How to select the correct size DS7 soft start controller
|
|
- Jane Francis
- 5 years ago
- Views:
Transcription
1 Effective May 7 How to select the correct size D7 soft start controller Application The D7 is a two phase control soft start controller utilized to accomplish motor starting using the reduced voltage method. Typically, the motor Horsepower or kw rating is used to determine the minimum required size of the soft start controller. This document addresses ramp time (T-tart) and start voltage (U-tart) parameters that require consideration in accomplishing the proper match of soft start controller to the load. Overview oft start controller sizing is typically determined beginning with the Horsepower or kw rating of the motor, coupled with the mains operating voltage. Using this information, a table or graph is consulted to factor in the starting time (t-tart) to determine the minimum size soft start controller that is appropriate for the application. If the application is considered to be severe due to a higher current inrush and/or longer starting time, it is commonplace to select a larger rated soft start controller to accommodate the higher loading on the CR s. The graphs and tables published for the D7 are based on an inrush value of 300% FLA or 400% FLA of the motor. A NEMA category B motor that is very common will demonstrate a 300% current rise during the start under normal conditions. If the actual inrush current approaches a value of 400% FLA as would be the case with higher NEMA Motor Code Letters, the maximum allowable ramp times are significantly affected. The t-tart starting time must be seriously considered and kept as short as practical (5 seconds). As the start time parameter is increased, the maximum allowable current capacity is decreased. When selecting the size of the, Tables 4-7 may be used if the anticipated starting time is seconds or less. Please note that either 300% or 400% Current Limit refers to the maximum anticipated start current in terms of motor FLA (3x or 4x). The D7 does not have a current limiter function. If the starting time is expected to be longer, Tables 8-4 should be reviewed to ensure that the soft starter is not subjected to excessive current resulting in CR failure. The size of the soft start controller may be required to be increased specifically due to a longer ramp time. NNote: The D7 oft tart controller may be incorrectly sized if based solely on motor Horsepower or kw rating and mains voltage alone.
2 Effective May 7 How to select the correct size The D7 oft tarter requires that specific attention is given to two factorse: Ultimate load the maximum inrush current that the soft start controller will transmit anytime during the start process. Ramp time the expected, or required, starting time required for the motor to achieve synchronous speed. Example 7.5HP Motor (A FLA) Motor Code Letter 460V Application, with an estimated starting time time of 8 seconds and 4 starts per hour. First, the locked rotor current (LRC) is used to determine the initial current rise when the motor is energized. This information may be noted on the Motor Nameplate. If the LRC is not indicated on the nameplate, the LRC may be calculated from the formula shown in Equation. Calculations indicate an LRC range of amps. A 300% current rise for this motor yields 33 amps (3 x amps), so the 300% Current Rise Table will be used for basic product selection. Consulting Table 4, the D7-340X02N0-N soft start controller shows an acceptable maximum motor size of 7.5HP. Please note that Tables 4 thru 7 indicate maximum allowable start ramp times of start/hr for these selections. Consulting Table and/ or Figure 4, the maximum allowable start current is noted as 8 second start time If needed, the starting time could be increased to seconds as the maximum allowable start current is 33.6 amps. Under these conditions, a D7-340X02N0-N soft starter is the appropriate selection for this application. Control Voltages for the D7 D7-340X...N0-N = 24 Vac/Vdc Uc D7-342X...N0-N = /240 Vac Uc D7-34DX...N0-D = 24 Vdc Uc upporting documentation Manuals D7 User Manual D7 Instructional Leaflet Program Files Outline Drawings Additional help Reference Number MN03900Z-EN IL Frame (4-2A) IL039004E - Frame 2 (6-32A) IL039005Z - Frames 3 & 4 (4-0A) none In the event additional help is needed, please contact the Technical Resource Center at -877-ETN-CARE. Option 2, ub Option 2. Example 2 With the same operating conditions as in Example, it is determined that the starting time must be extended to 2 seconds for the motor to achieve synchronous speed. Consulting Table and/or Figure 4, the maximum allowable start current for 2 seconds is indicated as 3.2 amps, less than the required 33A (3 x amps). Under these conditions, the D7-340X02N0-N soft start controller would not be an appropriate selection. Table 2 and/or Figure 5 for the next higher size unit, lists the maximum allowable start 2 seconds as approximately 36.8A. If needed, the starting time could be increased to 5 seconds as the maximum allowable start current is 33.6 amps. Under these new conditions, the next size higher soft start controller, D7-340X06N0-N is the suitable choice, as the maximum allowable start current for these conditions is sufficient for proper operation. Example 3 With the same operating conditions as in Example, it is discovered that the Motor Code Letter is D instead of B. Using Equation, the LRC current is 37.7 to 42.3 amps, so Table 5 (400% current rise) will be used for basic product selection. Table 5 indicates the D7-340X06N0-N is the appropriate selection for this 7.5 hp motor. Consulting Table 2 and/or Figure 5, the maximum allowable start current for 8 seconds is 46.4 amps. Please note that this product selection is at the maximum allowable starting time. Consulting Table 2 and/or Figure 5 shows the maximum allowable current for a 9 second start time is 43.2 amps. A larger soft start controller, the D7-340X024N0-N should be seriously considered if the starting time may exceed 8 seconds.. This operating condition will also require a larger capacity unit (D7-340X06N0-N) to accommodate the higher operating current (44 amps) during the starting time. NNote: Examples - 3 refer to LRC values at full mains voltage. Please keep in mind that these values are very close to the ultimate maximum rating of the CR s. etting the U-tart potentiometer to settings below 0% will lower the currents and extend the service life of the unit. Eaton does not recommend sizing based on U-tart settings below 0%. 2
3 How to select the correct size Application Paper AP039004EN Effective May 7 Determining initial current based on locked rotor current The National Electrical Code requires that all alternating current motors of /2 horsepower and higher must have code letters on the data plate indicating motor current in a locked rotor condition. This code denotes the Kilovolt-Ampere per horsepower of the motor. The KVAhp value is obtained from NEMA and/or NEC publications. The table below is provided as a reference. Locked rotor current of a three phase motor may be calculated using the following formula: Equation e: Calculating Locked Rotor Current (LRC): Locked Rotor Current = Horsepower x KVAhp x 00 E x.73 Example 4 To calculate the locked rotor current range of a 50 horsepower motor operating at 460 volts with a code letter B, proceed as follows; Locked Rotor Current = 50 x 3.5 x 00 = 97.9 Amperes (minimum) 460 x.73 Locked Rotor Current = 50 x 3.54 x 00 = Amperes (maximum) 460 x.73 Table. Motor Code Letter Locked Rotor kv-amp / hp Motor Code Letters Code Letter Locked Rotor Kilovolt-Ampere per hp Minimum Maximum A B C D E F G H J K L M.00.9 N P R T U V D7 Parameterization To determine the expected Initial Current value after determining the locked rotor current, apply the corresponding current reduction value based on the U-tart setting of the soft start controller in Table. electing a value of 53 (4th increment mark), the expected current will be 53% of the above values, or 4.89 amps to 7.88 amps respectively. Please note that the motor will develop approximately 28% of full voltage torque which is very similar to the starting current of a wye-delta configuration. NNote: The values in Table correspond to the increment marks on the U-tart potentiometer. Table 2. U-tart Initial Current U-tart ettings U-tart Current % Torque % The diagrams below show various potentiometer settings that have proven to be effective for standard application in real-life environments. NNote: The current in the motor circuit will be subject to the total impedance of the motor circuit, so actual values may be slightly different than calculated values. 3
4 Effective May 7 How to select the correct size Examples The following default settings are recommended for an application: Table 3. Parameterization Examples t-tart (s) U-tart (%) t-top (s) t - tart (s) U - tart (%) t - top (s) Application examples ~ ~30 0 ~25 ~ ~30 ~ ~ J 0 Low flywheel mass Conveyor belt with loose belt Roller conveyers ~ 0 30 ~ ~ Centrifugal pump ~5 30 ~ Fan general (building) with belt drive ~8 30 ~ J 0 High flywheel mass D7 >P Motor ~5 30 ~ Tunnel fan Axial fan D7 >P Motor ~ ~60 0 Bulk conveyor Escalator ~ ~60 0 Mixers Agitators D7 >P Motor
5 How to select the correct size Application Paper AP039004EN Effective May 7 D7 oft tart Controllers Horsepower Ratings Table 4. econd Ramp, tart per Hour, 300% Current 40ºC. D7-340X004N0-N D7-342X004N0-N D7-34DX004N0-D D7-340X007N0-N D7-342X007N0-N D7-34DX007N0-D D7-340X009N0-N D7-342X009N0-N D7-34DX009N0-D D7-340X02N0-N D7-342X02N0-N D7-34DX02N0-D D7-340X06N0-N D7-342X06N0-N D7-34DX06N0-D D7-340X024N0-N D7-342X024N0-N D7-34DX024N0-D D7-340X032N0-N D7-342X032N0-N D7-34DX032N0-D D7-340X04N0-N D7-342X04N0-N D7-34DX04N0-D D7-340X055N0-N D7-342X055N0-N D7-34DX055N0-D D7-340X070N0-N D7-342X070N0-N D7-34DX070N0-D D7-340X08N0-N D7-342X08N0-N D7-34DX08N0-D D7-340X0N0-N D7-342X0N0-N D7-34DX0N0-D D7-340X35N0-N D7-342X35N0-N D7-34DX35N0-D D7-340X60N0-N D7-342X60N0-N D7-34DX60N0-D D7-340X0N0-N D7-342X0N0-N D7-34DX0N0-D Motor Power (hp) Rated Current Amps 0V 230V 480V Maximum Allowable Breaker ize Maximum Allowable Fuse ize Recommended XTOB Overload Recommended C440 Overload HFD305 5A Class RK5 XTOB040DC C440AA00AX HFD305 5A Class RK5 XTOB057DC C440AA0AX HFD30 A Class RK5 XTOB065DC C440AA0AX HFD3030 A Class RK5 XTOB0GC 2 C440AA0AX HFD A Class RK5 XTOB0GC 2 C440AA0AX HFD A Class RK5 XTOB25GC 2 C440AA04AX HFD A Class RK5 XTOB60GC 2 C440AA04AX HFD350L 50A Class RK5 XTOB040DC 2 C440AA04AX HFD30L 0A Class RK5 XTOB057DC 2 C440BA0AX HJD3250 0A Class RK5 XTOB065DC 2 C440BA0AX HKD A Class RK5 XTOB0GC C440BA0AX HKD A Class RK5 XTOB0GC C440BA0AX HKD A Class RK5 XTOB25GC C440AA00AX HLD A Class RK5 XTOB60LC 3 C440AA00AX HLD A Class RK5 XTOB2LC 3 C440AA00AX 4 XTOBXDIND Panel Mounting Adapter must be used with this overload. 2 XTOBXTLL line and load lugs must be used with this overload. 5
6 Effective May 7 How to select the correct size D7 oft tart Controllers Horsepower Ratings Table 5. econd Ramp, tart per Hour, 400% Current 40ºC. D7-340X004N0-N D7-342X004N0-N D7-34DX004N0-D D7-340X007N0-N D7-342X007N0-N D7-34DX007N0-D D7-340X009N0-N D7-342X009N0-N D7-34DX009N0-D D7-340X02N0-N D7-342X02N0-N D7-34DX02N0-D D7-340X06N0-N D7-342X06N0-N D7-34DX06N0-D D7-340X024N0-N D7-342X024N0-N D7-34DX024N0-D D7-340X032N0-N D7-342X032N0-N D7-34DX032N0-D D7-340X04N0-N D7-342X04N0-N D7-34DX04N0-D D7-340X055N0-N D7-342X055N0-N D7-34DX055N0-D D7-340X070N0-N D7-342X070N0-N D7-34DX070N0-D D7-340X08N0-N D7-342X08N0-N D7-34DX08N0-D D7-340X0N0-N D7-342X0N0-N D7-34DX0N0-D D7-340X35N0-N D7-342X35N0-N D7-34DX35N0-D D7-340X60N0-N D7-342X60N0-N D7-34DX60N0-D D7-340X0N0-N D7-342X0N0-N D7-34DX0N0-D Motor Power (hp) Rated Current Amps 0V 230V 480V Maximum Allowable Breaker ize Maximum Allowable Fuse ize Recommended XTOB Overload Recommended C440 Overload HFD305 5A Class RK5 XTOB040DC C440AA00AX HFD305 5A Class RK5 XTOB057DC C440AA0AX HFD30 A Class RK5 XTOB065DC C440AA0AX HFD3030 A Class RK5 XTOB0GC 2 C440AA0AX HFD A Class RK5 XTOB0GC 2 C440AA0AX HFD A Class RK5 XTOB25GC 2 C440AA04AX HFD A Class RK5 XTOB60GC 2 C440AA04AX HFD350L 50A Class RK5 XTOB040DC C440AA04AX HFD30L 0A Class RK5 XTOB040DC C440AA04AX HJD3250 0A Class RK5 XTOB057DC 2 C440AA04AX HKD A Class RK5 XTOB057DC 2 C440BA0AX HKD A Class RK5 XTOB0GC C440BA0AX HKD A Class RK5 XTOB0GC C440BA0AX HLD A Class RK5 XTOB0GC C440BA0AX HLD A Class RK5 XTOB50GC C440AA00AX 3 XTOBXDIND Panel Mounting Adapter must be used with this overload. 2 XTOBXTLL line and load lugs must be used with this overload. 6
7 How to select the correct size Application Paper AP039004EN Effective May 7 D7 oft tart Controllers kw Ratings According to IEC Table 6. econd Ramp, tart per Hour, 300% Current 40ºC. D7-340X004N0-N D7-342X004N0-N D7-34DX004N0-D D7-340X007N0-N D7-342X007N0-N D7-34DX007N0-D D7-340X009N0-N D7-342X009N0-N D7-34DX009N0-D D7-340X02N0-N D7-342X02N0-N D7-34DX02N0-D D7-340X06N0-N D7-342X06N0-N D7-34DX06N0-D D7-340X024N0-N D7-342X024N0-N D7-34DX024N0-D D7-340X032N0-N D7-342X032N0-N D7-34DX032N0-D D7-340X04N0-N D7-342X04N0-N D7-34DX04N0-D D7-340X055N0-N D7-342X055N0-N D7-34DX055N0-D D7-340X070N0-N D7-342X070N0-N D7-34DX070N0-D D7-340X08N0-N D7-342X08N0-N D7-34DX08N0-D D7-340X0N0-N D7-342X0N0-N D7-34DX0N0-D D7-340X35N0-N D7-342X35N0-N D7-34DX35N0-D D7-340X60N0-N D7-342X60N0-N D7-34DX60N0-D D7-340X0N0-N D7-342X0N0-N D7-34DX0N0-D Motor Power (kw) Rated Current Amps 230V 400V Maximum Allowable Breaker ize Maximum Allowable Fuse ize Recommended XTOB Overload Recommended C440 Overload HFD305 5A Class RK5 XTOB040DC C440AA00AX HFD305 5A Class RK5 XTOB057DC C440AA0AX HFD30 A Class RK5 XTOB065DC C440AA0AX HFD3030 A Class RK5 XTOB0GC 2 C440AA0AX HFD A Class RK5 XTOB0GC 2 C440AA0AX HFD A Class RK5 XTOB25GC 2 C440AA04AX HFD A Class RK5 XTOB60GC 2 C440AA04AX 4 22 HFD350L 50A Class RK5 XTOB057DC 2 C440AA04AX HFD30L 0A Class RK5 XTOB057DC 2 C440BA0AX HJD3250 0A Class RK5 XTOB070GC 2 C440BA0AX HKD A Class RK5 XTOB0GC C440BA0AX HKD A Class RK5 XTOB0GC C440BA0AX HKD A Class RK5 XTOB50GC C440AA00AX HLD A Class RK5 XTOB60LC 3 C440AA00AX HLD A Class RK5 XTOB2LC 3 C440AA00AX 4 XTOBXDIND Panel Mounting Adapter must be used with this overload. 2 XTOBXTLL line and load lugs must be used with this overload. 7
8 Effective May 7 How to select the correct size D7 oft tart Controllers kw Ratings According to IEC Table 7. econd Ramp, tart per Hour, 400% Current 40ºC. Motor Power (kw) Rated Current Amps 230V 400V Maximum Allowable Breaker ize Maximum Allowable Fuse ize D7-340X004N0-N D7-342X004N0-N D7-34DX004N0-D D7-340X007N0-N D7-342X007N0-N D7-34DX007N0-D D7-340X009N0-N D7-342X009N0-N D7-34DX009N0-D D7-340X02N0-N D7-342X02N0-N D7-34DX02N0-D D7-340X06N0-N D7-342X06N0-N D7-34DX06N0-D D7-340X024N0-N D7-342X024N0-N D7-34DX024N0-D D7-340X032N0-N D7-342X032N0-N D7-34DX032N0-D D7-340X04N0-N D7-342X04N0-N D7-34DX04N0-D D7-340X055N0-N D7-342X055N0-N D7-34DX055N0-D D7-340X070N0-N D7-342X070N0-N D7-34DX070N0-D D7-340X08N0-N D7-342X08N0-N D7-34DX08N0-D D7-340X0N0-N D7-342X0N0-N D7-34DX0N0-D D7-340X35N0-N D7-342X35N0-N D7-34DX35N0-D D7-340X60N0-N D7-342X60N0-N D7-34DX60N0-D D7-340X0N0-N D7-342X0N0-N D7-34DX0N0-D Recommended XTOB Overload Recommended C440 Overload HFD305 5A Class RK5 XTOB040DC C440AA00AX HFD305 5A Class RK5 XTOB057DC C440AA0AX HFD30 A Class RK5 XTOB065DC C440AA0AX HFD3030 A Class RK5 XTOB0GC 2 C440AA0AX HFD A Class RK5 XTOB0GC 2 C440AA0AX HFD A Class RK5 XTOB25GC 2 C440AA04AX HFD A Class RK5 XTOB60GC 2 C440AA04AX HFD350L 50A Class RK5 XTOB040DC C440AA04AX HFD30L 0A Class RK5 XTOB040DC C440AA04AX HJD3250 0A Class RK5 XTOB057DC 2 C440BA0AX HKD A Class RK5 XTOB065DC 2 C440BA0AX HKD A Class RK5 XTOB0GC C440BA0AX HKD A Class RK5 XTOB0GC C440BA0AX HLD A Class RK5 XTOB60LC 3 C440AA00AX HLD A Class RK5 XTOB60LC 3 C440AA00AX 4 XTOBXDIND Panel Mounting Adapter must be used with this overload. 2 XTOBXTLL line and load lugs must be used with this overload. 8
9 How to select the correct size Application Paper AP039004EN Effective May 7 Figure e: 4 Amp Rated D7-340X004N0-N, D7-342X004N0-N D7-34DX004N0-D Figure 2e: 7 Amp Rated D7-340X007N0-N, D7-342X007N0-N D7-34DX007N0-D 30 2 D7-4A /hr (25 C ) /hr (40 C ) 4/hr (40 C ) /hr (40 C ) /hr (40 C ) 30 2 D7-7A /hr (25 C ) /hr (40 C ) 4/hr (40 C ) /hr (40 C ) /hr (40 C ) tart Time (s) tart Time (s) Table 8. 4A 8A 2A 6A A tart Current (A) D7-340X004N0-N, D7-342X004N0-N, D7-34DX004N0-D 4 A /hr /hr 4/hr /hr /hr Time (econds) 6.4 A 6.4 A 6.4 A 6.4 A 6.4 A A 6.4 A 6.4 A 5.6 A 3.6 A A 6.4 A 6.0 A 4.0 A 2.0 A A 5.2 A 4.8 A 2.8 A.4 A A 4.4 A 3.6 A 2.0 A 9.6 A A 4.0 A 3.2 A.2 A 8.8 A A 3.2 A 2.8 A.8 A 8.0 A A 2.8 A 2.0 A.0 A 7.6 A A 2.4 A.6 A 9.6 A 7.2 A 2.8 A 2.0 A.2 A 9.2 A 6.8 A 2.4 A.6 A.8 A 9.2 A 6.4 A A.2 A.4 A 8.8 A 6.4 A 3.6 A.8 A.0 A 8.4 A 6.0 A 4.6 A.4 A 9.6 A 8.4 A 5.6 A 5.2 A.4 A 9.2 A 8.0 A 5.6 A 6.8 A.0 A 9.2 A 7.6 A 5.6 A 7.4 A 9.6 A 8.8 A 7.6 A 5.2 A 8.4 A 9.6 A 8.4 A 7.6 A 5.2 A 9.0 A 9.2 A 8.4 A 7.2 A 5.2 A 9.6 A 9.2 A 8.0 A 7.2 A 4.8 A A 8.8 A 8.0 A 6.8 A 4.8 A A 8.8 A 8.0 A 6.8 A 4.8 A A 8.4 A 7.6 A 6.8 A 4.4 A A 8.4 A 7.6 A 6.8 A 4.4 A A 8.0 A 7.6 A 6.4 A 4.4 A A 8.0 A 7.2 A 6.4 A 4.4 A A 8.0 A 7.2 A 6.4 A 4.4 A A 7.6 A 7.2 A 6.4 A 4.0 A A 7.6 A 6.8 A 6.0 A 4.0 A A 7.6 A 6.8 A 6.0 A 4.0 A Table 9. 7A 4A 2A 28A 35A tart Current (A) D7-340X007N0-N, D7-342X007N0-N, D7-34DX007N0-D 7 A /hr /hr 4/hr /hr /hr Time (econds) 28.7 A 28.7 A 28.7 A 28.7 A 28.7 A A 28.7 A 28.7 A 27.3 A 23.8 A A 28.7 A 28.0 A 24.5 A 2.0 A A 26.6 A 25.9 A 22.4 A 8.2 A A 25.2 A 23.8 A 2.0 A 6.8 A A 24.5 A 23. A 9.6 A 5.4 A A 23. A 22.4 A 8.9 A 4.0 A A 22.4 A 2.0 A 7.5 A 3.3 A A 2.7 A.3 A 6.8 A 2.6 A 22.4 A 2.0 A 9.6 A 6. A.9 A 2.7 A.3 A 8.9 A 6. A.2 A A 9.6 A 8.2 A 5.4 A.2 A 3.3 A 8.9 A 7.5 A 4.7 A.5 A 4.3 A 8.2 A 6.8 A 4.7 A 9.8 A A 8.2 A 6. A 4.0 A 9.8 A A 7.5 A 6. A 3.3 A 9.8 A A 6.8 A 5.4 A 3.3 A 9. A A 6.8 A 4.7 A 3.3 A 9. A A 6. A 4.7 A 2.6 A 9. A 6.8 A 6. A 4.0 A 2.6 A 8.4 A A 5.4 A 4.0 A.9 A 8.4 A A 5.4 A 4.0 A.9 A 8.4 A A 4.7 A 3.3 A.9 A 7.7 A A 4.7 A 3.3 A.9 A 7.7 A A 4.0 A 3.3 A.2 A 7.7 A A 4.0 A 2.6 A.2 A 7.7 A A 4.0 A 2.6 A.2 A 7.7 A A 3.3 A 2.6 A.2 A 7.0 A A 3.3 A.9 A.5 A 7.0 A A 3.3 A.9 A.5 A 7.0 A 9
10 Effective May 7 How to select the correct size Figure 3e: 9 Amp Rated D7-340X009N0-N, D7-342X009N0-N D7-34DX009N0-D Figure 4e: 2 Amp Rated D7-340X02N0-N, D7-342X02N0-N, D7-34DX02N0-D 30 2 D7-9A /hr (25 C ) /hr (40 C ) 4/hr (40 C ) /hr (40 C ) /hr (40 C ) 30 2 D7-2A /hr (25 C ) /hr (40 C ) 4/hr (40 C ) /hr (40 C ) /hr (40 C ) tart Time (s) tart Time (s) 9A 8A 27A 36A 45A tart Current (A) Table. D7-340X009N0-N, D7-342X009N0-N, D7-34DX009N0-D 9 A /hr /hr 4/hr /hr /hr Time (econds) 36.9 A 36.9 A 36.9 A 36.9 A 36.9 A A 36.9 A 36.9 A 35. A 30.6 A A 36.9 A 36.0 A 3.5 A 27.0 A A 34.2 A 33.3 A 28.8 A 23.4 A A 32.4 A 30.6 A 27.0 A 2.6 A A 3.5 A 29.7 A 25.2 A 9.8 A A 29.7 A 28.8 A 24.3 A 8.0 A A 28.8 A 27.0 A 22.5 A 7. A A 27.9 A 26. A 2.6 A 6.2 A 28.8 A 27.0 A 25.2 A.7 A 5.3 A 27.9 A 26. A 24.3 A.7 A 4.4 A A 25.2 A 23.4 A 9.8 A 4.4 A A 24.3 A 22.5 A 8.9 A 3.5 A A 23.4 A 2.6 A 8.9 A 2.6 A A 23.4 A.7 A 8.0 A 2.6 A A 22.5 A.7 A 7. A 2.6 A A 2.6 A 9.8 A 7. A.7 A A 2.6 A 8.9 A 7. A.7 A A.7 A 8.9 A 6.2 A.7 A 2.6 A.7 A 8.0 A 6.2 A.8 A A 9.8 A 8.0 A 5.3 A.8 A 22.7 A 9.8 A 8.0 A 5.3 A.8 A 23.7 A 8.9 A 7. A 5.3 A 9.9 A 24.7 A 8.9 A 7. A 5.3 A 9.9 A A 8.0 A 7. A 4.4 A 9.9 A A 8.0 A 6.2 A 4.4 A 9.9 A A 8.0 A 6.2 A 4.4 A 9.9 A A 7. A 6.2 A 4.4 A 9.0 A A 7. A 5.3 A 3.5 A 9.0 A A 7. A 5.3 A 3.5 A 9.0 A 2A 24A 36A 48A 60A tart Current (A) Table. D7-340X02N0-N, D7342X02N0-N, D7-34DX02N0-D 2 A /hr /hr 4/hr /hr /hr Time (econds) 49.2 A 49.2 A 49.2 A 49.2 A 49.2 A A 49.2 A 49.2 A 46.8 A 40.8 A A 49.2 A 48.0 A 42.0 A 36.0 A A 45.6 A 44.4 A 38.4 A 3.2 A A 43.2 A 40.8 A 36.0 A 28.8 A A 42.0 A 39.6 A 33.6 A 26.4 A A 39.6 A 38.4 A 32.4 A 24.0 A A 38.4 A 36.0 A 30.0 A 22.8 A A 37.2 A 34.8 A 28.8 A 2.6 A 38.4 A 36.0 A 33.6 A 27.6 A.4 A 37.2 A 34.8 A 32.4 A 27.6 A 9.2 A A 33.6 A 3.2 A 26.4 A 9.2 A A 32.4 A 30.0 A 25.2 A 8.0 A A 3.2 A 28.8 A 25.2 A 6.8 A A 3.2 A 27.6 A 24.0 A 6.8 A A 30.0 A 27.6 A 22.8 A 6.8 A A 28.8 A 26.4 A 22.8 A 5.6 A A 28.8 A 25.2 A 22.8 A 5.6 A A 27.6 A 25.2 A 2.6 A 5.6 A 28.8 A 27.6 A 24.0 A 2.6 A 4.4 A A 26.4 A 24.0 A.4 A 4.4 A A 26.4 A 24.0 A.4 A 4.4 A A 25.2 A 22.8 A.4 A 3.2 A A 25.2 A 22.8 A.4 A 3.2 A A 24.0 A 22.8 A 9.2 A 3.2 A A 24.0 A 2.6 A 9.2 A 3.2 A A 24.0 A 2.6 A 9.2 A 3.2 A A 22.8 A 2.6 A 9.2 A 2.0 A A 22.8 A.4 A 8.0 A 2.0 A A 22.8 A.4 A 8.0 A 2.0 A
11 How to select the correct size Application Paper AP039004EN Effective May 7 Figure 5e: 6 Amp Rated D7-340X06N0-N, D7-342X06N0-N, D7-34DX06N0-D Figure 6e: 24 Amp Rated D7-340X024N0-N, D7-342X024N0-N, D7-34DX024N0-D 30 2 D7-6A /hr (25 C ) /hr (40 C ) 4/hr (40 C ) /hr (40 C ) /hr (40 C ) 30 2 D7-24A /hr (25 C ) /hr (40 C ) 4/hr (40 C ) /hr (40 C ) /hr (40 C ) tart Time (s) tart Time (s) 6A 32A 48A 64A 80A tart Current (A) Table 2. D7-340X06N0-N, D7-342X06N0-N, D7-34DX06N0-D 6 A /hr /hr 4/hr /hr /hr Time (econds) 65.6 A 65.6 A 65.6 A 65.6 A 62.4 A A 65.6 A 65.6 A 65.6 A 5.2 A A 65.6 A 65.6 A 60.8 A 44.8 A A 64.0 A 60.8 A 54.4 A 38.4 A A 60.8 A 56.0 A 48.0 A 35.2 A A 57.6 A 52.8 A 4.6 A 32.0 A A 54.4 A 49.6 A 36.8 A 28.8 A A 52.8 A 46.4 A 33.6 A 27.2 A A 49.6 A 43.2 A 32.0 A 25.6 A 5.2 A 48.0 A 4.6 A 30.4 A 25.6 A 49.6 A 46.4 A 40.0 A 28.8 A 24.0 A A 44.8 A 36.8 A 27.2 A 22.4 A A 43.2 A 35.2 A 25.6 A 22.4 A A 4.6 A 33.6 A 24.0 A.8 A A 40.0 A 33.6 A 24.0 A.8 A A 38.4 A 32.0 A 22.4 A 9.2 A A 38.4 A 30.4 A 22.4 A 9.2 A A 36.8 A 30.4 A.8 A 9.2 A A 35.2 A 28.8 A.8 A 7.6 A 38.4 A 35.2 A 28.8 A.8 A 7.6 A A 33.6 A 27.2 A 9.2 A 7.6 A A 33.6 A 27.2 A 9.2 A 7.6 A A 32.0 A 27.2 A 9.2 A 6.0 A A 32.0 A 25.6 A 7.6 A 6.0 A A 32.0 A 25.6 A 7.6 A 6.0 A A 30.4 A 25.6 A 7.6 A 6.0 A A 30.4 A 24.0 A 7.6 A 6.0 A A 30.4 A 24.0 A 7.6 A 6.0 A A 28.8 A 24.0 A 6.0 A 6.0 A A 28.8 A 22.4 A 6.0 A 6.0 A 24A 48A 72A 96A A tart Current (A) Table 3. D7-340X024N0-N, D7-342X024N0-N, D7-34DX024N0-D 24 A /hr /hr 4/hr /hr /hr Time (econds) 98.4 A 98.4 A 98.4 A 98.4 A 93.6 A A 98.4 A 98.4 A 98.4 A 76.8 A A 98.4 A 98.4 A 9.2 A 67.2 A A 96.0 A 9.2 A 8.6 A 57.6 A A 9.2 A 84.0 A 72.0 A 52.8 A A 86.4 A 79.2 A 62.4 A 48.0 A A 8.6 A 74.4 A 55.2 A 43.2 A A 79.2 A 69.6 A 50.4 A 40.8 A A 74.4 A 64.8 A 48.0 A 38.4 A 76.8 A 72.0 A 62.4 A 45.6 A 38.4 A 74.4 A 69.6 A 60.0 A 43.2 A 36.0 A A 67.2 A 55.2 A 40.8 A 33.6 A A 64.8 A 52.8 A 38.4 A 33.6 A A 62.4 A 50.4 A 36.0 A 3.2 A A 60.0 A 50.4 A 36.0 A 3.2 A A 57.6 A 48.0 A 33.6 A 28.8 A A 57.6 A 45.6 A 33.6 A 28.8 A A 55.2 A 45.6 A 3.2 A 28.8 A A 52.8 A 43.2 A 3.2 A 26.4 A 57.6 A 52.8 A 43.2 A 3.2 A 26.4 A A 50.4 A 40.8 A 28.8 A 26.4 A A 50.4 A 40.8 A 28.8 A 26.4 A A 48.0 A 40.8 A 28.8 A 24.0 A A 48.0 A 38.4 A 26.4 A 24.0 A A 48.0 A 38.4 A 26.4 A 24.0 A A 45.6 A 38.4 A 26.4 A 24.0 A A 45.6 A 36.0 A 26.4 A 24.0 A A 45.6 A 36.0 A 26.4 A 24.0 A A 43.2 A 36.0 A 24.0 A 24.0 A A 43.2 A 33.6 A 24.0 A 24.0 A
12 Effective May 7 How to select the correct size Figure 7e: 32 Amp Rated D7-340X032N0-N, D7-342X032N0-N, D7-34DX032N0-D 30 2 D7-32A /hr (25 C ) /hr (40 C ) 4/hr (40 C ) /hr (40 C ) /hr (40 C ) tart Time (s) 32A 64A 96A 28A 60A tart Current (A) Table 4. D7-340X032N0-N, D7-342X032N0-N, D7-34DX032N0-D 32 A /hr /hr 4/hr /hr /hr Time (econds) 3.2 A 3.2 A 3.2 A 3.2 A 3.2 A A 3.2 A 3.2 A 3.2 A 8.8 A A 3.2 A 3.2 A 24.8 A 83.2 A A 28.0 A 2.6 A 8.8 A 67.2 A A 2.6 A 2.0 A 96.0 A 60.8 A A 5.2 A 5.6 A 83.2 A 54.4 A A 8.8 A 99.2 A 73.6 A 48.0 A A 5.6 A 92.8 A 67.2 A 44.8 A A 99.2 A 86.4 A 64.0 A 4.6 A 2.4 A 96.0 A 83.2 A 60.8 A 4.6 A 99.2 A 92.8 A 80.0 A 57.6 A 38.4 A A 89.6 A 73.6 A 54.4 A 35.2 A A 86.4 A 70.4 A 5.2 A 35.2 A A 83.2 A 67.2 A 48.0 A 35.2 A A 80.0 A 67.2 A 48.0 A 32.0 A A 76.8 A 64.0 A 44.8 A 32.0 A A 76.8 A 60.8 A 44.8 A 32.0 A A 73.6 A 60.8 A 4.6 A 32.0 A A 70.4 A 57.6 A 4.6 A 32.0 A 76.8 A 70.4 A 57.6 A 4.6 A 32.0 A A 67.2 A 54.4 A 38.4 A 32.0 A A 67.2 A 54.4 A 38.4 A 32.0 A A 64.0 A 54.4 A 38.4 A 32.0 A A 64.0 A 5.2 A 35.2 A 32.0 A A 64.0 A 5.2 A 35.2 A 32.0 A A 60.8 A 5.2 A 35.2 A 32.0 A A 60.8 A 48.0 A 35.2 A 32.0 A A 60.8 A 48.0 A 35.2 A 32.0 A A 57.6 A 48.0 A 32.0 A 32.0 A A 57.6 A 44.8 A 32.0 A 32.0 A 2
13 How to select the correct size Application Paper AP039004EN Effective May 7 Table 5. ee also Figure 8 D7-340X04N0-N, D7-342X04N0-N, D7-34DX04N0-D 4 Amps Ramp Time /hr /hr 4/hr /hr /hr 55A 36A 33A 29A 27A 3 52A 33A 3A 29A 27A 4 50A 3A 28A 26A 24A 5 49A 29A 26A 24A 2A 6 46A 28A 25A 2A 8A 7 45A 26A 23A 9A 5A 8 44A 25A 2A 7A 3A 9 42A 24A A 5A A 42A 23A 8A 4A 8A 2 23A A 4A 98A 94A 3 2A 8A 2A 96A 9A 5 7A 5A 99A 92A 87A 9 2A A 93A 86A 80A A 0A 92A 84A 79A 23 9A 97A 89A 8A 73A 26 8A 96A 87A 79A 67A 29 6A 94A 85A 77A 62A 30 5A 94A 85A 76A 60A Table 7. ee also Figure D7-340X070N0-N, D7-342X070N0-N, D7-34DX070N0-D 68 Amps Ramp Time /hr /hr 4/hr /hr /hr 258A 226A 2A 24A 2A 3 253A 22A 27A 24A 2A 4 249A 27A 23A 9A 5A 5 246A 24A 2A 5A 0A 6 242A 22A 7A A 95A 7 24A 9A 3A 98A 9A 8 239A 8A A 94A 87A 9 236A 5A 98A 9A 83A 235A 4A 96A 89A 80A 2 4A 83A 73A 63A 55A 3 0A 80A 69A 59A 50A 5 94A 74A 64A 53A 44A 9 86A 67A 55A 42A 33A 85A 66A 53A 40A 3A 23 8A 62A 48A 35A 2A 26 78A 59A 45A 3A A 29 76A 57A 42A 27A 3A 30 74A 55A 40A 26A 0A Table 6. ee also Figure 9 D7-340X055N0-N, D7-342X055N0-N, D7-34DX055N0-D 55 Amps Ramp Time /hr /hr 4/hr /hr /hr 9A 83A 78A 73A 70A 3 4A 78A 76A 73A 70A 4 A 75A 72A 69A 66A 5 99A 73A 70A 66A 62A 6 96A 7A 67A 63A 58A 7 95A 69A 76A 60A 55A 8 93A 68A 62A 57A 52A 9 9A 66A 60A 55A 48A 90A 65A 59A 53A 45A 2 65A 48A 40A 32A 26A 3 62A 45A 37A 29A 2A 5 57A 4A 32A 23A 6A 9 50A 35A 25A 5A 8A 49A 34A 23A 3A 6A 23 46A 3A A 9A 98A 26 44A 29A 7A 6A 89A 29 42A 27A 5A 3A 83A 30 4A 26A 4A 2A 8A Table 8. ee also Figure D7-340X08N0-N, D7-342X08N0-N, D7-34DX08-N0-D 8 Amps Ramp Time /hr /hr 4/hr /hr /hr 25 C 25 C 40 C 40 C 40 C 307A 269A 262A 255A 25A 3 30A 263A 259A 255A 25A 4 296A 258A 254A 249A 245A 5 293A 255A 250A 245A 238A 6 289A 252A 246A 240A 232A 7 287A 249A 242A 235A 228A 8 284A 248A 239A 23A 223A 9 28A 245A 236A 228A 29A 280A 243A 234A 225A 24A 2 243A 29A 6A 94A 85A 3 238A 24A 2A 90A 79A 5 23A 8A 95A 82A 7A 9 222A 99A 84A 70A 59A 2A 97A 82A 67A 56A 23 25A 93A 77A 60A 44A 26 22A 90A 73A 56A 3A 29 9A 86A 69A 5A 22A 30 8A 85A 67A 50A 9A 3
14 Effective May 7 How to select the correct size Table 9. ee also Figure 2 D7-340X0N0-N, D7-342X0N0-N, D7-34DX0N0-D 99 Amps Ramp Time /hr /hr 4/hr /hr /hr 375A 329A 3A 32A 306A 3 368A 32A 37A 32A 306A 4 362A 36A 3A 304A 299A 5 359A 32A 305A 299A 29A 6 353A 308A 30A 293A 284A 7 35A 304A 296A 288A 278A 8 347A 303A 292A 282A 273A 9 344A 299A 289A 278A 267A 342A 297A 286A 275A 262A 2 297A 267A 252A 237A 226A 3 29A 262A 247A 232A 29A 5 282A 254A 238A 222A 9A 9 27A 243A 225A 7A 94A 269A 24A 222A 4A 9A A 235A 26A 96A 76A A 232A 2A 9A 6A A 228A 6A 85A 49A A 226A 5A 83A 46A Table. ee also Figure 3 D7-340X35N0-N, D7-342X35N0-N, D7-34DX35N0-D 34 Amps Ramp Time /hr /hr 4/hr /hr /hr 540A 482A 473A 440A 429A 3 532A 46A 462A 440A 429A 4 5A 450A 448A 424A 4A 5 5A 442A 437A 4A 395A 6 503A 436A 429A 400A 382A 7 497A 430A 42A 390A 370A 8 49A 425A 43A 38A 360A 9 486A 4A 407A 373A 335A 48A 46A 40A 365A 3A 2 434A 388A 379A 35A 272A 3 46A 37A 367A 344A 257A 5 398A 355A 329A 287A 23A 9 378A 337A 308A 264A 93A 374A 333A 304A 259A 85A A 323A 29A 245A 66A A 34A 28A 233A 50A A 307A 272A 223A 38A A 305A 269A 2A 34A Table 2. ee also Figure 4 D7-340X60N0-N, D7-342X60N0-N, D7-34DX60N0-D 60 Amps Ramp Time /hr /hr 4/hr /hr /hr 640A 57A 560A 52A 508A 3 63A 546A 548A 52A 508A 4 66A 533A 53A 503A 486A 5 606A 524A 58A 487A 468A 6 596A 56A 508A 474A 453A 7 589A 5A 498A 462A 439A 8 582A 504A 490A 452A 427A 9 576A 498A 482A 442A 397A 570A 493A 475A 433A 367A 2 54A 460A 449A 46A 322A 3 493A 440A 435A 408A 305A 5 472A 42A 390A 340A 274A 9 448A 399A 365A 33A 229A 443A 395A 360A 307A 29A A 383A 345A 290A 97A 26 4A 372A 332A 276A 78A 29 4A 364A 322A 264A 64A A 36A 39A 26A 59A Table 22. ee also Figure 5 D7-340X0N0-N, D7-342X0N0-N, D7-DX0N0-D 96 Amps Ramp Time /hr /hr 4/hr /hr /hr 800A 74A 700A 652A 636A 3 788A 683A 685A 652A 636A 4 770A 667A 664A 628A 607A 5 757A 655A 648A 609A 585A 6 745A 646A 635A 593A 566A 7 736A 637A 623A 578A 548A 8 727A 630A 62A 564A 533A 9 7A 622A 602A 553A 496A 73A 66A 593A 54A 459A 2 643A 575A 56A 5A 403A 3 66A 550A 543A 5A 38A 5 590A 526A 488A 425A 342A 9 560A 499A 457A 39A 286A 554A 493A 450A 384A 274A A 479A 432A 363A 246A A 465A 46A 345A 222A 29 53A 455A 403A 330A 4A A 452A 399A 326A 99A 4
15 How to select the correct size Application Paper AP039004EN Effective May 7 tart Time 30 (25 C),, 4, & (40 C) tarts per Hour 2 /hr 25 C /hr 40 C 4/hr 40 C /hr 40 C /hr 40 C 60A Maximum ramp 300% frame size (3 x 4 = 23A) start per hour (25 C) = 2 seconds start per hour (40 C) = seconds 4 starts per hour (40 C) = 7 seconds 70A 80A 90A 0A A A 30A 40A 50A tart Current Figure 8. 4A Rated D7-340X04N0-N, D7-342X04N0-N, D7-34DX04N0-D tart Time 30 (25 C),, 4, & (40 C) tarts per Hour 2 /hr 25 C /hr 40 C 4/hr 40 C /hr 40 C /hr 40 C 80A Maximum ramp 300% frame size (3 x 55 = 65A) start per hour (25 C) = 2 seconds start per hour (40 C) = seconds 4 starts per hour (40 C) = 6 seconds 0A A 40A 60A 80A tart Current 0A Figure 9. 55A Rated D7-340X055N0-N, D7-342X055N0-N, D7-34DX055N0-D 5
16 Effective May 7 How to select the correct size tart Time 30 (25 C),, 4, & (40 C) tarts per Hour 2 /hr 25 C /hr 40 C 4/hr 40 C /hr 40 C /hr 40 C 0A Maximum ramp 300% frame size (3 x = 65A) 4A) start per hour (25 C) = 2 seconds start per hour (40 C) = seconds 4 starts per hour (40 C) = 6 seconds 25A 50A 75A 0A 225A tart Current 250A Figure. 68A Rated D7-340X070N0-N, D7-342X070N0-N, D7-34DX070N0-D tart Time 30 (25 C),, 4, & (40 C) tarts per Hour 2 /hr 25 C /hr 40 C 4/hr 40 C /hr 40 C /hr 40 C 0A Maximum ramp 300% frame size (3 x 8 = 24A) start per hour (25 C) = 2 seconds start per hour (40 C) = seconds 4 starts per hour (40 C) = 7 seconds 25A 50A 75A 0A 225A 250A 275A 300A tart Current Figure. 8A Rated D7-340X08N0-N, D7-342X08N0-N, D7-34DX08N0-D 6
17 How to select the correct size Application Paper AP039004EN Effective May 7 tart Time 30 (25 C),, 4, & (40 C) tarts per Hour 2 /hr 25 C /hr 40 C 4/hr 40 C /hr 40 C /hr 40 C 50A Maximum ramp 300% frame size (3 x 99 = 297A) start per hour (25 C) = 2 seconds start per hour (40 C) = seconds 4 starts per hour (40 C) = 6 seconds 75A 0A 225A 250A 275A 300A 325A 350A tart Current Figure 2. 99A Rated D7-340X0N0-N, D7-342X0N0-N, D7-34DX0N0-D tart Time 30 (25 C),, 4, & (40 C) tarts per Hour 2 /hr 25 C /hr 40 C 4/hr 40 C /hr 40 C /hr 40 C 25A Maximum ramp 300% frame size (3 x 34 = 402A) start per hour (25 C) = 3 seconds start per hour (40 C) = seconds 4 starts per hour (40 C) = 9 seconds 50A 75A 0A 225A 250A 275A 300A 325A 350A 375A 400A 425A 450A 475A 500A 525A 550A tart Current Figure 3. 34A Rated D7-340X35N0-N, D7-342X35N0-N, D7-34DX0N0-D 7
18 Effective May 7 How to select the correct size tart Time 30 (25 C),, 4, & (40 C) tarts per Hour 2 /hr 25 C /hr 40 C 4/hr 40 C /hr 40 C /hr 40 C 50A Maximum ramp 300% frame size (3 x 6 = 483A) start per hour (25 C) = 3 seconds start per hour (40 C) = seconds 4 starts per hour (40 C) = 8 seconds 0A 250A 300A 350A 400A 450A 500A 550A 600A 650A tart Current Figure 4. 60A Rated D7-340X60N0-N, D7-342X60N0-N, D7-34DX6N0-D tart Time 30 (25 C),, 4, & (40 C) tarts per Hour 2 /hr 25 C /hr 40 C 4/hr 40 C /hr 40 C /hr 40 C 0A Maximum ramp 300% frame size (3 x 96 = 588A) start per hour (25 C) = 5 seconds start per hour (40 C) = seconds 4 starts per hour (40 C) = seconds 250A 300A 350A 400A 450A 500A 550A 600A 650A 700A 750A 800A tart Current Figure 5. 96A Rated D7-340X0N0-N, D7-342X0N0-N, D7-34DX0N0-D Eaton Electrical ector uperior Ave. Cleveland, OH 444 United tates 877-ETN-CARE ( ) Eaton.com 7 Eaton All Rights Reserved Printed in UA Publication No. AP EN / CC-2552 May 7 Eaton and PowerChain Management are registered trademarks of Eaton Corporation. All other trademarks are property of their respective owners.
Reduced Voltage Motor Starters
Reduced Voltage Motor Starters Soft Start Controllers. Solid-State Controllers Product Overview........................................ DS7 Soft Start Controllers.................................. Type
More information1.1. Reduced Voltage Motor Starters
Reduced Voltage Motor Starters. DS7 Soft Start Controllers Contents Description Type S70, Soft Start Controllers.............. Type S70, Soft Start Controllers with Auxiliary Contact.........................
More informationReduced Voltage Motor Starters
Reduced Voltage Motor Starters Soft Start Controllers. Solid-State Controllers Product Overview........................................ Type S70, Soft Start Controllers............................. Type
More informationReduced Voltage Motor Starters
Soft Start Controllers. Solid-State Controllers Product Overview........................................ Type S70, Soft Start Controllers............................. Type S70, Soft Start Controllers with
More informationXT UL short-circuit. current ratings. Technical Data TD E. Contents
Changes to ULT 8A and the NECT in recent years have brought a focus to control panel safety with regard to short-circuit (SCCR). Eaton s XT line of IEC power control has a wide variety of SCCR solutions
More informationAND LOAD PARAMETERS IMPORTANT MOTOR. Torque x Speed Constant. Horsepower= Mechanical Power Rating Expressed in either horsepower or watts
MOTOR SELECTION Electric motors should be selected to satisfy the requirements of the machines on which they are applied without exceeding rated electric motor temperature IMPORTANT MOTOR AND LOAD PARAMETERS
More informationLow Voltage Fuses For Motor Protection
Code Requirements The NEC or CEC requires that motor branch circuits be protected against overloads and short circuits. Overload protection may be provided by fuses, overload relays or motor thermal protectors.
More informationApplication Description
-14 Type, Intelligent Technologies (IT.) Soft Starters February 2007 Contents Description Page Type, Intelligent Technologies (IT.) Soft Starters Product Description....... -14 Application Description....
More information300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds
Digital Soft Start Controls 9 thru 900 Amps 208-460V 50/60 Hz. 9 thru 900 Amps 208-575V 50/60 Hz. Applications: Controlled ramp start and stop, minimize spillage in material handling, reduced water hammer
More information1.2. Reduced Voltage Motor Starters. Contents Description Type S611, Solid-State Soft Starters... Type S801+, Soft Starters. Solid-State Starters
.2 Type S80+, Soft Starters Contents Description Type S6, Solid-State Soft Starters........... Type S80+, Soft Starters Operation............................. Features.............................. Benefits...............................
More informationET 332b Ac Motors, Generators and Power Systems. lesson14_et332b.pptx. Learning Objectives. After this presentation you will be able to:
ET 332b Ac Motors, Generators and Power Systems lesson14_et332b.pptx 1 Learning Objectives After this presentation you will be able to: List the characteristics of NEMA Design motors. Identify and interpret
More information1.2. Reduced Voltage Motor Starters. Contents Description Type S611, Soft Starters... Type S801+, Soft Starters. Type S801+, Soft Starters
Reduced Voltage Motor Starters.2 Type S80+, Soft Starters Contents Type S6, Soft Starters..................... Type S80+, Soft Starters Operation.............................. Features...............................
More informationQuick selector reference guide. Motor Control Center Aftermarket Buckets
Quick selector reference guide Motor Control Center Aftermarket Buckets 2 EATON WWW.EATON.COM/MCCAFTERMARKET Table of contents Series 2100 MCC bucket Motor Control Center (MCC) Aftermarket Buckets Overview
More information300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds
Digital Soft Start Controls Soft Starters & 9 thru 900 s 208-460V 50/60 Hz. 9 thru 900 s 208-575V 50/60 Hz. Farm Duty Applications: Controlled ramp start and stop, minimize spillage in material handling,
More informationBenefits of using the Eaton S811+ soft starter to improve uptime and lower maintenance costs
Why soft start a motor? The most significant benefits of soft starting a motor come from reduced mechanical and electrical stress. This not only translates to lower maintenance costs, but significantly
More informationBussmann series Quik-Spec Power Module Switch elevator disconnect
Supersedes January 2016 Agency information UL 98 enclosed and dead-front switch - Guide WIAX, WIAX7 (Canada), File E182262 culus, NEMA 1, UL 50, Listed enclosure cul per Canadian Standards C22.2, No. 0-M91-CAN/
More informationSoftstarters Type PSS. Softstarters. General information
General information The PSS Softstarter line brings a wide array of benefits for smaller motors in a flexible, compact form. The PSS "Flexible" Softstarter line PSS18/30 to PSS300/515 softstarters provide
More informationThe Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller
The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller A pre-engineered solution with an integrated circuit breaker disconnect and an Altistart 22 soft start in a stand-alone enclosure Make the
More informationPerfectSpeed NEMA 48 Pump Motor. With User Interface
PerfectSpeed NEMA 48 Pump Motor With User Interface Table of Contents Section 1 - PerfectSpeed Motor... 1 Important Safety Information...1 Overview...3 PerfectSpeed User Interface Box...4 Minimum and Maximum
More informationLow-Peak 600V Class RK1
LPS-RK 600Vac/300Vdc, 1 10-60A, Dual Element, Time-Delay Fuses Dimensions - in 5" (± 0.31) 5.5" (± 0.31) Available with easyid open fuse indication 1/10 to 30A 0.81" (±0.008) 35 to 60A 1.06" (±0.008) Description:
More informationMotor Starters. Reduced Voltage. Reduced Voltage Motor Starters 1. Contents
1 January 00 Reduced Voltage Motor Starters Contents Description Page Open Type S7, Intelligent Technologies (IT.) Soft Starters Product Description............................................. Application
More informationFusetron FRN-R Class RK5 250Vac/125Vdc A, dual element, time-delay fuses
Technical Data1019 Supersedes July 2013 Fusetron FRN-R Class RK5 250Vac/125Vdc Catalog symbols: FRN-R-_ (non-indicating) FRN-R-_ID (indicating) Description: Eaton Bussmann series advanced protection, energy
More informationRVS-AX Instruction Manual
RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3
More informationElectrical Design/Build Guide
2017 Electrical Design/Build Guide Based on the 2017 National Electrical Code Copyright Durand & Associates 1986-2016 60 C Copper Ampacity 4 - Wire Fill - (Non-Current Carrying Neutral) 4 or 5 - Parallel
More informationAxpert-CSS AMTECH DRIVES Axpert-CSS Amtech
The Axpert-CSS is a range of Combination Soft Starter panels offered by AMTECH DRIVES. We also offer the module unit as an individual product, named as Axpert-Opti torque Soft Starter. This is only the
More informationNon-fusible. Non-fusible disconnect switches 16A 3150A, 600VAC A, 1000VDC. International acceptance. Disconnect switches.
disconnect 16A 31A, 0VAC 200-0A, 1000VDC Disconnect Disconnect ABB SwitchLine includes 16 different amperage sizes from 16A to 31A. The basic construction provides flexibility, safety, and high performance
More informationMotors " GRUNDFOS GROUNDWATER SERVICE MANUAL CONTENTS. Grundfos Motor Specifications... Page 2
GRUNDFOS GROUNDWATER SERVICE MANUAL Motors 4-6-8-10" CONTENTS Grundfos Motor Specifications... Page 2 Electrical Requirements... Page 8 -Transformer Capacity Maximum Motor Cable Length... Page 10 Full
More informationTypes of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:
Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor.
More informationOverload Relay Heater Tables
Overload Relay Tables of Elements for Overload Relays General Use only when motor full load current is not known. Motor amps will vary depending on the type and manufacturer of the motor. These average
More information2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4
CHAPTER ELECTRICAL 2 INSTALLATION Contents of this Chapter... 2.1 Warnings & Agency Approvals..................2 2 2.1.1 Isolation..............................................2 2 2.1.2 Electrical Power
More informationSingle-Phase Step Voltage Regulators
Voltage Regulators Catalog Data CA225001EN Supersedes March 2017 COOPER POWER SERIES Single-Phase Step Voltage Regulators Contents GENERAL....2 STANDARD FEATURES....4 OPTIONAL ACCESSORIES...4 ARRESTERS....4
More informationIndustrial and Commercial Duty IEC Motors
Industrial and Commercial Duty IEC Motors A Regal Brand Five product families delivering a world of opportunity LEESON Passport Series IEC Motors. There s a world of opportunity right here at home. The
More informationSingle-phase pad-mounted step voltage regulator
Voltage Regulators Catalog Data CA225002EN Supersedes February 2015 COOPER POWER SERIES Single-phase pad-mounted step voltage regulator General Eaton's Cooper Power series single-phase pad-mounted voltage
More informationFRNR A 250V TD Class RK5 Dual Elem Fuse-Fusetron
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 FRNR400 400A 250V TD Class RK5 Dual Elem Fuse-Fusetron Catalog Number Manufacturer Description Weight per unit Product
More informationSIRIUS Soft Starters: Protection of motors and mechanics, reduced load on the mains SIRIUS. Answers for industry.
SIRIUS Soft Starters: Protection of motors and mechanics, reduced load on the mains SIRIUS Answers for industry. The Range at a Glance Overview of SIRIUS soft starters Standard applications SIRIUS 3RW03
More informationSingle-phase step voltage regulators
Voltage Regulators Catalog Data CA225001EN Supersedes 225-10 February 2014 COOPER POWER SERIES General Eaton's Cooper Power series VR-32 singlephase step voltage regulators are tap-changing autotransformers.
More informationSECTION MOTOR CONTROL
SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters
More informationECET 211 Electric Machines & Controls Lecture 2-3 (Part 3 of 3) Symbols and Drawing for Electric Motor Control Systems
ECET 211 Electric Machines & Controls Lecture 2-3 (Part 3 of 3) Symbols and Drawing for Electric Motor Control Systems Text Book: Chapter 2. Understanding Electrical Drawings, Electric Motors and Control
More informationPoles 3 Starter Size NEMA 3 NON ALUMINUM LINE TERMINAL, LOAD TERMINAL
3804 South Street 75964-763, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 H100R3C 3P 100A 600V F-Frame MC Protector Eaton Corp Catalog Number H100R3C Manufacturer Eaton Corp Description Motor Circuit
More informationRVS-DX Digital Reduced Voltage Motor Starter
RVS-DX Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3
More informationXFE. The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications
The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications The XFE Soft Starter range provides a combination of competitive prices, flexible
More informationDATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.
DATASHEET - DILMC9-10(24VDC) Technical data General Contactor, 3p+1N/O, 4kW/400V/AC3 Part no. DILMC9-10(24VDC) Catalog No. 277468 Eaton Catalog No. XTCEC009B10TD EL-Nummer 4110305 (Norway) Standards IEC/EN
More informationAutodesk Inc. CB (Circuit Breakers): Following series contents are added/updated. CR (Control Relays) Following series contents are added.
EATON Content Details: This document describes brief details about EATON content update released for customer use. Each category describes type & series that got updated with the patch. CB (Circuit Breakers):
More informationProduct Description. Application Description
-2 Solid-State Controllers Type TL, Torque Limiter August 6 Contents Description Page Torque Limiters............ -2 Soft Start Controllers........ -4 Soft Start Controllers with Auxiliary Contact.....
More informationMATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation
MATRIX FILTER SERIES D 600 Volts, 60HZ USER MANUAL PART NO. INSTR 026 REL. 080920 2008 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter is designed for harmonic mitigation
More informationEOEM panelboard and switchboard (OPS) Program
Instructional Leaflet IL02009EN EOEM panelboard and switchboard (OPS) Program OPS Program overview The OPS Program enables EOEMs to purchase panelboard/switchboard chassis, boxes, trims, molded-case circuit
More informationNumber 1 in efficiency
PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The easiest way of variable motor speed NEW Variation DE11 The new device category! The PowerXL DE1 Variable Speed Starter The
More informationa revolution in soft start motor control The future of soft start motor control at your fingertips
The future of soft start motor control at your fingertips As the original pioneers of soft start technology Fairford have been at the forefront of motor control innovation since the 1970 s. A major designer
More informationThe future of soft start motor control at your fingertips
Low Voltage Soft Starters a revolution in soft start motor control The future of soft start motor control at your fingertips a revolution in soft start motor control As the original pioneers of soft start
More informationSoft Starters and Energy Optimising Soft Starters Guide to contents - applicable to
Soft Starters and Energy Optimising Soft Starters Guide to contents - applicable to 5MC software V56 Basic Guide to the Installation and Operation Of the Soft Starter 1 Mechanical Outlines Referring to
More informationDrive, Fuse & Circuit Breaker Ratings
Fuses 1, Fuse & Breaker s The tables on the following pages provide drive ratings (including continuous, 1 minute and 3 second) and recommended AC line input fuse and circuit breaker information. Both
More informationSOLSTART Instruction Manual
Solstart Analog Soft Starter 8-58A, 220-600V Instruction Manual Ver. 23/03/2009 2 Table of Content SOLSTART Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3
More informationInstructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers
Instruction Leaflet IL0330300E Supersedes I.L. 7055C, Pages 8, Dated June 998 Instructions for A00, A0, A50 size 6, two- or three-pole non-reversing or reversing motor controllers Contents Description
More informationACCESS Always replace the cover panel on the unit after gaining access to the electrical connections.
F A I R F O R D E L E C T R O N I C S Soft Starters and Energy Optimising Soft Starters Guide to contents - applicable to Basic Guide to the Installation and Operation Of the Soft Starter 5MC software
More informationCENTERLINE 2100 Motor Control Centers
TECHNICAL DATA CENTERLINE 2 Motor Control Centers Instantaneous Trip Motor Circuit Protectors (MCP) in Combination NEMA Starter, Soft Starter (SMC) and Variable Frequency AC Drive Units 1A Frame Instantaneous
More informationManual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X
Manual motor protectors Type MS116 Type MS32 Type MS4X Type MS49X Manual motor protectors Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL Listed and CSA certifi ed for
More informationProduct index. 4 - Manual motor protectors. Phone: Fax: Web: -
Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type
More informationLPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse
LPSRK100SP 600V TD Dual Elem Class RK1 Low Peak Fuse Catalog Number Manufacturer Description Weight per unit Product Category LPSRK100SP 600V Class RK1 Low Peak Dual Element, Time Delay Fuse 0.4100 (lbs/each)
More informationMotor Protection. Presented By. Scott Peele PE
Motor Protection Presented By Scott Peele PE Motor Protection Overload on the motor load Fuses Heater Magnetic relay Short Circuit on motor circuit Fuses Breakers Single Phasing Overload Protection NEC
More information201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE
201 S. Anaheim Blvd. Page No. 3.2.1 A. GENERAL 1. The character of electric service available at any particular location should be ascertained by inquiry at the City's Electrical Engineering Division office.
More informationa revolution in soft start motor control The future of soft start motor control at your fingertips
The future of soft start motor control at your fingertips As the original pioneers of soft start technology Fairford have been at the forefront of motor control innovation since the 1970 s. A major designer
More informationAF09... AF30 3-pole Contactors up to 20 HP / 480 VAC
AF0... AF0 -pole Contactors up to 20 HP / 480 VAC Contactors and Overload Relays Overview...2 AF0... AF0 -pole Contactors Ordering Details...4 Main Technical Data...20 DC Circuit switching...2 Main Accessory
More informationECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits
ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Paul I-Hai Lin, Professor
More informationMotor Starters. Reduced Voltage. Reduced Voltage Motor Starters Contents
June 5 Vol. 2, Ref. No. [067] -1 Reduced Voltage Motor Starters Contents Description Page Solid-State Controllers Type S701, Soft Start.......................................... -2 Type TL, Torque Limiter........................................
More informationTechnical data OT16E3 OT160E3 UL & CSA
Technical data OT16E3 OT16E3 UL & CSA UL & CSA Catalog number 3 pole OT16E3 OT25E3 OT32E3 OT45E3 OT63E3 OT3E3 OT6E3 OT1E3 OT16E3 Approvals 1 2 pole N/A N/A N/A N/A N/A N/A N/A N/A UL98 & EC 3 pole UL58
More informationEngine Generator Circuit Breakers
Engine Generator Circuit Breakers Product Description............................................. 2 Application Description........................................... 2 Standards and Certifications......................................
More informationDISTRIBUTION EQUIPMENT: NEC/CEC HAZARDOUS LOCATION SWITCHES. Application
- and 3-Pole, Non-Interchangeable Trip. Bolted Enclosure Type. Class I, Division 1 and, Groups B, C, D Class II, Division 1 and, Groups E, F, G Application Explosionproof circuit breaker enclosures are
More informationProduct index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.
Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type
More informationECET Circuit Design Motor Loads. Branch Circuits. Article 210
ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Circuit Design Motor Loads Branch Circuits Article 210 210.1 Scope This article covers branch circuits except for those that supply
More informationNumber 1 in efficiency
PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The new device category! The PowerXL DE1 Variable Speed Starter The PowerXL DE1 Variable Speed Starter one device, all the advantages
More informationGuide to contents - applicable to
FAIRFORD ELECTRONICS Basic Guide to the Installation and Operation Of the QFE Soft Starter Guide to contents - applicable to 5MC software V55 Mechanical Outlines Referring to the appropriate size of QFE,
More informationMotor Protection. Voltage Unbalance & Single-Phasing
For Summary of Suggestions to Protect Three-Phase Motors Against Single-Phasing see the end of this section, page 137. Historically, the causes of motor failure can be attributed to: Overloads 30% Contaminants
More informationLow-Peak LPJ Class J 600Vac/300Vdc, 1-60A, dual element, time-delay fuses
Technical Data 6 Supersedes August 2015 Low-Peak LPJ Class J 600Vac/Vdc, 1-60A, Catalog symbol: LPJ-(amp)SP (non-indicating) LPJ-(amp)SPI (indicating) Description: Bussmann series Ultimate protection LPJ
More informationSoftstarters. Softstarters Type SSM Medium voltage ,800V 1
Medium voltage 2300 13,800V 1 Description Fused disconnect switch with blown fuse indicators and door safety interlocks rated for load break/fault make with automatic grounding arm Inline isolation vacuum
More informationProtectors. 35mm DIN rail snap-on mounting. Wide range of accessories
Manual motor protectors Manual motor protectors Manual motor Protectors MS116 MS32 MS4X MS49X Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL Listed and CSA certified
More informationThe Z Series. SCR Power controllers for resistance heating applications. Zero-Fired SCR Power Controllers AMPS VAC
The Z Series Zero-Fired SCR Power Controllers 60-1200 AMPS 120-600 VAC SCR Power controllers for resistance heating applications. ROBICON 1996 Rev. 7/96 Applications Robicon s Z series power controls are
More informationSIRIUS Soft Starters Introduction
Introduction Overview Products at a glance 3RW30/3RW31 3RW40 3RW44 Class 73/74 Enclosed 16 CONTROL SIRIUS soft starters for standard applications SIRIUS 3RW30 soft starters SIRIUS 3RW40 soft starters for
More informationPRODUCT DRAWING WIRING DIAGRAM FIELD CONNECTIONS MILLENNIUM MODEL YT CHILLERS (STYLE J) WITH ELECTRO-MECHANICAL STARTER JOB DATA:
Supersedes: 160.55-PW4 (1199) FORM 160.55-PW4 (600) PRODUCT DRAWING YORK INTERNATIONAL CORPORATION P.O. Box 1592, YORK, PA 17405 CONTRACTOR ORDER NO. YORK CONTRACT NO. YORK ORDER NO. WIRING DIAGRAM FIELD
More informationFile E31519 Project 10CA February 4, 2011 REPORT MAGNETIC MOTOR CONTROLLERS. Siemens AG Amberg, Germany
File E31519 Project 10CA65262 February 4, 2011 REPORT on MAGNETIC MOTOR CONTROLLERS Siemens AG Amberg, Germany Copyright 2011 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the
More informationInstructions for Type W Three Phase, Standalone Overload Relays, Size 1 through 6
Revision D Instructions for Type W Three Phase, Standalone Overload Relays, Size 1 through 6 Size 2 Size 3 Fig. 1 Type W Standalone Overload Relays Size 5 THE OVERLOAD RELAYS Advantage Type W three phase,
More information3RW Soft Starters. General data. 6/2 Siemens LV 1 N SIRIUS Soft Starters 01/2008. Siemens AG 2008
Siemens AG 2008 General data The advantages of the SIRIUS soft starters at a glance: Soft starting and smooth ramp-down 1) Stepless starting Reduction of current peaks Avoidance of mains voltage fluctuations
More informationEnclosed Full-Voltage Starters
GE Energy Connections Made in USA Enclosed Full-Voltage Starters * www.geindustrial.com/products/starters GE Global Offer & Warranty starters utilize globally-rated IEC components which make it ideal for
More informationMATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL REV MTE Corporation
MATRIX FILTER SERIES D 600 Volts, 60HZ USER MANUAL PART NO. INSTR 026 REL. 120628 REV. 007 2012 MTE Corporation Matrix Series D User s Manual 600VAC IMPORTANT USER INFORMATION NOTICE The MTE Corporation
More informationVariable Frequency Drive Basics
Variable Frequency Drive Basics Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Variable Frequency Drives are
More informationFeatures and Benefits
-52 August 2006 Contents Page Type MV801, Intelligent Technologies (IT.) Medium Voltage Soft Starters Operation.............. -53 Selection.............. -55 Product Selection........ -56 Options................
More informationMATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation
MATRIX FILTER SERIES D 480 Volts, 60HZ USER MANUAL PART NO. INSTR 024 REL. 120628 REV. 012 2012 MTE Corporation Matrix Series D User s Manual 480VAC IMPORTANT USER INFORMATION NOTICE The MTE Corporation
More informationEnclosed Full-Voltage Starters
GE Energy Connections Made in Canada Enclosed Full-Voltage Starters * ca.geindustrial.com/products/starters GE Global Offer & Warranty starters utilize globally-rated IEC components which make it ideal
More informationSeries C, F-frame molded case circuit breaker, 15A, Two-pole, Thermal Magnetic Trip, FD Breaker
FD2015 2 Pole 15A FD Eaton Corp Catalog Number Manufacturer Description Weight per unit Product Category Features amperage rating 15 Frame Size F-frame interrupt rating 35 kaic at 480V Poles 2 Trip Type
More informationAF09... AF30 3-pole Contactors up to 25 HP / 600 VAC
AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24
More informationDRAFT 1400HP 1000HP 100HP. Reduced Voltage Solid State Starters. Softstarters SOFT. PF Controller PCS Controller PDS Controller V 1...
100HP 400HP 700HP 1000HP 1400HP PCS Softstarter Controller IN-rail mountable microprocessor controller for 3-phase motors up to 480A (3...85A din-rail mountable) Provides three different starting modes
More informationPanorama. Softstarters The complete range
Panorama Softstarters The complete range Why does soft starting matter? Controlling industrial electricity. The vast majority of the world s industrial applications are driven by motors. It is estimated
More informationContents. MCD 200 Design Guide. Contents
Contents Warnings... 2 MCD 200 Series Overview Description... 3 Ratings... 4 General Technical Data... 5 Mechanical Installation... 7 Dimensions and Weights... 7 Cable Size... 9 Semiconductor Fuses...
More informationShort form catalogue. Motor protection & control
Short form catalogue Star Series Motor protection & control Motor Protection and Control up to 25 HP / 600 VAC Overview...2 Contactors and Overload Relays...11 4-pole Contactors...41 Control Relays...59
More informationSeries C, F-frame molded case circuit breaker, 125A, Three-pole, Thermal magnetic trip. Thermal magnetic
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 HFD3125 HFD3125 125A 3P CKT BRKR Eaton Corp Catalog Number Manufacturer Description Weight per unit Product Category Features
More informationDry Type Distribution Transformers
Selection Steps A. Use the following steps below to manually select a transformer. B. Find the electrical load requirements. These are: 1. Load operating voltage. 2. Load frequency (expressed in Hz). 3.
More informationSecondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor
Reducing Arc Flash Energies on Transformer Secondaries arc flash note 6 By Mike Lang, principal field engineer and Dave Komm, Technical Services Supervisor 1. Introduction Arc flash incident energy calculations
More informationWARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.
SECTION 230513 - MOTORS AND ADJUSTABLE SPEED DRIVES PART 1 - GENERAL 1.1 DESCRIPTION A. Provide labor, materials, equipment and services as required for the complete installation designed in Contract Documents.
More informationWastewater Solutions. DECONTACTOR TM Series. Featuring Meltric s. Switch Rated Plugs, Receptacles and Electrical Connectors
Wastewater Solutions Featuring Meltric s DECONTACTOR TM Series Switch Rated Plugs, Receptacles and Electrical Connectors Meltric DECONTACTOR TM Series Plugs & Receptacles Decontactors are a combination
More informationCT430 - Soft Starters on Motor Applications
CT430 - Soft Starters on Motor Applications Bill Bernhardt Sr. Commercial Engineer May 16, 2018 PUBLIC Copyright 2018 Rockwell Automation, Inc. All Rights Reserved. 1 Topics Traditional Motor Starting
More informationECET 211 Electric Machines & Controls Lecture 5-4 Electric Motors. Lecture 5-4 Electric Motors
ECET 211 Electric Machines & Controls Lecture 5-4 Electric Motors (4 of 4) Text Book: Chapter 5 Electric Motors, Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015.
More information