7.0 Technical Guarantee Specification of 60MVA, 132/33kV Mobile Substation. TECHNICAL DATA SCHEDULE 60MVA, 132/33 kv MOBILE SUBSTATION
|
|
- Arabella Webb
- 6 years ago
- Views:
Transcription
1 92 Section VI. Schedule of Requirements 7.0 Technical Guarantee Specification of 60MV, 132/33 Mobile Substation TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED POWER TRNSFORMER 1 Manufacturer 1.1 Country of Origin 1.2 Type Oil iersed 1.3 No. of phase / winding Threephase with 2 windings 2.0 Rated data and characteristics 2.1 Rated power: primary/secondary MV Cooling ONN/ONF 2.3 Rated voltage HV winding LV winding 2.4 Tap changer: manufacturer Country of Origin model type onload tap changer location regulating range rating 2.5 Frequency Hz Connection of the threephase windings (group of vectors IEC 76) 2.7 Rated current at ONF rated power and rated voltage tap: HV winding LV winding 2.8 Noload current through: HV winding LV winding OLTC YNd11 CFVV HV neutral x x 1.25 Rated power on all taps specify 2.9 Short circuit capacity HV system 7000 MV Short circuit capacity LV system 1000MV Direct impedance at nominal voltage tap: HV/LV Direct impedance at minimum voltage tap: 10.6
2 Section VI. Schedule of Requirements 93 TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED HV/LV Direct impedance at maximum voltage tap Zero sequence impedance at nominal voltage tap HV / LV 2.10 Tolerance to be applied to the short circuit impedance, in terms of of the guaranteed value on: nominal voltage tap other taps 2.11 Short circuit data Short circuit syetrical current duration Sec Syetrical short circuit current withstand during the indicated period and asyetrical short circuit withstand: HV winding k k (peak) LV winding k k (peak) ±7.5 ±10 ltitude M 1000 prefault voltage p.u Guaranteed losses Noload losses at rated voltage and frequency at 75 degree centigrade kw Noload current at rated voltage, frequency and power Noload losses capitalized value US $/kw Tolerance to be applied to noload and on load losses (in of the guaranteed value) Onload losses at rated voltage and frequency, with rated voltage tap and ONN rating: HV winding LV winding tertiary winding kw kw kw Onload losses capitalized value US $/kw Load loss at 75 degrees centigrade, 60MV, 132/ uxiliaries consumption at second stage of cooling (ONF) kw kw
3 94 Section VI. Schedule of Requirements TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED 2.13 Highest voltage for equipment: HV winding LV winding Rated insulation level: Short time low frequency applied voltage withstand: HV winding line terminal LV winding line terminal H.V neutralgraded insulation control wiring Full Wave Impulse Basic impulse level: HV winding line terminal LV winding line terminal HV neutral graded insulation 2.15 Temperature rise limits at maximum power output at ONN and ONF ratings and at lowest voltage tap and corresponding voltage: mbient temperature Top oil temperature rise verage winding temperature rise Temperature class 2.16 Permissible overload in emergency cases: permanent permissible overload based on highest winding temperature which exceeds by 5 o C the guaranteed limit permanent permissible overvoltage based on the maximum top oil temperature which exceeds by 5 o C the guaranteed limit at rated power (in of the rated voltage) 2.17 Oil: (peak) (peak) (peak) o C o C o C MV PCB prohibited manufacturer type data sheet attached 2.18 Bushings HV bushings: class manufacturer type designation rated current short circuit withstand basic insulation level power frequency withstand for 1 minute creepage distance LV bushings: class manufacturer type designation rated current k (peak) NYNS Yes / 36
4 Section VI. Schedule of Requirements 95 TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED short circuit withstand basic insulation level power frequency withstand for 1 minute creepage distance Neutral bushings: class manufacturer type designation rated current short circuit withstand basic insulation level power frequency withstand for 1 minute Creepage distance Design data: Maximum flux density in the columns at: rated voltage 105 of the rated voltage Maximum flux density in the yokes at: rated voltage 105 of the rated voltage Maximum current density at ONN rated power and rated voltage tap: HV winding LV winding Winding resistance: HV winding LV winding Voltage regulation at ONN rating and rated voltage tap (in of the rated voltage): with unity power factor:. HV side. LV side with 0.9 power factor (lagging):. HV side. LV side with 0.8 power factor (lagging):. HV side. LV side Primary exciting current, LV side: at 0.01 second at 0.1 second Core type (core or shell) k k tesla tesla tesla tesla / 2 / 2 ohms ohms k k (peak) (peak) / / Winding conductor Copper 2.20 udible noise level Voltage in percent of rated value ONN rating db() max
5 96 Section VI. Schedule of Requirements TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED ONF maximum rating db() 78 max 2.21 Radio Interference Voltage at 0.5 MHz as per IEC Weights and dimensions 3.1 Total weight of transformer, equipped for service 3.2 Weight: oil core and coil assembling tank and accessories net copper net core steel µv 2500 max Kg kg kg kg kg kg 3.3 Maximum shipping weight (heaviest item) Kg 3.4 Height from foundation to: highest point of HV bushing highest point of tank highest point of conservator tank highest point of lifting hook to remove core and coil assembly 3.5 Outline dimensions: length width specify 3.6 Layout drawing To be enclosed with bid 3.7 Maximum shipping dimensions of tank: outside height outside width outside length 3.8 Transportation drawing To be enclosed with bid 4.0 Onload tap changer 4.1 Manufacturer 4.2 Type 4.3 Rated current 4.4 Number of steps Short circuit withstand k 4.6 BIL to ground through the regulating coil (peak) 4.7 Power frequency withstand voltage for 1 minute through the regulating coil 4.8 Tap transition device Resistance type 4.9 Parallel automatic controller Masterfollower
6 Section VI. Schedule of Requirements 97 TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED 5.0 Current transformer incorporated into the power transformer 5.1 CT in HV phase bushings: Number of cores per bushing Primary rated current Secondary rated current ccuracy class and Burden: protection metering 1 (3) 5P20, 20V (1) CL0.2, 20V Ratio 300:1:1:1: Short circuit withstand Continuous secondary current thermal limit 5.2 CT in LV phase bushings: Number of cores per bushing Primary rated current Secondary rated current ccuracy class and Burden: protection metering (3) 5P20, 20V (1) CL0.2, 20V Ratio :1:1:1: Shortcircuit withstand Continuous secondary current (thermal limit) 5.3 CT in HV neutral bushing: Number of cores per bushing Primary rated current Secondary rated current ccuracy class protection 5P20, 20 V Ratio 300: Short circuit withstand Continuous secondary current (thermal limit) 6.0 Layout 6.1 Primary winding bushings (3) Long. xis 6.2 Secondary winding bushings (3) Long. xis (opposite to HV) 6.3 Conservator tank Transv. xis
7 98 Section VI. Schedule of Requirements TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED 6.4 Tap changer Transv. xis 6.5 Control cabinet 6.6 Radiators 6.7 Terminal block connection drawing drawings to be enclosed 7.0 Standards 7.1 Manufacturing IEC IEC IEC IEC IEC IEC IEC NEM TR1 7.2 Quality assurance ISO uxiliary supply voltages 8.1 OLTC motor and fans, at 50Hz Vac OLTC & cooling control circuits Vac Heaters and lights Vac Relays & instruments Vdc High voltage switchgear Insulation Type ir or Gas 9.2 Rated voltage / maximum voltage 132 / Power frequency withstand voltage(1/ min (rms) Lightening impulse withstand voltage (peak) Rated current Rated short time withstand current (1sec) k Current transformer ratio /1 Metering class ( core 1) burden Security factor Protection class ( core 2) burden ccuracy limit factor 9.9 Design pressure of circuit breaker enclosure Rated circuit breaker operating sequence Stored switching sequence Rated current of circuit breaker Rated short time withstand current Rated DC voltage Rated making current 9.10 Routine test pressure kpa 1200 kpa k V k <10 5p O0.3sCO1min CO O CO
8 Section VI. Schedule of Requirements 99 TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED 9.11 Bursting disc release pressure kpa Combined disconnector & earthing switch 132 Manufacturer Country of origin Type Rated voltage Rated current Rated short time withstand current Rated peak current Disconnector motor operating time uxiliary contacts Disconnector dc voltage Power frequency Impulse Operated mechanism Surge rrester (with counter) Manufacturer Country of origin Type Rated voltage Nominal discharge current TOV capability 1.0s Shortcircuit capability high current 0.2s Line discharge class, IEC Energy capability Insulator colour / material Creepage distance (nominal) Maximum usable bending moment k, 1sec k sec V kcrest rms k Class Ur Nm 3 pole double break for outdoor <4 4NO + 4NC Motor operated with manually operated earthing blade Metal oxide, Gapless Gray / Silicon Medium Voltage Switchgear Manufacturer Country of origin Type Type of insulation SF6 for outdoor ir Rated / maximum voltage 36 Power frequency withstand voltage(1/min) rms 70 Rated normal current 1250 Rated short time withstand current of circuit breaker (3sec) Rated breaking current Rated making current k k k
9 100 Section VI. Schedule of Requirements TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED 11.2 Rated operating sequence acc to IEC Rated DC voltage uxiliary contacts Power frequency Impulse 36 Disconnector Manufacturer Country of origin Type Rated current Power frequency withstand across isolating distance Lightning impulse withstand voltage (1sec) Rated peak current Short circuit withstand at 1sec voltage transformer Manufacturer Country of origin Type Thermal capacity Rated output accuracy class V k k O0.3sCO15sCO 110 4NO + 6 NC Outdoor/Indoor Voltage factor/time 1.5 / 30s Voltage ratio 33000/ 3:110/ 3: 110/ 3 One minute power frequency withstand voltage on: Primary winding Secondary winding Ratted voltage insulation material / color Grounding Transformer Rated power Primary Rated voltage Primary connection Vector group Rated insulation level HV side Rated insulation level LV side Secondary connection Secondary rated voltage, no load Insulation class V V Class V Outdoor/Indoor p Porcelain / brown , 2x2.5 Zigzag Znyn 36/70/170 3 Star + neutral 415/240
10 Section VI. Schedule of Requirements 101 TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED Noload losses Short circuit losses short circuit impedance Surge rresters W W Type Metaloxide, gapless Rated voltage (Ur) rms 33.8 Maximum continuous operating voltage (Uc) KVrms 27 Short circuit capability, high current, 0.2s k 20 Discharge current withstand strength: High current, 4/10microsecond Low current, 2000micro second k (crest) (crest) Line discharge class, IEC Class 2 Energy capability (Ur) 5.5 TOV Capability (after rated energy): 1sec 10sec rms rms cantilever strength Nm 350 Torsion strength Nm 68 Vertical load N 1200 Insulation colour / material Gray / Silicon Energy at one high current impulse 100k 4/10microsecond 11.6 Expulsion fuse cutout kj/uc 3.6 Rated voltage 36 Rated frequency withstand voltage: To ground cross insulated distance Rated current 100 Rated short time withstand current k 11.2 Rated current of fuse Trailer Qty Type Lowbed
11 102 Section VI. Schedule of Requirements TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED 12.2 Load on King Pin (approx) Ton 18 xels Qty 6 (3 steerable) Dimensions (approx) m (LxWxH) 17x3.5x uxiliary 24VDC connection to 24VDC system of prime mover spirit level on trailer 12.4 Brakes Qty 2 pneumatic brake systems 13.0 Control Cubicle: No General Consists of two compartments, one contains relays, control equipment, C/DC panel and the other one contains the batteries. The floor of the building shall be covered with rubber sheet. Walls and roof: This shall be of sandwitch construction using plastic coated aluzink sheet on both sides of an polyurethane insulation layer. Total thickness not less than 60. The roof shall be covered with rubber sheet. Lighting: Both compartments shall be illuminated with compact fluorescent lamps (CFL). Heating: The rooms shall be installed with panel type, adjustable temperature regulator. Ventilation: The cubicle shall be equipped with an airconditioning unit with adequate cooling capacity for ambient temperature of 45 o C. The cubicle shall be installed with ventilators capable of keeping dust outside the room.
12 Section VI. Schedule of Requirements 103 TECHNICL DT SCHEDULE MOBILE SUBSTTION 60MV, 132/33 ITEM DESCRIPTION UNITS REQUIRED GURNTEED 14 Control, protection and metering panel. Make County of origin Type of cubicle Surface treatment with acrylic paint Dimension Type of Energy meter Type of Battery charging system: Type of battery Number of cells Nominal capacity Numerical transformer protection with over current & distance protection functions but prograable for temperature and buchholz etc) Make Feeder terminal relay for protection, measurement, control, counication and monitoring functions. Earth fault and under voltage Make Voltage regulator, with three phase over current & under voltage blocking Make NiCad No h RL x2200x /5h Yes Yes Yes 14.0 Installation Outdoor 15.0 Mandatory Spares SF6 gas Gas refilling unit kg No. 40 1
Maximum temp. rise in oil by 40 thermometer above design ambient (deg C) specified time Short circuit rating (Sec) for As per IS 2026
TECHNICAL PERTICULAR FOR 1.6 MVA 6.6/0.433 KV SERVICE TRANSFORMER 1.00.00 GENERAL 1.01.00 Service SERVICE 1.02.00 Make ASHOK/VOLTAMP/DANKE/CGL 1.03.00 Type CORE 1.04.00 Location OUTDOOR 1.05.00 Specification
More informationCP Automatic capacitor bank
CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor
More informationVOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS
VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.
More informationSUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationTGK Prefabricated Substation Technical Data
TGK Prefabricated Substation Technical Data Ref Item Data 1 General Technical 1.1 Frequency (Hz) 50 1.2 Transformer Rating (kva) 315/750 1.3 Transformer Primary Voltage (kv) 11 1.4 Transformer Secondary
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationDistribution transformers Efficiency over life-cycle
Distribution transformers Efficiency over life-cycle ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while
More informationOutdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications
Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers
More informationKey features. DESIGNS: - Conservator type - Hermetically sealed
Package Substations OTDS manufactures a large range of oil filled hermitically sealed and conservator type transformers to be used in conjunction with our package substations. We are able to utalise the
More informationTechnical Specification of GECOL. Packaged Transformers
GES 26211 Technical Specification of GECOL Packaged Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company of Libya Contents 1 SCOPE AND SERVICE CONDITIONS... 6 1.1 SCOPE...
More informationSmall wonder. Station service voltage transformers for small power requirements
Small wonder Station service voltage transformers for small power requirements MATHEW PAUL An estimated 1.3 billion people worldwide have no access to electricity. In small communities, this is often due
More informationCOMPACT SUBSTATION GUIDE
COMPACT SUBSTATION GUIDE Certificate Number FM35831 1 The substation is a compact enclosure consisting of MV switchgear, a transformer and an LV switchboard located in three separate compartments which
More informationC1000 Series Automatic Cap Bank
C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements
More informationFixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated
www.siemens.com/medium-voltage-switchgear Fixed-Mounted Circuit-Breaker Switchgear Type 8D and 8DB up to 0.5 kv, Gas-Insulated Medium-Voltage Switchgear Catalog H 35.11 201 nswers for infrastructure and
More informationGENERAL. CONSTRUCTION External
Surge Arresters VariSTAR Type AZG4 Surge Arresters for Systems through 400 kv IEC 20-kA; Line Discharge Class 4 Electrical Apparatus I235-84 GENERAL VariSTAR AZG4 Surge Arresters incorporate the latest
More informationEMPAC Metal enclosed capacitor bank for wind applications
EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks
More informationSF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv
Three-phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv 06B1-E-0020 Small Space Requirement, High Reliability and Safety ー 72.5 to 145kV GIS, SDH714 The number of application
More informationMV Air Insulated Switchgear TAP17. Technical Data TGOOD
MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)
More informationINTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.
INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side
More informationCONTENT. EPE METALCLAD SWITCHGEARS AMS SERIES 12kV AMS METALCLAD SWITCHGEAR 24kV AMS METALCLAD SWITCHGEAR 40.5KV AMS METALCLAD SWITCHGEAR
CONTENT EPE METLCLD SWITCHGERS SERIES EPE 1220 / - 12KV METLCLD SWITCHGER EPE 10D - 12KV METLCLD SWITCHGER EPE 24-24KV METLCLD SWITCHGER EPE 36-36KV METLCLD SWITCHGER EPE METLCLD SWITCHGERS MS SERIES 12
More informationNXPLUS C Single busbar. Maintenance-free for lifetime
NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage
More informationProduct Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...
More informationM-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)
M-RING 24 SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A) Contents General Description Advanced facilities and process Advanced design philosophy Definition of M-RING 24 Standards Service conditions
More informationSF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv 06B1-E-0002 Small Space Requirement, High Reliability and Safety ー 72.5 to 145 kv GIS, SDH314/SDHa314
More informationTECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)
TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationDead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability
Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
More informationMESG 12 / 17.5 / 24 / 36 KV
MESG 12 / 17.5 / 24 / 36 KV Medium Voltage Air Insulated Metal Enclosed Switchgear up to 36 kv- up to 1250 A - up to 25 ka for 1 sec. with SF6 or vacuum circuit breakers. 750 METAL ENCLOSED 1 1 ) GENERAL
More informationType SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.
Type SDV6 distribution circuit breaker Top performance - proven reliability Answers for energy. Table of contents Introduction 2-4 Type 3AH3 stored-energy operating mechanism 6 Vacuum interrupters 7 Ratings
More informationProduct Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...
More information33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT
33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,
More informationpower pazifik Metal Oxide Surge Arrester with composite polymer insulator Type series SBK-I to IV /10.3
Manufactured by: Metal Oxide Surge Arrester with composite polymer insulator Type series SBK-I to IV-6... 150/10.3 BT-A3/8 Surge Arresters housed in polymer housing, developed to protect switchgear, over
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationtests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.
tests ( Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. electrical tests These tests verify contractual
More informationPower Voltage Transformers for Air Insulated Substations
Power Voltage Transformers for Air Insulated Substations Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the application of a
More informationUniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions
UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions ABB a global leader ABB is a global leader in power and automation technologies that
More informationCatalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec
Catalog HA 41.43 Edition 2018 Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Medium-Voltage Switchgear siemens.com/simosec Application Typical uses R-HA41-135.tif R-HA40-112.tif R-HA41-115.tif
More informationAIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR
AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationKYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS
KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS 2001.09 KYN28A-12 (GZS1) A.C Metalclad Removable Switchgear for Indoor Use --------The Leader in Switchgear Up to 12kV 1. The
More informationQUEENSLAND URBAN UTILITIES
DOCUMENT NO : EQUIPMENT NO : PREPRED : CHECKED : PPROVED : SHEET NO : 1 of 6 GENERL 1 Battery Charger DCC Inverters 3 DCDC Converters 4 System Design Life (other than batteries) Years 5 Battery Design
More informationVariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified
Surge s Catalog Data CA235022EN Supersedes TD235009EN September 2014 COOPER POWER SERIES VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified General Eaton s Cooper
More informationBHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2
BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR 1.00.00 GENERAL 1.01.00 Make : Jinan Power Equipment Factory 1.02.00 Type : WX21Z-073LLT 1.03.00 Reference Standard : GB/T7064-2002
More informationTransformer bushings, type GOH. Technical guide
Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More informationPIX-H Metal-clad switchgear up to 17.5kV
AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...
More informationSafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin
2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin SafeGear Motor Control Center Arc resistant Metal-Clad construction Descriptive Bulletin Table of Contents
More informationwith Vacuum Circuit Breaker HAF
M E T A L - C L A D S W I T C H G E A R Safety and Reliability with Vacuum Circuit Breaker HAF Flexible Design and Compact with Vacuum Circuit Breaker HVF Easy Installation and Maintenance We build a better
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation SF 6 -gas insulated EGF (245 550) kv General description Voltage transformers type EGF are used in high voltage substations within the 245 550 kv range.
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation SF 6 -gas insulated EGF (245 550) kv General description Voltage transformers type EGF are used in high voltage substations within the 245 550 kv range.
More informationCAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION
CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION TMC TRANSFORMERS - GLOBAL NETWORK UK & IRELAND SPAIN NORTH AMERICA & CANADA GERMANY SWITZERLAND BENELUX & AUSTRIA ITALY POLAND INDIA CENTRAL & SOUTH AMERICA
More information3EP6 porcelain surge arrester
www.siemens.com/energy/arrester 3EP6 porcelain surge arrester Safe, reliable, long-lasting, and stable Answers for energy. Compact design high mechanical stability Sealing system Spring Maximum values
More informationCPG.0 Single busbar gas-insulated cubicles
MV Switchgear Primary Distribution CPG.0 Single busbar gas-insulated cubicles Up to 36 kv CPG System The quality of products designed, manufactured and installed by Ormazabal is underpinned by the implementation
More informationTransformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC
Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC 60137-2008 High current bushings for transformer Features Bushing Type CFPT version Porcelain Insulator Trench RIG technology for
More informationOutdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications
Outdoor live tank SF 6 circuit breaker Type OHB for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers
More informationPART C: GUARANTEED TECHNICAL PARTICULARS OF 33 KV, 2x5/6.67 MVA RURAL TYPE SUB-STATION MATERIALS
PART C: GUARANTEED TECHNICAL PARTICULARS OF 33 KV, 2x5/6.67 MVA RURAL TYPE SUB-STATION MATERIALS C.8.1: TECHNICAL PARTICULARS AND GUARANTEES OF 33/11KV, 5 /6.67 MVA POWER TRANSFORMER (To be filled up by
More informationMAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-
MKING MODERN LIVING POSSIBLE Technical brochure Minicontactors CI 5- www.danfoss.com 2 IC.PD.C10.F3.02-520B4167 Danfoss /S, C-SMC, mr, 07-2010 Contents Page Minicontactor CI 5- Introduction...............................................................................4
More informationUBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit
More informationSafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin
SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin Contents 1. Introduction 2 2. Product highlights 2 3. Available configuration/competitive
More informationSection S7 - DC and AC auxiliary services installations
S7/2 Section S7 - DC and AC auxiliary services installations Contents S7. Generalities...3 S7. Generalities...4 S7..1 Scope of work...4 S7..2 Dimensioning the auxiliary services equipment...4 S7.1 General
More informationR-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A
R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A - 3700 A R-MAG The R-MAG is truly the next generation in vacuum circuit breakers, combining industry recognized magnetic
More informationGeneral. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment
General The switchgear must be suitable for 36 kv rated voltage and specifically conceived for the secondary distribution substations in M.V. with either ring or radial type networks. The switchgear must
More informationHigh-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution
High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching
More informationOutdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv
Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker
More informationB kv T&D GAS INSULATED SWITCHGEAR
GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission
More informationCompact Integrated Distribution Substation (CIDS)
Compact Integrated Distribution Substation (CIDS) 1- INTRODUCTION SAVE SPACE 2.5m 2 footprint for CIDS up to 630kVA. SAVE THE ENVIRONMENT No SF6, No PCB. SAVE MONEY Save up to 50% from conventional package
More informationINESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation
MOBILE SUBSTATIONS Energy Solution INTERNATIONAL FAIR MOBILE SUBSTATIONS ENERGY SOLUTION Complete design for energy s generations, transmission and distribution Mobile Substations Applications of Inesing
More informationABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers
ABB PTTR SPAIN Zaragoza. The product: Cast coil transformers ABB BA Transformers - 1-5/7/2007 Dry Type Vacuum Cast Coil Transformer INTRODUCTION ABB BA Transformers - 2 - Product Portfolio II Dry Type
More informationB kv Gas-insulated Substations
72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.
More informationCITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008
CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION
More informationChapter 6 Generator-Voltage System
Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals
More informationAdvance 27 ANSI 27 kv switchgear
Advance 27 ANSI 27 kv switchgear Table of contents Advance 27...3 AMVAC breaker...4 Instrument transformers...5 Current transformers...5 27 kv voltage transformers...6 Distribution protection and control...7
More informationSF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)
SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) About company The «Elektroapparat» plant starts its operation in 1922 as a plant manufacturing high-voltage electrical equipment. During the first two
More informationDynaVar Arresters IEC Line Discharge Classes 2, 3, 4 & 5
Section 204-1 204 DynaVar Arresters IEC Line Discharge Classes 2, 3, 4 & 5 Web: http://www.hubbellpowersystems.com E-mail: hpsliterature@hps.hubbell.com Printed in USA RGS 1M 204-2 Table of Contents Page
More informationCombined instrument transformers
Combined instrument transformers Outdoor operation SF 6 -gas insulated EJGF (245 550) kv General description Type EJGF combined transformers are used in high-voltage substations within the 245 550 kv range.
More informationR-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism
R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Features: Low maintenance 10,000 mechanical operations (five times ANSI requirements) Simple magnetic actuator Vacuum interruption Definite
More informationOn_Disc. 2 o/c1 BS 7671 applies to a lift installations b highway equipment c equipment on board ships d electrical equipment of machines.
1 PAPER 4 Sample Questions - C&G 2382 17th Edition full paper D 1 o/c 1 - A recommendation for the interval to the first periodic inspection shall be made by: a the installation electrician. b the main
More informationMake : BHEL / Siemens Type : THDF 115/ Reference Standard : IEC 60034
B. GENERATOR AND ACCESSORIES 1.00.00 General 1.01.00 Make : BHEL / Siemens 1.02.00 Type : THDF 115/67 1.03.00 Reference Standard : IEC 60034 1.04.00 Enclosure and degree of protection : Generator:IP54
More informationResin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK
1ZSC563-AAA en, Rev. 2 Resin Impregnated Paper Bushing, Oil to SF 6, Type GSBK Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More information8DJ. Maintenance-free for lifetime
8DJ Maintenance-free for lifetime Energy Distribution Welcome! Page 2 October 1 st 2008 8DJ Main Applications for Medium-Voltage Switchgear Power generation Power stations G Power transmission High and
More informationPretest Module 29 High Voltage Unit 1
Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition
More informationSPECIFICATION SS-52/15 8 MVAR 25 MVAR, 157.5kV SHUNT REACTORS
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION September 2015 SPECIFICATION SS-52/15 8 MVAR 25 MVAR, 157.5kV SHUNT REACTORS I. SCOPE This Specification
More informationResin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide
1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More informationMedium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION
Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium
More informationDM Condenser bushings, kV DURESCA
DM Condenser bushings, 36 DURESCA Through wall bushings for indoor and outdoor applications, Resin Impregnated Paper IEC 601378 and IEEE C57.19.01.004 DURESCA Wall bushings Swiss quality combined with
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY Phone: +91 431 257 79 38 Fax
More informationPolymer Insulator. ITEM 15kV 25kV 35kV 69kV. Section length(l) 330±15mm 445mm 539mm 888mm. Min. arcing distance 215mm 300mm 340mm 701
Polymer Insulator Characteristics of Polymer Insulator The main element of polymer insulator displays very excellent properties in terms of heatproof performance, chemical stability, electrical insulation,
More informationBus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:
4 (Four) Pole Monoblock: Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers: Designed and manufactured in accordance with EN 50336:2002 and BS 2562: 1979 1 Introduction:
More informationSwitchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable
www.siemens.com/medium-voltage-switchgear Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Medium-Voltage Switchgear Catalog HA 41.43 2012 Answers for infrastructure and cities. Neue Bilder
More informationFA Off-Load Switches. Up to 8000 A and 3000 V AC/DC Expertly engineered for reliable performance
F Off-Load Switches Up to 8000 and C/DC Expertly engineered for reliable performance For more than years has been providing safe and reliable solutions for switching and disconnecting high power. High
More informationGROUP D. Switch & Protective device.
GROUP D Switch & Protective device PYUNGIL Bldg., 147-10, Gwanyang 2-dong, Dongan-gu, Anyang-si, Gyeonggi-do, 431-808, Korea Tel : 82-31-420-0~3 FAX : 82-31-424-7300 www.pyungil.com Pole-mounted SF Insulated
More information24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A)
M6 24kV Medium Voltage Switchgear MetalEnclosed (LSC2A) GENERAL FEATURES GENERAL DESCRIPTION The structure of the cubicles, of considerable strength, has selfsupporting structure and is made of steel sheet
More informationwww. ElectricalPartManuals. com WeSTinghouse Secondary Unit Substation Transformers (Power Centers) Descriptive Bulletin Page 1
WeSTinghouse Descriptive Bulletin 47-156 Page 1 liquid Filled, Self-Contained 112% 2500 Kva June, 1974 Supersedes DB 47-350, dated August 1972 E, D, C/2082/DB Descriptive Bulletin 47-156 Page 2 Westinghouse
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly
More informationLV Capacitor CLMD03 Power Module Instruction manual
LV Capacitor CLMD03 Power Module Instruction manual Table of Contents 1 Safety... 3 2 Upon reception... 3 2.1 Inspection on reception... 3 2.2 Storage- transportation handling... 3 3 Hardware Description...
More informationFixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kv, SF 6 -Insulated. Medium-Voltage Switchgear Catalog HA 35.
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to kv, SF 6 -Insulated Medium-Voltage Switchgear Catalog HA 5. 00 Invalid: Catalog HA 5. 00 R-HA5-05 eps Fixed-Mounted Circuit-Breaker Switchgear
More informationCompact Gas Insulated Switchgear (GIS) up to 145kV 126kV,145kV Compact Gas Insulated Switchgear (GIS)
Compact Gas Insulated Switchgear (GIS) up to 45 6,45 Compact Gas Insulated Switchgear (GIS). Standard: IEC 6703. Typical Feature. Great Breaking Character of Circuit Breaker The circuit breaker adopt the
More informationTechnical information
Technical information General Regulations WTL current transformers are special transformers which transfer the primary circuits with prescribed accuracy in smaller secondary circuits. Primary and secondary
More information