W Datasheet: Residual current circuit breaker, series PRIORI, 10kA, Typ B

Size: px
Start display at page:

Download "W Datasheet: Residual current circuit breaker, series PRIORI, 10kA, Typ B"

Transcription

1 W Datasheet: Residual current circuit breaker, series PRIORI, 10kA, Typ B W SCHRACK-INFO All-current sensitive RCCB ( type B, B+ and Bfq) B+ types also meet the requirements of superior fire-protection systems No monthly test required Residual current indicator with 3 LED Warning before the RCD trips in case of leakage currents with an integrated auxiliary contact 4-pole types can also be used as 2-pole devices for photovoltaic applications Real contact position indicator Fault current tripping indicator Automatic re-setting possible W Technical datas Standards Types B and Bfq acc. to IEC/EN 61008, IEC/EN Type B+ acc. to VDE Type G/B and G/B+ additional acc. to ÖVE E 8601 Poles 4-pole Type B, B+, Bfq Sensitivity Alternating, pulsed and direct currents Rated current I n 25A, 40A, 63A Rated voltage U n 240/415 VAC, 50 Hz PAGE 1/11

2 Operation voltage electronic VAC Voltage range test circuit 30mA V AC Rated tripping current I Δn 300mA V AC 30mA, 300mA Tripping time Type G IΔn 10ms and 300ms No tripping residual current I Δno Rated insulation voltage U i Rated impulse withstand voltage U imp Rated short circuit capacity I cn 2 xiδn 10ms and 150ms 5 x IΔn 10ms and 40ms Type S IΔn 130ms and 500ms 2 xiδn 60ms and 200ms 5 x IΔn 50ms and 150ms 0,5 IΔn 440V 4kV (1.2/50µs) 10kA Bemessungsschaltvermögen I m 25A - type 500A 40A - type 500A 63A - type 630A Bemessungsfehlerschaltvermögen I m 25A - type 500A Peak withstand current 40A - type 63A - type Type G/B, G/B+ and G/Bfq Type S/B, S/B+ and S/Bfq 500A 630A 3kA (8/20µs) surge current proof typ. 5kA (8/20µs) selective + surge current proof Electrical isolation > 4mm contact space Maximum back-up fuse short circuit protection I n = 25A 63A gg/gl I n = 40A 63A gg/gl I n = 63A 63A gg/gl Maximum back-up fuse overload protection I n = 25A 63A gg/gl Power loss I n = 40A I n = 63A 63A gg/gl 63A gg/gl according to the following diagram PAGE 2/11

3 Prevents nuisance tripping caused by switching electronic light: delayed G,S 30mA delayed G,S 100mA with commercially available ballast according to the manufacturer max. 30 EVG each phase, max. 90 each RCCB delayed G,S with commercially available ballast according to the manufacturer max. 90 EVG each phase Endurance electrical components > 4,000 operating cycles mechanical components > 20,000 operating cycles Tripping temperature Storage- and transport temperature Resistance to climatic conditions Dimensions Frame size 45mm Mounting Device height Device width Polution degree 2 Degree of protection Upper and lower terminals Terminal protection Terminal capacity Terminal screw Terminal torque Busbar thickness Terminal capacity warning contact Contact position indicator Tripping indicator -25 C to +40 C -35 C to +60 C C/90-95% relative humidity acc. to IEC mm 70mm (4MW) quick fastening with 2 lock-in positions on DIN rail IEC/EN IP20 built-in IP40 open mouthed/lift terminals finger and hand touch safe, BGV A3, ÖVE- EN mm² single wire 2 x 16mm² multi wire M5 (Pozidriv PZ2) 2-2.4Nm 0.8-2mm mm2 (plug in terminals) red / green white / blue PAGE 3/11

4 W Tripping diagram PAGE 4/11

5 W Power loss Order no. Pole I N I Δn Type Power loss BC pole 25 A 30 ma G/B 4,6 W BC pole 25 A 300 ma G/B 4,6 W BC pole 40 A 30 ma G/B 6,2 W BC pole 40 A 300 ma G/B 6,2 W BC pole 63 A 30 ma G/B 10 W BC pole 63 A 300 ma G/B 10 W BC pole 25 A 30 ma G/B+ 4,6 W BC pole 25 A 300 ma G/B+ 4,6 W BC pole 40 A 30 ma G/B+ 6,2 W BC pole 40 A 300 ma G/B+ 6,2 W BC pole 63 A 30 ma G/B+ 10 W BC pole 63 A 300 ma G/B+ 10 W BC pole 25 A 300 ma S/B 4,6 W BC pole 40 A 300 ma S/B 6,2 W BC pole 63 A 300 ma S/B 10 W BC pole 25 A 300 ma S/Bfq 4,6 W BC pole 40 A 300 ma S/Bfq 6,2 W BC pole 63 A 300 ma S/Bfq 10 W BC pole 25 A 30 ma G/Bfq 5 W BC pole 25 A 300 ma G/Bfq 4,6 W BC pole 40 A 30 ma G/Bfq 7 W BC pole 40 A 300 ma G/Bfq 6,2 W BC pole 63 A 30 ma G/Bfq 11 W BC pole 63 A 300 ma G/Bfq 10 W BC pole 25 A 300 ma S/B+ 4,6 W BC pole 40 A 300 ma S/B+ 6,2 W BC pole 63 A 300 ma S/B+ 10 W PAGE 5/11

6 W Wiring diagram W LED signal and auxiliary contact PAGE 6/11

7 W Test Circuit W Instruction RCCB must be tested by PUSHING the TEST BUTTON 1x yearly. A test is further needed if red and yellow LED are on together. The switch must trip immediately. The testing is the responsibility of the user! The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it is recommended to test in shorter intervals. PAGE 7/11

8 W Possible connections PAGE 8/11

9 W Dimensions W Articles Residual current circuit breaker, series PRIORI, 10kA, Typ B, G, 30mA Residual current circuit breaker 25A, 4-p, 30mA, type B, G Residual current circuit breaker 40A, 4-p, 30mA, type B, G Residual current circuit breaker 63A, 4-p, 30mA, type B, G BC BC BC Residual current circuit breaker, series PRIORI, 10kA, Typ B, G, 300mA Residual current circuit breaker 25A, 4-p, 300mA, type B, G Residual current circuit breaker 40A, 4-p, 300mA, type B, G Residual current circuit breaker 63A, 4-p, 300mA, type B, G BC BC BC PAGE 9/11

10 Residual current circuit breaker, series PRIORI, 10kA, Typ B, S, 300mA Residual current circuit breaker 25A, 4-p, 300mA, type B, S Residual current circuit breaker 40A, 4-p, 300mA, type B, S Residual current circuit breaker 63A, 4-p, 300mA, type B, S BC BC BC Residual current circuit breaker, series PRIORI, 10kA, Typ B+, G, 30mA Residual current circuit breaker 25A, 4-p, 30mA, type B+, G Residual current circuit breaker 40A, 4-p, 30mA, type B+, G Residual current circuit breaker 63A, 4-p, 30mA, type B+, G BC BC BC Residual current circuit breaker, series PRIORI, 10kA, Typ B+, G, 300mA Residual current circuit breaker 25A, 4-p, 300mA, type B+, G Residual current circuit breaker 40A, 4-p, 300mA, type B+, G Residual current circuit breaker 63A, 4-p, 300mA, type B+, G BC BC BC Residual current circuit breaker, series PRIORI, 10kA, Typ B+, S, 300mA Residual current circuit breaker 25A, 4-p, 300mA, type B+, S Residual current circuit breaker 40A, 4-p, 300mA, type B+, S Residual current circuit breaker 63A, 4-p, 300mA, type B+, S BC BC BC Residual current circuit breaker, series PRIORI, 10kA, Typ B-fq B for frequncy converters, G, 30mA Residual current circuit breaker 25A, 4-p, 30mA,type B-fq,G Residual current circuit breaker 40A, 4-p, 30mA,type B-fq,G Residual current circuit breaker 63A, 4-p, 30mA,type B-fq,G BC BC BC PAGE 10/11

11 Residual current circuit breaker, series PRIORI, 10kA, Typ B-fq B for frequncy converters, G, 300mA Residual current circuit breaker 25A, 4-p, 300mA,type B-fq,G Residual current circuit breaker 40A, 4-p, 300mA,type B-fq,G Residual current circuit breaker 63A, 4-p, 300mA,type B-fq,G BC BC BC Residual current circuit breaker, series PRIORI, 10kA, Typ B-fq B for frequncy converters, S, 300mA Residual current circuit breaker 25A, 4-p, 300mA,type B-fq,S Residual current circuit breaker 40A, 4-p, 300mA,type B-fq,S Residual current circuit breaker 63A, 4-p, 300mA,type B-fq,S BC BC BC PAGE 11/11

W DATA SHEET: COMBINED RCD/MCB DEVICES BO, 3-POLE

W DATA SHEET: COMBINED RCD/MCB DEVICES BO, 3-POLE W DATA SHEET: COMBINED RCD/MCB DEVICES BO, 3-POLE W SCHRACK-INFO Combined RCD/MCB device Type-A: Protects against special forms of residual pulsating DC which have not been smoothed Line voltage-independent

More information

W DATASHEET: MINIATURE CIRCUIT BREAKER (MCB), SERIES AMPARO

W DATASHEET: MINIATURE CIRCUIT BREAKER (MCB), SERIES AMPARO W DATASHEET: MINIATURE CIRCUIT BREAKER (MCB), SERIES AMPARO W SCHRACK-INFO Lift and clamp terminals on both sides Terminal guide for secure connection Terminal cross-section: 1-25mm² Snap-on mounting for

More information

W DATA SHEET: COMBINED FAULT-CURRENT PROTECTIVE SWITCH, SERIES BOLF, 3P+N

W DATA SHEET: COMBINED FAULT-CURRENT PROTECTIVE SWITCH, SERIES BOLF, 3P+N W DATA SHEET: COMBINED FAULT-CURRENT PROTECTIVE SWITCH, SERIES BOLF, 3P+N W SCHRACK-INFO Typ A (pulse) Connection on both sides are possible Tripping independent of line voltage Additional connection capability

More information

COMBINATION CIRCUIT BREAKERS RCBO

COMBINATION CIRCUIT BREAKERS RCBO COMBINATION CIRCUIT BREAKERS RCBO W COMBINED MCB AND RCCB, SERIES BOLF W CONTACT POSITION INDICATOR 108 TYPE EAN CODE FOR QUICK ORDERING TRIP INDICATOR WHITE/BLUE CONTACT POSITION INDICATOR RED/GREEN W

More information

Residual current devices

Residual current devices Residual devices FH00 Plus of range /30 Technical features table /3 Ordering information /34 Technical details /37 DS01 and DS0C Plus of range /38 Technical features table /40 Ordering information DS01

More information

Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs)

Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs) Introduction Overview Devices Page Application Standards Used in / Personnel, material and fire protection, as well as protection against direct contact. SIGRES with active condensation protection for

More information

and other modular devices for low voltage installation

and other modular devices for low voltage installation Technical catalogue System and other modular devices for low voltage installation 2CSC400002D0204 SUMMARY Introduction Miniature Circuit-Breakers Residual Current Devices Auxiliary elements and accessories

More information

Modular contactor for installation into distribution boards

Modular contactor for installation into distribution boards Modular contactor for installation into distribution boards Description Modular contactors are used for installation in consumer units in dwellings, business premises, hotels, hospitals, shopping centres,

More information

DSE201 Compact design with enhanced protection

DSE201 Compact design with enhanced protection DSE201 Compact design with enhanced protection The best of safety DSE201 6 ka: the highest level of reliability The 1P+N electronic residual current circuit-breakers with overcurrent protection (RCBOs)

More information

IP20 degree of protection; IP40 degree of protection after installation in a distribution box

IP20 degree of protection; IP40 degree of protection after installation in a distribution box RI 50 RI 50 is used for the protection of installations and devices (overload and short circuit), and as a disconnector in case of electric shock Simple and quick fixing to a 35 mm mounting rail in accordance

More information

RSC09 RSC16 RSC22 RSC38 RSC43 RSC63 RSC-AUX

RSC09 RSC16 RSC22 RSC38 RSC43 RSC63 RSC-AUX IEC-Contactor RSC 1 Features Rated operational current 9 63 (C-3) Coil voltages C 24, 230V 3 main contacts and auxiliary contact Extendable with auxiliary contact block Mounting position any 2 Description

More information

RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION OLE

RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION OLE OLE Residual current circuit breakers RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION OLE OLE-10B-1N-030AC The device is a combination of residual current circuit breaker and circuit breaker.

More information

schneider-electric.com/sg K60 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads schneider-electric.

schneider-electric.com/sg K60 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads schneider-electric. K0 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads Overview K0 Circuit Breaker Technical Specification MCB RCCB K0 Circuit Breaker K0N K0H ID K Number of poles

More information

Thermal-Magnetic Circuit Breaker 2210-S291-P9M A

Thermal-Magnetic Circuit Breaker 2210-S291-P9M A Thermal-Magnetic Circuit Breaker 0-S9-P9M-40033-...A Description Single pole thermal-magnetic circuit breaker with trip-free mechanism and toggle actuation. Two-chamber construction with cascade contact

More information

W Datasheet: DIN Rail Contactors, series AMPARO

W Datasheet: DIN Rail Contactors, series AMPARO W Datasheet: DIN Rail Contactors, series AMPARO W SCHRACK-INFO For suiting of fans, pumps, heating & lighting Noise reducing design Low vibration on DIN-rail 230V 50/60Hz oder 24V 50/60 Hz coil DIN-Rail

More information

Residual current circuit breakers with conditional shortcircuit

Residual current circuit breakers with conditional shortcircuit LFE Residual current circuit breakers RESIDUAL CURRENT CIRCUIT BREAKERS LFE Residual current circuit breakers with conditional shortcircuit current 6 ka. They react to sine-wave residual current (type

More information

BETA Switching Switches and Light Indicators

BETA Switching Switches and Light Indicators Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION OLFE (6 ka)

RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION OLFE (6 ka) Residual current circuit breakers MINIA RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION OLFE ( ka) The device is a combination of residual current circuit breaker and circuit breaker For

More information

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases Index Page Circuit-Breakers M4 166 for motor protection Auxiliary contacts 167 Signalling switch Auxiliary releases Insulated 3-pole busbar system 168 Terminal block DIN-rail adapters 169 Busbar adapters

More information

max pole for t=15 ms

max pole for t=15 ms Types RI 61 RI 61N RI 61J RI 62 RI 62J RI 63 RI 63N RI 64 single-pole single-pole + neutral pole single-pole (for DC circuits) two-pole two-pole (for DC circuits) three-pole three-pole + neutral pole three-pole

More information

MS25, MST25, MS20, MST20

MS25, MST25, MS20, MST20 Versions: - MS25 with thermal and magnetic releases - MST25 with a thermal release - MS20 - with thermal and magnetic releases for single-phase consumers - MST20 with a thermal for single phase consumers

More information

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting.

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting. DATASHEET - ZB12-2,4 Delivery program Overload relay, 1.6-2.4 A, 1N/O+1N/C Part no. ZB12-2,4 Catalog No. 278437 Eaton Catalog No. XTOB2P4BC1 EL-Nummer 0004131832 (Norway) Product range Overload relay ZB

More information

Technical Data Accessories MCBs Ex9B.

Technical Data Accessories MCBs Ex9B. Auxiliary and signal contact units AX31, A31, AX31 General parameters With one circuit breaker Ex9B., it can be used up to three contact units with single CO contact or up to two contact units with 2 CO

More information

Cat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. .

Cat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. . 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s 0090 00/01/02/06/07/11/12/13/14 0/01/02/06/07/11/12/13/14/18/19/23/24/25/26/ /18/19/23/24/25/26/45/46 45/46 0090

More information

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer DATASHEET - ZB65-65 Delivery program Overload relay, 50-65A, 1N/O+1N/C Part no. ZB65-65 Catalog No. 278460 Eaton Catalog No. XTOB065DC1 EL-Nummer 0004131855 (Norway) Product range Overload relay ZB up

More information

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product Overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristics Rated current I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SQ2

More information

ATyS S - ATyS d S Remotely operated Transfer Switching Equipment from 40 to 125 A

ATyS S - ATyS d S Remotely operated Transfer Switching Equipment from 40 to 125 A Transfer switches The solution for > Genset < 90 kva > Heating systems > Climate control > Ventilation systems > Telecommunications atys-s_018_a Strong points Function products are 4 pole remotely operated

More information

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489 Data Sheet System pro M compact for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU200 M is BB s solution for UL 489 branch circuit protection

More information

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS 87045 LIMOGES Cedex Phone : + 33 5 55 06 87 87 Fax : + 33 5 55 06 88 88 R.C.B.O. DX 6000 A Phase + Neutral,, neutral on right side Cat. n (s) : 077 31 077 44-077 77 077 84 078 79 079 01-083 95 084 06 084

More information

3VU13, 3VU16 Circuit-Breakers

3VU13, 3VU16 Circuit-Breakers 3VU3, 3VU6 Circuit-Breakers Description The 3VU3, 3VU6 circuit-breakers are compact circuit-breakers for currents up to 80 A which operate according to the current limiting principle. The devices are used

More information

Multi 9 TM. Catalogue 2017 Multistandard protection for OEM. schneider-electric.com

Multi 9 TM. Catalogue 2017 Multistandard protection for OEM. schneider-electric.com Multi 9 TM Catalogue 207 Multistandard protection for OEM schneider-electric.com Green Premium TM Endorsing industry eco-friendly products Schneider Electric s Green Premium ecolabel is committed to offering

More information

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU 200 M is ABB s solution for UL 489 branch

More information

MS25, MST25, MS20, MST20

MS25, MST25, MS20, MST20 Motor protection switches MS25, MST25, MS20, MST20 Versions: - MS25 with thermal and magnetic releases - MST25 with a thermal release - MS20 - with thermal and magnetic releases for single-phase consumers

More information

Low Voltage A GE Power Controls Company. General catalogue

Low Voltage A GE Power Controls Company. General catalogue Low Voltage A GE Power Controls Company General catalogue this is a blanc page Miniature circuit breakers A Miniature circuit breakers AC miniature circuit breakers Benefits of the new MCB s A 3 The AEG

More information

Btdin RCBO 6000A up to 63A (2P)

Btdin RCBO 6000A up to 63A (2P) Index Pages 1. Descripton... 2 2. Product range... 2 3. Overall dimensions... 2 4. Fixing Connection... 3 5. Generl characteristics.... 4-29 6. Compliance - Approvals... 30 7. Curves... 30-34 8.Auxiliaries-

More information

Control Circuit Protection

Control Circuit Protection Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC

More information

3NP1 Fuse Switch Disconnectors up to 630 A

3NP1 Fuse Switch Disconnectors up to 630 A Switch Disconnectors 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors

More information

MS General Information Extended Product Type: MS

MS General Information Extended Product Type: MS MS132-1.6 General Information Extended Product Type: MS132-1.6 Product ID: 1SAM350000R1006 EAN: 4013614400063 Catalog Description: MS132-1.6 Manual Motor Starter Long Description: The MS132-1.6 manual

More information

ABB STOTZ-KONTAKT GmbH

ABB STOTZ-KONTAKT GmbH ABB STOTZ-KONTAKT GmbH MULTIPLE 89 Motijheel C/A, Lucky Chamber (3rd floor, Room #61), Dhaka-1000, Bangladesh. Tel: (02) 9559692, Fax: (02)9566596 E-mail: info@multipletrading.net PAGE : 02 The ABB Line

More information

TX³ RCCBs 2P up to 100 A

TX³ RCCBs 2P up to 100 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 TX³ RCCBs CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1 MainswitchSurfacemounting Partno. T0-2-8900/I1/SVB Articleno. 207151 CatalogNo. CT02-8900-I1CRQ Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

Product range Overload relay ZB up to 150 A. Phase-failure sensitivity IEC/EN 60947, VDE 0660 Part 102

Product range Overload relay ZB up to 150 A. Phase-failure sensitivity IEC/EN 60947, VDE 0660 Part 102 Overloadrelay,10-16A,1N/O+1N/C Partno. ZB12-16 Articleno. 290168 CatalogNo. XTOB016BC1 Deliveryprogramme Product range Overload relay ZB up to 150 A Frame size ZB12 Phase-failure sensitivity IEC/EN 60947,

More information

Offers. QOvs RCBO residual current devices. Protection Earth leakage protection. Variants

Offers. QOvs RCBO residual current devices. Protection Earth leakage protection. Variants devices Offers This page must be removed before publishing The Schneider Electric residual current devices range comprises various offers (A, B, C, D) so as to be as competitive as possible in each country,

More information

MS /27/2015. ABB contact for United States of America. General Information Extended Product Type: Categories

MS /27/2015. ABB contact for United States of America. General Information Extended Product Type: Categories Page 1 of 5 MS132-10 ABB contact for United States of America General Information Extended Product Type: Product ID: EAN: Catalog Description: Long Description: MS132-10 1SAM350000R1010 4013614400100 MS132-10

More information

Motor-protectivecircuit-breaker,3p,Ir=2.5-4A. Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton actuation

Motor-protectivecircuit-breaker,3p,Ir=2.5-4A. Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton actuation Motor-protectivecircuit-breaker,3p,Ir=2.5-4A Partno. PKZM01-4 Articleno. 278482 CatalogNo. XTPB004BC1 Deliveryprogramme Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton

More information

For Info: Phone: Fax:

For Info:   Phone: Fax: Page -2 TWO POLES IEC rated current Ith: 20A (AC1) IEC operational power: 1.3kW (AC3 230V) Ideal for domestic applications. Page -2 THREE AND FOUR POLES IEC rated current Ith: 25A, 40A and 63A (AC1) IEC

More information

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors MOTOR STARTERS SM Basic function Switching and protection of motors up to A Protection against short-circuit and protection against overload The device responds to phase failure The device is provided

More information

Emergency stop without emergency switching off/emergency stop function. Locking facility Lockable in the 0 (Off) position N/O 0 B 0

Emergency stop without emergency switching off/emergency stop function. Locking facility Lockable in the 0 (Off) position N/O 0 B 0 MainswitchSurfacemounting Partno. T0-2-1/I1/SVB-SW Articleno. 207148 IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches

More information

Electronic overload relays EF205 and EF370

Electronic overload relays EF205 and EF370 Data sheet Electronic overload relays EF205 and EF370 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD. DATASHEET - DILMC9-10(24VDC) Technical data General Contactor, 3p+1N/O, 4kW/400V/AC3 Part no. DILMC9-10(24VDC) Catalog No. 277468 Eaton Catalog No. XTCEC009B10TD EL-Nummer 4110305 (Norway) Standards IEC/EN

More information

DX³ RCCBs - ID 4P up to 100 A

DX³ RCCBs - ID 4P up to 100 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ s - ID CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Subrange SmartWire-DT electronic motor starters. Basic function Reversing starters (complete devices)

Subrange SmartWire-DT electronic motor starters. Basic function Reversing starters (complete devices) DATASHEET - EMS-RO-T-9-SWD-ADP Reversing starter 9A with SmartWire-DT Part no. EMS-RO-T-9-SWD-ADP Catalog No. 172763 Eaton Catalog No. EMS-RO-T-9-SWD-ADP EL-Nummer 4110026 (Norway) Delivery program Product

More information

The breakers offer thermal-magnetic trip protection according to Z and K characteristics.

The breakers offer thermal-magnetic trip protection according to Z and K characteristics. Series High Performance Circuit Breakers Description The high performance MCB offers a compact solution to circuit protection. The devices are DIN rail mounted. The is available with application-specific

More information

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristic Rated currents I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SX2

More information

RESIDUAL CURRENT CIRCUIT BREAKER

RESIDUAL CURRENT CIRCUIT BREAKER Quality Features Mid Trip - Different knob position to indicate whether the device is Switched OFF by a fault or Switched OFF manually Inscription Window - Ensures circuit identification and hence reduces

More information

CA Z-EN Overload relays, CT-operated overload relays

CA Z-EN   Overload relays, CT-operated overload relays Overload relays, CT-operated overload relays Electronic overload relays, thermistor overload relay for machine protection Setting ranges (A) (note max. current of the contactor) 0.1-12 0.1-16 0.1-38 6-75

More information

06/001. Overload Relays, Motor-Protective Relays Overview. Overload / Motor-Protective Relays. Moeller HPL /2002

06/001. Overload Relays, Motor-Protective Relays Overview. Overload / Motor-Protective Relays. Moeller HPL /2002 Overload Relays, Motor-Protective Relays Overview 06/00 Overload relays, motor-protective relays Page Technical overview 06/00 System overview 05/006 Overload relays, motor-protective relays 06/004 ZE,

More information

SIRIUS 3RU2 Thermal Overload Relays

SIRIUS 3RU2 Thermal Overload Relays Overview 1 2 3 4 6 1 2 NSB0_0207a Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors. The overload relay can be connected directly to

More information

Protection Equipment

Protection Equipment Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection

More information

DX³ 4-pole RCBO 6000 A/10 ka

DX³ 4-pole RCBO 6000 A/10 ka 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

cor Long Run Experience

cor Long Run Experience Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30

More information

B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors Technical data

B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors Technical data B6, B7, BC6, BC7, TBC7 - and 4-pole mini contactors VB6, VB7, VBC6, VBC7 - and 4-pole mini reversing contactors Main pole Utilization characteristics according to IEC Standards IEC/EN 60947-1, IEC/EN 60947-4-1

More information

NH DIN Dual Indication Fuse Links

NH DIN Dual Indication Fuse Links Class gg/gl, 400Vac, 2 to 630 Amps, Sizes 000 to 3 Standards/Approvals IEC 60269, VDE 0636, DIN 43620 Part 1 and 3 Description A square bodied range of industrial fuse links for a wide variety of applications.

More information

INNOZED D0 fuse-bases with touch protection

INNOZED D0 fuse-bases with touch protection D0 fusebases with touch protection D0 fusebases with touch protection FUSE HOLDERS, FUSE BASES AND SUPPORTS IEC D0 & D FUSE BASES FEATURES & BENEFITS is a fuse base for D0 fuselinks, sizes D0 and D02.

More information

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX³ RCBO 4500/6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information

15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250

More information

Btdin RCD Add-on modules 125A for MCBs 1,5 modules per pole

Btdin RCD Add-on modules 125A for MCBs 1,5 modules per pole Index Pages 1. Descripton... 2 2. Product range... 2 3. Overall dimensions... 2 4. Fixing Connection... 3 5. Generl characteristics... 4 6. Compliance - Approvals... 6 7. Curves... 7 8. Auxiliares and

More information

Technical data. Miniature Circuit Breakers. System pro M. System pro M

Technical data. Miniature Circuit Breakers. System pro M. System pro M Technical data System pro M System pro M 1 Prior to connection of aluminium conductors ensure that their contact points are cleaned, brushed and coated with grease. The contact terminals must be tighten

More information

VB6, VB7 3-pole mini reversing contactors with screw terminals 4 to 5.5 kw AC operated

VB6, VB7 3-pole mini reversing contactors with screw terminals 4 to 5.5 kw AC operated VB6, VB7 -pole mini reversing contactors with screw terminals 4 to 5.5 kw AC operated VB7-0-10 2CDC211006F0011 Description VB6, VB7 -pole compact design reversing contactors are space optimized control

More information

Technical data for manual motor starters Type MS325

Technical data for manual motor starters Type MS325 for manual mor starters Type MS325 General data Rated voltage 600 V Rated current 25 A (14 setting ranges, 0.1 25A) Rated frequency 50-60 Hz Electrical and mechanical life endurance 100,000 operations

More information

R.C.B.O. SP / 1 module

R.C.B.O. SP / 1 module 87045 LIMOGES Cedex - France Telephone : (+33) 5 55 06 87 87 Fax : (+33) 5 55 06 88 88 R.C.B.O. SP / 1 module 6064 04 6064 64 05 6064 10 6064 11 6064 12 CONTENTS PAGES 1. Description, use... 1 2. Range...

More information

Thermal overload relay TF65 and TF96

Thermal overload relay TF65 and TF96 Data sheet Thermal overload relay TF65 and TF96 Thermal overload relays are economic electromechanical protection devices for the main circuit. They are used mainly to protect motors against overload and

More information

Thermal overload relay TF140DU and TF140DU-V1000

Thermal overload relay TF140DU and TF140DU-V1000 Data sheet Thermal overload relay TF140DU and TF140DU-V1000 Thermal overload relays are economic electromechanical protection devices for the main circuit. They are used mainly to protect motors against

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays are the alternative to the thermal overload relays. An electronic overload relay offers reliable and fast protection

More information

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV Switch Disconnectors Introduction Siemens AG 2010 Overview 3NP5 0 3NP5 2 3NP5 fuse disconnector range 3NP5 4 SENTRON 3NP5 fuse disconnectors are controls for the occasional manual ing/isolating of loads

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker

Magnetic and Hydraulic-Magnetic Circuit Breaker Magnetic and Hydraulic-Magnetic Circuit Breaker 835-... Description Single or multipole hydraulic-magnetic circuit breakers with trip-free - mechanism and toggle actuation. A choice of switching characteristics

More information

MC FRAME SIZE 1 / UP TO 160A

MC FRAME SIZE 1 / UP TO 160A 8 W CIRCUIT BREAKER 3 POLE UP TO 160A WITH THERMAL MAGNETIC RELEASE TYPES MC1B-A, MC1N-A, MC1H-A For system and line protection Adjustable overload release Ir: 0,8 1 x In (factory setting 0,8 x In) Adjustable

More information

Control switch/load disconnect switch Series 8008

Control switch/load disconnect switch Series 8008 > s Control switch with 2, 3 or 4 pole Load switch 3 pole + 1 auxiliary contact > Rated operational voltage up to 690 V AC > Positive opening contacts > Contacts suitable for EM-STOP > Isolating characteristics

More information

Thermal Overcurrent Circuit Breaker 3120-F...

Thermal Overcurrent Circuit Breaker 3120-F... Thermal Overcurrent Circuit Breaker 20-F... Description An extremely versatile range of rocker switch/thermal circuit breakers (S-type TO CBE to EN 6094 with trip free mechanism) offering the choice of

More information

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI . Technical Data and Specifications Ratings Frames EG, JG and LG EG JG LG Maximum rated current (amperes) 15, 160 1 50 400, 630 Breaker type 3 B B E S S H H C E S H C U X E S H C U X of poles 1, 3, 4,

More information

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077 Data Sheet System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077 2CDC021026S0011 2CDC021016S0012 The S 200 PR is a high-performance supplementary protector with

More information

Contents. Acti 9 MCBs, RCCB. ic60h circuit breakers (curve B, C, D)... pages 2/2 to 2/4. ic60h and ic60h2 RCB0 10, 30 and 100 ma...

Contents. Acti 9 MCBs, RCCB. ic60h circuit breakers (curve B, C, D)... pages 2/2 to 2/4. ic60h and ic60h2 RCB0 10, 30 and 100 ma... Contents Acti 9 MCBs, RCCB ic60h circuit breakers (curve B, C, D)... pages / to /4 ic60h and ic60h RCB0 10, 30 and 100 ma.... pages /5 to /8 Vigi ic60 add-on residual current devices.... pages /9 to /1

More information

Application Mini Contactors for Motors and Resistive Loads

Application Mini Contactors for Motors and Resistive Loads Delivery program Contactor, 4p, 4kW/400V/AC3 Part no. DILEM4-G(24VDC) Catalog No. 012701 Eaton Catalog No. XTMF9A00TD Product range Contactors Application Mini Contactors for Motors and Resistive Loads

More information

LINOCUR Size D02 63A 230VAC/440VAC

LINOCUR Size D02 63A 230VAC/440VAC IEC FUSE SWITCH DISCONNECTORS D0 FUSE COMBINATION UNITS The D0 Linocur is a combination of switch disconnector fuse and Neozed 63A fuse-link, equiped with significant safety characeristics and sophisticated

More information

Deliveryprogramme. Overloadrelay,24-40A,1N/O+1N/C. Articleno CatalogNo. XTOB040DC1. Auxiliarycontacts. Short-circuitprotection

Deliveryprogramme. Overloadrelay,24-40A,1N/O+1N/C. Articleno CatalogNo. XTOB040DC1. Auxiliarycontacts. Short-circuitprotection Deliveryprogramme Overloadrelay,24-40A,1N/O+1N/C Partno. ZB65-40 Articleno. 278458 CatalogNo. XTOB040DC1 Product range Overload relay ZB up to 150 A Frame size ZB65 Phase-failure sensitivity IEC/EN 60947,

More information

INNOZED D0 fuse-bases with touch protection

INNOZED D0 fuse-bases with touch protection INNOZED D0 fusebases with touch protection INNOZED D0 fusebases with touch protection FUSE HOLDERS, FUSE BASES AND SUPPORTS IEC D0 & D FUSE BASES FEATURES & BENEFITS INNOZED is a fuse base for D0 fuselinks,

More information

Overloadrelay,10-16A,1N/O+1N/C. Articleno

Overloadrelay,10-16A,1N/O+1N/C. Articleno Overloadrelay,10-16A,1N/O+1N/C Partno. ZB32-16 Articleno. 278452 CatalogNo. XTOB016CC1 Deliveryprogramme Product range Overload relay ZB up to 150 A Product range Accessories Accessories Overload relays

More information

abb.ch ABB Switzerland Ltd. Low Voltage Products Fulachstrasse 150 CH-8201 Schaffhausen Telefon +41 (0) Telefax +41 (0)

abb.ch ABB Switzerland Ltd. Low Voltage Products Fulachstrasse 150 CH-8201 Schaffhausen Telefon +41 (0) Telefax +41 (0) ABB Switzerland Ltd. Low Voltage Products Fulachstrasse 150 CH-8201 Schaffhausen Telefon +41 (0) 58 586 41 11 Telefax +41 (0) 58 586 42 22 abb.ch We reserve the right to make technical changes or modify

More information

Thermal Overcurrent Circuit Breaker 3120-F...

Thermal Overcurrent Circuit Breaker 3120-F... Thermal Overcurrent Circuit Breaker 20-F... Description An extremely versatile range of rocker switch/thermal circuit breakers (Stype TO CBE to EN 6094 with trip free mechanism) offering the choice of

More information

Instantaneous tripping TYPE B, C, D TYPE B, C TYPE B, C, D TYPE B, C IEC RCCB TYPE C IEC61008 RCBO 25, 40, 63A. IEC61009 Isolating Switch

Instantaneous tripping TYPE B, C, D TYPE B, C TYPE B, C, D TYPE B, C IEC RCCB TYPE C IEC61008 RCBO 25, 40, 63A. IEC61009 Isolating Switch Features (1) All models fully comply with IEC regulations (2) Units can be mounted on a standard 35mm IEC rail (3) Residual current circuit breakers use an original Mitsubishi Electric IC securing reliable

More information

MULTIBLOC 2.RST8 Size 2, 400A, 690VAC, Design for bus bar installation, Triple Pole

MULTIBLOC 2.RST8 Size 2, 400A, 690VAC, Design for bus bar installation, Triple Pole MULTIBLOC 2.RST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC 2.RST8 comprises NH fuse switch disconnectors for 400A. Products are designed in triple

More information

Deliveryprogramme. Overloadrelay,6-9A,1N/O+1N/C. Articleno CatalogNo. XTOM009AC1. Settingrange. Auxiliarycontacts. Short-circuitprotection

Deliveryprogramme. Overloadrelay,6-9A,1N/O+1N/C. Articleno CatalogNo. XTOM009AC1. Settingrange. Auxiliarycontacts. Short-circuitprotection Deliveryprogramme Overloadrelay,6-9A,1N/O+1N/C Partno. ZE-9 Articleno. 014708 CatalogNo. XTOM009AC1 Product range ZE overload relays for mini contactor relays Phase-failure sensitivity IEC/EN 60947, VDE

More information

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications 2CDC021031S0011 2CDC021033S0011 The miniature circuit breaker S 200 M UC extends the established ABB System pro M compact

More information

4 - Miniature controls

4 - Miniature controls Index -....1.22 Selection Contactors for connection to PLCs, B6S & B7S, 3 phase...6 Contactors, Interface, B6 & B7, 3 phase...5 Contactors, features...1 Contactors, mechanically interlocked, B6 & B7, 3

More information

Components for EEx e Panels

Components for EEx e Panels Circuit Interrupters / Motor Switches 8006/3 8543/1 8543/2 8548/2 40 A 63 A 80 A 1 160 A 500 V 660 V 500 V 01766E00 No. of poles 12 poles Isolator features Switching capacity 400 V, AC3 11 kw 22 kw 37

More information

Thermal Overcurrent Circuit Breaker 3120-F...

Thermal Overcurrent Circuit Breaker 3120-F... Thermal Overcurrent Circuit Breaker 0-F... Description An extremely versatile range of rocker switch/thermal circuit breakers (S-type TO CBE to EN 6094 with trip free mechanism) offering the choice of

More information

The effective choice The benefits of a product with the highest quality standards

The effective choice The benefits of a product with the highest quality standards The effective choice The benefits of a product with the highest quality standards Compact size for easy installation in small spaces and retrofitting of already existing facilities. Terminals designed

More information

1489-M Circuit Breakers

1489-M Circuit Breakers Dual terminals provide wiring/bus bar flexibility and clamp from both sides to improve connection reliability Terminal design helps prevent wiring misses Scratch- and solventresistant printing Suitable

More information

DPX earth leakage DPX 3 -I earth leakage

DPX earth leakage DPX 3 -I earth leakage 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 250 + earth leakage Reference(s) : 420 225/ 227/ 228/229/ 255/ 257/ 258/ 259/ 285/ 287/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3.

More information