1 GRUNDFOS INSTRUCTIONS Control HVAC Installation and operating instructions Other languages net.grundfos.com/qr/i/

2 English (GB) English (GB) Installation and operating instructions Original installation and operating instructions. These installation and operating instructions describe the Grundfos Control HVAC. Sections 1-6 give the information necessary to be able to unpack, install and start up the product in a safe way. Sections 7-13 give important information about the product, as well as information on service, fault finding and disposal of the product. These instructions are available in other languages. Use the URL or QR code below to download them: CONTENTS Page 1. General information Symbols used in this document Abbreviations used in this document 2 2. Safety instructions 2 3. Receiving the product Inspecting the product 2 4. Installing the product Location Mechanical installation Electrical connection 3 5. Commissioning Configuring the controller Testing the system 8 6. Starting up the product Product introduction Product description System control Pump cascade control Control of the bypass valve Controller reaction time Type key Operating the controller Reading the system status Alarms Operating modes Changing settings Locking and unlocking menus Adding new components to the system Adding new data communication system Servicing the product Maintaining the product Repairing the product Taking the product out of operation Fault finding the product Technical data General CP6606 controller I/O modules and terminals Disposing of the product 19 QR Warning Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice. 1. General information 1.1 Symbols used in this document Note Warning If these safety instructions are not observed, it may result in personal injury. Warning If these instructions are not observed, it may lead to electric shock with consequent risk of serious personal injury or death. If these safety instructions are not observed, it may result in malfunction or damage to the equipment. Notes or instructions that make the job easier and ensure safe operation. 1.2 Abbreviations used in this document BMS CUE GRM HVAC VFD Building management system Grundfos frequency converter Grundfos Remote Management Heating, ventilation and air-conditioning Variable frequency drive 2. Safety instructions Warning The product must be installed and put into operation by a person authorised by Grundfos. Warning Make sure that the power supply cannot be accidentally switched on during electrical installation. 3. Receiving the product 3.1 Inspecting the product Before installation, check that the system is as ordered, and that no visible parts have been damaged. If components are damaged or missing, contact your local Grundfos sales company Scope of delivery Main cabinet installation and operating instructions in English wiring diagram for main cabinet Optional: 1-3 subcabinets differential-pressure sensors temperature sensors flow sensor wiring diagram for subcabinets. 2

3 4. Installing the product 4.3 Electrical connection 4.1 Location The product is not designed for outdoor installation and must not be exposed to direct sunlight. Main cabinet The main cabinet must be installed in a well-ventilated room to ensure sufficient cooling of its components. Install the cabinet so that the user can easily access the touchscreen and switches. The cabinet can be mounted on a wall. Use screws and rawlplugs appropriate to the type of wall. Subcabinets (optional) The subcabinets must be installed in a well-ventilated room to ensure sufficient cooling of its components. The maximum distance to the main cabinet is 100 m (328 feet). The subcabinets can be mounted on a wall. Use screws and plugs appropriate to the type of wall. 4.2 Mechanical installation The Control HVAC is designed exclusively for variable-primaryflow systems. The system must include pumps, chillers, zones, sensors and a bypass valve. See fig. 1. Up to 26 sensors for air-handling zones can be connected to the controller. We recommend that you install differential-pressure sensors in the most critical zones, for example those located the farthest from the chillers. Fig. 1 Example of variable-primary-flow HVAC system with 3 pumps, 3 chillers and 3 air-handling zones Pos. Temperature sensor Flow sensor Differential-pressure sensor Bypass valve Isolating valve of the chiller Speed-controlled pump Chiller T F CHILLER CHILLER CHILLER T Air-handling zone: air-handling unit (AHU), fan coil, etc. T M ZONE ZONE ZONE Up to 8 pumps Up to 8 chillers Up to 26 zones T F M CHILLER ZONE TM Warning The electrical installation must be carried out by an authorised person in accordance with local regulations and the relevant wiring diagram. Warning During electrical installation, make sure that the power supply cannot be accidentally switched on. Before connecting your devices to the main cabinet and the subcabinets, check that the following requirements are met: The electrical installation must comply with enclosure class IP54 or UL type 3R. The supply voltage and frequency must correspond to the values stated on the nameplate. The wire cross-section must correspond to the specifications in the wiring diagrams. The type of control and/or feedback signal of your devices must correspond to your Control HVAC version. The signals are described in the table below: Available signal Device Standard Control HVAC Option Grundfos E- pumps or CUE GENIbus External VFD 0-10 V Bypass valve 4-20 ma 0-10 V Main cabinet Connect the following devices to the terminals in the main cabinet according to the wiring diagram delivered with your product. power supply Grundfos E-Pumps, CUE or VFD differential-pressure sensors (pumps, chillers and the two first air-handling zones) chiller on/off signals (from chiller controller, BMS or isolating valve) bypass valve. Optional Temperature sensor(s) flow sensor external emergency switch for system external emergency switches for pumps. Note Grundfos E-pumps and CUE: Make sure that each pump has a unique GENIbus address (1 to 8), and that the pump is connected to the corresponding terminal. If there is only one air-handling zone in your system, you can connect a redundant differential-pressure sensor for the zone. Connect the redundant sensor to the terminal for the sensor of the second air-handling zone. Subcabinets (optional) Connect the following devices to the subcabinets according to the wiring diagram delivered with your product. power supply EtherCAT cable to main cabinet EtherCAT cable to the next subcabinets, if any differential-pressure sensors (air-handling zones). English (GB) 3

4 English (GB) 5. Commissioning After connecting the power supply and all the devices to the cabinet, you must configure the controller and check that all components of the system are connected properly to the controller and that they function correctly. Warning The product must be installed and put into operation by a person authorised by Grundfos. Switch off all chillers, pumps and air-handling zones and set the system selector switch on the main cabinet to "Off". Text Enable pump changeover Time of day for changeover Enable fixed intervals for periodic stop attempts Interval between stop attempts Set a check mark if you want the controller to automatically change the operating pump after a defined time. Enter the time for pump changeover (1-24) Set a check mark if you want the controller to check at fixed intervals whether a pump can be stopped for better efficiency. Set the interval in minutes. 5.1 Configuring the controller It is important to follow these steps in the correct order to successfully configure the controller. To start the configuration, switch on the controller via the main switch on the front panel Setting the controller clock 1. Press the clock in the bottom left corner. See fig In the new window, press [date/time]. 3. Enter date and time. 4. Press [Apply]. 5. Press [x] to close the window. Pump ramp up/ ramp down time Min. time between start and stop Stop speed Start speed Cut-out speed Enter the time for the pump ramp up (time for the pump to accelerate to its operating speed) and ramp down (time for the pump to decelerate to its stop speed). Enter the minimum time in seconds for a pump to stop after having started. Enter the speed at which the pump is to be stopped. Enter the speed at which the pump is to be started. Enter the speed at which a pump is to be cut out. Cut-in speed Enter the speed at which a new pump is to be cut in. Fig. 2 Clock Setting the pump cascade control 1. Press [Settings] [Pump cascade control]. 2. Enter the parameters using the table below. 3. Press [Save]. TM For more information about the pump cascade control, see section 7.3 Pump cascade control Tuning the controller 1. Press [Settings] [Controller tuning]. 2. Set the gain (Kp) and the integral time (Ti) for the pump controller and for the main controller. You may need to adjust the values after having started the product. If you want a faster reaction, increase the gain and reduce the integral time. If you want a slower reaction, reduce the gain and increase the integral time. 3. Press [Save] for both controllers. TM Fig. 3 Pump cascade control TM Fig. 4 Text Kp (x - y) Ti (x - y) Controller tuning Enter the gain. The value must be between x and y. Enter the integral time. The value must be between x and y. 4

5 5.1.4 Enabling and disabling data logging 1. Press [Settings] [Data log]. 2. Set a check mark if you want data logging. Data logging requires a USB stick plugged into the controller. See section 12.2 CP6606 controller. 3. Press [Save] Selecting the communication channels 1. Press [Settings] [Communication channels]. 2. Select your communication system. 3. Press [Save]. Fig. 5 Text Enable/disable communication channels Enter the AMS address Communication channels Set a check mark if you want to enable communication between the controller and the remote management system. Only enter a new AMS address when replacing the controller. The original controller has been given an AMS address from factory. TM Locking a menu 1. Press [Settings] [Passwords]. 2. In "Menu", set a check mark in "Enable/Disable". 3. Enter a password (maximum four digits). 4. Press [Save]. 5. Press [Status]. The menu is now locked. It is no longer possible to press the menu button in the sidebar. Note: When the setting menu is locked, it is still possible to press [Settings] [Passwords]. Unlocking a menu temporarily 1. Press [Settings] [Passwords]. 2. In menu "Password status", enter the password. 3. Press [Unlock]. The menu is now unlocked. The menu will be locked again when you go to the "Status" menu. Unlocking a menu permanently 1. Press [Settings] [Passwords]. 2. In "Menu", remove the check mark in "Enable/Disable". 3. Enter the password. 4. Press [Save]. The menu is now unlocked and the password is erased Configuring the application Before entering the settings related to each device, you must configure the system according to your application: 1. Press [Application configuration]. 2. Enter the system parameters using the table below. 3. If status says "OK", press [Save]. If not, check that the values entered are correct, or that the devices are connected properly to the cabinet. English (GB) Selecting units 1. Press [Settings] [Units]. 2. Select SI (metric system) or US (imperial system) to set the units automatically, or use the drop-down menus to select your preferred units. 3. Press [Save] Locking menus You can set two passwords to control the access to the following menus: Operation Configurations and settings. Fig. 7 Application configuration TM Text Number of pumps Enter the number of pumps connected to the controller. Number of chillers Enter the number of chillers connected to the controller. Zone sensors, main cabinet Enter the number of sensors of air-handling zones connected to the main cabinet. Fig. 6 Password menu TM Zone sensors, subcabinets Status Enter the number of sensors of air-handling zones connected to the subcabinets. Enter 0 if there are no subcabinets. The controller checks that the values entered correspond to the connections at the terminals. If the status is not OK, check that the values are correct and/or that the connection is well established. 5

6 English (GB) Setting the pumps 1. Press [Configuration]. 2. Press the pump icon. 3. Enter the settings using the table below. 4. Press [Save]. 5. Repeat steps 1-3 for the other pumps, if any Setting the chiller sensors 1. Press [Configuration]. 2. Press the chiller icon. 3. Enter the settings using the table below. 4. Press [Save]. 5. Repeat steps 1-3 for the other chillers, if any. TM TM Fig. 8 Setting the pump Fig. 9 Setting the chiller sensor Text Pump number Select Genibus number Enable VFD alarms Enable Genibus alarms Max. head Max. flow Max. power Number of the selected pump Set a check mark if you want the pump to be part of the pump system. If you leave the box empty, the pump is ignored. GENIbus number of the selected pump Versions with VFD only: Set a check mark if you want the controller to register alarms related to the VFD and report them in the "Alarms" menu. Versions with E-pumps or CUE only: Set a check mark if you want the controller to register alarms related to the E-pumps/ CUE and report them in the "Alarms" menu. Enter the maximum head in the pressure unit selected in the "Units" menu. Enter the maximum flow rate in the unit selected in the "Units" menu. Enter the maximum power in the unit selected in the "Units" menu. Text Chiller number Select Enable sensor alarm Sensor range Min. Max. Fault signal Number of the selected chiller Set a check mark if you want the sensor to be part of the system. If you leave the box empty, the sensor is ignored. Set a check mark if you want the controller to register alarms related to the sensor and report them in the "Alarms" menu. Enter the maximum pressure that can be measured by the sensor in the unit selected in the "Units" menu. Enter the minimum pressure allowed through the chiller in the unit selected in the "Units" menu. Enter the maximum pressure allowed through the chiller in the unit selected in the "Units" menu. Enter the pressure that the controller is to use as reference in the event of sensor failure. 6

7 Setting the zone sensors 1. Press [Configuration]. 2. Press the icon for air-handling zones. 3. Enter the settings using the table below. 4. Press [Save]. 5. Repeat steps 1-3 for the other zones, if any Setting the bypass valve 1. Press [Configuration]. 2. Press the icon for the bypass valve. 3. Enter the settings using the table below. 4. Press [Save]. English (GB) Fig. 10 Setting the zone sensor TM Fig. 11 Setting the bypass valve TM Text Zone number Select Enable sensor alarm Sensor range Reference Fault signal The number of the selected zone Set a check mark if you want the sensor to be part of the system. If you leave the box empty, the sensor is ignored. Set a check mark if the controller is to register alarms related to the sensor and report them in the "Alarms" menu. Enter the maximum pressure that the sensor can measure in the unit selected in the "Units" menu. Enter the differential pressure required by the air-handling zone. It is the reference for the controller. Enter the pressure that the controller is to use as reference in the event of sensor failure. If you want to stop the flow through the zone when its sensor fails, enter a value greater than the reference value. If you want the flow to continue through the zone, enter a reasonable value, for example the most frequently measured value. Text Enable feedback Enable sensor alarm Type Gain factor Gamma Deadband Set a check mark if there is a position feedback connected to the controller. Set a check mark if you want the controller to register alarms related to the bypass valve and report them in the "Alarms" menu. Select the type of bypass valve. Enter the gain factor for the valve. The higher the gain factor, the faster the bypass valve reacts.* Enter the gamma factor of the valve. This value can be found in the instructions for the bypass valve.* Note: For linear types of valve, gamma is 0. Enter the deviation in bar between the reference and the measured differential pressure across the air-handling zones within which the bypass valve must not react. Enter a value in the unit selected in the "Units" menu. We recommend a deadband of 10 % of the maximum reference required by your airhandling zones.* * For more information about the gain factor, gamma factor and deadband, see section 7.4 Control of the bypass valve. 7

8 English (GB) Setting the flow sensor 1. Press [Configuration]. 2. Press [FS]. 3. Enter the settings using the table below. 4. Press [Save]. Fig. 12 Setting the flow sensor Text Select Type Sensor range Set a check mark if you want the sensor to be part of the system. If you leave the box empty, the sensor is ignored. Select the sensor type. Enter the maximum flow rate that the sensor can measure in the unit selected in the "Units" menu Setting the temperature sensor 1. Press [Configuration]. 2. Press [TS1]. 3. Enter the settings using the table below. 4. Press [Save]. 5. Repeat steps 1-3 for TS2 and TS3. TM TM Testing the system Testing the connections Test all analog and digital inputs using the LEDs on the terminals. See section 12.3 I/O modules and terminals for a detailed description of the terminals and LEDs. For each device, check the following: The device has been connected to the right terminal. Example: LED 1 receives signals from chiller 1, LED 2 from chiller 2, etc. The signal is rational. Digital inputs Switch off all chillers, pumps and air-handling zones and set all pump selector switches on the main cabinet to "Off". Set the system selector switch to "Manual/Local". Do not switch on the chillers to test their connections. Open and close the isolating valves of the chillers instead. Switch each device on and off, one at a time, to test the digital inputs. Analog inputs Check that the LEDs indicate the status of the sensors and bypass valve. Version with VFD: As you must not start the pumps at this point, you cannot check the analog signal from the VFD. You can do this when you start the pumps for the first time. See section Testing the pumps Testing the bypass valve 1. Set the operating mode of the bypass valve to "Manual": Press [Operation]. Press the icon for the bypass valve. Select "Manual" and enter a value between 0 and 100, i.e. the valve opening in percentage. Press [Save]. 2. Check that the bypass valve changes its position according to the setting. You may have to remove the cover of the bypass valve. 3. Bypass valves with position feedback: Press [Status] and check that the value shown next to the icon for the bypass valve corresponds to the setting. See section 8.1 Reading the system status. Bypass valves without position feedback: Disregard this step. Fig. 13 Setting the temperature sensor Text Sensor number Select Sensor range Offset Number of the selected temperature sensor Set a check mark if you want the sensor to be part of the system. If you leave the box empty, the sensor is ignored. Enter the maximum temperature that the sensor can measure in the unit selected in the "Units" menu. Enter the temperature offset, if any, in the unit selected in the "Units" menu. 8

9 5.2.3 Testing the pumps Set all pump selector switches on the main cabinet to "Off". Versions without pump selector switches: Disconnect all pump wires (24 V) from the terminals "Auto pump X". See the wiring diagram delivered with the product. Versions with pump selector switches on the main cabinet 1. Set the bypass valve position to 100 %. See step 1 in section Testing the bypass valve. 2. Set a low speed for all pumps: Press [Operation]. Press the first pump icon. Select "start" and in the field "Manual speed", enter a low value in percentage, for instance 20 % of the maximum speed. Press [Save]. Repeat this step for all pumps. 3. Open the isolating valve of one chiller. Do not start the chillers. Note: The controller prevents the pumps from starting if the isolating valves of all other chillers are closed. 4. Set the first pump selector switch to "Manual". 5. Switch on the pump system. 6. Check that the first pump starts and runs at the selected speed. Depending on the product, you can read the pump speed on the following: Grundfos CUE: Grundfos E-pumps: External VFD: Display Grundfos GO See the product manual. 7. Press [Status] and check that the pump icon is green and that the measured speed displayed on the icon is correct. 8. Set the pump selector switch to "Off" to switch the pump off. 9. Follow steps 4 to 8 to test the other pumps, one at a time. Make sure to set each pump selector switch to "Off" after testing the pump and before testing the next one. Versions without pump selector switches 1. Set the bypass valve position to 100 %. See step 1 in section Testing the bypass valve. 2. Set a low speed for all pumps: Press [Operation]. Press the first pump icon. Select "start" and in the field "Manual speed", enter a low value in percentage, for instance 20 % of the maximum speed. Press [Save]. Repeat this step for all pumps. 3. Set pump 1 to manual mode: Connect the wire (24 V) for pump 1 to the terminal "Manual pump 1". See the wiring diagram delivered with the product. 4. Open the isolating valve of one chiller. Do not start the chillers. Note: The controller prevents the pumps from starting if the isolating valves of all other chillers are closed. 5. Switch on the pump system. 6. Check that the first pump starts and runs at the selected speed. Depending on the product, you can read the pump speed on the following: Grundfos CUE: Grundfos E-pumps: External VFD: Controller display Grundfos GO See the product manual. 7. Press [Status], and check that the pump icon is green and that the measured speed displayed on the icon is correct. 8. Switch off the pump system. 9. Set pump 1 to "Auto" mode: Disconnect the wire (24 V) from the terminal "Manual pump 1". See the wiring diagram delivered with the product. 10. Follow steps 3 to 9 to test the other pumps, one at a time. Make sure to disconnect the pump wire (24 V) from the terminal "Manual pump X" after testing each pump and before testing the next one. Note VFD: If no value is displayed on the touchscreen, check the connections via the LEDs of the terminals corresponding to the analog signal from the VFD. See section 12.3 I/O modules and terminals Testing the pump cascade 1. Versions with pump selector switches: Set all pump selector switches to "Auto". Versions without pump selector switches: Connect all pump wires (24 V) to the "Auto pump X" terminals. See the wiring diagram delivered with the product. 2. Open the isolating valve of one chiller. Do not start the chiller. Check that at least one pump is starting. 3. Open the other isolating valves one at a time and check that the pump system reacts normally. Pumps must cut in and/or increase in speed. See section 7.3 Pump cascade control Testing the overall system 1. Open some of the isolating valves of the chillers, for example half of them. Do not start the chillers. 2. Set the operating mode of the bypass valve to "Auto": Press [Operation] and press the icon for the bypass valve. Select the operating mode "Auto". 3. Change the cooling load, for example by turning on and off some air-handling zones or fan coils. Check that the system reacts correctly: Check that the value of the sensors is rational. Check that the colour of the device icons corresponds to the status of the devices. Check that the bypass valve opens when necessary. 4. Turn on all air-handling zones. 5. Switch on the chillers one at a time and check that the system reacts correctly. The system is now ready to start. English (GB) 9

10 English (GB) 6. Starting up the product Before starting up the system, make sure that it has been tested by an authorised person. See section 5. Commissioning. 1. Switch on the controller via the main switch on the front panel. 2. Check the following: The pump selector switches have been set to "Auto". Disregard this step if your cabinet does not have pump selector switches. The system selector switch has been set to "Manual/Local" or "Auto/Remote", depending on your configuration. See section Pump operating modes. The operating mode of the bypass valve has been set to "Auto": Press [Operation], press the icon for the bypass valve and check the operating mode. 3. Switch on the pumps. 4. Switch on all air-handling zones. 5. Switch on the chillers one at a time. 7. Product introduction 7.1 Product description The Control HVAC is designed to optimise pump operation in variable-primary-flow systems, as part of air-conditioning systems. It controls speed-controlled pumps and a bypass valve placed between the flow pipe and return pipe of the air-handling zones. According to the demand from the air-handling zones, the Control HVAC operates the pumps in the most efficient way. Additionally, when the demand is too low, the controller adjusts the opening of the bypass valve to ensure a minimum flow through the operating chillers. The Control HVAC can support the following: eight speed-controlled pumps: Grundfos E-pumps, Grundfos pumps with CUE or other pumps with VFD (0-10 V) eight chillers 26 air-handling zones. The main cabinet supports the connection to two differentialpressure sensors for air-handling zones. More sensors can be connected via up to three subcabinets connected to the main cabinet via an EtherCAT cable. 7.2 System control The air-handling zones, chillers and isolating valves are controlled by a building management system. The Control HVAC controls the pumps and the bypass valve, based on the feedback from the sensors and isolating valves of the chillers. The cooling load from the air-handling zones determines the number of chillers in operation. According to the number of chillers in operation, the controller adapts the pump operation to maintain a differential flow across the chillers within the allowed range. The controller then adjusts the pump operation further to reach the demand from the air-handling zone with the largest difference between its reference and its actual value. When the flow demand from the zones is lower than the minimum flow rate required across the chillers, the controller opens the bypass valve and hence maintains a minimum flow through the chillers. Fig. 14 Variable-primary-flow system with three pumps, three chillers and three air-handling zones 7.3 Pump cascade control The Control HVAC is designed to control Grundfos E-pumps and CUE frequency converters, as well as other types of pumps with variable frequency drives (VFD). The performance is adjusted to the demand through cutting pumps in or out and through parallel control of the pumps in operation. The Control HVAC maintains a constant pressure through continuous adjustment of the speed of the pumps. Pump changeover is automatic and depends on load, operating hours and fault. All operating pumps run at the same speed. The number of pumps in operation also depends on the energy consumption of the pumps. If only one pump is required, two pumps will run at a lower speed if this results in a lower energy consumption. Examples of operation with one and three E-pumps: H H set Fig. 15 One E-pump in operation H H set Fig. 16 Three E-pumps in operation T F Pump start, stop, cut-out and cut-in speeds When the speed of the operating pumps reaches the cut-in speed, a new pump is cut in. The pump starts at its start speed and accelerates until it reaches the speed of the operating pumps. This is called ramp up. When the speed of the operating pumps reaches the cut-out speed, a pump is cut out. The pump decelerates until it reaches its stop speed and stops. This is called ramp down. CHILLER CHILLER CHILLER T T M ZONE ZONE ZONE Q Q TM TM TM

11 7.4 Control of the bypass valve The controller takes the characteristics of the bypass valve into consideration when adjusting the valve position Gamma There are two types of bypass valve: linear and equal percentage. Linear valves open linearly from 0 to 100 %, whereas equal percentage valves open exponentially. This exponential characteristic, called gamma, can be different from valve to valve, and the controller takes this into consideration when calculating the valve position Deadband When the differential pressure measured across the air-handling zones differs from the reference value, the controller adjusts the position of the bypass valve in order for the measured pressure to reach the reference. In order to prevent the bypass valve from opening and closing too frequently, which could wear the valve, the controller does not adjust the valve position within a certain deviation between the reference and the measured value. This deviation is called deadband. Example A system has three zone sensors with reference values of 2, 3 and 4 bar. If the deadband has been set to 0.4 bar, the bypass valve does not react when the measured value is between 3.6 and 4.4 bar. Note: The reference for the controller is the zone with the largest difference between its reference value and the its actual value Gain factor The gain factor determines how quickly the bypass valve reacts to a change in the differential pressure measured across the airhandling zones. The higher the gain factor, the faster the bypass valve reacts. A high gain factor may, however, result in a unstable system. 7.5 Controller reaction time The system includes a standard proportional-integral (PI) controller which ensures that the pressure is stable and corresponds to the setpoint. It involves two parameters that can be adjusted to obtain a faster or slower reaction to changes of consumption, i.e. the gain (Kp) and the integral time (Ti). To obtain a faster reaction, increase Kp and reduce Ti. To obtain a slower reaction, reduce Kp and increase Ti. Setting range of main controller Gain Kp: Integral time Ti: 2 to 80 seconds. Setting range of pump controller Gain Kp: Integral time Ti: 0.1 to 20 seconds. 7.6 Type key Example: Control HVAC 3x x380 Type 3R OPT Type range Number of pumps (2x - 8x) Current range of pumps in Ampere (A) Supply voltage Panel type: Type 3R (UL) or IP54 (IEC) OPT: Optional equipment. See the nameplate. 8. Operating the controller The front door of the cabinet hosts the user interface where you can read the system status and alarms, and change settings and operating modes. 8.1 Reading the system status To read the system status, press [Status] on the touchscreen. The table below describes the different elements that can be read on the status screen. Fig. 17 "Status" menu Text Mode R M Temp. 1 Temp. 2 Temp. 3 Flow rate Spec. energy System operating mode: "Remote", "Local" or "Off". See section System modes. R: reference value Pumps: The pressure reference currently calculated by the controller for the pump system. Chillers: The minimum differential pressure required across the chiller in focus.* Zones: The pressure reference over the airhandling zone in focus.* M: measured value Pumps: The pressure delivered by the pump system. It is equal to the maximum pressure measured across all the chillers. Chillers: The pressure measured across the chiller in focus.* Zones: The pressure measured across the airhandling zone in focus.* The temperature measured at the booster outlet. A temperature sensor must be installed and activated in the "Configuration" menu. The temperature measured at the chiller outlet. A temperature sensor must be installed and activated in the "Configuration" menu. The temperature measured at the outlet of the airhandling zones. A temperature sensor must be installed and activated in the "Configuration" menu. The flow rate measured at the booster outlet. It is equal to the flow rate created by the booster system. A flow sensor must be installed at booster outlet and activated in the "Configuration" menu. The specific energy of the pump system if a flow sensor is installed at the booster outlet and has been activated in the "Configuration" menu. TM English (GB) 11

12 English (GB) Icon Bypass valve Pumps The position of the bypass valve as percentage of its maximum opening. 8.3 Operating modes You can manage the operating modes via the selector switches on the front panel and via the touchscreen. Chillers Zones Green icon and black text: The pump is running, and the measured speed is displayed as percentage of the maximum speed. Green icon and red text: The pump is switched off. Red icon: Alarm. Find more information about the alarm in the "Alarms" menu. Green with pipes at both ends: The chiller is on and is in focus.* The differential pressure measured across the chiller is displayed. Green without pipe: The chiller is on. The differential pressure measured across the chiller is displayed. Blue: The chiller is off. Blue with a cross: The chiller is off and not selected. Red: Alarm. Find more information about the alarm in the "Alarms" menu. Green with pipes at both ends: The air-handling zone is on and is in focus.* The measured differential pressure across the zone is displayed. Green without pipe: The zone is on. The differential pressure measured across the zone is displayed. Blue: The zone is off. Blue with a cross: The zone is off and is not selected. Red: Alarm. Find more information about the alarm in the "Alarms" menu. Fig. 18 "Operation" menu System modes The table below describes the three system operating modes that can be activated with the system selector switch. Mode Auto/ Remote Manual/ Local Off The system operates according to the data collected by the controller. It can be controlled and monitored via the remote management system. The communication to the remote management system is deactivated. The controller operates according to the data configured via the touchscreen only. The user can set a manual setpoint for the pump system and can stop the pump system. The controller is switched off. It cannot be activated via the touchscreen nor by the remote management system. Note: The touchscreen is still on and settings can be changed Pump operating modes The table below describes the three pump operating modes that can be activated via the pump selector switches. Cabinets without pump selector switches are by default set to "Auto". TM * The air-handling zone in focus is the zone in operation with the highest differential pressure. The controller uses this pressure as a reference value for operating the pumps. The chiller in focus is the chiller with the greatest deviation between the minimum differential pressure required and the actual differential pressure. 8.2 Alarms Reading alarms Press [Alarms] to read the alarms status. Press [Logs] to read the alarm log. If the controller registers an alarm for every chiller, it stops the pumps Resetting alarms 1. Press [Alarms]. 2. Select the row of the alarm you wish to reset. 3. Press [Reset]. If the alarm disappears, the controller removes the alarm record. Mode Auto Manual Off The pump is controlled by the internal pump controller and operates as part of the pump cascade system. The pump runs according to the settings set via the touchscreen. It can either start at a selected speed or stop. See section Setting the manual mode of pumps (cabinets with pump selector switches) on page 13. It is not controlled by the internal pump controller and therefore runs independently of the pump cascade system. The pump is switched off. It cannot be started via the touchscreen nor the remote management system. 12

13 Setting the manual mode of pumps (cabinets with pump selector switches) To operate the pump manually, you must configure the manual mode via the touchscreen: 1. Press [Operation]. 2. Press the pump icon. 3. Select "Start" or "Stop". 4. If you have selected "Start", enter a speed for the manual mode as percentage of the maximum speed. If you have selected "Stop", go to step Press [OK]. Setting the operating mode of the bypass valve 1. Press [Operation]. 2. Press the icon for the bypass valve. 3. Select the operating mode: "Auto", "Manual", "Off". 4. If you have selected "Auto" or "Off", go to step 5. If you have selected "Manual", enter a position between 0 and 100, i.e. the valve opening as percentage. 5. Press [OK]. In manual mode, the valve changes to the entered value. English (GB) TM Fig. 19 Setting the manual mode of pumps Operating the pump system in manual mode The pump system can be set to run in manual mode and can be stopped via the touchscreen. 1. Set the system selector switch to "Manual/Local". 2. Set all the pump selector switches to "Auto". Disregard this step if your cabinet does not have pump selector switches. 3. Press [Operation]. 4. Select "Start" if you want to start the pump system. Select "stop" if you want to stop the pump system. 5. In the field "R", enter the reference speed for the pump system as percentage of the maximum speed. 6. Press. If you have chosen "Start", the pump system starts and accelerates until it reaches the reference speed set in step 5. If you have chosen "Stop", the pump system stops Operating modes of the bypass valve The table below describes the three operating modes for the bypass valve that can be activated via the touchscreen. Mode Auto Manual Off The valve is controlled by the controller. The valve is not controlled by the controller, and its position is adjusted according to the manual position set via the touchscreen. The valve cannot be operated by the controller. TM Fig. 20 Setting the operating mode of the valve 8.4 Changing settings Changing the controller clock See section Setting the controller clock Changing pump cut-in and cut-out speed See section Setting the pump cascade control Changing the controller gain and integral time For tuning the pump controller, see section Tuning the controller. For tuning the main controller, see section Tuning the controller Changing sensor fault signals This operation must be carried out by a person authorised by Grundfos. This operation must be carried out by a person authorised by Grundfos. This operation must be carried out by a person authorised by Grundfos. You can adjust the fault signals of the chiller and zone sensors. See section Setting the chiller sensors and Setting the zone sensors. 8.5 Locking and unlocking menus You can set two passwords to control the access to the following menus: Operation Configurations and settings See section Locking menus. 13

14 English (GB) 8.6 Adding new components to the system This operation must be carried out by a person authorized by Grundfos. You can add pumps, chillers, zones and sensors to the system. See section 4.3 Electrical connection. See section 5. Commissioning Adding a subcabinet In order to add zones to your system, you may need to connect a new subcabinet to the main cabinet. Contact your local Grundfos sales company and use the product number below to order a new subcabinet. Product name Product number Kit set extension, I/O Connect an EtherCAT cable from the free ethernet port of the EK1100 bus coupler to one of the ethernet ports of the subcabinet. Connect the zone sensors to the terminals of the subcabinet according to the wiring diagram delivered with the product. Note: The maximum cable length between cabinets is 100 m (328 feet). See section 12.3 I/O modules and terminals. 8.7 Adding new data communication system Contact your local Grundfos sales company in order to add a new communication system. 9.2 Repairing the product Replacing parts Part Whom to contact Remarks Lithium battery for the controller clock Micro SD card I/O modules and terminals Controller including touchscreen Contact the nearest Beckhoff sales company. See Contact your local Grundfos sales company. Contact the nearest Beckhoff sales company. See Contact the nearest Beckhoff sales company. See The battery is located underneath the controller. See fig. 21. The micro SD hosts the Grundfos software. The card is located underneath the controller. See fig. 21. The product name of each terminal is written at the bottom of it. Follow the instructions below when ordering a new controller Ordering a new controller If your controller is defective, contact the nearest Grundfos sales company to order a new one. You will receive a serial number with the new controller. Keep it as you will have to place it on the new controller. 9. Servicing the product Use the URL or QR code below to download the complete service instructions. Warning Before starting work on the cabinets, pumps, bypass valve, etc., switch off the power supply. Lock the main switch with a padlock to ensure that the power supply cannot be accidentally switched on. 9.1 Maintaining the product In order to ensure that the system is operating efficiently and prevent any breakdowns, check the following items regularly. Backup battery Check that the backup battery of the controller is operational. After a few years, it may be necessary to replace the backup battery. See fig. 21. Contact the nearest Beckhoff sales company. See Selector switches Check that all selector switches on the front panel of the cabinet are operational. Test all switch positions. Alarms Check regularly the alarm list and fix the related problems: 1. Press [Alarm]. 2. Fix problems according to the alarm log, if any. 3. Reset each alarm and make sure that it has been removed from the list. See section Resetting alarms. QR Note Do not discard the micro SD card of your controller. It contains the Grundfos firmware that you need for the new controller. 10. Taking the product out of operation Follow these instructions to take the Control HVAC out of operation and remove the cabinet. 1. Switch off all chillers. 2. Switch off all pumps. 3. Switch off the bypass valve. 4. Switch off the system by turning the main switch to position "0". Lock the switch in this position with a padlock. 5. Remove all cables connected to the main cabinet. The Control HVAC has now been taken out of operation and the cabinet can be removed. Warning The conductors in front of the main switch are still energised. Before starting any work on the cabinet, lock the switch with a padlock to ensure that the controller cannot be accidentally switched on. 14

15 11. Fault finding the product Warning Before starting work on the cabinets, pumps, bypass valve, etc., make sure that the power supply has been switched off. Lock the main switch with a padlock to ensure that the power supply cannot be accidentally switched on. English (GB) Fault Cause Remedy 1. The touchscreen is black. The power supply is switched on. 2. The Control HVAC has stopped and cannot be restarted. a) The LED next to the power connection of the controller is off. The controller is defective. b) The LED next to the power connection of the controller is yellow. Power supply failure. Contact your local Grundfos sales company for assistance in ordering a new controller. Check the power supply. a) System bug 1. Stop the chillers. 2. Switch off the power supply by means of the main switch on the cabinet. 3. Wait 20 seconds and switch on the power supply. 4. Start the chillers one at a time. b) The system selector switch on the front panel has been set to "Off". c) The remote management system is switched off. d) The pump selector switches on the front panel have been set to "Off". e) The external emergency switch has been set to "Off". f) The on/off chiller signal is not detected by the controller. All chiller icons are grey on the touchscreen. Chillers are switched off. g) The on/off chiller signal is not detected by the controller. All chiller icons are grey. The chillers are defective. h) The on/off chiller signal is not detected by the controller. All chiller icons are grey. The cables connecting the chillers to the main cabinet are defective. Set the system selector switch to "Manual/Local" or "Auto/ Remote", depending on your configuration. Switch on the remote management system or set the system selector switch on the front panel to "Manual/Local". Set the pump selector switches to "Auto". Set the external emergency switch to "On". Switch on the chillers one at a time. Check the power supply, isolating valve, contactor, etc. of the chiller. Check cables. Repair or replace defective cables. i) Cables are defective. Check cables. Repair or replace defective cables. j) Cables are short-circuited. Check cables. Repair or replace defective cables. Note: Short circuits can occur at the cable ends if wires are crossing each others. k) Voltage drop. The touchscreen may still be on, but the controller does not react properly. Check the power supply. 15

16 English (GB) Fault Cause Remedy 3. The bypass valve does not react. a) The operating mode of the bypass valve is "Manual" or "Off". b) The cables of the bypass valve are defective. c) The cables of the bypass valve are short-circuited. d) The feedback signal of the bypass valve is inaccurate. To find out whether the feedback is inaccurate, test the bypass valve manually. See section Testing the bypass valve. 1. Set the bypass valve to "Auto": 2. Press [Operation]. 3. Press the icon for the bypass valve. 4. Select "Auto". 5. Press [Save]. Check cables. Repair or replace defective cables. Check cables. Repair or replace defective cables. Note: Short circuits can occur at the cable ends if wires cross each others. Replace the bypass valve. e) No power supply to the bypass valve. Check the power supply. f) The fuse of the bypass valve has blown. Replace the fuse. g) The motor of the bypass valve is defective. To find out whether the motor is defective, connect an external power supply to the motor. It may be necessary to remove the cover of the bypass valve. Replace the bypass valve. 4. No sensor signal a) The sensor is not connected properly. Connect the sensor according to the wiring diagram delivered with the sensor and the Control HVAC. Make sure the sensor cable is correctly connected to the terminal in the cabinet. Note: Most differential-pressure sensors must to be connected to a 24 V supply, whereas most flow meters must to be connected to 0 V. b) The sensor cable is defective. Depending on the terminal, the LED of the related sensor is red or off. See section 12.3 I/O modules and terminals. Check cables. Repair or replace defective cables. 5. Irrational sensor signal c) The sensor is defective. Depending on the terminal, the LED of the related sensor is red or off. See section 12.3 I/O modules and terminals. d) Cables are short-circuited. Check cables. Repair or replace defective cables. Note: Short circuits can occur at the cable ends if wires are crossing each others. e) The I/O module is defective. The sensor and the cable are intact. a) The sensor is connected to the wrong terminal. b) The sensor is defective and sends irrational signal to the controller, for instance the measured flow decreases when the pumps speed increase. Contact the nearest Beckhoff sales company for assistance in replacing the I/O module. See Connect the sensor to the correct terminal according to the wiring diagram delivered with the Control HVAC. Replace the sensor. 16

17 Fault Cause Remedy 6. The pump does not start. 7. The pump does not operate correctly. 8. The pump has stopped and does not restart. a) The pump selector switch on the front panel has been set to "Off. b) The cable connecting the E-pumps/CUE/ VFD to the controller is defective (the E- pump/cue/vd does not detect the start/ stop signal sent by the controller) c) Version with VFD: The LED of the I/O module is on when the controller sends a start signal, but the VFD does not detect the start/stop signal sent by the controller. d) Version with VFD: The corresponding EL2008 module is defective. The LED is not on when the controller sends a start signal to the VFD. Set the pump selector switch to "Auto". Check cables. Repair or replace defective cables. Check cables. Repair or replace defective cables. Contact the nearest Beckhoff sales company for assistance in replacing the I/O module. See e) The external pump emergency switch is Check the external emergency switch. defective, if any. f) The E-pump and CUE or VFD are not Check the power supply to the E-pump and CUE or VFD. supplied with power. g) Cables are defective. Check cables. Repair or replace defective cables. h) Cables are short-circuited. Check cables. Repair or replace defective cables. Note: Short circuits can occur at the cable ends if wires are crossing each others. i) The pump is defective. To find out if the pump is defective, test it in manual mode. See section Testing the pumps. Repair or replace the pump. For E-pumps and CUE, contact your local Grundfos sales company. j) System bug 1. Stop the chillers. 2. Switch off the power supply by means of the main switch on the cabinet. 3. Wait 20 seconds and switch on the power supply. 4. Start the chillers one at a time. k) The relay inside the cabinet is defective. Replace the relay. l) The pump selector switch on the front panel has been set to "Manual", and the manual mode defined via the touchscreen has been set to "Stop". a) The E-pump and the CUE or VFD are not configured correctly, for instance with incorrect minimum and maximum speed. a) The controller has registered an alarm and stopped the pumps. If you want to operate the pump in manual mode, set the manual mode to "Start". See section Testing the pumps. If not, set the pump selector switch to "Auto". Check the settings of the E-pump and CUE or VFD. See the "Alarms" menu. Fix the problem if needed. Reset the alarm and check that it has been removed from the list. See section Resetting alarms. English (GB) 17

GRUNDFOS DATA BOOKLET. Control HVAC. For variable-primary-flow systems

GRUNDFOS DATA BOOKLET. Control HVAC. For variable-primary-flow systems GRUNDFOS DATA BOOKLET Control HVAC For variable-primary-flow systems Control HVAC Table of contents 1. Product description 3 Introduction..................................................................................

More information

GRUNDFOS INSTRUCTIONS. Hydro MPC. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Hydro MPC. Installation and operating instructions GRUNDFOS INSTRUCTIONS Hydro MPC Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions These installation

More information

GRUNDFOS INSTRUCTIONS. Hydro MPC. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Hydro MPC. Installation and operating instructions GRUNDFOS INSTRUCTIONS Hydro MPC Installation and operating instructions Declaration of Conformity We, Grundfos, declare under our sole responsibility that the products Hydro MPC, to which this declaration

More information

Service instructions. MAGNA Series 2000

Service instructions. MAGNA Series 2000 Service instructions MAGNA Series 2000 Magna 32-120, 40-120, 50-60, 50-120, 65-60, 65-120 1 phase 50/60 Hz The pump must be serviced by a qualified person. Service must be carried out in accordance with

More information

BoosterpaQ - Hydro MPC

BoosterpaQ - Hydro MPC GRUNDFOS INSTRUCTIONS BoosterpaQ - Hydro MPC Installation and operating instructions LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only

More information

BoosterpaQ - Hydro MPC

BoosterpaQ - Hydro MPC GRUNDFOS INSTRUCTIONS BoosterpaQ - Hydro MPC Installation and operating instructions LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only

More information

CRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE, CME

CRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE, CME GRUNDFOS INSTRUCTIONS CRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE, CME 1 & 3 phase Installation and operating instructions 2 English (US) Installation and operating instructions Original installation and operating

More information

Combined Ventilation Controller RVWS-T-224HA

Combined Ventilation Controller RVWS-T-224HA Combined Ventilation Controller RVWS-T-224HA 8-stage Control for Power/Natural Applications 2 variable speed stages, 2 curtain winch stages, 2 fixed speed ventilation stages, 1 thermo/mister cycle stage

More information

CRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE 1 & 3 phase

CRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE 1 & 3 phase GRUNDFOS INSTRUCTIONS CRE, CRIE, CRNE CRKE, SPKE, MTRE, CIE 1 & 3 phase Installation and operating instructions LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted

More information

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING AUGUST, 2004 REV.A CURTIS TOLEDO OPERATOR S MANUAL SUPPLEMENT AF Series Compressors VS models with VFD WARNING Personal injury and/or equipment damage will result by failing to pay attention to the vital

More information

Company name: GSI Created by: Xiao Ying Wong Phone: Date: 10/03/2017 Client: Client Number: Contact:

Company name: GSI Created by: Xiao Ying Wong Phone: Date: 10/03/2017 Client: Client Number: Contact: Position Qty. Description 2 NBG 125-8-16/156 A-F2-A-BAQE Product No.: On request Non-self-priming, single-stage, centrifugal volute pump designed according to ISO 5199 with dimensions and rated performance

More information

ECL Apex 10. User Guide. ECL Apex 10 *087R9745* Installation and configuration. *vijem102*

ECL Apex 10. User Guide. ECL Apex 10 *087R9745* Installation and configuration. *vijem102* User Guide ECL Apex 10 *087R9745* *vijem102* Installation and configuration VI.JE.M1.02 Danfoss 11/2004 DH-SMT VI.JE.M1.02 Danfoss 11/2004 DH-SMT ECL Apex 10 VI.JE.M1.02 Danfoss 11/2004 DH-SMT VI.JE.M1.02

More information

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0 Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n 107065-01 Revision 0 May 20, 2016 Contents Introduction 2 Installation Pre-installation 3 Installation Procedure 4 Electrical

More information

Grundfos MAGNA, Relay Module

Grundfos MAGNA, Relay Module GRUNDFOS INSTRUCTIONS Grundfos MAGNA, Relay Module Installation and operating instructions 2 Grundfos MAGNA, Relay Module Installation and operating instructions 4 3 LIMITED WARRANTY Products manufactured

More information

HBLT-C1 Controller. Instruction Manual. For pump control of levels in industrial refrigeration systems

HBLT-C1 Controller. Instruction Manual. For pump control of levels in industrial refrigeration systems Instruction Manual HBLT-C1 Controller For pump control of levels in industrial refrigeration systems Instruction manual HBLT-C1 Controller (006-UK) 1 / 14 Table of Contents Safety Instructions... 3 Introduction...

More information

User manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS.

User manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS. User manual Manual version: 2.4 dated 27/02/08 Program code: FLSTDmMCDE LEGGI

More information

GRUNDFOS DATA BOOKLET. Hydro Multi-B. Booster systems with 2 or 3 pumps. 50/60 Hz

GRUNDFOS DATA BOOKLET. Hydro Multi-B. Booster systems with 2 or 3 pumps. 50/60 Hz GRUNDFOS DATA BOOKLET Hydro Multi-B Booster systems with 2 or 3 pumps 50/60 Hz Hydro Multi-B Table of contents 1. Product introduction 3 Applications..................................................................................

More information

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER INSTALLATION AND MAINTENANCE INSTRUCTIONS Risk of electric shock: Motor terminals may still be live if the impeller is rotating, even when

More information

Advanced Variable Torque Application Training Eaton Corporation. All rights reserved.

Advanced Variable Torque Application Training Eaton Corporation. All rights reserved. Advanced Variable Torque Application Training 2012 Eaton Corporation. All rights reserved. Introduction HVAC & some pumping applications frequently include multiple pumps & fans, require redundant drive

More information

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: , Revision 1

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: , Revision 1 Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: 107065-01, Revision 1 March 03, 2017 Contents Introduction 2 Installation Pre-installation 3 Installation Procedure 4 Electrical

More information

AC drive has detected too high a Check loading

AC drive has detected too high a Check loading Fault code Fault Name Fault type Default Possible Cause Remedy 1 Over Current Fault AC drive has detected too high a Check loading current (>4*IH) in the motor cable: Check motor Sudden heavy load increase

More information

PJC321, PJC322 PJC321-L, PJC322-L PJC321-MCL2, PJC322-MCL2 S-link Control Panel

PJC321, PJC322 PJC321-L, PJC322-L PJC321-MCL2, PJC322-MCL2 S-link Control Panel SIDE-POWER Thruster Systems PJC321, PJC322 PJC321-L, PJC322-L PJC321-MCL2, PJC322-MCL2 S-link Control Panel Keep this manual onboard! EN Installation and user s manual SLEIPNER MOTOR AS P.O. Box 519 N-1612

More information

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0 APP EOLE4 Applicable to program versions TAC5 Version DT 2.8.2 & DG 2.7.0 2 THE APP EOLE4 INTERFACE This interface can be used on Android, IOS and PC. Download the app from the App Store/Google Play or

More information

Temperature Controller OVATION 214 User's Guide

Temperature Controller OVATION 214 User's Guide Temperature Controller User's Guide Read this guide carefully before using the controller. 890-00045 rev.00 TABLE OF CONTENTS Page TABLE OF CONTENTS... 2 PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE

More information

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM DSE 520 ISSUE 4 4/4/02 MR 1 TABLE OF CONTENTS Section Page INTRODUCTION... 4 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION.... 4 1. OPERATION...

More information

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO:

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO: YMC 2 - MOD A STARTUP CHECKLIST Supersedes 160.78-CL2 (512) Form 160.78-CL2 (615) STARTUP CHECKLIST CUSTOMER: JOB NAME: ADDRESS: LOCATION: PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT

More information

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00 Inlet Controller TC5-ITA USER'S MANUAL M 890-00047 rev. 02 K 895-00458 rev. 00 TABLE OF CONTENTS PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 5 Status Leds...5 Internal Switches...6 INSTALLATION

More information

MiG2 TIME SWITCHES. 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches

MiG2 TIME SWITCHES. 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches MiG2 TIME SWITCHES 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches The MiG2 series of timers are programmable 365-day time-switches, incorporating: Multiple switching times per day Single and block

More information

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016 PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS v1.1 Revised Table of Contents 1 Common Alarms and Warnings... 1 2 Common Issues... 6 2.1 Communication problems... 6 2.1.1 Controller communication

More information

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD Safety Precautions Read this manual thoroughly before proceeding with installation, connections (wiring), or maintenance and inspection. Ensure you

More information

SI AT A22. English. Printed: Doc-Nr: PUB / / 000 / 01

SI AT A22. English. Printed: Doc-Nr: PUB / / 000 / 01 SI AT A22 English 1 Information about the documentation 1.1 About this documentation Read this documentation before initial operation or use. This is a prerequisite for safe, trouble-free handling and

More information

INSTALLATION INFORMATION

INSTALLATION INFORMATION INSTALLATION INFORMATION BMS ZE6000i-PCBT.xxxx / ver. 2 Programmable battery management system for Lithium Ion battery cells, for up to 32 round or prismatic cells, 10 to 400Ah NOTE: This installation

More information

SI AT A22. English. Printed: Doc-Nr: PUB / / 000 / 03

SI AT A22. English. Printed: Doc-Nr: PUB / / 000 / 03 SI AT A22 English 1 Information about the documentation 1.1 About this documentation Read this documentation before initial operation or use. This is a prerequisite for safe, trouble-free handling and

More information

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL Temperature Controller TC5+2V4SA Plus USER'S MANUAL NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject

More information

Overview of operation modes

Overview of operation modes Overview of operation modes There are three main operation modes available. Any of the modes can be selected at any time. The three main modes are: manual, automatic and mappable modes 1 to 4. The MapDCCD

More information

Delta Products VFD CP2000 Bypass Control Packages.

Delta Products VFD CP2000 Bypass Control Packages. Delta Products VFD CP2000 Bypass Control Packages www.deltaww.com Delta Products VFD CP2000 Bypass Control Packages The Delta Products VFD CP2000 Bypass Control Packages are designed for the Delta Products

More information

CLA-VAL e-drive-34. User Manual. Motorised Pilots. CLA-VAL Europe LIN072UE - 04/16

CLA-VAL e-drive-34. User Manual. Motorised Pilots. CLA-VAL Europe LIN072UE - 04/16 User Manual CLA-VAL Europe www.cla-val.ch cla-val@cla-val.ch 1 - LIN072UE - 04/16 Table of Contents 1 Introduction... 3 1.1 Precautions Before Starting... 3 1.2 Troubleshooting... 3 1.3 General Disclaimer...

More information

1. Product Information

1. Product Information AVS Control Panel 1. Product Information AVS is a pump control panel having 4.3 TFT touch screen, uniquely designed high efficient variable speed control and relay board. The touch control panel is located

More information

GRUNDFOS INSTRUCTIONS. Hydro Multi-B. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Hydro Multi-B. Installation and operating instructions GRUNDFOS INSTRUCTIONS Hydro Multi-B Installation and operating instructions English (US) English (US) Installation and operating instructions Original installation and operating instructions. CONTENTS

More information

ST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number

ST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number ST48-WHUV.12 PID controller Order number 935.15 Wiring diagram Product description This micro-processed controller serves for temperature control at high measuring accuracy. Beside resistance sensors and

More information

GRUNDFOS INSTRUCTIONS. CUE, Hp. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. CUE, Hp. Installation and operating instructions GRUNDFOS INSTRUCTIONS CUE, 0.75-125 Hp Installation and operating instructions English (US) English (US) Installation and operating instructions Original installation and operating instructions. CONTENTS

More information

ECU1000 ELECTRONIC CONTROL UNIT

ECU1000 ELECTRONIC CONTROL UNIT An advanced electronic system capable to be integrated in a SMART Electro Hydraulic System for heavy modulating, stepping, PST, diagnostic and ESD/BDV actions FEATURES GENERAL APPLICATION is a control

More information

TABLE OF CONTENTS General information... 4 Benefits of the system... 4 OPERATION CONCEPT... 5 Algorithm of deactivation... 5 Authorization with the

TABLE OF CONTENTS General information... 4 Benefits of the system... 4 OPERATION CONCEPT... 5 Algorithm of deactivation... 5 Authorization with the OPERATING MANUAL Dear car owner! Please note that the AUTHOR Alarm s anti-theft devices are not intended for self-installation. We strongly recommend to install and configure the purchased equipment only

More information

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL PHASETEC digital power conditioners are designed to safely operate electrical equipment in the harshest power quality environments. With a wide

More information

Inverter / Charger Accessory for Steca Solarix PLI Phase / Parallel Kit. Installation and operating instructions Z01 17.

Inverter / Charger Accessory for Steca Solarix PLI Phase / Parallel Kit. Installation and operating instructions Z01 17. Inverter / Charger Accessory for Steca Solarix PLI 5000-48 3-Phase / Parallel Kit Installation and operating instructions GB Z01 17.31 Table of Contents About this Manual... 2 Purpose... 2 Scope... 2 Keywords

More information

Documentation. RM-BV4 Micro DP. Filter control

Documentation. RM-BV4 Micro DP. Filter control Documentation RM-BV4 Micro DP Filter control Contents 1 Safety instructions... 3 2 Device description... 3 3 Installation... 4 4 Installation... 5 4.1 Connection of the differential pressure measuring

More information

OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets

OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets Art. nr. 40200261 OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets WHISPERPOWER BV Kelvinlaan 82 9207 JB Drachten Netherlands Tel.: +31-512-571550 Fax.: +31-512-571599

More information

RVS-AX Instruction Manual

RVS-AX Instruction Manual RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3

More information

Installation Guide. ECL Comfort 210 / 310, application A231 / A Table of Contents

Installation Guide. ECL Comfort 210 / 310, application A231 / A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 4 2.1 Before you start.....................................................

More information

GRUNDFOS INSTRUCTIONS. MGE model F. s Service instructions, extended

GRUNDFOS INSTRUCTIONS. MGE model F. s Service instructions, extended GRUNDFOS INSTRUCTIONS MGE model F s Service instructions, extended Preface These service instructions describe fault finding and correction of pumps with Grundfos motors, type MGE model F (hereafter called

More information

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology HGM1780 Automatic Genset Controller USER MANUAL Smartgen Technology Smartgen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951

More information

TRIPS AND FAULT FINDING

TRIPS AND FAULT FINDING WWW.SDS.LTD.UK 0117 9381800 Trips and Fault Finding Chapter 6 6-1 TRIPS AND FAULT FINDING Trips What Happens when a Trip Occurs When a trip occurs, the drive s power stage is immediately disabled causing

More information

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

1333 (SERIES B & C) TROUBLESHOOTING GUIDE 1333 (SERIES B & C) TROUBLESHOOTING GUIDE Preventive Maintenance: Problems with Your Drive? Bulletin 1333 is convection or fan cooled by air flowing through the heat sink slots. The slots must never be

More information

TOUCH PLS TOUCHSCREEN PLS A NEW HORIZON IN PROGRAMMABLE LIMIT SWITCHES

TOUCH PLS TOUCHSCREEN PLS A NEW HORIZON IN PROGRAMMABLE LIMIT SWITCHES TOUCH PLS TOUCHSCREEN PLS A NEW HORIZON IN PROGRAMMABLE LIMIT SWITCHES Touchscreen PLS and Graphical Operator Interface in One Unit Five Screen Sizes Available: 5" Color, 6" Monochrome, 8" Color, 9" Monochrome

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

Inlet Controller SB3500 USER'S MANUAL

Inlet Controller SB3500 USER'S MANUAL Inlet Controller USER'S MANUAL NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject to change without notice

More information

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web:  - MAKING MODERN LIVING POSSIBLE Quick Setup VLT FCM 300 Series Factory setting Motors type B14 & B34 mounting Reset (pushbutton) Start Jog Speed reference Fig. 1 - Reset to be closed short time for resetting

More information

Continental Hydraulics Installation Manual CEM-AA-A

Continental Hydraulics Installation Manual CEM-AA-A Continental Hydraulics Installation Manual CEM-AA-A Description: This power amplifier drives either single or dual solenoid proportional valve coils up to 2.6A. It is suitable to control current to proportional

More information

HYDRO BOOSTER RANGE HYDRO MULTI-S HYDRO MULTI-B CME HYDRO MULTI-B CR HYDRO MPC

HYDRO BOOSTER RANGE HYDRO MULTI-S HYDRO MULTI-B CME HYDRO MULTI-B CR HYDRO MPC GRUNDFOS HYDRO BOOSTERS PRE-ENGINEERED FOR ASEAN GRUNDFOS HYDRO BOOSTER RANGE HYDRO MULTI-S HYDRO MULTI-B CME HYDRO MULTI-B CR HYDRO MPC PRE-ENGINEERED BY GRUNDFOS TESTED AND VERIFIED บร ษ ท ด บบล ว พ

More information

SINAMICS GM150 IGCT version

SINAMICS GM150 IGCT version /2 Overview /2 Benefits /2 Design /6 Function /8 Selection and ordering data /8 Options Technical data /14 General technical data /15 Control properties /15 Ambient conditions /16 Installation conditions

More information

SNMP dedicated to ORVALDI Solar Infini

SNMP dedicated to ORVALDI Solar Infini SNMP dedicated to ORVALDI Solar Infini User s Manual Management Software for Solar Inverter Table of Contents 1. 2. 3. Overview...1 1.1 Introduction...1 1.2 Features...1 1.3 Overlook...1 1.4 Installation

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i

Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i OPERATING MANUAL Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i Art. nr. 40200801 WHISPER POWER BV ENGLISH: PAGE 1 Kelvinlaan 82 9207 JB Drachten NEDERLANDS: PAGINA 41 Netherlands

More information

SPREADER SYSTEM. Proportional three function. 1. Features and Specifications. User Manual 12 INPUTS 12 OUTPUTS CONNECTIVITY MAIN FEATURES

SPREADER SYSTEM. Proportional three function. 1. Features and Specifications. User Manual 12 INPUTS 12 OUTPUTS CONNECTIVITY MAIN FEATURES User Manual SPREADER SYSTEM Proportional three function 12 INPUTS 3 interrupt digital inputs. 3 digital inputs for engine control (alternator, accelerator, oil alarm). 1 digital input for tachometer (squared,

More information

:43 1/13 Victron & BYD B-Box

:43 1/13 Victron & BYD B-Box 2018-11-04 15:43 1/13 Victron & BYD B-Box Victron & BYD B-Box The combination of Victron products with BYD B-Box lithium batteries (2.5, 5.0, 7.5, 10.0 and 12.8 models) has been tested and certified by

More information

GRUNDFOS DATA BOOKLET. Grundfos CUE. Frequency converters for pump control. 50/60 Hz

GRUNDFOS DATA BOOKLET. Grundfos CUE. Frequency converters for pump control. 50/60 Hz GRUNDFOS DATA BOOKLET Grundfos Frequency converters for pump control 50/60 Hz Grundfos Table of contents 1. Introduction 3 Grundfos 3 Built-in E-pump functionality 3 Designed for Grundfos pumps 3 Further

More information

User Manual Solar Charge Controller 3KW

User Manual Solar Charge Controller 3KW User Manual Solar Charge Controller 3KW Version: 1.3 CONTENTS 1 ABOUT THIS MANUAL... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 SAFETY INSTRUCTIONS... 1 2 INTRODUCTION... 2 2.1 Features... 2 2.2 Product Overview...

More information

ECL Comfort Installation and Maintenance. User s Guide. ECL Comfort. C60 Double mixing controller C60. Table of Contents. Daily use.

ECL Comfort Installation and Maintenance. User s Guide. ECL Comfort. C60 Double mixing controller C60. Table of Contents. Daily use. ECL COMFORT VI.7C.B4.0 C60 Table of Contents Daily use ECL Comfort User s Guide Section Choose favourite display Select controller mode 3 Adjust room temperature 4 Set personal day plan 5 Advantages of

More information

ECONOMISER SERIES E2T USER MANUAL

ECONOMISER SERIES E2T USER MANUAL TURBO S.R.L. Electronic Control Systems for Dust Collectors e-mail: info@turbocontrols.it web: www.turbocontrols.it TEL. ++39 (0)362 574024 FAX ++39 (0)362 574092 ECONOMISER SERIES E2T USER MANUAL 24/06/2014

More information

Instruction Manual. Q Series 2 Motor Control Modules - OEM

Instruction Manual. Q Series 2 Motor Control Modules - OEM A382-21-880 Issue B Instruction Manual Q Series 2 Motor Control Modules - OEM Pump/ Q Motor Control Module Item Number pumping system Electrical supply 24 V d.c. control 24 V a.c. control QDP40 200-230

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary

More information

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech The Axpert-CSS is a range of Combination Soft Starter panels offered by AMTECH DRIVES. We also offer the module unit as an individual product, named as Axpert-Opti torque Soft Starter. This is only the

More information

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic CONTENT 1. SUMMARY... 4 2. PERFORMANCE AND CHARACTERISTICS... 4 3. SPECIFICATIONS... 5 4. OPERATION... 6 5. PROTECTION...

More information

1. General description CONTENTS. 1.1 Applications. The Buerkert 7800 dosing pump is a self-priming diaphragm

1. General description CONTENTS. 1.1 Applications. The Buerkert 7800 dosing pump is a self-priming diaphragm CONTENTS Page 1. General description 4 1.1 Applications 4 1.2 Type key 5 2. Technical data 6 2.1 Mechanical data 6 2.2 Electrical data 6 2.3 Input/output data 6 2.4 Dimensions 7 3. Installation 7 3.1 Safety

More information

Welcome to the presentation about safety functions of ACS880 functional safety, FSO- 12 Safety functions module.

Welcome to the presentation about safety functions of ACS880 functional safety, FSO- 12 Safety functions module. Welcome to the presentation about safety functions of ACS880 functional safety, FSO- 12 Safety functions module. 1 Here is a list of the FSO-12 supported safety functions and example applications they

More information

BoosterpaQ Grundfos CR-Booster Systems 60 Hz Installation and operating instructions

BoosterpaQ Grundfos CR-Booster Systems 60 Hz Installation and operating instructions GRUNDFOS INSTRUCTIONS BoosterpaQ Grundfos CR-Booster Systems 60 Hz Installation and operating instructions Factory settings are documented in this manual. Please leave these instructions with the BoosterpaQ

More information

SE8300 Series Installation Guide 24 Vac Low Voltage

SE8300 Series Installation Guide 24 Vac Low Voltage Installation Guide 24 Vac Voltage mercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Configurable BI/UI Universal Inputs Overview 3 Setup Screen Display 3 Terminal Identification

More information

FKP-R/R2. User Guide for Pressure and Temperature controller with integrated pressure sensor

FKP-R/R2. User Guide for Pressure and Temperature controller with integrated pressure sensor FKP-R/R2 User Guide for Pressure and Temperature controller with integrated pressure sensor Rev 1.6 Frabil El AB Phone: +46 40-287090 Bjurögatan 38 Fax: +46 40-184709 2 FKP-R2 FUNCTION FKP-R/R2 is a complete

More information

A6Z OPERATING MANUAL

A6Z OPERATING MANUAL A6Z OPERATING MANUAL TABLE OF CONTENTS Introduction... p. 2 Features... p. 2 Description... p. 3 Theory of Operation... p. 3 Installation... p. 4 Electrical Connections... p. 5 Options... p. 6 Warranty.p.

More information

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK PART 1 - GENERAL 1.1 GENERAL: SECTION 15150 MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK A. The Mechanical Contractor shall furnish to the Electrical Contractor for installation,

More information

Orion BMS Purchasing Guide Rev. 1.2

Orion BMS Purchasing Guide Rev. 1.2 www.orionbms.com Orion BMS Purchasing Guide Rev. 1.2 Main Components... 2 Orion BMS Unit... 2 Current Sensor... 4 Thermistors... 5 CANdapter... 6 Wiring Harnesses... 7 Cell voltage tap wiring harnesses...

More information

RVS-DN Digital Reduced Voltage Motor Starter

RVS-DN Digital Reduced Voltage Motor Starter RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

Ucontrol. 1 Data sheet. Multipurpose controllers for variable voltage 3 ~ fans PXDM Examples of application. 1.2 Equipment / Function

Ucontrol. 1 Data sheet. Multipurpose controllers for variable voltage 3 ~ fans PXDM Examples of application. 1.2 Equipment / Function english Multipurpose controllers for variable voltage 3 ~ fans Ucontrol PXDM6..35 1 1.1 Examples of application Speed controller with manual adjustment of output voltage at the unit or via external signal,

More information

Mitsubishi. VFD Manuals

Mitsubishi. VFD Manuals Mitsubishi VFD Manuals Mitsubishi D700 VFD Installation Mitsubishi FR-D700 VFD User Manual Mitsubishi D700 Parallel Braking Resistors VFD Wiring Diagram - Apollo Mitsubishi VFD to Interpreter Mitsubishi

More information

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION... CONTENT 1. SUMMARY...4 2. PERFORMANCE AND CHARACTERISTICS...4 3. SPECIFICATION...5 4. OPERATION...6 4.1. DISPLAY PANEL...6 4.2. LCD ICON INSTRUCTION...7 4.3. DISPLAY INSTRUCTIONS...7 4.4. DISPLAY DESCRIPTION...8

More information

A problem with the motor windings. A phase loss on mains terminals L1, L2, or L3 during run mode. Parameter 2-3 Current Imbalance Delay.

A problem with the motor windings. A phase loss on mains terminals L1, L2, or L3 during run mode. Parameter 2-3 Current Imbalance Delay. 10 Troubleshooting When a protection condition is detected, the VLT Soft Starter MCD 500 writes this condition to the event log and may also trip or issue a warning. The soft starter response depends on

More information

MGE TM Galaxy TM 7000

MGE TM Galaxy TM 7000 MGE TM Galaxy TM 7000 Power efficiency for business continuity 160/200/250/300/400/500 kva > Performance 3 Phase Power Protection with high adaptability to meet the unique requirements of Medium to Large

More information

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual On Line UPS LUC 1000E / LUC 2000E / LUC 3000E User Manual Save This Manual Please read this manual carefully prior to storage, installation, wiring, operation and maintenance of the UPS. This manual contains

More information

HERZ Electronic room thermostat analog and digital

HERZ Electronic room thermostat analog and digital Dimension in mm 3 F799 11-3 F799 14 HERZ Electronic room thermostat analog and digital Data sheet for F799, Issue 0317 3 F799 15 3 F799 18 Mounting plate Page 1 Technical data 3 F799 11-14 3 F799 15-18

More information

Installation Instructions

Installation Instructions Installation Instructions Power Exhaust Part Numbers: CRPWREXH07A00 THROUGH CRPWREXH079A00 Conversion Package Numbers: CRPECONV005A00, CRPECONV006A00 CONTENTS Page SAFETY CONSIDERATIONS......................

More information

ACCESS Always replace the cover panel on the unit after gaining access to the electrical connections.

ACCESS Always replace the cover panel on the unit after gaining access to the electrical connections. F A I R F O R D E L E C T R O N I C S Soft Starters and Energy Optimising Soft Starters Guide to contents - applicable to Basic Guide to the Installation and Operation Of the Soft Starter 5MC software

More information

EXPERT 2V4SA. Temperature Controller. User s manual CLEAN MODE COMPENSATION HUMIDITY OUTSIDE TEMPERATURE

EXPERT 2V4SA. Temperature Controller. User s manual CLEAN MODE COMPENSATION HUMIDITY OUTSIDE TEMPERATURE CLEAN MODE Temperature Controller User s manual CURRENT CONDITIONS ROOM TEMPERATURE PROBE TEMPERATURE OUTSIDE TEMPERATURE RELATIVE HUMIDITY STATIC PRESSURE TIME / DATE SETTINGS SET POINT / CURVE MINIMUM

More information

MGE Galaxy PW kva 480 V. Operation

MGE Galaxy PW kva 480 V. Operation MGE Galaxy PW 5 5 kva 48 V Operation Table of Contents About This Manual... Companion Manuals... Find Updates to this Manual... Overview... User Interface... Configuration... 4 Select Language... 4 Set

More information

Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount

Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount Important Safety Messages Read the instructions carefully to become familiar with the equipment before

More information

HYDROVAR IncReAseD flexibility AnD control with new generation

HYDROVAR IncReAseD flexibility AnD control with new generation HYDROVAR Increased flexibility and control with new generation HYDROVAR, the modern variable speed pump drive is taking pumping to a new level of flexibility and efficiency. m Motor or wall mountable m

More information

GENERAL INFORMATION. H-1649, H-1650, H-1651 H-1653, H-1654 Easy-Count. uline.com. that may hurt accuracy:

GENERAL INFORMATION. H-1649, H-1650, H-1651 H-1653, H-1654 Easy-Count. uline.com. that may hurt accuracy: π H-1649, H-1650, H-1651 H-1653, H-1654 Easy-Count counting scale 1-800-295-5510 uline.com 1-800-295-5510 GENERAL INFORMATION Avoid placing the scale in locations that may hurt accuracy: 1. Temperature

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

INSTALLATION INSTRUCTIONS DNLOWAMB015A00, DNLOWAMB016A00

INSTALLATION INSTRUCTIONS DNLOWAMB015A00, DNLOWAMB016A00 INSTALLATION INSTRUCTIONS DNLOWAMB015A00, DNLOWAMB016A00 and DNLOWAMB017A00 Accessory Low Ambient Motor Controller For Models PGS/PAS240, 300 and PGE/PAE240 These instructions must be read and understood

More information

LAMBDA SENSOR CONTROLLER

LAMBDA SENSOR CONTROLLER LAMBDA SENSOR CONTROLLER INSTALLATION & PROGRAMMING MANUAL version : V1.77 -V1.79 Manufacturer: AC Spółka Akcyjna. 15-182 Białystok, ul. 27 Lipca 64, Poland tel. +48 85 7438148, fax +48 85 653 8649 www.ac.com.pl,

More information

A1P OPERATING MANUAL

A1P OPERATING MANUAL A1P OPERATING MANUAL TABLE OF CONTENTS Introduction... p. 2 Features... p. 2 Description... p. 3 Theory of Operation... p. 3 Installation... p. 4 Electrical Connections... p. 5 Options... p. 6 Warranty...

More information