1 LARSEN & TOUBRO LIMITED TYPICAL SCHEME FOR PROTECTION OF SYNCHRONOUS MOTORS R.Seshadri Larsen & Toubro Limited Mysore works
2 1.0 GENERAL DETAILS 1.1 Synchronous Motors: Synchronous motors come in large sizes like 1 MW and above. Protection of a synchronous motor is different from a normal induction motor protection since a synchronous motor has DC rotor in addition to stator. This document gives details of a protection scheme for large size synchronous motors. 2.0 Relays to be used for protection of Synchronous motor, typical size ( 1750 kw) L&T recommends following relays : a) Comprehensive Motor Protection Relay type MM30W b) Stator differential relay type MD32-G c) Rotor Earth fault relay type UBO/CR d) DC under voltage relay for rotor side, Type UBC-80 e) DC under current relay for rotor side, Type UBC/A/37 One each of above relays are required to offer a complete protection to the synchronous motor. The SLD for the protection is enclosed. Section 3 gives details of individual protections offered by the above relays. 3.0 Protections offered by Motor Protection Relay MM30W MM30W is completely microprocessor based and uses state of the art technology. It provides totally 12 protections. It receives inputs from three phase CTs, one bus PT and gives trip contact as outputs. Following are the protections offered by MM30W: 3.1 Thermal overload This protection will save the motor from any over load conditions from 105% to 600%. If at any time, the motor draws more current than its rated current, thermal over load protection will first give alarm and then eventually trip after a time delay which is defined by the over load trip time characteristics of the motor. Relay has facility to match closely its trip time characteristics with the over load characteristics of the motor. 2
3 -2-3
4 3.2 Locked rotor protection : -3- MM30W offers protection against a locked rotor condition both while starting as well as while running. The LR trip time delay while running can be set by the user. When starting the trip time delay is automatically made as twice that of the starting time. This will save the motor from frequent momentaer over loads ( like crusher moros etc.) 3.3 Repeat Starts Protection: Large machines can be damaged when the operator tries to start them again and again without knowing the cause of trip. It should be noted that every time a start impulse is given, the motor experiences a high current impulse, which progressively increases heating in the stator. This protection saves the motor from damage due to frequent starts. If the number of starts have exceeded a set value within a set time, the start command is inhibited by the relay. 3.4 Negative sequence protection : The motor can get over heated whenever there is unbalance current flowing in the stator. Even a small unbalance in voltage, of the order of 2%, can cause a temperature rise by 10% for the same load. This will not be detected by the thermal overload element since the motor current is still at rated current. This protection monitors the unbalance level and trips the motor if unbalance level exceeds say 30%. 3.5 Over current Protection : This is a protection against external short circuits in the feeder. 3.6 Earth Fault Portection : This is a protection against E/F which can happen frequently in an industry. E/F pick up levels can be set to as low as 10% levels there will not be any spurious tripping since the E/F element in MM30W has a third harmonic filter. 3.7 Under current protection : This is a protection against motor running without load. This saves the motor from conditions of sudden load throw off - like gear box detachment etc...4
5 3.8 Prolonged start protection : -4- When the motor is starting, some times it may take a longer time than specified, to start. This happens in high inertia motors. This may also be due to some maintanence problems. If this happens frequently, then motor can get damaged. MM30W monitors the starting current and starting time if the current does not reduce to a preset level at the end of the starting time, it will initiate the trip, thus savung the motor from further damage. 3.9 Single phasing protection : Single phasing is condition where a large amount of negative sequence will be present, of the order of 53% and above MM30W has inverse time characteristics for trip for negative sequence. It will trip on negative sequence, with shorter time delay, in shorter timehence, whenver there is single phasing Phase reversal Protection: Motors can run in reverse direction when there is phase reversal. Phase reversal is 100% negative sequence condition. MM30W will protect the motor feeder by tripping on negative sequence whenever there is a phase reversal.while starting 3.11 Under Voltage / Over voltage Protection : This protects the motor from stator side under / Over voltages Under / Over frequency protection : This protects the motor from stator side under / Over frequencies Low PF protection : Synchronous motors can easily go into a low PF condition since their rotor excitation is externally controlled. MM30W monitors the PF level of the motor and gives an alarm contact under low PF conditions Auxiliary supply failure protection: If the auxiliary supply to relay is absent, then there is no protection MM30W has a facility where by it will generate a contact whenever its auxiliary supply fails. This contact can be used for alarm / trip Protection against unathorised change in settings : MM30 generates an alarm contact whenever it is taken into programme mode. Consequently it is difficult to change the settings without raising an alarm...5
6 4.0 Differential protection : -5- Relay MD32-G offers a comprehensive differential protection for the synchronous motor. In large machines, it is advaisable to monitor the internal short circuits with a separate relay which will trip instantaneously. MD32 G provides this protection. With a dual slope trip characteristics, MD32G offers a very high through fault stability and avoids spurious trippings under fluctuating loads and external faults. 5.0 Rotor side protections : Rotor of a synchronous machine is a DC winding- hence it needs DC relays. 5.1 Relay UBO-CR protects the rotor from any earth faults. 5.2 Relay UBC-80 provides protection against under voltage for rotor. 5.3 Relay UBC/A/37 provides protection against under excitaion to rotor. All these protections take care of the motor from any loss of field condition also. 6.0 Out of step protection : The normal method is to use a separate relay for out of step protection. L&T has a separate relay IM30-GOS for this application. This is basically caculating the out of step condition by evaluating the position and magnitude of the impedance vector ( from the stator side measurement of current and voltage). While this may be good for a generator, it may not be effective for a motor. MM30W provides a more direct monitoring for an impending out of step condition. Out of step occurs due to sudden over load ( exceeding peak torque rating )on the machine or fall in the applied voltage to stator. Under these conditions motor draws excessive current - it produces a non uniform or pulsating torque - and goes into stalling mode. This current drawn during out of step is of a low PF. 6
7 -6- b) MM30W monitors all above conditions independently and on line. - it has current measurement and a LR setting to save motor from momentary over loads - it has U/V element - to save motor from Under voltage conditions - it has PF element to monitor quality of current and recognise out of step condition. Only thing is motor PF is low during starting - hence PF element should be inhibited during starting. This can be automatically done by ITR/TTR contact. 7. PC Communication software : Many of the relays ( except the DC relays) proposed above have RS485 port through which they can communicate all data with a central PC system. MSCOM communication software is available this will help in continuous polling of the relays from a remote point and log all the relevant feeder data. 8. Control & Relay Panel for Synchronous Motor Protection ; Since there are a total of 5 relays ( MM30W, MD32G, UBO/CR, UBC/80, UBC/A/37), it is advisable to mount all these rel;ays on a small panel with all associated control accessories duly wired together. L&T can offer a total solution for synchronous motor protection in the form of a pre wired C&R panel. ---oooooo@&@oooooo---
A21M. Introduction: Functional Overview: Key Protection & Control Functions:
Introduction: ASHIDA has designed economical & reliable Multifunction A21M Protection & Control System. The simple and compact construction of A21 series, A21M relay provides integrated Protection, Control
More informationUnit Protection System for Pumped-Storage Power Stations
Unit Protection System for Pumped-Storage Power Stations 1. Introduction In many power systems, pumped-storage power stations are used in addition to run-of-river power stations. These power stations serve
More informationSynchronous motor control. 8/15/2007 Powerflow Technologies Inc 1
Synchronous motor control 8/15/2007 Powerflow Technologies Inc 1 PLC Lubrication units Cooling Water DCS PLC Dampers SUB BD Breaker Protection relay Field Application Kiln System Fan Hydraulic Unit Instrumentation
More informationMotor Protection Fundamentals. Motor Protection - Agenda
Motor Protection Fundamentals IEEE SF Power and Energy Society May 29, 2015 Ali Kazemi, PE Regional Technical Manager Schweitzer Engineering Laboratories Irvine, CA Copyright SEL 2015 Motor Protection
More informationLegal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:
Generating Facility Level 2 or 3 Interconnection Review (For Generating Facilities with Electric Nameplate Capacities no Larger than 20 MW) Instructions An Interconnection Customer who requests a Utah
More informationRVS-DN Digital Reduced Voltage Motor Starter
RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3
More informationElectrical Drives I. Week 11: Three phase Induction Motor Starting
Electrical Drives I Week 11: Three phase Induction otor Starting Starting Problem Definition: ' I r Rs Vs 2 R ' r S 2 Xeq At S=0 and S=1, thus the current can be determined as: ' I r st Vs 2 ' Rs Rr Xeq
More informationSynchronous motor with fluid coupling drive arrangement for a preheater ID Fan. presenter Nathan Schachter CIMENTEC Engineering Ltd
Synchronous motor with fluid coupling drive arrangement for a preheater ID Fan presenter Nathan Schachter SLC PLC Lubrication units Cooling Water DCS SUB BD Breaker SR469 GE STAT-XTOR PLC Field Application
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:
More informationProtective Device Coordination ETAP Star
Protective Device Coordination ETAP Star Agenda Concepts & Applications Star Overview Features & Capabilities Protective Device Type TCC Curves STAR Short-circuit PD Sequence of Operation Normalized TCC
More informationKD LV Motor Protection Relay
1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage
More information19 A.C. Motor Protection
9 A.C. Motor Protection Introduction 9. Modern relay design 9. Thermal (Overload) protection 9.3 Start/Stall protection 9.4 Short circuit protection 9.5 Earth fault protection 9.6 Negative phase sequence
More informationCHAPTER 4 PROTECTION REQUIREMENTS
CHAPTER 4 PROTECTION REQUIREMENTS CHAPTER 4 PROTECTION REQUIREMENTS 4.1 General Means of protection for automatic disconnection against phase and earth faults shall be provided on the customer main switch.
More informationApplication Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80
Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80 Motor settings using the SIPROTEC Compact motor protection relay 7SK80 is explained below. Information is given on how to
More informationAIR COOLED RECTIFIER SPECIFICATION S-50-A
SPECIFICATIONS AIR COOLED RECTIFIER Spec50a1 5JAN1999 SPECIFICATION S-50-A HIGH VOLTAGE SINGLE TRANSFORMER AIR COOLED RECTIFIER Standard output power range: 250 to 600 volts at 100 to 1,200 amperes TECHNICAL
More information34 th Hands-On Relay School
34 th Hands-On Relay School Generation Track Overview Lecture Generator Design, Connections, and Grounding 1 Generator Main Components Stator Core lamination Winding Rotor Shaft Poles Slip rings Stator
More informationDG SYNCHRONIZING &AMF PANEL
A 80, Sector 80, Phase 2, Noida 201305, Utter Pradesh, India DG SYNCHRONIZING &AMF PANEL Clients Bharat Petroleum Corp.Ltd PROJECT- DG Synchronization panel with AMF function. Design BY:- Errection By
More informationSeries Motor Protection
320-327 Series Motor Protection Relay Physical Address: 298 Soutter Street, Pretoria West Tel: 083 454 6949, +27 12 327 1729 Fax: +27 (0)12 327 1733 Toll Assist: 0860 10 30 41 www.newelec.co.za sales@newelec.co.za
More informationChapter 3.1: Electrical System
Part-I: Objective type Questions and Answers Chapter 3.1: Electrical System 1. The heat input required for generating one kilo watt-hour of electrical output is called as. a) Efficiency b) Heat Rate c)
More informationCHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS
22 CHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS 3.1 INTRODUCTION A large number of asynchronous motors are used in industrial processes even in sensitive applications. Consequently, a defect can induce
More informationT-Line Generator Control, Protection and Monitoring
T-Line Generator Control, Protection and Monitoring» Control. Monitor. Protect. SELCO T-Line The SELCO T-line offers a complete range of system components for generator control, protection and power monitoring.
More informationSECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.
SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products
More informationRVS-DX Digital Reduced Voltage Motor Starter
RVS-DX Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3
More informationInstallation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor
World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com
More information320 to 327 M Series Low and Medium Voltage Motor Protection Relays
1. Protection Features 320 to 327 M Series Low and Medium Voltage Motor Protection Relays INSTALLATION AND SETTING UP PROCEDURE Overloading (for both cyclic and sustained overload conditions) Start stall
More informationModule 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS
1 Module 2 CONTROL SYSTEM COMPONENTS Lecture - 4 RELAYS Shameer A Koya Introduction Relays are generally used to accept information from some form of sensing device and convert it into proper power level,
More informationBulletin 825 SMM Smart Motor Manager
Bulletin 825 SMM Smart Motor Manager Your order must include: Cat. no. of the Smart Motor Manager selected with supply Voltage Suffix Code, Cat. no. of Converter Module selected, and, If required, Cat.
More informationThis webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB
This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,
More informationEE042: Practical Power System Protection for Engineers & Technicians
EE042: Practical Power System Protection for Engineers & Technicians EE042 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: This intensive course has been designed to give plant operators,
More informationTRIPS AND FAULT FINDING
WWW.SDS.LTD.UK 0117 9381800 Trips and Fault Finding Chapter 6 6-1 TRIPS AND FAULT FINDING Trips What Happens when a Trip Occurs When a trip occurs, the drive s power stage is immediately disabled causing
More informationApplication Note RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS
Application Note GET-8558 RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS REVISION 01 March 17 th, 2016 1 INDEX 1. INTRODUCTION 4 2. RELAY ORDER CODE 5 3. RELAY IO CONNECTIONS
More informationAC Motor Protection. Course No: E Credit: 3 PDH. Velimir Lackovic, Char. Eng.
AC Motor Protection Course No: E03-034 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
More informationVOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS
VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.
More informationNORTH CAROLINA INTERCONNECTION REQUEST APPLICATION FORM. Utility: Duke Energy Progress
NORTH CAROLINA INTERCONNECTION REQUEST APPLICATION FORM ATTACHMENT 2 Utility: Duke Energy Progress Designated Utility Contact: Attention: Customer Owned Generation Mail Code ST13A E-Mail Address: Customerownedgeneration@duke-energy.com
More informationDirect On Line (DOL) Motor Starter. Direct Online Motor Starter
Direct On Line (DOL) Motor Starter Direct Online Motor Starter Different starting methods are employed for starting induction motors because Induction Motor draws more starting current during starting.
More informationThis webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB
This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,
More informationXM1 - Motor protection relay
XM1 - Motor protection relay Contents 1 Applications and features 1 Applications and features 2 Design 3 Working principle 3.1 Overload protection 3.2 Stalling protection 3.3 Earth fault protection 3.4
More informationCase Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI
Case Study on On EHV Circuit Breaker Flashover AUTHORS: B. K. SINGH (AGM-ELECT) S.C.SINGH (SUPDT-ELECT) MANOJ SHARMA (Dy SUPDT-ELECT) ANAND PANDEY (ENGR-ELECT) BREAKER-FLASHOVER There has been a rising
More informationDate Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS
Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...
More informationDEEP SEA ELECTRONICS PLC
DEEP SEA ELECTRONICS PLC 703 AUTOMATIC START MODULE OPERATING INSTRUCTIONS Author:- John Ruddock 703 Operating Instructions Issue Beta1 25/08/2003 2:45 PM JR - 1 - >
More informationPower Systems Trainer
Electrical Power Systems PSS A self-contained unit that simulates all parts of electrical power systems and their protection, from generation to utilisation Key Features Simulates generation, transmission,
More informationSECTION MOTOR CONTROL
SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters
More informationEFFECT OF CAPACITOR ON STARTING & RUNNING OF SINGLE PHASE INDUCTION MOTOR
INDEX NO. : M-145 TECHNICAL MANUAL FOR EFFECT OF CAPACITOR ON STARTING & RUNNING OF SINGLE PHASE INDUCTION MOTOR Manufactured by : PREMIER TRADING CORPORATION 212/1, Mansarover Civil Lines, MEERUT. Phone
More informationMotor Protection Application Considerations
Motor Protection Application Considerations About the Authors Paul Lerley has 28 years of utility and electronics experience, including 15 years at Central Maine Power Co. He is a graduate of the University
More information150 B180 N B D A 8L. Enclosure Type. Input Line Voltage Open Type V AC, 3-phase, 50 and 60 Hz V AC, 3-phase, 50 and 60 Hz
Catalog Number Explanation Open Controllers a Bulletin Number Solid-State Controller B H H B B B B B B B B B B B B B Solid-State Controller and Isolation Contactor (enclosed only) b Controller Ratings
More informationStandby Power Systems
Source: Power Quality in Electrical Systems Chapter 13 Standby Power Systems The term standby power systems describes the equipment interposed between the utility power source and the electrical load to
More informationMemshield - ACB Ratings & Specifications
Memshield Memshield - ACB Ratings & Specifications Rating and specifications Current rating, A List No Number of poles RATED CURRENT (A) [In] IEC, BS, VDE, AS Neutral pole ampere frame (A) RATED PRIMARY
More informationSDC,Inc. SCR-Regenerative Ac Drive
SDC,Inc WWW.STEVENSDRIVES.COM APPLICATION NOTE #: AN_REG_GEN000 EFFECTIVE DATE: 12 MAR 02 SUPERSEDES DATE: Original NO. OF PAGES: 10 SCR-Regenerative Ac Drive Using a regeneration controller with adjustable-frequency
More informationDESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)
DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN) -A.R. Subraaanian -R.A.A. Palani -J. Thomson A new 3.3 K.V. 4200 KVAR auto switching capacitor bank has been installed
More informationAlternator protection, part 1: Understanding code requirements
Power topic #6002 Part 1 of 3 Technical information from Cummins Power Generation Alternator protection, part 1: Understanding code requirements > White paper By Gary Olson, Technical Counsel This paper
More informationSINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options
/2 Overview /2 Benefits /2 Design /6 Function /8 Selection and ordering data /8 Options Technical data /1 General technical data /15 Control properties /15 Ambient conditions /16 Installation conditions
More informationLA Motor Protection. A South African Company to be Proud of
LA Motor Protection Relay Physical Address: 298 Soutter Street, Pretoria West Tel: 083 454 6949, +27 12 327 1729 Fax: +27 (0)12 327 1733 Toll Assist: 0860 10 30 41 www.newelec.co.za sales@newelec.co.za
More informationChapter 3.2: Electric Motors
Part I: Objective type questions and answers Chapter 3.2: Electric Motors 1. The synchronous speed of a motor with 6 poles and operating at 50 Hz frequency is. a) 1500 b) 1000 c) 3000 d) 750 2. The efficiency
More informationElectrical Systems - Course 135 COMPOSITE ELECTRICAL PROTECTIVE SCHEMES: PART II
135 05-1 Electrical Systems - Course 135 COMPOSITE ELECTRICAL PROTECTIVE SCHEMES: PART II TURBINE-GENERATOR: rhipping AND ALARM CIRCUITS i.o' I titrodljction Following on from Lessons 135.03-1 and 135.04-1,
More informationJemena Electricity Networks (Vic) Ltd
Jemena Electricity Networks (Vic) Ltd Embedded Generation - Technical Access Standards Embedded Generation - 5 MW or Greater ELE SP 0003 Public 1 October 2014 TABLE OF CONTENTS TABLE OF CONTENTS Abbreviations...
More informationQUOTATION BLADE 7 LX. Product code GEAL6S2BAA
1 of 10 Mattei rotary vane compressors are the result of 90 years of investments in research and development to improve performance and lessen the impact on the environment. Designed for industrial continuous
More informationNEW ZEALAND POST OFFICE NEGATIVE 50V D.C. TO POSITIVE 50V D.C. SUPPLY NOTES PR 2157 ISSUE 1 APRIL 1977
NEW ZEALAND POST OFFICE NEGATIVE 50V D.C. TO POSITIVE 50V D.C. SUPPLY NOTES PR 2157 ISSUE 1 APRIL 1977 1. GENERAL. 1.1 These PR notes supersede notes PR 2133 and should only be used in conjunction with
More informationStarters. Overview. Siemens caters with following types of starters to agricultural and industrial sector.
Starters Overview Siemens caters with following types of starters to agricultural and industrial sector. 55 Application The main purpose of motor starters is to start the electrical motor by switching
More informationStarting of Induction Motors
1- Star Delta Starter The method achieved low starting current by first connecting the stator winding in star configuration, and then after the motor reaches a certain speed, throw switch changes the winding
More informationPSNH INTERCONNECTION REQUEST
PSNH INTERCONNECTION REQUEST Send the completed Interconnection Request and required attachments to: Public Service of New Hampshire Attn: Michael Motta, Senior Engineer Supplemental Energy Sources P.
More informationSoftstarters. Softstarters Type SSM Medium voltage ,800V 1
Medium voltage 2300 13,800V 1 Description Fused disconnect switch with blown fuse indicators and door safety interlocks rated for load break/fault make with automatic grounding arm Inline isolation vacuum
More informationCIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems
CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems Ben Huckaba, P.E. President & Principal Engineer 317-273-9841 benh@alphaeng.us Indiana University Bloomington,
More informationRVS-AX Instruction Manual
RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3
More informationRM B. Features. Drive Model Number Scheme. A RM6 Product Series
Features RM6 series are suitable for constant and variable torque loads (mixer, conveyor, fan, pump, etc.) Overload capacity with 150% drive s rated output current for 1 min can sustain heavy load conditions
More informationGuidelines for connection of generators:
Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...
More informationDiesel Generator Set S3.8 Series Engine
Diesel Generator Set S3.8 Series Engine > Specification Sheet 44 kva 66 kva 50Hz 40 kw 60 kw 60Hz Description This Cummins Power Generation commercial generator set is a fully integrated power generation
More informationSingle Phase Induction Motor. Dr. Sanjay Jain Department Of EE/EX
Single Phase Induction Motor Dr. Sanjay Jain Department Of EE/EX Application :- The single-phase induction machine is the most frequently used motor for refrigerators, washing machines, clocks, drills,
More information130 KW / 165 KVA POWERED by
130 KW / 165 KVA POWERED by MODEL Triton Power is a world leader in the design, manufacture of stationary, mobile and rental generator sets and Power Modules from 10 to 2000 kw. Through our commitment
More informationExperiences in a Motor Protection Retrofit
Special Feature by Kyle Craig, Ontario Power Generation Amy Sinclair, Schweitzer Engineering Laboratories, Inc. Experiences in a Motor Protection Retrofit Introduction The initial stage of any project
More informationSubmittal Data Information
Effective: NOVEMBER 3, 2014 JOB CONTRCTOR ITEM NO. Submittal Data Information TS - Taco dvanced Starter ENGINEER REP. 301-2690 Supersedes: NEW TS - Taco dvanced Starter 1Ø, 120-230V, 1/10-30HP 3Ø, 200-600V,
More informationFusesaver specification form
Fusesaver specification form Please send this sheet attached to your inquiry / order to: Customer Support Center Phone: +49 180 524 70 00 Fax: +49 180 524 24 71 (Charges depending on provider) E-mail:
More informationSynchronous Motor Drives
UNIT V SYNCHRONOUS MOTOR DRIVES 5.1 Introduction Synchronous motor is an AC motor which rotates at synchronous speed at all loads. Construction of the stator of synchronous motor is similar to the stator
More informationA comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear
Robert J. Gustin Eaton Fellow Application Engineer, P. E. Southfield, Michigan Definitions Metal-enclosed load interrupter switchgear type ME Metal-enclosed switchgear is defined in ANSI C37.20.3-1987,
More informationQuestion Number: 1. (a)
Session: Summer 2008 Page: 1of 8 Question Number: 1 (a) A single winding machine cannot generate starting torque. During starting the switch connects the starting winding via the capacitor. The capacitor
More informationUnit-II Synchronous Motor
Unit-II Synchronous Motor CONSTRUCTION OF THREE PHASE SYNCHRONOUS MOTOR PRINCIPLE OF OPERATION Prepared By P.Priyadharshini Ap/EEE - 1 - Note: 1. The average torque exerted on the rotor of synchronous
More informationLevel 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)
Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less) Interconnection Customer Contact Information Name Alternative Contact Information (if different
More informationMotor Protection. Voltage Unbalance & Single-Phasing
For Summary of Suggestions to Protect Three-Phase Motors Against Single-Phasing see the end of this section, page 137. Historically, the causes of motor failure can be attributed to: Overloads 30% Contaminants
More informationDynamic Study of Bonaire Island Power System: Model Validation and Project Experience
Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience Y. Sun 1, 2,*, W. G. Kuijpers 3, E. C. W. de Jong 1,2, and H. Pustjens 3 1 Electrical Energy System, Eindhoven University
More informationThis generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.
This generator set has been designed to meet ISO 88 regulation. This generator set is manufactured in facilities certified to ISO 900. This generator set is available with CE certification. Enclosed product
More informationA problem with the motor windings. A phase loss on mains terminals L1, L2, or L3 during run mode. Parameter 2-3 Current Imbalance Delay.
10 Troubleshooting When a protection condition is detected, the VLT Soft Starter MCD 500 writes this condition to the event log and may also trip or issue a warning. The soft starter response depends on
More informationAmerican Traction Systems. DC Bus Capacitorss. Total. Dual Chopper Module. Dual. Inverter. 750kW. 750kW Generator Module. Module
EFFECTIVE DATE JULY 28 204 OF 8 Dual Hybrid Ship Propulsion System 750V BUS Generator Generator Propulsion Propulsion Bus Capacitorss 50,000µF Total Traction Inverter Dual Inverterr e Power Inverter L
More informationMP-4000 Motor Protection
MP-4000 Motor Protection Product Focus EATON CORPORATION 1-800-525-2000 Eaton.com 1 Multi-function motor protection Introducing Eaton s Cutler-Hammer MP-4000 motor protection relay. Eaton s Cutler-Hammer
More informationDKG-705 AUTOMATIC MAINS FAILURE AND REMOTE START UNIT WITH PARALLEL TO MAINS AND DUAL GENSET PARALLEL FEATURES
Genset Automation Control Pte Ltd DKG-705 AUTOMATIC MAINS FAILURE AND REMOTE START UNIT WITH PARALLEL TO MAINS AND DUAL GENSET PARALLEL FEATURES FEATURES Automatic mains failure, Remote start operation,
More informationData Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931
Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC
More informationMaryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)
Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less) Interconnection Customer Contact Information Name: Address: Alternative Contact Information
More informationThis generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.
This generator set has been designed to meet ISO 88 regulation. This generator set is manufactured in facilities certified to ISO 900. This generator set is available with CE certification. Enclosed product
More informationTechnical Explanation for Inverters
CSM_Inverter_TG_E_1_2 Introduction What Is an Inverter? An inverter controls the frequency of power supplied to an AC motor to control the rotation speed of the motor. Without an inverter, the AC motor
More informationThis generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.
This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001. This generator set is available with CE certification. Enclosed
More informationSECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2
SECTION 1. 600V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2 Soft Starters SECTION 2. LIQUID COOLED VFD I 3 Liquid Cooled
More informationBurden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM
Contents Section Page 1.0 Introduction 1 2.0 Specification 1-4 3.0 Installation 5-8 4.0 Programming 9-10 5.0 Menus 10-12 6.0 Fault Finding/Diagnostics 12-13 7.0 Communication 13 8.0 Setting Up 13-16 1.0
More informationThis generator set has been designed to meet ISO 8528 regulation. Enclosed product is tested according to EU noise legislation 2000/14/EC
This generator set has been designed to meet ISO 8528 regulation. This generator set is available with CE certification. Enclosed product is tested according to EU noise legislation 2000/14/EC 3 Phase
More informationMono Pumps PSS Eco 1-60
Mono Pumps PSS Eco 1-60 Page 1 of 12 Pump Unit Specification G60 Grifter (grinder pump) Specification Specification Topic Manufacturer Model Nominal flow rate Maximum Head capability Flow at Max. Head
More informationGENERATOR & SINGLE-FUNCTION PROTECTION
PGR-4300 Generator Ground-Fault Relay No CTs required Provides a simple method for tripping a groundfault condition on generators Use with 3- or 4-pole transfer switches Monitors neutral-to-ground integrity
More informationCHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM
106 CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 5.1 INTRODUCTION Inherent characteristics of renewable energy resources cause technical issues not encountered with conventional thermal,
More informationAGN Alternator Ratings and Overload
Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 013 - Alternator Ratings and Overload ALTERNATOR RATINGS AC synchronous generator (alternator) ratings are specified
More informationFeatures IN THIS CHAPTER
CHAPTER THREE 3Special Features IN THIS CHAPTER Motor Braking Regeneration Solutions Sharing the Power Bus: V Bus+ and V Bus- Current Foldback (I T Limit) Front Panel Test Points Resolver Alignment ➂ Special
More informationApplication Note CTAN #127
Application Note CTAN #127 Guidelines and Considerations for Common Bus Connection of AC Drives An important advantage of AC drives with a fixed DC is the ability to connect the es together so that energy
More informationDiesel generator set QSK78 series engine 2750kVA kVA 50 Hz
Specification sheet Diesel generator set QSK78 series engine 2750kVA - 3000kVA 50 Hz Description This Cummins commercial generator set is a fully integrated power generation system, providing optimum performance,
More informationMAGNETIC MOTOR STARTERS
Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors
More informationGrid Stability Analysis for High Penetration Solar Photovoltaics
Grid Stability Analysis for High Penetration Solar Photovoltaics Ajit Kumar K Asst. Manager Solar Business Unit Larsen & Toubro Construction, Chennai Co Authors Dr. M. P. Selvan Asst. Professor Department
More information