R410A INDOOR UNIT 1. WALL MOUNTED TYPE : AS A07LCC AS A09LCC AS A12LCC AS A14LCC AS A18LCC D1D_AS007E/

Size: px
Start display at page:

Download "R410A INDOOR UNIT 1. WALL MOUNTED TYPE : AS A07LCC AS A09LCC AS A12LCC AS A14LCC AS A18LCC D1D_AS007E/"

Transcription

1 R4A INDOOR UNIT. : AS A7LCC AS A9LCC AS ALCC AS A4LCC AS A8LCC DD_AS7E/ 8..

2 . FEATURE MODEL : AS A7LCC AS A9LCC AS ALCC AS A4LCC AS A8LCC (AO R7/9LC) (AO RLC) (AO R4/8LC) FEATURES Energy saving Rank A (7/9//4TYPE) Europe energy saving Rank A achieved ALL DC (4/8TYPE) a b a DC fan motor a Indoor unit : ALL TYPE Outdoor unit : 4/8TYPE b i-pam control (7/9TYPE) When operation starts, the machine operates at high voltage and high power and when operation stabilizes, the set temperature is maintained at low voltage. VP V-PAM control (/4/8TYPE) c Front view V-PAM technology makes a compressor more powerful. V-P c DC rotary compressor Super quiet Air flow mode can be set in 4 steps and more detailed air flow setting is possible. Easy maintenance Easy maintenance and always clean. Troublesome maintenance has been made easy. Since the front panel is easy to remove, maintenance is also easy. - ( - ) -

3 - ( - ) - Inner drying operation This model is equipped with an inner drying function. After the power is turned off, the dry operation starts inside the air conditioner. This prevents the growth of mold and bacteria inside the air conditioner. During dew condensation Approx. mins Drying Low outdoor air temperature cooling correspondence (4, 8TYPE) Corresponds to cooling operation at - C outdoor air temperature Corresponds to maximum m long piping Air conditioner filter features Dirty Air Apple-catechin Filter Ion Deodorization Filter Clean Air Long-life Ion Deodorization Filter Applecatechin Filter

4 - ( - ) -. REMOTE CONTROLLER -. WIRELESS REMOTE CONTROLLER FEATURES Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible. Four kinds of timers. Easy operation. Built-in timers Select from four different timer programs (On/Off/Program/Sleep). Program timer The program timer operates the ON and OFF timer once within a 4 hour period. Sleep timer The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping. operation/dry operation When the sleep timer is set, the set temperature automatically rises C every hour. The set temperature can rise up to a maximum of C. Heating operation When the sleep timer is set, the set temperature automatically drops C every minutes. The set temperature can drop to a maximum of 4 C. Timer setting C C C 4 C 6min. min. C C 6min. 9min. Timer setting

5 - ( - 4) - FUNCTIONS SLEEP button 5 MASTER CONTROL button SET TEMP. button ( COIL DRY button Signal Transmitter TIMER MODE button / ) 7 TIMER SET ( / ) button 8 FAN CONTROL button START/STOP button SET button (Vertical) SWING button RESET button TEST RUN button This button is used when installing the conditioner, and should not be used under normal conditions, as it will cause the air conditioner s thermostat function to operate incorrectly. If this button is pressed during normal operation, the unit will switch to test operation mode, and the Indoor Unit s OPERA- TION Indicator Lamp and TIMER Indicator Lamp will begin to flash simultaneously. To stop the test operation mode, press the START/STOP button to stop the air conditioner. 4 CLOCK ADJUST button Display panel Remote Control Unit Display Transmit Indicator Clock Display Operating Mode Display 9 Timer Mode Display 8 Fan Speed Display Temperature SET Display 4 COIL DRY Display 9 4 SLEEP Display SWING Display 7 SPECIFICATION SIZE (H x W x D mm) 76 x 56 x 8 WEIGHT ( g ) ACCESSORY Holder

6 - ( - 5) -. SPECIFICATIONS Type Model name Power source Available voltage range European energy label Capacity Input power Current EER COP SENSIBLE CAPACITY POWER FACTOR Moisture removal Fan Heating Heating Heating Airflow rate Type Q'ty Motor output Rated Min-Max Rated Min-Max Rated Min-Max Rated Min-Max Rated Max Rated Max Heating Heating Heating AS A7LCC AS A9LCC AS ALCC A A A Heating A A A kw..6.5 BTU/h 7, 8,9,9 kw BTU/h,7 -,,7 -,, - 4,7 kw BTU/h,, 6,4 kw BTU/h,7-5,7,7-8,, -, kw l/h (pints/h). (.). (.7).8 (.8) High Med 5 55 Low 4 4 Quiet 9 9 High m /h Med Low Quiet W High Med Low Quiet Noise level db(a) High Heating kw A kw/kw % WALL MOUNTED INVERTER HEAT PUMP V 5Hz 98-64V 5Hz Cross flow fan Med Low 9 Quiet Heat exchanger type Enclosure Dimensions (H W D) Weight Operation range Net Gross Net Gross Connection pipe Size Method Remote controller type Drain pipe Material Size Dimensions (H W D) Fin pitch Rows x Stages Pipe type Fin type Material Colour Liquid Gas Heating mm mm kg (lb.) mm C %RH C mm Copper Aluminium Polystyrene White () (7) 6.5 ( /4 in.) 9.5 ( /8 in.) Flare 8 to 8 or less or less Wireless PP + LLDPE Outer diameter : 9 / Inner diameter :.6 Note : Specifications are based on the following conditions. : Indoor temperature of 7 CDB/9 CWB. and outdoor temperature of 5 CDB/4 CWB. Heating : Indoor temperature of CDB/5 CWB. and outdoor temperature of 7 CDB/6 CWB. Pipe length : 7.5 m, Height difference : m. (Outdoor unit - Indoor unit) The maximum current is the maximum value when operated within the operation range (temperature).

7 - ( - 6) - Type Model name Power source Available voltage range European energy label Capacity Input power Current EER COP SENSIBLE CAPACITY POWER FACTOR Moisture removal Fan High Med Low Quiet High Med Low Quiet AS A4LCC AS A8LCC A B Heating A A kw BTU/h 4, 7,7 kw BTU/h, - 8,, - 9,4 kw BTU/h 9,, kw BTU/h, - 8,7, -, kw l/h (pints/h). (4.4).8 (5.9) W 4 4 High Med 8 8 Low Quiet 5 5 Noise level db(a) High 4 4 Heat exchanger type Enclosure Dimensions (H W D) Weight Net Gross Net Gross Connection pipe Size Operation range Method Remote controller type Drain pipe Heating Heating Heating Airflow rate Type Q'ty Motor output Material Size Rated Min-Max Rated Min-Max Rated Min-Max Rated Min-Max Rated Max Rated Max Heating Heating Heating Heating Dimensions (H W D) Fin pitch Rows Stages Pipe type Fin type Material Colour Liquid Gas Heating kw A kw/kw % m /h Med 7 7 Low Quiet 7 7 mm mm kg(lb.) mm C %RH C mm WALL MOUNTED INVERTER HEAT PUMP V 5Hz 98-64V 5Hz Cross flow fan MAIN : SUB : Main :., Sub :.4 Main : 6, Sub : 4 Copper Aluminium Polystyrene White () (6) 6.5 ( /4 in.).7 ( / in.) Flare 8 to 8 or less or less Wireless PP + LLDPE Outer diameter : 9 / Inner diameter :.6 Note : Specifications are based on the following conditions. : Indoor temperature of 7 CDB/9 CWB. and outdoor temperature of 5 CDB/4 CWB. Heating : Indoor temperature of CDB/5 CWB. and outdoor temperature of 7 CDB/6 CWB. Pipe length : 7.5 m, Height difference : m. (Outdoor unit - Indoor unit) The maximum current is the maximum value when operated within the operation range (temperature).

8 - ( - 7) - 4. DIMENSIONS MODEL : AS A7LC, AS A9LC, AS ALC, AS A4LC, AS A8LC (Unit : mm) 79 5, 75 INSTALLATION PLACE Wall hook bracket 5 cm or more 6 cm or more 9 cm or more 5 cm or more cm or more (Wall cap)

9 - ( - 8) - 5. WIRING DIAGRAMS MODEL : AS A7LC, AS A9LC, AS ALC, AS A4LC, AS A8LC CN INDICATOR PCB F M FAN MOTOR RED WHITE WHITE WHITE WHITE WHITE WHITE BLUE YELLOW WHITE RED CN CN CONTROLLER PCB CN4 CN5 CN7 CN RED ORANGE YELLOW PINK BLUE TEST or GRAY or GRAY M STEP MOTOR PIPE TEMPERATURE THERMISTOR ROOM TEMPERATURE THERMISTOR POWER RELAY WHITE TM 4 W GREEN BROWN L POWER SOURCE TERMINAL THERMAL FUSE N L TM RED GREEN / YELLOW N BLUE TO

10 - ( - 9) - 6. CAPACITY TABLE 6-. COOLING CAPACITY MODEL : AS A7LC AFR 9.9 Outdoor temperature CDB CWB CDB Indoor temperature TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI MODEL : AS A9LC AFR 9.9 Outdoor temperature CDB CWB CDB Indoor temperature TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI MODEL : AS ALC AFR.6 Outdoor temperature CDB CWB CDB Indoor temperature TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI AFR : Air Flow Rate (m /min) TC : Total Capacity (kw) SHC : Sensible Heat Capacity (kw) PI : Power Input (kw)

11 - ( - ) - MODEL : AS A4LC AFR.7 Outdoor temperature CDB CDB CWB 8 5 Indoor temperature TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI MODEL : AS A8LC AFR.7 Outdoor temperature CDB CDB CWB 8 5 Indoor temperature TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI AFR : Air Flow Rate (m /min) TC : Total Capacity (kw) SHC : Sensible Heat Capacity (kw) PI : Power Input (kw)

12 - ( - ) HEATING CAPACITY MODEL : AS A7LC AFR 9.9 Outdoor temperature CDB CDB CWB Indoor temperature TC PI TC PI TC PI TC PI TC PI MODEL : AS A9LC AFR 9.9 Outdoor temperature CDB CDB CWB Indoor temperature TC PI TC PI TC PI TC PI TC PI MODEL : AS ALC AFR.6 Outdoor temperature CDB CDB CWB Indoor temperature TC PI TC PI TC PI TC PI TC PI AFR : Air Flow Rate (m /min) TC : Total Capacity (kw) PI : Power Input (kw)

13 - ( - ) - MODEL : AS A4LC AFR.7 Outdoor temperature CDB CDB CWB Indoor temperature TC PI TC PI TC PI TC PI TC PI MODEL : AS A8LC AFR.7 Outdoor temperature CDB CDB CWB Indoor temperature TC PI TC PI TC PI TC PI TC PI AFR : Air Flow Rate (m /min) TC : Total Capacity (kw) PI : Power Input (kw)

14 - ( - ) - 7. FAN PERFORMANCE 7-. AIR VELOCITY DISTRIBUTION MODEL : AS A7LC, AS A9LC (m) Unit : m/s TOP VIEW FLOW CONTROL PANEL : Horiz. LOUVER : Center Note : Fan speed : High Operation mode :FAN Voltage : V (m) (m)...5 Unit : m/s TOP VIEW FLOW CONTROL PANEL : Horiz. LOUVER : Right & Left (m) (m) Unit : m/s SIDE VIEW FLOW CONTROL PANEL : Horiz. LOUVER : Center (m) (m). Unit : m/s SIDE VIEW FLOW CONTROL PANEL : Vert. LOUVER : Center (m)

15 - ( - 4) - MODEL : AS ALC (m) Unit : m/s TOP VIEW FLOW CONTROL PANEL : Horiz. LOUVER : Center Note : Fan speed : High Operation mode :FAN Voltage : V (m) (m)...5 Unit : m/s TOP VIEW FLOW CONTROL PANEL : Horiz. LOUVER : Right & Left (m) (m)...5 Unit : m/s SIDE VIEW FLOW CONTROL PANEL : Horiz. LOUVER : Center (m) (m). Unit : m/s SIDE VIEW FLOW CONTROL PANEL : Vert. LOUVER : Center (m)

16 - ( - 5) - MODEL : AS A4LC, AS A8LC (m) Unit : m/s TOP VIEW FLOW CONTROL PANEL : Horiz. LOUVER : Center Note : Fan speed : High Operation mode :FAN Voltage : V (m) (m).. Unit : m/s.5 TOP VIEW FLOW CONTROL PANEL : Horiz. LOUVER : Right & Left (m) (m). Unit : m/s..5 SIDE VIEW FLOW CONTROL PANEL : Horiz. LOUVER : Center (m) (m). Unit : m/s SIDE VIEW FLOW CONTROL PANEL : Vert. LOUVER : Center (m)

17 - ( - 6) AIR FLOW MODEL : AS A7LC COOLING Fan speed Number of rotations (r.p.m) Airflow HIGH MED LOW 95 QUIET m /h 65 l/s 5 CFM 5 m /h 9 l/s 94 CFM 4 m /h 4 l/s 4 CFM 9 m /h 8 l/s 7 CFM HEATING Fan speed HIGH MED LOW QUIET Number of rotations (r.p.m) 9 76 Airflow 645 m /h 79 l/s 8 CFM 54 m /h 5 l/s 8 CFM 45 m /h l/s 56 CFM m /h 89 l/s 88 CFM

18 - ( - 7) - MODEL : AS A9LC COOLING Fan speed HIGH MED LOW QUIET Number of rotations (r.p.m) 95 7 Airflow 595 m /h 65 l/s 5 CFM 5 m /h 9 l/s 94 CFM 4 m /h 4 l/s 4 CFM 9 m /h 8 l/s 7 CFM HEATING Fan speed HIGH MED LOW QUIET Number of rotations (r.p.m) 9 76 Airflow 645 m /h 79 l/s 8 CFM 54 m /h 5 l/s 8 CFM 45 m /h l/s 56 CFM m /h 89 l/s 88 CFM

19 - ( - 8) - MODEL : AS ALC COOLING Fan speed HIGH MED LOW QUIET Number of rotations (r.p.m) Airflow 65 m /h 76 l/s 74 CFM 55 m /h 4 l/s CFM 4 m /h 4 l/s 4 CFM 9 m /h 8 l/s 7 CFM HEATING Fan speed Number of rotations (r.p.m) Airflow HIGH 44 MED LOW QUIET m /h 86 l/s 94 CFM 54 m /h 5 l/s 8 CFM 45 m /h l/s 56 CFM m /h 89 l/s 88 CFM

20 - ( - 9) - MODEL : AS A4LC COOLING Fan speed HIGH MED LOW QUIET Number of rotations (r.p.m) Air flow 7 m /h 94 l/s 4 CFM 58 m /h 6 l/s 4 CFM 46 m /h 8 l/s 7 CFM 7 m /h l/s 8 CFM HEATING Fan speed Number of rotations (r.p.m) Air flow HIGH 48 MED LOW QUIET 95 7 m /h 94 l/s 4 CFM 6 m /h 67 l/s 5 CFM 5 m /h 9 l/s 94 CFM 4 m /h 7 l/s 47 CFM

21 - ( - ) - MODEL : AS A8LC COOLING Fan speed HIGH MED LOW QUIET Number of rotations (r.p.m) Air flow 7 m /h 94 l/s 4 CFM 58 m /h 6 l/s 4 CFM 46 m /h 8 l/s 7 CFM 7 m /h l/s 8 CFM HEATING Fan speed HIGH MED LOW QUIET Number of rotations (r.p.m) Air flow 7 m /h 94 l/s 4 CFM 6 m /h 67 l/s 5 CFM 5 m /h 9 l/s 94 CFM 4 m /h 7 l/s 47 CFM

22 - ( - ) - 8. OPERATION NOISE 8-. NOISE LEVEL CURVE MODEL : AS A7LC COOLING HEATING NC-65 NC-65 Octave band sound pressure level, db:(db=.µbar) Quiet High NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 Octave band sound pressure level, db:(db=.µbar) Quiet High NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz MODEL : AS A9LC COOLING 8 HEATING NC-65 NC-65 Octave band sound pressure level, db:(db=.µbar) Quiet High NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 Octave band sound pressure level, db:(db=.µbar) Quiet High NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz

23 - ( - ) - MODEL : AS ALC COOLING HEATING NC-65 NC-65 Octave band sound pressure level, db:(db=.µbar) High Quiet NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 Octave band sound pressure level, db:(db=.µbar) High Quiet NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz MODEL : AS A4LC COOLING 8 HEATING NC-65 NC-65 Octave band sound pressure level, db:(db=.µbar) Quiet High NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 Octave band sound pressure level, db:(db=.µbar) Quiet High NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz

24 - ( - ) - MODEL : AS A8LC COOLING HEATING NC-65 NC-65 Octave band sound pressure level, db:(db=.µbar) Quiet High NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 Octave band sound pressure level, db:(db=.µbar) Quiet High NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz

25 - ( - 4) SOUND LEVEL CHECK POINT

26 - ( - 5) - 9. ELECTRIC CHARACTERISTICS Model Name AS A7LC AS A9LC AS ALC Power Supply Voltage V Frequency Hz 5 Max Operating Current A Circuit breaker A 5 5 *)Wiring Spec. Connection Cable mm Limited wiring length m Model Name Power Supply Max Operating Current *)Wiring Spec. Voltage Frequency Main Fuse (Circuit breaker) Current V Hz AS A4LC AS A8LC A.5.5 A Connection Cable mm Limited wiring length m *) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E5) 5

27 - ( - 6) -. SAFETY DEVICES Model Protection form AS A7LC / AS A9LC / AS ALC / AS A4LC / AS A8LC Circuit protection Terminal protection Fan motor protection Current fuse (PCB) Current (thermal) fuse Thermal protection program.5a 5V A 5V C +5 - C OFF C ON

28 - ( - 7) -. OPTIONAL PARTS Exterior Parts name Model No. Summary Apple-catechin filter UTR-FA- Fine dust, invisible mold spores, and harmful microorganisms are absorbed onto the filter by static electricity, and further growth is inhibited and deactivated by the polyphenol ingredient extracted from apples. Ion deodorisation filter UTR-FA- The filter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra fine-particle ceramic.

29 R4A. SINGLE TYPE : AO R7LCC AO R9LCC AO RLCC AO R4LCC AO R8LCC DD_AO8E/ 7..6

30 - ( - ) -. SPECIFICATIONS AO R7-8LC Type Model name Power source Available voltage range Starting current Fan Compressor Refrigerant Refrigerant oil Enclosure Dimensions (H W D) Weight Operation range Airflow rate Sound pressure level Heat exchanger type Connection pipe Type Q'ty Motor output Type Q'ty Motor output Net Gross Net Gross Size Method Max. length Heating Heating Dimensions (H W D) Fin pitch Rows Stages Pipe type Fin type Type Charge Type Material Colour Liquid Gas Max. height difference Heating INVERTER HEAT PUMP AO R7LCC AO R9LCC AO RLCC V 5Hz 98-64V 5Hz A m /h,87,87,85,87,87,85 Propeller fan W db(a) mm Copper Aluminium Rotary W 75 R4A g 9,5 POE (VG74) Steel Beige mm kg (lb.) (7) (8) (77) (9) mm 6.5 ( /4 in.) 9.5 ( /8 in.) Flare m (chargeless : 5) 5 C to 4-5 to 4 AO R7-8LC Note : Specifications are based on the following conditions. : Indoor temperature of 7 CDB/9 CWB. and outdoor temperature of 5 CDB/4 CWB. Heating : Indoor temperature of CDB/5 CWB. and outdoor temperature of 7 CDB/6 CWB. Pipe length : 7.5 m, Height difference : m. (Outdoor unit - Indoor unit)

31 - ( - ) - Type INVERTER HEAT PUMP Model name Power source AO R4LCC AO R8LCC V 5Hz AO R7-8LC Available voltage range Starting current Fan Airflow rate Type Q'ty Heating 98-64V 5Hz A ,9, m /h,75,9 Propeller fan AO R7-8LC Sound pressure level Heat exchanger type Motor output Heating Dimensions (H W D) Fin pitch Rows Stages W db(a) mm Pipe type Copper Fin type Aluminium Compressor Refrigerant Refrigerant oil Type Q'ty Motor output Type Charge Type W g Rotary, R4A,5 POE(VG74) Enclosure Material Colour Steel Beige Dimensions (H W D) Net Gross mm Weight Net Gross kg(lb.) 4 (88) 44 (97) Size Liquid Gas mm 6.5 ( /4 in.).7 ( / in.) Connection pipe Method Flare Max. length Max. height difference m (chargeless : 5) 5 Operation range Heating C - to 4-5 to 4 Note : Specifications are based on the following conditions. : Indoor temperature of 7 CDB/9 CWB. and outdoor temperature of 5 CDB/4 CWB. Heating : Indoor temperature of CDB/5 CWB. and outdoor temperature of 7 CDB/6 CWB. Pipe length : 7.5 m, Height difference : m. (Outdoor unit - Indoor unit)

32 - ( - ) -. DIMENSIONS MODEL : AO R7LC, AO R9LC AO R7-8LC 54 (Unit : mm) AO R7-8LC Top view Front view Side view INSTALLATION PLACE 6 mm or more 54 5 mm or more mm or more 5 mm or more (Service space) mm or more If the space is larger that is stated, the condition will be the same as that are no obstacles.

33 - ( - 4) - MODEL : AO RLC (Unit : mm) 54 AO R7-8LC AO R7-8LC Top view 6 mm or more Front view 5 Side view INSTALLATION PLACE mm or more mm or more 5 mm or more (Service space) 5 mm or more If the space is larger that is stated, the condition will be the same as that are no obstacles.

34 - ( - 5) - MODEL : AO R4LC, AO R8LC (Unit : mm) AO R7-8LC AO R7-8LC Top view 79 6 Air flow 6 mm or more 578 Front view Side view INSTALLATION PLACE Bottom view mm or more mm or more mm or more (Service space) mm or more If the space is larger that is stated, the condition will be the same as that are no obstacles.

35 - ( - 6) -. REFRIGERANT CIRCUIT MODEL : AO R7LC, AO R9LC AO R7-8LC Muffler -Way valve Heat exchanger ( INDOOR ) -Way valve AO R7-8LC Compressor 4-Way valve Strainer Expansion valve Heat exchanger ( OUTDOOR ) Strainer Heating Refrigerant pipe diameter Liquid : /4" (6.5 mm) Gas : /8" (9.5 mm)

36 - ( - 7) - MODEL : AO RLC AO R7-8LC Muffler -Way valve Heat exchanger ( INDOOR ) -Way valve AO R7-8LC Compressor Muffler 4-Way valve Strainer Expansion valve Heat exchanger ( OUTDOOR ) Strainer Heating Refrigerant pipe diameter Liquid : /4" (6.5 mm) Gas : /8" (9.5 mm)

37 - ( - 8) - MODEL : AO R4LC, AO R8LC AO R7-8LC Sub-accumulator Muffler Compressor -Way valve 4-Way valve Heat exchanger ( INDOOR ) Heat exchanger ( OUTDOOR ) Sub-heat exchanger ( INDOOR ) -Way valve Strainer Expansion valve Strainer AO R7-8LC Heating Refrigerant pipe diameter Liquid : /4" (6.5 mm) Gas : /" (.7 mm)

38 - ( - 9) - 4. WIRING DIAGRAMS MODEL : AO R7LC, AO R9LC AO R7-8LC Reactor WHITE RED OR Reactor WHITE RED W W PCB (MAIN) W 7 W 8 W 9 RED WHITE RED WHITE R(U) Compressor CM S(V) C(W) AO R7-8LC Thermistor (pipe) BROWN BROWN Thermistor (Discharge Pipe) 4 4 C N 7 C N ORANGE WHITE FM Fan Motor Thermistor (outdoor temp.) RED WHITE W 4 W C N 7 C N RED BROWN BLUE ORANGE YELLOW WHITE PMV Expansion Valve Terminal N L Fuse 5VA GREEN W W C N 4WV 4-Way Valve Assy TO INDOOR UNIT

39 - ( - ) - MODEL : AO RLC AO R7-8LC Reactor WHITE RED OR Reactor WHITE RED W W PCB (MAIN) W 7 W 8 W 9 RED WHITE RED WHITE R(U) Compressor CM S(V) C(W) AO R7-8LC Thermistor (Discharge Pipe) Thermistor (pipe) BROWN BROWN 4 4 C N 7 C N ORANGE WHITE FM Fan Motor Thermistor (outdoor temp.) RED WHITE W 4 W C N 7 C N RED BROWN BLUE ORANGE YELLOW WHITE PMV Expansion Valve Terminal N L Fuse 5VA GREEN W W C N 4WV 4-Way Valve Assy TO INDOOR UNIT

40 - ( - ) - MODEL : AO R4LC, AO R8LC REACTOR AO R7-8LC YELLOW YELLOW WHITE RED W W W7 W8 W9 RED WHITE RED R(R) WHITE C M S(S) C(T) COMPRESSOR AO R7-8LC PIPE TEMP. THERMISTOR BROWN BROWN 4 DISCHARGE TEMP. THERMISTOR OUTDOOR TEMP. THERMISTOR TERMINAL N L RED WHITE GREEN FUSE 5V-A 4 W4 W W W CN7 CN7 CONTROLLER PCB ASSY CN8 CN4 CN RED WHITE YELLOW BLUE RED BROWN BLUE ORANGE YELLOW WHITE F M PMV 4WV FAN MOTOR EXPANSION VALVE 4-WAY VALVE TO INDOOR UNIT

41 - ( - ) - 5. COEFFICIENT OF COMPENSATION FOR PIPE LENGTH AND HEIGHT DIFFERENCE MODEL : AO R7LC, AO R9LC, AO RLC, AO R4LC, AO R8LC AO R7-8LC Height difference H (m) COOLING Indoor unit is upper than outdoor unit. Indoor unit is under than outdoor unit Pipe length (m) AO R7-8LC HEATING Pipe length (m) Height difference H (m) Indoor unit is upper than outdoor unit. Indoor unit is under than outdoor unit Height difference H Indoor unit Outdoor unit H Outdoor unit H Connection pipe Connection pipe Indoor unit Indoor unit is upper than outdoor unit. Indoor unit is under than outdoor unit.

42 - ( - ) - 6. ADDITIONAL CHARGE CALCULATION MODEL : AO R7LC, AO R9LC AO R7-8LC Refrigerant type Refrigerant amount g REFRIGERANT CHARGE R4A 9 AO R7-8LC Pipe length m 5 Additional charge g (Chargeless) + g/m MODEL : AO RLC Refrigerant type Refrigerant amount g R4A,5 REFRIGERANT CHARGE Pipe length m 5 Additional charge g (Chargeless) + g/m MODEL : AO R4LC, AO R8LC Refrigerant type Refrigerant amount g R4A 5 REFRIGERANT CHARGE Pipe length m 5 Additional charge g (Chargeless) + g/m

43 - ( - 4) - 7. AIR FLOW MODEL : AO R7LC, AO R9LC COOLING AO R7-8LC Number of rotations (r.p.m) 8 Airflow 87 m /h 59 l/s AO R7-8LC CFM HEATING Number of rotations (r.p.m) Airflow 87 m /h 8 59 l/s CFM MODEL : AO RLC COOLING Number of rotations (r.p.m) 8 Airflow 85 m /h 54 l/s 89 CFM HEATING Number of rotations (r.p.m) 8 Airflow 85 m /h 54 l/s 89 CFM

44 - ( - 5) - MODEL : AO R4LC COOLING AO R7-8LC Number of rotations (r.p.m) 8 Air flow 9 m /h 5 l/s 4 CFM AO R7-8LC HEATING Number of rotations (r.p.m) Air flow m /h 486 l/s CFM MODEL : AO R8LC COOLING Number of rotations (r.p.m) 86 Air flow m /h 556 l/s 77 CFM HEATING Number of rotations (r.p.m) 8 Air flow 9 m /h 5 l/s 4 CFM

45 - ( - 6) - 8. OPERATION NOISE 8-. NOISE LEVEL CURVE MODEL : AO R7LC AO R7-8LC Octave band sound pressure level, db:(db=.µbar) COOLING NC-65 NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 Octave band sound pressure level, db:(db=.µbar) HEATING NC-65 NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 AO R7-8LC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz MODEL : AO R9LC COOLING 8 HEATING NC-65 Octave band sound pressure level, db:(db=.µbar) NC-65 NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 Octave band sound pressure level, db:(db=.µbar) NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz

46 - ( - 7) - MODEL : AO RLC AO R7-8LC COOLING 8 7 NC-65 HEATING 8 7 NC-65 AO R7-8LC Octave band sound pressure level, db:(db=.µbar) NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 Octave band sound pressure level, db:(db=.µbar) NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz MODEL : AO R4LC COOLING 8 HEATING NC-65 NC-65 Octave band sound pressure level, db:(db=.µbar) NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 Octave band sound pressure level, db:(db=.µbar) NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz

47 - ( - 8) - MODEL : AO R8LC AO R7-8LC COOLING 8 7 NC-65 HEATING 8 7 NC-65 AO R7-8LC Octave band sound pressure level, db:(db=.µbar) NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 Octave band sound pressure level, db:(db=.µbar) NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz

48 - ( - 9) SOUND LEVEL CHECK POINT AO R7-8LC AO R7-8LC

49 - ( - ) - 9. ELECTRIC CHARACTERISTICS AO R7-8LC Model Name AO R7LC AO R9LC AO RLC Voltage V Power Supply Frequency Hz 5 Starting Current A AO R7-8LC Model Name AO R4LC AO R8LC Power Supply Starting Current Voltage Frequency V Hz A

50 - ( - ) -. SAFETY DEVICES Model AO R7-8LC Circuit protection Protection form Current fuse (NEAR THE TERMINAL) Current fuse (MAIN PRINTED CIRCUIT BOARD) AO R7LC / AO R9LC / AO RLC A 5V 5A 5V.5A 5V AO R4LC / AO R8LC AO R7-8LC Fan motor protection Thermal protection program OFF : C ON : C OFF : +5 - C ON : C Compressor protection Thermal protection program (DISCHARGE TEMP.) OFF : C ON : After 7 minutes

51 AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A4LCC AS ALCC AS ALFC OUTDOOR AO R4LCC AO RLCT AO RLFT

52 . INDOOR UNIT : ASÝA4LCC ASÝALCC ASÝALFC DD_ASE/4..

53 AS A4-LC(F). INDOOR UNIT CONTENTS AS A4-LC(F). FEATURE WIRELESS REMOTE CONTROLLER SPECIFICATIONS DIMENSIONS WIRING DIAGRAMS CAPACITY TABLE COOLING CAPACITY HEATING CAPACITY FAN PERFORMANCE AIR VELOCITY DISTRIBUTION AIR FLOW OPERATION NOISE NOISE LEVEL CURVE SOUND LEVEL CHECK POINT ELECTRIC CHARACTERISTICS SAFETY DEVICES OPTIONAL PARTS WIRED REMOTE CONTROLLER EXTERNAL CONNECT KIT

54 - ( - ) - AS A4-LC(F) FEATURE MODEL AS A4LCC AS ALCC AS ALFC AS A4-LC(F) FEATURES zall DC AO R4LCC AO RLCT AO RLFT Heat exchange capacities % up compared to conventional models DC fan motor High efficiency layout Large air flow and quiet operation by new air flow path b a b c DC fan motor V-PAM control V-PAM technology makes a compressor more powerful. DC scroll compressor More compact compared with conventional model a c Front view Back view New -row heat exchange system (4TYPE) zsuper quiet Air flow mode can be set in 4 steps and more detailed air flow setting is possible. zeasy maintenance Easy maintenance and always clean. Troublesome maintenance has been made easy. Since the front panel is easy to remove, maintenance is also easy. zinner drying operation This model is equipped with an inner drying function. After the power is turned off, the dry operation starts inside the air conditioner. This prevents the growth of mold and bacterial inside the air conditioner. During dew condensation Approx. mins Drying

55 - ( - ) - AS A4-LC(F) zpower diffuser Adoption of large power diffuser Strong vertical air flow provides powerful floor level heating. Healthy horizontal air flow does not blow cool air directly at the occupants in the room. AS A4-LC(F) o Power diffuser (full open) 6 9 (m) Outside air conditions: o C 6% Operation contents: Heating, Set temperature (Max set temp) o 9 ( C) o C, Air flow Hi, Air direction downward and front Power diffuser 6 9 (m) Outside air conditions: 5 o C 4% Operation contents:, Set temperature (Min set temp) o 8 ( C) 8 o C, Air flow Hi, Air direction downward and front zcompact design 998mm width compact design New model H x W998 x D8 H x W, x D (unit:mm) zlow outdoor air temperature cooling correspondence Corresponds to cooling operation at - C outdoor air temperature zcorresponds to maximum 5m long piping (TYPE) zair conditioner filter features Organic coating fin used heat exchanger Ion Deodorization Filter Apple-catechin Filter Pre Filter Antibacterial deodorizing pre-filter with special ceramic powder Long-life Ion Deodorization Filter Applecatechin Filter

56 - ( - ) - AS A4-LC(F) WIRELESS REMOTE CONTROLLER FEATURES ¾¾Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible. ¾¾Four kinds of timers. Easy operation. AS A4-LC(F) zbuilt-in timers Select from four different timer programs (On/Off/Program/Sleep). zprogram timer The program timer operates the ON and OFF timer once within a 4 hour period. zsleep timer The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping. operation/dry operation When the sleep timer is set, the set temperature automatically rises C every hour. The set temperature can rise up to a maximum of C. Heating operation When the sleep timer is set, the set temperature automatically drops C every minutes. The set temperature can drop to a maximum of 4 C. Timer setting C C C 4 C 6min. min. C C 6min. 9min. Timer setting

57 - ( - 4) - AS A4-LC(F) FUNCTIONS 5 SLEEP button MODE button AS A4-LC(F) SET TEMP. button ( / ) 4 COIL DRY button 5 Signal Transmitter 6 TIMER MODE button 7 TIMER SET ( + / - ) button 8 FAN CONTROL button START/STOP button SET button (Vertical) SET button (Horizontal) SWING button 4 RESET button TEST RUN button This button is used when installing the air conditioner, and should not be used under normal conditions, as it will cause the indoor unit s thermostat function to operate incorrectly. If this button is pressed during normal operation, the indoor unit will switch to test operation mode, and the Indoor Unit s OPERATION Indicator Lamp and TIMER Indicator Lamp will begin to flash simultaneously. To stop the test operation mode, press the SRART/STOP button to stop the air conditioner. 5 CLOCK ADJUST button 6 Remote Control Unit Display 7 Transmit Indicator 8 Clock Display Display panel Operating Mode Display Timer Mode Display Fan Speed Display Temperature SET Display COIL DRY Display 4 SLEEP Display 5 SWING Display SPECIFICATION SIZE (H x W x D mm) 76 x 56 x 8 WEIGHT ( g ) ACCESSORY Holder

58 - ( - 5) - AS A4-LC(F) SPECIFICATIONS Type WALL MOUNTED INVERTER HEAT PUMP Model name AS A4LCC AS ALCC Power source V~ 5Hz Available voltage range 98-64V ~ 5Hz ENERGY STAR RANK A B Heating A B Capacity Rated kw BTU/h 4, 7, Min.-Max. kw BTU/h,-7, 9,9-,7 Heating Rated kw BTU/h 7,6,7 Min.-Max. kw BTU/h,-6, 7,5-7,6 Input power Rated..66 Min.-Max kw Rated.4.64 Heating Min.-Max Current Rated Max.* 7 A Rated Heating Max.* EER.. kw/kw COP Heating.6.4 SENSIBLE CAPACITY kw POWER FACTOR % Heating Moisture removal l/h (pints/h).(5.).4(6.) High Med 9 9 Low Fan Sound pressure level Heat exchanger type Enclosure Dimensions ( H W D ) Weight Connection pipe Operation range Remote controller type Drain pipe Airflow rate Heating Quiet 6 6 m /h High Med 9 9 Low Quiet 6 6 Type Q'ty Cross flow fan Motor output W 4 4 High Med 4 4 Low 6 6 Quiet db(a) High Med 6 6 Heating Low Quiet Dimensions (H W D) mm Main : Sub : Main : Sub : 84 8., Sub : Fin pitch Main :., Sub :.4 Main :., Sub :.4, Sub :.4 Rows x Stages Main : 8, Sub : 4 Main : 8, Sub : 4, Sub : 4 Pipe type Copper Fin type Aluminium Material Polystyrene Colour WHITE Approximate colour of MANSELL N9.5/ Net mm Gross Net 4 (.8) kg(lb.) Gross 8 (9.6) Size Liquid Ø6.5 (Ø /4 in.) Ø9.5 (Ø /8 in.) mm Gas Ø5.88 (Ø 5/8 in.) Method Flare C 8 to %RH 8 or less Heating C or less Wireless Material PVC Size mm Outer diameter: 8 / Inner diameter: 6 AS A4-LC(F) Note : Specifications are based on the following conditions. : Indoor temperature of 7 CDB/9 CWB. and outdoor temperature of 5 CDB/4 CWB. Heating : Indoor temperature of CDB/5 CWB. and outdoor temperature of 7 CDB/6 CWBA. Pipe length : 7.5 m, Height difference : m.(outdoor unit - Indoor unit) The maximum current is the maximum value when operated within the operation range(temperature) * The maximum current is the total current of indoor unit and outdoor unit.

59 - ( - 6) - AS A4-LC(F) Type WALL MOUNTED INVERTER HEAT PUMP Model name AS ALFC Power source V~ 5Hz Available voltage range 98-64V ~ 5Hz European energy label A Heating A Capacity Rated kw 8. BTU/h 7, Min-Max kw.9-9. BTU/h 9,9-,7 Heating Rated kw 8.8 BTU/h, Min-Max kw.-. BTU/h 7,5-7,6 Input power Rated.49 Min-Max kw Rated.44 Heating Min-Max.5-4. Current Rated.9 Max 7. A Rated.7 Heating Max 9. EER. kw/kw COP Heating.6 SENSIBLE CAPACITY kw 6. POWER FACTOR 99 % Heating 99 Moisture removal l/h (pints/h). (5.6) High Med 9 Low 74 Fan Airflow Quiet 6 m /h rate High 5 Med 9 Heating Low 74 Quiet 6 Type Q'ty Cross flow fan Motor output W 4 High 48 Med 4 Low 7 Sound pressure level Quiet db(a) High 49 Heating Med 4 Low 7 Quiet Heat exchanger type Enclosure Dimensions ( H W D ) Weight Connection pipe Operation range Remote controller type Drain pipe Dimensions (H W D) mm Fin pitch Rows x Stages Pipe type Fin type Material Colour Main: Sub:84 8.,Sub:84 8. Main:., Sub:.4, Sub:.4 Main: 8, Sub: 4, Sub: 4 Copper Aluminium Polystyrene WHITE Approximate colour of MANSELL N9.5/ Net mm Gross Net 4 (.8 ) kg(lb.) Gross 8 (9.6 ) Liquid Ø9.5 (Ø/8 in.) Size mm Gas Ø5.88 (Ø5 /8 in.) Method Flare C 8 to %RH 8 or less Heating C or less Wireless Material PVC Size mm Outer diameter: 8 / Inner diameter: 6 AS A4-LC(F) Note : Specifications are based on the following conditions. : Indoor temperature of 7 CDB/9 CWB. and outdoor temperature of 5 CDB/4 CWB. Heating : Indoor temperature of CDB/5 CWB. and outdoor temperature of 7 CDB/6 CWBA. Pipe length : 7.5 m, Height difference : m.(outdoor unit - Indoor unit) The maximum current is the maximum value when operated within the opration range(temperature) * The maximum current is the total current of indoor unit and outdoor unit.

60 - ( - 7) - AS A4-LC(F) 444DIMENSIONS MODEL: AS A4LC, AS ALC, AS ALF (Unit : mm) AS A4-LC(F) INSTALLATION PLACE zmodel : AS A4LC, AS ALC Wall hook bracket 5 cm or more 6 cm or more 5 cm or more 5 cm or more cm or more (Wall cap) zmodel : AS ALF 5 cm or more 6 cm or more Wall hook bracket 5 cm or more 5 cm or more 8 cm or more (Wall cap)

61 - ( - 8) - AS A4-LC(F) 555WIRING DIAGRAMS MODEL: AS A4LC, AS ALC AS A4-LC(F) TO

62 - ( - 9) - AS A4-LC(F) MODEL: AS ALF AS A4-LC(F) TEST EX.OUT (OPTION) CN6 CN EX.IN (OPTION) CN4 CONTROOL BOARD REMOTE CONTROL UNIT (OPTION) WHITE RED TO

63 - ( - ) - AS A4-LC(F) 666CAPACITY TABLE 66666COOLING CAPACITY MODEL: AS A4LC AS A4-LC(F) AFR 8. Outdoor temperature Indoor temperature CDB CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI MODEL: AS ALC AFR 8. Outdoor temperature Indoor temperature CDB CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI MODEL: AS ALF AFR 8. Outdoor temperature Indoor temperature CDB CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI AFR : Air flow rate (m /min) TC : Total capacity (kw) SHC : Sensible Heat capacity (kw) PI : Power Input (kw)

64 - ( - ) - AS A4-LC(F) 66666HEATING CAPACITY MODEL: AS A4LC AS A4-LC(F) AFR 8. Outdoor temperature Indoor temperature ( CDB) ( CWB) TC PI TC PI TC PI TC PI TC PI MODEL: AS ALC AFR 8. Outdoor temperature Indoor temperature ( CDB) ( CWB) TC PI TC PI TC PI TC PI TC PI MODEL: AS ALF AFR 9. Outdoor temperature Indoor temperature ( CDB) ( CWB) TC PI TC PI TC PI TC PI TC PI AFR : Air flow rate (m /min) TC : Total capacity (kw) PI : Power Input (kw)

65 - ( - ) - AS A4-LC(F) 777FAN PERFORMANCE 77777AIR VELOCITY DISTRIBUTION MODEL: AS A4LC, AS ALC, AS ALF (m) Unit : m/s Note: Fan speed : High Operation mode : FAN Voltage : V AS A4-LC(F) Top view Vertical flap:up Horizontal flap:center (m) (m) Unit : m/s Top view Vertical flap:up Horizontal flap:right & Left (m) (m) Unit : m/s Side view Vertical flap:up Horizontal flap:center (m) (m) Unit : m/s Side view Vertical flap:down Horizontal flap:center (m)

66 - ( - ) - AS A4-LC(F) 77777AIR FLOW MODEL: AS A4LC zcooling AS A4-LC(F) Fan speed Number of rotations (r.p.m.) Air flow m /h HIGH 6 l/s 647 CFM 9 m /h MED 5 l/s 5 CFM 74 m /h LOW 94 6 l/s 45 CFM 6 m /h QUIET 8 7 l/s 65 CFM zheating Fan speed Number of rotations (r.p.m.) Air flow m /h HIGH 6 l/s 647 CFM 9 m /h MED 5 l/s 5 CFM 74 m /h LOW 94 6 l/s 45 CFM 6 m /h QUIET 8 7 l/s 65 CFM

67 - ( - 4) - AS A4-LC(F) MODEL: AS ALC zcooling AS A4-LC(F) Fan speed Number of rotations (r.p.m.) Air flow m /h HIGH 6 l/s 647 CFM 9 m /h MED 5 l/s 5 CFM 74 m /h LOW 94 6 l/s 45 CFM 6 m /h QUIET 8 7 l/s 65 CFM zheating Fan speed Number of rotations (r.p.m.) Air flow m /h HIGH 6 l/s 647 CFM 9 m /h MED 5 l/s 5 CFM 74 m /h LOW 94 6 l/s 45 CFM 6 m /h QUIET 8 7 l/s 65 CFM

68 - ( - 5) - AS A4-LC(F) MODEL: AS ALF zcooling AS A4-LC(F) Fan speed Number of rotations (r.p.m.) Air flow m /h HIGH 4 6 l/s 647 CFM 9 m /h MED 5 l/s 5 CFM 74 m /h LOW 6 l/s 45 CFM 6 m /h QUIET 9 7 l/s 65 CFM zheating Fan speed Number of rotations (r.p.m.) Air flow 5 m /h HIGH 5 9 l/s 677 CFM 9 m /h MED 5 l/s 5 CFM 74 m /h LOW 6 l/s 45 CFM 6 m /h QUIET 9 7 l/s 65 CFM

69 - ( - 6) - AS A4-LC(F) 888OPERATION NOISE 88888NOISE LEVEL CURVE MODEL: AS A4LC AS A4-LC(F) z zheating Octave band sound pressure level, db:(db=.µbar) High Quiet NC-65 NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- Octave band sound pressure level, db:(db=.µbar) Quiet High NC-65 NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz MODEL: AS ALC z zheating Octave band sound pressure level, db:(db=.µbar) High Quiet NC-65 NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- Octave band sound pressure level, db:(db=.µbar) Quiet High NC-65 NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz

70 - ( - 7) - AS A4-LC(F) MODEL: AS ALF AS A4-LC(F) z zheating Octave band sound pressure level, db:(db=.µbar) Quiet High NC-65 NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- Octave band sound pressure level, db:(db=.µbar) Quiet High NC-65 NC-6 NC-55 NC-5 NC-45 NC-4 NC-5 NC- NC-5 NC- NC-5 NC ,, 4, 8, Octave band center frequency,hz ,, 4, 8, Octave band center frequency,hz

71 - ( - 8) - AS A4-LC(F) 88888SOUND LEVEL CHECK POINT AS A4-LC(F)

72 - ( - 9) - AS A4-LC(F) 999ELECTRIC CHARACTERISTICS Model name AS A4LC AS ALC, AS ALF Power supply Voltage V ~ Frequency Hz 5 Max. operating current A.. Circuit breaker A.4.4 *)Wiring Spec. Connection cable mm Limited wiring length m 5 *) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E5) AS A4-LC(F)

73 - ( - ) - AS A4-LC(F) SAFETY DEVICES Protection form Model AS A4LC, AS ALC, AS ALF AS A4-LC(F) Circuit protection Current fuse (PCB).5A 5V Terminal protection Current (thermal) fuse A 5V Fan motor protection Thermal protector program +5 - C OFF C ON

74 - ( - ) - AS A4-LC(F) OPTIONAL PARTS Exterior Parts name Model No. Summary AS A4-LC(F) SU MO TU WE TH FR SA AM PM Wired remote controller UTB- UD Unit control is performed by wired remote controller. Apple-catechin filter UTR-FA- Fine dust, invisible mold spores, and harmful microorganisms are absorbed onto the filter by static electricity, and further growth is inhibited and deactivated by the polyphenol ingredient extracted from apples. Ion deodorisation fi lter UTR-FA- The filter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra fine-particle ceramic. External connect kit UTY-XWZX Use to connect with various peripheral devices and air conditioner PC board.

75 - ( - ) - AS A4-LC(F) FEATURES WIRED REMOTE CONTROLLER ¾¾Various timer setup (ON / OFF / WEEKLY) are possible. ¾¾Equipped with weekly timer as standard function. ( times Start / Stop per day for a week) ¾¾When setting up a timer, operation mode and a temperature setup can be changed. ¾¾When a failure occurs,the error code is displayed. ¾¾Error indication. ¾¾Easy installation with a slim shape with no bulge in the back. AS A4-LC(F) zsimple function setting Setting of the air conditioner selection function is performed by remote controller. zhigh performance and compact size Three functions are combined in one unit. Wired remote controller Weekly + + timer Setback timer zbuilt-in timers Weekly timer Possible to set ON/OFF time to operate twice each day of the week. SU MO TU WE TH FR SA Easy-to-understand time bar display Setback timer Possible to set temperature for two time spans and for each day of the week. SU MO TU WE TH FR SA 7 7 SU MO TU WE TH FR SA Setup screen example (Set to Wednesday: 8: to :.) 4 C Screen after setup Setup screen example (Set from Sunday to Saturday: : to 5:, 8 C.) 8 C Time Time At "Weekly timer" + "Set back timer" setup 4 C 8 C 4 C 8 C 4 C Time zeasy-to-understand operation Timer area Operation area zsimple installation Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is needed. [Variable timer control] The operation/display sections are zoned according to time and operation, enabling variable programming to match application. European switch box JIS box

76 - ( - ) - AS A4-LC(F) FUNCTIONS Display panel DIMENSION [ Unit : mm ] 7 START/STOP button Pressed to start and stop operation. Set temperature button Selects the setting temperature. Master control button Selects the operating mode(auto, HEAT, FAN, COOL, DRY). 4 Fan control button Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH). 5 Economy button Turns the economy efficient mode on and off. 6 Timer mode (CLOCK ADJUST) button Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER). Set the current time. 7 Day (DAY OFF) button Temporarily cancels of one day timer. 8 Set back button Pressed to select the set back timer. 9 Set time button Pressed to set time. Delete button The schedule of a weekly timer is deleted. Set button Sets the date, hour, minute and on-off time. Vertical airflow direction and swing button Push for two seconds to change the swing mode. Horizontal airflow direction and swing button Push for two seconds to change the swing mode. 4 Filter button 5 Operation lamp Lights during operation and when the timer is on. 6 Timer and clock display 7 Operation mode display 8 Fan speed display 9 Operation lock display Temperature display Function display Defrost display AS A4-LC(F) Thermo sensor display Economy display Vertical swing display Horizontal swing display Filter display Functions will be different due to type of indoor unit. For details, please see operation manual. SPECIFICATION SIZE (H x W x D mm) x x 7 WEIGHT ( g ) 6 CABLE LENGTH ( m ) POWER ( V )

77 - ( - 4) - AS A4-LC(F) EXTERNAL CONNECT KIT This kit allows to operate the air conditioner, such as stopping and starting, using an external device, and output the operation status of the air conditioner. AS A4-LC(F) Only operation and stop signals will be output. Use the remote control to check the operation mode, temperature, and airflow. Check the error information on the display area of the main unit. Operation mode, temperature, and airflow cannot be set by external input. Use the remote controller to set. If the air-conditioner is activated by external input, it will operate in the settings before stop. To change the settings, use the remote controller. CONTROL INPUT SETTING You can control air conditioner ON / OFF operation by external input. zsignal specification No voltage ON/OFF continuous signal. Contact capacity : DCV ma External input signal ON OFF Remote controller signal ON OFF ON OFF Indoor unit status OPERATION STOP zinstallation example For remote operation Indoor unit Print circuit board External input Orange Yellow External device ( Field supply ) External output For external timer operation Indoor unit Print circuit board External input Orange Yellow External device ( Field supply ) External output

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR OUTDOOR 1. INDOOR UNIT : DTR_AS046E_02 2010.12.02 1. INDOOR UNIT CONTENTS 1. FEATURE... 01-01 2. WIRELESS REMOTE CONTROLLER... 01-03 3.

More information

SPLIT TYPE ROOM AIR CONDITIONER FLOOR TYPE

SPLIT TYPE ROOM AIR CONDITIONER FLOOR TYPE SPLIT TYPE ROOM AIR CONDITIONER FLOOR TYPE Indoor unit AGYF09LAC AGYFLAC AGYFLAC AGYFLAC Outdoor unit AOYV09LAC AOYVLAC AOYVLAC AOYVLAL CONTENTS SPECIFICATIONS..................... DIMENSIONS.........................

More information

SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE

SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE Indoor unit ASYA24LCC ASYA24LCC ASYA24LCC Outdoor unit AOYR24LCC AOYR24LCD AOYR24LCL CONTENTS SPECIFICATIONS..................1 DIMENSIONS.....................

More information

R410A TECHNICAL MANUAL. Inverter Single Split Series Air Conditioner. FTK-J, FTXN-J Series. Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2

R410A TECHNICAL MANUAL. Inverter Single Split Series Air Conditioner. FTK-J, FTXN-J Series. Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2 R410A TECHNICAL MANUAL Inverter Single Split Series Air Conditioner FTK-J, FTXN-J Series Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2 Table of Contents Table of Contents Nomenclature...1 Indoor...1 Outdoor...1

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASH9LSACW ASH12LSACW Outdoor unit AOH9LSAC AOH12LSAC CONTENTS SPECIFICATIONS...................... 1 DIMENSIONS..........................

More information

ASU18RLB ASU24RLB AOU18RLB AOU24RLB SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE CONTENTS

ASU18RLB ASU24RLB AOU18RLB AOU24RLB SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE CONTENTS SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE Indoor unit ASU8RL ASURL Outdoor unit AOU8RL AOURL CONTENTS SPECIFICATIONS................... DIMENSIONS...................... REFRIGERANT SYSTEM DIAGRAM....

More information

High Wall Type ( 2 Series )

High Wall Type ( 2 Series ) Jan.05' Engineering Data High Wall Type ( 2 Series ) Indoor Unit MMK-AP0072H MMK-AP0092H MMK-AP0122H 1. Equipments 2. Technical Specifications 3. Dimensional Drawing 4. Wiring Diagram 5. Refrigerant Cycle

More information

Indoor Console. Slim Design This is only 199mm thick, the slimmest on the market. Its slim design easily integrates the unit into your décor.

Indoor Console. Slim Design This is only 199mm thick, the slimmest on the market. Its slim design easily integrates the unit into your décor. Indoor Console Slim Design This is only 199mm thick, the slimmest on the market. Its slim design easily integrates the unit into your décor. Black Display Functional art, the touch screen display is elegant

More information

Outdoor Units R-410A ARX-GV1B

Outdoor Units R-410A ARX-GV1B Outdoor Units R-40A ARX-GVB t A i n y U k BS r o AV t o0g i d- lt4x pur- SRAO 2 Specifications Outdoor Units R-40A ARX-GVB 2- NOMINAL CAPACITY AND NOMINAL INPUT ARX20GVB ARX25GVB ARX5GVB For combination

More information

Split-Sky Air FAYP-B Wall Mounted Unit

Split-Sky Air FAYP-B Wall Mounted Unit TECHNICAL DATA Split-Sky Air FAYP-B Wall Mounted Unit Split Sky Air ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential

More information

R22 TECHNICAL MANUAL. Split Unit Air Conditioner Ceiling Cassette C & E Series FF-C, FHC-E, FFY-C, FHYC-E. Cooling only & Heatpump [50Hz]

R22 TECHNICAL MANUAL. Split Unit Air Conditioner Ceiling Cassette C & E Series FF-C, FHC-E, FFY-C, FHYC-E. Cooling only & Heatpump [50Hz] R22 TECHNICAL MANUAL Split Unit Air Conditioner Ceiling Cassette C & E Series FF-C, FHC-E, FFY-C, FHYC-E Cooling only & Heatpump [50Hz] Table of Contents Table of Contents Nomenclature...1 Indoor...1

More information

VRF Indoor Unit 50Hz. Type: Wall Mounted M Series Wall Mounted S Series

VRF Indoor Unit 50Hz. Type: Wall Mounted M Series Wall Mounted S Series VRF Indoor Unit 50Hz Type: Wall Mounted M Series Wall Mounted S Series Contents 01 Wall Mounted M Series 20 Wall Mounted S Series MCAC-VTSM-2016-05 Wall Mounted M Series Wall Mounted M Series 1. Features...

More information

DUCT type. SPLIT TYPE AIR CONDITIONER (50Hz) Models Indoor unit Outdoor unit C O N T E N T S

DUCT type. SPLIT TYPE AIR CONDITIONER (50Hz) Models Indoor unit Outdoor unit C O N T E N T S SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type Models Indoor unit Outdoor unit RD-90EB RO-90EPB C O N T E N T S SPECIFICATIONS... OUTLINE AND DIMENSIONS... CIRCUIT DIAGRAM...5 REFRIGERANT SYSTEM DIAGRAM...6

More information

technical data air conditioning systems Round Flow Cassette FXFQ-P9VEB

technical data air conditioning systems Round Flow Cassette FXFQ-P9VEB technical data Round Flow Cassette FXFQ-P9VEB air conditioning systems technical data Round Flow Cassette FXFQ-P9VEB air conditioning systems TABLE OF CONTENTS FXFQ-P9VEB 1 Specifications.......................................................

More information

FFQN-C, FCRN-E, FFRN-C

FFQN-C, FCRN-E, FFRN-C R410A TECHNICAL MANUAL Split Unit Air Conditioner Ceiling Cassette C & E Series FCQN-E, FFQN-C, FCRN-E, FFRN-C Cooling only & Heatpump [50Hz] DAIKIN_FFRN.indb i 12/27/2012 9:28:06 AM DAIKIN_FFRN.indb ii

More information

1. Features Specifications Dimensions Service Spaces Piping Diagrams Wiring Diagrams...

1. Features Specifications Dimensions Service Spaces Piping Diagrams Wiring Diagrams... MCAC-VTSM-2013-08 1. Features... 264 2. Specifications... 265 3. Dimensions... 268 4. Service Spaces... 272 5. Piping Diagrams... 273 6. Wiring Diagrams... 274 7. Capacity Tables... 276 8. Electrical Characteristics...

More information

technical data air conditioning systems RXG-C Wall Mounted, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems RXG-C Wall Mounted, Inverter Controlled Unit Split Sky Air technical data RXG-C Wall Mounted, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human

More information

Digital Inverter 4 series

Digital Inverter 4 series TCTC-E14-LC005-2 Digital Inverter 4 series Outdoor Unit RAV-SM304ATP-E RAV-SM304ATJP-E RAV-SM4ATP-E RAV-SM4ATJP-E I ndoor Unit RAV-SM307KRTP-E RAV-SM7KRTP-E RAV-SM7CTP-E RAV-SM304MUT-E RAV-SM4MUT-E RAV-SM304SDT-E

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER ASY9USBCW AOY9UGBC ASY12USBCW AOY12UGBC. Models Indoor unit Outdoor unit

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER ASY9USBCW AOY9UGBC ASY12USBCW AOY12UGBC. Models Indoor unit Outdoor unit SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit Outdoor unit ASY9USBCW AOY9UGBC ASY12USBCW AOY12UGBC CONTENTS SPECIFICATIONS....................... 1 OUTLINE AND DIMENSIONS............

More information

Engineering Data Book. High Static Duct 8, 10HP Digital Inverter. Indoor Unit. Outdoor Unit

Engineering Data Book. High Static Duct 8, 10HP Digital Inverter. Indoor Unit. Outdoor Unit E10-1 High Static Duct 8, 10HP Digital Inverter Engineering Data Book Indoor Unit RAV-SM2242DT-E RAV-SM2802DT-E RAV-SM2242DT-TR RAV-SM2802DT-TR Outdoor Unit RAV-SM2244AT8-E RAV-SM2804AT8-E Contents 1 Specifications..............................................................

More information

SPLIT TYPE AIR CONDITIONER. CASSETTE type. Models Indoor unit Outdoor unit MC24Y3E

SPLIT TYPE AIR CONDITIONER. CASSETTE type. Models Indoor unit Outdoor unit MC24Y3E SPLIT TYPE AIR CONDITIONER CASSETTE type Models Indoor unit Outdoor unit C24YE MC24Y3E MR24Y3E1 SPECIFICATIONS TYPE COOL & HEAT INDOOR UNIT MC24Y3E OUTDOOR UNIT MR24Y3E1 COOLING CAPACITY 23,500-22,500

More information

Engineering Data Book. High Static Duct 8, 10HP Digital Inverter. Indoor Unit. Outdoor Unit

Engineering Data Book. High Static Duct 8, 10HP Digital Inverter. Indoor Unit. Outdoor Unit E0--2 High Static Duct 8, 0HP Digital Inverter Engineering Data Book Indoor Unit RAV-SM2242DT-E RAV-SM2802DT-E RAV-SM2242DT-TR RAV-SM2802DT-TR Outdoor Unit RAV-SM2244AT8-E RAV-SM2804AT8-E Contents Specifications..............................................................

More information

ROOF TOP (SERIES SR) 10.8 TO 103 KW 37,000 TO 351,000 Btuh

ROOF TOP (SERIES SR) 10.8 TO 103 KW 37,000 TO 351,000 Btuh ROOF TOP (SERIES ) 10.8 TO 103 KW 37,000 TO 351,000 Btuh These rooftop units are complete, self contained air conditioners fully assembled, wire, charged and tested prior to shipment, each unit is delivered

More information

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU18RLXFW AOU24RLXFW ASU18RLF ASU24RLF R410A

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU18RLXFW AOU24RLXFW ASU18RLF ASU24RLF R410A SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU18RLF ASU24RLF AOU18RLXFW AOU24RLXFW R410A CONTENTS 1. DESCRIPTION OF EACH CONTROL OPERATION

More information

technical data air conditioning systems RKS-C RKS-B Pair Application, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems RKS-C RKS-B Pair Application, Inverter Controlled Unit Split Sky Air technical data RKS-C RKS-B Pair Application, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help

More information

technical data air conditioning systems MXS-B Multi Application Split Sky Air

technical data air conditioning systems MXS-B Multi Application Split Sky Air technical data MXS-B Multi Application air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the environment

More information

Superior Performance in Extreme Temperature Submittal Data: SAP09HP230V1A

Superior Performance in Extreme Temperature Submittal Data: SAP09HP230V1A Superior Performance in Extreme Temperature Submittal Data: 9,000 BTU/H Wall Mounted Heat- Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES

More information

AHN 064 to 304 EHN/CHN 064 to 304

AHN 064 to 304 EHN/CHN 064 to 304 u Horizontal Packaged and Split Air Conditioners AHN 64 to 34 EHN/CHN 64 to 34 6. to 29.2 kw 6.4 to 29.4 kw Engineering Data Manual EDM AECHN-A.1GB Date : June 28 Supersedes : None Technical Description

More information

Split. Air Conditioning Technical Data FTXC-A > FTXC25AV1B > FTXC35AV1B > FTXC50AV1B > FTXC60AV1B

Split. Air Conditioning Technical Data FTXC-A > FTXC25AV1B > FTXC35AV1B > FTXC50AV1B > FTXC60AV1B Split Air Conditioning Technical Data FTXC-A > FTXC25AV1B > FTXC35AV1B > FTXC50AV1B > FTXC60AV1B Indoor Unit FTXC-A TABLE OF CONTENTS FTXC-A 1 Features.............................................................

More information

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit SPLIT TYPE AIR CONDITIONER CASSETTE type (50Hz) Models Indoor unit Outdoor unit RCW-25CA RCW-30CA RO-25A RO-30A C O N T E N T S SPECIFICATIONS........................................ 1 OUTLINE AND DIMENSIONS..............................

More information

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit CONTENTS RO-25A RO-25RA RO-30A RO-30RA RC-25A RC-25RA RC-30A RC-30RA

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit CONTENTS RO-25A RO-25RA RO-30A RO-30RA RC-25A RC-25RA RC-30A RC-30RA SPLIT TYPE AIR CONDITIONER CASSETTE type (50Hz) Models Indoor unit Outdoor unit RC-25A RC-25RA RC-30A RC-30RA RO-25A RO-25RA RO-30A RO-30RA CONTENTS SPECIFICATIONS........................................

More information

D M S 760 C01 A A 1 1

D M S 760 C01 A A 1 1 CONTENTS Description Features Options Available Selection Method Product Data Cooling Performance Data (85 F Ambient Cooling Performance Data (95 F Ambient) Cooling Performance Data (105 F Ambient)..............................

More information

SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type

SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type Models Indoor unit Outdoor unit ARY7RLB AOY7RGA CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... 2 CIRCUIT DIAGRAM... 3 INDOOR P. C. BOARD CIRCUIT DIAGRAM...

More information

Ceiling Concealed Series FDMRN-AV1K. 50Hz. Preliminary

Ceiling Concealed Series FDMRN-AV1K. 50Hz. Preliminary Ceiling Concealed Series FDMRN-AV1K 50Hz Nomenclature Main Benefits Engineering and Physical Data Electrical Data Capacity Tables Outline and Dimensions Electrical Connection Refrigerant Piping Nomenclature

More information

SINGLE. Technical Data Book. Big Duct for Europe (R410A, 50Hz, H/P) Model : AC180JNHPKH/EU AC180JXAPNH/EU AC200JNHPKH/EU AC200JXAPNH/EU

SINGLE. Technical Data Book. Big Duct for Europe (R410A, 50Hz, H/P) Model : AC180JNHPKH/EU AC180JXAPNH/EU AC200JNHPKH/EU AC200JXAPNH/EU SINGLE Technical Data Book Big Duct for Europe (R410A, 50Hz, H/P) Model : AC180JNHPKH/EU AC180JXAPNH/EU AC200JNHPKH/EU AC200JXAPNH/EU History Version Modification Date Remark Ver.1.0 Release SINGLE Big

More information

Outdoor Units, 50Hz, R410A

Outdoor Units, 50Hz, R410A LG AIR CONDITIONERS Outdoor Units, 50Hz, R410A 20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355 Seoul 150-721, Korea Phone: 3777-7969 Fax: 3777-5137/8 http://www.lge.com Approvals: EN ISO 9001 BS EN ISO

More information

FDYMP-D, FDP-D, FGP-D, FDYP-E, FGYP-E

FDYMP-D, FDP-D, FGP-D, FDYP-E, FGYP-E R407C TECHNICAL MANUAL Split Systems Air Conditioner Ducted Blower D & E Series FDMP-D, FDYMP-D, FDP-D, FGP-D, FDYP-E, FGYP-E series Cooling only & Heatpump [50Hz] Table of Contents Table of Contents

More information

Four-way Cassette Type

Four-way Cassette Type Four-way Cassette Type Four-way Cassette Type 1. Features... 9 2. Specifications... 12 3. Dimensions... 17 4. Service Space... 18 5. Wiring Diagrams... 19 6. Capacity Tables... 21 7. Electric Characteristics...

More information

SERVICE MANUAL OUTDOOR UNIT. No. OB386

SERVICE MANUAL OUTDOOR UNIT. No. OB386 SPLIT-TYPE AIR CONDITIONERS Revision D: MU-A20VB- E and MU-A5VB- E have been added. Please void OB86 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A No. OB86 REVISED EDITION-D Models MU-A20VB-

More information

technical data Systems RSX(Y)P-K7W1 Inverter cooling only / heat pump series

technical data Systems RSX(Y)P-K7W1 Inverter cooling only / heat pump series technical data Systems RSX(Y)P-K7W1 Inverter cooling only / heat pump series Inverter cooling only / heat pump series RSX(Y)P5,8,10K7W1 RSX(Y)P-K7W1 1 Inverter cooling only / heat pump series 1 1 Specifications

More information

Air Cooled Packaged Units

Air Cooled Packaged Units Air Cooled Packaged Units Technical Data OPA 465, OPA 550, OPA 705, OPA 855, OPA 960 (ECO) Cooling Capacity 44.9kW - 96.0kW Heating Capacity 41.1kW - 90.0kW Contents OPA 465 960 ECO 3 General 3 Applications

More information

DRAFT. Technical Data OPA Ducted Three Phase Packaged Air Conditioners. 47 kw 96 kw

DRAFT. Technical Data OPA Ducted Three Phase Packaged Air Conditioners. 47 kw 96 kw DRAFT Ducted Three Phase Packaged Air Conditioners Technical Data 96 Twin System Enables Staging Extra Long Life Epoxy Coated Outdoor Coil OPTION TZT-71 Controller & Digital Scroll Compressor for close

More information

CASSETTE type SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit CONTENTS

CASSETTE type SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit CONTENTS SPLIT TYPE AIR CONDITIONER CASSETTE type Models Indoor unit Outdoor unit AUU8RC AUU4RC AOU8RC AOU4RC CONTENTS SPECIFICATIONS........................................ OUTLINE AND DIMENSIONS..............................

More information

Fault Codes. J control

Fault Codes. J control J control Timer Temp Fault Codes 12 11 10 9 8 7 6 5 4 3 2 1 30 29 28 27 26 25 24 23 22 21 20 Enter unit inspection mode by pushing the UP and DOWN buttons simultaneously for two seconds. Ensure that the

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Compact Wall Mounted Wall Mounted / Floor Compact Cassette / Slim Duct INVERTER MULTI

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Compact Wall Mounted Wall Mounted / Floor Compact Cassette / Slim Duct INVERTER MULTI SPLIT TYPE ROOM AIR CONDITIONER Compact Wall Mounted Wall Mounted / Floor Compact Cassette / Slim Duct INVERTER MULTI SERVICE INSTRUCTION Models Indoor unit Outdoor unit ASU7RLF ASU9RLF ASU2RLF ASU8RLF

More information

Concealed Ducted Split Series R22

Concealed Ducted Split Series R22 Concealed Ducted Split Series R22 24-60 MBH Ducted Split with Hermetic Compressor Tropical 50 Hz For more technical information please visit Table of Contents INTRODUCTION 2 NOMENCLATURE 2 UNIT RATING

More information

Split-Sky Air RMX-JZ Super Multi Plus

Split-Sky Air RMX-JZ Super Multi Plus TECHNICAL DATA Split-Sky Air RMX-JZ Super Multi Plus Split Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the environment from the potential

More information

Split-Sky Air FDYP-B7 Concealed Ceiling Unit

Split-Sky Air FDYP-B7 Concealed Ceiling Unit TECHNICAL DATA Split-Sky Air FDYP-B7 Concealed Ceiling Unit Split Sky Air ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the

More information

1 Features. Indoor Units CONCEALED CEILING UNIT FXSQ-P7VEB. VRV Systems Indoor Units

1 Features. Indoor Units CONCEALED CEILING UNIT FXSQ-P7VEB. VRV Systems Indoor Units t i t l r - I Features s e Cs m B ne d E Ue V s 7 ya P os e oc Q dvn S nr ox VF C Reduction of power consumption of 20% (compared to FXSQ-M8 series) through use of new DC fan Improved comfort thanks to

More information

SPLIT DUCTED UNIT SCA300C / SCA300E TECHNICAL SELECTION DATA SPECIFICATION SUMMARY UNIT FEATURES CONTROL OPTIONS UNIT COMPLIANCE

SPLIT DUCTED UNIT SCA300C / SCA300E TECHNICAL SELECTION DATA SPECIFICATION SUMMARY UNIT FEATURES CONTROL OPTIONS UNIT COMPLIANCE TECHNICAL SELECTION DATA SPLIT DUCTED UNIT 3 THREE PHASE SCROLL TWO STAGE CENTRIFUGAL LOUVRE AXIAL UNIT FEATURES Scroll Compressor Multiple Speed Outdoor Fans Louvred Outdoor Coil Guard Pre-charged with

More information

PACKAGE UNIT PCA340U TECHNICAL SELECTION DATA. -10 o C UNIT FEATURES SPECIFICATION SUMMARY UNIT OPTIONS CONTROL OPTIONS UNIT COMPLIANCE.

PACKAGE UNIT PCA340U TECHNICAL SELECTION DATA. -10 o C UNIT FEATURES SPECIFICATION SUMMARY UNIT OPTIONS CONTROL OPTIONS UNIT COMPLIANCE. TECHNICAL SELECTION DATA PACKAGE UNIT + o C -10 o C 3 THREE PHASE SCROLL TWO STAGE CENTRIFUGAL LOUVRE LIANT SCROLL RESSOR AXIAL UNIT FEATURES SPECIFICATION SUMMARY Scroll Compressor Multiple Speed Outdoor

More information

V33A Standard/High Efficiency 360 Cassette Indoor Models - 60HZ

V33A Standard/High Efficiency 360 Cassette Indoor Models - 60HZ PRODUCT SPECIFICATIONS Low-sound, standard or high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has

More information

Room Air Conditioner SVC MANUAL(Exploded View)

Room Air Conditioner SVC MANUAL(Exploded View) Internal Use Only http://biz.lgservice.com Room Air Conditioner SVC MANUAL(Exploded View) MODEL : AS-W093F2B2(LAN090HVP/LAU090HVP) AS-W123F2B2(LAN120HVP/LAU090HVP) CAUTION Before Servicing the unit, read

More information

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD. Technical Support Division 2012.10 1 1. External appearance 2. Nomenclature 3. Specifications 4. Dimensions 5. Service space 6. Piping diagram 7. Wiring diagram 8. Capacity tables 9. Electric characteristics

More information

Bosch Climate 5000 Ductless Minisplit System

Bosch Climate 5000 Ductless Minisplit System Engineering Submittal Sheet Overview and Certifications [single zone only] Standard Features and Field Installed Accessories Standard Features R-410A chlorine-free refrigerant with pre-charge for line

More information

V33B High Efficiency 360 Cassette Indoor Models - 60HZ

V33B High Efficiency 360 Cassette Indoor Models - 60HZ PRODUCT SPECIFICATIONS Low-sound, high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has motor-driven

More information

Air Conditioning Technical Data FXDQ-A3 > FXDQ15A3VEB > FXDQ20A3VEB > FXDQ25A3VEB > FXDQ32A3VEB > FXDQ40A3VEB > FXDQ50A3VEB > FXDQ63A3VEB

Air Conditioning Technical Data FXDQ-A3 > FXDQ15A3VEB > FXDQ20A3VEB > FXDQ25A3VEB > FXDQ32A3VEB > FXDQ40A3VEB > FXDQ50A3VEB > FXDQ63A3VEB Air Conditioning Technical Data FXDQ-A3 > FXDQ15A3VEB > FXDQA3VEB > FXDQ25A3VEB > FXDQ32A3VEB > FXDQ40A3VEB > FXDQ50A3VEB > FXDQ63A3VEB TABLE OF CONTENTS FXDQ-A3 1 Features.............................................................

More information

PRODUCT CODE MODEL NAME. No. DESCRIPTION DWG No. PART No. Qty Qty Qty Qty Qty Qty REMARKS

PRODUCT CODE MODEL NAME. No. DESCRIPTION DWG No. PART No. Qty Qty Qty Qty Qty Qty REMARKS ERSATZTEILE RAS-4HNC1E, 3~ 400V 50Hz RAS-5HNC1E, 3~ 400V 50Hz RAS-6HNC1E, 3~ 400V 50Hz 1 Rear Cover Assy XEK24870 A E03946 1 1 1 1 1 1 Assembly 1-1 Pipe Cover B 17C86251 A P27003 1 1 1 1 1 1 1-2 Handle

More information

VRF. For Commercial and Light Commercial

VRF. For Commercial and Light Commercial 118 VRF For Commercial and Light Commercial 119 SOLUTIONS SMALL OFFICES Fujitsu General provides perfect total air conditioning systems that take into account energy saving, low noise, comfortable airflow,

More information

Vertical Air Handling Unit type

Vertical Air Handling Unit type Vertical Air Handling Unit type Engineering Databook MMD-AP0120VHG2UL MMD-AP0180VHG2UL MMD-AP0240VHG2UL MMD-AP0300VHG2UL MMD-AP0360VHG2UL MMD-AP0420VHG2UL MMD-AP0480VHG2UL MMD-AP0600VHG2UL Contents 1.

More information

Room Air Conditioner SVC MANUAL(Exploded View)

Room Air Conditioner SVC MANUAL(Exploded View) Internal Use Only http://biz.lgservice.com Room Air Conditioner SVC MANUAL(Exploded View) MODEL : AS-W363DGU1(Set) ASNW363DGU1 ASUW363DGU1 AS-W303DGU1(Set) ASNW303DGU1 ASUW303DGU1 CAUTION Before Servicing

More information

DC INVERTER VRF SYSTEMS C-VRF

DC INVERTER VRF SYSTEMS C-VRF DC INVERTER VRF SYSTEMS C-VRF Index VRF System Overview 4 C-VRF 9 Advantages 10 Benefits For Users 14 Benefits For Installers 18 C-VRF MINI 27 Advantages 28 Indoor Units 33 Indoor Units Line Up 34 Indoor

More information

DVM. Technical Data Book

DVM. Technical Data Book DVM Technical Data Book Outdoor Units I. Products 1 2 3 Outdoor units Indoor units Accessories 6 7 9 2 II. Outdoor units 1 2 3 4 5 6 Specifications Operation limit Electrical wiring diagram Sound level

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit Outdoor unit RSW-17AC ROW-17AC C O N T E N T S SPECIFICATIONS........................................ 1 REFRIGERANT SYSTEM DIAGRAM........................

More information

VWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ

VWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ PRODUCT SPECIFICATIONS VARIABLE REFRIGERANT FLOW SYSTEMS VRF VWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ Bulletin No. 210712 March 2018 Low-sound, three-speed Wall Mount with LED display offers three

More information

SVC Manual (Exploded View)

SVC Manual (Exploded View) SVC Manual (Exploded View) TYPE : WALL MOUNTED Applied Models : M09YJ M12YJ M09CJ M12CJ FAC P/no : 960-920-00 Product Specifications FAC Model Name System M09CJ M12CJ M09YJ M12YJ Outdoor Unit MR09C1J MR12C1J

More information

Version Modification Date Remark

Version Modification Date Remark Version Modification Date Remark Index 1 Nomenclature 2 Specifications 3 Capacity table 4 Dimensional drawing 5 Electrical wiring diagram 6 Sound pressure level 7 Temperature and air flow distribution

More information

RESIDENTIAL & LIGHT COMMERCIAL AIR CONDITIONERS 2015 / 2016 EVERY BUILDING MATTERS

RESIDENTIAL & LIGHT COMMERCIAL AIR CONDITIONERS 2015 / 2016 EVERY BUILDING MATTERS RESIDENTIAL & LIGHT COMMERCIAL AIR CONDITIONERS 2015 / 2016 EVERY BUILDING MATTERS A Better Life, A Better World As we move towards our Centenary in 2018, our new brand slogan encapsulates Panasonic s

More information

SERVICE MANUAL OUTDOOR UNIT. No. OB387

SERVICE MANUAL OUTDOOR UNIT. No. OB387 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Revision C: MUH-A25VB - E has been added. Please void OB87 REVISED EDITION-B. OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A. OB87 REVISED EDITION-C Wireless type

More information

VMDB Concealed Medium Static Ducted Indoor Models - 60HZ

VMDB Concealed Medium Static Ducted Indoor Models - 60HZ VARIABLE REFRIGERANT FLOW SYSTEMS VRF VMDB Concealed Medium Static Ducted Indoor Models - 60HZ PRODUCT ECIFICATIONS Bulletin No. 210711 March 2018 Slim, compact design for limited space requirements. Installs

More information

MSP Duct S Specifications

MSP Duct S Specifications MSP Duct S Specifications Model Name AM022FNMDEH AM028FNMDEH AM036HNMPKH AM045HNMPKH AM056HNMPKH Capacity *2) 2.2 2.8 3.6 4.5 5.6 *3) 2.5 3.2 4.0 5.0 6.3 Perfomance (Total) *5) kw 1.8 2.3 2.9 3.7 4.6 VRF

More information

Part Ⅰ : Technical Information

Part Ⅰ : Technical Information Service Manual Part Ⅰ : 1. Summary Outdoor Unit GWHD(18)NK3JO(DRED) GWHD(24)NK3JO(DRED) GWHD(28)NK3JO(DRED) 1 2. Specifications Model GWHD(18)NK3JO(DRED) Product Code CB228W05900 Rated Voltage V~ 220-240

More information

Tons BTU/h S.E.E.R* E.E.R** HSPF

Tons BTU/h S.E.E.R* E.E.R** HSPF SOUND REFRIGERANT ENVIRONMENTALLY PHD3 Product Specifications 13 SEER, R -410A PACKAGE HEAT PUMP, 2½ to 5 TONS 3 -Phase, 208/230-3 -60 and 460-3 -60 REFRIGERATION CIRCUIT R--410A refrigerant Copper tube/aluminum

More information

PRPHP14 PRODUCT SPECIFICATIONS 14 SEER HEAT PUMP PACKAGED UNIT REFRIGERANT SYSTEM CABINET CONSTRUCTION BLOWER CONTROLS INSTALLATION ACCESSORIES

PRPHP14 PRODUCT SPECIFICATIONS 14 SEER HEAT PUMP PACKAGED UNIT REFRIGERANT SYSTEM CABINET CONSTRUCTION BLOWER CONTROLS INSTALLATION ACCESSORIES PRODUCT SPECIFICATIONS 4 SEER HEAT PUMP PACKAGED UNIT FORM NO. -00 (03/207) REFRIGERANT SYSTEM Environmentally friendly R40A refrigerant Copper tubing with enhanced fin coils Internal service gauge ports

More information

Heating Nom. dba Cooling Nom. dba Night quiet mode Level 1 dba Item Tie-wraps Tie-wraps Tie-wraps Tie-wraps

Heating Nom. dba Cooling Nom. dba Night quiet mode Level 1 dba Item Tie-wraps Tie-wraps Tie-wraps Tie-wraps RZQG71L8Y1B RZQG100L8Y1B RZQG125L8Y1B RZQG140L7Y1B Sound pressure level Heating Nom. dba 50 52 53 53 Cooling Nom. dba 48 50 51 52 Night quiet mode Level 1 dba 43 45 45 45 Standard Accessories Item Tie-wraps

More information

Technical Service Manual. TVR LX Systems Medium Static Pressure Duct Units with DC Fan Motor V/50-60Hz/1ph

Technical Service Manual. TVR LX Systems Medium Static Pressure Duct Units with DC Fan Motor V/50-60Hz/1ph Technical Service Manual TVR LX Systems Medium Static Pressure Duct Units with DC Fan Motor 220-240V/50-60Hz/1ph August 20 Medium Static Pressure Duct Unit With DC Fan Motor 1. Features...2 2. Specifications...4

More information

technical data air conditioning systems MA-GZ7 Multi Model Application Split Sky Air

technical data air conditioning systems MA-GZ7 Multi Model Application Split Sky Air technical data MA-GZ7 Multi Model Application air conditioning systems Split Sky Air Split - Sky Air ISO14001 assures an effective environmental management system in order to help protect human health

More information

SINGLE. Technical Data Book. 4Way Cassette S for Nordic (R410A, 50Hz) Model : AC***JN4CEH/EU (ODU: AC***JXSC*H/EU)

SINGLE. Technical Data Book. 4Way Cassette S for Nordic (R410A, 50Hz) Model : AC***JN4CEH/EU (ODU: AC***JXSC*H/EU) SINGLE Technical Data Book 4Way Cassette S for Nordic (R4A, 5Hz) Model : AC***JN4CEH/EU (ODU: AC***JXSC*H/EU) History Version Modification Date Remark Ver.1. Released SINGLE for Nordic TDB 15.3.. Ver.1.1

More information

VMDA Concealed Medium Static Ducted Indoor Models - 60HZ

VMDA Concealed Medium Static Ducted Indoor Models - 60HZ VARIABLE REFRIGERANT FLOW SYSTEMS VRF VMDA Concealed Medium Static Ducted Indoor Models - 60HZ PRODUCT ECIFICATIONS Slim, compact design for limited space requirements. Installs out of sight between the

More information

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO technical sales guide - 60Hz Taurus R Ducted Split Units UPTO HIGH AMBIENT OPERATION 52 O C Page CONTENTS Nomenclature.. 2 Description. 3 Features.. 3 Product Data. 4 Condensing Unit Cooling Performance

More information

40KQV. Direct expansion split system Inverter Cassette. Nominal Cooling capacity: 4,85-12,40 kw Nominal Heating capacity: 5,10-13,00 kw

40KQV. Direct expansion split system Inverter Cassette. Nominal Cooling capacity: 4,85-12,40 kw Nominal Heating capacity: 5,10-13,00 kw LLOYD'S REGISTER QUALITY ASSURANCE Direct expansion split system Inverter Cassette I S O 9 00 1 40KQV Nominal Cooling capacity: 4,85-12,40 kw Nominal Heating capacity: 5,10-13,00 kw 40KQV cassette belongs

More information

BAC / BHC Product Specifications

BAC / BHC Product Specifications COMMERCIAL AIR HANDLERS (3 PHASE) 6 to 20 TON / Product Specifications REFRIGERATION CIRCUIT Standard factory-installed thermostatic expansion valves (TXVs) on units; units include TXVs and check valves

More information

GPC14H. 2- to 5-Ton Packaged Air Conditioner 14 SEER. Cooling Capacity: 24,000-57,500 BTU/H

GPC14H. 2- to 5-Ton Packaged Air Conditioner 14 SEER. Cooling Capacity: 24,000-57,500 BTU/H H Cooling Capacity: 24,000-57,500 BTU/H 2- to 5-Ton Packaged Air Conditioner 14 SEER Contents Nomenclature... 2 Product Specifications... 3 Expanded Cooling Data... 4 Airflow Data... 16 Heater Kit Specifications...

More information

SINGLE. Technical Data Book. Big Ceiling for Europe (R410A, 50Hz, H/P)

SINGLE. Technical Data Book. Big Ceiling for Europe (R410A, 50Hz, H/P) SINGLE Technical Data Book Big Ceiling for Europe (R4A, Hz, H/P) Version Modification Date Remark Ver.1. Release SINGLE Big Ceiling for Europe (R4A, Hz, H/P) TDB 1.4.3 Ver.1.1 Modification for drain pipe

More information

Multizone Multi Split systems

Multizone Multi Split systems 19 Multizone Multi Split systems Features and Benefits 2 Room 3 Room 4 Room 5 Room 6 Room RAM-36NP2A RAM-53NP2A RAM-53NP3A RAM-68NP3A RAM-70NP4A RAM-90NP5A RAM-130NP6A Nominal Cooling Capacity (kw) 3.6

More information

SERVICE MANUAL MU-GA20VB- MU-GA20VB- MU-GA25VB- MU-GA25VB- MU-GA35VB- E1 OUTDOOR UNIT. No. OB386. Wireless type Models HFC

SERVICE MANUAL MU-GA20VB- MU-GA20VB- MU-GA25VB- MU-GA25VB- MU-GA35VB- E1 OUTDOOR UNIT. No. OB386. Wireless type Models HFC SPLIT-TYPE, AIR CONDITIONERS Revision B: MU-A20VB- E2 and MU-A25VB - have been added. Please void OB86 REVISED EDITION-A. E2 OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A No. OB86 REVISED EDITION-B Wireless

More information

Q6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.

Q6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11. TECHNICAL SPECIFICATIONS Q6SP Series Rev A 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.0 EER Commercial Systems Meet or Exceed ASHRAE 90.1-2010 These 7½ and 10 ton units are designed

More information

PRK PREVIEW. System. OZONE FRIENDLY R-407C Series. Inverter Heat Pump Series Heat Recovery Series PLUS Series (Heat Pump)

PRK PREVIEW. System. OZONE FRIENDLY R-407C Series. Inverter Heat Pump Series Heat Recovery Series PLUS Series (Heat Pump) PRK 00-04 PREVIEW System OZONE FRIENDLY R-407C Series Inverter Heat Pump Series Heat Recovery Series PLUS Series (Heat Pump) 3DUW#4 2XWGRRU#8QLWV 111111111111111111111111111111111111111111111111111111111111111111111

More information

PH120. Rooftop Packaged. R410a Refrigerant PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C

PH120. Rooftop Packaged. R410a Refrigerant PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C PH120 R410a Refrigerant Rooftop Packaged INDOOR COIL ENTERING AIR TEMP 0 c DB WB 21 23 25 27 29 31 PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C 30 35 40 45 Cap Cap Cap Cap 17 115.3 70.7 11.5

More information

PCB COMMERCIAL SERIES

PCB COMMERCIAL SERIES PCB COMMERCIAL SERIES 50 Hz SELF-CONTAINED PACKAGE CONDITIONER 7½, 0, AND 5 TON [6.4 kw to 5.8 kw] COOLING CAPACITY: 90,000 TO 80,000 BTU/H The PCB Commercial 50 Hz self-contained packaged air conditioner

More information

S5BP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

S5BP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS TECHNICAL SPECIFICATIONS S5BP Series Split System Air Conditioner 71/2 Ton Energy Star rated at 11.7 EER and 11.8 IEER 10 Ton rated at 11.2 EER and 11.5 IEER R-410A Refrigerant The S5BP Series of air conditioners

More information

Product Data. FS3QX Slim Line Ducted Fan Coil With Plenum Sizes 018 thru 060 SLIM LINE DUCTED FAN COIL WITH PLENUM ON/OFF DISPLAY TEMP

Product Data. FS3QX Slim Line Ducted Fan Coil With Plenum Sizes 018 thru 060 SLIM LINE DUCTED FAN COIL WITH PLENUM ON/OFF DISPLAY TEMP FS3QX Slim Line Ducted Fan Coil With Plenum Sizes 018 thru 060 Product Data A114 SLIM LINE DUCTED FAN COIL WITH PLENUM Installation Ease S Factory installed 24 volt transformer and relay S High and low

More information

PRPDF14 PRODUCT SPECIFICATIONS 14 SEER DUAL FUEL PACKAGED UNIT REFRIGERANT SYSTEM HEAT EXCHANGER CABINET CONSTRUCTION ACCESSORIES WARRANTY BLOWER

PRPDF14 PRODUCT SPECIFICATIONS 14 SEER DUAL FUEL PACKAGED UNIT REFRIGERANT SYSTEM HEAT EXCHANGER CABINET CONSTRUCTION ACCESSORIES WARRANTY BLOWER PRODUCT SPECIFICATIONS 14 SEER DUAL FUEL PACKAGED UNIT FORM NO. -100 (01/2017) REFRIGERANT SYSTEM Environmentally friendly R410A refrigerant Copper tubing with enhanced fin coils Internal service gauge

More information

technical data air conditioning systems 600x600 4-Way Blow Ceiling Mounted Cassette FXZQ-M9V1B

technical data air conditioning systems 600x600 4-Way Blow Ceiling Mounted Cassette FXZQ-M9V1B technical data 600x600 4-Way Blow Ceiling Mounted Cassette FXZQ-M9V1B air conditioning systems technical data 600x600 4-Way Blow Ceiling Mounted Cassette FXZQ-M9V1B air conditioning systems Indoor Units

More information

VHIA High-Static Ducted Indoor Units - 60HZ

VHIA High-Static Ducted Indoor Units - 60HZ PRODUCT SPECIFICATIONS Compact design for limited space requirements. Installs out of sight between the drop ceiling and ceiling slab with ducted distribution to the indoor space. All models have three-stage

More information

technical data air conditioning systems RQ-B7 Pair/Twin/Triple/Double Twin Application Split Sky Air

technical data air conditioning systems RQ-B7 Pair/Twin/Triple/Double Twin Application Split Sky Air technical data RQ-B7 Pair/Twin/Triple/Double Twin Application air conditioning systems Split Sky Air Split - Sky Air ISO14001 assures an effective environmental management system in order to help protect

More information

Hi-Wall Inverter Split System. Cooling and heating, exactly where and when you need it

Hi-Wall Inverter Split System. Cooling and heating, exactly where and when you need it Hi-Wall Inverter Split System Cooling and heating, exactly where and when you need it Save on Running Costs 2.6kW & 3.2kW 4.2kW & 5.0kW 7.0kW & 8.0kW High Efficiency Along with running cost savings due

More information

Fan Coil Units. Technical Data

Fan Coil Units. Technical Data Fan Coil Units Technical Data F a n c o i l u n i t s E E D E N 1 1-4 0 0 Fan Coil Units Technical Data F a n c o i l u n i t s E E D E N 1 1-4 0 0 Table of Contents Table of Contents 3 Round Flow Cassette...

More information

Product Data. CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) FMA4P1800AL 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

Product Data. CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) FMA4P1800AL 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15 Product Data FMA4X, FMA4P APARTMENT FAN COIL UNIT 1 1/2 TONS THROUGH 3 TONS APARTMENT FAN COILS ALL MODELS 1 1/2, 2, 2 1/2, and 3 Tons Upflow application only Accessory field installed electric heat kits

More information

Air Conditioners. Technical Data UATYQ-CY1

Air Conditioners. Technical Data UATYQ-CY1 Air Conditioners Technical Data R o o f t o p s E E D E N 2-2 0 UATYQ-CY Air Conditioners Technical Data R o o f t o p s E E D E N 2-2 0 UATYQ-CY Single Unit Rooftop UATYQ-CY TABLE OF CONTENTS UATYQ-CY

More information