SPEEDRIVE INSTRUCTIONS MANUAL
|
|
- William Hines
- 5 years ago
- Views:
Transcription
1 EN SPEEDRIVE INSTRUCTIONS MANUAL
2 Safety warning. The following symbols shown beside a paragraph represent danger warnings associated to the failure to comply with the corresponding instructions. DANGER! Risk of electrocution. DANGER! Not observing this precaution involves a risk of electrocution. Warns that not observing the precaution involves a risk of damage to people and/or materials. WARNING Warns that not observing the precaution involves a risk of damage to the pump or the installation. TABLE OF CONTENTS 1) GENERAL INFORMATION...3 2) TECHNICAL SPECIFICATIONS ) Models ) Dimensions ) Features ) INSTALLATION ) Hydraulic installation ) Electrical connection to the motor ) Installation on the pump ) Power supply connection ) Signals wires connection ) OPERATING MODES ) SETUP ) Definitions ) Browsing ) Description of the menus ) PROTECTION AND ERRORS ELECTRONIC CIRCUIT FAILURE ) MULTIPLE OPERATION ) Booster set with "On-Off" auxiliary pumps ) Booster set with inverter regulated auxiliary pumps ) MAIN COMPONENTS ) EVIDENCE OF CONFORMITY ) LOW VOLTAGE ) ELECTROMAGNETIC COMPATIBILITY ) OTHER INSTALLATIONS ) MENU DIAGRAM
3 1) GENERAL INFORMATION. The Speedrive inverters have been designed to adjust the speed of three-phase motors used with water pumps. The inverter receives a signal from the pressure transducer that is proportional to the installation's pressure. This signal is processed and it regulates the speed of the motor to keep the pressure constant, even though the consumption of water varies. It can be used with 50Hz or 60Hz motors. Selecting the output frequency with the menu option. The units have a constant pressure control system. The PI system used provides two numerical constants that are processed by the unit to achieve a stable regulation. This type of regulation can greatly reduce the consumption of energy when compared to unregulated systems, since the consumption of electricity will be proportional to the consumption of water. Another of the advantages of regulated units is the decrease in voltage surges, softening current peaks and, therefore, increasing the working life of the pump. WARNING: Correct compliance with the installation and operating instructions and the electrical connection diagrams will guarantee the correct operation of the unit. DANGER: The failure to follow the instructions in this Manual can lead to motor overloads, diminishment in technical characteristics, reduction of the unit's working life and all types of subsequent results, for which we decline any responsibility. 2) TECHNICAL SPECIFICATIONS. 2.1) Models. Model Speedrive M2 2.2) Dimensions. Power supply voltage [V] 1~ 230V AC ±10% INPUT OUTPUT Dimensions Weight Max. Recommended Max. Motor rated line motor voltage A B current protection current [A] [A] [A] [V] [mm] [mm] [kg] ~ 230V AC T2 3~ 400V AC ~ 400V T3 ±10% AC ) Features. Degree of protection: IP55. Maximum working ambient temperature: 40 ºC. Inputs: 1 analogue 4-20mA, with 24V DC power supply. 1 digital input for the level switch. Outputs: Only M..., 1 potential-free contact, maximum current 2A at 250V AC. Communications: RS 485 serial port
4 3) INSTALLATION. 3.1) Hydraulic installation ) Installation layout. 1. Pump with Speedrive Non-return valve. Not required others non-return valves in the delivery pipe. 3. Pressure transducer. The 4-20 ma, 10 bar type, EMC according EN Accumulator. Its sole function is to compensate minor water losses in the installation, preventing continuous pump start-ups and stops. The accumulator's volume must be at least 10% of the nominal flow of the pump(s) installed, calculated in litres per minute. (For ex.: Multi35 5, QMAX=100 [l/min]x0.1=10 accumulator 10l) The preload pressure must be 1 bar below to the rated pressure ) Hydraulic connections. See the pump manual. For facilities in negative suction, it is required that the pipes are primed completely. 3.2) Electrical connection to the motor ) Speedrive with single-phase input (Figure 1): The motor must be connected to a 230 V power supply source. The cable (1) supplied with the inverter must be connected to the motor. If you wish to activate the 60Hz motor output, select the corresponding parameter in the menu. Make sure that electrical consumption shown on the motor's data plate does not exceed that supplied by the inverter. DANGER. Risk of electrocution. Always connect the supplied grounding cable (2) between the motor and inverter set. DANGER. Risk of electrocution. Never open the Speedrive cover before disconnecting the power supply during at least 5 minutes. Yellow/Green Black Brown Blue Figure 1-4 -
5 3.2.2) Speedrive with three-phase input (Figure 2): The motor must be connected to a 400 V power supply source. The cable (1) supplied with the frequency inverter must be connected to the motor. If you wish to activate the 60Hz motor output, select the corresponding parameter in the menu. Make sure that electrical consumption shown on the motor's data plate does not exceed that supplied by the inverter. DANGER. Risk of electrocution. Always connect the supplied grounding cable (2) between the motor and inverter set. DANGER. Risk of electrocution. Never open the Speedrive cover before disconnecting the power supply during at least 5 minutes. Yellow/Green Negro Marrón Azul Black Brown Blue Figure 2 3.3) Installation on the pump. The Speedrive is installed on the motor with a special supplied adapter. The inverter is cooled with the use of the motor's cooling elements. The unit has been designed for vertical and horizontal installation ) Motor adapter (Figure 3): Replace the connections box with the supplied motor adapter. Use the same screws. Torque 1~1.2 Nm. Figure 3-5 -
6 3.3.2) Speedrive. e. Installation of the Speedrive on the adapter. Use the screws (1) supplied. Torque: 3 Nm. Single-Phase Version Three-Phase Version 1 1 Prepare the motor wires with ferrites: connect the grounding wire (2) Connect the motor wires to the provided socket (3) Single-Phase Version Three-Phase Version Figure 4 Figure 5-6 -
7 3.4) Power supply connection. DANGER. Risk of electrocution. Connection and grounding are compulsory. All electrical connections will be in accordance with the IEC Regulations (electrical installation in buildings) or the regulations in force in the destination country and local regulations. The power supply line of equipment must be adequately protected. These protection elements will prevent damage to persons during an electrical leakage. An exclusive power supply line is recommended. The system protection will be based on an earth leakage switch (I n = 30 ma). The recommended earth leakage switch is "class A" for pulsed and continuous currents, marked with the following symbols: The earth leakage value will depend on the number of units connected to the line and their power. Motor size Leakage current 0.75 to 3 kw < 3.5 ma 4 to 5.5 kw < 5 ma The electrical installation should have a multiple separation system with contact openings 3 mm. Single-phase frequency inverters. These units are supplied with a H07 RN-F power supply cable, 2m length and a connection plug. The power supply input must be single-phase, at 230 V, 50 or 60 Hz. See Figure 6 for reference. Voltage variations allowed ±10 Three-phase frequency inverters. These units have a three-phase power supply input, at 400 V, 50 or 60 Hz. The cabling procedures must be undertaken by a professional installation entity. Connection socket according figure 5 (4). Connections, in accordance with Figure 7. 7 Voltage variations allowed ±10%. Preparing the power supply wires: - 7 -
8 3.5) Signals wires connection. Single-phase version Three-Phase Version Figure 6 Figure RS 485 communications output to connect various inverters. Up to 4 units. 2.- Auxiliary input for an external level switch or a potential-free contact to activate or stop the circuit. Note: This input is supplied from the factory with an electric cable bridge. 3.- Input of the 4-20mA pressure transducer. 4.- Potential-free auxiliary input. Not used. 5.- Auxiliary transducer input. Not used. 6.- Only in single-phase versions. 230 V potential output, 2A maximum, external display or acoustic operation for alarm signals. 7.- Micro-switches used to configure the inverter's operation. WARNING: All external cabling connections must use terminal tips on the ends of each cable. External cables must comply with the corresponding electrical safety and insulation regulations. Installation should be made by qualified service personnel. Avoid any cable pieces from falling inside the circuit, which could lead to its destruction. DANGER. Risk of electrocution. If the unit has to be uncovered due to any circumstance, first disconnect the power supply and wait 5 minutes before starting work with the circuit. The circuit's capacitors store energy. There is enough energy inside the circuit to cause a strong electric discharge, even when the unit is not powered
9 If necessary, reconnect the display cable to the motherboard. Give special attention to positioning. Single-Phase Version Three-Phase Version 4) OPERATING MODES. Automatic mode. This is the common operating mode. The inverter controls the motor's rotation speed to maintain a constant pressure in the installation (set pressure). Manual mode. Allows the pump start-up or stop manually at an adjustable frequency. 5) SETUP. Espa ESD pumps and Espa pressure booster sets are pre-configured in origin with an optimum pressure set point for equipped pumps. Do not need any further adjustment. Speedrive module purchased separately, is necessary its configuration, according to the following paragraphs. 5.1) Definitions. Set pressure: is the pressure that the unit will maintain in the installation. Differential l pressure: is the differential pressure required for the unit to activate again. Stop frequency: frequency at which the inverter stops the pump. Stop delay: timer used by the unit before it stops. Auxiliary on-off off pump: auxiliary pump that is not equipped with Speedrive. Auxiliary regulated pump: auxiliary pump that is equipped with a Speedrive. 5.2) Browsing. Screen displaying the menus Failure See description on screen Flashing = pump waiting Fixed = pump operating Power supply plug-in Browsing keys Browsing the menus. Variation of the flashing parameter. Browsing a submenu
10 Accepting changes. Return to the general screen from display of parameters. Pressure: View 2.0bar Menu Backlight The screen is backlit display for better reading. To save power, the backlight turns off in 60 seconds without pressing any keys. To activate the backlight, press OK. Without backlight does not work any other key. 5.3) Description of the menus. START SCREENS Introduction screen Displayed during a few seconds when connecting the equipment. Indicates: model, software version and pressure sensor configuration. MAIN SCREEN Start screen The pump is not activated. To start the pump manually, press (Man) For automatic operation, press (Auto) To configure parameters, press (Config) It shows the system pressure. The pump will run automatically, as needed. To display parameters, press (View) To return to the start screen, press (Menu) MANUAL OPERATION It shows the system pressure and Speedrive output frequency. Press ON, to activate the pump. Start-up is always performed at 15Hz. Press OFF, to stop the pump. Press or, to adjust the frequency. Press OK to exit the screen. CONFIGURATION Screen descriptions: - Top : parameter being configured. - Lower left : current value of the parameter. - Lower right, "flashing": new value being configured. Press OK to confirm. LANGUAGE Select the desired language. MOTOR FREQUENCY Configuration of the nominal frequency of the motor, 50Hz or 60Hz. Check the motor's nameplate. Note: This screen only appears in the initial preset or retrieving the factory settings. MAXIMUM PUMP HEIGHT Setting the maximum pressure the pump can provide. Check the pump s nameplate. Note: This screen only appears in the initial preset or retrieving the factory settings
11 MAXIMUM MOTOR CURRENT Maximum operating current of the motor. Adjust in accordance with the motor's data plate, plus 10%. Note: This screen only appears in the initial preset or retrieving the factory settings NOMINAL PRESSURE Configuration of the work pressure of the unit. CONFIGURATION OF THE STOP FREQUENCY ADDITIONAL PARAMETERS SETTING CALCULATED STOP FREQUENCY The stop frequency is calculated automatically. Will be recalculated every time that is changed the nominal pressure. To set a value in the manual mode, press (Man) STOP FREQUENCY MANUALLY Enter the desired stop frequency. Note: This value should only be entered by experts. FINE ADJUSTMENTS To set additional parameters, press (Config) To complete the setup, press (Exit) DIFFERENTIAL PRESSURE Configuration of the difference between the set and start-up pressure. For ex. : 3 bars set 0.5 bars differential = 2.5 bars start-up STOP DELAY Timing of the unit before a stop. This timing process is associated to the stop frequency. REVESE ROTATION To check the motor rotation direction, press (Check) To change rotation direction, press (Change) Starting the motor, to 25Hz, for CHECK TURN DIRECTION Press ON, to activate the pump. Press OFF, to stop the pump. Press OK to exit the screen. Confirm INVERT TURN. Change to "YES" to reverse the turn direction AUXILIARY PUMPS For adjust auxiliary pumps parameters, press (Adjust) If there are no regulated pumps, press to advance to screen
12 CONFIGURATION SUBMENU FOR AUXILIARY PUMPS MAXIMUM CURRENT OF THE AUXILIARY PUMP (ELV only) Maximum motor current of the auxiliary pumps equipped with "ELV" box. All motors have the same power rating. Adjust in accordance with the motor's data plate, plus 10%. For auxiliary pumps equipped with "SPEEDRIVE" box this parameter must be regulated individually, for each equipment. The value of this screen is ignored. FREQUENCY "ON" FOR AUXILIARY PUMPS Auxiliary pump activation frequency. Maximum frequency achieved by the main pump. At this frequency, the 1 st auxiliary pump is activated, lowering the main pump frequency until it balances the set pressure. If the main pump reaches this frequency again, the 2 nd auxiliary pump will be activated, and so forth. The number of auxiliary pumps does not have to be determined, since the circuit communications system detects its number. DELAY ON Delay time between the activation of auxiliary pumps. Avoid continuous start-ups of reserve pumps due to fluctuations in the installation. HYSTERESIS OFF Difference between the stop frequency of the main pump and each auxiliary pump. DELAY HYSTERESIS OFF Delay time in the stop sequence of auxiliary pumps. PARAMETER RESET FACTORY PARAMETER To reset all changes of parameters and return to default settings, click OK. Confirm the change to default parameters. Select "Yes" and click OK to return to the default settings. CONFIGURATION OF ADVANCED PARAMETERS AND METER RESET ADVANCED PARAMETERS To modify the advanced parameters or reset the meters, press To complete the setup, click OK. ATTENTION. These parameters can only be configured by expert staff. PASSWORD There are 2 passwords available, depending on the action: + OK: to reset all meters. + OK: to adjust the unit's regulation and operation
13 SUBMENU USED TO RESET METERS (password ) RESET METER Select "Yes" and click OK to reset all meters. Confirm RESET METER. Select "Yes" and click OK to confirm reset all meters. RESET ALARMS Select "Yes" and click OK to reset all alarms. Confirm RESET ALARMS. Select "Yes" and click OK to confirm reset all alarms. SUBMENU FOR THE CONFIGURATION OF ADVANCED PARAMETERS (password ) WORK PROPORTIONAL CONSTANT Allows the variation of the unit's proportional constant after start-up. WORK INTEGRAL CONSTANT Allows the variation of the unit's integral constant after start-up. START PROPORTIONAL CONSTANT Allows the variation of the unit's proportional constant upon start-up. STAR INTEGRAL CONSTANT Allows the variation of the unit's integral constant upon start-up. PWM FREQUENCY (Pulse Width Modulation) Allows the variation of the internal module switching tasks. A high-pitched sound will be heard from the motor (depending on the type of motor) when the switching frequency is varied. DISPLAY OF PARAMETERS DISPLAY OF PARAMETERS Press OK to confirm. Parameters can only be displayed, not modified. To display the alarms, press (Alarm) To return to the main screen, press (Auto) From any screen, tap OK to return to the main screen 2.1 NOMINAL PRESSURE Work pressure assigned to the unit
14 DIFFERENTIAL PRESSURE Difference between the set and start-up pressure. For ex. : 3 bars set 0.5 bars differential = 2.5 bars start-up MAXIMUM MOTOR CURRENT Maximum configured current/ Present current STOP FREQUENCY Stop frequency of the inverter / Present output frequency STOP DELAY Timing before a stop. MODULE TEMPERATURE Current temperature of the module or circuit. DISPLAY OF THE ALARM LOG DISPLAY ALARMS Press OK to confirm. To display the log, press (Hist) To display the parameters, press (Param) From any screen, tap OK to return to the main screen 2.1 OVERCURRENT Number of times an overcurrent is detected. (see Section 6) SHORT-CIRCUIT Number of times a fault caused by a short-circuit is detected. (see Section 6) VOLTAGE Number of times the inverter has stopped due to a voltage fault. (see Section 6) MODULE TEMPERATURE Number of times the inverter has stopped due to excess temperature in the module. (see Section 6) LACK OF WATER LEVEL IN TANK Number of times the inverter has stopped by activating the probe level. (see Section 6) DISPLAY OF THE OPERATION LOG DISPLAY LOG Press Ok to confirm. To display the alarms, press (Alarm)
15 From any screen, tap OK to return to the main screen 2.1 NUMBER OF START-UPS Number of pump start-ups. OPERATING HOURS Number of hours of operation of the pump. LINE CONNECTION Number of hours of connection to the line, even when the pump is stopped. 6) PROTECTION AND ERRORS. OVERCURRENT ERROR SHORT-CIRCUIT ERROR TEMPERATURE ERROR LACK LEVEL ERROR VOLTAGE ERROR PRESS TRANSD. ERROR OVERCURRENTS The circuit permanently controls the motor s current consumption. If the current exceeds the values established in parameter "MAXIMUM MOTOR CURRENT" at any moment, the system will stop. The reset is automatic. If the error is not solved 4 new attempts* are performed. If the error is still present after the fourth attempt, the system will be set to a permanent fault. Press OK to reset. The start screen (#2) will appear. SHORT-CIRCUIT The state of connections will be diagnosed upon the motor's start-up. The system will stop when a short-circuit is detected in the motor. The reset is automatic. If the error is not solved 4 new attempts* are performed. If the error is still present after the fourth attempt, the system will be set to a permanent fault. MODULE TEMPERATURE The module's (T models) or circuit's (M models) temperature is monitored at all times. If the limit values established (not configurable) are exceeded in each circuit, the system will stop. The reset is automatic when the normal temperature is reinstated. LACK OF WATER LEVEL IN TANK If you have installed a float level in the inlet water tank (see apt. 3.5, n º 2), the water level is below the minimum. The reset is automatic when the water level recovered. VOLTAGE The input voltage of the system will be monitored constantly. The system will stop if the ±10% limits are exceeded. The reset is automatic when the nominal voltage is reinstated. PRESSURE TRANSDUCER The pressure transducer connected to the unit is not working properly The system will stop. (For booster sets, if other transducers are connected to Speedrive slaves, the booster will not stop and automatically switch to another transducer)
16 LACK OF WATER ERROR INTERNAL FAILURE ERROR EEPROM FILURE ERROR LACK OF WATER / PIPE BREAKAGE If the unit works more than 60 seconds at 50Hz, but the pressure does not exceed 0.3 bar, is declared "error for lack of water." the system will be set to a permanent fault. Press OK to reset. ELECTRONIC CIRCUIT FAILURE The electronic circuit is breakdown. The Speedrive stops working. It can only be repaired by official technical service. MEMORY MODULE FAILURE EEPROM memory module has had a serious malfunction and has stopped working. The Speedrive enters standby mode, with a reference pressure of 2 bar. It can only be repaired by official technical service. DISPLAY CONNECTION ERROR 3 LED sequential lighting indicates an error in connection the display signal cable to the motherboard. Reverse connector. Take care to position *= Illustration of the sequence and times of the 4 attempts, if not none of them succeed: ON OFF 1º 2º 3º 4º 7) MULTIPLE OPERATION. The Speedrive inverter can control more up to 4 pumps, equipped with various Espa solutions, for a multiple pump booster set control. a) Booster set with "On-Off" auxiliary pumps, equipped with "ELV" box. b) Booster set with inverter regulated auxiliary pumps, equipped with "Speedrive" box in slave mode. Communication is through communication port RS ) Booster set with "On-Off" Off" auxiliary pumps Sequence of Operation: - Faced with a demand for water, the pump A starts fast enough to meet the need for installation. - If the need is beyond the capacity of the pump A, pump B is activated at 100% capacity. The pump A reduce speed to meet demand (exchange rate set according to menu 10.1) - If the need exceeds the capacity of the pumps A + B, the pump C is activated. The pump A reduce speed to meet demand. - And successively... The operation mode is alternated. Each activation of the booster set, the order of start pumps is random. This will equal the operation hours. Installation and connections. The Speedrive installation and electrical wiring is done as described in this manual. For installation and connections of the modules "ELV", see its installation manual. The connection of the pressure transducer must be made solely on the drive Speedrive. A 2-wire twisted and shielded cable 0.5mm2 section must make the communication between devices
17 Figure 8 Adjust the micro-switches on the ELV as needed. See section 5 of the ELV manual. Respect the polarity of the RS-485connection: A B A B A B A B Configuration. Set Speedrive menus as follows: AUXILIARY PUMP Press (Adjust) for the adjustment of the parameters that govern to the auxiliary pumps. MAXIMUM CURRENT OF THE AUXILIARY PUMP. Set the maximum motor current of the auxiliary pumps, according to his motor's data plate plus 10%. All auxiliary pump motors should be of the same power. CHANGE FREQUENCY Set the maximum frequency of the main pump to be activated the auxiliary pumps. The number of auxiliary pumps does not have to be determined, since the circuit communications system detects the number (maximum 4). DELAY ON Set the desired delay time before the start of each auxiliary pump. Programming cascade spreads auxiliary pumps. Ignore. Press Ignore. Press 7.2) Booster set with inverter regulated auxiliary pumps. Synchronous sequence of Operation: - Faced with a demand for water, the pump A starts fast enough to meet the need for installation
18 - If the need is beyond the capacity of the pump A, pump B is activated. Both pumps sync speed to meet demand (exchange rate set according to menu 10.4) - If the need exceeds the capacity of the pumps A + B, the pump C is activated. Three pumps sync speed to meet demand. - And successively... The operation mode is alternated. For each activation of the booster set, the order of start pumps is random. This will equal the operation hours. Installation and connections. The Speedrive installation and electrical wiring is done as described in this manual. The connection of the pressure transducer must be made solely on the "Master" Speedrive. A 2-wire twisted and shielded cable 0.5mm2 section must make the communication between devices. Figure 9 Adjust the micro-switches (figure 6 o figure 7) as needed: MASTER/SLAVE SWITCH 1 SWITCH 2 SWITCH 3 SWITCH 4 MASTER OFF OFF OFF OFF SLAVE 1 OFF OFF OFF ON SLAVE 2 OFF OFF ON OFF SLAVE 3 OFF OFF ON ON Respect the polarity of the RS-485connection: A B A B A B A B Configuration. Set master Speedrive menus as follows: AUXILIARY PUMP Press (Adjust) for the adjustment of the parameters that govern to the auxiliary pumps. Ignore. Press
19 CHANGE FREQUENCY Set the maximum frequency of the main pump to be activated the auxiliary pumps. The number of auxiliary pumps does not have to be determined, since the circuit communications system detects the number (maximum of 4). DELAY ON Set the desired delay time before the start of each auxiliary pump. Programming cascade spreads auxiliary pumps. HYSTERESIS OFF Set the desired difference between the stop frequency of the main pump and each auxiliary pump. Programming cascade spreads auxiliary pumps. DELAY OFF. Set the desired delay time in the stop sequence of auxiliary pumps. Programming cascade spreads auxiliary pumps. Set slave Speedrive menu as follows: MOTOR FREQUENCY Configuration of the nominal frequency of the motor, 50Hz or 60Hz. Check the motor's nameplate. Note: This screen only appears in the initial preset or retrieving the factory settings. MAXIMUM MOTOR CURRENT Maximum operating current of the motor. Adjust in accordance with the motor's data plate, plus 10%. Note: This screen only appears in the initial preset or retrieving the factory settings Transducer failure. In a booster unit equipped with multiple transducers, if the main transducer fails, it automatically switches to a secondary transducer. In this case, displays the following error: MAIN TRANSDUCER ERROR It appears an asterisk in the pressure display = it is reading the pressure of an auxiliary transducer
20 8) MAIN COMPONENTS Motor adapter with connections box 85x85 2 Motor adapter with connections box 70x70 3 Speedrive box with electronic power circuit 4 Cable with plug (only M... versions) 5 Electronic control circuit 6 Speedrive cover 9) EVIDENCE OF CONFORMITY 9.1) LOW VOLTAGE. Speedrive is in compliance with directive 2006/95/CE (low voltage) and with harmonized standards EN and EN ) ELECTROMAGNETIC COMPATIBILITY. Speedrive M1 and M2 are in compliance with directive 2004/108/CE (electromagnetic compatibility), for industrial environment. For residential environment, it will require the installation of a lead currents filter to prevent interference in the mains. The Espa filter code is recommended. Speedrive T1, T2 and T3 are in compliance with directive 2004/108/CE (electromagnetic compatibility) for industrial environment. Harmonized standards: EN and EN ) OTHER INSTALLATIONS. Speedrive module has been designed, and is certified, for united installation to the pump electric motor. Any other configuration or installation can be subject to additional certifications. ESPA 2025 SL disclaims all liability for uses not covered in this manual. Pere Tubert Technical manager ESPA 2025, S.L
21 10) MENU DIAGRAM
22 - 22 -
23 - 23 -
24 ESPA 2025, S.L. C/ Mieres, s/n BANYOLES GIRONA SPAIN Cod.: /05
COUNTIS E22 Three-phase energy meter Direct - 80 A
Instruction manual COUNTIS E22 Three-phase energy meter Direct - 80 A EN www.socomec.com/ en/countis-e2x EN Contents 1. Documentation.... 3 2. Hazards and warnings... 4 2.1. Risk of electrocution, burns
More informationElectronic Ballast EVG 2000-T
Electronic Ballast EVG 2000-T Operating Manual Table of contents 1 Description 1.1 Advantages of this ballast... 3 1.2 Functional principle... 3 1.3 Energization... 4 1.4 Visualization... 5 1.5 Indications
More informationECONOMISER SERIES E2T USER MANUAL
TURBO S.R.L. Electronic Control Systems for Dust Collectors e-mail: info@turbocontrols.it web: www.turbocontrols.it TEL. ++39 (0)362 574024 FAX ++39 (0)362 574092 ECONOMISER SERIES E2T USER MANUAL 24/06/2014
More informationThree-Phase Soft Starters
Submittal Data English Language/IP Units 04/14 Contact Information: Hyper Engineering, Pty. Ltd. 4 / 14 Ralph Black Dr Wollongong Nth, NSW 2500 AUSTRALIA www.hypereng.com sales@hypereng.com (+61) 2 4229
More informationObserve all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.
Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary
More informationSingle & Three-Phase Soft Starters
Submittal Data English Language/IP Units 11/13 Contact Information: Hyper Engineering, Pty. Ltd. 9000 Conservation Way Fort Wayne, IN 46809 www.hypereng.com sales@hypereng.com (877) 304-0724 Model Nomenclature
More informationPCT-3001 plus. Display LCD
PCT3 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS DESCRIPTION Pressure controller for refrigeration systems capable to control suction (compressors) and discharge (fans) pressures. It is possible
More informationMAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -
MAKING MODERN LIVING POSSIBLE Quick Setup VLT FCM 300 Series Factory setting Motors type B14 & B34 mounting Reset (pushbutton) Start Jog Speed reference Fig. 1 - Reset to be closed short time for resetting
More informationAutomatic Genset Controller, AGC-4 Display readings Push-button functions Alarm handling Log list
OPERATOR'S MANUAL Automatic Genset Controller, AGC-4 Display readings Push-button functions handling Log list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com
More informationUser Manual Solar Charge Controller 3KW
User Manual Solar Charge Controller 3KW Version: 1.3 CONTENTS 1 ABOUT THIS MANUAL... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 SAFETY INSTRUCTIONS... 1 2 INTRODUCTION... 2 2.1 Features... 2 2.2 Product Overview...
More informationSYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN
SYMBOL LEGEND DANGER THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN WARNING THIS WARNS THAT MATERIALS MAY BE DAMAGED IF APPROPRIATE PRECAUTIONS ARE NOT
More informationDuplex Booster System Instruction Manual
Duplex Booster System Instruction Manual ISO 9001 Certified Walrus America Inc Congratulations on your purchase of Walrus IC Series Inverter Control System. Please read all instructions carefully before
More informationINSTALLATION INSTRUCTIONS
Page 1 of 2 Ref: IW012346 Rev 4 July 03 Indicators Saxon & Fiesta Series Products Covered 012-**, 013-**, 014-** & 016-** Installation The product should be panel mounted using the mounting kit provided.
More informationHGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology
HGM1780 Automatic Genset Controller USER MANUAL Smartgen Technology Smartgen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951
More informationUser Manual. Solar Charge Controller 3KW
User Manual Solar Charge Controller 3KW 1 CONTENTS 1 ABOUT THIS MANUAL... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 SAFETY INSTRUCTIONS... 3 2 INTRODUCTION... 4 2.1 Features... 4 2.2 Product Overview... 5
More informationAdvanced Hybrid Wind / Solar Charge Controller. User Manual
Advanced Hybrid Wind / Solar Charge Controller User Manual Safety 1. Please read the instructions carefully prior to product use or installation and refer back to them throughout the installation. 2. This
More informationUSERS MANUAL MCD REMOTE OPERATOR
USERS MANUAL MCD REMOTE OPERATOR Order Code: 175G9004, 175G3061 Contents Contents Introduction...2 Important User Information...2 General Description...2 Symbols Used in this Manual...2 Installation...3
More informationPressure Boosting Systems Multiple-Pump Units
Multiple-Pump Units Programm Overview, Multiple-Pump Units Multiple-pump units (non-self-priming) Programm Overview, Multiple-Pump Units Wilo-Comfort-N-Vario COR MVISE / VR Duty chart 16m 56 m /h Factory-assembled
More informationZB0050 / ZB0051 ZB0070 / ZB0071
Operating instructions Safety Rope Emergency Stop Switches UK ZB0050 / ZB0051 ZB0070 / ZB0071 7390877 / 02 08/2013 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4 2.2
More information55185 EMERGENCY PACK FOR LED PANEL TECHNICAL DATA SHEET
FEATURES SPECIFICATIONS Power Consumption 10W Output Voltage 18~59Vdc MAX Input Current 500 ma Emergency Time 90 Minutes Battery Specification 14.4V/2000mAH Dimension (Inches) 12.6 (L) x 1.8 (W) x 1.3
More informationBurden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM
Contents Section Page 1.0 Introduction 1 2.0 Specification 1-4 3.0 Installation 5-8 4.0 Programming 9-10 5.0 Menus 10-12 6.0 Fault Finding/Diagnostics 12-13 7.0 Communication 13 8.0 Setting Up 13-16 1.0
More informationFLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER
FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER INSTALLATION AND MAINTENANCE INSTRUCTIONS Risk of electric shock: Motor terminals may still be live if the impeller is rotating, even when
More informationMAKING MODERN LIVING POSSIBLE. UniLynx Indoor Installation Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS
MAKING MODERN LIVING POSSIBLE UniLynx Indoor Installation Manual ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS Contents Contents 1. Introduction 2 Introduction 2 Installation Sequence 2 Important
More informationUser manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS.
Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS. User manual Manual version: 2.4 dated 27/02/08 Program code: FLSTDmMCDE LEGGI
More informationPCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS
PCT plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS Ver. DESCRIPTION The PCT plus is a pressure controller for refrigeration plants that require control in their suction and discharge stages. With
More information8 Troubleshooting and Maintenance
8 Troubleshooting and Maintenance 8.1 Troubleshooting 8.1.1 Troubleshooting of LED Indicators See Tab. 7-4 State Descriptions of LED Indicators for the definition. Fault Type LED indicators and LCD screen
More informationDC POWER SUPPLY ALIMENTATION C.C.
DC POWER SUPPLY ALIMENTATION C.C. ISO-TECH IPS 303A 201-3424 ISO-TECH IPS 601A 201-3446 SAFETY TERMS AND SYMBOLS These terms may appear in this manual or on the product: WARNING. Warning statements identify
More informationHGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...
CONTENT 1. SUMMARY...4 2. PERFORMANCE AND CHARACTERISTICS...4 3. SPECIFICATION...5 4. OPERATION...6 4.1. DISPLAY PANEL...6 4.2. LCD ICON INSTRUCTION...7 4.3. DISPLAY INSTRUCTIONS...7 4.4. DISPLAY DESCRIPTION...8
More informationDUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL
72-7570 DUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL Table of Contents Specification 1 Safety 3 EMC 4 Installation 5 Connections 5 Operation 6 Maintenance 8 Specification General specifications
More informationMODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM
MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM DSE 520 ISSUE 4 4/4/02 MR 1 TABLE OF CONTENTS Section Page INTRODUCTION... 4 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION.... 4 1. OPERATION...
More informationSOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V
SOLAR LIGHTING CONTROLLER OPERATOR S MANUAL SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V 10A / 12V 10A / 24V 20A / 12V 20A / 24V 1098 Washington Crossing Road Washington Crossing,
More informationInstallation and Operating Instructions. Solar System Controller ISC3020
Installation and Operating Instructions Solar System Controller ISC3020 ABOUT THIS MANUAL These operating instructions come with the product and should be kept with it as a reference to all user s of
More informationINSTRUCTION AND USE MANUAL
CONTROL UNITS FOR ENGINE CONTROL AND PROTECTION TYPE CEP-090 INSTRUCTION AND USE MANUAL It is equipped with display to show the INSTRUMENTS: - hour-meter - fuel level indicator - tachometer - battery voltmeter
More informationInstallation and Operating Instructions. Solar System Controller ISC3030
Installation and Operating Instructions Solar System Controller ISC3030 ABOUT THIS MANUAL These operating instructions come with the product and should be kept with it as a reference to all user s of the
More informationFREQUENCY INVERTER INSTALLATION & USER GUIDE
En FREQUENCY INVERTER INSTALLATION & USER GUIDE Thank you for purchasing our frequency inverter. Please read the manual carefully before installing or using it and keep it for future reference after installation.
More informationUser Manual. SP10000 Premium
User Manual Solar Hybrid 3Phase PV Inverter SP10000 Premium Version: 1.2 Table Of Contents 1. Introduction... 1 2. Important Safety Warning... 2 3. Unpacking & Overview... 4 3-1. Packing List... 4 3-2.
More informationST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number
ST48-WHUV.12 PID controller Order number 935.15 Wiring diagram Product description This micro-processed controller serves for temperature control at high measuring accuracy. Beside resistance sensors and
More informationPWM Charge Controller with LCD Display 30A. User Manual
PWM Charge Controller with LCD Display 30A User Manual 1 Product Features 1. 12V/ 24 V system voltages are automatically recognized. 2. Charging program options for sealed, GEL and flooded lead-acid batteries
More informationMANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER. MicroMax. Article no. F IBC control Made in Sweden
MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MicroMax Article no. F21009201 IBC control Made in Sweden TABLE OF CONTENTS Installation instructions 2 Mounting 2 Safety instructions 3 Manufacturer's
More informationHGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic
HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic CONTENT 1. SUMMARY... 4 2. PERFORMANCE AND CHARACTERISTICS... 4 3. SPECIFICATIONS... 5 4. OPERATION... 6 5. PROTECTION...
More informationVigilec doble. Pump controlller and protection for two (3ph/1ph) pumps INSTALLATION AND OPERATION
V2P/V2T Vigilec doble INSTALLATION AND OPERATION V2P V2T Pump controlller and protection for two (3ph/1ph) pumps (V2P: control by pressure switches/ V2T: control by pressure transducer) General Description
More informationSYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN
SYMBOL LEGEND DANGER THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN WARNING THIS WARNS THAT MATERIALS MAY BE DAMAGED IF APPROPRIATE PRECAUTIONS ARE NOT
More informationDEEP SEA ELECTRONICS PLC
COMPLEX SOLUTIONS MADE SIMPLE. DEEP SEA ELECTRONICS PLC DSE710 AUTOSTART CONTROL MODULE OPERATING MANUAL Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44
More informationUSE AND INSTALLATION HANDBOOK
Date : 10/02/14 Rev. 01 PR.T : FG006172 USE AND INSTALLATION HANDBOOK DUPLEX-UP CONTROL PANEL FOR 2 ELECTRIC PUMPS WITH CURRENT CONTROL. DUPLEX-UP Via Enrico Fermi 8-35020 Polverara PD Tel.049/9772407
More informationSC-Max 48V series. User Manual. Solar Charge Controller 30A
SC-Max 48V series Solar Charge Controller 30A User Manual Contents 1 Description of function 2 Safety Instructions and Waiver of Liability 2.1 Safety 2.2 Liability Exclusion 3 Dimensions 4 Optional 4.1
More informationc-go 24V/6A 24V/8A 24V/12A
c-go 24V/6A 24V/8A 24V/12A Battery charger GB Instruction manual 1 Index 1. Product description... 2 2. Safety advices... 3 3. Quick start guide... 4 4. Operation... 4 5. Problem solving... 6 6. Specifications...
More informationThe Traveler Series: Adventurer
The Traveler Series: Adventurer RENOGY 30A Flush Mount Charge Controller Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 Version: 2.2 Important Safety Instructions Please save these instructions.
More informationGRUNDFOS INSTRUCTIONS. Hydro MPC. Installation and operating instructions
GRUNDFOS INSTRUCTIONS Hydro MPC Installation and operating instructions Declaration of Conformity We, Grundfos, declare under our sole responsibility that the products Hydro MPC, to which this declaration
More informationFlight Systems. Replacement for KASSEC DESCRIPTION
DESCRIPTION The is a universal generator controller that will start, stop, and provide engine protection for most generators. Universal replacement for both the 90353 and 90354 KASSEC Compatible with most
More informationExtended Battery Cabinet for Nfinity
POWER PROTECTION Extended Battery Cabinet for Nfinity USER MANUAL TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS................................... 1 ELECTROMAGNETIC COMPATIBILITY.......................................
More informationPowerOhm Installation Manual for BM R Series Braking Modules
PowerOhm Installation Manual for BM R Series Braking Modules IMPORTANT: These instructions should be read thoroughly before installation. All warnings and precautions should be observed for both personal
More informationISO-TECH IPS1810H and IPS1603D DC power supply ISO-TECH IPS 1810H et IPS 1603D Alimentation électrique c.c.
ISO-TECH IPS1810H and IPS1603D DC power supply ISO-TECH IPS 1810H et IPS 1603D Alimentation électrique c.c. ISO-TECH IPS 1810H 204-713 ISO-TECH IPS 1603D 204-729 82IP-1810HME Ei Statement of Compliance
More informationKD LV Motor Protection Relay
1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage
More informationCompact Heat Meters. Features. -A Pulsed output. -B M-Bus output. Accessories. UK Sales Tel: International Tel:
Compact Heat Meters Features Compact design Simple operation Pulsed output Measures heating or cooling Specification Product Codes Water Meter Temp. range 10 to 90 C Nominal pressure 16bar Installation
More informationDiesel generator set QSK78 series engine
Specification sheet Diesel generator set QSK78 series engine 1950 kw - 2500 kw Description Cummins commercial generator sets are fully integrated power generation systems providing optimum performance,
More informationHGM1750 Genset Security Module USER MANUAL Smartgen Technology
HGM1750 Genset Security Module USER MANUAL Smartgen Technology CONTENT 1. SUMMARY... 4 2. PERFORMANCE AND CHARACTERISTICS... 5 3. SPECIFICATION... 7 4. OPERATION... 8 5. PROTECTION... 9 6. PARAMETER RANGE
More informationDEEP SEA ELECTRONICS PLC
COMPLEX SOLUTIONS MADE SIMPLE DEEP SEA ELECTRONICS PLC DSE720 AUTOSTART CONTROL MODULE OPERATING MANUAL http://bestgenerator.spb.ru/?page_id=6765 Deep Sea Electronics Plc Highfield House Hunmanby North
More informationENGINE PROTECTION BOARD PDM1
ENGINE PROTECTION BOARD REFERENCE MANUAL. Standard of reference: IEC/EN 60255-6 IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4, IEC/EN 61000-4-5 IEC/EN 61000-4-6 IEC/EN 55011 IEC/EN 60028-2-61 IEC/EN
More informationDEVICE STATE/BYPASSED FAILURE OVERLOAD
Technical specifications Type 5. 7. Control electronics Rated values Terminal Rated control supply voltage A1A2 V AC 115 230 115 230 Tolerance % -15+10-15+10 Rated control supply STANDBY ma 15 15 Rated
More informationVASCO. Variable Speed Controller ENGLISH
VASCO Variable Speed Controller ENGLISH Variable Speed Controller VASCO is a purpose-built family of variable frequency drives, designed to control and protect pumping systems based on changing pump speed.
More informationInstrucciones de instalación y funcionamiento Installation and operating instructions
Wilo-ElectronicControl D Einbau- und Betriebsanleitung E Instrucciones de instalación y funcionamiento GB Installation and operating instructions I Istruzioni di montaggio, uso e manutenzione F Notice
More informationINTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY
INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,
More informationSC SERIES SOLAR CONTROLLER USER MANUAL Ver 1.0
SC SERIES SOLAR CONTROLLER USER MANUAL Ver 1.0 (for SC-2420, 2430, 2440, 2450, 2460,4840 and 4860) 1 2 Solar Controller SC series solar controller USER MANUAL Congratulations on choosing a ROC-SOLID SC
More informationAUTOMATIC STANDBY ACTIVATION. Operation Manual
AUTOMATIC STANDBY ACTIVATION Operation Manual ATTENTION! Prior to use this unit ple carefully read the Operation Manual 1. INTRODUCTION 1.1 The present Operation Manual applies to study automatic standby
More informationTe 803 Electronic Controller. Service, Operation & Technical Information Manual
Te 803 Electronic Controller Service, Operation & Technical Information Manual WARNING! Technical descriptions and data given in this document are accurate, to the best of our knowledge, but can be subject
More informationENG GENERAL DESCRIPTION
GENERAL DESCRIPTION ORLANDO SOLAR MULTI ISLAND SOLAR DRIVE is a system for pumping water powered by photovoltaic panel. The application relates to systems of lifting water from a well, irrigation systems,
More informationUser Guide. Lubricus Lubrication System LUB-D1/LUB-D2/LUB-D3/LUB-D4 (24 VDC)
User Guide Lubricus Lubrication System LUB-D1/LUB-D2/LUB-D3/LUB-D4 (24 VDC) version 04/2013 Content General Information 3 Warning 3 Scope of Supply 3 Overview 3 General safety details 4 Intended use 4
More informationINSTALLATION USER MANUAL
INSTALLATION & USER MANUAL DYNAMIC LOAD MANAGEMENT -PREMIUM- This document is copyrighted, 2016 by Circontrol, S.A. All rights are reserved. Circontrol, S.A. reserves the right to make improvements to
More informationCRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE 1 & 3 phase
GRUNDFOS INSTRUCTIONS CRE, CRIE, CRNE CRKE, SPKE, MTRE, CIE 1 & 3 phase Installation and operating instructions LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted
More informationUser Manual. Hybrid PV Inverter. Version: 2.1
User Manual Hybrid PV Inverter Version: 2.1 Table Of Contents 1. Introduction...1 2. Important Safety Warning...2 3. Unpacking & Overview...4 3-1. Packing List... 4 3-2. Product Overview... 4 4. Installation...5
More informationUser Manual / Manuel utilisateur
User Manual / Manuel utilisateur Inverter Charger / Convertisseur Chargeur English version...1 English Version 1 Table of Contents ABOUT THIS MANUAL... 3 Purpose... 3 Scope... 3 SAFETY INSTRUCTIONS...
More informationElectronic Limit Switch Type
Electronic Limit Switch Type 3738-20 with optional solenoid valve for on/off rotary actuators Application Electronic limit switch for on/off applications to indicate the end position of rotary actuators.
More informationDELPHYS. Operating manual GB
DELPHYS DS Operating manual GB UPS/NTA GB/DSEXPC1.F Certificate of Warranty The warranty conditions are stipulated in the sales contract, if not the following points shall apply. The manufacturer exclusively
More informationMod: KLD6-12/35XLAS-N
12/2011 Mod: KLD6-12/35XLAS-N Production code: 1914070 INSTRUCTION MANUAL LOGIC LINE PLUS HOOD Reseller Stamp for Warranty Dear customer, Above all, thank you for choosing our product and we would like
More informationBSPDDRIVE ITT. Goulds Pumps. Aquavar SPD (Single Pump Drive) Simplex Variable Speed Pump Controller
ITT BSPDDRIVE Goulds Pumps Aquavar SPD (Single Pump Drive) C U L US Do you want to Simplify your Commercial Pumping System? Goulds Pumps SPD variable speed, constant pressure pump controller is designed
More informationINSTALLATION AND OPERATING INSTRUCTIONS MANUAL Owner s manual FIXED SPEED BOOSTER SETS SERIES:
INSTALLATION AND OPERATING INSTRUCTIONS MANUAL Owner s manual FIXED SPEED BOOSTER SETS SERIES: CPD: Two pumps CPT: Three pumps CPC: Four pumps Page 1 of 15 INSTRUCTIONS FOR INSTALLATION AND USE 2009 CAREFULLY
More informationM u l t i P o w e r. CM MultiPower. Installation and Operating Manual
M u l t i P o w e r CM MultiPower Installation and Operating Manual Index 1. Introduction of the 4HS submersible pumps range... 3 2. Safety Instructions... 4 3. CM MP installation... 5 3.1 Electric wiring...
More informationTIMER INTERFACE USER MANUAL
TIMER INTERFACE USER MANUAL Premium Efficiency Two-Speed Motor with Integrated Timer Formerly A. O. Smith Electrical Products Company A Regal Beloit Company COPYRIGHT Copyright 2011, Regal Beloit EPC,
More informationCURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING
AUGUST, 2004 REV.A CURTIS TOLEDO OPERATOR S MANUAL SUPPLEMENT AF Series Compressors VS models with VFD WARNING Personal injury and/or equipment damage will result by failing to pay attention to the vital
More informationProduct Overview. Product Identification. Amps One CT Two CTs Three CTs
AH06 (optional mounting bracket for small, medium, and large CTs) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationWATERFLUX 3070 Quick Start
WATERFLUX 3070 Quick Start Battery powered electromagnetic water meter Electronic Revision ER 4.3.0_ up to ER 4.3.4_ (SW.REV 4.2.2_ up to 4.2.5_) KROHNE CONTENTS WATERFLUX 3070 1 Safety instructions 4
More informationBrake Chopper BC BC 4.1. Instruction and Operation Manual
Brake Chopper BC 2.1 - BC 4.1 Instruction and Operation Manual Caution: There is always a risk involved in the handling of electrical machinery! Therefore mounting and maintenance should only be done by
More informationHGM501 Gen-set Controller USER MANUAL. Smartgen Technology
HGM501 Gen-set Controller USER MANUAL Smartgen Technology Contents 1. 2. 3. 4. 5. 6. 7. 8. 9. OVERVIEW... 4 PERFORMANCE AND CHARACTERISTICS... 4 TECHNICAL DATA... 5 OPERATION... 6 4.1. BUTTON DESCRIPTION...
More informationPowerOhm Installation Manual for LG ATV Series Braking Modules
PowerOhm Installation Manual for LG ATV Series Braking Modules IMPORTANT: These instructions should be read thoroughly before installation. All warnings and precautions should be observed for both personal
More informationTECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT
TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT 1.0 PURPOSE: 1. To charge the battery bank through Solar PV source and AC supply. 2. To invert and produce utility quality sine wave. 3. Inverters
More informationMB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR
MB-3688 120A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR User Manual Warning and Precautions MB-3688 is built with corrosion resistant material and the main electronic assembly is well sealed inside
More informationCompany name: GSI Created by: Xiao Ying Wong Phone: Date: 10/03/2017 Client: Client Number: Contact:
Position Qty. Description 2 NBG 125-8-16/156 A-F2-A-BAQE Product No.: On request Non-self-priming, single-stage, centrifugal volute pump designed according to ISO 5199 with dimensions and rated performance
More informationTECHNICAL MANUAL. Inverter / Charger Combi. Combi SW 12V 1600VA Réf : PF Combi SW 24V 3800VA Réf : PF NOT_COMBI_SW-00
TECHNICAL MANUAL EN Inverter / Charger Combi Combi SW 12V 1600VA Réf : PF.16088 Combi SW 24V 3800VA Réf : PF.16089 SAFETY PRECAUTIONS TO PREVENT ANY RISK OF ELECTRIC SHOCK OR FIRE, READ THIS MANUAL CAREFULLY
More informationRECOMMENDATIONS FOR USING FREQUENCY INVERTERS WITH POSITIVE DISPLACEMENT REFRIGERANT COMPRESSORS
RECOMMENDATIONS FOR USING FREQUENCY INVERTERS WITH POSITIVE DISPLACEMENT REFRIGERANT COMPRESSORS Contents Page 1 Scope and purpose... 1 2 General... 1 3 Operation... 2 4 Application ranges... 5 5 Design
More informationPV Charge Controller SBC-7108 / 7112 / 7120
PV Charge Controller SBC-7108 / 7112 / 7120 User's Manual NOTE: Please note that features like LCD read out of AH logging of 3 days (see Section 3.3) and 10 Night-light mode (see Section 4.3) are available
More informationThyristor power controller TE10A. Burst-firing Single-cycle Advanced Single-cycle
Thyristor power controller TE10A Burst-firing Single-cycle Advanced Single-cycle Control of short-wave infrared elements and loads of constant resistance up to 20kW User Manual Copyright Eurotherm Automation
More informationDC Master 24/ A
USERS MANUAL DC Master 24/12 50-60A DC-DC converter MASTERVOLT Snijdersbergweg 93, 1105 AN Amsterdam The Netherlands Tel.: +31-20-3422100 Fax.: +31-20-6971006 www.mastervolt.com ENGLISH Copyright 2015
More informationPhoenix Inverter
Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Appendix Phoenix Inverter 12 250 12 375 12 500 12 800 24 250 24 375 24 500 24 800 48 250 48 375 48 500 48 800 1. Safety instructions WARNING: ELECTRIC
More information& Operation Manual. Growatt 10000HY. Installation GR-UM-A03-A-00
Growatt 10000HY Installation & Operation Manual GROWATT NEW ENERGY TECHNOLOGY Co.,LTD No.28 Guangming Road, Shiyan, Baoan District, Shenzhen, P.R. China T F E W + 86 755 2747 1900 + 86 755 2747 2131 info@ginverter.com
More informationTOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS
INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...
More informationSIZING OF SOLAR GENERATOR
MULTI ISLAND is a water pumping system with power from photovoltaic panels. It is designed for use in water wells, irrigation systems, or the power supply network is not available, or when the user wishes
More informationUser Manual Rittal PMC UPS 6kVA
User Manual Rittal PMC UPS 6kVA Germany Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Tel.: ++49-27 72-5 05-0 Fax: ++49-27 72-5 05-23 19 Internet: www.rittal.de 26 Contents 1. Introduction...
More informationDiesel generator set QSK78 series engine 2750kVA kVA 50 Hz
Specification sheet Diesel generator set QSK78 series engine 2750kVA - 3000kVA 50 Hz Description This Cummins commercial generator set is a fully integrated power generation system, providing optimum performance,
More informationInstallation and Operating Instructions. MPPT Solar System Controller ISC3040
Installation and Operating Instructions MPPT Solar System Controller ISC3040 ABOUT THIS MANUAL These operating instructions come with the product and should be kept with it as a reference to all user s
More informationSwitching DC Power Supply
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Model 1693, 1694 Switching DC Power Supply INSTRUCTION MANUAL 1 Safety Summary
More information