technical data air conditioning systems MXS-B Multi Application Split Sky Air
|
|
- Arabella Clarke
- 6 years ago
- Views:
Transcription
1 technical data MXS-B Multi Application air conditioning systems Split Sky Air
2 Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment Daikin units comply with the European regulations that guarantee the safety of the product. Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO900 standard. ISO900 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product. Daikin Europe N.V. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products. Multi Units are certified by Eurovent for combinations up to 2 indoor units. Specifications are subject to change without prior notice. Zandvoordestraat 300 B Ostend Belgium Internet: EEDE03-/2 04/2003 Prepared in Belgium by Goekint Graphics
3 Multi Application R-40A MXS40,52,68,80B TABLE OF CONTENTS MXS-B Features Specifications... 3 Technical specifications Electrical specifications 3 Combination table Dimensional drawings Operation range Piping diagrams Wiring diagrams Sound level... 2 Sound level data Sound pressure spectrum 9 Accessories Standard accessories Optional accessories 0 Installation Split - Sky Air Outdoor Units
4 Multi Application R-40A MXS40,52,68,80B Features Outdoor units for Multi application + With Multi B-outdoor units, it is possible to connect up to 4 indoor units of different capacities to a single outdoor unit, thereby reducing installation space and costs. + It is possible to combine different types of SPLIT indoor units as well as small SKY AIR indoor units (e.g. wall mounted, Floor standing, 60x60 cassette). + All DC-Inverter indoor units can be installed in Multi Model application. Combination with AC and NON inverter units is impossible. + All indoor units remain individually controllable and do not need to be installed at the same time or in the same room. Further units can always be added at a later stage. Moreover, the energy consumption of a Daikin Multi system can be up to 20% lower than that of a separate indoor and outdoor unit application. + Daikin outdoor units can be mounted easily on a roof or terrace or simply placed against an outside wall. They are fitted with a swing compressor, renowned for its low noise and high energy efficiency. + Multi B-outdoor units are fitted with a swing compressor, renowned for its low noise and energy efficiency. 2 Split - Sky Air Outdoor Units
5 Multi Application R-40A MXS40,52,68,80B 2 Specifications TECHNICAL SPECIFICATIONS OUTDOOR UNITS 2MXS40BVMB 3MXS52BVMB 4MXS68BVMB 4MXS80BVMB DIMENSIONS Unit H mm W mm D mm WEIGHT Unit kg COLOUR Unit Ivory white SOUND LEVEL Sound pressure () cooling (H/L) dba 47/43 46/* 48/* 48/* heating (H/L) dba 48/44 47/* 49/* 49/* Sound power (2) cooling (H) dba heating (H) dba * FAN Air flow rate cooling (H/L) m 3 /min 35/30 44/37 5/ /42 heating (H/L) m 3 /min 32/27 44/ /45 45/42 Speed cooling (H/L) rpm 880/ / / /680 heating (H/L) rpm 880/ / / /680 Model Propeller Motor output W HEAT EXCHANGER Type WF fin, J8 Hi-XA tube Rows x stages x fin pitch mm x 28 x.4 2 x 32 x.8 2 x 32 x.6 2 x 40 x.4 REFRIGERANT CIRCUIT Refrigerant type R-40A Refrigerant charge kg Maximum allowable distance between indoor m 30 (for total of each room) 45 (for total of each room) 60 (for total of each room) 70 (for total of each room) and outdoor 20 (for one room) 25 (for one room) 25 (for one room) 25 (for one room) Maximum allowable level difference m 5 (Between indoor and outdoor units) 7.5 (between indoor units) Additional refrigerant g/m 20 (20m or more) 20 (30m or more) 20 (30m or more) 20 (40m or more) COMPRESSOR Type Hermetically sealed swing type Model YC23GXD 2YC32HXD 2YC45BXD 2YC45BXD Motor output ,380,380 Oil type FVC50K Oil charge volume! PIPING CONNECTIONS liquid mm φ6.4x2 φ6.4x3 φ6.4x4 φ6.4x4 gas mm φ9.5x2 φ9.5x2,φ2.7 x φ9.5x2,φ2.7 x 2 φ9.5x2,φ2.7 x, φ5.9 x drain mm φ8.0 φ8.0 φ8.0 φ25.0 INSULATION MATERIAL Heat insulation tape Both liquid and gas pipes 2 * This information was not available at the time of publication. ELECTRICAL SPECIFICATIONS OUTDOOR UNITS 2MXS40BVMB 3MXS52BVMB 4MXS68BVMB 4MXS80BVMB CURRENT Nominal running current cooling A Please refer to electrical data Max. running current cooling A Please refer to electrical data Starting current cooling A OUTDOOR UNITS 2MXS40BVMB 3MXS52BVMB 4MXS68BVMB 4MXS80BVMB POWER SUPPLY VM VM VM VM NOMINAL DISTRIBUTION Phase SYSTEM VOLTAGE Frequency Hz Voltage V NOTES The sound pressure level is measured via a microphone at m distance from the unit. For measuring conditions: please refer to item 9 of this chapter. 2 The sound power level is an absolute value indicating the power which a sound source generates. Split - Sky Air Outdoor Units 3
6 Multi Application R-40A MXS40,52,68,80B 2 Specifications 2 ELECTRICAL DATA 2MXS40B Cooling (50Hz 230V) Units Power supply Comp. OFM IFM Combination Hz Volts Min. Max. MCA MFA RLA W FLA W FLA Heating (50Hz 230V) Units Power supply Comp. OFM IFM Combination Hz Volts Min. Max. MCA MFA RLA W FLA W FLA MXS52B Cooling (50Hz 230V) Combination Units Power supply Comp. OFM IFM Hz Volts Min. Max. MCA MFA RLA W FLA W FLA D Heating (50Hz 230V) Combination Units Power supply Comp. OFM IFM Hz Volts Min. Max. MCA MFA RLA W FLA W FLA D04097 SYMBOLS Nominal current = MCA : Min. Circuit Amps (A) MFA : Max. Fuse Amps (A) RLA : Rated Load Amps (A) OFM : Outdoor Fan Motor IFM : Indoor Fan Motor FLA : Full Load Amps (A) W : Fan Motor Rated Output (W) NOTES. RLA is based on the following conditions: Power supply: 50Hz 230V Cooling Indoor temp.: 20 CDB Outdoor temp. : 35 CDB Heating Indoor temp.: 27 CDB/9.0 CWB Outdoor temp.: 7 CDB/6 CWB 2. Maximum allowable voltage unbalance between phases is 2% 3. Select wire size based on the larger value of MCA. 4. Instead of fuse, use circuit breaker 4 Split - Sky Air Outdoor Units
7 Multi Application R-40A MXS40,52,68,80B 2 Specifications ELECTRICAL DATA 2 4MXS68B Cooling (50Hz 230V) Combination Units Power supply Comp. OFM IFM Hz Volts Min. Max. MCA MFA RLA W FLA W FLA D040099# Heating (50Hz 230V) Combination Units Power supply Comp. OFM IFM Hz Volts Min. Max. MCA MFA RLA W FLA W FLA D040099#2 SYMBOLS Nominal current = MCA : Min. Circuit Amps (A) MFA : Max. Fuse Amps (A) RLA : Rated Load Amps (A) OFM : Outdoor Fan Motor IFM : Indoor Fan Motor FLA : Full Load Amps (A) W : Fan Motor Rated Output NOTES. RLA is based on the following conditions: Power supply: 50Hz 230V Cooling Indoor temp.: 20 CDB Outdoor temp. : 35 CDB Heating Indoor temp.: 27 CDB/9.0 CWB Outdoor temp.: 7 CDB/6 CWB 2. Maximum allowable voltage unbalance between phases is 2% 3. Select wire size based on the larger value of MCA. 4. Instead of fuse, use circuit breaker Split - Sky Air Outdoor Units 5
8 Multi Application R-40A MXS40,52,68,80B 2 Specifications 2 ELECTRICAL DATA 4MXS80B Cooling (50Hz 230V) Combination Units Power supply Comp. OFM IFM Hz Volts Min. Max. MCA MFA RLA W FLA W FLA D040096# SYMBOLS Nominal current = MCA : Min. Circuit Amps (A) MFA : Max. Fuse Amps (A) RLA : Rated Load Amps (A) OFM : Outdoor Fan Motor IFM : Indoor Fan Motor FLA : Full Load Amps (A) W : Fan Motor Rated Output NOTES. RLA is based on the following conditions: Power supply: 50Hz 230V Cooling Indoor temp.: 20 CDB Outdoor temp. : 35 CDB Heating Indoor temp.: 27 CDB/9.0 CWB Outdoor temp.: 7 CDB/6 CWB 2. Maximum allowable voltage unbalance between phases is 2% 3. Select wire size based on the larger value of MCA. 4. Instead of fuse, use circuit breaker 6 Split - Sky Air Outdoor Units
9 Multi Application R-40A MXS40,52,68,80B 2 Specifications ELECTRICAL DATA 2 4MXS80B Heating (50Hz 230V) Combination Units Power supply Comp. OFM IFM Hz Volts Min. Max. MCA MFA RLA W FLA W FLA D040096#2 SYMBOLS Nominal current = MCA : Min. Circuit Amps (A) MFA : Max. Fuse Amps (A) RLA : Rated Load Amps (A) OFM : Outdoor Fan Motor IFM : Indoor Fan Motor FLA : Full Load Amps (A) W : Fan Motor Rated Output NOTES. RLA is based on the following conditions: Power supply: 50Hz 230V Cooling Indoor temp.: 20 CDB Outdoor temp. : 35 CDB Heating Indoor temp.: 27 CDB/9.0 CWB Outdoor temp.: 7 CDB/6 CWB 2. Maximum allowable voltage unbalance between phases is 2% 3. Select wire size based on the larger value of MCA. 4. Instead of fuse, use circuit breaker Split - Sky Air Outdoor Units 7
10 Multi Application R-40A MXS40,52,68,80B 3 Combination table 3 2MXS40B Cooling [50Hz 230V] Combination (Capacity) Outdoor air temp. CDB Indoor air temp.: CWB 4 C 6 C 8 C 9 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw Heating (50Hz 230V) Combination (Capacity) Indoor air temp.: CWB Outdoor air temp. CDB -0 C -5 C 0 C 6 C 0 C TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw D SYMBOLS TC: Total capacity (kw) PI: Power input (kw) NOTES. Capacities are based on the following conditions: Corresponding refrigerant piping length: Level difference: 7.5 m 0 m 8 Split - Sky Air Outdoor Units
11 Multi Application R-40A MXS40,52,68,80B 3 Combination table 3MXS52B Cooling [50Hz 230V] 3 Combination of indoor unit Capacity of each indoor unit (input current without limit) Each capacity (kw) Total capacity (kw) Total input (W) Total current (A) Power factor % A Room B Room C Room D Room Rating (Min. max.) Rating (Min. max.) Rating (Min. max.) Rating D039603# Heating (50Hz 230V) Combination of indoor unit Capacity of each indoor unit (input current without limit) Each capacity (kw) Total capacity (kw) Total input (W) Total current (A) Power factor % A Room B Room C Room D Room Rating (Min. max.) Rating (Min. max.) Rating (Min. max.) Rating D039603#2 TC PI SYMBOLS : Total cooling capacity (A) : Power input (A) NOTES Cooling capacity is based on 27 CDB / 9 CWB (indoor temperature), 35 CDB (outdoor temperature). 2 The total ability of connected a indoor unit is up to 0.0 kw 3 It is impossible to connect the indoor unit for one room only. Split - Sky Air Outdoor Units 9
12 Multi Application R-40A MXS40,52,68,80B 3 Combination table 3 4MXS68B Cooling [50Hz 230V] Combination of indoor unit Capacity of each indoor unit (input current without limit) Each capacity (kw) Total capacity (kw) Total input (W) Total current (A) Power factor % A Room B Room C Room D Room Rating (Min. max.) Rating (Min. max.) Rating (Min. max.) Rating , , , , D039604#2 Heating (50Hz 230V) Combination of indoor unit Capacity of each indoor unit (input current without limit) Each capacity (kw) Total capacity (kw) Total input (W) Total current (A) Power factor % A Room B Room C Room D Room Rating (Min. max.) Rating (Min. max.) Rating (Min. max.) Rating D039604#3 TC PI SYMBOLS : Total cooling capacity (A) : Power input (A) NOTES Cooling capacity is based on 27 CDB / 9 CWB (indoor temperature), 35 CDB (outdoor temperature). 2 The total ability of connected a indoor unit is up to 0.0 kw 3 It is impossible to connect the indoor unit for one room only. 0 Split - Sky Air Outdoor Units
13 Multi Application R-40A MXS40,52,68,80B 3 Combination table 4MXS80B Cooling [50Hz 230V] 3 Combination of indoor unit Capacity of each indoor unit (input current without limit) Each capacity (kw) Total capacity (kw) Total input (W) Total current (A) Power factor % A Room B Room C Room D Room Rating (Min. max.) Rating (Min. max.) Rating (Min. max.) Rating D039605#2 TC PI SYMBOLS : Total cooling capacity (A) : Power input (A) NOTES Cooling capacity is based on 27 CDB / 9 CWB (indoor temperature), 35 CDB (outdoor temperature). 2 The total ability of connected a indoor unit is up to 0.0 kw 3 It is impossible to connect the indoor unit for one room only. Split - Sky Air Outdoor Units
14 Multi Application R-40A MXS40,52,68,80B 3 Combination table 3 4MXS80B Heating (50Hz 230V) Combination of indoor unit Capacity of each indoor unit (input current without limit) Each capacity (kw) Total capacity (kw) Total input (W) Total current (A) Power factor % A Room B Room C Room D Room Rating (Min. max.) Rating (Min. max.) Rating (Min. max.) Rating D039605#3 TC PI SYMBOLS : Total cooling capacity (A) : Power input (A) NOTES Cooling capacity is based on 27 CDB / 9 CWB (indoor temperature), 35 CDB (outdoor temperature). 2 The total ability of connected a indoor unit is up to 0.0 kw 3 It is impossible to connect the indoor unit for one room only. 2 Split - Sky Air Outdoor Units
15 Multi Application R-40A MXS40,52,68,80B 4 Dimensional drawings 2MXS40B Drain outlet Drainage fitting may be connected. (I.D. J5.9 hose for connection) 4-cuts for anchor bolts (M8 or M0) unit (mm) 4 Interconnecting piping and wiring inlet Outdoor air thermistor Brand name label 2-Terminal strip with earth terminal <room A> Liquid stop valve (J 6.4 Cut) Gas stop valve (J 9.5 Cut) Minimum space for air passage Wall height on air outlet side = less than 200 Name plate Service port In case of removing stop valve cover <room B> Liquid stop valve (J 6.4 Cut) Gas stop valve (J 9.5 Cut) 3D MXS52B 4-cuts for anchor bolts (M8 or M0) <room A> Gas pipe (J9.5 single union) Liquid pipe (J6.4 single union) <room B> Gas pipe (J9.5 single union) Liquid pipe (J6.4 single union) Minimum space for air passage Wall height on air outlet side = less than 200 unit (mm) Drain outlet Drainage fitting may be connected. (I.D. J5.9 hose for connection) <room C> Gas pipe (J2.7 single union) Liquid pipe (J6.4 single union) 5-Terminal strip with earth terminal Name plate Interconnecting piping and wiring inlet Outdoor air thermistor A Liquid J Gas J Liquid stop valve Service port Gas stop valve 3D03473B Split - Sky Air Outdoor Units 3
16 Multi Application R-40A MXS40,52,68,80B 4 Dimensional drawings 4 4MXS68B 4-cuts for anchor bolts (M8 or M0) <room A> Gas pipe (J9.5 single union) Liquid pipe (J6.4 single union) <room B> Gas pipe (J9.5 single union) Liquid pipe (J6.4 single union) Minimum space for air passage Wall height on air outlet side = less than 200 unit (mm) Drain outlet Drainage fitting may be connected. (I.D. J5.9 hose for connection) Terminal strip with earth terminal <room C> Gas pipe (J2.7 single union) Liquid pipe (J6.4 single union) <room D> Gas pipe (J5.9 single union) Liquid pipe (J6.4 single union) Name plate Interconnecting piping and wiring inlet Outdoor air thermistor A Liquid J Gas J J Liquid stop valve Service port Gas stop valve 3D034732B 4MXS80B Minimum space for air passage Wall height on air outlet side = less than 200 unit (mm) 4-cuts for anchor bolts Drain outlet Drainage fitting may be connected. (I.D. J5.9 hose for connection) 5-Terminal strip with earth terminal Gas stop valve Liquid stop valve Name plate <room A> Gas pipe (J9.5 single union) Liquid pipe (J6.4 single union) <room B> Gas pipe (J9.5 single union) Liquid pipe (J6.4 single union) A Liquid J J Gas J J Interconnecting piping and wiring inlet Outdoor air thermistor <room C> Gas pipe (J2.7 single union) Liquid pipe (J6.4 single union) <room D> Gas pipe (J5.9 single union) Liquid pipe (J6.4 single union) 3D034733B 4 Split - Sky Air Outdoor Units
17 Multi Application R-40A MXS40,52,68,80B 5 Operation range 2MXS40B 5 Cooling Heating Outdoor temperature ( CDB) Pull-down period Outdoor temperature ( CDB) Indoor temp. ( CWB) Notes: The graphs are based on the following conditions: d Equivalent piping length 5m d Level difference 0m d Air flow rate Hi speed Indoor temp. ( CDB) 3D MXS52B 4MXS68B Cooling Heating Outdoor temperature ( CDB) Pull-down period Outdoor temperature ( CDB) Indoor temp. ( CWB) Indoor temp. ( CDB) Notes: The graphs are based on the following conditions: d Equivalent piping length 5m d Level difference 0m d Air flow rate Hi speed 3D034956B Split - Sky Air Outdoor Units 5
18 Multi Application R-40A MXS40,52,68,80B 5 Operation range 5 4MXS80B Cooling Heating Outdoor temperature ( CDB) Pull-down period Outdoor temperature ( CDB) Indoor temp. ( CWB) Indoor temp. ( CDB) Notes: The graphs are based on the following conditions: d Equivalent piping length 5m d Level difference 0m d Air flow rate Hi speed 3D034958B 6 Split - Sky Air Outdoor Units
19 Multi Application R-40A MXS40,52,68,80B 6 Piping diagrams 2MXS40B Outdoor unit 6 Branch pipe Heat exchanger Outdoor temperature thermistor Liquid receiver Distributor Liquid receiver Motor operated valve Motor operated valve Liquid pipe thermistor (DLA) Liquid pipe thermistor (DLA) Liquid line stop valve Liquid line stop valve Room A (6.4 CuT) Room B (6.4 CuT) Field piping liquid Heat exchanger thermistor(de) Fan motor Propeller fan Reversing solenoid valve Branch pipe Muffler Muffler Gas pipe thermistor (DGA) Gas pipe thermistor (DGB) Gas line stop valve Gas line stop valve Room A (9.5 CuT) Room B (9.5 CuT) Field piping gas Discharge pipe thermistor (DO) Muffler Muffler Refrigerant flow Cooling Heating Compressor Accumulator 3D MXS52B Outdoor unit Heat exchanger Outdoor temperature thermistor Header Motor operated valve Heat exchanger thermistor(de) DC fan motor Distributor Capillary tube Defrost solenoid valve Liquid line stop valve Thermistor (DLA) Motor operated valve Thermistor (DLB) Motor operated valve Thermistor (DLC) Room A (6.4 CuT) Room A (6.4 CuT) Room A (6.4 CuT) Field piping liquid Propeller fan Reversing solenoid valve Header Gas pipe thermistor (DGA) Room A (9.5 CuT) Refrigerant flow Cooling Heating Muffler Discharge pipe thermistor (DO) Compressor Accumulator Accumulator Gas line stop valve Gas pipe thermistor (DGB) Gas pipe thermistor (DGC) Room B (9.5 CuT) Room C (9.5 CuT) Field piping gas 3D03452A Split - Sky Air Outdoor Units 7
20 Multi Application R-40A MXS40,52,68,80B 6 Piping diagrams 6 4MXS68B Outdoor unit Header Heat exchanger thermistor(de) DC fan motor Propeller fan Heat exchanger Outdoor temperature thermistor Distributor Capillary tube Defrost solenoid valve Header Liquid line stop valve Motor operated valve Thermistor (DLA) Motor operated valve Thermistor (DLB) Motor operated valve Thermistor (DLC) Motor operated valve Thermistor (DLD) Room A (6.4 CuT) Room B (6.4 CuT) Room C (6.4 CuT) Room D (6.4 CuT) Field piping liquid Refrigerant flow Cooling Heating Reversing solenoid valve Muffler Discharge pipe thermistor (DO) Compressor Accumulator Accumulator Header Gas line stop valve Gas pipe thermistor (DGA) Gas pipe thermistor (DGB) Gas pipe thermistor (DGC) Gas pipe thermistor (DGD) Room A (9.5 CuT) Room B (9.5 CuT) Room C (2.7 CuT) Room D (2.7 CuT) Field piping gas 3D0345A 4MXS80B Outdoor unit Header Heat exchanger thermistor(de) DC fan motor Heat exchanger Outdoor temperature thermistor Capillary tube Distributor Solenoid valve Liquid line stop valve Header Motor operated valve Thermistor (DLA) Motor operated valve Thermistor (DLB) Motor operated valve Thermistor (DLC) Motor operated valve Thermistor (DLD) Room A (6.4 CuT) Room B (6.4 CuT) Room C (6.4 CuT) Room D (6.4 CuT) Field piping liquid Propeller fan Refrigerant flow Cooling Heating Muffler Discharge pipe thermistor Compressor 4-way valve Accumulator Accumulator Gas line stop valve Header Gas pipe thermistor (DGA) Gas pipe thermistor (DGB) Gas pipe thermistor (DGC) Gas pipe thermistor (DGD) Room A (9.5 CuT) Room B (2.7 CuT) Room C (5.9 CuT) Room D (5.9 CuT) Field piping gas 3D034480B 8 Split - Sky Air Outdoor Units
21 Multi Application R-40A MXS40,52,68,80B 7 Wiring diagrams 2MXS40B 7 Indoor Room A Room B Power supply 50Hz V 60Hz V g Field wiring Outdoor (Room A) (Room A) (Room B) (Room B) Liquid pipe Gas pipe (outdoor) (discharge) (condenser) (Room A) (Room B) C5 C8, SHC CT DB, DB2 FU, F2U L L LR MC MF MRCW, MRM0, MRM20 N : Capacitor : Current transformer : Diode bridge : Fuse : Live : Coil : Reactor : Compressor motor : Fan motor : Magnetic relay : Neutral OIS3 : Solid state relay PCB, PCB2 : Printed circuit board QL : Overload protector RT R8T : Thermistor SA : Surge arrester TFU : Thermal fuse TRM : Transistor module V, V2, V3 : Varistor XM, X2M : Terminal strip YE Y2E : Electronic expansion valve coil YR : Reversing solenoide valve coil ZC : Ferrite core R : Protective earth S0 S2, S20, S2, S30 S40, S45, S70, S80, S90 S92, HL, HL2, HN, HN2, HR3, HR4, AC, AC2, HC3, HC4, E, X30A : Connector 3D MXS52B g Field wiring To indoor unit Room A Room B Room C Power supply 50Hz V 60Hz V (outdoor) (discharge) (Room A) (Room C) (Room A) (Room C) (condenser) (Room B) (Room B) Gas pipe Liquid pipe ZC Z3C XM X4M YE Y3E V2 V5 FU, F2U, FU20: Fuse HE, HL, HN E, AC, AC2 H, H2, L, L2 : Connector MRM0, MRM20 MRB, MRD, MRC/W : Ferrite core : Terminal strip : Electronic expansion valve coil : Varistor : Magnetic relay RT R2T S2 S02 HP H5P L N SW S2W S3W S4W S5W SA : Thermistor : Pilot lamp : Live : Neutral : Forced operation on/off switch (SW) : Forced operation mode select sw (SW2) : Wiring error check SW (SW3) : Priority room setting SW (SW4) : Night quiet mode setting SW (SW5) : Surge arrester YR YS PCB DB MC MF LR QL CT : Reversing solenoide valve coil : Defrost solenoid valve : Printed circuit board : Diode bridge : Compressor motor : Fan motor : Reactor : Overload protector : Current transformer 3D03434C Split - Sky Air Outdoor Units 9
22 Multi Application R-40A MXS40,52,68,80B 7 Wiring diagrams 7 4MXS68B 4MXS80B g Field wiring To indoor unit Room A Room B Room C Room D Power supply 50Hz V 60Hz V (discharge) (Room A) (Room C) (outdoor) (Room A) (Room C) (condenser) (Room B) (Room (Room B) (Room D) D) Gas pipe Liquid pipe ZC Z3C XM X5M YE Y4E V2 V5 FU, F2U, FU20 : Fuse HE, HL, HN E, AC, AC2 H, H2, L, L2 : Connector MRM0, MRM20 MRB, MRD MRC/W : Ferrite core : Terminal strip : Electronic expansion valve coil : Varistor : Magnetic relay RT R2T S2 S02 HP H5P L N SW S2W S3W S4W S5W SA : Thermistor : Connector : Pilot lamp : Live : Neutral : Forced operation on/off switch (SW) : Select SW (SW2) : Wiring error check SW (SW3) : Priority room setting SW (SW4) : Night quiet mode setting SW (SW5) : Surge arrester YR YS PCB DB MC MF LR QL CT : Reversing solenoide valve coil : Defrost solenoid valve : Printed circuit board : Diode bridge : Compressor motor : Fan motor : Reactor : Overload protector : Current transformer 3D03432C 20 Split - Sky Air Outdoor Units
23 Multi Application R-40A MXS40,52,68,80B 8 Sound level 8- Sound level data Heat pump Model 230V, 50Hz Cooling/Heating Sound pressure level Measuring location Sound power level (cooling/heating) 8 8- H L 2MXS40B 47/48 43/44 60/6 3MXS52B 46/47 */* 59/60 4MXS68B 48/49 */* 6/62 4MXS80B 48/49 */* 6/62 * This information was not available at the time of publication. 8-2 Sound pressure spectrum 2MXS40B (Cooling) 2MXS40B (Heating) Octave band sound pressure level db:(0db = µ bar) Octave band sound pressure level db:(0db = µ bar) approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise 3D D Octave band center frequency (Hz) Octave band center frequency (Hz) Legend NOTES Operation sound is measured in an anechoic chamber. 2 Operation sound level differs with operation and ambient conditions. 3 Reference acoustic pressure 0dB = 20µPa 50/60Hz, / V Split - Sky Air Outdoor Units 2
24 Multi Application R-40A MXS40,52,68,80B 8 Sound level Sound pressure spectrum Heat pump 3MXS52B (Cooling) 3MXS52B (Heating) Octave band sound pressure level db:(0db = µ bar) Octave band sound pressure level db:(0db = µ bar) approximate threshold hearing for approximate threshold hearing continuous noise for continuous noise 3D034806A Octave band center frequency (Hz) 3D034806A Octave band center frequency (Hz) 4MXS68B (Cooling) 4MXS68B (Heating) Octave band sound pressure level db:(0db = µ bar) Octave band sound pressure level db:(0db = µ bar) approximate threshold hearing approximate threshold hearing for continuous noise for continuous noise 3D034807A 3D034807A Octave band center frequency (Hz) Octave band center frequency (Hz) Legend 50/60Hz, / V NOTES Operation sound is measured in an anechoic chamber. 2 Operation sound level differs with operation and ambient conditions. 3 Reference acoustic pressure 0dB = 20µPa 22 Split - Sky Air Outdoor Units
25 Multi Application R-40A MXS40,52,68,80B 8 Sound level 8-2 Sound pressure spectrum Heat pump 4MXS80B (Cooling) 4MXS80B (Heating) Octave band sound pressure level db:(0db = µ bar) Octave band sound pressure level db:(0db = µ bar) approximate threshold hearing for approximate threshold hearing continuous noise for continuous noise 3D034808A Octave band center frequency (Hz) 3D034808A Octave band center frequency (Hz) Legend 50/60Hz, / V NOTES Operation sound is measured in an anechoic chamber. 2 Operation sound level differs with operation and ambient conditions. 3 Reference acoustic pressure 0dB = 20µPa Split - Sky Air Outdoor Units 23
26 Multi Application R-40A MXS40,52,68,80B 9 Accessories Standard accessories 2MXS40B Accessories supplied with the outdoor unit: Screw bag Installation manual There are two screws for the wire retainer inside. 3MXS52/4MXS68B Accessories supplied with the outdoor unit: (B) Drain plug (A) Installation manual (C) Reducer assy There is on the bottom packing case. (D) Screw bag For fixing electrical wire anchor bands There is on the bottom packing case. There is on the bottom packing case. 4MXS80B (A) Drain socket (B) Drain cap Accessories supplied with the outdoor unit: (C) Drain receiver 2 3 (D) Reducer assy (E) Screw bag For fixing electrical wire anchor bands (F) Installation manual 9-2 Optional accessories MXS-B 2MXS40BVMB 3MXS52BVMB 4MXS68BVMB Air direction adjustment grille KPW937A4 KPW945A4 4MXS80BVMB 24 Split - Sky Air Outdoor Units
27 Multi Application R-40A MXS40,52,68,80B 0 Installation 2MXS40B 0 Indoor/outdoor unit installation drawings Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe s cut line. Caulk pipe hole gap with putty. Wrap the insulation pipe with tape from bottom to top. Allow30cmofwork space below the ceiling surface. If there is the danger of the unit falling or overturning, fix the unit with foundation bolts, or with wire or other means. Allow space for piping and electrical servicing. If the location does not have good drainage, place the unit on a level mounting base (or a plastic pedestal). Install the outdoor unit in a level position. Failure to do so may result in water leakage or accumulation. 30 cm from wall Service lid Use the optional outdoor vibration damping rubber if the vibration is too strong. 3.5cm Foot bolt-hole centres 47cm Foot bolt-hole centres Also insulate the connection on the outdoor unit. Clamping material Insulation tube Level mounting base (available separately) Tape Service lid Use tape or insulating material on all connections to prevent air from getting in between the copper piping and the insulation tube. Be sure to do this if the outdoor unit is installed above. Split - Sky Air Outdoor Units 25
28 Multi Application R-40A MXS40,52,68,80B 0 Installation 0 3MXS52B 4MXS68B Indoor/outdoor unit installation drawings Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe s cut line. Caulk pipe hole gap with putty. Allow30cmofwork space below the ceiling surface. Wrap the insulation pipe with tape from bottom to top. If there is the danger of the unit falling or overturning, fix the unit with foundation bolts, or with wire or other means. 30 cm from wall Allow space for piping and electrical servicing. If the location does not have good drainage, place the unit on a level mounting base (or a plastic pedestal). Install the outdoor unit in a level position. Failure to do so may result in water leakage or accumulation. 33cm Foot bolt-hole centres 58cm Foot bolt-hole centres Also insulate the connection on the outdoor unit. Level mounting base (available separately) Clamping material Insulation tube Tape Service lid Use tape or insulating material on all connections to prevent air from getting in between the copper piping and the insulation tube. Be sure to do this if the outdoor unit is installed above. 26 Split - Sky Air Outdoor Units
29 Multi Application R-40A MXS40,52,68,80B 0 Installation 4MXS80B 0 Indoor/outdoor unit installation drawings Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe s cut line. Caulk pipe hole gap with putty. Allow30cmofwork space below the ceiling surface. Wrap the insulation pipe with tape from bottom to top. If there is the danger of the unit falling or overturning, fix the unit with foundation bolts, or with wire or other means. 30 cm from wall Allow space for piping and electrical servicing. If the location does not have good drainage, place the unit on a level mounting base (or a plastic pedestal). Install the outdoor unit in a level position. Failure to do so may result in water leakage or accumulation. Foot bolt-hole centres 62cm Level mounting base (available separately) 35cm Foot bolt-hole centres Also insulate the connection on the outdoor unit. Clamping material Insulation tube Tape Service lid Use tape or insulating material on all connections to prevent air from getting in between the copper piping and the insulation tube. Be sure to do this if the outdoor unit is installed above. Split - Sky Air Outdoor Units 27
technical data air conditioning systems RXG-C Wall Mounted, Inverter Controlled Unit Split Sky Air
technical data RXG-C Wall Mounted, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human
More informationtechnical data air conditioning systems RKS-C RKS-B Pair Application, Inverter Controlled Unit Split Sky Air
technical data RKS-C RKS-B Pair Application, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help
More informationtechnical data air conditioning systems FCQ-D MXS-E 4-way Blow Ceiling Mounted Cassette (edited) Split Sky Air
technical data FCQ-D MXS-E 4-way Blow Ceiling Mounted Cassette Multi (950mm Split Heat x 950mm) Pump (edited) air conditioning systems Split Sky Air Outdoor Units R40A MXS-DAVMB_E2VB_E7VB Features V i
More informationOutdoor Units R-410A ARX-GV1B
Outdoor Units R-40A ARX-GVB t A i n y U k BS r o AV t o0g i d- lt4x pur- SRAO 2 Specifications Outdoor Units R-40A ARX-GVB 2- NOMINAL CAPACITY AND NOMINAL INPUT ARX20GVB ARX25GVB ARX5GVB For combination
More informationtechnical data air conditioning systems MA-GZ7 Multi Model Application Split Sky Air
technical data MA-GZ7 Multi Model Application air conditioning systems Split Sky Air Split - Sky Air ISO14001 assures an effective environmental management system in order to help protect human health
More informationSplit-Sky Air RMX-JZ Super Multi Plus
TECHNICAL DATA Split-Sky Air RMX-JZ Super Multi Plus Split Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the environment from the potential
More informationtechnical data air conditioning systems RYP-L7/B7 Pair Application Split Sky Air
technical data RYP-L7/B7 Pair Application air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the
More informationSplit-Sky Air FDYP-B7 Concealed Ceiling Unit
TECHNICAL DATA Split-Sky Air FDYP-B7 Concealed Ceiling Unit Split Sky Air ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the
More informationSplit-Sky Air FAYP-B Wall Mounted Unit
TECHNICAL DATA Split-Sky Air FAYP-B Wall Mounted Unit Split Sky Air ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential
More informationSplit-Sky Air RP-B7 Twin/Triple/Double Twin Application
TECHNICAL DATA Split-Sky Air RP-B7 Twin/Triple/Double Twin Application Split Sky Air ISO14001 assures an effective environmental management system in order to help protect human health and the environment
More informationtechnical data air conditioning systems RQ-B7 Pair/Twin/Triple/Double Twin Application Split Sky Air
technical data RQ-B7 Pair/Twin/Triple/Double Twin Application air conditioning systems Split Sky Air Split - Sky Air ISO14001 assures an effective environmental management system in order to help protect
More informationtechnical data air conditioning systems Round Flow Cassette FXFQ-P9VEB
technical data Round Flow Cassette FXFQ-P9VEB air conditioning systems technical data Round Flow Cassette FXFQ-P9VEB air conditioning systems TABLE OF CONTENTS FXFQ-P9VEB 1 Specifications.......................................................
More informationtechnical data Systems RSX(Y)P-K7W1 Inverter cooling only / heat pump series
technical data Systems RSX(Y)P-K7W1 Inverter cooling only / heat pump series Inverter cooling only / heat pump series RSX(Y)P5,8,10K7W1 RSX(Y)P-K7W1 1 Inverter cooling only / heat pump series 1 1 Specifications
More informationEEDEN technical data. air conditioning systems FDQ-B8V3B9. Split Sky Air
EEDEN08-00 technical data FDQ-B8V3B9 air conditioning systems Split Sky Air Split - Sky Air Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led
More information1 Features. Indoor Units CONCEALED CEILING UNIT FXSQ-P7VEB. VRV Systems Indoor Units
t i t l r - I Features s e Cs m B ne d E Ue V s 7 ya P os e oc Q dvn S nr ox VF C Reduction of power consumption of 20% (compared to FXSQ-M8 series) through use of new DC fan Improved comfort thanks to
More information19 Series. High-Efficiency Wall-Mounted Ductless systems. Performance: Up to 19 SEER 12.5 EER 9.0 HSPF. Product Features
19 Series High-Efficiency Wall-Mounted Ductless systems Performance: Up to 19 SEER 12.5 EER 9.0 HSPF Product Features Inverter Compressor 208/230/1 Power Supply Cooling Range: -4-115 F (with optional wind
More informationAir Conditioning. Technical Data EEDEN RXZ-N
Air Conditioning Technical Data EEDEN14-100 RXZ-N TABLE OF CONTENTS RXZ-N 1 Features............................................................. 2 2 Specifications.......................................................
More informationAir Conditioners. Technical Data. Individual branch selector for VRV heat recovery (Individual BS box) EEDEN BSVQ P8
Air Conditioners Technical Data Individual branch selector for VRV heat recovery (Individual BS box) EEDEN11-200 BSVQ100-250P8 Air Conditioners Technical Data Individual branch selector for VRV heat recovery
More informationR410A TECHNICAL MANUAL. Inverter Single Split Series Air Conditioner. FTK-J, FTXN-J Series. Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2
R410A TECHNICAL MANUAL Inverter Single Split Series Air Conditioner FTK-J, FTXN-J Series Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2 Table of Contents Table of Contents Nomenclature...1 Indoor...1 Outdoor...1
More informationtechnical data air conditioning systems 600x600 4-Way Blow Ceiling Mounted Cassette FXZQ-M9V1B
technical data 600x600 4-Way Blow Ceiling Mounted Cassette FXZQ-M9V1B air conditioning systems technical data 600x600 4-Way Blow Ceiling Mounted Cassette FXZQ-M9V1B air conditioning systems Indoor Units
More informationAir Conditioning. Technical Data. Wall mounted unit EEDEN FTX-GV
Air Conditioning Technical Data Wall mounted unit EEDEN15-100 FTX-GV TABLE OF CONTENTS FTX-GV 1 Features............................................................. 2 2 Specifications.......................................................
More informationAir Conditioners Technical Data
Air Conditioners Technical Data O u t d o o r u n i t E E D E N 2-0 0 RXG-K Outdoor Unit Pair application RXG-K TABLE OF CONTENTS RXG-K Features.............................................................
More informationHeating Nom. dba Cooling Nom. dba Night quiet mode Level 1 dba Item Tie-wraps Tie-wraps Tie-wraps Tie-wraps
RZQG71L8Y1B RZQG100L8Y1B RZQG125L8Y1B RZQG140L7Y1B Sound pressure level Heating Nom. dba 50 52 53 53 Cooling Nom. dba 48 50 51 52 Night quiet mode Level 1 dba 43 45 45 45 Standard Accessories Item Tie-wraps
More informationSplit. Air Conditioning Technical Data FTXC-A > FTXC25AV1B > FTXC35AV1B > FTXC50AV1B > FTXC60AV1B
Split Air Conditioning Technical Data FTXC-A > FTXC25AV1B > FTXC35AV1B > FTXC50AV1B > FTXC60AV1B Indoor Unit FTXC-A TABLE OF CONTENTS FTXC-A 1 Features.............................................................
More informationAir Conditioning. Technical Data EEDEN RXZ-N
Air Conditioning Technical Data EEDEN15-100 RXZ-N Outdoor Unit RXZ-N TABLE OF CONTENTS RXZ-N 1 Features............................................................. 2 2 Specifications.......................................................
More informationAir Conditioning Technical Data RZQG-L(8)Y1
Air Conditioning Technical Data RZQG-L(8)Y TABLE OF CONTENTS RZQG-L(8)Y Features............................................................. 2 2 Specifications.......................................................
More informationtechnical data Systems FXMQ-MVE Conceiled ceiling unit (large)
technical data Systems FXMQ-MVE Conceiled ceiling unit (large) FXMQ-MVE 11 Concealed ceiling unit (large) 11 1 Features...2 2 Specifications Technical specifications...3 Electrical specifications...4 Safety
More informationAir Conditioning. Technical Data EEDEN RXJ-L
ir Conditioning Technical Data EEDEN5-0 RXJ-L Outdoor Unit RXJ-L TLE OF CONTENTS RXJ-L Features............................................................. Specifications.......................................................
More informationCeiling Concealed Series FDMRN-AV1K. 50Hz. Preliminary
Ceiling Concealed Series FDMRN-AV1K 50Hz Nomenclature Main Benefits Engineering and Physical Data Electrical Data Capacity Tables Outline and Dimensions Electrical Connection Refrigerant Piping Nomenclature
More informationtechnical data air conditioning systems FH(Y)C-BZ7/FHYCP-B7 4-Way Blow Ceiling Mounted Cassette Split Sky Air
technical data FH(Y)C-BZ7/FHYCP-B7 4-Way Blow Ceiling Mounted Cassette air conditioning systems Split Sky Air Split - Sky Air ISO14001 assures an effective environmental management system in order to help
More informationAir Conditioning Technical Data FXDQ-A3 > FXDQ15A3VEB > FXDQ20A3VEB > FXDQ25A3VEB > FXDQ32A3VEB > FXDQ40A3VEB > FXDQ50A3VEB > FXDQ63A3VEB
Air Conditioning Technical Data FXDQ-A3 > FXDQ15A3VEB > FXDQA3VEB > FXDQ25A3VEB > FXDQ32A3VEB > FXDQ40A3VEB > FXDQ50A3VEB > FXDQ63A3VEB TABLE OF CONTENTS FXDQ-A3 1 Features.............................................................
More information1 Features. Outdoor Units R-410A RZQ71-140C7V1B. Split Sky Air Outdoor Units
i r -t i l t - Outdoor Units R-40A RZQ7-40C7VB Features V 7n y CU k 0 S 4 oa o 0 d 7 4Q puz RO S Outdoor units for pair, twin, triple, double twin application The Sky Air Inverter is developed for use
More informationAir Conditioning Technical Data RZQSG-L3/9V1
Air Conditioning Technical Data RZQSG-L/9V1 Outdoor Unit RZQSG-L/9V1 TABLE OF CONTENTS RZQSG-L/9V1 1 Features............................................................. 2 2 Specifications.......................................................
More informationTechnical Service Manual
Technical Service Manual 60 Hz Low/Mid Pressure Duct Units 7 48 MBH Units 96 MBH Unit June 2009 VRF-SVM21A-EN Low and Mid Pressure Duct Units 1. Features......... 2 2. Specifications......... 3 3. Dimensions.........
More informationSPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE
SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE Indoor unit ASYA24LCC ASYA24LCC ASYA24LCC Outdoor unit AOYR24LCC AOYR24LCD AOYR24LCL CONTENTS SPECIFICATIONS..................1 DIMENSIONS.....................
More informationVRF Indoor Unit 50Hz. Type: Wall Mounted M Series Wall Mounted S Series
VRF Indoor Unit 50Hz Type: Wall Mounted M Series Wall Mounted S Series Contents 01 Wall Mounted M Series 20 Wall Mounted S Series MCAC-VTSM-2016-05 Wall Mounted M Series Wall Mounted M Series 1. Features...
More information1. Features Specifications Dimensions Service Spaces Piping Diagrams Wiring Diagrams...
MCAC-VTSM-2013-08 1. Features... 264 2. Specifications... 265 3. Dimensions... 268 4. Service Spaces... 272 5. Piping Diagrams... 273 6. Wiring Diagrams... 274 7. Capacity Tables... 276 8. Electrical Characteristics...
More informationCompact Four-way Cassette Type
1. Features... 34 2. Specifications... 35 3. Dimensions... 37 4. Service Spaces... 38 5. Piping Diagrams (EXV beside)... 39 6. Wiring Diagrams... 40 7. Capacity Tables... 41 8. Electrical Characteristics...
More informationPL Split Indoor Units FTKD25GVM, FTKD35GVM FTKD25GVM4, FTKD35GVM4. Split Outdoor Units RKD50GVM RKD60GVM RKD50GVM4 RKD60GVM4
Split Indoor Units FTKD25GVM, FTKD35GVM FTKD25GVM4, FTKD35GVM4 Split Outdoor Units RKD50GVM RKD60GVM RKD50GVM4 RKD60GVM4 Ceiling Consealed Split - OYL Malaysian Products (for Midle East) FDM30JEVLK, FDYM30JEVLK,
More informationOil Cooler AKZ328-D142 PL
Oil Cooler PL-1009-15 1 2 Parts Parts Name Drwg. Parts Model & Specifi cation A1 A 1250093 SWING COMPRESSOR 1YC23HXD 1 M2C A2 0401393 RUBBER BUSH/ LEAD WIRE W443132-2 1 A4 390204 NUT WITH WASHER R4911377-1
More informationService manual MIV V4+ Indoor units
Service manual MIV V4+ Indoor units Floor Standing MVF22A-VA1 MVF28A-VA1 MVF36A-VA1 MV5A-VA1 MVF56A-VA1 MVF71A-VA1 MVF80A-VA1 MVB22A-VA1 MVB28A-VA1 MVB36A-VA1 MVB45A-VA1 MVB56A-VA1 MVB71A-VA1 MVB80A-VA1
More informationSPLIT DUCTED UNIT SCA300C / SCA300E TECHNICAL SELECTION DATA SPECIFICATION SUMMARY UNIT FEATURES CONTROL OPTIONS UNIT COMPLIANCE
TECHNICAL SELECTION DATA SPLIT DUCTED UNIT 3 THREE PHASE SCROLL TWO STAGE CENTRIFUGAL LOUVRE AXIAL UNIT FEATURES Scroll Compressor Multiple Speed Outdoor Fans Louvred Outdoor Coil Guard Pre-charged with
More informationSkyAir, Packaged Outdoor Units (RoHS application) RQ71KBV4A, RZQ71KBV1, RZQ71KBV4A, RZQ100KBV1 RZQ150HY4A RZQ150KV4A PL-908-1
SkyAir, Packaged Outdoor Units (RoHS application) RQKBV4A, KBV1, KBV4A, 100KBV1 150HY4A 150KV4A PL-908-1 RQKBV4A / KBV1 / KBV4A / 100KBV1 (RoHS application) RQKBV4A / KBV1 / KBV4A / 100KBV1 (RoHS application)
More informationHigh Wall Type ( 2 Series )
Jan.05' Engineering Data High Wall Type ( 2 Series ) Indoor Unit MMK-AP0072H MMK-AP0092H MMK-AP0122H 1. Equipments 2. Technical Specifications 3. Dimensional Drawing 4. Wiring Diagram 5. Refrigerant Cycle
More informationFour-way Cassette Type
Four-way Cassette Type Four-way Cassette Type 1. Features... 9 2. Specifications... 12 3. Dimensions... 17 4. Service Space... 18 5. Wiring Diagrams... 19 6. Capacity Tables... 21 7. Electric Characteristics...
More informationPL-804. Remote Controller (RoHS application) BRC7F634F, BRC7F635F
Split Indoor Units (RoHS application) FTK20GVLT, FTK25GVLT, FTK30GVLT FTX20GVLT, FTX25GVLT, FTX30GVLT FTKS42GVLT FTXS42GVLT Split Indoor Units (RoHS application) (Revised from PL-802) FTY25GXV1, FTY35GXV1
More informationWALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models
SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASH9LSACW ASH12LSACW Outdoor unit AOH9LSAC AOH12LSAC CONTENTS SPECIFICATIONS...................... 1 DIMENSIONS..........................
More informationA2P H2P H4P H6P H1P H3P H5P H7P. Outdoor X205A OFF Y1E E1H R6T X5A F8U F7U K14R K2R X28A X6A SEE NOTE 7 HAP X77A X31A X13A X21A P< S1PL P> S1PH
RZQSG00L9V N L N 50Hz 0-40V Z5 GRN D089497B WHT HR BRNHR3 PPLHR4 HR + E K0R V3D L N LA FU FU ZF ZF KM Z GRN/YLW Z 5 NA VT VT VD + R VR FU V Z3F Z4 X0A WHT X50A 4 MF MS M3 MS ~ Position of compressor terminal
More informationTECHNICAL GUIDE R410a SPLIT SYSTEM 1.5 to 5.0 NOMINAL TONS
Version.MDT-2016.T3.103 TECHNICAL GUIDE R410a SPLIT SYSTEM 1.5 to 5.0 NOMINAL TONS FEATURES AND BENEFITS COMPRESSOR: Compressors are protected with internal temperature and current overloads. An internal
More informationROOF TOP (SERIES SR) 10.8 TO 103 KW 37,000 TO 351,000 Btuh
ROOF TOP (SERIES ) 10.8 TO 103 KW 37,000 TO 351,000 Btuh These rooftop units are complete, self contained air conditioners fully assembled, wire, charged and tested prior to shipment, each unit is delivered
More informationPRODUCT CODE MODEL NAME. No. DESCRIPTION DWG No. PART No. Qty Qty Qty Qty Qty Qty REMARKS
ERSATZTEILE RAS-4HNC1E, 3~ 400V 50Hz RAS-5HNC1E, 3~ 400V 50Hz RAS-6HNC1E, 3~ 400V 50Hz 1 Rear Cover Assy XEK24870 A E03946 1 1 1 1 1 1 Assembly 1-1 Pipe Cover B 17C86251 A P27003 1 1 1 1 1 1 1-2 Handle
More informationFTXS50EV1B, FTXS60EV1B (RoHS application) FTXS50EV1B, FTXS60EV1B Wiring Diagram
42 FTXS50EV1B, FTXS60EV1B (RoHS application) FTXS50EV1B, FTXS60EV1B Diagram FTXS50EV1B, FTXS60EV1B (RoHS application) 43 44 FTXS50EV1B, FTXS60EV1B (RoHS application) Parts Parts Name Drwg. Parts Model
More informationTechnical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.
Technical Support Division 2012.10 1 1. External appearance 2. Nomenclature 3. Specifications 4. Dimensions 5. Service space 6. Piping diagram 7. Wiring diagram 8. Capacity tables 9. Electric characteristics
More informationSPLIT TYPE AIR CONDITIONER. CASSETTE type. Models Indoor unit Outdoor unit MC24Y3E
SPLIT TYPE AIR CONDITIONER CASSETTE type Models Indoor unit Outdoor unit C24YE MC24Y3E MR24Y3E1 SPECIFICATIONS TYPE COOL & HEAT INDOOR UNIT MC24Y3E OUTDOOR UNIT MR24Y3E1 COOLING CAPACITY 23,500-22,500
More informationPRK PREVIEW. System. OZONE FRIENDLY R-407C Series. Inverter Heat Pump Series Heat Recovery Series PLUS Series (Heat Pump)
PRK 00-04 PREVIEW System OZONE FRIENDLY R-407C Series Inverter Heat Pump Series Heat Recovery Series PLUS Series (Heat Pump) 3DUW#4 2XWGRRU#8QLWV 111111111111111111111111111111111111111111111111111111111111111111111
More informationModel RAS-25YHA2 RAS-35YHA3 RAS-50YHA2 RAS-60YHA2 RAS-70YHA2 RAS-80YHA2
2-8 GENERAL DATA 2.3. INVERTER SERIES 2.3.1. INVERTER (RAS-25YHA2/35YHA3/50YHA2/60YHA2/70YHA2/80YHA2) Model RAS-25YHA2 RAS-35YHA3 RAS-50YHA2 RAS-60YHA2 RAS-70YHA2 RAS-80YHA2 Power Supply From Outdoor Unit
More informationAir Conditioning. Technical Data. Heat reclaim ventilation EEDEN VAM-FA/FB
Air Conditioning Technical Data Heat reclaim ventilation EEDEN14-205 VAM-FA/FB Heat reclaim ventilation VAM-FA/FB VAM-FA/FB 1 Features............................................................. 2 2 Specifications.......................................................
More informationN4A6. Product Specifications
ENVIRONMENTALLY SOUND REFRIGERANT N4A6 Product Specifications EFFICIENT UP TO 16.5 SEER/12.2 13.0 EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/2 Volt,
More informationFan Coil Units. Technical Data
Fan Coil Units Technical Data F a n c o i l u n i t s E E D E N 1 1-4 0 0 Fan Coil Units Technical Data F a n c o i l u n i t s E E D E N 1 1-4 0 0 Table of Contents Table of Contents 3 Round Flow Cassette...
More informationMODEL: DCT 35 INV-Si DCT 50 INV-Si DCT 70 INV-Si DCT 100 INV-Si DCT 140 INV-Si DCT 170 INV-Si
MODEL: DCT 35 INV-Si DCT 50 INV-Si DCT 70 INV-Si DCT 100 INV-Si DCT 140 INV-Si DCT 170 INV-Si Part 1 General Information.. 1 Part 2 Indoor Units. Part 3 Outdoor Units. Part 5 Control... Part 6 Control
More informationPRODUCT CODE MODEL NAME RASC-10HNPE. No. DESCRIPTION DWG No. PART No. Qty Qty Qty Qty Qty REMARKS
7E343107 RASC-4HNPE RASC-5HNPE RASC-6HNPE 7E343108 7E343109 No. DESCRIPTION DWG No. PART No. Qty Qty Qty Qty Qty REMARKS 1 Foot Assy XEK38712 A E04359 1 1 1 Assembly 1 Foot Assy XEK39008 A E04384 1 1 Assembly
More informationLow Static Pressure Duct(V shape evaporator)
Low Static Pressure Duct (V shape evaporator) 1. Features... 116 2. Specifications... 118 3. Dimensions... 121 4. Service Spaces... 123 5. Piping Diagrams... 124 7.Fan Performance... 126 8.Capacity Tables...
More informationMulti-Room Ductless heat-pump systems Submittal Data: MULTI56HP230V1AO 56,000 BTUH Super +Multi-port Heat Pump System Job Name Location Date
Multi-Room Ductless heat-pump systems Submittal Data: 56,000 BTUH Super +Multi-port Heat Pump System Job Name Location Date Purchaser Engineer Submitted To For Reference Approval Construction Unit Designation
More informationHeating. Technical Data. Daikin Altherma low temperature split EEDEN ERLQ-CV3
Heating Technical Data Daikin Altherma low temperature split EEDEN2-725 ERLQ-CV Daikin Altherma low temperature split ERLQ-CV TABLE OF CONTENTS ERLQ-CV Features.............................................................
More informationTechnical Service Manual. TVR LX Systems Low Static Pressure Duct Units with DC Fan Motor V/50-60Hz/1ph
Technical Service Manual TVR LX Systems Low Static Pressure Duct Units with DC Fan Motor 220-240V/50-60Hz/1ph August 2015 1. Features...2 2. Specifications...3 3. Dimensions...7 4.Service Spaces...8 5.Piping
More informationTechnical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.
Technical Support Division 2013.12 1 1. External appearance 2. Nomenclature 3. Specifications 4. Dimensions 5. Service space 6. Piping diagram 7. Wiring diagram 8. Capacity tables 9. Electric characteristics
More informationPL-601. SkyAir Connection Units (RoHS application) BSVQ100MAV1, BSVQ160MAV1, BSVQ250MAV1. Air Cleaner (RoHS application) MC707SC, MC757SC, MC757SC-D
Split Indoor Units (RoHS application) FTKS20D3VML, FTKS20D3VMW, FTKS25D3VML, FTKS25D3VMW FTKS35D3VML, FTKS35D3VMW FTXS20D3VML, FTXS20D3VMW, FTXS25D3VML, FTXS25D3VMW FTXS35D3VML, FTXS35D3VMW FTYN25DAV3B,
More informationTechnical Service Manual. TVR LX Systems Medium Static Pressure Duct Units with DC Fan Motor V/50-60Hz/1ph
Technical Service Manual TVR LX Systems Medium Static Pressure Duct Units with DC Fan Motor 220-240V/50-60Hz/1ph August 20 Medium Static Pressure Duct Unit With DC Fan Motor 1. Features...2 2. Specifications...4
More informationPreface. After sales service division
EX-38 JULY 2001 Preface 1. This express parts list is made for offering spare parts information to customer as soon as possible. This spare parts list has list of spare parts information of this month
More informationWCA4**4. Product Specifications
WCA4**4 AIR CONDITIONER EFFICIENT 14 SEER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208/2 Volt, 1 phase, 60 Hz Use of the AHRI Certified TM Mark indicates a manufacturer s participation
More informationR22 TECHNICAL MANUAL. Split Unit Air Conditioner Ceiling Cassette C & E Series FF-C, FHC-E, FFY-C, FHYC-E. Cooling only & Heatpump [50Hz]
R22 TECHNICAL MANUAL Split Unit Air Conditioner Ceiling Cassette C & E Series FF-C, FHC-E, FFY-C, FHYC-E Cooling only & Heatpump [50Hz] Table of Contents Table of Contents Nomenclature...1 Indoor...1
More informationDUCT type. SPLIT TYPE AIR CONDITIONER (50Hz) Models Indoor unit Outdoor unit C O N T E N T S
SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type Models Indoor unit Outdoor unit RD-90EB RO-90EPB C O N T E N T S SPECIFICATIONS... OUTLINE AND DIMENSIONS... CIRCUIT DIAGRAM...5 REFRIGERANT SYSTEM DIAGRAM...6
More informationR4A3. Product Specifications EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT
EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 1-1/2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt, 1- phase, 60 Hz R4A3 Product Specifications REFRIGERATION CIRCUIT S Scroll compressors
More informationSINGLE. Technical Data Book. 4Way Cassette S for Nordic (R410A, 50Hz) Model : AC***JN4CEH/EU (ODU: AC***JXSC*H/EU)
SINGLE Technical Data Book 4Way Cassette S for Nordic (R4A, 5Hz) Model : AC***JN4CEH/EU (ODU: AC***JXSC*H/EU) History Version Modification Date Remark Ver.1. Released SINGLE for Nordic TDB 15.3.. Ver.1.1
More informationEngineering Data Book
40VMA Outside Air Processing Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without
More informationTSTAT0201CW (Sold Separately) Qualifying models only. Max. Fuse or Breaker
HVA9 Product Specifications HIGH EFFICIENCY UP TO 19 SEER VARIABLE SPEED AIR CONDITIONER WITH OBSERVER COMMUNICATING CONTROL SYSTEM 2 THRU 5 TONS SPLIT SYSTEM 208 230 Volt, 1 phase, 60 Hz REFRIGERATION
More informationPL Split Indoor Units (RoHS application) CDKS30JVLT CDKS40JVLT CDXS30JVLT CDXS40JVLT
Split Indoor Units (RoHS application) CDKS30 CDKS40 CDXS30 CDXS40 Sky Air, Packaged Indoor Units (RoHS application) 25, 30, 40, 50, 60 PL-1007-1 CDKS30 (RoHS application) 1 2 CDKS30 (RoHS application)
More informationPACKAGE UNIT PCA340U TECHNICAL SELECTION DATA. -10 o C UNIT FEATURES SPECIFICATION SUMMARY UNIT OPTIONS CONTROL OPTIONS UNIT COMPLIANCE.
TECHNICAL SELECTION DATA PACKAGE UNIT + o C -10 o C 3 THREE PHASE SCROLL TWO STAGE CENTRIFUGAL LOUVRE LIANT SCROLL RESSOR AXIAL UNIT FEATURES SPECIFICATION SUMMARY Scroll Compressor Multiple Speed Outdoor
More informationSERVICE MANUAL OUTDOOR UNIT. No. OB386
SPLIT-TYPE AIR CONDITIONERS Revision D: MU-A20VB- E and MU-A5VB- E have been added. Please void OB86 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A No. OB86 REVISED EDITION-D Models MU-A20VB-
More informationEngineering Data Book
40VMH High Static Duct Indoor Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without
More informationLow Static Pressure Duct (V shape evaporator)
MCAC-VTSM-2015-04 Low Static Pressure Duct Type Low Static Pressure Duct (V shape evaporator) 1. Features... 100 2. Specifications... 101 3. Dimensions... 105 4.Service Spaces... 106 5.Piping Diagrams...
More informationR4A4. Product Specifications EFFICIENT 14 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT
R4A4 Product Specifications EFFICIENT 14 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/2 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT Scroll compressors
More informationJob Name: Tag# 3 Port, 2-Ton Outdoor Heat Pump
Job Name: Tag# Submittal Data Sheet 3 Port, 2-Ton Outdoor Heat Pump 3MXS24RMVJU Efficiency SEER EER HSPF COP Non-Ducted 18 12.7 12.5 3.53 Ducted 14 9.7 8.2 3.44 Mixed 15.95 11.2 10.35 3.49 Performance
More informationAir Conditioning. Technical Data. VRV IV water cooled series EEDEN RWEYQ-T8
Air Conditioning Technical Data VRV IV water cooled series EEDEN15-201 Outdoor Unit TABLE OF CONTENTS 1 Features............................................................. 2 2 Specifications.......................................................
More informationyour comfort. our world. Biddle air curtains For connection to Daikin Sky Air Systems
your comfort. our world. Biddle air curtains For connection to Daikin Sky Air Systems CityM-DK-F Air curtains for Sky Air Biddle City air curtains are the ideal solution for retailers and consultants to
More informationR4A5. Product Specifications EFFICIENT 14 SEER/ EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT
ENVIRONMENTALLY SOUND REFRIGERANT R4A5 Product Specifications EFFICIENT 14 SEER/11.7 12.2 EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt, 1 phase,
More informationCooling Compressor Type DC Inverter Driven Rotary Rated Capacity 48,000 BTU/H RLA 23.0 A
Submittal Data: Multi-Room Ductless heat-pump systems 48,000 BTUH Super +Multi-port Heat Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES
More informationSERVICE MANUAL OUTDOOR UNIT. No. OB387
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Revision C: MUH-A25VB - E has been added. Please void OB87 REVISED EDITION-B. OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A. OB87 REVISED EDITION-C Wireless type
More informationTSA6. Product Specifications. SmartComfort TXC 5600
ENVIRONMENTALLY SOUND REFRIGERANT TSA6 SmartComfort TXC 5600 Product Specifications 16 SEER SINGLE STAGE AIR CONDITIONER WITH OBSERVER COMMUNICATING CONTROL SYSTEM 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230
More informationV33B High Efficiency 360 Cassette Indoor Models - 60HZ
PRODUCT SPECIFICATIONS Low-sound, high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has motor-driven
More informationCSA6. Product Specifications. SoftSound SXC 2600
16 SEER SINGLE STAGE AIR CONDITIONER WITH OBSERVERr COMMUNICATING CONTROL SYSTEM 1½ THRU 5 TONS SPLIT SYSTEM 208 / 2 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Copeland Scroll compressors on all models
More informationIndoor Console. Slim Design This is only 199mm thick, the slimmest on the market. Its slim design easily integrates the unit into your décor.
Indoor Console Slim Design This is only 199mm thick, the slimmest on the market. Its slim design easily integrates the unit into your décor. Black Display Functional art, the touch screen display is elegant
More informationVWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ
PRODUCT SPECIFICATIONS VARIABLE REFRIGERANT FLOW SYSTEMS VRF VWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ Bulletin No. 210712 March 2018 Low-sound, three-speed Wall Mount with LED display offers three
More informationMulti-Room Ductless heat-pump systems Submittal Data: MULTI18HP230V1AO 18,000 BTU/H Wall Mounted Heat- Pump System Job Name Location Date
Multi-Room Ductless heat-pump systems Submittal Data: 18,000 BTU/H Wall Mounted Heat- Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. Reference Approval
More informationConcealed Ducted Split Series R22
Concealed Ducted Split Series R22 24-60 MBH Ducted Split with Hermetic Compressor Tropical 50 Hz For more technical information please visit Table of Contents INTRODUCTION 2 NOMENCLATURE 2 UNIT RATING
More informationPL Split Indoor Units (RoHS application) FTXS25J2VMA FTXS35J2VMA. Split Outdoor Units 2M56GV1G
Split Indoor Units (RoHS application) FTXS25J2VMA FTXS35J2VMA Split Outdoor Units 2M56GV1G Sky Air, Packaged Indoor Units (RoHS application) FFQ25BV1B9, FFQ35BV1B9, FFQ50BV1B9, FFQ60BV1B9 FXZQ20MVE9, FXZQ25MVE9,
More informationN4A4 C. Product Specifications
COASTAL 14 SEER AIR CONDITIONER 14 SEER/11.5 12.5 EER R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT Scroll compressors on all models Filter drier
More informationFBQ125KMV2C (RoHS application) FBQ125KMV2C Wiring Diagram
FBQ125KMV2C (RoHS application) FBQ125KMV2C Diagram 167 FBQ125KMV2C (RoHS application) 168 FBQ125KMV2C (RoHS application) Parts Parts Name Drwg. Parts Model & Specifi cation FBQ125KMV2C B1 6002954 EVAPORATOR
More informationV33A Standard/High Efficiency 360 Cassette Indoor Models - 60HZ
PRODUCT SPECIFICATIONS Low-sound, standard or high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has
More informationSPLIT TYPE ROOM AIR CONDITIONER FLOOR TYPE
SPLIT TYPE ROOM AIR CONDITIONER FLOOR TYPE Indoor unit AGYF09LAC AGYFLAC AGYFLAC AGYFLAC Outdoor unit AOYV09LAC AOYVLAC AOYVLAC AOYVLAL CONTENTS SPECIFICATIONS..................... DIMENSIONS.........................
More information