04.02 SPLICES AUTOMATIC SPLICE INSTALLATION ONE PIECE COMPRESSION SPLICE SPLICING SLEEVES AND DIE SIZES FOR ALUMINUM AND COPPER CONDUCTORS

Size: px
Start display at page:

Download "04.02 SPLICES AUTOMATIC SPLICE INSTALLATION ONE PIECE COMPRESSION SPLICE SPLICING SLEEVES AND DIE SIZES FOR ALUMINUM AND COPPER CONDUCTORS"

Transcription

1 4. GENERAL INSTALLATION GUIDE FOR CONNECTORS 4. INSTALLATION GUIDE FOR CONNECTORS 4.4 ELECTRIC CONTACT INHIBITORS 4.6 CONDUCTOR CLEANING TOOLS SPLICES AUTOMATIC SPLICE INSTALLATION AUTOMATIC SPLICE INSTALLATION ONE PIECE COMPRESSION SPLICE COMPRESSION SPLICES SPLICING SLEEVES AND DIE SIZES FOR ALUMINUM AND COPPER CONDUCTORS 4.A 4.B 4.4A 4.4B 4.4C 4.6 COMPRESSION CONNECTORS INSTALLATION OF PARALLEL GROOVE COMPRESSION CONNECTORS PARALLEL GROOVE COMPRESSION CONNECTORS AND DIE SIZES FOR ALUMINUM CONNECTORS COMPRESSION CONNECTORS AND DIE SIZES FOR COPPER CONNECTORS COMPRESSION STIRRUPS A 4.64B BOLTED CONNECTORS INSTALLATION OF REMOVABLE CONNECTORS WITH LIVE LINE TOOLS 4.8 ALUMINUM BOLTED WEDGE CONNECTORS 4.8A BOLTED CONNECTORS FOR COPPER 4.8B BOLTED WEDGE TAP REFERENCE CHART 4.8C ALUMINUM REMOVABLE STIRRUPS 4.84A COPPER REMOVABLE STIRRUPS 4.84B HOTLINE CLAMPS CONNECTOR APPLICATION GUIDE LEADS TO TRANSFORMERS AND CAPACITORS ALL SIZES OF AL AND CU 4.9 FUSED LINE TAPS (UP TO A) 4.94 TAPS AND JUMPERS ALUMINUM 4.96 COPPER TO COPPER / AND 4/ TAPS 4.94 COPPER TO COPPER / AND SMALLER NONFUSED TAPS 4.96 TENSION SPLICES 4.9A SLACK SPAN SPLICES 4.9B REGULATOR CONNECTIONS 4.9 RECLOSER CONNECTIONS 4.9 COASTAL CONNECTIONS COASTAL AND CONTAMINATED AREAS COASTAL AND CONTAMINATED AREA CONNECTIONS 4. //6 KATIGBAK BURLISON ADCOCK SECTION 4 OVERHEAD ELECTRICAL CONNECTORS TABLE OF CONTENTS X 4.A

2 GENERAL: ALL APPROVED CONNECTORS, COMPRESSION OR BOLTED, SHOULD PERFORM IN A SATISFACTORY MANNER PROVIDED THE CORRECT SIZE IS SELECTED FOR THE APPLICATION AND IS INSTALLED CORRECTLY. THE QUALITY OF THE ELECTRICAL CONNECTION IS GREATLY AFFECTED BY THE SURFACE CONDITION OF THE CONDUCTORS CONTACT AREA TO BE JOINED. SELECTING A CONNECTOR: THERE ARE THREE CONSIDERATIONS IN SELECTING A CONNECTOR OR SLEEVE:. OBTAIN THE CONNECTOR WITH THE PROPER WIRE OR CABLE RANGE. THE RANGE IS MARKED ON ALL CONNECTORS AND SPLICES.. USE ALUMINUM CONNECTORS ON "ALUMINUM TO ALUMINUM" AND "ALUMINUM TO COPPER". USE COPPER OR BRONZE CONNECTORS ON "COPPER TO COPPER". WHEN COPPER CONNECTORS ARE USED ON ALUMINUM CONDUCTORS, THE INITIAL PRESSURE IS MAINTAINED ONLY AS LONG AS THE TEMPERATURE REMAINS CONSTANT. WHEN THE TEMPERATURE RISES, THE ALUMINUM CONDUCTOR EXPANDS MORE THAN THE COPPER CONNECTOR THAT SURROUNDS IT. AS A RESULT, THE CONNECTOR BECOMES TOO SMALL FOR THE CONDUCTOR, AND DUE TO THE TREMENDOUS PRESSURE, THE ALUMINUM EXTRUDES OUT OF THE CONNECTOR. WHEN THE JOINT COOLS, THE REVERSE ACTION TAKES PLACE. THE ALUMINUM CONDUCTOR CONTRACTS AT A GREATER RATE THAN THE COPPER CONNECTOR, AND THE COPPER CONNECTOR CANNOT SHRINK ENOUGH TO MAKE A GOOD TIGHT CONNECTION ON THE REDUCED DIAMETER ON THE CONDUCTOR. THIS CYCLE, WHEN REPEATED MANY TIMES, RESULTS IN A LOOSE CONNECTION. THE CONNECTOR HEATS UP AND EVENTUALLY FAILS.. USE FULL TENSION SLEEVES FOR ALL CONDUCTORS UNDER FULL TENSION. REDUCED TENSION SLEEVES MAY ONLY BE USED IN REDUCED TENSION (SLACK SPAN) APPLICATIONS. COMPRESSION TOOL AND DIE: THE EFFICIENCY OF THE CONNECTOR DEPENDS ON THE PERMANENT "SET" WHICH HAS BEEN INTRODUCED. IF AN IMPROPER DIE IS USED OR THE TOOL IS NOT PROPERLY ADJUSTED, THE CONNECTOR WILL BE OVER OR UNDER DEFORMED RESULTING IN AN INEFFECTIVE CONNECTION. TYPES OF DIES:. ROUND OR CIRCULAR DIES REQUIRE UNCRIMPED SPACE BETWEEN EACH CRIMP. CRIMPS SHOULD BE APPROXIMATELY /6" APART.. HEXAGONAL DIES REQUIRE CRIMPS TO BE OVERLAPPED MARKINGS ON CONNECTORS:. CONNECTORS AND SLEEVES ARE STAMPED WITH KNURL MARKS. WHEN CIRCULAR DIES ARE USED, ONE CRIMP SHOULD BE PLACED BETWEEN EACH SET OF KNURL MARKS.. DIE AND WIRE SIZES ARE ALSO STAMPED ON EACH CONNECTOR. WIRE BRUSHING: THE INVISIBLE ALUMINUM OXIDE FILM THAT FORMS ON ALUMINUM AND THE HARD COPPER OXIDE SCALE THAT FORMS ON COPPER ACT AS INSULATORS. THEY TEND TO INSULATE THE CONDUCTOR STRAND FROM THE CONNECTOR BODY AND INSULATE THE INDIVIDUAL STRANDS FROM EACH OTHER. THIS OXIDE FILM MUST BE REMOVED BY WIRE BRUSHING THE CONTACT AREA UNTIL THERE IS A FRESH BRIGHT COLOR. A COATING OF INHIBITOR MUST BE APPLIED IMMEDIATELY TO REDUCE THE FORMATION OF ADDITIONAL OXIDES. TIN PLATING ELIMINATES THE FORMATION OF ALUMINUM OXIDE ON CONDUCTORS. DO NOT WIRE BRUSH TIN PLATED SURFACES. SEE DWG. 4.8 FOR DETAILS ON AVAILABLE WIRE BRUSHES. //6 BRUINS BURLISON REVISED BY CK'D ADCOCK APPR. INSTALLATION GUIDE FOR CONNECTORS X X X X 4.

3 INHIBITOR INHIBITORS ARE USED AFTER WIRE BRUSHING. THE USE OF INHIBITORS, ALONG WITH WIRE BRUSHING, PROVIDES A GOOD FOUNDATION FOR THE CONNECTION. TYPES OF INHIBITORS PREFILLED CONNECTORS CONTAIN AN INHIBITOR WITH A CONDUCTIVE GRIT ADDED. AS THE CONNECTOR IS APPLIED TO THE LINE, THE GRIT PARTICLES ARE PUSHED INTO THE MATING SURFACES CAUSING THE METAL TO FORM CRATERS AROUND THEM. THIS RAISES NONOXIDIZED METAL AROUND THE RIM OF THE CRATER FORMING A GOOD CONNECTION. IF INSUFFICIENT FORCE IS APPLIED, THE GRIT WILL NOT PENETRATE AND ACTUALLY SEPARATE THE CONNECTOR AND CONDUCTOR. THIS EXPLAINS THE IMPORTANCE OF PROPER COMPRESSION FOR GOOD CONDUCTIVITY AND CORROSION PREVENTION. FLAT TO FLAT CONNECTIONS SHALL USE INHIBITORS WITHOUT GRIT. APPLY A VERY THIN LAYER ON THE CONNECTION BEFORE BOLTING TOGETHER. THE APPLICATION OF THE INHIBITOR AND THE NUMBER OF CRIMPS PROPERLY INSTALLED WILL ENSURE GOOD CONTACT AND ENHANCE THE LONGEVITY OF THE CONNECTION. BENEFITS OF USING INHIBITORS: INHIBITORS PREVENT OXIDATION AND CORROSION BY SEALING THE JOINT FROM AIR AND MOISTURE. INHIBITORS HELP MAINTAIN CONNECTION INTEGRITY OVER A WIDE TEMPERATURE RANGES. INHIBITORS WITH GRIT INCREASES PULLOUT STRENGTH AT THE CONNECTIONCONDUCTOR INTERFACE. INHIBITORS WITH GRIT PENETRATE THE REMAINING OXIDE LAYER TO HELP PRODUCE LOW INITIAL CONTACT RESISTANCE, RESULTING IN IMPROVED CONNECTION CONNECTIVITY. CRIMPING: APPLYING THE PROPER NUMBER OF CRIMPS ON A CONNECTOR CANNOT BE OVEREMPHASIZED. ALL CRIMPS INDICATED ON THE CONNECTOR ARE REQUIRED IN ORDER TO MEET THE FULL ELECTRICAL CAPACITY. ON SLEEVES, ALL CRIMPS ARE NECESSARY IN ORDER TO PASS TENSION REQUIREMENTS. BARREL TYPE CONNECTORS ARE FILLED WITH INHIBITOR AND IT IS SOMETIMES NECESSARY TO TWIST THE CONNECTOR TO ALLOW EASIER AND FULL INSERTION OF THE CONDUCTOR INTO THE BARREL. IT IS SUGGESTED THAT THE CONDUCTOR BE MARKED TO THE DEPTH OF THE BARREL TO ENSURE FULL INSERTION. ON LUG TYPE CONNECTORS WITH ONE OPEN END, BEGIN CRIMPING AT THE CLOSED END OF THE COMPRESSION BARREL AND WORK TOWARDS THE OPEN END. ON SLEEVE TYPE CONNECTORS WITH BOTH ENDS OPEN, BEGIN CRIMPING AT THE CENTER OF THE SLEEVE AND WORK OUT TO THE END. DO NOT LEAVE SPACES BETWEEN CRIMPS TO COME BACK AND CRIMP LATER. THIS CAUSES "COLD FLOW" WHICH ESSENTIALLY RELIEVES THE COMPRESSIVE FORCE ON THE ADJACENT CRIMPS. AFTER CRIMPING, "FLASHING" (METAL PROTRUSIONS) CAUSED BY THE COMPRESSION DIE IS SOMETIMES PRESENT ON THE CONNECTOR. THE FLASHING MUST BE FILED OFF SINCE IT COULD CUT THROUGH THE SPLICE OR CABLE INSULATION AND CAUSE A FAILURE. ALUMINUM COMPRESSION CONNECTORS ON COPPER CONDUCTORS: USE THE FOLLOWING PROCEDURE:. THOROUGHLY CLEAN BOTH CONDUCTORS BY WIRE BRUSHING TO REMOVE OXIDE AND CONTAMINATES. (BRUSHES ARE MADE TO ATTACH TO LIVE LINE TOOLS. DO THIS WHEN WORK STANDARDS REQUIRES USE OF LIVE LINE TOOLS.). USE THE PROPER SIZE ALUMINUM CONNECTOR. INSPECT THE COMPRESSION CONNECTOR TO BE SURE THAT A SUFFICIENT AMOUNT OF INHIBITOR IS IN EACH GROOVE TO THOROUGHLY COAT THE CONDUCTORS. IF THERE IS NOT A SUFFICIENT AMOUNT OF INHIBITOR, THEN ADD GRIT INHIBITOR.. POSITION THE CONDUCTORS SO THAT THE ALUMINUM CONDUCTOR IS LOCATED ABOVE THE COPPER CONDUCTOR TO PREVENT COPPER SALTS FROM CORRODING THE ALUMINUM CONDUCTOR. 4. USE THE PROPER TOOL AND DIE TO COMPRESS THE CONNECTOR, BEGINNING IN THE MIDDLE AND WORKING TO EACH END WITH THE CORRECT NUMBER OF CRIMPS. NOTE: FOR ALUMINUM TO ALUMINUM CONNECTIONS AND OTHER DETAILS, SEE DWGS. 4. AND 4.4. INSTALLATION GUIDE FOR CONNECTORS X X X X //6 BRUINS BURLISON ADCOCK 4.4

4 INHIBITORS AND CONNECTIONS TYPE OF CONNECTION TYPE OF INHIBITOR NONFLAT CONNECTIONS INHIBITORS W/ METALLIC GRIT FLAT TO FLAT CONNECTIONS INHIBITORS W/ NO GRIT INHIBITORS WITH METALLIC GRIT ITEM NUMBER DESCRIPTION 9856 INHIBITOR, 8 OZ PLASTIC BOTTLE, NONPETROLEUM BASED, W/ METALLIC GRIT INHIBITORS WITH NO METALLIC GRIT ITEM NUMBER DESCRIPTION INHIBITOR, 8 OZ BOTTLE, SYNTHETIC BASE W/ NO GRIT. BE SURE TO BRUSH THE CONDUCTOR(S) BEFORE APPLYING INHIBITOR.. DO NOT USE PETROLEUM BASED INHIBITORS AROUND RUBBER OR POLYETHYLENE INSULATED CONDUCTORS.. SYNTHETIC BASED INHIBITORS ARE COMPATIBLE WITH RUBBER, POLYETHYLENE AND OTHER INSULATING MATERIALS. 4. DO NOT USE INHIBITORS WITH NONMETALLIC GRIT. THIS GRIT IS NOT CONDUCTIVE. 5. DO NOT USE INHIBITORS WITH MINERAL OIL. MINERAL OIL IS NOT CONDUCTIVE. ELECTRIC CONTACT INHIBITORS X X //6 BRUINS BURLISON ADCOCK 4.6

5 REPLACEMENT BRUSH ITEM # DOG BONE ITEM # 9855 FLAT ROUND ITEM # ITEM # ITEM # REPLACEMENT BRUSH ITEM # ITEM # 9854 ITEM # 96 BILL OF MATERIALS ITEM NUMBER DESCRIPTION BRUSH, WIRE, CONDUCTOR CLEANING V, SS BRISTLE, W/ HANDLE BRUSH, WIRE, FLATROUND, LINEMANS, IN TOOL, FLAT & ROUND UP TO 59 MCM BRUSH, WIRE, LINEMAN REPLACEMENT, LARGE, F/ DOGBONE & FLATROUND WIRE BRUSHES BRUSH, WIRE, /4"" CLEANING SIZE IN, SS HARDWARE, V SHAPE, CONDUCTOR CLEANING BRUSH, WIRE, "" CLEANING SIZE IN, SS HARDWARE, V SHAPE, CONDUCTOR CLEANING PAD, REPLACEMENT, MED, F/ CONDUCTOR CLEANINIG BRUSH CAT ID BRUSH, WIRE, LINEMAN, DBL J DESIGN, WORKS W/ LIVE LINE TOOLS, SWIVELS, LOCKS IN POSITIONS BRUSH, WIRE, LINEMAN, SS BRISTLE, PLASTIC HANDLE, BRUSHES IN TOOL, RND HEAD END, F/ CU & F/ ALUM, UP. ALWAYS BRUSH CONDUCTORS BEFORE APPLYING INHIBITOR.. SEE WORK STANDARD 5.. FOR MORE DETAIL.. ONE BRUSH MAY BE USED FOR BOTH ALUMINUM AND COPPER CONDUCTORS. 4. DO NOT BRUSH TINNED PLATED SURFACES. //6 BRUINS BURLISON ADCOCK CONDUCTOR CLEANING TOOLS X X 4.8

6 INSERTION MARKS INSERTION MARKS ** DO NOT DEFORM WIRE POPUP INSERTION TABS 7. FOR MACLEAN CRS SLEEVES, POP UP TABS WILL DISPLAY ONCE CONDUCTOR IS PROPERLY INSERTED. 8. WIPE OFF EXCESS INHIBITOR.. CUT THE CONDUCTOR CLEAN AND SQUARE. TAPE THE CONDUCTOR AND CUT THROUGH THE TAPE TO PREVENT UNWRAPPING OF STRANDS. USE CABLE OR BOLT CUTTERS TO MAKE A CLEAN WIRE CUT. THE OBJECT IS TO AVOID FLATTENING THE ENDS OF THE CONDUCTOR WHICH CAUSES PARTIAL INSERTION AND FAILURE. ENSURE END IS CLEAN AND FREE OF BURRS.. WIRE BRUSH CONDUCTOR THOROUGHLY. AUTOMATIC SLEEVES ARE FACTORY FILLED WITH INHIBITOR GREASE.. MEASURE AND MARK CONDUCTOR FOR INSERTION FROM THE KNURL TO END OF FUNNEL GUIDE. MARK WITH TAPE OR MARKER. PILOT CUP JAWS /4" TO /4" 9. BEFORE TENSION IS APPLIED, IT IS EXTREMELY IMPORTANT THAT MOMENTARY TENSION IS APPLIED TO THE CONDUCTOR USING SEVERAL QUICK PULLS TO SET THE JAWS INSIDE THE SLEEVE. THIS ACTION PULLS THE JAWS TO THE TAPERED END, WHICH IN TURN INCREASES THE COMPRESSIVE FORCES OF THE JAWS ON THE CONDUCTOR. (IF THE DISTANCE BETWEEN THE SLEEVE AND THE MARK EXCEEDS /4", THEN START OVER WITH A NEW SLEEVE). AS LINE TENSION INCREASES, SO DOES THE GRIPPING FORCE OF THE JAWS.. ONCE THE CONDUCTOR IS IN PLACE, PULL IT AGAIN PRIOR TO APPLYING TENSION. 4. AUTOMATIC SLEEVES HAVE A PILOT CUP WHICH CONFINES THE STRANDS DURING INSERTION. INSERT CONDUCTORS TO FULL DEPTH. PUSH SLOWLY AND DO NOT TWIST. ' MIN. ' MIN. 5. AS THE WIRE IS INSERTED, THE JAWS ARE FORCED TOWARD THE WIDER PORTION OF THE TAPERED SLEEVE, PERMITTING THE JAWS TO SEPARATE AND ACCEPT THE CONDUCTOR. THE INTERNAL SPRING KEEPS THE JAWS FROM OPENING ANY MORE THAN NECESSARY. SPLICES SHALL NOT BE CLOSER THAN ' FROM A SUPPORT. LIMIT SPLICES TO TWO PER SPAN PER CONDUCTOR. IMPORTANT: NO AUTOMATIC SPLICE IS TO BE USED UNLESS THE CONDUCTOR IS UNDER TENSION (NO SLACK SPANS). //6 BRUINS BURLISON ADCOCK AUTOMATIC SPLICE INSTALLATION X X X X 4.A

7 CONDUCTOR COLOR CODE ITEM NUMBER ALUMINUM #4 # AAAC, AAC, ACSR ORANGE/RED #/ AAAC, AAC ACSR YELLOW 6.4 ACSR (8/) GREEN COPPER #6 SOLID 45 #4 SOLID 469 # SOLID 997 / STRANDED AWA MESSENGER, / 968 AUTOMATIC SPLICE INSTALLATION X //6 BRUINS BURLISON ADCOCK 4.B

8 STEP : SEE TABLES ON DWG. 4.4B FOR SLEEVE ITEM NUMBERS. SLEEVES ARE MARKED TO INDICATE CONDUCTOR AND DIE SIZE.. ENSURE CONDUCTOR ENDS ARE CLEAN, SQUARE AND FREE OF BURRS.. WIRE BRUSH CONDUCTOR THOROUGHLY. STEP INSERTION MARKS CENTER STOP. MEASURE AND MARK CONDUCTOR FOR INSERTION FROM THE CENTER STOP TO THE SLEEVE END.. SLIP SLEEVE OVER THE CONDUCTOR UNTIL IT REACHES THE CENTER STOP. STEP FIRST PRESS SECOND PRESS THIRD PRESS FOURTH PRESS. COMPRESS SLEEVE OVER ITS ENTIRE LENGTH, START AT MIDDLE AND WORKING TOWARD ENDS, ROTATE TOOL TO AVOID UNNECESSARY STRAIGHTENING. STEP 4. STRAIGHTEN SPLICE TO PREVENT UNDUE STRESS ON CONDUCTOR.. SEMITENSION SLEEVES ARE RATED AT 4% OF CONDUCTOR STRENGTH. THEY CAN ONLY BE USED IN JUMPERS AND SLACK SPANS.. TENSION SLEEVES MAY ALSO BE USED IN SLACK SPANS.. REPAIR SLEEVES ARE DESIGNED TO RESTORE FULL CURRENT RATING AND MECHANICAL REINFORCEMENT TO AAC AND ACSR CONDUCTORS WITH 5% OR LESS CROSSSECTIONAL AREA DAMAGE TO ALUMINUM STRANDS. REPAIR SLEEVES ARE NOT DESIGNED TO SPLICE CONDUCTOR. 4. SEE DWG. 4.4B FOR BILL OF MATERIALS. //6 BRUINS BURLISON ADCOCK ONE PIECE COMPRESSION SPLICE X X X X 4.4A

9 COMP. UNIT KSFN4ALF KSFNALF KSF4ALF KSFALF KSF79ALF FULL TENSION ALUMINUM SLEEVES CONDUCTOR SIZE CONNECTOR SLEEVE FULL TENSION COMP #4 ALUMINUM CONNECTOR SLEEVE FULL TENSION COMP # ALUMINUM CONNECTOR SLEEVE FULL TENSION COMP #4/ ALUMINUM CONNECTOR SLEEVE FULL TENSION COMP 6 MCM ALUMINUM CONNECTOR SLEEVE FULL TENSION COMP 795 MCM ALUMINUM ITEM NUMBER COMP. UNIT KSFN6CUF KSFN4CUF KSFCUF KSF4CUF FULL TENSION COPPER SLEEVES CONDUCTOR SIZE CONNECTOR SLEEVE FULL TENSION COMP #6 CU CONNECTOR SLEEVE FULL TENSION COMP #4 CU CONNECTOR SLEEVE FULL TENSION COMP #/ CU CONNECTOR SLEEVE FULL TENSION COMP #4/ CU ITEM NUMBER COMP. UNIT KSNF KSNF KSNALF KSN5F KSN5ALF KSN5F KSN79ALF NON TENSION SLEEVES CONDUCTOR SIZE CONNECTOR SLEEVE NON TENSION COMP #/ TO #/ CONNECTOR SLEEVE NON TENSION COMP 6 MCM TO #/ CONNECTOR SLEEVE NON TENSION COMP 6 MCM ALUMINUM CONNECTOR SLEEVE NON TENSION COMP 5 MCM CONNECTOR SLEEVE NON TENSION COMP 5 MCM ALUMINUM CONNECTOR SLEEVE NON TENSION COMP 5 MCM CONNECTOR SLEEVE NON TENSION COMP 795 MCM ALUMINUM ITEM NUMBER SEMITENSION SLEEVES ARE RATED AT 4% OF CONDUCTOR STRENGTH. THEY CAN ONLY BE USED IN JUMPERS AND SLACK SPANS.. SEE DWG. 4.4A FOR SPLICE INSTRUCTIONS. //6 BRUINS BURLISON ADCOCK COMPRESSION SPLICES X 4.4B

10 COPPER SLEEVES FULL TENSION STR COMPRESSION CONDUCTOR SIZE SOLID COMPRESSION ITEM NUMBER BURNDY DIES REQUIRED KEARNEY ALCOA NICOPRESS HUSKIE 6 W6 5/6 J HT58BX 4 W6 /8 P HT58BX W6 / X HT58CB / W65/U65 9/6 U5YDT HT58CE / W66/U66 /6 U6YDT HT58CF / U67 78 HT58CG 4/ WK84/U68 84 U8YDT HT58AE U INDICATES DIES FOR HYDRAULIC COMPRESSION TOOLS. ALL OTHER DIES ARE USED WITH MANUAL COMPRESSION TOOLS ( i.e. 6 MD6) ALUMINUM SLEEVES REDUCED TENSION ACSR SAC ITEM NUMBER BURNDY DIES REQUIRED KEARNEY ALCOA HUSKIE 6 WBG 5/8 HT58G 4 WBG 5/8 HT58G WBG 5/8 HT58G / WBG 5/8 B7AH HT58G 4/ WK84 84 B75AH HT58AE 6.4 WC/U655 B76AH HT58J * 6.4 WC/U7 BAH HT58J *. TUBULAR ALUMINUM COMPRESSION REPAIR SLEEVE FOR 6.4 MCM ACSR (6/7 & /7), 97.5 MCM ACSR (6/7 & /7), AND 477 MCM SAC (9STR).. CONDUCTORS MUST BE THOROUGHLY CLEANED BY WIRE BRUSHING THE CORRECT SIZE SLEEVE USED, AND THE PROPER NUMBER OF COMPRESSIONS MADE USING THE CORRECT DIE AND TOOL IN PROPER ADJUSTMENT/CALIBRATION. SPLICING SLEEVES AND DIE SIZES FOR ALUMINUM AND COPPER CONDUCTORS X //6 BRUINS BURLISON ADCOCK 4.4C

11 STEP STEP STEP CLEAN BOTH CONDUCTORS THOROUGHLY BY WIRE BRUSHING INSERT TAP CONDUCTOR IN TAP SIDE AND BEND TAB OVER CON DUCTOR IF USING DOUBLE TAB PARALLEL GROOVE CONNECTOR PLACE CONNECTOR ON LINE CONDUCTOR AND BEND TAB OVER CONDUCTOR STEP 4 STEP 5 STEP 6 STEP 7 INSERT PROPER DIE TOOL FOR CONNECTOR BEING COMPRESSED GRIP TOOL WITH THUMB POSITIONED AS SHOWN SLIDE TOOL OVER CONNECTOR AND POSITION TOOL TO MAKE CENTER COMPRESSION FIRST RELEASE THUMB PRESSURE SO THAT TOOL GRIPS CONNECTOR STEP 8 STEP 9 SECOND FOURTH FIRST THIRD ALUMINUM ALUMINUM COPPER COPPER MAKE COMPRESSIONS FROM CENTER OUT TO ENDS AS SHOWN ABOVE. ALL COPPER PARALLEL GROOVE CONNECTORS INSTALLED WITH THE 5 TOOL SHALL HAVE COMPRESSIONS. ALUMINUM PARALLEL GROOVE CONNECTORS SHALL HAVE 4 OR MORE COMPRESSIONS AS INDICATED ON THE CONNECTOR. ALWAYS POSITION CONNECTOR SO THAT ALUMINUM CONDUCTOR IS ABOVE COPPER WHEN CONNECTING ALUMINUM AND COPPER. THE SAME GENERAL PROCEDURE SHOULD BE FOLLOWED FOR INSTALLING PARALLEL GROOVE CONNECTORS WITH THE BATTERY OR HYDRAULIC PRESSES, EXCEPT FEWER COMPRESSIONS WILL BE REQUIRED AND THE ENTIRE LENGTH OF THE CONDUCTOR IS TO BE COMPRESSED. INSTALLATION OF PARALLEL GROOVE COMPRESSION CONNECTORS X X X X //6 BRUINS BURLISON ADCOCK 4.6

12 SIDE A PARALLEL GROOVE SIDE B SIDE A B A B A B A B A B A B A B A B A B CONDUCTOR RANGE 6 SOL STR 4 STR 8 STR 6 SOL ACSR 6 SOL ACSR STR / STR 4 SOL 8 STR STR / ACSR 6 SOL STR / ACSR / STR 6 SOL STR / STR / STR / STR / ACSR / ACSR 4/ ACSR 6 SOL STR / STR 4/ ACSR / STR / ACSR / STR 4/ ACSR / STR 4/ ACSR ALUMINUM COMPRESSION CONNECTORS DIAMETER RANGE [MIN] [MAX] CONNECTOR ITEM NUMBER BURNDY WBG O O O D D D D KEARNEY 5/8 O O O D D D D DIE SIZE ALCOA 5/8 O O O (D) (D) (D) (D) HUSKIE HT58G HT58AK HT58AK HT58AK D D (D) D D D D D. WBG, 5/8, O, HT58G, HT58AK, AND D INDICATE DIES TO USE IN MANUAL AND 6T PRESSES. (D) INDICATES DIES TO USE WITH A T PRESS.. USE ALUMINUM CONNECTORS FOR ALUMINUMTOALUMINUM, ALUMINUMTOCOPPER, AND ALUMINUMTOSTEEL CONNECTIONS.. CONDUCTORS MUST BE THOROUGHLY CLEANED BY WIRE BRUSHING, THE CORRECT SIZE CONNECTORS USED, AND THE PROPER NUMBER OF COMPRESSIONS MADE USING THE CORRECT DIE AND TOOL IN PROPER ADJUSTMENT/CALIBRATION. 4. SEE DWG..6C FOR SECONDARY COVERS. //6 BRUINS BURLISON ADCOCK PARALLEL GROOVE COMPRESSION CONNECTORS AND DIE SIZES FOR ALUMINUM CONNECTORS X 4.64A

13 SIDE A PARALLEL GROOVE SIDE B COPPER COMPRESSION CONNECTORS SIDE A CONDUCTOR SIZE SIDE B ITEM NUMBER BURNDY DIES REQUIRED KEARNEY ALCOA HUSKIE WKT B,T / 6 59 (U49) (O) HT4DW / / 59 (U49) (O) HT4DW. USE BURNDY, HUSKIE OR KEARNEY CRIMPING TOOL TO COMPRESS CONNECTORS USED ON CONDUCTOR SIZE (64, 64).. DIES LISTED IN "( )" INDICATE DIES TO USE IN HYDRAULIC TOOLS. WHERE DIES FOR BOTH TOOLS ARE SHOWN UNDER A CONNECTOR, EITHER TOOL MAY BE USED. WHERE DIE FOR HYDRAULIC ONLY IS SHOWN, HYDRAULIC TOOL MUST BE USED.. ONLY USE COPPER PARALLEL GROOVE CONNECTORS FOR COPPERTOCOPPER CONNECTIONS. 4. CONDUCTORS MUST BE THOROUGHLY CLEANED BY WIRE BRUSHING, THE CORRECT SIZE CONNECTORS USED, AND THE PROPER NUMBER OF COMPRESSIONS MADE USING THE CORRECT DIE AND TOOL IN PROPER ADJUSTMENT/CALIBRATION. 5. SEE DWG..6C FOR SECONDARY COVERS. //6 BRUINS BURLISON ADCOCK COMPRESSION CONNECTORS AND DIE SIZES FOR COPPER CONNECTORS X 4.64B

14 STEP STEP STEP CLEAN BOTH CONDUCTORS THOROUGHLY BY WIRE BRUSHING. SECURE THE BOLTED CONNECTOR WITH THE LIVE LINE TOOL AND PLACE IT ONTO THE CONDUCTOR WHERE IT WAS BRUSHED. TIGHTEN THE BOLTED CONNECTOR ONTO THE LINE. STEP 4 ALTERNATE BETWEEN THE TWO EYEBOLTS TO ENSURE BOTH ARE SECURELY FASTENED TO THE LINE. DO NOT OVERTIGHTEN. STEP 5 WIGGLE THE CONNECTOR WITH THE LIVE LINE TOOL TO ENSURE THE CONNECTOR DOES NOT SLIP ON THE LINE. TIGHTEN BOTH EYEBOLTS IF NECESSARY.. USE ALUMINUM BOLTED STIRRUPS ON ALUMINUM WIRE AND BRONZE BOLTED STIRRUPS ON COPPER WIRE.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY.. BRUSH CONDUCTOR AND REAPPLY INHIBITOR TO CONNECTOR EACH TIME BEFORE REATTACHING CONNECTOR TO PRIMARY. 4. SEE DWGS. 4.84A AND 4.84B FOR DETAILED INFORMATION ON BOLTED CONNECTORS. INSTALLATION OF REMOVABLE CONNECTORS WITH LIVE LINE TOOLS X X X X //6 BRUINS BURLISON ADCOCK 4.8

15 MAINLINE CONDUCTOR TAP CONDUCTOR TAPE STRANDED TAP CONDUCTORS TO KEEP STRANDS FROM SEPARATING DURING INSTALLATION COMP. UNIT KWF KWF KWF KW4F KWNF KW5F KW5F KW54F KW55F KW5NF KW79F KW79F KW79F KW794F KW795F KW7975F KW79NF BOLTED WEDGES ALUMINUM TO ALUMINUM CONDUCTOR SIZE CONNECTOR WEDGE 6 MCM TO #/ CONNECTOR WEDGE 6 MCM TO #/ CONNECTOR WEDGE 6 MCM TO 6 MCM CONNECTOR WEDGE 6 MCM TO #4/ CONNECTOR WEDGE 6 MCM TO # CONNECTOR WEDGE 5 MCM TO #/ CONNECTOR WEDGE 5 MCM TO 6 MCM CONNECTOR WEDGE 5 MCM TO #4/ CONNECTOR WEDGE 5 MCM TO 5 MCM CONNECTOR WEDGE 5 MCM TO # CONNECTOR WEDGE 795 MCM TO #/ CONNECTOR WEDGE 795 MCM TO #/ CONNECTOR WEDGE 795 MCM TO 6 MCM CONNECTOR WEDGE 795 MCM TO #4/ CONNECTOR WEDGE 795 MCM TO 5 MCM CONNECTOR WEDGE 795 MCM TO 795 MCM CONNECTOR WEDGE 795 MCM TO # ITEM NUMBER CONNECTOR WEDGE #/ TO #/ 654 CONNECTOR WEDGE #4/ TO #/ 656 CONNECTOR WEDGE #4/ TO #4/ COMPATIBLE UNIT KWP4H79F BOLTED WEDGE PADTAPS DESCRIPTION CONNECTOR WEDGE TO 4 HOLE PAD 795 MCM ITEM NUMBER CLEAN BOTH CONDUCTORS THOROUGHLY BY WIRE BRUSHING.. NEW CONNECTORS COME WITH INHIBITOR.. POSITION CONNECTOR. 4. TIGHTEN BOLT UNTIL TORQUE CONTROL NUT SHEARS OFF. 5. USE A COPPER CONNECTOR FOR COPPERTOCOPPER CONNECTIONS. //6 BRUINS BURLISON ADCOCK BOLTED WEDGE CONNECTORS X 4.8A

16 COMPATIBLE UNIT BOLTED WEDGES COPPER TO COPPER DESCRIPTION CONNECTOR OH TAP BOLTED WEDGE /CU LINE TO /CU TAP CONNECTOR OH TAP BOLTED WEDGE 4/CU LINE TO /CU TAP CONNECTOR OH TAP BOLTED WEDGE 4/CU LINE TO 4/CU TAP ITEM NUMBER. BRUSH BOTH CONDUCTORS THOROUGHLY.. TIGHTEN BOLT UNTIL TORQUE CONTROL NUT SHEARS OFF.. USE A COPPER CONNECTOR FOR COPPER TO COPPER CONNECTIONS. 4. NEW CONNECTORS COME WITH INHIBITOR. 5. SEE DWG. 4.8A FOR ALUMINUM TO ALUMINUM AND ALUMINUM TO COPPER CONNECTORS. BOLTED CONNECTORS FOR COPPER X X //6 BRUINS BURLISON ADCOCK 4.8B

17 MAIN CONDUCTOR TYPE DIA. /AAAC7.447" /ACSR6/ 4/AAAC7.56" 4/ACSR6/.56" 6.4AAC.666" 6.4ACSR8/.684" 6.4AAAC.7" 556AAC9.856" 795AAC7.6" #4A #CU7 AL ALUMINUM TO ALUMINUM, ALUMINUM TO COPPER /CU7 /AAAC7 /AAC7 /ACSR6/ TAP CONDUCTOR 4/AAAC7 556AAC9 /CU7 /AL 4/ACSR6/ 6.4AAC9 795AAC7 4/AL 4/CU7 559AAAC9.9".6".68".98".44".447".56".666".858".6" COMPATIBLE UNITS AND DESCRIPTIONS MAY BE FOUND ON DWG. 4.8A. BOLTED WEDGE TAP REFERENCE CHART X //6 BRUINS BURLISON ADCOCK 4.8C

18 BOLTED WEDGE STIRRUPS COMPATIBLE UNIT # 795 BOLTED WEDGE STIRRUPS ALUMINUM DESCRIPTION CONNECTOR OH STIRRUP BOLTED WEDGE 4/AL LINE CONNECTOR OH STIRRUP BOLTED WEDGE 6AL LINE CONNECTOR OH STIRRUP BOLTED WEDGE 556AL477AL LINE CONNECTOR OH STIRRUP BOLTED WEDGE 795AL LINE ITEM NUMBER BOLTED WEDGE STIRRUPS ARE TO BE USED WHERE: A. LOCATIONS ARE BUCKET TRUCK ACCESSIBLE B. TOOLING LIMITS COMPRESSION STIRRUPS C. STIRRUP NEEDS TO BE REMOVABLE.. WIRE BRUSH THE LINE CONDUCTOR THOROUGHLY.. STIRRUPS SHOULD BE PLACED " MIN. FROM ANY SUPPORT HARDWARE TO ALLOW FOR RESAGGING OF CONDUCTORS. 4. SEE SECTION 4.9 (CONNECTOR APPLICATION GUIDE) FOR PERMISSIBLE USES. BOLTED STIRRUPS #4 4/ COMPATIBLE UNIT BOLTED STIRRUPS ALUMINUM DESCRIPTION CONNECTOR OH STIRRUP BOLTED #4 /AL LINE CONNECTOR OH STIRRUP BOLTED / 556AL LINE CONNECTOR OH STIRRUP BOLTED 795AL LINE ITEM NUMBER BOLTED STIRRUPS MAY BE USED WHERE COMPRESSION TOOLS CANNOT BE USED AND STIRRUP MUST BE APPLIED WITH A LIVE LINE TOOL.. ALUMINUM STIRRUPS FOR ALUMINUM CONDUCTORS AND COPPER STIRRUPS FOR COPPER CONDUCTORS.. WIRE BRUSH LINE CONDUCTOR AND THE BAIL OF THE STIRRUP THOROUGHLY. APPLY INHIBITOR TO GROOVE OF STIRRUP IF NECESSARY. DO NOT BRUSH BAILS IF THEY ARE TINNED. 4. STIRRUPS SHOULD BE PLACED A MINIMUM OF " FROM ANY SUPPORT HARDWARE TO ALLOW FOR RESAGGING OF CONDUCTORS. 5. SEE SECTION 4.9 (CONNECTOR APPLICATION GUIDE) FOR PERMISSIBLE USES. //6 BRUINS BURLISON ADCOCK ALUMINUM REMOVABLE STIRRUPS X X 4.84A

19 BOLTED STIRRUPS COMPATIBLE UNIT #6 / / 4/ BOLTED STIRRUPS COPPER DESCRIPTION CONNECTOR OH STIRRUP BOLTED /CU6CU LINE CONNECTOR OH STIRRUP BOLTED 4/CU/CU LINE ITEM NUMBER BOLTED STIRRUPS MAY BE USED WHERE COMPRESSION TOOLS CANNOT BE USED AND STIRRUP MUST BE APPLIED WITH A LIVE LINE TOOL.. ALUMINUM STIRRUPS FOR ALUMINUM CONDUCTORS AND COPPER STIRRUPS FOR COPPER CONDUCTORS.. WIRE BRUSH LINE CONDUCTOR AND THE BAIL OF THE STIRRUP THOROUGHLY. APPLY INHIBITOR TO GROOVE OF STIRRUP IF NECESSARY. DO NOT BRUSH BAILS IF THEY ARE TINNED. 4. STIRRUPS SHOULD BE PLACED A MINIMUM OF " FROM ANY SUPPORT HARDWARE TO ALLOW FOR RESAGGING OF CONDUCTORS. 5. SEE SECTION 4.9 (CONNECTOR APPLICATION GUIDE) FOR PERMISSIBLE USES. //6 BRUINS BURLISON ADCOCK COPPER REMOVABLE STIRRUPS X X 4.84B

20 HOT LINE CLAMP (STIRRUP REQUIRED) 6 / CU POLY (TAP SIDE) MACRO UNIT CU ITEM NO. BILL OF MATERIALS QTY COMPATIBLE QTY ITEM PER DESCRIPTION UNIT REQ'D NUMBER CU KHNF CLAMP, HOT LINE, SM, BRONZE. SALVAGE AND REUSE WITH A STIRRUP. //6 BRUINS BURLISON REVISED BY CK'D ADCOCK APPR. HOT LINE CLAMPS X 4.86

21 BUCKET TRUCK ACCESSIBLE (NOT INCLUDING DEM 5KV) ALUMINUM COPPER *COMPRESSION STIRRUP #4 4/ (DEC,DEM,DEF) #4 477 (DEP) *BOLT STIRRUP BOLTED STIRRUP #6 / BOLTED STIRRUP 4/ *BOLTED WEDGE STIRRUP #4795 MAY BE USED IN PLACE OF THE COMPRESSION STIRRUP OR THE BOLT STIRRUP TRANSFORMERS AND CAPACITORS USE BRONZE HOTLINE CLAMP WITH THE STIRRUP NOT BUCKET TRUCK ACCESSIBLE (OR DEM 5KV) ALUMINUM COPPER BOLTED STIRRUP #4 795 BOLTED STIRRUP #6 / BOLTED STIRRUP 4/ TRANSFORMERS AND CAPACITORS USE BRONZE HOTLINE CLAMP WITH THE STIRRUP. COMPRESSION AND BOLTED WEDGE CONNECTORS ARE PREFERRED OVER DOUBLE (OR SINGLE) BOLTED STIRRUPS BECAUSE IT IS NOT POSSIBLE TO INSTALL THE BOLTED STIRRUPS IN A PRECISE AND CALIBRATED MANNER.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY.. BRUSH CONDUCTOR AND REAPPLY INHIBITOR TO CONNECTOR EACH TIME BEFORE REATTACHING CONNECTOR TO PRIMARY. 4. SEE SECTION 4.6 FOR COMPRESSION CONNECTION ITEM NUMBERS AND SECTION 4.8 FOR BOLTED CONNECTION ITEM NUMBERS. //6 BRUINS BURLISON ADCOCK LEADS TO TRANSFORMERS AND CAPACITORS ALL SIZES OF AL AND CU X X X X 4.9

22 BUCKET TRUCK ACCESSIBLE (NOT INCLUDING DEM 5KV) ALUMINUM COPPER PARALLEL GROOVE #4 4/ COMPRESSION STIRRUP #4 4/ BOLTED WEDGE / 795 BOLTED WEDGE STIRRUP #4 795 PARALLEL GROOVE #6 4/ BOLTED STIRRUP #6 / BOLTED STIRRUP 4/ MAINLINE SIZE JUMPER TO MATCH TAP LINE COMPRESSION CONNECTOR USE A BRONZE HOTLINE CLAMP WITH THE STIRRUP ALUMINUM NOT BUCKET TRUCK ACCESSIBLE (OR DEM 5KV) COPPER BOLTED STIRRUP #4 795 BOLTED STIRRUP #6 / BOLTED STIRRUP 4/ MAINLINE SIZE JUMPER TO MATCH TAP LINE COMPRESSION CONNECTOR USE A BRONZE HOTLINE CLAMP WITH THE STIRRUP. COMPRESSION AND BOLTED WEDGE CONNECTORS ARE PREFERRED OVER DOUBLE (OR SINGLE) BOLTED STIRRUPS BECAUSE IT IS NOT POSSIBLE TO INSTALL THE BOLTED STIRRUPS IN A PRECISE AND CALIBRATED MANNER.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY.. BRUSH CONDUCTOR AND REAPPLY INHIBITOR TO CONNECTOR EACH TIME BEFORE REATTACHING CONNECTOR TO PRIMARY. 4. SEE SECTION 4.6 FOR COMPRESSION CONNECTION ITEM NUMBERS AND SECTION 4.8 FOR BOLTED CONNECTION ITEM NUMBERS. //6 BRUINS BURLISON ADCOCK FUSED LINE TAPS (UP TO A) X X X X 4.94

23 BUCKET TRUCK ACCESSIBLE (NOT INCLUDING DEM 5KV) ALUMINUM PARALLEL GROOVE 6477 (DEP) #4 4/ BOLTEDWEDGE / 795 COMPRESSION SPLICE #4 795 MAINLINE WIRE TAP WIRE NOT BUCKET TRUCK ACCESSIBLE (OR DEM 5KV) ALUMINUM BOLT STIRRUP FOR 4/ AND SMALLER TAPS SEE NOTE PARALLEL GROOVE 6477 (DEP) #4 4/ BOLTEDWEDGE / 795 COMPRESSION SPLICE #4 795 MAINLINE WIRE TAP WIRE POLE WORK SHALL BE DEENERGIZED UNLESS WORK PRACTICES ALLOW OTHERWISE.. COMPRESSION AND BOLTED WEDGE CONNECTORS ARE PREFERRED OVER DOUBLE (OR SINGLE) BOLTED STIRRUPS BECAUSE IT IS NOT POSSIBLE TO INSTALL THE BOLTED STIRRUPS IN A PRECISE AND CALIBRATED MANNER.. THE BOLT STIRRUP MAY BE USED FOR ALUMINUM TAPS OF 4/ AND SMALLER.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY. 4. BRUSH CONDUCTOR AND REAPPLY INHIBITOR TO CONNECTOR EACH TIME BEFORE REATTACHING CONNECTOR TO PRIMARY. 5. SEE SECTION 4.6 FOR COMPRESSION CONNECTION ITEM NUMBERS AND SECTION 4.8 FOR BOLTED CONNECTION ITEM NUMBERS. //6 BRUINS BURLISON ADCOCK TAPS AND JUMPERS ALUMINUM X X X X 4.96

24 BUCKET TRUCK ACCESSIBLE (NOT INCLUDING DEM 5KV) COPPER PARALLEL GROOVE / & 4/ BOLT CLAMP BOLTED WEDGE MAINLINE WIRE SIZE JUMPER TO MATCH TAP COMPRESSION CONNECTOR TAP WIRE NOT BUCKET TRUCK ACCESSIBLE (OR DEM 5KV) COPPER PARALLEL GROOVE / & 4/ BOLT CLAMP BOLTED WEDGE MAINLINE WIRE SIZE JUMPER TO MATCH TAP COMPRESSION CONNECTOR TAP WIRE POLE WORK SHALL BE DEENERGIZED UNLESS WORK METHODS ALLOW OTHERWISE.. COMPRESSION CONNECTORS ARE PREFERRED OVER BOLTED CONNECTORS.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY.. BRUSH CONDUCTOR AND REAPPLY INHIBITOR TO CONNECTOR EACH TIME BEFORE REATTACHING CONNECTOR TO PRIMARY. 4. SEE SECTION 4.6 FOR COMPRESSION CONNECTION ITEM NUMBERS AND SECTION 4.8 FOR BOLTED CONNECTION ITEM NUMBERS. //6 BRUINS BURLISON ADCOCK COPPER TO COPPER / AND 4/ TAPS X X X X 4.94

25 BUCKET TRUCK ACCESSIBLE (NOT INCLUDING DEM 5KV) COPPER *PARALLEL GROOVE #6 / MAINLINE WIRE SIZE JUMPER TO MATCH TAP COMPRESSION CONNECTOR *MAY USE A BOLTED STIRRUP IF CONNECTION NEEDS TO BE REMOVABLE TAP WIRE / CU AND SMALLER NOT BUCKET TRUCK ACCESSIBLE (OR DEM 5KV) COPPER BOLTED STIRRUP #6 / MAINLINE WIRE SIZE JUMPER TO MATCH TAP COMPRESSION CONNECTOR USE A BRONZE HOTLINE CLAMP WITH THE STIRRUP TAP WIRE / CU AND SMALLER. COMPRESSION CONNECTORS ARE PREFERRED OVER BOLTED CONNECTORS.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY.. BRUSH CONDUCTOR AND REAPPLY INHIBITOR TO CONNECTOR EACH TIME BEFORE REATTACHING CONNECTOR TO PRIMARY. 4. SEE SECTION 4.6 FOR COMPRESSION CONNECTION ITEM NUMBERS AND SECTION 4.8 FOR BOLTED CONNECTION ITEM NUMBERS. //6 BRUINS BURLISON ADCOCK COPPER TO COPPER / AND SMALLER NONFUSED TAPS X X X X 4.96

26 BUCKET TRUCK ACCESSIBLE (NOT INCLUDING DEM 5KV) ALUMINUM COPPER MACLEAN VIPCRS AUTOSPLICE WITH POPUP TABS AUTOMATICS WITHOUT POPUP TABS FOR CU COMPRESSION SPLICE SPLICE SIZE DEPENDENT ON TOOLING AVAILABILITY TINNED COPPER COMPRESSION SPLICE AUTOMATIC SPLICES ARE FOR CONDUCTORS UNDER TENSION ( NO SLACK SPANS ). AUTOMATIC SPLICES SHOULD ALWAYS BE GIVEN AN INITIAL "SET" WHEN INSTALLED. A FIRM PULL BY HAND IS CONSIDERED SUFFICIENT TO "SET" THE SPLICE. THE RATED STRENGTH OF A FULLTENSION SPLICE IS 95% OF THE CONDUCTOR BREAKING STRENGTH. AUTOMATIC SPLICES SHOULD NEVER BE CLOSER THAN ' ON A NEW LINE OR ' ON AN EXISTING LINE TO THE CONDUCTOR ATTACHMENT POINT. IF A BREAK OCCURS NEARER THE STRUCTURE THAN ', A SUITABLE LENGTH OF CONDUCTOR SHOULD BE SPLICED IN TO MEET THIS REQUIREMENT. EMERGENCY REPAIRS MAY BE MADE CLOSER TO THE STRUCTURE THAN '. NOT BUCKET TRUCK ACCESSIBLE (OR DEM 5KV) ALUMINUM COPPER MACLEAN VIPCRS AUTOSPLICE WITH POPUP TABS AUTOMATICS WITHOUT POPUP TABS FOR CU COMPRESSION SPLICE SPLICE SIZE DEPENDENT ON TOOLING AVAILABILITY COPPER COMPRESSION SPLICE CONDUCTOR SHALL BE DEENERGIZED. SPLICE MAY BE WORKED FROM THE POLE OR FROM THE GROUND AND THEN RAISED INTO POSITION.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY.. SPLICE SHALL NEVER BE CLOSER THAN ' FROM POLE LINE HARDWARE. ' FOR NEW LINES.. LIMIT SPLICES TO TWO PER SPAN PER CONDUCTOR. 4. DO NOT PLACE SPLICES IN CONTROLLED ACCESS HIGHWAY AND RAILROAD CROSSINGS. 5. SEE SECTION 4. FOR INSTALLATION DETAILS AND ITEM NUMBERS. //6 BRUINS BURLISON ADCOCK TENSION SPLICES X X X X 4.9A

27 BUCKET TRUCK ACCESSIBLE (NOT INCLUDING DEM 5KV) COMPRESSION SLEEVES TENSION COMPRESSION SLEEVES MAY BE USED IN SLACK SPANS AUTOMATICS SHALL NOT BE USED IN ANY SLACK SPANS REDUCED TENSION (4% RATED BREAKING STRENGTH OF THE CONDUCTOR) REDUCED TENSION SPLICES (SOMETIMES REFERRED TO AS PARTIAL OR SEMITENSION SPLICES) ARE SLEEVES FOR USE WHEN SPLICING JUMPERS OR SLACK SPANS. REDUCED TENSION AND FULL TENSION SPLICES MAY BE USED FOR REPAIRS IN SLACK SPANS. COMPRESSION SPLICES SHOULD NEVER BE CLOSER THAN ' ON A NEW LINE OR ' ON AN EXISTING LINE TO THE CONDUCTOR ATTACHMENT POINT. IF A BREAK OCCURS NEARER THE STRUCTURE THAN ', A SUITABLE LENGTH OF CONDUCTOR SHOULD BE SPLICED IN TO MEET THIS REQUIREMENT. TEMPORARY EMERGENCY REPAIRS MAY BE MADE CLOSER TO THE STRUCTURE. NOT BUCKET TRUCK ACCESSIBLE (OR DEM 5KV) COMPRESSION SLEEVES TENSION SLEEVES MAY BE USED IN SLACK SPANS AUTOMATICS SHALL NOT BE USED IN ANY SLACK SPANS CONDUCTOR SHALL BE DEENERGIZED. SPLICE MAY BE WORKED FROM THE POLE OR FROM THE GROUND AND THEN CONDUCTOR RAISED INTO POSITION.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY.. SPLICE SHALL NEVER BE CLOSER THAN ' FROM POLE LINE HARDWARE. ' FOR NEW LINES.. LIMIT SPLICES TO TWO PER SPAN PER CONDUCTOR. 4. SPLICE SIZE IS DEPENDENT ON TOOLING AVAILABILITY. 5. AVOID PLACING SPLICES IN CONTROLLED ACCESS HIGHWAY AND RAILROAD CROSSINGS. 6. SEE DWGS. 4. AND 4.4 FOR INSTALLATION DETAILS AND ITEM NUMBERS. //6 BRUINS BURLISON ADCOCK SLACK SPAN SPLICES X X X X 4.9B

28 PARALLEL GROOVE #/ #4/ # 477 (DEP) BOLTEDWEDGE (ALL MW 5KV) #4 795 FOR REGULATORS WITH ISOLATION SWITCHES, COMPRESSION CONNECTORS OR BOLTEDWEDGES ARE TO BE USED. SOURCE LOAD BYPASS CUTOUT SOURCE CUTOUT SOURCE LOAD TO EQUIPMENT TO EQUIPMENT TO EQUIPMENT. COMPRESSION CONNECTORS ARE PREFERRED OVER BOLTED CONNECTIONS.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY.. SEE SECTION 4.6 FOR COMPRESSION CONNECTION ITEM NUMBERS AND SECTION 4.8 FOR BOLTED CONNECTION ITEM NUMBERS. //6 BRUINS BURLISON ADCOCK REGULATOR CONNECTIONS X X X X 4.9

29 PARALLEL GROOVE #/ #4/ # 477 (DEP) BOLTEDWEDGE (ALL MW 5KV) #4 795 LOAD SOURCE SIDE VIEW. COMPRESSION CONNECTORS ARE PREFERRED OVER BOLTED CONNECTIONS.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY.. SEE SECTION 4.6 FOR COMPRESSION CONNECTION ITEM NUMBERS AND SECTION 4.8 FOR BOLTED CONNECTION ITEM NUMBERS. //6 BRUINS BURLISON ADCOCK RECLOSER CONNECTIONS X X X X 4.9

30 ALUMINUM WIRE BRONZE FITTING TINNED COPPER PIN PIN CONNECTOR (FOR CONNECTING ALUMINUM WIRE TO COPPER) ALUMINUM SERVICE CONDUCTOR PIN CONNECTOR PARALLEL GROOVE (FOR ALUMINUM TO ALUMINUM CONNECTIONS) COPPER PARALLEL GROOVE CONNECTOR COPPER SECONDARY (FOR CONNECTING PIN CONNECTOR TO COPPER WIRE) CONDUCTOR SPLICES AND CONNECTIONS ALL CONDUCTOR CONNECTIONS MUST BE PROPERLY PREPARED BEFORE MAKING A CONNECTION REGARDLESS OF HOW NEW THE CONDUCTOR MAY BE. IT IS ESPECIALLY IMPORTANT IN CONTAMINATED AND COASTAL AREAS TO WIRE BRUSH AND APPLY INHIBITOR TO ALL CONNECTIONS. FOR COPPER TO ALUMINUM CONNECTION, ALWAYS POSITION THE ALUMINUM CONDUCTOR ABOVE THE COPPER. PIN CONNECTORS WILL BE USED TO CONNECT ALUMINUM CONDUCTOR TO TRANSFORMER TERMINALS AND TO COPPER CONDUCTOR. FOR ALUMINUM TO ALUMINUM CONNECTIONS, USE ALUMINUM PARALLEL GROOVE CONNECTORS WITH A LIBERAL AMOUNT OF INHIBITOR APPLIED. USE PIN CONNECTORS WHEN TERMINATING ALUMINUM CONDUCTORS TO COPPER OR BRONZE FITTINGS.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY.. SEE DWG. 4. FOR ITEM NUMBERS. //6 BRUINS BURLISON ADCOCK COASTAL CONNECTIONS X X 4.96

31 ALUMINUM WIRE BRONZE FITTING TINNED COPPER PIN PIN CONNECTOR (FOR CONNECTING ALUMINUM WIRE TO COPPER) ALUMINUM SERVICE CONDUCTOR PIN CONNECTOR COPPER PARALLEL GROOVE CONNECTOR PARALLEL GROOVE (FOR ALUMINUM TO ALUMINUM CONNECTIONS) COPPER SECONDARY (FOR CONNECTING PIN CONNECTOR TO COPPER WIRE) CONDUCTOR SPLICES AND CONNECTIONS ALL CONDUCTOR CONNECTIONS MUST BE PROPERLY PREPARED BEFORE MAKING A CONNECTION REGARDLESS OF HOW NEW THE CONDUCTOR MAY BE. IT IS ESPECIALLY IMPORTANT IN CONTAMINATED AND COASTAL AREAS TO WIRE BRUSH AND APPLY INHIBITOR TO ALL CONNECTIONS. FOR COPPER TO ALUMINUM CONNECTION, ALWAYS POSITION THE ALUMINUM CONDUCTOR ABOVE THE COPPER. PIN CONNECTORS WILL BE USED TO CONNECT ALUMINUM CONDUCTOR TO TRANSFORMER TERMINALS AND TO COPPER CONDUCTOR. FOR ALUMINUM TO ALUMINUM CONNECTIONS, USE ALUMINUM PARALLEL GROOVE CONNECTORS WITH A LIBERAL AMOUNT OF INHIBITOR APPLIED. USE PIN CONNECTORS WHEN TERMINATING ALUMINUM CONDUCTORS TO COPPER OR BRONZE FITTINGS.. BRUSH CONDUCTOR AND APPLY INHIBITOR TO CONNECTOR BEFORE ATTACHING TO PRIMARY. //6 BRUINS BURLISON ADCOCK COASTAL AND CONTAMINATED AREA CONNECTIONS X 4.

SECTION 3 - PRIMARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS

SECTION 3 - PRIMARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS 03.00 GENERAL CONSTRUCTION NOTES PRIMARY CONSTRUCTION PRIMARY CONSTRUCTION PIN INSULATOR INSTALLATION 03.00-02 03.00-04 03.00-20 03.02 CONNECTORS AUTOMATIC SPLICE INSTALLATION 03.02-01 INSTALLATION GUIDE

More information

PRODUCTS FOR THE RAIL AND UTILITY INDUSTRY

PRODUCTS FOR THE RAIL AND UTILITY INDUSTRY PRODUCTS FOR THE RAIL AND UTILITY INDUSTRY connectorproducts.com 1300 John Tipton Blvd. Pennsauken, NJ 08110 Phone: 856.829.9190 Fax: 856.829.9195 Catalog IX.1 American Design American Made Our success

More information

Standard Compression Dead End for ACSR and ACSS Conductor CAUTION: ACSR Dead Ends Cannot Be Used on ACSS HT Conductor

Standard Compression Dead End for ACSR and ACSS Conductor CAUTION: ACSR Dead Ends Cannot Be Used on ACSS HT Conductor INS-ACA089 Installation Instructions Standard Compression Dead End for ACSR and ACSS Conductor CAUTION: ACSR Dead Ends Cannot Be Used on ACSS HT Conductor 1. Mark the conductor a distance of 3 /4 the length

More information

Connector Installation Guide Compression and Mechanical Connectors

Connector Installation Guide Compression and Mechanical Connectors Connector Installation Guide Compression and Mechanical Connectors Typical Cross Section of a Compression Connector Before Installation Before compression, a typical cross section of cable consists of

More information

SUBMERSIBLE SECONDARY CONNECTORS SSBC350-4LI. Cond. Range H W L

SUBMERSIBLE SECONDARY CONNECTORS SSBC350-4LI. Cond. Range H W L SUBMERSIBLE SECONDARY CONNECTORS -1- Index TYPE SSBC350-L (Wide-Port Spacing) Rubber Insulated Secondary Connectors SURE-SEAL RUS Approved User friendly wide-port spacing (50% more room for cable training).

More information

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions Class I Indoor Termination Voltage Designation: 12/20(24) kv Kit Contents: 1 HeatShrinkBreakoutBootAssembly 3 HeatShrinkBindingSleeves

More information

SECTION 8 - SWITCHES AND PROTECTIVE DEVICES TABLE OF CONTENTS

SECTION 8 - SWITCHES AND PROTECTIVE DEVICES TABLE OF CONTENTS 08.00 GENERAL DISTRIBUTION SURGE ARRESTERS 08.00-0 CUTOUTS AND ARRESTERS GENERAL 08.00-03 08.0 CUTOUTS AND ARRESTERS METAL OXIDE ARRESTERS WITH POLYMER HOUSINGS 08.0-0 APPLICATION OF DIRECT CONNECTED ARRESTERS

More information

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits 3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Instructions IEEE Std. No. 48 Class 1 Termination 8 kv Class, 95 kv BIL:

More information

PLP Compression Dead-end & Jumper Terminal for ACSR & ACSS Conductors

PLP Compression Dead-end & Jumper Terminal for ACSR & ACSS Conductors MARCH 2017 PLP Compression Dead-end & Jumper Terminal for ACSR & ACSS Conductors Be sure to read and completely understand this procedure before applying product. Be sure to select the proper PREFORMED

More information

026-2 : 1996 CEB STANDARD

026-2 : 1996 CEB STANDARD 026-2 : 1996 CEB STANDARD COMPRESSION CONNECTORS & TERMINATIONS FOR OVERHEAD LINE CONDUCTORS CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable

More information

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits 3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits With High-K Stress Relief For 3-Conductor Type G (Ground Wire), Copper Tape Shield, Armored Cables 7600-S-3G Series Instructions IEEE Std.

More information

DISTRIBUTION CONNECTORS SECTION DF COMPRESSION TERMINALS. Aluminum Compression Lugs Aluminum Bi-Metal Pin Terminals Copper Compression Lugs

DISTRIBUTION CONNECTORS SECTION DF COMPRESSION TERMINALS. Aluminum Compression Lugs Aluminum Bi-Metal Pin Terminals Copper Compression Lugs DISTRIBUTION CONNECTORS COMPRESSION TERMINALS Aluminum Compression Lugs Aluminum Bi-Metal Pin Terminals Copper Compression Lugs SECTION VERSAtile ALUMINUM COMPRESSION TERMINAL TYPE VCEL For use with either

More information

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4. METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4.-4 4. SELF-CONTAINED METERING, SINGE-PHASE INSTALLATION DETAILS /4 VOLT SINGLE-PHASE UNDERGROUND RESIDENTIAL SERVICE AND METER

More information

Item Code Description Unit Qty Total

Item Code Description Unit Qty Total UNDP ELECTRICITY SECTOR NORTHERN GOVERNORATES Phase XI Item Code Description Unit Qty Total 04-02-00001 Service Pole - 6m, 75mm dia GS Pipe 11250 04-02-00002 9m Tubular Steel Poles complete with all Accessories

More information

Installation Instructions

Installation Instructions 517 Lyons Ave, Irvington, NJ 07111 Phone: 973-371-1771 Fax: 973-371-4304 Installation Instructions Deadbreak Elbow Applicable Current Ratings 600A (Aluminum) 900A (Copper) Applicable Catalog Prefix 35kV

More information

Armor Rods. Armor Rods NOMENCLATURE GENERAL RECOMMENDATIONS

Armor Rods. Armor Rods NOMENCLATURE GENERAL RECOMMENDATIONS Transmission: Section 1 NOMENCLATURE Single Support and Double Support : Identified by S and D appearing in the length column on the catalog page. Should the maximum distance between tied supports exceed

More information

Jumpers & Load Pickup Tools

Jumpers & Load Pickup Tools Jumpers & Load Pickup Tools Catalog 2300 May 2016 Jumpers & Load Pickup Tools 2300 May 2016 Page 2301 All Chance Insulated Jumpers meet ASTM F 2321 Standard Specification. G4758 15kV 5 5 / 8 " G4765 25kV

More information

CONTENTS OVERHEAD SLEEVES AND LUGS

CONTENTS OVERHEAD SLEEVES AND LUGS CONTENTS OVERHEAD SLEEVES AND LUGS SECTION 5 SECTION 5 OVERHEAD CONDUCTOR SLEEVES & LUGS..................45 NON TENSION SLEEVES.......................................46 FULL TENSION SLEEVES TYPE A...............................46

More information

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination 3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination Instructions IEEE Std. No. 48 Class 1 Termination CAUTION Working around energized electrical systems may

More information

ELB ES. Product Installation Instructions

ELB ES. Product Installation Instructions ELB-25-210-ES 200A 25kV Class Loadbreak Elbow with Integral Jacket Seal for Copper Tape (CT) and Jacketed Concentric Neutral (JCN) cables Product Installation Instructions Safety Instructions When installing

More information

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit 3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit With High-K Stress Relief For 3-Conductor Copper Tape Shield Cables with or without Ground Wires 7600-T-3RJS Series Instructions

More information

Easy-On II Terminations

Easy-On II Terminations Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables, concentric neutral, metal tape shielded or wire shielded cables without need for additional

More information

PRODUCTS FOR THE RAIL AND UTILITY INDUSTRY

PRODUCTS FOR THE RAIL AND UTILITY INDUSTRY PRODUCTS FOR THE RAIL AND UTILITY INDUSTRY connectorproducts.com 1300 John Tipton Blvd. Pennsauken, NJ 08110 Phone: 856.829.9190 Fax: 856.829.9195 CATALOG IX.1 American Design American Made Our success

More information

Copyright 1999 Inter-Industry Conference On Auto Collision Repair v.4.0

Copyright 1999 Inter-Industry Conference On Auto Collision Repair v.4.0 Uniform Procedures For Collision Repair UPCR SP08A Rail, Rear 1. Description This procedure describes the repair and complete or partial replacement of an aluminum rear rail. Inspection and evaluation

More information

Our overhead products go above and beyond all others. QUICK REFERENCE. Overhead Connectors. & Covers. Overview

Our overhead products go above and beyond all others. QUICK REFERENCE. Overhead Connectors. & Covers. Overview Overview QUICK REFERENCE Overhead Connectors & Covers page(s) Our overhead products go above and beyond all others. We have plenty of overhead connectors. From transformer eyebolts and stirrup connectors

More information

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet Quick Term II Cold Shrink Silicone Rubber Termination Instruction Sheet IEEE Std. No. 48 1990 Class 1 Termination 15 kv Class 110 kv BIL Kit Contents: 1 Hi K Silicone Rubber Termination 2 Scotch 70 Silicone

More information

SP41A B-Pillar. Copyright 1999 Inter-Industry Conference On Auto Collision Repair v.4.0

SP41A B-Pillar. Copyright 1999 Inter-Industry Conference On Auto Collision Repair v.4.0 Uniform Procedures For Collision Repair SP41A B-Pillar 1. Description This procedure describes the repair and complete or partial replacement of an aluminum B-pillar assembly. Inspection and evaluation

More information

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING NON-NETWORK SYSTEMS

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING NON-NETWORK SYSTEMS CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT NON-NETWORK SYSTEMS SPECIFICATION EO-100186 REVISION #10 MAY 2007 EFFECTIVE DATE MAY

More information

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit 3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7622-T-110, 7624-T-110, 7625-T-110, 7626-T-110 Instructions

More information

SUBMERSIBLE SECONDARY CONNECTORS

SUBMERSIBLE SECONDARY CONNECTORS SUBMERSIBE SECONDARY CONNECTORS TYPE SSBC350- (Wide-Port Spacing) Rubber Insulated Secondary Connectors SURE-SEA RUS Approved User friendly wide-port spacing (50% more room for cable training). Multiple

More information

SP01A Rail, Front Upper

SP01A Rail, Front Upper Uniform Procedures For Collision Repair UPCR SP01A Rail, Front Upper 1. Description This procedure describes the repair and complete or partial replacement of an aluminum front upper rail. Inspection and

More information

Grounding equipment COOPER POWER SERIES. Temporary Connections CA325004EN. Contents

Grounding equipment COOPER POWER SERIES. Temporary Connections CA325004EN. Contents Temporary Connections CA325004EN Supersedes November 2016 Grounding equipment COOPER POWER SERIES Contents Description Page Grounding elbow products... 2 Grounding elbow and kit product ratings... 5 200

More information

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series 3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series For 3-Conductor Copper Tape Shield Cables without Ground Wires Instructions IEEE Std. No. 48 Class 1 Termination CAUTION Working

More information

3 Terminals, Kits and Tools

3 Terminals, Kits and Tools 3 Terminals, Kits and Tools Glossary of Product Terminology 2 Terminals 5 Butt onnectors 5 Disconnects 11 Female 11 Male 17 Multi-Stack 22 Ring Tongue Terminals 23 For more than 30 years, 3M has been a

More information

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief 3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7621-T-95, 7622-T-95, 7624-T-95, 7625-T-95 Instructions IEEE Std.

More information

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4 3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4 With High-K Stress Relief For Tape Shielded, Wire Shielded and UniShield Cable Instructions

More information

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief 3M Cold Shrink QTlll Silicone Rubber Indoor Tubular Termination Kits With HighK Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7693T150, 7695T150, 7696T150 Instructions IEEE Std. No. 48

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit 3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief For Tape Shielded, Wire Shielded and UniShield Cable 7685-S-8 Instructions IEEE Std. No. 48 Class 1 Termination 35

More information

BRACKETS, MOUNTS & HARDWARE

BRACKETS, MOUNTS & HARDWARE HIGH VOLTAGE SWITCHGEAR & AUTOMATION EQUIPMENT SECTION 6 Brackets, Mounts & Misc. Hardware CAT. NO: 040930G May, 2008 INERTIA Engineering & Machine Works, INC. Fax: (209) 931-8186 6665 Hardaway Road, Stockton,

More information

(K),(M)430TB/G Up to 36 kv

(K),(M)430TB/G Up to 36 kv IS90722-ENG - 430TB/G-45 25 June 2009 - Revision 8A - Supersedes edition of 25 November 2008 Page 1 of 10 CAUTION : Read instructions thoroughly and completely prior to beginning installation. Installation

More information

QT-III Cold Shrink Silicone Rubber

QT-III Cold Shrink Silicone Rubber QT-III Cold Shrink Silicone Rubber 7600-T-3RJS Series 3/C Cabinet Termination Instructions Kit Contents: 3ÑSilicone Rubber Phase Re-jacketing Sleeve Assembly 3ÑCold Shrink Silicone Rubber Termination Assembly

More information

AUTOMATIC SPLICES THE INSIDE STORY

AUTOMATIC SPLICES THE INSIDE STORY AUTOMATIC SPLICES THE INSIDE STORY Carl R. Tamm September - 2013 Tel.800-269-1462 Fax.800-311-9857 382 Park Ave. East Mansfield, OH 44905 www.classicconnectors.com Classic Connectors, Inc. We wish to begin

More information

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN 3 Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class 350 kv BIL IEC 60840 72,5 kv Kit Contents: 1 Silicone Rubber Lug Seal Insulator

More information

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink Splice Kit QS-III 5536A 3M Cold Shrink Splice Kit QS-III 5536A for UniShield, Wire Shielded, Longitudinally Corrugated (LC), and Tape Shielded (Ribbon Shielded) Cable or Transitions to Concentric Neutral (CN)/Jacketed Concentric

More information

MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates

MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS Larry Vogt Manager, Rates Minimum Distribution System What is MDS? MDS is an analysis module of the cost-of-service study in which distribution investment

More information

Cold Shrink QS T Trifurcating Transition Splice Kit

Cold Shrink QS T Trifurcating Transition Splice Kit Cold Shrink QS2012-13-3T Trifurcating Transition Splice Kit Instructions IEEE Std. 404-1993 15 kv Class 110 kv BIL Completed Splice Cable Size Range Requirements PILC 500 kcmil Conductor Size (240 mm 2

More information

3M Cold Shrink QT-III Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber Termination 3M Cold Shrink QT-III Silicone Rubber Termination For Tape-Over-Wire (TOW) or Wire-Over-Tape (WOT) Shielded Cable 7673-S-8(S)-TOW/WOT Instructions IEEE Std. No. 48 Class 1 Termination 69 kv Class, 350

More information

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions Raychem CSJA 1521 Cold-Shrinkable Splice for single core polymeric insulated (XLPE-EPR) cables up to 15kV for tape, wire, Unishield, LC shield, JCN, and flat strap neutral cable UniShield is a trademark

More information

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN 3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN For Jacketed Concentric Neutral (JCN) Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350 kv BIL IEC 60840 72,5

More information

DISTRIBUTION PRODUCTS

DISTRIBUTION PRODUCTS DISTRIBUTION PRODUCTS INDEX SECTION DI OTHER DISTRIBUTION SERIES DESCRIPTION PAGE WILDLIFE PROTECTORS CC101 / CC170.. CUT-OUT COVER, ONE PIECE WILDLIFE PROTECTOR... DI-3 GS... ONE PIECE WILDLIFE PROTECTOR...

More information

Kcmil. Mass kg/each. Tel:

Kcmil. Mass kg/each. Tel: Catalog Number Conductor Size Kcmil Conductor Strand Alu Dead End Alu Jumper Steel Dead End Approximative Mass kg/each Cicame Alu Die Cicame Steel Die CSA Alu Die CSA Steel Die TD6N TD7N TD8N TD9N TDN

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits 3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits With High Ampacity Ground Connection and High-K Stress Relief For Tape Shield, Wire-Over-Tape Shield and Longitudinally Corrugated (LC) Shield

More information

Installation Instructions

Installation Instructions 517 Lyons Ave, Irvington, NJ 07111 Phone: 973-371-1771 Fax: 973-371-4304 Installation Instructions Series Cold Shrink R-800 Appli Ftener Type G Style Appli Housing Sizes O, P, & Q Appli Catalog Prefix

More information

Instruction Sheet Crimping Die Assemblies , , and

Instruction Sheet Crimping Die Assemblies , , and Instruction Sheet Crimping Die Assemblies 08-8 986-1, 98-1, and 988-1 1 Mar 11 Moving Dies Color Code For complete instructions concerning the related applicators or machines, refer to the customer documents

More information

JUMPERS & SWITCHING TOOLS

JUMPERS & SWITCHING TOOLS INSULATED JUMPER SETS 368 INSULATED JUMPER SETS FOR 15 KV, 25KV AND 35 KV Used for bypassing work areas when upgrading lines and when making temporary or emergency repairs Continuous-current ratings for

More information

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief) Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief) Instruction Sheet IEEE Std. No. 48 1990 Class 1 Termination 5/8.7 kv Class 95 kv BIL Kit Contents: 3 Hi K, Tracking Resistant,

More information

3 Terminals, Kits and Tools

3 Terminals, Kits and Tools 3 Terminals, Kits and Tools Glossary of Product Terminology 2 Terminals 6 For more than 30 years, 3M has been a leading supplier of Scotchlok terminals, disconnects, connectors and tools for use in the

More information

TEMPORARY PROTECTIVE GROUNDING EQUIPMENT ACCESSORIES

TEMPORARY PROTECTIVE GROUNDING EQUIPMENT ACCESSORIES TEMPORARY PROTECTIVE GROUNDING EQUIPMENT ACCESSORIES TEMPORARY PROTECTIVE GROUNDING EQUIPMENT ACCESSORIES J-2 Grounding Equipment Accessories. www.salisburybyhoneywell.com BALL & SOCKET SYSTEM BALL STUDS

More information

QUICKTERM TERMINATION KIT

QUICKTERM TERMINATION KIT PYROTENAX QUICKTERM TERMINATION KIT INSTALLATION INSTRUCTIONS FOR TERMINATING SINGLE CONDUCTOR COPPER SHEATHED MINERAL INSULATED CABLE DESCRIPTION This termination kit is used to terminate #6 AWG and larger

More information

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief) Instructions Quick Term II Silicone Rubber Termination (with High-K Stress Relief) IEEE Std. No. 48 990 Class Termination 5 kv Class 50 kv BIL Kit Contents Hi K Silicone Rubber Termination Scotch 70 Silicone

More information

Bonding & Grounding. Telecommunications Main Ground Bars. Telecommunications Main Ground Bar Kits

Bonding & Grounding. Telecommunications Main Ground Bars. Telecommunications Main Ground Bar Kits PhysicalSupport.D 1/21/08 2:10 PM Page 121 GB4X12TMGB GB4X20TMGB GB4X12TMGBKIT Telecommunications Main Ground Bars and Kits Manufactured of 1/4 thick electrolytic tough pitch 110 alloy copper bar. Includes

More information

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW) 3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW) for Tape Over Wire and Wire Over Tape Shielded Cable Instructions Class 1 Termination IEC 60840 72,5 kv 69 kv Class 325

More information

SP06A Rail, Front Lower

SP06A Rail, Front Lower Uniform Procedures For Collision Repair SP06A Rail, Front Lower 1. Description This procedure describes the repair and complete or partial replacement of an aluminum front lower rail. Inspection and evaluation

More information

Jumper Terminals and Tee Taps. delivery

Jumper Terminals and Tee Taps. delivery Jumper Terminals and Tee Taps delivery November 017 November 017 Jumper Terminals & Tee Taps Index Compression/Aluminum JTS... Straight Pad for AAC, AAAC, ACAR & ACSR Conductor... -1 JTF... 15 Degree Pad

More information

Industrial Turbo Meters, Sizes 2" through 6"

Industrial Turbo Meters, Sizes 2 through 6 Industrial Turbo Meters Sizes 2" through 6" TUR-UM-00530-EN-19 (October 2014) User Manual Industrial Turbo Meters, Sizes 2" through 6" User Manual CONTENTS Scope of the Manual 5 Specifications 5 Product

More information

MICRO WELD MODEL DP1 & DP2 HEAVY DUTY NON-FERROUS BUTT WELDERS MICRO PRODUCTS COMPANY SERVICE MANUAL

MICRO WELD MODEL DP1 & DP2 HEAVY DUTY NON-FERROUS BUTT WELDERS MICRO PRODUCTS COMPANY SERVICE MANUAL MICRO WELD MODEL DP1 & DP2 HEAVY DUTY NON-FERROUS BUTT WELDERS MICRO PRODUCTS COMPANY SERVICE MANUAL 1 TABLE OF CONTENTS 1.0 SPECIFICATIONS 2.0 GENERAL OPERATING INSTRUCTIONS 3.0 BASIC OPERATING PARTS

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief 3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief 7642-S-2, 7642-S-2(L) For Jacketed Concentric Neutral (JCN) and Concentric Neutral (CN) Cable Instructions IEEE Std.

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL PIPE WORK. This work covers part of outcome 2 of the Edexcel standard module:

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL PIPE WORK. This work covers part of outcome 2 of the Edexcel standard module: FLUID POWER FLUID POWER EQUIPMENT TUTORIAL PIPE WORK This work covers part of outcome 2 of the Edexcel standard module: UNIT 21746P APPLIED PNEUMATICS AND HYDRAULICS The material needed for outcome 2 is

More information

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW) 3M Cold Shrink Skirted Termination Kit QT-III 7672-S-8-TS (RW) for Tape Shielded Cable Instructions Class 1 Termination IEC 60840 72,5 kv 69 kv Class 325 kv BIL CAUTION Working around energized systems

More information

Thank you for your interest in the Copper Battery Terminals through the farm magazine.

Thank you for your interest in the Copper Battery Terminals through the farm magazine. Thank you for your interest in the Copper Battery Terminals through the farm magazine. We have enclosed our literature on the battery terminals and related products along with our product listing and catalog

More information

GROUNDING & BONDING PRODUCTS

GROUNDING & BONDING PRODUCTS GROUNDING & BONDING PRODUCTS Busbars Page 5-3 Insulators Page 5-8 Grounding Products Page 5-9 Compression Tools, Lugs & Taps Page 5-14 Learn About CPI s Extended Limited Warranties for coverage of (2)

More information

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC 3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC For Tape Shield or Longitudinally Corrugated (LC) Shielded Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350

More information

Disconnect & ByPass Switches

Disconnect & ByPass Switches Disconnect & ByPass Switches Disconnect & Oil Circuit Recloser Bypass Switches; Regulator & Current Transformer Bypass Switches Electrical Apparatus K-SEC 060 & 090 Contents Type D-73 Distribution Class

More information

RIG-I-FLEX 140 SERIES CURTAIN TRACKS

RIG-I-FLEX 140 SERIES CURTAIN TRACKS RIG-I-FLEX 140 SERIES CURTAIN TRACKS Parts Included 140 RIG-I-FLEX CWANA code CORD OPERATED/MOTORIZED WALK-ALONG 140 (240) 140-R (240-R) 141 (241) 141-R (241-R) 142 (242) 142-R (242-R) STRAIGHT CURVED

More information

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles IS---K656CY,CH,I Page 1 of 6 CONTENTS: Receptacle housings, Cable adapters, I, Wye or H Center sections, Aluminum holding collars,

More information

3M Mechanical Shearbolt Connectors, QCI Series

3M Mechanical Shearbolt Connectors, QCI Series M Mechanical Shearbolt Connectors, QCI Series Data Sheet November 2011 Description Connector Contents M Mechanical Shearbolt Connectors, QCI Series are designed to cover a wide range of conductor sizes

More information

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 (S600-12-3) 600 A 15/25 kv class T-OP II connector assembly installation instructions COOPER POWER SERIES DISCLAIMER OF

More information

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650023EN Effective October 2016 Supersedes March 2012 (IS550-60-1) COOPER POWER SERIES DTS1242 Deadbreak Bolted Tee Connector: Interface C for Single Core Cable with Copper

More information

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650024EN Effective October 2016 Supersedes March 2012 (IS550-61-1) COOPER POWER SERIES DTB1242 Deadbreak Bolted Companion Tee Connector: Interface C for Single Core Cable

More information

Maintenance Information

Maintenance Information 45530136 Edition 1 July 2008 Electric Screwdrivers EL 24V DC Series Maintenance Information Save These Instructions WARNING Always wear eye protection when operating or performing maintenance on this tool.

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit 3M Cold Shrink QTIII Silicone Rubber Skirted Termination Kit With HighK Stress Relief 3M Cold Shrink QTIII Silicone Rubber Skirted Termination Kit With HighK Stress Relief For Jacketed Concentric Neutral

More information

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables) Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables) Instructions Kit Contents 3 Lug Covers 3 Cold Shrink Terminations 12

More information

UNSIGNED HARDCOPY NOT CONTROLLED

UNSIGNED HARDCOPY NOT CONTROLLED Subject: APPROVED BY STATUS PURPOSE AFFECTED FUNCTIONS Flat Braid Cables Manager, Hardware Engineering Maintenance Revision Establishes the requirements for the fabrication of special-purpose electrical

More information

JFETIGER RUNNING MANUAL. Downloaded From JFETC.COM Thu, 20 Sep :15: JFETIGER. * valid at time of download * JANUARY 2015

JFETIGER RUNNING MANUAL. Downloaded From JFETC.COM Thu, 20 Sep :15: JFETIGER. * valid at time of download * JANUARY 2015 JFETIGER-TP-M-001 (REV.3) JFETIGER RUNNING MANUAL JFETIGER JANUARY 2015 JFE STEEL CORPORATION CONTENTS JFETIGER... 1 PREFACE...1 1 PREPARATIONS BEFORE RUNNING...1 1.1 Handle Pipes Carefully...1 1.2 Racking

More information

HVS S 15kV Class

HVS S 15kV Class Product HVS-3-1580S 15kV Class Transition Splice for 3/C to 3/C Extruded Dielectric (Poly/EPR) Power Cables Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526 PII-54864, Rev

More information

Jumpering and grounding equipment and assemblies

Jumpering and grounding equipment and assemblies Supersedes 325-50 July 2014 Jumpering and grounding equipment and assemblies Contents Description Page Jumpering Equipment Load Pickup Clamps... 2 Jumper Clamps.... 3 Jumper Components.... 4 C-Type Grounding

More information

Non-insulated terminals : 8, 14, 22, 38, 60, 70, 80, 100, 150, 180, 200, 325 mm 2

Non-insulated terminals : 8, 14, 22, 38, 60, 70, 80, 100, 150, 180, 200, 325 mm 2 12A Non-insulated terminals : 8, 14, 22, 38, 60, 70, 80, 100, 150, 180, 200, 325 mm 2 Maximum input pressure: 700 bar Oil volume required : 90 cc Output force : 226 kn 280 (L) mm 7.5 kg Steel carrying

More information

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K) IS94012-ENG - AFN 20-45 5 February 2013 - Revision 6 - Supersedes edition of 28 January 2013 Page 1 of 7 CAUTION: Read instructions thoroughly and completely prior to beginning installation. Installation

More information

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN Loadbreak Apparatus Connectors MN650014EN Effective January 2016 Supersedes S500-110-1 April 2015 COOPER POWER SERIES Fused loadbreak elbow connector installation instructions DISCLAIMER OF WARRANTIES

More information

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT 3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT For Tape-Over-Wire (TOW) or Wire-Over-Tape (WOT) Shielded Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350

More information

Chapter 1. Connectors & Fittings for Railways

Chapter 1. Connectors & Fittings for Railways Chapter Connectors & Fittings for Railways Current Carrying Catenary Dropper Component N Messenger Bz Cable length from L Component N 3 Component N 2 Contact Wire SNCF approved This dropper provides a

More information

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION Page 1 of 11 R1 ****This Standard Supercedes CE Macros MPR1S, MUR1S, MPR3S & MUR3S and portions of BECo Standards CS2.7-1.1, CS2.7-1.5 & CS2.7-1.7**** PRIMARY URD RISER CONSTRUCTION TABLE OF CONTENTS Page

More information

PSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables.

PSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables. Sizes are available for all shielded cables in voltage classes from 15kV through 46kV.

More information

Heavy Duty Copper Battery Terminals

Heavy Duty Copper Battery Terminals Heavy Duty Copper Battery Terminals Constructed of 131 contact copper to provide high conductivity. Raised characters to ensure legibility of important information regarding cable size, post type, and

More information

FR11A Fender, Welded-On

FR11A Fender, Welded-On Uniform Procedures For Collision Repair FR11A Fender, Welded-On 1. Description This procedure describes the repair and complete replacement of a welded-on aluminum fender. Inspection and evaluation requirements

More information

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254. 3 Loadbreak Elbows 200 Amp 5-15 kv Industrial pg. 252 Loadbreak Elbows 200 Amp 25 kv Industrial pg. 254 Loadbreak Elbows 200 Amp Industrial pg. 255 Loadbreak Elbows Accessories 3 Loadbreak Elbows 3M 200

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

JOSLYN. Underground Cable Accessories. Table of Contents. JPT/JIPT Polymer Terminations. ShrinkTite Sealing Kits. Easy-On II Terminations

JOSLYN. Underground Cable Accessories. Table of Contents. JPT/JIPT Polymer Terminations. ShrinkTite Sealing Kits. Easy-On II Terminations Underground Cable Accessories JOSLYN Table of Contents JPT/JIPT Polymer Terminations 15kV, 25kV & 35kV ShrinkTite Sealing Kits 1kV In-Line Splice Sealing Kit Cable Jacket Sealing Kit Easy-On II Terminations

More information

OLS U T I L I T Y S E G M E N T

OLS U T I L I T Y S E G M E N T BURNDY TOOLS UTILITY SEGMENT BURNDY Tools exemplify both reliability and engineering knowledge unsurpassed in the industry. BURNDY.COM 3 BURNDY TOOL SERVICE GETS IT DONE! GET IT FIXED Tools repaired at

More information