ÒÌÃ TRANSFORMERS. ÒÌÃ 1250 kv.a
|
|
- Noel Cameron
- 6 years ago
- Views:
Transcription
1 ÒÌÃ TRNSFORMERS ÒÌÃ three-phase oil transformers are intended for transforming of electric energy in networks of power systems and in energy consumer networks. Transformers are designed for indoor or outdoor installation under conditions of moderate (+ 40 o C to - 45 o C) or cold (+40 o C to -60 o C) climate. Transformers are assigned for operation in inexplosive environments excluding dust content that could affect transformer parameters to inadmissible limits. Transformers are not assigned either for operation under jolting, vibration, or impact effects, or in chemically active environments. Operable altitude elevation above sea level is not more than 1000 m. ÒÌÃ Rated frequency: 50 Hz. Voltage regulation within ±5 % range is carried out with a fully de-energized transformer (power-off changing) through HV tap-changing in 2.5 % steps. ÒÌÃ transformers are of a sealed version, they have no conservators. Temperature induced changes of oil volume are neutralized due to volume changes in goffers of the tank owing to their flexible deformability. For oil-level control transformers are fitted with float-type oil indicators. To prevent excessive pressure in a tank over permissible value the 16 to 63. transformers are equipped with release valves. For control of inner pressure in a tank and for signalling in the event of inadmissible overpressure the indoor transformers of 100. and higher ratings are fitted with electrocontact vacuum manometers (option). To make measurements of top oil temperature a pocket for liquid-filled thermometer mounting is provided on the transformer cover. To measure top oil temperature and to control external electric circuits the transformers are fitted with manometric signalling thermometers (option). Transformers of 160. and higher ratings are equipped with carrying rollers for transformer moving (option). here resettable rollers are provided as an option H, H 1 sizes in 160 to 400. transformers (see Table) are increased by 94 mm.
2 Transformer type Specifications of TMÃ transformers rating Rated power, Rated voltage,. HV LV ÒÌÃ-16/10-Ó1(ÕË1) 16 6,10 inding connection/ vector group no-load, shortcircuit No-load current, % 3,0 3,0 Short-circuit Dimensions, mm Mass, kg voltage, % L H Í1 À b b1 of oil total 5, ÒÌÃ-25/10-Ó1(ÕË1) 6, , ÒÌÃ-25/27,5-Ó1 ÒÌÃ-40/10-Ó1(ÕË1) 40 6,10 ÒÌÃ-63/10-Ó1(ÕË1) 63 6,10 27, ,1 6, ,6 1, ÒÌÃ-100/10-Ó1(ÕË1) 100 6,10 8,05 0,38 Ynd11 27, , , ÒÌÃ-100/35-Ó ,4 6,5 6, ÒÌÃ-160/10-Ó1(ÕË1) 6,10 ÒÌÃ-160/35-Ó1 160 ÒÌÃ-250/10-Ó1(ÕË1) 6,10 ÒÌÃ-250/35-Ó , , ,2 6, ,0 Ynd ,2 6,5 6, , ,9 6, ,9 6,5 6, , , ÒÌÃ-400/10-Ó1(ÕË1) 400 8, 0,38 Ynd , , ,9 6, ÒÌÃ-400/35-Ó ,9 6, ÒÌÃ-630/10-Ó1(ÕË1) 630 6, ,6 5, ÒÌÃ-1000/10-Ó ,10 ÒÌÃ-1250/10-Ó , ,5 5, ,5 6, ÒÌÃ-1600/10-Ó , ,5 6,
3 Specifications of TMÃ transformers of and voltage class Transformer type Rated power,. Rated voltage HV, Rated voltage LV, inding connection/ vector group no-load, short-circuit, Short-circuit voltage, % Dimensions, mm L H ÒÌÃ-16/-Ó Yzn ÒÌÃ-16/-Ó ÒÌÃ-25/-Ó Yzn ÒÌÃ-25/-Ó ÒÌÃ-40/-Ó Yzn ÒÌÃ-40/-Ó ÒÌÃ-63/-Ó Yzn ÒÌÃ-63/-Ó ÒÌÃ-100/-Ó Yzn ÒÌÃ-100/-Ó ÒÌÃ-100/-Ó Dyn5 ÒÌÃ-100/-Ó ÒÌÃ-160/-Ó Yzn ÒÌÃ-160/-Ó ÒÌÃ-160/-Ó Dyn5 ÒÌÃ-160/-Ó ÒÌÃ-250/-Ó ÒÌÃ-250/-Ó ÒÌÃ-400/-Ó ÒÌÃ-400/-Ó Mass, kg
4 Transformer type ÒÌÃ-630/-Ó1 ÒÌÃ-630/-Ó1 ÒÌÃ-800/-Ó1 ÒÌÃ-800/-Ó1 ÒÌÃ-1000/-Ó1 ÒÌÃ-1000/-Ó1 ÒÌÃ-1250/-Ó1 ÒÌÃ-1250/-Ó1 Specifications of TMÃ transformers of and voltage class Rated power, Rated voltage HV, Rated voltage LV, inding connection/ vector group no-load, short-circuit, Short-circuit voltage, % Dimensions, mm L H Mass, kg
5 1 - oil-fill branch 2 - release valve 3 - HV-bushing 4 - LV-bushing 5 - oil-level indicator 6 - eye-ring for transformer hoisting 7 - thermometer pocket 8 - nameplate 9 - tank 10 - earth terminal 11 - drain plug 12 - tap-changer 13 - film cut-out (option) TMÃ transformers rating
6 7 6 TMÃ transformers rating H1 H C 12 b 10 c b a b L 1 - carrying roller (option for the transformers rating 160, 250, 400. ) 2 - earth terminal 3 - drain plug 4 - tank 5 - nameplate 6 - oil-level indicator 7 - LV-bushing 8 - HV-bushing 9 - thermometer pocket 10 - oil-fill branch 11 - eye-ring for transformer hoisting* 12 - tap-changer 13 - film cut-out (option) * 400 transformers are manufactured with eye-rings located on a tank 12
7 TMÃ transformers rating H 4 H C c b a 0 b1 b carrying roller 2 - drain plug 3 - earth terminal 4 - tank 5 - nameplate 6 - thermometer pocket 7 - oil-level indicator 8 - HV-bushing 9 - LV-bushing 10 - oil-fill branch 11 - tap-changer 12 - eye-ring for transformer hoisting 13 - film cut-out (option) L
Minera. Oil distribution transformers up to kva. eco design. Minera at a glance. Standards
Minera Oil distribution transformers up to 3 150 kva Minera at a glance Mineral oil-immersed, 50 Hz, three-phase distribution transformers with the following characteristics: Hermetically sealed with integral
More informationDistribution transformers Efficiency over life-cycle
Distribution transformers Efficiency over life-cycle ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while
More information1500 kva Pad Mount Transformer GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled
1500 kva Pad Mount Transformer - 24940GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled Part #: MT-PMO-3P-24940GRDY.14400-1500KVA-208Y.120-N3R Page: 1 The MT-PMO-3P-24940GRDY.14400-1500KVA-208Y.120-N3R
More informationMaximum temp. rise in oil by 40 thermometer above design ambient (deg C) specified time Short circuit rating (Sec) for As per IS 2026
TECHNICAL PERTICULAR FOR 1.6 MVA 6.6/0.433 KV SERVICE TRANSFORMER 1.00.00 GENERAL 1.01.00 Service SERVICE 1.02.00 Make ASHOK/VOLTAMP/DANKE/CGL 1.03.00 Type CORE 1.04.00 Location OUTDOOR 1.05.00 Specification
More informationTGK Prefabricated Substation Technical Data
TGK Prefabricated Substation Technical Data Ref Item Data 1 General Technical 1.1 Frequency (Hz) 50 1.2 Transformer Rating (kva) 315/750 1.3 Transformer Primary Voltage (kv) 11 1.4 Transformer Secondary
More informationKey features. DESIGNS: - Conservator type - Hermetically sealed
Package Substations OTDS manufactures a large range of oil filled hermitically sealed and conservator type transformers to be used in conjunction with our package substations. We are able to utalise the
More informationTRANSPORT. Take all the necessary precautions to prevent the load from knocking against the vehicle during transport. - 1/5 -
TRANSPORT The unit is arranged lengthwise in the vehicle. The rollers must be removed and can be fastened the wrong way around on the substructures or packed in a cardboard box inside the box. The unit
More information500 kva Pad Mount Transformer V Delta Primary - 208Y/120 Secondary - NEMA 4X - Oil Cooled
500 kva Pad Mount Transformer - 12470V Delta Primary - 208Y/120 Secondary - NEMA 4X - Oil Cooled Part #: MT-PDO-SS-3P-12.47KV-500KVA-208Y.120-FR3-CU Page: 1 The MT-PDO-SS-3P-12.47KV-500KVA-208Y.120-FR3-CU
More informationDistribution Transformers. The most comprehensive range of solutions for distribution transformer applications
Distribution The most comprehensive range of solutions for distribution transformer applications Oil Type Single-phase and three-phase transformers for the range above 16 kva and up to 72.5 kv. These units
More informationHistory of the company. TUMETIC and TUNORMA: Tailor-Made Technology
History of the company Csepel Transformer Factory was founded in 1960 as a state owned company in the location of the large industrial estate in southern Budapest situated on the island of the Danube river.
More informationABB Ltd. FACTORY IN HANOI
ABB LTD. ABB Ltd. was originally a JVC between the Vietnamese Transformers Manufacture CTBT and the International Electromechanical group ABB Company was established 1st Sep. 1994 Distribution Transformers
More informationABB Transformers Egypt
Kamel Elhamy, 2013 ABB Transformers Egypt Our transformers support the systems that keep our world running ABB January 31, 2012 Slide 1 Factory Information Key data 2012 Annual volume 40 MUSD Employees
More informationCertified for best-in-class performance, reliability, and safety. Trihal sets a new standard for dry-type cast resin transformers
Certified for best-in-class performance, reliability, and safety Trihal sets a new standard for dry-type cast resin transformers Setting a new standard for dry-type cast resin transformers hospitals wind
More informationSF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)
SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) About company The «Elektroapparat» plant starts its operation in 1922 as a plant manufacturing high-voltage electrical equipment. During the first two
More informationTRANSPORT. Take all the necessary precautions to prevent the load from knocking against the vehicle during transport. - 1/5 -
TRANSPORT The unit is arranged lengthwise in the vehicle. The rollers must be removed and can be fastened the wrong way around on the substructures or packed in a cardboard box inside the box. The unit
More informationAC/DC Arc Furnace and Ladle Furnace Transformers
AC/DC Arc Furnace and Ladle Furnace Transformers Specification parameter Specify the requirements for 1. Environmental condition and standards Applicable standard Electrical standard Mechanical standard
More informationCOMPACT SUBSTATION GUIDE
COMPACT SUBSTATION GUIDE Certificate Number FM35831 1 The substation is a compact enclosure consisting of MV switchgear, a transformer and an LV switchboard located in three separate compartments which
More informationCAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION
CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION TMC TRANSFORMERS - GLOBAL NETWORK UK & IRELAND SPAIN NORTH AMERICA & CANADA GERMANY SWITZERLAND BENELUX & AUSTRIA ITALY POLAND INDIA CENTRAL & SOUTH AMERICA
More information7.0 Technical Guarantee Specification of 60MVA, 132/33kV Mobile Substation. TECHNICAL DATA SCHEDULE 60MVA, 132/33 kv MOBILE SUBSTATION
92 Section VI. Schedule of Requirements 7.0 Technical Guarantee Specification of 60MV, 132/33 Mobile Substation TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED
More informationPower IT Liquid Filled Transformers. IEC standard, small and medium, rated power 2000kVA, HV 36kV
Power IT Liquid Filled Transformers IEC standard, small and medium, rated power 2000kVA, HV 36kV Even our standard solutions are special In almost every place where people live and work you will find at
More informationCast resin transformers
Product catalogue Cast resin transformers according to IEC/EN 60076, VDE 0532, DIN 42523 Power range up to 8 MVA Voltage range up to 36 kv Conductor material: copper or aluminum Protection types: IP 00
More informationSubmersible Vacuum Fault Interrupters
Submersible Vacuum Fault Interrupters UG Distribution Medium Voltage Vacuum Fault Interrupters Functional Specification Guide PS024002EN Functional Specification for 2.4kV to 17.5kV UG Distribution Medium
More informationCONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Technical Data 3.2 Standard Accessories 3.3 Tolerances
CONTENTS 1 GENERAL 2 STANDARDS 3 TECHNICAL FEATURES 3.1 Basic Technical Data 3.2 Standard Accessories 3.3 Tolerances 4 MOTOR DESIGN 4.1 Stator Casing 4.2 Stator Core with Winding 4.3 Stator Winding 4.4
More informationINESING GROUP. Power System Solution
INESING GROUP INESING GROUP Power System Solution Power System Solution INESING Group Via Dell'Industria 18B 24040 Casirate D'Adda Italy t: +39 3388263363 f: +39 04381890521 e: info@inesing.com introduction
More informationtests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.
tests ( Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. electrical tests These tests verify contractual
More informationUniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions
UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions ABB a global leader ABB is a global leader in power and automation technologies that
More informationMEDIUM POWER TRANSFORMER
MEDIUM POWER TRANSFORMER MEDIUM POWER TRANSFORMER FROM 3,15 TO 31,5 MVA HIGHEST VOLTAGE FOR MATERIAL 72,5kV GENERAL CHARACTERISTICS Three phase oil-immersed naturally cooled type ONAN medium power transformers.
More information1TSF /CD Attachment B. City and County of San Francisco Office of Contract Administration
1TSF14000167/CD LINE ITEM 1: 37,5 KVA 1 PHASE PAD MOUNTED TRANSFORMER, ENVIROTEMP FR3 37.5 KVA, 10 Pad Mounted Transformer, AIMS! TYPE 2 SHRUBLINE insulating fluid 12470 Deita Two position ioadbreak switch
More informationOLIVER ONLINE VOLTAGE REGULATION
CAST-RESIN TRANSFORMERS ACCORDING TO IEC/EN 60076, VDE 0532, DIN 42523, DIN EN 50541-1, EU NR. 548/2014 OLIVER ONLINE VOLTAGE REGULATION With Ruhstrat transformers you provide the right voltage for the
More informationDRY TYPE TRANSFORMERS
DRY TYPE TRANSFORMERS Single-phase, Three-phase/Single-phase, Three-phase/Two-phase,Three-phase 1.1 kv to 7.2kV Class Dry Type Transformers Transformers meant to be installed in a dry and air conditioned
More informationProduct presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 Dry-type transformers Innovative Technology What is a dry transformer? ABB manufactures a transformer which does
More informationPowering industry since 1947.
Powering industry since 1947. Need Power? Get in touch today. 2 EU Compliant, Tier 1 and Tier 2 Distribution & Power Transformers. British heritage, global reputation, world-renowned expertise. Why Bowers?
More information*(1(5$/7(&+1,&$/63(&,),&$7,2162) +9/9 ',675,%87,2175$16)250(56
T *(1(5$/7(&+1,&$/63(&,),&$7,2162) +9/9 ',675,%87,2175$16)250(56 TUNISIE TRANSFORMATEUR S.A :ULWWHQE\ M. BOUMALLA Adel Checked by : Mll. LAOUINI Radhia Approved by : M.LARIBI Mohamed Kamel %XVLQHVV'HSDUWPHQW,PP(O+DELE%XUHDX1ƒ%ORF%/HV%HUJHVGXODF$RXLQD
More informationTransformer Stations
ISO 9001 99-320 Żychlin, ul. Narutowicza 70 www.ftz.com.pl Secretary s Office Tel.: +48 24 285 46 05, Fax: +48 24 285 46 31, zarzad@ftz.com.pl Marketing and Sales Department Tel.: +48 24 285 18 53, Fax:
More informationOIL LEVEL GAUGES FOR DISTRIBUTION TRANSFORMERS
(Model Year 2014) OIL LEVEL GAUGES FOR DISTRIBUTION TRANSFORMERS MAGNETIC OIL LEVEL GAUGES (without contacts) Page 5.26. Type IML 80 and IML 99. They are the two cheapest gauges of our range, with aluminium
More informationH1 H2 H3 X0 X1 X2 X3
H0 H H H H0 H H H X0 X X X X0 X X X S- S- S- S- FB H0 H H H X0 X X X H0 H H H X0 X X X 7 NOTES:. ITEMS REMOVED FOR SHIPMENT. TANK DESIGNED FOR FULL VACUUM. MANUFACTURED IN ACCORDANCE WITH ANSI
More informationTHERMOMETERS For distribution transformers
THERMOMETERS For distribution transformers Page 5.15 : Thermometer MTVT 84 Oil temperature indicator, new concept, fitted with two independent microswirches, range 0...120 C, only with bottom entry rigid
More informationPRESENTATION ON STANDARDSDISTRIBUTION TRANSFORMERS BUREAU OF INDIAN STANDARDS BHOPAL
PRESENTATION ON STANDARDSDISTRIBUTION TRANSFORMERS BUREAU OF INDIAN STANDARDS BHOPAL BIS Act WTO Principle on Standard Process for development of Indian Standard Standards on Transformers Detailed provision
More informationwww. ElectricalPartManuals. com Substation Transformers Primary or Secondary Open
Substation Transformers Primary or Secondary Open GENERAL Cooper Power Systems Primary or Secondary Open Substation Transformers are designed to meet exact customer specifications. Flexibility in design,
More informationZREW Transformers Perfection in Detail. a company of Rauscher & Stoecklin SERW ZREW Tesar
ZREW Transformers Perfection in Detail a company of Rauscher & Stoecklin SERW ZREW Tesar ZREW Your partner for high quality transformers A basic requirement for power transformers is a reliable and efficient
More informationTRANSFORMERS UP TO 750 kv
Electric Co. Ltd. TRANSFORMERS UP TO 750 kv CONTENTS General... 2 Products... 3 Construction...4 Magnetic core... 4 Windings...5 Frame structure... 6 Connections...6 Tap changer and motor drive...7 Tank...
More informationHPS EnduraCoil. Cast Resin Transformer
HPS EnduraCoil Cast Resin Transformer Hammond Power Solutions Inc. (HPS) is a leading manufacturer of standard and custom dry-type transformers in North America. Every HPS product is built with the quality
More informationCAST RESIN TRANSFORMERS
CAST RESIN TRANSFORMERS 2 CAST RESIN TRANSFORMERS GRAVITY LINE WHO WE ARE SGB-SMIT AT A GLANCE 415 YEARS OF EXPERIENCE Combined, more than Basis for know-how and for know-why More than 2,000 EMPLOYEES
More informationINESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation
MOBILE SUBSTATIONS Energy Solution INTERNATIONAL FAIR MOBILE SUBSTATIONS ENERGY SOLUTION Complete design for energy s generations, transmission and distribution Mobile Substations Applications of Inesing
More informationP2 : About Us. P3 : Elsewedy Transformers. P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers. P7 : Technical Data Sheets
P2 : About Us P3 : Elsewedy Transformers P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers P7 : Technical Data Sheets P8 : Transformer s Outline Drawing P9 : Accessories About Us
More informationQuality Reliability Flexibility. Trasformatori di potenza in olio Oil Transformers
Quality Trasformatori di potenza in olio Oil Transformers TESAR OIL FILLED TRANSFORMERS: RELIABILITY AND QUALITY NEVER FORGETTING THE ENVIRONMENTAL ASPECTS. Trasformatori trifase a raffreddamento naturale
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationDrive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer
Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer This document contains sample specifications for Liquid-Filled Type Drive Transformers You may
More informationSUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More informationSECTION PADMOUNT TRANSFORMER - OIL FILLED
SECTION 26 12 19.01 PADMOUNT TRANSFORMER - OIL FILLED PART 1 GENERAL 1.1 DESCRIPTION: Padmount Transformers and Insulating Oil with underground primary and secondary connections for use in distribution
More informationCONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Design Data 3.2 Standard Accessories 3.3 Tolerances
CONTENTS 1 GENERAL 2 STANDARDS 3 TECHNICAL FEATURES 3.1 Basic Design Data 3.2 Standard Accessories 3.3 Tolerances 4 MOTOR DESIGN 4.1 Stator Casing 4.2 Stator Core with Winding 4.3 Stator Winding and Insulation
More informationCompact Integrated Distribution Substation (CIDS)
Compact Integrated Distribution Substation (CIDS) 1- INTRODUCTION SAVE SPACE 2.5m 2 footprint for CIDS up to 630kVA. SAVE THE ENVIRONMENT No SF6, No PCB. SAVE MONEY Save up to 50% from conventional package
More informationSection S7 - DC and AC auxiliary services installations
S7/2 Section S7 - DC and AC auxiliary services installations Contents S7. Generalities...3 S7. Generalities...4 S7..1 Scope of work...4 S7..2 Dimensioning the auxiliary services equipment...4 S7.1 General
More informationFUSES. Safety through quality
Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced
More informationGE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc
GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4
More informationINSTALLATION MANUAL. Instructions, precautions, suggestions for installing and servicing resin transformers in full compliance with safety rules
INSTALLATION MANUAL Instructions, precautions, suggestions for installing and servicing resin transformers in full compliance with safety rules ING TABLE OF CONTENTS 1. General information 2 1.1 Standards
More informationKECA 80 C85 Current Sensor Instructions for installation, use and maintenance
Medium Voltage Products KECA 80 C85 Current Sensor Instructions for installation, use and maintenance 1. Operating conditions 2 2. Technical details 2 3. Instructions for installation 3 Safety instruction
More informationGENERAL INFORMATION POLE MOUNT TRANSFORMER SINGLE PHASE PAD MOUNT TRANSFORMER SINGLE PHASE POLE MOUNT TRANSFORMER THREE PHASE 17
GENERAL INFORMATION SECTION GUIDE SECTION 10 PAGE 1 DESCRIPTION SECTION NUMBER GENERAL INFORMATION... 10 POLE MOUNT TRANSFORMER SINGLE PHASE... 15 PAD MOUNT TRANSFORMER SINGLE PHASE..... 16 POLE MOUNT
More informationMedium Voltage Products. KEVA 24 B20; KEVA 24 B21 Voltage Sensors Instructions for installation, use and maintenance
Medium Voltage Products KEVA 24 B20; KEVA 24 B21 Voltage Sensors Instructions for installation, use and maintenance Instructions for installation, use and maintenance for the KEVA 24 B20 and KEVA 24 B21
More informationOn-Load Tap changer Type V
Easun - MR Tap changers (P) Ltd., Chennai, India ON-LOAD TAP CHANGER TYPE V Easun - MR Tap Changers (P) Ltd., 612 (232), M.T.H. Road, Tiruninravur, Chennai - 602 024, India Phone : 91-44 - 26390863 ( Hunting
More informationCLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised
More information1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.
More informationormaset-m PREFABRICATED METALLIC TRANSFORMER SUBSTATION
IG-199-GB GENERAL INSTRUCTIONS FOR IG-199-GB General Instructions ormaset-m Transformer Substations Primary Distribution Switchgear Secondary Distribution Switchgear Protection and Automation Low Voltage
More informationCAST RESIN DISTRIBUTION TRANSFORMERS 2017 EDITION
CAST RESIN DISTRIBUTION TRANSFORMERS 2017 EDITION TMC TRANSFORMERS - GLOBAL NETWORK UK & IRELAND SPAIN NORTH AMERICA & CANADA GERMANY SWITZERLAND BENELUX & AUSTRIA CENTRAL & SOUTH AMERICA MIDDLE EAST &
More informationTransformer Installation, Operation, and Maintenance Manual
Transformer Installation, Operation, and Maintenance Manual CONTENTS INTRODUCTION......................................... 2 INSPECTION UPON RECEIVING... 2 STORAGE...............................................
More informationDry Type Distribution Transformers
Selection Steps A. Use the following steps below to manually select a transformer. B. Find the electrical load requirements. These are: 1. Load operating voltage. 2. Load frequency (expressed in Hz). 3.
More informationCLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised
More informationTransformer bushings, type GOH. Technical guide
Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More informationTechnical Specification of GECOL. Packaged Transformers
GES 26211 Technical Specification of GECOL Packaged Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company of Libya Contents 1 SCOPE AND SERVICE CONDITIONS... 6 1.1 SCOPE...
More informationMEDIUM VOLTAGE PRODUCT. KECA 80 C85 Current Sensor Instructions for installation, use and maintenance
MEDIUM VOLTAGE PRODUCT KECA 80 C85 Current Sensor Instructions for installation, use and maintenance 2 KECA 80 C85 CURRENT SENSOR INSTRUCTIONS FOR INSTALLATION, USE AND MAINTENANCE Scope of Contents 2
More informationKYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS
KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS 2001.09 KYN28A-12 (GZS1) A.C Metalclad Removable Switchgear for Indoor Use --------The Leader in Switchgear Up to 12kV 1. The
More information60 MW GE LM6000 PC Gas Turbine Power Plant
60 MW GE LM6000 PC Gas Turbine Power Plant The power plant consists of 50 MW GE LM6000 PC gas turbine, Year: 2011, 7000 hrs since new, 3000 rpm, 50 HZ, 13 MW Siemens SST 300 steam turbine with 5000 hours.
More informationSingle phase pole mounted. 11kV. Electrical Engineer KEU ID#:
Single phase pole mounted Distribution Transformers 11kV Prepared by: ARY SAIDAHMED SHEKSAEED Electrical Engineer KEU ID#: 4252 Email: ary.sayd@hotmail.com 1 S # Contents Page # 1 Introduction 3 2 Type
More informationNEXT STEP B) SAFETY :
SUMMARY : EVOLUTION OF MV/LV SUBSTATIONS COMPACT SUBSTATIONS J. M. Solans, C. Prevé, R. Farrán, R. Muñoz. SCHNEIDER ELECTRIC S.A. - SPAIN INTRODUCTION The recent liberalisation of the electricity supply
More informationType SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear
Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated
More informationMEDIUM VOLTAGE PRODUCT. KECA 250 B1 Current Sensor Instructions for installation, use and maintenance
MEDIUM VOLTAGE PRODUCT KECA 250 B1 Current Sensor Instructions for installation, use and maintenance 2 KECA 80 C184; KECA 80 C216 CURRENT SENSORS INSTRUCTIONS FOR INSTALLATION, USE AND MAINTENANCE Scope
More informationJoined Forces Extensive product portfolio and technologies. Cable Accessories from 1 kv to 550 kv. nkt.com
Joined Forces Extensive product portfolio and technologies Cable Accessories from kv to 550 kv nkt.com NKT manufacturing and testing equipment ensures high quality products. Concentrated Competence With
More informationCar Battery Charger Instructions for Use
BATTERY CHARGER 12Volt 4Amp FOR INDOOR USE ONLY Power Details: Input: 230-240Vac; 50Hz; 52W Output: 12V DC; 2.8A Maximum Charge Rate: 4A RMS Read these instructions before operating this car battery charger
More informationProduct Information. Neutral Wall Bushing GOFL
ABB Components Info-No. 2750 515-93en, Rev. 1 From / Date Product Information Neutral Wall Bushing GOFL Description Page Design 2 Voltage tap 2 Dimensions 2 Terminals 2 Mounting instruction Packing 4 Storing
More informationABB Transformadores para aplicaciones solares y eolicas
ABB Transformadores para aplicaciones solares y eolicas Product offering overview - Jeff City 1Ø and 3Ø pad-mounted transformers 10-250 kva 45-3000 kva ABB Group abril 9, 2016 Slide 2 Product offering
More informationGUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY
PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationFuji Electric. Oil immersed. Transformer FTU08A1-E-0024
Fuji Electric Oil immersed Transformer 1 FTU08A1-E-0024 History Fuji Electric (T&D Business) 1923 Established Fuji Electric Manufacturing Co.,Ltd. 1962 Started operation of Chiba factory (transformer)
More informationYOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS
YOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS 1 TABLE OF CONTENTS ABOUT SVEL GROUP CAST-RESIN TRANSFORMERS ACCESSORIES AND OPTIONAL EQUIPMENT ENCLOSURE AND HOUSING TESTS AND QUALITY
More informationHVDC bushing without oil side porcelain Type GOF, for outdoor mounting. Installation and maintenance guide
HVDC bushing without oil side porcelain Type GOF, for outdoor mounting Installation and maintenance guide This document must not be copied without our written permission, and the contents thereof must
More informationwith Vacuum Circuit Breaker HAF
M E T A L - C L A D S W I T C H G E A R Safety and Reliability with Vacuum Circuit Breaker HAF Flexible Design and Compact with Vacuum Circuit Breaker HVF Easy Installation and Maintenance We build a better
More informationNEW Solutions for Underground System Growth
NEW Solutions for Underground System Growth Cooper s Single-Phase Voltage Regulator Improved Power Quality More Economical Improved System Reliability Increased Safety Better Aesthetics Lower Maintenance
More informationInternet For latest information, PDF catalogs and operation manuals
DJ Series ew DIPK omenclature Features DJ - - 0-4 6 7 Low noise The tank contains the pump and motor inside and functions itself as noise insulation panels to trap noise internally. Low oil temperature
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationThis tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows:
This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. ADDENDUM Isinya Mandatory Spares list Description Quantity A AIS 400kV
More informationPowerstar Virtue Brochure. British Chambers of Commerce.
Powerstar Virtue Brochure British Chambers of Commerce www.powerstar.com INTEGRATING ENERGY STORAGE WITH RENEWABLE ENERGY Power generators like power plants and wind farms make energy which is then passed
More informationwww. ElectricalPartManuals. com Substation Transformers Primary or Secondary Unit
Substation Transformers Primary or Secondary Unit GENERAL Cooper Power Systems Primary or Secondary Unit Substation Transformers are designed to meet exact customer specifications. Flexibility in design,
More information132/11 kv, 25 MVA MOBILE SUBSTATION
File name: Mob EN katalog1 Zagreb, 11.11.2014. Page: 1 od 9 Summary Mobile substation consists of two semitrailers. One trailer is for 132 kv equipment (HV equipment) and another trailer is for medium
More information1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide
1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationStandard Features and Accessories
14.0-12 Secondary Unit Substations Secondary Below 1000V Product Overview General Description December 2012 Sheet 14012 Liquid-Filled Substation Transformers Application Description Eaton s liquid-filled
More informationMEDIUM VOLTAGE PRODUCT. KECA 80 D85 Current Sensor Instructions for installation, use and maintenance
MEDIUM VOLTAGE PRODUCT KECA 80 D85 Current Sensor Instructions for installation, use and maintenance 2 KECA 80 D85 CURRENT SENSOR INSTRUCTIONS FOR INSTALLATION, USE AND MAINTENANCE Scope of Contents 2
More informationInstallation manual. Intake system and ventilation. Industrial engines DC09, DC13, DC16 OC16. 01:02 Issue 10 en-gb. Scania CV AB 2018, Sweden
Installation manual Intake system and ventilation Industrial engines DC09, DC13, DC16 OC16 01:02 Issue 10 en-gb Changes from the previous issue...3 Intake air...4 Intake air taken from outside engine room...
More information300 kw ~ 6,300 kw (400 HP ~ 8,500 HP) MEDIUM VOLTAGE VERTICAL MOTORS
300 kw ~ 6,300 kw (400 HP ~ 8,500 HP) MEDIUM VOLTAGE VERTICAL MOTORS series: Combining over 100 years of experience with innovative new technology makes the 21-L series the right choice for the demanding
More informationSPECIFICATION SS-52/15 8 MVAR 25 MVAR, 157.5kV SHUNT REACTORS
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION September 2015 SPECIFICATION SS-52/15 8 MVAR 25 MVAR, 157.5kV SHUNT REACTORS I. SCOPE This Specification
More informationShanghai Huaming Power Equipment Co.,Ltd.
HM 0.460.4101-03-02/2017 Shanghai Huaming Power Equipment Co.,Ltd. 1 General CV2 on load tap changer (herein referred as the tap changer) is of selector switch structure, which combines the functions
More information