products 22 º C Ventilation Air Conditioning Refrigeration Inside PROVIDED BY HEINEN & HOPMAN

Size: px
Start display at page:

Download "products 22 º C Ventilation Air Conditioning Refrigeration Inside PROVIDED BY HEINEN & HOPMAN"

Transcription

1 products > Dampers HT OUTSIDE 35 C HUMIDITY 90% 22 º C Inside PROVIDED BY HEINEN & HOPMAN Heating Ventilation Air Conditioning Refrigeration

2 dampers HT There are different types of dampers: Fire and gas dampers Shutoff dampers Balancing dampers Nonreturn dampers / Pressure relief dampers Blast dampers Airflow adjustment dampers Fire and gas dampers Fire and gas dampers prevent the spread of fire, smoke and gas between fire zones, where people must have the maximum amount of time to react to possible fire. The dampers are typeapproved according to A0 (A60) or H0 (H120). The patented blade structure of the FDB2 dampers have special seals that are effective up to 300 C and thermally activated graphite seals that expand when the heat rises to 150 C in ductwork. These unique safety features ensure air tightness and low leakage to prevent fire, gas and smoke progression in a ductwork. FDB2 AO (A60) fire and gas dampers Frame: AISI 316 or painted or galvanized steel. Thickness: 3 or 35 mm. Blades: AISI 316 or galvanized steel. Blades have thermal expansion and special seals. Sizes: 100x100 ~ 1200x1600 mm. Circular connection pieces: 100 ~ 1250 mm. Note: Special drilling patterns available as an option. Modules possible. FDL AO (A60) fire dampers Frame: AISI 316 or painted or galvanized steel. Thickness: 3 or 35 mm. Blades: AISI 316 or painted or galvanized steel. Blades without seals. Sizes: 100x100 ~ 1300x1200 mm. Circular connection pieces: from 100 ~ 1250 mm. Note: Special drilling patterns available as an option. Modules possible. FDD AO (A60) fire and gas dampers FEX HO (H120) fire and gas dampers Frame: AISI 316 or AISI 316 with painted steel. Thickness: 3 or 35 mm. Blades: AISI 316. Blades without seals. Sizes: 100x100 ~ 1200x1200 mm. Circular connection pieces: 100 ~ 1250 mm Note: Special drilling patterns available as an option. Modules case by case. Frame: AISI 316 or painted or galvanized steel. Thickness: min. 3 mm. Blades: AISI 316. Blades have thermal expansion and glassfiber seals. Sizes: Ø100, 125, 160, 200, 250, 315 mm Note: Special drilling patterns available as an option. Modules possible.

3 Shutoff dampers Shutoff dampers shut off the airflow in ductwork where tightness, thermal insulation and reliability are important. The dampers meet international standards for rectangular and circular ducts. The leakage class is accordance with the EM1751 standards. UTT shutoff dampers Frame: AISI 316 or galvanized steel. Thickness: 1 mm. Blades: AISI 316 or galvanized steel. Blades are insulated and have seals. Sizes: 100x100 ~ 2400x2400 mm at 50mm intervals (special sizes available). Circular connection pieces: 100 ~ 1250 mm. Operation system: by static air pressure. Balancing dampers Balancing dampers adjust or control the air flow rates in ductwork where leakage does not have significant importance. UTK balancing dampers Frame: AISI 316 or galvanized steel. Thickness: 1 mm. Blades: AISI 316 or galvanized steel. Blades have seals (tightness class 1). Size: 100x100 ~ 2400x2400 mm at 50mm intervals (special sizes available). Circular connection pieces: 100 ~ 1250 mm. Operation system: by static air pressure. Maximum pressure across the dampers: 4000 Pa. Maximum air velocity: 16 m/s. Nonreturn dampers / Pressure relief dampers Nonreturn dampers and pressure relief dampers are used in oil and gas applications to prevent backflow and relieve the pressure through ventilation ductwork. The opening pressure can be individually adjusted. The dampers are also applicable in marine ventilation systems. BLD nonreturn dampers / BRD pressure relief dampers Frame: AISI 316 or painted or galvanized steel. Thickness: 3 mm. Blades: AISI 316 or galvanized steel. Blades have special seals. Size: 100x100 ~ 1200x1400 mm Circular connection pieces: 100 ~ 1250 mm. Note: Special drilling patterns available as an option. BRD dampers have counterweights. Modules possible. Blast dampers Blast dampers protect ventilation systems against the effects of explosions. The dampers shield industrial facilities and related buildings against destructive blast forces. The dampers offer higher air flow capacity and increased level of safety as well as flexibility for design of duct systems. HV blast dampers Material: AISI 316 or galvanized steel. Blast protection: up to 1 bar (14,5 psi). Standard sizes: 300x300 ~ 1500x1500 mm. Note: Modular construction available for high airflows and large ducts. Maintenancefree design. Minimum leakage on passthrough pressure and impulse. Minimum turbulence and pressure drop. Air flow adjustment dampers PRA air flow adjustment dampers are manually adjustable measurement units for circular ducts. The dampers are used in duct systems to control the air flow. PRA air flow adjustment dampers Casing and blades: Galvanized steel. Circular construction: 100 to 315 and 350 to 1000 mm. Adjustable cone and air flow measurement taps for differential pressure adjustment. Classification of casing leakage: EN1751 Class C. Control The dampers can be controlled electrically, pneumatically or manually. In case of fire, the fire and gas dampers will close automatically. The electrically and pneumatically controlled dampers are driven by an actuator. Belimo actuators: As standard actuator. Schischeck actuators: Actuator used in explosionproof areas or if the actuator must open/close within 3s/90 0. Certified quality In addition to ISO 9001, ISO 14001, quality and environmental management certificates, marine fire dampers conform to leading classification societies worldwide. Several dampers are ATEXcertified and shocktested products for naval applications, ships and submarines.

4 FDB2 fire and gas dampers FDB2 fire and gas dampers are used in offshore, marine and navy ventilation systems. The dampers are typeapproved according to A0 (A60). The dampers can be installed in rectangular or circular ducts. The dampers have a fusible link and prevent the spread of fire and gases within the ventilation ductwork. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance. The dampers are set from outside and can be installed in any position. An openclosed indicator is visible on the outside of the dampers. Nonstandard dimensions are available on request. Typeapproved by most recognized classification societies: class A0 without insulation, class A15A60 when suitably insulated. Available as ATEXapproved. Shock tested. Blades contain silicone (effective up to 300 ºC) for low leakage in normal conditions and thermal expansion graphite seals (effective from 150 ºC) to increase tightness up to 50% in case of fire. Closed damper meets the requirement of leakage class 3 (EN1751:1998) Tested size 1000x1000 mm. Nominal fuse release temperature: 50 ºC, 74 ºC or 100 ºC. Other temperatures available. Low weight due to patented double skin blade structure. Automatic electrical, pneumatic or spring operation system available. Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s. Part Material Finishing Frame Carbon steel Painted or galvanized Frame Stainless steel EN (AISI 304), EN (AISI 316L), EN (AISI 316L) Blades Steel Galvanized Blades Stainless steel EN (AISI 304), EN (AISI 316L), EN (AISI 316L) Bearings Stainless steel EN (AISI 316L) / Bronze bearings optional Shafts Stainless steel EN (AISI 316L) Dimensions and material thickness The dampers meet international standards for rectangular (width B mm and height H mm, 1 mm division) and circular ducts (Ø mm). Modular constructions are available for larger sizes. Nonstandard dimensions and flange drilling are available on request. Frame thickness according to SOLAS Dimensions S L If B or H > 100, but < If B or H > 450, but < If B or H > Actuator effect in dimensions Actuator Electrical GGA 326, 1E 100 Pneumatic PNL Pneumatic PNR Pneumatic PNR Linear actuator 245/300N Pneumatic rotating atuator AT100 Pneumatic rotating actuator AT200 R Dimensions A H< 300 = 300 H>300 = H H<500 = 500 H>500 = H H<300 = 300 H>300 = H H<350 = 350 H>350 = H Spring Spring 140 H

5 GENERAL FDB2 DRAWING FDB2 CIRCULAR CONNECTIONS GENERAL FDB2 MODULE ASSEMBLY ø12 10 A 30 ACTUATOR 18 R MIN n*150 n*150 B+4 B n*150 n* H+4 MIN. 50 H , S=3 365, S=4 370, S=5 S, ACCORDING TO SOLAS GENERAL FDB2 DRAWING, TOP FDB2 CIRCULAR, WITH CONNECTION FLANGES 215, S=5 212, S=4 210, S=3 160 FDB2 CIRCULAR CONNECTIONS GENERAL FDB2 MODULE ASSEMBLY S, ACCORDING TO SOLAS S, ACCORDING TO SOLAS 240, BLADES IN OPEN POSITION 361, S=3 365, S=4 370, S=5 FDB2 CIRCULAR, WITH CONNECTION FLANGES S, ACCORDING TO SOLAS 367, S=3 373, S=4 380, S=5 367, S=3 373, S=4 S, ACCORDING TO SOLAS 380, S=5 10 H+58 H n*150 n*150 MIN , BLADES IN OPEN POSITION S, ACCORDING TO SOLAS

6 FEX fire and gas dampers FEX fire and gas dampers are used in offshore, nuclear and navy ventilation systems. The dampers are typeapproved according to H0 (H120). The dampers protect the integrity of bulkheads where they are penetrated by ventilation ducts. The dampers can be installed in rectangular or circular ducts. The dampers have a fusible link and prevent the spread of fire and gases (lowleakage model) within the ventilation ductwork. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance. The dampers are set from outside and can be installed in bulkheads. An openclosed indicator is visible on the outside of the dampers. Typeapproved by most recognized classification societies: class H0 (H120) when suitably insulated. Fixed frame and blades of stainless steel AISI 316L. Painted frame surface as an option available on request. Welding cleaned by acid treatment. Lifting lugs as standard. Blades have thermal expansion seals. Nominal fuse release temperature: 50 ºC, 74 ºC or 100 ºC. Other temperatures available. Automatic electrical, pneumatic or spring operation system available. Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s. ATEXapproved. Dimensions and material thickness The dampers are for rectangular and circular ducts. Sizes for rectangular ducts (BxH) are available from 100x100 to 1200x1200 mm in 1mm increments of duct. Sizes for circular ducts (BxH) are available from Ø 100 mm to 1250 mm. Nonstandard dimensions are available on request. Standard flange size: 40 mm. Flanges and drilling are available according to ISO standards or customer specifications. Standard frame material thickness: 3 mm. Blades are made of two sheets of 1 mm thickness each. Actuators effect on dimensions Actuator Electrical GGA 326, 1E 100 Pneumatic Electrical, EX Pneumatic rotating atuator Schischek ExMax / RedMax Dimensions Spring Spring 140 H The table shows only some examples of actuators and their effect on dimensions. R A H< 300 = 300 H>300 = H H<300 = 300 H>300 = H H<300 = 300 H>300 = H Part Material Finishing Note Frame Stainless steel Painted Frame Stainless steel Blades Stainless steel Blades Stainless steel Maintenancefree bearings Stainless steel Bronze bearings optional Shafts Stainless steel

7 GENERAL FEX DRAWING FEX CIRCULAR CONNECTIONS A ACTUATOR x n*150 n*150 H+4 H+84 MIN R n*150 n*150 B+4 B MIN GENERAL FEX DRAWING, TOP FEX CIRCULAR, WITH CONNECTION FLANGES

8 FDL fire dampers FDL fire dampers are used in offshore, marine and navy ventilation systems. The dampers are typeapproved according to A0 (A60). The dampers can be installed in rectangular or circular ducts. The dampers have a fusible link and spring return actuator. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance. The dampers are set from outside and can be installed in any position. An openclosed indicator is visible on the outside of the dampers. Nonstandard dimensions are available on request. Typeapproved by most recognized classification societies: class A0 without insulation, class A15A60 when suitably insulated. Available as ATEX approved. Shocktested. Fixed frame and blades of painted, galvanized or stainless steel. Maintenancefree stainlesssteel bearings and shafts. Blades without sealing. Nominal fuse release temperature: 50 ºC, 74 ºC or 100 ºC. Other temperatures available. Can be installed in any position. Automatic electrical, pneumatic or spring operation system available. Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s. Part Material Finishing Frame Carbon steel Painted or galvanized Frame Stainless steel EN (AISI 304), EN (AISI 316L), EN (AISI 316L) Blades Steel Galvanized Blades Bearings Stainless steel EN (AISI 304), EN (AISI 316L), EN (AISI 316L) Stainless steel EN (AISI 316L) / Bronze bearings optional Shafts Stainless steel EN (AISI 316L) Dimensions and material thickness The dampers meet international standards for rectangular (width B mm and height H mm, 1 mm division) and circular ducts (Ø mm). Modular constructions are available for bigger sizes. Modular constructions are available for larger sizes. Nonstandard dimensions and flange drilling are available on request. Standard flange size: 27 mm. Flanges and drilling are available according to ISO Modular construction sizes up to 2600x2400 mm. Standard frame material thickness: 35 mm. Material thickness according to SOLAS available on request. Frame thickness according to SOLAS Dimensions S L If B or H > 100, but < If B or H > 450, but < If B or H > Actuators effect on dimensions Actuator Electrical GGA 326, 1E 100 Pneumatic PNL Pneumatic PNR Pneumatic PNR Linear actuator 245/300N Pneumatic rotating atuator AT100 Pneumatic rotating actuator AT200 Dimensions The table shows only some examples of actuators and their effect on dimensions. R A H< 300 = 300 H>300 = H H<500 = 500 H>500 = H H<300 = 300 H>300 = H H<350 = 350 H>350 = H Spring Spring 140 H

9 2 GENERAL FDL DRAWING A ACTUATOR Ø n*150 n*150 H+2 H+56 MIN. 50 FDL CIRCULAR CONNECTIONS 217, S=5 214, S=4 212, S=3 160 S, ACCORDING TO SOLAS S, ACCORDING TO SOLAS 2 240, BLADES IN OPEN POSITION GENERAL FDL MODULE ASSEMBLY Size limitation: FDB2: Nominal Width 2060 x Nominal Height 3260 or Nominal Width 2460 x Nominal Height 2860 FDL Nominal Width 2660 x Nominal Height 2460 FDB2 Nominal height+58 FDL Nominal height+56 >50 nx 150 nx 150 >50 367, S=3 373, S=4 380, S=5 S, ACCORDING TO SOLAS >50 nx 150 nx 150 >50 FDB2 Nominal with+58 FDL Nominal with+56 FDL Max.1302 FDB2 Max R MIN n*150 n*150 B+2 B GENERAL FDL MODULE ASSEMBLY 361, S=3 365, S=4 370, S=5 >50 nx 150 nx 150 >50 FDB2 Nominal with+58 FDL Nominal with+56 FDL Max.1302 FDB2 Max (FDB2) 9 (FDL) 10 (FDB2) 9 (FDL) Flat bar cross steel L± 2 2 GENERAL FDL DRAWING, TOP 217, S=5 214, S=4 212, S=3 160 S, ACCORDING TO SOLAS 240, BLADES IN OPEN POSITION FDL CIRCULAR, WITH CONNECTION FLANGES Size limitation: FDB2: Nominal Width 2060 x Nominal Height 3260 or Nominal Width 2460 x Nominal Height 2860 FDL Nominal Width 2660 x Nominal Height 2460 S, ACCORDING TO SOLAS FDB2 Nominal height+58 FDL Nominal height+56 >50 nx 150 nx 150 >50 10 (FDB2) 9 (FDL) C FDB2 Max.1604 FDL Max.1202 Flat bar steel Flat bars to be sealed with pyrocryl sealant DETAIL C SCALE 1 : 5 Flat bar steel both side of the damper S Min 3 Max (FDB2) 9 (FDL) 2 367, S=3 373, S=4 380, S=5 Flat bar cross steel Flat bar steel Flat bars to be sealed with pyrocryl sealant S Min 3 Max 10 >50 nx 150 nx 150 >50 FDB2 Nominal with+58 FDL Nominal with+56 FDL Max.1302 FDB2 Max L± 2 Size limitation: nx 150 nx 150 >50 Alternatives FDB2: available on request. Nominal Width 2060 x Nominal Height 3260 Due or to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice. 56 FDB2 Max.1604 FDL Max.1202

10 FDD fire and gas dampers FDD fire and gas dampers are used in offshore and marine ventilation systems. The dampers are typeapproved according to A0 (A60). The dampers can be installed in circular ducts. The dampers have a fusible link and prevent the spread of fire and gases within the ventilation ductwork. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance. The dampers are set from outside and can be installed in any position. An openclosed indicator is visible on the outside of the dampers. Typeapproved by most recognized classification societies: class A0A60 when suitably insulated. Fixed frame of painted, galvanized or stainless steel. Blades of stainless steel. Flanges available as an option. Blades have glassfiber seals (effective up to 300 ºC) and thermalexpansion graphite seals (effective from 150 ºC). Nominal fuse release temperature: 50 ºC, 74 ºC or 100 ºC. Other temperatures available. Very low leakage. Automatic electrical, pneumatic or spring operation system available. Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s. Dimensions and material thickness The dampers meet international standards for circular ducts (Ø mm). Sizes Ø100 and Ø125 are not available in stainless steel. Special flange drilling is available on request. Standard flange size: 27 mm. Frame material thickness: min. 3 mm. FDDEL FDDPNL FDDPNR FDDSP D L R R R R Part Material Finishing Frame Carbon steel Painted or galvanized Frame Stainless steel EN (AISI 304), EN (AISI 316L), EN (AISI 316L) Blades Steel Galvanized Blades Stainless steel EN (AISI 304), EN (AISI 316L), EN (AISI 316L) Bearings Stainless steel EN (AISI 316L) / Bronze bearings optional Shafts Stainless steel EN (AISI 316L) FDDEL FDDPNL FDDPNR FDDSP D S K T N L H A R H A R H A R H A R

11 GENERAL FDD DRAWING (without flanges) GENERAL FDD DRAWING (without flanges) FDD DRAWING (without flanges), TOP ALT. POSITION OF ACTUATOR CLOSED Firedamper FDD HALTON No: XXXX Lahti Finland XXXX OPEN L D R GENERAL FDD DRAWING (without flanges) ALT. POSITION OF ACTUATOR CLOSED Firedamper FDD HALTON No: XXXX Lahti Finland XXXX OPEN GENERAL FDD DRAWING (with flanges) Ø T N pcs Optional flange ACTUATOR H FDD DRAWING (with flanges), TOP L WITHOUT FLANGES L6 ACTUATOR WITHOUT FLANGES R3 R D D K S ALTERNATIVE POSITION OF ACTUATOR R A FDD A0(A60) Fire And Gas Damper FDD DRAWING (with flanges), TOP L WITHOUT FLANGES L6 ACTUATOR WITHOUT FLANGES R3 R

12 UTT shutoff dampers / UTK balancing dampers UTK, UTT Temperature operation range up to +100 C, optionally up to +200 C. Classification of casing leakage EN 1751 class B. UTK Shutoff, balancing, adjustment or control damper with opposed blades. Tightness in closed position meets EN 1751 class 1 requirements. Part Material Note Casing Blades (sandwich design) Galvanized steel Stainless steel EN (AISI 316L) also available Galvanized steel Stainless steel EN (AISI 316L) also available Blade gaskets Silicon Heatproof model: LTE silicon Duct gasket Rubber compound Circular connections Slides bearings Alloy of polyamide and molybdenum sulphide Selflubricated heatproof model stainless steel AISI 316L Drive shaft Galvanized steel Rectangular bar (15x15 mm) UTT Shutoff and balancing damper for outdoor air intake and exhaust air with opposed blades. Blades have thermal insulation. Tightness in closed position meets EN 1751 class 4 requirements (tested size 600x600 mm). Part Material Note Product models and accessories Model with stainless steel EN (AISI316L) design Model with mineralwool (20 mm) insulated casing Model with heatproof design Circular duct connections Several actuator options Dimensions and material thickness The dampers are for rectangular (width B mm and height H mm, 1 mm division) and circular ducts (Ø mm). Nonstandard dimensions and flange drilling are available on request Modular construction sizes up to 4900x4900 mm. Standard frame material thickness: 1 mm. HxW (mm) Qmin (l/s) m3/h Qmax (l/s) m3/h 200x x x x x x W H Q min 1 m/s duct velocity Q max 6 m/s duct velocity 100, 200,..., , 200,..., 2400 WxH x150 Casing Galvanized steel Stainless steel EN (AISI 316L) also available x x200 Blades (sandwich design) Galvanized steel Stainless steel EN (AISI 316L) also available Blade insulation Polyurethane CFCfree Blade gaskets Silicon Heatproof model: LTE silicon Gaskets inside the casing (only Silicon Fixed in an aluminium profile UTT) Duct gasket Rubber compound Circular connections Slides bearings Alloy of polyamide and molybdenum sulphide Selflubricated heatproof model stainless steel AISI 316L Drive shaft Galvanized steel Rectangular bar (15x15 mm) x x x x x x x x x x1250

13

14 BLD nonreturn dampers BLD nonreturn dampers are used in offshore and marine applications to prevent backflow through ventilation ductwork. The dampers do not require an actuator or motor. The dampers can be installed in rectangular or circular ducts, horizontally or vertically. If required, the dampers can easily be set by adjusting the weight of each damper/ installation. Weights for the dampers are available as an option. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance (with weights). Nonstandard dimensions are available on request. Dimensions and material thickness The dampers meet international standards for rectangular (width B and height H mm, 1 mm division) and circular ducts (Ø mm). Nonstandard dimensions are available on request. Modular construction sizes up to 2400x2800 mm are available. Standard frame material thickness: 3 mm. Standard flange width: 27 mm. Blades are made of two sheets of 0.8 mm thickness each. Fixed frame in painted, galvanized or stainless steel. Blades of galvanized or stainless steel. Models for horizontal or vertical installation. Closed damper meets the leakage requirement of NORSOK. Leakage class of closed damper according to EN 1751 class 2 (VTT test report no. RTE4306/04). Blades have silicone seal to lower the leakage through blades. Blades linked and open in parallel. Adjustable by changing the position of counterweights. Counterweights available on request. Standard construction places weights on the righthand side. Weights on the lefthand side available as an option. Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s. ATEX approved. Part Material Finishing Note Frame Carbon steel Painted or galvanized Frame Stainless steel Blades Steel Galvanized Blades Stainless steel Maintenancefree bearings Stainless steel Bronze bearings optional Shafts Stainless steel

15 GENERAL BLD DRAWING 130 thickness 3 mm. Standard flange width 27 mm. Blades made of two sheets, each being 0.8 mm thick ALL BOLT HOLES Ø 12 BOLTS M10x30 BLD DRAWING TOP BLD CIRCULAR, WITH CONNECTION FLANGES RIGHT HAND MODEL 185 IF H= < IF H=> IF H< IF H=>250 H+58 H+4 Min50 nx150 nx AIRFLOW 10 Ø nx150 nx150 Min50 B+4 B+58 BLD NonReturn Damper BLD DRAWING, CIRCULAR CONNECTIONS BLD DRAWING, CIRCULAR CONNECTIONS 34 WIDTH nx150 nx150 Min50 HEIGHT+58 DIAMETER2 nx150 nx IF H= IF H>200 Min50 10 ALL BOLT HOLES Ø 12 BOLTS M10x BLD CIRCULAR, WITH CONNECTION FLANGES 185 IF H< IF H=> AIRFLOW

16 BRD pressure relief dampers BRD pressurerelief dampers are used in offshore and marine applications to prevent backflow through ventilation ductwork. The dampers do not require an actuator or motor. The dampers can be installed in rectangular or circular ducts, horizontally or vertically. The opening pressure can easily be set by adjusting the weight of each damper/ installation. Weights are included in the delivery. Nonstandard dimensions are available on request. Dimensions and material thickness The dampers meet international standards for rectangular (width B mm and height H mm, 1 mm division) and circular ducts (Ø mm). Nonstandard dimensions are available on request. Standard flange width: 27 mm. Flanges and drilling are available according to ISO standards. Modular construction sizes up to 2400x2800 mm. Standard frame material thickness: 3 mm. Blades are made of two sheets of 0.8 mm thickness each. Fixed frame in painted, galvanized or stainless steel. Blades of galvanized or stainless steel. Models for horizontal or vertical installation. Blades have silicone seal to lower the leakage through blades. Available as ATEXapproved. Leakage class of closed damper according to EN 1751 class 2. Tested size 1000x1000 mm. Blades linked and open in parallel. Opening pressure adjusted by changing the position of counterweight(s). Opening pressure range: 30 Pa ~ 150 Pa (up to 300 Pa optional). Counterweights included. Standard construction places weights on the righthand side. Weights on the lefthand side available as an option. Final adjustment of counterweights carried out during commissioning. Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s. Part Material Finishing Frame Carbon steel Painted or galvanized Frame Stainless steel EN (AISI 304), EN (AISI 316L), EN (AISI 316L) Blades Steel Galvanized Blades Stainless steel EN (AISI 304), EN (AISI 316L), EN (AISI L) Bearings Stainless steel EN (AISI 316L) / Bronze bearings optional Shafts Stainless steel EN (AISI 316L)

17

18 HV blast dampers HV blast dampers protect ventilation systems against the effects of vapor and dust cloud explosions. The dampers shield industrial facilities and related buildings against destructive blast forces. The dampers offer higher air flow capacity and increased level of safety as well as flexibility for design of duct systems. The structure of the dampers is corrosionfree, hotdip galvanized steel (AISI316 in the HVSS version). The dampers have springloaded closing blades in a fully welded damper body to close the air passage in case of explosion or sudden increase of overpressure in the HVAC system. The threshold trigger pressure can be adjusted according customer specification. When the blades are closed, they will remain in closed position until they are manually reset. The dampers are approved according ATEX (Ex II 2 G D) for equipment in hazardous environment. Made of galvanized or stainless steel, AISI316. Fully welded damper body made of 5mm steel. Closing blades and shafts with stainlesssteel bearings. Adjustable trigger mechanism. Fragment grill. Flow guides. General drawing The dampers are dimensioned according to the duct size or wall opening. Standard sizes: 300x300 mm 500x500 mm 700x700 mm 1000x1000 mm 1500x1500 mm The dampers are also available in custom sizes with steps of 100 mm in each direction between the limits. Type Dimensions (mm) and Weights (kg) A B C D E F G H Depth HV300x HV500x HV700x HV 1000x HV 1500x

19 PRA air flow adjustment dampers Airflow balancing, adjustment and measurement unit. Manual adjustment, no tools required. Accurate airflow measurement based on flow nozzle principle. Reduced sound generation due to conical adjustment section. Temperature operation range from 30 C to +70 C. Selflocking adjustment mechanism; position can be ensured with locking screw. Duct cleaning enabled through the unit up to size 315. Adjustment position marker indicates proper position (e.g. repositioning after cleaning). Inlet and outlet spigots have integral rubber gaskets. Application option as supply air jet nozzle for air diffusion in large spaces. Classification of casing leakage EN 1751 class C. Part Material Note Casing Galvanized steel Blades Galvanized steel Operating mechanism ABS and PBT classic Sizes Duct gaskets 1Cpolyurethane hybrid Measurement taps Polyurethane (mm) Qmin (l/s) Q min 1 m/s duct velocity Q max 6 m/s duct velocity m3/h Qmax m3/h PRA PRA NS NS H

20 Brazil T: /4244 E: France La Ciotat T: E: France Grasse T: E: Germany T: E: India T: E: Italy T: E: The Netherlands (HQ) T: E: The Netherlands (Rotterdam) T: E: Norway T: E: Peoples Republic of China T: E: Peoples Republic of China T: E: Poland T: E: Romania T: E: Russia T: +7 (4012) E: Singapore T: E: South Korea T: E: Spain T: E: Sweden T: E: Turkey T: E: UAE (Abu Dhabi) T: E: UAE (Dubai) T: E: USA Fort Lauderdale, Florida T: E: USA Houma, Louisiana T: E: Heinen & Hopman encourages a more sustainable world. By providing ecofriendly solutions and services we offer our clients the option of reducing energy consumption and thus CO2 emissions. Visit greenmanifest.info for more information.

products 22 º C Ventilation Air Conditioning Refrigeration Inside PROVIDED BY HEINEN & HOPMAN

products 22 º C Ventilation Air Conditioning Refrigeration Inside PROVIDED BY HEINEN & HOPMAN products > Dampers - SF OUTSIDE 35 C HUMIDITY 90% 22 º C Inside PROVIDED BY HEINEN & HOPMAN Heating Ventilation Air Conditioning Refrigeration dampers Fire and smoke dampers Fire and smoke dampers prevent

More information

products 22 º C Ventilation Air Conditioning Refrigeration Inside PROVIDED BY HEINEN & HOPMAN

products 22 º C Ventilation Air Conditioning Refrigeration Inside PROVIDED BY HEINEN & HOPMAN products > Duct fan WMR OUTSIDE 35 C HUMIDITY 90% 22 º C Inside PROVIDED BY HEINEN & HOPMAN Heating Ventilation Air Conditioning Refrigeration To stand by our clients in the harshest environments WMR duct

More information

products 22 º C Ventilation Air Conditioning Refrigeration Self Contained Units - 90MA self-contained marine air conditioning unit Inside

products 22 º C Ventilation Air Conditioning Refrigeration Self Contained Units - 90MA self-contained marine air conditioning unit Inside products > Self Contained Units - 90MA self-contained marine air conditioning unit OUTSIDE 35 C HUMIDITY 90% 22 º C Inside PROVIDED BY HEINEN & HOPMAN Heating Ventilation Air Conditioning Refrigeration

More information

PART MATERIAL FINISHING. Frame Carbon steel Painted or galvanised

PART MATERIAL FINISHING. Frame Carbon steel Painted or galvanised FDO A0(A0) Fire Damper FDO in picture with flanges (available as an option) Halton FDO fire dampers are type-approved class A0(A0) fire dampers for use in marine and offshore ventilation systems. The FDO

More information

products 22 º C Ventilation Air Conditioning Refrigeration MGO Cooler - The reliable solution towards lower sulphur emissions Inside

products 22 º C Ventilation Air Conditioning Refrigeration MGO Cooler - The reliable solution towards lower sulphur emissions Inside products > MGO Cooler - The reliable solution towards lower sulphur emissions OUTSIDE 35 C HUMIDITY 90% 22 º C Inside PROVIDED BY HEINEN & HOPMAN Heating Ventilation Air Conditioning Refrigeration The

More information

UTK/UTT - Multi-blade Damper. Halton UTK, UTT. Multi-blade Damper

UTK/UTT - Multi-blade Damper. Halton UTK, UTT. Multi-blade Damper Halton UTK, UTT Multi-blade Damper Temperature operation range up to +100 C, optionally up to +200 C Galvanised steel design Classification of casing leakage EN 1751 class B UTK: Shut-off, adjustment,

More information

FDR - Fire Damper for Rectangular and Circular Ducts. Halton FDR. Fire Damper for Rectangular and Circular Ducts

FDR - Fire Damper for Rectangular and Circular Ducts. Halton FDR. Fire Damper for Rectangular and Circular Ducts Halton FDR Fire Damper for Rectangular and Circular Ducts Type-approved and compliant with the EN 1366-2 and EN 13501-3 standards. Design for installation in separating concrete and masonry walls and ceilings

More information

Fire & Gas Dampers. Fire & Gas Dampers are used in ventilation systems to prevent the spread of flame and/or smoke between divisions.

Fire & Gas Dampers. Fire & Gas Dampers are used in ventilation systems to prevent the spread of flame and/or smoke between divisions. Fire & Gas Introduction Fire & Gas are used in ventilation systems to prevent the spread of flame and/or smoke between divisions. Authority/Certification Wozair manufacture three types of Fire & Gas Damper

More information

DSA HIGH EFFICIENCY DROPLET SEPARATOR DROPLET SEPARATOR DSA. With heated vanes

DSA HIGH EFFICIENCY DROPLET SEPARATOR DROPLET SEPARATOR DSA. With heated vanes DSA MATERIALS HIGH EFFICIENCY DROPLET SEPARATOR With heated vanes PART MATERIAL FINISHING Droplet separator Aluminium EN AW 6060 - Frame Aluminium EN AW 5754 Painted RAL9010, C5-M as standard* Frame Heating

More information

DAMPERS LSS - R. N-6230 SYKKYLVEN, NORWAY TEL FAX

DAMPERS LSS - R. N-6230 SYKKYLVEN, NORWAY TEL FAX DAMPERS LSS - R LSS / SOD circular single blade shut off damper SSVent rectangular multiblade shut off damper S.Ventil R1OVL circular single blade weather tight damper/valve RD circular regulating damper

More information

PTS - Single-Blade Damper. Halton PTS. Single-Blade Damper

PTS - Single-Blade Damper. Halton PTS. Single-Blade Damper Halton PTS Single-Blade Damper Shut-off, adjustment, balancing or control damper Casing leakage classification: EN 1751, Class C Casing and damper blade made of galvanised steel Tightness classification

More information

Shut-off dampers. Type AK-Ex. For low-leakage shut-off of volume flows in potentially. explosive atmospheres (ATEX) PD AK-Ex 1.

Shut-off dampers. Type AK-Ex. For low-leakage shut-off of volume flows in potentially. explosive atmospheres (ATEX) PD AK-Ex 1. X X testregistrierung Shut-off dampers Type ATEX-compliant parts and units For low-leakage shut-off of volume flows in potentially explosive atmospheres (ATEX) Circular shut-off dampers for shutting off

More information

Fire/combustion gas damper EKO-JBL

Fire/combustion gas damper EKO-JBL Fire/combustion Description The fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting. The damper is designed

More information

series FSD-FLD Fire and smoke dampers UL Approval

series FSD-FLD Fire and smoke dampers UL Approval series FSD-FLD Fire and smoke dampers UL Approval www.koolair.com Series FSD-FLD 1 Fire and smoke dampers UL Approval FSD-B-U / FSD-A-U and FLD-S-U / FLD-S-UD CONTENTS Description FSD-B-U / FSD-A-U 2 Construction

More information

Fire/combustion gas damper EKO-JBG

Fire/combustion gas damper EKO-JBG Fire/combustion EKO-JBG Description The EKO-JBG fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting.

More information

MOTORIZED VOLUME DAMPER

MOTORIZED VOLUME DAMPER MOTORIZED VOLUME DAMPER 1 a perfect partner in performance... Our Product Ranges Dampers 1 Fire Dampers 2 Fire / Smoke Dampers 3 Volume Control Dampers 4 Motorized Control Dampers 5 Pressure Relief Dampers

More information

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX) X X testregistrierung CAV controllers Type Adjustment scale For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX) Rectangular, mechanical self-powered

More information

Type AK-Ex FOR LOW-LEAKAGE SHUT-OFF OF VOLUME FLOWS IN POTENTIALLY EXPLOSIVE ATMOSPHERES (ATEX)

Type AK-Ex FOR LOW-LEAKAGE SHUT-OFF OF VOLUME FLOWS IN POTENTIALLY EXPLOSIVE ATMOSPHERES (ATEX) Homepage > Products > Control units > Shut-off and restriction > Shut-Off Devices > Type AK-Ex Type AK-Ex FOR LOW-LEAKAGE SHUT-OFF OF VOLUME FLOWS IN POTENTIALLY EXPLOSIVE ATMOSPHERES (ATEX) Circular shut-off

More information

For installation into ductwork

For installation into ductwork X X testregistrierung Non-return dampers Type For installation into ductwork Non-return dampers prevent unwanted airflows against the intended airflow direction when the system is not in operation Maximum

More information

(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm.

(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm. Fire damper pl-30 General characteristics Application Fire dampers prevent fire and smoke from spreading through ventilation ducts in buildings. The dampers are intended for use inside buildings and are

More information

Combustion gas damper EKO-JB

Combustion gas damper EKO-JB EKO-JB Description The EKO-JB combustion is a Class E6 type-approved damper intended to prevent the spread of combustion gases in ventilation ducting that penetrates fire rated compartment wall or floor

More information

INDEX. Chapter1 6. air master. Volume Control Dampers

INDEX. Chapter1 6. air master. Volume Control Dampers Chapter1 6 INDEX 1 Volume control damper...:avcd...16.1 Standard sizes...16.2 Fixing details...16.2 How to order...16.2 Performance chart...16.3 2. Circular volume control damper....:avcd-c....16.4 Standard

More information

EnergyShield ES. Air Control and Shut off Dampers. Dampers Controls Fancoils. Ruskin Air Management Limited

EnergyShield ES. Air Control and Shut off Dampers. Dampers Controls Fancoils. Ruskin Air Management Limited April 11 EnergyShield ES EnergyShield ES Air Control and Shut off Dampers Features Dampers suitable for systems requiring air control and low closed blade leakage characteristics. Low torque characteristics.

More information

U X Y W L. Gear wheels. Linkage. In option: Stainless steel AISI 304L , AISI 316L or painted steel (standard RAL)

U X Y W L. Gear wheels. Linkage. In option: Stainless steel AISI 304L , AISI 316L or painted steel (standard RAL) CODIFICATION CONSTRUCTION Commercial dampers of the U range are designed to control or shut off ductworks with airtightness classifi cation going from non-classifi ed to class 4 according to EN1751. The

More information

Motorized Fire Dampers

Motorized Fire Dampers Model : OMFD-611 (Fusible link and spring return actuator) GI steel sheet construction In accordance with UL555 & UL555S suitable for installation in walls and partitions having rating 2 Hrs. Static and

More information

VOLUME CONTROL / REGULATING DAMPERS

VOLUME CONTROL / REGULATING DAMPERS VOLUME CONTROL / REGULATING S PRODUCT RANGE Model Range Includes A - Multi-Leaf. (Flanged - Rectangular Duct) B - Multi-Leaf. (Slip joint / Spigot - Rectangular Duct) C - Multi-Leaf. (Slip joint / Spigot

More information

Zero Leakage Isolation Damper

Zero Leakage Isolation Damper SPECIFICATION The damper casing is formed from 3.0 mm thick sheet steel into a rigid channel section to ensure proper alignment of blades and shafts. Where circular dampers are required, additional spigot

More information

A Complete Line of Quality Products for Marine Applications

A Complete Line of Quality Products for Marine Applications american warming and ventilating A Mestek Company A Complete Line of Quality Products for Marine Applications 1 About AWV Marine Dampers At American Warming and Ventilating, we are committed to design

More information

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1 X X testregistrierung CAV controllers Type Adjustment scale ATEX-Zertifizierung For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) Circular, mechanical self-powered

More information

U X Y W L. Gear wheels. Linkage. In option: Stainless steel AISI 304L , AISI 316L or painted steel (standard RAL)

U X Y W L. Gear wheels. Linkage. In option: Stainless steel AISI 304L , AISI 316L or painted steel (standard RAL) Commercial dampers of the U range are designed to control or shut off ductworks with airtightness classifi cation going from non-classifi ed to class 4 according to EN1751. The handling and installation

More information

Actionair Control and Shut Off Dampers

Actionair Control and Shut Off Dampers December 2003 Air/Shield (Incorporating Energy/Shield ES35 & ES36) Actionair Control and Shut Off Dampers Air/Shield Aerofoil Air Control Dampers Air/Shield Aeroseal Air Control and Shut-Off Dampers Energy/Shield

More information

Introduction to Johnson Controls Dampers

Introduction to Johnson Controls Dampers Damper and Actuator Product Guide 268.1 Damper Engineering Section Product Bulletin Issue Date 1297 Introduction to Johnson Controls Dampers For over 100 years, Johnson Controls has been the industry leader

More information

KWT GALLEY WATER WASH HOOD GALLEY WATER WASH HOOD KWT. With supply air and Capture Jet technology

KWT GALLEY WATER WASH HOOD GALLEY WATER WASH HOOD KWT. With supply air and Capture Jet technology KWT GALLEY WATER WASH HOOD With supply air and Capture Jet technology APPLICATIONS Halton KWT is a galley water wash hood for use in marine & offshore applications. The highly efficient KWT hood uses Halton

More information

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades X X testregistrierung Type Vertical air discharge Horizontal air discharge For large temperature differences in heating mode, high penetration of air, with adjustable air control blades Circular ceiling

More information

RETROFIT TERMINAL UNITS

RETROFIT TERMINAL UNITS GENERAL PROUCT OVERVIEW Retrofit Terminal s Convert Constant Air Volume Systems to Variable Air Volume. Convert Constant Volume ual uct Systems to Variable Air Volume. Convert Multizone Systems to Variable

More information

Combustion gas damper EKO-SRB

Combustion gas damper EKO-SRB Combustion EKO-SRB Description The EKO-SRB combustion is a Class E60 type-approved damper intended to prevent the spread of combustion gases in ventilation ducting that penetrates fire rated compartment

More information

Variable Air Volume Dampers

Variable Air Volume Dampers OVAV 2000 SERIES OPTIMA VAV DAMPERS Overview OPTIMA make Variable Air Volume (OVAV) box is a part of an Air Conditioning system. It is located inside the duct work. VAV Dampers are designed to control

More information

7/S5 FIRE DAMPER FD40. v 2.9 (en)

7/S5 FIRE DAMPER FD40. v 2.9 (en) 7/S v.9 (en) FIRE DAMPER FD0 www.klimaoprema.hr 69 FIRE DAMPER - FDC TABLE OF CONTENTS FIRE DAMPER FD0 7 FIRE CLASSIFICATION 7 SELECTION DIAGRAM 7 ORDERING KEY 7 DAMPER MODELS 7 FD0-M rectangular fire

More information

PLENUM WITH ABSOLUTE FILTER HOLDER FOR SUPPLY GRILLES

PLENUM WITH ABSOLUTE FILTER HOLDER FOR SUPPLY GRILLES PLENUM WITH ABSOLUTE FILTER HOLDER FOR SUPPLY GRILLES TECHNICAL CHARACTERISTICS PP30 OVERVIEW : The PP 30F (rear connection) and PP 31F (lateral connection) are employed for the diffusion of air using

More information

PK-I-Ex. Fire resistance class Circular: EI60S, EI90S, EI120S Square: EI90S, EI120S. Systemair Fire Dampers for Explosive Areas.

PK-I-Ex. Fire resistance class Circular: EI60S, EI90S, EI120S Square: EI90S, EI120S. Systemair Fire Dampers for Explosive Areas. Systemair Fire Dampers for Explosive Areas Fire resistance class Circular: EI60S, EI90S, EI120S Square: EI90S, EI120S www.systemair.com Description Fire damper (hereafter referred to as damper) is a fire

More information

METAL SEATED NELDISC BUTTERFLY VALVES, SERIES L12

METAL SEATED NELDISC BUTTERFLY VALVES, SERIES L12 METAL SEATED NELDISC BUTTERFLY ALES, SERIES L12 2 L12 20 Issue 4/99 SIZES AND PRESSURE RATINGS Size range DN 80-600, 3" - 24". Pressure ratings PN 10, 16, 25 and ANSI 150. FEATURES Third-generation, metal-to-metal

More information

Volume Flow Limiters Type VFL

Volume Flow Limiters Type VFL X X Volume Flow Limiters Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical self-powered

More information

DHL - HEPA terminal filter diffuser DHL. HEPA terminal filter diffuser

DHL - HEPA terminal filter diffuser DHL. HEPA terminal filter diffuser DHL HEPA terminal filter diffuser Low turbulent flow diffuser (LTF), also suitable for exhaust Installation flush to the ceiling, also suitable for wall installation A measurement access through the diffuser

More information

Volume Control Dampers. Series LF upvc-vcd High performance plastic volume control dampers. Incorporating

Volume Control Dampers. Series LF upvc-vcd High performance plastic volume control dampers. Incorporating Volume Control Dampers Incorporating Series LF upvc-vcd 2.76 m 3 /hr/m 2 leakage at 50 Pa, over 70% better than required by Part L of Building Regulations Corrosion resistant, perfect for chlorinated atmospheres

More information

Fire damper FK120/FK90 TECHNICAL DATA

Fire damper FK120/FK90 TECHNICAL DATA Fire damper FK120/FK90 TECHNICAL DATA 2 Fire damper FK120/FK90 Figure 1 ER1 Figure 2 ER3 The rectangular fire damper FK120/FK90 is available both as motorized and with fuse. The damper casing is manufactured

More information

Fire Dampers Catalogue

Fire Dampers Catalogue Fire s Catalogue DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) CRFD - Type A, B, CR & CO Rectangular, Round & Flat Oval UL 555 Classified 2013 For Use in Static & Dynamic Systems 3 Hour Rating Made in

More information

JVR CONTENTS. Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6

JVR CONTENTS. Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6 1 CONTENTS Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6 2 VAV regulator, model Description The variable air volume regulators

More information

NYBORG AS N-6230 SYKKYLVEN, NORWAY TEL FAX

NYBORG AS N-6230 SYKKYLVEN, NORWAY TEL FAX NYBORG AS N-6230 SYKKYLVEN, NORWAY TEL +47 70 25 40 80 - FAX +47 70 25 29 08 office@nyborgfan.com - www.nyborgfan.com OPERATION AND MAINTENANCE NYBORG CIRCULAR FIRE DAMPER TYPE BSS 500-400 R-LD Version

More information

M A D E L. FOK-EIS-180 Fire dampers CE

M A D E L. FOK-EIS-180 Fire dampers CE M A D E L EN 60: FOK-EIS-80 Fire dampers CE The fire dampers FOK-EIS-80 work as a separator between two sectors of fire and ensure the same fire resistance that the structural elements of compartmentalisation,

More information

BC 4.3. Gas Tight Dampers GTD-GB40-B-E LISTED

BC 4.3. Gas Tight Dampers GTD-GB40-B-E LISTED BC 4.3 Gas Tight Dampers GTD-GB40-B-E Table Of Contents S. No Description Page No 1 Gas Tight Damper with Electric Drive 1 2 Electric Drive - Details 2-3 3 Gas Tight Damper with Pneumatic Drive 4 4 Pneumatic

More information

Standard Product Program. AirLINE & AirLINE Quick Type 8640 & Type 8644

Standard Product Program. AirLINE & AirLINE Quick Type 8640 & Type 8644 Standard Product Program AirLINE & AirLINE Quick Type 8640 & Type 8644 2 Bürkert AirLINE standard product program 3 The AirLINE product program The standard product program provides a supplement to the

More information

SafidDampers SPK Description. Standard Construction SPK ( Flange Type )

SafidDampers SPK Description. Standard Construction SPK ( Flange Type ) ( Flange Type ) SPK 30-300 Description SPK 30 - Series The single and multi-leaf s with extruded aluminum airfoil blades are designed for quite, efficient and reliable air volume control in air conditioning

More information

SafidDampers SPK Standard Construction SPK Description SPK ( Flange Type )

SafidDampers SPK Standard Construction SPK Description SPK ( Flange Type ) ( Flange Type ) SPK 30-100 Standard Construction FRAME: 160mm x 30mm x 1.5mm (16 Ga.) galvanized steel formed channel for flange connection. BLADES: 250mm max. width, 1.5mm (16 Ga.) galvanized steel. FINISH:

More information

Front panel Perforated galvanised steel Stainless steel AISI 316 as option Casing Galvanised steel Stainless steel AISI 316 as option

Front panel Perforated galvanised steel Stainless steel AISI 316 as option Casing Galvanised steel Stainless steel AISI 316 as option ZSC - Halton Zen Semi-Circle Displacement ventilation unit Capacity for wide supply airflow range. Uniform supply air distribution is achieved through small perforations, providing optimal conditions in

More information

AL-Maraj Central A/C Systems Accessories Mfg Co.

AL-Maraj Central A/C Systems Accessories Mfg Co. AL-Maraj is one of the renowned Manufacturer, Stockist and Supplier of all kinds of HVAC products, Ducting accessories, Pipe support system, Electro-mechanical and A/C Accessories in U.A.E since 2000.

More information

Actionair A-60 Marine Fire Damper Designed for inclusion in Marine and Offshore Projects

Actionair A-60 Marine Fire Damper Designed for inclusion in Marine and Offshore Projects March 06 A-60 Marine Fire Dampers Tests and Approvals A60 Fire Rated. Lloyds Register of Shipping Approved. Marine Equipment Directive compliant. USCG Approved. Germanischer Lloyds Approved. American Bureau

More information

DFB - Conical Ceiling Diffuser. Halton DFB. Conical Ceiling Diffuser

DFB - Conical Ceiling Diffuser. Halton DFB. Conical Ceiling Diffuser Halton DFB Conical Ceiling Diffuser Horizontal air supply, suitable also for exhaust Installation flush to the ceiling, light-weight aluminium design Circular duct connection with rubber gasket All sizes

More information

TYPE EK-EU SMOKE CONTROL DAMPER

TYPE EK-EU SMOKE CONTROL DAMPER Homepage > PRODUCTS > Fire and Smoke Protection > Smoke Control Damper > Type EK-EU TYPE EK-EU SMOKE CONTROL DAMPER WITH TROXNETCOM AS AN OPTION CE COMPLIANT ACCORDING TO EUROPEAN REGULATIONS EK-EU WITH

More information

Homepage > Products > External louvres - louvre blades > Mechanically self-powered dampers > Non-return dampers > Type KUL.

Homepage > Products > External louvres - louvre blades > Mechanically self-powered dampers > Non-return dampers > Type KUL. Homepage > Products > External louvres - louvre blades > Mechanically self-powered dampers > Non-return dampers > Type KUL Type KUL FOR INSTALLATION INTO DUCTWORK Non-return dampers prevent unwanted airflows

More information

RVP-R- VAV controller. In explosion-proof version

RVP-R- VAV controller. In explosion-proof version VAV controller In explosion-proof version RVP-R- SMAY LLC / 29 Ciep³ownicza St. / 31-587 Cracow / Poland tel. +48 12 378 18 00 / fax. +48 12 378 18 88 / e-mail: info@smay.eu Intended use VAV control units

More information

DD Series. Duct Regulating Dampers M A N U F A C T U R E R S O F A I R, F I R E A N D S M O K E C O N T R O L P R O D U C T S. Two blade options.

DD Series. Duct Regulating Dampers M A N U F A C T U R E R S O F A I R, F I R E A N D S M O K E C O N T R O L P R O D U C T S. Two blade options. Duct Regulating Dampers Two blade options. DW144 compliant Four case options Three control options Nylon bushes as standard Suitable for vertical and horizontal ducted systems. M A N U F A C T U R E R

More information

Regulation and shut-off damper SPB and SPC

Regulation and shut-off damper SPB and SPC SPB / SP -type multi leaf damper is a robust and reliable regulation and shut-off device to be used for different purposes in air handling systems. SPB SP.01.13 Area of application Multi leaf dampers are

More information

HCD-230 Industrial Control Damper

HCD-230 Industrial Control Damper Application and Design Model is a heavy duty industrial control damper with a flanged frame. It is designed to control airflow and provide shut off in HVAC or industrial process control systems. A variety

More information

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K .1 X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical

More information

HEAVY DUTY BALANCE AND CONTROL DAMPER B A L A N C E C O N T R O L SERIES

HEAVY DUTY BALANCE AND CONTROL DAMPER B A L A N C E C O N T R O L SERIES HEAVY DUTY BALANCE AND CONTROL DAMPER B A L A N C E C O N T R O L HD SERIES MANUFACTURERS OF AIR/FIRE/SMOKE CONTROL PRODUCTS Product Description and Features Introduction The HD Series Multi-Leaf Volume

More information

CFSD Series. Product Description

CFSD Series. Product Description COMBINATION FIRE AND SMOKE DAMPER 1-1/2 HR LEAKAGE RESISTANCE CLASS II 250 O F FILE NO: R22165 Product Description Combination Fire / Smoke dampers provide an automatic means of localizing areas of smoke

More information

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction. Application and Design Model is a heavy duty industrial control damper with a flanged frame. It is designed to control airflow and provide shut off in HVAC or industrial process control systems. A variety

More information

Fan - Powered Terminal Unit Series Flow

Fan - Powered Terminal Unit Series Flow 5/22/M/1 Fan - Powered Terminal Unit Series Flow Type TFP Trox (Malaysia) Sdn Bhd 20 Persiaran Bunga Tanjung 1 Senawang Land Industrial Park 70400 Seremban Negeri Sembilan Darul Khusus Malaysia Telephone

More information

2.6. Air Flow Control Valve Type PRD

2.6. Air Flow Control Valve Type PRD 2.6. Air Flow Control Valve Type PRD Page 1/10 Air Flow Control Valve, Type PRD Page 2/10 Air Flow Control Valve Type PRD Description and Design The PRD remains the air valve of choice for critical heating,

More information

XeteX, Inc. All Rights Reserved.

XeteX, Inc. All Rights Reserved. Model XC Indoor or outdoor mounted, simple, in-case aluminum flat plate exchanger with options for frost control. Ideal for inline installations: in duct-work systems, in built-up units, or in modular

More information

HFB - Airflow Management Damper HFB. Airflow Management Damper. Product models and Accessories

HFB - Airflow Management Damper HFB. Airflow Management Damper. Product models and Accessories HFB Airflow Management Damper Control damper for different airflow and duct pressure control applications Pressure-independent operation Galvanised steel design Circular duct connection equipped with integrated

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

C O L M A N. Air Distribution JET DIFFUSERS DCJ SERIES DCJ SERIES

C O L M A N. Air Distribution JET DIFFUSERS DCJ SERIES DCJ SERIES C O L M A N Air Distribution E N G I N E E R E D A I R P R O D U C T S JET DIFFUSERS DCJ SERIES DCJ SERIES DCJ SERIES JET DIFFUSERS Application Colman s DCJ jet diffuser has been designed to supply cooled

More information

7/S1 FIRE DAMPER PPZEN. v 2.5 (en)

7/S1 FIRE DAMPER PPZEN. v 2.5 (en) 7/S1 v.5 (en) FIRE DAMPER PPZEN www.klimaoprema.hr 39 TABLE OF CONTENTS Product description... Range... Fire classification according to EN 13501-3... Operating mechanisms and dimensions... Operating manual...

More information

Particle Filter Box FKU

Particle Filter Box FKU Particle Filter Box FKU Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telephone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980 - 200 info@schako.de www.schako.de Contents Description...3 Construction...

More information

Blade Features. AirShield Control and Shut Off Dampers. AirShield

Blade Features. AirShield Control and Shut Off Dampers. AirShield April 2011 AirShield AirShield AirShield Aerofoil Air Control Dampers AirShield Aeroseal Air Control and Shut Off Dampers AirShield Features and Design Guide Opposed blade dampers suitable for systems

More information

HFB - Airflow Management Damper. Halton HFB. Airflow Management Damper

HFB - Airflow Management Damper. Halton HFB. Airflow Management Damper Halton HFB Airflow Management Damper Control damper for different airflow and duct pressure control applications Pressure-independent operation Galvanised steel design Circular duct connection equipped

More information

SINGLE DUCT TERMINAL UNITS

SINGLE DUCT TERMINAL UNITS www.igcaire.com SINGLE DUCT TERMINAL UNITS Direct Digital Control, Pressure Independent FEATURES 22 Gauge Galvanized Steel Casing Construction with a 20 Gauge Casing Option that Provides Strength and Product

More information

VAV Terminal Units SDS

VAV Terminal Units SDS VAV Terminal Units SDS VAV Terminal Units SDS STEKON SDS; controls the volume of conditioned air into an occupied space in response to a thermostat or Building Management System control signal with minimal

More information

Technical information

Technical information 6-8 Application Rectangular NK and NL types are pressure-independent VAV and CAV air volume control terminals. The terminals are designed particularly for systems with large air volumes and duct sizes

More information

VC Series. Volume Control Dampers M A N U F A C T U R E R S O F A I R, F I R E A N D S M O K E C O N T R O L P R O D U C T S

VC Series. Volume Control Dampers M A N U F A C T U R E R S O F A I R, F I R E A N D S M O K E C O N T R O L P R O D U C T S V41706 VC Series Volume Control Dampers Roll formed steel blades with three material options DW144 compliant Flanged models with 65mm deep mechanically fixed casings Rectangular spigotted models with 85mm

More information

SentronicPLUS IO-Link CLASS A Electronic Pressure Regulator. Installation Manual

SentronicPLUS IO-Link CLASS A Electronic Pressure Regulator. Installation Manual SentronicPLUS IO-Link CLASS A Electronic Pressure Regulator Installation Manual Sentronic PLUS ASCO NUMATICS Sentronic PLUS Electronic Pressure Regulator Sentronic PLUS is a 3-way proportional valve with

More information

SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS

SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS 96 97 SD SERIES SD for Use in Dynamic Systems Types Galvanized Steel Construction as Standard.. Sleeve Type, Model: SD - 0-00. Circular Type, Model: SD - 50-00. Oval Type, Model: SD - 60-00

More information

DVAX-ARS. Roof-mounted unit for mechanical smoke extract

DVAX-ARS. Roof-mounted unit for mechanical smoke extract Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans DVAX- Roof-mounted unit for mechanical smoke extract 2 DVAX DVAX- Roof-mounted axial fan unit

More information

NGS. Dual-Magnet Float Switch. Pressure: up to 25 bar. Density: > 0.7 kg/dm 3. High switch capacity. Material: stainless steel 1.

NGS. Dual-Magnet Float Switch. Pressure: up to 25 bar. Density: > 0.7 kg/dm 3. High switch capacity. Material: stainless steel 1. Dual-Magnet Float Switch measuring monitoring analysing NGS Pressure: up to 5 bar O O Medium temperature: up to 50 C Density: > 0.7 kg/dm 3 High switch capacity O O Connection: square flange, DIN flange,

More information

USS - External Louvre. Halton USS. External Louvre

USS - External Louvre. Halton USS. External Louvre Halton USS External Louvre External louvre for air intake and exhaust to prevent rain, snow, leaf and animal ingress Rainwater ingress penetration efficiency of approx. 95% (USS/I) Operation based on special

More information

KWF Water Wash Canopy with Supply Air

KWF Water Wash Canopy with Supply Air KWF Water Wash Canopy with Supply Air SCHLIEREN THERMAL IMAGING SYSTEM Photographer: Matti Lehto The KWF is a highly effective kitchen ventilation canopy for the removal of contaminated air and excess

More information

Blast Protection Damper

Blast Protection Damper Protection Damper plate shown as transparent height width 250mm wide 6.35mm thick blast plate bolted to damper frame 178mm 250mm standard depth 76mm standard flange Application The damper is designed for

More information

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE FIRE SAFETY AIR MANAGEMENT FIRE DAMPERS ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE 2 ETPR-E-1 Fire damper Technical catalogue Fire and smoke damper ETPR-E-1 is used as a closing device for preventing the

More information

7/S6 FIRE DAMPER FDC40. v 2.9 (en)

7/S6 FIRE DAMPER FDC40. v 2.9 (en) 7/S6 v.9 (en) FIRE DAMPER FDC0 www.klimaoprema.hr 8 TABLE OF CONTENTS FIRE DAMPER FDC0 87 FIRE CLASSIFICATION 87 SELECTION DIAGRAM 88 ORDERING KEY 88 DAMPER MODELS 89 FDC0-M cylindrical fire damper with

More information

Stainless Steel Chimneys Ducts and Fittings for Air Conditioning & Ventilation

Stainless Steel Chimneys Ducts and Fittings for Air Conditioning & Ventilation Stainless Steel Chimneys Ducts and Fittings for Air Conditioning & Ventilation ATRITUBE HVAC PRODUCTS Our facilities are located in the industrial area of Sindos, Thessaloniki, Greece. Since 2004 we have

More information

WGA Long throw nozzle grille

WGA Long throw nozzle grille Technical documentation WGA Long throw nozzle grille Contents Function and use... 2 Models... 2 Processing... 3 Accessories... 3 Models and dimensions... 4 Quick selection... 12 Installation situation...

More information

Extraction arms for every type of application

Extraction arms for every type of application 1 Extraction arms for every type of application 2 Improved workspaces within arm s reach A workspace free from dust, hazardous particles, fumes and exhaust is good in many ways. It improves the working

More information

Marine Fire and Gas Dampers

Marine Fire and Gas Dampers M 3.2/2/EN/ 2 Marine Fire and Gas Dampers Type JFD Telephone + 6 06-678 8188 Telefax + 6 06-678 8288 / 388 E-mail enquiry@troxapo.com www.troxapo.com Contents Description Description 2 Accessories 6 Construction;

More information

Ventilation grilles for installation into walls, sills or rectangular

Ventilation grilles for installation into walls, sills or rectangular X X testregistrierung Ventilation grilles for installation into walls, sills or rectangular ducts Type Ventilation grilles, made of aluminium, with fixed horizontal blades also for horizontal runs Single

More information

Fire Damper. Grilles Diffusers Dampers Louvers VAV Boxes Sound Attenuators. Spectrum Industries

Fire Damper. Grilles Diffusers Dampers Louvers VAV Boxes Sound Attenuators. Spectrum Industries Fire Damper A Wide Range of High Quality Air Distribution Products. Grilles Diffusers Dampers Louvers VAV Boxes Sound Attenuators Spectrum Industries Fire Damper Application Fire damper are required by

More information

FORGED STAINLESS STEEL Rack And Pinion Actuator S Series

FORGED STAINLESS STEEL Rack And Pinion Actuator S Series FORGED STAINLESS STEEL Rack And Pinion Actuator S Series The Air Torque S Series stainless steel actuators are a corrosion resistant rack and pinion actuator particularly engineered for corrosive environments

More information

Volume Control Dampers. Series HVC-VCD Aluminium volume control dampers. Incorporating. Excellent general purpose volume control damper

Volume Control Dampers. Series HVC-VCD Aluminium volume control dampers. Incorporating. Excellent general purpose volume control damper Volume Control Dampers Incorporating Series HVC-VCD Excellent general purpose volume control damper Lightweight aluminium construction Fully protected linkage system positioned outside of airstream Very

More information

Systemair Fire Dampers

Systemair Fire Dampers Systemair Fire Dampers Fire resistance class EI60S; EI90S and EI120S www.systemair.com As standard, all fire dampers are designed and certified to comply with EI-S performance attributes. fire dampers

More information

Positive Seal Damper Blades with Vinyl Gaskets 2.5" SERIES 3000 SIDE MOUNT - NO FLANGE ORDERING METHOD FOR BACKDRAFT & MOTORIZED BACKDRAFT DAMPERS

Positive Seal Damper Blades with Vinyl Gaskets 2.5 SERIES 3000 SIDE MOUNT - NO FLANGE ORDERING METHOD FOR BACKDRAFT & MOTORIZED BACKDRAFT DAMPERS BACKDRAFT DAMPERS BLADE OPTION: SR: 0.016-0.020 roll formed aluminum with vinyl gasket - used with fan motors under 1 HP SE: 0.05 extruded aluminum with vinyl gasket - used with fan motors over 1 HP Positive

More information