THE ISRAEL ELECTRIC CORPORATION LTD. GENERATION DIVISION SPECIFICATION GD1/16
|
|
- Kerry Hancock
- 5 years ago
- Views:
Transcription
1 . POWER STATION HIGH-VOLTAGE MOTOR REWINDING INDUCED DRAFT FAN MOTOR RUTENBERG 3-4 Prepared by: Checked by: Approved by: Relu ILIE Igor GOBENKO December 2016
2 1. Purchaser The Israel Electric Corporation Ltd. (IECo) - Israel. 2. Name Of Item / Project Full rewinding of induced draft fan motor Rutenberg Location Of Item / Project The motor covered by this specification is located in Purchaser s power station or storage. 4. Scope The scope of work covered by this specification is full rewinding of induced draft fan motor stator, located in Rutenberg 3-4 power station. Based on results of tests from Item 11.1 and motor history, the scope of work shall be in details defined between Purchaser and Contractor Project Description N/A 4.2. Scope Of Supply The motor name plate rated data for the specific motor to be repaired are as following. The single line diagram is attached to this specification. IECo will decide if the motor to be repaired is originally made either by KONČAR Croatia, respectively by ABB Switzerland as detailed below Phases: Frequency: 50 Hz Rated voltage: V Rated speed: 746 rpm Insulation Class: F Rating: 6125 kw Rated current: 314 A Power factor: Connection of stator winding: star Original manufacturer: KONČAR Croatia, respectively ABB Switzerland Type: 6AJZ0a 900L1-8, respectively ONG 900 fa Serial number: 23358, respectively HM Protection: IP 55, respectively W24. The scope of work shall include at least the following (but not only): Stator core flux test (including thermographic test), after removing the old coils and after installing the new coils Full rewinding, which shall include dedicated turn insulation (in addition to strand insulation) End-winding support hardware repair or replacement (if necessary) Replacement of motor heaters 2
3 Renovation or replacement of motor main terminals. It shall include suitable protection for overvoltage originated by vacuum circuit breakers (surge arresters and capacitors) The neutral point of stator windings shall be externally accessible and shall allow dismantling in order to permit each phase separate insulation testing Replacement of support isolators Cleaning and painting the motor and motor leads box (first layer epoxy and second layer polyurethane RAL 1023) Replacement of the bearings (IECo will supply the bearings) Replacement of the RTD's Rotor check and repair (if necessary) Rotor balance, if repaired Check, test and adjustment of accessories (e.g. cable entries, earthing bolts, terminal boxes, terminal marking, enclosure, nameplate labels, lubrication, fans, thermal monitors, coolers etc.). 5. Terminal Points &Terminal Connections N/A 6. Cyber & Information Security N/A 7. Quality Assurance & Quality Control 7.1. General Quality Requirements To be checked by Purchaser's Quality Control representative. The manufacturing and all components shall confirm to quality requirements and shall ensure high reliability. The Bidder shall submit with his proposal copies of quality assurance and quality control procedures. The Bidder shall provide a full I&T plan with references to his shop specifications, standards used, and acceptance criteria. The acceptance tests (paragraph 11.2) shall be performed in the factory, in presence of Purchaser s Quality Control representative. The purchaser reserves the right to send a representative to attend part or all of the acceptance tests. The contractor shall include in its technical offer a test plan (appendix A), which will include at least all of the tests according to this specification (paragraph acceptance test), including tentative time schedule. The contractor shall announce the updated time schedule, immediately after receiving the order and shall update it if necessary. The Contractor shall notify IECo by a non-conformance report in any case or process a problem occurs, for any component which is out of specification, for any component testing if a failure occurs Interchangeability 3
4 The repaired motor shall provide the same or better parameters, characteristics and performance, from all points of view, as the motor before repairing. 8. Standards & Codes In principle, the required tests procedure shall conform to IEC relevant standards (mainly IEC series). For tests not covered by IEC standards, ANSI, IEEE, NEMA, VDE standards shall be applied, or the normal Purchaser internal practice. 9. Technical Documentation 9.1. General N/A 9.2. Technical Documentation Attached to Proposal The Bidder shall supply to Purchaser the guarantee values of motor relevant data that will be achieved after the repair. The tolerances for guarantee values shall be according to IEC Technical Documentation to Deliver after Award Notification The Contractor shall provide with the repaired or overhauled motor all data and drawings showing the details of the work performed (i.e. active core dimensions, slot details, insulation material type, cross section of coils, rated power if changed, losses if influenced by repair, etc.). If applicable, these data shall be presented comparatively with the condition before repair. In addition, the Contractor shall supply type and routine test reports and operation and maintenance manual (if relevant). 10. Technical Requirements Environmental Considerations & Service Conditions The altitude of the power station does not exceed 1000 m above the sea level. The motor shall be outdoor mounted. The expected ambient air temperatures are: - Maximum momentary C - Minimum momentary C - Monthly average of the hottest month C - Yearly average C The motor is expected to be exposed to long dry periods without rain, sometimes with very fine sand dust, changing suddenly to periods of high humidity and rain. The motor might also be exposed to a moderate combination of conductive or abrasive dust (such as coal dust, fly ash, etc.), sulfur smokes,moisture, etc., as encountered in usual power plant applications. The motor at seashore location is expected to be additionally exposed to coastal conditions with salt laden spray and storms. 4
5 The motor might be exposed during summer days to very intensive solar radiation Reliability, Availability, Maintainability (RAM) The repair performed shall be intended to improve the reliability and availability of the motor Functional Requirements The stator winding insulation shall be of Class F or Class H, but the temperature rise shall correspond to Class B conditions The insulation system of stator winding shall be Vacuum Pressure Impregnated (VPI). If approved by IECo, resin rich insulation system can be used, assuring a similar winding quality, reliability and operation life as VPI The Contractor shall use wires with at least the same cross section as the existing one in the motor If applicable for repairing work, the rotor squirrel cage shall be made of copper or copper-alloy bars The minimum monitoring devices (RTD's, thermocouples, etc.) shall be of the same type and quantity as in the motor before the repair / overhaul. 11. Tests & Inspections Motor Test Before Repair The motor shall be dismantled and tested in presence of Purchaser's representative. The Contractor shall send to the Purchaser an initial detail report of the condition of the motor At least the following tests shall be performed: Visual inspection of stator and rotor Air gap clearance measurement Measurement of insulation resistance of stator winding, at 5000 V DC Measurement of stator winding resistance Acceptance Tests 5
6 The Purchaser has the right to witness any process or tests performed in the Contractor's facilities without any additional price. The witnessing will be performed in such way to avoid any impact on the contractual repair or overhaul schedule/delivery time The tests and acceptance conditions detailed in the items below shall be completed. Additional tests and additional/changed acceptance values can be agreed between Purchaser and Contractor Factory tests shall be performed for each coil before install, e.g.: Strand strand isolation check Insulation resistance & PI DC Ramp Dissipation Factor and Tip-Up Partial Discharge Final Hi-Pot These tests shall all have acceptance criteria spelled out in advance and reports shall be supplied for each coil The following tests shall be performed on 2 sample coils: Voltage Endurance Surge test (IEC ) Hi-Pot to Breakdown Dissection A full report on these tests shall be provided The following tests shall be performed on the repaired motor in the factory, in presence of Purchaser s representative: Measurement of stator winding resistance, each phase separately (the winding neutral point is accessible by ). For acceptance, each measurement shall not differ from each other by more than 2% Measurement of stator insulation resistance and polarization index, each phase separately (the winding neutral point is accessible by ), at 5000 V DC. The minimum acceptance value of insulation resistance at 40 C shall be 300 MΩ. The minimum acceptance value of polarization index shall be Measurement of insulation resistance of heaters, thermometers, thermocouples, thermistors, thermostats, etc. used for windings, bearings or cooling circuits at 500V DC, 1 min Measurement of no-load current (including current symmetry) and losses at rated voltage and frequency. 6
7 The no-load running shall be performed for about 1 3 hours, until thermal equilibrium is achieved. The no-load currents unbalance shall not exceed 20% Check of direction of rotation versus phase sequence and mark it on the wires and the motor. The phase sequence in the connection box shall be kept as it was before starting the work Measurement of mechanical vibrations for housing and attachments, performance of noise assessment. Maximum acceptable values according to ISO : r.m.s. velocity 2.3 mm/s, radial and axial direction, at bearing housing Behavior of bearings (lubricant level, temperature, noise, vibrations) On motors supplied with insulation bearings, measurement of bearing insulation resistance at 500V DC, 1 min. and measurement of shaft voltage Measurement of locked-rotor torque and current (including current symmetry) at rated current times service factor, rated frequency and reduced voltage. The short-circuit currents unbalance shall not exceed 5% Performing of moisture withstand test for sealed stator winding (water immersion or spray test) according to NEMA MG1. The Contractor shall announce to the purchaser at which method he will perform the test (either submerge or spraying), in the technical stage Measurement of dielectric dissipation factor (tgδ) with different applied voltages, up to rated voltage, each phase separately. The maximum acceptance value of tgδ shall be 2% (at 20 C 30 C). The maximum acceptance change in tgδ value from 20% of rated voltage to rated voltage shall be 50% Partial discharge measurements of stator with voltages up to rated voltage, each phase separately Power frequency withstand test of the stator winding with voltage (2UN + 1) kv for 1 min, each phase separately Impulse withstand test of main insulation of 2 individual sample coils with peak voltage of 4UN + 5 kv (1.2/50µs). 7
8 11.3. Field Tests Impulse test (inter-turn insulation) withstand test of 2 sample coils with peak voltage of 0.65 x (4UN + 5) kv having a front time of 0.2 µs Air gap clearance measurement. As acceptance condition, the difference between the measurements at diametrical opposite air gap points shall be less than 5% from air gap average clearance Rotor tests analyses of stator current harmonics by Motor Monitoring or similar method (if applicable for repairing work) Over-speed test for rotor if repaired, at 120% rated speed. In addition, rotor dynamic balancing test, if repaired Check, test and adjustment of accessories (e.g. cable entries, earthing bolts, terminal boxes, terminal marking, enclosure, nameplate labels, lubrication, fans, thermal monitors, coolers etc.) Direct rated voltage starting test, including measurement of starting currents and starting time and successive starts test according to motor design. This test can be performed also in Contractor or Purchaser s facilities under Contractor responsibility. Acceptable locked rotor current is until +20% of rated value The Purchaser shall have the right to perform all or a part of the following field tests, on motor mounted in power station, before the first operation following the repair: Check of direction of rotation versus phase sequence Measurement of no-load current and losses (with the load uncoupled) Measurement of mechanical vibration Measurement of insulation resistance and polarization index at the same DC voltage as in Items , Measurement of partial discharge with voltage up to nominal voltage. 8
9 12. Packaging & Delivery Power frequency withstand test of stator winding at 0.80 x (2UN +1) kv Tgδ measurement according to item Measurement of bearing insulation resistance on motors supplied with insulated bearings Rotor tests analyses of stator current harmonics by Motor Monitoring according to item Check of the accessories Direct rated voltage starting test, including measurement of starting currents and starting time according to item The repair or overhaul shall be performed in Contractor s factory. The transportation to and from the Contractor s factory, including the insurance, shall be the Contractor s responsibility (as an integral part of the contractual repair or overhaul schedule/delivery time) unless otherwise agree. 13. Storage & Handling The Contractor shall submit instructions for long term motor storage. 14. Nameplate & Marking The contractor shall renew the nameplate, include IECo motor number. The contractor shall mark the motor phases. 15. Notes Within this specification, the word "shall" indicates mandatory requirements, from which no deviation is permitted. The word "should" indicates a preferred or recommended possibility. IECo keeps its rights to qualify or disqualify any Bidder following the fulfilling of any specification requirement. All deviations from this specification shall be separately listed. In the absence of such list, it will be presumed that the provision of the specification are complied with by the Bidder. (See also non-conformance reporting requirement in item 7.1 above). 16. Special Requirements Warranty The warranty period of the repaired motor shall be at least 12 months from first operation Repair Duration 9
10 The works detailed above (scope of work and tests) shall be performed in the Contractor facilities during 60 calendar days or less Threshold Conditions The Contractor shall provide with the proposal a reference list showing his proven experience performing rewinding of similar motors (rated power, voltage) - at least 2 similar motors in the last five years The Bidder shall include in his technical proposal ISO-9001 qualification certificate or similar Others The repair or overhaul shall be performed in Contractor s factory The Contractor shall issue a Root Cause Analysis of the original failed motor The Contractor shall issue an acceptance test report, before shipment The Contractor shall issue a final report, within 30 days after completion of the scope of work All documentation shall be issued in English or Hebrew. 10
11 Appendix A TEST PLAN CONTRACTOR`S: NAME, I&T PLAN TITLE, THE PRODUCT INSPECTED/TESTED, AND DOCUMENT IDENTITY & APPROVAL. PURCHASER`S : NAME AND PROJECT`S NAME AND LOCATION NO. THE INSPECTI ON OR TEST APPLICABL E DOCUMENT S WP/HP OR OTHER SUB- CONT./ SUPPLYE R INSPECTED/TESTED BY : CONTR- ACTOR PURCH- ASER OTHER TIME SCHEDULE REMAR KS 11
12 12
Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society
Guideline No.: E-07(201610) E-07 TRANSFORMERS Issued date: October 28,2016 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and
More informationGuideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society
Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection
More informationGuideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society
Guideline No.: E-07(201501) E-07 TRANSFORMERS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and
More information020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)
020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service
More information34-SDMS-01 SPECIFICATIONS FOR
SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES
More informationCP Automatic capacitor bank
CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor
More informationBHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2
BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR 1.00.00 GENERAL 1.01.00 Make : Jinan Power Equipment Factory 1.02.00 Type : WX21Z-073LLT 1.03.00 Reference Standard : GB/T7064-2002
More informationCONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Technical Data 3.2 Standard Accessories 3.3 Tolerances
CONTENTS 1 GENERAL 2 STANDARDS 3 TECHNICAL FEATURES 3.1 Basic Technical Data 3.2 Standard Accessories 3.3 Tolerances 4 MOTOR DESIGN 4.1 Stator Casing 4.2 Stator Core with Winding 4.3 Stator Winding 4.4
More informationABMA , Radial Bearings of Ball, Cylindrical Roller and Spherical Roller Types Metric Design.
Specification CT841-2016 Standard for Petroleum and Chemical Industry Definite Purpose, Severe- Duty, Totally Enclosed Air Over (TEAO) Permanent Magnet Synchronous Cooling Tower and Air Cooled Heat Exchanger
More informationSECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT
SECTION 22 05 12 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable in the section
More informationINTER PLANT STANDARD STEEL INDUSTRY. Corresponding IS does not exist
INTER PLANT STANDARD STEEL INDUSTRY IPSS SPECIFICATION FOR ac ROLLER TABLE MOTORS (Second Revision) Corresponding IS does not exist IPSS:1-03-007-14 Formerly : IPSS:1-03-007-03 0. FOREWORD 0.1 This Inter
More informationTECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK
TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV.CAPACITOR BANK 1.0 SCOPE: This specification covers
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationGenerator Test Report
Generator Test Report Customer : Total Wind B.V. Project name : Reparatie ABB AMK500L Project : EMRI reference : Date : WO1399 32140133 07-02-2014 Generator Test Report Generator details Make: ABB Power:
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More informationTechnical Specification For Outdoor Substation Harmonic Filter Banks
Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field
More informationINTER PLANT STANDARD STEEL INDUSTRY. SPECIFICATION FOR GENERAL PURPOSE SQUIRREL CAGE INDUCTION MOTORS (Fifth Revision) BASED ON IS 325:1996
INTER PLANT STANDARD STEEL INDUSTRY IPSS SPECIFICATION FOR GENERAL PURPOSE SQUIRREL CAGE INDUCTION MOTORS (Fifth Revision) BASED ON IS 325:1996 IPSS: 1-03-001-14 Formerly: IPSS:1-03-001-05 0. FOREWORD
More information1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide
1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover
More information34-SDMS-02 SPECIFICATIONS FOR
SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE
More informationCONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Design Data 3.2 Standard Accessories 3.3 Tolerances
CONTENTS 1 GENERAL 2 STANDARDS 3 TECHNICAL FEATURES 3.1 Basic Design Data 3.2 Standard Accessories 3.3 Tolerances 4 MOTOR DESIGN 4.1 Stator Casing 4.2 Stator Core with Winding 4.3 Stator Winding and Insulation
More informationSPECIFICATIONS - DETAILED PROVISIONS Section Vertical Hollowshaft Electric Motors C O N T E N T S
Revised 04/14/2016 SPECIFICATIONS - DETAILED PROVISIONS Section 16151 - Vertical Hollowshaft Electric Motors C O N T E N T S PART 1 - GENERAL... 1 1.01 SCOPE... 1 1.02 SPECIFIC PROJECT REQUIREMENTS...
More informationHPS EnduraCoil. Cast Resin Transformer
HPS EnduraCoil Cast Resin Transformer Hammond Power Solutions Inc. (HPS) is a leading manufacturer of standard and custom dry-type transformers in North America. Every HPS product is built with the quality
More informationTechnical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear (In Air)
Ergon Energy Corporation Limited Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear ETS12-01-02 Specification ETS12-01-02 Ver 3 Contents 1. Purpose
More informationLV Capacitor CLMD03 Power Module Instruction manual
LV Capacitor CLMD03 Power Module Instruction manual Table of Contents 1 Safety... 3 2 Upon reception... 3 2.1 Inspection on reception... 3 2.2 Storage- transportation handling... 3 3 Hardware Description...
More informationE-15 Uninterruptible Power Systems (UPS)
Guideline No.E-15 (201510) E-15 Uninterruptible Power Systems (UPS) Issued date:20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,
More informationSPECIFICATION AND PERFORMANCE TABLE OF CONTENT. 1. Scope Reference Documents Material and Components... 2
TABLE OF CONTENT 1. Scope... 2 2. Reference Documents.. 2 3. Material and Components...... 2 4. Design and Construction..... 2 5. Rating.. 2 6. Performance and Test Descriptions. 2 7. Test Requirements
More informationA. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.
1. APPLICATION A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 2. REFERENCE STANDARDS A. The transformers supplied shall
More information1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide
1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationResin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK
1ZSC563-AAA en, Rev. 2 Resin Impregnated Paper Bushing, Oil to SF 6, Type GSBK Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More informationElectrical Machine Service. Overhaul, Conditioning, On-Site Service and Diagnostics. Excellent Technology, Efficiency and Quality
World Class Power Solutions Excellent Technology, Efficiency and Quality Electrical Machine Service Overhaul, Conditioning, On-Site Service and Diagnostics 2 3 Your partner for Electrical Machine Service
More informationINTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)
INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This
More informationFletcher Moorland Ltd. Electric Motor Repair Specification
Fletcher Moorland Ltd Electric Motor Repair Specification Fletcher Moorland promotes best practice and reliability throughout its business. As an SKF certified rebuilder for electric motors we ensure each
More informationTECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH
TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:
More informationDesign specifications
Design specifications Design To relevant standards: IEC, VDE, DIN, ISO, EN With squirrel-cage or slipring rotor Degree of protection IP 55 / IP 65 Cooling method IC511, suitable for both indoor and outdoor
More informationResin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide
1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More informationINTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.
INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side
More informationTransformer bushings, type GOH. Technical guide
Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More information017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA
017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS PAGE 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable Standards 3 5. Basic Features 4 6. Quality
More information1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide
1ZSE 2750-112 EN, REV. 4 Wall bushings type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationHigh Voltage Generators. TM21-TG Series. 2-Pole Air Cooled Turbine Generator Up to 80,000 kw (107,000 HP)
High Voltage Generators TM21-TG Series 2-Pole Air Cooled Turbine Generator Up to 80,000 kw (107,000 HP) TMEIC has a proud and rich history of providing the latest generator technology for a broad range
More informationCAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION
CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION TMC TRANSFORMERS - GLOBAL NETWORK UK & IRELAND SPAIN NORTH AMERICA & CANADA GERMANY SWITZERLAND BENELUX & AUSTRIA ITALY POLAND INDIA CENTRAL & SOUTH AMERICA
More informationCORE VALUES TECHNOLOGIES ESS-ESD PRODUCT CATALOGUE Enjoy the peace of mind ENGINE POWER SUPPLIERS AND EQUIPMENT HEAT
TECHNOLOGIES ENGINE POWER SUPPLIERS AND EQUIPMENT HEAT Enjoy the peace of mind ESS-ESD PRODUCT CATALOGUE CORE VALUES PEACE OF MIND EFFICIENCY FAIRNESS RESPONSIBILITY CUSTOMER ORIENTATION GROWING DEVELOPED
More information023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA
023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir
More informationGuideline No.: E-03(201806) E-03 MOTORS. Issued date: June 7, China Classification Society
Guideline No.: E-03(201806) E-03 MOTORS Issued date: June 7, 2018 China Classification Society Foreword: This Guideline is a part of CCS Rules, which contains technical requirements, inspection and testing
More informationAIR CORE REACTORS. Phoenix Electric Corporation
AIR CORE REACTORS Phoenix Electric Corporation PHOENIX ELECTRIC CORPORATION designs and manufactures Dry Type Air Core Reactors for operation on systems rated through 800 kv. All reactors are custom designed
More informationTurbogenerators. With Top Performance for Steam and Gas Applications. Specifically tailored 4-pole Synchronous Turbogenerators
Turbogenerators With Top Performance for Steam and Gas Applications Specifically tailored 4-pole Synchronous Turbogenerators siemens.com / automation 2 Top Performance Turbogenerators for Steam and Gas
More informationEU RO Mutual Recognition Technical Requirements
1. PRODUCT DESCRIPTION... 1 2. DESIGN EVALUATION... 2 3. PRODUCTION REQUIREMENTS... 6 4. MARKING REQUIREMENTS... 6 5. TYPE APPROVAL CERTIFICATE CONTENT... 7 6. APPROVAL DATE AND REVISION NUMBER... 7 7.
More informationINTER PLANT STANDARD STEEL INDUSTRY
INTER PLANT STANDARD STEEL INDUSTRY IPSS SPECIFICATION FOR ac CRANE (Hoist and Winches) DUTY SQUIRREL CAGE INDUCTION MOTORS (Fourth Revision) BASED ON IS 325:1996 Formerly: IPSS:1-03-004-05 0. FOREWORD
More informationTechnical Specification for 33 KV 200 AMPs,H.G,Fuse set.
Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. 1. SCOPE:- This specification covers the manufacture, testing and supply of 33KV 200 Amps, H.G. Fuse sets 2. The 33 KV H.G. Fuses shall be suitable
More informationTeepak Totally Enclosed Tube Ventilated High Voltage Induction Motors. A Regal Brand.
Teepak Totally Enclosed Tube Ventilated High Voltage Induction Motors A Regal Brand www.regalbeloit.com Specifications Range Poles Voltage : Upto 3000 KW : Upto 14 Pole : Upto 11000 Volt Frame : 450 1000
More informationFIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z
PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install fixed power factor correction equipment as specified herein and as shown on the contract drawings. This specification
More information1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide
1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationSECTION MOTOR REQUIREMENTS for HVAC
PART 1 GENERAL 1.1 SECTION INCLUDES A. Single-phase electric motors B. Three-phase electric motors 1.2 REFERENCES SECTION 23 05 13 MOTOR REQUIREMENTS for HVAC A. ABMA 9 - Load Ratings and Fatigue Life
More informationREFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS
TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3
More informationC. System Design and Performance Requirements
Change History Date Description of Change Pages / Sections Modified 6/15/16 Updated division section from 16361-E-E to 26 10 03, removed references to other section numbers A. Summary - mgl44 Change Approver
More information33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT
33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,
More informationtests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.
tests ( Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. electrical tests These tests verify contractual
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationTechnical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP
United Nations Development Programme Recovery and Crisis Prevention برنامج األمم المتحدة اإلنمائي Iraq Technical Specification for Supply, installation and commissioning of Diesel Generators for UNDP February
More information43-SDMS-04 REV. 00 SPECIFICATIONS FOR
43-SDMS-04 REV. 00 SPECIFICATIONS FOR SHUNT CAPACITOR BANK 13.8 kv THROUGH 69 kv FOR PRIMARY DISTRIBUTION SUBSTATIONS This specification is property of SEC and subject to change or modification without
More informationGE Motors. PegasusTMMHV. Medium Voltage AC Induction Motors. NEMA Frames ,000 HP IEC Frames ,000 kw
GE Motors PegasusTMMHV Medium Voltage AC Induction Motors NEMA Frames 8200-8900 500-22,000 HP IEC Frames 400-1000 400-15,000 kw Experience Matters We ve manufactured motors for over 125 years. In 1879,
More informationSubmersible Vacuum Fault Interrupters
Submersible Vacuum Fault Interrupters UG Distribution Medium Voltage Vacuum Fault Interrupters Functional Specification Guide PS024002EN Functional Specification for 2.4kV to 17.5kV UG Distribution Medium
More informationAC Line / Load Reactors
AC Line / Load Reactors Table of Contents Delivery / Lead Time.PB03-1100 -2 Selection & Pricing PB03-1100 -4 Replacement Parts..PB03-1100-8 Product Modifications / Options..PB03-1100 -9 Product Specifications..PB03-1100
More informationSTR-1415 SPECIFICATION FOR BATTERY CHARGERS 220V, 30A FOR SUBSTATIONS ANNEXURES B
STR-1415 SPECIFICATION FOR BATTERY CHARGERS 220V, 30A FOR SUBSTATIONS ANNEXURES B February 2017 STR-1415 SPECIFICATION FOR BATTERY CHARGERS 220V, 30A FOR SUBSTATIONS ANNEXURES B DRAFT FINAL DRAFT CONTRACT
More informationTECHNICAL REQUIREMENTS FOR ELECTRICAL EQUIPMENT
Page 1 (7) TECHNICAL REQUIREMENTS FOR ELECTRICAL EQUIPMENT Title Document Asynchronous electric motors TBE 103 Issue 6 (E) Contents 1 GENERAL... 2 2 DEFINITIONS... 2 3 GENERAL PRODUCT REQUIREMENTS... 3
More informationLow voltage capacitors CLMD Improving power factor and enhancing power quality of your network
PRODUCT BROCHURE Low voltage capacitors CLMD Improving power factor and enhancing power quality of your network s.a. ABB n.v. Power Quality Products Allée Centrale 10 Z.I. Jumet B-6040 Charleroi (Jumet)
More informationCutting-edge technologies backed by a century of experience
AHNAM is the world's leading supplier of high voltage induction machines used in a wide range of application in virtually every industry including oil, gas & petrochemicals, power generation, marine, pulp
More informationAlternating Current Motors in Detail
Alternating Current Motors in Detail Overview/Objectives: o Advanced motor component descriptions/details o Design, materials and construction o Starting and operation o Temperature effects on performance
More informationGuideline No.: E-03(201610) E-03 MOTORS. Issued date: October 28,2016. China Classification Society
Guideline No.: E-03(201610) E-03 MOTORS Issued date: October 28,2016 China Classification Society Foreword: This Guideline is a part of CCS Rules, which contains technical requirements, inspection and
More informationTest requirements for Rotating Machines
(1996) (Rev.1 May 2001) (Corr.1 May 2004) (Rev.2 Aug 2015) Test requirements for Rotating Machines 1. General All machines are to be tested by the manufacturer. Manufacturer s test records are to be provided
More informationINSTALLATION MANUAL. Instructions, precautions, suggestions for installing and servicing resin transformers in full compliance with safety rules
INSTALLATION MANUAL Instructions, precautions, suggestions for installing and servicing resin transformers in full compliance with safety rules ING TABLE OF CONTENTS 1. General information 2 1.1 Standards
More informationMTE AC Line / Load Reactors Price book
Table of Contents TABLE OF CONTENTS...1 STANDARD DELIVERY SCHEDULE...2 REACTOR SELECTION & PRICING...4 208-240 VOLT (3-PHASE)...4 400 VOLT (50 HZ) USE FOR 380-415 VOLTS...5 480 VOLT (3-PHASE) REACTOR...6
More information045 : 2000 CEB STANDARD
045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.
More informationMV Air Insulated Switchgear TAP17. Technical Data TGOOD
MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)
More informationSpecification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers
Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and
More informationTest report. Type VRLTC load tap changer VRLTC 1500A Type test summary report
Test report Type VRLTC load tap changer VRLTC 1500A Type test summary report Date: 10 October 2012 Type Test Summary Report Type VRLTC Vacuum/Reactance Load Tap Changer ABB has tested the Type VRLTC, vacuum
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationAF series contactors (9 2650)
R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00
More informationCITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008
CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationGenerators for the age of variable power generation
6 ABB REVIEW SERVICE AND RELIABILITY SERVICE AND RELIABILITY Generators for the age of variable power generation Grid-support plants are subject to frequent starts and stops, and rapid load cycling. Improving
More informationTechnical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear (In Oil)
Ergon Energy Corporation Limited Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear ETS12-01-03 Specification ETS12-01-03 Ver 3 Contents 1. Purpose and Scope...
More informationP2 : About Us. P3 : Elsewedy Transformers. P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers. P7 : Technical Data Sheets
P2 : About Us P3 : Elsewedy Transformers P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers P7 : Technical Data Sheets P8 : Transformer s Outline Drawing P9 : Accessories About Us
More informationSINGLE PHASE TEFC CAGE MOTORS
SINGLE PHASE TEFC CAGE MOTORS 2 SINGLE PHASE TEF CAGE MOTORS Mechanical protection: IP 54 Voltage: 220 V, 50 Hz Type Output power P N kw Rated speed n N min -1 Efficiency % Power factor cos Rated current
More information1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide
1ZSE 2750-102 en, Rev. 7 Transformer bushings, type GOB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical
More informationHigh Voltage Technology & Testing
The Power of Trust. The Future of Energy. HIGH VOLTAGE TESTING Qualification testing, condition assessment, and forensic analysis Manufacturers and utility users of high-voltage electrical equipment face
More informationwith Vacuum Circuit Breaker HAF
M E T A L - C L A D S W I T C H G E A R Safety and Reliability with Vacuum Circuit Breaker HAF Flexible Design and Compact with Vacuum Circuit Breaker HVF Easy Installation and Maintenance We build a better
More information(i) in paragraph 9, for sub-paragraph (i) the following shall be substituted, namely:-
Revision 3 Date: 28/01/2016 Amendment to Schedule 6 for Induction Motor In the said schedule, (i) in paragraph 9, for sub-paragraph (i) the following shall be substituted, namely:- Effective from 1 st
More informationPI734G - Winding 312. Technical Data Sheet APPROVED DOCUMENT
- Winding 312 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards
More informationPI736F - Winding 312. Technical Data Sheet
PI736F - Winding 312 Technical Data Sheet PI736F SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
More informationODP SERIES PREMIUM INDUSTRIAL OPEN DRIP PROOF MOTORS C280M to C355LB Frame. Australian Version October 2013
ODP SERIES PREMIUM INDUSTRIAL OPEN DRIP PROOF MOTORS C280M to C355LB Frame Australian Version October 2013 ODP SERIES (OPEN DRIP PROOF) PREMIUM INDUSTRIAL OPEN DRIP PROOF MOTORS, C280M TO C355LB FRAME
More informationGuide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break
Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated
More informationSurge arrester POLIM-H.. ND
DATA SHEET Surge arrester POLIM-H.. ND Technical data Classification according to EN 50526-1 and IEC 62848-1 Nominal discharge current I n (8/20 µs) 10 ka peak Class DC-B High current impulse I hc (4/10
More informationM T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation
M T E C o r p o r a t i o n MTE Series RL Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL. 050516 2002 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RL Line/Load Reactors are components
More informationABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers
ABB PTTR SPAIN Zaragoza. The product: Cast coil transformers ABB BA Transformers - 1-5/7/2007 Dry Type Vacuum Cast Coil Transformer INTRODUCTION ABB BA Transformers - 2 - Product Portfolio II Dry Type
More informationSEWPCC UPGRADING/EXPANSION PROJECT BID OPPORTUNITY SECTION LOW-VOLTAGE AC INDUCTION MOTORS
SECTION 26 20 00 LOW-VOLTAGE AC INDUCTION MOTORS SEWPCC UPGRADING/EXPANSION PROJECT PART 1 GENERAL 1.1 RELATED SECTIONS A. This section applies only when referenced by a motor-driven equipment specification.
More informationLV Capacitor CLMD Reliability for Power Factor Correction
LV Capacitor CLMD Reliability for Power Factor Correction Reliability for power factor correction CLMD construction The CLMD capacitor consists of a number of wound elements made with a dielectric of metallized
More informationThree Phase Modifiable NEMA Horizontal Motors Accessories and Modifications
1. Altitude Standard motors are designed for 3,300 feet altitude and 40 C ambient temperature. Atmospheric conditions at higher altitudes inhibit the motor s ability to dissipate heat, resulting in an
More information