solutions, LLC
More informationElectrical Theory. Generator Theory. PJM State & Member Training Dept. PJM /22/2018
Electrical Theory Generator Theory PJM State & Member Training Dept. PJM 2018 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components of
More informationA Case Study on Aggregate Load Modeling in Transient Stability Studies
A Case Study on Aggregate Load Modeling in Transient Stability Studies Presented by: Daniel Feltes Siemens PTI Coauthors: Carlos Grande-Moran, Bernardo Fernandes, James Feltes, Ming Wu and Robert Wells
More informationAPPLICATION OF VARIABLE FREQUENCY TRANSFORMER (VFT) FOR INTEGRATION OF WIND ENERGY SYSTEM
APPLICATION OF VARIABLE FREQUENCY TRANSFORMER (VFT) FOR INTEGRATION OF WIND ENERGY SYSTEM A THESIS Submitted in partial fulfilment of the requirements for the award of the degree of DOCTOR OF PHILOSOPHY
More informationRULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)
- (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility
More informationAE105 PRINCIPLES OF ELECTRICAL ENGINEERING JUNE 2014
Q.2 a. Explain in detail eddy current losses in a magnetic material. Explain the factors on which it depends. How it can be reduced? IETE 1 b. A magnetic circuit with a single air gap is shown in given
More informationStatcom Operation for Wind Power Generator with Improved Transient Stability
Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 4, Number 3 (2014), pp. 259-264 Research India Publications http://www.ripublication.com/aeee.htm Statcom Operation for Wind Power
More informationPlanning and Commissioning Guideline for NORD IE4 Motors with NORD Frequency Inverters
Planning and Commissioning Guideline for NORD IE4 Motors with NORD Frequency Inverters General Information From their basic function, motors with efficiency class IE4 are synchronous motors and are suitable
More informationComparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 12, Issue 3 Ver. II (May June 2017), PP 124-129 www.iosrjournals.org Comparative Analysis
More informationConnection of Power Generating Modules to DNO Distribution Networks in accordance with EREC G99
Connection of Power Generating Modules to DNO Distribution Networks in accordance with EREC G99 Version 2, January 2019 www.energynetworks.org 2 Introduction Connection of Power Generating Modules to DNO
More informationBy Mahesh Morjaria, Dmitriy Anichkov, Vladimir Chadliev and Sachin Soni First Solar, Tempe, Arizona
Grid Integration of Large Utility-Scale PV Plants: Key Lessons Learned By Mahesh Morjaria, Dmitriy Anichkov, Vladimir Chadliev and Sachin Soni First Solar, Tempe, Arizona Abstract The increase in competitiveness
More informationBack Up Power for Sochi
Back Up Power for Sochi May 6 th, 2014 1 Outline Introduction Project Background Problem Statement Solution Overview Site Overview Results Conclusion Page 2 Who We Are Manufacturer of high-energy and highpower,
More informationHawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER
1 Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER Lisa Dangelmaier Hawaii Electric Light lisa.dangelmaier@hawaiielectriclight.com Hawai'i Electric Light System Overview
More informationUse of High-Power Thyristor Technology for Short-Circuit Current Limitation in High Voltage Systems
Advanced Power Transmission Solutions Power Transmission and Distribution Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in Systems s Development of Power Markets Increasing
More informationCIGRE US National Committee 2013 Grid of the Future Symposium. Facilitating Bulk Wind Power Integration Using LCC HVDC
CIGRE US National Committee 2013 Grid of the Future Symposium Facilitating Bulk Wind Power Integration Using LCC HVDC Introduction Many states in US need to meet their renewable energy mandate Wind energy
More informationEH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map
EH2741 Communication and Control in Electric Power Systems Lecture 3 Lars Nordström larsn@ics.kth.se 1 Course map 2 1 Outline 1. Repeating Power System Control 2. Power System Topologies Transmission Grids
More informationExperiences in a Motor Protection Retrofit
Special Feature by Kyle Craig, Ontario Power Generation Amy Sinclair, Schweitzer Engineering Laboratories, Inc. Experiences in a Motor Protection Retrofit Introduction The initial stage of any project
More informationDESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)
DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN) -A.R. Subraaanian -R.A.A. Palani -J. Thomson A new 3.3 K.V. 4200 KVAR auto switching capacitor bank has been installed
More informationConnection of Power Generating Modules to DNO Distribution Networks in accordance with EREC G99
Connection of Power Generating Modules to DNO Distribution Networks in accordance with EREC G99 Version 1 August 2018 www.energynetworks.org 2 Introduction Connection of Power Generating Modules to DNO
More informationUse of Microgrids and DERs for black start and islanding operation
Use of Microgrids and DERs for black start and islanding operation João A. Peças Lopes, FIEEE May 14 17, 17 Wiesloch The MicroGrid Concept A Low Voltage distribution system with small modular generation
More informationEssential Reliability Services From PV Plants
Essential Reliability Services From PV Plants Mahesh Morjaria, Ph. D. VP, PV Systems Enabling a world powered by reliable, affordable solar electricity. Utility-Scale PV Plants Support Grid Stability &
More informationGalapagos San Cristobal Wind Project. VOLT/VAR Optimization Report. Prepared by the General Secretariat
Galapagos San Cristobal Wind Project VOLT/VAR Optimization Report Prepared by the General Secretariat May 2015 Foreword The GSEP 2.4 MW Wind Park and its Hybrid control system was commissioned in October
More informationPSO project EaseWind Enhanced ancillary services from Wind Power Plants. Anca D. Hansen DTU Wind Energy
PSO project EaseWind Enhanced ancillary services from Wind Power Plants Anca D. Hansen DTU Wind Energy Background PSO project EaseWind (2011-2014) Enhanced Ancillary Services from Wind Power Plants Partners:
More informationENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG
ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG C.Nikhitha 1, C.Prasanth Sai 2, Dr.M.Vijaya Kumar 3 1 PG Student, Department of EEE, JNTUCE Anantapur, Andhra Pradesh, India.
More informationCIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems
CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems Ben Huckaba, P.E. President & Principal Engineer 317-273-9841 benh@alphaeng.us Indiana University Bloomington,
More informationSINAMICS GM150 IGCT version
/2 Overview /2 Benefits /2 Design /6 Function /8 Selection and ordering data /8 Options Technical data /14 General technical data /15 Control properties /15 Ambient conditions /16 Installation conditions
More informationTargeted Application of STATCOM Technology in the Distribution Zone
Targeted Application of STATCOM Technology in the Distribution Zone Christopher J. Lee Senior Power Controls Design Engineer Electrical Distribution Division Mitsubishi Electric Power Products Electric
More informationNew Method for Improving On-Line Loading Rates on Mechanical Governors By Gerald G. Runyan
New Method for Improving On-Line Loading Rates on Mechanical Governors By Gerald G. Runyan Abstract Properly tuned and calibrated, mechanical governors provide excellent frequency control, passing all
More informationModelling of Wind Generators for WT3 Transient Stability Analysis in Networks
Modelling of Wind Generators for WT3 Transient Stability Analysis in Networks Tiago Câmara, Under Supervision of Prof. Pedro Flores Correia Abstract The influence of wind turbines in power systems is becoming
More informationPower Generation. PowerStore Renewable microgrid stabilization
Power Generation PowerStore Renewable microgrid stabilization PowerStore Renewable microgrid stabilization ABB`s microgrids and renewable integration platform provides a modular and scalable solution that
More informationDynamic Control of Grid Assets
Dynamic Control of Grid Assets Panel on Power Electronics in the Smart Grid Prof Deepak Divan Associate Director, Strategic Energy Institute Director, Intelligent Power Infrastructure Consortium School
More informationEnhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor
> 57 < 1 Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor Masaki Yagami, Non Member, IEEE, Junji Tamura, Senior Member, IEEE Abstract This paper
More informationHVDC Back-to-Back Interconnections Enabling reliable integration of power system
HVDC Back-to-Back Interconnections Enabling reliable integration of power system Dr Liliana Oprea FICHTNER GmbH&Co KG Swiss Chapter of IEEE PES Baden-Dättwil, 4 September 2013 Table of Contents Need for
More informationDynamic Control of Grid Assets
Dynamic Control of Grid Assets ISGT Panel on Power Electronics in the Smart Grid Prof Deepak Divan Associate Director, Strategic Energy Institute Director, Intelligent Power Infrastructure Consortium School
More informationEE 456 Design Project
F-2014 EE 456 Design Project PROJECT REPORT MALUWELMENG, CONNIE SHARP, MEGAN Table of Contents Introduction... 2 Assignment I... 2 Setup... 2 Simulation... 2 Assignment II... 3 Problems... 3 Solution...
More information