ECL Comfort Installation and Maintenance. User s Guide. ECL Comfort. C60 Double mixing controller C60. Table of Contents. Daily use.

Size: px
Start display at page:

Download "ECL Comfort Installation and Maintenance. User s Guide. ECL Comfort. C60 Double mixing controller C60. Table of Contents. Daily use."

Transcription

1 ECL COMFORT VI.7C.B4.0 C60 Table of Contents Daily use ECL Comfort User s Guide Section Choose favourite display Select controller mode 3 Adjust room temperature 4 Set personal day plan 5 Advantages of the 6 Hot points 7 Definitions The documentation for the ECL Comfort controller is composed of numbered sections. Only sections that are relevant to your ECL Comfort controller are included here. Installation and maintenance. Grey sections 0 and onwards. Turn the guide over. Your personal week plan: Heating Monday Tuesday 3 Wednesday 4 Thursday 5 Friday 6 Saturday 7 Sunday Heating Monday Tuesday 3 Wednesday 4 Thursday 5 Friday 6 Saturday 7 Sunday Factory settings are grey. 8-3 ECL Comfort Installation and Maintenance This guide is associated to 087B4756 Installer: C60 Double mixing controller Table of Contents Sections of the Installer s part of this guide The documentation for the ECL Comfort controller is composed of numbered sections. Only sections that are relevant to your ECL Comfort controller are included here. Before you start Installation 0 Identifying the system type Mounting the ECL Comfort controller 3 Electrical connections 4 V a.c. 4 Placing the temperature sensors 5 Inserting the Basic Set-up 6 Adjusting the settings 7 Setting the time and date - Line A 8 Monitoring temperatures and system units -Line B 9 Manual control - Line B 0 Setting the heat curve - Line C Heating cut-out - Line Flow temperature limits - Line 3 Room temperature influence - Line 3 6 Setting PI-regulation - Line 4-7 Control & Overviews 9 Check list 30 settings 3 Service parameters Extended Service Electrical connections 30 V a.c. 3 Adjusting the service parameters 0-99 Miscellaneous 34 Copying with the Daily use, turn the guide over sections 0-07 Choose favourite display Select controller mode 3 Adjust room temperatures 4 Set personal day plan 5 Advantages of the 6 Hot points 7 Definitions ECL COMFORT By: Date:

2 List of components: S S ECL Comfort 300 Outdoor temperature sensor (ESM-0) Room temperature sensor (ESM-0) - circuit I S3 S4 S5 S6 P P M M Flow temperature sensor (ESM-) - circuit I Return temperature sensor (ESM-) Flow temperature sensor (ESM-) - circuit II Room temperature sensor (ESM-) - circuit II Circulation pump for heating - circuit I Circulation pump for heating - circuit II Mixing valve with motor - circuit I Mixing valve with motor - circuit II Day plans Installation & maintenance The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in heating systems. The, grey side for installation and maintenance. Lines A to C, and lines to 7 for basic settings, see overview section 30. B Heating system information B C Today s programme 3 C C B Extended service parameters, see section 3 If the system you are about to install is different than the shown diagram of a standard heating system, feel free to sketch an outline for comparison. Adaptation of heating systems, see section 0. The : Installer s instruction card must face you when you change settings. For daily use and during start-up, the yellow card must face you Heating - circuit II A Circuit Line indicator Heating - circuit I A Room temperature II Room temperature I / The display Each line, A, B, C,, etc. of the has its own display. See section. A Controller mode Manual operation (used only at maintenance and service) Automatic operation Circuit selector for switching between heating circuit I and II. The For daily use and your personal adjustments the yellow side of the must be facing you. The circuit indicator shows the selected heating circuit. Constant comfort temperature Adjust temperatures and values etc. Constant reduced temperature Standby mode Shift button. Switches between temperatures, changeover points etc. Arrow buttons. Switch between the lines of the. Arrow buttons. Switch between the lines of the. Shift button. Switches between temperatures, changeover points etc. Standby mode Constant reduced temperature Adjust temperatures and values etc. Constant comfort temperature Circuit selector for switching between heating circuit I and II. Automatic operation Manual operation (used only at maintenance and service) Circuit indicator Circuit selector Shift button Adjustment Controller mode Controller mode

3 Before you start Save energy - save money - improve your comfort temperature The ECL Comfort controller is designed by Danfoss for temperature control of heating systems. The ECL Comfort controller ensures you of the following; Room and hot water temperatures will be adjusted to your personal settings. Lower temperatures and lower energy consumption reduce costs and ensure optimum use of energy resources. The automatic pump motion program protects the circulation pump against blocking. Sketch an outline of your heating system The ECL Comfort controller is designed for a wide range of heating systems with different configurations and capacities. If your heating system differs from the diagrams shown in section 0, you may want to sketch an outline of the system about to be installed. This makes it easier to use the Installer s Guide, which will guide you step-by-step from installation to final adjustments before the end-user takes over. Note! The controller is pre-programmed with factory settings which are shown in the relevant sections of this guide. However, you might come across some settings that are not listed in this instruction. These settings are used in connection with optional modules, and you can find a description of the settings and the corresponding parameters in the instruction for optional module in question. How to use this guide This guide is divided into two parts: Daily Use (Turn the guide over) Yellow sections -7 Installation and maintenance: Grey sections 0 and onwards VI.7C.B4.0

4 0a Identifying the system type 0b Installation In this section you find the most frequently used systems. If your system is not quite as shown below, find the diagram which has the best resemblance to your system and make your own combinations. Alternatives using the same settings: Heat exchanger or direct district heating -, 3-, or 4-way control valve Heating system type 3 Radiator heating circuit and secondary connected floor heating circuit. Installation Heating system type Two parallel connected heating circuits with heat exchangers. Set line 7 to 4K Check line 4 in circuit I and II (gear motor/thermo actuator) Heating system type 4 Boiler with two parallel connected heating circuits with heat exchangers. Set line 7 to OFF Check line 4 in circuit I and II (gear motor/thermo actuator) Heating system type Two parallel connected heating circuits. Set line 7 to OFF Check line 4 in circuit I and II (gear motor/thermo actuator) Note! System diagrams in this instruction are principal drawings and do not contain all components which are necessary in heating systems. Set line 7 to OFF Check line 4 i circuit I and II (gear motor/thermo actuator)

5 Installation a Mounting the ECL Comfort controller For easy access, you should mount the ECL Comfort controller near the heating unit. Select one of the three following methods: Mounting on a wall Mounting on a DIN rail Mounting in a panel Screws and rawlplugs are not supplied. b Installation Mounting on a wall Socket for mounting on wall: Order code No. 087B49. Mount the terminal box on a wall with a smooth surface. Establish the electrical connections and position the controller in the box. Secure the controller with the fixing screw. Mounting on a DIN rail Mounting kit: Order code No. 087B45. A mounting kit is necessary to mount the box with the controller on a DIN rail. Mounting in a panel Connector set: Order code No. 087B48. The panel plate thickness must not exceed 3 mm. Prepare a cut-out with the dimensions 9 x 38 mm. Pull off the right lid by means of a screwdriver. Insert the controller into the panel cut-out and fix it with the two locks which are placed diagonally in two corners of the controller.

6 a Electrical connections - 30 V a.c. b Connecting the 30 V a.c. units Connecting the sensors Installation Installation Terminal Description Max. load L Supply voltage 30 V a.c. (Live) N Supply voltage 30 V a.c. (Neutral) 3 M Gear motor - open/cir. I 0. A 30 V a.c. 4 M Gear motor - close/cir. I alt.: ABV thermo actuator 0. A 30 V a.c V a.c. supply for M/cir. I 6 M Gear motor - open/cir. II 0. A 30 V a.c. 7 M Gear motor - close/cir. II 0. A 30 V a.c V a.c. supply for M/cir. II 9 P Circulation pump for 4()A 30 V a.c. heating circuit I 0 30 V a.c. supply for pump relay R P Circulation pump for heating circuit II 4()A 30 V a.c. 30 V a.c. supply for pump relay R Terminal Description Type (recommended) 5 and 6 System device bus 7 and 6 Outdoor sensor (S) ESM-0 8 and 6 Room sensor (S) circuit I ESM-0 9 and 6 Flow sensor (S3) circuit I ESMU/ESM-/ESMC 0 and 6 Return sensor (S4) ESMU/ESM-/ESMC and 6 Flow sensor (S5) circuit II ESMU/ESM-/ESMC and 6 Room sensor (S6) circuit II ESM-0 Establish the jumper from 6 to common terminal. Cable cross section for sensor connections: Min. 0.4 mm Total cable length: Max. 50 m (sensors and bus). Cable type: Copper cable Note! Cable lengths above 00 m may cause noise sensibility (EMC). Establish these jumpers: Jumper from to 5 Jumper from 5 to 8 Jumper from 8 to 0 Jumper from 0 to Jumper from to common N-terminal Cable cross section for voltage conductor: mm Cable length: Max. 50 m Electrical connections Max. x.5 mm cables can be inserted into each screw terminal.

7 3a Electrical connections - 4 V a.c. 3b Installation Connecting the 4 V a.c. and 30 V a.c. units Connecting the sensors Installation Terminal Description Max. load L Supply voltage 4 V a.c. N Supply voltage 4 V a.c. 3 M Gear motor - open/cir. I A 4 V a.c. 4 M Gear motor - close/cir. I alt.: ABV thermo actuator A 4 V a.c. 5 4 V a.c. supply for M/cir. I 6 M Gear motor - open/cir. II A 4 V a.c. 7 M Gear motor - close/cir. II A 4 V a.c. 8 4 V a.c. supply for M/cir. II 9 K* Relay for circulation pump for heating circuit I 0 4 V a.c. supply for pump relay K K* Relay for circulation pump for heating circuit II 4 V a.c. supply for pump relay K * K/K auxiliary relay Coil: 4 V a.c. Contacts: 4A 30 V a.c. Terminal Description Type (recommended) 5 and 6 System device bus 7 and 6 Outdoor sensor (S) ESM-0 8 and 6 Room sensor (S) circuit I ESM-0 9 and 6 Flow sensor (S3) circuit I ESMU/ESM-/ESMC 0 and 6 Return sensor (S4) ESMU/ESM-/ESMC and 6 Flow sensor (S5) circuit II ESMU/ESM-/ESMC and 6 Room sensor (S6) circuit II ESM-0 Establish the jumper from 6 to common terminal. Cable cross section for sensor connections: Min. 0.4 mm Total cable length: Max. 50 m (sensors and bus). Cable type: Copper cable Note! Cable lengths above 00 m may cause noise sensibility (EMC). Establish these jumpers: Jumper from to 5 Jumper from 5 to 8 Jumper from 8 to 0 Jumper from 0 to Jumper from to common N-terminal Cable cross section for voltage conductor: mm Cable length: Max. 50 m Electrical connections Max. x.5 mm cables can be inserted into each screw terminal.

8 Installation Placing the temperature sensors 4 It is important that the sensors are mounted in the correct position in your heating system. Special attention should be paid to the following sensors: Outdoor temperature sensor (ESM-0 type) The outdoor sensor should be mounted on the north side of the building where it is less likely to be exposed to direct sunshine. It should not be placed close to doors or windows. Installation Flow temperature sensor (ESMU, ESM- or ESMC types) Place the sensor max. 5 cm from the mixing point. In systems with heat exchanger, Danfoss recommends the ESMU-type to be inserted into the exchanger flow outlet. Make sure that the surface of the pipe is clean at the area where the sensor is mounted. Do not move the sensor after it has been fastened in order to avoid damage to the sensor element. Return temperature sensor (ESMU, ESM- or ESMC types) The return sensor should always be placed max. 5 cm from the mixing point. It should always be placed on a pipe in which the water flow never stops. Room temperature sensor (ESM-0, ECA 60 and 6 remote control) Place the room sensor in the room where the temperature is to be controlled. Do not place it on outside walls or close to radiators, windows or doors.

9 5a Inserting the 5b Installation Understanding the The contains factory settings for a standard heating system. If the actual heating system differs from the standard system, the controller must be adjusted accordingly. After the adjustment, the new settings should be stored on the. For copying and daily use including adjustment of temperatures and time periods, insert the with the yellow side facing you. Installation For system set-up adjustments, the grey ECL Card - the installer s side - must be facing you. As a main rule, the should always remain in the controller during service, maintenance and settings. How to insert your the first time After the power has been switched on, open the lid on the front controller. If the card is removed please note that: The controller settings are locked after approx. 0 min. The must not be exposed to direct heat or sunshine Place the with the yellow side facing you. This enables the controller to read the data. The controller immediately starts to copy the factory settings and heating system type from the. After copying, the display will show the heating system type the controller is set to control. After approx. 0 sec. the display will change to display line C. 0 CPY C99 C If several controllers are installed in the heating system you can write a title on the with a permanent ink pen. Line Circuit Time Outdoor temperature C Desired room temperature The controller is now ready to be set to control your heating system.

10 6 Adjusting the settings General principles When the controller is connected and operating you can check and adjust all or some of the basic settings on the grey. Setting the time and date - Line A Go to line A. A Actual time 7 Use the arrow buttons to move from line to line of the, for example line : Year Month, day Basic set-up Circuit Line indicator Settings to be adjusted Value in range indicator Use the minus/plus buttons to adjust the settings. In some displays more than one setting or value can be adjusted. Use the shift button to switch between the possibilities. The circuit selector shifts between circuit I and II. You can adjust all settings and service parameters individually in both circuits, ie. circuit II. Use the shift button to switch between minutes, hours, year, month and day Set the correct time and date In case of a power failure which lasts longer than hours, the time and the date have to be set again. All other settings are stored as programmed. Use the yellow to enter the day plan settings. See User s Guide, section 4. Basic set-up Update of the after maintenance and service All new settings can be stored on the. For details about copying, see section 34. Insert the ECL Card with the yellow side facing you. Go to line 9 (bottom line) 0 CPY C99 Accept to copy as indicated. No other keys are active. When the copying is finished display line C will appear C You can make other changes in the day plan, set time and date or change settings (see User s Guide).

11 8 Monitoring temperatures and system units - Line B Manual control - Line B 9 Go to line B. Go to line B. B Controlled units State indicator The circuit selector shifts between circuit I and II. Shift to manual mode Flow temperature Return temperature Controlled units B Controller mode Basic set-up Push the shift button to see: - the calculated flow temperature - the return temperature set points The activity of the motorized valve is shown as arrows below the valve symbol. When the circulation pump is operating, it is indicated as below the pump symbol. If a sensor is not mounted or is disconnected, the display will indicate it as - -. If the sensor is short-circuited, the display will indicate it as If you are in doubt, remove the controller and check the ohmic value between the relevant terminals. Relationship between temperature and ohmic value Select the unit you want to control. The selected unit symbol will flash. The gear motor opens or closes the valve as long as the the relevant button is pressed. The thermo actuator (according to version *)), closes (NO) or opens (NC) Basic set-up -0 C 96 Ohm 0 C 000 Ohm 0 C 039 Ohm 0 C 078 Ohm 30 C 7 Ohm 40 C 56 Ohm 50 C 95 Ohm 60 C 34 Ohm 70 C 73 Ohm Ohm the valve as long as the relevant button is pressed. *) NO - normally open NC - normally closed Pumps are switched off or on when the relevant button is pressed Check the activation direction of the motorized valve either by looking at it or by feeling whether the temperature of the actual pipe changes as expected Temperature This operation applies to both circuits. Press the button to select circuit II. Note! During manual operation, the pump motion is OFF.

12 0a Setting the heat curve - Line C 0b Go to line C. The symbol for the slope of the heat curve will flash. 90 oc,4,8, C 8 0 Slope Displacement ,0 0,6 40 0, Slope 30 Basic set-up I/II Adjust the slope of the heat curve, if required. If you want to adjust the parallel displacement of the heat curve, push the shift button. The symbol for the parallel displacement will flash. Parallel displacement l/ii Make your adjustments Floor heating systems This controller is factory set for radiator systems, which are typically high flow temperature systems. To control floor heating systems, which are typically low flow temperature systems, you need to change the heat curve according to your type of system. Slope Circuit Setting range Typical setting I oc Basic set-up Parallel displacement Circuit Setting range Typical setting I

13 Heating cut-out - Line Flow temperature limits - Line Limit for heating cut-out I/II C 8 C Flow temperature min., max. limits I/II C min. 40 C max. 90 C Go to line. Go to line. Basic set-up 8 C Temp 8 Set the outdoor temperature limit at which you want the heating system to stop. Actual T out Accumulated Tout Time Min. flow temperature Max. flow temperature Temperature range for flow temperature The left end of the range indicator flashes. Adjust the min. limit of the heating system. Select the max. limit. The right end of the range indicator flashes. Basic set-up Adjust the max. limit. Heating Heating off Heating This function can save energy by stopping the heating system when the outdoor temperature gets above a set limit. The heating system is activated again when the actual outdoor and the accumulated temperatures get below the set limit. The accumulated Tout symbolises the heat stored in the building.

14 3a Room temperature influence - Line 3 This section is only relevant if you have installed a room sensor. There are two basic principles for control of the room temperature influence: A: Max. room temperature limitation Use this limitation if your heating system is fully equipped with radiator thermostats and you also want to obtain a max. limitation of the room temperature. The controller will allow for free heat gains, i.e. solar radiation or heat from a fire place, etc. B: Reference room control Used if your heating system is not equipped with radiator thermostats and you select the room with room sensor as a temperature reference for the rest of the rooms. (However, should you have a few radiator thermostats installed, make sure that they are fully open). Set a positive value for min. influence and a negative value for max. influence. 3b Basic set-up 3 Room temperature influence I/II / min. 0 max. -40 Go to line _ Influence Min. limitation set Max. limitation T ROOM Basic set-up Min. influence Max. influence Select the max. influence. The bar below the range indicator flashes in the right display. The room sensor in the reference room registers the difference between the desired and the actual room temperature. The flow temperature reference will be corrected to eliminate this difference. Adjust the max. influence. + _ Influence set Max. limitation TROOM The max. influence determines how much the room temperature should influence the flow temperature. Example The actual room temperature is degrees too low. The influence at max. limitation (right corner of the display) is set to 0. The influence at min. limitation(left corner of the display) is set to 0. Heat curve H is.8. Result: The flow temperature reference is changed by x 0 x 0. x H = 7. degrees. The actual room temperature is degrees too high. The influence at max. limitation (right corner of the display) is set to -35. The influence at min. limitation(left corner of the display) is set to 0. Heat curve H is.8. Result: The flow temperature reference is changed by x (-35) x 0. x H = -.6 degrees. Example The actual room temperature is degrees too high. The influence at max. limitation (right corner of the display) is set to -40. The influence at min. limitation (left corner of the display) is set to 0. Heat curve H is.8. Result: The flow temperature reference is changed by x -40 x 0. x H = -4.4 degrees.

15 6a Setting the PI-regulation - Line 4-7 6b 4 Proportional band I/II K 80 K Line indicator Go to line Setting to be adjusted If you want to tune the PI-regulation precisely, you can use the following method: Set the integration time (line 5) to its max. value (999 sec.). Decrease the value for the proportional band (Line 4) until the system starts hunting with a constant amplitude (it might be necessary to force the system by setting an extreme value). Find the critical time period on the temperature recording or use a stop watch. Temp Critical time period Basic set-up Set the proportional band. A higher value will result in a stable, but slow regulation of the flow temperature. 5 Integration time constant I/II sec. 30 sec. This time period will be characteristic for the system, and you can evaluate the settings from this critical period. Time Basic set-up Go to line 5. Integration time = Proportional band = 0.85 x critical time period. x proportional band value in the critical time period. Set a high integration time constant to obtain a slow but stable reaction to deviations. A low integration time constant will make the controller react fast but with less stability. If the regulation seems to be too slow, you can decrease the proportional band value by 0%. Note! Make sure there is a consumption when you set the parameters. 6 Running time of the motorized valve I/II sec. 35 sec. Go to line 6. Set the running time of the motorized valve according to the example on the opposite page. This is the time it takes the valve to move from closed to fully open position. 7 Neutral zone I/II K 3 K Go to line 7. Set the neutral zone to a high value if you can accept a high variation in flow temperature. When the actual flow temperature is within the neutral zone, the controller does not activate the motorized valve. How to calculate the running time of the motorized valve Valve type Valve Actuator Actuator Running stroke type speed time (mm) (sec./mm) (sec.) VS AMV VS 5...5, VM 5...5, AMV(E) VB , VS 5...5, VM 5...5, VB AMV(E) VM 3, VB AMV(E) VM 3, VB AMV(E) 30 3 The running time of the motorized valve is calculated using the following methods: Seated Valves Running time = Valve stroke (mm) x actuator speed (sec./mm) Example: 5.0 mm x 5 sec/mm = 75 sec. Rotating Valves Running time = Turning degrees x actuator speed (sec./degr.) Example: 90 degrees x = 80 sec. Note! The valve is symmetrically around the flow reference value.

16 9a Check list Is the ECL Comfort controller ready for use? Make sure that the power supply is connected to terminals (Live) and (Neutral). See section or 3. Check that valves and pumps are connected to the correct terminals. See section or 3. Check that all sensors are connected to the correct terminals. Mount the controller, and switch on the power. Insert the with the yellow side facing you and push, if necessary. See section 5. Check list 9b Adapting the ECL Comfort controller to the heating system Turn the so that the grey side faces you. Set the time and the date (Line A) See section 7. Check all settings on the grey See sections 0 to 6. Check all settings in the extended service parameters line 0 to 99. If your heating system differs from the diagram shown on the overleaf of the cover, you should check and perhaps alter the following service parameter. Select manual operation in the controller mode. See section in the user s guide. Line 4 Thermo actuator/gear motor circuit I and II Control & overviews Check that valves open and close, and that pumps start and stop when operated manually. See section 9. Check that the temperatures shown in display A and B match the actual sensors, both for circuit I and circuit II. See section in the user s guide. To ensure that you have the correct settings see section 0 for examples of different heating systems. Control & overviews

17 30a settings (circuit I: Heating) settings (circuit II: Heating) 30b A Time and date See sections 6 & 7 A Time and date See sections 6 & 7 B System information See sections 8 & 9 B System information See sections 8 & 9 C Heat curve See section 0 C Heat curve See section 0 Setting range Factory setting Your settings Heat curve - Slope Set the slope of the heat curve, see section 0 Setting range Factory setting Your settings Heat curve - Slope Set the slope of the heat curve, see section 0 Heat curve - Parallel displacement K Set the parallel displacement of the heat curve, see section 0 Heat curve - Parallel displacement K Set the parallel displacement of the heat curve, see section 0 Control & overviews Limit for heating cut-out C 8 C Save energy by stopping the heating system when the outdoor temperature gets above a certain limit, see section. Flow temperature min.-/max. limits C min. 40, max. 90 C The limits for min.- and max. flow temperature, see section. 3 Room temperature influence / min. 0, max. -40 The room temperature s influence on the flow temperature control, see section 3. Limit for heating cut-out C 8 C Save energy by stopping the heating system when the outdoor temperature gets above a certain limit, see section. Flow temperature min.-/max. limits C min. 40, max. 90 C The limits for min. - and max. flow temperature, see section. 3 Room temperature influence / min. 0, max. -40 The room temperature s influence on the flow temperature control, see section 3. Control & overviews 4 Proportional band K 80 K Set the PI-regulation, see section 6. 4 Proportional band K 80 K Set the PI-regulation, see section 6. 5 Integration time constant sec. 30 sec. Set the PI-regulation, see section 6. 5 Integration time constant sec. 30 sec. Set the PI-regulation, see section 6. 6 Motor / valve running time sec. 35 sec. Set the PI-regulation, see section 6. 6 Motor / valve running time sec. 35 sec. Set the PI-regulation, see section 6. 7 Neutral zone K 3 K Set the PI-regulation, see section 6. 7 Neutral zone K 3 K Set the PI-regulation, see section 6.

18 3a Service parameters Service parameters 3b Circuit I (heating) Line Setting range Factory seting Your setting Circuit I (heating) Line Setting range Factory seting Your setting 0 Choice of time control unit Summer time change /OFF Reduced temperature dependent on outdoor temperature OFF/ C -5 C C Boost % 0% % 3 Reference ramping min 0 min min 4 Optimising time constant OFF/ OFF 99 Slave address Circuit II (heating) Line Setting range Factory setting Your setting 0 Choice of time control unit Reduced temperature dependent on outdoor temperature OFF/ C -5 C C Control & overviews 5 Adaptive function of room temperature OFF/ OFF 7 Temperature reference feed back OFF/... 0 OFF 0 Optimisation based on room/ outdoor temperature /OFF OFF Total stop /OFF Pump motion /OFF 3 Valve motion /OFF 4 Gear motor/thermo actuator /OFF OFF OFF 3 Return temperature limitation (X) C +5 C C Boost % 0% % 3 Reference ramping min 0 min min 4 Optimising time constant OFF/ Adaptive function of room temperature OFF/ OFF OFF 0 Optimisation based on room/ outdoor temperature /OFF OFF Total stop /OFF Pump motion /OFF 3 Valve motion /OFF OFF OFF Control & overviews 3 Return temperature limitation (Y) C 40 C C 4 Gear motor/thermo actuator /OFF 33 Return temperature limitation (X) C -5 C C 3 Return temperature limitation (X) C +5 C 34 Return temperature limitation (Y) C 60 C C 3 Return temperature limitation (Y) C 40 C C 35 Return temperature influence - max C - C C 33 Return temperature limitation (X) C -5 C C 36 Return temperature influence - min C 0 C C 34 Return temperature limitation (Y) C 60 C C 37 Adaptive function of return limitation OFF/ Return temperature influence - max C - C C 5 Closed valve/pi-regulation /OFF OFF 36 Return temperature influence - min C 0 C C 4 Override input selection OFF/... 6 OFF 37 Adaptive function of return limitation OFF/ C 74 Motor protection OFF/ min OFF 5 Closed valve/pi-regulation /OFF OFF 96 Service pin - L /OFF OFF 4 Override input selection OFF/... 6 OFF 97 L reset /OFF 74 Motor protection OFF/ min OFF

19 3a Adjusting the service parameters Service parameters 0-3b In addition to the settings in line to 7 on the grey, there is an extended service menu from line 0 and onwards. Push repeatedly to reach the lines numbered 0 and onwards. 0 Choice of time control unit I/II Dedicates the unit for the time control of the comfort and reduced temperature periods Select between Line number 0 0 Value Range indicator 0 ECL Comfort controller - day plan for circuit Room panel ECA 60 or remote control ECA 6 on address A Room panel ECA 60 or remote control ECA 6 on address B Now you can move to any line of your choice. Set the parameter value. You can select any of the two circuits no matter what line you are in. You will not necessarily enter the same line number. See the service parameters in section 3. When you have entered all your personal settings, turn the over so that the yellow side faces you. If you want to copy the new settings to the (recommended by Danfoss), see section 34. Make a note of your new settings on the parameter list in section 3. Reduced temperature dependent on outdoor temperature I/II OFF / C -5 C Limit of the outdoor temperature at which the reduced temperature setting is switched off. -9 to +0 C The setting of reduced temperature depends on the outdoor temperature, when the outdoor temperature is above the set limit. The lower the outdoor temperature the less the temperature reduction. When the outdoor temperature is below the set limit, there is no temperature reduction. Reduction 00% Extended service 0% OFF: Outdoor temp. o C The reduced temperature setting will be constant at all outdoor temperatures. Extended service

20 3c Service parameters -3 Service parameters 4-5 3d Boost I/II % 0% Shortens the heating-up period by increasing the flow temperature by the percentage you set. In order to shorten the heating-up period after a reduced temperature period, the flow temperature can be increased temporarily. If a room sensor is installed, the boost stops when the optimising period is over or the room temperature has been reached. T ref C Set the percentage at which you want the flow temperature to be changed temporarily. 3 Reference ramping I/II min 0 The time in which the flow temperature increases slowly to avoid load peaks in the supply. Set the opening time you want the valve to use. 4 Optimising time constant I/II OFF / OFF Optimises the start and stop times for the reduced temperature period to obtain the best comfort at the lowest energy consumption. Adjust the optimising time constant. The value consists of a number of two digits. You can select the following values:,, The two digits have the following meaning:. digit (system type and heat accumulation of the building). digit Heat accumulation System type of the building light medium heavy medium heavy Radiator system Floor heating system. digit (capacity of the heating system). digit Dimensioning Capacity temperature 0-50 C large C normal C small T ref Extended service Setting line 3 Time In order to avoid load peaks in the supply network, the flow temperature reference can be set to increase slowly after a period with reduced temperature. This causes the valve to open slowly. OFF: 4 5 No optimisation. The heating starts and stops at the times set in the week plan. Dimensioning temperature: The lowest outdoor temperature at which the heating system can secure the desired temperature. 5 Adaptive function of room temperature I/II OFF / OFF Controls how fast the room temperature adapts to the desired temperature. Extended service OFF: The adaptive function is cancelled. : The desired temperature is adapted quickly. 30: The desired temperature is adapted slowly. The adaptive function will eliminate the difference between the required and the actual room temperature by integrating the difference and adjusting the reference for the flow temperature.

21 3e Service parameters 7-0 Service parameter 3f 7 Temperature reference feedback I OFF /... 0 OFF The temperature reference in heating circuit I can be influenced by another external. The set number determines the influence of the flow temperature reference in circuit I or the reference signal by any other connected controller. Total stop I/II / OFF OFF Decide whether you want a total stop during reduced temperature period. Select total stop function. OFF: The temperature reference in circuit I is not influenced by any other controller. -0: The temperature reference in circuit I will always at least correspond with the value of the set number + the highest temperature reference degree of an external controller. : Total stop function is. At total stop the flow temperature reference is lowered to 0 C, and the minimum setting of the flow temperature limit of line (see section ) is overruled in the reduced temperature period. C Setting line 7 Ref. temp. T REF T ref (l) T MIN T ref (ll) 0 o C Time Time This function is used if circuit I is the main supply for other mixing circuits. OFF: No total stop 0 Optimisation based on room/outdoor temperature I/II / OFF OFF The optimised start and stop time calculation can be based on either the room temperature or on the outdoor temperature. T REF Ref. temp. T MIN Extended service Select calculation method: : OFF: Calculation based on room temperature (only if a room sensor is used). Calculation based on outdoor temperature. Use this setting if you have no room sensor. 0 o C Time Extended service

22 3g Service parameters -4 Pump motion I/II / OFF Exercises the pump to avoid blocking in periods without heat demand. Set the anti-blocking function to or OFF. : OFF: The pump is switched on for minute every third day. The pump motion is switched off. 3 Valve motion I/II / OFF OFF Exercises the valve to avoid blocking in periods without heat demand. Set the anti-blocking function to or OFF. : OFF: The valve motion is switched on. The valve receives a signal to open and close every third day. The valve motion is switched off. In district heating systems you have to switch off the valve motion to avoid unnecessary heat consumption. Extended service 4 Gear motor / thermo actuator I/II / OFF Choose the actuator type. Select actuator type: : OFF: Gear motor Thermo actuator Extended service

23 3h Service parameters 3-3 Service parameters i 3 Return temperature limitation - upper limit (X) I/II C +5 C Set the return temperature limitation - upper limit X-axis. 33 Return temperature limitation - lower limit (X) I/II C -5 C Set the return temperature limitation - lower limit X-axis. Set the value for the upper limit (X-coordinate) of the outdoor temperature. (The corresponding Y-coordinate is set in line 3). Set the value for the lower limit (X-coordinate) of the outdoor temperature. Line 34 T return Lower limit Upper limit 34 Return temperature limitation - lower limit (Y) I/II C 60 C Set the return temperature limitation - lower limit Y-axis. Line 3 Set the acceptable value of the return temperature which corresponds to the lower limit setting in line 33. Line 33 Line 3 T out The return temperature limitation is based on the outdoor temperature. When the outdoor temperature drops, a higher return temperature can be set. The relationship between the return temperature limits and outdoor temperature is set in two points. The upper limit point is set in line 3 and 3 and the lower limit point in line 33 and Return temperature limitation - upper limit (Y) I/II C 40 C Set the return temperature limitation - upper limit Y-axis. Extended service Set the acceptable return temperature value which corresponds to the upper limit setting in line 3. Extended service

24 3j Service parameter 35 Service parameter 36 3k 35 Return temperature influence - max. limitation I/II How much the flow temperature reference should be influenced 36 Return temperature influence - min. limitation I/II How much the flow temperature should be influenced. Set the influence of the max. return temperature limitation. If the displayed value does not equal 0, the function prevents the return temperature from getting above the settings in lines Influence higher than 0: The reference for the flow temperature is increased, when the return temperature gets above the settings in lines Influence lower than 0: The reference for the flow temperature is decreased, when the return temperature gets above the setting in lines Set the influence of the min. return temperature limitation. If the displayed value does not equal 0, the function prevents the return temperature from falling below the limit set in line 30. Influence higher than 0: The reference for the flow temperature is increased, when the return temperature gets below the setting in line 30. Influence lower than 0: The reference for the flow temperature is decreased, when the return temperature gets below the setting in line 30. Influence + Min. limitation > 0 Influence + 0 Return limit Max. limitation > 0 Return temp. 0 Return limit _ Min. limitation < 0 Return temp. _ Max. limitation < 0 Example The return limit is set to 50 degrees. The influence is set to -. The actual return temperature is degrees too high. Result: The flow temperature is lowered by x- = -4 degrees. Example Return limit is set to 50 degrees. Influence is set to Actual return temperature is degrees too low. Result: The flow temperature reference is increased with x = 4 degrees. Extended service Normally, the value set in line 35 is lower than 0 in district heating systems and equals 0 in boiler systems. Normally, the setting in line 36 is 0 in district heating systems and lower than 0 in boiler systems. With a normal return limitation you have to set a 0 in either line 35 or 36. Extended service

25 3l Service parameters 37-5 Service parameter 4 3m 37 Adaptive function of return limitation I/II OFF / Controls how fast the return temperature adapts to the desired temperature. Select circuit. Adjust the adaptive function of the return limitation. The setting will eliminate the difference between required and actual return temperature by integrating the difference and adjusting the reference for the flow temperature. In circuit I the settings mean: OFF: The heating curve will not be adjusted. : The heating curve will be adjusted quickly. 50: The heating curve will be adjusted slowly. 4 Override input selection I/II OFF/... 6 OFF/OFF Choose a free sensor input for the override of circuit I and/or circuit II. Each circuit can be overridden independently of each other. Choose circuit I or II. OFF: The controller is not overridden.... 6: Select a free sensor input S... S6 for the override of the circuit in question. Connection example without ECA 900 In circuit II the settings mean: OFF: The charging temperature reference will not be adjusted. : The charging temperature will be adjusted quickly. 50: The charging temperature will be adjusted slowly. 5 Closed valve/pi-regulation I/II /OFF OFF The heating circuit can be closed, when the controller functions as a slave controller. Closed switch: Reduced temperature Closed switch: Comfort temperature Extended service Note! Line 5 is set if this controller is a slave. : OFF: The valve in the heating circuit is closed during hot water service demand from a master controller. The flow temperature control remains unchanged during a hot water service demand from a master controller. Changeover switch: Reduced or comfort temperature Connection example with ECA 900 Extended service and closed: and 3 closed: Reduced temperature Comfort temperature Note: To avoid contact resistance, the use of the override module ECA 900 is recommended. For an active override, you have to choose the mode automatic operation!

26 3n Service parameters Service parameters o 74 Motor protection I/II OFF/ min. OFF Prevents the acutator from hunting when the load in the heating circuit is very low. This stabilization increases the lifetime of the involved components. Set the motor protection function to be on or off: OFF: Motor protection is turned off : Motor protection is turned on. When a load change occurs, motor protection is automatically disabled and will be reactivated when hunting is detected again. The disabling period can be set to 0-59 minutes. A high value should be used for installations with many consumers and vice versa. 96 Service pin - L I /OFF OFF This setting is only used in connection with communication (see the documentation for the used communication unit). 97 L reset I /OFF This setting is only used in connection with communication (see the documentation for the used communication unit). 98 Summer time change I /OFF Choose whether you want the change to summer-/winter time to be automatic or manual. Set the time-change function to be on or off: : OFF: The controller s built-in clock automatically changes +/- one hour on the standardized days for summer time changeover for Central Europe. You change manually between summer and winter time by turning the clock one hour backward or forward. 99 Slave address I The settings are relevant when more controllers are working in the same system. Assign addresses to the slaves: 0: The slave receives information about the outdoor temperature and the system time. - 9: The slave receives information about the outdoor temperature, the system time and control parameters. The slave sends the reference temperature to the master. Extended service 5: The controller is master. The master only sends information about the outdoor temperature and the system time. The master receives reference temperature values from slaves with addresses -9. Cannot be set. The ECL Comfort controllers can be interconnected via the ECL Comfort Bus to perform a larger system. One outdoor sensor can send the same information to all of them. The controller, which is physically connected with the outdoor sensor, is the master of the entire system and gets automatically the address 5. The other controllers in the system can be addressed with a slave number and receive information from the outdoor sensor through the master. Only one address for one slave. Extended service

27 34a Copying with the Store new settings on the All settings, adjustments, etc. can be stored on the ECL Card. Insert the with the yellow side facing you. Go to line 9 (bottom line). 34b Copy to or from? The controller enables you either to copy settings from the to the controller or from the controller to the. The display will show the symbols of the ECL Card (to the left) and the controller (to the right). 0 CPY C99 0 CPY C99 The bar beneath the copy direction line builds up in the copying direction while the copying is in progress. Accept to copy settings from controller to ECL Card. When the copying is finished, display line C will appear. Make sure that you update your adjustments and settings. Copy settings to an additional controller Make sure the other controller uses the same card type. Change copy direction. Accept to copy. Check the type of system(s) and the software generation Insert the with the yellow side facing you. Go to line 9. Go to line 9 (bottom line). Select the copying direction. Copy. Change to a different heating system Purchase an for a different type of heating system. Use this function if you modify or extend the heating system. Accept to copy. After copying the display will show the controller s software generation and the type of system which has been loaded. Line 8 will always show the type of system selected and the software generation. Miscellaneous Miscellaneous The yellow

28 7a Definitions 7b Actual flow temperature Temperature measured in the flow at any time. Comfort period A period of the day where comfort temperature is selected. Comfort temperature Temperature maintained in the heating or hot water circuits during comfort periods. Normally during daytime. Controller mode indicator Black arrow to the right of the symbols indicating the present mode selected. Day plan Schedule for different periods with comfort and reduced temperatures. The day plan can be made individually for each day and may consist of up to 3 comfort periods per day. Desired temperature Temperature which is set as the desired room temperature. The temperature can be controlled only if a room sensor is installed. If no sensor is installed, the desired temperature is only an expression for a possible obtainable room temperature, meaning that the room temperature is controlled by radiator thermostats/valves. Factory settings Settings stored on the to simplify the set up of your controller the first time. Flow temperature reference Temperature calculated by the controller on basis of the outdoor temperature and influences from the room- and/or return sensors. This temperature is used as a set point for the control. Reduced temperature Temperature maintained in the heating/hot water circuit during setback periods. Return temperature Temperature measured in the return pipe. Room sensor Temperature sensor placed in the room where the temperature is to be controlled. The sensor is based on the Pt 000 Ohm type. Room temperature Temperature measured by the room sensor. The room temperature can be controlled only when a sensor is installed. State indicator White arrow to the left of the symbols in the controller mode. The white arrow indicates the present state (comfort or reduced temperature period) when the controller is in automatic mode (the clock symbol). Time bar Bars representing periods with comfort temperature. The bar is divided in half hour sections. Time line Bar with numbers representing the hours in the lower part of the display. Weather compensation Facility enabling the controller to take outdoor weather conditions into consideration for heat control. Weather compensation is based on a user-defined heat curve which determines the flow temperature at varying outdoor temperatures. Function selector Facility making it possible to override the mode of the controller. Each circuit can be overriddden individually. Heating circuit The circuit for heating the room/building. Optimising system Changeover time between two programmed temperature periods. The controller automatically controls the flow temperature in order to reach the comfort temperature at the set time. Pt 000 Ohm sensor All sensors used with the ECL Comfort controller are based on the Pt000 Ohm type. The resistance is 000 Ohm at 0 degrees and it changes with 3.9 degrees.

29 6 Hot points The time shown in the display is one hour off? If the time shown is one hour off, the automatic summer time changeover may work incorrectly. Set the summer time change in line 98 to off. See Extended Service in the Installer s Guide. The time shown in the display is not correct? The internal clock may have been reset, if there has been a power break for more than hours. Set time and date. See section 7 in the Installer s Guide. The is lost? Switch the power off and on again to see the heating system type and the software generation of the controller. Order a replacement from your Danfoss dealer. Insert the new with the yellow side facing you and make sure that you copy your personal settings from the controller to the. See section 34 in the Installer s Guide. The room temperature is too low? If you have radiator thermostats in the same room as the room sensor, please check that the radiator thermostats are set to the highest value. If this does not increase the room temperature, the flow temperature might be too low. Increase the desired temperature by setting a higher value for the desired room temperature or the heat curve. See section in the User s Guide. The temperature is unstable? Check that the flow temperature sensor is correctly mounted and in the right place. Adjust the control parameters. See section 3 in the Installer s Guide. How to make an extra comfort period? You can make an additional comfort period by pushing the shift and + buttons simultaneously. See section 4 of the User s Guide. How to remove a comfort period? You can remove a comfort period by pushing the shift and - buttons simultaneously, and hold for two seconds. See section 4 of the User s Guide. How to restore your personal settings? Insert the with the yellow side facing you. Go to line 9 and select card to controller direction of copying (left to right) using the Shift button. Push + button to copy. See section 5 of the User s Guide.

Installation Guide. ECL Comfort 210 / 310, application A231 / A Table of Contents

Installation Guide. ECL Comfort 210 / 310, application A231 / A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 4 2.1 Before you start.....................................................

More information

ECL Apex 10. User Guide. ECL Apex 10 *087R9745* Installation and configuration. *vijem102*

ECL Apex 10. User Guide. ECL Apex 10 *087R9745* Installation and configuration. *vijem102* User Guide ECL Apex 10 *087R9745* *vijem102* Installation and configuration VI.JE.M1.02 Danfoss 11/2004 DH-SMT VI.JE.M1.02 Danfoss 11/2004 DH-SMT ECL Apex 10 VI.JE.M1.02 Danfoss 11/2004 DH-SMT VI.JE.M1.02

More information

RVD G2383en. Installation. - Compact station - Control cabinet (in the front, on the inner wall or on a

RVD G2383en. Installation. - Compact station - Control cabinet (in the front, on the inner wall or on a 4 319 2968 0 G2383en en Installation Instructions District heating controller for one heating circuit and d.h.w. RVD230 Installation Place of installation In a dry room, e.g. in the heat exchanger room

More information

RVD110 RVD G2381en. Installation. Commissioning

RVD110 RVD G2381en. Installation. Commissioning 4 319 2788 0 G2381en en Installation Instructions District heating and d.h.w. controller RVD110 RVD130 Installation Place of installation In a dry room, e.g. the heat exchanger room Mounting choices: -

More information

G2515. Installation. Place of installation. Electrical installation. Permissible cable lengths. Securing the controller to the base

G2515. Installation. Place of installation. Electrical installation. Permissible cable lengths. Securing the controller to the base 74 319 726 G2515 en Installation Instructions District heating controller for 2 heating circuits and d.h.w. RVD26 Keep these instructions with the controller! Installation Place of installation In a dry

More information

RVD235. G2385en. Installation without base

RVD235. G2385en. Installation without base 2382Z04 G2385en en Installation Instructions District heating controller for one heating circuit and d.h.w. RVD235 Installation without base Place of installation Compact station front or control panel

More information

RVD125/109 RVD145/109

RVD125/109 RVD145/109 G2511 en Installation Instructions District heating and d.h.w. controller RVD125/109 RVD145/109 Installation without base Place of installation Compact station front or control panel front Permissible

More information

RVD120 RVD G2510. Installation. Place of installation. Electrical installation. Permissible cable lengths

RVD120 RVD G2510. Installation. Place of installation. Electrical installation. Permissible cable lengths en Installation Instructions District heating and d.h.w. controller 74 39 68 G25 RVD2 RVD4 Keep these instructions with the controller! Installation Place of installation In a dry room, e.g. the heat exchanger

More information

TC62D Installation Instructions

TC62D Installation Instructions TC62D Installation Instructions January 2007 This TC62D has a return water low temperature limit option. Using the low limit precludes using a room sensor because both sensors plug into the same port.

More information

Rain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English RAIN BIRD ( ) or visit

Rain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English RAIN BIRD ( ) or visit Rain+Birdt Simple To Set r (SST) Setup & Operation Instructions English Installation...2 Tools and Supplies Needed...2 Step 1. Mount r...2 Step 2. Connect Power...2 Indoor r...2 Outdoor r...2 Step 3. Connect

More information

ECL Comfort 310, application A361

ECL Comfort 310, application A361 Operating Guide ECL Comfort 310, application A361 1.0 Table of Contents 1.0 TableofContents...1 1.1 Importantsafetyandproductinformation... 2 2.0 Installation...5 2.1 Beforeyoustart... 5 2.2 Identifyingthesystemtype...

More information

Temperature controls, Type RT

Temperature controls, Type RT MAKING MODERN LIVING POSSIBLE Technical brochure Temperature controls, Type RT RT temperature controls incorporate a temperature controlled, single-pole changeover switch where the contact position depends

More information

GRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/

GRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/ GRUNDFOS INSTRUCTIONS Control HVAC Installation and operating instructions Other languages net.grundfos.com/qr/i/98800750 English (GB) English (GB) Installation and operating instructions Original installation

More information

Battery Operated Advanced Computerized Irrigation Controller Installation and Operating Instructions

Battery Operated Advanced Computerized Irrigation Controller Installation and Operating Instructions Battery Operated Advanced Computerized Irrigation Controller Installation and Operating Instructions This handbook provides the installation and operating instructions for the DC-1 and DC-4 controllers.

More information

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00 Inlet Controller TC5-ITA USER'S MANUAL M 890-00047 rev. 02 K 895-00458 rev. 00 TABLE OF CONTENTS PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 5 Status Leds...5 Internal Switches...6 INSTALLATION

More information

Temperature Controller OVATION 214 User's Guide

Temperature Controller OVATION 214 User's Guide Temperature Controller User's Guide Read this guide carefully before using the controller. 890-00045 rev.00 TABLE OF CONTENTS Page TABLE OF CONTENTS... 2 PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE

More information

Variable speed application guidelines

Variable speed application guidelines Variable speed application guidelines Frequency converter VLT 00 SCROLL COMPRESSORS REFRIGERATION AND AIR CONDITIONING www.danfoss.com Introduction The introduction of speed control for refrigeration

More information

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version Optimal Series Automatic Transfer Switch Installation and User Manual for the OPT2225 Automatic Transfer Switch Full Version File: OPT2225 Rev2.5.doc November, 2004 2 Thank You For Purchasing This DynaGen

More information

MiG2 TIME SWITCHES. 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches

MiG2 TIME SWITCHES. 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches MiG2 TIME SWITCHES 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches The MiG2 series of timers are programmable 365-day time-switches, incorporating: Multiple switching times per day Single and block

More information

M1 Idle Stepper Motor Calibration

M1 Idle Stepper Motor Calibration M1 Idle Stepper Motor Calibration Version 1.0 Published: February 2017 TABLE OF CONTENTS Overview... 2 What is a Stepper Motor?... 2 What is needed?... 2 Four Wire Stepper... 3 Six Wire Stepper Motor...

More information

LK Control v.3 & LK Control v.3 - RA

LK Control v.3 & LK Control v.3 - RA LK Control v.3 & LK Control v.3 - RA Design LK Control v. 3 and LK Control v.3 -RA is complete unit for outdoor temperature-compensated heat regulation, adapted and pre-programmed for LK s Floor Heating

More information

Installation, Service, and Troubleshooting Instructions

Installation, Service, and Troubleshooting Instructions Installation, Service, and Troubleshooting Instructions Page GENERAL........................................ 2 INSTALLATION................................. 2-4 Zone Controller Placement.......................

More information

Remote-adjustable Radiator Controller HR 40 F. Mounting and Operation

Remote-adjustable Radiator Controller HR 40 F. Mounting and Operation Remote-adjustable Radiator Controller HR 40 F Mounting and Operation Content Content Overview 3 Mounting 5 Selecting the mounting site 5 Mounting the drive unit 5 Mounting the operating unit 11 Connecting

More information

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL Temperature Controller TC5+2V4SA Plus USER'S MANUAL NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject

More information

Troubleshooting Bosch Proportional Valves

Troubleshooting Bosch Proportional Valves Troubleshooting Bosch Proportional Valves An Informative Webinar Developed by GPM Hydraulic Consulting, Inc. Instructed By Copyright, 2009 GPM Hydraulic Consulting, Inc. TABLE OF CONTENTS Bosch Valves

More information

CM707 (UK Version) PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

CM707 (UK Version) PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET CM707 (UK Version) PROGRAMMABLE THERMOSTAT PRODUCT SPECIFICATION SHEET The CM707 thermostat is designed to provide automatic time and temperature control of heating systems in villas and apartments. It

More information

Battery Operated Advanced Computerized Irrigation Controller Installation and Operating Instructions

Battery Operated Advanced Computerized Irrigation Controller Installation and Operating Instructions Battery Operated Advanced Computerized Irrigation Controller Installation and Operating Instructions This handbook provides the installation and operating instructions for the DC-1 and DC-4 controllers

More information

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators Installation Sheets Manual 121 Relays and Contactors Section R Technical Bulletin R81EAA Application R81 plug-in electronic

More information

STRA-24 for chilled beams

STRA-24 for chilled beams STRA- Installation and commissioning manual STRA- for chilled beams STRA- is the room controller for the pressure independent (Pi) and constant air volume chilled beams. It is possible to set different

More information

HERZ Electronic room thermostat analog and digital

HERZ Electronic room thermostat analog and digital Dimension in mm 3 F799 11-3 F799 14 HERZ Electronic room thermostat analog and digital Data sheet for F799, Issue 0317 3 F799 15 3 F799 18 Mounting plate Page 1 Technical data 3 F799 11-14 3 F799 15-18

More information

Controller Specification Sheet

Controller Specification Sheet Controller Specification Sheet MC9320AXXXBX Proportional Inhibitor Dosing, Conductivity Bleed Control, Redox Control of Oxidising Biocide and Secondary Biocide Dosing PULSAtrol Controllers are microprocessor

More information

Dynamic Adjustment Procedure for 700-series Digital Controls. Application Note (Revision A,8/1998) Original Instructions

Dynamic Adjustment Procedure for 700-series Digital Controls. Application Note (Revision A,8/1998) Original Instructions Application Note 01304 (Revision A,8/1998) Original Instructions Dynamic Adjustment Procedure for 700-series Digital Controls (700, 701, 701A, 702, 705, 721, 723, 723PLUS, 828) General Precautions Read

More information

Combined Ventilation Controller RVWS-T-224HA

Combined Ventilation Controller RVWS-T-224HA Combined Ventilation Controller RVWS-T-224HA 8-stage Control for Power/Natural Applications 2 variable speed stages, 2 curtain winch stages, 2 fixed speed ventilation stages, 1 thermo/mister cycle stage

More information

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0 APP EOLE4 Applicable to program versions TAC5 Version DT 2.8.2 & DG 2.7.0 2 THE APP EOLE4 INTERFACE This interface can be used on Android, IOS and PC. Download the app from the App Store/Google Play or

More information

Start-Up, Operation and Service Instructions

Start-Up, Operation and Service Instructions Article I. Krueger Proportional LineaHeat W/ Discharge Temperature Start-Up, Operation and Service Instructions SAFETY NOTE Air-handling equipment will provide safe and reliable service when operated within

More information

Installation Instructions Spector compact Conductivity Transmitter System LRGT 16-1

Installation Instructions Spector compact Conductivity Transmitter System LRGT 16-1 Installation Instructions 810701-00 Spector compact Conductivity Transmitter System LRGT 16-1 IMPORTANT NOTES...4 SAFETY NOTES...4 Danger...4 EXPLANATORY NOTES...4 Scope of supply...4 System description...4

More information

Product Manual (Revision A, 8/2015) Original Instructions. ProAct II Digital Speed Control System. Technical Supplement

Product Manual (Revision A, 8/2015) Original Instructions. ProAct II Digital Speed Control System. Technical Supplement Product Manual 36060 (Revision A, 8/2015) Original Instructions ProAct II Digital Speed Control System Technical Supplement DEFINITIONS This is the safety alert symbol. It is used to alert you to potential

More information

Air Conditioning Clinic. HVAC System Control One of the Systems Series TRG-TRC017-EN

Air Conditioning Clinic. HVAC System Control One of the Systems Series TRG-TRC017-EN Air Conditioning Clinic HVAC System Control One of the Systems Series TRG-TRC017-EN NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES BUSINESS REPLY MAIL FIRST-CLASS MAIL PERMIT NO 11 LA CROSSE, WI POSTAGE

More information

Overview of operation modes

Overview of operation modes Overview of operation modes There are three main operation modes available. Any of the modes can be selected at any time. The three main modes are: manual, automatic and mappable modes 1 to 4. The MapDCCD

More information

DENISON HYDRAULICS Jupiter 500 Driver Card Series S

DENISON HYDRAULICS Jupiter 500 Driver Card Series S Back to Content DENISON HYDRAULICS Jupiter 500 Driver Card Series S20-11712-0 Publ. 9-AM681 E-Mail: denison@denisonhydraulics.com Internet: http://www.denisonhydraulics.com SYSTEM FEATURES SYSTEM FEATURES

More information

Revision THERMO TECHNOLOGIES. USDT 2001 Differential Controller. Installation and User s Guide

Revision THERMO TECHNOLOGIES. USDT 2001 Differential Controller. Installation and User s Guide Revision 8 THERMO TECHNOLOGIES USDT 2001 Differential Controller Installation and User s Guide USDT 2001 DIFFERENTIAL CONTROLLER Installation and User s Guide Table of Contents Introduction General Information

More information

HBLT-C1 Controller. Instruction Manual. For pump control of levels in industrial refrigeration systems

HBLT-C1 Controller. Instruction Manual. For pump control of levels in industrial refrigeration systems Instruction Manual HBLT-C1 Controller For pump control of levels in industrial refrigeration systems Instruction manual HBLT-C1 Controller (006-UK) 1 / 14 Table of Contents Safety Instructions... 3 Introduction...

More information

Version 11 Controls for natural ventilation. NV Comfort Standard / Plus KNX control

Version 11 Controls for natural ventilation. NV Comfort Standard / Plus KNX control Version 11 Controls for natural ventilation NV Comfort Standard / Plus KNX control NV Comfort software card 230V 1.20 NV Comfort basis package Application central control of indoor climate with the potential

More information

Operations Manual. Automated Fuel Maintenance System FUEL TECHNOLOGIES INTERNATIONAL

Operations Manual. Automated Fuel Maintenance System FUEL TECHNOLOGIES INTERNATIONAL Operations Manual Automated Fuel Maintenance System FTI-10A & 20A FUEL TECHNOLOGIES INTERNATIONAL Replacement Manuals Available on Website: www.fueltechnologiesinternational.com 07/15/2015 Rev E Fuel Technologies

More information

Silencers. Transmission and Insertion Loss

Silencers. Transmission and Insertion Loss Silencers Practical silencers are complex devices, which operate reducing pressure oscillations before they reach the atmosphere, producing the minimum possible loss of engine performance. However they

More information

RATE CONTROLLED TORQUE WRENCH TESTER

RATE CONTROLLED TORQUE WRENCH TESTER RATE CONTROLLED TORQUE WRENCH TESTER OPERATOR S HANDBOOK (PART NO. 34078) ISSUE 8 NORBAR TORQUE TOOLS LTD, Beaumont Road, Banbury, Oxfordshire, OX16 1XJ, UNITED KINGDOM Tel : + 44 (0) 1295 270333, Fax

More information

Features: Enhanced throttle response, excellent acceleration, linearity and driveability

Features: Enhanced throttle response, excellent acceleration, linearity and driveability 120A/150A ESC X-Car 120A/150A Series Sensored/Sensorless Brushless ESC for 1:8 scale Car or Truck Thank you for purchasing the X-Car Brushless Electronic Speed Controller (ESC). The X-Car 1:8 Scale 120A/150A

More information

WP Series Solar Charge Controller User s Manual. Please read this manual carefully before using this product.

WP Series Solar Charge Controller User s Manual. Please read this manual carefully before using this product. WP Series Solar Charge Controller User s Manual Please read this manual carefully before using this product. Content 1. Safety attentions... 1 2. Introduction of WP series solar charge controller... 2

More information

Tension Control Inverter

Tension Control Inverter Tension Control Inverter MD330 User Manual V0.0 Contents Chapter 1 Overview...1 Chapter 2 Tension Control Principles...2 2.1 Schematic diagram for typical curling tension control...2 2.2 Tension control

More information

EXPERT 2V4SA. Temperature Controller. User s manual CLEAN MODE COMPENSATION HUMIDITY OUTSIDE TEMPERATURE

EXPERT 2V4SA. Temperature Controller. User s manual CLEAN MODE COMPENSATION HUMIDITY OUTSIDE TEMPERATURE CLEAN MODE Temperature Controller User s manual CURRENT CONDITIONS ROOM TEMPERATURE PROBE TEMPERATURE OUTSIDE TEMPERATURE RELATIVE HUMIDITY STATIC PRESSURE TIME / DATE SETTINGS SET POINT / CURVE MINIMUM

More information

WP37 & HT37 User Manual

WP37 & HT37 User Manual WP37 & HT37 User Manual Origio WP37 & HT37 Warming Plates & Heated Trolley Warming Plates WP37 300 WP37 500 Heated Trolley HT37 Origio WP37 Component Description Heated work surface Model WP37 300 Power

More information

ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE A

ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE A ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE 012945A0 040906 1 MAIN FEATURES Power supply 230V~ ±10% 50Hz Backlit alphanumeric LCD display Management of 5 output

More information

GENERATION, CONVERSION, OR DISTRIBUTION OF ELECTRIC POWER

GENERATION, CONVERSION, OR DISTRIBUTION OF ELECTRIC POWER XXXX H02 GENERATION, CONVERSION, OR DISTRIBUTION OF ELECTRIC POWER XXXX CONTROL OR REGULATION OF ELECTRIC MOTORS, GENERATORS, OR DYNAMO-ELECTRIC CONVERTERS; CONTROLLING TRANSFORMERS, REACTORS OR CHOKE

More information

ST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number

ST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number ST48-WHUV.12 PID controller Order number 935.15 Wiring diagram Product description This micro-processed controller serves for temperature control at high measuring accuracy. Beside resistance sensors and

More information

MAGPOWR Spyder-Plus-S1 Tension Control

MAGPOWR Spyder-Plus-S1 Tension Control MAGPOWR TENSION CONTROL MAGPOWR Spyder-Plus-S1 Tension Control Instruction Manual Figure 1 EN MI 850A351 1 A COPYRIGHT All of the information herein is the exclusive proprietary property of Maxcess International,

More information

N-03 STEERING GEAR CONTROL SYSTEMS

N-03 STEERING GEAR CONTROL SYSTEMS Guideline No.: N-03(201510) N-03 STEERING GEAR CONTROL SYSTEMS Issued date: October 20,2015 China Classification Society Foreword: This Guideline is a part of CCS Rules, which contains technical requirements,

More information

MANIFOLDS & WATER TEMPERATURE CONTROL

MANIFOLDS & WATER TEMPERATURE CONTROL MANIFOLDS & WATER TEMPERATURE CONTROL Overview Water based underfloor heating (UFH) systems work by turning the entire floor into one large low temperature radiator which is heated via a network of pipes

More information

Installation and User Manual. with RAIN SENSOR.

Installation and User Manual. with RAIN SENSOR. with RAIN SENSOR www.solarsmartopener.com Revision..0 TABLE OF CONTENTS Features In The Box Further Items Required Basic Operation Solar Panel and Operator Installation Operator Installation Solar Panel

More information

AC Irrigation and Propagation Controllers I Four Station, 5006-I and 5006-IP Six Station

AC Irrigation and Propagation Controllers I Four Station, 5006-I and 5006-IP Six Station AC Irrigation and Propagation Controllers 5004-I Four Station, 5006-I and 5006-IP Six Station I N S T R U C T I O N M A N U A L Table of contents Introduction 1 1. Specifications 1 2. Controller Mounting

More information

OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets

OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets Art. nr. 40200261 OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets WHISPERPOWER BV Kelvinlaan 82 9207 JB Drachten Netherlands Tel.: +31-512-571550 Fax.: +31-512-571599

More information

Induction Power Supplies

Induction Power Supplies Induction Power Supplies 7.5kW; 135 400kHz 480V version (Integral Heat Station) User s Guide Model 7.5-135/400-3-480 SMD Control Brds Rev. D 5/08 Table of Contents 1. Specifications and features...3 2.

More information

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016 PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS v1.1 Revised Table of Contents 1 Common Alarms and Warnings... 1 2 Common Issues... 6 2.1 Communication problems... 6 2.1.1 Controller communication

More information

CONTROL PTY LTD Phone: (02) UNIT 14/62 OWEN ST Fax: (02) GLENDENNING NSW 2761 INCA MODEL PV2

CONTROL PTY LTD Phone: (02) UNIT 14/62 OWEN ST Fax: (02) GLENDENNING NSW 2761 INCA MODEL PV2 1 INCA CONTROL PTY LTD Phone: (02) 9675 3815 UNIT 14/62 OWEN ST Fax: (02) 9675 1381 GLENDENNING NSW 2761 ELECTRICAL ENGINEERS Email: sales@incacontrol.com.au Design & Manufacture of: Custom-built switchboards

More information

V200 V200. Control on water, proportional integral. Simplified Master / Slave operation GENERAL DESCRIPTION

V200 V200. Control on water, proportional integral. Simplified Master / Slave operation GENERAL DESCRIPTION Master Slave 1 Slave (n + 1) Master Slave 1 Slave (n + 1) Simplified Master / Slave operation GENERAL is a CIAT electronic control system designed to control non-independent air conditioning terminal units

More information

CHAPTER 6 INTRODUCTION TO MOTORS AND GENERATORS

CHAPTER 6 INTRODUCTION TO MOTORS AND GENERATORS CHAPTER 6 INTRODUCTION TO MOTORS AND GENERATORS Objective Describe the necessary conditions for motor and generator operation. Calculate the force on a conductor carrying current in the presence of the

More information

TECHNICAL HANDBOOK. for MULTISPLIT NETWORK SYSTEMS OR GROUP CONTROL

TECHNICAL HANDBOOK. for MULTISPLIT NETWORK SYSTEMS OR GROUP CONTROL TECHNICAL HANDBOOK for MULTISPLIT NETWORK SYSTEMS OR GROUP CONTROL DESCRIPTION * Compatible with IMPACT E, IMAGE E and IMAGE 600² E systems * Configurable as either group control or multisplit * Single

More information

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS HVAC/BAC ELECTRIC IOM ELECTRIC ACTUATOR E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS Electric Actuator Specifications... 2 Overview... 3 Actuator

More information

The Brake Assist System

The Brake Assist System Service. Self-study programme 264 The Brake Assist System Design and function Accident statistics show that in 1999 alone, 493,527 accidents in Germany were caused by driver error. Many accidents caused

More information

Model 1:8 Beast-ZTWSS120A 1:8 Beast-ZTWSS150A. PN#Model Cont.Current 120A 150A. Burst Current 760A 1080A

Model 1:8 Beast-ZTWSS120A 1:8 Beast-ZTWSS150A. PN#Model Cont.Current 120A 150A. Burst Current 760A 1080A Alien Power System BEAST Series Sensored/Sensorless Brushless ESC for 1:8 scale Car or Truck Thank you for purchasing the Alien Power System Brushless Electronic Speed Controller (ESC). The Alien Power

More information

CM707 PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

CM707 PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET CM707 PROGRAMMABLE THERMOSTAT PRODUCT SPECIFICATION SHEET The CM707 thermostat is designed to provide automatic time and temperature control of heating systems in villas and apartments. It can be used

More information

HECU Clock frequency 32 MHz 50 MHz Memory 128 KB 512 KB Switch Orifice Orifice. Operating temperature - 40 C to 150 C - 40 C to 150 C

HECU Clock frequency 32 MHz 50 MHz Memory 128 KB 512 KB Switch Orifice Orifice. Operating temperature - 40 C to 150 C - 40 C to 150 C 489000 113 1. SPECIFICATION Unit Description Specification ABS ESP HECU Clock frequency 32 MHz 50 MHz Memory 128 KB 512 KB Switch Orifice Orifice Wheel speed sensor ABS / ESP CBS Operating temperature

More information

Electric Actuator Instructions

Electric Actuator Instructions BAC IOM Electric Actuator Instructions E024, E025, E026, E029 & E030 TABLE OF CONTENTS Electric Actuator Specifications...2 Overview...3 Actuator Wiring Diagrams...4 VMS-35 Specifications and Wiring Diagram...5

More information

Project Manual Industrial Hydraulics

Project Manual Industrial Hydraulics Electric Drives and Controls Hydraulics Linear Motion and Assembly Technologies Pneumatics Service Project Manual Industrial Hydraulics RE 00845/04.07 Trainer s manual Electric Drives and Controls Hydraulics

More information

Features: Enhanced throttle response, excellent acceleration, strong brakes and throttle linearity. Using LED program card to make adjustments.

Features: Enhanced throttle response, excellent acceleration, strong brakes and throttle linearity. Using LED program card to make adjustments. Thank you for purchasing the ZTW Brushless Electronic Speed Controller (ESC). The ZTW 1:10 Scale BEAST Series ESC is specifically designed for operating 4 Pole Sensorless brushless motors. This is a high

More information

i n s t r u c t i o n m a n u a l

i n s t r u c t i o n m a n u a l i n s t r u c t i o n m a n u a l 8006 Six-Station AC Timer Residential/Light Commercial Independent Program Irrigation Controllers Installation, Programming and Operating Instructions Features Operates

More information

Automatic Genset Controller, AGC-4 Display readings Push-button functions Alarm handling Log list

Automatic Genset Controller, AGC-4 Display readings Push-button functions Alarm handling Log list OPERATOR'S MANUAL Automatic Genset Controller, AGC-4 Display readings Push-button functions handling Log list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com

More information

Declaration of Conformity No. 42/2010

Declaration of Conformity No. 42/2010 -1- ST-431 user manual Declaration of Conformity No. 42/2010 Hereby, we declare under sole responsibility that the ST-431 230V 50Hz thermoregulator manufactured by TECH, ul. St. Batorego 14, 34-120 Andrychów,

More information

AQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start)

AQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start) AQUASTAR C6 (Comfort 6000) Next Generation Auto Backwash Valve System (selectable time-pressure or remote cycle start) SIDE MOUNTED AND TOP MOUNTED VALVES WITH QUICK INSTALL ELECTRIC ACTUATORS FOR PIPE

More information

AGA Oil to Electric Conversion kit with AIMS (AGA INTELLIGENT MANAGEMENT SYSTEM)

AGA Oil to Electric Conversion kit with AIMS (AGA INTELLIGENT MANAGEMENT SYSTEM) AGA Oil to Electric Conversion kit with AIMS (AGA INTELLIGENT MANAGEMENT SYSTEM) FREQUENTLY ASKED QUESTIONS AIMS was discontinued as a factory option for 13amp electric and gas AGAs in 2015 however the

More information

Circuit breaker interlocking and operation requirements SIEMENS

Circuit breaker interlocking and operation requirements SIEMENS Circuit breaker interlocking and operation requirements SIEMENS When manufacturers and specifiers discuss circuit breaker operational and interlocking requirements, several terms are used repeatedly. Despite

More information

4KVA/5KVA Parallel Installation Guide

4KVA/5KVA Parallel Installation Guide 1. Introduction 4KVA/5KVA Parallel Installation Guide This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to 6 units. The supported maximum

More information

User manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS.

User manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS. User manual Manual version: 2.4 dated 27/02/08 Program code: FLSTDmMCDE LEGGI

More information

VisionPRO 8000 Thermostats

VisionPRO 8000 Thermostats VisionPRO 8000 Thermostats INSTALLER SETUP AND SYSTEM TEST POCKET GUIDE 62-0266 INSTALLER SETUP 1. Press SYSTEM. FAN ON AUTO Inside SYSTEM HEAT AM SCHED HOLD M24079 2. Press and hold these two blank buttons

More information

Pilot control unit with end position lock for the remote control of directional valves

Pilot control unit with end position lock for the remote control of directional valves Pilot control unit with end position lock for the remote control of directional valves RE 64 553/02.07 1/12 Replaces : 05.05 Type 4THF6 or 5THF6 Series 2X Contents Functional description, section, symbol

More information

Rally computer 3 Rally computer 3.GPS *

Rally computer 3 Rally computer 3.GPS * Rally computer 3 Rally computer 3.GPS * User manual. Installation and configuration instructions. (with links to video instructions online at : www.rallycomputer.com ) * Content marked applies only to

More information

SE8300 Series Installation Guide 24 Vac Low Voltage

SE8300 Series Installation Guide 24 Vac Low Voltage Installation Guide 24 Vac Voltage mercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Configurable BI/UI Universal Inputs Overview 3 Setup Screen Display 3 Terminal Identification

More information

Tecomotive - tinycwa - User Manual Intercooler Version

Tecomotive - tinycwa - User Manual Intercooler Version Tecomotive - tinycwa - User Manual Intercooler Version Operation Overview When activated the controller is measuring the coolant temperature and the rate of increase with the connected temperature sensor.

More information

DS DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL

DS DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL DS 2.042 07/02 TM DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL DC1100 Specification No. 04-03-105 The DC1100 energy controller is a self configuring

More information

three different ways, so it is important to be aware of how flow is to be specified

three different ways, so it is important to be aware of how flow is to be specified Flow-control valves Flow-control valves include simple s to sophisticated closed-loop electrohydraulic valves that automatically adjust to variations in pressure and temperature. The purpose of flow control

More information

MANUAL. SIMRAD FU25 and FU50 Steering Levers

MANUAL. SIMRAD FU25 and FU50 Steering Levers MANUAL SIMRAD FU25 and FU50 Steering Levers 20221065E English Simrad FU25 and FU50 Follow-up steering levers 2 20221065 / E Introduction Instruction Manual This manual is intended as a reference guide

More information

MX431 Generator Automatic Voltage Regulator Operation Manual

MX431 Generator Automatic Voltage Regulator Operation Manual Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator 1 1. SPECIFICATION Sensing Input Voltage Frequency 190 ~ 264 VAC Max, 1 phase, 2 wire 50 / 60 Hz, selectable

More information

Declaration of Conformity No. 33/2010

Declaration of Conformity No. 33/2010 tech -1- ST 430 user's manual Declaration of Conformity No. 33/2010 Hereby, we declare under sole responsibility that the ST-430 230V, 50Hz thermoregulator manufactured by TECH, ul. St. Batorego 14, 34-120

More information

Temperature Controller TC5-2V8SA USER'S MANUAL. M rev. 03 K rev. 00

Temperature Controller TC5-2V8SA USER'S MANUAL. M rev. 03 K rev. 00 Temperature Controller USER'S MANUAL M 890-00174 rev. 03 K 895-00327 rev. 00 TABLE OF CONTENTS Page PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 6 Controller Status Leds... 7 Internal Switches...

More information

Forging Industry Technical Conference Long Beach, CA

Forging Industry Technical Conference Long Beach, CA Forging Industry Technical Conference Long Beach, CA Servo Direct drive for Hydraulic Machines Mike Gill LASCO Engineering Services, LLC September 11 12, 2018 What is Servo Direct Drive hydraulic? Servo

More information

Battery, Mounting and Cables - Battery and Cables Description and Operation

Battery, Mounting and Cables - Battery and Cables Description and Operation Battery, Mounting and Cables - Battery and Cables Description and Operation COMPONENT LOCATION - SINGLE BATTERY VEHICLES Item 1 2 3 4 5 6 7 8 9 10 Description Jump start terminal negative (-) Jump start

More information

DKG-705 AUTOMATIC MAINS FAILURE AND REMOTE START UNIT WITH PARALLEL TO MAINS AND DUAL GENSET PARALLEL FEATURES

DKG-705 AUTOMATIC MAINS FAILURE AND REMOTE START UNIT WITH PARALLEL TO MAINS AND DUAL GENSET PARALLEL FEATURES Genset Automation Control Pte Ltd DKG-705 AUTOMATIC MAINS FAILURE AND REMOTE START UNIT WITH PARALLEL TO MAINS AND DUAL GENSET PARALLEL FEATURES FEATURES Automatic mains failure, Remote start operation,

More information

Inlet Controller SB3500 USER'S MANUAL

Inlet Controller SB3500 USER'S MANUAL Inlet Controller USER'S MANUAL NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject to change without notice

More information

User Manual Solar Charge Controller 3KW

User Manual Solar Charge Controller 3KW User Manual Solar Charge Controller 3KW Version: 1.3 CONTENTS 1 ABOUT THIS MANUAL... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 SAFETY INSTRUCTIONS... 1 2 INTRODUCTION... 2 2.1 Features... 2 2.2 Product Overview...

More information

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number: INSTRUCTION MANUAL FOR VOLTAGE REGULATOR Model: APR 125-5 Part Number: 9 1688 00 100 Publication Number: 9 1688 00 990 Revision H: 07/2001 CONTENTS SECTION 1 GENERAL INFORMATION...1-1 DESCRIPTION... 1-1

More information

HT-DDD100 Digital Dual Driver Governor. Instruction manual

HT-DDD100 Digital Dual Driver Governor. Instruction manual Instruction manual Doc. No.: HT-DDD100_MN_DE_ Version: 1.2 Edition: Table of contents Installation declaration (for an incomplete machine)... 4 1 General... 5 1.1 Introduction... 5 1.2 Safety instructions

More information