Low Voltage Apparatus. Technical Brochure. FuseLine HRC Fuse Links OFAA, OFAM. Brochure OF 1 GB ABB Control Oy
|
|
- Hilda Ramsey
- 5 years ago
- Views:
Transcription
1 Technical Brochure Low Voltage Apparatus FuseLine HRC Fuse Links OFAA, OFAM Brochure OF GB ABB Control Oy
2 95MDN5447 HRC Fuse-Links OFAA and OFAM OFAA gg Fuse-Links for Overload and Short-Circuit Protection OFAA fuse-links are designed to meet all the requirements of the modern industrial installations and electrical power plants. Their breaking capacity is sufficient even at the highest shortcircuit levels. The breaking capacity of OFAA fuses is over ka, when service voltage is the same as rated voltage and frequency is 50 Hz. This is valid for all fuse sizes. Strömberg OFAA 00 5A Strömberg Strömberg OFAA 50A OFAA 400A Strömberg OFAA 3 630A S00346A O OFAM am Fuses for Short-Circuit Protection in Motor Circuits M ~ OFAM am fuse links provide reliable and fast short-circuit protection for motor circuit equipment and cables. Breaking capacity is ka. Overload protection for motor circuit is provided with an overload relay and a contactor. At high overload currents, the am fuse link is faster than the gg fuse link, and at motor starting currents, the am fuse link is slower than the gg fuse link. OFAM am fuse link is now available even in IEC size 00. Rated voltage is V for all fuse sizes. OFAM 00/aM 60A OFAM /am 50A OFAM /am 400A OFAM 3/aM 630A S00347A O How a Fuse-Link Limits Current To prevent danger, and damage to equipment and circuits, short circuit currents need to be intercepted extremely quickly. It is generally the quick temperature rise generated within the short circuit current that causes equipment to breakdown. Fuse links are designed to react to this temperature rise and, therefore, their current limiting capability is very good. Fuse links contain granulated quartz which binds the temperature generated in the arc created by short circuit. At the same time the pressure rises inside the fuse link and the fusing element ruptures. Ceramic cylinder Granulated quartz Fusing element Prospective short circuit current S00398A arc current I ^ i c ^ i s t s t t t v ^ i s = 44kA ^ i c = ka t I t pre-arc I t total 0 0 t s t t I dt I dt t s tv tt ^ i c = melting time of fusing element = arc time = total operation time = current peak value limited by the fuse Construction of the fuse link. ABB Control Oy
3 Fuse Protection - Easy and Reliable Superior Current Limiting Capability Fuse links have an excellent current limiting capability. With standard cable and apparatus dimensions the protection is assured for contactors and overload relays. Short-circuit capacity remains very small. High Safety Factor Visual inspection of a circuit clearly reveals when a fuse link has been removed. Thus, service and maintenance can be safely carried out. Fuses are tested according to IEC 947 standard requirements. IEC 947 type coordination withstands up to V. Type coordination states that all apparatus in the circuit must be in full operation after short circuit. Fuse protection guarantees this without over dimensioning the apparatus. Economical Installation Life time costs of fuse systems are low. Fuse links which can withstand a high fault level and fault current are available at economical prices. After tripping, only the fuse-link has to be changed. Because the fuse links can be rapidly and easily replaced, plant down-time and maintenance is substantially reduced with a fuse link system. Simple Selectivity Fuse links provide a simple procedure for selecting the right fuse type for your installation, without complicated calculations. Fuses prevent "blackouts". Only the fuse nearest a fault trips without upstream fuses (feeders or mains) beeing affected. Fuses thus provide selective coordination. The selectivity, see the pictures below and on previous page: On the feeder side the I t pre-arc value (in the picture fuse size 60 A) has to be bigger than I t total on the load side(in the picture fuse size A). I t-values are on page for OFAA- fuses and on page 5 for OFAM- fuses. S0035A Reliable visible isolation when the fuse link is removed. Fuse M Time S00354A Time Perfect selectivity for all currents 63 A 63A A 60A S0035A Current Fuses: Selectivity between sequential fuse links easily achieved. Breaker Selectivity up to the magnetic trip level of supply side circuit breaker only. Selective Non-selective Thermal trip level Magnetic trip level Intentional trip delay S00355A S00353A M 0x60 A Current Magnetic trip level setting e.g. 0 x 60 A =,6 ka U = V N Breaker: Selectivity condition for MCCB has to be separately calculated. 60A I I S00356A A S00357A A 60A t s t vk Example of selectivity ABB Control Oy 3
4 Fuses Are Key Components to Reliable Protection A reliable protection is costeffectively achieved with fuse links Relative advantage Acc. to IEC standard regarding motor starters, certain coordination categories are defined to protection. Coordination type allows damage to contactor and thermal overload relay after a short-circuit. Operator must inspect starter afterwards and change the apparatus. Failure to do this means the circuit is not protected against overload which can lead to motor damage and cable fire. Circuit breaker Fuse Coordination type guarantees that the starter is in full operation after short-circuit. S00350A The fuse-links are protected acc. to coordination type category even at V. With breakers, to achieve coordination type, problems arise particularly at higher voltages. Generally can be said that at higher voltages, the fuse system is stronger. Low Type Short circuit level Selectivity level Current Voltage Coordination High Type Fuses provide a reliable protection. Fuse-Link Operates Independently of Corrosion Operation time Because the fusing elements operate in a cylinder, they are not affected by their surroundings. Thus their protecting characteristics remain unchanged year after year. Rated current Unlike circuit breakers, corrosion of a motor cannot damage the inside of the fuse link. Fuse The breaking capacity of the contactor Fuse links are designed for different environments: Universal fuses for installations under normal conditions. Fuse links for harsher environments, industrial fuses, provided with an extra thick silver coating (0 µm). S00399A Thermal overload relay Starting current of a motor A Damaging area of thermal relay Welding area of the contactor contacts 0 6 Current I / In Contactor, thermal overload relay and fuse in a motor circuit. With the fuses the short circuit protection of coordination type can be easily ensured without over-dimensioning the components. 4 ABB Control Oy
5 HRC Fuse links Types OFAA, OFAM Contents: HRC Fuse link, type OFAA Ordering information... 6 OFAA -fuses, time-current characteristics... 7 OFAA -fuses, current limitation... 8 OFAA -fuses, I t -values... 0 Dimension drawings... HRC Fuse link, type OFAM M ~ Ordering information... OFAM -fuses, time-current characteristics... 3 OFAM -fuses, current limitation... 4 OFAM -fuses, I t -values... 5 Dimension drawings... 6 ABB Control Oy 5
6 Fuse links, type OFAA Ordering information S00406A S00407A S00405A S00404A Strömberg OFAA 00 5A Strömberg OFAA 50A Strömberg OFAA 400A Strömberg OFAA 3 630A Fuse links OFAA, universal fuses Type code includes one fuse link, but the delivery batch is 3 pieces/package. Type OFAA 00 H OFAA 00 H4 OFAA 00 H6 OFAA 00 H0 OFAA 00 H6 OFAA 00 H0 OFAA 00 H5 OFAA 00 H3 OFAA 00 H35 OFAA 00 H40 OFAA 00 H50 OFAA 00 H63 OFAA 00 H80 OFAA 00 H OFAA 00 H5 OFAA H6 OFAA H0 OFAA H5 OFAA H3 OFAA H35 OFAA H40 OFAA H50 OFAA H63 OFAA H80 OFAA H OFAA H5 OFAA H60 OFAA H00 OFAA H50 OFAA H60 OFAA H00 OFAA H50 OFAA H35 OFAA H400 OFAA 3 H35 OFAA 3 H400 OFAA 3 H OFAA 3 H630 OFAA 00 H-H0 OFAA 00 H4-H0 OFAA 00 H6-H0 OFAA 00 H0-H0 OFAA 00 H6-H0 OFAA 00 H0-H0 OFAA 00 H5-H0 OFAA 00 H3-H0 OFAA 00 H35-H0 OFAA 00 H40-H0 OFAA 00 H50-H0 OFAA 00 H63-H0 OFAA 00 H80-H0 OFAA 00 H-H0 OFAA 00 H5-H0 OFAA H6-H0 OFAA H0-H0 OFAA H5-H0 OFAA H3-H0 OFAA H35-H0 OFAA H40-H0 OFAA H50-H0 OFAA H63-H0 OFAA H80-H0 OFAA H-H0 OFAA H5-H0 OFAA H60-H0 OFAA H00-H0 OFAA H50-H0 OFAA H60-H0 OFAA H00-H0 OFAA H50-H0 OFAA H35-H0 OFAA H400-H0 OFAA 3 H35-H0 OFAA 3 H400-H0 OFAA 3 H-H0 OFAA 3 H630-H0 IEC -size I n [A] U n [V] Fuse links OFAA, industrial fuses Industrial fuses with 0 µm silver coating. Type code includes one fuse link, but the delivery batch is 3 pieces/package. P h [W] Weight [kg] 6 ABB Control Oy
7 OFAA -fuses, melting times FuseLine Fuse links, type OFAA Melting times Values are valid also for industrial fuses OFAA_-H0. S0036A Melting time t v / s Short circuit current I p / A ABB Control Oy 7
8 Fuse links, type OFAA Current limitation OFAA 00 -fuses, current limitation (cut-off characteristic) Values are valid also for industrial fuses OFAA_-H0. Current peak without the fuse =.4 x x I p S00363A Maximum value of current, peak value I s / ka Prospective current I p / ka 8 ABB Control Oy
9 Fuse links, type OFAA Current limitation OFAA -fuses, current limitation (cut-off characteristics) Values are valid also for industrial fuses OFAA_-H0. Current peak without the fuse =.4 x x I p S00365A Maximum value of current, peak value I s / ka Prospective current I p / ka ABB Control Oy 9
10 Fuse links, type OFAA OFAA -fuses, Current limitation OFAA och 3 -fuses, current limitation (cut-off characteristics) Values are valid also for industrial fuses OFAA_-H0. Peak current without the fuse =.4 x x I p S00360A Maximum value of current, peak value I s / ka Prospective current I p / ka 0 ABB Control Oy
11 Fuse links, type OFAA I t -values, Dimension drawings I t -values OFAA 00H 5, _ H 50, _H 400 and _3H 630 for voltage V, other types for voltage V. Values are valid also for industrial fuses OFAA_-H0. I t / A s Total-I kokonais-i t t Melting-I sulamis- I t t Selektiivinen Selectivity B > A + B S004A A B B 0 Fuse, Sulaketyyppi type OFAA OFAA 00H4 00H6 00H0 00 and H6 00 and H0 00 and H5 00 and H3 00 and H40 00 and H50 00 and H63 00 and H80 00 and H 00 H5 H5 and H60 and H00 H50 H50 and 3H35 H400 3H400 3H 3H630 S0048A OFAA -fuses, dimension drawings Values are valid also for industrial fuses OFAA_-H0. e e d f a d f a OFAA 00 H g c S0046A b OFAA H OFAA H OFAA 3 H Type Laji a b c d e f g g c OFAA00H OFAAH OFAAH OFAA3H b ABB Control Oy
12 Fuse links, type OFAM Ordering information Fuse links OFAM, universal fuses Type code includes one fuse link, but the delivery batch is 3 pieces/package. Typ IEC -storlek I n [A] U n [V] P h [W] Weight [kg] M ~ S00409A S00408A OFAM 00 60A OFAM 50A OFAM 00 am 6 OFAM 00 am 0 OFAM 00 am 5 OFAM 00 am 3 OFAM 00 am 40 OFAM 00 am 50 OFAM 00 am 63 OFAM 00 am 80 OFAM 00 am OFAM 00 am 5 OFAM 00 am 60 OFAM am 50 OFAM am 63 OFAM am 80 OFAM am OFAM am 5 OFAM am 60 OFAM am 00 OFAM am 50 OFAM am 5 OFAM am 60 OFAM am 00 OFAM am 50 OFAM am 35 OFAM am 355 OFAM am 400 OFAM 3 am 35 OFAM 3 am 355 OFAM 3 am 400 OFAM 3 am OFAM 3 am S004A S0040A OFAM 400A OFAM 3 630A Fuse links OFAM, industrial fuses Industrial fuses with 0 µm silver coating. Type code includes one fuse link, but the delivery batch is 3 pieces/package. OFAM 00 am 6-H0 OFAM 00 am 0-H0 OFAM 00 am 5-H0 OFAM 00 am 3-H0 OFAM 00 am 40-H0 OFAM 00 am 50-H0 OFAM 00 am 63-H0 OFAM 00 am 80-H0 OFAM 00 am -H0 OFAM 00 am 5-H0 OFAM 00 am 60-H0 OFAM am 50-H0 OFAM am 63-H0 OFAM am 80-H0 OFAM am -H0 OFAM am 5-H0 OFAM am 60-H0 OFAM am 00-H0 OFAM am 50-H0 OFAM am 5-H0 OFAM am 60-H0 OFAM am 00-H0 OFAM am 50-H0 OFAM am 35-H0 OFAM am 355-H0 OFAM am 400-H0 OFAM 3 am 35-H0 OFAM 3 am 355-H0 OFAM 3 am 400-H0 OFAM 3 am -H0 OFAM 3 am 630-H ABB Control Oy
13 Fuse links, type OFAM Melting times OFAM -fuses, melting times Values are valid also for industrial fuses OFAM_-H0. M ~ S00364A Melting time t v / s Short circuit current I p / A ABB Control Oy 3
14 Fuse links, type OFAM Current limitation OFAM -fuses, current limitation (cut-off characteristics) Values are valid also for indusatrial fuses OFAM_-H0. M ~ Current peak without the fuse =.4 x x I p S0036A Maximum value of current, peak value I s / ka Prospective current I p / ka 4 ABB Control Oy
15 Fuse links, type OFAM I t -values I t -values Values are valid also for indusatrial fuses OFAM_-H0. I t / A s Total-I kokonais-i t, Vt, V Total-I kokonais- t, I V t, V Total-I kokonais- t, 400 I Vt, 400V Melting-I sulamis- t I t, 400V M ~ 0 I t / A s aM6 00aM0 00aM5 00aM3 00aM40 00aM50 00aM63 00aM80 00aM 00aM5 00aM60 Total-I kokonais-i t, Vt, V Melting-I sulamis- t I t, 400V Fuse, Sulaketyyppi type OFAM OFAM S0049A Selektiivinen Selectivity B > A + B S004A A B B Sulaketyyppi Fuse, type OFAM OFAM am50 am63 am80 am am5 am60 am00 am50 am5 am60 am00 am50 am35 am355 am400 3aM35 3aM355 3aM400 3aM 3aM630 S0040A ABB Control Oy 5
16 Fuse links, type OFAM Dimension drawings Dimension drawings Values are valid also for indusatrial fuses OFAM_-H0. e e d f a OFAM 00 d f a S0047A b g c OFAM OFAM OFAM 3 Type Laji a b c d e f g g c OFAM00aM OFAM00aM...60 OFAMaM OFAMaM OFAM3aM b ABB Control Oy P.O.Box 6 FIN VAASA Finland Telephone Telefax The technical data and dimensions are valid at the time of printing. We reserve the right to subsequent alterations. Waasa Graphics Oy, 3/996
FUSE: SAFE & RELIABLE
FUSE: SAFE & RELIABLE VS. CIRCUIT BREAKER Tech Topics: Selective Coordination Note 2, Issue 1 Franck Charlier Technical Support Engineer Points of interest: Power fuse needs no repair only to be replaced
More informationLow Voltage Products. HRC Fuse Links OFAFN_ and OFFN_ DIN and BS types, gg 500V 630A OFAFN 3. >80kA. 2 / gg MADE IN ABB
Low Voltage Products HRC Fuse Links OFAFN_ and OFFN_ DIN and BS types, gg OFFNC 2 OFAFN 3 3/gG Fuse protection - safe an 2A...1250 A, 500 V DIN-Type HRC fuse links (blade-type), 2A. DIN-size I n [A] S01350A
More informationProtectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.
Types MS116, MS132, MS5x, MS9x are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/OFF control, and protection against short circuit,
More informationApplications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders
Applications HV HRC (high-voltage high rupturing capacity) fuses are used for short circuit protection in high-voltage switchgear for the 50 to 60 Hz frequency range Distribution transformers up to 2000
More informationPower systems Protection course
Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used
More informationPowerLine OS Switch Fuses A, 690V
Technical Brochure PowerLine OS Switch Fuses 20...160 A, 690V Brochure OS 10 GB 99-04 9902CD04 ABB Control New Switch Fuse Range 2 3 Total user safety Total user safety Fuse carriers fully IP20 protected
More informationElectrical Protection
Electrical Protection Excessive current in any electrical circuit is hazardous and not desired, and these maybe caused by the following; 1. Overloads, and 2. Short-circuits. Overload Currents: These are
More informationProduct brochure. ABB Fusegear EasyLine Fuse switch disconnector
Product brochure ABB Fusegear EasyLine Fuse switch disconnector 2 EasyLine Fuse Switch Disconnector ABB Fusegear Content Fuse protection 4 Technical Data 5 General 6 Apparatus overview 7 Electronic Fuse
More informationFuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A
DISTRIBUTION SOLUTIONS Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A Superior performance versus standard fuses ensuring up to 40% faster protection in case of low
More informationMotor Starting Solutions Open Type Version, in Kit Form
Motor Starting Solutions Open Version, in Kit Form Starters Protected by Manual Motor Starters Direct-On-Line Starters I> Reversing Starters I> MS... Manual motor starter MS... Manual motor starter BEA...
More informationMiniature circuit breaker Application guide
Miniature circuit breaker Application guide Miniature Miniature circuit circuit breakers breakers Application S200 guide Introduction The circuit breaker plays an important role in providing over-current
More informationFuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A
DISTRIBUTION SOLUTIONS Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A Efficient protection of voltage transformer circuits Extending the lifetime of installed electrical
More informationTechnical Brochure. Switch Fuses DIN and NFC-Standard. Selection Table. Brochure OESA 2DIN GB Mallipohja. Low Voltage Products
Technical Brochure Switch Fuses DN and NFC-Standard Selection Table Brochure ESA 2DN GB 99-12 Mallipohja Powerline S switch fuses 20...160A, 690 V Unique patented design for the 21st century Total user
More informationCatalogue March InLine II - ZLBM/ZHBM Fuse Switch Disconnector
Catalogue March 2015 InLine II - ZLBM/ZHBM Fuse Switch Disconnector 2 1SEC312022B0202 ABB Catalogue Contents Introduction 1 Apparatus 2 Accessories 3 Technical Data 4 Cable terminations and cable shrouds
More informationMedium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A
DISTRIBUTION SOLUTIONS Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A Continuous protection and reliable operation Proven design and compliance with newest fuses standards Compatibility with other ABB
More informationFUSERBLOC CD. The universal Fuse Combination Switch FROM 20 TO 1250 A. Industrial Switching & Protection Systems
FUSERBLOC CD The universal Fuse Combination Switch FROM 20 TO 1250 A SOCOMEC GROUP SWITCHING PROTECTION & UPS Industrial Switching & Protection Systems SWITCHING FUSERBLOC CD THE UNIVERSAL FUSE COMBINATION
More informationSentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification
543 technical hotline +44 ()1268 56372 Standards and approvals Sentry MCBs are designed to fully comply with the relevant requirements of BS EN 6898: 23. They all feature positive contact status indication
More informationShort-circuit current limiter S800-SCL-SR
Short-circuit current limiter S800-SCL-SR 2 ABB Short-circuit current limiter S800-SCL-SR Self-resetting current limiting module S800-SCL-SR is ABB s innovative self-resetting current limiting module which
More informationDX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data
Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC
More informationHHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction.
HHD High Voltage Fuses German DIN Standard For Air & Gas Insulated Switchgear Indoor and Outdoor Application The striker pin system is connected by means of a high resistance parallel conductor. After
More informationACS motor protection circuit breakers KT 7 Introduction
Introduction Automatic Type 2 coordination The right circuit breaker for all applications The KT 7 circuit breaker family consists of two basic frame sizes of mm and 5 mm in three variations with different
More informationData sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427
Data sheet CI-TI TM Contactors and Motor Starters Circuit Breakers November 2002 DKACT.PD.C00.L2.02 520B1427 Introduction Circuit breakers/manual motor starters cover the power ranges 0.09-12.5 kw This
More informationNEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY
NEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY WHAT IS SELECTIVITY? Selectivity in mean of protective devices is also called by other terms as discrimination or coordination of protective devices. To
More informationProtection and Connection Motorized and automatic transfer switches IEC Technical guide
Protection and Connection Motorized and automatic transfer switches IEC 61439 Technical guide Motorized change-over switches Uninterrupted power supply with motorized functionality ABB offers a wide variety
More informationAir-insulated switchgear UniGear type ZS1
Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5
More informationCharacteristics of LV circuit breakers Releases, tripping curves, and limitation
Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break
More informationMedium voltage products. Fuses
Medium voltage products Fuses Index Introduction... 3 Main definitions... 4 ABB HV Fuses with Temperature Control Unit... 5 General principles for fuse link selection... 6 CEF... 8 CEF-S... 16 CEF-VT...
More informationSelective main circuit breakers S 750 series Technical Data
Selective main circuit breakers S 750 series Technical Data When connecting aluminium conductors ( 4 mm 2 ) ensure that the contact surfaces of the conductors are cleaned, brushed and treated with grease.
More informationLow Voltage Products BaseLine, OFAX Fuse Bases
Low Voltage Products BaseLine, OFAX Fuse Bases Brochure OFA1GB 02_09 1SCC316001C0201 S00279A Fuse Bases OFAX 00, 1, 2, 3 and 4a The OFAX fuse bases are designed for fuse-links up to 1250 A, according to
More informationCascading & Discrimination
Cascading & Discrimination Typical LV System Level 1 ACBs - 6300A General LV Switchboard Level 2 ACB - 3200A MCCB 3200A Level 3 MCCB 1250A Fuses 630A Switchboard, Panelboard or MCC Level 4 MCBs - 100A
More informationMedium voltage products. Fuses
Medium voltage products Fuses Index Introduction... 3 Main definitions... 4 ABB HV Fuses with Temperature Control Unit... 5 General principles for fuse link selection... 6 CEF... 8 CEF-S... 16 CEF-VT...
More informationTechnical Information
-100 Controller IEC Performance Data (CSA C22.2, UL 508 No. 14 in connection with a short-circuit protection device Catalog No. -100... 25A 40A 63A 90A Maximum Short-Circuit Current 480V [ka] 65 65 42
More informationParamount HRC Cartridge
Paramount HRC Cartridge Eaton MEM HRC fuselinks are manufactured to exacting standards using precision assembly methods and undergo rigorous quality checking before dispatch including resistance testing
More informationFUSES. Safety through quality
Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced
More informationMOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.
MOLDED CASE CIRCUIT BREAKER BASICS David Castor, P.E. History of MCCBs 1904 - Cutter Manufacturing Co., Philadelphia, produces circuit breakers. They called it the Inverse Time Element breaker, or I-T-E
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly
More informationLow Voltage Products. ABB Building Technologies. PowerLine OS and OESA Switch Fuses. Brochure OS-OESA 1 GB 00-05
Low Voltage Products PowerLine S and ESA Switch Fuses Brochure S-ESA 1 GB 00-05 ABB Building Technologies < < Fuse Protection - Easy and Reliable Complete range of switch fuses 20A to 800A, 690V S 20...200
More informationLow Voltage Products. Enclosed switches. Brochure OT_KSE 1 GB 05_02 1SCC340007C0201
Low Voltage Products Enclosed switches Brochure OT_KSE 1 GB 05_02 O I N O SafeLine OF F 2 I Enclosed switches Contents: General... 4 Technical data... 5 Switches in plastic enclosure General... 6 Ordering
More informationDNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation
More informationELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH
HH DRIESCHER - High-voltage high breaking capacity fuses from 1 kv up to 36 kv HH HH ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-866 MOOSBURG TEL. +9 87 61 6 81-0 FAX +9 87 61 68 11 37 http://www.driescher.com
More informationFuses still the best form of overload protection
Fuses still the best form of overload protection 2001 George Moraitis (Fuseco Pty. Ltd.) Often when I visit people to talk about circuit protection I hear the comments fuses are a thing of the past and
More informationMAGNETIC MOTOR STARTERS
Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors
More informationMiniature Circuit-Breakers (MCBs)
Product Overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristics Rated current I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SQ2
More informationAdvanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR
Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR Assembly Short-Circuit Current Ratings What Is A Short-Circuit
More informationHigh voltage high-breaking capacity VV fuse-links
High fuse-links High fuse-links High high-breaking capacity VV fuse-links VV General information ET fuse-links named VV THERMO are designed to protect devices in switch-gears and other equipment (distribution
More informationElectronic overload relays EF205 and EF370
Data sheet Electronic overload relays EF205 and EF370 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
More informationThermal overload relay TF140DU and TF140DU-V1000
Data sheet Thermal overload relay TF140DU and TF140DU-V1000 Thermal overload relays are economic electromechanical protection devices for the main circuit. They are used mainly to protect motors against
More informationSelf-protected Combination Starters System PKZ 2-SP
Self-protected Combination Starters System PKZ 2-SP 03/035 PKZ 2/ZM/S-SP motor starters: a higher level of protection and versatility : The PKZ 2/ZM/S-SP is a self-protected starter, the first motor controller
More informationTechnical data. Miniature Circuit Breakers. System pro M. System pro M
Technical data System pro M System pro M 1 Prior to connection of aluminium conductors ensure that their contact points are cleaned, brushed and coated with grease. The contact terminals must be tighten
More informationSchool of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering
University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering ELEC 5205 - High Voltage Engineering 3. Switchgear Types of Power System Switchgear
More informationABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.
September, 1990 Supersedes Descriptive Bulletin 41-100, pages 1-4, dated June, 1989 Mailed to: E, D, C/41-100A Hi-Lo co induction-disc type overcurrent relays are activated when the current in them exceeds
More informationLow Voltage Apparatus. Technical Brochure. BaseLine. Fuse Bases OFAX, OFAS_ 690 V. Brochure OFA 1A GB 91-02/ 95-11/97-03.
Technical Brochure Low Voltage Apparatus BaseLine Fuse Bases OFAX, OFAS_ 690 V Brochure OFA 1A GB 91-02/ 95-11/97-03 ABB Control Oy S00279A Fuse Bases OFAX 00, 1, 2 and OFAS_3 Standards: IEC 269-2-1 IN
More informationCapacitor Switching Contactors Type K3...-A, K3...-K
Type K3...-A, K3...-K Features that matter: Patented design with significant damping on inrush-current Long-life contactors tested by FRAKO up to 100,000 switching operations Suitable for unchoked and
More informationSpecial Purpose Fuses
Special Purpose Fuses Multimeter fuses Metering Fuses Telecom fuses NH 80V Fuses for DC voltage applications NH am 00V a.c. NH gg 0V a.c. Safe work fuses SWF Fuses for protection of forklift batteries
More informationHHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction.
HHD HIGH VOLTAGE GERMAN DIN STANDARD FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS The striker pin system is connected by means of a high resistance parallel conductor. After melting the main
More informationNH fuse-links gg 400VAC double indicator/live gripping-lugs size 000, 00, 1, 2, 3
NH fuse-links gg 4VAC double indicator/live gripping-lugs size,, 1, 2, 3 NH fuse-links gg 4VAC double indicator/live gripping-lugs size,, 1, 2, 3 LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS
More informationLow Voltage Fuses For Motor Protection
Code Requirements The NEC or CEC requires that motor branch circuits be protected against overloads and short circuits. Overload protection may be provided by fuses, overload relays or motor thermal protectors.
More informationMedium Voltage current limiting Fuse links
Medium Voltage current limiting Fuse links Type PCEF for indoor and outdoor use Rated Voltage 12-24 kv Current Rating 6 200A 1. General information P&C Medium Voltage fuse-links named PCEF are designed
More informationPhase + Neutral, neutral on right side
87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34
More informationReliably Switching Highest Currents up to 2000 A
www.moeller.net Reliably Switching Highest Currents up to 2000 A The complete range for the motor circuit. From contactors to efficient motor-starters to controlled drives. New solutions that rely on communication.
More informationSimplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT
Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Are You Ready For The New SCCR Marking Requirements? What Is A Short-Circuit Current Rating (SCCR)? SCCRs on components
More informationMAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-
MKING MODERN LIVING POSSIBLE Technical brochure Minicontactors CI 5- www.danfoss.com 2 IC.PD.C10.F3.02-520B4167 Danfoss /S, C-SMC, mr, 07-2010 Contents Page Minicontactor CI 5- Introduction...............................................................................4
More informationHigh voltage current limiting Fuse links type CEF
High voltage current limiting Fuse links type CEF Index 1. General........................................... 9 2. Overvoltages...................................... 9 3. Pre-arcing times and cut-off characteristics..............
More informationNH fuse-links am 690VAC top indicator/live tags size 4, 4a
NH fuse-links am 69VAC LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS Dimensions according to DIN 43 62 parts 1 to 4 Non-isolated gripping lugs Double indicator Lead free contact blades %
More informationControl Circuit Protection
Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC
More informationAF series contactors (9 2650)
R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00
More informationLatch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5
3-pole DC Operated Ratings Rated Aux. Contacts Type Coil voltage 1) AC2 Current Built-in Additional 24 24V= DC 5 AC3 see 48 60V= DC 6 380V AC1 page 34 110 110V= DC 7 400V 660V 220 220V= DC 8 415V 690V
More informationMedium Voltage current limiting Fuse links
Medium Voltage current limiting Fuse links Type PCEF for indoor and outdoor use Rated Voltage 12-24 kv Current Rating 6 0A 1. General information P&C Medium Voltage fuse-links named PCEF are designed to
More informationMotorized switch-disconnectors OTM 40 to 125 Amperes
Motorized switch-disconnectors OTM to 125 mperes With the new range of motorized-switch disconnectors, BB offers now a full range from to 2500 mperes. Thanks to the design, OTM...125 are a good solution
More informationComponents for EEx e Panels
Circuit Interrupters / Motor Switches 8006/3 8543/1 8543/2 8548/2 40 A 63 A 80 A 1 160 A 500 V 660 V 500 V 01766E00 No. of poles 12 poles Isolator features Switching capacity 400 V, AC3 11 kw 22 kw 37
More informationLow voltage NH knife-blade fuse-links
Low voltage NH knife-blade fuse-links NV KOMBI advantages ETI is introducing a new generation of low-voltage fuse-links from size NV00C up to NV3 with new, dual indication of fuse-link operation, called
More informationPhase + Neutral, neutral on left side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1
More informationINDUSTRIAL CYLINDRICAL FUSE LINKS
gg Cylindrical gg class for use as general protection against overloads and short circuits, intended as protection of cables, power lines and equipment. Made of ceramic tube with high withstand to internal
More informationMicro Contactor MA Series
Relay-sized contactor, making it the world s smallest >3mm contact clearance acc. to IEC 60335-1 for Safety Applications Reversing contactor with mechanical interlock 3 Pole and 1 Aux. Contact NO or NC
More informationXT IEC Power Control Manual Motor Protectors
May 07 Product Selection Table 7. Rotary with Screw Terminals Global Ratings and North American Ratings Type and Type 2 Coordination Motor Protective Device with Thermal and Magnetic Trip Rated Uninterrupted
More informationIndex. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.
Index Index Page Manual Motor Starters 1 Auxiliary Contact Blocks 1 Trip Alarm Auxiliary 1 Switch Shunt Release 1 Under-voltage Release 2 Accessories 2 Busbar Connectors 2 Enclosures 2 Leistung, kw C mv
More informationProtection Equipment
Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection
More informationAF40... AF96 3-pole contactors Technical data
Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional
More informationClose-Open (Short-Circuit) Time Results Interpretation
Application Note Close-Open (Short-Circuit) Time Results Interpretation Close-Open (C-O, trip-free) cycles simulate closing on a short circuit. In the actual event, the breaker closes first, then the protection
More informationManual motor starters Overview and benefits
Manual motor starters Overview and benefits ABB offers a complete standard motor-protection concept for the world market IEC motor branch protection UL type E/F Motor applications with fuseless protection
More informationNH fuse-links gg 500VAC size 000, 00, 0, 1, 2, 3
IEC LV NH fuse links with blade contacts The NH system is classified among plug-in fuse systems and is composed of: fuse-base, (possibly including terminal covers and phase barriers) fuse-link with blade
More informationCOMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker
DR-6/DT-6 COMPACT AND EXTENSIBLE RING MAIN UNIT BUILT TO LAST! DR-6/DT-6 Compact and/or extensible SF 6 insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker SAFETY, RELIABILITY,
More informationMiniature Circuit-Breakers (MCBs)
Product overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristic Rated currents I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SX2
More information3 - Protection components Motor circuit-breakers
Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page
More informationLow-Peak 600V Class RK1
LPS-RK 600Vac/300Vdc, 1 10-60A, Dual Element, Time-Delay Fuses Dimensions - in 5" (± 0.31) 5.5" (± 0.31) Available with easyid open fuse indication 1/10 to 30A 0.81" (±0.008) 35 to 60A 1.06" (±0.008) Description:
More informationTechnical Journal September 2012
Technical Journal September 2012 Earth leakage protection in polluted low voltage network In present day irrespective of the application be it in process industry or in IT industry, Pollution of electrical
More information, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationNew Dimension in Motor Protection Manual Motor Starter MS116
New Dimension in Motor Protection Manual Motor Starter MS116 Economic fuseless protection for motors up to 7.5 kw Know-how you can trust As a manufacturer of electrical motors ABB has gathered quite some
More informationEST Electrical Service Technician Answer Schedule
EST 2075 - Electrical Service Technician Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A
More informationABB s new control and protection devices
ABB s new control and protection devices One product family ABB presents a new generation of first-class specialized components: manual motor starters, contactors, overload relays and softstarters for
More informationLow Voltage Products. Breakers and Switches for the HVAC segment
ow Voltage Products Breakers and witches for the VAC segment ABB s extensive range of products for the VAC segment ABB s very extensive range of appliances and systems for low voltage power distribution
More informationAF series contactors (9 2650)
R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00
More informationEE 741 Over-voltage and Overcurrent. Spring 2014
EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with
More informationSemiconductor Fuses European Fuses
66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection - rated current (or ) I N - pre-arcing I²t (I²t p ) at ms - total ope I²t (I²tt) at 66 V, cos
More informationonlinecomponents.com
66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection Rated current Pre-arcing I²t Total I²t at 66VAC I N (A) I²t p (A²s) I²t (A²s) - rated current
More informationDIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.
DIN HV Distribution DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from 2.3-38kV. Their compact dimensions and non-venting characteristics make them
More information3RT14 Contactors with 3 Main Contacts
3RT14 Contactors with 3 Main Contacts for Switching Resistive Loads Contactor Size 3RT14 46 Mechanical endurance Oper. 10 million Electrical endurance Oper. 0.5 million C-1 utilization category at I e
More informationW Datasheet: Residual current circuit breaker, series PRIORI, 10kA, Typ B
W Datasheet: Residual current circuit breaker, series PRIORI, 10kA, Typ B W SCHRACK-INFO All-current sensitive RCCB ( type B, B+ and Bfq) B+ types also meet the requirements of superior fire-protection
More information2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4
CHAPTER ELECTRICAL 2 INSTALLATION Contents of this Chapter... 2.1 Warnings & Agency Approvals..................2 2 2.1.1 Isolation..............................................2 2 2.1.2 Electrical Power
More information