R22 TECHNICAL MANUAL. Split Unit Air Conditioner Ceiling Cassette C & E Series FF-C, FHC-E, FFY-C, FHYC-E. Cooling only & Heatpump [50Hz]
|
|
- Felicity Thornton
- 5 years ago
- Views:
Transcription
1 R22 TECHNICAL MANUAL Split Unit Air Conditioner Ceiling Cassette C & E Series FF-C, FHC-E, FFY-C, FHYC-E Cooling only & Heatpump [50Hz]
2
3 Table of Contents Table of Contents Nomenclature...1 Indoor...1 Outdoor...1 Product Line-Up...2 Application Information...4 Operating Range...4 Refrigerant Circuit Diagrams (C Series)...5 Refrigerant Circuit Diagrams (E Series)...7 Installation Guideline Sound Data...16 Sound Pressure Level...16 NC Curve...17 Engineering & Physical Data...21 Performance Data...26 Calculation Steps...26 Performance Tables...28 Outline & Dimension...49 Wiring Diagram...52 Service & Maintenance...63 Troubleshooting...65
4 Nomenclature Nomenclature Indoor FF(Y) 10 C X V1 Power Supply V1: 1 phase 50 Hz V Production X: OYLM Product Series C: C Series E: E Series Capacity 10: Btu/hr Model FF: Ceiling Cassette 2"x2" (Cooling Only) FHC: Ceiling Cassette 3"x3" (Cooling Only) FFY: Ceiling Cassette 2"x2" (Heatpump) FHYC: Ceiling Cassette 3"x3" (Heatpump) Outdoor R(Y) 10 C X V1 Power Supply V1: 1 phase 50 Hz V Y1: 3 phase 50 Hz V Production X: OYLM Product Series C: C Series D: D Series Capacity 10: Btu/hr Model R: Single Split Condensing Unit (Cooling Only) RY: Single Split Condensing Unit (Heatpump) 1
5 Nomenclature Product Line-Up Indoor Unit FF(Y)/FH(Y)C Classifi cation Panel (Handset) PCB Fin Refrigerant Control Nomenclature BC20CXW (BRC52A62) BYC20CXW (BRC52A61) BC50EXW (BRC52A62) BYC50EXW (BRC52A61) L208A EC L208A AP L2CKE EC L2CKE AP Hydrophilic (Blue) Cap Tube w/o Cap Tube FF10CXV1 X X X X FF15CXV1 X X X X COOLING HEATPUMP FF20CXV1 X X X X FHC20EXV1 X X X X FHC25EXV1 X X X X FHC28EXV1 X X X X FHC40EXV1 X X X X FHC50EXV1 X X X X FFY10CXV1 X X X X FFY15CXV1 X X X X FFY20CXV1 X X X X FHYC20EXV1 X X X X FHYC25EXV1 X X X X FHYC28EXV1 X X X X FHYC40EXV1 X X X X FHYC50EXV1 X X X X 2
6 Nomenclature Outdoor Unit R(Y) Classifi cation Nomenclature Cap Tube Refrigerant Control TXV w/o Cap Tube Hydrophilic (Blue) Hydrophilic (Gold) Bare Aluminium Fin Safety Devices Compressor Others COOLING HEATPUMP Contactor HP LP Rotary Scroll Drain Elbow R10CXV1 X X X R10CGXV1 X X X R15CXV1 X X X R15CGXV1 X X X R20CXV1 X X X R20CGXV1 X X X R25CXV1 X X X R25CGXV1 X X X R28CXV1 X X X R28CGXV1 X X X R35DXV1 X X X X X X R35DGXV1 X X X X X X R40DXV1 X X X X X X R40DGXV1 X X X X X X R40DXY1 X X X X X X R40DGXY1 X X X X X X R50DXY1 X X X X X X R50DGXY1 X X X X X X RY10CXV1 X X X X RY10CGXV1 X X X X RY15CXV1 X X X X RY15CGXV1 X X X X RY18CXV1 X X X X RY18CGXV1 X X X X RY20CXV1 X X X X RY20CGXV1 X X X X RY25CXV1 X X X X RY25CGXV1 X X X X RY28CXV1 X X X X RY28CGXV1 X X X X RY35DXV1 X X X X X X X RY35DGXV1 X X X X X X X RY40DXV1 X X X X X X RY40DGXV1 X X X X X X RY40DXY1 X X X X X X RY40DGXY1 X X X X X X RY50DXY1 X X X X X X RY50DGXY1 X X X X X X 3
7 Application Information Application Information Operating Range Ensure the operating temperature is in allowance range. Cooling Outdoor DB ( C) The use of your air conditioner outside the range of working temperature and humidity can result in serious failure Indoor WB ( C) Heating Outdoor WB ( C) The use of your air conditioner outside the range of working temperature and humidity can result in serious failure Indoor DB ( C) 4
8 Application Information Refrigerant Circuit Diagrams (C Series) Model: FF10CXV1 R10CXV1 / FF15CXV1 R15CXV1 / FF20CXV1 R20CXV1 COOLING OPERATION 3 WAY VALVE RETURN AIR SENSOR HEAT EXCHANGER (INDOOR UNIT) PIPE TEMPERATURE SENSOR DISCHARGE ACCUMULATOR COMPRESSOR HEAT EXCHANGER (OUTDOOR UNIT) COOLING CAP TUBE 2 WAY VALVE STRAINER INDOOR UNIT OUTDOOR UNIT Model: FFY10CXV1 RY10CXV1 / FFY20CXV1 RY18CXV1 PIPING GAS 3 WAY VALVE COOLING OPERATION HEATING OPERATION RETURN AIR SENSOR 4 WAY VALVE DISCHARGE ACCUMULATOR HEAT EXCHANGER (INDOOR UNIT) PIPE TEMPERATURE SENSOR COMPRESSOR PIPE TEMPERATURE SENSOR HEAT EXCHANGER (OUTDOOR UNIT) PIPING LIQUID COOLING & HEATING CAP TUBE 2 WAY VALVE STRAINER STRAINER INDOOR UNIT OUTDOOR UNIT 5
9 Application Information Model: FFY15CXV1 RY15CXV1 / FFY20CXV1 RY20CXV1 PIPING GAS 3 WAY VALVE COOLING OPERATION HEATING OPERATION RETURN AIR SENSOR 4 WAY VALVE DISCHARGE ACCUMULATOR HEAT EXCHANGER (INDOOR UNIT) PIPE TEMPERATURE SENSOR COMPRESSOR PIPE TEMPERATURE SENSOR HEAT EXCHANGER (OUTDOOR UNIT) HEATING CAP TUBE PIPING LIQUID COOLING & HEATING CAP TUBE INDOOR UNIT 2 WAY VALVE STRAINER CHECK VALVE STRAINER OUTDOOR UNIT 6
10 Application Information Refrigerant Circuit Diagrams (E Series) Model: FHC20EXV1 R20CXV1 COOLING OPERATION 3 WAY VALVE RETURN AIR SENSOR HEAT EXCHANGER (INDOOR UNIT) PIPE TEMPERATURE SENSOR DISCHARGE ACCUMULATOR COMPRESSOR HEAT EXCHANGER (OUTDOOR UNIT) COOLING CAP TUBE 2 WAY VALVE STRAINER INDOOR UNIT OUTDOOR UNIT Model: FHC25EXV1 R25CXV1 COOLING OPERATION 3 WAY VALVE RETURN AIR SENSOR HEAT EXCHANGER (INDOOR UNIT) DISCHARGE PIPE TEMPERATURE SENSOR COMPRESSOR ACCUMULATOR HEAT EXCHANGER (OUTDOOR UNIT) COOLING CAP TUBE 3 WAY VALVE STRAINER INDOOR UNIT OUTDOOR UNIT 7
11 Application Information Model: FHC28EXV1 R28CXV1 COOLING OPERATION 3 WAY VALVE RETURN AIR SENSOR DISCHARGE HEAT EXCHANGER (INDOOR UNIT) PIPE TEMPERATURE SENSOR COMPRESSOR ACCUMULATOR HEAT EXCHANGER (OUTDOOR UNIT) COOLING CAP TUBE STRAINER 3 WAY VALVE INDOOR UNIT OUTDOOR UNIT Model: FHC40EXV1 R35DXV1 / FHC40EXV1 R40DXV1 / FHC40EXV1 R40DXY1 / FHC50EXV1 R50DXY1 COOLING OPERATION 3 WAY VALVE RETURN AIR SENSOR LOW PRESSURE SWITCH HIGH PRESSURE SWITCH DISCHARGE HEAT EXCHANGER (INDOOR UNIT) PIPE TEMPERATURE SENSOR HEAT EXCHANGER (OUTDOOR UNIT) ACCUMULATOR COMPRESSOR 3 WAY VALVE CAP TUBE STRAINER INDOOR UNIT OUTDOOR UNIT 8
12 Application Information Model: FHYC20EXV1 RY20CXV1 PIPING GAS 3 WAY VALVE COOLING OPERATION HEATING OPERATION RETURN AIR SENSOR 4 WAY VALVE DISCHARGE ACCUMULATOR HEAT EXCHANGER (INDOOR UNIT) PIPE TEMPERATURE SENSOR COMPRESSOR PIPE TEMPERATURE SENSOR HEAT EXCHANGER (OUTDOOR UNIT) HEATING CAP TUBE PIPING LIQUID COOLING & HEATING CAP TUBE INDOOR UNIT 2 WAY VALVE STRAINER CHECK VALVE STRAINER OUTDOOR UNIT Model: FHYC25EXV1 RY25CXV1 / FHYC28EXV1 RY28CXV1 PIPING GAS 3 WAY VALVE COOLING OPERATION HEATING OPERATION RETURN AIR SENSOR 4 WAY VALVE DISCHARGE ACCUMULATOR HEAT EXCHANGER (INDOOR UNIT) PIPE TEMPERATURE SENSOR COMPRESSOR PIPE TEMPERATURE SENSOR HEAT EXCHANGER (OUTDOOR UNIT) PIPING LIQUID COOLING & HEATING CAP TUBE 3 WAY VALVE STRAINER STRAINER INDOOR UNIT OUTDOOR UNIT 9
13 Application Information Model: FHYC40EXV1 RY35DXV1 COOLING OPERATION PIPING GAS 3 WAY VALVE HEATING OPERATION RETURN AIR SENSOR 4 WAY VALVE HIGH PRESSURE SWITCH DISCHARGE HEAT EXCHANGER (INDOOR UNIT) PIPE TEMPERATURE SENSOR PIPE TEMPERATURE SENSOR HEAT EXCHANGER (OUTDOOR UNIT) COMPRESSOR ACCUMULATOR BIFLOW TXV PIPING LIQUID 3 WAY VALVE STRAINER COOLING & HEATING CAP TUBE STRAINER INDOOR UNIT OUTDOOR UNIT Model: FHYC40EXV1 RY40DXV1 / FHYC40EXV1 RY40DXY1 / FHYC50EXV1 RY50DXY1 COOLING OPERATION PIPING GAS 3 WAY VALVE HEATING OPERATION RETURN AIR SENSOR 4 WAY VALVE HIGH PRESSURE SWITCH DISCHARGE HEAT EXCHANGER (INDOOR UNIT) PIPE TEMPERATURE SENSOR PIPE TEMPERATURE SENSOR HEAT EXCHANGER (OUTDOOR UNIT) COMPRESSOR ACCUMULATOR ACCESS VALVE HEATING CAP. TUBE PIPING LIQUID COOLING CAP. TUBE 3 WAY VALVE STRAINER CHECK VALVE STRAINER INDOOR UNIT OUTDOOR UNIT 10
14 Application Information Installation Guideline Safety Precautions Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance. All fi eld wiring must be installed in accordance with the national wiring regulation. Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram. The unit must be GROUNDED to prevent possible hazard due to insulation failure. All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors. Confi rm that the unit has been switched OFF before installing or servicing the unit. Disconnect from the main power supply before servicing the air conditioner unit. DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in fi re hazards. Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static may be heard even when more than 1m away}. Please take note of the following important points when installing. Do not install the unit where leakage of flammable gas may occur. If gas leaks and accumulates around the unit, it may cause fi re ignition. Ensure that drainage piping is connected properly. If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture. Do not overcharge the unit. This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor. Ensure that the unit s panel is closed after service or installation. Unsecured panels will cause the unit to operate noisily. Sharp edges and coil surfaces are potential locations which may cause injury hazards. Avoid from being in contact with these places. Before turning off the power supply, set the remote controller s ON/OFF switch to the OFF position to prevent the nuisance tripping of the unit. If this is not done, the unit s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user. Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt or deform as a result of the excessive heat. Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively. IMPORTANT : DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM. Do not use joined and twisted wires for incoming power supply. NOTICE Disposal requirements Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with unsorted household waste. Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of other parts must be done by a qualified installer in accordance with relevant local and national legislation. Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more information. Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation. 11
15 Application Information 1) Indoor Installation Clearance Clearance must be provided for the indoor unit from wall and obstacles as shown in fi gure below. Max. 3.0 m Min 0.5 m Min 0.5 m Min 0.5 m Beam Max. 0.3 m Obstacles Floor The installation place (handling ceiling surface) must be level and the height in the ceiling is 350mm or more. 2) Outdoor Installation Clearance Outdoor unit must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air fl ow. Select the coolest possible place where intake air should not hotter than the outside temperature (Max. 45 C). ALL MODELS A B C D Minimum Distance 300 mm 1000 mm 300 mm 500 mm If the condensing unit is operated in an atmosphere containing oils (including machine oils), salt (coastal area), sulphide gas (near hot spring, oil refinery plant), such substances may lead to failure the unit. 12
16 Application Information 3) Cable Size Cooling only Model Power supply cable size Number of wire Interconnection cable size Number of wire Unit mm² mm² FF10/15CXV1 FF20CXV1 FHC20EXV1 R10/15CXV1 R20CXV1 R20CXV1 Recommended fuse A Model Power supply cable size Number of wire Interconnection cable size Number of wire Unit mm mm FHC25EXV1 FHC28EXV1 FHC40EXV1 R25CXV1 R28CXV1 R35DXV1 Recommended fuse A Model Power supply cable size Number of wire Interconnection cable size Number of wire Unit 4.0 mm mm FHC40EXV1 FHC40EXV1 FHC50EXV1 R40DXV1 R40DXY1 R50DXY1 Recommended fuse A Heatpump Model Power supply cable size Number of wire Interconnection cable size Number of wire Unit 1.5 mm mm 2 3 FFY10/15CXV1 FFY20CXV1 FHYC20EXV1 RY10/15CXV1 RY18/20CXV1 RY20CXV1 Recommended fuse A Model Power supply cable size Number of wire Interconnection cable size Number of wire Unit 2.5 mm mm FHYC25EXV1 FHYC28EXV1 FHYC40EXV1 RY25CXV1 RY28CXV1 RY35DXV1 Recommended fuse A Model Power supply cable size Number of wire Interconnection cable size Number of wire Unit 4.0 mm mm 2 3 & & 4 FHYC40EXV1 FHYC40EXV1 FHYC50EXV1 RY40DXV1 RY40DXY1 RY50DXY & & 4 Recommended fuse A
17 Application Information 4) Refrigerant Piping Maximum Piping Length and Maximum Number of Bends When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases, system piping resistance to the refrigerant fl ow increases, thus lowering the cooling capacity, and as the result the compressor may become defective. Always choose the shortest path and follow the recommendation as tabulated below: Model Indoor FF(Y)10CXV1 FF(Y)15CXV1 FF(Y)20CXV1 Outdoor R(Y)10CXV1 R(Y)15CXV1 R(Y)18/20CXV1 Max. Length, m Max. Elevation, m Max. No. of Bends Model Indoor FH(Y)C20EXV1 FH(Y)C25EXV1 FH(Y)C28EXV1 Outdoor R(Y)20CXV1 R(Y)25CXV1 R(Y)28CXV1 Max. Length, m Max. Elevation, m Max. No. of Bends Model Indoor FH(Y)C40EXV1 FH(Y)C50EXV1 Outdoor R(Y)35/40DXV1 R(Y)40DXY1 R(Y)50DXY1 Max. Length, m Max. Elevation, m Max. No. of Bends Piping sizes (flare connection type) are as follows: Model R(Y)10CXV1 R(Y)15CXV1 R(Y)18/20CXV1 R(Y)20CXV1 Liquid, mm / in 6.35 / 1/ / 1/ / 1/ / 1/4 Suction, mm / in 9.52 / 3/ / 1/ / 5/ / 5/8 Model R(Y)25CXV1 R(Y)28CXV1 R(Y)35DXV1 Liquid, mm / in 9.52 / 3/ / 3/ / 3/8 Suction, mm / in / 5/ / 5/ / 3/4 Model R(Y)40DXV1 R(Y)40DXY1 R(Y)50DXY1 Liquid, mm / in 9.52 / 3/8 Suction, mm / in / 3/4 14
18 Application Information 5) Additional Charge The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.6m, additional refrigerant charge after vacuuming is not necessary. When the piping length is more than 7.6m, please use the table below (unit in gram). Cooling Only Indoor FF10CXV1 FF15CXV1 FF20CXV1 Outdoor R10CXV1 R15CXV1 R20CXV1 Add. Charge, g/m Indoor FHC20EXV1 FHC25EXV1 FHC28EXV1 Outdoor R20CXV1 R25CXV1 R28CXV1 Add. Charge, g/m Indoor FHC40EXV1 FHC50EXV1 Outdoor R35DXV1 R40DXV1 R40DXY1 R50DXY1 Add. Charge, g/m Heatpump Indoor FFY10CXV1 FFY15CXV1 FFY20CXV1 Outdoor RY10CXV1 RY15CXV1 RY18/20CXV1 Add. Charge, g/m Indoor FHYC20EXV1 FHYC25EXV1 FHYC28EXV1 Outdoor RY20CXV1 RY25CXV1 RY28CXV1 Add. Charge, g/m Indoor FHYC40EXV1 FHYC50EXV1 Outdoor RY35DXV1 RY40DXV1 RY40DXY1 RY50DXY1 Add. Charge, g/m Example: FHC25EXV1 & R25CXV1 with 13m piping length, additional piping length is 5.5m. Thus, Additional Charge = 5.5m x 38g/m = 209g 15
19 Sound Data Sound Data Sound Pressure Level Model FF(Y)10CXV1 FF(Y)15CXV1 FF(Y)20CXV1 FH(Y)C20EXV1 FH(Y)C25EXV1 FH(Y)C28EXV1 FH(Y)C40EXV1 FH(Y)C50EXV1 Speed 1/1 Octave Sound Pressure (db, ref 20μPa) Overall Noise 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dba) Criteria High Med Low High Med Low High Med Low High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet Model Measuring Location FF(Y)10/15/20CXV1 FH(Y)C20/25/28EXV1 Standard : JIS C 9612 Microphone 1.4m FH(Y)C40EXV1 FH(Y)C50EXV1 1.5m Standard: JIS B 8616 Microphone 16
20 Sound Data NC Curve FF(Y)10CXV Sound pressure level (db, ref 20μPa) H M L NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC Octave-band frequency (Hz) FF(Y)15CXV Sound pressure level (db, ref 20μPa) H M L NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC Octave-band frequency (Hz) 17
21 Sound Data FF(Y)20CXV1 70 Sound pressure level (db, ref 20μPa) H M L NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC Octave-band frequency (Hz) FH(Y)C20EXV1 70 Sound pressure level (db, ref 20μPa) H M L Q NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC Octave-band frequency (Hz) 18
22 Sound Data FH(Y)C25EXV1 70 Sound pressure level (db, ref 20μPa) H M L Q NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC Octave-band frequency (Hz) FH(Y)C28EXV Sound pressure level (db, ref 20μPa) H M L Q NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC Octave-band frequency (Hz) 19
23 Sound Data FH(Y)C40EXV Sound pressure level (db, ref 20μPa) H M L Q NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC Octave-band frequency (Hz) FH(Y)C50EXV Sound pressure level (db, ref 20μPa) H M L Q NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC Octave-band frequency (Hz) 20
24 Engineering & Physical Data Engineering & Physical Data Engineering Data - R22 MODEL MODEL INDOOR UNIT FF10CXV1 FF15CXV1 FF20CXV1 OUTDOOR UNIT R10CXV1 R15CXV1 R20CXV1 NOMINAL COOLING CAPACITY Btu/h W NOMINAL TOTAL INPUT POWER (COOLING) W NOMINAL RUNNING CURRENT (COOLING) A EER W/W REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAPILLARY TUBE REFRIGERANT CHARGE kg MODEL INDOOR UNIT FFY10CXV1 FFY15CXV1 FFY20CXV1 OUTDOOR UNIT RY10CXV1 RY15CXV1 RY18CXV1 RY20CXV1 NOMINAL COOLING CAPACITY Btu/h W NOMINAL HEATING CAPACITY Btu/h W NOMINAL TOTAL INPUT POWER (COOLING) W NOMINAL TOTAL INPUT POWER (HEATING) W NOMINAL RUNNING CURRENT (COOLING) A NOMINAL RUNNING CURRENT (HEATING) A EER W/W COP W/W REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAPILLARY TUBE REFRIGERANT CHARGE kg POWER SOURCE V/Ph/Hz / 1/ 50 REFRIGERANT TYPE R22 CONTROL AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN) OPERATION WIRELESS MICROCOMPUTER REMOTE CONTROL HIGH l/s / CFM 194 / / / 450 AIR FLOW MEDIUM l/s / CFM 170 / / / 410 LOW l/s / CFM 156 / / / 340 SOUND PRESSURE LEVEL (H/M/L) dba 41 / 38 / / 38 / / 41 / 37 UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 250 X 570 X 570 PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 317 X 630 X 630 UNIT WEIGHT (UNIT + PANEL) kg CONDENSATE DRAIN SIZE mm FAN TYPE TURBO DRIVE DIRECT TYPE INDUCTION INDEX OF PROTECTION (IP) IP20 INSULATION GRADE CLASS B FAN MOTOR RATED INPUT POWER W RATED RUNNING CURRENT A MOTOR OUTPUT W POLES 6 TUBE MATERIAL COPPER DIAMETER mm 7 COIL MATERIAL ALUMINIUM FIN FACE AREA m ROW 1 2 AIR QUALITY FILTER TYPE WASHABLE SARANET FILTER QUANTITY pc 1 CASING COLOUR WITHOUT PAINT AIR FLOW l/s / CFM 453 / / 1300 SOUND PRESSURE LEVEL dba UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 540 X 700 X X 855 X 328 PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 620 X 810 X X 990 X 415 UNIT WEIGHT (R / RY) kg 28 / TYPE FLARE VALVE PIPE LIQUID mm 6.35 CONNECTION SIZE GAS mm FAN TYPE PROPELLER DRIVE DIRECT TYPE INDUCTION INDEX OF PROTECTION (IP) IP23 INSULATION GRADE CLASS B CLASS F FAN MOTOR RATED INPUT POWER W RATED RUNNING CURRENT A MOTOR OUTPUT W POLES 6 TYPE ROTARY OIL TYPE ATMOS NM56M or SUNISO 4GDID OIL AMOUNT cm R RATED INPUT POWER W COMPRESSOR RY RATED INPUT POWER (COOLING) W RATED INPUT POWER (HEATING) W R RATED INPUT CURRENT A RY RATED INPUT CURRENT (COOLING) A RATED INPUT CURRENT (HEATING) A LOCKED ROTOR AMP. A TUBE MATERIAL COPPER DIAMETER (R / RY) mm 7 7 / COIL MATERIAL ALUMINIUM FIN FACE AREA m ROW 1 2 CASING COLOUR LIGHT GREY INDOOR UNIT OUTDOOR UNIT ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO (DUCTED UNIT). COOLING HEATING INDOOR: 27 C DB/ WB INDOOR: 20 C DB OUTDOOR: 35 C DB/ 24 C WB OUTDOOR: 7 C DB/ 6 C WB 21
25 Engineering & Physical Data Engineering Data - R22 MODEL MODEL INDOOR UNIT FHC20EXV1 FHC25EXV1 FHC28EXV1 FHC40EXV1 OUTDOOR UNIT R20CXV1 R25CXV1 R28CXV1 R35CXV1 NOMINAL COOLING CAPACITY Btu/h W NOMINAL TOTAL INPUT POWER (COOLING) W NOMINAL RUNNING CURRENT (COOLING) A EER W/W REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE INDOOR CAP. TUBE REFRIGERANT CHARGE kg MODEL INDOOR UNIT FHYC20EXV1 FHYC25EXV1 FHYC28EXV1 FHYC40EXV1 OUTDOOR UNIT RY20CXV1 RY25CXV1 RY28CXV1 RY35CXV1 NOMINAL COOLING CAPACITY Btu/h W NOMINAL HEATING CAPACITY Btu/h W NOMINAL TOTAL INPUT POWER (COOLING) W NOMINAL TOTAL INPUT POWER (HEATING) W NOMINAL RUNNING CURRENT (COOLING) A NOMINAL RUNNING CURRENT (HEATING) A EER W/W COP W/W REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE OUTDOOR CAP. TUBE + TXV REFRIGERANT CHARGE kg POWER SOURCE V/Ph/Hz / 1/ 50 REFRIGERANT TYPE R22 CONTROL AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN) OPERATION WIRELESS MICROCOMPUTER REMOTE CONTROL HIGH l/s / CFM 280 / / / / 1030 AIR FLOW MEDIUM l/s / CFM 250 / / / / 860 LOW l/s / CFM 200 / / / / 740 SUPER LOW l/s / CFM 190 / / / / 620 SOUND PRESSURE LEVEL (H/M/L/SL) dba 34 / 32 / 30 / / 34 / 33 / / 38 / 35 / / 44 / 40 / 36 UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 265 X 820 X X 820 X 820 PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 300 X 916 X X 916 X 916 UNIT WEIGHT (UNIT + PANEL) kg CONDENSATE DRAIN SIZE mm FAN TYPE TURBO DRIVE DIRECT TYPE INDUCTION INDEX OF PROTECTION (IP) IP20 INSULATION GRADE CLASS B FAN MOTOR RATED INPUT POWER W RATED RUNNING CURRENT A MOTOR OUTPUT W POLES 6 TUBE MATERIAL COPPER DIAMETER mm 7 COIL MATERIAL ALUMINIUM FIN FACE AREA m ROW 2 3 AIR QUALITY FILTER TYPE WASHABLE SARANET FILTER QUANTITY pc 1 CASING COLOUR WITHOUT PAINT AIR FLOW l/s / CFM 614 / / / / 3400 SOUND PRESSURE LEVEL dba UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 651 X 855 X X 855 X X 1030 X 400 PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 710 X 990 X X 990 X X 1180 X 514 UNIT WEIGHT kg TYPE FLARE VALVE PIPE LIQUID mm CONNECTION SIZE GAS mm FAN TYPE PROPELLER DRIVE DIRECT TYPE INDUCTION INDEX OF PROTECTION (IP) IP23 IP54 INSULATION GRADE CLASS F CLASS B RATED INPUT POWER (R) W FAN MOTOR RATED INPUT POWER (RY) W RATED RUNNING CURRENT (R) A RATED RUNNING CURRENT (RY) A MOTOR OUTPUT W POLES 6 8 TYPE ROTARY SCROLL OIL TYPE ATMOS NM56M or SUNISO 4GDID MOBIL EAL OIL AMOUNT cm R RATED INPUT POWER W COMPRESSOR RATED INPUT POWER (COOLING) W RY RATED INPUT POWER (HEATING) W R RATED INPUT CURRENT A RY RATED INPUT CURRENT (COOLING) A RATED INPUT CURRENT (HEATING) A LOCKED ROTOR AMP. A TUBE MATERIAL COPPER DIAMETER (R / RY) mm COIL MATERIAL ALUMINIUM FIN FACE AREA m ROW 2 CASING COLOUR LIGHT GREY INDOOR UNIT OUTDOOR UNIT ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO (DUCTED UNIT). COOLING HEATING INDOOR: 27 C DB/ WB INDOOR: 20 C DB OUTDOOR: 35 C DB/ 24 C WB OUTDOOR: 7 C DB/ 6 C WB 22
26 Engineering & Physical Data Engineering Data - R22 MODEL MODEL INDOOR UNIT FHC40EXV1 FHC50EXV1 OUTDOOR UNIT R40DXV1 R40DXY1 R50DXY1 NOMINAL COOLING CAPACITY Btu/h W NOMINAL TOTAL INPUT POWER (COOLING) W NOMINAL RUNNING CURRENT (COOLING) A EER W/W REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR CAP. TUBE REFRIGERANT CHARGE kg MODEL INDOOR UNIT FHYC40EXV1 FHYC50EXV1 OUTDOOR UNIT RY40DXV1 RY40DXY1 RY50DXY1 NOMINAL COOLING CAPACITY Btu/h W NOMINAL HEATING CAPACITY Btu/h W NOMINAL TOTAL INPUT POWER (COOLING) W NOMINAL TOTAL INPUT POWER (HEATING) W NOMINAL RUNNING CURRENT (COOLING) A NOMINAL RUNNING CURRENT (HEATING) A EER W/W COP W/W REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE REFRIGERANT CHARGE kg POWER SOURCE V/Ph/Hz / 1/ / 3 / 50 REFRIGERANT TYPE R22 CONTROL AIR DISCHARGE 4 WAY AUTO LOUVER (UP & DOWN) OPERATION WIRELESS MICROCOM. REMOTE CONTROL HIGH l/s / CFM 490 / / 1200 AIR FLOW MEDIUM l/s / CFM 410 / / 1030 LOW l/s / CFM 350 / / 930 SUPER LOW l/s / CFM 295 / / 780 SOUND PRESSURE LEVEL (H/M/L/SL) dba 47 / 44 / 40 / / 45 / 43 / 39 UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 300 X 820 X 820 PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 335 X 916 X 916 UNIT WEIGHT (UNIT + PANEL) kg CONDENSATE DRAIN SIZE mm FAN TYPE TURBO DRIVE DIRECT TYPE INDUCTION INDEX OF PROTECTION (IP) IP20 INSULATION GRADE CLASS B FAN MOTOR RATED INPUT POWER W RATED RUNNING CURRENT A MOTOR OUTPUT W POLES 6 TUBE MATERIAL COPPER DIAMETER mm 7 COIL MATERIAL ALUMINIUM FIN FACE AREA m ROW 3 AIR QUALITY FILTER TYPE WASHABLE SARANET FILTER QUANTITY pc 1 CASING COLOUR WITHOUT PAINT AIR FLOW l/s / CFM 1605 / 3400 SOUND PRESSURE LEVEL dba 58 UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 852 X 1030 X 400 PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 1010 X 1180 X 514 UNIT WEIGHT kg TYPE FLARE VALVE PIPE LIQUID mm 9.52 CONNECTION SIZE GAS mm FAN TYPE PROPELLER DRIVE DIRECT TYPE INDUCTION INDEX OF PROTECTION (IP) IP54 INSULATION GRADE CLASS B RATED INPUT POWER (R) W 257 FAN MOTOR RATED INPUT POWER (RY) W 276 RATED RUNNING CURRENT (R) A 1.10 RATED RUNNING CURRENT (RY) A 1.34 MOTOR OUTPUT W 145 POLES 8 TYPE SCROLL OIL TYPE MOBIL EAL MINERAL OIL OIL AMOUNT cm R RATED INPUT POWER W COMPRESSOR RATED INPUT POWER (COOLING) W RY RATED INPUT POWER (HEATING) W R RATED INPUT CURRENT A RY RATED INPUT CURRENT (COOLING) A RATED INPUT CURRENT (HEATING) A LOCKED ROTOR AMP. A TUBE MATERIAL COPPER DIAMETER (R / RY) mm 9.52 / 7 7 COIL MATERIAL ALUMINIUM FIN FACE AREA m ROW 2 CASING COLOUR LIGHT GREY INDOOR UNIT OUTDOOR UNIT ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO (DUCTED UNIT). COOLING HEATING INDOOR: 27 C DB/ WB INDOOR: 20 C DB OUTDOOR: 35 C DB/ 24 C WB OUTDOOR: 7 C DB/ 6 C WB 23
27 Engineering & Physical Data Safety Device R22 MODEL SAFETY DEVICE INDOOR FF(Y)10/15EXV1 FF(Y)20CXV1 OUTDOOR R(Y)10/15CXV1 RY18CXV1 R(Y)20CXV1 HIGH PRESSURE SWITCH TYPE N/A OPEN kpa / psi N/A CLOSE kpa / psi N/A TYPE N/A LOW PRESSURE SWITCH OPEN kpa / psi N/A CLOSE kpa / psi N/A PHASE SEQUENCER N/A DISC. THERMOSTAT SETTING C / F N/A MODEL SAFETY DEVICE INDOOR OUTDOOR HIGH PRESSURE SWITCH FH(Y)C20/25/28EXV1 R(Y)20/25/28CXV1 TYPE N/A OPEN kpa / psi N/A CLOSE kpa / psi N/A TYPE N/A LOW PRESSURE SWITCH OPEN kpa / psi N/A CLOSE kpa / psi N/A PHASE SEQUENCER N/A DISC. THERMOSTAT SETTING C / F N/A MODEL SAFETY DEVICE INDOOR FHC40EXV1 OUTDOOR R35DXV1 R40DXV1 R40DXY1 HIGH PRESSURE SWITCH TYPE NC OPEN kpa / psi 2937 / 426 CLOSE kpa / psi 2413 / 350 TYPE NC LOW PRESSURE SWITCH OPEN kpa / psi 124 / 18 CLOSE kpa / psi 192 / 28 PHASE SEQUENCER N/A YES DISC. THERMOSTAT SETTING C / F N/A N/A 130 / 266 MODEL SAFETY DEVICE INDOOR OUTDOOR HIGH PRESSURE SWITCH FHC50EXV1 R50DXY1 TYPE NC OPEN kpa / psi 2937 / 426 CLOSE kpa / psi 2413 / 350 TYPE NC LOW PRESSURE SWITCH OPEN kpa / psi 124 / 18 CLOSE kpa / psi 192 / 28 PHASE SEQUENCER YES DISC. THERMOSTAT SETTING C / F 130 / 266 ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 24
28 Engineering & Physical Data MODEL SAFETY DEVICE INDOOR FHYC40EXV1 OUTDOOR RY35DXV1 RY40DXV1 RY40DXY1 HIGH PRESSURE SWITCH TYPE NC OPEN kpa / psi 2937 / 426 CLOSE kpa / psi 2413 / 350 TYPE N/A LOW PRESSURE SWITCH OPEN kpa / psi N/A CLOSE kpa / psi N/A PHASE SEQUENCER N/A YES DISC. THERMOSTAT SETTING C / F N/A N/A 130 / 266 MODEL SAFETY DEVICE INDOOR OUTDOOR HIGH PRESSURE SWITCH FHYC50EXV1 R50DXY1 TYPE NC OPEN kpa / psi 2937 / 426 CLOSE kpa / psi 2413 / 350 TYPE N/A LOW PRESSURE SWITCH OPEN kpa / psi N/A CLOSE kpa / psi N/A PHASE SEQUENCER YES DISC. THERMOSTAT SETTING C / F 130 / 266 ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 25
29 Performance Data Performance Data Calculation Steps Interpolation method can be used to get the total cooling capacity, TC and sensible cooling capacity, SC and power input, PI at those temperatures which are not stated out in the table. Extrapolation method is not allowed to be used. Example: Model: FF10CXV1 R10CXV1 Indoor Condition: 25 C DB, 17 C WB Outdoor Condition: 37 C DB Fan Speed: High Solution: Based on the Performance Table, 1. Refer to the Indoor DB column, - 25 C is located between 24 C & 27 C for WB C is located between 24 C & 27 C for WB. - Thus, Interpolation needs to be applied. 2. Refer to the Indoor WB column, - 17 C is located between & for 25 C DB. - Thus, Interpolation needs to be applied. 3. Refer to the Outdoor DB column, - 37 C is located between 35 C & 40 C. - Thus, Interpolation needs to be applied. 1 st Step Interpolation of Indoor WB Find TC, SC & PI (a) Indoor: 25 C DB, WB Outdoor: 35 C DB (b) Indoor: 25 C DB, WB Outdoor: 35 C DB (c) Indoor: 25 C DB, WB Outdoor: 40 C DB (d) Indoor: 25 C DB, WB Outdoor: 40 C DB 2 nd Step Interpolation of Indoor DB Find TC, SC & PI (a) Indoor: 25 C DB, 17 C WB Outdoor: 35 C DB (b) Indoor: 25 C DB, 17 C WB Outdoor: 40 C DB 3 rd Step Interpolation of Outdoor DB Find TC, SC & PI (a) Indoor: 25 C DB, 17 C WB Outdoor: 37 C DB Details of Calculation: 1 st Step: To obtain the TC, SC & PI for (a) Indoor Condition: 25 C DB, WB Outdoor Condition: 35 C DB EWB EDB Outdoor temperature 35 C TC SC PI By Interpolation Method 25 C 24 C x kW = 27 C 24 C 3.30kW 3.20kW x 1 = 3.23kW Similarly, y 1 = 3.23kW z 1 = 1.27kW x 1 y 1 z
30 Performance Data (b) Indoor Condition: 25 C DB, WB Outdoor Condition: 35 C DB EWB 19 EDB Outdoor temperature 35 C TC SC PI x 2 y 2 z By Interpolation Method 25 C 24 C x kW = 27 C 24 C 3.52kW 3.51kW x 2 = 3.51kW Similarly, y 2 = 2.71kW z 2 = 1.29kW Repeat the same process for (c) & (d) in 1 st Step (c) x 3 = 2.98 kw; y 3 = 2.98 kw; z 3 = 1.38 kw (d) x 4 = 3.22 W; y 4 = 2.53 kw; z 4 = 1.40 kw 2 nd Step: To obtain the TC, SC & PI for (a) Indoor Condition: 25 C DB, 17 C WB Outdoor Condition: 35 C DB EWB EDB Outdoor temperature 35 C TC SC PI By Interpolation Method 17 C x kW = 3.51kW 3.23kW x 5 = 3.32kW Similarly, y 5 = 3.06kW z 5 = 1.28kW x 5 y 5 z Repeat the same process for (b) in 2 nd Step (c) x 6 = 3.06 kw; y 6 = 2.83 kw; z 6 = 1.39 kw 3 rd Step: To obtain the TC, SC & PI for (a) Indoor Condition: 25 C DB, 17 C WB Outdoor Condition: 37 C DB EWB EDB Outdoor temperature 35 C 37 C 40 C TC SC PI TC SC PI TC SC PI x y z By Interpolation Method 37 C 35 C x 3.32kW = 40 C 35 C 3.06kW 3.32kW x = 3.22kW Similarly, y = 2.97kW z = 1.35kW 27
31 Performance Data Performance Tables Cooling Only Model: FF10CXV1 - R10CXV1 Cooling Mode AFR (CFM) EWB Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling Capacity (kw) SC: Sensible Cooling Capacity (kw) PI: Power Input (kw) Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB without pressure trip. 28
32 Performance Data Model: FF15CXV1 - R15CXV1 Cooling Mode AFR (CFM) EWB Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling Capacity (kw) SC: Sensible Cooling Capacity (kw) PI: Power Input (kw) Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB without pressure trip. 29
33 Performance Data Model: FF20CXV1 - R20CXV1 Cooling Mode AFR (CFM) EWB Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling Capacity (kw) SC: Sensible Cooling Capacity (kw) PI: Power Input (kw) Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB without pressure trip. 30
34 Performance Data Model: FHC20EXV1 - R20CXV1 Cooling Mode AFR (CFM) EWB Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling Capacity (kw) SC: Sensible Cooling Capacity (kw) PI: Power Input (kw) Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB without pressure trip. 31
35 Performance Data Model: FHC25EXV1 - R25CXV1 Cooling Mode AFR (CFM) EWB Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling Capacity (kw) SC: Sensible Cooling Capacity (kw) PI: Power Input (kw) Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB without pressure trip. 32
36 Performance Data Model: FHC28EXV1 - R28CXV1 Cooling Mode AFR (CFM) EWB Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling Capacity (kw) SC: Sensible Cooling Capacity (kw) PI: Power Input (kw) Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB without pressure trip. 33
37 Performance Data Model: FHC40EXV1 - R35DXV1 Cooling Mode AFR (CFM) EWB Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling Capacity (kw) SC: Sensible Cooling Capacity (kw) PI: Power Input (kw) Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB without pressure trip. 34
38 Performance Data Model: FHC40EXV1 - R40DXV1 Cooling Mode AFR (CFM) EWB Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling Capacity (kw) SC: Sensible Cooling Capacity (kw) PI: Power Input (kw) Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB without pressure trip. 35
39 Performance Data Model: FHC40EXV1 - R40DXY1 Cooling Mode AFR (CFM) EWB Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling Capacity (kw) SC: Sensible Cooling Capacity (kw) PI: Power Input (kw) Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB without pressure trip. 36
40 Performance Data Model: FHC50EXV1 - R50DXY1 Cooling Mode AFR (CFM) EWB Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling Capacity (kw) SC: Sensible Cooling Capacity (kw) PI: Power Input (kw) Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB without pressure trip. 37
41 Performance Data Heatpump Model: FFY10CXV1 - RY10CXV1 Cooling Mode AFR (CFM) EWB Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Model: FFY10CXV1 - RY10CXV1 Heating Mode Outdoor WB ID DB -9 C -6 C -5 C 6 C 12 C 15 C 18 C TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) 15 C C C C C C Frost Region Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling / Heating Capacity (kw) SC: Sensible Cooling / Heating Capacity (kw) PI: Power Input (kw) Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB (cooling) / -9 C to 18 C WB (heating) without pressure trip. 38
42 Performance Data Model: FFY15CXV1 - RY15CXV1 Cooling Mode AFR (CFM) EWB Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Model: FFY15CXV1 - RY15CXV1 Heating Mode Outdoor WB ID DB -9 C -6 C -5 C 6 C 12 C 15 C 18 C TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) 15 C C C C C C Frost Region Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling / Heating Capacity (kw) SC: Sensible Cooling / Heating Capacity (kw) PI: Power Input (kw) Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB (cooling) / -9 C to 18 C WB (heating) without pressure trip. 39
43 Performance Data Model: FFY20CXV1 - RY18CXV1 Cooling Mode AFR (CFM) EWB Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Model: FFY20CXV1 - RY18CXV1 Heating Mode Outdoor WB ID DB -9 C -6 C -5 C 6 C 12 C 15 C 18 C TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) 15 C C C C C C Frost Region Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling / Heating Capacity (kw) SC: Sensible Cooling / Heating Capacity (kw) PI: Power Input (kw) Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB (cooling) / -9 C to 18 C WB (heating) without pressure trip. 40
44 Performance Data Model: FFY20CXV1 - RY20CXV1 Cooling Mode AFR (CFM) EWB Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Model: FFY20CXV1 - RY20CXV1 Heating Mode Outdoor WB ID DB -9 C -6 C -5 C 6 C 12 C 15 C 18 C TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) 15 C C C C C C Frost Region Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling / Heating Capacity (kw) SC: Sensible Cooling / Heating Capacity (kw) PI: Power Input (kw) Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB (cooling) / -9 C to 18 C WB (heating) without pressure trip. 41
45 Performance Data Model: FHYC20EXV1 - RY20CXV1 Cooling Mode AFR (CFM) EWB Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Model: FHYC20EXV1 - RY20CXV1 Heating Mode Outdoor WB ID DB -9 C -6 C -5 C 6 C 12 C 15 C 18 C TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) 15 C C C C C C Frost Region Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling / Heating Capacity (kw) SC: Sensible Cooling / Heating Capacity (kw) PI: Power Input (kw) Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB (cooling) / -9 C to 18 C WB (heating) without pressure trip. 42
46 Performance Data Model: FHYC25EXV1 - RY25CXV1 Cooling Mode AFR (CFM) EWB Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Model: FHYC25EXV1 - RY25CXV1 Heating Mode Outdoor WB ID DB -9 C -6 C -5 C 6 C 12 C 15 C 18 C TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) 15 C C C C C C Frost Region Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling / Heating Capacity (kw) SC: Sensible Cooling / Heating Capacity (kw) PI: Power Input (kw) Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB (cooling) / -9 C to 18 C WB (heating) without pressure trip. 43
47 Performance Data Model: FHYC28EXV1 - RY28CXV1 Cooling Mode AFR (CFM) EWB Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Model: FHYC28EXV1 - RY28CXV1 Heating Mode Outdoor WB ID DB -9 C -6 C -5 C 6 C 12 C 15 C 18 C TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) 15 C C C C C C Frost Region Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling / Heating Capacity (kw) SC: Sensible Cooling / Heating Capacity (kw) PI: Power Input (kw) Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB (cooling) / -9 C to 18 C WB (heating) without pressure trip. 44
48 Performance Data Model: FHYC40EXV1 - RY35DXV1 Cooling Mode AFR (CFM) EWB Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Model: FHYC40EXV1 - RY35DXV1 Heating Mode Outdoor WB ID DB -9 C -6 C -5 C 6 C 12 C 15 C 18 C TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) 15 C C C C C C Frost Region Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling / Heating Capacity (kw) SC: Sensible Cooling / Heating Capacity (kw) PI: Power Input (kw) Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB (cooling) / -9 C to 18 C WB (heating) without pressure trip. 45
49 Performance Data Model: FHYC40EXV1 - RY40DXV1 Cooling Mode AFR (CFM) EWB Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Model: FHYC40EXV1 - RY40DXV1 Heating Mode Outdoor WB ID DB -9 C -6 C -5 C 6 C 12 C 15 C 18 C TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) 15 C C C C C C Frost Region Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling / Heating Capacity (kw) SC: Sensible Cooling / Heating Capacity (kw) PI: Power Input (kw) Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB (cooling) / -9 C to 18 C WB (heating) without pressure trip. 46
50 Performance Data Model: FHYC40EXV1 - RY40DXY1 Cooling Mode AFR (CFM) EWB Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Model: FHYC40EXV1 - RY40DXY1 Heating Mode Outdoor WB ID DB -9 C -6 C -5 C 6 C 12 C 15 C 18 C TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) 15 C C C C C C Frost Region Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling / Heating Capacity (kw) SC: Sensible Cooling / Heating Capacity (kw) PI: Power Input (kw) Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB (cooling) / -9 C to 18 C WB (heating) without pressure trip. 47
51 Performance Data Model: FHYC50EXV1 - RY50DXY1 Cooling Mode AFR (CFM) EWB Outdoor temperature EDB 25 C 30 C 35 C 40 C 46 C TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 21 C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C Model: FHYC50EXV1 - RY50DXY1 Heating Mode Outdoor WB ID DB -9 C -6 C -5 C 6 C 12 C 15 C 18 C TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) TC (kw) SC (kw) 15 C C C C C C Frost Region Remark: AFR: Air fl ow rate (CFM) EWB: Entering Wet Bulb Temp. ( C) EDB: Entering Dry Bulb Temp. ( C) TC: Total Cooling / Heating Capacity (kw) SC: Sensible Cooling / Heating Capacity (kw) PI: Power Input (kw) Notes: 1. Ratings shown are net capacities. 2. shows nominal capacities. 3. Direct interpolation is permissible. Do not extrapolate. 4. Unit is able to operate at ambient from to 46 C DB (cooling) / -9 C to 18 C WB (heating) without pressure trip. 48
52 Outline & Dimension Outline & Dimension Indoor Unit Model: FF(Y)10/15/20CXV1 Note: Dimension in mm Model: FH(Y)C20/25/28/40/50EXV1 B C D E K F H A J I G Dimension Model A B C D E F G H I J K FH(Y)C20/25/28EXV FH(Y)C40/50EXV Note: Dimension in mm 49
FFQN-C, FCRN-E, FFRN-C
R410A TECHNICAL MANUAL Split Unit Air Conditioner Ceiling Cassette C & E Series FCQN-E, FFQN-C, FCRN-E, FFRN-C Cooling only & Heatpump [50Hz] DAIKIN_FFRN.indb i 12/27/2012 9:28:06 AM DAIKIN_FFRN.indb ii
More informationR410A TECHNICAL MANUAL. Inverter Single Split Series Air Conditioner. FTK-J, FTXN-J Series. Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2
R410A TECHNICAL MANUAL Inverter Single Split Series Air Conditioner FTK-J, FTXN-J Series Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2 Table of Contents Table of Contents Nomenclature...1 Indoor...1 Outdoor...1
More informationFDYMP-D, FDP-D, FGP-D, FDYP-E, FGYP-E
R407C TECHNICAL MANUAL Split Systems Air Conditioner Ducted Blower D & E Series FDMP-D, FDYMP-D, FDP-D, FGP-D, FDYP-E, FGYP-E series Cooling only & Heatpump [50Hz] Table of Contents Table of Contents
More informationCeiling Concealed Series FDMRN-AV1K. 50Hz. Preliminary
Ceiling Concealed Series FDMRN-AV1K 50Hz Nomenclature Main Benefits Engineering and Physical Data Electrical Data Capacity Tables Outline and Dimensions Electrical Connection Refrigerant Piping Nomenclature
More informationtechnical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO
technical sales guide - 60Hz Taurus R Ducted Split Units UPTO HIGH AMBIENT OPERATION 52 O C Page CONTENTS Nomenclature.. 2 Description. 3 Features.. 3 Product Data. 4 Condensing Unit Cooling Performance
More informationV33B High Efficiency 360 Cassette Indoor Models - 60HZ
PRODUCT SPECIFICATIONS Low-sound, high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has motor-driven
More informationV33A Standard/High Efficiency 360 Cassette Indoor Models - 60HZ
PRODUCT SPECIFICATIONS Low-sound, standard or high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has
More informationVMDA Concealed Medium Static Ducted Indoor Models - 60HZ
VARIABLE REFRIGERANT FLOW SYSTEMS VRF VMDA Concealed Medium Static Ducted Indoor Models - 60HZ PRODUCT ECIFICATIONS Slim, compact design for limited space requirements. Installs out of sight between the
More informationVWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ
PRODUCT SPECIFICATIONS VARIABLE REFRIGERANT FLOW SYSTEMS VRF VWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ Bulletin No. 210712 March 2018 Low-sound, three-speed Wall Mount with LED display offers three
More informationOperating Net Capacity BTU/h. Input BTU/h Efficiency. lbs (kg) PGR524040KGP* 23, ,000/26, /8 x 47 x 31-7/16
SOUND REFRIGERANT ENVIRONMENTALLY Product Specifications UP to 16 SEER, UP to 12.5 EER, PACKAGE GAS / ELECTRIC, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz 208/230 Volt, 3 phase, 60 Hz REFRIGERATION CIRCUIT
More informationVMDB Concealed Medium Static Ducted Indoor Models - 60HZ
VARIABLE REFRIGERANT FLOW SYSTEMS VRF VMDB Concealed Medium Static Ducted Indoor Models - 60HZ PRODUCT ECIFICATIONS Bulletin No. 210711 March 2018 Slim, compact design for limited space requirements. Installs
More informationN4A6. Product Specifications
ENVIRONMENTALLY SOUND REFRIGERANT N4A6 Product Specifications EFFICIENT UP TO 16.5 SEER/12.2 13.0 EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/2 Volt,
More informationtechnical data air conditioning systems MA-GZ7 Multi Model Application Split Sky Air
technical data MA-GZ7 Multi Model Application air conditioning systems Split Sky Air Split - Sky Air ISO14001 assures an effective environmental management system in order to help protect human health
More informationROOF TOP (SERIES SR) 10.8 TO 103 KW 37,000 TO 351,000 Btuh
ROOF TOP (SERIES ) 10.8 TO 103 KW 37,000 TO 351,000 Btuh These rooftop units are complete, self contained air conditioners fully assembled, wire, charged and tested prior to shipment, each unit is delivered
More informationR4A5. Product Specifications EFFICIENT 14 SEER/ EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT
ENVIRONMENTALLY SOUND REFRIGERANT R4A5 Product Specifications EFFICIENT 14 SEER/11.7 12.2 EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt, 1 phase,
More information1. Features Specifications Dimensions Service Spaces Piping Diagrams Wiring Diagrams...
MCAC-VTSM-2013-08 1. Features... 264 2. Specifications... 265 3. Dimensions... 268 4. Service Spaces... 272 5. Piping Diagrams... 273 6. Wiring Diagrams... 274 7. Capacity Tables... 276 8. Electrical Characteristics...
More information6-1/3 and 7-1/2 Ton Split System Air Conditioner (3 Phase) 75 to 89 MBtuh R -22 Refrigerant. Nominal Capacity BTUH
CAE Product Specifications 6-1/3 and 7-1/2 Ton Split System Air Conditioner (3 Phase) 75 to 89 MBtuh R -22 Refrigerant REFRIGERATION CIRCUIT Copeland scroll compressors on all models with single refrigeration
More informationVHIA High-Static Ducted Indoor Units - 60HZ
PRODUCT SPECIFICATIONS Compact design for limited space requirements. Installs out of sight between the drop ceiling and ceiling slab with ducted distribution to the indoor space. All models have three-stage
More informationtechnical data air conditioning systems RXG-C Wall Mounted, Inverter Controlled Unit Split Sky Air
technical data RXG-C Wall Mounted, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human
More information40KQV. Direct expansion split system Inverter Cassette. Nominal Cooling capacity: 4,85-12,40 kw Nominal Heating capacity: 5,10-13,00 kw
LLOYD'S REGISTER QUALITY ASSURANCE Direct expansion split system Inverter Cassette I S O 9 00 1 40KQV Nominal Cooling capacity: 4,85-12,40 kw Nominal Heating capacity: 5,10-13,00 kw 40KQV cassette belongs
More informationSplit. Air Conditioning Technical Data FTXC-A > FTXC25AV1B > FTXC35AV1B > FTXC50AV1B > FTXC60AV1B
Split Air Conditioning Technical Data FTXC-A > FTXC25AV1B > FTXC35AV1B > FTXC50AV1B > FTXC60AV1B Indoor Unit FTXC-A TABLE OF CONTENTS FTXC-A 1 Features.............................................................
More informationCSA6. Product Specifications. SoftSound SXC 2600
16 SEER SINGLE STAGE AIR CONDITIONER WITH OBSERVERr COMMUNICATING CONTROL SYSTEM 1½ THRU 5 TONS SPLIT SYSTEM 208 / 2 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Copeland Scroll compressors on all models
More informationPACKAGE UNIT PCA340U TECHNICAL SELECTION DATA. -10 o C UNIT FEATURES SPECIFICATION SUMMARY UNIT OPTIONS CONTROL OPTIONS UNIT COMPLIANCE.
TECHNICAL SELECTION DATA PACKAGE UNIT + o C -10 o C 3 THREE PHASE SCROLL TWO STAGE CENTRIFUGAL LOUVRE LIANT SCROLL RESSOR AXIAL UNIT FEATURES SPECIFICATION SUMMARY Scroll Compressor Multiple Speed Outdoor
More informationBAC / BHC Product Specifications
COMMERCIAL AIR HANDLERS (3 PHASE) 6 to 20 TON / Product Specifications REFRIGERATION CIRCUIT Standard factory-installed thermostatic expansion valves (TXVs) on units; units include TXVs and check valves
More informationOutdoor Units R-410A ARX-GV1B
Outdoor Units R-40A ARX-GVB t A i n y U k BS r o AV t o0g i d- lt4x pur- SRAO 2 Specifications Outdoor Units R-40A ARX-GVB 2- NOMINAL CAPACITY AND NOMINAL INPUT ARX20GVB ARX25GVB ARX5GVB For combination
More informationTechnical Service Manual. TVR LX Systems Low Static Pressure Duct Units with DC Fan Motor V/50-60Hz/1ph
Technical Service Manual TVR LX Systems Low Static Pressure Duct Units with DC Fan Motor 220-240V/50-60Hz/1ph August 2015 1. Features...2 2. Specifications...3 3. Dimensions...7 4.Service Spaces...8 5.Piping
More informationProduct Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES
FFMA Base Series Fan Coil Sizes 018 thru 037 Product Data A13417 FEATURES The FFMA Series Fan Coil unit is primarily designed for apartment applications as an upflow only indoor fan coil for split -system
More informationN4A4 C. Product Specifications
COASTAL 14 SEER AIR CONDITIONER 14 SEER/11.5 12.5 EER R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT Scroll compressors on all models Filter drier
More information38P 60Hz Nominal Cooling Capacity Tons HFC R -410A Refrigerant
38P Condensing Units 60Hz 38P 36K 60K 38P 18K 24K Quality Assurance Certificate Reg. No: 04 100 950420 Product Data Catalog Subject to change without notice Manufacturer s Name: Saudi Airconditioning Manufacturing
More informationWCA4**4. Product Specifications
WCA4**4 AIR CONDITIONER EFFICIENT 14 SEER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208/2 Volt, 1 phase, 60 Hz Use of the AHRI Certified TM Mark indicates a manufacturer s participation
More informationProduct Data PH3Z 13 SEER SINGLE -PACKAGED HEAT PUMP SYSTEM WITH R -22 REFRIGERANT SINGLE AND THREE PHASE 2-5 NOMINAL TONS ( )
13 SEER SINGLE -PACKAGED HEAT PUMP SYSTEM WITH R -22 REFRIGERANT SINGLE AND THREE PHASE 2-5 NOMINAL TONS (024-0) Product Data Fig. 1 - Unit 664B Single -Packaged Heat Pump Units with: S easy installation
More informationtechnical data air conditioning systems Round Flow Cassette FXFQ-P9VEB
technical data Round Flow Cassette FXFQ-P9VEB air conditioning systems technical data Round Flow Cassette FXFQ-P9VEB air conditioning systems TABLE OF CONTENTS FXFQ-P9VEB 1 Specifications.......................................................
More informationCAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE
COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE Single stage cooling capacity control on all 0 241 models Two stage cooling capacity control on
More informationProduct Data. FF1E Base Series Fan Coil Sizes 018 thru 036 FEATURES
Base Series Fan Coil Sizes 018 thru 036 Product Data FEATURES The Series Fan Coil unit is primarily designed for apartment applications as upflow indoor air handlers for split system heat pumps and air
More informationCFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) 1800Aǂ 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15
ENVIRONMENTALLY SOUND REFRIGERANT FMA4X, FMA4P Product Specifications APARTMENT FAN COILS ALL MODELS 1 1/2, 2, 2 1/2, and 3 Tons Upflow application only Accessory field installed electric heat kits available
More informationCAC SERIES 12-1/2 Thru 20 Ton
CAC SERIES 12-1/2 Thru 20 Ton SPLIT SYSTEM COMMERCIAL AIR CONDITIONER CONSTRUCTION Triple step pre--painted galvanized steal pre--coated inside and out -- using a polyester top coat, over a urethane primer
More informationConcealed Ducted Split Series R22
Concealed Ducted Split Series R22 24-60 MBH Ducted Split with Hermetic Compressor Tropical 50 Hz For more technical information please visit Table of Contents INTRODUCTION 2 NOMENCLATURE 2 UNIT RATING
More informationFrom: Toong Way See (Engineer, Global UP Product Marketing, OYLM) Date ( )
Dear Valued Customers, From: Toong Way See (Engineer, Global UP Product Marketing, OYLM) Date (02-02-2009) SUBJECT: Compressor Change of AMC75C/100B/125B/150C with New Compressor Compressor Change of AMC75C/100B/125B/150C
More informationTons BTU/h S.E.E.R* E.E.R** HSPF
SOUND REFRIGERANT ENVIRONMENTALLY PHD3 Product Specifications 13 SEER, R -410A PACKAGE HEAT PUMP, 2½ to 5 TONS 3 -Phase, 208/230-3 -60 and 460-3 -60 REFRIGERATION CIRCUIT R--410A refrigerant Copper tube/aluminum
More informationSPLIT DUCTED UNIT SCA300C / SCA300E TECHNICAL SELECTION DATA SPECIFICATION SUMMARY UNIT FEATURES CONTROL OPTIONS UNIT COMPLIANCE
TECHNICAL SELECTION DATA SPLIT DUCTED UNIT 3 THREE PHASE SCROLL TWO STAGE CENTRIFUGAL LOUVRE AXIAL UNIT FEATURES Scroll Compressor Multiple Speed Outdoor Fans Louvred Outdoor Coil Guard Pre-charged with
More informationLow Static Pressure Duct(V shape evaporator)
Low Static Pressure Duct (V shape evaporator) 1. Features... 116 2. Specifications... 118 3. Dimensions... 121 4. Service Spaces... 123 5. Piping Diagrams... 124 7.Fan Performance... 126 8.Capacity Tables...
More informationTechnical Service Manual
Technical Service Manual 60 Hz Low/Mid Pressure Duct Units 7 48 MBH Units 96 MBH Unit June 2009 VRF-SVM21A-EN Low and Mid Pressure Duct Units 1. Features......... 2 2. Specifications......... 3 3. Dimensions.........
More informationProduct Data. Features/Benefits. 38HDL Cooling Only Condensing Unit. 1 1 / 2 to 5 Nominal Tons
Product Data 38HDL018-060 Cooling Only Condensing Unit 1 1 / 2 to 5 Nominal Tons The 38HDL energy-efficient condensing unit incorporates innovative technology to provide reliable cooling performance. Built
More informationProduct Data FFMA BASE SERIES FAN COIL SIZES 018 TO 037 FEATURES
FFMA BASE SERIES FAN COIL SIZES 018 TO 037 Product Data A13417 FEATURES The FFMA Series Fan Coil unit is primarily designed for apartment applications as an upflow only indoor fan coil for split- system
More informationBAC / BHC SERIES 6 to 20 Ton Air Handlers
/ SERIES 6 to 20 Ton Air Handlers COMMERCIAL SPLIT SYSTEM AIR HANDLER FEATURES CONSTRUCTION Die-formed galvanizedsteel casingsprovide durabilityand structuralintegrity. HIGH STATIC DESIGN High static design
More informationD M S 760 C01 A A 1 1
CONTENTS Description Features Options Available Selection Method Product Data Cooling Performance Data (85 F Ambient Cooling Performance Data (95 F Ambient) Cooling Performance Data (105 F Ambient)..............................
More informationR4A4. Product Specifications EFFICIENT 14 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT
R4A4 Product Specifications EFFICIENT 14 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/2 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT Scroll compressors
More informationBAC / BHC SERIES 6 to 20 Ton Air Handlers
/ SERIES 6 to 20 Ton Air Handlers COMMERCIAL SPLIT SYSTEM AIR HANDLER FEATURES CONSTRUCTION Die-formed galvanizedsteel casingsprovide durabilityand structuralintegrity. HIGH STATIC DESIGN High static design
More informationProduct Data. CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) FMA4P1800AL 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15
Product Data FMA4X, FMA4P APARTMENT FAN COIL UNIT 1 1/2 TONS THROUGH 3 TONS APARTMENT FAN COILS ALL MODELS 1 1/2, 2, 2 1/2, and 3 Tons Upflow application only Accessory field installed electric heat kits
More information50 Hz AIR - COOLED SPLIT SYSTEM. Products That Perform...By People Who Care AIR CONDITIONERS WITH SCROLL COMPRESSORS
R FORM NO: MS0305F Products That Perform...By People Who Care AIR - COOLED SPLIT SYSTEM AIR CONDITIONERS WITH SCROLL COMPRESSORS 50 Hz COOLING CAPACITY- 60 MBH TO 1360 MBH ACCS SERIES HEB-D, EB-D SERIES
More informationTSTAT0201CW (Sold Separately) Qualifying models only. Max. Fuse or Breaker
HVA9 Product Specifications HIGH EFFICIENCY UP TO 19 SEER VARIABLE SPEED AIR CONDITIONER WITH OBSERVER COMMUNICATING CONTROL SYSTEM 2 THRU 5 TONS SPLIT SYSTEM 208 230 Volt, 1 phase, 60 Hz REFRIGERATION
More informationTechnical Service Manual. TVR LX Systems Medium Static Pressure Duct Units with DC Fan Motor V/50-60Hz/1ph
Technical Service Manual TVR LX Systems Medium Static Pressure Duct Units with DC Fan Motor 220-240V/50-60Hz/1ph August 20 Medium Static Pressure Duct Unit With DC Fan Motor 1. Features...2 2. Specifications...4
More informationCHILLED WATER FAN-COIL UNITS
40LM - PRODUCT DATA DIGEST CHILLED WATER FAN-COIL UNITS QUALITY SYSTEM MALAYSIA MS ISO 001 REG. NO: AR 023 1 Any room, every room flexibility in an air conditioning system FEATURES: Chilled Water Furred-in
More informationProduct Data. FF1E Base Series Fan Coil Sizes 018 thru 036 FEATURES
Base Series Fan Coil Sizes 018 thru 036 Product Data FEATURES The Series Fan Coil unit is primarily designed for apartment applications as upflow indoor air handlers for split -system heat pumps and air
More informationSINGLE. Technical Data Book. 4Way Cassette S for Nordic (R410A, 50Hz) Model : AC***JN4CEH/EU (ODU: AC***JXSC*H/EU)
SINGLE Technical Data Book 4Way Cassette S for Nordic (R4A, 5Hz) Model : AC***JN4CEH/EU (ODU: AC***JXSC*H/EU) History Version Modification Date Remark Ver.1. Released SINGLE for Nordic TDB 15.3.. Ver.1.1
More informationProduct Data. FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil
FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil A13303 Fig. 1 - FPM(A,B)NU Uncased Horizontal Fan Coil (FPMANU model shown) Fig. 2 - FPM(A,B)NC Cased Horizontal Fan Coil
More informationPCB COMMERCIAL SERIES
PCB COMMERCIAL SERIES 50 Hz SELF-CONTAINED PACKAGE CONDITIONER 7½, 0, AND 5 TON [6.4 kw to 5.8 kw] COOLING CAPACITY: 90,000 TO 80,000 BTU/H The PCB Commercial 50 Hz self-contained packaged air conditioner
More informationDAIKIN INDUSTRIES, LTD. Ceiling Concealed Chilled Water Fan Coil Unit (50Hz/60Hz)
Engineering Data ED-FWW-201501 Ceiling Concealed Chilled Water Fan Coil Unit (50Hz/60Hz) Models: FWW200 FWW300 FWW400 FWW600 FWW800 FWW1000 FWW1200 FWW1400 FWW1600 FWW1800 Air Flow: 360-3020m 3 /h DAIKIN
More informationQ6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.
TECHNICAL SPECIFICATIONS Q6SP Series Rev A 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.0 EER Commercial Systems Meet or Exceed ASHRAE 90.1-2010 These 7½ and 10 ton units are designed
More informationProduct Data FF1E LEGACY LINE FAN COIL SIZES 018 THRU 037 FEATURES
LEGACY LINE FAN COIL SIZES 018 THRU 037 Product Data FEATURES The Series Fan Coil unit is primarily designed for apartment applications as upflow indoor air handlers for split-system heat pumps and air
More informationN2AE - 50 Hz PRODUCT SPECIFICATIONS
ISO 9001:2000 REGISTERED N2AE - 50 Hz PRODUCT SPECIFICATIONS 50 Hz AIR CONDITIONING CONDENSING UNIT 230 Volt, 1-phase, 50 Hz in 1½, 2, 2½, 3, 4 tons 400 Volt, 3-phase, 50 Hz in 3, 3½, 4, 5 tons REFRIGERATION
More informationEngineering Data Book
40VMA Outside Air Processing Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without
More informationPerformance Data OUTDOOR COIL ENTERING AIR TEMPERATURE C 30 C 35 C 40 C 45 C LWB C. Sens Cap KW
R410a Refrigerant SHS1 Split Ducted Model INDOOR COIL ENTERING AIR TEMP DB WB 21 23 2 27 29 31 Performance Data OUTDOOR COIL ENTERING AIR TEMPERATURE 30 3 40 4 17 14.0 9.1 9.8 13.2 8.8 9.0 12. 8. 12.9
More informationFSH1BG Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Ultra High Efficiency Heat Pump, Up to 19 SEER Residential System 2-5 Ton Capacities
TECHNICAL SPECIFICATIONS FSH1BG Series Ultra High Efficiency Heat Pump, Up to 19 SEER Residential System 2-5 Ton Capacities The iq Drive heat pump system features modulating compressor technology and variable
More informationVRF Indoor Unit 50Hz. Type: Wall Mounted M Series Wall Mounted S Series
VRF Indoor Unit 50Hz Type: Wall Mounted M Series Wall Mounted S Series Contents 01 Wall Mounted M Series 20 Wall Mounted S Series MCAC-VTSM-2016-05 Wall Mounted M Series Wall Mounted M Series 1. Features...
More informationProduct Data. 38HK HQ18-24 Condensing Units - 50Hz 1 to 6 Nominal Tons
38HK18-70 38HQ18-24 Condensing Units - 50Hz 1 to 6 Nominal Tons Product Data The 38H Series Energy-Efficient Split condensing units incorporate innovative technology to provide reliable cooling performance.
More informationCompact Four-way Cassette Type
1. Features... 34 2. Specifications... 35 3. Dimensions... 37 4. Service Spaces... 38 5. Piping Diagrams (EXV beside)... 39 6. Wiring Diagrams... 40 7. Capacity Tables... 41 8. Electrical Characteristics...
More informationtechnical data air conditioning systems RKS-C RKS-B Pair Application, Inverter Controlled Unit Split Sky Air
technical data RKS-C RKS-B Pair Application, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help
More informationS5BP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS
TECHNICAL SPECIFICATIONS S5BP Series Split System Air Conditioner 71/2 Ton Energy Star rated at 11.7 EER and 11.8 IEER 10 Ton rated at 11.2 EER and 11.5 IEER R-410A Refrigerant The S5BP Series of air conditioners
More informationProduct Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES
FFMA Base Series Fan Coil Sizes 018 thru 037 Product Data A13417 FEATURES The FFMA Series Fan Coil unit is primarily designed for apartment applications as an upflow only indoor fan coil for split -system
More informationCFM (L/s) Min Max 450 (212) 600 (283) 750 (354) Dimensions H x W x D in. (mm) 675 (319) 36 1/2 x 20 1/2 x (425)
ENVIRONMENTALLY SOUND REFRIGERANT FMA4P Product Specifications APARTMENT FAN COILS ALL MODELS 1 1/2, 2, 2.5, and 3 Tons Upflow application only For use with R 410A refrigerant or R 22 with accessory TXV
More informationTECHNICAL GUIDE R410a SPLIT SYSTEM 1.5 to 5.0 NOMINAL TONS
Version.MDT-2016.T3.103 TECHNICAL GUIDE R410a SPLIT SYSTEM 1.5 to 5.0 NOMINAL TONS FEATURES AND BENEFITS COMPRESSOR: Compressors are protected with internal temperature and current overloads. An internal
More informationEngineering Data Book
40VMH High Static Duct Indoor Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without
More informationFMU4X, FMC4X FMU4Z, FMC4Z
HORIZONTAL FAN COILS FMU4Z and FMC4Z 1 1/2, 2, 2 1/2, and 3 Tons FMU4X and FMC4X 1 1/2, 2, 2 1/2, and 3 Tons Horizontal application only Accessory field installed electric heat kits available in 3, 5,
More informationCFM (L/s) Dimensions. Filter Size Ship Wt. HxWxDin.(mm) 1800Aǂ 1-1/2 18, (212) 675 (319) 36-1/2 x 20-1/2 x (45) FMA4P (928 x 521 x 381)
FMA4X, FMA4P Product Specifications APARTMENT FAN COILS ALL MODELS 1-1/2, 2, 2-1/2, and 3 Tons Upflow application only Accessory field- installed electric heat kits available in, 7., or 10 kw 208/230-1-
More informationCFM (L/s) Dimensions. Filter Size in. Ship Wt. H x W x D in. (mm) 1800A 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15
ENVIRONMENTALLY SOUND REFRIGERANT FMA4X, FMA4P Product Specifications APARTMENT FAN COILS ALL MODELS 1 1/2, 2, 2 1/2, and 3 Tons Upflow application only Accessory field installed electric heat kits available
More informationRooftop Packaged Air Conditioners
Catalog Rooftop Packaged Air Conditioners Models: MRT 055 A/AR MRT 060 A/AR MRT 080 A/AR MRT 100 A/AR MRT 120 A/AR MRT 150 A/AR MRT 200 A/AR MRT 250 A/AR MRT 300 A/AR MRT 360 A/AR MRT 420 A/AR M4RT M4RT
More informationtechnical data air conditioning systems RYP-L7/B7 Pair Application Split Sky Air
technical data RYP-L7/B7 Pair Application air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the
More informationProduct Data. Features/Benefits. Omnizone 50XCA06-14 Air-Cooled Indoor Self-Contained Systems with Puron Refrigerant (R-410A) 5 to 12 Nominal Tons
Product Data Omnizone 50XCA06-14 Air-Cooled Indoor Self-Contained Systems with Puron Refrigerant (R-410A) 5 to 1 Nominal Tons The 50XCA single-package cooling units with integral air-cooled condensers
More informationTECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS Model PSA4BG Series M1200 Product Line Ultra High Efficiency Air Conditioner 20 SEER Residential System 2-5 Ton Capacities 2 The iq Drive air conditioner system features modulating
More informationCeiling Concealed Chilled Water Fan Coil Unit
Technical Manual MODELS: ACW200 ACW300 ACW400 ACW600 ACW800 ACW1000 ACW1200 Air Flow: 112~2040 m 3 /h ACW - C/F/H - 2009-001 Ceiling Concealed Chilled Water Fan Coil Unit Contents Nomenclature... 2 Features...
More informationPHR5. Product Specifications
PHR5 Product Specifications UP to 15.5 SEER, UP to 12.5 EER, PACKAGE HEAT PUMP UNITS, 2 5 TONS 208/230 Volt, 1 phase, 60 Hz 208/230 Volt, 3 phase, 60 Hz REFRIGERATION CIRCUIT Environmentally balanced R
More informationR4A3. Product Specifications EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT
EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 1-1/2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt, 1- phase, 60 Hz R4A3 Product Specifications REFRIGERATION CIRCUIT S Scroll compressors
More informationSPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE
SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE Indoor unit ASYA24LCC ASYA24LCC ASYA24LCC Outdoor unit AOYR24LCC AOYR24LCD AOYR24LCL CONTENTS SPECIFICATIONS..................1 DIMENSIONS.....................
More informationS6BQ Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Split System 2-Stage Air Conditioner. 7 1/2 and 10 Ton rated at 11.2 EER and 12.
TECHNICAL SPECIFICATIONS S6BQ Series Split System 2-Stage Air Conditioner 7 1/2 and 10 Ton rated at 11.2 EER and 12.9 IEER The S6BQ Series of air conditioners offers exceptional performance. The unit,
More informationModel RAS-25YHA2 RAS-35YHA3 RAS-50YHA2 RAS-60YHA2 RAS-70YHA2 RAS-80YHA2
2-8 GENERAL DATA 2.3. INVERTER SERIES 2.3.1. INVERTER (RAS-25YHA2/35YHA3/50YHA2/60YHA2/70YHA2/80YHA2) Model RAS-25YHA2 RAS-35YHA3 RAS-50YHA2 RAS-60YHA2 RAS-70YHA2 RAS-80YHA2 Power Supply From Outdoor Unit
More informationQ5RD Series Single Packaged Heat Pump, Single Phase
TECHNICAL SPECIFICATIONS Q5RD Series Single Packaged Heat Pump, Single Phase 13 SEER, R-410A 2 thru 5 Ton Units Cooling: 24,000 to 56,000 Btuh Heating: 24,000 to 54,500 Btuh The Q5 Series single packaged
More informationS3BN Series Split System Air Conditioner 10.3 EER Commercial System 7½ and 10 Ton Capacity R-22 Refrigerant
TECHNICAL SPECIFICATIONS S3BN Series Split System Air Conditioner 10.3 EER Commercial System 7½ and 10 Ton Capacity R-22 Refrigerant The S3BN Series of air conditioners offers exceptional performance from
More informationPH120. Rooftop Packaged. R410a Refrigerant PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C
PH120 R410a Refrigerant Rooftop Packaged INDOOR COIL ENTERING AIR TEMP 0 c DB WB 21 23 25 27 29 31 PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C 30 35 40 45 Cap Cap Cap Cap 17 115.3 70.7 11.5
More informationLow Static Pressure Duct (V shape evaporator)
MCAC-VTSM-2015-04 Low Static Pressure Duct Type Low Static Pressure Duct (V shape evaporator) 1. Features... 100 2. Specifications... 101 3. Dimensions... 105 4.Service Spaces... 106 5.Piping Diagrams...
More informationR4H4. Product Specifications
ENVIRONMENTALLY SOUND REFRIGERANT R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION
More information38AUM Air Cooled Condensing Units 50Hz
38AUM Air Cooled Condensing Units 50Hz Quality Assurance Certificate Reg. No: 04 100 950420 Product Data Catalog Subject to change without notice Manufacturer s Name: Saudi Airconditioning Manufacturing
More informationSplit-Sky Air RP-B7 Twin/Triple/Double Twin Application
TECHNICAL DATA Split-Sky Air RP-B7 Twin/Triple/Double Twin Application Split Sky Air ISO14001 assures an effective environmental management system in order to help protect human health and the environment
More informationPerformance Data OUTDOOR COIL ENTERING AIR TEMPERATURE C 30 C 35 C 40 C 45 C LWB C. Sens Cap KW
R410a Refrigerant SHS25 Split Ducted Model INDOOR COIL ENTERING AIR TEMP DB WB 21 2 25 27 29 1 Performance Data OUTDOOR COIL ENTERING AIR TEMPERATURE 0 5 40 45 17 2.4 1.8 11. 22.2 1.4 11.9 21.1 12.9 12.2
More informationP5RF Series Single Packaged Air Conditioner Single Phase
TECHNICAL SPECIFICATIONS P5RF Series Single Packaged Air Conditioner Single Phase 15 SEER, 12 EER, R-410A 2 thru 5 Ton Units Cooling: 24,000 to 57,500 Btuh The P5 Series single packaged air conditioners
More informationPerformance Data OUTDOOR COIL ENTERING AIR TEMPERATURE C 30 C 35 C 40 C 45 C LWB C. Sens Cap KW
R410a Refrigerant SHS35 Split Ducted Model INDOOR COIL ENTERING AIR TEMP DB WB 21 23 25 27 29 31 Performance Data OUTDOOR COIL ENTERING AIR TEMPERATURE 30 35 40 45 17 34.1 21.1 11.4 32.5 20.4 11.7 30.8
More informationHigh Static Pressure Duct Fan Coil Unit
MCAC-KTSM-2012-03 High static pressure ducted FCU High Static Pressure Duct Fan Coil Unit 1. Introduction... 2 2. Nomenclature... 2 3. Product Schedule... 3 4. External Appearance... 3 5. Features... 4
More informationProduct Data PH13NA PH13PA FEATURES AND BENEFITS. 13SEERSplitSystemHeatPump with R---410A Refrigerant 1.5 To 5 Nominal Tons AVAILABLE SIZES:
PH13PA 13SEERSplitSystemHeatPump with R---410A Refrigerant 1.5 To 5 Nominal Tons Product Data NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory
More informationDC INVERTER DUCTED AIR CONDITIONERS
DC INVERTER DUCTED AIR CONDITIONERS DC Inverter Ducted Air Conditioners Technology. With over 5% of revenue invested in research and development programs, Hitachi has developed world leading technologies
More informationCFFWA Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 12,000-60,000 BTUH
CFFWA Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 12,000-60,000 BTUH 207 CFFWA NOMENCLATURE BREAKDOWN 2-Pipe Heat/Cool Universal Mount Fan Coil CFFWA- XX - 1 - U 2-Pipe Heat/Cool
More information