VCB VACUUM CIRCUIT BREAKER

Size: px
Start display at page:

Download "VCB VACUUM CIRCUIT BREAKER"

Transcription

1 VCB VACUUM CIRCUIT BREAKER 7,5 kv, 3,5 ka, 350 A 4 kv, 6 ka, 800 A PRODUCT GUIDE

2 Contents. Introduction Abbreviations Definitions Disclaimers Precautions Warranty Presentation Product application field Key benefits Compliance Product coding Circuit breaker coding Circuit breaker component coding ISM coding CM coding Circuit breaker kits coding Optional circuit breaker kit coding Optional release cable coding Optional position indicator coding Optional Manual Generator coding Technical parameters Design and operation Design Indoor Switching Module Control Module Insulation kits Interlocking kits Switching module main contacts position indicator Operation Closing Opening Emergency opening Functionality Indication Application notes Configuration options Primary connections ISM installation Minimum clearances due to electromagnetic influence Minimum clearances due to rated insulation voltage Secondary equipment Three-phase ISM secondary connections Single-phase ISM secondary connections CM secondary connections CM and ISM secondary connections Auxiliary supply Appendix. Type tests Appendix. Product range... 7 Appendix 3. Overall drawings Appendix 4. Secondary schemes... 9

3 . Introduction

4

5 This Product Guide describes the Vacuum Circuit Breakers manufactured by Tavrida Electric. Tavrida Electric circuit breakers are designed for rated voltages up to 4 kv. Vacuum Circuit Breakers described in the current document can be used in various kinds of switchgear and RMUs and are intended to perform switching operations in network rated and faulty modes. The breakers are comprised of following main components: Indoor Switching Module (ISM) - The air insulated ISM incorporates Tavrida Electric vacuum interrupters with monstable magnetic actuators and solid dielectric insulating materials. No SF-6 or oil insulation is used in the ISM; Control Module (CM) - The CM is a microprocessor based controller that provides ISM operation, protection and data logging functions; Kits - The kits of components are used to provide circuit breaker application properties. This guide contains information about the circuit breaker technical parameters, functionality and operating principles. The purpose of the document is to provide necessary product information for application engineers and technical personnel utilizing the equipment. List of other technical documents covering the product: Document name Target audience Purpose of the document User guide Routine test certificate Users providing installation, commissioning and utilizing installed equipment Customer procurement service Provide information on switching operations, required check-ups and maintenance, as well as service and disposal procedures Provide information on supplied equipment serial numbers. Abbreviations AC AS BIL EMC CM CO Com I/O ISM LED (P)MCB PS NA NC NO PCD USB VCB VI HD ISM LD ISM Actuator coil Auxiliary switch Basic Insulation Level Electromagnetic capability Control Module Close - Open operations cycle Common point of contact Input / Output Indoor Switching Module Light emitting diode Protective miniature circuit breaker Position switch Not applicable Normally closed contact Normally open contact Pole center distance Universal Serial Bus Vacuum Circuit Breaker Vacuum interrupter Heavy duty ISM Light duty ISM 5

6 . Definitions Closing time The closing time is the time period from the moment the close command is applied to the CM to the time when all ISM poles make contact. Opening time The opening time is the time period from the moment the trip command is applied to the CM to the time when all ISM poles are separated. Break time The break time is the time period from the moment the trip command is applied to the CM to the time when the arcs in all phases are extinguished..3 Disclaimers Tavrida Electric will not accept any claims for damages caused by improper transport, storage as well as unpacking. Transport damage must be reported in writing to the supplier as soon as it is discovered. The User Guide contains information necessary for the installation, commissioning and operation. It is absolutely necessary for the proper use of the Vacuum Circuit Breakers to read the User Guide carefully before starting and to adhere to the instructions and the relevant regulations. Tavrida Electric will not accept any claims for damages caused by improper usage of the Vacuum Circuit Breakers. In case of special configurations please contact Tavrida Electric prior of usage of the Vacuum Circuit Breakers..4 Precautions Check whether the installation position (distances, spatial separation, and the surroundings) is suitable for the switching devices. Installation, operation and maintenance shall only be carried out by trained and experienced personnel who are familiar with the equipment and the electrical safety requirements. During installation, commissioning, operation and maintenance of the equipment the relevant legal regulations (such as DIN/VDE/IEC), accident prevention regulations and the connecting conditions of the electric utilities shall be followed. Take note that during operation of the Vacuum Circuit Breakers certain parts are subject to dangerous voltage. Mechanical parts, also remote-controlled, can move quickly. Failure to comply may result in death, severe personal injury or damage to equipment. Pay attention to the hazard statements located throughout the User Guide. The operating conditions of the Vacuum Circuit Breakers shall comply with the technical data specified in the Product Guide. Personnel installing, operating and maintaining the equipment shall be familiar with the User Guide and its contents..5 Warranty Unless otherwise stated in the contract, the warranty period is stated in Standard warranty policy. If agreed to otherwise, the contract conditions apply. No warranty is given in the case of a) the warranty period having run out during the period of storage with the customer; b) the operating conditions, ambient conditions, transport and storage conditions have not been adhered to according to the application description or the Installation and Operating Instructions; c) an unauthorized manipulation of the device has been carried out, such as opening the housing or damaging the seal; d) the device has not been properly installed, such as incorrect connection of supply voltage of auxiliary circuits. 6

7 . Presentation

8 . Product application field The circuit breaker is usually installed in radial or loop cable distribution systems. The main applications are: Switching different types of load in normal and fault modes; Isolating faults in the cable network. Due to their short closing and opening times (see Table 5), Tavrida Electric circuit breakers can bring significant benefits to the following applications: Arc flash protection; Automatic backfeed restoration.. Key benefits Tavrida Electric circuit breakers provide the following competitive advantages: Environmentally friendly The ISM does not use SF-6 insulation materials. The CM and ISM modules are manufactured from environmentally friendly materials. Light weight and compact dimensions Compact design and light weight of switching modules make the VCB an advantageous solution for many applications of compact switchgear. Highest Reliability 50,000 CO operations at rated current and 00 full rated short-circuit operations without any maintenance make it the most reliable circuit breaker on the market..3 Compliance Tavrida Electric Vacuum Circuit Breakers have been tested by world-renowned testing laboratories. A list of test reports is presented in Appendix. Type tests. 8

9 3. Product coding

10 3. Circuit breaker coding VCB5_LD_6F(Par_Par_Par3_Par4_Par5_Par6_Par7_Par8) Product group ISM type CM and VCB implementation type Table - Product group description Code Description VCB5 Vacuum Circuit Breaker with rated voltage up to 7.5 kv VCB5 Vacuum Circuit Breaker with rated voltage up to 4 kv Table - ISM type description Code Description LD Three-phase Light duty Indoor Switching Module LD Three-phase Light duty Indoor Switching Module for SF6 switchgears LD3 Single-phase Light duty Indoor Switching Module LD6 Three-phase Light duty Indoor Switching Module for British retrofit (LMT/AG6 retrofit) MD Three-phase Heavy duty Indoor switching module with rated normal current up to 50 A Shell Three-phase Heavy duty Indoor switching module with rated normal current up to 000 A HD Three-phase Heavy duty Indoor switching module with rated normal current up to 350 A Table 3 - CM and VCB implementation type description Code Description 6F The 6th series of Control Module and Fixed type VCB 6RD The 6th series of Control Module and Retrofit Draw-out type VCB 0

11 VCB5_LD_6F(Par_Par_Par3_Par4_Par5_Par6_Par7_Par8) Product group ISM type CM and VCB implementation type Table 4 - Circuit breaker parameters description Parameter Parameter description Applicable options Code Par VCB application type Standard circuit breaker CB kv Par Par3 Par4 Rated voltage Rated short cicuit current Rated normal current 7.5 kv kv 4.5 ka.5 6 ka 6 0 ka ka A A A A A A 350 Not applicable (for single-phase ISM) NA Par5 Par6 Par7 Pole centre distance ISM lower terminal design Rated auxiliary supply voltage 33 mm mm mm 80 0 mm 0 75 mm 75 One main lower terminal Two main lower terminals 4-60 V DC V AC/DC 0 Default 0 Par8 Customization Contact your nearest sales representatives to choose the option suitable for you DY800 LMT AG6 Allowed VCB combinations and their delivery sets are presented in Appendix. Product range

12 3. Circuit breaker component coding 3.. ISM coding ISM5_LD_(Par) Indoor switching module Rated voltage ISM type The following ISM types are available: ISM5_LD_(Par) ISM5_LD_3 ISM5_LD_6 ISM5_MD_(Par_Par) ISM5_Shell_(Par_Par) ISM5_HD_(Par) ISM5_LD_(Par_Par) ISM5_LD_(Par) ISM5_LD_3 ISM5 - Indoor Switching Module with rated voltage up to 7.5 kv ISM5 - Indoor Switching Module with rated voltage up to 4 kv See Table for description of ISM types. Parameter Par Par Applicable ISM ISM5_LD_ ISM5_MD_ ISM5_Shell_ ISM5_HD_ ISM5_LD_ ISM5_LD_ ISM5_MD_ ISM5_Shell_ Table 5 - Circuit breaker parameters description Parameter description Applicable options Code Design type (Pole centre distance and main lower terminal design) Pole centre distance Pole centre distance Design type (One or two main lower terminals) Side of position indicator connection to ISM Upper terminal type (High upper terminal allows for higher normal rated current) Pole centre distance 0 mm, one main lower terminal Pole centre distance 50 mm, one main lower terminal Pole centre distance 50 mm, two main lower terminals Pole centre distance 80 mm, one main lower terminal 50 mm 0 mm 50 mm 0 mm 75 mm 0 mm 75 mm 0 mm 75 mm One main lower terminal Two main lower terminal Left side (between phases A and B) Low upper terminal for rated normal current up to 50 A High upper terminal for rated normal current up to 000 A L L H ISM5_LD_ ISM auxiliary contacts type (ISM auxiliary contacts material) ) Silver contacts Gold plated contacts S G_ Please specify the rated voltage required with your order. ) Silver contacts are applicable for usage in conventional low voltage circuits. Gold plated contacts should be used for digital signal circuits with low levels of voltage and current.

13 Each ISM has the following plate and label: Label Serial number plate Figure ISM label Figure Serial number plate placement The serial number plate contains information about ISM type and serial number. The label contains brief information about ISM technical parameters. Label and serial number plate arrangement is shown below a) ISM5_LD and ISM5_LD labeling b) ISM5_Shell labeling c) ISM5_MD labeling d) ISM5_HD labeling. Label. Serial number plate Figure 3 Serial number plate and label arrangement 3

14 3.. CM coding CM_6_(Par_Par_Par3) Control module Control module series CM type Table 6 - CM parameters description Parameter Parameter description Applicable options Code Par Rated supply voltage 4-60 V DC V AC/DC 0 ISM5_LD_, ISM5_LD_6 and Standard circuit breaker 5.LD.6 ISM5_LD_3 and Standard circuit breaker 5.LD3 Par Application type ISM driver firmware used in CM ) ISM5_MD_ and Standard circuit breaker ISM5_Shell_ and Standard circuit breaker 5.MD 5.Shell and Application type ISM5_HD_ and Standard circuit breaker 5.HD ISM5_LD_, ISM5_LD_ and Standard circuit breaker 5.LD. ISM5_LD_3 and Standard circuit breaker 5.LD3 ) This parameter describes the ISM type(s) that the CM can control. To optimize the operation of each ISM, corresponding settings are used in the CM firmware. Usage of CM with incorrect type of ISM can lead to a mismatch of declared parameters of VCB. Each CM has the following labels : Designation label Serial number label Figure 4 Serial number label Figure 5 Designation label. Serial number label. Designation label Figure 6 Serial number and designation label arrangement 4

15 3..3 Circuit breaker kits coding CBkit_Shell5_(Par) Circuit breaker kit Kit for ISM5_Shell Kit type CBkit_Shell5_ is applicable for the ISM5_Shell_ only. This kit provides for flat bus bar connection to the ISM while maintaining the declared BIL level. Table 7 - CBkit parameters description Parameter Parameter description Applicable options Code Par Terminal distance ) 05 mm mm 30 ) Parameter describes the distance between bus bar connection points on the upper and lower terminals of the ISM5_Shell_ per Figure 7 and Figure 8. The mounting kit for 05 mm terminal distance is used for the ISM5_Shell_ with lower upper terminal and normal rated currents up to 50 A, 30 mm is used for the ISM5_Shell_ with higher upper terminal and normal rated currents up to 000 A. Figure 7 CBkit_Shell5_(05) Figure 8 CBkit_Shell5_(30) Insulation caps provide ISM terminal insulation. Two sets of bolts are provided for different bus bar configurations (single or double stacked). 5

16 CBkit_Ins_3 Circuit breaker kit Insulation kit Kit type CBkit_Ins_3 is used with the ISM5_LD_ and ISM5_LD_3 switching modules only and provides compliance with declared BIL level. Figure 9 CBkit_Ins_3 6

17 CBkit_LD5_ Circuit breaker kit Kit for ISM5_LD Kit type CBkit_LD5_ is used with the ISM5_LD_6 only. CBkit_LD5_ is a kit of plastic parts providing insulation of main circuits and indication of main contacts state for LMT Retrofit Draw-out type VCB. Please contact your nearest Tavrida Electric sales representative for more information. Figure 0 CBkit_LD5_ 7

18 CBkit_LD5_3 Circuit breaker kit Kit for ISM5_LD Kit type CBkit_LD5_3 is used with the ISM5_LD_6 only. CBkit_LD5_3 is a kit of plastic parts providing insulation of main circuits and indication of main contacts state for AG6 Retrofit Draw-out type VCB. Please contact your nearest Tavrida Electric sales representative for more information. Figure CBkit_LD5_3 8

19 3..4 Optional circuit breaker kit coding CBkit_ Interlock_ Circuit breaker kit Interlock kit Kit type CBkit_Interlock_ is used with the ISM5_LD_, ISM5_LD_ and ISM5_LD_ only. The kit attaches to the ISM synchronizing shaft and serves as an interface for various manual trip / indication / lockout accessories. Figure CBkit_ Interlock_ 9

20 CBkit_ Interlock_(Par) Circuit breaker kit Interlock kit Kit type CBkit_Interlock_ is used with the ISM5_Shell_ only. The kit attaches to the ISM Interlocking shaft and serves as a manual trip / lockout accessory. Table 8 - Circuit breaker kit parameters description Parameter Parameter description Applicable options Code Par Cable length 000 mm 000 Figure 3 CBkit_ Interlock_ 0

21 CBkit_Interlock_3(Par) Circuit breaker kit Interlock kit Kit type CBkit_Interlock_3 is used with the ISM5_MD_ and ISM5_HD_ only. The kit attaches to the ISM Interlocking shaft and serves as a manual trip / lockout accessory by key switch. Table 9 - Circuit breaker parameters description Parameter Parameter description Applicable options Code Par Cable length 000 mm 000 Figure 4 CBkit_Interlock_3

22 CBkit_Interlock_4(Par_Par) Circuit breaker kit Interlock kit Kit type CBkit_Interlock_4 is used with the ISM5_MD_ and ISM5_HD_ only. The kit attaches to the ISM Interlocking shaft and serves as a manual trip / lockout accessory by rotary switch. Table 0 - Circuit breaker parameters description Parameter Parameter description Applicable options Code Par Cable length 000 mm 000 Par Labels language English language EN Figure 5 CBkit_Interlock_4

23 CBkit_Interlock_5(Par) Circuit breaker kit Interlock kit Kit type CBkit_Interlock_5 is used with the ISM5_MD_ and ISM5_HD_ only. The kit attaches to the ISM Interlocking shaft and serves as a manual trip button. Table - Circuit breaker parameters description Parameter Parameter description Applicable options Code Par Cable length 000 mm 000 Figure 6 CBkit_Interlock_5 3

24 CBkit_Ins_4(Par) Circuit breaker kit Interlock kit Kit type CBkit_Ins_4 is used with the ISM5_MD_ only and provides compliance with declared BIL level. Table - Circuit breaker parameters description Parameter Parameter description Applicable options Code Par Bus bars type 0x40 mm Single or Double bars 0x80 mm Single bars a) 0x40 mm b) 0x80 mm Figure 7 CBkit_Ins_4 4

25 CBmount_ISM5_ Circuit breaker mounting kit Kit for ISM5 Kit type CBmount_ISM5_ is used with the ISM5_HD_ only. The kit attaches to the ISM required mounting points to provide 95 kv BIL. Figure 8 CBmount_ISM5_ 5

26 3..5 Optional release cable coding CBcomp_ RelCable_(Par) Circuit breaker component Release cable Cable type CBcomp_RelCable_ is a flexible release cable used for interlock or ISM position indicator connection to the ISM. Table 3 - Release cable parameters description Parameter Parameter description Applicable options Code Par Cable length 000 mm 000 Par Parameter describes length of release cable. Figure 9 CBcomp_RelCable_ 6

27 3..6 Optional position indicator coding CBkit_PosInd_ Circuit breaker kit Position indicator Indicator type CBkit_PosInd_ is a position indicator used together with CBcomp_RelCable_ to indicate the ISM main circuit position. VCB5_MD_6F, VCB5_Shell_6F, VCB5_HD_6F and ISM5_Shell_ already include CBcomp_ RelCable_(000) and CBkit_PosInd_. Figure 0 CBkit_PosInd_ 7

28 3..7 Optional Manual Generator coding CBunit_ManGen_ Circuit breaker unit Manual generator Generator type CBunit_ManGen is used to charge the CM_6_ in cases where the main auxiliary power supply is not available. Table 4 - Generator type description Code Description Manual generator for use with CM_6_(0_Par) Manual generator for use with CM_6_(60_Par) Figure CBunit_ ManGen_ (CBunit_ ManGen_) Figure Designation label Figure 3 Serial number label 8

29 4. Technical parameters

30

31 Main technical data and circuit breaker technical parameters are presented in the tables below. Type VCB5_LD VCB5_MD VCB5_Shell VCB5_HD VCB5_LD Rated voltage (Ur) kv 7.5 kv 7.5 kv 7.5 kv 4 kv Rated normal current (Ir) 800 A 50 A Table 5 - VCB technical parameters 50 A ) 000 A 000 A 350 A ) 800 A Rated power frequency withstand voltage (Ud) 8 (4) 3) kv 38 (4) kv 3) 38 (4) kv 3) 38 (4) kv 3) 50 kv Rated lightning impulse withstand voltage (peak) (Up) 75 kv 95 kv 4) 95 kv 5) 95 kv 5 kv Rated short-circuit breaking current (Isc) 0 ka 6) 3.5 ka 6) 3.5 ka 6) 3.5 ka 6) 6 ka 6) Rated peak withstand current (Ip) 50 ka 8 ka 8 ka 8 ka 40 ka Rated short-time withstand current (Ik) 0 ka 3.5 ka 3.5 ka 3.5 ka 6 ka Rated duration of short circuit (tk) Rated frequency (fr) 4 s 50/60 Hz Mechanical life (CO-cycles) ) ) Maximum number of CO-cycles per hour 60 Operating cycles, rated short circuit breaking current Closing time 70 9) ms 60 9) ms 60 9) ms 60 9) ms 70 9) ms Opening time 35 9) ms 35 9) ms 35 9) ms 35 9) ms 35 9) ms Break time 45 9) ms 45 9) ms 45 9) ms 45 9) ms 45 9) ms Rated operating sequence at rated normal current O-0.3s-CO-0s-CO-0s-CO 0) Rated operating sequence at rated short-circuit breaking current O-0.3s-CO-5s-CO Auxiliary circuits insulation strength ) Power frequency test voltage ( min) according to IEC Lightning impulse. m s/50 m s/0.5 J according to IEC Insulation resistance, 000V DC according to IEC Design class of switching module with regard to severity of service conditions in accordance with IEC 6093 kv 5 kv 5 MOhm Class Class 0 Class 0 Class 0 Class 0 Standards Mechanical vibration withstand capability according to IEC IEC GB IEC GB IEC GB Class 4M4 IEC GB IEC Resistance of main circuit 40 μohm 7 μohm 8 μohm 5 μohm 40 μohm Weight (depending on Pole centre distance) for three-phase ISM kg kg 5-55 kg 70-7 kg kg Weight for single phase ISM 3 kg kg Weight for CM Overall dimensions of CM ) kg 90x65x45 mm Altitude above sea level 000 m 3) Relative humidity in 4 hours 95 % Relative humidity over month 90 % Temperature Range -5 C C Degree of protection according to IEC 6059 of actuator compartment Type of driving mechanism IP40 Monostable magnetic actuator 3

32 Type VCB5_LD VCB5_MD VCB5_Shell VCB5_HD VCB5_LD Design, switching capacity of silver auxiliary contacts Number of available auxiliary contacts for three-phase ISM Number of available auxiliary contacts for single-phase ISM Minimum current for V AC / DC, ohmic load 6 NO + 6 NC NO + NC 00 ma Minimum current for V AC / DC, inductive load (t=0 ms, cosj =0,3) 00 ma Maximum current for 30 V DC, ohmic load 0 A ) Maximum current for 30 V DC, inductive load (t=0 ms) 3 A Maximum current for 60 V DC, ohmic load 0.9 A Maximum current for 60 V DC, inductive load (t=0 ms) 0.9 A Maximum current for 5 V DC, ohmic load 0.5 A Maximum current for 5 V DC, inductive load (t=0 ms) 0.03 A Maximum current for 50 V DC, ohmic load 0.5 A Maximum current for 50 V DC, inductive load (t=0 ms) 0.03 A Maximum current for 5 V AC, ohmic load 0 A 4) Maximum current for 5 V AC, inductive load (cosj =0,3) 5 A Maximum current for 50 V AC, ohmic load 0 A 4) Maximum current for 50 V AC, inductive load (cosj =0,3) 5 A Design, switching capacity of gold-plated auxiliary contacts Number of available auxiliary contacts for three-phase ISM NO + 6 NC Number of available auxiliary contacts for single-phase ISM - Minimum current for 5 V AC / DC ma Maximum current for 0 V AC / DC 300 ma Maximum current for 30 V AC / DC 00 ma Maximum voltage AC / DC 30 V CM reaction times Preparation time for the operation of the CM after switching on the auxiliary power supply 5 s Preparation time for the close operation of the CM after a previous close operation 0 s Preparation time for the trip operation of the CM after switching on the auxiliary power supply 0. s Trip capability after failure of the auxiliary power supply 60 s 5) CM supply voltage Rated range of supply voltage of CM_6_(60_x) Rated range of supply voltage of CM_6_(0_x) Operating range (80-0%) of CM_6_(60_x) Operating range (80-0%) of CM_6_(0_x) 4V to 60V DC 0V to 0V AC/DC 9V to 7V DC 85V to 65V AC/DC 3

33 Power consumption of CM Type VCB5_LD VCB5_MD VCB5_Shell VCB5_HD VCB5_LD Charging the close and trip capacitors of CM_6_(60_x) Charging the close and trip capacitors of CM_6_(0_x) Permanent power consumption (standby) of CM_6_(60_x) Permanent power consumption (standby) of CM_6_(0_x) Inrush current of CM_6_(60_x) with discharged capacitors Inrush current of CM_6_(0_x) with discharged capacitors Inrush time constant of CM_6_(60_x) with discharged capacitors Inrush time constant of CM_6_(0_x) with discharged capacitors 5 W 4 W AC 6) 37 W DC 5 W 7 W AC 7) 5 W DC 0 A 8 A 0.5 ms 4 ms Design, switching capacity of CM inbuilt relays Number of relays in CM 3 Number of available contacts for one relay Rated voltage Rated current AC Maximum breaking power AC Maximum switching current 50V DC Maximum switching current 5V DC Maximum switching current 48V DC Maximum switching current 4V DC Switching time NO + NC with common point 40 V 6 A 4000 VA 0.35 A 0.45 A.3 A A 5 ms Close and Trip dry contacts inputs of CM Output voltage Contacts closed current Steady state current 30 V 50 ma 5 ma ) For VCB ISM5_Shell with Low upper terminal up to 50 A, with High upper terminal up to 000 A. ) 350 A for PCD 75 mm 3) The information in brackets refers to the national Chinese standards GB at an installation altitude of 000 m maximum. 4) Parameter valid only when ISM is used with insulation kit. For details see dimensional drawings and accessory information 5) Parameter valid only when ISM is used with insulation caps. For details see dimensional drawings and accessory information. 6) At 40% d.c. component. 7) CO for ISM5_LD_6. 8) 0000 CO for ISM5_Shell_(50_L) and ISM5_Shell_(0_L) in horizontal actuator position. 9) Smaller timing on request 0) The number of sequential Close-Trip operations with a 0 second interval should not exceed 0. The number of Close-Trip operations should not exceed 60 per hour. Sequence of 0s Close-Trip operations can be repeated only after 60 s pause. ) Isolation resistance check is not applicable for Actuator Coil circuits of CM. ) Overall dimensions of ISM are given in Appendix 3. Overall drawings 3) Up to an installation altitude of 000 m above sea level. Above 000m, the external insulation measurement of the ISM must be increased by the atmospheric correction factor Ka according to IEC 67- compared to the insulation measurement at sea level. The maximum allowed altitude is 000 m above sea level. 4) At 5 min short-term duty. Continuous current 5 A. 5) In case of Dry contacts Close and Trip are open. 6) At Cos j > ) At Cos j >

34 Parameter Table 6 - CM EMC parameters Applicable Rated Value standard Electromagnetic compatibility (EMC) requirements ) Electrostatic discharge Radiated EM field Immunity Fast transient burst Immunity Surge Immunity Conducted disturbance induced by Radio frequency fields Power Frequency Magnetic Field IEC VCB5_LD IEC VCB5_LD IEC IEC IEC IEC67- IEC IEC IEC IEC IEC IEC IEC kv contact 5 kv air 80 MHz 3 GHz Sweep & spot AM khz 80% 0 V/m 4 kv common mode 4 kv common mode kv differential mode 50 khz 80 MHz AM khz 80% 0 V 00 A/m continuously 000 A/m sec Pulse Magnetic Field IEC A/m 00 khz Damped Oscillatory Magnetic Field IEC A/m MHz damped oscillatory magnetic field IEC A/m AC Voltage Dips and Interruptions Power Frequency Disturbance Voltage 00 khz and MHz Damped Oscillatory Wave Immunity Ripple on DC Power Supply IEC IEC IEC IEC IEC IEC 67- IEC IEC IEC ΔU 30% period ΔU 60% 50 periods ΔU 00% 5 periods ΔU 00% 50 periods 300 V common mode 50 V differential mode ).5 kv common mode kv differential mode 0% of Supply voltage, 00 Hz DC Voltage Dips and Interruptions IEC IEC IEC ΔU 30% sec ΔU 60% sec ΔU 00% 0,3 sec ±0 % 0 sec ) Cable from electronic relay to connector block should be shielded and the case grounded near the connector. The total length of unshielded wires from connector block to CM WAGO connector should not exceed 00 mm. Electromagnetic compatibility requirements are not applicable for the CM USB port as this port is used only for CM programming during production and not used under service conditions. ) Test influence is not applicable for CM Close and Trip dry contacts. 34

35 5. Design and operation

36 5. Design 5.. Indoor Switching Module The VCB main component is the innovative Tavrida Electric Indoor Switching Module. Tavrida Electric has simplified the mechanical structure of the switching module to the greatest possible extent. It uses three single-coil magnetic actuators, one per pole. All switching elements are assembled along a single axis. All mechanical operations are therefore direct and linear. Three actuators are installed in a steel frame and mechanically linked by a synchronizing shaft. This design eliminates failure modes caused by components in conventional technology such as gears, charging motors, and trip / closing coils. Tavrida Electric manufactures vacuum interrupters that combine small dimensions with an extraordinarily long mechanical and electrical lifespan. The use of a specially designed axial magnetic field distribution provides even current density distribution over the contact surface and consequently a substantial improvement of vacuum interrupting performance. The result is up to 50,000 CO cycles at rated current or up to 50 O-CO cycles at maximum short-circuit breaking current without replacing or adjusting any parts of the circuit breaker. Tavrida Electric Vacuum Circuit Breakers are completely maintenance free over a total life expectancy of at least 30 years. 5.. Control Module Tavrida Electric Control modules provide the following advantages: Low power consumption A low energy level required to close or trip the ISM, no energy consumption by the ISM in its closed or open state and optimization of CM electrical diagrams leads to low CM power consumption - no more than 4 Watts during CM capacitors charging and no more than 7 Watts in standby mode. Optimal ISM control One CM can be applied to several different ISM types. The CM is programmed for use with a particular ISM type. The result is optimal ISM close and trip through a wide range of temperatures. Self-diagnostic functionality The CM has an internal self-diagnostic system that monitors ISM connection, power supply level and internal states of the CM. As a result, the CM can indicate issues by means of LEDs and built-in relays. The malfunction types are indicated by the number of corresponding LED blinks. Wiring optimization The CM controls the ISM main contact state via the same circuit used to close or trip the ISM. Therefore, only one circuit connection between ISM and CM is required. The CM can provide external circuits with information about ISM main contacts state by means of built in relays, which simplifies the switchgear secondary wiring significantly. Position indication of ISM provided by CM can be incorrect, in case CM is not operable due to absence of auxiliary supply. The relay keeps its state after CM power supply disconnection. Compact dimensions and small weight of CM The compact size and weight of the CM (90x65x45 mm, kg) simplifies the installation. The aluminum housing of the CM provides a high EMC level (Table 6). 36

37 The CM is delivered with mounting brackets for mounting on flat surfaces. The LED indicators are visible from two directions.. Earthing stud. Terminals for power supply 3. Terminals for I/O (control and indication) 4. Terminals for Switching Module 5. Power LED indicator 6. USB port (for CM programming during production, not used under service conditions) 7. Malfunction LED indicator 8. Ready LED indicator Figure 4 CM_ Insulation kits Tavrida Electric switching modules have a very compact design allowing for easy installation in many applications. Tavrida Electric offers several kits to ensure that external bus bar connection will not reduce the insulation level of the ISM. CBkit_Ins_3 To comply with the rated impulse withstand voltage of 5 kv according to IEC 67- it is recommended to cover the top connections of ISM5_LD_ and ISM5_LD_3 with insulation kit CBkit_Ins_3. The arrangement is shown below. If the insulation cap set is not used, compliance with the rated insulation level must be verified by a dielectric test. Not applicable for ISM5_LD_. CBkit_Ins_4 To comply with the rated impulse withstand voltage of 95 kv according to IEC 67- it is recommended to cover the terminals of ISM5_MD_ with insulation kit CBkit_Ins_4. The arrangement is shown below. If the insulation cap set is not used, compliance with the rated insulation level must be verified by a dielectric test. CBkit_Shell5_ This kit is used to provide 95 kv BIL level between terminals of the ISM5_Shell_. The external air insulation can withstand 75 kv BIL. The ISM5_Shell_(50_L) requires CBkit_Shell5_ for 75 kv BIL. CBkit_Shell5_ also includes round copper bars and screws for flat bars connection to the ISM5_Shell_ terminals. CBkit_Shell5_ has two sets of bolts with different lengths, selection of their usage depends on the number of bars connected to ISM terminals - single or double bars. CBkit_LD5_ and CBkit_LD5_3 Kits CBkit_LD5_ and CBkit_LD5_3 provide 75 kv BIL level for ISM5_LD_6 when this ISM is used as an LMT or AG6 Retrofit Draw-out type VCB. The kits also include plastic moulded parts to provide emergency (manual) trip and main contacts position indication. For details of these Retrofit Draw-out type VCB designs please contact your nearest Tavrida Electric office or Distributor. 37

38 Figure 5 CBkit_Ins_3 installed on ISM5_LD Figure 6 CBkit_Ins_4(), Single 40x0 mm bars connection Figure 7 CBkit_Ins_4(), Double 40x0 mm bars connection Figure 8 CBkit_Ins_4(), Single 80x0 mm bars connection 38

39 Figure 9 CBkit_Shell5_(05) installed on ISM5_Shell_(50_L) Figure 30 CBkit_Shell5_(30) installed on ISM5_Shell_(0_H) 39

40 5..4 Interlocking kits CBkit_Interlock_ This kit is used to link the ISM synchronizing shaft with mechanical interlocks. CBkit_Interlock_ linked with ISM s shaft can provide information about ISM main contacts state (closed, open), emergency (mechanical) trip of ISM and mechanical blocking of ISM closing. CBkit_Interlock_ is optional for ISM5_LD_ and ISM5_LD_. ISM5_LD_3 and ISM5_LD_3 are already equipped with the CBkit_Interlock_ pre-installed. Figure 3 Interlocking kits installed on ISM5_LD_3 CBkit_Interlock_ This kit is used to link the ISM interlocking shaft with mechanical interlocks. CBkit_Interlock_ linked with ISM s shaft can provide manual (emergency) trip / lockout (mechanical blocking of ISM closing) functionality. The kit has an interface for connection with other mechanical interlocks of switchgear and RMU. CBkit_Interlock_ is not applicable for ISM5_Shell_ and ISM5_LD_6. Figure 3 Interlocking kits installed on ISM5_Shell_ CBkit_Interlock_ is applicable for ISM5_Shell only 40

41 CBkit_Interlock_3 This kit is used to link the ISM interlocking shaft with mechanical interlocks. CBkit_Interlock_3 linked with ISM s shaft can provide manual (emergency) trip / lockout (mechanical blocking of ISM closing) functionality by key switch. The kit has an interface for connection with other mechanical interlocks of switchgear and RMU. Figure 33 CBkit_Interlock_3 Interlocking kit installed on ISM5_HD_ CBkit_Interlock_3 is applicable for ISM5_MD and ISM5_HD only CBkit_Interlock_4 This kit is used to link the ISM interlocking shaft with mechanical interlocks. CBkit_Interlock_4 linked with ISM s shaft can provide manual (emergency) trip / lockout (mechanical blocking of ISM closing) functionality by rotary switch. The kit has an interface for connection with other mechanical interlocks of switchgear and RMU. Figure 34 CBkit_Interlock_4 Interlocking kit installed on ISM5_HD_ CBkit_Interlock_4 is applicable for ISM5_MD and ISM5_HD only 4

42 CBkit_Interlock_5 This kit is used to link the ISM interlocking shaft with mechanical interlocks. CBkit_Interlock_5 linked with ISM s shaft can provide manual (emergency) trip by push-button switch. Figure 35 CBkit_Interlock_5 Interlocking kit installed on ISM5_HD_ CBkit_Interlock_5 is applicable for ISM5_MD and ISM5_HD only 5..5 Switching module main contacts position indicator If position indicator is used CBkit_PosInd_ shall be connected to ISM with CBcomp_RelCable_ to provide ISM main contact position indication. ISM5_Shell_ already includes these components. Figure 36 CBkit_PosInd_ with connected CBcomp_RelCable_ 4

43 5. Operation 5.. Closing To close the ISM main contacts, the CM close command shall be applied. It is a dry contact input so no external voltage should be applied. The Close command will be accepted if: CM state is Ready (Ready LED flashes green); no Trip command is applied; optional electrical interlock is unlocked; mechanical and electrical interlock is unlocked (in case of ISM5_MD_, ISM5_Shell_ and ISM5_HD_ only). If Close command is applied and held before the CM is in a Ready state the Close command will not be accepted. If auxiliary power is not available, the manual generator CBunit_ManGen shall be used to charge the CM capacitors and to close the ISM. Mechanical closing is not possible.. Close command input. Trip command input Figure 37 CM_6 close and trip inputs If Manual generators CBunit_ManGen are used to charge the CM, the Manual generator handle shall be rotated until the Ready LED of the CM flashes green (approximately 30 seconds). Then the ISM close command can be applied to the CM. 5.. Opening To open the ISM main circuits, a trip command should be applied to the CM trip command input. It is a dry contact input so no external voltage should be applied. The trip command will be accepted if: CM state is Ready (Ready LED flashes green) or within 60 seconds after the removal of the auxiliary power supply; optional electrical interlock is unlocked; mechanical and electrical interlock is unlocked (in case of ISM5_MD_, ISM5_Shell_ and ISM5_HD_ only). If the trip command is applied and kept before the CM is in a Ready state, the trip command will be accepted after CM is in a Ready state Emergency opening The ISM can also be opened manually. When the synchronizing shaft is rotated, a force exceeding the magnetic attraction forces of the ring magnet is applied to the armature, which subsequently starts to move. As the air gap increases, the opening springs and the contact pressure springs overcome the magnetic holding force, and the vacuum interrupter opens. To open the ISM5_LD and ISM5_LD manually, the force shall be applied to the interlocking pins or torque shall be applied to the stub shaft evenly during their movement - see Figure 9 above and Figure 9 below. Force shall be applied along the pin s movement axis and directed to the ISM frame. The torque shall be applied in the direction of shaft rotation during ISM opening. The force or torque influence shall not be applied at the end of pin s stroke or shaft rotation and shall not be applied to the pin or shaft before ISM closing. 43

44 Figure 38 ISM5_LD and ISM5_LD manual trip execution. Force or torque can be applied to any of the points shown below To open the ISM5_MD, ISM5_Shell and ISM5_HD manually, the torque shall be applied to the interlocking shaft evenly during its movement - see Figure 5 above and Figure 43 below. The torque shall be applied counterclockwise of shaft rotation (90 degrees angle). The torque shall not be applied at the end of shaft rotation. ISM5_MD_, ISM5_Shell_ and ISM5_HD_ has a built in electrical interlock that interrupts the ISM coil circuit after the intelocking shaft is rotated counterclockwise. After manual trip, the shaft should be rotated clockwise to unlock the ISM. Figure 39 ISM5_Shell manual trip execution (ISM5_MD and ISM5_HD have same manual trip execution) 44

45 6. Functionality

46

47 6. Indication The VCB has the following indication functionality: indication provided by ISM: ISM main contacts position (mechanical indication) - CBkit_PosInd_ with connected CBcomp_RelCable_; ISM main contacts position (electrical indication) - ISM auxiliary switches (6NO+6NC switches for three phase ISMs and NO+NC - for single phase ISMs). indication provided by CM: ISM main contacts position (electrical indication) - one inbuilt CM relay ( NO + NC with common point); CM Power indication - LED indicator; CM Ready state indication - LED indicator and one built in CM relay ( NO + NC with common point); CM Malfunction state indication - LED indicator and one built in CM relay ( NO + NC with common point). Parameters of allowed ISM auxiliary switch load and built in CM relays are given in Chapter 4. The self-diagnostic system inside the CM detects possible malfunctions and reports them via the Malfunction LED blink signals and Malfunction or Loss of auxiliary supply Relay state. The explanation of the blink codes is given in Table 7. Table 7 - CM self-diagnostic indication Indication CM state LED Power LED Ready LED Malfunction Relay Ready Relay Malfunction or Loss of auxiliary supply Power supply voltage is absent more than 3 minutes "Close" operation is preparing off off off O C continuous off off O O CM is ready and operable continuous continuous off C O Power supply voltage is absent for more than.5 seconds off continuous blink C C Excessive trip or close time continuous off blinks O C Actuator coil isolated continuous off 3 blinks O C Short circuit of Actuator coil continuous off 4 blinks O C Manual Trip and Lock continuous off 5 blinks O O Overheat continuous off 6 blinks O O ISM state is open without command from the CM continuous off 7 blinks O C Internal fault of the CM continuous off continuous O C Notes.. Number of blinks in series followed by.5 s intervals, continuous light or off state are shown for LED indicators.. State of relay contact groups (C closed, O opened) is indicated for NC Ready Relay and Malfunction or Loss of auxiliary supply Relay. 3. Period of checking Actuator Coil state (short circuit / isolated) 0 s. Priority of the fault indication starting from the lowest one:. CM overheat ;. ISM state is open without command from the CM; 3. Excessive trip or close time; 4. Manual Trip and Lock; 5. Actuator coil isolated; 6. Short circuit of Actuator coil; 7. Power supply voltage is absent more than.5 seconds. 47

48 CM performs the checkup of ISM main contacts position and updates the ISM main contacts position relay status in the following cases: In case Close command was applied from the CM. In this case the update is performed not later than in 50ms after ISM main contacts closing; In case Trip command was applied from the CM. In this case the update is performed not later than in 70ms after ISM main contacts opening; Periodically every 0s in case no Close or Open command was applied from the CM. In case application project requires to define main contacts position faster than the timing mentioned above it is recommended to use auxiliary switches installed at the ISM. 48

49 7. Application notes

50

51 7. Configuration options Lower terminal design of ISM The one lower main terminal (conventional terminal) of ISM is usually sufficient for standard applications, but there may be applications where the switchgear is so compact that ISM terminals are used as bus bars, for example Ring main units in city electrical networks. Figure 40 ISM with one lower main terminal Figure 4 ISM with two lower main terminals Figure 4 Example of ISM with two lower main terminals inside of SF-6 isolated Ring main unit 5

52 BIL level of ISM The selection of BIL level of an ISM is related to the VCB and associated insulation parts kits, not necessarily to the ISM itself. Selection of either 75 kv or 95 kv BIL defines whether VCB5_MD_6F will be equipped with CBkit_Ins_4. This kit is optional accessory as its selection depends on the type of bars used for ISM5_MD_ main terminals connection: for bars with cross-section 40x0 mm (single or double bars) the CBkit_Ins_4() shall be used for 95 kv BIL; for bars with cross-section 80x0 mm (single bar) the CBkit_Ins_4() shall be used for 95 kv BIL. The bars with cross-section 80x0 mm are not applicable for ISM5_MD_ with PCD 50 mm due to the bars width that decreases the distance between bars. Figure 43 ISM5_MD_ with CBkit_Ins_4() and double bars 40x0 mm Figure 44 ISM5_MD_ with CBkit_Ins_4() and single bars 80x0 mm The selection of BIL level of an ISM is related to the VCB and associated insulation parts kits, not necessarily to the ISM itself. Selection of either 75 kv or 95 kv BIL defines whether VCB5_Shell_6F will be equipped with CBkit_Shell5_. Only the VCB5_Shell_6F with PCD 50 mm is always equipped with CBkit_Shell5_(05) since distance between poles of ISM5_Shell_(50_L) requires it at 75 kv BIL. Figure 45 ISM5_Shell_ without CBkit_Shell5_: ISM5_Shell_(50_L) - BIL 60 kv due to short distance between poles; ISM5_Shell_ with other PCD - BIL 75 kv. Figure 46 ISM5_Shell_ with CBkit_Shell5_ - BIL 95 kv for all variants of PCD 5

53 Selection of either 75 kv or 95 kv BIL defines whether VCB5_HD_6F will be equipped with bare or isolated bars used for ISM5_HD_ main terminals connection. The shrinkable tube is recommended for the bars isolating. The bars shall have radius at least 3 mm on their edges. Figure 47 ISM5_HD_ with isolated double bars 00x0 mm Selection of either 95 kv or 5 kv BIL defines whether VCB5_LD_6F or VCB5_LD3_6F will be equipped with CBkit_Ins_3. Figure 48 ISM5_LD_, ISM5_LD_3 without CBkit_Ins_3 - BIL 95 kv Figure 49 ISM5_LD_, ISM5_LD_3 with CBkit_Ins_3 - BIL 5 kv CBkit_Ins_3 used in place of bar connections to ISM upper teminals to provide 5 kv BIL. If another design is used, the rated insulation level shall be verified by a dielectric test. CBkit_Ins_3 is not applicable for VCB5_LD_6F as VCB5_LD_6F is intended for usage inside of SF-6 isolated switchgear which already provide 5 kv BIL. Rated voltage of auxiliary circuits Selection of rated supply voltage range defines the rated supply voltage of the CM. Information about ranges of rated voltage of other VCB auxiliary circuits such as ISM auxiliary switches, CM built in relay switching contacts and CM control input circuits is given in Chapter 4. 53

54 7. Primary connections 7.. ISM installation In any switchgear application, the ISM5_Shell and ISM5_HD shall may be installed in position actuator up or actuator down. The ISM5_LD, ISM5_MD and ISM5_LD can be installed in any position. Additionally ISM5_Shell_(50_L) and ISM5_Shell_(0_L) can be installed in horizontal actuator position. In this case the plane of all ISM terminals surfaces shall be horizontal as well and terminals surfaces shall be up oriented. Figure 50 Fixed compact installation of HD ISM, vertical arrangement, actuator up Figure 5 Fixed compact installation of LD ISM, vertical arrangement, actuator down 54

55 Points shown below should be used for mounting the ISM. 3A 3C 3B Figure 5 ISM5_LD and ISM5_LD mounting points Figure 53 ISM5_Shell mounting points Figure 54 ISM5_MD mounting points Figure 55 ISM5_HD mounting points ISM5_HD_ for 95 kv BIL installation extension part between obligatory mounting holes and an external frame has to be used. CBmount_ISM5_ includes the studs to provide required extension: Figure 56 ISM5_HD mounting with help of studs from CBmount_ISM5_ Required mounting points 3 Each two mounting points are required, either 3A+3B or 3A+3C Optional mounting points 55

56 7.. Minimum clearances due to electromagnetic influence Short-circuit current magnetic field influences the ISM magnetic actuator. To avoid unwanted tripping, the minimum clearances between bus bars and the ISM frame should be not less than stated in Table 8. Table 8 - Minimum clearances due to electromagnetic influence Short circuit current Minimum clearance (a) Applicable for 0 ka 00 mm ISM5_MD 0 mm all ISM excluding ISM5_MD 0 mm ISM5_MD 5 ka 50 mm ISM5_Shell 90 mm ) ISM5_HD 50 mm ISM5_MD 3.5 ka 90 mm ISM5_Shell 40 mm ) ISM5_HD Notes.. Shorter clearance on request a Figure 57 Electromagnetic clearances limitations 7..3 Minimum clearances due to rated insulation voltage The recommended minimum phase-to-phase and phase-to-ground air clearances are stated in Table 9. Shorter clearances shall be verified by a voltage test. b b Metal housing Table 9 - Minimum clearances due to rated insulation voltage Power frequency rated voltage Impulse test voltage (BIL) Minimum clearance (b) for LD ISM kv 75 kv 0 mm 7.5 kv 95 kv 40 mm 4 kv 5 kv 0 mm b Figure 58 LD ISM insulating clearances limitations 56

57 Figure 59 Insulating clearance limitations of ISM5_MD for 75 kv BIL Figure 60 Insulating clearance limitations of ISM5_MD for 95 kv BIL 57

58 Figure 6 Insulating clearance limitations of ISM5_Shell_ with low upper terminal Figure 6 Insulating clearance limitations of ISM5_Shell_ with high upper terminal Figure 63 Insulating clearance limitations of ISM5_HD_ The minimum clearance between bus bars and the HD ISM frame shall be no less than 0 mm for 75 kv BIL and no less than 40 mm for 95 kv BIL. Metal housing Coordination of minimum clearances Based on electromagnetic influence (a) and rated insulation voltage (b), the greater clearance should be selected. a b Figure 64 Clearance coordination 58

59 7.3 Secondary equipment 7.3. Three-phase ISM secondary connections All three-phase ISM5_LD, ISM5_Shell and ISM5_LD have secondary connectors as shown below. Figure 65 Terminal arrangement of the three-phase ISM5_LD, ISM5_Shell and ISM5_LD Table 0 - Three-phase ISM5_LD, ISM5_Shell and ISM5_LD terminal arrangement XT XT Terminal No. Connection Terminal No. Connection Auxiliary switch S () 5 Auxiliary switch S 3 (AS) Auxiliary switch S (4) 6 Auxiliary switch S 3 (AS) 3 Auxiliary switch S () 7 Auxiliary switch S 7 () 4 Auxiliary switch S (4) 8 Auxiliary switch S 7( ) 5 Auxiliary switch S 3 () 9 Auxiliary switch S 8 () 6 Auxiliary switch S 3 (4) 0 Auxiliary switch S 8 () 7 Auxiliary switch S 4 () Auxiliary switch S 9 () 8 Auxiliary switch S 4 (4) Auxiliary switch S 9 () 9 Auxiliary switch S 5 () 3 Auxiliary switch S 0 () 0 Auxiliary switch S 5 (4) 4 Auxiliary switch S 0 () Auxiliary switch S 6 () 5 Auxiliary switch S () Auxiliary switch S 6 (4) 6 Auxiliary switch S () 3 Actuator coil (SC) 7 Auxiliary switch S () 4 Actuator coil (SC) 8 Auxiliary switch S () 59

60 ISM5_MD_ and ISM5_HD_ have secondary connectors as shown below. a) ISM actuator coil terminal b) Auxiliary switches board EA_Asboard_8 (XT, XT3) Figure 66 Terminal arrangement of the ISM5_MD_ and ISM5_HD_ Each of the ISM5_MD_ and ISM5_HD_ has two auxiliary switches boards EA_Asboard_8. Table - ISM5_MD_ and ISM5_HD_ terminal arrangement XT Terminal No. Connection Actuator coil (SC) Actuator coil (SC) XT, XT3 (Auxiliary switches board EA_Asboard_8) Terminal No. Connection NC auxiliary switch S () NC auxiliary switch S () 3 NC auxiliary switch S () 4 NC auxiliary switch S () 5 NC auxiliary switch S 3() 6 NC auxiliary switch S 3() 7 NC auxiliary switch S 4() 8 NC auxiliary switch S 4() 9 NC auxiliary switch S 5() 0 NC auxiliary switch S 5() NC auxiliary switch S 6() NC auxiliary switch S 6() 60

61 7.3. Single-phase ISM secondary connections All single-phase ISMs have secondary connectors as shown below. Figure 67 Terminal arrangement of the single-phase ISM Table - Single-phase ISM terminal arrangement XT Terminal No. Connection Auxiliary switch SF (AS) Auxiliary switch SF (AS) 3 Auxiliary switch SF 4 Auxiliary switch SF 5 Auxiliary switch SF3 6 Auxiliary switch SF3 7 Auxiliary switch SF4 8 Auxiliary switch SF4 9 Auxiliary switch SF5 0 Auxiliary switch SF5 Actuator coil (SC) Actuator coil (SC) 6

62 7.3.3 CM secondary connections CM_6_ has secondary connectors as shown below. Figure 68 Terminal arrangement of the CM Table 3 - CM terminal arrangement X X3 Terminal No. Connection Terminal No. Connection Power supply input (+) Actuator coil output Power supply input (-) Actuator coil output 3 Relay output NC 4 Relay output Com 5 Relay output NO 6 Relay output NC 7 Relay output Com 8 Relay output NO 9 Relay output 3 NC 0 Relay output 3 Com Relay output 3 NO Close input 3 Close input 4 Trip input 5 Trip input CM relay functionality: Relay - ISM main contact position relay; Relay - Ready relay; Relay 3 - Malfunction or Loss of auxiliary supply relay. Relay ISM main contact position keeps its state ( NO and NC contacts with common point) after CM power supply disconnection. Relays functionality and number of relays with same functionality can be changed on request. Please contact the nearest Tavrida Electric sales representative for more information. 6

63 7.3.4 CM and ISM secondary connections The CM is connected to the ISM actuator coil circuits only. The position of the ISM main contacts is determined by detecting the ISM coil inductance level. CM relay ISM main contact position indicates the result. CM Actuator coil R PS ISM AC AC actuator coil; PS position switch with current not less than 0 A; R resistor kohm±5%, average power 0.5 W, peak power 8 W Figure 69 CM and ISM secondary connections Resistor R is used to prevent the CM alarm Actuator Coil Isolated while position switch PS is open. PS - optional electrical interlock position switch. PS and R are not required for ISM5_MD_, ISM5_Shell_ and ISM5_HD_ since these ISMs already have a built in electrical interlock. Capacity of the cable between CM and ISM shall be no more than nf and its resistance shall be no more than 0.3 Ohm. 63

64 7.4 Auxiliary supply Connection of CM_6_ to power supply is shown below. ~ (+) ~ (-) MCB Power supply inputs Figure 70 CM_6 power supply connection Type of MCB shall be selected according to the CM. Consumption data given in Chapter 4. If Manual generators CBunit_ManGen are used for charging, the CM DC voltage outputs shall be connected to power supply inputs of CM_6_. 64

65 Appendix. Type tests

66 Type tests of ISM5_LD Standard Chapter Test name IEC IEC IEC Power-frequency withstand voltage test Lightning impulse withstand voltage test Measurement of the resistance of the main circuit Test center name KEMA KEMA KEMA IEC Temperature-rise tests KEMA IEC IEC IEC IEC IEC Short-time withstand current and peak withstand current tests Additional tests on auxiliary and control circuits Mechanical operation test at ambient temperature Short-circuit current making and breaking tests KEMA KEMA KEMA TEL Testlab KEMA Test report KEMA_70747_000- HVL03-03 KEMA_70747_000- HVL03-03 KEMA_70747_000- HVL03-03 KEMA_70747_000- HVL03-03 KEMA_79-03 KEMA_70747_000- HVL03-03 KEMA_67-03 EDRTL_3-007E KEMA_79-03 IEC Single-phase earth fault test KEMA KEMA_79-03 IEEE C37.09 Table Short-circuit current making and breaking tests KEMA KEMA_6-08 V IEEE C Load current switching test KEMA KEMA_6-08 V IEC Cable charging current switching test KEMA KEMA_ IEEE C37.09 Table Cable charging current switching test KEMA KEMA_7-08 V EEE C37.09 Table Capacitor switching current tests KEMA KEMA_7-08 V IEC Radiated electromagnetic field immunity test CESI CESI B

67 Type tests of ISM5_MD Standard Chapter Test name IEC IEC Power-frequency withstand voltage test Lightning impulse withstand voltage test Test center name Test report KEMA KEMA KEMA KEMA IEC Partial discharge tests KEMA KEMA IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC , , , 6. IEC Dielectric tests on auxiliary and control circuits Electrical continuity of earthed metallic parts test Measurement of the resistance of the main circuit Temperature-rise tests on the main circuits Temperature-rise tests on auxiliary and control equipment Mechanical and electromechanical interlocks tests Short-time withstand current and peak withstand current tests Short-circuit current making and breaking tests KEMA KEMA KEMA KEMA KEMA KEMA KEMA KEMA KEMA KEMA KEMA KEMA -8 KEMA KEMA -8 KEMA Not tested yet Single-phase earth fault test KEMA KEMA -8 Double-earth fault test KEMA KEMA -8 Making and breaking tests on class E KEMA Not tested yet Mechanical operation test at ambient temperature KEMA IEC Low and high temperature tests KEMA TBD IEC IEC Line-charging and cable-charging current switching tests Radiated electromagnetic field immunity test KEMA CESI TBD TBD CESI B

68 Type tests of ISM5_Shell Standard Chapter Test name IEC IEC IEC Power-frequency withstand voltage test Lightning impulse withstand voltage test Measurement of the resistance of the main circuit Test center name CESI CESI CESI IEC Temperature-rise tests CESI IEC IEC IEC IEC IEC IEC Short-time withstand current and peak withstand current tests Additional tests on auxiliary and control circuits Mechanical operation test at ambient temperature Short-circuit current making and breaking tests Short-circuit current making and breaking tests, E class Single-phase and double-earth fault tests CESI XIHARI CESI XIHARI CESI CESI CESI Test report CESI_B03637 CESI_B03637 CESI_B0760 CESI_B046 CESI_B0760 CESI_B046 CESI_B XIHARI_044G CESI_B05746 XIHARI_044G CESI_B CESI_B CESI_B GB Cable charging current switching test XIHARI XIHARI_044G IEC Radiated electromagnetic field immunity test CESI CESI B

69 Type tests of ISM5_LD Standard Chapter Test name IEC IEC IEC Power-frequency withstand voltage test Lightning impulse withstand voltage test Measurement of the resistance of the main circuit Test center name KEMA KEMA KEMA Test report KEMA_ A KEMA_ A KEMA_ A IEC Temperature-rise tests KEMA KEMA_ A IEC IEC IEC IEC Short-time withstand current and peak withstand current tests Additional tests on auxiliary and control circuits Mechanical operation test at ambient temperature Short-circuit current making and breaking tests CESI KEMA KEMA TEL Testlab CESI CESI_A KEMA_ A KEMA_ A Pr43-0E CESI_A CESI_A IEC Partial discharge tests CESI CESI_A60904 IEC Cable charging current switching test CESI CESI_A CESI_A CESI_A60364 IEC Short-circuit current making and breaking tests, E class CESI CESI_A IEC IEC Single-phase and double-earth fault tests Radiated electromagnetic field immunity test CESI CESI_A CESI_A KEMA KEMA Final

70 Type tests of CM_6 Standard IEC IEC IEC IEC IEC IEC 67- IEC IEC IEC IEC IEC IEC IEC Test name Test center name Test report Electrostatic discharge immunity test KEMA KEMA TIC 37-4 Radiated electromagnetic field immunity test KEMA KEMA TIC 37-4 Fast transient burst immunity test KEMA KEMA TIC 37-4 Surge immunity test KEMA KEMA TIC 37-4 Conducted disturbance induced by radio frequency fields immunity test KEMA KEMA TIC 37-4 Power frequency magnetic field immunity test KEMA KEMA TIC 37-4 IEC Pulse magnetic field immunity test KEMA KEMA TIC 37-4 IEC IEC IEC IEC IEC IEC IEC IEC 67- IEC IEC IEC 67- IEC IEC IEC IEC IEC IEC IEC IEC khz damped oscillatory magnetic field immunity test MHz damped oscillatory magnetic field immunity test KEMA KEMA TIC 37-4 KEMA KEMA TIC 37-4 AC voltage dips and interruptions immunity test KEMA KEMA TIC 37-4 Power frequency disturbance voltage immunity test KEMA KEMA TIC khz damped oscillatory wave immunity test KEMA KEMA TIC 37-4 MHz damped oscillatory wave immunity test KEMA KEMA TIC 37-4 Ripple on DC power supply immunity test KEMA KEMA TIC 37-4 DC voltage dips and interruptions immunity test KEMA KEMA TIC 37-4 Power frequency withstand voltage test KEMA KEMA TIC 37-4 IEC Insulation resistance test KEMA KEMA TIC 37-4 IEC Impulse withstand voltage test KEMA KEMA TIC

71 Appendix. Product range

72 VCB Product range, delivery sets and package parameters VCB designation Item Quantity VCB5_LD_6F(CB 0_800_0 60_No) VCB5_LD_6F(CB 0_800_0 0_No) VCB5_LD_6F(CB 0_800_50 60_No) VCB5_LD_6F(CB 0_800_50 0_No) VCB5_LD_6F(CB 0_800_50 60_No) VCB5_LD_6F(CB 0_800_50 0_No) VCB5_LD_6F(CB 0_800_80 60_No) VCB5_LD_6F(CB 0_800_80 0_No) VCB5_LD3_6F(CB 0_800_NA 60_No) VCB5_LD3_6F(CB 0_800_NA 0_No) VCB5_LD6_6RD(CB 0_630_33 60_AG6) VCB5_LD6_6RD(CB 0_630_33 0_AG6) VCB5_LD6_6RD(CB 0_630_33 60_LMT) VCB5_LD6_6RD(CB 0_630_33 0_LMT) VCB5_Shell_6F(CB_7.5_3.5_50_50 60_No) VCB5_Shell_6F(CB_7.5_3.5_50_50 0_No) VCB5_Shell_6F(CB 3.5_50_0 60_No) VCB5_Shell_6F(CB 3.5_50_0 0_No) VCB5_Shell_6F(CB_7.5_3.5_50_0 60_No) VCB5_Shell_6F(CB_7.5_3.5_50_0 0_No) ISM5_LD_(55) CM_6_(60_5.LD.6) ISM5_LD_(55) CM_6_(0_5.LD.6) ISM5_LD_(67) CM_6_(60_5.LD.6) ISM5_LD_(67) CM_6_(0_5.LD.6) ISM5_LD_(80) CM_6_(60_5.LD.6) ISM5_LD_(80) CM_6_(0_5.LD.6) ISM5_LD_(90) CM_6_(60_5.LD.6) ISM5_LD_(90) CM_6_(0_5.LD.6) ISM5_LD_3 CM_6_(60_5.LD3) ISM5_LD_3 CM_6_(0_5.LD3) ISM5_LD_6 CM_6_(60_5.LD.6) CBkit_LD5_3 ISM5_LD_6 CM_6_(0_5.LD.6) CBkit_LD5_3 ISM5_LD_6 CM_6_(60_5.LD.6) CBkit_LD5_ ISM5_LD_6 CM_6_(0_5.LD.6) CBkit_LD5_ ISM5_Shell_(50_L) CM_6_(60_5.Shell) CBkit_Shell5_(05) ISM5_Shell_(50_L) CM_6_(0_5.Shell) CBkit_Shell5_(05) ISM5_Shell_(0_L) CM_6_(60_5.Shell) ISM5_Shell_(0_L) CM_6_(0_5.Shell) ISM5_Shell_(0_L) CM_6_(60_5.Shell) CBkit_Shell5_(05) ISM5_Shell_(0_L) CM_6_(0_5.Shell) CBkit_Shell5_(05) Package dimensions (LxWxH), mm Gross weight, kg Net weight, kg 645x90x x90x x90x x90x x330x x330x x90x x90x x90x x90x x40x x40x x40x x40x x75x x75x x75x x75x x75x x75x

73 VCB designation Item Quantity VCB5_Shell_6F(CB 3.5_000_0 60_No) VCB5_Shell_6F(CB 3.5_000_0 0_No) VCB5_Shell_6F(CB_7.5_3.5_000_0 60_No) VCB5_Shell_6F(CB_7.5_3.5_000_0 0_No) VCB5_Shell_6F(CB 3.5_000_75 60_No) VCB5_Shell_6F(CB 3.5_000_75 0_No) VCB5_Shell_6F(CB_7.5_3.5_000_75 60_No) VCB5_Shell_6F(CB_7.5_3.5_000_75 0_No) VCB5_LD_6F(CB_7.5_6_800_0 60_No) VCB5_LD_6F(CB_7.5_6_800_0 0_No) VCB5_LD_6F(CB_4_6_800_0 60_No) VCB5_LD_6F(CB_4_6_800_0 0_No) VCB5_LD_6F(CB_4_.5_630_0 60_DY800) VCB5_LD_6F(CB_4_6_800_75 60_No) VCB5_LD_6F(CB_4_6_800_75 0_No) VCB5_LD_6F (CB_4_6_630_50 60_No) VCB5_LD_6F (CB_4_6_630_50 0_No) VCB5_LD_6F (CB_4_6_630_50 60_No) VCB5_LD_6F (CB_4_6_630_50 0_No) VCB5_LD3_6F(CB_4_6_800_NA 60_No) VCB5_LD3_6F(CB_4_6_800_NA 0_No) ISM5_Shell_(0_H) CM_6_(60_5.Shell) ISM5_Shell_(0_H) CM_6_(0_5.Shell) ISM5_Shell_(0_H) CM_6_(60_5.Shell) CBkit_Shell5_(30) ISM5_Shell_(0_H) CM_6_(0_5.Shell) CBkit_Shell5_(30) ISM5_Shell_(75_H) CM_6_(60_5.Shell) ISM5_Shell_(75_H) CM_6_(0_5.Shell) ISM5_Shell_(75_H) CM_6_(60_5.Shell) CBkit_Shell5_(30) ISM5_Shell_(75_H) CM_6_(0_5.Shell CBkit_Shell5_(30) ISM5_LD_(0_S) CM_6_(60_5.LD.) ISM5_LD_(0_S) CM_6_(0_CB_4) ISM5_LD_(0_S) CM_6_(60_5.LD.) CBkit_Ins_3 ISM5_LD_(0_S) CM_6_(0_5.LD.) CBkit_Ins_3 ISM5_LD_(0_G_) CM_6_(60_5.LD.) ISM5_LD_(75_S) CM_6_(60_5.LD.) CBkit_Ins_3 ISM5_LD_(75_S) CM_6_(0_5.LD.) CBkit_Ins_3 ISM5_LD_() CM_6_(60_5.LD.) ISM5_LD_() CM_6_(0_5.LD.) ISM5_LD_() CM_6_(60_5.LD.) ISM5_LD_() CM_6_(0_5.LD.) ISM5_LD_3 CM_6_(60_5.LD3) CBkit_Ins_3 ISM5_LD_3 CM_6_(0_5.LD3) CBkit_Ins_ Package dimensions (LxWxH), mm Gross weight, kg Net weight, kg 790x75x x75x x75x x75x x75x x75x x75x x75x x90x x90x x90x x90x x90x x90x x90x x90x x90x x330x x330x x90x x90x

74 VCB designation Item Quantity TES_VCB5_MD_6F(CB_7.5_3.5_50_50 60_0) TES_VCB5_MD_6F(CB_7.5_3.5_50_50 0_0) TES_VCB5_MD_6F(CB 3.5_50_50 60_0) TES_VCB5_MD_6F(CB 3.5_50_50 0_0) TES_VCB5_MD_6F(CB_7.5_3.5_50_0 60_0) TES_VCB5_MD_6F(CB_7.5_3.5_50_0 0_0) TES_VCB5_MD_6F(CB 3.5_50_0 60_0) TES_VCB5_MD_6F(CB 3.5_50_0 0_0) TES_VCB5_HD_6F(CB_7.5_3.5_500_0 60_0) TES_VCB5_HD_6F(CB_7.5_3.5_500_0 0_0) TES_VCB5_HD_6F(CB 3.5_500_0 60_0) TES_VCB5_HD_6F(CB 3.5_500_0 0_0) TES_VCB5_HD_6F(CB_7.5_3.5_500_75 60_0) TES_VCB5_HD_6F(CB_7.5_3.5_500_75 0_0) TES_VCB5_HD_6F(CB 3.5_500_75 60_0) TES_VCB5_HD_6F(CB 3.5_500_75 0_0) TES_VCB5_HD_6F(CB_7.5_3.5_350_75 60_0) TES_VCB5_HD_6F(CB_7.5_3.5_350_75 0_0) TES_VCB5_HD_6F(CB 3.5_350_75 60_0) TES_VCB5_HD_6F(CB 3.5_350_75 0_0) ISM5_MD_(50_L) CM_6_(60_5.MD) EA_ASboard_8 ISM5_MD_(50_L) CM_6_(0_5.MD) EA_ASboard_8 ISM5_MD_(50_L) CM_6_(60_5.MD) EA_ASboard_8 ISM5_MD_(50_L) CM_6_(0_5.MD) EA_ASboard_8 ISM5_MD_(0_L) CM_6_(60_5.MD) EA_ASboard_8 ISM5_MD_(0_L) CM_6_(0_5.MD) EA_ASboard_8 ISM5_MD_(0_L) CM_6_(60_5.MD) EA_ASboard_8 ISM5_MD_(0_L) CM_6_(0_5.MD) EA_ASboard_8 ISM5_HD_(0) CM_6_(60_5.HD) EA_ASboard_8 ISM5_HD_(0) CM_6_(0_5.HD) EA_ASboard_8 ISM5_HD_(0) CM_6_(60_5.HD) EA_ASboard_8 ISM5_HD_(0) CM_6_(0_5.HD) EA_ASboard_8 ISM5_HD_(75) CM_6_(60_5.HD) EA_ASboard_8 ISM5_HD_(75) CM_6_(0_5.HD) EA_ASboard_8 ISM5_HD_(75) CM_6_(60_5.HD) EA_ASboard_8 ISM5_HD_(75) CM_6_(0_5.HD) EA_ASboard_8 ISM5_HD_(75) CM_6_(0_5.HD) EA_ASboard_8 ISM5_HD_(75) CM_6_(0_5.HD) EA_ASboard_8 ISM5_HD_(75) CM_6_(0_5.HD) EA_ASboard_8 ISM5_HD_(75) CM_6_(0_5.HD) EA_ASboard_8 Package dimensions (LxWxH), mm Gross weight, kg Net weight, kg 760x35x x35x x35x x35x x35x x35x x35x x35x x330x x330x x330x x330x x330x x330x x330x x330x x330x x330x x330x x330x

75 Appendix 3. Overall drawings

76 Dimensions of Indoor Switching Modules ISM5_LD_(67), PCD 50 mm Weight: 34 kg ISM5_LD_(55), PCD 0 mm Weight: 36 kg 76

77 ISM5_LD_(80), two lower terminals (continuous busbar), PCD 50 mm Weight: 36 kg ISM5_LD_(90), PCD 80 mm Weight: 36 kg 77

78 ISM5_LD_3, Weight: 3 kg ISM5_LD_6, PCD 33 mm Weight: 55 kg 78

79 ISM5_MD_(50_L), PCD 50 mm, Weight: 33 kg ISM5_MD_(0_L), PCD 0 mm, Weight: 35 kg 79

80 ISM5_Shell_(50_L), PCD 50 mm, Weight: 5 kg ISM5_Shell_(50_L) with CBkit_Shell5_(05) installed*, PCD 50 mm, Weight: 59,5 kg *- busbars shown for reference and are not supplied. 80

81 ISM5_Shell_(0_L), PCD 0 mm, Weight: 5 kg ISM5_Shell_(0_L) with CBkit_Shell5_(05) installed*, PCD 0 mm, Weight: 60,5 kg *- busbars shown for reference and are not supplied. 8

82 ISM5_Shell_(0_H), PCD 0 mm, Weight: 53 kg ISM5_Shell_(0_H) with CBkit_Shell5_(30) installed*, PCD 0 mm, Weight: 6,5 kg *- busbars shown for reference and are not supplied. 8

83 ISM5_Shell_(75_H), PCD 75 mm, Weight: 55 kg ISM5_Shell_(75_H) with CBkit_Shell5_(30) installed*, PCD 75 mm, Weight: 63,5 kg *- busbars shown for reference and are not supplied. 83

84 ISM5_HD_(0), PCD 0 mm, Weight: 70 kg ISM5_HD_(75), PCD 75 mm, Weight: 7 kg 84

85 ISM5_LD_(0_Par), PCD 0 mm Weight: 36 kg ISM5_LD_(0_Par) with CBkit_Ins_3 installed*, PCD 0 mm, Weight: 36,5 kg *- upper busbars shown for reference and are not supplied. 85

86 ISM5_LD_(75_S), PCD 75 mm Weight: 38 kg ISM5_LD_(75_S) with CBkit_Ins_3 installed*, PCD 75 mm, Weight: 38,5 kg *- upper busbars shown for reference and are not supplied. 86

87 ISM5_LD_(), PCD 50 mm Weight: 35 kg ISM5_LD_(), PCD 50 mm Weight: 37 kg 87

88 ISM5_LD_3, Weight: 4 kg ISM5_LD_3 with CBkit_Ins_3 installed*, Weight: 4,5 kg *- upper busbar shown for reference and is not supplied. 88

89 Dimensions of Control Module , CM_6_(Par_Par) Weight: kg 89

90 Dimensions of accessories Dimensions of Position Indicator Rope length L=m Unit_PosInd_3 with connected CBcomp_RelCable_ Dimensions of Manual Generator CBunit_ManGen_, CBunit_ ManGen_ 90

ISM. Vacuum Circuit Breaker 12kV, kA, A 24kV,...16kA,...800A. Technical Manual

ISM. Vacuum Circuit Breaker 12kV, kA, A 24kV,...16kA,...800A. Technical Manual ISM Vacuum Circuit Breaker 12kV, 315kA, 1600A 2kV, 16kA, 800A 35 165 ± 0,5 100 112 50 ± 0,2 30 5 103 279 Technical Manual The present Technical Manual contains information necessary for the installation,

More information

ISM Vacuum Circuit Breaker. 17.5kV, kA, A. Product Guide

ISM Vacuum Circuit Breaker. 17.5kV, kA, A. Product Guide ISM Vacuum Circuit Breaker 12kV 31.5kA 2000A 17.5kV,...31.5kA,...2000A 24kV 16kA 800A Product Guide Low-Duty Vacuum Circuit Breaker (LD ISM) 2 3 4 5 6 7 8 9 10 13 11 14 15 12 16 1 17 1. Vacuum interrupter

More information

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.0 008 Answers for energy. R-HG11-17.tif Siemens HG 11.0 008 Contents Contents Page SION Vacuum Circuit-Breakers Description General Construction

More information

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.02 2011 Answers for energy. R-HG11-172.tif 2 Siemens HG 11.02 2011 Contents SION Vacuum Circuit-Breakers Medium-Voltage Equipment Catalog

More information

Auxiliary Relay (7PJ11) and Trip Relay (7PJ12)

Auxiliary Relay (7PJ11) and Trip Relay (7PJ12) s www.siemens.com/energy Auxiliary Relay (7PJ) and Trip Relay (7PJ2) Better protection and more efficiency for your power system Answers for infrastructure and cities. Auxiliary Relay and Trip Relay Catalogue

More information

Outdoor vacuum breaker for railway applications - FSK II

Outdoor vacuum breaker for railway applications - FSK II Outdoor vacuum breaker for railway applications - FSK II Single or two-pole outdoor vacuum breaker with magnetic actuator 27.5 kv - 250 kv BIL - 1250 A. 2000 A - 25.0 ka - 50/60 Hz 27.5 kv - 200 kv BIL

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report Test report Type VRLTC load tap changer VRLTC 1500A Type test summary report Date: 10 October 2012 Type Test Summary Report Type VRLTC Vacuum/Reactance Load Tap Changer ABB has tested the Type VRLTC, vacuum

More information

3TM Vacuum Contactors

3TM Vacuum Contactors Catalog Extract HG 11.23 Edition 2016 Catalog Extract Medium-Voltage Equipment siemens.com/3tm R-HG11-343.psd 2 Siemens HG 11.23 2016 Contents Medium-Voltage Equipment Catalog Extract HG 11.23 2016 Contents

More information

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A - 3700 A R-MAG The R-MAG is truly the next generation in vacuum circuit breakers, combining industry recognized magnetic

More information

HD4. Gas insulated MV circuit-breakers kv A ka

HD4. Gas insulated MV circuit-breakers kv A ka HD4 Gas insulated MV circuit-breakers 12... 40.5 kv - 630... 3600 A - 16... 50 ka 1 DESCRIPTION Autopuffer breaking technique Electric arc extinction without chopped current No restriking after breaking

More information

Reverse power relay and protection assemblies

Reverse power relay and protection assemblies Reverse power relay and protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE980053) (SE980054) Features Micro-processor based time directionalcurrent relay/protection

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop

More information

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Features: Low maintenance 10,000 mechanical operations (five times ANSI requirements) Simple magnetic actuator Vacuum interruption Definite

More information

SIRIUS 3RU2 Thermal Overload Relays

SIRIUS 3RU2 Thermal Overload Relays Overview 1 2 3 4 6 1 2 NSB0_0207a Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors. The overload relay can be connected directly to

More information

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines Abstract: The development of the magnetically actuated vacuum interrupter

More information

Features. LED Driver. RACT09 9 Watt. TRIAC Dimmable. Single Output RACT09- AC/DC Converter

Features. LED Driver. RACT09 9 Watt. TRIAC Dimmable. Single Output RACT09- AC/DC Converter Features TRIAC Dimmable LED Driver Triac dimmable with leading or trailing edge dimmers Class II with SELV output (no earth required) Extra-large screw terminals and integrated cable clamps for easy installation

More information

EMPAC Metal enclosed capacitor bank for wind applications

EMPAC Metal enclosed capacitor bank for wind applications EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks

More information

VD4 Installation and service instructions kv A ka

VD4 Installation and service instructions kv A ka Medium voltage products VD4 Installation and service instructions 12... 36 kv - 630... 3150 A - 16... 50 ka Index For your safety! 1 I. Introduction 2 II. Programme for environmental protection 2 1. Packing

More information

PSW102 type CT powered protection unit

PSW102 type CT powered protection unit PSW102 type CT powered protection unit Summary PSW102CT self-powered protection device is a 10Kv feeder protection device which has the function of over current, fast breaking protection and grounding

More information

Electronic Ballast EVG 2000-T

Electronic Ballast EVG 2000-T Electronic Ballast EVG 2000-T Operating Manual Table of contents 1 Description 1.1 Advantages of this ballast... 3 1.2 Functional principle... 3 1.3 Energization... 4 1.4 Visualization... 5 1.5 Indications

More information

The vacuum circuit breaker for commercial buildings, industrial plants and utilities

The vacuum circuit breaker for commercial buildings, industrial plants and utilities The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing

More information

Gas Insulated Metal-clad Switchgear, HMGS!

Gas Insulated Metal-clad Switchgear, HMGS! Medium Voltage HMGS-G10 HYUNDAI Medium Voltage Gas Insulated Metal-clad Switchgear, HMGS! SF6 Gas Insulated Metal-clad Switchgear is an integrated assembly of vacuum circuit breaker, 3-position switch,

More information

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC Characteristics time delay relay 2 functions - 0.02 s..300 h - 24..240 V AC - 2 OC Main Range of product Product or component type Electrical connection Discrete output type Contacts type and composition

More information

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MV Air Insulated Switchgear TAP17. Technical Data TGOOD MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)

More information

TGI Vacuum Circuit-Breaker Air isolator Earthing switch

TGI Vacuum Circuit-Breaker Air isolator Earthing switch TGI Vacuum Circuit-Breaker Air isolator Earthing switch PATENT Versatile Visible isolation Simple Removable Index 3 in 1 2 Simple and versatile 4 Operations sequence ON Commissioning 8 Operations sequence

More information

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications Outdoor live tank SF 6 circuit breaker Type OHB for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers

More information

Model Number Structure

Model Number Structure Solid State Relays (Single-phase) G3PB New Single-phase Solid State Relays with Compact Size for Heater Control Slim models with a thickness of only 22.5 mm are also available. Compact design achieved

More information

DISTRIBUTION SOLUTIONS HA Breaker Retrofit. Medium Voltage Service Marketing and Sales

DISTRIBUTION SOLUTIONS HA Breaker Retrofit. Medium Voltage Service Marketing and Sales DISTRIBUTION SOLUTIONS HA Breaker Retrofit Medium Voltage Service Marketing and Sales Table of contents Retrofit concept General description Technical specification Necessary details for standard retrofit

More information

Technical Documentation

Technical Documentation Technical Documentation Product manual Holding brake controller Document: 0198441113316 Edition: V1.00, 03.2006 Important information The drive systems described here are products for general use that

More information

A21M. Introduction: Functional Overview: Key Protection & Control Functions:

A21M. Introduction: Functional Overview: Key Protection & Control Functions: Introduction: ASHIDA has designed economical & reliable Multifunction A21M Protection & Control System. The simple and compact construction of A21 series, A21M relay provides integrated Protection, Control

More information

TECHNICAL MANUAL AND APPLICATION GUIDE. Engineering Your Power

TECHNICAL MANUAL AND APPLICATION GUIDE. Engineering Your Power r e v. 0 3 r e l e a s e d 0 1. 0 5. 2 0 1 1 Engineering Your Power Medium-Voltage Switchgear MILE MP12, MP17 and MP24 Single Busbar Air-Insulated Metal-Clad Switchgear Circuit Breaker mounted on withdrawable

More information

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution

More information

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC Characteristics time delay relay 2 functions - 0.02 s..300 h - 24..240 V AC - 2 OC Complementary Product front plate size Control type Housing material Main Range of product Product or component type Electrical

More information

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers

More information

NXPLUS C Single busbar. Maintenance-free for lifetime

NXPLUS C Single busbar. Maintenance-free for lifetime NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage

More information

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) About company The «Elektroapparat» plant starts its operation in 1922 as a plant manufacturing high-voltage electrical equipment. During the first two

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document. General information Actuator controls AC 01.2 for controlling multi-turn actuators of the SA/SAR type range and part-turn actuators of the SQ/SQR.2 type range. Features and functions Power supply Standard

More information

EU RO Mutual Recognition Technical Requirements

EU RO Mutual Recognition Technical Requirements 1. PRODUCT DESCRIPTION... 1 2. DESIGN EVALUATION... 2 3. PRODUCTION REQUIREMENTS... 6 4. MARKING REQUIREMENTS... 6 5. TYPE APPROVAL CERTIFICATE CONTENT... 7 6. APPROVAL DATE AND REVISION NUMBER... 7 7.

More information

1. Safety practices General Introduction Standards...3

1. Safety practices General Introduction Standards...3 1. Safety practices...2 2. General...3 2.1 Introduction...3 2.2 Standards...3 3. Technical data...3 3.1 Designation...3 3.2 Electrical ratings and dimensions...4 3.3 Fixation...6 3.4 Connecting terminals...6

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h) Mechatronic Analog Timer H3AM Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Refer to Warranty and

More information

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

Prüffeld der Schaltwerke

Prüffeld der Schaltwerke Report No.: 16-043-MS Sheet: 2 Notes 1. The testing station of the Siemens switchgear factory (Prüffeld der Schaltwerke),, Berlin, has been approved by the DAkkS (German accreditation body) for rendering

More information

Vacuum Circuit Breaker VS1

Vacuum Circuit Breaker VS1 Vacuum Circuit Breaker VS1 Product features Conform to GB, IEC, DL and JB standards KEMA type test Level A certificate Ideal contact material and shape, ensuring low current carrying value and stable contact

More information

RVS-AX Instruction Manual

RVS-AX Instruction Manual RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3

More information

Time scale: from 0.05 s to 100 h Multi-function Plug-in for use with 96 series sockets. Relay + socket. Wiring diagram (without control signal)

Time scale: from 0.05 s to 100 h Multi-function Plug-in for use with 96 series sockets. Relay + socket. Wiring diagram (without control signal) 86 Timer modules 86 Timer modules for use in conjunction with relay & socket. 86.00T - Multi-function & multi-voltage timer module 86.30T - Bi-function & multi-voltage timer module Complies with EN 45545-2:2013

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V6-4A00 www.usa.siemens.com/sdv7 Hazardous voltages and stored

More information

ZB0050 / ZB0051 ZB0070 / ZB0071

ZB0050 / ZB0051 ZB0070 / ZB0071 Operating instructions Safety Rope Emergency Stop Switches UK ZB0050 / ZB0051 ZB0070 / ZB0071 7390877 / 02 08/2013 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4 2.2

More information

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12 16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting

More information

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated

More information

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism AMVAC Universal applications: Medium voltage motor starting applications Capacitor switching Retrofit applications to replace

More information

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03 INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR469000 OR25 REV03 I II CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment

More information

Siemens AG Catalog HG11.07 Edition 10/ AE6 Medium-Voltage Equipment. siemens.com/sion

Siemens AG Catalog HG11.07 Edition 10/ AE6 Medium-Voltage Equipment. siemens.com/sion Siemens AG 2018 Catalog HG11.07 Edition 10/ 2018 SION Lateral Vacuum Circuit-B Breaker with Laterrall Operating Mechaniism m 3AE6 Medium-Voltage Equipment siemens.com/sion 2 Catalog HG11.07 10 / 2018 SION

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

BETA Switching Switches and Light Indicators

BETA Switching Switches and Light Indicators Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction

SafeGear TM Motor Control Center Arc resistant metal-clad construction SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor

More information

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work GE Consumer & Industrial Power Protection New SecoGear 12-24kV GE imagination at work General SecoGear metal-clad switchgear is designed and manufactured with advance technology and has been comprehensively

More information

M-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)

M-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A) M-RING 24 SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A) Contents General Description Advanced facilities and process Advanced design philosophy Definition of M-RING 24 Standards Service conditions

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive Vacuum Circuit-Breakers, Type HVX 12 24 kv, of cassette design, cassette with motor drive Operating Instructions No. 531 321, Edition 09/00 Table of Contents 1 General 4 1.1 Operating Conditions 4 2 Design,

More information

Medium voltage vacuum circuit breaker. E-VAC series

Medium voltage vacuum circuit breaker. E-VAC series Medium voltage vacuum circuit breaker E-VAC series Product description E-VAC vacuum circuit breaker Contents Description Product description... Technical data... Dimensions... Wiring diagram... E-VAC series

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

CPG.0 Single busbar gas-insulated cubicles

CPG.0 Single busbar gas-insulated cubicles MV Switchgear Primary Distribution CPG.0 Single busbar gas-insulated cubicles Up to 36 kv CPG System The quality of products designed, manufactured and installed by Ormazabal is underpinned by the implementation

More information

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A DISTRIBUTION SOLUTIONS Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A Continuous protection and reliable operation Proven design and compliance with newest fuses standards Compatibility with other ABB

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Models. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery

Models. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery AC/DC Battery Controller Power Supply TSPC-240UPS Series Compact universal 24 VDC power supply with integrated battery controller module Battery protection for over voltage, deep discharge, short circuit

More information

Contactors. CH1130/02 Series Single pole high-voltage contactor up to 3 kv Catalogue C170.en. Connect - Contact - Control

Contactors. CH1130/02 Series Single pole high-voltage contactor up to 3 kv Catalogue C170.en. Connect - Contact - Control Connect - Contact - Control 3 Contactors CH1130/02 Series Single pole high-voltage contactor up to 3 kv Catalogue C170.en More information at: schaltbau-gmbh.com 42 CH1130/02 Single pole high-voltage contactor

More information

Pantograph disconnector type GW54, up to 550 kv Maximum reliability and minimal maintenance

Pantograph disconnector type GW54, up to 550 kv Maximum reliability and minimal maintenance Pantograph disconnector type GW54, up to 550 kv Maximum reliability and minimal maintenance Table of contents 02 03 04 05 06 07 08 Disconnectors from ABB Maximum reliability and minimal maintenance Technical

More information

1.1 Caution Statements

1.1 Caution Statements USER MANUAL 1.1 Caution Statements Caution Statements cannot cover every potential cause of equipment damage but can highlight common causes of damage. It is the installer's responsibility to read and

More information

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2. Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.12 Product Overview ABB's type-tested ring main unit (RMU) is an SF 6 insulated RMU utilising the latest developments

More information

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls 11kV Compact Switchgear tec - range Minimum to Zero SF6 Insulation Gas. Outec Controls 1 tec xx - 11kV Switchgear Contents 1 tec CB - SF6 Free Switchgear... 3 1.1 Description:... 3 1.2 1.3 Features the

More information

PATENT PENDING. Phone: (877) Operation and Service Manual

PATENT PENDING.   Phone: (877) Operation and Service Manual PATENT PENDING Phone: (877) 544-2291 Operation and Service Manual 2 IMPORTANT NOTICE This document contains information intended to aid in the proper installation, operation, and maintenance of the product

More information

Air-insulated switchgear UniGear type ZS1

Air-insulated switchgear UniGear type ZS1 Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5

More information

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1. DISTRIBUTION SOLUTIONS ZX1.5-R Gas-insulated medium voltage for railway application Safety and reliability 20% footprint saving Easy operation Complete solution ZX1.5-R Gas-insulated medium voltage for

More information

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED) PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Issue 3 2012 SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED) www.energynetworks.org 2012 Energy Networks

More information

QS20.241, QS C1

QS20.241, QS C1 QS2.21, QS2.21C1 QSeries 27. APPLICATION NOTES 27.1. REPETITIVE PULSE LOADING Typically, a load current is not constant. It varies over time. For pulse load compatibility, following rules must be met:

More information

Vacuum Circuit Breaker

Vacuum Circuit Breaker Vacuum Circuit Breaker 12/24kV VECTOR series Vacuum Circuit Breaker VMS series Metal-clad Switchgear Medium Voltage Systems 003 FM 73638 12/24kV VECTOR VCB Features of the VECTOR Vacuum Circuit Breaker:

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment General The switchgear must be suitable for 36 kv rated voltage and specifically conceived for the secondary distribution substations in M.V. with either ring or radial type networks. The switchgear must

More information

Electrical network protection VIP30, VIP35. User s manual 12/2008

Electrical network protection VIP30, VIP35. User s manual 12/2008 Electrical network protection VIP30, VIP35 User s manual 1/008 Safety instructions ANSI symbol. IEC symbol. Safety symbols and messages Read these instructions carefully and look at the equipment to become

More information

HIGH POWER SOLENOID DRIVER 1

HIGH POWER SOLENOID DRIVER 1 Elactis SA Switzerland Phone : Fax : E-mail : Web : +41 22 364 65 85 +41 22 364 65 87 info@elactis.com http://www.elactis.com HIGH POWER SOLENOID DRIVER 1 ADRV1012K 1 This datasheet is a preliminary description.

More information

Subrange SmartWire-DT electronic motor starters. Basic function Reversing starters (complete devices)

Subrange SmartWire-DT electronic motor starters. Basic function Reversing starters (complete devices) DATASHEET - EMS-RO-T-9-SWD-ADP Reversing starter 9A with SmartWire-DT Part no. EMS-RO-T-9-SWD-ADP Catalog No. 172763 Eaton Catalog No. EMS-RO-T-9-SWD-ADP EL-Nummer 4110026 (Norway) Delivery program Product

More information

SINAMICS GM150 IGCT version

SINAMICS GM150 IGCT version /2 Overview /2 Benefits /2 Design /6 Function /8 Selection and ordering data /8 Options Technical data /14 General technical data /15 Control properties /15 Ambient conditions /16 Installation conditions

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. www.usa.siemens.com/sdv7 Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V2-4A00 Answers for infrastructure

More information

N-03 STEERING GEAR CONTROL SYSTEMS

N-03 STEERING GEAR CONTROL SYSTEMS Guideline No.: N-03(201510) N-03 STEERING GEAR CONTROL SYSTEMS Issued date: October 20,2015 China Classification Society Foreword: This Guideline is a part of CCS Rules, which contains technical requirements,

More information

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering ELEC 5205 - High Voltage Engineering 3. Switchgear Types of Power System Switchgear

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

Time scale: from 0.05s to 100h Multi-function Plug-in for use with 90.02, 90.03, and sockets

Time scale: from 0.05s to 100h Multi-function Plug-in for use with 90.02, 90.03, and sockets 86 Series - Timer modules Features 86.00 86.30 Timer modules for use in conjunction with relay & socket. 86.00 - Multi-function & multi-voltage timer module 86.30 - Bi-function & multi-voltage timer module

More information

StarEye. 350 ma version. No control electronics on board

StarEye. 350 ma version. No control electronics on board StarEye 350 ma version No control electronics on board CONTENT 1 PICTURE... 3 1.1 GENERAL... 3 2 DIMENSIONS... 4 3 SAFETY INFORMATION... 5 3.1 SYMBOLS... 5 3.2 PROTECTION FROM ELECTRIC SHOCK... 6 3.3 PROTECTIONS

More information

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker DR-6/DT-6 COMPACT AND EXTENSIBLE RING MAIN UNIT BUILT TO LAST! DR-6/DT-6 Compact and/or extensible SF 6 insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker SAFETY, RELIABILITY,

More information

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear. Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear www.siemens.com/energy Technology s Contents Application Page Benefits 2 Typical uses 2 and 3 Technical

More information

Three-Phase Soft Starters

Three-Phase Soft Starters Submittal Data English Language/IP Units 04/14 Contact Information: Hyper Engineering, Pty. Ltd. 4 / 14 Ralph Black Dr Wollongong Nth, NSW 2500 AUSTRALIA www.hypereng.com sales@hypereng.com (+61) 2 4229

More information

Retrofit solutions Tavrida Electric. tavrida.com

Retrofit solutions Tavrida Electric. tavrida.com Retrofit solutions Tavrida Electric tavrida.com Tavrida Electric has nearly 30 years of experience in Retrofit. Thanks to the unique design of Tavrida Electric circuit breaker even the most complex switchgear

More information