1 User Guide ECL Apex 10 *087R9745* *vijem102* Installation and configuration VI.JE.M1.02 Danfoss 11/2004 DH-SMT VI.JE.M1.02 Danfoss 11/2004 DH-SMT
2 ECL Apex 10 VI.JE.M1.02 Danfoss 11/2004 DH-SMT VI.JE.M1.02 Danfoss 11/2004 DH-SMT
3 Table of Contents Mounting and wiring...4 Mounting of an analog output extension module... 4 Mounting of an additional I/O module... 5 Wiring... 6 Connect service tool... 8 Login with user name SUPV... 8 Configuration...8 Change language... 9 Unlock the configuration of the controller System setup Set application type Your wiring notes! Configuration of inputs and outputs Schedule setup...22 Lock and check configuration...23 Reference control Sensor filter and offset...25 Thermostats etc Alarm priorities Backup / restore I/O status and manual...28 Overview...30 Schedule...32 Alarm...33 Log...34 First start of the controller...36 Check alarms...36 Start the controller DH-SMT VI.JE.M1.02 Danfoss 11/2004 1
4 Before you start 1. Make a drawing of your system application 2. Select your inputs and outputs - and write down what you have chosen 3. Configure the controller How to use these instructions These instructions describe how the Danfoss district heating controller ECL Apex 10 is set up. Heating system example In this user guide we describe the setup by means of an example comprising a weather compensated heating circuit and a domestic hot-water (DHW) circuit. Please note that the system diagrams in this instruction are principle drawings and they do not contain all components that are necessary in your system. 2 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
5 Fig. 1: Heating system example used in this user guide The heating supply is provided with a strainer and a differential pressure switch / filter guard (DI1), as well as sensors to monitor primary temperature (ST2) and pressure (SP1). The heating circuit consists of a motorized control valve (M1), a heat exchanger with flow (ST3) and return (ST4) temperature sensors, two sequentially controlled pumps (P1 and P2) with flow (SP2) and return (SP3) pressure transmitters. The heating circuit as such is weather compensated by means of the outdoor temperature sensor (ST1). The DHW comprises a motorized control valve (M2), a heat exchanger with flow (ST5) and return (ST6) temperature sensors, one set of twin-pump controlled pumps (P3 and P4) supervised by a differential pressure switch (DI2). DH-SMT VI.JE.M1.02 Danfoss 11/2004 3
6 Mounting and wiring Mounting of an analog output extension module 1. Disconnect the ECL Apex 10 from the mains supply. 2. Remove the processing unit from the base part by pressing in the plates on both sides. 3. Mount the extension module in the base part. 4. Remount the processing unit on the base part. 4 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
7 Mounting of an additional I/O module 1. Move the protective cap from the ECL Apex 10 to the I/O module. Remove the protective cap from the connection plug on the right-hand side of the base part. Place the cap on the connection plug of the I/O module, which is to be mounted on the far righthand side of the array. 2. Assemble the I/O module and the ECL Apex 10. DH-SMT VI.JE.M1.02 Danfoss 11/2004 5
8 Wiring Example of electrical connections 1 Outdoor temp. sensor (ST1) 2 Flow temp. sensor, primary (ST2) 3 Flow temp. sensor, heating (ST3) 4 Return temp. sensor, heating (ST4) 5 Flow temp. sensor, DHW (ST5) 6 Return temp. sensor, DHW (ST6) 7 Flow pressure, primary (SP1) Points (Pt) 8 Flow pressure, heating (SP2) 9 Return pressure, heating (SP3) 10 Diff. pressure switch, primary (DI1) 11 Diff. pressure switch, DHW (DI2) Module (Mod) 19 Circulation pump 2, DHW (P4) 18 Circulation pump 1, DHW (P3) 17 Circulation pump 2, heating (P2) 16 Circulation pump 1, heating (P1) 15 Mot. control valve close, DHW (M2) Points (Pt) Light emitting diodes 14 Mot. control valve open, DHW (M2) 13 Mot. control valve close, heating (M1) 12 Mot. control valve open, heating (M1) 6 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
9 Table 1: Wiring of analog inputs Sensor Input Module Point Type Outdoor temperature sensor (ST1) AI1 1 1 Pt 1000 Flow temperature sensor, primary (ST2) AI2 1 2 Pt 1000 Flow temperature sensor, heating (ST3) AI3 1 3 Pt 1000 Return temperature sensor, heating (ST4) AI4 1 4 Pt 1000 Flow temperature sensor, DHW (ST5) AI5 1 5 Pt 1000 Return temperature sensor, DHW (ST6) AI6 1 6 Pt 1000 Flow pressure, primary (SP1) AI7 1 7 Userdefined Flow pressure, heating (SP2) AI8 1 8 AKS32-12 Return pressure, heating (SP3) AI9 1 9 AKS32-12 Differential pressure switch, primary (DI1) AI Normal Differential pressure switch, DHW (DI2) AI Normal Table 2: Wiring of digital outputs Load Output Module Point Active at Motorized control valve open, heating (M1) DO Normal Motorized control valve close, heating (M1) DO Normal Motorized control valve open, DHW (M2) DO Normal Motorized control valve close, DHW (M2) DO Normal Circulation pump 1, heating (P1) DO NO Circulation pump 2, heating (P2) DO NO Circulation pump 1, DHW (P3) DO NO Circulation pump 2, DHW (P4) DO NO NO = Normally Open NC = Normally Closed DH-SMT VI.JE.M1.02 Danfoss 11/2004 7
10 Configuration Connect service tool The service tool is connected to the controller by placing the plug from the PC or PDA into the service tool socket on the controller. The controller has to be switched ON before the service tool program is started. The first time the service tool is connected to a new controller version, the start-up of the service tool will take longer than usual. Login with user name SUPV To change the controller configuration you have logon as SUPV (supervisor) and enter the belonging access code. On delivery the controller is supplied with the access code VI.JE.M1.02 Danfoss 11/2004 DH-SMT
11 When you are logged on to the controller, you will get this overview. Normally it will be empty until one or more circuits have been configured. It will always be possible to return to the overview by pressing the button at the bottom left. If there is a red bell at the bottom right, it tells you that there is an active alarm. Change language On delivery the language of the service tool display is English. Follow this procedure to change the language: 1. Go to the configuration menu Press the orange setup button with the screw spanner at the bottom of the display 2. Select Authorization Press the line Authorization to get to the user setup display. DH-SMT VI.JE.M1.02 Danfoss 11/2004 9
12 3. Change the settings for the user SUPV Mark the line with the user name SUPV. Press the button Change. 4. Choose language Press the OK button to save the new settings. 5. Carry out a new login with the user name SUPV To activate the chosen language, it is necessary to carry out a new login as SUPV. Press the padlock at the top left corner of the display to login again. 10 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
13 Unlock the configuration of the controller The controller must be stopped and unlocked in order to change the configuration. 1. Go to the Configuration menu 2. Select Lock/unlock configuration Press the line Lock/unlock configuration. 3. Select Configuration lock Press the field with the text Locked. 4. Select Unlocked Selected Unlocked and press OK. DH-SMT VI.JE.M1.02 Danfoss 11/
14 System setup 1. Go to the Configuration menu 2. Choose System and clock setup Press the line System and clock setup. You have to set the time and date in order to activate the control functions. 3. Set system settings Controller name and Mains frequency can be changed by pressing the field and then entering the new settings. Set time and date by pressing the field Year and then enter the correct data incl. the desired daylight saving time changeover setting. 12 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
15 Set application type From factory the controller is not configured and the entire system must be set up to cover the demands of the actual system. The choices you make now will help you by limiting your possible choices later in the configuration procedure. 1. Go to the Configuration menu 2. Select Application configuration The number of submenus will adapt itself so that only relevant submenus are visible. 3. Choose the function of your circuit(s) Choose the type of each circuit, i.e. heating or DHW. At reconfiguration, reset all inputs and outputs before you define the new configuration. DH-SMT VI.JE.M1.02 Danfoss 11/
16 4. Choose Control strategy (heating circuits only) Constant temp. = Constant temperature control (no weather compensation) 6-pt weather comp. = Weather compensation according to a heat curve with 6 points Std w.comp. + room T = Standard weather compensation + room temperature control 6-pt w.comp. + room T = Weather compensation according to a heat curve with 6 points + room temperature control. 5. Select PI(D) type (heating as well as DHW circuits) 3-pt PI = PI control, 3-point (recommended) 0-10 V, PID = PID control, 0-10 V (requires ECA-OB 003A) 3-pt PID = PID control, 3-point 14 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
17 6. Set Input type (heating circuits only) Choose whether you want to control the temperature in the flow or as an average of the flow and return temperatures Flow temp. = Flow temperature Avg. temp. = Average temperature (flow temperature + return temperature) / 2 7. Set Pump strategy (heating as well as DHW circuits) Sequence = Sequence controlled pumps PID (0-10 V) = PID controlled pump, 0-10 V Twin pump = Two pump control Std controller = Standard one pump control Depending on chosen Pump strategy, choose - No. of pumps - Pressure type Pressure control (sensors) Diff. pressure control (switch) DH-SMT VI.JE.M1.02 Danfoss 11/
18 8. Select Makeup water (heating circuit only) ON/OFF = ON/OFF controlled makeup pump PID (0-10 V) = PID controlled makeup pump Depending on chosen Makeup water type, choose - No. of pumps - Makeup pressure Analog or Digital (sensor(s)) 9. Set Universal limiter (heating as well as DHW circuits) Analog = Analog controlled limiter Temperature = Temperature controlled limiter Pressure = Pressure controlled limiter This limiter is for special applications only, e.g. for limiting the flow temperature based on the primary supply temperature. 16 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
19 Your wiring notes! Configuration of inputs and outputs! Wiring of analog inputs (AI) Sensor Input Mod. Pt Terminals Type Wiring of digital outputs (DO) Load Output Mod. Pt Terminals Active at DH-SMT VI.JE.M1.02 Danfoss 11/
20 Configuration of inputs and outputs According to heating system example fig Go to the Configuration menu 2. Select Input and output setup 3. Select Application input selection Select sensors according to your wiring table on the previous page. When finished go back to I/O setup. 18 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
21 4. Select Monitoring input selection Select and describe sensors for monitoring according to your system application. (These sensors do not affect the control functions). When finished go back to I/O setup. 5. Select General input setup - Analog inputs Set up the analog inputs according to your system application (see Wiring, table 1). Mod. = module Pt = point When finished go to next page. An analog input can be configured as Pt 1000, voltage, current or contact input (DI). DH-SMT VI.JE.M1.02 Danfoss 11/
22 6. Configuration of Digital inputs (DI) Set up the digital inputs according to your system application (see Wiring, table 1). Mod. = module Pt = point Analog inputs (AI) can also be set up as digital inputs (DI) as seen in this example. When finished go back to I/O setup. 7. Configuration of User-defined input setup It is possible to define pressure sensors yourself. When finished go back to I/O setup. 20 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
23 8. Configuration of Analog outputs (AO) Example of a setup of an analog output. This can be used for analog motorized control valves e.g. It requires the option board ECA-OB 003A. When finished go back to I/O setup. 9. Configuration of Digital outputs (DO) Set up the digital outputs according to your system application (see Wiring, table 2). Mod. = module Pt = point DH-SMT VI.JE.M1.02 Danfoss 11/
24 Schedule setup 1. Go to the Configuration menu 2. Select Schedule setup Choose which week schedule you want to use for your circuit(s). The week schedules are defined in the schedule list (see additional information in the paragraph Schedule). 22 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
25 Lock and check configuration 1. Go to the Configuration menu 2. Select the Lock/unlock configuration Choose Locked. When the controller is locked, it verifies the configuration setup and checks that points are used only once. If a point is used twice, the last set point will be reset. When finished go back to Configuration menu. 3. Select Input and output setup Check that all inputs and outputs are set correctly. In this example, sensor ST3 as well as ST4 was set up to Mod. 1 and Pt 4. Sensor ST4 was reset to 0 when the controller was locked and must be corrected. Remember to unlock the controller before changes can be made. DH-SMT VI.JE.M1.02 Danfoss 11/
26 Reference control 1. Go to the Configuration menu 2. Select Reference control Decide which circuit, if any, should be influenced by another circuit (slave). This function is not needed for the chosen heating system example in this user guide but will be relevant for systems similar with the one shown below. Fig. 2: Master / slave controlled heating system 24 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
27 Sensor filter and offset 1. Go to the Configuration menu 2. Select the Sensor filter and offset Set the offset of the sensor. This can be used to correct the measured value, for instance to compensate for the increased temperature due to a long cable (see ST1). Set the filter time constant to a high constant for outdoor and room temperatures. Low values should only be set for flow temperatures. Thermostats etc. 1. Go to the Configuration menu 2. Choose Thermostats etc. Define the required thermostat functions. A room thermostat is chosen in this setup. However, it does not apply to the heating system example chosen in general for this instruction. Select a name for the thermostat and set the values. DH-SMT VI.JE.M1.02 Danfoss 11/
28 Alarm priorities It is possible to set 5 different alarm levels or disable an alarm. Critical is the most important level and Log only has the lowest importance. 1. Go to the Configuration menu 2. Select Alarm priorities Set the alarm priorities for the circuits. Go to next pages Set the alarm priorities for the Sensor inputs and Monitoring. 26 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
29 Backup / restore 1. Go to the Configuration menu 2. Choose Backup / restore It is possible to secure all your settings by saving them to a file. Later you can then restore your settings again by copying this file. A restore is only possible to same controller version. You can see your version number by pushing and then 3. Select Backup Choose where to save the file and give it a meaningful name. To restore your settings, you have to unlock the controller and choose the backup file. DH-SMT VI.JE.M1.02 Danfoss 11/
30 I/O status and manual In the I/O status and manual menu it is possible to monitor the current input and output status and override it. 1. Go to Configuration menu 2. Select I/O status and manual - DIgital inputs The first display shows you the status (control mode) and values of the various digital inputs. It is possible to force the input from the normal setting AUTO (automatic control) to either MAN ON (manually ON) or MAN OFF (manually OFF). Go to next display by pushing 3. Select I/O status and manual - Digital outputs This display shows you the status (control mode) and values of the digital outputs such as motorized control valves and pumps. It is possible to force the output from the normal setting AUTO (automatic control) to either MAN ON (manually ON) or MAN OFF (manually OFF). Go to next display by pushing 28 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
31 4. Select I/O status and manual - Analog inputs This display monitors all analog inputs. Go to next display by pushing 5. Select I/O status and manual - Analog outputs Analog output status and value are displayed here. Choose whether the analog output should be controlled automatically (AUTO) or manually (MAN). The actual output ratio is shown as a value below the setpoint. This example does not apply to chosen heating system example. DH-SMT VI.JE.M1.02 Danfoss 11/
32 Overview This is the initial display for daily operation. The essential information for each circuit is displayed here. Go to Overview Actual = actual flow temperature Reference = actual setpoint Status = controller mode Outdoor temperature Comfort mode Setback mode Standby mode Press the circuit buttons or to see specific circuit information. Heating circuit DHW circuit Flow = flow temperature Ref. = flow temperature reference Return = return temperature Only values in the boxes can be changed. 30 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
33 Go to Overview and press to see Monitoring input Displays sensor inputs that are not used for the calculated flow temperature. Press to see Outdoor status The outdoor status shows the min, avg. and max temperatures since midnight. Press to see Controller ID In this display you can always see which controller type you have installed and its version number. In connection with service calls this information is required. DH-SMT VI.JE.M1.02 Danfoss 11/
34 Schedule Press the Schedules button The Schedule list shows the activated week schedules. Choose the week schedule you want to see or modify. Press a week schedule The example shows you week schedule 1, which is set to follow the heating circuit. From the example can be seen that the comfort periods have been set from 7:00 to 21:00 for all days of the week except Saturday. To change the setting for a week day, choose the day in question by pushing it. To enter holiday periods, push Holiday It is possible to set individual holiday periods as well as yearly events, i.e. fixed yearly holiday periods. 32 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
35 Alarm If you press the log. button, you will access two alarm displays and an event Active alarms This display shows you all active alarms. Press the button to get more information about the alarm. If you wish to confirm that you have seen an alarm, press the Ack. (acknowledge) button. Moves an alarm to cleared alarms Refreshes the display information Move between pages Cleared alarms and Event log In the Cleared alarms display you will be able to see all cleared alarms. The Event log shows all the changes you have made. DH-SMT VI.JE.M1.02 Danfoss 11/
36 Log The log function makes it possible to collect, show and export logged data. Press the Log button In this display new log groups can be established, deleted or changed. Select a log group by pressing the log group name and press the Change button to go to Log setup This is the start picture for new log groups. Choose name, mode etc. for your log group. 34 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
37 Press the button twice to go to Log probe selection. Select the data you want to log. If you press the button, the Log probes will show you the parameters you have chosen to log. Press the button again to go back to the Log display. Press the button to see log charts for the chosen log group and your selected log probes. Choose between two chart types: Actual / trend chart showing the current data Historic chart showing the log for a past period It is possible to export or print the charts by pressing the button. Press the button twice to go to Chart settings, in which you can modify the appearance of the logged data. Log group charts are not stored! DH-SMT VI.JE.M1.02 Danfoss 11/
38 First start of the controller Check alarms 1. Go to the alarm list 2. Check Active alarms Press the information button to get more information about each alarms and enter your check mark, to show that you have acknowledged the alarm. In this display the first alarm was caused by the controller having been set up but not started. The second alarm was caused by a changed setting for the motorized valve. 3. Remove cancelled alarms from the list by pressing. 4. Check active alarms again In this case an alarm remains active because the control has stopped. The alarm cannot be cancelled until the control has been restarted again. If there are other active alarms, the cause should be found and corrected before the control is restarted. 36 VI.JE.M1.02 Danfoss 11/2004 DH-SMT
39 Start the controller 1. Go to Configuration menu 2. Select Lock/unlock configuration Press the line Lock/unlock configuration 3. Start the controller Choose the field next to the main switch. Select START and OK. The controller will now start controlling the various components in the system. DH-SMT VI.JE.M1.02 Danfoss 11/
Installation Guide. ECL Comfort 210 / 310, application A231 / A Table of Contents
1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 4 2.1 Before you start.....................................................
More informationECL Comfort Installation and Maintenance. User s Guide. ECL Comfort. C60 Double mixing controller C60. Table of Contents. Daily use.
ECL COMFORT VI.7C.B4.0 C60 Table of Contents Daily use ECL Comfort User s Guide Section Choose favourite display Select controller mode 3 Adjust room temperature 4 Set personal day plan 5 Advantages of
More informationUser manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS.
Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS. User manual Manual version: 2.4 dated 27/02/08 Program code: FLSTDmMCDE LEGGI
More informationCapacity controller with cascade control AK-PC 783. Manual
Capacity controller with cascade control AK-PC 783 Manual Contents 1. Introduction...3 Application... 3 Principles... 4 2. Design of a controller...7 Module survey... 8 Common data for modules...10 Controller...12
More informationCapacity controller AK-PC 730 REFRIGERATION AND AIR CONDITIONING. Manual
Capacity controller AK-PC 730 REFRIGERATION AND AIR CONDITIONING Manual Contents 1. Introduction...3 Application... 3 Principles... 4 2. Design of a controller...7 Module survey... 8 Common data for modules...10
More informationGRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/
GRUNDFOS INSTRUCTIONS Control HVAC Installation and operating instructions Other languages net.grundfos.com/qr/i/98800750 English (GB) English (GB) Installation and operating instructions Original installation
More informationGRUNDFOS INSTRUCTIONS. Hydro MPC. Installation and operating instructions
GRUNDFOS INSTRUCTIONS Hydro MPC Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions These installation
More informationCapacity controller with heat recovery function AK-PC 781. Manual
Capacity controller with heat recovery function AK-PC 781 Manual Contents 1. Introduction...3 Application... 3 Principles... 4 2. Design of a controller...7 Module survey... 8 Common data for modules...10
More informationICL Three Pump Controller
ICL Three Pump Controller Pump Operation The number of pumps that the program controls can be selected by enabling only the ones that are currently installed and in service. The enable/disable setting
More informationBoosterpaQ - Hydro MPC
GRUNDFOS INSTRUCTIONS BoosterpaQ - Hydro MPC Installation and operating instructions LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only
More informationGRUNDFOS INSTRUCTIONS. Hydro MPC. Installation and operating instructions
GRUNDFOS INSTRUCTIONS Hydro MPC Installation and operating instructions Declaration of Conformity We, Grundfos, declare under our sole responsibility that the products Hydro MPC, to which this declaration
More informationAPP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0
APP EOLE4 Applicable to program versions TAC5 Version DT 2.8.2 & DG 2.7.0 2 THE APP EOLE4 INTERFACE This interface can be used on Android, IOS and PC. Download the app from the App Store/Google Play or
More informationBoosterpaQ - Hydro MPC
GRUNDFOS INSTRUCTIONS BoosterpaQ - Hydro MPC Installation and operating instructions LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only
More informationAutomatic Genset Controller, AGC-4 Display readings Push-button functions Alarm handling Log list
OPERATOR'S MANUAL Automatic Genset Controller, AGC-4 Display readings Push-button functions handling Log list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com
More informationECL Comfort 310, application A361
Operating Guide ECL Comfort 310, application A361 1.0 Table of Contents 1.0 TableofContents...1 1.1 Importantsafetyandproductinformation... 2 2.0 Installation...5 2.1 Beforeyoustart... 5 2.2 Identifyingthesystemtype...
More informationRVD110 RVD G2381en. Installation. Commissioning
4 319 2788 0 G2381en en Installation Instructions District heating and d.h.w. controller RVD110 RVD130 Installation Place of installation In a dry room, e.g. the heat exchanger room Mounting choices: -
More informationInstructions EKC 313. Dimensions. Identification 084B7253. Principle
Instructions EKC 313 Identification Dimensions 084B7253 Principle EKC 313 Additional information Manual RS8FZ--- Weitere Information Manual RS8FZ--- Renseignements supplémentaires: Manual RS8FZ--- Yderligere
More informationG2515. Installation. Place of installation. Electrical installation. Permissible cable lengths. Securing the controller to the base
74 319 726 G2515 en Installation Instructions District heating controller for 2 heating circuits and d.h.w. RVD26 Keep these instructions with the controller! Installation Place of installation In a dry
More informationRVD G2383en. Installation. - Compact station - Control cabinet (in the front, on the inner wall or on a
4 319 2968 0 G2383en en Installation Instructions District heating controller for one heating circuit and d.h.w. RVD230 Installation Place of installation In a dry room, e.g. in the heat exchanger room
More informationSE8300 Series Installation Guide 24 Vac Low Voltage
Installation Guide 24 Vac Voltage mercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Configurable BI/UI Universal Inputs Overview 3 Setup Screen Display 3 Terminal Identification
More informationVission 20/20 micro-controller. Operation and service manual
Vission 20/20 micro-controller Operation and service manual Section Title Table of Contents Section Number How To Use This Manual...TOC-8 Section 1 Operational Flow Charts Requirements to Start Compressor...1-1
More informationWelcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.
Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module. 1 Upon the completion of this module, you will be able to describe the
More informationBKF Control Panel Instruction Manual for the Owners
1 Contents 2 Exploitation and maintenance... 2 2.1 Control Panel (CP)... 2 2.1.1 Panel Operation... 2 2.1.2 Start Page... 2 2.1.3 Stands... 3 2.1.4 Osmosis... 3 2.1.5 Diagnostics... 4 2.1.6 Engine speed...
More informationSuperheat controller EKC 315A
User Guide Superheat controller EKC 315A The controller and valve can be used where there are requirements to accurate control of superheat and temperature in connection with refrigeration. E.g.: Cold
More informationRVD235. G2385en. Installation without base
2382Z04 G2385en en Installation Instructions District heating controller for one heating circuit and d.h.w. RVD235 Installation without base Place of installation Compact station front or control panel
More informationVisionPRO 8000 Thermostats
VisionPRO 8000 Thermostats INSTALLER SETUP AND SYSTEM TEST POCKET GUIDE 62-0266 INSTALLER SETUP 1. Press SYSTEM. FAN ON AUTO Inside SYSTEM HEAT AM SCHED HOLD M24079 2. Press and hold these two blank buttons
More informationOPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets
Art. nr. 40200261 OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets WHISPERPOWER BV Kelvinlaan 82 9207 JB Drachten Netherlands Tel.: +31-512-571550 Fax.: +31-512-571599
More informationFunctional Performance Test
Functional Performance Test FT: 15540 ITEM: Pumps (HVAC) ID: AREA SERVED: Form Filled Out By: Name & Company Date GC MC EC BC CC OR A/E CA GC = General Contractor; MC = Mechanical Contractor; EC = Electrical
More informationMiG2 TIME SWITCHES. 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches
MiG2 TIME SWITCHES 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches The MiG2 series of timers are programmable 365-day time-switches, incorporating: Multiple switching times per day Single and block
More informationCRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE, CME
GRUNDFOS INSTRUCTIONS CRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE, CME 1 & 3 phase Installation and operating instructions 2 English (US) Installation and operating instructions Original installation and operating
More informationModbus Integration Integration for Modbus Functionality for VT8600 Series
Modbus Integration Integration for Modbus Functionality for VT8600 Series Building Management System *For data visualization and analysis Modbus Controller VT8000 Series room controllers 2 TABLE OF CONTENTS
More informationRVD120 RVD G2510. Installation. Place of installation. Electrical installation. Permissible cable lengths
en Installation Instructions District heating and d.h.w. controller 74 39 68 G25 RVD2 RVD4 Keep these instructions with the controller! Installation Place of installation In a dry room, e.g. the heat exchanger
More informationCompany name: GSI Created by: Xiao Ying Wong Phone: Date: 10/03/2017 Client: Client Number: Contact:
Position Qty. Description 2 NBG 125-8-16/156 A-F2-A-BAQE Product No.: On request Non-self-priming, single-stage, centrifugal volute pump designed according to ISO 5199 with dimensions and rated performance
More informationELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE A
ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE 012945A0 040906 1 MAIN FEATURES Power supply 230V~ ±10% 50Hz Backlit alphanumeric LCD display Management of 5 output
More informationINSTALLATION AND OPERATION INSTRUCTION
INSTALLATION AND OPERATION INSTRUCTION ATi Max 2-1/2-6, 65-150mm Install the ATi Max valve either in the supply or return pipework for the unit. It is recommended that a strainer be installed prior to
More informationTemperature Controller OVATION 214 User's Guide
Temperature Controller User's Guide Read this guide carefully before using the controller. 890-00045 rev.00 TABLE OF CONTENTS Page TABLE OF CONTENTS... 2 PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE
More informationRVD125/109 RVD145/109
G2511 en Installation Instructions District heating and d.h.w. controller RVD125/109 RVD145/109 Installation without base Place of installation Compact station front or control panel front Permissible
More informationDTR CG OPTIMA ver.3.0 ( )
Compact controlling units of supply as well as supply and exhaust air-handling units VS 10 75 CG OPTIMA VS 40 150 CG OPTIMA SUP VS 40 150 CG OPTIMA SUP EXH Operating and maintenance manual DTR CG OPTIMA
More informationCURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING
AUGUST, 2004 REV.A CURTIS TOLEDO OPERATOR S MANUAL SUPPLEMENT AF Series Compressors VS models with VFD WARNING Personal injury and/or equipment damage will result by failing to pay attention to the vital
More informationSTRA-24 for chilled beams
STRA- Installation and commissioning manual STRA- for chilled beams STRA- is the room controller for the pressure independent (Pi) and constant air volume chilled beams. It is possible to set different
More informationVission 20/20 micro-controller. Operation and service manual Version 2.6
Vission 20/20 micro-controller Operation and service manual Version 2.6 Important Message READ CAREFULLY BEFORE OPERATING YOUR COMPRESSOR. The following instructions have been prepared to assist in operation
More informationVolkswagen Information System. Introduction
Volkswagen Information System Introduction In this section you ll find information about: Using the instrument cluster menus: Basic version Using the instrument cluster menus: Premium version with multi-function
More informationFKP-R/R2. User Guide for Pressure and Temperature controller with integrated pressure sensor
FKP-R/R2 User Guide for Pressure and Temperature controller with integrated pressure sensor Rev 1.6 Frabil El AB Phone: +46 40-287090 Bjurögatan 38 Fax: +46 40-184709 2 FKP-R2 FUNCTION FKP-R/R2 is a complete
More informationDigital Diesel Control Remote control panel for GENVERTER GV4 and GV7i
OPERATING MANUAL Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i Art. nr. 40200801 WHISPER POWER BV ENGLISH: PAGE 1 Kelvinlaan 82 9207 JB Drachten NEDERLANDS: PAGINA 41 Netherlands
More informationTemperature Controller. TC5+2V4SA Plus USER'S MANUAL
Temperature Controller TC5+2V4SA Plus USER'S MANUAL NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject
More informationInstallation, Service, and Troubleshooting Instructions
Installation, Service, and Troubleshooting Instructions Page GENERAL........................................ 2 INSTALLATION................................. 2-4 Zone Controller Placement.......................
More informationITCEMS950 Idle Timer Controller - Engine Monitor Shutdown Isuzu NPR 6.0L Gasoline Engine
Introduction An ISO 9001:2008 Registered Company ITCEMS950 Idle Timer Controller - Engine Monitor Shutdown 2014-2016 Isuzu NPR 6.0L Gasoline Engine Contact InterMotive for additional vehicle applications
More informationGRUNDFOS INSTRUCTIONS. CUE, Hp. Installation and operating instructions
GRUNDFOS INSTRUCTIONS CUE, 0.75-125 Hp Installation and operating instructions English (US) English (US) Installation and operating instructions Original installation and operating instructions. CONTENTS
More informationECON-ZIP-DETF; ZIP PACK
71765-00001_A INSTUTION MANUAL EON-ZIP-DETF; ZIP PAK EON-ZIP-DETF; ZIP PAK Differential Enthalpy with DV apability and TF Spring eturn Actuator ontains: Application This kit offers all the components to
More informationSE8300 Series Installation Guide 24 Vac Low Voltage
SE00 Series Installation Guide Low Voltage mercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation Terminal Identification & Function Terminal identification Wiring Typical Applications
More informationJUMO DSM software. PC software for management, configuration, and maintenance of digital sensors. Operating Manual T90Z001K000
JUMO DSM software PC software for management, configuration, and maintenance of digital sensors Operating Manual 20359900T90Z001K000 V1.00/EN/00661398 Contents 1 Introduction...................................................
More informationYOSHI AWS D3 YoshiAirWaterSystem
Always read the instructions before use YOSHI AWS D3 YoshiAirWaterSystem SERVICE MANUAL 8-10-13-16-20-25 HP Safety Precautions The following safety warnings need to be respected in order to prevent injury
More informationINSTALLER MANUAL USER MANUAL. Contents
Installation & user manual two way Contents INSTALLER MANUAL Important information General 1. Technical data 2. Description Installation: 1. Positioning the unit 2. Connection. 3. Parts description. 4.
More informationOPERATING AND MAINTENANCE INSTRUCTIONS for the GOLD Air Handling Unit, Sizes Applicable to Program Version 1.20 and newer versions
OPERATING AND MAINTENANCE INSTRUCTIONS for the GOLD Air Handling Unit, Sizes 11-52 Applicable to Program Version 1.20 and newer versions Specifications are subject to alteration without notice. www.swegon.se
More informationSMT-AZC INSTALLATION / OPERATION MANUAL
SMT-AZC INSTALLATION / OPERATION MANUAL 22o OFF VERSION 2.0 www.smarttemp.com INTRODUCTION The SMT-AZC thermostat is designed to work with the Smart Temp 24Volt Zone Dampers TERMINAL DESIGNATIONS The SMT-AZC
More information! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.
Technical Information Electric Slide-In Range JES9750AAB/S/W JES9800AAB/Q/S/W JES9860AAB/S/W Due to possibility of personal injury or property damage, always contact an authorized technician for servicing
More informationMetasys Zoning Package Installation
Technical Bulletin Issue Date August 28, 2002 Metasys Zoning Package Installation Metasys Zoning Package Installation...2 Introduction... 2 Key Concepts... 3 Installation Overview... 3 Metasys Zoning Package
More informationEXPERT 2V4SA. Temperature Controller. User s manual CLEAN MODE COMPENSATION HUMIDITY OUTSIDE TEMPERATURE
CLEAN MODE Temperature Controller User s manual CURRENT CONDITIONS ROOM TEMPERATURE PROBE TEMPERATURE OUTSIDE TEMPERATURE RELATIVE HUMIDITY STATIC PRESSURE TIME / DATE SETTINGS SET POINT / CURVE MINIMUM
More informationCombined Ventilation Controller RVWS-T-113HA
Combined Ventilation Controller RVWS-T-113HA 5-stage Control for Power/Natural Applications 1 variable speed stage, 1 curtain winch stage, 1 fixed speed ventilation stage, 1 thermo/mister cycle stage and
More informationTension Control Inverter
Tension Control Inverter MD330 User Manual V0.0 Contents Chapter 1 Overview...1 Chapter 2 Tension Control Principles...2 2.1 Schematic diagram for typical curling tension control...2 2.2 Tension control
More informationSupersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO:
YMC 2 - MOD A STARTUP CHECKLIST Supersedes 160.78-CL2 (512) Form 160.78-CL2 (615) STARTUP CHECKLIST CUSTOMER: JOB NAME: ADDRESS: LOCATION: PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT
More informationService Manual BLACK DIAMOND SERVICE MANUAL. V.160 November
BLACK DIAMOND SERVICE MANUAL V.160 November 2011 www.montrealchargeur.com www.battelec.ca www.doctorfleet.com Page 1/30 1. SAFETY PRECAUTIONS 1 Before to start using the Black Diamond Charger, read these
More informationTemperature Controller TC5-2V8SA USER'S MANUAL. M rev. 03 K rev. 00
Temperature Controller USER'S MANUAL M 890-00174 rev. 03 K 895-00327 rev. 00 TABLE OF CONTENTS Page PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 6 Controller Status Leds... 7 Internal Switches...
More informationDeclaration of Conformity No. 33/2010
tech -1- ST 430 user's manual Declaration of Conformity No. 33/2010 Hereby, we declare under sole responsibility that the ST-430 230V, 50Hz thermoregulator manufactured by TECH, ul. St. Batorego 14, 34-120
More informationGRUNDFOS INSTRUCTIONS MAGNA3. Installation and operating instructions
GRUNDFOS INSTRUCTIONS MAGNA3 Installation and operating instructions English (US) English (US) Installation and operating instructions Original installation and operating instructions. CONTENTS Page 1.
More informationAQUATIC INTELLIGENCE FILTER CONTROL GUIDE
AQUATIC INTELLIGENCE FILTER CONTROL GUIDE Installation and Operations AQUATIC INTELLIGENCE FILTER CONTROL SYSTEM This instruction guide of the Aquatic Intelligence Filter Control System (AIF) is intended
More informationDate: Project #: Engineer: Prepared By: Bid Date: 30 psi pressure relief valve 50 psi pressure relief valve 60 psi pressure relief valve
NEOTHERM Hydronic Boiler NTH Hydronic Boiler Date: Indoor Sizes 285-850 Submittal Data Project #: Engineer: Project Name: Prepared By: Location: Bid Date: Contractor: Standard Equipment Large LCD display
More informationPCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS
PCT plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS Ver. DESCRIPTION The PCT plus is a pressure controller for refrigeration plants that require control in their suction and discharge stages. With
More informationINSTALLATION/OPERATING INSTRUCTIONS VSP. A Variable Speed Pump Control
INSTALLATION/OPERATING INSTRUCTIONS VSP A Variable Speed Pump Control The VSP is a hydronic heating control. The temperature of the heating water is controlled by regulating the speed of a pump which injects
More informationGRUNDFOS INSTRUCTIONS MAGNA3. Installation and operating instructions
GRUNDFOS INSTRUCTIONS MAGNA3 Installation and operating instructions English (US) English (US) Installation and operating instructions Original installation and operating instructions. CONTENTS Page 1.
More informationST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number
ST48-WHUV.12 PID controller Order number 935.15 Wiring diagram Product description This micro-processed controller serves for temperature control at high measuring accuracy. Beside resistance sensors and
More informationWater Specialist CK and EQ Control Valve Programming and Cover Drawing Manual
Water Specialist CK and EQ Control Valve Programming and Cover Drawing Manual Page 2 CK and EQ Manual CK and EQ Manual Page 3 Table of Contents CK Front Cover and Drive Assembly...4 OEM General Programming
More informationE1.x Instruction Manual Supplement for Model 32 and 40
E1.x Instruction Manual Supplement for Model 32 and 40 Installation Note: When a hub is used with conduit connections to the panel, they are to be connected to the conduit before the hub is connected to
More informationMulti Wheel Bluetooth Tire Pressure Monitoring System User Manual Model: External
T P M S Multi Wheel Bluetooth Tire Pressure Monitoring System User Manual Model: External Table of Contents 1. PRODUCT INTRODUCTION... 2 2. NOTICE... 2 3. BLE TPMS SPECIFICATION... 3 4. BLE TPMS PACKAGE...
More informationThermal Solutions Communications Gateway Instruction Manual Part Number Revised: April 13, 2015 Contents
Thermal Solutions Communications Gateway Instruction Manual Part Number 104568-01 Revised: April 13, 2015 Contents 1. Introduction 2 2. ProtoNode Setup 3 3. Wiring 7 4. Commissioning 16 5. Field Validating
More informationUsing the Gratec Gasoline software
Using the Gratec Gasoline software The Gratec Software is a sophisticated yet user friendly program in which configures the Gratec CNG or LPG system to perform with your vehicle. Software version 2.002
More informationREV F2.0. User's Manual. Hydraulic ABS (HABS) Hydraulic Power Brake (HPB) Page 1 of 28
REV F2.0 User's Manual Hydraulic ABS (HABS) Hydraulic Power Brake (HPB) Page 1 of 28 Table of Contents INTRODUCTION...4 Starting TOOLBOX Software... 5 MAIN MENU...6 System Setup... 6 Language... 7 Select
More information32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide
32XR 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide RED ALARM LIGHT LEVEL CONTROLLER H-O-A SWITCHES HORN SILENCE INNER DOOR MOTOR STARTERS WITH INTERCHANGEABLE OVERLOAD MODULES
More informatione-track Certified Driver Operating Manual
e-track Certified Driver Operating Manual Copyright 2016 all rights reserved. Page: Table of Contents System Overview 4 Login 5 Certifying Logs 6 Unidentified Driver Records 8 Requested Edits 9 ECM Link
More informationThe measurements module provides the following engine features information:
1. INTRODUCTION The CEM6 control board is a monitoring network signal and monitoring and control generator feeding device. The device consists of 2 different modules: - Visualization module. The visualization
More informationCombined Ventilation Controller RVWS-T-224HA
Combined Ventilation Controller RVWS-T-224HA 8-stage Control for Power/Natural Applications 2 variable speed stages, 2 curtain winch stages, 2 fixed speed ventilation stages, 1 thermo/mister cycle stage
More informationZIP Economizer Fault Detection and Diagnostics (FDD) Table
Fault Detection and Diagnostics (FDD) Table Fault Detection Problem Diagnostic ction (in addition to alarm stored / transmitted) Potential Cause C Fault Code OT sensor predetermined range O damper returns
More informationPCT-3001 plus. Display LCD
PCT3 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS DESCRIPTION Pressure controller for refrigeration systems capable to control suction (compressors) and discharge (fans) pressures. It is possible
More informationRDG160TU Commercial Thermostat
Document No. 129-588 RDG160TU Commercial Thermostat Selecting Location Install the thermostat about 4 feet (120 cm) above the floor on an inside wall. Ensure that there is free airflow around the thermostat.
More informationAdvanced Genset Controller, AGC 200 Display readings Push-button functions Alarm handling Log list
OPERATOR'S MANUAL Advanced Genset Controller, AGC 200 Display readings Push-button functions Alarm handling Log list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com
More informationT P M S. Multi Wheel Bluetooth. Tire Pressure Monitoring System. User Manual. Model: External
T P M S Multi Wheel Bluetooth Tire Pressure Monitoring System User Manual Model: External Table of Contents 1. PRODUCT INTRODUCTION... 2 2. NOTICE... 2 3. BLE TPMS SPECIFICATION... 3 4. BLE TPMS PACKAGE...
More informationUltiMate Vehicle Systems ultimate-10-edp
UltiMate Vehicle Systems ultimate-10-edp Deluxe Oem upgrade & range extender march 6, 2013 Operation guide Table Of Contents Transmitter Overview...3 Transmitter Functions...4 Other Remote Start Features...5
More informationFlow-compensated temperature controller AVTQ DN 15
Data sheet Flow-compensated temperature controller AVTQ DN 15 Description AVTQ is a self-acting flow-compensated temperature controller primarily for use in district heating systems with plate heat exchangers
More informationSPEEDRIVE INSTRUCTIONS MANUAL
EN SPEEDRIVE INSTRUCTIONS MANUAL Safety warning. The following symbols shown beside a paragraph represent danger warnings associated to the failure to comply with the corresponding instructions. DANGER!
More informationInstallation. Part A, Section 3. This section covers the following unit configurations. 3400V 3500V. Voltage 4. Pump Piston (E, F, G)
Part A, Section 3 Model This section covers the following unit configurations. Voltage 4 300V 3400V 3500V Pump Piston (E, F, G) Manifold Control 4-Port (A) 6-Port (B or C) -Port (S or T) Vista Pattern
More informationTechnician Manual. Electronic Table -Top Autoclaves Models EZ9Plus & EZ11Plus
Technician Manual Electronic Table -Top Autoclaves Models EZ9Plus & EZ11Plus Cat. No. MAN205-0443002EN Rev. E Manufactured by: Tuttnauer Co. Ltd., Har Tuv Industrial zone B P.O.Box 170, Beit Shemesh 99000,
More informationUsing Apollo Solar Remote Monitoring Software
Using Apollo Solar Remote Monitoring Software Apollo Solar, Inc. 23 F. J. Clarke Circle Bethel, Connecticut 06801 USA +1 (203) 790-6400 www.apollosolar.com 1 Overview We will see how all the components
More information1. Connect the Tester to the L300 FS Cuff plug holes. See Figure Figure 11-1: Tester connected to the L300 FS Cuff.
Troubleshooting 11 Using the Tester The Tester is used to troubleshoot if there is a disconnection in one of the FS Cuffs or a faulty RF Stim Unit. The Tester provides audio feedback when connected to
More informationobdtoolshop.co.uk EasyCoding User Manual
EasyCoding User Manual Table of contests 1. Software operating system...2 2. Software download and installation...2 2.1 Software download...2 2.2 Software installation...2 3. Product instruction...6 3.1
More informationSubject Underhood G System Error Codes and Symptoms System or Parts affected
System or Parts affected Index Underhood70G (V90Gxxx) System or Parts affected... 1 Overview... 1 Identifying your System... 1 Retrieving Logged Error Messages... 1 Error Messages... 3 Error Message Table...
More informationOverview of operation modes
Overview of operation modes There are three main operation modes available. Any of the modes can be selected at any time. The three main modes are: manual, automatic and mappable modes 1 to 4. The MapDCCD
More informationParalleling Equipment
Paralleling Equipment PowerCommand Model 300 Digital Master Control Description The PowerCommand TM Digital MasterControl is a microprocessor-based paralleling system component, designed to directly interface
More informationRADION Automatic sprayer control Software version 1.07
RADION 8140 U S E R G U I D E Automatic sprayer control Software version 1.07 Safety information TeeJet Technologies is not responsible for damage or physical harm caused by failure to adhere to the following
More informationQUICK INSTALLATION GUIDE
MANUAL/AUTOMATIC T R A N S M I S S I O N 2 - B U T T O N R E M O T E S T A R T E R W I T H V I R T U A L T A C H S Y S T E M ( A S P R G - 1 0 0 0 C O M P A T I B L E ) QUICK INSTALLATION GUIDE Manual
More informationRC-DO. Room controllers with display and manual forced ventilation function
revision 10 2017 RC-DO Room controllers with display and manual forced ventilation function RC-DO is a room controller from the Regio Mini series intended to control heating and cooling in a single zone.
More information