Technical Information

Size: px
Start display at page:

Download "Technical Information"

Transcription

1 Technical Information

2 Basic Definition VOLT A measure of electrical pressure - The higher the potential difference the greater the pressure (flow) of electricity - Potiantial difference is the higher negative electrons over positive electrons. AMP A measurement of electrical flow - The rate at which the electricity passes through a conductor (wire). OHMS Measurement of resistance - The longer the conductor the greater the resistance - The wider the conductor the less resistance. HORSE POWER One horse lifting 100 pounds 5.5 feet in one second Equals 1HP - Lifting 100 lbs feet in one sec. = 2HP. WATT The amount of energy expanded by one amp of current at one volt of potential change. KILOWATT One thousand watts. TORQUE The form of mechanical energy generated by a rotating shaft or wheel (Waterwheel, windmill or electric motor). FT.-POUNDS OF TORQUE One FT. pound of torque is equivalent to one pound of force applied to a wheel one foot from the center of rotation. DC Direct Current - when the direction of current remains constant as in a battery. PULSATING DIRECT CURRENT Created by generators but pulsates with each rotation of the shaft. ARMATURE A coil of wire that rotates around a magnet.as it rotates current is induced into the wire. ALTERNATING CURRENT (AC) Current that charges direction with each 1/2 turn of the Armature - The natural product of rotating a wire loop with a magnetic field. CYCLE A matched pair of up & down curves reflecting one rotation of the armature. HERTZ One cycle per second. THREE PHASE SYSTEM The current in one coil will always be equal to the opposite of the current in the other two coils. Ohm s Law For Direct or Single Phase Non-Inductive Alternating Current Let: 1 = Ampere = unit of current strength or rate of flow. E = Volt = unit of electromotive force or electric pressure. R = Ohm = unit of resistance to flow of current. W = Watt = unit of power. Then: I = E E = IR R = E W = IE = E2 = 1 2 R R I R 1000W = 1 Kw or kilowatt; this is the usual unit of measure of electric power. 1 Kw hr. is the work done by one Kw in one hour. For alternating current circuits, the following rules are useful for finding the power of polyphase circuit. Let P.F. = Power Factor. Kw = Kw = Kw = 1.73 x E x I x P.F x E x I x P.F E x I x P.F (3-phase AC) (2-phase AC) (1-phase AC) 746 watts 1 HP = ft-lbs/min heat-units/hr., BTU 2.64 lbs. water evaporated 1 ft-lb - raising one pound one foot. 1 BTU (British Thermal Unit) = heat required to raise the temperature of one pound of pure water one degree Fahrenheit. Electrical Formula for Determining Amperes, Horsepower, Kilowatts and Kilovolt-Amperes Alternating Current Single Phase Two-Phase, 4 Wire Kilowatts I x E X P.F. I x E x 2 x P.F Kva I x E I x E x Horsepower Output I x E x %Eff. x P.F. I x E x 2 x %Eff. x P.F Amperes When HP is Known HP x 746 HP x 746 E x %Eff. x P.F. 2 x E x %Eff. P.F. Amperes When Kw is Known Kw x 1000 Kw x 1000 E x P.F. 2 x E x P.F. Amperes When Kva is Known Kva x 1000 Kva x 1000 E 2 x E 587

3 AC 3-Phase DC Kilowatts I x E x 1.73 x P.F. I x E Kva I x E x Horsepower Output I x E x 1.73%Eff. x P.F. I x E x 2 x %Eff Amperes When HP is Known HP x 746 HP x x E x %Eff. x P.F. E x %Eff. Amperes When Kw is Known Kw x 1000 Kw x x E x P.F. E Amperes When Kva is Known Kva x x E * In three-wire, two-phase circuits the current in the common conductor is 1.41 times that in either other conductor. Note: E=Volts; 1=Amperes; %Eff.=Percent Efficiency; P.F.=Power Factory. Equivalent Values In Different Units 746 watts.746 Kw ft-lbs/min. 550 ft-lbs/sec. 1 HP = 3545 heat-units/hr heat-units/min..707 heat-units/sec..175 lbs. carbon oxidized/hr lbs. water evaporated hr. from and at 212 F. 746 watts ft-lbs heat-units 1 HP kgm Hour =.175 lb. carbon oxidized with perfect efficiency 2.64 lbs. water evaporated from and at 212 F lbs. water raised from 62 to 212 F watts 1.34 HP ft-lbs/hr ft-lbs/min ft-lbs/sec. 1 Kw = 3412 heat-units/hr heat-units/min..948 heat-units/sec lb. carbon oxidized/hr lbs. water evaporated from and at 212 F. 8.9 heat-units/sq.ft/min. 1 Watt/ 6371 ft-lbs/sq. ft/min. Sq. In. =.193 HP/sq. ft ft. lbs HP hr. 1 Kg Kw hr. Meter =.0093 heat-units.283 Kw hr. 1 Lb..379 HP hr. Water heat-units Evap kgm from & at joules 212 F= ft-lbs lb. of carbon oxidized 1055 watt seconds 778 ft-lbs kgm meters 1 Heat Kw hrs. unit = HP hrs lb. carbon oxidized lbs. water evaporated from and at 212 F. 1 Heat-.122 watt/sq. in. unit/sq Kw/sq. ft. Ft./Min.=.0236 HP/sq. ft. Wiring Formula Ohm s law is practically the basis for the various formulae in general use for determining the proper size of wire to use to carry various currents. It is essential to know the amount of current expressed in amperes, the distance, and to decide upon the loss to allow in transmission; the best rule is as follows: The cross section (CM) of the necessary wire is found by multiplying twice the distance one way (2D) by the amount of current expressed in amperes (C) and this by the resistance of one mil-foot (10.7) and dividing by the loss in transmission expressed in volts (v), or CM = 2D x C x 10.7 or CM = D x C x 21.4 v v Comparison of Methods of Starting Squirrel-Cage Induction Motors % Full Voltage Value Voltage Motor Starter at Line Output Type Motor Current Torque Full Voltage Autotransformer- 80pc tap (60) 65pc tap (35) 50pc tap (20) Primary reactor- 80pc tap (60) 65pc tap (35) 50pc tap (20) Primary-resistor typical rating (60) Part-winding Low speed motors (1/2-1/2) High speed motors (1/2-1/2) High speed motors (2/3-1/3) Wye start-delta run (27) Note: The nominal torque values given neglect the effects of motor saturation.actual torque ratios may be more on the order of the values shown in parentheses, and it is advisable to review the actual reduced voltage starting characteristics with the motor manufacturer. 588

4 NEMA Code Letters for Locked Rotor KVA (Alternating-Current Motors) NEMA Code KVA/HP NEMA Code KVA/HP A L B M C N D P E R F S G T H U J V K DC Generator Connection (NEMA) A2 C A1 S2 S1 = (EQUALIZER IF USED) Compound Generator-Clockwise Rotation Facing End Opposite Drive, Counterclockwise Rotation Facing Drive End F2 A1 C A2 S2 S1 = (EQUALIZER IF USED) Compound Generator-Clockwise Rotation Facing End Opposite Drive, Counterclockwise Rotation Facing Drive End Note: RHEO RHEO Interchange S1 and S2 for differentially compounded generator (voltage decreasing with load). DC Motor Connections (NEMA) These connection diagrams show all leads from the armature, the shunt field and the series (or stabilizing) field brought out of the machine.the dotted connections may be made inside the machine or outside the machine as conditions require. RHEO Compound or Stabilized Shunt Motor-Counterclockwise Rotation Facing End Opposite Drive, Clockwise Rotation Facing Drive End RHEO F1 F1 F1 F1 SHUNT SHUNT SHUNT COMP COMP COMM COMM SERIES Compound or Stabilized Shunt Motor-Clockwise Rotation Facing End Opposite Drive, Counterclockwise Rotation Facing Drive End Source: ANSI/NEMA Standards for Motors and Generators. (1980). F2 SERIES A1 C A2 S1 S2 SHUNT COMP COMM COMP COMM SERIES SERIES A2 C A1 S1 S2 F2 F2 Motor Application Formulas Power Transmission by Shaft Hp =[Torque (in lb-ft) x rpm] 5250 Power to Drive Pumps Gal. per min. x Sp. Gr. x total head (inc. friction) Hp = 3,960 x eff. of pump Where Approx. Friction head (ft.) = pipe length (ft.) x [velocity of flow (fps)] 2 x ,367 x diameter (in.) Eff = Approximately 0.50 to 0.85 Sp. Gr. = Specific gravity of Liquid Power to Drive Fans Cu. ft. gas per min. x water gage pressure (in.) Hp = x Eff. The volume of gas delivered by a fan varies directly as the fan speed. The pressure produced by a fan varies as the square of the fan speed and directly as the density of the gas handled.the horsepower of a fan varies as the cube of the fan speed and directly as the density of the gas handled. Equivalent Wye Delta Networks K1 = A + B + C K2 = ab + bc + ac B a c A b C a = b = c = BC K1 A = K 2 a AC K1 B = K 2 b AB K1 C = K 2 c Power Factor Improvement of Induction Motor Loads Power factor is defined as the cos ø in the equation Pav=Vrmslrms cos ø, where the the average power (Pav) is given in terms of root mean square voltage (V), current (I), and the phase angle ø between them. Power Factor Correction: When power factor correction capacitors are used, the total corrective kvar placed on the load side of the motor controller should not exceed the value required to raise the no-load power factor of the motor to unity. Corrective kvar in excess of this value may cause overexcitation resulting in high transient voltages, currents and torques that can increase safety hazards to personnel and can cause possible damage to the motor or to the driven equipment. The use of capacitors for power factor correction, switched at the motor terminals, is not recommended for elevator motors, multi-speed motors, motors used on plugging or jogging applications, motors subject to high speed bus transfer, and motors used with open transition, wye-delta or auto-transformer starting. For such applications the motor manufacturer should be consulted before installing power factor corrective capacitors switched at the motor terminals. Recommended Maximum Capacitor Rating When Capacitor and Motor Are Switched as a Unit. For Dripproof and Splashproof Enclosures; 230, 460, and 575 Volts, 3- Phase, 60 Hertz: General Electric Type K (NEMA Design B) Only. Normal Starting Torque and Current. 589

5 Nominal Motor Speed in Rpm & Number of Poles Induction Motor Horsepower Rating KVAR KVAR KVAR KVAR KVAR KVAR Also applicable to standard wound-rotor, open-type, three-phase, sixtycycle motors by multiplying the KVAR values in the table by a factor of I.1. Recommendations and Precautions Where possible, switch capacitors through the motor control controller at circuit location 2, illustration.this avoids resizing of motor overload devices and helps minimize possibility of excessive improvement at bus. Add power factor improvement capacitors to individual motor branch circuits using data provided by the motor manufacturer recomending the maximum capacitor rating that should be switched with the motor as a unit. If power factor improvement capacitors are connected at circuit location No. 3, illustration, account for reduced line current flowing through the motor controller s overload devices. Apply power factor improvement capacitors to the bus, ciruit location No. 1, illustration, if the motor is applied with one of the following motor controllers; reversing starter (with motor plugging), wye-delta starter, open transition, autotransformer starter, part-winding starter*, or if the motor is multi-speed. Be sure to maintain bus power factor below about 95% under all conditions of motor loading to help minimize possibility of excessive improvement. * Note: Capacitor switching by the motor starter may be acceptable in some part-winding starter applications; consult applicable motor manufacturer. DISCONNECT FUSE CONTACTOR OVERLOAD DEVICE MOTOR BUS COMBINATION MOTOR CONTROLLER 2 3 Capacitor Multipliers for Kilowatt Load (To give capacitor kvar required to improve power factor from original to desired value-see sample below.) Original Power Desired Power Factor- Per Cent Factor, Per Cent Motor Terminal Amperes At Full Load Average Values for All Speeds and Frequencies Assume total plant load is 100 kw at 60 per cent power factor. Capacitor kvar rating necessary to improve power factor to 80 per cent in found by multiplying kw (100) by multiplier in table (0.583), which gives kvar (58.3). Nearest standard rating 60 (kvar) should be recommended. Single- Polyphase A-C (Induction Type) Phase A-C Squirrel-Cage and Wound Rotor Direct Current 115 Volts 230 Volts 460 Volts 575 Volts Ph 2-Ph 2-Ph 2-Ph Hp Volts Volts* 3-Ph 4-Wire 3-Ph 4-Wire 3-Ph 4-Wire 3-Ph 4-Wire Volts Volts Volts 1 / / / / / / These values of full-load current are for motors running at speeds usual for belted motors and motors with normal torque characteristics. Motors built for especially low speeds or high torques may require more running current, in which case the nameplate current rating should be used. Current in common conductor of 2-phase, 3-wire system will be 1.41 times value given. * For full-load currents of 208- and 200-volt motors, increase the corresponding 230-volt motor full-load current by 10 and 15 percent respectively. 590

6 Full-Load Currents in Amperes-Single Phase Circuits KVA X 1000 Full Load Current = Circuit Voltage KVA KVA ,000 14, Full-Load Currents in Amperes Three-phase Circuits KVA X 1000 Full Load Current = x Circuit Voltage KVA KVA ,00 12,470 13,200 14, Power Transformer Insulation Levels (1) (1) (2) Nominal Basic Insulation Low Frequency System Voltage Levels (BIL) Voltage Insulation (kv rms) kv-crest Levels (kv rms) * * Nonpreferred voltage. Table is for reference only.the selection BIL depends on system conditions and transient over voltage protection used. Copper Data Resistivity and Density (Based on National Bureau of Standards) The international annealed-copper standard of 100% conductivity, based on the Absolute Ohm, is as follows at 20 C: Resistance of a uniform, annealed copper wire one square millimeter in cross section and one meter long = ohm. Density = 8.89 grams per cubic centimeter.these values also can be expressed as: microhm cm ohm gram/meter microhm inch ohm, pound/mile ohm circular mil/ft Temerature Coefficient of Resistance The temperature coefficient of resistance at constant mass and free expansion of standard annealed copper of 100% conductivity is, per degree Celsius, (centigrade) at 20 C or at 25 C. Resistance values of copper wire at 100% conductivity given in tables at 25 C or at any temperature t 2 by means of the following equations: t 2 Rt 2 = R 25 [ (t 2-25)] = Rt t 1 Where Rt 1 = resistance in ohms at t 1, degrees C Rt 2 = resistance in ohms at t 2, degrees C R 25 = resistance in ohms at 25 C Breaking Loads of Copper Wire Breaking Load, Breaking Load, * Hard- An- * Hard- An- Diam. Size, drawn nealed Diam. Size, drawn nealed In. AWG (Min.) (Max.) In. AWG (Min.) (Max.) * Based on ASTM B1-56. Based on ASTM B

7 Copper Wire Data Bare Copper Wire Resistance at 25 C Current Carrying Approx. Cross- Capacity OD sectional 700 CM Size* Inches Area CM LB/M Ft per M.Ft Per Amp 1000MCM AWG * Sizes 1000 MCM through #8 AWG Class B concentric stranded Sizes #10 AWG and smaller solid round Typical Equivalent Delta Phase Spacings For Single Circuit Lines Voltage Equiv. Voltage Equiv. Rating Spacing - Ft. Rating Spacing - Ft CAPACITIVE REACTANCE SPACING FACTOR Xc2 MEGOHMS/COND/MILE EQUIVALENT & SPACING-FEET INDUCTIVE REACTANCE SPACING FACTOR XI2 OHMS/COND/MILE Total 60 Cycle Inductive Reactance in ohms per mile: XL = XL1 + XL2 XL1 = Inductive Reactance at 1 ft. spacing. XL2 = Inductive Reactance spacing factor. (See graph) Total 60 Cycle Capacitive Reactance in megohms per mile: XC = XC = XC1 + XC2 XC1 = Capacitive Reactance at 1 ft. spacing. XC2 = Capacitive Reactance spacing factor. (See graph) Table - 3 Maximum Number of Conductors in Trade Sizes of Conduit or Tubing (From NEC Tables 3A, 3B, 3C) Conduit Trade Size 1 3 /2 /4 (inches) /4 1 1 / / / Conductor Size Type Letters AWG, MCM TW,T, RUH RUW, XHHW (14 thru 8) RHW and RHH (without outer covering), THW TW, T, THW, RUH ( 6 thru 2), RUW (6 thru 2), FEPB (6 thru 2), RHW and RHH (with out outer covering)

8 Table - 3 Maximum Number of Conductors in Trade Sizes of Conduit or Tubing (From NEC Tables 3A, 3B, 3C) Conduit Trade Size 1 3 (inches) /2 / /4 1 1 / / / Conductor Size Type Letters AWG, MCM THWN, THHN, FEP (14 thru 2), FEPB (14 thru 8), PFA (14-4/0), PFAH (14-4/0), Z (14-4/0), XHHW (4 thru MCM) XHHW RHW, RHH (with outer Covering)

9 Lamp Data General Electric Lamp Data Watts Lamp Code Replaces Energy Savings*S Incandescent Lamps-Watt Miser 34 40A/34WM 40A A/52WM 60A A/67WM 75A A/90WM 100A A/135WM 150A 0.79 Incandescent Lamps-Watt Miser PAR (Spot and Flood) 65 75PAR/FL/65WM 75PAR/FL PAR/SP/65WM 75PAR/SP PAR/FL/120WM 150PAR/FL PAR/SP/120WM 150PAR/SP 4.20 * Over rated average life of lamp at 7 /kwh. Nominal Approx. Lamp Initial Flourescent Lamps Watts Lumens 4-Foot Rapid Start (48 ) Standard Cool White 40 3,150 Maxi-Miser II Lite White 40 3,450 Watt-Miser Cool White 34 2,750 Watt-Miser II Lite White 34 2,925 Watt-Miser SP ,900 Watt-Miser SP ,900 Watt-Miser SP ,850 8-Foot Slimline (96 ) Standard Cool White 75 6,300 Watt-Miser Cool White 60 5,600 Watt-Miser II Lite White 60 6,000 8-Foot High Ouput-800mA (96 ) Standard Cool White 110 9,200 Watt-Miser Cool White 95 8,300 Watt-Miser II Lite White 95 8,800 8-Foot 1500mA (96 ) Power Groove Standard Cool White ,000 Watt-Miser II Cool White ,000 Watt-Miser II Lite White ,900 T12 (1 1 /2 dia.) Standard Cool White ,000 Watt-Miser Cool White ,000 Watt-Miser II Lite White ,800 Approx. Length Initial Watts Bulb Finish Type (In.) Lumens Multi-Vapor Lamps (Mogul Screw Base) 175 E-23 1 /2 Clear or Diffuse MV-II 7 3 /4 16, E-28 Clear or Phosphor Std. 8 1 /4 14, E-28 Clear or Phosphor Std. 8 1 /4 20, E-37 Clear or Phosphor 1-line* 11 1 /16 28, E-37 Clear or Phosphor High Output 11 5 /16 40, E-37 Clear or Phosphor Std. or 1-line* 15 5 /6 36, BT-56 Clear High Ouput or 1-line* 15 1 /16 115, BT-56 Clear or Phosphor Std /16 110, BT-56 Clear High Output 15 1 /16 155,000 Lucalox Lamps (Mogul Screw Base) 35 E-17 Clear (Medium Base) 5 1 /2 2, E-23 1 /2 Clear 7 3 /4 5, E-23 1 /2 Clear 7 3 /4 5, E-23 1 /2 Clear 7 3 /4 9, E-23 1 /2 Clear 7 3 /4 16, E-18 Clear 9 3 /4 22, E-18 Clear 9 3 /4 27, E-18 Clear Deluxe Color 9 3 /4 22, E-18 Clear 9 3 /4 37, E-18 Clear 9 3 /4 50, E-25 Clear 15 1 /16 140,000 E-Z Lux Lamps* (For 175W mercury ballasts) 150 E-28 Clear 9 12,000 Mercury Lamps (Mogul Screw Base) 100 E-23 1 /2 Deluxe White 7 1 /2 4, E-28 Deluxe White 8 1 /4 8, E-28 Deluxe White 8 1 /4 12, E-37 Deluxe White 11 5 /16 22, BT-56 Deluxe White 15 1 /16 63,000 * May be used on approved mercury ballasts. Also available with medium base, E-17 bulb. Circlite Replaces incandescent lamps (10 dia.) 44 1,

10 Industry Standards Enclosure Types for Non-Hazardous Locations National Electrical Manufacturers Association (NEMA Standard 250) Type Intended Use and Description 1 Enclosures are intended for indoor use primarily to provide a degree of protection against contact with the enclosed equipment or locations where unusual service conditions do not exist. 2 Enclosures are intended for indoor use primarily to provide a degree of protection against limited amounts of falling water and dirt. 3 Enclosures are intended for outdoor use primarily to provide a degree of protection against windblown dust, rain, and sleet; undamaged by the formation of ice on the enclosure. 3R Enclosures are intended for outdoor use primarily to provide a degree of protection against falling rain and sleet; undamaged by the formation of ice on the enclosure. 4 Enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against windblown dust and rain, splashing water, and hose-directed water; undamaged by the formation of ice on the enclosure. 4X Enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hosedirected water; undamaged by the formation of ice on the enclosure. 5 No NEMA equivalent. 6 Enclosures are intended for use indoors or outdoors where occasional submersion is encountered. 12 Enclosures are intended for indoor use primarily to provide a degree of protection against dust, falling dirt, and dripping noncorrosive liquids. 13 Enclosures are intended for indoor use primarily to provide a degree of protection against dust, falling dirt, and dripping noncorrosive liquids. The preceding descriptions are not intended to be complete representations of National Electrical Manufacturers Association standards for enclosures. Underwriters Laboratories Inc. (UL 50 and UL 508) Type Intended Use and Description 1 Indoor use primarily to provide protection against contact with the enclosed equipment and against a limited amount of falling dirt. 2 Indoor use to provide a degree of protection against limited amounts of falling water and dirt. 3 Outdoor use to provide a degree of protection against windblown dust and windblown rain; undamaged by the formation of ice on the enclosure. 3R Outdoor use to provide a degree of protection against falling rain; undamaged by the formation of ice on the enclosure. 4 Either indoor or outdoor use to provide a degree of protection against falling rain, splashing water, and hosedirected water; undamaged by the formation of ice on the enclosure. 4X Either indoor or outdoor use to provide a degree of protection against falling rain, splashing water, and hosedirected water; undamaged by the formation of ice on the enclosure; resists corrosion. 5 No UL equivalent. 6 Indoor or outdoor use to provide a degree of protection against entry of water during temporary submersion at a limited depth; undamaged by the formation of ice on the enclosure. 12 Indoor use to provide a degree of protection against dust, dirt, fiber flyings, dripping water, and external condensation of noncorrosive liquids. 13 Indoor use to provide a degree of protection against lint, dust seepage, external condensation and spraying of water, oil, and noncorrosive liquids. This material is reporduce, with permission from Underwriters Laboratories Inc. Standard for Safety for Cabinets and Boxes, UL 50, Copyright 1985 and Industrial Control Equipment, UL 508, Copyright 1984 by Underwriters Laboratories Inc. Underwriters Laboratories Inc. (UL) shall not be responsible to anyone for the use of or reliance upon a UL Standard by anyone. UL shall not incure any obligation or liability for damages, including consequential damages, arising out of or connection with the use, interpretation of, or reliance upon a UL Standard. Canadian Standards Association (Standard C22.2 Nos. 14, 40 and 94) Type Intended Use and Description 1 General purpose enclosure. Protects against accidental contact parts. 2 Indoor use and so constructed or protected that exposure to falling moisture will not impair the effectiveness of the enclosed equipment. 3 Outdoor use and so constructed or protected that exposure to the weather, to falling mositure, or to external splashing, will not impair the effectiveness of the enclosed equipment. 3R No CSA equivalent. 4 Indoor or outdoor use and so constructed that a stream of water from a hose will not result in water entering the enclosing case. 4X No CSA equivalent. 5 Indoor use and so constructed that dust cannot enter the enclosure; and accumulated dust will not result in temperatures exceeding specified values. 6 No CSA equivalent. 12 No CSA equivalent. 13 No CSA equivalent. 595

11 Degree of protection of the electrical equipment up to 1000 V a.c. and 1500V d.c. IP X1 X2 according to IEC 529 (1989) and EN (1991) X1 Protection of persons against contact with live parts Protection of equipment against ingress of solid foreign bodies X1 Protection against ingress of liquids 0 CEE-symbol Test None 0 CEE-symbol Test None Against access with hand and ingress of solid objects greater than 50 mm Against access with finger and ingress of solid objects greater than 12 mm Against access with tools and ingress of solid objects greater than 2.5 mm Against vertically falling drops Against drops of falling liquid at an angle up to 15 from the vertical Against water falling in rain at an angle up to 60 from the vertical Against water splashed from any direction (over 360 ) Against access with wires or strips and ingress of solid objects greater than 1 mm Complete protection against contact with live parts and ingress of harmful deposits of dust Complete protection against contact with live parts of ingress of dust Against water jets from any direction (over 360 ) Against water projects in powerful jets as from heavy seas Against immersion in water under defined conditions of pressure and time Against continuous submersion in water Additional letter to IP X1 X2 (optional) Additional letter Used with first characteristic numeral IPX1 Test Protection against access to hazardous parts A 0 Protection against access to hazardous parts B 0 and 1 Protection against access with a finger C 1 and 2 Protection against access with a tool D 1, 2 and 3 Protection against access with a wire 596

12 Decimal and Metric Equivalents of Common Fractions of an Inch Fraction Decimal Mm Fraction Decimal Mm. 1/ / / / / / / / / / / / / / / / ,875 9/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / Conversion Factors U.S. Customary Measures and Weights (Based on National Bureau of Standards) Length 1 inch = 1000 mils 1 furlong = 40 rods 1 foot = 12 inches 1 Statute mile = 8 furlongs 1 yard = 3 feet 1 Statute mile = feet 1 fathom = 6 feet 1 nautical mile = 6076 feet 1 rod = 5 1 /2 yards 1 league = 3 miles Area 1 sq foot = 144 sq inches 1 acre = 160 sq rods 1 sq yard = 9 sq feet 1 acre = 43,560 sq ft 1 sq rod = 30 1 /4 sq yards 1 sq mile = 640 acres Conversion Factors U.S. Customary Measures and Weights (Based on National Bureau of Standards) Liquid Capacity 1 gill = 4 fluid ounces 1 barrel = 31 1 /2 gallons 1 pint = 4 gills 1 hogshead = 2 bbl. (63 gal.) 1 quart = 2 pints 1 tun = 252 gallons 1 gallon = 4 quarts 1 barrel (petroleum) = 42 gallons Dry Capacity 2 pints = 1 quart = 67.2 cu in 8 quarts = 1 peck = cu in 4 pecks = 1 bushel = cu in Avoirdupois Weight (For other than drugs, gold, silver, etc.) 1 dram = grains 1 quarter = 25 pounds 1 ounce = 16 drams 1 short ton = 2000 pounds 1 pound = 16 ounces 1 long tonn = 2240 pounds 1 lb avdp = 7000 grains = grams = lb troy = lb apoth. 1 grain = 1 grain troy = 1 grain apoth. Temperature Conversion Table C F C F C F C F

13 Metric Equivalents of U. S. Customary Measures and Weights (Based on National Bureau of Standards) Length Cm = in. In. = cm Meter = ft. Ft. = m Meter = yd. Yd. = m Km = mile Mile = km Area Sq cm = sq. in. Sq. in. = sq cm Sq m = sq. ft. Sq. ft. = sq m Sq km = sq. mile sq. mile = sq km Volume Cu cm = cu. in. Cu. in. = cu cm Cu m = cu. ft. Cu. ft. = cu m Capacity Liters = cu. in. Cu. in. = liter Liter = cu. ft. Cu. ft. = liters Liter = gal. (U.S.) Gal. = liters Liter = bu. (U.S.) Bu. = liters cu. cm. Liter = qt. (liquid) or qt. (dry) lb. of pure water at 4 C=1 kg. Weight Gram = grains Grain = g. Gram = oz. avdp. Oz. avdp. = g. Kg = lb. avdp. Lb. avdp. = kg. Kg = ton (sht.) Ton (sht.) = kg. Pressure Kg per sq cm = lb. per sq. in. Lb per sq in = kg. per sq. cm. Kg per sq m = lb. per sq. ft. Lb per sq ft = kg. per sq. m. Kg per sq cm = normal atmosphere kg. per sq. cm. Normal atmosphere = bars lb. per sq. in. Pascals = lb/sq. in. Megapascals = 145 lb/sq. in. Lb per sq. in. = pascals Conversion Factors To Convert From To Multiply By # Angstrom unit... centimeters E-08 Atmospheres... mm of mercury at 0 C E+02 pounds/sq. in E+01 kilograms/sq. m E+04 Atomic mass unit... mass of electron E-04 mass of proton E+00 mass of neutron E+00 mass of A particle E+00 H, atom mass E+00 Bars... dynes/sq. cm E+06 Btu*... foot-pounds E+02 horsepower-hours E-04 kilopond-meters E+03 kilogram-calories* E-01 kilowatt-hours E-04 Btu*/hour... horsepower E-04 Btu*/(hour-sq ft)/ (gram-cal*/s.-sq. cm)/ ( F/in)... ( C/cm) E-04 Btu*/minute... foot-pounds/s E+01 horse power E-02 kilowatts E-02 Conversion Factors To Convert From To Multiply By # Btu*/second... kilopond-meters/s E+02 kilowatts E+00 Btu*/sq ft... gram-cal*/sq. cm E-01 Centimeters Hg (0 C) pounds-force/sq. in E-01 inches of water E+00 Centiposes... pound/foot-hours E+00 Circular mils... square mils E-01 Cubic feet/minute... gallons/second E-01 cubic cm/s E+02 Cubic feet/pound... cu. cm. /g E+01 Cubic feet/second... gallons/minute E+02 Cubic meters... cubic feet E+01 Degrees... radians E-02 Degrees/second... revolutions/minute E-01 Dynes... grams-force E-03 poundals E-05 Dyne-centimeters... pounds-force-feet E-08 Dynes/sq centimeter... atmospheres E-07 Electron volts... gram-calories* E-20 gram-cal*/mole E+04 cm- 1 (wave no.) E+03 kwh E-26 micrometers wavelength... ** Feet of H20 at 39.2 F.. inches of Hg at 32 F E-01 Foot-pounds-force... Btu* E-03 kilowatt-hours E-07 Foot-poundsforce/s... Btu*/min E-02 Gallons (U.S. Liquid)... cubic inches E+02 cubic feet E-01 Gal/min (of water)... pound/hr of water E+02 Gram-calories*... Btu E-03 Gram-cal*/sq. cm... Btu*/sq. ft E+00 Gram-force-cm... Btu* E-08 ergs E+02 Gram-mole Gas... cubic cm gas (0 C & 760mm) E+04 Grams-force... dynes E+02 Grams... pounds E-03 Grams of matter... electron volt E+32 Grams/cu cm... pounds/cu. inch E-02 pounds/cu. foot E+01 Grams-force/sq cm... centimeters of Hg E-02 atmosphere E-04 pounds-force/sq. ft E+02 Horsepower (mech)... foot-pounds-force/s E+02 kilowatts E-01 Horsepower hours... Btu* E+03 joule (abs) E+06 kilogram-cal* E+02 In of Hg at 32 F... pounds-force/sq. in E-01 In of H20 at 39.2 F (4 C)... centimeters of Hg E-01 pounds/sq. in E-02 pounds-force/sq. ft E+00 Joules (abs)... kilogram-calories* E-04 Kilogram-cal*... horse power-hours E-03 Kilopond-meter... Btu* E-03 ergs E+07 Kilowatt... average noon sunlight on 1 sq. m E+00 Btu* E+03 Kilowatt... horsepower E+00 Kilowatts... kilogram-cal*/minute E+01 Liter-atmospheres... Btu* E-02 Liters/kilogram... cubic ft/pound E-02 Liters/minute... cubic feet/s E-04 gallons/hours E+01 Lumens... watts E

14 Conversion Factors To Convert From To Multiply By # Newtons... dynes E+05 Newton-meters... joules E+00 Pound-celsius (Centrigrade) Unit... Btu* E+00 Pound-mol gas... cubic feet of gas (60 F at 1 atm) E+02 Pounds of H20 (4 C).. gallons of H2O E-01 Pounds of H20 at 64 F... cubic feet of H2O E-02 Pounds/gallon... grams/cu. cm E-01 Pounds/sq. in... atmospheres E-02 Radian... degrees E+01 Radians/s... revolutions/s E-01 Torricellis (Torr)... mm. of Hg. (0 C) E+00 Volt-coulomb... joules E+00 Watt-hour... Btu* E+00 Watts... foot-lb/minute E+01 horsepower E-03 lumens E+02 # E is the power of 10 by which the number must be multiplied. i.e., 4,047 E+03=4.047x10 3. Radiant watts at 5550 A. * Thermochemical. ** electron volts x micrometers wavelength = E+00. Factors for Conversion to International System (Si) Units Conversion Factors International System (SI) Units (from National Bureau of Standards Handbook 102) To Convert From To Multiply By # Acceleration Ft/sec 2... meter/sec E-01 In/sec 2... meter/sec E-02 Area Acre... meter E+03 Ft 2... meter E-02 In 2... meter E-04 Mile 2 (statute)... meter E+06 Yard meter E-01 Torque dyne-cm... newton-meter E-07 kgf-meter... newton-meter E+00 Ibf-inch... newton-meter E-01 Ibf-foot... newton-meter E+00 ozf-inch... newton-meter E-03 Torque/Length Ibf-ft/in... newton-m/m E+01 Ibf-in/in... newton-m/m E+00 Electricity and Magnetism amp hr... coulomb E+03 faraday (chem)... coulomb E+04 gauss... tesla E-04 gilbert... amp-turn E-01 maxwell... weber E-08 orested... amp/meter E+01 unit pole... weber E-07 Energy (includes Work) Btu*... joule E+03 calorie*... joule E+00 eletron volt... joule E-19 erg... joule E-07 ft-lb-force... joule E+00 kilowatt-hr... joule E+06 watt-sec... joule E+00 Energy/Area Time Btu*/ft 2 min... watt/meter E+02 Btu*/ft 2 hr... watt/meter E+00 cal*/cm 2 min... watt/meter E+02 To Convert From To Multiply By # Force dyne... newton E-05 kg-force... newton E+00 oz-force (av)... newton E-01 lb-force (av)... newton E+00 Force/Length lb-force/in... newton/meter E+02 lb-force/ft... newton/meter E+01 Heat Btu* in/sec ft2 deg F... watt/meter K E+02 Btu* in/hr ft2 deg F... watt/meter K E-01 Btu*/ft 2... joule/meter E+04 Btu*/hr ft 2 deg F... watt/meter 2 K E+00 Btu*/lbm deg F... joule/kg K E+03 Btu*/sec ft 2 deg F... watt/meter 2 K E+04 cal/cm 2... joule/meter E+04 cal/cm 2 sec... watt/meter E+04 cal/cm 2 sec deg C... watt/meter K E+02 cal*/g... joule/kg E+03 cal*/g deg C... joule/kg k E+03 Length astronomical unit... meter E+11 foot... meter E-01 inch... meter E-02 light year... meter E+15 mil... meter E-05 mile (statue)... meter E+03 yard... meter E-01 Light ft-candle... lux E+01 ft-lambert... candela/meter E+00 Mass oz mass (av)... kilogram E-02 lb-mass (av)... kilogram E-01 ton (2000 lbm)... kilogram E+02 Mass/Volume (includes Density) lbm/ft 3... kilogram/meter E+01 lbm/in 3... kilogram/meter E+04 oz mass (av)/in 3... kilogram/meter E+03 lb-mass (av)/gal... kilogram/meter E+02 Power Btu*/sec... watt E+03 Btu*/min... watt E+01 Btu*/hr... watt E-01 Cal*/sec... watt E+00 Cal*/min... watt E-02 erg/sec... watt E-07 ft-lb force/hr... watt E-04 ft-lb force/min... watt E-02 ft-lb force/sec... watt E+00 hp (elec)... watt E+02 Pressure (Force/Area) atm (760 Torr)... pascal E+05 bar... pascal E+05 dyne/cm 2... pascal E-01 gram (force)/cm 2... pascal E+01 in of Hg (60 F)... pascal E+03 in of water (60 F)... pascal E+02 mm of Hg (0 C)... pascal E+02 lb-force/ft 2... pascal E+01 lbf/in 2 (psi)... pascal E+03 Torr (mm Hg, 0 C)... pascal E+02 Velocity (includes Speed) ft/hr... meter/sec E-05 ft/min... meter/sec E

15 To Convert From To Multiply By # Velocity (Includes Speed) ft/sec... meter/sec E-01 in/sec... meter/sec E-02 mile/hr... meter/sec E-01 mile/min... meter/sec E+01 mile/sec... meter/sec E+03 mile/hr... km/hr E+00 Viscosity ft 2 /sec... meter 2 /sec E-02 poise... pascal-sec E-01 Ibm/ft sec... pascal-sec E+00 Ibf sec/ft 2... pascal-sec E+01 stokes... meter 2 /sec E-04 Volume (Includes Capacity) bushel (US)... meter E-02 ft 3... meter E-02 gallon (US)... meter E-03 inch 3... meter E-05 liter... meter E-03 oz (US fluid)... meter E-05 stere... meter E+00 yd 3... meter E-01 Volume/Time (Includes Flow) ft 3 /min... meter 3 /sec E-04 ft 3 /sec... meter 3 /sec E-02 in 3 /min... meter 3 /sec E-07 gal/min... meter 3 /sec E-05 * Thermochemical. # E indicates the power of 10 by which the number must be multiplied, i.e., 4.047E+03=4.047x10 3. Ampacities of Insulated Conductors Rated Volts, 60 to 90 C (140 to 194 F) Not More Than Three Conductors in Raceway or Cable or Earth (Directly Buried), Based on Ambient Temperature of 30 C (86 F) Size Temperature Rating of Conductor 60 C 75 C 85 C 90 C 60 C 75 C 85 C 90 C (140 F) (167 F) (185 F) (194 F) (140 F) (167 F) (185 F) (194 F) Type Types Type Types Types Types Type Types TW, FEPW, V TA,TBS, SA TW, RH, RHW, V TA,TBS, AWG UF RH, RHW, SIS, FEP, UF THHW, SA, SIS, THHW, FEPB, THW, RHH, kcmil THW, RHH, THWN, THHW, THWN, THHN, XHHW THHN, XHHW THHW, USE XHHW USE, ZW XHHW Copper Aluminum or Copper-Clad Aluminum / / / / The overcurrent protection for conductor types marked with an obelisk ( ) shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper; or 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum and copperclad aluminum after any correction factors for ambient temperature and number of conductors have been applied. For dry locations only. See 75 C column for wet locations. (From National Electrical Code 1990 NFPA Table ). Fuse Sizes Useful Information To Select Proper Size Fuse, Safety Switch or circuit Breaker For Motor Circuits 1. Single Phase, Squirrel- 2. Squirrel-Cade and Syn- Cage and Synchronous Chronous Auto-Trans- Full Full-Voltage, Reactor former Starting, High Types 1 and 2 Copper Load and Resistor Starting Reactance Squirrel-Cage Motors Wire Size Current Single Elem. Fuse Single Elem. Fuse Time Delay Fuse Rating Branch Branch Branch Types of Circuit Circuit Circuit Circuit Circuit Types RHW, Motor Fuse Switch Breaker Fuse Switch Breaker Fuse Switch T, THW, Amp Amp Size Amp* Amp Size Amp* Amp Size TW THWN

The Reliable Choice. Field Pocket Guide

The Reliable Choice. Field Pocket Guide The Reliable Choice Field Pocket Guide Allowable Ampacities of STABILOY Brand XHHW-2 and Copper 75 C (167 F) 90 C (194 F) 75 C (167 F) 90 C (194 F) Conductor Size (AWG or kcmil) Types RHW, THHW, THW, THWN,

More information

Electrical Design/Build Guide

Electrical Design/Build Guide 2017 Electrical Design/Build Guide Based on the 2017 National Electrical Code Copyright Durand & Associates 1986-2016 60 C Copper Ampacity 4 - Wire Fill - (Non-Current Carrying Neutral) 4 or 5 - Parallel

More information

Chapter 4 NEC & NEMA Standards 1

Chapter 4 NEC & NEMA Standards 1 Chapter 4 NEC & NEMA Standards 1 This section lists excerpts from industry, national, and international standards The excerpts are for illustration and educational purposes There are often several related

More information

Indoor use primarily to provide protection against contact with the enclosed equipment and against a limited amount of falling dust.

Indoor use primarily to provide protection against contact with the enclosed equipment and against a limited amount of falling dust. TECHNICAL REFERENCE Have a Technical question? Don t worry. Here in the c3controls Technical Reference section, you ll find all the information you need to help you make the right decision for your particular

More information

More information can be found at

More information can be found at A 1 Amperes Abcoulombs 2.998x10 10 Statcoulombs Acre-feet 43,560 Cubic feet Acre-feet 1233.49 Cubic meters Acre-feet 325,851 Gallons Acres.4047 Hectares Acres 43,560 Square feet Acres 4,047 Square meters

More information

If center column value is F, the C equivalent is to the left. If center column value is C, the F equivalent is to the right.

If center column value is F, the C equivalent is to the left. If center column value is C, the F equivalent is to the right. -40.00-40 -40.0-39.44-39 -38.2-38.89-38 -36.4-38.33-37 -34.6-37.78-36 -32.8-37.22-35 -31.0-36.67-34 -29.2-36.11-33 -27.4-35.56-32 -25.6-35.00-31 -23.8-34.44-30 -22.0-33.89-29 -20.2-33.33-28 -18.4-32.78-27

More information

ELECTRIC POWER RATINGS GUIDE

ELECTRIC POWER RATINGS GUIDE ELECTRIC POWER RATINGS GUIDE Generator Sets CONTENTS RATINGS GUIDE Caterpillar Diesel Ratings 4 Caterpillar Diesel Rental Ratings 9 Caterpillar Diesel Ratings Definitions 0 Caterpillar Ratings 4 Caterpillar

More information

CONVERSION TABLES TO CONVERT MULTIPLY BY TO OBTAIN TO CONVERT MULTIPLY BY TO OBTAIN TO CONVERT MULTIPLY BY TO OBTAIN

CONVERSION TABLES TO CONVERT MULTIPLY BY TO OBTAIN TO CONVERT MULTIPLY BY TO OBTAIN TO CONVERT MULTIPLY BY TO OBTAIN A acres 43,560 sq. ft. candlepow er 12.5664 lumens centipoise 0.01 gr./cm.-sec. acres 4,047 sq. Meters centares 1.00 sq. meters centipoise 6.72 x 10-4 pound/ft.-sec. acres 0.001562 sq. Miles centigrade

More information

Technical data OT16E3 OT160E3 UL & CSA

Technical data OT16E3 OT160E3 UL & CSA Technical data OT16E3 OT16E3 UL & CSA UL & CSA Catalog number 3 pole OT16E3 OT25E3 OT32E3 OT45E3 OT63E3 OT3E3 OT6E3 OT1E3 OT16E3 Approvals 1 2 pole N/A N/A N/A N/A N/A N/A N/A N/A UL98 & EC 3 pole UL58

More information

Mecklenburg County Common Code Defects

Mecklenburg County Common Code Defects Electrical Code Defects Improper Over Current Protection Code Description 310.15 Ampacities for s Rated 0 2000 Volts. (A) General. (1) Tables or Engineering Supervision. Ampacities for conductors shall

More information

YOUR CLEAR CHOICE FOR PREMIUM PACKAGING SOLUTIONS

YOUR CLEAR CHOICE FOR PREMIUM PACKAGING SOLUTIONS YOUR CLEAR CHOICE FOR PREMIUM PACKAGING SOLUTIONS Unit of Length Milli (mm) to Inches MM Decimal of inch Approx. Inch MM Decimal of inch Approx. inch 1 0.0394 3/64 14 0.5512 9/16 2 0.0787 5/64 15 0.5906

More information

Motor Branch Circuit Over-Current Protection

Motor Branch Circuit Over-Current Protection Motor Branch Circuit Over-Current Protection For HVAC Project Engineers Fachgesprach 9 WTF Institute of Higher Learning By Mat Ansari PE 2-18-2016 For HVAC Project Engineer's Reference Use Only Not for

More information

APPENDIX A MISCELLANEOUS DATA AND CONVERSION FACTORS. 9/85 (Reformatted 1/95) Appendix A A-1

APPENDIX A MISCELLANEOUS DATA AND CONVERSION FACTORS. 9/85 (Reformatted 1/95) Appendix A A-1 APPENDIX A MISCELLANEOUS DATA AND CONVERSION FACTORS 9/85 (Reformatted 1/95) Appendix A A-1 A-2 EMISSION FACTORS (Reformatted 1/95) 9/85 SOME USEFUL WEIGHTS AND MEASURES Unit Of Measure Equivalent grain

More information

311 Conversion Factors

311 Conversion Factors 311 Conversion Factors Master Converter Some excellent software for converting from nearly any unit of measure to another can be purchased for US$15.00 from Savard Software. Download it from this site

More information

Volume 2 Charts, Formulas, and Other Useful Information

Volume 2 Charts, Formulas, and Other Useful Information Volume 2 Charts, Formulas, and Other Useful Information Aluminum Conductor Conductor Terminations 61 Compact Aluminum (Conduit Fill Tables) 68-79 Ampacity Dwelling Services 48 1-phase Loads on a 3-phase

More information

Electrical Tech Note 106

Electrical Tech Note 106 Electrical Tech Note 106 Biosystems & Agricultural Engineering Department Michigan State University Master Exam Study Guide and Sample Questions 1 Based on the 2014 NEC, Part 8 of PA 230, PA 407, and the

More information

GENERAL CONVERSION FORMULAE

GENERAL CONVERSION FORMULAE Conversion Tables GENERAL CONVERSION FORMULAE inches millimetres 25.4 millimetres inches 0.0394 inches centimetres 2.54 centimetres inches 0.3937 feet metres 0.3048 metres feet 3.281 yards metres 0.9144

More information

TABLES & CONVERSIONS. Linear Conversions. Mass Conversions. Area Conversions. Mass per Area Conversions. Area per Volume Conversions

TABLES & CONVERSIONS. Linear Conversions. Mass Conversions. Area Conversions. Mass per Area Conversions. Area per Volume Conversions TABLES & CONVERSIONS Linear Conversions inches 25.4 millimeters millimeters 0.039 inches feet 0.3 meters meters 3.28 feet yards 0.91 meters meters 1.09 yards miles 1.61 kilometers kilometers 0.62 miles

More information

DISCONTINUED PRODUCT POWER PROTECTION. Series 600 UPS. Multi-Module Three Phase 338 kva to 1000 kva; 60 Hz. Installation Manual

DISCONTINUED PRODUCT POWER PROTECTION. Series 600 UPS. Multi-Module Three Phase 338 kva to 1000 kva; 60 Hz. Installation Manual POWER PROTECTION Series 600 UPS Multi-Module Three Phase 338 kva to 1000 kva; 60 Hz Installation Manual TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS.............................................1 1.0

More information

Temperature Conversion. degrees Fahrenheit to degrees Celcius > C =(F-32)/1.8. kelvin to degrees Celcius --> C = K-273.

Temperature Conversion. degrees Fahrenheit to degrees Celcius > C =(F-32)/1.8. kelvin to degrees Celcius --> C = K-273. Links to online conversion calculators: http://www.onlineconversion.com/ http://www.infoplease.com/pages/unitconversion.html http://www.worldwidemetric.com/metcal.htm http://www.convert-me.com/en/ http://education.yahoo.com/reference/weights_and_measures/

More information

PART A General Conductor Requirements

PART A General Conductor Requirements PART A General Conductor Requirements 6.1 Conductor Insulation Property Table 310.13 of the NEC provides information on conductor properties such as permitted use, maximum operating temperature, and other

More information

Metric Conversion Factors

Metric Conversion Factors Acres (a) 0.4047 Hectare (ha) Acres 43,560 Sq. feet (ft 2 ) Acres 0.00405 Sq. kilometer (km 2 ) Acres 4047 Sq. meter (m 2 ) Acres 4840 Sq. yards (yd 2 ) Acre-feet 325,851 Sq. feet (ft 2 ) Acre-feet 43560

More information

ELECTRIC POWER RATINGS GUIDE

ELECTRIC POWER RATINGS GUIDE ELECTRIC POWER RATINGS GUIDE Generator Sets OLYMPIAN RATINGS GUIDE Generator Sets 81-04.indd 1 6/12/13 8: 81-04.indd 2 6/12/13 8: CONTENTS Ratings Guide 4 Olympian Diesel Ratings 50 Hz 7 Olympian Diesel

More information

General information about motor protection

General information about motor protection Application guide General information about motor protection Typical construction of a motor starter Disconnect Switch UL 98 - UL489 CSA C22.2 # 4 CSA C22.2 # 5 Fuses SIRCO Non-Fusible Disconnect Switch

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 310 310.120 CHANGES FROM 2011 TO 2014 CODE ARE IN RED ARTICLE 310 Conductors for General Wiring I. General 310.2 Definitions Electrical Ducts Electrical conduits, or other

More information

Stearns Heavy Duty Clutches & Brakes... Rugged, Reliable

Stearns Heavy Duty Clutches & Brakes... Rugged, Reliable Stearns Heavy Duty Clutches & Brakes... Rugged, Reliable Stearns heavy duty clutches and brakes represent over 75 years of design, engineering and on-the-job experience. Stearns products are backed by

More information

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Journey Exam Study Guide and Sample Questions 1 Based on the 2002 NEC, Part 8 of PA 230, and the 2003 MRC The Journey

More information

To Convert From To Multiply By To Convert From To Multiply By

To Convert From To Multiply By To Convert From To Multiply By Reference Data Metric Conversion Chart Reference Data To Convert From To Multiply By To Convert From To Multiply By Angle Length degree radian (rad) 0.01745329 foot (ft) meter (m) 0.3048 radian (rad) degree

More information

Quick Engineering Facts Decimal Metric

Quick Engineering Facts Decimal Metric Decimal Metric A. Decimal and Metric Equivalents Fraction (Inch) Decimal (Inch) mm Fraction (Inch) Decimal (Inch) mm 1/64 0.01562 0.397 33/64 0.51562 13.097 1/32 0.03125 0.794 17/32 0.53125 13.494 3/64

More information

SECTION. Watertight & Dust-Tight Plugs & Connectors

SECTION. Watertight & Dust-Tight Plugs & Connectors SECTION Watertight & ust-tight Wetguard Product Line Section Contents LIFETIME Wetguard Plugs, Connectors & Straight Blade 2-Pole 3-Wire 2-Pole 3-Wire 3-Pole 4-Wire 3-Pole 3-Wire Non- 4-Pole 4-Wire Non-

More information

Overview V10-T1-2 V10-T1-2 V10-T1-3 V10-T1-4 V10-T1-5 V10-T1-6 V10-T1-7 V10-T1-7 V10-T1-8

Overview V10-T1-2 V10-T1-2 V10-T1-3 V10-T1-4 V10-T1-5 V10-T1-6 V10-T1-7 V10-T1-7 V10-T1-8 Enclosed Control. Welcome............................................... Eaton Corporation........................................ Eaton Support and Service Center Capabilities.................. Technical

More information

DISCONTINUED PRODUCT

DISCONTINUED PRODUCT The following WARNING applies to all battery cabinets supplied with UPS systems: WARNING HAZARD INTERNAL BATTERY STRAPPING MUST BE VERIFIED BY MANU- FACTURER PRIOR TO MOVING A BATTERY CABINET. Battery

More information

Engineering Information. Solenoid Valves Principles of Operation. Solenoid Valves. Direct Acting Valves (Figures 1A, 1B)

Engineering Information. Solenoid Valves Principles of Operation. Solenoid Valves. Direct Acting Valves (Figures 1A, 1B) 4 Engineering Information Principles of Operation A solenoid valve is a combination of two basic functional units: A solenoid (electromagnet) with its core A valve body containing one or more orifices

More information

Pretest Module 24 Three-phase Service Entrance

Pretest Module 24 Three-phase Service Entrance Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 060628 2006 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

2017 NEC Electrical Review RV

2017 NEC Electrical Review RV PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.

More information

ËÕߪ Õ» ç åé. 50BY/BL Series. Single-Package Cooling Units 90, ,500 BTUH. World's No.1 Air Conditioning Expert

ËÕߪ Õ» ç åé. 50BY/BL Series. Single-Package Cooling Units 90, ,500 BTUH. World's No.1 Air Conditioning Expert ËÕߪ Õ» ç åé BY/BL Series Single-Package Cooling Units 90,000-895,0 BTUH World's No.1 Air Conditioning Expert www.carrier.co.th BY/BL Series Features Commercial or Industrial Applications Single- or Multiple-Unit

More information

Modifiable TITAN Horizontal Motors Accessories and Modifications

Modifiable TITAN Horizontal Motors Accessories and Modifications 36. Rotor, Standard And Optional Construction Standard rotor construction of 449, 5000 and 5800 frame TITAN products is typically die-cast aluminum. 720 RPM and slower is typically fabricated aluminum.

More information

SECTION COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

SECTION COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT SECTION 230513 - COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Single phase electric motors. B. Three phase electric motors. 1.2 REFERENCE STANDARDS A. ABMA STD 9

More information

SECTION MOTOR REQUIREMENTS for HVAC

SECTION MOTOR REQUIREMENTS for HVAC PART 1 GENERAL 1.1 SECTION INCLUDES A. Single-phase electric motors B. Three-phase electric motors 1.2 REFERENCES SECTION 23 05 13 MOTOR REQUIREMENTS for HVAC A. ABMA 9 - Load Ratings and Fatigue Life

More information

FOR MORE INFORMATION CALL CLARK GENERAL ENGINEERING INFORMATION WARNING & SAFETY REMINDER...

FOR MORE INFORMATION CALL CLARK GENERAL ENGINEERING INFORMATION WARNING & SAFETY REMINDER... GENERAL ENGINEERING INFORMATION Index Section L WARNING & SAFETY REMINDER..................................................OPPOSITE PAGE ITEM PAGE HORSEPOWER/TORQUE..............................................................

More information

Series Low Pressure Steam Heating Boiler Safety Valves

Series Low Pressure Steam Heating Boiler Safety Valves 12-200 Series Low Pressure Steam Heating Boiler Safety Valves Section IV Heating Boilers Medium capacity safety valves protect ASME Section IV low pressure steam heating boilers. Cast bronze, full nozzle

More information

Section 10 Chapter 20

Section 10 Chapter 20 Section 10 Chapter 20 24 Valve, 8.3 Liter Engine Specifications Note: All coding used in the 8.3 Liter and 9 Liter engine manuals are Cuins engine codes. These engine codes have no meaning to New Holland

More information

NEMA Contactors & Starters (Freedom)

NEMA Contactors & Starters (Freedom) Page 1 February, 1 Supersedes TIP AN1, AN, CN1, CN Pages 1-0, Dated 1/1/4 ECN01, ECN0, ECN0, ECN0, ECN0 AN1, AN, CN1 & CN Sizes 00-, 00V Max. Non-Reversing & Reversing NEMA Type Enclosures 1, R, 4X & 1

More information

Liquid Weight. 1 gal. distilled water gal. sea water gal. proof spirits Oils

Liquid Weight. 1 gal. distilled water gal. sea water gal. proof spirits Oils Weights and Measures Avoirdupois Weight Drams 6 = oz. = 47. grains troy 26 = 6 = lb. =.2 lb. troy 6400 = 400 = 2 = quarter 2600 = 600 = 00 = 4 = cwt. 2000 = 2000 = 2000 = 80 = 20 = ton Troy Weight Grains

More information

PLUMBING MATHEMATICS

PLUMBING MATHEMATICS PLUMBING MATHEMATICS A review of basic fundamentals of mathematics is essential to successful applications of plumbing principals. An acceptable reference that may be used during your examination is Mathematics

More information

DC CIRCUITS ELECTROMAGNETISM

DC CIRCUITS ELECTROMAGNETISM DC CIRCUITS 1. State and Explain Ohm s Law. Write in brief about the limitations of Ohm s Law. 2. State and explain Kirchhoff s laws. 3. Write in brief about disadvantages of series circuit and advantages

More information

LOW STATIC FAN COIL UNITS District Cooling Chilled Water Application

LOW STATIC FAN COIL UNITS District Cooling Chilled Water Application STATIC FAN COIL UNITS District Cooling Chilled Water Application CLASSIFIED INSULATION & FILTER MEDIA GFC LD Series Cooling Capacity Range 9,690 yo 46,064 BTU/HR (4 ROWS ) GFC-LD-TC-10-13 3 General Specifications

More information

Proximity Sensors. Reference Information. Principles of Operation. Proximity Sensors

Proximity Sensors. Reference Information. Principles of Operation. Proximity Sensors Reference Proximity Sensors Principles of Operation Inductive Proximity sensors are generally constructed with four main elements: (1) a coil and ferrite core assembly; (2) an oscillator; (3) a convertor/trigger

More information

Product Information Packet CP500808LR-4 800HP,897RPM,3PH,60HZ,G50,A95260M,TEFC,F

Product Information Packet CP500808LR-4 800HP,897RPM,3PH,60HZ,G50,A95260M,TEFC,F Product Information Packet CP500808LR-4 800HP,897RPM,3PH,60HZ,G50,A95260M,TEFC,F Copyright All product information within this document is subject to ABB Motors and Mechanical Inc. copyright protection,

More information

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators MAx-305 & MAx-38 Series MAx-405 Through MAx-49 Series Two-Position Actuators General Instructions Application For two-position operation of dampers, valves, and other equipment which require the return

More information

Industrial and Commercial Duty IEC Motors

Industrial and Commercial Duty IEC Motors Industrial and Commercial Duty IEC Motors A Regal Brand Five product families delivering a world of opportunity LEESON Passport Series IEC Motors. There s a world of opportunity right here at home. The

More information

SECTION M CONTENTS ENGINEERING DATA DESCRIPTION Flow Data

SECTION M CONTENTS ENGINEERING DATA DESCRIPTION Flow Data SECTION M CONTENTS ENGINEERING DATA DESCRIPTION Flow Data PAGE 70-100, 71-100, 71AR, 73A-100, 74-100, 76-100, 80-100, 81-100 & 89-100 Series M-1 76F, 77, 77AR, 82-100, 82-200, 83R-100, 83R-200, 83-500,

More information

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1 TABLE OF CONTENTS Introduction...xv About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1 Unit 1 Electrician s Math and Basic Electrical Formulas... 1 Part A Electrician s Math...

More information

Pretest Module 21 Units 1-4 AC Generators & Three-Phase Motors

Pretest Module 21 Units 1-4 AC Generators & Three-Phase Motors Pretest Module 21 Units 1-4 AC Generators & Three-Phase Motors 1. What are the two main parts of a three-phase motor? Stator and Rotor 2. Which part of a three-phase squirrel-cage induction motor is a

More information

Introduction. Nexans wire and cable. Contact us for all your wire and cable needs

Introduction. Nexans wire and cable. Contact us for all your wire and cable needs Introduction Nexans is one of the largest wire and cable manufacturers in the world, and in North America. In North America we manufacture in locations across the United States and Canada. We design and

More information

Product Information Packet ECP50504L-4 500HP,1789RPM,3PH,60HZ,5010,TEFC,F1

Product Information Packet ECP50504L-4 500HP,1789RPM,3PH,60HZ,5010,TEFC,F1 Product Information Packet ECP50504L-4 500HP,1789RPM,3PH,60HZ,5010,TEFC,F1 Copyright All product information within this document is subject to ABB Motors and Mechanical Inc. copyright protection, unless

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 040709 2003 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

Appendix. Conversion Factors LENGTH

Appendix. Conversion Factors LENGTH Appendix Conversion Factors * LENGTH Inches feet 0.083333 angstrom units 2.54 x 10 8 micros 25400 millis 25.4 centis 2.54 s 0.0254 Feet inches 12.0 angstrom units 3.048 x 10 9 micros 304800 millis 304.80

More information

SEWPCC UPGRADING/EXPANSION PROJECT BID OPPORTUNITY SECTION LOW-VOLTAGE AC INDUCTION MOTORS

SEWPCC UPGRADING/EXPANSION PROJECT BID OPPORTUNITY SECTION LOW-VOLTAGE AC INDUCTION MOTORS SECTION 26 20 00 LOW-VOLTAGE AC INDUCTION MOTORS SEWPCC UPGRADING/EXPANSION PROJECT PART 1 GENERAL 1.1 RELATED SECTIONS A. This section applies only when referenced by a motor-driven equipment specification.

More information

Power Factor Correction

Power Factor Correction AE9-1249 R10 August 2008 Power Factor Correction Index Page 1. Introduction... 1 2. Electrical Fundamentals... 1 3. Electrical Formulas... 2 4. Apparent Power and Actual Power... 2 5. Effects of Poor Power

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

FRACTIONAL HORSEPOWER MOTORS & ACCESSORIES

FRACTIONAL HORSEPOWER MOTORS & ACCESSORIES TABLE OF CONTENTS Motor Information Guide Definitions And Abbreviations... page 2 Motor Identification Without A Nameplate What To Look For... page 3 Direct Drive Blower Motors: Two Speed... page 4 Three

More information

ECN A A A - B - C - D - E - F - A - B - C - D - E - F - NEMA Size 5 - Size Size Size Size Size 9

ECN A A A - B - C - D - E - F - A - B - C - D - E - F - NEMA Size 5 - Size Size Size Size Size 9 February 999 NEA Freedom Contactors and ers Catalog Number Selection - ECN A A F - Design N = Nema odification Codes (See Pages -6 to -) Class Page 0 - Contactors -4 0 - Reversing Contactors -8 05 - FVNR

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090529 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW Line/Load Reactors are components designed to improve the

More information

Code Calculations. for an Off-Grid PV System

Code Calculations. for an Off-Grid PV System Code Calculations for an Off-Grid PV System John Wiles Sponsored by the Photovoltaic Systems Assistance Center, Sandia National Laboratories Judy LaPointe s home is on its way to becoming a finished, off-grid

More information

Series Low Pressure Steam Boiler Safety Valves

Series Low Pressure Steam Boiler Safety Valves 14-200 Series Low Pressure Steam Boiler Safety Valves ASME Section IV Set pressures from 5 to 15. Sizes 2", 2-1/2" and 3". Section IV Heating Boilers Applications: The 14 Series is an ASME Section IV high

More information

High Reliability Power System Design

High Reliability Power System Design High Reliability Power System Design Buenos Aires, Argentina June 25 & 26, 2009 Keene M. Matsuda, P.E. Regional Electrical Manager Senior Member IEEE IEEE/PES Distinguished Lecturer ke.matsuda@ieee.org

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

Electrical Power Electric power electrical electric power Electric power electric electric

Electrical Power Electric power electrical electric power Electric power electric electric Power Calculations Electrical Power Electric power is the rate at which electrical energy is transferred by an electric circuit. The SI unit of power is the watt, one joule per second. Electric power is

More information

POCKET GUIDE for TROUBLESHOOTING Gas Products To be used by F.P.I. trained service technicians only.

POCKET GUIDE for TROUBLESHOOTING Gas Products To be used by F.P.I. trained service technicians only. POCKET GUIDE for TROUBLESHOOTING Gas Products To be used by F.P.I. trained service technicians only. 908-489 02/26/99 Table of Contents Tools and Instruments...3 Problem A Pilot not igniting after repeated

More information

Product Information Packet ECP4410T-4 125HP,1785RPM,3PH,60HZ,444T,A44076M,TEFC

Product Information Packet ECP4410T-4 125HP,1785RPM,3PH,60HZ,444T,A44076M,TEFC Product Information Packet ECP440T-4 5HP,785RPM,3PH,60HZ,444T,A44076M,TEFC Copyright All product information within this document is subject to ABB Motors and Mechanical Inc. copyright protection, unless

More information

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS November 17, 2016 Engineering Service Specifications Table of Contents Commercial Service Requirements SLEMCO Commercial

More information

MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC.

MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC. MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC. CALMANUAL HOW TO APPLY CAPACITORS TO LOW VOLTAGE POWER SYSTEMS. SECTION INDEX SECTION I POWER FACTOR UNDERSTANDING POWER FACTOR...

More information

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters Text Book: Chapter 6, Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Paul I-Hai

More information

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 480 Volts, 60Hz. Page 1 of 14. April 15, 2010: updated capacitor UL File number)

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 480 Volts, 60Hz. Page 1 of 14. April 15, 2010: updated capacitor UL File number) POWER QUALITY INSTRUCTION MANUAL Type SWF Sine Wave Filters 480 Volts, 60Hz April 15, 2010: updated capacitor UL File number) Page 1 of 14 Contents 1. Introduction & SAFETY 2. Theory of operation 3. Advantage

More information

Big performance in a small package

Big performance in a small package Series usible & Non-fusible 100 400A Suitable as a Service Entrance ing Means TIP! Manual Switching Devices: Control, oad or usible Which is Best or Your Application? Application Data Typical Control Switch

More information

Product Information Packet ECP4406T-4 150HP,1785RPM,3PH,60HZ,445T,A4488M,TEFC

Product Information Packet ECP4406T-4 150HP,1785RPM,3PH,60HZ,445T,A4488M,TEFC Product Information Packet ECP4406T-4 150HP,1785RPM,3PH,60HZ,445T,A4488M,TEFC Copyright All product information within this document is subject to ABB Motors and Mechanical Inc. copyright protection, unless

More information

Product Information Packet EM4313T 75HP,3550RPM,3PH,60HZ,365TS,1464M,TEFC,F

Product Information Packet EM4313T 75HP,3550RPM,3PH,60HZ,365TS,1464M,TEFC,F Product Information Packet EM1T 75HP,550RPM,PH,60HZ,65TS,16M,TEFC,F Copyright All product information within this document is subject to A Motors and Mechanical Inc. copyright protection, unless otherwise

More information

QHSAS APPROVED COMPANY APPROVED COMPANY APPROVED COMPANY. ISO 9001 Quality Management Systems. ISO Environmental Management Systems

QHSAS APPROVED COMPANY APPROVED COMPANY APPROVED COMPANY. ISO 9001 Quality Management Systems. ISO Environmental Management Systems APPROVED COMPANY ISO 9001 Quality Management Systems APPROVED COMPANY QHSAS 18001 ISO 1001 Environmental Management Systems APPROVED COMPANY FOREWORD Spell Group started its journey in 19 when two enthusiastic

More information

Q6SE Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase

Q6SE Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase TECHNICAL SPECIFICATIONS Q6SE Series Single Packaged Heat Pump, Single Phase Q6SE-14 SEER, 8.0 HSPF 2-5 Ton Units Cooling: 23,000 to 58,000 Btuh Heating: 22,800 to 59,000 Btuh The Q6 Series single packaged

More information

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS 50 AND 60 HZ DESCRIPTION FEATURES

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS 50 AND 60 HZ DESCRIPTION FEATURES (791) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS 50 AND 60 HZ H1CE180 & 240 15 AND 20 NOMINAL TONS (60 HZ) 13 AND 17-1/2 NOMINAL TONS (50 HZ) SUNLINE 2000 DESCRIPTION These Sunline 2000 units are completely

More information

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN Motor Contactor Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN rail) up to 45 kw Range from 4 to 110 kw (AC 3, 380/415V) Finger proof ( VBG 4) Accessoires

More information

Beaver Power Factor Correction Capacitors

Beaver Power Factor Correction Capacitors Beaver Power Factor Correction Capacitors Beaver Low Voltage Power Factor Correction Capacitors are designed for long life and are made with the highest quality materials. All units are assembled in Canada

More information

MATERIAL LIST SPECIFIC TO PART #05724

MATERIAL LIST SPECIFIC TO PART #05724 PD2C HOIST MATERIAL LIST SPECIFIC TO PART #05724 LIT2457-2009 Copyright 2009 PACCAR Winch Division All Rights Reserved This page intentioanlly left blank 2 MODEL NUMBER AND SERIAL NUMBER When information

More information

Q6SD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase

Q6SD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Heat Pump, Single Phase TECHNICAL SPECIFICATIONS Q6SD Series Single Packaged Heat Pump, Single Phase Q6SD-13 SEER, R-410A 2-5 Ton Units Cooling: 22,800 to 58,500 Btuh Heating: 22,800 to 58,500 Btuh The Q6 Series single packaged

More information

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code 2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of

More information

General Section. Fahrenheit to Celsius Temperature Conversions

General Section. Fahrenheit to Celsius Temperature Conversions General Section Table of Contents Temperature Conversions Days of the Month Periodic Table of the Elements Tables of Common Equivalents Length Area Cubic Liquid Weights Dry Weights Energy Time Amounts

More information

GQ6SD Series. Single Packaged Heat Pump 13 SEER, R-410A 2-5 Ton Units TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS WARRANTY

GQ6SD Series. Single Packaged Heat Pump 13 SEER, R-410A 2-5 Ton Units TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS WARRANTY TECHNICAL SPECIFICATIONS GQ6SD Series Single Packaged Heat Pump 13 SEER, R-410A 2-5 Ton Units The GQ6 Series single packaged units are high efficiency self contained cooling and heating units that can

More information

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

MATERIAL LIST PD7C. PACR WINCH DIVISION P.O. Box 547 Broken Arrow, Oklahoma PHONE: (918) FAX: (918)

MATERIAL LIST PD7C. PACR WINCH DIVISION P.O. Box 547 Broken Arrow, Oklahoma PHONE: (918) FAX: (918) PD7C MATERIAL LIST PACR WINCH DIVISION P.O. Box 57 Broken Arrow, Oklahoma 7013 PHONE: (9) 851-8511 FAX: (9) 259-1575 www.paccarwinch.com LIT-222 R2 12/2008 Printed in U.S.A. Copyright 2008 PACCAR Winch

More information

grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2

grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2 grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2 grounded in service wired to innovate www.cable.alcan.com Type XHHW-2 and Type USE-2/RHH/RHW-2 Alcan manufactures XHHW-2 and

More information

Electricity and Hydrogen: The energy carriers. Energy and Power for Electricity Electrical Distribution Hydrogen not a source, a carrier

Electricity and Hydrogen: The energy carriers. Energy and Power for Electricity Electrical Distribution Hydrogen not a source, a carrier Electricity and Hydrogen: The energy carriers Energy and Power for Electricity Electrical Distribution Hydrogen not a source, a carrier Unit 07 Electricity - Slide 1 Quiz The wheels of a 5000kg truck place

More information

Big performance in a small package

Big performance in a small package Series Fusible & Non-fusible Sprecher + Schuh s series of fused and non-fused disconnect switches comply with service entrance requirements. This family of rod operated switches is suitable for applications

More information

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com Power Quality Power Factor Wiring and Service Scope Power factor is a major consideration in efficient building or system operation. It is the measure of how effectively your equipment is converting electric

More information

Steve Schouten. Donna Densmore

Steve Schouten. Donna Densmore March 12, 2013 2 Steve Schouten Donna Densmore 3 Mike Carter Justin Kale 4 Basics Motor Loads Operation Advantages/ Disadvantages Sizing a VFD Power Quality Issues Source: Emerson Industrial Automation

More information

M3500 Industrial Pressure Transmitter

M3500 Industrial Pressure Transmitter M3500 Industrial Pressure Transmitter The M3500 is a high accuracy industrial pressure transmitter featuring HART communications and a cast aluminum enclosure for indoor or outdoor use. Typical output

More information

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49 UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1 PART A ELECTRICIAN S MATH...1 Introduction...1 1.1 Whole Numbers...1 1.2 Decimal...1 1.3 Fractions...1 1.4 Percentages...2 1.5

More information

GE 8000-Line Motor Control Centers

GE 8000-Line Motor Control Centers GE 8000-Line -1 ENCLOSURE TYPES TYPE 1 General Purpose, Indoor Intended for use indoors, primarily to prevent accidental contact of personnel with the enclosed equipment, in areas where unusual service

More information

Installation & Operating Manual

Installation & Operating Manual Installation & Operating Manual 6 WS Series Submersible Turbine Pumps Congratulations On Your Choice In Purchasing This Webtrol Pump 6/11 Edition Its Quality is unsurpassed in material and workmanship

More information