TeSys Motor Starter Solutions for the North American Market

Size: px
Start display at page:

Download "TeSys Motor Starter Solutions for the North American Market"

Transcription

1 TeSys Motor Starter Solutions for the North American Market Data Bulletin 8536DB0901

2 Tesys Motor Starter Solutions 8536DB0901 Table of Contents 11/2009 Table of Contents Introduction... 3 Overview of U.S. Standards and Regulations... 3 Certification Process... 3 Acceptance of Electrical Equipment in the U.S Structure of a Motor Starter in Accordance with UL508A... 4 Feeder Circuits and Branch Circuits... 4 Group Motor Installations... 5 Required Functions of Combination Starters... 6 Types of Combination Starter Constructions... 7 Disconnecting Means on a Feeder Circuit... 7 TeSys Motor Starters... 8 Disconnecting Means... 8 Industrial Machinery requirements (NFPA79 Section and UL508A Section 65, 66)... 8 TeSys Solutions... 9 UL98/ TeSys GS Disconnect Switches... 9 UL508 Type E Manual Self-Protected Combination Motor Controller, TeSys GV Self-Protected Combination Motor Controller, TeSys U UL508 Type F Combination Motor Controller, TeSys GV UL508 Group Motor Installations Manual Combination Motor Controller, TeSys GV UL508 Contactors TeSys K, D, and F Specifications UL248 TeSys DF Fuse Holder Characteristics Short Circuit Protection for Drives GV2P Controllers and ATV21 Drives Recommended Branch-Circuit Protection Devices GV2P or GV3P Controllers with ATV31 Drives GV2P or GV3P Controllers with ATV61 or ATV71 Drives Self-Protected Manual Combination Starter Values Meeting UL 508 Type E SCCR requirement in UL508A Specific Requirements for the Canadian Market Installation and Product Standards Certification Process Technical Differences between Canadian and U.S. Standards Average Full-Load Currents of Asynchronous Squirrel Cage Motors Schneider Electric All Rights Reserved

3 8536DB0901 TeSys Motor Starter Solutions 11/2009 Introduction Certification Process Introduction Overview of U.S. Standards and Regulations TeSys motor starters from Schneider Electric offer a wide range of solutions to meet your motor control and protection needs. This data bulletin contains information on applying TeSys motor starters in the United States and Canada. Figure 1 outlines the national standards governing electrical installations in the U.S. Figure 1: Standards Installation standard NEC = NFPA70 NOTE: UL508A is both an application and a product standard. Application standard NFPA79 UL508A Product UL489 UL98 UL508 UL508A UL508C UL512 UL248 UL1077 standard National Electrical Code (NEC), NFPA70: Electrical Installation NFPA79: Electrical Standard for Industrial Machinery UL508A: Industrial Control Panel UL489: Molded-Case Circuit Breaker, Molded-Case Switches UL508: Industrial Control Equipment UL508C: Power Conversion Equipment UL98: Enclosed and Dead-Front Switches UL512: Fuse Holders UL248: Low Voltage Fuses UL1077: Supplementary Protectors Certification Process Acceptance of Electrical Equipment in the U.S. A nationally recognized testing laboratory (NRTL) can list or certify the equipment according to these applications or product standards. NRTLs include UL, CSA, ETL, TUV, and others listed at the following website: The process for acceptance is as follows: 1. The equipment is listed or the manufacturer is certified: a. For mass production equipment, the industrial control panel itself is listed by an NRTL b. For custom or low-volume equipment, the manufacturer or supplier of the industrial control panel is certified 2. A local inspector under the authority having jurisdiction (AHJ) inspects and approves the electrical equipment and the installation prior to commissioning. The product listing or labeling may be used to assist in the inspection Schneider Electric All Rights Reserved 3

4 TeSys Motor Starter Solutions 8536DB0901 Structure of a Motor Starter in Accordance with UL508A Feeder Circuits and Branch Circuits 11/2009 Structure of a Motor Starter in Accordance with UL508A Feeder Circuits and Branch Circuits The feeder circuit includes all power conductors and components from the incoming feeder disconnect to the line side of the last branch short-circuit protection device (SCPD). The branch circuit includes all power conductors and components from the load side of the branch circuit SCPD to the controller load-side connections. Each branch circuit should be protected by its own disconnect and SCPD. Figure 2: Feeder Circuit and Branch Circuit Table 1: Circuit Components 1 Load provided in the field 14 2 Field wiring terminals 15 Control transformer ground (for 1000 VA max. control transformer) Control circuit devices and wiring Class 1 circuit isolated secondary circuit 3 Alternate field terminals 16 Solenoid or other control device provided in the field 4 Field wiring 17 Supplementary protection 5 Internal wiring of the power circuit 18 Class 2 transformer 6 Overload relay and heater elements 19 Class 2 circuit 7 Contactor or controller 20 8 Starter 21 9 Combination motor controller 22 Power transformer fuse branch circuit protection Power transformer for motor load and control protector Control circuit Class 1 circuit common control circuit 10 Branch circuit protection 23 Equipment ground and equipment ground terminal 11 Fused disconnect switch or circuit breaker 24 Bonding conductor bonding jumper 12 Control transformer 25 Grounding electrode conductor terminal 13 Control transformer fuse or supplementary protection 26 Grounding electrode conductor provided in the field Schneider Electric All Rights Reserved

5 8536DB0901 TeSys Motor Starter Solutions 11/2009 Structure of a Motor Starter in Accordance with UL508A Feeder Circuits and Branch Circuits Group Motor Installations In a group motor installation, a single disconnecting means and SCPD can be used for a group of motors. The specific rules are described in NEC Sections and A. Group installations are primarily used in the following applications: 1. Fractional hp motors NEC Section (A): For several motors, each rated 1 hp maximum on a branch circuit of 600 V maximum, a single SCPD not exceeding 15 A is permitted under the following circumstances: No single motor is rated greater than 6 A The branch short-circuit device rating marked on any controller (UL508 circuit breaker, switch or contactor) is not exceeded Appropriate motor overload protection is used 2. Smallest rated motor protected NEC Section (B): The SCPD is sized for the motor in the group with the lowest rating 3. Other group installations NEC Section (C): Two or more motors of any rating, or one or more motors and other loads, where all the following conditions are met: Each motor controller and overload protection device carries a Motor Group Installation listing. Each circuit breaker (if used) is listed and is of the inverse time type. The SCPD (fuse or circuit breaker) is sized for the largest motor plus the sum of all other motors and loads. The sizing of the SCPD (fuse or circuit breaker) does not exceed the maximum allowed for overload protection of the smallest motor. Appropriate overcurrent protection is provided for non-motor loads. B. The tap conductor sizing rules for group motor installations are governed by NEC Section (D). Conductors from the load side of the SCPD for the motor group must comply with one of the following: The ampacity is not less than that of the branch circuit conductors. The ampacity is not less than 1/3 that of the branch circuit conductors, and the length is not more than 7.5 m (25 ft). The ampacity is not less than 1/10 that of the SCPD for the motor group, the length is not more than 3 m (10 ft), and the manual motor controller is marked Suitable for Tap Conductor Protection in Group Installations. Products certified for motor grouping must carry the markings on the product label or instruction sheet required by NEC and UL (such as Suitable for Tap Conductor Protection in Group Installations ) Schneider Electric All Rights Reserved 5

6 TeSys Motor Starter Solutions 8536DB0901 Structure of a Motor Starter in Accordance with UL508A Required Functions of Combination Starters 11/2009 Required Functions of Combination Starters Combination starters are the most common type of packaged motor controllers. They are called combination because of their construction and combined functions. NEC Article 430 defines the required functions of combination starters. Underwriters Laboratories, Inc. (UL) specifies the tests and verifications that the components must pass before they can be listed as suitable for use for those functions. Figure 3 depicts the four component functions that compose a complete motor branch circuit as defined by the NEC. Figure 3: Required Functions of Combination Starters Motor Disconnect Motor Branch Circuit Protection Motor Controller Motor Overload Protection Schneider Electric All Rights Reserved

7 8536DB0901 TeSys Motor Starter Solutions 11/2009 Structure of a Motor Starter in Accordance with UL508A Types of Combination Starter Constructions Types of Combination Starter Constructions UL 508 is the UL safety standard for industrial control equipment. Part IV defines the component functions, construction, testing, and performance requirements of six styles of combination starters. Each of the six styles meets the requirements of NEC Article 430 for the motor disconnecting means, the motor branch circuit short-circuit and ground-fault protection, the motor controller, and the motor overload (OL) protection. Each provides adequate protection against fire or personal injury under fault conditions. The UL 508 type designations are differentiated by the actual components used to protect the motor branch circuit as illustrated in Table 2. Table 2: UL Combination Starter Type Designations Traditional Combination Starters from the 1980s and earlier UL Combination Starter Type A B C D Device Used for Component Function Disconnect UL 98 Manual Disconnect Branch Circuit Protection UL 248 Fuses UL 508 Motor Short Circuit Protector UL 489 Inverse Time Circuit Breaker UL 489 Instantaneous Trip Circuit Breaker Motor Controller UL 508 Magnetic or Solid State Controller Motor OL Relay UL 508 Motor Overload Relay UL98 Disconnect switch: TeSys GS UL 248 Fuses UL508 Controller: TeSys LC UL 508 Overload relay: TeSys LR UL489 Circuit Breaker: Compact NSF or Powerpact UL508 Controller: TeSys LC UL 508 Overload relay: TeSys LR Recognized 1990 E UL 508 Self-Protected Combination Controller UL 508 Type E Self-Protected Combination Starter: TeSys U UL 508 Type E Manual Self-Protected Combination Starter: TeSys GV.P Recognized 2002 F UL 508 Manual Self-Protected Combination Controller UL 508 Magnetic or Solid State Controller UL 508 Manual Self- Protected Combination Controller UL 508 Type F Combination Starter: TeSys GV + LC1D Disconnecting Means on a Feeder Circuit The disconnecting means on the feeder circuit, ahead of the last SCPD, must be a UL98 disconnect switch or UL489 circuit breaker. UL508 switches or motor protectors are not acceptable. On the branch circuit, the following are permitted as the disconnecting means when installed between the final motor branch circuit short circuit protection and the motor: any UL508 switch, suitable as a motor disconnect (according to NEC Section ), that is used to start and stop a motor, a manual motor controller that is suitable as a motor disconnect (according to NEC Section ) Schneider Electric All Rights Reserved 7

8 TeSys Motor Starter Solutions 8536DB0901 Disconnecting Means TeSys Motor Starters 11/2009 TeSys Motor Starters Figure 4: Power Supply Circuit or TeSys GS UL98 or Compact NSF or Powerpact UL489 Compact NSF or Powerpact or C60 UL489 LC1D if needed M M M M M M Other Loads TeSys U UL508 Type E TeSys GV2P + LC1D GV3P + LC1D UL508 Type F TeSys GV2ME + LC1D UL508 Group Installation TeSys GV2P or GV3P UL508 Type E + LC1D if needed + ATV drives Disconnecting Means Industrial Machinery requirements (NFPA79 Section and UL508A Section 65, 66) A disconnecting means must be provided for each incoming supply (branch) circuit, and must open each ungrounded conductor of the supply circuit. This disconnecting means could be one of the following: UL489 inverse-time or instantaneous-trip circuit breaker UL489 molded-case switch UL98 switch unit, either open type or enclosed For a motor starter, the disconnecting means could be a UL508 type E selfprotected combination motor controller. The sizing of the disconnecting means must meet UL508A Section A UL508 manual motor controller or switch (such as the TeSys Vario device) is certified for use on the load side of a motor's branch circuit protection. This is commonly called a load break switch. These requirements cover industrial control panels for industrial machinery (NFPA , Electrical Standard for Industrial Machinery). The following types of machines are identified as industrial machinery: Metalworking machine tools, including machines that cut or form metal Plastics machinery, including injection molding, extrusion, blow molding, specialized processing, thermoset molding, and size reduction machines Wood machinery, including woodworking, laminating, and sawmill machines Assembly machines Material handling machines, including industrial robots and transfer machines Inspection and testing machines, including coordinate measuring and inprocess gauging machines Schneider Electric All Rights Reserved

9 8536DB0901 TeSys Motor Starter Solutions 11/2009 TeSys Solutions UL98/489 An operating mechanism for the disconnecting means must have the following characteristics: Readily accessible when the enclosure doors are in the open or closed position Installed so that its operation is not restricted by the enclosure door while in the open position Operable independent of the door position without the use of accessory tools or devices Lockable in the Off position independent of the door position and when the mechanism is locked, the disconnect cannot be closed The UL98 TeSys GS disconnect switches meet these requirements. The TeSys GS1 disconnect switch requires the use of operating mechanism GS1AD010 and GS1AD020. The TeSys GS2 disconnect switch provides these features (effective in the fourth quarter of 2009). The UL489 NSF and PowerPact Circuit breakers meet these requirements when used in conjunction with a Class 92 or 91L operating mechanism and 91LH79 handle. TeSys Solutions UL98/489 TeSys GS Disconnect Switches Table 3: TeSys GS Horsepower and SCCR Ratings Ampere Rating (A): General Purpose Rated Enclosure Horsepower Rating (hp) 600 Vac (ka) Fuse Type Max. Fuse Rating (A) Wire Range (AWG) Catalog Number 3Ø Vac Vdc 220/ / [1] 250 [1] CC GS1DDU J GS1DU CC GS2EEU J GS2EU J GS2GU J /0 GS2JU J /0 GS2MU J x 2 AWG 600kcmil GS2QU J x 2 AWG 600kcmil GS2SU L x 2 AWG 600kcmil GS2TU3 [1] 2 poles in series Schneider Electric All Rights Reserved 9

10 TeSys Motor Starter Solutions 8536DB0901 TeSys Solutions UL508 Type E 11/2009 Table 4: UL508 TeSys Vario Load Break Switch Horsepower Ratings Ampere Rating (A): General Purpose Rated Enclosure Horsepower Rating (hp) 3Ø Vac 1Ø Vac V V V V V V V V V6 Catalog Number UL508 Type E Manual Self-Protected Combination Motor Controller, TeSys GV Manual Self-Protected Combination Starter Meeting UL508 Type E UL File E Table 5: TeSys GV2P Horsepower and SCCR Ratings In combination with line spacer GV2GH7 (stand-alone starters) or GV1G09 and GV2G busbars (multiple starters) Standard Motor 50/60 Hz (hp) 1Ø 3Ø 120 V 240 V 200 V 240 V 480 V 600 V Associated Cable, AWG 75 C, Cu Manual Self-Protected Starter Overload Trip Range (A) 10 GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P SCCR (ka) 480Y/277V Schneider Electric All Rights Reserved

11 8536DB0901 TeSys Motor Starter Solutions 11/2009 TeSys Solutions UL508 Type F Table 6: TeSys GV3P Horsepower and SCCR Ratings In combination with line spacer GV3G66 and GVAM11 (magnetic trip unit) for stand-alone starters Standard Motor 50/60 Hz (hp) 1Ø 3Ø 120V 240 V 200 V 240 V 480 V 600 V Associated Cable, AWG 75 C, Cu Manual Self-Protected Starter Overload Trip Range (A) 480Y / 277 V SCCR (ka) GV3P GV3P GV3P GV3P GV3P GV3P GV3P Y / 347 V Self-Protected Combination Motor Controller, TeSys U Meeting UL508 Type E UL File E Table 7: TeSys U Horsepower and SCCR Ratings In combination with line spacer LU9SP0 (stand-alone starters) or GV1G09 and GV2G busbars (multiple starters) Standard Motor 50/60 Hz (hp) 1Ø 3Ø 120 V 240 V 200 V 240 V 480 V 600 V UL508 Type F Associated Cable, AWG 75 C, Cu Self-Protected Combination Starter Overload Trip Range (A) 480Y / 277 V SCCR (ka) 480 V with LUALB1 Limiter LUB LUB When Limiter block LUALB1 is used, SCCR apply for stand alone starter or with GV1G09 and GV2G busbar for multistarter 600 V with LUALB1 Limiter Combination Motor Controller, TeSys GV Manual Self-Protected Combination Starter Meeting UL508 Type F UL File E Table 8: TeSys GV2P Horsepower and SCCR Ratings In combination with line spacer GV2GH7 (stand-alone starters) or GV1G09 and GV2G busbars (multiple starters) Standard Motor 50/60 Hz (hp) Associated Cable, AWG 75 C, Cu Manual Self-Protected Starter Overload Trip Range (A) Type of Contactor Required 1Ø 3Ø 120 V 240 V 200 V 240 V 480 V 600 V 10 GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P LC1 or D GV2P LC1 or D GV2P LC1D25 or D GV2P LC1D25 or D32 SCCR (ka) 480Y / 277 V 2009 Schneider Electric All Rights Reserved 11

12 TeSys Motor Starter Solutions 8536DB0901 TeSys Solutions UL508 Group Motor Installations 11/2009 Table 9: TeSys GV3P Horsepower and SCCR Ratings In combination with line spacer GV3G66 and GVAM11 (magnetic trip unit) for stand-alone starters Standard Motor 50/60 Hz (hp) 1Ø 3Ø 120V 240V 200V 240V 480V 600V Associated Cable, AWG 75 C, Cu Manual Self- Protected Starter Overload Trip Range (A) Type of Contactor Required SCCR (ka) 480Y/277V 600Y/347V GV3P LC1D GV3P LC1D GV3P LC1D GV3P LC1D GV3P LC1D40A/ 50A/65A GV3P LC1D50A/65A GV3P LC1D65A/ UL508 Group Motor Installations Manual Combination Motor Controller, TeSys GV GV2ME: UL File E GV2RT: UL pending, CSA accepted (MC , Report , Project ) Table 10: TeSys GV2ME or GV2RT Horsepower and SCCR Ratings In association with LC1D contactors, suitable for Group Installation when protected by fuses or a circuit breaker (including multi starter with GV1G09 or GV2G05 blocks plus GV2G busbars) Standard Motor 50/60 Hz (hp) 1Ø 3Ø 120 V 240 V 200 V 240 V 480 V 600 V Associated Cable, AWG 75 C, Cu Manual Motor Starter Overload Trip Range (A) 10 GV2ME GV2ME GV2ME03 GV2RT03 GV2ME04 GV2RT04 GV2ME05 GV2RT05 GV2ME06 GV2RT06 GV2ME07 GV2RT07 GV2ME08 GV2RT08 GV2ME10 GV2RT10 GV2ME14 GV2RT14 GV2ME16 GV2RT16 GV2ME20 GV2RT GV2ME21 GV2RT GV2ME GV2ME Contactor 240 / 480 V LC1 or D18 LC1 or D18 LC1D25 or D32 LC1D25 or D32 LC1D25 or D32 600Y / 347 V SCCR (ka) 480 V with GV1L3 Limiter Contactor LC1D32 or D38 LC1D32 or D38 LC1D32 or D38 LC1D32 or D38 LC1D32 or D V with LA9LB920 Limiter Schneider Electric All Rights Reserved

13 8536DB0901 TeSys Motor Starter Solutions 11/2009 TeSys Solutions UL508 Group Motor Installations Table 11: TeSys GV2P Horsepower and SCCR Ratings In association with LC1D contactors, suitable for Group Installation when protected by fuses or a circuit breaker (including multi starter with GV1G09 or GV2G05 blocks plus GV2G busbars) Standard Motor 50/60 Hz (hp) 1Ø 3Ø 120 V 240 V 200 V 240 V 480 V 600 V Associated Cable, AWG 75 C, Cu 10 Manual Motor Starter Overload Trip Range (A) Contactor 480 V GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P GV2P LC1 or D GV2P LC1 or D GV2P LC1D25 or D GV2P LC1D25 or D GV2P LC1D25 or D32 SCCR (ka) 600Y / 347 V with GV1L3 Limiter 480 V Contactor with LA9LB920 Limiter LC1D32 or D LC1D32 or D LC1D32 or D LC1D32 or D LC1D32 or D V Table 12: TeSys GV3P Horsepower and SCCR Ratings In association with LC1D contactors, suitable for Group Installation, when protected by fuses or a circuit breaker Standard Motor 50/60 Hz (hp) Associated Overload SCCR (ka) Manual 1Ø 3Ø Cable, AWG Trip Range Contactor Motor Starter 480Y / 600Y / 120V 240V 200V 240V 480V 600V 75 C, Cu (A) 277 V 347 V GV3P LC1D GV3P LC1D GV3P LC1D GV3P LC1D GV3P LC1D40A/50A/65A GV3P LC1D50A/65A GV3P LC1D65A/ These values are derived from the UL508 Type F certification (E164871) Schneider Electric All Rights Reserved 13

14 TeSys Motor Starter Solutions 8536DB0901 TeSys Solutions UL508 Contactors 11/2009 UL508 Contactors TeSys K, D, and F Specifications Table 13: TeSys K Ratings Standard Motor 50/60 Hz (hp) Associated Cable, AWG 75 C, Cu Max. Inductive AC3 Current (A) Max. Continuous Current (A) 1 Ø 3 Ø Contactor 115 V 230/240 V 200/208 V 230/240 V 460/480 V 575/600 V LC1K LC1K LC1K12 Table 14: TeSys D Ratings Standard Motor 50/60 Hz Associated Cable 75 C, Cu Max. Inductive AC3 Current (A) Max. Continuous Current (A) Type of Contactor Required 1 Ø 3 Ø 115 V 230/240 V 200/208 V 230/240 V 460/480 V 575/600 V AWG 9 20 LC1D AWG LC AWG LC1D AWG LC1D AWG LC1D AWG LC1D40A AWG LC1D50A AWG LC1D65A AWG LC1D mcm LC1D mcm LC1D mcm LC1D150 High-Fault Short-Circuit Rating Suitable For Use On A Circuit Capable Of Delivering Not More Than 100,000 rms Symmetrical Amperes, 600 Volts Maximum when protected by Class J time-delay fuse sized not larger than 225% of motor FLA: LC1D09,, D18, D25, D32, D40, D56, D65, D80, D115, D Schneider Electric All Rights Reserved

15 8536DB0901 TeSys Motor Starter Solutions 11/2009 TeSys Solutions UL508 Contactors Table 15: UL/CSA Lighting 575 / 600V Device Ballast Tungsten LC1D09 (AC coil only) 20 A 20 A LC1 (AC coil only) 25 A 20 A LC1D18 (AC coil only) 32 A 25 A LC1D25 (AC coil only) 40 A 40 A LC1D32 (AC coil only) 50 A 50 A LC1DT20 (AC coil only) 20 A 20 A LC1DT25 (AC coil only) 25 A 25 A LC1DT32 (AC coil only) 32 A 32 A LC1DT40 (AC coil only) 40 A 40 A LC1D40A 60 A 60 A LC1D50A 70 A 70 A LC1D65A 80 A 70 A LC1D80, LC1D A 100 A LC1D115, LC1D A 115 A LC1D150, LC1D A 150 A Table 16: Elevator Duty Ratings (hp) Catalog 1 Ø 3 Ø Number 230/240 V 200/208 V 230/240 V 460/480 V 575/600 V LC1 (AC) LC1D25 (AC) LC1D32 (AC) 5 10 LC1D40A (AC) LC1D50A (AC) LC1D65A (AC) LC1D LC1D95 LC1D115 LC1D Table 17: Definite Purpose Ratings, 3-Phase, Breaking All Lines Hermetic Refrigeration Compressor Device FLA LRA 240V 480V 600V LC1D09 (AC coil only) LC1 (AC coil only) LC1D18 (AC coil only) LC1D25 (AC coil only) LC1D32 (AC coil only) LC1D40A LC1D50A LC1D65A LC1D LC1D95 LC1D LC1D Schneider Electric All Rights Reserved 15

16 TeSys Motor Starter Solutions 8536DB0901 TeSys Solutions UL508 Contactors 11/2009 Table 18: TeSys F Ratings Standard Motor 50/60 Hz (hp) Associated Cable 75 C, Cu Max. Inductive AC3 Current (A) Max. Continuous Current (A) Contactor [1] 3Ø 200/208 V 230/240 V 460/480 V 575/600 V /0 AWG LC1F /0 AWG LC1F /0 AWG LC1F /0 AWG LC1F AWG 300 MCM LC1F AWG 300 MCM LC1F AWG 500 MCM LC1F x 2 AWG 600 MCM LC1F x 2 AWG 600 MCM LC1F x 2 AWG 600 MCM LC1F800 Table 19: UL/CSA Lighting 460 / 480V 3-Pole or 4-Pole Contactor Tungsten Rating Ballast Rating LC1F A 115A LC1F A 150A LC1F A 200A LC1F A 265A LC1F A 300A Table 20: Elevator Duty Ratings (hp) Contactor 1Ø 3Ø 230/240 V 200/208 V 230/240 V 460/480 V 575/600 V LC1F LC1F LC1F LC1F LC1F LC1F Table 21: Definite Purpose Ratings, 3-Phase, Breaking All Lines Hermetic Refrigeration Compressor Contactor FLA LRA 240V 480V 600V LC1F LC1F LC1F LC1F LC1F LC1F LC1F LC1F LC1F Schneider Electric All Rights Reserved

17 8536DB0901 TeSys Motor Starter Solutions 11/2009 Short Circuit Protection for Drives UL248 TeSys DF Fuse Holder Characteristics UL248 TeSys DF Fuse Holder Characteristics Table 22: Fuse Holder Ratings Fuse Holder Standards Electrical Ratings in Accordance with UL512 DF10 DFCC DF14 DF22 IEC, UL (UL Recognized) IEC, UL (UL Listed) IEC, UL (UL Recognized) IEC, UL (UL Recognized) AC: For catalog numbers US10 and CMS10: 30 A, 800 Vac max, 200 ka current withstand DC: For catalog numbers US10 and CMS10: 30 A, 1000 Vdc max, 100 ka current withstand AC: 30 A, 800 Vac max, 200 ka current withstand DC: 30 A, 1000 Vdc max, 100 ka current withstand Voltage: 800 Vac, 1000 Vdc Amperes: CMS14 and US14 = 50 A max.; CMS22 and US22 = 125 A max. Voltage: 800 Vac, 1000 Vdc Amperes: CMS14 and US14 = 50 A max.; CMS22 and US22 =125 A max. Short Circuit Protection for Drives Drives are not rated for group motor applications. When a variable-speed drive is connected to a single-motor circuit, the branch-circuit protection provided must be of the type and size specified by the manufacturer's instructions that come with the drive. When the instructions do not specify the type and size, a branch-circuit fuse or inverse-time circuit breaker must be used and must be sized based on the input current rating of the drive multiplied by the percentage from UL508A Table Schneider Electric tested drives in combination with the following: Fuses UL489 circuit breakers GV2P and GV3P UL508 Type E self-protected, manual combination starters The optimized solution for drives is the combination with UL508 Type E, TeSys GV self-protected, manual combination starters. This combination was tested for the following drives: ATV21 at 22 ka / 480 V ATV31, ATV61, and ATV71 at 65 ka / 480 V 2009 Schneider Electric All Rights Reserved 17

18 TeSys Motor Starter Solutions 8536DB0901 Short Circuit Protection for Drives GV2P Controllers and ATV21 Drives 11/2009 GV2P Controllers and ATV21 Drives Recommended Branch-Circuit Protection Devices Table 23: Circuit Breakers and Manual Motor Controllers for 208/230 V ATV21 Drives Drive Catalog No. Maximum Size Protective Device for SCCR SCCR, (ka) Thermal-Magnetic Circuit Breakers [1], [2] Manual Motor Controllers [3] Open [4] Enclosed [5] 208 V ATV21H075M3X FAL34015 HDL36015 GJL36015 GV2P ATV21H075M3X FAL34015 HDL36015 GJL36015 GV2PI ATV21HU15M3X FAL34015 HDL36015 GJL36015 GV2P ATV21HU22M3X FAL34020 HDL36020 GJL36020 GV2P ATV21HU40M3X FAL34040 HDL36040 GJL36040 GV2P ATV21HU55M3X FAL34050 HDL36050 GJL36050 GV2P ATV21HU75M3X FAL34070 HDL36070 GJL36070 GV2P ATV21HD11M3X FAL34100 HDL36100 GJL ATV21HD15M3X HDL ATV21HD18M3X JDL ATV21HD22M3X JDL ATV21HD30M3X JDL V ATV21H075M3X FAL34015 HDL36015 GJL36015 GV2P ATV21H075M3X FAL34015 HDL36015 GJL36015 GV2PI ATV21HU15M3X FAL34015 HDL36015 GJL36015 GV2P ATV21HU22M3X FAL34020 HDL36020 GJL36020 GV2P ATV21HU40M3X FAL34035 HDL36035 GJL36035 GV2P ATV21HU55M3X FAL34045 HDL36045 GJL36045 GV2P ATV21HU75M3X FAL34060 HDL36060 GJL36060 GV2P ATV21HD11M3X FAL34090 HDL36090 GJL ATV21HD15M3X HDL ATV21HD18M3X HDL ATV21HD22M3X JDL ATV21HD30M3X JDL [1] Square D Type FA, HD, or JD; or Merlin Gerin Type GJL. The third character of the Square D circuit breaker catalog number may be F (bus bar), L (line/load side lugs), M (line side lugs), or P (load side lugs). The fifth character of the Square D circuit breaker catalog number may be a 4 (480 V) or a 6 (600 V). [2] Square D circuit breakers with the following prefixes are also covered at the same amperage rating: FH, HG, HJ, HL, JG, JJ, JL, LH, and MH. These prefixes indicate higher interrupting ratings. [3] GV2 self-protected control device, UL 508 Type E. [4] Type 1 open drive with a conduit box installed. [5] Drive installed in a metallic enclosure, 8640 in³ minimum Schneider Electric All Rights Reserved

19 8536DB0901 TeSys Motor Starter Solutions 11/2009 Short Circuit Protection for Drives GV2P Controllers and ATV21 Drives Table 24: Circuit Breakers and Manual Motor Controllers for 480/460 V ATV21 Drive Drive Catalog No. Maximum Size Protective Device for Short-circuit Current Ratings SCCR (ka) Type 1 Metallic Enclosure Minimum Thermal-Magnetic Circuit Breakers [1], [2] Manual Motor Controllers [3] Open [4] Enclosed [5] Volume (in³) 480 Y/277 V ATV21H075N4 GV2P ATV21H075N4 GV2P ATV21HU15N4 GV2P ATV21HU22N4 GV2P ATV21HU30N4 GV2P ATV21HU55N4 GV2P ATV21HU75N4 GV2P ATV21HD11N4 GV2P ATV21HD15N4 GV2P ATV21HD18N4 GV2P ATV21HD22N4 22 ATV21HD30N V ATV21H075N4 FAL34015 HDL36015 GJL ATV21HU15N4 FAL34015 HDL36015 GJL ATV21HU22N4 FAL34015 HDL36015 GJL ATV21HU30N4 FAL34020 HDL36020 GJL ATV21HU55N4 FAL34025 HDL36025 GJL ATV21HU75N4 FAL34030 HDL36030 GJL ATV21HD11N4 FAL34045 HDL36045 GJL ATV21HD15N4 HDL34060 HDL36060 GJL ATV21HD18N4 HDL34070 HDL36070 GJL ATV21HD22N4 JDL34090 HDL36090 GJL ATV21HD30N4 JDL ATV21HD37N4 HDL ATV21HD45N4 HDL ATV21HD55N4 JDL [1] Square D Type FA, HD, or JD; or Merlin Gerin Type GJL. The third character of the Square D circuit breaker catalog number may be F (bus bar), L (line/load side lugs), M (line side lugs), or P (load side lugs). The fifth character of the Square D circuit breaker catalog number may be a 4 (480 V) or a 6 (600 V). [2] Square D circuit breakers with the following prefixes are also covered at the same amperage rating: FH, HG, HJ, HL, JG, JJ, JL, LH, MH. These prefixes indicate higher interrupting ratings. [3] GV2 self-protected control device, UL 508 Type E. [4] Type 1 open drive with a conduit box installed. [5] Drive installed in a Type 1 metallic enclosure, minimum volume as noted Schneider Electric All Rights Reserved 19

20 TeSys Motor Starter Solutions 8536DB0901 Short Circuit Protection for Drives GV2P or GV3P Controllers with ATV31 Drives 11/2009 GV2P or GV3P Controllers with ATV31 Drives Table 25: Input Line Voltage Type E Self-Protected Manual Combination Motor Starter Selection for 65 ka SCCR with a 3% Line Reactor hp Drive Catalog Number Self-Protected Control Devices [1] Type 12 Metallic Enclosure Min. Volume (in³) 0.25 ATV31H018M3X GV2P07 with GV2GH ATV31H037M3X GV2P08 with GV2GH ATV31H055M3X GV2P10 with GV2GH ATV31H075M3X GV2P10 with GV2GH7 [2] ATV31HU11M3X GV2P14 with GV2GH ATV31HU15M3X GV2P14 with GV2GH7 [2] ATV31HU22M3X GV3P18 with GV3G66 and GVAM11 GV3P13 with GV3G66 and GVAM11 [2] /240 Vac 3Ø ATV31HU30M3X GV3P18 with GV3G66 and GVAM11 [2] ATV31HU40M3X GV3P25 with GV3G66 and GVAM ATV31HU55M3X GV3P40 with GV3G66 and GVAM11 GV3P32 with GV3G66 and GVAM11 [2] ATV31HU75M3X GV3P50 with GV3G66 and GVAM ATV31HD11M3X GV3P65 with GV3G66 and GVAM ATV31H037N4 GV2P07 with GV2GH ATV31H055N4 GV2P07 with GV2GH7 [2] ATV31H075N4 GV2P08 with GV2GH ATV31HU11N4 GV2P08 with GV2GH7 [2] ATV31HU15N4 GV2P10 with GV2GH7 [2] ATV31HU22N4 GV2P14 with GV2GH ATV31HU30N4 GV2P14 with GV2GH7 [2] Y / 277 Vac 3Ø 5 ATV31HU40N4 GV3P13 with GV3G66 and GVAM11 [2] ATV31HU55N4 GV3P18 with GV3G66 and GVAM11 [2] ATV31HU75N4 GV3P25 with GV3G66 and GVAM11 [2] ATV31HD11N4 GV3P32 with GV3G66 and GVAM11 [2] ATV31HD15N4 GV3P40 with GV3G66 and GVAM11 [2] 4896 [1] All specified GV accessories must accompany the GV motor control device to retain the Type E rating and to meet the specified SCCR. [2] When sizing the GV at 208 V or 220 V: if the required current exceeds the GV current rating, use the next higher approved combination Schneider Electric All Rights Reserved

21 8536DB0901 TeSys Motor Starter Solutions 11/2009 Short Circuit Protection for Drives GV2P or GV3P Controllers with ATV61 or ATV71 Drives GV2P or GV3P Controllers with ATV61 or ATV71 Drives Self-Protected Manual Combination Starter Values Meeting UL 508 Type E Altivar 61 and 71, V Ratings A manual motor protector may be used as an overcurrent protective device (OCPD) for Altivar 61 and 71 drives with an input line voltage of V and installed in a Type 12 metallic enclosure with a 3% minimum line reactor. Table 26 shows the maximum current value and associated manual motor protector catalog number required for a 65 ka SCCR. The UL 508 Type E rating requires the addition of the following line side insulating barriers: GV2GH7 for GV2P GV3G66 and GVAM11 for GV3P Table 26: Altivar 61 and 71, V Drives Installed in Type 12 Metallic Enclosures, with 3% Minimum Line Reactor hp Catalog Number Minimum Enclosure Volume (in³) [1] OCPD Type 0.5 ATV71H037M GV2P08 1 ATV61H075M3 ATV71H075M GV2P ATV61HU15M3 ATV71HU15M3 ATV61HU22M3 ATV71HU22M3 ATV61HU30M3 ATV71HU30M3 ATV61HU40M3 ATV71HU40M3 ATV61HU55M3 ATV71HU55M3 ATV61HU75M3 ATV71HU75M3 ATV61HD11M3X ATV71HD11M3X 1600 GV2P14 [2] 1920 GV3P13 [2] or GV3P GV3P18 [2] 1920 GV3P25 [2] 2880 GV3P32 [2] or GV3P GV3P40 [2] or GV3P GV3P50 [2] 20 ATV61HD15M3X ATV71HD15M3X 5760 GV3P65 [3] [1] Minimum enclosure volume that permits the stated SCCR. Application-specific thermal requirements may require a larger enclosure. [2] For systems at voltages lower than 240 V, use the next higher OCPD and associated drive combination if the required current exceeds the OCPD current rating listed in this table. [3] This combination is valid on 240 V systems only. Do not apply on systems with lower voltage ratings Schneider Electric All Rights Reserved 21

22 TeSys Motor Starter Solutions 8536DB0901 Short Circuit Protection for Drives GV2P or GV3P Controllers with ATV61 or ATV71 Drives 11/2009 Altivar 61 and V Ratings A manual motor protector may be used as an OCPD for Altivar 61 and 71 drives with an input line voltage of 480 Y / 277 V and installed in a Type 12 metallic enclosure with a 3% minimum line reactor. Table 27 shows the maximum current value and associated manual motor protector catalog number required for a 65 ka SCCR. The UL 508 Type E rating requires the addition of the following line side insulating barriers: GV2GH7 for GV2P GV3G66 and GVAM11 for GV3P Table 27: Altivar 61 and Y/277 V Drives Installed in Type 12 Metallic Enclosures, with 3% Minimum Line Reactor hp Catalog Number Minimum Enclosure Volume (in³) [1] OCPD Type ATV61H075N4 ATV71H075N4 ATV61HU15N4 ATV71HU15N4 ATV61HU22N4 ATV71HU22N4 ATV61HU30N4 ATV71HU30N4 ATV61HU40N4 ATV71HU40N4 ATV61HU55N4 ATV71HU55N4 ATV61HU75N4 ATV71HU75N4 ATV61HD11N4 ATV71HD11N4 ATV61HD15N4 ATV71HD15N4 ATV61HD18N4 ATV71HD18N4 ATV61HD22N4 ATV71HD22N GV2P GV2P GV2P GV2P GV3P GV3P18 or GV3P GV3P GV3P32 or GV3P GV3P40 or GV3P GV3P40 or GV3P GV3P50 40 ATV61HD30N4 ATV71HD30N GV3P65 [1] Minimum enclosure volume that permits the stated SCCR. Application-specific thermal requirements may require a larger enclosure Schneider Electric All Rights Reserved

23 8536DB0901 TeSys Motor Starter Solutions 11/2009 Short Circuit Protection for Drives SCCR requirement in UL508A SCCR requirement in UL508A NEC Article 409, NFPA 79, and UL508A require that the SCCR be marked on all control panels. The final builder or assembler of the equipment inside the panel is responsible for providing the SCCR for the overall panel, determined by one of the following three options: Testing each panel construction and recording the construction in the follow-up procedure. With the multitude of possible product combinations within a panel, this option can require much testing and maintenance. Third party testing and certification may also be required. Purchasing previously tested constructions (combinations) from a major supplier of equipment that can be tabulated in the control or machine panel builder's procedure. Once you have all the component ratings, either use an outside service or UL 508A, Supplement SB. Using a method described in UL 508A, Supplement SB. Important: Using the interrupting rating of the main OCPD for the panel is not an acceptable practice! WARNING INADEQUATE SHORT CIRCUIT INTERRUPTING RATING Do not use the interrupting rating of the main OCPD as the SCCR rating for the controller. Failure to follow these instructions can result in death, serious injury, or equipment damage. By using discrete components to assemble a combination motor controller within a panel, and providing UL508A combination motor controller data (some listed under the Square D brand name), Schneider Electric offers solutions for achieving an SCCR that is higher than the rating of the lowestrated individual discrete component. These combinations can be found at the following websites: Square D UL508A website: 1FB03C85256EBE0047F560/$file/ul508aFrameset.htm (In the What s New area, select Fully UL508A Tested and Approved Combination Spreadsheets Now Available.) UL s UL508A Combination Motor Controller website: Schneider Electric All Rights Reserved 23

24 TeSys Motor Starter Solutions 8536DB0901 Specific Requirements for the Canadian Market Installation and Product Standards 11/2009 Specific Requirements for the Canadian Market Installation and Product Standards Certification Process Technical Differences between Canadian and U.S. Standards The installation standard in Canada is the Canadian Electrical Code (CEC). The CEC and the NEC are similar but not 100% equivalent. The same is true for the CSA standards and corresponding UL standards (see Table 28). Some of the major differences are detailed below. As in the U.S., Nationally Recognized Testing Laboratories (such as CSA, ETL, TUV, and UL) are able to certify equipment according to these CSA standards. Refer to Acceptance of Electrical Equipment in the U.S. on page 3. The procedure is the same. Some examples of differences between the Canadian and U.S. standards that currently apply to motor starters are listed below. (Note that the TeSys product line is designed for compliance and capatibility with both the UL and the CSA requirements.) Type E combination motors starters are also recognized in Canada but Type F currently are not. Type E applications don't require the use of large spacing adapters as in the U.S. Group installation is recognized but the rules to define the common branch-circuit protection setting is quite different. Industrial control panels must meet CSA C22.2 No. 14 Elevator equipment appliances must comply with the specific CSA Nr. B44.1 standard. Product marking requirements differ slightly. Table 28: Comparison of CSA and UL Standards Standard Name CSA Standard UL Standard Enclosed and Dead-Front Switches CSA C22.2 No. 4 UL98 Low-Voltage Fuses: Part 1: General Requirements CSA C22.2 No. 248 UL248 Molded-Case Circuit Breakers, Molded-Case Switches, and CSA C22.2 No. 5 UL489 Circuit-Breaker Enclosures Industrial Control Equipment CSA C22.2 No. 14 UL508 Elevator Equipment CSA No. B44.1 Partially UL Schneider Electric All Rights Reserved

25 8536DB0901 TeSys Motor Starter Solutions 11/2009 Average Full-Load Currents of Asynchronous Squirrel Cage Motors Installation and Product Standards Average Full-Load Currents of Asynchronous Squirrel Cage Motors These values conform to the NEC. They vary according to the type of motor, its polarity, and the manufacturer Schneider Electric All Rights Reserved 25

26 Tesys Motor Starter Solutions Data Bulletin Schneider Electric and TeSys are trademarks or registered trademarks of Schneider Electric. Other trademarks used herein are the property of their respective owners. Schneider Electric USA 8001 Knightdale Blvd. Knightdale, NC SquareD ( ) Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 8536DB / Schneider Electric All Rights Reserved

Short-Circuit Current Ratings

Short-Circuit Current Ratings UL 508 Type E Combination Motor Controller, TeSys GV Combination Meeting UL 508 Type E, UL File E164871 Table 2: TeSys GV2P Horsepower and SCCR Ratings In combination with line spacer GV2GH7 (stand-alone

More information

Multistandard offer for OEM applications. Single solution source for business without borders

Multistandard offer for OEM applications. Single solution source for business without borders Multistandard offer for OEM applications Single solution source for business without borders 1 Improving customer satisfaction means producing industrial machines that are compliant to international standards,

More information

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features Standard Features Table : Standard Features GV2ME GV2P GV3P GV7RE/GV7RS 0. to 32 A Up to 20 hp @ 460 V 0 SCCR @ 480 V Push Button Operator 0. to 30 A Up to 5 hp @ 460 V 50 SCCR @ 480 V Rotary Handle Operator

More information

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction Introduction Introduction Schneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection

More information

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

ECET Circuit Design Motor Loads. Branch Circuits. Article 210 ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Circuit Design Motor Loads Branch Circuits Article 210 210.1 Scope This article covers branch circuits except for those that supply

More information

PowerPact Circuit Breakers for Control Panel Disconnects Class 0611

PowerPact Circuit Breakers for Control Panel Disconnects Class 0611 Data Bulletin 0611DB0402 R04/16 05/2016 Replaces 0611DB0401 R11/11 PowerPact Circuit Breakers for Control Panel Disconnects Class 0611 Retain for future use. Introduction Certifications The electrical

More information

Devices for Branch Circuits and Feeders

Devices for Branch Circuits and Feeders Devices for Branch Circuits and Feeders Branch Circuit Overcurrent Protective Devices and s Fusible Solutions: When selecting fusible overcurrent protective devices, the type of fuse holder or switch is

More information

Certi cation Record INDUSTRIAL CONTROL EQUIPMENT Motor Controllers Magnetic

Certi cation Record INDUSTRIAL CONTROL EQUIPMENT Motor Controllers Magnetic Certi cation Record Customer Schneider Electric USA, Inc. Square D Raleigh (Knightdale) Plant, 8001 Knightdale Blvd Knightdale NC USA 27545 Class 3211 04 INDUSTRIAL CONTROL EQUIPMENT Motor Controllers

More information

Bussmann series Quik-Spec Power Module Switch elevator disconnect

Bussmann series Quik-Spec Power Module Switch elevator disconnect Supersedes January 2016 Agency information UL 98 enclosed and dead-front switch - Guide WIAX, WIAX7 (Canada), File E182262 culus, NEMA 1, UL 50, Listed enclosure cul per Canadian Standards C22.2, No. 0-M91-CAN/

More information

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller A pre-engineered solution with an integrated circuit breaker disconnect and an Altistart 22 soft start in a stand-alone enclosure Make the

More information

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x. Types MS116, MS132, MS5x, MS9x are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/OFF control, and protection against short circuit,

More information

Selection Guide. Control Circuit and Load Protection

Selection Guide. Control Circuit and Load Protection Selection Guide Control Circuit and Load Protection Circuit Protection Portfolio 1489-M Circuit Breakers Approved for branch circuit protection in the United States and Canada, and certified as Miniature

More information

Compact Circuit Protector (CCP) Application Note

Compact Circuit Protector (CCP) Application Note Compact Circuit Protector (CCP) Application Note Table Of Contents Application Note Description Page Objective............................................... 3 Compact Circuit Protector (CCP).............................

More information

TeSys GV2 - GV3 Manual Starters and Protectors

TeSys GV2 - GV3 Manual Starters and Protectors TeSys GV GV Manual Starters and Protectors A stronger, longterm connection Courtesy of Steven Engineering, Inc. 0 Ryan Way, South San Francisco, CA 94080670 General Inquiries: (800) 67048 www.stevenengineering.com

More information

KT7. Methods. of Applying. & Molded Case Circuit Breakers F119. Motor Circuit Controllers

KT7. Methods. of Applying. & Molded Case Circuit Breakers F119. Motor Circuit Controllers Methods of Applying KT7 & Molded Case Circuit Breakers This information is provided to aid in proper system design and utilization of the KTA7, KTB7 & KTC7 Controller in North American applications. UL

More information

Overcurrent Protection According to the 2011 NEC

Overcurrent Protection According to the 2011 NEC Overcurrent Protection According to the 2011 NEC Utah Electrical License This course will cover overcurrent protection according to the 2011 NEC. The key sections of Article 240 will be discussed. Overcurrent

More information

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR Assembly Short-Circuit Current Ratings What Is A Short-Circuit

More information

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer Achieving Higher Short Circuit Current Ratings for Industrial Control Panels Standards & codes note 1 By Steve Hansen Sr. Field Engineer Introduction Articles 9.1 and. in the National Electrical Code require

More information

Bulletin 1489 Circuit Breakers. Selection Guide

Bulletin 1489 Circuit Breakers. Selection Guide Bulletin 1489 s Selection Guide Bulletin 1489-A Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00,

3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00, Low-Voltage Controls and Distribution > Industrial Controls > Protection Equipment > Circuit Breakers/Motor Starter Protectors > Motor Starter Protectors SIRIUS RV up to 00 A RV0-0DA5 CIRCUIT-BREAKER,

More information

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Are You Ready For The New SCCR Marking Requirements? What Is A Short-Circuit Current Rating (SCCR)? SCCRs on components

More information

1489-M Circuit Breakers

1489-M Circuit Breakers Dual terminals provide wiring/bus bar flexibility and clamp from both sides to improve connection reliability Terminal design helps prevent wiring misses Scratch- and solventresistant printing Suitable

More information

Self-protected Combination Starters System PKZ 2-SP

Self-protected Combination Starters System PKZ 2-SP Self-protected Combination Starters System PKZ 2-SP 03/035 PKZ 2/ZM/S-SP motor starters: a higher level of protection and versatility : The PKZ 2/ZM/S-SP is a self-protected starter, the first motor controller

More information

PowerPact B. Molded case circuit breakers and switches from A

PowerPact B. Molded case circuit breakers and switches from A PowerPact B Molded case circuit breakers and switches from 15-125 A 2 schneider-electric.us Efficiency that clicks. PowerPact B molded case circuit breakers Schneider Electric introduces a new family member

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein. 16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X Manual motor protectors Type MS116 Type MS32 Type MS4X Type MS49X Manual motor protectors MS116 MS32 MS4X MS49X Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL ed and

More information

C E R T I F I C A T E O F C O M P L I A N C E

C E R T I F I C A T E O F C O M P L I A N C E Issued to: SIEMENS AG I IA CE CP R&D-VI 4 WERNER-VON-SIEMENS-STRASSE 48 92220 AMBERG, GERMANY This is to certify that representative samples of Motor Controllers, Magnetic USL, CNL - Type No 3RT10, 3RT11,

More information

XT IEC Power Control Manual Motor Protectors

XT IEC Power Control Manual Motor Protectors May 07 Product Selection Table 7. Rotary with Screw Terminals Global Ratings and North American Ratings Type and Type 2 Coordination Motor Protective Device with Thermal and Magnetic Trip Rated Uninterrupted

More information

Protection Equipment. 5/2 Introduction

Protection Equipment. 5/2 Introduction Protection Equipment /2 Introduction SIRIUS 3RV2 Motor Starter Protectors/ Circuit Breakers up to 40 A /6 General data /12 For motor protection /14 For motor protection with overload relay function /1

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Selection Guide Motor Control Device Solutions

Selection Guide Motor Control Device Solutions Selection Guide Motor Control Device Solutions Expect more and get it from c3controls. Our portfolio of Motor Control Devices consists of worldclass products designed and manufactured to meet your requirements

More information

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Paul I-Hai Lin, Professor

More information

Quick Start Guide TS 910 & TS 920

Quick Start Guide TS 910 & TS 920 Quick Start Guide TS 910 & TS 920 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

Motor Controllers + Circuit Breakers

Motor Controllers + Circuit Breakers Series General...2 Series & KTA3-100 Base Units...4 Series Base Units...6 Series Base Units...8 Accessories...10 Technical Information -...20 Dimensions -...33 Technical Information - KTA3-100...39 Dimensions

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are: Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor.

More information

Enhancing Short Circuit Selective Coordination with Low Voltage Circuit Breakers

Enhancing Short Circuit Selective Coordination with Low Voltage Circuit Breakers Data Bulletin 0100DB0403R5/05 05/2005 Cedar Rapids, Iowa, USA Enhancing Short Coordination with Low Voltage s Retain for future use. INTRODUCTION DEFINITIONS ASSUMPTIONS CIRCUIT BREAKER BASICS The purpose

More information

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD. DATASHEET - DILMC9-10(24VDC) Technical data General Contactor, 3p+1N/O, 4kW/400V/AC3 Part no. DILMC9-10(24VDC) Catalog No. 277468 Eaton Catalog No. XTCEC009B10TD EL-Nummer 4110305 (Norway) Standards IEC/EN

More information

PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ)

PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ) PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ) Catalog Class 734 0734CT0201R1/07 07 CONTENTS Description..............................................Page Description.............................................

More information

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories Manual motor protectors Manual motor protectors Manual motor Protectors MS116 MS32 MS4X MS49X Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL Listed and CSA certified

More information

Series KTU7 UL489 Molded Case Circuit Breakers

Series KTU7 UL489 Molded Case Circuit Breakers Series KTU7 UL489 Molded Case Circuit Breakers Versatile, convenient and space saving for a variety of applications Sprecher+Schuh s KTU7 series of UL Molded Case Circuit Breakers are UL489 and CE listed

More information

Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals?

Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals? White paper Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals? Darryl Moser, Business Development Manager, DEM Sales, ABB, Electrification Products Division

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

Altivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit

Altivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit Altivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit Instruction Bulletin 30072-453-27 Retain for future use. For Frame Sizes 2 5: ATV61H075M3, -HU15M3, -HU22M3, -HU30M3, -HU40M3,

More information

Bussmann series Quik-Spec Coordination Panelboard

Bussmann series Quik-Spec Coordination Panelboard Quik-Spec electrical gear 12 Contents Bussmann series Quik-Spec Coordination Panelboard Section page Description Quik-Spec Coordination Panelboards Up to 400 A 2 600 to 1200 A 3 Quik-Spec elevator disconnects

More information

F Motor Circuit Controllers. Series KT7 Motor Circuit Controllers. KT4 Manual Motor Starters. General Description...F2

F Motor Circuit Controllers. Series KT7 Motor Circuit Controllers. KT4 Manual Motor Starters. General Description...F2 Series KT7 General...2 Series & KTA3-100 Base Units...4 Series Base Units...6 Series Base Units...8 Accessories...10 Technical Information - KT7...20 Dimensions - KT7...32 Technical Information - KTA3-100...37

More information

ALTIVAR FLEX58 Chassis Drive Controller Product Selection

ALTIVAR FLEX58 Chassis Drive Controller Product Selection ALTIVAR FLEX58 Chassis Drive Controller Product Selection Class 8806 CONTENTS Description Page General Information and Selection....................................... 2 Specifications and Ratings...........................................

More information

Control Circuit Protection

Control Circuit Protection Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC

More information

Enclosures. See Section Typical Description

Enclosures. See Section Typical Description January 00 Sheet 1187 Motor Starters & Contactors Low Voltage Enclosures General Individual Enclosed, ac Full Voltage.7- Combination Starters Maximum 00 hp, Volts Application Size 1, NEMA 1, Enclosed Magnetic

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4. Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type

More information

Bulletin 190-M Compact Starters. Selection Guide

Bulletin 190-M Compact Starters. Selection Guide Bulletin 190-M Selection Guide Bulletin 190-M Selection Guide 3 Bulletin 190-M Compact Design to 45mm Wide Common Adapter for Panel or DIN Rail Mounting Pre-Wired Assembly All Control Terminations Located

More information

3. Coils shall be of molded construction

3. Coils shall be of molded construction .7-4 Motor Starters & Contactors Low Voltage Enclosures General Non-Combination Starters January 00 Sheet 8 0 7 8 9 4 Non-Combination Starters Maximum hp, Volts Typical Non-Combination Starter Application

More information

Bulletin 140M Motor Protectors

Bulletin 140M Motor Protectors 0Circuit Breaker Bulletin 140M Bulletin 140M Cat. No. 140M-C2E Cat. No. 140M-F8E Current Range 0.1...45 A With 140-CMN up to 90 A Type 2 Coordination with Bulletin 100-C Contactors UL Listed Self-protected

More information

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control . Contents Description Relays and Timers......................... Miniature Controls......................... Contactors and Starters.................... Thermal Relays.................... C440/XT Electronic

More information

Series KTU7 UL489 Molded Case Circuit Breakers

Series KTU7 UL489 Molded Case Circuit Breakers Series UL489 Molded Case Circuit Breakers Versatile, convenient and space saving for a variety of applications Sprecher+Schuh s series of UL are UL489 and CE listed for global applications. The current

More information

File E47705 Project 97ME August 21, 1997 REPORT. MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany

File E47705 Project 97ME August 21, 1997 REPORT. MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany File E47705 Project 97ME18400 August 21, 1997 REPORT on MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany Copyright 1997 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the above

More information

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse LPSRK100SP 600V TD Dual Elem Class RK1 Low Peak Fuse Catalog Number Manufacturer Description Weight per unit Product Category LPSRK100SP 600V Class RK1 Low Peak Dual Element, Time Delay Fuse 0.4100 (lbs/each)

More information

LPSRK30SP 30A 600V TD Dual Elem Class RK1 Low Peak Fuse

LPSRK30SP 30A 600V TD Dual Elem Class RK1 Low Peak Fuse LPSRK30SP 30A 600V TD Dual Elem Class RK Low Peak Fuse Catalog Number Manufacturer Description Weight per unit Product Category LPSRK30SP 30A 600V Class RK Low Peak Dual Element, Time Delay Fuse 600 (lbs/each)

More information

Industrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw

Industrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw Industrial Generator Set Accessories Line Circuit Breakers 15-2500 kw Standard Features Single Circuit Breaker Kit with Neutral Bus Bar 15-300 kw Model Shown The line circuit breaker interrupts the generator

More information

S-Flex 212. Adjustable Speed Enclosed Drive Instruction Bulletin Rev. 07, 10/2018. Retain for future use.

S-Flex 212. Adjustable Speed Enclosed Drive Instruction Bulletin Rev. 07, 10/2018. Retain for future use. S-Flex 212 Adjustable Speed Enclosed Drive Instruction Bulletin 30072-451-83 Rev. 07, 10/2018 Retain for future use. Table of Contents Table of Contents Hazard Categories and Special Symbols... 6 Please

More information

Altivar 31 AC Drives. Simply Smart! For 3-phase asynchronous motors from 0.25 to 20 HP

Altivar 31 AC Drives. Simply Smart! For 3-phase asynchronous motors from 0.25 to 20 HP Altivar 31 AC Drives Simply Smart! For 3-phase asynchronous motors from 0.25 to 20 HP T A complete offer: Wide choice of voltage ranges Single-phase 208 to 240 V. 3-phase 208 to 240 V. 3-phase 400 to 460

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

Quik-Spec Electrical Gear

Quik-Spec Electrical Gear Section Contents Page Quik-Spec Coordination Panel Boards......... 266-267 Quik-Spec Power Module Switches and Panels.. 268-269 Quik-Spec DC Safety Switches.................. 270 Quik-Spec AC Safety Switches..................

More information

KT4 Manual Motor Starter

KT4 Manual Motor Starter KT4 Manual Motor Starter Ideal for use as a manual starter The KT4 is a manual motor starter that employs the features of power switching, thermal overload protection and control circuit signaling in one

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance (012730_C_000) Issued to: Siemens AG DF CP R&D VC 2 WernervonSiemensStrasse 48 Amberg, 92224 GERMANY The products listed below are eligible to bear the CSA Mark shown Issued by:

More information

Applying More Than One ArmorStart Motor Controller in a Single Branch Circuit on Industrial Machinery

Applying More Than One ArmorStart Motor Controller in a Single Branch Circuit on Industrial Machinery Application Guide Applying More Than One ArmorStart Motor Controller in a Single Branch Circuit on Industrial Machinery Bulletin Numbers 280, 281, 284, 290, 291 Topic Introduction 2 Background 2 ArmorStart

More information

Switchboards Instant Service

Switchboards Instant Service January 1 Vol. 1, Ref. No. [0845] Switchboards Instant Service - Accessories Table -57. Meter Compartment Doors (Meter Sockets Not Included) Door Size Dimensions Drilling Inches mm H x 32 W 381.0 H x 8.8

More information

Panel SCCR 50kA RMS Symmetrical 480V Maximum

Panel SCCR 50kA RMS Symmetrical 480V Maximum Panel SCCR 50kA RMS Symmetrical 480V Maximum 4 Short-Circuit Current Rating SCCR: The perspective or maximum symmetrical fault current at a nominal voltage to which an apparatus or system is able to be

More information

Low-Peak 600V Class RK1

Low-Peak 600V Class RK1 LPS-RK 600Vac/300Vdc, 1 10-60A, Dual Element, Time-Delay Fuses Dimensions - in 5" (± 0.31) 5.5" (± 0.31) Available with easyid open fuse indication 1/10 to 30A 0.81" (±0.008) 35 to 60A 1.06" (±0.008) Description:

More information

2016 Photovoltaic Solar System Plan Review List

2016 Photovoltaic Solar System Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE

More information

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service No One Does It Like Mipco Mipco Interlocked Reefer Power Outlets are used extensively in port terminals and shipboard applications to provide a safe, watertight electrical connection for refrigerated containers.

More information

Series L9 UL-489 Miniature Circuit Breakers

Series L9 UL-489 Miniature Circuit Breakers Series UL-489 iniature Breakers Industrial Breakers for Branch up to 40 Amps Sprecher+Schuh includes a line of circuit breakers approved for branch circuit applications in the United States and Canada

More information

NEMA Contactors & Starters (Freedom)

NEMA Contactors & Starters (Freedom) Page 1 February, 1 Supersedes TIP AN1, AN, CN1, CN Pages 1-0, Dated 1/1/4 ECN01, ECN0, ECN0, ECN0, ECN0 AN1, AN, CN1 & CN Sizes 00-, 00V Max. Non-Reversing & Reversing NEMA Type Enclosures 1, R, 4X & 1

More information

Features 1 Phase HP/Volts 1/6 HP AT 230 V 3 Phase HP/Volts 1/2 HP AT 200/230 V, 1-1/2 HP AT 460/575 V

Features 1 Phase HP/Volts 1/6 HP AT 230 V 3 Phase HP/Volts 1/2 HP AT 200/230 V, 1-1/2 HP AT 460/575 V 804 South Street 7964-76, TX Nacogdoches Phone: 96-69-794 Fax: 96-60-468 A07NN A Man Motor Protector Eaton Corp Catalog Number A07NN Manufacturer Eaton Corp Description Manual Motor Starter, Motor Protector;

More information

Design Standards NEMA

Design Standards NEMA Design Standards Although several organizations are involved in establishing standards for the design, construction, and application of motor control centers, the primary standards are established by UL,

More information

Certifications UL Listed (File No. E 14841, Guide NLRV; File No. E 47426, Guide WHTY) CSA Certified (File No. LR1234) CE

Certifications UL Listed (File No. E 14841, Guide NLRV; File No. E 47426, Guide WHTY) CSA Certified (File No. LR1234) CE Bulletin R Overview Bulletin R Next Generation Global Fused and Non-Fused Disconnects 0 A A Sizes Fused Switch Versions: - BS - DIN - CSA HRCII-C - CSA HRCI-MISC - UL Class J - UL Class CC - NFC Non-Fused

More information

Technical data OT16E3 OT160E3 UL & CSA

Technical data OT16E3 OT160E3 UL & CSA Technical data OT16E3 OT16E3 UL & CSA UL & CSA Catalog number 3 pole OT16E3 OT25E3 OT32E3 OT45E3 OT63E3 OT3E3 OT6E3 OT1E3 OT16E3 Approvals 1 2 pole N/A N/A N/A N/A N/A N/A N/A N/A UL98 & EC 3 pole UL58

More information

Fuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules.

Fuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules. Fuseology Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression Optima Fuse Holders & Overcurrent Protection Modules Compact, full-featured modules that deliver Type 2 coordinated protection,

More information

SIGNAL WORDS QUALIFIED PERSON

SIGNAL WORDS QUALIFIED PERSON SIGNAL WORDS The signal words Danger, Warning and Caution used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as: Danger - Indicates death or

More information

Bulletin 194R Next Generation Global Fused and Non-Fused Disconnects

Bulletin 194R Next Generation Global Fused and Non-Fused Disconnects Bulletin R IEC Fused and Non-Fused Disconnects, & A Overview Bulletin R Next Generation Global Fused and Non-Fused Disconnects A A Sizes Fused switch versions: - BS - DIN - CSA HRCII-C - CSA HRCI-MISC

More information

Protection Equipment

Protection Equipment Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection

More information

Poles 3 Starter Size NEMA 3 NON ALUMINUM LINE TERMINAL, LOAD TERMINAL

Poles 3 Starter Size NEMA 3 NON ALUMINUM LINE TERMINAL, LOAD TERMINAL 3804 South Street 75964-763, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 H100R3C 3P 100A 600V F-Frame MC Protector Eaton Corp Catalog Number H100R3C Manufacturer Eaton Corp Description Motor Circuit

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI . Technical Data and Specifications Ratings Frames EG, JG and LG EG JG LG Maximum rated current (amperes) 15, 160 1 50 400, 630 Breaker type 3 B B E S S H H C E S H C U X E S H C U X of poles 1, 3, 4,

More information

Product index. 4 - Manual motor protectors. Phone: Fax: Web: -

Product index. 4 - Manual motor protectors. Phone: Fax: Web:  - Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type

More information

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control Contents Description Relays and Timers......................... Miniature Controls......................... Contactors and Starters.................... Thermal Overload Relays.................... C440/XT

More information

Motor Starter Protectors

Motor Starter Protectors Motor Starter Protectors Industrial Controls Product Catalog 207 Section contents Section Overview /2 - /3 Motor Starter Protectors 3RV20 MSP, Class 0/20 /4 - /5 Circuit Breakers 3RV27, 3RV28 Circuit Breaker

More information

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers Instruction Leaflet IL0330300E Supersedes I.L. 7055C, Pages 8, Dated June 998 Instructions for A00, A0, A50 size 6, two- or three-pole non-reversing or reversing motor controllers Contents Description

More information

File E47705 Vol. 7 Sec. 9 Page 1 Issued: and Report Revised:

File E47705 Vol. 7 Sec. 9 Page 1 Issued: and Report Revised: File E47705 Vol. 7 Sec. 9 Page 1 Issued: 1997-08-29 and Report Revised: 2005-06-30 DESCRIPTION PRODUCT COVERED: USL, CNL - Type Nos. 3RV1021, 3RV1121, 3RV1321 or 3RV1421, followed by combination of 0,

More information

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X Manual motor protectors Type MS116 Type MS32 Type MS4X Type MS49X Manual motor protectors Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL Listed and CSA certifi ed for

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

ALTIVAR 58 AC Drives

ALTIVAR 58 AC Drives Class 8806 / 8839 / 8998 CONTENTS Schneider Electric Brands Page ALTIVAR 58 AC Drives............................................... 3 Drives Overview...................................................

More information

Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA

Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA Table of Contents TPS NQ & AQ Series Overview 2 Switchboard Technical Data 3-5 Panelboard Technical Data 5-11 1 Tier Power

More information

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0

More information