Time Delay Technique for Pinpointing PD Noise on Combined Cycle Systems Troy Coleman, Plant Technical Services
|
|
- Scott Copeland
- 5 years ago
- Views:
Transcription
1 Time Delay Technique for Pinpointing PD Noise on Combined Cycle s Troy Coleman, Plant Technical Services
2 Puget Sound Energy >1 Million Customers 772 MW Wind 3 Farms 276 MW Hydro 2 Projects 2481 MW Thermal 11 Sites 3529 MW Total 21.9% 7.8% 70.3% 2
3 Generator Stator Partial Discharge Record data every 6 months TGA-BP Pulse Qm (Magnitude) and NQN (Quantity) Check for changes in PD over time Doubling of PD in 6 months Severe Sumas Gas Turbine Generator 3
4 Goldendale, 1:1 Combined Cycle GE 7FA Gas Turbine 168 MW 18 kv Siemens Steam Turbine 84 MW 13.8 kv 4
5 High PD ( mv) Date Analyzing Stator (A PD phase) Difficult (A phase) Needed to use a 10:1 Attenuator to capture PD. 5
6 Hunting the elusive PD signal High PD throughout plant 230 kv 13.8 kv 18 kv 5 kv Switchgear 480 Switchgear 84 MW 168 MW Steam Turbine Generator Gas Turbine Generator 6
7 Need distance between both couplers 5ft Between 10ft 200ft Coupler Coupler 7
8 Adding Additional Coupler 10 feet apart Generator Generator Circuit Breaker Partial Discharge 80 pf Coupler 49 feet apart *New A B C Generator Step-Up Transformer 8
9 New distance between couplers Between 5ft 60ft 150ft Coupler Coupler New* Coupler 9
10 PD Coupler Coupler Equal Lengths Coax Cable A B C Coupler receives pulse after the Coupler = + Between Length ref 10
11 PD Coupler Coupler Equal Lengths Coax Cable A B C Coupler receives pulse before the Coupler = - Between Length ref 11
12 Between PD Coupler Coupler Equal Lengths Coax Cable A B C ref Pulse will arrive at one of the couplers before the other at a time delay < Between Length < Between Length 12
13 PDView Between Plot Technique! Notice Scale Between Coupler Coupler Where is your PD? Pulse Time Compared to Pulse Time = + Between Length = - Between Length Between < Between Length 13
14 PDView Plots Source: Iris PDView 14
15 Changing Time Delay Setting Source: Iris PDView 15
16 Adjusting Time Delay Settings Time Delay Setting: 90 nano seconds (thinks bus is 90 feet) Between Activity 65 feet 100 nano seconds 65 feet 100 nano seconds A Activity B C ref Pulses will travel at.65 ft/ns in coax Pulses will travel at 1 ft/ns in bus Time difference is 60 ns. Therefore PD is Between 16
17 Adjusting Time Delay Settings Time Delay Setting: 70 nano seconds (thinks bus is 70 feet) Between Activity 65 feet 100 nano seconds 65 feet 100 nano seconds Receives pulse at 175 ns A B C Receives pulse at 115 ns Activity ref Difference is 60 ns. Therefore PD is Between 17
18 Adjusting Time Delay Settings Time Delay Setting: 50 nano seconds (thinks bus is 50 feet) Between Activity 65 feet 100 nano seconds 65 feet 100 nano seconds Receives pulse at 175 ns A B C Receives pulse at 115 ns Activity ref Difference is 60 ns. Therefore PD is 18
19 Adding Additional Coupler 15 kv Coupler Actuator SF6 Breaker Disconnect 19
20 Adding Additional Coupler 20
21 Creating Equal Lengths Existing couplers had 24 coax cables. Our new* system coupler had a 88 coax cable. To create equal lengths, we needed a temporary 64 coax cable. Generator Generator Circuit Breaker 24' cable 24' cable *New A 64' cable B C ref 88' cable Generator Step-Up Transformer Off by 48.6 ns (Bus Length) 21
22 Changing Time Delays (59 feet apart) Time Delay Between 56 ns 55 ns 54 ns Shifted the Time Delay by 5ns. The noise is occurring a few feet from the coupler, which puts us in the circuit breaker 22
23 Source in Circuit Breaker? 23
24 SF 6 Gas Testing The gas tested normal: 99.9% Purity < 200 ppm dew 0 ppm SO PSI 24
25 Visual Inspection Aux Equipment Tested all the auxiliary equipment: Disconnect Bushing Surge Arrester Capacitor Voltage Transformer 25
26 Visual Inspection Inside Breaker CB DS 26
27 Source of Partial Discharge? MegOhm Tester: 1.65 MΩ 13.8 kv Actuator Grease Ground 27
28 Next Steps 1. Contacted manufacturer 2. Consulted other engineers 3. Cleaned actuator grease off 4. Put unit back in service 5. Re-perform PD testing 6. Re-inspect on next outage 28
29 Mint Farm, 1:1 Combined Cycle GE 7FA Gas Turbine 174 MW 18 kv Fuji Electric Steam Turbine 86 MW 13.8 kv 29
30 Hunting for Discharge Date (C phase) Between (C phase) (C phase) June 1 st 2015 (rain) June 9 th 2015 (dry) No or Between PD, so we decided to add an additional coupler further down the bus to increase our Between distance. 30
31 Adding Coupler Generator 24 feet apart Generator Circuit Breaker Partial Discharge 80 pf Coupler 150 feet apart Coax: 89 feet *New 89 feet A B C ref Generator Step-Up Transformer 31
32 Next Steps 1. Wait for the end of the outage when the unit is back in service. 2. Perform PD testing at earliest convenience, on a dry day. 3. Adjust time delay settings until the Between signal switches to a signal. 32
33 Thank you! Questions? 33
Energy Transmission & Distribution Services - Italy. SVEPPI laboratory...our services for your success. Answers for energy.
Energy Transmission & Distribution Services - Italy SVEPPI laboratory...our services for your success. Answers for energy. ...our services for your success ENERGY - T&D Services Experience teaches us that
More informationCentro América Application of EMI Diagnostics to Diesel Generators
Application of EMI Diagnostics to Diesel Generators CATEGORIAS *Experiencias con características de lotes de combustibles * Control de eficiencia de motores * Aliados clave para operadores de motores *
More informationPrimary Heat Transport (PHT) Motor Rotor Retaining Ring Failure
1 Primary Heat Transport (PHT) Motor Rotor Retaining Ring Failure Ali Malik Components & Equipment Eng. Ontario Power Generation - Darlington Nuclear 2 Ontario Power Generation Darlington Darlington Nuclear
More informationENGINEERED TO ORDER SOLUTIONS
DM-Series ENGINEERED TO ORDER SOLUTIONS for Transformer Bushing, Winding Hot Spot and PD Monitoring Features & Benefits Advanced Analytics Flexible and Modular Hardware Platform Bushing Monitoring Optional
More information78-EL-CS-E-1994 Senior Electrical Engineer. PERSONAL DATA Nationality : Egyptian
78-EL-CS-E-1994 Senior Electrical Engineer Holds a B. Sc. in Electrical Power & Machines Engineering and a Diploma of Electrical Switchgear and Protection. Has 16 years experience in construction, commissioning,
More informationengineered to order solutions
DM-Series engineered to order solutions for Transformer Bushing and Partial Discharge (PD) Monitoring Features & Benefits Bushing Monitoring Partial Discharge Monitoring Optional Thermal Modelling with
More informationSF 6 gas insulated RMU SafePlus 24 kv. ABB SafePlus 24 kv SF6 gas insulated RMU 1
SF 6 gas insulated RMU SafePlus 24 kv 25.03.2010 SafePlus 24 kv SF6 gas insulated RMU 1 Secondary distribution 400 kv Transmission substation Transformer 40-70 kv 130 kv Main Substation Secondary distribution
More informationMV Air Insulated Switchgear TAP17. Technical Data TGOOD
MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)
More informationAir-insulated switchgear UniGear type ZS1
Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5
More informationSF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv
Three-phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv 06B1-E-0020 Small Space Requirement, High Reliability and Safety ー 72.5 to 145kV GIS, SDH714 The number of application
More informationFirst Applications on AltaLink s Network. Roggero Ciofani, P. Eng. Colin Clark, P. Eng.
First Applications on AltaLink s Network Roggero Ciofani, P. Eng. Colin Clark, P. Eng. Overview Technology Overview Applications and Alternatives Advantages Alberta Special Considerations Operational Implications
More informationELE-PT-E-2005 Electrical Testing & Protection Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS
102926-ELE-PT-E-2005 Electrical Testing & Protection Engineer Holds B. Sc. and M. Sc. in Electrical Power & Machines Engineering and has about 9 years hands-on experience in protection, testing and commissioning.
More informationADVISE DESIGN IMPLEMENT FOR ELECTROTECHNICAL EXCELLENCE
ADVISE DESIGN FOR ELECTROTECHNICAL EXCELLENCE IMPLEMENT ADVISE DESIGN FOR ELECTROTECHNICAL EXCELLENCE Gemitech was founded in 1990 and, in just a few short years, grew to be recognized as medium and IMPLEMENT
More informationXQ-5200 Solar T60 Gas Turbine-Generator 5,200 ekw Iso Conditions 13.8 kv
XQ-5200 Solar T60 Gas Turbine-Generator 5,200 ekw Iso Conditions 13.8 kv XQ-5200_Specs.doc Page 1 of 11 Index 1. Overview... 3 2. Equipment... 4 3. Performance Data... 4 4. Gas Composition Requirement...
More informationSF6 free high-voltage GIS installation in Zürich, CH.
SF6 free high-voltage GIS installation in Zürich, CH. Dr. Walter Holaus, Global Product Manager, ABB Switzerland. 25.11.2015 Current developments in High-voltage switchgear Some examples November 27, 2015
More informationBETA Low-Voltage Circuit Protection
BETA Low-Voltage Circuit Protection /2 Introduction Miniature Circuit Breakers /4 5SP and 5SY miniature circuit breakers / 5SJ6...-.KS miniature circuit breakers with plug-in terminal /21 5SY6 0 miniature
More informationSolar Farms: design & construction
Solar Farms: design & construction Impacts to utility distribution systems John W. Gajda, P.E. Duke Energy Manager, DER Operations Support Agenda North Carolina s unique situation, which is coming to a
More informationPankaj Khali, ABB India Limited Representing :ABB Switzerland limited, September 2016 Generator Circuit-Breakers. Technical Seminar: PLN
Pankaj Khali, ABB India Limited Representing :ABB Switzerland limited, September 2016 Generator Circuit-Breakers Technical Seminar: PLN Agenda Advantages of Generator Circuit-Breakers Criteria of Selection
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationASEC scope of work and services can be classified as
Electromechanical, electronic and telecommunication contracting, maintenance and technical support projects ASEC scope of work and services can be classified as ASEC services can be broadly classified
More informationApplications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders
Applications HV HRC (high-voltage high rupturing capacity) fuses are used for short circuit protection in high-voltage switchgear for the 50 to 60 Hz frequency range Distribution transformers up to 2000
More informationELE-CMS-E-2007 Electrical Project Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS
103313-ELE-CMS-E-2007 Electrical Project Engineer Holds a B. Sc. in Electrical Power & Machines Engineering and has about 10 years hands-on experience working in construction, commissioning and maintenance.
More informationExtra-High-Voltage SF 6 Gas-Insulated Switchgear
Extra-High-Voltage SF 6 Gas-Insulated Switchgear Shuichi Sugiyama Masahiko Fujita Takahiro Shinohara 1. Introduction Due to location criteria and toughened restrictions on transportation, it has become
More informationTHP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com
THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com TGOOD produces over 5000 switchgear units annually for projects around the globe SOLUTION OVERVIEW For use in affordable air insulated
More informationFrequency of Maintenance Tests These specifications have been developed by the InterNational Electrical Testing Association for use by electrical power distribution system engineers. Copyright 2001 InterNational
More informationNew 115 kv Disconnect Switches at Bloomsburg MTS
115 kv Line tap from C9 to Bloomsburg MTS & New Bus Tie Switch CAA ID Number: 2007-EX353 Final Draft ASSESSMENT SUMMARY 1. GENERAL DESCRIPTION Norfolk TS and Bloomsburg MTS are supplied by a single 115
More informationEL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION
EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION El Paso Electric Company System Operations Department System Planning Section August 2006 I. INTRODUCTION The
More information11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls
11kV Compact Switchgear tec - range Minimum to Zero SF6 Insulation Gas. Outec Controls 1 tec xx - 11kV Switchgear Contents 1 tec CB - SF6 Free Switchgear... 3 1.1 Description:... 3 1.2 1.3 Features the
More information93 MWe natural gas fired Combined Cycle Power Plant
93 MWe natural gas fired Combined Cycle Power Plant 1. Power Plant General Description This is a Combined Cycle Cogeneration Power Plant (CCCPP) located in (Milan) able to supply about 30 t/h of surplus
More informationINDUSTRIAL GENERATOR SERVICE
INDUSTRIAL GENERATOR SERVICE PREVENTATIVE MAINTENANCE PROGRAM Customer: Date: Contact Person: Work Order #: Contact Number: ( ) Technician: INSPECTION COMPONENTS 1. GENERAL Check fuel tank level. Check
More informationAge-dependent & multi-load reliability analysis in transmission systems
CIGRE US National Committee 2013 Grid of the Future Symposium October 20-22, 2013 Boston, USA Age-dependent & multi-load reliability analysis in transmission systems Marco Fleckenstein, Prof. Dr. -Ing.
More informationPoweMr' With 18 Mechanism '. 1 . / ,, ( c :11t
) rvac Vacuu m Circuit. Breaker PoweMr' With 8 Mechanism L- '.. /,, ( (' p c :t ) FRONT VIEW,. 0 3 Fig. Front View of Breaker with Front Cover 3. COUNTER 0. INTERRUPTER ASSEMBLY Fig. 2 Front View of Breaker
More informationLEAP - Life Expectancy Analysis Program For Electrical Rotating Machines. Marcio Gennari ABB Brazil Automation Products Machines Service Osasco
LEAP - Life Expectancy Analysis Program For Electrical Rotating Machines Marcio Gennari ABB Brazil Automation Products Machines Service Osasco LEAP - Introduction ABB India (excellence center in insulation
More informationSimulation and Visualization of Power Grid Operations with High Renewable Penetration
Simulation and Visualization of Power Grid Operations with High Renewable Penetration Thomas J Overbye Fox Family Professor of Elect. & Comp. Eng. University of Illinois at Urbana-Champaign overbye@illinois.edu
More informationGas Insulated Substation Testing and Application
Gas Insulated Substation Testing and Application Course No: E02-020 Credit: 2 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P:
More informationRecommended Procedures
Selective Coordination Study Recommended Procedures The following steps are recommended when conducting a selective coordination study.. One-Line Diagram Obtain the electrical system one-line diagram that
More informationABB Switzerland Ltd High Voltage Products PTHG-V / Marta Lacorte Business Development LAM High Current Systems. Generator Circuit- Breaker Systems
ABB Switzerland Ltd High Voltage Products PTHG-V / Marta Lacorte Business Development LAM High Current Systems Generator Circuit- Breaker Systems. All rights reserved. - 1-07/05/2007 Generator Circuit-Breaker?
More informationEnergy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th. Alex Bettencourt Managing Director
Energy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th Alex Bettencourt Managing Director National Association Made Up of Entire Industry Utilities Industry Academia / R&D
More informationUse of High-Power Thyristor Technology for Short-Circuit Current Limitation in High Voltage Systems
Advanced Power Transmission Solutions Power Transmission and Distribution Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in Systems s Development of Power Markets Increasing
More informationIntroducing the TM /
Introducing the TM2500+ 8 / What s New? LM2500 PLUS gas turbine Up to 30% more power! Two-trailer design 75% reduction in footprint Improved interconnection design Faster installation and set-up 9 / 31%
More information132/11 kv, 25 MVA MOBILE SUBSTATION
File name: Mob EN katalog1 Zagreb, 11.11.2014. Page: 1 od 9 Summary Mobile substation consists of two semitrailers. One trailer is for 132 kv equipment (HV equipment) and another trailer is for medium
More informationCP Automatic capacitor bank
CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor
More informationM-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)
M-RING 24 SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A) Contents General Description Advanced facilities and process Advanced design philosophy Definition of M-RING 24 Standards Service conditions
More informationH U B B ELL L ABOR ATORIES CAPABILITY GUIDE
H U B B ELL L ABO R ATO R I E S CAPABILITY GUIDE INTRODUCTION Hubbell Power Systems, Inc. manufactures a wide variety of products for the electric utility, telecommunications, civil construction, transportation,
More informationELE-MOS-E-2006 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS
101162-ELE-MOS-E-2006 Electrical Engineer Holds a B. Sc. in Electrical Power & Machines Engineering and has over 7 years hands-on experience, mainly in operation, maintenance, commissioning and start-up.
More informationELE-CMOS-E-2004 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS
100403-ELE-CMOS-E-2004 Electrical Engineer Holds a B. Sc. in Electrical Power & Machines Engineering and has about 10 years hands-on experience working in operation, construction, commissioning and maintenance.
More informationUBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit
More informationElectrical Systems - Course 135 COMPOSITE ELECTRICAL PROTECTIVE SCHEMES: PART II
135 05-1 Electrical Systems - Course 135 COMPOSITE ELECTRICAL PROTECTIVE SCHEMES: PART II TURBINE-GENERATOR: rhipping AND ALARM CIRCUITS i.o' I titrodljction Following on from Lessons 135.03-1 and 135.04-1,
More informationGeneration equipment cost in nominal $ million, at purchase price, at installed cost and % share of capex, World, 2000 to 2020
GTD Capex and Markets Database, 2016 Ed 1, Contents of Spreadsheets Analysis of GTD Capex Generation equipment cost in nominal $ million, at purchase price, at installed cost and % share of capex, World,
More informationOverview Overvoltage protection
A P P L I C AT I O N N OT E 1.0 Overview Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage protection Metal-oxide surge
More informationOBJECTIVES LCC HVDC SYSTEMS VSC HVDC SYSTEMS COMMON EQUIPMENT DIFFERENT OPTIONS ECONOMIC IMPACTS CONCLUSIONS
OBJECTIVES LCC HVDC SYSTEMS VSC HVDC SYSTEMS COMMON EQUIPMENT DIFFERENT OPTIONS ECONOMIC IMPACTS CONCLUSIONS Investigate Feasibility of Converting or Upgrading Existing LCC to VSC Two Scenarios Considered
More informationMINISOLA, PGHV ITABB ABB Power Products High Voltage Italy
MINISOLA, PGHV ITABB ABB Power Products High Voltage Italy Slide 1 History of ABB s Lodi Unit 1926 Established Oil insulated Current Transformers for more than 50 years. 1981 SF6 Stand-alone Current Transformers
More informationThe Status of Energy Storage Renewable Energy Depends on It. Pedro C. Elizondo Flex Energy Orlando, FL July 21, 2016
The Status of Energy Storage Renewable Energy Depends on It Pedro C. Elizondo Flex Energy Orlando, FL July 21, 2016 Energy Storage Systems Current operating mode of electrical networks Electricity must
More informationPUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4
PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 1 2 3 4 5 6 7 8 9 Q. Please describe Hydro s terminal station and substation inspections policies and practices. In
More informationCONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation
CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent
More informationSPEN, Rasmus Larsson, High Voltage Breakers Innovative breaker solutions Substation design
SPEN, Rasmus Larsson, High Voltage Breakers 2014-05-06 Innovative breaker solutions Substation design Innovative breaker solutions High performance substations ABB FOCS Ludvika High Performance DCB HVDC
More informationAppendix G Examples and Recommended Methods
Reporting Outages to the Generating Availability Data System (GADS) Introduction The examples in this appendix illustrate the reporting of outages and deratings to GADS. They are based on a fictional 600
More informationImproving Power System s Performance with Line Arresters
Arr ArresterWorks Improving Power System s Performance with Line Arresters Jonathan Woodworth April 208 Copyright 208 ArresterWorks ArresterFacts 043 Improving Power System s Performance with Line Arresters
More informationNational Certificate in Electricity Supply (Sub Station Maintainer) (Level 4)
NZQF NQ Ref 1118 Version 2 Page 1 of 7 (Sub Station Maintainer) (Level 4) Level 4 Credits 140 This qualification has been reviewed. The last date to meet the requirements is 31 December 2018. Transition
More informationLarge Air Cooled Generator Failure
Large Air Cooled Generator Failure Henry Tarnecky AVP - Sr. Engineering Specialist, FM Global 2017 IRIS Rotating Machinery Conference FM Global Basics Commercial/Industrial Property Insurer Mutual Co.,
More informationHigh Voltage Surge Arresters Station Class
Power Transmission and Distribution High Voltage Surge Arresters Station Class Product Overview High Voltage High Protection Just as the Golden Gate Bridge has successfully defied all winds, weather and
More informationThe comprehensive portfolio of the testing laboratories at Schaltwerk Berlin siemens.com/energy/psw
Powerful, efficient, independent The comprehensive portfolio of the testing laboratories at Schaltwerk Berlin siemens.com/energy/psw Outstanding testing expertise and always up to date Benefit from decades
More informationNXPLUS C Single busbar. Maintenance-free for lifetime
NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage
More informationRESERVOIR SOLUTIONS. GE Power. Flexible, modular Energy Storage Solutions unlocking value across the electricity network
GE Power RESERVOIR SOLUTIONS Flexible, modular Energy Storage Solutions unlocking value across the electricity network TRENDS DISRUPTING THE POWER SECTOR FROM GENERATION TO T&D DECARBONIZATION DIGITIZATION
More informationZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.
ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW High performance alternative to air
More informationSF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv 06B1-E-0002 Small Space Requirement, High Reliability and Safety ー 72.5 to 145 kv GIS, SDH314/SDHa314
More informationCGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.
MV Switchgear for CGMCOSMOS Fully gas insulated modular and compact (RMU)system Up to 24 kv Up to 27 kv mediumvoltage mediumvoltageag AG Langackerstrasse Langackerstrasse 25 25 CH CH 6330 6330 Cham Cham
More informationGas Insulated Metal-clad Switchgear, HMGS!
Medium Voltage HMGS-G10 HYUNDAI Medium Voltage Gas Insulated Metal-clad Switchgear, HMGS! SF6 Gas Insulated Metal-clad Switchgear is an integrated assembly of vacuum circuit breaker, 3-position switch,
More information100 MW Wind Generation Project
A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility
More informationSubstation Maintenance Training
Substation Maintenance Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Electrical Substation maintenance
More informationVALVES WITH UV ELECTRIC ACTUATOR
505-507 VALVES WITH UV ELECTRIC ACTUATOR CHARACTERISTICS The 505+UV and 507+UV cast iron ball valves are dedicated to the automatic opening/shut-off of pipes carrying low pressure unloaded common fluids.
More informationINESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation
MOBILE SUBSTATIONS Energy Solution INTERNATIONAL FAIR MOBILE SUBSTATIONS ENERGY SOLUTION Complete design for energy s generations, transmission and distribution Mobile Substations Applications of Inesing
More informationMAINTENANCE TESTING SPECIFICATIONS
MTS-2001 Appendix B Frequency of Maintenance Tests MAINTENANCE SPECIFICATIONS FOR POWER DISTRIBUTION EQUIPMENT AND SYSTEMS InterNational Electrical Testing Association Inc. Quality Since 1972 Copyright
More informationELE-CMS-E-2001 Electrical Manager PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS
100297-ELE-CMS-E-2001 Electrical Manager Holds a B. Sc. in Electrical Power Engineering and has about 14 years hands-on experience working in construction, commissioning, start-up and maintenance of power
More informationMedium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.
Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution
More informationGreen energy conversion
Green energy conversion Prof. Dr.-Ing. habil. Andreas Binder Department of Electrical Energy Conversion Darmstadt University of Technology abinder@ew.tu-darmstadt.de Prof. A. Binder 1.1/1 Contents of lecture
More informationZX2 Gas-insulated medium voltage switchgear
Gas-insulated medium voltage switchgear Double busbar 13 8 10 12 11 10 9 8 7 2 1 3 4 5 6 2 Versatile Partitioned single or double busbar system for all applications even with the most demanding parameters
More informationVariable frequency transformer for asynchronous power transfer
Variable frequency transformer for asynchronous power transfer by Einar Larsen, Richard Piwko and Donald McLaren, GE Energy A new power transmission technology has been developed. The variable frequency
More informationPORTISHEAD B POWER STATION
PORTISHEAD B POWER STATION Portishead B Statistics: Main Building (General) Overall length: 704 ft. Overall width: 186 ft. Height above ground: 138 ft. (boiler house) Height above ground: 80 ft. (turbine
More informationPOWER SYSTEM CONSULTANTS POWER-LINKER
GROUP POWER SYSTEM CONSULTANTS POWER-LINKER REFERENCE LIST : CONDITION MONITORING TESTING Given below is a list of Condition Monitoring Testing job executed by us: SR. 132.0 Petronet LNG Ltd., Dahej 131.0
More informationHigh Voltage Technology & Testing
The Power of Trust. The Future of Energy. HIGH VOLTAGE TESTING Qualification testing, condition assessment, and forensic analysis Manufacturers and utility users of high-voltage electrical equipment face
More informationAn Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks
An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks D. M. Nobre W. L. A. Neves B. A. de Souza Departamento de Engenharia Elétrica - UFPB Av. Aprígio Veloso, 882 Bodocongó 58.109-970,
More informationFlexible Fossil Power Generation- A Manufacturer s Perspective
Flexible Fossil Power Generation- A Manufacturer s Perspective Greg Kelsall 12/03/ 2014 Agenda Alstom Background Clean Power, Clean Solutions Flexible Fossil Power Generation - 12/03/2014 P 2 Three main
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationFinal Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description
Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing
More informationSIEMENS Transmission and Distribution
TITLE Long Term Maintenance and Care for Reyrolle L800/1000T E. C. Wright 19/07/04 This document is to be used in conjunction with Installation, Operation and Maintenance Schedule IOMS 864. Its aim is
More informationWind Turbine. Commissioning Utilizing Mini-Grid Power. Scottish Renewables Onshore Wind Conference & Exhibition Aggreko
Wind Turbine Commissioning Utilizing Mini-Grid Power Scottish Renewables Onshore Wind Conference & Exhibition Agenda 41 Aggreko: 10 years in North America wind industry Wind Farm Mini-Grid Projects Why
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationPumped Storage Power Plants Solution
GE Grid Solutions Pumped Storage Power Plants Solution Flexibility for Grid Operators Pumped storage power plants are the largest and most cost-effective means of storing energy for electricity grids.
More informationBurns & McDonnell ISU Senior Design Project 2010/2011
Burns & McDonnell ISU Senior Design Project 2010/2011 STATION DATA BY BTJ DATE 02/04/2013 SHEET 1 OF 10 PROTECTION AND MEASUREMENTS EQUIPMENT SPECIFICATIONS PROJECT SCOPE New substation installaton. Add
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationTECHNICAL BROCHURE BC3WIRE-G2 R4
FEATURES 304 SS casing and end bells for corrosion resistance 304 SS casing and end bells for corrosion resistance Kingsbury type, 3 shoe, thrust bearing, see chart for ratings. Stainless steel, 17-4 PH
More informationGrounding Of Standby & Emergency Power Systems
July / August 2007 ELECTRICAL LINE 53 Grounding Of Standby & Emergency Power Systems By Andrew Cochran Power continuity is essential in many industrial and commercial installations where a trip out due
More informationCABLE SYSTEMS. Accessories and Systems for Medium and High-Voltage Cables up to 300 kv.
MV-CONNEX, HV-CONNEX, IXOSIL Terminations, IXOSIL MSA Slip-on Joint Boxes CABLE SYSTEMS Accessories and Systems for Medium and High-Voltage Cables up to 300 kv. Welcome to the CABLE SYSTEMS Centre of Competence.
More informationDate Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS
Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...
More informationKYN28-12(GZSI-12Z)Armoured Middle-Mounted Metal. Enclosed Switch. 1.General. 2.Model Definition
KYN28-12(GZSI-12Z)Armoured Middle-Mounted Metal Enclosed Switch 1.General KYN28-12 armoured middle-mounted metal enclosed switchgear (hereinafter referred to as switchgear) is a new product with own design
More informationAnnex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005
Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate DPL110551000 according to DIN EN ISO/IEC 17025:2005 Period of validity: 20140612 to 20160711 Date of issue: 20140612 Holder of
More informationIntegration of Large Wind Farms into Electric Grids
Integration of Large Wind Farms into Electric Grids Dr Mohammad AlZoubi Introduction Development WHAT IS NEXT!! Over the next 12 years, Europe must build new power capacity equal to half the current total.
More informationWind Generation and its Grid Conection
Wind Generation and its Grid Conection J.B. Ekanayake PhD, FIET, SMIEEE Department of Electrical and Electronic Eng., University of Peradeniya Content Wind turbine basics Wind generators Why variable speed?
More informationCustomer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment
Customer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment ABB LEAP Overview ABB LEAP - Benefits for customer Motivation to perform LEAP Failures
More information