Pankaj Khali, ABB India Limited Representing :ABB Switzerland limited, September 2016 Generator Circuit-Breakers. Technical Seminar: PLN
|
|
- Arnold Porter
- 6 years ago
- Views:
Transcription
1 Pankaj Khali, ABB India Limited Representing :ABB Switzerland limited, September 2016 Generator Circuit-Breakers Technical Seminar: PLN
2 Agenda Advantages of Generator Circuit-Breakers Criteria of Selection and Technical Requirements ABB Portfolio Overview and Critical Design Aspects New Standard: IEC/IEEE September 17, 2016 Slide 2
3 Advantages of Generator Circuit-Breakers September 17, 2016 Slide 3
4 Introduction Unit connection (without Generator Circuit-Breaker) Connection with Generator Circuit-Breaker EHV HV EHV HV MT MT G UT ST GenCB UT ST AUX G AUX September 17, 2016 Slide 4
5 Introduction with Generator Circuit-Breaker EHV EHV MT MT UT UT GenCB GenCB G AUX G AUX September 17, 2016 Slide 5
6 Introduction without Generator Circuit-Breaker with Generator Circuit-Breaker EHV HV EHV MT MT G SS SFC AUX ST GenCB G SS SFC UT September 17, 2016 Slide 6 Typical Layouts for Gas Turbine Power Plants
7 Advantages of Generator Circuit-Breakers Simplified Operational Procedures Simplified operation procedures Improved protection Higher power plant availability During the starting-up or shutting-down of the generator only one circuit-breaker has to be operated thus reducing the number of switching operations necessary The responsibilities for the operation of the power plant and the high-voltage grid are clearly defined Economic benefits September 17, 2016 Slide 7
8 Advantages of Generator Circuit-Breakers Improved Protection Simplified operation procedures Improved protection Maximum selectivity of protection zones Rapid and selective clearance of all types of faults Bursting of the transformer tank following an internal fault in the main or unit transformer Higher power plant availability Economic benefits September 17, 2016 Slide 8
9 Advantages of Generator Circuit-Breakers Interruption of Generator-Fed Fault Currents Interruption of Generator-Fed Fault Currents Case without Generator Circuit-Breaker (Unit Connection) G I g I s Grid Fault Current I s +I g I g tens of ms Interruption of HV Circuit-Breaker seconds Time September 17, 2016 Slide 9
10 Advantages of Generator Circuit-Breakers Interruption of Generator-Fed Fault Currents Interruption of Generator-Fed Fault Currents Case with Generator Circuit-Breaker G I g I s Grid Fault Current I s +I g I g tens of ms seconds Interruption of HV of Generator Circuit-Breaker Circuit-Breaker Time September 17, 2016 Slide 10
11 Pressure Rise in Power Transformers P [bar] HV Circuit-Breaker Generator Circuit-Breaker fault across bushing full winding shorted HV side tank withstand pressure Tap Changer fault to tank from HV winding tap changer contact fault 15% 25% 30% 10% shorted winding (portion) t [ms] September 17, 2016 Slide 11
12 Equipment Failures Main Transformer Failures Sequence of events: t = 0 ms: earth fault at HV-side of transformer t = 45 ms: 2-phase short-circuit t = 95 ms: 3-phase short-circuit t 150 ms: explosion of transformer Generator Transformer Failure - without Generator Circuit-Breaker September 17, 2016 Slide 12
13 Advantages of Generator Circuit-Breakers Improved Protection Simplified operation procedures Improved protection Higher power plant availability Maximum selectivity of protection zones Rapid and selective clearance of all types of faults Bursting of the transformer tank following an internal fault in the main or unit transformer Thermal destruction of the generator damper winding due to short-time unbalanced load conditions Economic benefits September 17, 2016 Slide 13
14 Advantages of Generator Circuit-Breakers Short-Time Unbalanced Load Conditions Single and two phase faults Inverse component interacts with damper windings Critical mechanical and thermal stresses September 17, 2016 Slide 14
15 Equipment Failures Short-Time Unbalanced Load Conditions Unbalanced Load Condition without Generator Circuit-Breaker September 17, 2016 Slide 15
16 Advantages of Generator Circuit-Breakers Improved Protection Simplified operation procedures Improved protection Higher power plant availability Maximum selectivity of protection zones Rapid and selective clearance of all types of faults Bursting of the transformer tank following an internal fault in the main or unit transformer Thermal destruction of the generator damper winding due to short-time unbalanced load conditions Mechanical destruction of a turbine-generator set due to generator motoring Economic benefits September 17, 2016 Slide 16
17 Equipment Failures Generator Motoring - without Generator Circuit-Breaker Generator P n = 500 MW Main Transformer HV Circuit-Breaker Overhead Line (Transmission) GS 3~ Overhead Line Coupling Internal Open Mechanical command breakdown destruction at HV of circuit-breaker, turbine-generator pole set L1 Generator Three-phase Shaft and starts bearings network working are interruption destroyed as motor Speed Turbine-generator Generator is increasing is lifted unit out again is of running the foundation down normally 12 meter high explosive flame September 17, 2016 Slide 17
18 Equipment Failures Generator Motoring - without Generator Circuit-Breaker n [min -1 ] Critical Rotor Speed 3000 n [min -1 ] Object after mechanical destruction 2420 Generator Turbine Generator normal run down t [min] September 17, 2016 Slide 18
19 Advantages of Generator Circuit-Breakers Improved Protection Simplified operation procedures Improved protection Higher power plant availability Economic benefits Maximum selectivity of protection zones Rapid and selective clearance of all types of faults Bursting of the transformer tank following an internal fault in the main or unit transformer Thermal destruction of the generator damper winding due to short-time unbalanced load conditions Mechanical destruction of a turbine-generator set due to generator motoring Thermal/dynamic stress caused to the generator by synchronising under out-of-phase conditions September 17, 2016 Slide 19
20 Advantages of Generator Circuit-Breakers Higher Power Plant Availability Simplified operation procedures The rapid and selective clearance of all types of faults Improved protection Higher power plant availability Simplified operational procedures Increased Availability More reliable synchronisation Economic benefits The avoidance of changeover switching operations Unit auxiliaries supplies drawn directly from main grid September 17, 2016 Slide 20
21 Advantages of Generator Circuit-Breakers Economic Benefits Simplified operation procedures Improved protection Higher power plant availability Economic benefits Integration of all the associated items of switchgear into the generator circuit-breaker enclosure Possible to omit the station transformer and the associated high-voltage and medium-voltage switchgear The through-fault capability required of the unit transformers is substantially reduced Higher availability in turn leads to an increased number of the operating hours and therefore to a higher profit for the operator of the power plant September 17, 2016 Slide 21
22 Availability Calculation Layout of Power Station Reference Scenario Case x 600 MW Power Station Layout Unit Connection with Generator Circuit -Breaker and Shut-Down Transformer September 17, 2016 Slide 22
23 Availability Calculation Results of Availability Calculation Results of Availability Calculation for one 600 MW Unit - Average Power Throughput Average Power Output of Unit (Assumed Value) Power [MW] Case 1 Case 2 Case September 17, 2016 Slide 23
24 Criteria of Selection and Technical Requirements September 17, 2016 Slide 24
25 Criteria of Selection and Technical Requirements Duties of Generator Circuit-Breakers Synchronise the generator with the main system Separate the generator from the main system (switching off the unloaded/lightly loaded generator) Carry and interrupt load currents (up to the full load current of the generator) Interrupt system-source short-circuit currents Interrupt generator-source short-circuit currents Interrupt fault currents due to out-of-phase conditions up to out-ofphase angles of 180 September 17, 2016 Slide 25
26 Short-Circuit Current Interruption i (t) u (t) t [ms] separation of arcing contact Characteristics of short-circuit current Characteristics of transient recovery voltage (TRV) September 17, 2016 Slide 26
27 Criteria of Selection and Technical Requirements Requirements for Generator Circuit-Breakers i (t) u (t) Magnitude Asymmetry t [ms] Characteristics of short-circuit current Rate-of-rise High technical requirements are imposed on the circuitbreaker with respect to: Rated current Short-circuit currents (system-source and generatorsource) September 17, 2016 Slide 27 Characteristics of transient recovery voltage (TRV) Fault currents due to out-of-phase conditions Degree of asymmetry of fault currents, fault currents with delayed current zeros Rate-of-rise of the recovery voltages
28 Criteria of Selection and Technical Requirements Standards for Generator Circuit-Breakers IEC IEEE Std C / IEEE Std C37.013a Circuit-breakers that have been designed and tested in accordance with IEC do not meet the stringent requirements imposed on generator circuit-breakers and therefore are not suitable for the use as generator circuitbreakers. September 17, 2016 Slide 28
29 Criteria of Selection and Technical Requirements Selection of Generator Circuit-Breaker Rated maximum voltage Rated power frequency Rated insulation level (dielectric strength): Lightning impulse withstand voltage and power frequency withstand voltage Rated peak and short-time withstand current Rated current Closing and making time Opening and breaking (interrupting) time Duty cycle (operating sequence) Rated short-circuit making current (closing and latching capability) September 17, 2016 Slide 29
30 Selection of Generator Circuit-Breaker Rated short-circuit breaking current (system-source short-circuit breaking current): Symmetrical value, degree of asymmetry, TRV capabilities Generator-source short switching capability: Symmetrical value, degree of asymmetry, TRV capabilities Out of phase current switching capability: Symmetrical value, degree of asymmetry, TRV capabilities Load current switching capability: Symmetrical value, TRV capabilities September 17, 2016 Slide 30
31 System-Source Short-Circuit Current 110 kv S k = 10 GVA 100 MVA 110/13.8 kv u k = 12 % I scts G 99 MVA 13.8 kv cos j = 0.8 X dv = 13.5% Contact parting time 50ms: I pk = 90.5 ka I sym = 33.2 ka a = 63.5 % September 17, 2016 Slide 31
32 System-Source Short-Circuit Current Characteristics of asymmetry: a = I dc 2I ac AC / symmetrical current 2I ac + DC current I dc = Asymmetrical current September 17, 2016 Slide 32
33 System-Source Short-Circuit Current Survey - Terminal Fault Prospective Currents (tcs = 40 ms) 250 I SCsys (karms) Generator Rated Power (MVA) September 17, 2016 Slide 33
34 System-Source Short-Circuit Current Survey - Terminal Fault Prospective Currents (tcs = 40 ms) 100 DOA sys (%) Generator Rated Power (MVA) Average DOA sys = 72.2% No DOA sys > 100% September 17, 2016 Slide 34
35 Generator-Source Short-Circuit Current 110 kv S k = 10 GVA 100 MVA 110/13.8 kv u k = 12 % I scg G 99 MVA 13.8 kv cos j = 0.8 X dv = 13.5% Contact parting time 50ms: I pk = 95.6 ka I sym = 23.8 ka a = % September 17, 2016 Slide 35
36 Generator-Source Short-Circuit Current Characteristics of asymmetry: a = I dc 2I ac September 17, 2016 Slide 36
37 Generator-Source Short-Circuit Current Survey - Terminal Fault Prospective Currents (tcs = 40 ms) Gas turbines of smaller power usually have a higher degree of asymmetry Salient-pole machines usually have a lower degree of asymmetry in case of generator-fed fault currents ABB is testing 130% degree of asymmetry September 17, 2016 Slide 37
38 Out-of-Phase Conditions 110 kv S k = 10 GVA 100 MVA 110/13.8 kv u k = 12 % I op G 99 MVA 13.8 kv cos j = 0.8 X dv = 13.5% Contact parting time 50ms: I pk = 68.2 ka I sym = 17.8 ka a = % September 17, 2016 Slide 38
39 Criteria of Selection and Technical Requirements Out-of-Phase Conditions Characteristics of asymmetry: a = I dc 2I ac September 17, 2016 Slide 39
40 Out-of-Phase Conditions Influence of outof-phase angle 180 out-of-phase condition 120 out-of-phase condition 90 out-of-phase condition 60 out-of-phase condition September 17, 2016 Slide 40
41 Selection of Generator Circuit-Breakers 180 Out-of-Phase Synchronisation Ratio between Isc OoP 180 and Isc system fault currents as function of generator rated power * * Paper submitted to the International Conference of Power Systems Transients (IPST2013) in Vancouver (CA) Example: HECS-130 system source breaking current OoP breaking current ka ka September 17, 2016 Slide 41
42 Tests 180 Out-Of-Phase Tests Tests demonstrating the capability of a GCB to interrupt currents resulting from 180 out-of-phase conditions shall show Current magnitude higher than 85% of system-source short-circuit current; Rate-of-rise of the transient recovery voltage (RRRV) 6.3 kv/ms. A test performed with Current magnitude equal to 50% of system-source short-circuit current; RRRV equal to 5.2 kv/ms or less; is not a proof of the capability of the tested GCB to interrupt currents resulting from 180 out-of-phase conditions. ABB September 17, 2016 Slide 42
43 Criteria of Selection and Technical Requirements Short-Circuit Current Current Interruption i (t) u (t) separation of arcing contact t [ms] September 17, 2016 Slide 43 Characteristics of short-circuit current Characteristics of transient recovery voltage (TRV)
44 Criteria of Selection and Technical Requirements Transient Recovery Voltage (TRV) September 17, 2016 Slide 44
45 Criteria of Selection and Technical Requirements Transient Recovery Voltage (TRV) - Surge Capacitors addition of capacitor The capacitor is connected during the testing of the interrupting performance rate-of-rise decresaes with capacitance value The capacitor is therefore to be considered as an integral part of a generator circuit-breaker time delay increases with capacitance value The interrupting capability demonstrated by these tests is valid only if capacitors of the same capacitance value as used during the tests are installed according to the tested configuration. September 17, 2016 Slide 45
46 Criteria of Selection and Technical Requirements Summary of Power Tests September 17, 2016 Slide 46
47 ABB Portfolio Overview and Critical Design Aspects September 17, 2016 Slide 47
48 ABB Generator Circuit Breakers Portfolio Overview (50/60 Hz) ABB
49 Generator Circuit-Breaker System type HECS-130L September 17, 2016 Slide 49
50 GCB System Typical single line diagram (1) Generator Circuit-Breaker 7 (2) Series Disconnector 9 (3) Capacitors 8 3 T (4) Starting Switch for SFC 6 T (5) Manual Short-Circuit Connection 5 2 (6) Earthing Switches G 10 (7) (8) Current Transformers Potential Transformers 8 3 G (9) Surge Arresters 9 (10) Motorized Short-Circuit Connection 7 G September 17, 2016 Slide 50
51 Service during Tender and Project Execution Application Studies Group for GCB s Application Studies Group is able to perform any kind of calculation required for the proper selection and verification of GCB s. Active in the Working Groups of the main IEC/IEEE Standards for HV breakers. Active in the revision of the IEEE C for GCB s bringing the most significant experience of ABB in the GCB field into requirements. September 17, 2016 Slide 51
52 Critical Design Aspects GCB Cooling System Natural Cooling Forced Cooling September 17, 2016 Slide 52
53 ABB GCB portfolio
54 Critical Design Aspects GCB Cooling System The fans provide a linear and even distribution of air in order to enhance natural convection. Natural Cooling Forced Cooling Enhanced Cooling Important: Which ratio of the capability is dependent on the cooling system? September 17, 2016 Slide 54
55 Critical Design Aspects Independent Cooling and Breaking Cooling through air convection Failure of cooling does not influence breaking capacity Less SF6 Low maintenance High reliability Cooling should not depend on SF6! September 17, 2016 Slide 55
56 HECS-XLp, XXLp Innovative passive cooling by heat pipes Latest technology patented by ABB for natural cooling and 20y maintenance free in accordance with the overhaul concept of HECS September 17, 2016 Slide 56
57 Interrupting chamber design SF6/SF6 vs SF6/Air SF6/SF6 contact system used by ABB SF6/Air contact system not used by ABB main contacts SF6 arcing contacts disconnector main contacts SF6 arcing contacts disconnector Disconnector in series to arcing and main contacts Main contacts in SF6 «Disconnector» in series only to arcing contacs Main contacts in air September 17, 2016 Slide 57
58 Contact System Design SF6/SF6 contact system used by ABB SF6/Air contact system not used by ABB main contacts SF6 arcing contacts disconnector main contacts SF6 arcing contacts disconnector Commutation of current path from main contacts to arcing contacts occurs in SF6. No sparks occur in air, thus eliminating the risk of a reduction of dielectric strength. Problems of moisture and pollution when the air in IPB is at atmospheric pressure do not affect the safe operation. Viewing windows of disconnector provide clear indication If circuit-breaker contacts accidentally close with disconnector open, no risk of explosion safe!! Isolation redundancy Commutation of current path from main contacts to arcing contacts occurs in air. Sparks which occur in air can lead to (commutation time times longer : I. a reduction of dielectric strength. II. wear of main contacts Problems of moisture and pollution when the air in IPB is at atmospheric pressure. «Disconnector» visibility: main contacts and disconnector If circuit-breaker contacts accidentally close with disconnector open, no possibility to extinguish arcs, risk of explosion not safe!! No isolation redundancy September 17, 2016 Slide 58
59 Design of Generator Circuit-Breakers Contact System SF6/SF6 v/s SF6/Air Example of specification The circuit-breaker shall have two separate contact systems: one for carrying load current, the other for arc interruption. Both contact systems shall be contained in SF6 and the current commutation shall occur in SF6. Contacts in air are not acceptable. Current commutation in air is not acceptable. A disconnector shall be provided on the transformer-side in series with the main and arcing contacts of the circuit-breaker. The series disconnector must be able to isolate the entire circuit and allow isolation for maintenance using industry accepted practices.
60 Critical Design Aspects Operating Mechanism Hydraulically charged spring operating mechanism in all ABB applications September 17, 2016 Slide 60
61 Critical Design Aspects Reliability of Operating Mechanism According to CIGRE survey hydro-mechanical spring mechanism is more reliable than full spring mechanism Number of Major Failures per 100 CB-years Highest reliability of hydro-mechanical spring operating mechanism Hydro-mechanical spring *) Spring **) Pneumatic *) *) source: CIGRE Session 2012, paper A3-206 **) source: CIGRE Brochure 510: Final Report of the International Enquiry on Reliability of High Voltage Equipment - Part 2 Reliability of High Voltage SF6 Circuit Breakers
62 New Standard: IEC/IEEE
63 History of Development of GCB Standard IEEE Std C IEEE Std C IEEE Std C IEEE Std C37.013a IEEE Std C (R2008) Number of pages of the document More than double number of pages compared to the previous revision!! IEC/IEEE IEEE C IEEE C IEEE C IEC/IEEE September 17, 2016 Slide 63
64 New IEC/IEEE IEC/IEEE IEEE C IEEE C37.013a September 17, 2016 Slide 64
65 New IEC/IEEE Structure of the Document IEC/IEEE Joint Development Procedure. The document number IEC/IEEE results from merging the numbering system of the two organizations. Because IEC includes the use of High-Voltage Switchgear and Controlgear Part xxx:, this needs to be part of the title. Document is placed in the IEC template.
66 New IEC/IEEE Generator-Source Short-Circuit Current Ratings A degree of asymmetry of 110% is not representative of interrupting conditions in actual power plant applications. A degree of asymmetry of 130% is more appropriate. Two classes for the rated generator-source short-circuit breaking current have been introduced: Class G1 Iscg = 100 ka Class G2 rating is assigned by the manufacturer Iscg with 110% degree of asymmetry % 0.74 x Iscg with 130% degree of asymmetry % Most of ABB GCBs already tested as G2 class! Iscg with 130% degree of asymmetry % Degree of asymmery at contact separation irrespectively of the time that contact separation occurs
67 New IEC/IEEE Ratings Mechanical Endurance Two classes for the mechanical endurance have been introduced. Standard generator circuit-breaker (normal mechanical endurance) class M operating cycles Generator circuit-breaker for special service requirements (extended mechanical endurance) class M operating cycles
68 New IEC/IEEE Type Tests IEEE C New IEC/IEEE Test procedures are not always well defined. A more detailed description of test procedures is implemented. This is especially true for tests in which the current exhibits delayed zero crossing. Detailed parameters are defined to characterize the current waveforms that should be tested. Customer cannot judge and evaluate objectively the validity of a test. Customer can easily judge and evaluate the validity of a test.
69 New IEC/IEEE Type Tests Delayed Current Zeros Generator Terminal Fault IEEE C IEC/IEEE Out-of-Phase Synchronization Fault at LV windings of 3W Transformer
70 New IEC/IEEE Delayed Current Zeros A test is not a sufficient proof of the breaking capability of the generator circuit-breaker with currents that exhibit delayed current zeros. The test is required to derive the arc voltage vs current characteristics and determine the arc voltage model of the generator circuit-breaker. The capability of the generator circuit-breaker to interrupt the current with delayed zero crossings shall be ascertained by studies that take into account the effect of the arc voltage.. The capability of the generator circuit-breaker to interrupt the current with delayed zero crossings shall be ascertained by computations that consider the effect of the arc voltage on the prospective shortcircuit current. Source: IEC/IEEE Edition 1.0, 2015
71 New IEC/IEEE Application Guide The following studies shall be performed for each project: system-source short-circuit current generator-source short-circuit current unloaded loaded with leading p.f Loaded with lagging p.f UA = 0 UA = max effect of arc voltage out-of-phase fault current September 17, 2016 Slide 71 UA = 0 UA = max effect of arc voltage SF6 or Vacuum
72 Application Guide Influence of Capacitors - 3 Rules 1. The amount of equivalent capacitance required for breaking tests shall be given in the test report and on the nameplate. 2. The same capacitance value shall be used for all breaking tests. 3. The interrupting capability demonstrated by breaking tests is valid only if capacitors of the same capacitance value as used during the tests are installed in the generator circuit-breaker system delivered for a specific project. Single line diagram of a SF 6 generator circuit-breaker (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) Generator Circuit-Breaker Disconnector Earthing switch Starting switch Manually mounted short-circuiting connection Surge capacitor Current transformer Voltage transformer Surge arrester Motor-operated short-circuiting link September 17, 2016 Slide
73 Pankaj Khali Territory Marketing & Sales Manager: India, Sub Regions & South East Asia Product Group: GCB, Power Grid Division High Voltage Products ABB India Limited Phone: Mobile: , Subscribe for GCB Insights today - It's free Question September 17, 2016 Slide 73
74
ABB Switzerland Ltd High Voltage Products PTHG-V / Marta Lacorte Business Development LAM High Current Systems. Generator Circuit- Breaker Systems
ABB Switzerland Ltd High Voltage Products PTHG-V / Marta Lacorte Business Development LAM High Current Systems Generator Circuit- Breaker Systems. All rights reserved. - 1-07/05/2007 Generator Circuit-Breaker?
More informationProduct brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring
Product brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring ABB is a leader in power and automation technologies that enable utility and industry customers to
More informationVacuum Generator Circuit Breaker - A trend-setting power plant technology
Vacuum Generator Circuit Breaker - A trend-setting power plant technology Stefan Schmid, Business Development Generator Breaker Switchgear siemens.at/future-of-energy for the power supply of tomorrow Table
More informationStudy of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank
Day 2 - Session V-B 299 Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Murali Kandakatla, B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Thane Introduction
More informationIndependent Testing Laboratory for High Voltage Equipment
T E S T I N G L A B O R A T O R Y Independent Testing Laboratory for High Voltage Equipment 1 CHALLENGING ENVIRONMENT The primary concern for utilities is to ensure grid reliability, efficiency, and security.
More informationHigh voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv
High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv PASS M0S 252 kv Innovation In today s market, the HV substation is increasingly becoming a key element
More informationBreaking new ground. A circuit breaker with the capacity to switch 15 large power plants
Breaking new ground A circuit breaker with the capacity to switch 15 large power plants Helmut Heiermeier, Reto Karrer The power networks that span the landscape and bring electrical energy to cities and
More informationChapter 6 Generator-Voltage System
Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals
More informationHB3 Generator Circuit-Breaker Switchgear
Catalog HB3 Edition 2017 HB3 Generator Circuit-Breaker Switchgear Medium-Voltage Switchgear siemens.com/generatorswitchgear R-HB1-001.tif R-HB3 001.tif R-HB3 003.tif R-HB3 002.jpg 2 HB3 Generator Circuit-Breaker
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60470 Second edition 1999-10 High-voltage alternating current contactors and contactor-based motor-starters Contacteurs pour courants alternatifs haute tension et démarreurs
More informationMV Air Insulated Switchgear TAP17. Technical Data TGOOD
MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)
More informationHB3-80 Generator Circuit-Breaker Switchgear. Medium-Voltage Switchgear. Totally Integrated Power HB3-80. Catalog HB3-80.
HB3-80 Generator Circuit-Breaker Switchgear Medium-Voltage Switchgear Totally Integrated Power HB3-80 Catalog HB3-80 Edition 2014 www.siemens.com/generatorswitchgear R-HB1-001.tif R-HB3-001.tif R-HB3-003.tif
More informationAn Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks
An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks D. M. Nobre W. L. A. Neves B. A. de Souza Departamento de Engenharia Elétrica - UFPB Av. Aprígio Veloso, 882 Bodocongó 58.109-970,
More informationRaising the bar. UHV switchgear and components
Raising the bar UHV switchgear and components Walter Holaus, Michael Lane, Richard Thomas The reliable supply of electrical energy is a backbone of the modern economy. Its ability to operate safely and
More informationMAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI
MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK --------------------------------------------------------------------------------------------------------------- Sub. Code : EE2402 Semester
More informationSchool of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering
University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering ELEC 5205 - High Voltage Engineering 3. Switchgear Types of Power System Switchgear
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly
More informationB kv Gas-insulated Substations
72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 62271-102 First edition 2001-12 High-voltage switchgear and controlgear Part 102: Alternating current disconnectors and earthing switches This English-language version is derived
More informationOutdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications
Outdoor live tank SF 6 circuit breaker Type OHB for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers
More informationSWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT
SWITCHCRAFT Switchcraft Europe GmbH Switchgear Product Overview igis Gas Insulated Switchgear isis Solid Insulated Switchgear icb - Vacuum Circuit Breaker iair - Air insulated switchgear panel Switchcraft
More informationDocuments and Addresses
Report No.: 05-035-MS/E Sheet: 2 Documents and Addresses Accreditation The Prüffeld der Schaltwerke, Berlin has been approved by the DATech (German accreditation body for technology) according to EN ISO/IEC
More informationGas Insulated Metal-clad Switchgear, HMGS!
Medium Voltage HMGS-G10 HYUNDAI Medium Voltage Gas Insulated Metal-clad Switchgear, HMGS! SF6 Gas Insulated Metal-clad Switchgear is an integrated assembly of vacuum circuit breaker, 3-position switch,
More informationPower/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers
Section Contents 9 Section 9 Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers Page INTRODUCTION... 9- APPLICATION... 9- TESTING... 9- LONGER LIFE... 9- QUALITY... 9- INSTALLATION...
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationNXPLUS C Single busbar. Maintenance-free for lifetime
NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage
More informationPrüffeld der Schaltwerke
Report No.: 16-043-MS Sheet: 2 Notes 1. The testing station of the Siemens switchgear factory (Prüffeld der Schaltwerke),, Berlin, has been approved by the DAkkS (German accreditation body) for rendering
More informationDISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus
DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution
More informationHD4. Gas insulated MV circuit-breakers kv A ka
HD4 Gas insulated MV circuit-breakers 12... 40.5 kv - 630... 3600 A - 16... 50 ka 1 DESCRIPTION Autopuffer breaking technique Electric arc extinction without chopped current No restriking after breaking
More informationZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.
DISTRIBUTION SOLUTIONS ZX1.5-R Gas-insulated medium voltage for railway application Safety and reliability 20% footprint saving Easy operation Complete solution ZX1.5-R Gas-insulated medium voltage for
More informationClose-Open (Short-Circuit) Time Results Interpretation
Application Note Close-Open (Short-Circuit) Time Results Interpretation Close-Open (C-O, trip-free) cycles simulate closing on a short circuit. In the actual event, the breaker closes first, then the protection
More informationCPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards
Medium Voltage Switchgear Primary Distribution CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka General description Presentation Ormazabal s CPG System includes the CPG.1
More informationHIGS Highly Integrated Generator Circuit-Breaker Switchgear
Catalog HIGS Edition 2018 HIGS Highly Integrated Generator Circuit-Breaker Switchgear Medium-Voltage Switchgear siemens.com/generatorswitchgear HIGS_2 tif HIGS_1 jpg HIGS_3 tif Application: Gas-fired steam
More informationGas Insulated Substation Testing and Application
Gas Insulated Substation Testing and Application Course No: E02-020 Credit: 2 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P:
More informationSolid Dielectric, Triple Option Reclosers Catalog O-vlt14
Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical
More informationSPEN, Rasmus Larsson, High Voltage Breakers Innovative breaker solutions Substation design
SPEN, Rasmus Larsson, High Voltage Breakers 2014-05-06 Innovative breaker solutions Substation design Innovative breaker solutions High performance substations ABB FOCS Ludvika High Performance DCB HVDC
More informationFinal Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description
Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing
More informationOutdoor vacuum breaker for railway applications - FSK II
Outdoor vacuum breaker for railway applications - FSK II Single or two-pole outdoor vacuum breaker with magnetic actuator 27.5 kv - 250 kv BIL - 1250 A. 2000 A - 25.0 ka - 50/60 Hz 27.5 kv - 200 kv BIL
More informationLive Tank Circuit Breakers Buyer s Guide
Live Tank Circuit Breakers Buyer s Guide Live Tank Circuit Breakers Buyer s Guide Edition 2, 2003-06 0-1 Contents Table of Contents Products Chapter-Page Introduction A-2 Explanations B-1 Puffer, Auto-Puffer
More informationA 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids
A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids Author Company Email Presenter T.A. Messinger BC Hydro toly.messinger@bchydro.com E. Burt BC Hydro ed.burt@bchydro.com P.Glaubitz Siemens
More informationEnergy Transmission & Distribution Services - Italy. SVEPPI laboratory...our services for your success. Answers for energy.
Energy Transmission & Distribution Services - Italy SVEPPI laboratory...our services for your success. Answers for energy. ...our services for your success ENERGY - T&D Services Experience teaches us that
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationDead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability
Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationB kv T&D GAS INSULATED SWITCHGEAR
GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission
More informationPresented to the IAPMO Standards Review Committee on December 9, 2013
Summary of Substantive Changes between the 2010 edition including Updates No. 1 and No. 2 dated September 2010 and August 2011 and the 2013 edition of CSA C22.2 No. 14 Industrial control equipment Presented
More informationOverview Gas Insulated Switchgear Modular and flexible, kV. ABB Group April 17, 2009 Slide 1
Overview Gas Insulated Switchgear Modular and flexible, 52-1100kV April 17, 2009 Slide 1 Tradition and Innovation Milestones from more than 40 Years of Experience Pioneer & Leader in GIS-Technology 1956
More informationVOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS
VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.
More information8DJ. Maintenance-free for lifetime
8DJ Maintenance-free for lifetime Energy Distribution Welcome! Page 2 October 1 st 2008 8DJ Main Applications for Medium-Voltage Switchgear Power generation Power stations G Power transmission High and
More informationVB1-D Generator Circuit-Breaker Switchgear
Catalog VB1-D Edition 2016 VB1-D Generator Circuit-Breaker Switchgear Medium-Voltage Switchgear siemens.com/generatorswitchgear 05_VB1_D_ECI tif 11_VB1_D_ECI tif R-HB1-001 tif R-HB3-001 tif Application:
More informationHigh-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution
High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching
More informationAir-insulated switchgear UniGear type ZS1
Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5
More informationSF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)
SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) About company The «Elektroapparat» plant starts its operation in 1922 as a plant manufacturing high-voltage electrical equipment. During the first two
More informationMedium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A
DISTRIBUTION SOLUTIONS Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A Continuous protection and reliable operation Proven design and compliance with newest fuses standards Compatibility with other ABB
More informationOverview Gas Insulated Switchgear Modular and flexible, kV. ABB Group May 15, 2013 Slide 1
Overview Gas Insulated Switchgear Modular and flexible, 52-1100kV May 15, 2013 Slide 1 Tradition and Innovation Milestones from more than 40 Years of Experience Pioneer & Leader in GIS-Technology 1956
More informationPower IT MV Live Tank Vacuum Circuit Breaker Model VBF
Power IT MV Live Tank Vacuum Circuit Breaker Model VBF ABB - a global leader in power and automation technologies ABB (www.abb.com) is a global leader in power and automation technologies that enable utility
More informationCharacteristics of LV circuit breakers Releases, tripping curves, and limitation
Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break
More informationSERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES
SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT SUBMERSIBLE AND VAULT MOUNTED
More informationSF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv 06B1-E-0002 Small Space Requirement, High Reliability and Safety ー 72.5 to 145 kv GIS, SDH314/SDHa314
More informationMEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices
MEDIUM VOLTAGE PRODUCTS The worldʼs fastest switching devices 2 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices ABBʼs fault current limiters disconnect
More informationOutdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications
Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers
More informationPower IT MV Live Tank Vacuum Circuit Breaker. Model OVB-SDB
Power IT MV Live Tank Vacuum Circuit Breaker Model OVB-SDB ABB - a global leader in power and automation technologies ABB (www.abb.com) is a global leader in power and automation technologies that enable
More informationDISTRIBUTION SOLUTIONS HA Breaker Retrofit. Medium Voltage Service Marketing and Sales
DISTRIBUTION SOLUTIONS HA Breaker Retrofit Medium Voltage Service Marketing and Sales Table of contents Retrofit concept General description Technical specification Necessary details for standard retrofit
More informationCompact Gas Insulated Switchgear (GIS) up to 145kV 126kV,145kV Compact Gas Insulated Switchgear (GIS)
Compact Gas Insulated Switchgear (GIS) up to 45 6,45 Compact Gas Insulated Switchgear (GIS). Standard: IEC 6703. Typical Feature. Great Breaking Character of Circuit Breaker The circuit breaker adopt the
More informationOutdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv
Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker
More informationLongest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!
DB 750-205 January 2007 Supercedes: December 2006 Now available with Vacuum Interrupter Monitor VBT Switch 15kV - 69kV VBU-T Switch 69kV - 230kV Longest Life Product for Electric Furnace Applications!
More informationPumped Storage Power Plants Solution
GE Grid Solutions Pumped Storage Power Plants Solution Flexibility for Grid Operators Pumped storage power plants are the largest and most cost-effective means of storing energy for electricity grids.
More informationEE 741 Over-voltage and Overcurrent. Spring 2014
EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with
More informationGas-Insulated Switchgear. Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A
Gas-Insulated Switchgear Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A siemens.com/energy-management Table of content Gas-insulated switchgear Product portfolio 72.5 550 kv Vacuum interrupters for switching
More informationSF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv
Three-phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv 06B1-E-0020 Small Space Requirement, High Reliability and Safety ー 72.5 to 145kV GIS, SDH714 The number of application
More informationProduct Group Brochure. PS Range Capacitor Vacuum Switches
Product Group Brochure PS Range Capacitor Vacuum Switches Introduction ABB introduces the latest range of PS capacitor vacuum switches. Building on the proven PS switch design, new single phase and three
More informationTechnical Data. Low Voltage Regulation System LVRSys. Flexible solution for power utilities. Voltage stabilization for industrial grids
Technical Data Low Voltage Regulation System LVRSys 1 Power range: 7.5 kva up to 3150 kva 1 Regulation: single- or three-phase 1 Regulation ranges: ± 6 % to ± 24 % 1 Overall efficiency: 99.4 % to 99.8
More informationStudy of 345 kv Transient Recovery Voltages on the Illinois Power System
Study of 345 Transient Recovery Voltages on the Illinois Power System R. A. Niemerg, Member, IEEE, T. E. Grebe, Senior Member, IEEE Abstract--Illinois Power will be installing twenty-two new 345 breakers
More informationNEXT STEP B) SAFETY :
SUMMARY : EVOLUTION OF MV/LV SUBSTATIONS COMPACT SUBSTATIONS J. M. Solans, C. Prevé, R. Farrán, R. Muñoz. SCHNEIDER ELECTRIC S.A. - SPAIN INTRODUCTION The recent liberalisation of the electricity supply
More informationCGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.
MV Switchgear for CGMCOSMOS Fully gas insulated modular and compact (RMU)system Up to 24 kv Up to 27 kv mediumvoltage mediumvoltageag AG Langackerstrasse Langackerstrasse 25 25 CH CH 6330 6330 Cham Cham
More informationZX2.2 Gas-insulated medium voltage switchgear
ZX2.2 Gas-insulated medium voltage switchgear 2 Brochure ZX2.2 Power engineering from ABB Solutions for the future As a technology group with global operations, ABB supplies the solutions of the future
More informationItem 1: Contents of the complete training & CV of the lecturer
Course DESIGN CONCEPTS + software SwitchgearDesign for SWITCHGEAR, SWITCHBOARDS, BUSDUCTS & SUBSTATIONS" Item 1: Contents of the complete training & CV of the lecturer Presented by Sergio Feitoza Costa
More informationSWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)
PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Issue 3 2012 SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED) www.energynetworks.org 2012 Energy Networks
More information020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)
020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service
More informationHMI, APRIL, Test Laboratories in Ratingen
HMI, 24.-28. APRIL, 2017 Test Laboratories in Ratingen Test Laboratories Ratingen Overview Basic Features Flexible Independent Well experienced in testing of medium and low voltage equipment (testing since
More informationHigh Voltage Surge Arresters Station Class
Power Transmission and Distribution High Voltage Surge Arresters Station Class Product Overview High Voltage High Protection Just as the Golden Gate Bridge has successfully defied all winds, weather and
More informationCPG.0 Single busbar gas-insulated cubicles
MV Switchgear Primary Distribution CPG.0 Single busbar gas-insulated cubicles Up to 36 kv CPG System The quality of products designed, manufactured and installed by Ormazabal is underpinned by the implementation
More informationFuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A
DISTRIBUTION SOLUTIONS Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A Superior performance versus standard fuses ensuring up to 40% faster protection in case of low
More informationFixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated
www.siemens.com/medium-voltage-switchgear Fixed-Mounted Circuit-Breaker Switchgear Type 8D and 8DB up to 0.5 kv, Gas-Insulated Medium-Voltage Switchgear Catalog H 35.11 201 nswers for infrastructure and
More informationFuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A
DISTRIBUTION SOLUTIONS Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A Efficient protection of voltage transformer circuits Extending the lifetime of installed electrical
More informationTHP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com
THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com TGOOD produces over 5000 switchgear units annually for projects around the globe SOLUTION OVERVIEW For use in affordable air insulated
More informationR-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A
R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A - 3700 A R-MAG The R-MAG is truly the next generation in vacuum circuit breakers, combining industry recognized magnetic
More information6545(Print), ISSN (Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET)
INTERNATIONAL International Journal of JOURNAL Electrical Engineering OF ELECTRICAL and Technology (IJEET), ENGINEERING ISSN 0976 & TECHNOLOGY (IJEET) ISSN 0976 6545(Print) ISSN 0976 6553(Online) Volume
More informationAnnex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005
Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate DPL110551000 according to DIN EN ISO/IEC 17025:2005 Period of validity: 20140612 to 20160711 Date of issue: 20140612 Holder of
More informationSolid Dielectric, Triple Option Reclosers Catalog O-vlt14
Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical
More informationMetal Clad Air Insulated Switchgear
Metal Clad Air Insulated Switchgear 1/ SecoGear Metal Clad Switchgear Features Fully metal-clad Equipped with Embedded pole VCB Full Front access (can be installed against wall) Perfect interlocking system
More informationH U B B ELL L ABOR ATORIES CAPABILITY GUIDE
H U B B ELL L ABO R ATO R I E S CAPABILITY GUIDE INTRODUCTION Hubbell Power Systems, Inc. manufactures a wide variety of products for the electric utility, telecommunications, civil construction, transportation,
More informationStefano Cervidi - ABB S.p.A. PPHV Santiago de Chile J.T. ABB Chile de Abril 2015 PASS - Plug and Switch System Subestaciones con tecnologìa
Stefano Cervidi - ABB S.p.A. PPHV Santiago de Chile J.T. ABB Chile 14-15 de Abril 2015 PASS - Plug and Switch System Subestaciones con tecnologìa hibrida PASS ABB in Lodi - History Long heritage based
More informationZX-Family Gas-insulated medium voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear Minimum overall costs ZX offers maximum economy The compact design of the panels reduces the space required and therefore the size of the station. Freedom
More informationZX2 Gas-insulated medium voltage switchgear
Gas-insulated medium voltage switchgear Double busbar 13 8 10 12 11 10 9 8 7 2 1 3 4 5 6 2 Versatile Partitioned single or double busbar system for all applications even with the most demanding parameters
More informationMINISOLA, PGHV ITABB ABB Power Products High Voltage Italy
MINISOLA, PGHV ITABB ABB Power Products High Voltage Italy Slide 1 History of ABB s Lodi Unit 1926 Established Oil insulated Current Transformers for more than 50 years. 1981 SF6 Stand-alone Current Transformers
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationPASS M0. Innovative solutions for distribution substations up to 170 kv
PASS M0 Innovative solutions for distribution substations up to 170 kv The concept In the today s changing market, the substation is becoming more and more a key element to meet end users requirements
More informationTargeted Application of STATCOM Technology in the Distribution Zone
Targeted Application of STATCOM Technology in the Distribution Zone Christopher J. Lee Senior Power Controls Design Engineer Electrical Distribution Division Mitsubishi Electric Power Products Electric
More information16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12
16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting
More information