1 CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008

2 SPECIFICATION NO. E-112 SPECIFICATIONS SUBSTATION CLASS VACUUM CIRCUIT BREAKERS Scope These specifications cover the electrical and mechanical requirements of high voltage vacuum circuit breakers for use in the City of Lompoc s Electrical Receiving Station. This document shall be limited to 15.5 kv class equipment. It is the intent of these specifications to describe equipment of the best design and construction for the service for which it is intended. Consequently, it shall be the City s desire to award contracts to the bidder who is bidding equipment from a manufacturer that has demonstrated high quality by having a considerable number of this type of equipment in substations of electric utilities over a period of years. 1.1 Purpose These specifications covers the engineering requirements for 15.5 kv, three-pole (phase), single-throw, free-standing, dead-tank, vacuum circuit breakers for substation application. 1.2 Definitions The term Manufacturer is used interchangeably with supplier and bidder The term COL is used to represent the City of Lompoc, Electric Utility Division Specification is defined as this document. Certified Test Results is used to describe those test results, which are certified by the Manufacturer to be true and correct. Certification requires the signature of the Manufacturer s representative that is responsible for overseeing that all of the tests made on the equipment supplied are in accordance with this specification 2.0 CONFORMANCE 2.1 Applicable Standards The vacuum circuit breakers manufactured in accordance with these specifications shall meet or exceed the applicable requirements of the latest revision of ANSI C SPECIFICATION NO: ELE_112_R1.doc Page 2 of 3 Rev. 10/28/2008

3 2.2 Approval Only vacuum circuit breakers that have been approved by COL are acceptable Approved vacuum circuit breakers are those that have been satisfactory tested to industry standards and are recommended by other satisfied users Manufacturers requesting approval of vacuum circuit breakers shall submit a written requests for approval to COL. The request shall include a description of the equipment for which approval is requested, supplementary data and certified test reports, and the completed Vacuum Circuit Breaker Manufacturer s Questionnaire included in Appendix A of the specifications. 2.3 Deviation and Non-Conformance COL shall be notified, in writing, of any proposed or actual deviation from the requirements of these specifications COL s prior written approval is required for acceptance of any deviation from these specifications. 2.4 Rejection Non-conformance to any of the requirements of this specification shall be reason for rejection, non-payment and/or liquidated damages. 2.5 Certification of Ratings The Manufacturer of the circuit breakers shall be responsible for the compliance of the circuit breakers with the requirements of these specifications and the referenced Standards. The Manufacturer shall furnish, with delivery, a certification of ratings of the circuit breakers. 3.0 GENERAL REQUIREMENTS 3.1 These specifications apply to outdoor, three-pole (three-phase), singlethrow, free-standing, dead-tank, vacuum circuit breakers 3.2 The circuit breaker will be used on a 15.5-kv, three-phase, 60-hertz system and be complete from the incoming bushing studs to the outgoing bushing studs which shall include straight 2-bolt NEMA pad type connectors. SPECIFICATION NO: ELE_112_R1.doc Page 3 of 3 Rev. 10/28/2008

4 3.3 The breaker shall be designed, manufactured, and tested in accordance with the latest revisions of the ANSI, IEEE, NESC, and NEMA specifications. 3.4 The breaker shall be manufactured in a facility that is Quality Systems Registered by Underwriters Laboratories, Inc. to ISO RATINGS 4.1 The breaker shall meet the following ratings and electrical characteristics: Required Maximum Voltage Insulation level: Low Frequency (Dry, 1 minute) Impulse Crest (Fullwave) Impulse Crest (Chopped Wave, 2 μs) 15.5 kv, RMS 50 kv, RMS 110 kv, RMS 142 kv, RMS Impulse Crest (Chopped Wave, 3 μs) 126 kv, RMS Rated Continuous Current 600 A Rated Short-Circuit Current 12kA, RMS Rated Interrupting Time (max.) 3 cycles Rated Reclosing Time (max.) 15 cycles Rated Permissible Tripping Delay, Y 2 seconds Maximum Symmetrical Interrupting Current 12kA, RMS 3-Second Short-time Current Rating 12kA, RMS Close and Latch Rating 32kA, peak Duty Cycle OCO-15 sec-co Closing Coil Voltage 48Vdc Tripping Coil Voltage 48Vdc Motor Voltage 120Vac Heater Voltage 120Vac Bushing Current Transformer (Multi Ratio) CT Ratios 600/5 Accuracy Class at Full Winding C200 Number of CT s on each bushing (1,2,3,4,5,6) The breaker shall be rated for an ambient temperature range of -30 C to +40 C. 4.3 The breaker shall be rated for Seismic Zone 4 as described by ANSI/IEEE , or latest revision. SPECIFICATION NO: ELE_112_R1.doc Page 4 of 4 Rev. 10/28/2008

5 4.4 The breaker shall be rated to withstand wind load of up to 90 mph per ANSI C37.04 Section 6.2 (latest revision). 5.0 CONSTRUCTION 5.1 Enclosure a) The enclosure shall be arc-resistant based on EEMAC standards, for personnel and equipment safety. Arc-resistance protection shall be provided for the front, back, and sides of the enclosure. b) The enclosure shall be weatherproof and have a modular design that isolates line potential components from secondary control devices. c) The high-voltage compartment shall house the vacuum interrupter assemblies, which shall be supported on standoff insulators. d) The enclosure shall be provided with lifting eyes for lifting the entire unit during loading and unloading. e) The breaker shall be shipped completely assembled. f) The enclosure shall be painted ANSI #70 light gray with a TGIC polyester powder-coat protective paint finish. Total paint thickness on exterior surfaces shall be mils. Production samples shall have passed 4,000 hours minimum of salt spray testing, per ASTM B-117 and ASTM D-1654 Procedure A, with a rating of 6 or higher. One 6-ounce spray can of touch-up paint that matches the exterior finish shall be provided. g) Ground pads shall be 2 X 3.5 and stainless steel, with provision for NEMA 2-hole connectors. The ground pads shall be welded on each side of the enclosure for external ground connections. Number 4 cables from the roof and high-voltage and low-voltage compartments shall be connected internally to the ground pads to ensure a solidly grounded enclosure, with negligible difference in ground potential between compartments. Enclosure grounding shall not depend on bolted connectors or star washers. h) The breaker legs shall be painted with the same requirements of section 5.1 (f), and have an adjustable height range of 24-inches in 3-inch increments. The maximum height of the breaker shall not exceed 126-inches (top of bushing connector). SPECIFICATION NO: ELE_112_R1.doc Page 5 of 5 Rev. 10/28/2008

6 i) The leg assemblies shall have a galvanized base channel. j) Outer doors shall have padlockable handles for preventing access to all controls in the enclosure. Doors are to be vertically hinged. Provisions for holding all doors in the open position 180 shall also be provided. It shall be documented that the breaker passed rain testing per ANSI C , Section k) The low-voltage cabinet bottom shall have a removable cover, with a minimum size of 8-inches by 14-inches, for entry of the control conduits. l) All external hardware shall be stainless steel. 5.2 Interrupters a) The vacuum interrupters shall be hermetically sealed in a high vacuum, protecting contacts from moisture and dirt. b) The interrupters shall be maintenance free. c) The breaker shall have readily accessible provisions for measuring the contact wear on each interrupter. 5.3 Operating Mechanism a) The mechanism shall utilize stored energy from springs charged by an electric motor. b) The mechanism and control circuits shall be located in the lowvoltage compartment. The mechanism shall not be mounted in a separate housing. c) The mechanism shall be designed with an integral, manualcharging handle. The charging handle shall not be removable. d) The mechanism shall be mechanically and electrically trip-free and non-pumping for both manual and automatic operations. e) The following shall be clearly visible on the mechanism when the outer door is closed: 1) A non-resettable, 5-digit operation counter that increases on each trip operation. SPECIFICATION NO: ELE_112_R1.doc Page 6 of 6 Rev. 10/28/2008

7 5.4 Bushings 2) A mechanical indicator to show whether the circuit breaker is open or closed. 3) A mechanical indicator to display the status of the closing springs. 4) Open and close push buttons for operating the circuit breaker. f) The standard design shall have a contact auxiliary switch, which shall have an adequate number of (AC and DC) contacts used for internal breaker wiring. An additional auxiliary switch with 6 a and 6 b contacts shall be provided for external use. g) The mechanism shall be designed with a latch-check switch as standard. a) Six roof bushings shall be provided. The bushing material shall be porcelain and shall conform to applicable ANSI standards and shall be capable of carrying the breaker ampere rating within their normal life expectancy. b) Bushing terminals shall be threaded-stud type and capable of accepting either 2-hole NEMA stud-to-flat connectors (Type HDSF). c) Bushings shall have a minimum rating of 15 kv, 110 kv BIL, dry type with a minimum bushing extra creepage distance of inches and tested in accordance with applicable ANSI and NEMA standards. d) Each bushing shall be capable of being equipped with either three standard-accuracy, two double-accuracy, or one triple-accuracy 600/5 multi-ratio current transformers. e) Each Circuit Breaker bushing shall be provided with one, 600/5, 5- tap, multi-ratio current transformer with a relaying accuracy class of C200. All secondary leads shall be terminated on short-circuit type terminal blocks in the low-voltage compartment and shall be accessible even when the breaker is energized. f) Bushing insulators shall be ANSI No. 70 gray in color. g) Tin-plated, flexible connectors shall be used between the bushings and the interrupters. SPECIFICATION NO: ELE_112_R1.doc Page 7 of 7 Rev. 10/28/2008

8 5.5 Controls a) Control wiring shall be not less than #14 AWG Type SIS for general control and #10 AWG Type SIS for current transformer circuits. The wire color shall be gray. b) Terminal blocks for control circuits and the user s external connections shall be Type EB25 with terminal marking strips labeled in accordance with the wiring diagrams. c) Short-Circuit terminal blocks shall be Type EB27 with shorting screws and a common shorting bar for each current transformer. d) The control circuit shall be provided with fused switches for disconnecting external low-voltage supply circuits. e) An anti-pump relay shall be provided to inhibit multi close-open operations in the event that a continuous close signal is applied. f) One pistol-grip control switch, Electroswitch Series 24, engraved TRIP-CLOSE, shall be supplied. g) Red and green indicating lamps, LED Type, Lee Craft 75 Series, Part No. L75R-(color) TXP, shall be provided to indicate whether the breaker the closed or open. h) Space Heater, rated 120 VAC, shall be supplied to prevent condensation in the breaker enclosure. Heaters shall be thermostatically controlled and located in the low-voltage compartment. The heater control circuit shall be provided with fused switches for disconnecting external low-voltage supply circuits. i) An emergency manual trip, ANSI Device Number 69, shall be provided and shall be readily accessible on the exterior mechanism side of the breaker. It shall be labeled MANUAL TRIP OPEN and the actuating handle shall be painted red. The device shall be operable from the exterior of the breaker without opening any doors or panels. Actuation of the device will block any electrical closing of the breaker until the switch has been manually reset. 5.6 Spare Parts SPECIFICATION NO: ELE_112_R1.doc Page 8 of 8 Rev. 10/28/2008

9 a) The following spare parts for the circuit breaker shall be available and cost shown as separate items on bidder s quotation. A complete set of spare parts shall be quoted. 5.7 Drawings and Data 1) One vacuum interrupter 2) One complete circuit breaker bushing, excluding current transformer. 3) One complete set of contacts and coils for each type and size of special relay and contactor used. 4) One complete set of all special tools and appliances, as may be required to dismantle and reassemble the circuit breaker. a) Bid Submittal: Each proposal shall be accompanied by drawings and data sheets giving outline dimensions including static and dynamic loads, typical control schematics, bushing current transformer characteristics, and recommended spare parts lists. Bidder is requested to furnish the above information in duplicate with proposal. b) Approval Submittal: Within 20 working days after award of contract, the successful Bidder shall submit (two sets) outline drawings, schematic diagrams, connection diagrams, and characteristic curves for approval. c) Shipping Submittal: 1) One copy of all approved drawings, approved curves, certified test reports, and installation, operation and maintenance instructions shall be bound, indexed and shipped with the breaker. 2) Three copies of the above documentation shall be mailed to the City 21 days prior to shipment. d) Mailing Address: All submittals shall be mailed to: City of Lompoc 100 Civic Center Plaza Lompoc, CA Attention: Electrical Substation Supervisor e) All the above submittals may be transmitted to the City via a preapproved electronic format. These arrangements must be made with the Electrical Substation Supervisor upon receipt of contract. SPECIFICATION NO: ELE_112_R1.doc Page 9 of 9 Rev. 10/28/2008

10 APPENDIX A VACUUM CIRCUIT BREAKER MANUFACTURER S QUESTIONAIRE QUESTIONS Number of consecutive years manufacturing 15.5 kv three-phase free standing mounted vacuum circuit breakers for installation by electric utilities operating in the United States of America Number of 15.5 kv three-phase free standing mounted vacuum circuit breakers sold in the past five (5) consecutive years to electric utilities operating in the United States of America Do you take any exceptions to City of Lompoc, Electric Division Specification for these 15.5kV free standing mounted vacuum circuit breakers? If yes, list all the exceptions. (Use separate sheet if necessary) Are the parts used on the freestanding mounted vacuum circuit breakers manufactured by your organization or by other companies? List any parts made by other companies with their names. Is the manufacturer of the vacuum circuit breakers utilizing a facility that is Quality Systems Registered by Underwriters Laboratories, Inc. to ISO 9001? RESPONSES Manufacturing plant: Its location How long has it been in operation? Are there plans for updating the equipment? Name of the contact person, name of the company, and telephone numbers of three (3) electric utilities operating in the United States of America that have purchased 15.5 kv free standing mounted vacuum circuit breakers from your organization in the past five (5) years. Date: Contact Person Name: Company Name: Telephone: Contact Person Name: Company Name: Telephone Contact Person Name: Company Name: Telephone Company Name: Name of person completing this questionaire: Title: Telephone: SPECIFICATION NO: ELE_112_R1.doc Page 10 of 10 Rev. 10/28/2008

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy. Type SDV6 distribution circuit breaker Top performance - proven reliability Answers for energy. Table of contents Introduction 2-4 Type 3AH3 stored-energy operating mechanism 6 Vacuum interrupters 7 Ratings

More information

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

CITY OF MARYVILLE ELECRIC DEPARTMENT Maryville, Tennessee SPECIFICATIONS FOR 15KV POWER CIRCUIT BREAKERS. September 2018

CITY OF MARYVILLE ELECRIC DEPARTMENT Maryville, Tennessee SPECIFICATIONS FOR 15KV POWER CIRCUIT BREAKERS. September 2018 CITY OF MARYVILLE ELECRIC DEPARTMENT Maryville, Tennessee SPECIFICATIONS FOR 15KV POWER CIRCUIT BREAKERS September 2018 Myrick Clinton Cannon TN P.E. #112337 Patterson & Dewar Engineers, Inc. P. O. Box

More information

Three-Phase Pole Mounted Recloser

Three-Phase Pole Mounted Recloser Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

56-SDMS-07 REV. 01 SPECIFICATIONS FOR 56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 1. APPLICATION A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 2. REFERENCE STANDARDS A. The transformers supplied shall

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

34-SDMS-01 SPECIFICATIONS FOR

34-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES

More information

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

SECTION III SF6 GAS CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS

SECTION III SF6 GAS CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS SECTION III SF6 GAS CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS SUBSECTION PAGE 1. SCOPE... 1 2. PROJECT ENGINEER... 1 3. STANDARDS... 1 4. RATINGS... 1 5. MATERIALS & WORKMANSHIP... 3 6.

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

SECTION V - TECHNICAL SPECIFICATIONS TABLE OF CONTENTS

SECTION V - TECHNICAL SPECIFICATIONS TABLE OF CONTENTS SECTION V - TECHNICAL SPECIFICATIONS TABLE OF CONTENTS SUBSECTION PAGE 1. SCOPE... 1 2. PROJECT ENGINEER... 1 3. STANDARDS... 1 4. RATINGS... 1 5. MATERIALS & WORKMANSHIP... 6 6. BUSHINGS... 6 7. CURRENT

More information

Submersible Vacuum Fault Interrupters

Submersible Vacuum Fault Interrupters Submersible Vacuum Fault Interrupters UG Distribution Medium Voltage Vacuum Fault Interrupters Functional Specification Guide PS024002EN Functional Specification for 2.4kV to 17.5kV UG Distribution Medium

More information

34-SDMS-02 SPECIFICATIONS FOR

34-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

43-SDMS-01 SPECIFICATIONS FOR

43-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR MV SHUNT POWER CAPACITOR BANK UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description Page 1.0 SCOPE 3

More information

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised

More information

Acknowledge receipt of this addendum on page one of the Bid Form.

Acknowledge receipt of this addendum on page one of the Bid Form. Procurement Department Bid Office 21 W. Church Street Customer Center 1 st Floor, Room 002 Jacksonville, Florida 32202 September 25, 2017 ADDENDUM NUMBER One (1) TITLE: PURCHASE OF TWO (2) SYNCHRONOUS

More information

SECTION III - VACUUM CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS 1. SCOPE PROJECT ENGINEER STANDARDS...

SECTION III - VACUUM CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS 1. SCOPE PROJECT ENGINEER STANDARDS... SECTION III - VACUUM CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS 1. SCOPE... 1 2. PROJECT ENGINEER... 1 3. STANDARDS... 1 4. RATINGS... 1 5. MATERIAL AND WORKMANSHIP... 2 6. BUSHINGS...

More information

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order Amphitheater High School Medium Voltage Switchgear Replacement Basis of Design 8/21/17 1of3 Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Technical Specification For Outdoor Substation Harmonic Filter Banks

Technical Specification For Outdoor Substation Harmonic Filter Banks Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field

More information

City of Jacksonville Beach

City of Jacksonville Beach Bid #: 1314-07 City of Jacksonville Beach Purchasing Division: 1460A Shetter Ave., Jacksonville Beach, FL 32250 Tel: 904-247-6229 Fax: 904-270-1639 THIS IS NOT COMPLETE BID INVITATION TO BID Title: SF6

More information

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED SWITCHGEAR WITH VACUUM LOAD

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

SDV7. Outdoor distribution circuit breaker family 15.5 kv to 38.0 kv. usa.siemens.com/sdv7

SDV7. Outdoor distribution circuit breaker family 15.5 kv to 38.0 kv. usa.siemens.com/sdv7 0 000 0000000 0000 000000 0000 000 0000000 0000 000000 0000 000 0000000 SDV7 Outdoor distribution circuit breaker family 5.5 kv to 8.0 kv usa.siemens.com/sdv7 SDV7 Brochure Brochure SDV7 The type SDV7

More information

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-115

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-115 CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-115 PADMOUNTED TRANSFORMERS 12kV AND DUAL VOLTAGE, RADIAL FEED STAINLESS STEEL NOVEMBER 2011 Specification:ELE_115_R1 Page

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RMVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope... 3 2.0 Standards... 3 3.0 Supplier Qualifications... 4 4.0 Circuit Breaker

More information

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified. SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

100 / 110 DRYWELL FUSE SPECIFICATION

100 / 110 DRYWELL FUSE SPECIFICATION 100 / 110 DRYWELL FUSE SPECIFICATION 15KV & 25KV SUBMERSIBLE VACUUM LOAD INTERRUPTERS AND DRYWELL FUSE ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED SUBMERSIBLE SWITCHGEAR WITH LOAD INTERRUPTING SWITCHES

More information

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Descriptive Bulletin R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Introduction The R-MAG TM is truly the next generation in medium voltage vacuum circuit breaker

More information

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT SUBMERSIBLE AND VAULT MOUNTED

More information

SWITCHGEAR DIVISION PRODUCT PROFILES

SWITCHGEAR DIVISION PRODUCT PROFILES SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed. City of Cartersville Electric System P.O. Box 1390 320 S. Erwin St. Cartersville, GA 30120 770-387-5631 March 2006 SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS This specification provides standardization

More information

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER Solid Dielectric Load Break Switch SPECIFICATION 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED VACUUM LOAD INTERRUPTING

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

SECTION PADMOUNT TRANSFORMER - OIL FILLED

SECTION PADMOUNT TRANSFORMER - OIL FILLED SECTION 26 12 19.01 PADMOUNT TRANSFORMER - OIL FILLED PART 1 GENERAL 1.1 DESCRIPTION: Padmount Transformers and Insulating Oil with underground primary and secondary connections for use in distribution

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES Description JRS arc-resistant fused/non-fused load break and fused/non-fused disconnect switches are available for applications

More information

Underground Distribution Switchgear

Underground Distribution Switchgear Underground Distribution Switchgear Type VFI, Vacuum Fault Interrupter Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

Type SDV7 distribution circuit breaker family

Type SDV7 distribution circuit breaker family www.usa.siemens.com/sdv7 Type SDV7 distribution circuit breaker family 5.5 kv to 8.0 kv Answers for infrastructure. Table of contents Introduction 0 Vacuum interrupters 0 Simple current path 05 Low-maintenance

More information

Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification 1. General 1.1 This specification is for a fixed, medium-voltage, padmounted, three-phase power capacitor bank

More information

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION Specification Number: 26 24 13.20 Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION 26 24 13.20 SWITCHBOARDS (Long) Main Disconnect Group Mounted Fusible

More information

Automatic, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

Automatic, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification Automatic, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification 1. General 1.1 This specification is for an automatic, medium-voltage, padmounted, three-phase power capacitor

More information

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated

More information

Underground Distribution Switchgear

Underground Distribution Switchgear Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,

More information

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear 13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of

More information

Issued Revised Approved Reviewed September 9, 1984 December 2008 G. Saini J. Fuller

Issued Revised Approved Reviewed September 9, 1984 December 2008 G. Saini J. Fuller Specification Medium Voltage Metalclad Switchgear Medium Voltage Number: 5342-02.01.310 Issued Revised Approved Reviewed September 9, 1984 December 2008 G. Saini J. Fuller Rev. 2 SCOPE This specification

More information

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General 13 SWITCHGEAR Medium Voltage Equipment -1 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General Overview Features Siemens, 7, 1 and 38kV class medium voltage, one- or two-high vacuum circuit breaker switchgear

More information

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers Medium-voltage vacuum circuit breakers Catalog information Medium-voltage vacuum circuit breakers catalog Technical Data Effective

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

BGE STRATEGIC CUSTOMER ENGINEERING

BGE STRATEGIC CUSTOMER ENGINEERING TABLE OF CONTENTS 1. GENERAL.. 2 2. BGE SUPPLY FEEDER.. 4 3. SWITCHGEAR ENCLOSURE AND ASSEMBLY... 5 4. SWITCHGEAR MANUFACTURERS.. 8 5. CIRCUIT BREAKER.. 8 6. SWITCHGEAR EQUIPMENT.... 10 7. MAIN AND GROUND

More information

Descriptive Bulletin. R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Descriptive Bulletin. R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Descriptive Bulletin R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Introduction The R-MAG is truly the next generation in medium voltage vacuum circuit breaker technology.

More information

Switchgear Skid, C1192

Switchgear Skid, C1192 CUSTOM SOLUTIONS 15kV Modular Stairs stored on floor in front of battery bay Ground grid stored on front tongue of trailer Stairs deployed for unit access Storage box for fencing materials and other parts

More information

COOPER POWER CA280012EN

COOPER POWER CA280012EN Reclosers Catalog Data CA280012EN Supersedes May 2014 (290-25) COOPER POWER SERIES Type VSA20B air-insulated, vacuum, electronically Description The Type VSA20B electronically controlled, vacuum circuit

More information

D. Operation and Maintenance Data. In addition to items specified in Division 1 Section "Operation and Maintenance Data," include the following:

D. Operation and Maintenance Data. In addition to items specified in Division 1 Section Operation and Maintenance Data, include the following: SECTION 16211 - ELECTRICITY METERING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

C. System Design and Performance Requirements

C. System Design and Performance Requirements Change History Date Description of Change Pages / Sections Modified 6/15/16 Updated division section from 16361-E-E to 26 10 03, removed references to other section numbers A. Summary - mgl44 Change Approver

More information

REVISIONS App PC. App Sud. App Thom TC 2014/03/25

REVISIONS App PC. App Sud. App Thom TC 2014/03/25 /9 Rev Description Document format and number changed. Previous number 543-0.0.30 Rev n by TC 204/03/25 Sud TC 204/03/25 REVISIONS PC Thom VB LH Clyd r Act Issue Date YYYY/MM/DD Pending Pending Pending

More information

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI BHARAT HEAVY ELECTRICALS LIMITED, JHANSI DESIGN, MANUFACTURING, TESTING, SUPPLY INSTALLATION AND COMMISSIONING OF 11KV VACUUM CIRCUIT BREAKER NOTE : 1 VENDOR must submit complete information against clause

More information

Type SDV7 distribution circuit breaker family Answers for energy.

Type SDV7 distribution circuit breaker family Answers for energy. www.usa.siemens.com/energy Type SDV7 distribution circuit breaker family Answers for energy. Table of contents Table of contents Page Introduction Vacuum interrupters Simple current path Low maintenance

More information

EMERGENCY GENERATOR SET

EMERGENCY GENERATOR SET PART 8.1: EMERGENCY GENERATOR SET PART 1 - GENERAL I SCOPE A. This specification covers the design, furnishing, installation and start up of a factory built, production tested, operable, liquid cooled

More information

BUSWAY Low Voltage (Pow-R-Flex)

BUSWAY Low Voltage (Pow-R-Flex) BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and

More information

Technical Specification for Pole Mounted Capacitor Rack

Technical Specification for Pole Mounted Capacitor Rack Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to

More information

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin SafeGear Motor Control Center Arc resistant Metal-Clad construction Descriptive Bulletin Table of Contents

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Typical Specification

Typical Specification Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,

More information

C1000 Series Automatic Cap Bank

C1000 Series Automatic Cap Bank C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution

More information

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser Reclosers Catalog Data CA280008EN Supersedes 280-45 July 2014 COOPER POWER SERIES Types VSA12, VSA12B, VSA16, VSA20, and ; three-phase; air-insulated; electronically controlled recloser VSA16 recloser

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 24 14 600 VOLT DRAWOUT SWITCHGEAR PART 1 - GENERAL 1.01 SECTION INCLUDES: A. Individually mounted rear-accessible low voltage switchgear ANSI rated switchgear and low voltage power circuit breakers

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings Page 1 Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings I. General This specification covers the design requirements for a pad-mounted capacitor

More information

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller Number: 5344-1.1.311 Rev. 8 Portable Mine Power Centres Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller SCOPE This specification covers general material and design

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Contents. Page INTRODUCTION Power/Vac GUIDE FORM SPECIFICATION thru

Contents. Page INTRODUCTION Power/Vac GUIDE FORM SPECIFICATION thru Contents Page INTRODUCTION... 10-2 Power/Vac GUIDE FORM SPECIFICATION... 10-2 thru 10-12 10-1 Power/Vac Guide Form Specifications Guide Form Specifications INTRODUCTION Upon completion of the one-line

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A - 3700 A R-MAG The R-MAG is truly the next generation in vacuum circuit breakers, combining industry recognized magnetic

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed,

More information

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Features: Low maintenance 10,000 mechanical operations (five times ANSI requirements) Simple magnetic actuator Vacuum interruption Definite

More information

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install fixed power factor correction equipment as specified herein and as shown on the contract drawings. This specification

More information