Experiences in a Motor Protection Retrofit

Size: px
Start display at page:

Download "Experiences in a Motor Protection Retrofit"

Transcription

1 Special Feature by Kyle Craig, Ontario Power Generation Amy Sinclair, Schweitzer Engineering Laboratories, Inc. Experiences in a Motor Protection Retrofit Introduction The initial stage of any project is often the business case development. This article outlines the business case for the motor protection retrofit at a large thermal generation plant. The key protection improvements for this installation are reviewed including the advantages of the thermal model and the application of the slip-dependent thermal model. Silver Migration The existing auxiliary relay cases in the motor protection panels have proven to be susceptible to silver migration. Silver migration is the ionic movement of silver between two potentials. The moisture present in the humid air of the thermal plant acts as an electrolyte. The silver transfers from the contacts of an auxiliary relay onto the terminals of its mounting case. When the silver migrates so that two terminals are bridged, protection failures can occur. The plant has recorded several false trips during the past few years. Background and Issues Maintenance Schedule and Spare Parts The existing electromechanical thermal-replica motor protection and interposing relays are well beyond their service life, obsolete from a manufacturing perspective, and have limited spare parts. The plant requirement for maintenance on this existing equipment is to calibrate and complete functional tests every five years. Historically, the calibration on a single thermal-replica motor protection and interposing relay scheme takes a full day. There are a total of 90 motor protection schemes within the facility. Digital relays are self-checking and do not require the same extent of calibration and functional testing. Digital relays are capable of recording and storing event reports, sequential event report data, motor start reports, motor start trending, and motor operating statistics, as well as alarming for self-diagnosed failures. Digital relays are continuously self-testing and reporting operating status. Only functional testing is required after the original in-service commissioning is complete. This functional testing takes less than 30 minutes. The cycle for the digital relay functional testing corresponds to the current Northeast Power Coordinating Council requirements for digital relay reverification. Figure 1 Auxiliary Relay Case Showing Silver Migration The new digital relays have internal timers, internal latches, digital inputs, and enough output contacts so that the auxiliary relays and auxiliary relay cases are no longer required. Digital Recording and Data The plant currently has no digital fault recording equipment on the 4 kv motors or 4 kv bus. The new digital relays sample and store analog and digital data. This provides the operating data required to quickly determine what caused a trip without completing all the detailed tests that were Fall 2010 NETA WORLD 1

2 required previously to troubleshoot any motor protection trips. Following a motor protection trip from existing electromechanical protection, it was a requirement to functional test the protection. With the stored digital data from the new digital relays, this is no longer a requirement. The new digital relays also provide motor operating statistics and motor trend reports. These files can be used to provide an early warning regarding changes in motor start current, thermal capacity used during starting, and motor start time. As an example, these types of detailed data can indicate gradually increasing load torque, which could lead to an unwanted motor trip. Analyzing these types of data can assist with planning motor maintenance schedules and help to avoid unplanned downtime. Thermal Model and Motor Cooling The existing motor protection relies on operators and operating procedures to determine the correct time between starts and prevent damage to motors caused by frequent multiple motor starts. The new digital relays provide a lockout feature to prevent motor starting until the thermal element calculates that there is enough available thermal capacity to allow a start without tripping. The protection engineer sets the rotor and stator thermal capacity used during starting, and the relay provides a lockout until the motor has cooled to the defined capacity. High-Inertia Loads The standby boiler feed pump (SBFP) and the forced draft (FD) fan motors each have starting times considerably longer than their safe stall times. The existing electromechanical thermal-replica protection relays have been desensitized to accommodate the long starting times. The plant had used speed switches in the past, but over time the speed switches proved to be too unreliable and were retired. The probability of a motor stall is low, but the consequence of a failure is higher. The failure of an FD fan motor would cause a forced derating to half load until the motor was repaired. Repair for this 2,300 hp motor could take one week to three months, depending on the severity of the motor damage. If both SBFP motors are unavailable, the generator will be on forced outage until the motor is repaired or a spare unit is made available. Repair or replacement of this 5,500 hp motor could take from one week to three months. Alternatives and Economic Analysis The base case considered for this business case is status quo. This plan could lead to the failure of a critical motor that could leave a main unit unavailable or derated for one day to three months, depending on the severity of the failure. This option will still cost $104,000 (Canadian) over the next five years while the auxiliary relay cases are replaced per an existing program. Because it is not practical or possible to replace all the auxiliary cases at once, nuisance motor tripping may be an issue because of the silver migration. All costs associated with this alternative are avoided by upgrading all of the 4 kv motor protection schemes. Alternative 1: Upgrade 4 kv Motor Protection on Critical Motors Only This option addresses the spare parts availability, system reliability problems, and the silver migration issue on half of the motor protection schemes. The auxiliary relay cases on the motor protection schemes that are not changed will still have to be replaced as scheduled. As the original 35-yearold motor protection schemes left on the noncritical motors age, more failures will occur. Although these failures will not affect the availability of a generator unit, motor protection failures could cause costly motor damage and will eventually require upgrading the relays. Alternative 2: Delay Work One Year Delaying the project will not immediately address the spare parts availability and system reliability. The frequency of motor protection calibration and troubleshooting to verify proper operation will only increase as the equipment continues to age. Similar to the base case, delaying the project will increase the probability of a forced outage or equipment damage. Alternative 3: Upgrade 4 kv Motor Protection The recommended and accepted proposal is to replace all existing 4 kv motor protection relays and the auxiliary relay cases with new digital relays that meet the motor protection requirements. The new protective relays provide the following: Protection for motors with start times longer than their safe stall time. Thermal lockout for multiple start protection. Improved protection for motors previously protected with 51 elements. Data acquisition and troubleshooting using the digital data stored in the relay. The photos in Fig. 2 show the installation of the digital relays. Installation costs were kept to a minimum by taking advantage of existing wiring. The photos show that generally only internal panel wiring required modification. 2 NETA WORLD Fall 2010

3 The relay used for this retrofit uses a thermal model that calculates motor slip during start. During the start of an induction motor, the rotor resistance changes from a high locked rotor value to a low running value. This motor protection relay uses voltage and current to calculate the slip-dependent rotor resistance that enables the calculation of rotor temperature while it varies during a motor start. The details of this thermal model can be reviewed in [2]. In summary, four quantities are required by the slipdependent thermal model in order to calculate the locked rotor resistance and rotor resistance at rated speed. These four quantities are the locked rotor torque (LRQ), the locked rotor current in per unit (I L ), the full-load speed (FLω), and the synchronous speed (Synω). The locked rotor resistance R M is calculated directly from LRQ in per unit of rated torque and the locked rotor current in per-unit current. Locked Rotor Resistance (1) The rotor resistance at rated speed R N is calculated directly from FLω and Synω. The rotor resistance at rated speed is the motor full-load slip (FLS). Rotor Resistance at Rated Speed (2) At the instant of motor starting, the relay calculates the motor resistance by sampling the positive-sequence voltage V 1 (cyc) and the positive-sequence current I 1 (cyc) at a selected initial cycle. The real part of this impedance is the initial motor resistance R P. Initial Motor Resistance (3) Now, with a sampled value for R P and the locked rotor resistance R M, the stator resistance can be calculated, where A = 1.2, a constant shown in [2]. Stator Resistance (4) Figure 2 Motor Protection Retrofit Motor Starting and Calculating Motor Slip Most digital motor protection relays calculate the heating in the motor by measuring the current. The relay calculates the heating in terms of thermal capacity. The thermal capacity is defined where zero percent is completely cooled and 100 percent is the limit threshold. The thermal capacity is accumulated based on measured current so that during motor starting, the protection is essentially an I 2 t element, with the maximum starting time limited by the hot motor safe stall time. Problems arise when starting motors with high-inertia loads, as the time required to start the motor may approach or even exceed the hot safe stall time [1]. he slip, shown in (6), is a function of the changing motor input resistance, shown in (5), the previously calculated locked rotor resistance R M, the rotor resistance at rated speed R N, and the stator resistance R S. The motor input resistance is measured and updated every processing interval. The motor slip is calculated every two cycles. Motor Resistance (5) Motor Slip (6) Positive-Sequence Rotor Resistance (7) Fall 2010 NETA WORLD 3

4 A comparison of the standard I 2 t starting element, which assumes a constant rotor resistance, with the slip-dependent starting element shows that the slip-dependent model simply includes the slip-dependent rotor resistance in the heat source of the thermal model [2] [3]. Settings and Testing for 5,500 hp Standby Boiler Feed Pump The available motor data provided most of the information required to calculate the settings for the digital relay. Full-load amperes (FLA) was set to 685 A. The setting for locked rotor current was increased from 4.82 FLA to 5.5 FLA (an increase of roughly 300 A) as suggested by the company that rebarred the rotor to a larger style rotor bar. The stator was not modified. Service factor (SF) was set to 1.05 as per the motor ratings. FLS was calculated as: (FLS = 1 nr/ns) (FLS = /3600 = ). The hot safe stall time was set at 9.0 seconds. The following settings were applied to the relay: The following settings were applied to the relay: The applied settings used a hot safe stall time that was less conservative than suggested at 8.0 seconds. Fig. 4 is the start report for the revised settings. During the 11-second start, the rotor temperature reaches 75 percent of the maximum allowed temperature. The revised LRQ quantity results in a new stored constant for locked rotor resistance R M (1) and also results in a revised calculated value for R S (4). The stator resistance R S is dependent on R M and R P, as per (3). The relay measures and calculates R S during every start. Fig. 3 is the motor start report for this 5,500 hp SBFP. The traces show the motor current, terminal voltage, rotor temperature in per unit of the trip value or thermal capacity, and slip. Figure 4 SBFP Motor Start Report, LRQ = 0.7, Start 1 The motor was started twice more with LRQ at 0.7 and the hot safe stall time at 8.0 seconds. Fig. 5 is a motor start report for Start 3 of the 5,500 hp SBFP with the revised settings. Note that on this repeated start, the traces show the normal motor current and relay terminal voltage. However, in this case, the calculated slip remains at 1.0 for an extended time. The rotor resistance remains at R M for this time, and the thermal capacity reaches 100 percent. Figure 3 SBFP Motor Start Report, LRQ = 0.96 Fig. 3 shows that the slip remained at 1.0 for the entire start. Because of the high-inertia load, the motor start time is longer than the hot safe stall time, and the thermal capacity reaches 100 percent. When the calculated slip exceeds 1.0, the relay assigns a slip of 1.0 and calculates the temperature rise using the high locked rotor resistance. Following a review of the motor start data, the motor manufacturer suggested a revised LRQ of 0.7 per unit of rated torque and a hot safe stall time of 6.5 seconds. Figure 5 SBFP Motor Start Report, LRQ = 0.7, Start 3 4 NETA WORLD Fall 2010

5 Figure 7 SBFP Motor Start Report, August 2009 Figure 6 Varying Starting Resistance During Start 3 A detailed examination of the digital data provided by the relay shows that although the current and voltages are as expected for motor starting, there is a variation in the positive-sequence voltage V 1 (cyc) and the positive-sequence current I 1 (cyc). Fig. 6 shows a plot of the resulting varying starting resistance over the first eight cycles of the motor start. During the first few cycles of starting, the rotor resistance is at its initial value R M, and the slip S is 1.0. Thus, the stator resistance R S can be determined using the initial measured resistance R P in (4). The initial cycle at which R P is measured is not critical when the initial resistance remains constant after a 1- or 2-cycle settling time. This is not the case for this 5,500 hp SBFP, as seen in Fig. 6. To account for this varying starting resistance, the relay software was modified to select the minimum value of R P over the first few cycles. Fig. 7 shows a motor start report for this 5,500 hp SBFP with no new settings changes and relay software that is selecting the minimum value of R P over the first few cycles. The traces show the motor current, relay terminal voltage, rotor temperature in per unit of the trip value or thermal capacity, and slip. This motor start report shows that as the slip decreases, the calculated rotor resistance is decreasing as the motor accelerates. During the 11-second start, the rotor temperature reaches 89.5 percent of the maximum allowed temperature, while the motor takes a full three seconds more than the hot safe stall time of eight seconds to successfully start. The Unit 4 SBFP motor protection relay has been in service since August The motor start trend report in Fig. 8 shows consistent start data in terms of average starting time and thermal capacity used for the motor. The starting conditions are clearly very consistent for this Unit 4 SBFP; otherwise, there would have been more variation in the percent thermal capacity. An increase in percent thermal capacity over time could indicate a gradually increasing load torque. Figure 8 Motor Start Trend Report for Unit 4 SBFP Conclusions Motor protection at this plant has been enhanced with the use of digital relays. The slip-dependent thermal model protects the motors while allowing for long acceleration times. The digital relay provides supervision to prevent motor starting until the motor thermal capacity has enough available starting capacity and to prevent damage to motors caused by frequent multiple motor starts. The motor start reports and monthly trend data in the relays can be used to monitor changing starting conditions. The event reports and motor start reports provide data that can be used to enhance the settings and improve the motor protection, as well as confirm a valid protection operation without the need to complete a full protection reverification. Fall 2010 NETA WORLD 5

6 Replacement of the existing 4 kv motor protection relays and the auxiliary relay cases with new digital relays provides the following benefits: Ensures reliable protection for the motors. Removes the safety hazard associated with a catastrophic failure of a large piece of rotating equipment. Reduces the risk associated with equipment failure and silver migration-induced trips. Eliminates the maintenance time spent calibrating each relay. Removes the need to replace auxiliary relay cases. References P. Whatley, M. Lanier, L. Underwood, and S. Zocholl, Enhanced Motor Protection With the Slip-Dependent Thermal Model: A Case Study, proceedings of the 34th Annual Western Protective Relay Conference, Spokane, WA, October S. E. Zocholl, Tutorial: From the Steinmetz Model to the Protection of High Inertia Drives, proceedings of the 33rd Annual Western Protective Relay Conference, Spokane, WA, October S. E. Zocholl, AC Motor Protection, Schweitzer Engineering Laboratories, Inc., Kyle Craig received his BEng in electrical engineering from Carleton University, Ottawa, Canada, in 2004 and his MEng in electrical power engineering from the University of Waterloo, Waterloo, Canada, in He joined Ontario Power Generation in 2004 as a grad engineer trainee at Lennox GS in Kingston, Ontario. In 2005, he became a thermal station engineer at Lennox GS with a focus on project management and protective relaying. He has been registered as a Professional Engineer in Ontario since Amy Sinclair received her BSc in electrical engineering from Queen s University, Kingston, in She joined Ontario Hydro in 1989, working for ten years as a protection and control engineer in the areas of design, operations, and project management. In 2000, she joined ELECSAR Engineering as a project manager with a focus on protective relaying and substation design. Since December 2006, she has been employed with Schweitzer Engineering Laboratories, Inc. as a field application engineer, located in Chatham, Ontario. She has been registered as a Professional Engineer of Ontario since NETA WORLD Fall 2010

Enhanced Motor Protection With the Slip-Dependent Thermal Model: A Case Study

Enhanced Motor Protection With the Slip-Dependent Thermal Model: A Case Study Enhanced Motor Protection With the Slip-Dependent Thermal Model: A Case Study Patrick Whatley Plant Power and Control Systems, LLC Mark Lanier, Lee Underwood, and Stan Zocholl Schweitzer Engineering Laboratories,

More information

Motor Protection Fundamentals. Motor Protection - Agenda

Motor Protection Fundamentals. Motor Protection - Agenda Motor Protection Fundamentals IEEE SF Power and Energy Society May 29, 2015 Ali Kazemi, PE Regional Technical Manager Schweitzer Engineering Laboratories Irvine, CA Copyright SEL 2015 Motor Protection

More information

Case Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI

Case Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI Case Study on On EHV Circuit Breaker Flashover AUTHORS: B. K. SINGH (AGM-ELECT) S.C.SINGH (SUPDT-ELECT) MANOJ SHARMA (Dy SUPDT-ELECT) ANAND PANDEY (ENGR-ELECT) BREAKER-FLASHOVER There has been a rising

More information

Low and medium voltage service. Power Care Customer Support Agreements

Low and medium voltage service. Power Care Customer Support Agreements Low and medium voltage service Power Care Customer Support Agreements Power Care Power Care is the best, most convenient and guaranteed way of ensuring electrification system availability and reliability.

More information

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1. Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations

More information

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design Presented at the 2018 Transmission and Substation Design and Operation Symposium Revision presented at the

More information

Hydro Plant Risk Assessment Guide

Hydro Plant Risk Assessment Guide September 2006 Hydro Plant Risk Assessment Guide Appendix E8: Battery Condition Assessment E8.1 GENERAL Plant or station batteries are key components in hydroelectric powerplants and are appropriate for

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical.1_ UFSS#p A:_. DAVID/ IC, L re Mechanical Civil Protection & Control an LAND& 4^ Transmission & Distribution Telecontrol System Planning

More information

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Modular Standardized Electrical and Control Solutions for Fast Track Projects Modular Standardized Electrical and Control Solutions for Supporting fast track projects ABB is the leading supplier of electrical and control equipment for power plants. The company offers a comprehensive

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Hybrid DC-DC-AC Main Drive for ILVA, Taranto Finishing Mill

Hybrid DC-DC-AC Main Drive for ILVA, Taranto Finishing Mill Hybrid DC-DC-AC Main Drive for ILVA, Taranto Finishing Mill Michael A DeCarli TM GE Automation Systems, LLC 2060 Cook Drive Salem, VA 24153, USA Tel: 540-283-2118 Fax: 540-283-2395 E-mail: Michael.DeCarli@TMEIC-GE.com

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience

Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience Y. Sun 1, 2,*, W. G. Kuijpers 3, E. C. W. de Jong 1,2, and H. Pustjens 3 1 Electrical Energy System, Eindhoven University

More information

BREAKER FAILURE PROTECTION

BREAKER FAILURE PROTECTION 29 th Annual HANDS-ON RELAY SCHOOL March 12-16, 2012 BREAKER FAILURE PROTECTION Brent Carper, PE Protection & Integration Engineer brent.c@relayapplication.com OUTLINE Protection System Failures and Breaker

More information

Grounding Of Standby & Emergency Power Systems

Grounding Of Standby & Emergency Power Systems July / August 2007 ELECTRICAL LINE 53 Grounding Of Standby & Emergency Power Systems By Andrew Cochran Power continuity is essential in many industrial and commercial installations where a trip out due

More information

Steam Turbine Seal Rub

Steam Turbine Seal Rub Steam Turbine Seal Rub Date : November 19, 2014 Steam Turbine Seal Rub Vibration data helps to identify a steam turbine seal rub. Sotirios Christofi Deputy Manager, Head of Mechanical Maintenance, Thessaloniki

More information

Functional Overview and Operating Principles for the AR-OH and AR360 Overhead AutoRANGER Fault Indicators

Functional Overview and Operating Principles for the AR-OH and AR360 Overhead AutoRANGER Fault Indicators WHITE PAPER Functional Overview and Operating Principles for the AR-OH and AR360 Overhead AutoRANGER Fault Indicators Tyson Salewske and Anthony Patenaude INTRODUCTION The purpose of this document is to

More information

Transformer Protection

Transformer Protection Transformer Protection Course No: E01-006 Credit: 1 PDH Andre LeBleu, P.E. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com

More information

Improving Breaker Failure Protection for Generator Applications

Improving Breaker Failure Protection for Generator Applications 1 Improving Breaker Failure Protection for Generator Applications Greg Hataway and Jonathan Ellison, PowerSouth Energy Cooperative Michael Thompson, Schweitzer Engineering Laboratories, Inc. Abstract The

More information

LARSEN & TOUBRO LIMITED TYPICAL SCHEME FOR PROTECTION OF SYNCHRONOUS MOTORS

LARSEN & TOUBRO LIMITED TYPICAL SCHEME FOR PROTECTION OF SYNCHRONOUS MOTORS LARSEN & TOUBRO LIMITED TYPICAL SCHEME FOR PROTECTION OF SYNCHRONOUS MOTORS R.Seshadri Larsen & Toubro Limited Mysore works 1.0 GENERAL DETAILS 1.1 Synchronous Motors: Synchronous motors come in large

More information

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are: Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor.

More information

Cost Benefit Analysis of Faster Transmission System Protection Systems

Cost Benefit Analysis of Faster Transmission System Protection Systems Cost Benefit Analysis of Faster Transmission System Protection Systems Presented at the 71st Annual Conference for Protective Engineers Brian Ehsani, Black & Veatch Jason Hulme, Black & Veatch Abstract

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD May 1, 2017 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

Source-Side Fuse/Load-Side Recloser Coordination

Source-Side Fuse/Load-Side Recloser Coordination How to Coordinate ransformer Primary-Side Fuses with Feeder Reclosers Using Coordinaide M he S&C Protection and Coordination Assistant Part I: Conservative Method his is the first in a series of articles

More information

We trust the foregoing is satisfactory. If you have any questions or comments, please contact the undersigned.

We trust the foregoing is satisfactory. If you have any questions or comments, please contact the undersigned. \ newfoundland labrador hydro a nalcor energy company Hydro Place. 00 Columbus Drive. P.O. Box 00. St. John's. NL Canada AB K t. 0..00 f. 0..00 www.nh.nl.ca December, 0 The Board of Commissioners of Public

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

lectronic starter for single phase duction motor

lectronic starter for single phase duction motor lectronic starter for single phase duction motor PROJECT NO: 104 SUPERVISOR: DR. WEKESA EXAMINER: PROF MANG OLI Prepared by: GITONGA HILDA WANJIKU- F17/39921/2011 PROJECT OUTLINE 1. Project Objective 2.

More information

Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80

Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80 Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80 Motor settings using the SIPROTEC Compact motor protection relay 7SK80 is explained below. Information is given on how to

More information

Application Note. First trip test. A circuit breaker spends most of its lifetime conducting current without any

Application Note. First trip test. A circuit breaker spends most of its lifetime conducting current without any Application Note First trip test A circuit breaker spends most of its lifetime conducting current without any operation. Once the protective relay detects a problem, the breaker that was idle for maybe

More information

Impact of Distributed Energy Resources on Transmission System Reliability

Impact of Distributed Energy Resources on Transmission System Reliability S E P T E M B E R 1 3, 2 0 1 8 W E B I N A R Impact of Distributed Energy Resources on Transmission System Reliability National Council on Electricity Policy (NCEP) Alan McBride D I R E C T O R, T R A

More information

EXPERIMENTAL VERIFICATION OF INDUCED VOLTAGE SELF- EXCITATION OF A SWITCHED RELUCTANCE GENERATOR

EXPERIMENTAL VERIFICATION OF INDUCED VOLTAGE SELF- EXCITATION OF A SWITCHED RELUCTANCE GENERATOR EXPERIMENTAL VERIFICATION OF INDUCED VOLTAGE SELF- EXCITATION OF A SWITCHED RELUCTANCE GENERATOR Velimir Nedic Thomas A. Lipo Wisconsin Power Electronic Research Center University of Wisconsin Madison

More information

Dual Power. Protection. Protection

Dual Power. Protection. Protection 54 Fault Clearing Systems by Damien Tholomier., AREVA T&D Automation, Canada Dual Power Single Battery What if it? Short circuits and other abnormal power system conditions are very rear, but may result

More information

Variable Frequency Drive Basics

Variable Frequency Drive Basics Variable Frequency Drive Basics Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Variable Frequency Drives are

More information

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent

More information

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

Seabrook Substation Reliability Improvement Project

Seabrook Substation Reliability Improvement Project New England Division Seabrook Substation Reliability Improvement Project 1. Project Summary Description Seabrook Substation is critical to ISO-New England as a Pool Transmission Facility, to grid availability

More information

Based on the findings, a preventive maintenance strategy can be prepared for the equipment in order to increase reliability and reduce costs.

Based on the findings, a preventive maintenance strategy can be prepared for the equipment in order to increase reliability and reduce costs. What is ABB MACHsense-R? ABB MACHsense-R is a service for monitoring the condition of motors and generators which is provided by ABB Local Service Centers. It is a remote monitoring service using sensors

More information

Primary Heat Transport (PHT) Motor Rotor Retaining Ring Failure

Primary Heat Transport (PHT) Motor Rotor Retaining Ring Failure 1 Primary Heat Transport (PHT) Motor Rotor Retaining Ring Failure Ali Malik Components & Equipment Eng. Ontario Power Generation - Darlington Nuclear 2 Ontario Power Generation Darlington Darlington Nuclear

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD June 1, 2018 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

Protection for 2500KVA High Tension Transformer Ankita S.Kulkarni 1, Priyanka S.Dhayarkar 2, Harsha H.Ambure 3, Ashwini S.Shinde 4

Protection for 2500KVA High Tension Transformer Ankita S.Kulkarni 1, Priyanka S.Dhayarkar 2, Harsha H.Ambure 3, Ashwini S.Shinde 4 Protection for 2500KVA High Tension Transformer Ankita S.Kulkarni 1, Priyanka S.Dhayarkar 2, Harsha H.Ambure 3, Ashwini S.Shinde 4 Graduate Student, Dept. of E&TC, Pimpri Chinchwad College of Engineering,

More information

Motors Damage Curves

Motors Damage Curves Motors Damage Curves The information presented in this application guide is for review, approval, interpretation and application by a registered professional engineer only. SKM disclaims any responsibility

More information

Development of a High Efficiency Induction Motor and the Estimation of Energy Conservation Effect

Development of a High Efficiency Induction Motor and the Estimation of Energy Conservation Effect PAPER Development of a High Efficiency Induction Motor and the Estimation of Energy Conservation Effect Minoru KONDO Drive Systems Laboratory, Minoru MIYABE Formerly Drive Systems Laboratory, Vehicle Control

More information

High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development Co., Ltd.

High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development Co., Ltd. Hitachi Review Vol. 53 (2004), No. 3 121 High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development Co., Ltd. Hiroaki Yamada Kiyoshi

More information

Advanced Protective Relay Training

Advanced Protective Relay Training Advanced Protective Relay Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq A properly designed protection

More information

Motor Protection Application Guide

Motor Protection Application Guide Motor Protection Application Guide About the Authors Paul Lerley has 28 years of utility and electronics experience, including 15 years at Central Maine Power Company. He is a graduate of the University

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

Small Generator Interconnection Program Interconnection Technical Requirements

Small Generator Interconnection Program Interconnection Technical Requirements General Program Information What is the purpose of the PGE Small Generator Interconnection Program? How do I initiate a distribution interconnection request for my project? The purpose of our Small Generator

More information

Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers

Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers 2 Introduction This discussion describes in detail retrofitting medium voltage circuit

More information

VARIABLE FREQUENCY DRIVES

VARIABLE FREQUENCY DRIVES 262923 VARIABLE FREQUENCY DRIVES PART 1: GENERAL 1.01 SUMMARY A. Section Includes: 1. Variable Frequency Drives (VFD) B. Related Sections: 1. Section 230000 - Basic HVAC Requirements 2. Section 230900

More information

Technical Service Bulletin IOX/DCX Transmitter Maintenance Schedule

Technical Service Bulletin IOX/DCX Transmitter Maintenance Schedule Technical Service Bulletin 140610 IOX/DCX Transmitter Maintenance Schedule Service Bulletin 140610 applies to Comark IOX, DCX and Paragon transmitters. This bulletin contains important maintenance schedule

More information

Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks

Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks by Georges Barbarin Executive summary Aging electrical switchgear infrastructure is a threat to the reliability of power

More information

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n dv/dt Filter Series A 440-600 VAC USER MANUAL PART NO. INSTR - 019 REL. 041119 2004 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation dv/dt Filter is designed

More information

SENTINEL BATTERY MONITORING

SENTINEL BATTERY MONITORING Protecting your power supply SENTINEL BATTERY MONITORING Helios Power Solutions If you re operating mission critical systems and relying on the protection of a UPS and battery bank, then it has to make

More information

REMOTE SENSING DEVICE HIGH EMITTER IDENTIFICATION WITH CONFIRMATORY ROADSIDE INSPECTION

REMOTE SENSING DEVICE HIGH EMITTER IDENTIFICATION WITH CONFIRMATORY ROADSIDE INSPECTION Final Report 2001-06 August 30, 2001 REMOTE SENSING DEVICE HIGH EMITTER IDENTIFICATION WITH CONFIRMATORY ROADSIDE INSPECTION Bureau of Automotive Repair Engineering and Research Branch INTRODUCTION Several

More information

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual Electronic Motor Brake Type G Instructions and Setup Manual Table of Contents Table of Contents Electronic Motor Brake Type G... 1 1. INTRODUCTION... 2 2. DESCRIPTION AND APPLICATIONS... 2 3. SAFETY NOTES...

More information

Appendix 3. DRAFT Policy on Vehicle Activated Signs

Appendix 3. DRAFT Policy on Vehicle Activated Signs Appendix 3 DRAFT Policy on Vehicle Activated Signs Ealing Council has been installing vehicle activated signs for around three years and there are now 45 across the borough. These signs help to reduce

More information

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008 NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0

More information

Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC

Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC One of the most frequently quoted studies related to electric motor reliability

More information

Benefits of a Cooling Tower VFD Retrofit

Benefits of a Cooling Tower VFD Retrofit Benefits of a Cooling Tower VFD Retrofit Greg Owen Electrical Engineer Ryan Carlson Electrical Engineer 54 th Annual MIPSYCON Conference November 7, 2018 Agenda Project Introduction Project Development

More information

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0 ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES 2018-04-24 - Revision 0 EUB Decision 2007-071 Board Direction 52 For questions or comments regarding

More information

Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers

Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers Puget Sound Area Study Team Bonneville Power Administration, Puget Sound Energy, Seattle City Light,

More information

ISLANDING SCHEME FOR STATION DURING GRID BLACK-OUT

ISLANDING SCHEME FOR STATION DURING GRID BLACK-OUT ISLANDING SCHEME FOR STATION DURING GRID BLACK-OUT By Girija Shankar Sharma, M.Tech (Power System), DGM (O&M-Opn), NTPC-Rihand, E-mail: gssharma@ntpc.co.in Presentation Points System Description and Grid

More information

Power stability for manufacturers

Power stability for manufacturers ARTICLE Power stability for manufacturers Manufacturing is a critical aspect of many economies. However, many places lack power grid stability, which leads to production disruption. ABB s PCS100 family

More information

for Pumping Applications

for Pumping Applications ENGINEERED SOLUTIONS for MATERIAL HANDLING Secondary Resistance Controllers (SRC) for Pumping Applications 135 Glacier Street Coquitlam, BC V3K 5Z1 Canada Date: September, 2002 Author: Nicole Neuman Synergy

More information

Overview of Helicopter HUMS Research in DSTO Air Vehicles Division

Overview of Helicopter HUMS Research in DSTO Air Vehicles Division AIAC-12 Twelfth Australian International Aerospace Congress Overview of Helicopter HUMS Research in DSTO Air Vehicles Division Dr Ken Anderson 1 Chief Air Vehicles Division DSTO Australia Abstract: This

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard A manufacturer s view of bushing reliability, testing and analysis By Lars Jonsson Håkan Rudegard 1 A manufacturer s view of bushing reliability, testing and analysis Lars Jonsson Håkan Rudegard ABB Sweden

More information

Advances in Motor Protection Relay Features

Advances in Motor Protection Relay Features Advances in Motor Protection Relay Features Ricardo Abboud, Paulo Lima, John Needs, and Alejandro Rodriguez Schweitzer Engineering Laboratories, Inc. Dibyendu Bhattacharya BP Exploration Operating Co.,

More information

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) 41-242.5E 2 Typical 60 Hertz time product curves for the type CWP-1 relay are shown in Figure 4 with 100 volts

More information

Project Summary Fuzzy Logic Control of Electric Motors and Motor Drives: Feasibility Study

Project Summary Fuzzy Logic Control of Electric Motors and Motor Drives: Feasibility Study EPA United States Air and Energy Engineering Environmental Protection Research Laboratory Agency Research Triangle Park, NC 277 Research and Development EPA/600/SR-95/75 April 996 Project Summary Fuzzy

More information

Exceeding the standards with MNS

Exceeding the standards with MNS Exceeding the standards with MNS Exceeding the standards with MNS 5 essentials of switchgear solutions Since ABB first introduced MNS the modular low voltage switchgear platform over forty years ago, MNS

More information

Islanding of 24-bus IEEE Reliability Test System

Islanding of 24-bus IEEE Reliability Test System Islanding of 24-bus IEEE Reliability Test System Paul Trodden February 14, 211 List of Figures 1 24-bus IEEE RTS, with line (3,24) tripped and buses 3,24 and line (3,9) uncertain....................................

More information

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA Instruction Leaflet I.L. 41-661.1B Effective: June 1997 Supersedes I.L. 41-661.1A, Dated February 1994 Type

More information

Thermo Scientific APEX 500 Rx Metal Detector User s Guide. REC 4345 Rev B Part number English

Thermo Scientific APEX 500 Rx Metal Detector User s Guide. REC 4345 Rev B Part number English Thermo Scientific APEX 500 Rx Metal Detector User s Guide REC 4345 Rev B Part number 109541 English 2010 Thermo Fisher Scientific, Inc. All rights reserved For future reference, write your APEX 500 Rx

More information

Application of Undervoltage Protection to Critical Motors

Application of Undervoltage Protection to Critical Motors 1 Application of Undervoltage Protection to Critical Motors Matt Proctor, Member, IEEE Abstract Undervoltage protection is commonly used to protect motors from damage during abnormal conditions and to

More information

Double earth fault in a PSP during back to back launching sequence

Double earth fault in a PSP during back to back launching sequence Double earth fault in a PSP during back to back launching sequence Jean-Louis DROMMI EDF Hydro Engineering Center, France Pump Storage Scheme, back to back launching Electricité de France Hydro Department

More information

SWITCHGEAR OPERATING PERSONNEL SAFETY UPGRADE SOLUTIONS FOR AGED INSTALLED BASE

SWITCHGEAR OPERATING PERSONNEL SAFETY UPGRADE SOLUTIONS FOR AGED INSTALLED BASE SWITCHGEAR OPERATING PERSONNEL SAFETY UPGRADE SOLUTIONS FOR AGED INSTALLED BASE Carlo GEMME Paola BASSI Giorgio MAGNO ABB - Italy ABB - Italy ABB - Italy carlo.gemme@it.abb.com paola.bassi@it.abb.com giorgio.magno@it.abb.com

More information

High-Impedance Differential Applications With Mismatched CTs

High-Impedance Differential Applications With Mismatched CTs High-Impedance Differential Applications With Mismatched CTs Russ Franklin, Alliant Energy Hossein Nabi-Bidhendi, ABB Inc. Michael J. Thompson and Héctor J. Altuve, Schweitzer Engineering Laboratories,

More information

825-P Modular Protection System for motors Specification Guide

825-P Modular Protection System for motors Specification Guide Specification Guide 1.0 General 1.01 The motor protection relay shall have a current operating range of 0.5 and 5000 amperes. 1.02 The motor protection relay shall provide current measurement-based protection

More information

Government of Canada Hopper Car Fleet 2011 Annual Report

Government of Canada Hopper Car Fleet 2011 Annual Report Government of Canada Hopper Car Fleet 2011 Annual Report Prairie and Northern Region TP 14995E Her Majesty the Queen in Right of Canada, represented by the Minister of Transport, the Honourable Denis Lebel

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

GREENER SHIPPING SUMMIT 2017

GREENER SHIPPING SUMMIT 2017 GREENER SHIPPING SUMMIT 2017 EU MRV Regulation Methods of Data Collection of Fuel Differences/Consequences/Evaluation of Methods Antonios Georgantzis 14 November 2017 Eugenides Foundation The EU MRV Timeline

More information

RVS-AX Instruction Manual

RVS-AX Instruction Manual RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3

More information

Hydraulic Drive Head Performance Curves For Prediction of Helical Pile Capacity

Hydraulic Drive Head Performance Curves For Prediction of Helical Pile Capacity Hydraulic Drive Head Performance Curves For Prediction of Helical Pile Capacity Don Deardorff, P.E. Senior Application Engineer Abstract Helical piles often rely on the final installation torque for ultimate

More information

Guidelines for connection of generators:

Guidelines for connection of generators: Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 MOTIVATION OF THE RESEARCH Electrical Machinery is more than 100 years old. While new types of machines have emerged recently (for example stepper motor, switched reluctance

More information

Artesis MCM Case Studies. March 2011

Artesis MCM Case Studies. March 2011 Artesis MCM Case Studies March 2011 Case 1 Automotive Company: Automobile Manufacturer A Equipment: Pump Stator Isolation Breakdown Decreasing current unbalance level Case 1 Automotive Company: Automobile

More information

INCREASING electrical network interconnection is

INCREASING electrical network interconnection is Analysis and Quantification of the Benefits of Interconnected Distribution System Operation Steven M. Blair, Campbell D. Booth, Paul Turner, and Victoria Turnham Abstract In the UK, the Capacity to Customers

More information

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter Direct On Line (DOL) Motor Starter Direct Online Motor Starter Different starting methods are employed for starting induction motors because Induction Motor draws more starting current during starting.

More information

Testing Lead-acid fire panel batteries

Testing Lead-acid fire panel batteries Thames House, 29 Thames Street Kingston upon Thames, Surrey, KT1 1PH Phone: +44 (0) 8549 5855 Website: www.fia.uk.com Testing Lead-acid fire panel batteries 1. Background - Methods of testing batteries

More information

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Operational Planning Study Report RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Report No. T&S Planning 2013-062 British Columbia Hydro and Power Authority British Columbia Hydro and

More information

Summary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers

Summary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers Summary of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection of Power Circuit Breakers Kevin Donahoe GE Grid Solutions 2018 Texas A&M Protective Relaying Conference Agenda Introduction

More information

ABB life cycle services Uninterruptible power supplies

ABB life cycle services Uninterruptible power supplies ABB life cycle services Uninterruptible power supplies 2 ABB Life cycle brochure UPS service portfolio Life cycle services for uninterruptible power supplies As your service partner, ABB guarantees you

More information

Variable frequency transformer for asynchronous power transfer

Variable frequency transformer for asynchronous power transfer Variable frequency transformer for asynchronous power transfer by Einar Larsen, Richard Piwko and Donald McLaren, GE Energy A new power transmission technology has been developed. The variable frequency

More information

Evolving Bump Chip Carrier

Evolving Bump Chip Carrier FUJITSU INTEGRATED MICROTECHNOLOGY LIMITED. The Bump Chip Carrier, which was developed as a small pin type, miniature, and lightweight CSP, is not only extremely small due to its characteristic structure,

More information

Battery Maintenance Solutions for Critical Facilities

Battery Maintenance Solutions for Critical Facilities Battery Maintenance Solutions for Critical Facilities Chapter Two: Meeting Regulatory Requirements and Observing Best Practices Click a section below In chapter one of Emerson Network Power s ebook entitled

More information

Case Study. Modernising gas fired power plant boiler damper drives and damper bearings

Case Study. Modernising gas fired power plant boiler damper drives and damper bearings Case Study Modernising gas fired power plant boiler damper drives and damper bearings Boiler Damper Drives & Bearings Modernisation Case Study - 10th December 2014 Boiler Damper Drives & Bearings Modernisation

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

Iowa State University Electrical and Computer Engineering. E E 452. Electric Machines and Power Electronic Drives

Iowa State University Electrical and Computer Engineering. E E 452. Electric Machines and Power Electronic Drives Electrical and Computer Engineering E E 452. Electric Machines and Power Electronic Drives Laboratory #12 Induction Machine Parameter Identification Summary The squirrel-cage induction machine equivalent

More information

Cost Affective Dockside Crane Retrofit Utilizing Existing SCR s

Cost Affective Dockside Crane Retrofit Utilizing Existing SCR s Cost Affective Dockside Crane Retrofit Barry W. Wiles Industry Manager Crane Systems Avtron Manufacturing Inc. 7900 E. Pleasant Valley Rd. Independence, OH 44131 Phone: (216) 642-1230 FAX: (216) 642-6037

More information