TEPCO's experiences of automatic voltage controllers and SIPS as measures to prevent massive power outages

Size: px
Start display at page:

Download "TEPCO's experiences of automatic voltage controllers and SIPS as measures to prevent massive power outages"

Transcription

1 TEPCO's experiences of automatic voltage controllers and SIPS as measures to prevent massive power outages Shinichi Imai, P.E. Teruo Ohno The Tokyo Electric Power Company, Inc. 1

2 The Tokyo Electric Power Company, Inc Wholesale: J-POWER (EPDC) The Japan Atomic Power Company, etc. Chugoku EPCO Okinawa EPCO Hokuriku EPCO Chubu EPCO Hokkaido EPCO Kansai EPCO Shikoku EPCO Kyushu EPCO Tohoku EPCO Tokyo EPCO North Latitude East Longitude Corporate Outline as of March 31, 2006 Date of Establishment: May 1, 1951 No. of Shareholders: 801,025 Electricity Sales: 4,630 billion (Approx. US$38.6 bil.) No. of employees: 38,235 No. of Customers: 27,780 thousand 75.3 GW Generations 14.1GW; Hydro 10.3GW; Oil Fired 3.2GW; Coal Fired 27.7GW; Gas Fired 18.2GW; Nuclear 1,572 Transmission Substations 28,693 circuit kilometers of transmission lines million electric customer accounts. Peak System Load 64.3 GW, 280 GWh 2

3 Contents Background; TEPCO s SIPS Observations on recent blackouts and related controllers & schemes in TEPCO August 14, 2003 Northeastern U.S. blackout Automatic Voltage Controllers and UVLS in TEPCO November 4, 2006 European blackout Adaptive load mitigation schemes & UFLS in TEPCO TEPCO s SIPS against short term instability and actual operational experiences Islanding protection system with P&Q balancing control 1999 and 2006 Tokyo power outages Summary 3

4 Background TEPCO s System Integrity Protection Schemes 4

5 TEPCO s SIPS Automatic actions by SIPS Overloading Voltage Instability Frequency Drop Transient Instability System Islanding Bus-coupler switching Tripping of pumped-hydros Generation runback/pickup Load shedding High side voltage control; PSVR Shunt switching; VQC Load shedding; UVLS Tripping of pumped-hydros BTB controls Load shedding; UFLS Fast generation rejection Shunt switching Load shedding 5

6 Features of TEPCO s SIPS Flat and centralized architecture inside substations or covering coherent subsystems Response based actions using on-line information rather than pre-determined actions like traditional RAS 2 out of 3 or 3 out of 4 voting redundancy ensuring security and dependability Custom designed microprocessor based relay and controller without using SCADA based information rather than utilizing industrial purpose Programmable Logic Controllers Based on co-development project with Japanese relay manufactures 6

7 Observations on recent blackouts and related controllers & schemes in TEPCO 7

8 Observations on 2003 US Blackout The loss of the Eastlake 5 unit did not put the grid into an unreliable state. However, the loss of the unit required the utility to import additional power to make up for the loss of the unit s output (612 MW), made voltage management in northern Ohio more challenging, and gave FE operators less flexibility in operating their system. (Final Report by US-Canada TF) After the loss of Sammis-Star 345kV line (Event 8), the voltage began a severe decline, which means n-8 contingencies caused voltage instability. (ECAR report) Installing shunt capacitors to transmission level can avoid tripping of critical generator 8

9 Coordination of voltage schedule and automatic voltage controllers in TEPCO PSVR AVR AVR AVR AVR PSVR PSVR PSVR 550kV Summer Peak 535kV Summer Peak Switching 545kV Normal 500kV power grid Shunt Shunt 525kV Normal Tap changing Switching Shunt Shunt VQC Transmission voltage schedule maintained High & Flat by reactive supplies from Gens and MSCs at S/Ss 50% at Gens and 20% of MSCs reserved in peak demand High side voltage control (PSVR) at reinforces reactive supply capabilities of Gens Fast switched shunts with numerical controllers can be regarded as dynamic resources Power system performance can be ensured against unexpected contingencies by a response-based control Automatic controllers effective to relieve operator s burden during emergency to stop or limit cascading 9

10 UVLS as Last Resort Installed just after 1987 Tokyo Blackout: Longest operation history of the world Microprocessor-based relaying Voltage collapse is detected: by central units located in the 500kV network, because 275kV or lower voltage are regulated by tap changing based on 3 out of 4 decision making logic to avoid unwanted operation Central units detect: Voltage Drop (Under Voltage) Rate of Voltage drop (dv/dt) CU 275kV,154kV radial network 500kV Main Grid Communication; Measured 500kV voltages CU CU Communication; Voltage collapse detection result RTU RTU CU Sub-Station 275,154/66 Sub-Station 275,154/66 (CU: Central Unit) 10

11 Observations on 2006 European Blackout Overloading; The overloading mitigation action led to result which was contrary to what operators expected Possible solution for overloading; Automatic mitigation to relieve operator s burden during emergency and to avoid cascading Actions would be adaptive in step by step manner with priorities until the overloading would be relieved. Frequency decay in western Europe Missing import from the East of 8940MW resulted total shedding of 17000MW of loads and 1600MW of pumps Coordination of underfrequency shedding/tripping schemes among TSOs may be reviewed to reduce the customer interruptions as much possible. 11

12 TEPCO s OLR (Overload Relay) Automatic load mitigation scheme When transmission lines or transformers are overloaded Generation Stations Rapid Output Control Selective Generator Shedding OLR Send out control signal Substations Load Shedding Generation controls with faster time delays executed prior to load shedding with slower time delays Automatically Relieve Overload in Network Facilities Prevent Unnecessary Trippings and Outages 12

13 TEPCO s UFLS with various time delays Increase timer settings for each frequency level. Settings Time Delay Shed loads s 4% (58.2) 1.0s 4% Hz 2.0s 4% 3.0s 4% 40% (Level2) 9.0s 4% 48.0 (57.6) Hz (Level3) 0.2s 8% 0.5s 8% 1.0s 4% 2.0s 4% 6.0s 4% 40% Shed load step by step. 13

14 TEPCO s SIPS against short term instability and actual operational experiences 14

15 Power system supplying to central Tokyo area SAIDI for Central Tokyo Area is less than one minute Radial operated to avoid high fault current and can be switched to adjacent system from different 500kV substations. Neither series reactors nor FCLs. Easy to know contingency flows, no loop flow problems and no cascading outages. No need for on-line contingency processor. Loss of parallel circuits on single tower can cause power outage in downstream system, which can be restored within 30 to 60 minutes by manually switched to adjacent system in each voltage level of 275, 154 and 66kV. Some amounts of generators connected to 154kV power systems in Tokyo bay area. Some systems including power stations are intentionally islanded with vital area by SIPS(UPSS). Training for operators is critical for fast system restoration. 15

16 TEPCO s bulk power grid 500kV 500kV 275kV 500kV 500kV; Meshed configuration and meshed operation 275kV and below; Meshed configuration and Radial operation Metropolitan Area including Tokyo 16

17 Bulk power system configuration 275kV OH Double Circuit Tower Caps; 3 to 4 GW in central Tokyo area 500kV Bulk Power Backbone Central Tokyo Area 275kV UG Triple Circuit Lines Caps; 1 to 2 GW 17

18 Bulk power system configuration in central Tokyo area Normally Opened 18

19 (NOTE) CU RTU Conceptual Diagram of UPSS 500kV & 275kV Overhead Transmission Line 275kV Under-ground Cable Line 154kV Under-ground Cable Line 66kV Under-ground Cable Line Central Unit Detects system separation. Calculates the balance of P and Q. Sends commands to RTUs. Remote Terminal Unit Measures P and Q. Trips feeders based on the command from CU. Opens or closes shunts and cables based on the command from CU. 500kV Power Grid 500kV 275kV Loss of mains Grid Network Radial System Metropolitan Area RTU UVR, UFR, f D ps CU C ss A ss B ss ShR 275kV L 154kV Load Shedding RTU ShR switching Intentional Islanding UVR, UFR, f L L L L L L Generators Sh.R Load UVR, UFR, f Load Shedding RTU Load Load Shedding RTU UVR, UFR, f 19

20 UPSS Controls both P and Q balance of Islanded System P Balance To Maintain the Frequency of the Islanded System. Shed Proper Amount of Load. Q Balance To Maintain Proper System Voltage. Switch on and off shunt capacitors and reactors. Switch off Cables if shunt control is not enough. UPSS watches the system condition every 2 seconds and determines how to control if the system becomes islanded. 20

21 Actual Operation of UPSS on August 14, 2006 Outline of the Outage Date: August 14, 2006 Interrupted Power: 2,160MW (1.39 million households are affected.) Area: A portion of Tokyo metropolitan area and neighboring area Duration: 0-59min Cause: One of 275kV major routes is Lost. Islanded System Scale: 620MW (310MW ACC Generator x 2) No.1 Line No.2 Line No.1 line No.2 line Faults Faults Faults 21

22 A Crane Vessel Crashed into Transmission Lines. No.1 Line No.2 Line Upper Pha ses Middle Phases Lower Phases 16.2m (53feet) Distance between lower phases and surface of the river Conductors of lines were severely damaged 22

23 Outline of UPSS Operation Result UPSS controlled PQ balance to maintain the islanded system Shed Load 66kV Bus Main Grid 275kV Bus 154kV Bus Shed Load: 666.5MW, MVar Switch on Shunt Capacitors: 80MVar Switch on Shunt Reactor: 70MVar Trip Cable including Tr: 163MVar Outage Area: 839MW 275kV Cable 154kV Bus Shed Load Shed Load Shed Load Shed Load No.1 Cable Off Q1: 146MVar Q2: 311MVar P: 620MW 154kV Bus 2 ACC Units SC On 66kV Bus 275kV Bus Main Grid P: 1,440MW Q: -40MVar Double circuit lines triped Shed Load ShR On P: 668MW Q: -345MVar 154kV Bus 66kV Bus Shed Load 66kV Bus 154kV Bus ShR On 23

24 UPSS Detected System Separation in 0.4 Second by Exceeding Phase Angle Difference. Frequency[Hz] Frequence[Hz] Main Grid Frequency System Separation Phase Angle Difference 0.4Sec :37:52.0 7:37:52.5 7:37:53.0 7:37:53.5 7:37:54.0 Time Setting (110 ) Islanded System Frequency Phase Angle Difference Phase Angle Difference 24

25 The Frequency and Voltage of the islanded system recovered in a few seconds Frequency[Hz] Nominal Frequency(50Hz) Islanded System Frequency 48.4 System Separation 7:37:50 7:37:52 7:37:54 7:37:56 7:37:58 7:38:00 7:38:02 Time Voltage[PU] Voltage of BUS A Voltage of BUS B Nominal Voltage(1PU) 0.7 Fault 0.6 7:37:50 7:37:52 7:37:54 7:37:56 7:37:58 7:38:00 7:38:02 Time 25

26 Air Plane Crash Another UPSS Operation history on November 22, GW Lost Hz Hz System Separation Synchronized to main grid Outage Area 498 Main grid Islanded system Hz 13 minutes 13:40 13:42 13:44 13:46 13:48 13:50 13:52 13:54 13:56 Islanded Area The Most Important Area 400MW 26

27 Islanded System Automatic Synchronizer Now: We rely on manual operation for system reconnection. Near Future: System reconnection will be done automatically. Main Grid Synchronizing Point 275kV 275kV Islanded Area fm, θ m Open Close fi, θi Power Plants 154kV 154kV Loads Substations 66kV Islanding System Automatic Synchronizer UPSS (Urban Power System Stabilizer) UPSS activate Detect the system islanding Command to close disconnectors Command to reconnect the islanded area and Main grid Check the synchronizing condithion < 0.3Hz is decreasing Close circuit breakers at the timing of fm, θ is m nearly 0. ISAS is now under development and will commence operation in July,

28 Challenges for future Retaining and keeping expertise especially for system design and testing Accelerated obsolescence of microprocessor based technology and spare parts problem Utilization of standardized technologies, products and communication protocols Sophisticated automated system restoration Coordinated setting and tuning among voltage controllers and SIPS by conducting many numerical calculations by more efficient manner Utilization of fast, reliable and high accurate data and information collected from whole of TEPCO s power system with synchronization. 28

29 Questions or Comments 29

30 VQC (Voltage Q Controller) 500kV Bus Detect Voltage Basic concept of VQ Control 275kV Bus voltage 275kV Bus Tap change SC, ShR switch VQC Down Tr tap SC on ShR off DEAD BAND SC off ShR on Raise Tr tap VQ Controller automatically controls Tr tap and Shunts according to Bus Voltages 500kV Bus voltage 30

31 Relaying Algorithm for Rate of Change of Frequency Detect high-speed rate of frequency decline. ROCOF settings Shed loads s 8% (58.8) Hz 1.0s 16% 48.0 (57.6) Hz 0.5s 24% 0.4s 32% For fast load shedding in case of large L-G imbalance. Measures Tc instead of df/dt. 31

32 Effect of ROCOF and Level+Timer Time Frequency characteristic Lowest tolerant frequency (in TEPCO s policy) Lowest frequency is raised (improved). Accommodate to TEPCO s policy in case of severe L-G imbalance such as 40%. 32

33 How to Detect System Separation? Phase Angle Difference between Islanded System and Main System Phase Angle Difference >110 Voltage Sag of Islanded System Voltage of Islanding system < 0.6pu (Sagged) Voltage of Main grid > 0.94pu (Normal) & >1 & Activate UPSS Distance Relay (Avoid Unnecessary UPSS operation during faults.) Note: Not Just Checking Status of the specified CBs. Whatever the system configuration is, UPSS must be able to detect system separation properly. 33

34 Measurement of phase angle difference Synchronized Sampling Master unit Slave unit Calculation of Phase Angle Difference Va Vb Va(m-3)= VaSin( ) Vb(m-3)= VbSin( -90 ) T Sampling Interval Tm Timing Flag Sampling Interval Synchronized 90 T Timing Flag Ts Va(m)= VaSin( + ) Vb(m)= VbSin( ) T Sampling = Ts - Tm 0 (Adjust Sampling Timing) 2 Assume delay times of both Upstream and Downstream are the same. -1 Va(m)Vb(m) + Va(m-3)Vb(m-3) =Cos ( ) Va Vb x x VaSin( + ) VbSin( ) + VaSin( ) x VbSin( -90 ) =VaSin( + ) VbSin( ) + VaCos( + ) x VbCos( ) =VaVbCos( + - ) =VaVbCos( ) Note: We don t rely on GPS for vital protection systems. 34

35 Power Station 66 kv 66 kv L L Substation Simplified Power System Model for Active & Reactive Power Balance Calculation L SC L Substation 154kV L L L Substation 154kV L Substation β1 Q1 L 275kV ShR L α 275kV X β2 Q2 P Failure 275kV Main Grid P: Excess Active Power which was received from the main grid. The same amount of load must be shed to maintain the frequency. Q1, Q2: Reactive Power which was passing the central transformer of the islanded system must be maintained to keep voltage proper. α : Detection point of receiving Active Power which is used for Load shedding Calculation. β : Detection points of passing Reactive Power which is used for Voltage Control Calculation. 35

TEPCO's operational technologies to prevent cascading outage

TEPCO's operational technologies to prevent cascading outage 1 CIGRE TNC Technical Seminar Future Renewable Energy and Smart Grid Technologies TEPCO's operational technologies to prevent cascading outage Shinichi Imai, P.E. THE Power Grid Solution, Inc. June 20,

More information

Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER

Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER 1 Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER Lisa Dangelmaier Hawaii Electric Light lisa.dangelmaier@hawaiielectriclight.com Hawai'i Electric Light System Overview

More information

The Evolution of System Protection Schemes for the Sarawak Power System By Victor Wong Sarawak Energy Berhad Presented at PQSynergy 2012, Sarawak

The Evolution of System Protection Schemes for the Sarawak Power System By Victor Wong Sarawak Energy Berhad Presented at PQSynergy 2012, Sarawak The Evolution of System Protection Schemes for the Sarawak Power System By Victor Wong Sarawak Energy Berhad Presented at PQSynergy 2012, Sarawak Evolution of System Protection Scheme UFLS- Under Frequency

More information

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing

More information

Generator Interconnection System Impact Study For

Generator Interconnection System Impact Study For Generator Interconnection System Impact Study For Prepared for: January 15, 2015 Prepared by: SCE&G Transmission Planning Table of Contents General Discussion... Page 3 I. Generator Interconnection Specifications...

More information

Accidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies

Accidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies CIGRÉ-EPRI Grid of the Future Symposium 21, rue d Artois, F-75008 PARIS Boston, MA, October 20-22, 2013 http : //www.cigre.org Accidental Islanding of Distribution Systems with Multiple Distributed Generation

More information

EH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map

EH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map EH2741 Communication and Control in Electric Power Systems Lecture 3 Lars Nordström larsn@ics.kth.se 1 Course map 2 1 Outline 1. Repeating Power System Control 2. Power System Topologies Transmission Grids

More information

Modelling Analysis for Optimal Integration of Solar PV in National Power Grid of Japan

Modelling Analysis for Optimal Integration of Solar PV in National Power Grid of Japan USAEE/IAEE 36th North American Conference, Concurrent Session 28, Hilton Crystal City, Washington DC USA, September 25, 2018 Modelling Analysis for imal Integration of Solar PV in National Power Grid of

More information

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Operational Planning Study Report RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Report No. T&S Planning 2013-062 British Columbia Hydro and Power Authority British Columbia Hydro and

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

Power Grid & Blackouts. Prof. Ramzy R. Obaid

Power Grid & Blackouts. Prof. Ramzy R. Obaid Power Grid & Blackouts Prof. Ramzy R. Obaid With many thanks and appreciation to Professor Mohamed A. El Sharkawi Power System The electric power systems in the North America and Europe are probably the

More information

Smart Grid Automation and Centralized FISR

Smart Grid Automation and Centralized FISR Smart Grid Automation and Centralized FISR March 21, 2016 Mike Colby Senior Engineer Distribution Control Center Smart Grid Automation and Centralized FISR Remote Controlled Devices & Communication Distribution

More information

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015 No. Comment Submitted ISO Response Date Q&A Posted 1 Will the ISO consider proposals that are not within the impedance range specified? Yes. However, the benefits estimated and studies performed by the

More information

ABB POWER SYSTEMS CONSULTING

ABB POWER SYSTEMS CONSULTING ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February

More information

SPIDER Modeling Sub-Group DER Modeling, CAISO Experience

SPIDER Modeling Sub-Group DER Modeling, CAISO Experience SPIDER Modeling Sub-Group DER Modeling, CAISO Experience Irina Green, Modeling Sub-Group Chair Regional Transmission Senior Advisor, California ISO NERC SPIDER Work Group Meeting, January 2019 Presentation

More information

Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation

Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation 1. Description In the 2013-2014 Transmission Planning Cycle, the ISO approved the construction

More information

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection B. Bagen, D. Jacobson, G. Lane and H. M. Turanli Manitoba

More information

100 MW Wind Generation Project

100 MW Wind Generation Project A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility

More information

Life Needs Power, Hannover Messe 2017 Inertia in Future Electrical Power Systems Challenges and Solutions Dr. Ervin Spahic

Life Needs Power, Hannover Messe 2017 Inertia in Future Electrical Power Systems Challenges and Solutions Dr. Ervin Spahic Life Needs Power, Hannover Messe 2017 Inertia in Future Electrical Power Systems Challenges and Solutions Dr. Ervin Spahic siemens.com/energy-management Motivation Challenge of reduced synchronous generators

More information

EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS

EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS El Paso Electric Company System Operations Department System Planning Section May 2004

More information

Why Japan remains skeptical of restructuring Study of Electricity Market Bidding Characteristics for Modeling Generation Capacity Growth

Why Japan remains skeptical of restructuring Study of Electricity Market Bidding Characteristics for Modeling Generation Capacity Growth Why Japan remains skeptical of restructuring Study of Electricity Market Bidding Characteristics for Modeling Generation Capacity Growth Satoru Ihara Retired (urotas@ieee.org) Tetsuo Sasaki, Toshihisa

More information

Blackouts. 29/10/2014 Dirk Van Hertem & Steven De Boeck

Blackouts. 29/10/2014 Dirk Van Hertem & Steven De Boeck Blackouts 29/10/2014 Dirk Van Hertem & Steven De Boeck Dirk.VanHertem@esat.kuleuven.be Quiz When was the last blackout in Belgium? First one to present his IEEE card with the correct answer receives a

More information

Northeast Wisconsin/Upper Peninsula Separation 11/14/01. Incident Investigation Report

Northeast Wisconsin/Upper Peninsula Separation 11/14/01. Incident Investigation Report Northeast Wisconsin/Upper Peninsula Separation 11/14/01 Incident Investigation Report Summary Contact by a high voltage electric transmission line with a tree in northeastern Wisconsin initiated a series

More information

NRECA Cooperative Research Network. Modern Grid Initiative Southeast Summit August 10, 2006 Nashville, TN

NRECA Cooperative Research Network. Modern Grid Initiative Southeast Summit August 10, 2006 Nashville, TN NRECA Cooperative Research Network Modern Grid Initiative Southeast Summit August 10, 2006 Nashville, TN Electric Cooperatives... 864 distribution, 66 G&Ts in 47 states 5% of power supply 43% of distribution

More information

Wang Bin & Michael Ho, TIIAE Power management system

Wang Bin & Michael Ho, TIIAE Power management system Wang Bin & Michael Ho, TIIAE 2011 Power management system Content Introduction System configuration Functionality Reference Summary Live demonstration Q & A ABB Group September 5, 2011 Slide 2 Content

More information

Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in High Voltage Systems

Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in High Voltage Systems Advanced Power Transmission Solutions Power Transmission and Distribution Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in Systems s Development of Power Markets Increasing

More information

Dual Power. Protection. Protection

Dual Power. Protection. Protection 54 Fault Clearing Systems by Damien Tholomier., AREVA T&D Automation, Canada Dual Power Single Battery What if it? Short circuits and other abnormal power system conditions are very rear, but may result

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

The 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027)

The 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027) The 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027) February 2013 Contents I. Introduction 1 II. Status of Electricity Supply and Demand 2 1. Electricity Demand 2 2. Electricity

More information

Targeted Application of STATCOM Technology in the Distribution Zone

Targeted Application of STATCOM Technology in the Distribution Zone Targeted Application of STATCOM Technology in the Distribution Zone Christopher J. Lee Senior Power Controls Design Engineer Electrical Distribution Division Mitsubishi Electric Power Products Electric

More information

BREAKER FAILURE PROTECTION

BREAKER FAILURE PROTECTION 29 th Annual HANDS-ON RELAY SCHOOL March 12-16, 2012 BREAKER FAILURE PROTECTION Brent Carper, PE Protection & Integration Engineer brent.c@relayapplication.com OUTLINE Protection System Failures and Breaker

More information

PRESENTATION BY ENERGY COMMISSION OF GHANA ON TACKLING POWER SYSTEM LOSSES

PRESENTATION BY ENERGY COMMISSION OF GHANA ON TACKLING POWER SYSTEM LOSSES PRESENTATION BY ENERGY COMMISSION OF GHANA ON TACKLING POWER SYSTEM LOSSES 1 PRESENTATION OUTLINE Generation System Demand Outlook Existing Generation Resources Transmission System National Interconnected

More information

S C ELECTRIC EUROPE LTD. Excellence Through Innovation. Harnessing the Wind. November 2011 Descriptive Bulletin E

S C ELECTRIC EUROPE LTD. Excellence Through Innovation. Harnessing the Wind. November 2011 Descriptive Bulletin E S C ELECTRIC EUROPE LTD. Excellence Through Innovation Harnessing the Wind November 2011 Descriptive Bulletin 2000-42E Introduction Founded in 1911, S&C Electric Company is a global provider of equipment

More information

TRANSMISSION PLANNING CRITERIA

TRANSMISSION PLANNING CRITERIA CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing

More information

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive

More information

APPENDIX F: Project Need and Description

APPENDIX F: Project Need and Description APPENDIX F: Project Need and Description California ISO/MID F-1 Intentionally left blank California ISO/MID F-2 Name Brief Description Type Lugo Victorville 500 kv Upgrade (SCE portion) The project was

More information

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008 PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral

More information

El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS

El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS El Paso Electric Company El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS 2015 2024 A Review on System Performance Following Extreme Bulk Electric System Events of the

More information

Climate change drivers for a single and smart EU grid

Climate change drivers for a single and smart EU grid Climate change drivers for a single and smart EU grid Smart and Secure Transmission Grids to Realise US and EU Renewable Energy Potentials Keith Bell University of Strathclyde, Scotland Expected growth

More information

APPENDIX E: Project Need and Description

APPENDIX E: Project Need and Description APPENDIX E: Project Need and California ISO/MID E-1 Intentionally left blank California ISO/MID E-2 Tyler 60 kv Shunt Capacitor Installation of a 2x10 MVAR capacitor bank at Tyler 60 kv bus Objectives

More information

National Research Council

National Research Council National Research Council The Initial Sources of Power February 28, 2013, Washington DC, USA. M. M. Adibi IRD Corporation Potomac, Maryland, USA madibird@aol.com (c) IRD 2013 1 The impact of a blackout

More information

US Japan Energy Opportunities. May 15, 2013 NEDO Silicon Valley Office Osamu Onodera

US Japan Energy Opportunities. May 15, 2013 NEDO Silicon Valley Office Osamu Onodera US Japan Energy Opportunities May 15, 2013 NEDO Silicon Valley Office Osamu Onodera Strategic Energy Plan of Japan (before Tohoku) Renewable and Nuclear were to be increased to reduce Co2 emissions but

More information

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0 ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES 2018-04-24 - Revision 0 EUB Decision 2007-071 Board Direction 52 For questions or comments regarding

More information

SECTION 9: ELECTRICAL POWER DISTRIBUTION. ESE 470 Energy Distribution Systems

SECTION 9: ELECTRICAL POWER DISTRIBUTION. ESE 470 Energy Distribution Systems SECTION 9: ELECTRICAL POWER DISTRIBUTION ESE 470 Energy Distribution Systems 2 Introduction The Electrical Grid 3 Three main components to the electrical grid Generation ESE 450 Transmission Transmission

More information

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008 NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0

More information

Interconnection Feasibility Study Report GIP-226-FEAS-R3

Interconnection Feasibility Study Report GIP-226-FEAS-R3 Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power

More information

Machine, Panel, and Plant Level Solutions

Machine, Panel, and Plant Level Solutions Machine, Panel, and Plant Level Solutions Mark Stephens, PE Manager Industrial Studies Electric Power Research Institute 942 Corridor Park Blvd Knoxville, Tennessee 37932 Phone 865.218.8022 mstephens@epri.com

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems Ben Huckaba, P.E. President & Principal Engineer 317-273-9841 benh@alphaeng.us Indiana University Bloomington,

More information

REPORT. System Impact Assessment Report. Thierry Mine Development CONNECTION ASSESSMENT & APPROVAL PROCESS CAA ID

REPORT. System Impact Assessment Report. Thierry Mine Development CONNECTION ASSESSMENT & APPROVAL PROCESS CAA ID REPORT IESO_PRO_0499 System Impact Assessment Report Thierry Mine Development CONNECTION ASSESSMENT & APPROVAL PROCESS CAA ID 2008-309 Applicant: Richview Resources Inc Market Facilitation Department 2009

More information

Facilities Study for Alberta to US Available Transfer Capability

Facilities Study for Alberta to US Available Transfer Capability Facilities Study for Alberta to US Available Transfer Capability Report No: NPP2002-05 June 3, 2002 System Planning & Grid Operations, Transmission Line of Business Engineering Services Executive Summary

More information

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent

More information

ABB WAMS Capabilities

ABB WAMS Capabilities Steven A. Kunsman Asst VP Global Product Management Ernst Scholtz, PhD Principal Scientist, Corp Research ABB WAMS Capabilities Acknowledgement: A. Leirbukt, R. Nuqui, M. Larsson, P. Korba ABB Group -1-

More information

Opportunities and Challenges for Smart Grid in Japan. March 8, Shuichi Ashidate

Opportunities and Challenges for Smart Grid in Japan. March 8, Shuichi Ashidate Opportunities and Challenges for Smart Grid in Japan March 8, 2016 Shuichi Ashidate Vice President of TEPCO Research Institute Tokyo Electric Power Co., Inc. TEPCO All Rights Reserved, March 8, 2016 Capacity

More information

IEEE-PES Chicago Chapter Presentation November 11, Smart Grid. Mike Born. Principal Engineer, Capacity Planning

IEEE-PES Chicago Chapter Presentation November 11, Smart Grid. Mike Born. Principal Engineer, Capacity Planning IEEE-PES Chicago Chapter Presentation November 11, 2009 Smart Grid Mike Born Principal Engineer, Capacity Planning Agenda 2 Smart Grid Brief Overview ComEd s Smart Grid Vision and Building Blocks Customer

More information

DP INNOVATION. A Novel Solution to Common Mode Failures in DP Class 2 Power Plant

DP INNOVATION. A Novel Solution to Common Mode Failures in DP Class 2 Power Plant DP INNOVATION A Novel Solution to Common Mode Failures in DP Class 2 Power Plant Dr. Steven Cargill Noble Denton Consultants, Ltd October 7-8, 2008 Return to Session Directory A Novel Solution to Common

More information

Impact of Islanding and Resynchroniza?on on Distribu?on Systems

Impact of Islanding and Resynchroniza?on on Distribu?on Systems 1 Impact of Islanding and Resynchroniza?on on Distribu?on Systems Authors: Dr. Vijay Sood Damanjot Singh Kush Duggal 2 Contents Introduction System Description Rural Radial Distribution System Urban Meshed

More information

SEL Microgrid Lessons Learned

SEL Microgrid Lessons Learned SEL Microgrid Lessons Learned Will Edwards (SEL Engineering Services Division) Copyright SEL 2016 Essential Keys to Successful Microgrid Projects? Comprehensive HIL testing Subcycle fast controls Adaptive

More information

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best. Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution

More information

Grid Integration Costs: Impact of The IRP Capacity Mix on System Operations

Grid Integration Costs: Impact of The IRP Capacity Mix on System Operations Grid Integration Costs: Impact of The IRP Capacity Mix on System Operations Presenter: Bernard Magoro, System Operator, Transmission Division, Eskom SOC Holdings Date: 05 October 2018 Contents 1. Background

More information

GRID INNOVATION CAUCUS CO-CHAIRS

GRID INNOVATION CAUCUS CO-CHAIRS February 16, 2017 GRID INNOVATION CAUCUS CO-CHAIRS REP. JERRY NCNERNEY (D-CA) REP. BOB LATTA (R-OH) 2 WIRES UNIVERSITY Transmission 101: The Fundamentals Of High Voltage Transmission February 16, 2017

More information

Dynamic Line Rating as a Means to Enhance Transmission Grid Resilience

Dynamic Line Rating as a Means to Enhance Transmission Grid Resilience Dynamic Line Rating as a Means to Enhance Transmission Grid Resilience McCall, J. Goodwin, T. Lindsey Manufacturing Tip Goodwin Consulting LLC USA Canada CIGRE US National Committee 2015 Grid of the Future

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

Texas A&M Microgrid and Electrical System Study. Cushing Memorial Library & Archives

Texas A&M Microgrid and Electrical System Study. Cushing Memorial Library & Archives Texas A&M Microgrid and Electrical System Study Cushing Memorial Library & Archives Introduction of Texas A&M Microgrid Study Purpose Why are we studying the TAMU electrical system? Process How do we want

More information

PMU-based Wide Area Protection System Concept and application in a large longitudinal system

PMU-based Wide Area Protection System Concept and application in a large longitudinal system Dr. U. Kerin, Siemens AG PMU-based Wide Area Protection System Concept and application in a large longitudinal system Siemens AG, EM SG PTI, 215 All rights reserved www.siemens.com Why is there an increasing

More information

Breaker failure relay REB 010

Breaker failure relay REB 010 Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970138) Features Local redundant protection when the circuit breaker does not operate The technique with microprocessors

More information

Transient Stability Analysis Tool (TSAT) Update April 11, Hongming Zhang EMS Network Applications Manager

Transient Stability Analysis Tool (TSAT) Update April 11, Hongming Zhang EMS Network Applications Manager Transient Stability Analysis Tool (TSAT) Update April 11, 2016 Hongming Zhang EMS Network Applications Manager Agenda Peak Online TSAT Introduction: Where we are on Wide-wide System Model (WSM) -TSAT online

More information

Electric Power Delivery To Big Cities

Electric Power Delivery To Big Cities Problem Definition Electric Power Delivery To Big Cities a) Socio-economic incentives are a major factor in the movement of population to big cities b) Increasing demand of electric power has strained

More information

The FREEDM System: components, main functions, system control

The FREEDM System: components, main functions, system control Short course on the FREEDM System Session L3 The FREEDM System: components, main functions, system control Dr. I. Husain, North Carolina State University Dr. G. T. Heydt, Arizona State University October,

More information

Supplemental Report on the NCTPC Collaborative Transmission Plan

Supplemental Report on the NCTPC Collaborative Transmission Plan Supplemental Report on the NCTPC 2007-2017 Collaborative Transmission Plan May 16, 2008 1 Table of Contents I. Executive Summary...1 II. Richmond-Fort Bragg Woodruff Street 230 kv Line...2 II.A. Need for

More information

New 115 kv Disconnect Switches at Bloomsburg MTS

New 115 kv Disconnect Switches at Bloomsburg MTS 115 kv Line tap from C9 to Bloomsburg MTS & New Bus Tie Switch CAA ID Number: 2007-EX353 Final Draft ASSESSMENT SUMMARY 1. GENERAL DESCRIPTION Norfolk TS and Bloomsburg MTS are supplied by a single 115

More information

Copyright 2003 Advanced Power Technologies, Inc.

Copyright 2003 Advanced Power Technologies, Inc. Overview of the Standard for Interconnecting Distributed Resources with Electric Power Systems, IEEE 1547 and it s potential impact on operation of the Distributed Generation (DG) systems and on the design

More information

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility

More information

The Energy Queensland Group Notice of no non-network options

The Energy Queensland Group Notice of no non-network options The Energy Queensland Group Notice of no non-network options 24 September 2018 MCE Mount Crosby East Establish new substation to replace Mount Crosby Substation (SSMTC) Page 1 of 1 DISCLAIMER While care

More information

Grid-Friendly Utility-Scale PV Plants

Grid-Friendly Utility-Scale PV Plants White Paper Grid-Friendly Utility-Scale PV Plants Mahesh Morjaria & Dmitriy Anichkov, First Solar, Tempe, Arizona, USA 13 August 2013 Table of Contents Introduction.... 3 Power Plant Controller Architecture...

More information

South Dakota 890 Study

South Dakota 890 Study South Dakota 890 Study September 16, 2011 South Dakota 890 Study Presentation of 890 Study results from 2011 Includes WAPA suggested system improvements and timelines Stakeholder Feedback Questions? 2

More information

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications Sectionalizing Rick Seeling Introduction Philosophy Pete Malamen Three Phase Reclosers High-Side Protection Specific Applications History Early 1970 s Small Substation Transformers

More information

DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY

DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY Transmission Department Transmission Planning Duke Energy Progress TABLE OF CONTENTS I. SCOPE 3 II. TRANSMISSION PLANNING OBJECTIVES 3 III. TRANSMISSION

More information

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY 2011-2020 P+ PowerPlus Engineering A Department of STAR Energy Services, LLC TEN YEAR PLANNING GUIDE 2011-2020 SHASTA LAKE ELECTRIC UTILITY CITY OF

More information

LESSONS LEARNED FORSMARK EVENT Presented To IEEEE

LESSONS LEARNED FORSMARK EVENT Presented To IEEEE LESSONS LEARNED FORSMARK EVENT Presented To IEEEE Thomas Koshy Member of the Task Group on Forsmark Chief of Mechanical & Electrical Engineering Office of Research, USNRC Thomas.Koshy@nrc.gov 1 Agenda

More information

Challenges of DMS Control Centers in the Smart Grid. Gary Ockwell Efacec Advanced Control Systems Chief Technology Officer

Challenges of DMS Control Centers in the Smart Grid. Gary Ockwell Efacec Advanced Control Systems Chief Technology Officer Challenges of DMS Control Centers in the Smart Grid Gary Ockwell Efacec Advanced Control Systems Chief Technology Officer June 5, 2013 Affected: 30 Million Inhabitants 800,000 in trapped subways 250 Flights

More information

North Oregon Coast Area Study. Adam Lint

North Oregon Coast Area Study. Adam Lint North Oregon Coast Area Study Adam Lint PAGE 2 North Oregon Coast System Overview - Clatsop Study Covers: Transmission Switching Stations (Clatsop District): Astoria Lewis and Clark 115 kv Distribution

More information

Southern California Edison s Circuit of the Future

Southern California Edison s Circuit of the Future Southern California Edison s Circuit of the Future Charlie Vartanian SCE Distributed Energy Resources (DER) 3 rd Microgrid Symposium April 6, 2007 SCE Profile 50,000 Mile 2 Service Territory 120 years

More information

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Interconnection Feasibility Study Report GIP-222-FEAS-R3 Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.

More information

Technology Roadmap for zzzzzzzzz Grid Automation

Technology Roadmap for zzzzzzzzz Grid Automation IEEE Nashville Chapter Technology Roadmap for zzzzzzzzz Grid Automation November 2010 2010 by R. W. Beck, An SAIC Company. All Rights Reserved. Projected Expenditures 2010-2030 Substation Transmission

More information

Distributed Energy Resources

Distributed Energy Resources Distributed Energy Resources WECC Data Subcommittee Rich Hydzik, Avista (ERSWG/DER Subgroup Lead) June 29, 2018 Why Are We Concerned About DER? Concern about changing generation fleet Large coal fired

More information

IFC Workshop on Distributed Generation, 13 February 2013, Moscow, Russia

IFC Workshop on Distributed Generation, 13 February 2013, Moscow, Russia Integration of Distributed Energy Resources Into the Electric Grid: Some Issues and Solutions Larry Adams Senior Electrical & Controls Engineer Spirae, Inc. IFC Workshop on Distributed Generation, 13 February

More information

2015 WDC Disturbance and Protection Standards Overview

2015 WDC Disturbance and Protection Standards Overview NERC Update 2015 WDC Disturbance and Protection Standards Overview Rich Bauer Senior Manager Reliability Risk Management / Event Analysis IEEE PSRC meeting Denver, Co May 12, 2016 2 System Protection and

More information

Southern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management

Southern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management Southern Company Interconnection Process Dexter Lewis Research Engineer Research and Technology Management Southern Company Outline Southern Company GPC Solar Interconnection Process Application requirements

More information

Georgia Transmission Corporation Georgia Systems Operations Corporation

Georgia Transmission Corporation Georgia Systems Operations Corporation Georgia Transmission Corporation Georgia Systems Operations Corporation Reactive Power Requirements for Generating Facilities Interconnecting to the Georgia Integrated Transmission System with Georgia

More information

ERCOT Overview. Paul Wattles Senior Analyst, Market Design & Development. Solar Energy Industries Association July 11, 2012

ERCOT Overview. Paul Wattles Senior Analyst, Market Design & Development. Solar Energy Industries Association July 11, 2012 ERCOT Overview Paul Wattles Senior Analyst, Market Design & Development Solar Energy Industries Association History of Electric Reliability Council of Texas, Inc. 1941 Utilities band together to aid war

More information

BC HYDRO REAL TIME OPERATIONS SYSTEM OPERATING ORDER 7T-35. PEACE 138/230 kv NETWORK OPERATION Supersedes 7T-35 issued 15 June 2017

BC HYDRO REAL TIME OPERATIONS SYSTEM OPERATING ORDER 7T-35. PEACE 138/230 kv NETWORK OPERATION Supersedes 7T-35 issued 15 June 2017 BC HYDRO REAL TIME OPERATIONS SYSTEM OPERATING ORDER 7T-35 PEACE 138/230 kv NETWORK OPERATION Supersedes 7T-35 issued 15 June 2017 Review Year: 2021 Original signed by Brett Hallborg for: APPROVED BY:

More information

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Solid Dielectric, Three Phase Reclosers CATALOG VS11 Solid Dielectric, Three Phase Reclosers Providing electronic, three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance

More information

Project #148. Generation Interconnection System Impact Study Report

Project #148. Generation Interconnection System Impact Study Report Project #148 Generation Interconnection System Impact Study Report June 05, 2012 Electric Transmission Planning Table of Contents Table of Contents... 2 Executive Summary... 3 Energy Resource Interconnection

More information

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew. Guide Department: Interconnection Services Document No: GD-1401 v1.0 Title: WIND ISLANDING Issue Date: 11-24-2014 Previous Date: N/A Contents 1 PURPOSE... 2 2 SCOPE AND APPLICABILITY... 2 3 ROLES AND RESPONSIBILITIES...

More information

Illinois State Report

Illinois State Report July 2016 Illinois State Report Table of Contents 1. Planning Generation Portfolio Analysis Transmission Analysis Load Forecast Gas Pipeline Information 2 Executive Summary (July 2016) Existing Capacity:

More information

Impact of Distributed Energy Resources on Transmission System Reliability

Impact of Distributed Energy Resources on Transmission System Reliability S E P T E M B E R 1 3, 2 0 1 8 W E B I N A R Impact of Distributed Energy Resources on Transmission System Reliability National Council on Electricity Policy (NCEP) Alan McBride D I R E C T O R, T R A

More information

APPENDIX E: Project Need and Description

APPENDIX E: Project Need and Description APPENDIX E: Project Need and California ISO/MID E-1 Intentionally left blank California ISO/MID E-2 Lakeville 115 kv Bus Upgrade Installation of a sectionalizing breaker to be installed on 115 kv bus section

More information

Strategy and Roadmap for PV Systems in Japan

Strategy and Roadmap for PV Systems in Japan APEC EGNRET44, Laoag, Philippines Strategy and Roadmap for PV Systems in Japan April 13-14th, 2015 Takao Ikeda The Institute of Energy Economics, Japan (IEEJ) Road Map for PV 2014 2020 2030 2050 Conversion

More information

Transmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting

Transmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting Transmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting BHE Wyoming Q4 Stakeholder Meeting November 17, 2016 @ 1:00PM MT Black Hills Energy Service Center 409 Deadwood Avenue, Rapid

More information