1 1 Cascade-Based Planning Analysis Robert W. Cummings NERC Senior Director of Engineering and Reliability Initiatives

2 WHAT SHOULD BE STUDIED 2

3 3 Tenets of Cascading Analysis Why do it? Learn from History What is a credible combinations of events? What should I think might get involved? Be imaginative Murphy is! Be a Student of the System!! Constantly observe how your system behaves normally and when under stress How does your system interact with the rest of the Interconnection? Practice simulating actual events Good for model validation Helps avoid complacency

4 4 Some Trends in Event Analysis 1. Protection system misoperations (39) 2. Unexpected Gen. Turbine Control Action (33) 3. Transmission equipment failures (18) (most initiating) 4. Voltage sensitivity of gen. aux. power systems (13) 5. Human Error (12) 6. Near-term load forecasting error (6) 7. Wiring errors (incidental) (5) 8. Relay loadability (5) 9. Inter-area oscillations (5) 10. SPS & RAS Misoperations (5)

5 5 Two Top Disturbance Elements 33 Unexpected generator turbine control actions 29 in 8 events 2 units CAUSAL in a system separation event 13 Voltage and/or frequency sensitivity of generation auxiliary power systems (not included above) or plant / Unit Digital Control Systems Problem: THESE BEHAVIORS ARE NOT MODELED OR STUDIED Boiler and Turbine controls are not modeled Understand roll of controls action Power-Load Unbalance (PLU) Typical dynamic analysis only analyzing t = 0 to t = 20 seconds control actions can go well beyond that What about fuel system controls?

6 6 Planning a Cascading Study Be imaginative! You may have to design study methodology to mimic past disturbances to see if the system is still susceptible Think in bus-breaker mode Bus-line model thinking will not get you there Break-to-breaker study needed to analyze protection system misoperations Know your protection system configurations Directional distance, reach, differentials, breaker failure local or remote, Remedial Action Schemes, transfer tripping, etc. Expect the analysis to piece-wise slices of time to mimic the developing overloads or potential voltage collapses

7 7 Planning a Cascading Study (cont.) What parameters do you have to monitor within the study to tell you what would be the next step of the cascade? Look for overloaded lines How overloaded are they? Voltages below 0.9 per unit How low? Results of one run flow into another Reactive flow into both ends of a line? Think about controls!! Inverter controls play a part too! Behavior during protracted faults breaker failure (to operate) emulation SLG faults transition to multi-phase in cycles Longer faults evolve into 3-phase faults

8 8 Planning a Cascading Study (cont.) Protracted faults mean protracted low voltages UVLS schemes? Inverter behavior during low voltages Inverter blocking current injection? Inverter tripping? Know your loads! Know your station load composition residential, commercial, industrial, etc. Helps characterize load behavior under abnormal conditions Loads with high-quality power requirements may leave the system Voltage-sensitive or frequency sensitive loads must be monitored during the study

9 9 Study Practices Cardinal Rule of forensic event analysis Everything happens for a reason!! There is no sympathy in the power system Think like a protection system or plant control system What the heck did it see?? Why did it react the way it did? Take advantage of all available disturbance monitoring data (PRC-002) Leave no questions unanswered Don t be myopic in the scope of your analysis! Examine the Interconnection to ensure there were no wider area impacts Timing is everything! Creating a detailed sequence of events is crucial!

10 10 Study Practices (Continued) Cascading typically starts slow and progresses as multiple things go wrong Know the cascade players Triggering event lightning arrestor failure Causal events Breaker fails to operate protection system failure Contributory events Protection system miscoordination widens impact Coincidental events It was a dark and stormy night Resultant events fault progressed from single-phase to multi-phase

11 11 EXAMPLE 1 NORTHEAST BLACKOUT AUGUST 14, 2003

12 Blackout Signature MW/MVAr 4000 MW kv kv MVAr :10:38 16:10:40 16:10:42 16:10:44 16:10:46 16:10:48 Time - EDT

13 13 Major Path to Cleveland Blocked ONTARIO 4:08:59-4:09:07 PM

14 8 Generation Trips ONTARIO

15 9 Cascade Moves into Michigan 4:10:36 PM

16 Power Transfers Shift 4:10:38.6 PM 10

17 11 Northeast Island Separates from EI North of Lake Superior 4:10:43 4:10:45 PM

18 12 End of the Cascade Area affected by blackout Service maintained in isolated pockets

19 Frequency (Hz) Start of split between East and West MI Detroit, Cleveland separated from W. MI. Cleveland cut off from PA NY separates from PA Cleveland separates from Toledo, islands 1630 MW Detroit generation trips NY separates from NJ NY and New England separate Split complete between East and West NY Ontario splits from West NY Ontario reconnects with West NY Power Flows (MW) 13 5,000 4,000 3,000 2,000 1, ,000-2, Blackout Analysis 16:10:36 16:10:38 16:10: :10: :10:48 16:10:50 16:10:56 16:10: :10:49 16:10: :10:42 New York into Ontario Ontario into Michigan New York into New England PJM into New York -3,000 16:10:30 16:10:40 Time 16:10:50 16:11:00 16:10:30 to 16:11: NY-West Lambton ONT-MI NY-East 57 16:10:30 16:10:40 Time 16:10:50 16:11:00

20 % of Normal Ratings (Amps) Dale-W.Can 138 kv W.Ak 138 kv Bkr Failure Cham-W.Ak 138 kv E.Lima-N.Fin 138 kv CantC Xfmr W.Ak-PV Q kv Babb-W.Ak 138 kv E.Lima-N.Lib 138 kv Clov-Torrey 138 kv Star-S.Cant 345 kv Hanna-Jun 345 kv Hard-Chamb 345 kv Blackout Simulations 3 Months to Build Sammis-Star 345 kv 100 CantC-Tidd 345 kv Star-S.Cant 345 kv Hanna-Jun 345 kv Hard-Chamb 345 kv 0 Outages

21 Some Key Elements of the Cascade Vegetation management Relay loadability Miscoordination of generator controls and system protection Generator underfrequency protection and under / over speed controls not coordinated Pole Slipping UFLS failures Constrained by extreme undervoltage Time delays too long 21

22 22 What to look for in the study Slow cascading not all cascades happen at dynamic speeds Slow, progressive Voltage collapse Increasing overloads of key elements over time Loading above Surge Impedance Limits (SIL) Reactive power entering the line from both ends Excessive bus angles across transmission lines Potential for parts of the system separating by out-of-step conditions If it trips can you reclose it?? Doubtful for angles above 45 degrees

23 Relative Phase Angle 16 Angular Separation Analysis :05:00 15:32:00 15:44:00 15:51:00 16:05:00 16:06:01 16:09:05 16:10:38 Reference: Browns Ferry Normal Angle ~ -25º Time (EDT) Cleveland West MI 23

24 24 16:05:50 to 16:08:52 Western MI Sammis - Star NJ Detroit Muskingum Ohio Central - Galion East Lima Fostoria Central 15 Degrees NY Ontario Cleveland 24

25 18 Detroit out of Synch 16:08:50 to 16:10:50 Western MI NY NJ 40 Degrees NY-PJM Separation Cleveland Separation Cleveland Ontario 25

26 26 EXAMPLE2 FLORIDA SYSTEM DISTURBANCE FEBRUARY 26, 2008

27 27 Event Overview Delayed clearing of 138 kv SLG fault progressed to a 1.7 second 3-Ø fault Loss of 1,350 MW load near fault Loss of 2,500 MW of generation near fault Loss of 2,300 MW more load by UFLS program Loss of 1,800 MW more generation across the Region Oscillatory effects across interconnection

28 30 Key Elements of Cascade Protection system turned off Single Ø fault progressed to three Ø fault 1.7 seconds Nuclear units tripped on undervoltage as designed Eight turbines unexpected trips; auxiliary bus voltage protection rate of frequency change -- burner lean blowout phenomenon Proper UFLS action prevented system separation Inter-area oscillations 1,000 MW swings in TVA 500 kv system 600 MW swings in New England 345 kv system 12 kv swings on Ontario 230 kv system

29 29 Florida UFLS Activation FRCC RC Visibility Event Summary Impact contained within FRCC Majority of load restored within 2 hrs. No major equipment damage reported No thermal O/L 2 Nuclear units (tripped as designed) Generation Trips Actuation of UFLS FRCC RC Footprint Location of 138 kv 3θ fault

30 29 Interconnection-wide Impact Turkey Point (FPL) Calloway / Rush Island TVA Dorsey (MH)

31 31 What to look for in the study Localized voltage collapse Low voltages on generators Motor controllers often drop out for voltages below 0.87 per unit Potential inter-area oscillations Excessive bus angles across transmission lines Potential for parts of the system separating by out-of-step conditions If it trips can you reclose it?? Doubtful for angles above 45 degrees

32 32 EXAMPLE 3 PACIFIC SOUTHWEST DISTURBANCE SEPTEMBER 8, 2011

33 CAISO Freq/ACE MST From RA Tool CISO Freq/ACE MST

34 1-Min. CAISO Freq MST From RA Tool

35 System Separation & SONGS Trip Loss of SDGE Loss of San Onofre Gen. Load From RA Tool

36 Initial FNet FDR Angular Plot AZ-NM-CO California

37 FNET FDR Locations

38 Event A

39 Event A Detail

40 Event B

41 Event C

42 Event D

43 What we learned with FNET The frequency shows four main events A. The initial separation around 22:27:39 (UTC), resulting in a slow frequency dip of about -30 mhz over about 25 seconds B. A frequency ramp beginning around 22:32:10 increasing frequency +30 mhz over about 15 seconds C. A frequency drop around 22:37:55 of over -40 mhz (B-A) over about 12 seconds D. A frequency jump around 22:38:21 of over +150 mhz (C-A) in less than 5 seconds, settling at around +80 mhz (B-A) in about 20 seconds

44 Components of the Outage Over 30 major element operations over the course of 11 minutes Line and transformer trips Generator trips and runback Load shedding Over 50 additional minor operations such as capacitor and reactor switching Over 6 GB of data of different qualities and resolution Operator logs, PI historian, SCADA, PMU, DFR, relay records

45 45 What to look for in the study Think like a phasor measurement unit (PMU) But don t be fooled by phase-jumps at inception of a fault, clearing of a fault, or significant reactive switching Think Multi- dimensionally! Don t fixate on single reading Frequency, voltage, current, time multi-dimensional plots Potential for inter-area oscillations Recognize tripping of various system elements Line trip, Transformer trip, Load trip Excessive bus angles across transmission lines If it trips can you reclose it?? Doubtful for angles above 45 degrees

46 Phase 1 Pre-Disturbance Hot, shoulder season day; some generation and transmission outages High loading on some key facilities: H-NG at 78% of normal rating; CV transformers at 83% 44 minutes before loss of H-NG, IID s RTCA results showed loss of CV-1 transformer would load CV-2 transformer above its relay trip point 15:27:39: APS technician skipped a critical step in isolating the series capacitor bank at North Gila substation; H-NG trips

47 Phase 2 Trip of H-NG 500 kv H-NG 500 kv trips at 15:27:39 15:27:39 15:28:16 APS tells WECC RC line expected to be restored quickly H-NG flow redistributes: 77% to SCE-SDGE (Path 44); remainder to IID, and WALC CV transformers immediately overloaded above relay settings Path 44 at 5,900 amps; 8,000 amp limit on SONGS separation scheme

48 Initiating Event Voltage Divergence Hassayampa North Gila 500 kv Trip Series Capacitor Bypass Switch Arcs Over

49 Hass. N. Gila 500 kv Line Trip South of SONGS Current CCM Unit 1 generator trip Hassyampa N. Gila 500 kv line trip

50 15:28:16 15:32:10 Phase 3 Trip of CV Transformers 15:28:16 CV-2 and CV-1 230/92kV transformers trip on overload relays Severe low voltage in WALC 161 kv system Loading on Path 44 increases to 6,700 amps

51 Coachella Valley Transf. Trip South of SONGS Current Coachella Valley 230/92 kv transformers trip

52 Phase 4 Ramon Transformer Trip 15:32:10 Ramon 230/92kV transformer trips on overload relay 15:32:10 15:35:40 15:32:13 Blythe-Niland 161kV line trips 15:32:15 Niland CV 161kV line trips IID undervoltage load shedding; loss of generation and 92 kv transmission lines Severe low voltage in WALC 161 kv system Loading on Path 44 increases to 7,800 amps; settles at 7,200 amps

53 Ramon Transformer Trip South of SONGS Current Voltage collapse in pocket, followed by load tripping Multiple line, generator and load trips Ramon 230/92 kv transformer trip

54 Voltage in Northern IID 92 kv System Over-Voltage Trip of 92 kv System Capacitors Ramon 230/92 kv Transformer Trip Trip of Over 400 MW in Northern IID 92 kv Load Pocket

55 Blythe 161 kv Voltage Trip of Hassayampa North Gila 500 kv Line El Centro Pilot Knob 161 kv Line Trip Trip of Coachella Valley 230/92 kv Transformers Yucca 161/69 kv Transformers 1 and 2 Trip Ramon 230/92 kv Transformer Trip Trip of Over 400 MW in Northern IID 92 kv Load Pocket

56 Phase 5 Yuma Separates 15:35:40 15:37:55 Yuma AZ Separates from IID and WALC when Gila and Yucca transformers trip Yuma load pocket isolated on single tie to SDG&E Loading on Path 44 increases to 7,400 amps after Gila transformer trip; to 7,800 amps after Yucca transformers and generator trip

57 Yuma Separation South of SONGS Current YCA generating units trip Yucca 161/69 kv transformers trip Pilot Knob 161/92 kv transformers trip Gila 161/69 kv transformers trip

58 15:37:55 Phase 6 High-Speed Cascade El Centro Pilot Knob 161kV line trips; all IID 92 kv system radial from SDG&E via S-Line WALC 161 kv system voltage returns to normal Path 44 exceeds 8,000 amp setting and timer starts

59 Phase 6 High-Speed Cascade South of SONGS Current CLR generating units trip Imperial Valley El Centro 230 kv S line trip SONGS separation El Centro Pilot Knob 161 kv line trip

60 SONGS Separation Frequency Impacts Hz Phase Jump Transient ~ Hz System Zenith (Point C) ~ Hz System Response (Value B) Hz Pre-Event (Value A) :38: :38: :38: :38: :38: :38: :38: :38: :38: Ault (Denver) Mead (Las Vegas) Tesla (Sacramento) Palo Verde Grand Coulee SONGS Recalculated Frequency Devers Recalculated Frequency

61 SONGS separation SONGS Unit 2 GSU trip and transfer of aux load SONGS aux load on startup transformers SONGS generators ring down SONGS Unit 3 GSU trip and transfer of aux load

62 UFLS Operations in the Island

63 Phase 4 Example Two GTs & UVLS CV-Niland UVLS Motor stalling Colmac GT Blythe-Niland

64 Phase 5 Example transformers trip generators trip

65 Phase 6 Example Blythe RAS S line RAS generators A line trip S line RAS generators

66 Devers SVC Output

67 Capacitor Switching capacitor switching candidate signatures location confirmed by comparing voltage

68 Questions? 68

PMUs and Blackout Analysis

PMUs and Blackout Analysis PMUs and Blackout Analysis Robert W. Cummings NERC Director, Reliability Initiatives and System Analysis NASPI Working Group Meeting Technical Session 2 February 21, 2013 Use of PMUs in EA 2 RELIABILITY

More information

Washington, DC Area Low Voltage Disturbance

Washington, DC Area Low Voltage Disturbance Washington, DC Area Low Voltage Disturbance April 7, 2015 Robert W. Cummings Sr. Director of Engineering and Reliability Initiatives NASPI Working Group Meeting October 15, 2015 Overview April 7, 2015-12:39

More information

August 14, 2003 Blackout

August 14, 2003 Blackout August 14, 2003 Blackout Gerry Cauley Director Reliability Performance North American Electric Reliability Council NERC Response First hours Working with reliability coordinators assessing restoration

More information

August 14, 2003 Outage Sequence of Events U.S./Canada Power Outage Task Force September 12, 2003

August 14, 2003 Outage Sequence of Events U.S./Canada Power Outage Task Force September 12, 2003 August 14, 2003 Outage Sequence of Events U.S./Canada Power Outage Task Force September 12, 2003 This is an outline of significant physical and electrical events that occurred in a narrow window of time,

More information

Distributed Energy Resources

Distributed Energy Resources Distributed Energy Resources WECC Data Subcommittee Rich Hydzik, Avista (ERSWG/DER Subgroup Lead) June 29, 2018 Why Are We Concerned About DER? Concern about changing generation fleet Large coal fired

More information

March 18, Subject: Imperial Irrigation District 2014 Annual Progress Report - Rev 1

March 18, Subject: Imperial Irrigation District 2014 Annual Progress Report - Rev 1 Energy Division P.O. Box 937 333 E. Barioni Blvd. Imperial, CA 92251 www.iid.com March 18, 2014 Mr. Tracy Rolstad Chair, WECC Technical Studies Subcommittee Senior Power System Consultant Avista System

More information

SDG&E High Voltage DC WECC Path 46 Rating Increase Comprehensive Progress Report

SDG&E High Voltage DC WECC Path 46 Rating Increase Comprehensive Progress Report SDG&E High Voltage DC WECC Path 46 Rating Increase Comprehensive Progress Report San Diego Gas & Electric, a Sempra Energy Utility SDGE HVDC Phase 1 Project No. 101512 Revision 01 11/29/2018 SDG&E High

More information

Load Modeling for Power System Studies

Load Modeling for Power System Studies Load Modeling for Power System Studies WECC Load Modeling Task Force Dmitry Kosterev Bonneville Power Administration Transmission Planning Timescale of Interest Our primary interest is the fast dynamic

More information

Transient Stability Analysis Tool (TSAT) Update April 11, Hongming Zhang EMS Network Applications Manager

Transient Stability Analysis Tool (TSAT) Update April 11, Hongming Zhang EMS Network Applications Manager Transient Stability Analysis Tool (TSAT) Update April 11, 2016 Hongming Zhang EMS Network Applications Manager Agenda Peak Online TSAT Introduction: Where we are on Wide-wide System Model (WSM) -TSAT online

More information

2015 WDC Disturbance and Protection Standards Overview

2015 WDC Disturbance and Protection Standards Overview NERC Update 2015 WDC Disturbance and Protection Standards Overview Rich Bauer Senior Manager Reliability Risk Management / Event Analysis IEEE PSRC meeting Denver, Co May 12, 2016 2 System Protection and

More information

Reliability Must-Run Analysis th BTA Presentation. Bob Smith Manager Transmission Planning June 6, 2006

Reliability Must-Run Analysis th BTA Presentation. Bob Smith Manager Transmission Planning June 6, 2006 Reliability Must-Run Analysis 2006 2015 4 th BTA Presentation Bob Smith Manager Transmission Planning June 6, 2006 Outline of Presentation 2006 RMR Study Process Description of network and constraint SIL/MLSC

More information

Generator Interconnection System Impact Study For

Generator Interconnection System Impact Study For Generator Interconnection System Impact Study For Prepared for: January 15, 2015 Prepared by: SCE&G Transmission Planning Table of Contents General Discussion... Page 3 I. Generator Interconnection Specifications...

More information

A Case Study on Aggregate Load Modeling in Transient Stability Studies

A Case Study on Aggregate Load Modeling in Transient Stability Studies A Case Study on Aggregate Load Modeling in Transient Stability Studies Presented by: Daniel Feltes Siemens PTI Coauthors: Carlos Grande-Moran, Bernardo Fernandes, James Feltes, Ming Wu and Robert Wells

More information

Ancillary Services & Essential Reliability Services

Ancillary Services & Essential Reliability Services Ancillary Services & Essential Reliability Services EGR 325 April 19, 2018 1 Basic Products & Ancillary Services Energy consumed by load Capacity to ensure reliability Power quality Other services? o (To

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

TransWest Express Project

TransWest Express Project TransWest Express Project Phase One--Feasibility Study Final Study Report November 2006 A subsidiary of Pinnacle West Capital Corporation Executive Summary On October 21, 2005 Arizona Public Service Company

More information

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015 No. Comment Submitted ISO Response Date Q&A Posted 1 Will the ISO consider proposals that are not within the impedance range specified? Yes. However, the benefits estimated and studies performed by the

More information

ATC Report Aug 14, 2003 Event Part 1. Edina Bajrektarević Transmission Operations

ATC Report Aug 14, 2003 Event Part 1. Edina Bajrektarević Transmission Operations ATC Report Aug 14, 2003 Event Part 1 Edina Bajrektarević Transmission Operations ATC Overview 1. ATC owns, plans, maintains and operates transmission assets in portions of Wisconsin, Michigan and Illinois

More information

El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS

El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS El Paso Electric Company El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS 2015 2024 A Review on System Performance Following Extreme Bulk Electric System Events of the

More information

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008 PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral

More information

Wide area monitoring and control activities in Norway and the Nordic power system

Wide area monitoring and control activities in Norway and the Nordic power system Working Group Meeting North American SynchroPhasor Initiative June 8-9, 2010, Vancouver, British Columbia Wide area monitoring and control activities in Norway and the Nordic power system Kjetil Uhlen,

More information

National Research Council

National Research Council National Research Council The Initial Sources of Power February 28, 2013, Washington DC, USA. M. M. Adibi IRD Corporation Potomac, Maryland, USA madibird@aol.com (c) IRD 2013 1 The impact of a blackout

More information

Simulation and Visualization of Power Grid Operations with High Renewable Penetration

Simulation and Visualization of Power Grid Operations with High Renewable Penetration Simulation and Visualization of Power Grid Operations with High Renewable Penetration Thomas J Overbye Fox Family Professor of Elect. & Comp. Eng. University of Illinois at Urbana-Champaign overbye@illinois.edu

More information

Q217 Generator Interconnection Project

Q217 Generator Interconnection Project Q217 Generator Interconnection System Impact Study APS Contract No. 52588 By Arizona Public Service Company Transmission Planning November 25, 2013 Version 2.0 Prepared by Utility System Efficiencies,

More information

Transmission Planning & Engineering P.O. Box MS 3259 Phoenix, Arizona

Transmission Planning & Engineering P.O. Box MS 3259 Phoenix, Arizona Transmission Planning & Engineering P.O. Box 53933 MS 3259 Phoenix, Arizona 85072-3933 March 9, 2016 Mr. Philip Augustin Chair, WECC Technical Studies Subcommittee Mr. Enoch Davies WECC Technical Staff

More information

TOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY

TOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY TOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY January 7, 2002 Prepared by Jorge Chacon (Consultant) Tucson Electric Power Company Ed Beck ii EXECUTIVE SUMMARY

More information

Midway/Monument Area TTC Study

Midway/Monument Area TTC Study Midway/Monument Area TTC Study (includes the following lines: Midway Geesen 115 kv, Geesen Falcon 115 kv, Falcon Fuller 115 kv, Fuller Black Squirrel 115 kv, and Black Squirrel Monument 115 kv) Johnny

More information

Essential Reliability Services Engineering the Changing Grid

Essential Reliability Services Engineering the Changing Grid Essential Reliability Services Engineering the Changing Grid Robert W. Cummings Senior Director Engineering and Reliability Initiatives i-pcgrid March 39, 2016 Change is Coming Characteristics and behavior

More information

Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience

Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience Y. Sun 1, 2,*, W. G. Kuijpers 3, E. C. W. de Jong 1,2, and H. Pustjens 3 1 Electrical Energy System, Eindhoven University

More information

Gateway South Transmission Project

Gateway South Transmission Project Phase 1 Comprehensive Progress Report Volume 1 - Technical Report Report Prepared by PacifiCorp Transmission Planning Department November 21, 2008 WECC1-V4 Phase 1 Comprehensive Progress Report Executive

More information

Western Area Power Administration Sierra Nevada Region

Western Area Power Administration Sierra Nevada Region Western Area Power Administration Sierra Nevada Region 2014 Annual Ten-Year Transmission Plan Assessment Report November 20, 2014 For information or questions regarding this Transmission Assessment Report,

More information

Seabrook Substation Reliability Improvement Project

Seabrook Substation Reliability Improvement Project New England Division Seabrook Substation Reliability Improvement Project 1. Project Summary Description Seabrook Substation is critical to ISO-New England as a Pool Transmission Facility, to grid availability

More information

100 MW Wind Generation Project

100 MW Wind Generation Project A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility

More information

SDG&E Valley-Rainbow Project

SDG&E Valley-Rainbow Project SDG&E Valley-Rainbow Project Presentation to Grid Reliability/Operations Committee Steven Mavis ISO Grid Planning Department May 24, 2000 1 Background SDG&E s 1999 Expansion Plan for 2000-2004 indicated

More information

Inverter-based DER Ride Through and IEEE Standard 1547

Inverter-based DER Ride Through and IEEE Standard 1547 Inverter-based DER Ride Through and IEEE Standard 1547 Andrew Levitt Applied Innovation August 9, 2018 Cumulative Non-wholesale Solar MW More DER deployment in PJM Ride Through Ride Through : generator

More information

DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY

DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY Transmission Department Transmission Planning Duke Energy Progress TABLE OF CONTENTS I. SCOPE 3 II. TRANSMISSION PLANNING OBJECTIVES 3 III. TRANSMISSION

More information

Climate change drivers for a single and smart EU grid

Climate change drivers for a single and smart EU grid Climate change drivers for a single and smart EU grid Smart and Secure Transmission Grids to Realise US and EU Renewable Energy Potentials Keith Bell University of Strathclyde, Scotland Expected growth

More information

Composite Load Model Sensitivity Study

Composite Load Model Sensitivity Study Composite Load Model Sensitivity Study An Analysis of the Sensitivity of WECC Grid Planning Models to Assumptions Regarding the Composition of Loads NERC LMTF Meeting Salt Lake City, UT January 12, 2016

More information

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation Feasibility Study Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection J.E.D. Solid Waste Management Facility Holopaw Substation September 2013 1 of 12 Table of Contents GENERAL... 3 SHORT

More information

DER Impacts on Bulk Grid Dynamic Performance

DER Impacts on Bulk Grid Dynamic Performance DER Impacts on Bulk Grid Dynamic Performance A Retrospective View of a Prescient Thought Exercise Presented at EPRI-PJM Inverter Interconnections Workshop Valley Forge, PA April 11, 2012 Reigh Walling

More information

WESTERN INTERCONNECTION TRANSMISSION TECHNOLGOY FORUM

WESTERN INTERCONNECTION TRANSMISSION TECHNOLGOY FORUM 1 1 The Latest in the MIT Future of Studies Recognizing the growing importance of energy issues and MIT s role as an honest broker, MIT faculty have undertaken a series of in-depth multidisciplinary studies.

More information

Why Japan remains skeptical of restructuring Study of Electricity Market Bidding Characteristics for Modeling Generation Capacity Growth

Why Japan remains skeptical of restructuring Study of Electricity Market Bidding Characteristics for Modeling Generation Capacity Growth Why Japan remains skeptical of restructuring Study of Electricity Market Bidding Characteristics for Modeling Generation Capacity Growth Satoru Ihara Retired (urotas@ieee.org) Tetsuo Sasaki, Toshihisa

More information

BREAKER FAILURE PROTECTION

BREAKER FAILURE PROTECTION 29 th Annual HANDS-ON RELAY SCHOOL March 12-16, 2012 BREAKER FAILURE PROTECTION Brent Carper, PE Protection & Integration Engineer brent.c@relayapplication.com OUTLINE Protection System Failures and Breaker

More information

Essential Reliability Services From PV Plants

Essential Reliability Services From PV Plants Essential Reliability Services From PV Plants Mahesh Morjaria, Ph. D. VP, PV Systems Enabling a world powered by reliable, affordable solar electricity. Utility-Scale PV Plants Support Grid Stability &

More information

Q85 Generation Interconnection

Q85 Generation Interconnection A subsidiary of Pinnacle West Capital Corporation Q85 Generation Interconnection Interconnection Facilities Study AMENDED APS Contract No. 52386 By Arizona Public Service Company Transmission Planning

More information

TRANSMISSION PLANNING CRITERIA

TRANSMISSION PLANNING CRITERIA CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing

More information

Islanding of 24-bus IEEE Reliability Test System

Islanding of 24-bus IEEE Reliability Test System Islanding of 24-bus IEEE Reliability Test System Paul Trodden February 14, 211 List of Figures 1 24-bus IEEE RTS, with line (3,24) tripped and buses 3,24 and line (3,9) uncertain....................................

More information

Reliability Standards Disturbance Monitoring Conference July 30-31, 2013 Tempe, AZ August 6-7, 2013 Atlanta, GA Day 1

Reliability Standards Disturbance Monitoring Conference July 30-31, 2013 Tempe, AZ August 6-7, 2013 Atlanta, GA Day 1 Reliability Standards Disturbance Monitoring Conference July 30-31, 2013 Tempe, AZ August 6-7, 2013 Atlanta, GA Day 1 Antitrust Compliance Guidelines NERC Antitrust Compliance Guidelines It is NERC s policy

More information

The Useful Blackouts

The Useful Blackouts 1 The Useful Blackouts The undisturbed supply of electricity depends on efficient operational strategies. The strategies should be updated concurrently with power system development. The current transition

More information

Project #148. Generation Interconnection System Impact Study Report

Project #148. Generation Interconnection System Impact Study Report Project #148 Generation Interconnection System Impact Study Report June 05, 2012 Electric Transmission Planning Table of Contents Table of Contents... 2 Executive Summary... 3 Energy Resource Interconnection

More information

Western Area Power Administration Sierra Nevada Region

Western Area Power Administration Sierra Nevada Region Western Area Power Administration Sierra Nevada Region 2013 Annual Ten-Year Transmission Plan Assessment Report December 1, 2013 For information or questions regarding this Transmission Assessment Report,

More information

INTERCONNECTED POWER SYSTEMS POWER GRIDS. Chapter 8

INTERCONNECTED POWER SYSTEMS POWER GRIDS. Chapter 8 INTERCONNECTED POWER SYSTEMS POWER GRIDS Chapter 8 POWER GRID ADVANTAGES Large Electrical Inertia Maximizes system stability, reliability and security Maintains frequency, voltage and load flows Offers

More information

SEL Microgrid Lessons Learned

SEL Microgrid Lessons Learned SEL Microgrid Lessons Learned Will Edwards (SEL Engineering Services Division) Copyright SEL 2016 Essential Keys to Successful Microgrid Projects? Comprehensive HIL testing Subcycle fast controls Adaptive

More information

NERC Load Modeling Activities. Ryan D. Quint, PhD, PE Senior Engineer, System Analysis, NERC MRO Fall Reliability Conference November 2016

NERC Load Modeling Activities. Ryan D. Quint, PhD, PE Senior Engineer, System Analysis, NERC MRO Fall Reliability Conference November 2016 NERC Load Modeling Activities Ryan D. Quint, PhD, PE Senior Engineer, System Analysis, NERC MRO Fall Reliability Conference November 2016 Introduction Kickoff January 2016 LMTF webpage Chair: Dmitry Kosterev,

More information

Steady-State Power System Security Analysis with PowerWorld Simulator

Steady-State Power System Security Analysis with PowerWorld Simulator Steady-State Power System Security Analysis with PowerWorld Simulator S3: Techniques for Conditioning Hard-to-Solve Cases 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com

More information

Interconnection Feasibility Study Report GIP-226-FEAS-R3

Interconnection Feasibility Study Report GIP-226-FEAS-R3 Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power

More information

North Oregon Coast Area Study. Adam Lint

North Oregon Coast Area Study. Adam Lint North Oregon Coast Area Study Adam Lint PAGE 2 North Oregon Coast System Overview - Clatsop Study Covers: Transmission Switching Stations (Clatsop District): Astoria Lewis and Clark 115 kv Distribution

More information

2019 & 2023 Final LCR Study Results San Diego-Imperial Valley non-bulk sub-areas

2019 & 2023 Final LCR Study Results San Diego-Imperial Valley non-bulk sub-areas 2019 & 2023 Final LCR Study Results San Diego-Imperial Valley non-bulk sub-areas Luba Kravchuk Senior Regional Transmission Engineer Frank Chen - Regional Transmission Engineer Lead Stakeholder Call May

More information

APPENDIX F: Project Need and Description

APPENDIX F: Project Need and Description APPENDIX F: Project Need and Description California ISO/MID F-1 Intentionally left blank California ISO/MID F-2 Name Brief Description Type Lugo Victorville 500 kv Upgrade (SCE portion) The project was

More information

Q87 Generation Interconnection

Q87 Generation Interconnection A subsidiary of Pinnacle West Capital Corporation Version 1.0 Q87 Generation Interconnection Interconnection Facilities Study APS Contract No. 52365 By Arizona Public Service Company Transmission Planning

More information

Interconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado

Interconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Executive Summary Interconnection Feasibility Study Report Request # GI-2016-6 Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Public Service Company of Colorado Transmission

More information

Unit Protection System for Pumped-Storage Power Stations

Unit Protection System for Pumped-Storage Power Stations Unit Protection System for Pumped-Storage Power Stations 1. Introduction In many power systems, pumped-storage power stations are used in addition to run-of-river power stations. These power stations serve

More information

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Interconnection Feasibility Study Report GIP-222-FEAS-R3 Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.

More information

Interconnection System Impact Study Report Request # GI

Interconnection System Impact Study Report Request # GI Executive Summary Interconnection System Impact Study Report Request # GI-2008-23 34 MW Solar Generation Ranch at Hartsel, Colorado Public Service Company of Colorado Transmission Planning August 19, 2010

More information

Facilities Study for Alberta to US Available Transfer Capability

Facilities Study for Alberta to US Available Transfer Capability Facilities Study for Alberta to US Available Transfer Capability Report No: NPP2002-05 June 3, 2002 System Planning & Grid Operations, Transmission Line of Business Engineering Services Executive Summary

More information

Implementing a Microgrid Using Standard Utility Control Equipment

Implementing a Microgrid Using Standard Utility Control Equipment Implementing a Microgrid Using Standard Utility Control Equipment Tom Fenimore Duke Energy Andy Gould and Larry Wright Schweitzer Engineering Laboratories, Inc. Copyright Duke Energy and SEL 2016 Overview

More information

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date

More information

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive

More information

Valley - Rainbow Interconnection Project Feasibility Study Report

Valley - Rainbow Interconnection Project Feasibility Study Report Attachment A Valley - Rainbow Interconnection Project Feasibility Study Report A Joint Study Effort of San Diego Gas & Electric (SDG&E) and Southern California Edison (SCE) in Cooperation with the California

More information

MULTIPLE LINE OUTAGES IN THE MOUNT ENGLAND TARONG AREA IN QUEENSLAND, 13 FEBRUARY 2017

MULTIPLE LINE OUTAGES IN THE MOUNT ENGLAND TARONG AREA IN QUEENSLAND, 13 FEBRUARY 2017 MULTIPLE LINE OUTAGES IN THE MOUNT ENGLAND TARONG AREA IN QUEENSLAND, 13 FEBRUARY 2017 REVIEWABLE OPERATING INCIDENT REPORT UNDER THE NATIONAL ELECTRICITY RULES Published: 3 August 2017 INCIDENT CLASSIFICATIONS

More information

Advanced Protective Relay Training

Advanced Protective Relay Training Advanced Protective Relay Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq A properly designed protection

More information

TransWest Express AC and DC Project Comprehensive Progress Report (CPR) 3,000 MW DC and 1,500 MW AC WECC Phase 1 Analysis

TransWest Express AC and DC Project Comprehensive Progress Report (CPR) 3,000 MW DC and 1,500 MW AC WECC Phase 1 Analysis TransWest Express AC and DC Project Comprehensive Progress Report (CPR) 3,000 MW DC and 1,500 MW AC WECC Phase 1 Analysis July 25, 2018 Table of Contents 1. Introduction... 5 1.1. Project Description and

More information

ABB WAMS Capabilities

ABB WAMS Capabilities Steven A. Kunsman Asst VP Global Product Management Ernst Scholtz, PhD Principal Scientist, Corp Research ABB WAMS Capabilities Acknowledgement: A. Leirbukt, R. Nuqui, M. Larsson, P. Korba ABB Group -1-

More information

An Introduction to Completing a NERC PRC Study

An Introduction to Completing a NERC PRC Study An Introduction to Completing a NERC PRC-019-2 Study For Synchronous and Distributed Generation Sources PRESENTED BY: MATTHEW MANLEY TEXAS A&M PROTECTIVE RELAYING CONFERENCE MARCH 26-29, 2018 Presentation

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

Generation Interconnection Impact Study Results for Eurus Energy America Corporation s Eurus Combine Hills I, LLC Power Project.

Generation Interconnection Impact Study Results for Eurus Energy America Corporation s Eurus Combine Hills I, LLC Power Project. Generation Interconnection Impact Study Results for Eurus Energy America Corporation s Eurus Combine Hills I, LLC Power Project April 23, 2003 Introduction Eurus originally requested an interconnection

More information

SPS Planning Criteria and Study Methodology

SPS Planning Criteria and Study Methodology SPS Planning Criteria and Study Methodology SPS subscribes to the Southwest Power Pool ("SPP") Reliability Criteria, which incorporates compliance with the appropriate North American Electric Reliability

More information

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,

More information

Updates and Modifications to Report

Updates and Modifications to Report QUARTERLY COMPLIANCE REPORT (OCTOBER 2016) OF SOUTHERN CALIFORNIA EDISON COMPANY (U 338-E) REGARDING STATUS OF TRANSMISSION PROJECTS AND GENERATION INTERCONNECTION PROJECTS Pursuant to Commission Decision

More information

Generating Unit Model Validation Policy

Generating Unit Model Validation Policy Generating Unit Model Validation Policy approved by WECC BOT WECC Generator Testing Task Force History August 10, 1996 WSCC Outage 4600 Observed COI Power (Dittmer Control Center) Real event 4400 4200

More information

Western Electricity Coordinating Council Modeling and Validation Work Group

Western Electricity Coordinating Council Modeling and Validation Work Group Western Electricity Coordinating Council Modeling and Validation Work Group Renewable Energy Modeling Task Force Development of Planning Models dl for Solar PV Systems November 18, 2009 Phoenix, AZ Contact:

More information

An Industry Perspective On Emerging Electricity Delivery Technologies

An Industry Perspective On Emerging Electricity Delivery Technologies GE Global Research An Industry Perspective On Emerging Electricity Delivery Technologies Juan de Bedout GE: A Broad Energy Footprint Sources Conversion Hydro Delivery Consumption ($B) Oil & Gas Users T&D

More information

SPIDER Modeling Sub-Group DER Modeling, CAISO Experience

SPIDER Modeling Sub-Group DER Modeling, CAISO Experience SPIDER Modeling Sub-Group DER Modeling, CAISO Experience Irina Green, Modeling Sub-Group Chair Regional Transmission Senior Advisor, California ISO NERC SPIDER Work Group Meeting, January 2019 Presentation

More information

Transportation Electrification

Transportation Electrification Transportation Electrification Bulk Power System Reliability Aspects of Electric Vehicle Charging Ryan Quint, Advanced Analytics and Modeling, NERC 2018 i-pcgrid Conference March 2018 Trends and Perspectives

More information

Battery Maintenance Solutions for Critical Facilities

Battery Maintenance Solutions for Critical Facilities Battery Maintenance Solutions for Critical Facilities Chapter Two: Meeting Regulatory Requirements and Observing Best Practices Click a section below In chapter one of Emerson Network Power s ebook entitled

More information

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection B. Bagen, D. Jacobson, G. Lane and H. M. Turanli Manitoba

More information

Stability Study for the Mt. Olive Hartburg 500 kv Line

Stability Study for the Mt. Olive Hartburg 500 kv Line Stability Study for the Mt. Olive Hartburg 500 kv Line Peng Yu Sharma Kolluri Transmission & Distribution Planning Group Energy Delivery Organization Entergy Sevices Inc April, 2011 New Orleans, LA 1.

More information

Managing California s Electrical Supply System after the shut down of San Onofre Nuclear Generating Station

Managing California s Electrical Supply System after the shut down of San Onofre Nuclear Generating Station Managing California s Electrical Supply System after the shut down of San Onofre Nuclear Generating Station East Asian Alternative Energy Futures Workshop By the Nonproliferation Policy Education Center

More information

Session 10 NERC Interconnection Requirements

Session 10 NERC Interconnection Requirements GE Energy Session 10 NERC Interconnection Requirements UVIG Short Course 2014 Portland, Oregon Jason MacDowell NERC Standards Recently Adopted NERC GVSDT* standards MOD (Model Validation): MOD-025: Verification

More information

Southern California Edison s Circuit of the Future

Southern California Edison s Circuit of the Future Southern California Edison s Circuit of the Future Charlie Vartanian SCE Distributed Energy Resources (DER) 3 rd Microgrid Symposium April 6, 2007 SCE Profile 50,000 Mile 2 Service Territory 120 years

More information

ECEN 667 Power System Stability Lecture 19: Load Models

ECEN 667 Power System Stability Lecture 19: Load Models ECEN 667 Power System Stability Lecture 19: Load Models Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements Read Chapter 7 Homework 6 is

More information

TEPCO's experiences of automatic voltage controllers and SIPS as measures to prevent massive power outages

TEPCO's experiences of automatic voltage controllers and SIPS as measures to prevent massive power outages TEPCO's experiences of automatic voltage controllers and SIPS as measures to prevent massive power outages Shinichi Imai, P.E. imai.shinichi@tepco.co.jp Teruo Ohno ohno.teruo@tepco.co.jp The Tokyo Electric

More information

Q51 Generation Interconnection

Q51 Generation Interconnection Q51 Generation Facilities Study Results APS Contract No. 52395 By Arizona Public Service Company Transmission Planning September 4, 2013 [Version 1.0] Q51 FACILITIES STUDY TABLE OF CONTENTS Contents 1.

More information

BC HYDRO REAL TIME OPERATIONS OPERATIONS SUPPORT SYSTEM OPERATING ORDER 7T-13

BC HYDRO REAL TIME OPERATIONS OPERATIONS SUPPORT SYSTEM OPERATING ORDER 7T-13 BC HYDRO REAL TIME OPERATIONS OPERATIONS SUPPORT SYSTEM OPERATING ORDER 7T-13 G.M. SHRUM / PEACE CANYON 500 kv SYSTEM Supersedes OO 7T-13 dated 07 November 2016 Effective Date: 06 February 2017 Review

More information

Texas A&M Microgrid and Electrical System Study. Cushing Memorial Library & Archives

Texas A&M Microgrid and Electrical System Study. Cushing Memorial Library & Archives Texas A&M Microgrid and Electrical System Study Cushing Memorial Library & Archives Introduction of Texas A&M Microgrid Study Purpose Why are we studying the TAMU electrical system? Process How do we want

More information

Project #94. Generation Interconnection System Impact Study Report Revision

Project #94. Generation Interconnection System Impact Study Report Revision Project #94 Generation Interconnection System Impact Study Report Revision October 2, 2009 Electric Transmission Planning Table of Contents Table of Contents...2 Executive Summary...3 Energy Resource Interconnection

More information

Power Systems Fundamentals

Power Systems Fundamentals Power Systems Fundamentals Yachi Lin Senior Manager, Transmission Planning New York Independent System Operator Market Overview Course September 20, 2017 Rensselaer, NY 2017 New York Independent System

More information

2016 SDG&E Grid Assessment Results

2016 SDG&E Grid Assessment Results 2016 SDG&E Grid Assessment Results CAISO Stakeholder Meeting September 22, 2016 Matthew Belden Engineer II San Diego Gas & Electric Email: MBelden@semprautilities.com 2016 Study Windows One to Five-Year

More information

POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS

POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS OVERVIEW Interconnected systems Generator scheduling/dispatching Load-generation balancing Area Control Error (ACE) Load

More information